1. SOCOMET 5 550 750 VA SAFETY STANDARDS novative Power Solutions U hse Product Manual NeTYS PL 550 750 VA PRODUCT MANUAL CONTENTS 1 520222045 2 202 1 0 KERNER AANE r ENE RERNE AANEEN NEKA A Ea 4 2 GENERAL DESCRIPTION 5 2 1 LED BASED CONTROL AND DISPLAY PANEL 2 6 3 UNPACKING AND 1131 1 7 3 1 25 7 3 2 ENVIRONMENTAL REQUIREMENTS FOR 7 3 3 CONNECTION TO THE MAINS POWER SUPPLY AND CONNECTING THE LOAD 7 4 OPERATING MODES 8 5 COMMUNICATION inr saa consacte S A EAE EE AA Aaaa ERa 9 6 MAINTENANCE aiea deeasiueasdiuet nsuabuseabbyiseuvensuvurieaay 10 6 1 REMEDIES FOR MINOR 65 6 10 T 11 SOCOMET NnetYs 550 750 VA SAFETY STANDARDS Innovative Power Solutions U Product Manual CERTIFICATE AND CONDITIONS OF WARRANTY This SOCOMEC UPS uninterruptible power system is guarante
2. SOCOMET 550 750 nnovative Power Solutions UPS Product Manual 1 SAFETY STANDARDS This manual must be kept next to the UPS so that the operator may consult it at any time for clarification on the correct use of the UPS Read the manual carefully before connecting the unit to the mains power supply and to the devices to be powered Before switching on the UPS Uninterruptible Power Supply the operator must be fully aware of the functions and positions of all the controls and of the technical and functional characteristics of the system in order to avoid any risk to persons and to the equipment e Before starting the unit must have an equipotential connection as established by the safety standards in force The earth cable of the UPS must be connected to an efficient earth point lf the unit is not earthed all devices connected to the UPS will not an equipotential connection In this case the manufacturer declines all responsibility for damage or accidents caused by non observance of the aforementioned standards This is pluggable type A equipment with battery already installed by the supplier it s operator installable and may be operated by layman e Incase of power failure UPS in back up mode do not disconnect the input cable from the mains so as to ensure earth connection to the powered loads e All subsequent maintenance operations must be carried out solely and exclusively by
3. authorized personnel Inside the system high electric voltages are generated which may endanger maintenance personnel who are not sufficiently prepared and trained for such tasks lf at any time a hazard condition is created during use disconnect the mains power supply if possible through the control panel upstream of the unit and shutdown the UPS completely following the appropriate procedure e When assembling and replacing the battery the UPS should always be switched off and disconnected from the mains power supply Do not dispose of batteries in a fire the battery may explode CAUTION a battery can present risk of electric shock and high short circuit current The following precaution should be observed when working on batteries remove watches rings or other metal objects and use tools with insulated handles e The batteries constitute an internal power source for the UPS and mean that the system output may be powered even when the UPS is not connected to the mains power supply e Do not force break or try to open the batteries They are sealed and do not require any maintenance They contain substances that are toxic to health and that pollute the atmosphere Do not switch the UPS on if any leakage of liquid or white powder residue is noted e Replace batteries with the same number and type of batteries as originally installed in the equipment e Replace the fuses ONLY with other fuses of the same type As the mains c
4. able of the UPS is considered a disconnecting device the mains socket to which the UPS is connected and or the rear of the UPS must be accessible and easy to disconnect e Avoid contact of the UPS unit with water or liquids in general Do not introduce foreign bodies If the unit needs to be scrapped it must be handed over solely and exclusively to specialist disposal companies These companies are obliged to break up and dispose of the various components in accordance with the national legal provisions in force e The UPS generates a leakage current of about 1 5mA To guarantee the maximum limit leakage current of 3 5mA make sure that the maximum leakage current of the load is 2 mA If the load current exceeds this value have qualified personnel connect the UPS to an industrial type IEC 309 compliant power supply mains with a current of correct dimensions for the UPS power rating e NeTYS UPS is intended for commercial and industrial use it is not recommended for use in medical applications that are essential to the survival of the patient e Use the UPS in accordance with the technical specifications given in the User Manual SECTION 1 SOCOMECT 5 550 750 VA GENERAL DESCRIPTION nnovative Power Solutions UPS ey Product Manual 2 GENERAL DESCRIPTION NeTYS sure power supply for PC servers graphics stations and network devices The main purpose of the UPS is to protect sensitive and critical equipment from
