1. lt i Eiz ma Zi Mep car A Ls script ype O Type i Condition ae toa Description t All the devices One or more devices System dl dle De he Code 030220491 rel 2 1 11 12 06 32 Quick Guide PlantVisorPRO Locale To create a new condition for the alarms on all the devices enter a cue name for the condition in the Description field for example All Then select the All the devices option and finally to add the condition click l Actions Select the Actions tab The following page will be displayed admin 1 19 06 2006 16 53 11 Alarms and events management Rules Alarm conditions Event conditions Time bands Actions To edit an action double click the corresponding row in the list below To add a new action enter the description then click the image Then double click the new row entered in the list highlighted in red Description AA OO a Sse na i To add a new action enter the cue name in the Name field for example Alarm action then click The settings will be saved Subsequently double click the new row that has been entered in the list highlighted in red This will allow the peripherals used to be set for this action admin 1 19 06 2006 16 56 24 Global Alarms and events management Rules Alarm conditions Event conditions Time bands Actions Cl
2. Code 030220491 rel 2 1 11 12 06 6 Quick Guide PlantVisorPRO Locale 2 Configuring the devices in the site The site is configured by setting the serial lines and the corresponding devices The devices are connected together by data lines multiple lines are possible in the same installation Each line is connected to a different serial port on the computer where the PlantVisorPRO Locale supervisor is installed To configure the site move the mouse arrow to the ICON a menu will be displayed select the item Site configuration admin il 19 06 2006 14 04 26 Alarms Devices not present e CONFIGURATION Site configuration Logical configuration Logical device creation Logical groups Logical areas User configuration System pages i SE di The following page will be displayed i antVi S O r e admin 1 19 06 2006 14 05 56 Global Site configuration New line Alarms safety Notes This page is used to set the site information To edit a configured line double click the row in the list below To remove a line select the its