5. atically All NeTYS models are equipped with RS232 and USB communication interface COMMUNICATION SOLUTIONS Uni Vision local management software for local shutdown of Windows amp Linux systems Free http www socomec fr page_uk lien_prod_ups htm RS232 USB INTERFACE Communication with the server can take place directly via the RS232 USB interface In addition to local or networked shutdown it is possible to perform full monitoring of the electrical parameters regarding battery status and the automatic programming of the UPS start up and shutdown procedures For a complete description of the software features refer to the Uni Vision SECTION 1 10 SOCOMET 5 550 750 Innovative Power Solutions UPS Product Manual 6 MAINTENANCE 6 1 REMEDIES FOR MINOR PROBLEMS This section examines some of most likely problems that can compromise correct operation of the UPS attempting to solve them and identifying the possible causes and remedies A THE UPS INTERNALLY GENERATES HAZARDOUS ELECTRICAL VOLTAGES ALL MAINTENANCE MUST BE PERFORMED SOLELY AND EXCLUSIVELY BY AUTHORIZED PERSONNEL If you have difficulty in getting the UPS to work the reason may be among those listed below For any other problem you are advised to get in touch with your dealer or service organisation directly For quick and effective action when you call it is important to give precise details of the defect the model number a
6. battery charge runs out fully low battery charge is signalled via a rapid intermittent acoustic alarm The UPS automatically returns to normal operating mode about two seconds after the mains power is restored The time taken to transfer from normal to battery mode and vice versa is imperceptible to the load OVERLOAD The UPS can power loads up to the power rating declared on the machine s data plate once this limit is exceeded the machine goes into overload condition Overloads are signalled by a rapid sounding acoustic alarm 29 Warning Significant overloads could cause permanent damage to the UPS Avoid connecting laser printers that generate absorption peaks liable to cause overloads on the UPS SECTION 1 SOCOMET NnetYs 550 750 VA COMMUNICATION nnovative Power Solutions UPS Product Manual 5 COMMUNICATION The UPS provides excellent protection against interruptions or imperfections in the mains power supply In these cases the computer load is powered by the UPS using battery power until this runs out Various software applications and communication options are available to optimise operation of the UPS and to correctly manage shutdown when back up power ends The status of the UPS can be monitored keeping track of all the mains failures and battery discharges so as to activate an automatic and orderly procedure to close the programs and shutdown the system When mains power returns the system will restart autom
7. ed against manufacturing and material defects for a period of 24 months from the date of purchase and not however more than 27 months from the date of shipment by SOCOMEC UPS The warranty is of the carry in type free supply of parts and labour for repairs with return of a product to be replaced to SOCOMEC UPS or authorized centres at the customer s cost and risk In order to use the warranty service the user must respect the following rules e the product must be returned exclusively in its original packaging Any damage caused during shipping in packaging other than the original is not covered by the warranty e the product must be accompanied by proof of purchase a document bill invoice receipt showing the date of purchase and the information necessary to identify the product model serial number The number of the authorization for return for repairs must also be attached with a detailed description of the defect found in the product If any of these elements is missing the warranty is invalid The return authorization number is issued by the service centres by telephone on receiving notification of the malfunction The warranty is recognised within Italian territory If the UPS is exported outside Italian territory the warranty shall be limited to the cover of the parts used to repair the fault The warranty shall not apply in the following cases Failures due to fortuitous circumstances or force majeure lightning flo
8. electrical disturbances that can compromise operation Black outs brown outs variations in voltage and frequency lightning electrostatic discharges and rapid over voltages are phenomena found in all office and industrial environments and which cause damage to the hardware and loss of data NeTYS is an Uninterruptible Power Supply designed to power computers and connected peripherals with the exception of any other electrical device such as household appliances television sets stereo systems and video recorders that may be connected only to the filtered output sockets INTRODUCTION The characteristic feature of these UPS is the constant monitoring of the power supply which duly filtered and if considered suitable is used to supply consumers In cases of a mains failure or if the mains is considered to be outside limits accepted by the load the inverter the heart of the UPS is activated immediately Drawing on the power stored in the batteries the inverter generates a voltage that instantly takes over from the mains without any disruption to the equipment connected During operation under emergency conditions the internal batteries discharge but are recharged again automatically when mains power returns Being hermetically sealed the batteries do not require maintenance of any kind at any stage of their working life Block diagram The block diagram provides a useful aid to understanding how the machine operates In 4 Legend 1 Main
9. from heat sources and exposure to direct sunlight Keep ambient temperature between 0 C and 40 C and humidity less than 90 non condensing the best temperature to guarantee longest possible battery life is 15 20 C Ensure that the environment where the UPS will be installed is not dusty and leave a space of at least 20 cm around it to allow for adequate ventilation and access to the rear panel Make sure not to place the UPS or any other heavy object on the cables Check that the voltage and frequency preset for operation is right for your electrical power supply looking the data can be found on the data plate Use only the manufacturer supplied or recommended cables and accessories for connections to the RS232 USB serial interface It is recommended that the batteries be left to charge for 8 hours the first time the unit is used 3 3 CONNECTION TO THE MAINS POWER SUPPLY AND CONNECTING THE LOAD Cables with the appropriate cross section and conforming to the safety standards in force should be used for connection to the mains and connection of the loads Connect the UPS power cord to the mains power supply Connect the loads to the outlet sockets on the rear of the UPS SWITCHING THE UPS ON Switch the UPS on by pressing the ON button on the front panel The Normal mode LED will light up allow ten seconds for the self teach procedures to run When you are sure that the UPS is functioning properly the various load
10. ion socket UPS and Surge protection Load connection socket Surge protection BATTERY Typical back up time PC 15 LCD monitor COMMUNICATION Communication interface Local communication software Telephone protection ENVIRONMENT Noise level at 1 meter Temperature Environment Reference Standards WEIGHT AND DIMENSIONS Dimensions WxDxH mm Net weight Specific model with French plug 550 750 550 VA 330 W 750 VA 450 W 1200 VA 1200 VA High Frequency Step Wave 170 260 V 50 60 Hz with automatic selection Cable with plug 230V 10 50 60 Hz 1 Hz Stepwave 2 6 milliseconds typical Overload deep discharge and short circuit 4 schuko type IT FR CEI 23 50 2 schuko type IT FR CEI 23 50 20 min 30 min RS232 USB UPS Management software Windows amp Linux free download Telephone line modem ADSL suppressors RJ 11 45 lt 45dBA 0 35 C 15 25 C for optimum battery life Altitude 2000 mt humidity 90 non condensing EN IEC 62040 1 1 safety EN 50091 2 IEC 62040 2 EMC EN 61000 4 5 C62 41 1991 surge CEI 23 50 IEC 60884 1 160 x 210 x 125 5 3 Kg 5 5 Kg SECTION1 11
11. nd the manufacturing serial number that can be found on the conformance and inspection certificate or on the data plate on the bottom of the UPS mains power is available The UPS works in battery mode even if Poor connection to the input mains The mains voltage is out of range Check the connection of the cable to the UPS and to the mains outlet No solution because mode of operation is correct Back up time shorter than expected Batteries not fully charged Batteries not working properly Leave the batteries to charge for 8 hours consecutively Have the batteries replaced by authorised personnel The UPS stalls goes into overload alarm Overload on the load line Check that the load applied is not greater than the maximum permitted or reduce the load power requirement IF THE EQUIPMENT IS TO BE LEFT IDLE FOR A LONG PERIOD WAIT FOR THE BATTERIES TO CHARGE FULLY BEFORE SWITCHING OFF WHILE THE UPS IS LEFT IDLE MAKE SURE THAT THE BATTERIES ARE RECHARGED FOR 24 HOURS AT LEAST ONCE EVERY 4 WEEKS SECTION 1 SOCOMET 5 550 750 nnovative Power Solutions UP Product Manual 7 TECHNICAL DATA TECHNICAL DATA NeTYS PL Power UPS protection Power Surge protection Technology INPUT Voltage Frequency Mains connection OUTPUT Voltage in Battery Mode Frequency Wave form Transfer time Protection Load connect
12. ods e Failures due to negligence or improper use use outside tolerance limits temperature humidity ventilation electric power supply applied load batteries e Insufficient or inadequate maintenance e Attempted maintenance repairs or modifications not carried out by SOCOMEC UPS personnel or personnel from a support centre authorised by SOCOMEC UPS e If the battery has not been recharged in accordance with the terms indicated on the packaging and in the manual in cases of extended storage or UPS inactivity SOCOMEC UPS may at its own discretion opt for the repair of the product or for the replacement of the faulty or defective parts with new parts or with used parts that are equivalent to new parts with regard to functions and performance Defective or faulty parts replaced free of charge are to be put at the disposal of SOCOMEC UPS that becomes the sole owner Replacements or repairs of parts and any modifications to the product during the warranty period shall not extend the duration of the warranty In no case will SOCOMEC UPS be responsible for damages including without limitations damage for loss of earnings interruption of activity loss of information or other economic losses deriving from the use of the product The present conditions are subject to Italian law Any dispute falls under the province of the Court of Vicenza For further information www socomec com SECTION1 4
13. s input 2 Battery charger 3 Mains filter and surge protections 2 4 Inverter DC AC 5 Automatic transfer switch 6 Output to power consumers sii 3 4 5 Out A surge SECTION 1 5 6 SOCOMECT 550 750 VA Innovative Power Solutions UP Product Manual 2 1 _LED BASED CONTROL AND DISPLAY PANEL O ON OFF switch Turns the UPS ON and OFF Visual indication of operating mode LED green lit NORMAL MODE mains OK LED yellow flashing BATTERY MODE mains absent or abnormal e Eoi UPS failure LED red MODELS 550 750 PL Acoustic alarm Intermittent alarm every 5 seconds BATTERY MODE Intermittent alarm every second battery low Intermittent alarm every 0 5 second overload Continuous alarm UPS failure SECTION 1 SOCOMET 5 550 750 VA UNPACKING AND Innovative power solutions UPS yt Manual INSTALLATION 3 UNPACKING AND INSTALLATION 3 1 UNPACKING Remove the UPS and all the accessories that come with it cables product manual etc from its packing case It is always advisable to keep the original packaging that has been specially designed for safe transport in case the unit has to be moved again 3 2 ENVIRONMENTAL REQUIREMENTS FOR INSTALLATION Install the UPS after first checking the following NeTYS has been designed for use in closed environments Place the UPS on a flat and stable surface in a ventilated environment away
14. s may be switched on and work may commence in protected mode SWITCHING THE UPS OFF Warning This UPS has been designed to control and maintain the battery charge therefore only in exceptional circumstances are you advised to switch it off completely To shutdown the UPS completely press and hold down the OFF button The UPS switches off all the LEDs and is then fully deactivated SECTION 1 8 SOCOMET 5 550 750 nnovative Power Solutions UPS Product Manual 4 OPERATING MODES NORMAL MODE When mains power is available and the voltage falls within the acceptable range the NORMAL MODE LED on the front panel remains on permanently In this mode the loads are powered from the mains power supply directly and protected in cases of voltage peaks The batteries are constantly recharged BATTERY MODE The UPS switches automatically to this operating mode when mains power fails spikes or lengthy black outs or if the mains is at a value considered to be dangerous the consumers are powered using the energy stored in the batteries converted to AC voltage through the inverter In this mode a slow intermittent acoustic alarm sounds while the BATTERY MODE LED on the front panel flashes In cases of prolonged mains failure the UPS powers the consumers until it shuts down when the batteries are fully depleted see the chapter on COMMUNICATION for orderly shutdown via software Just before shutdown when the

Download Pdf Manuals

image

Related Search

Related Contents

The iNEWS ControlAir ™ System Overview  tapping po Opera oints o ating m of the manua EM15/ al /EE15 seriess  ステレオ レコードプレーヤー 取扱説明書    UDS-J2 LED ULTRASONIC SCALER MANUAL DE INSTRUCCIONES  Hauck Bassinet & Carebox  For Dummies JavaScript and AJAX  Design House 517698 Instructions / Assembly  NGS iReader 3.0  Info - Adasat  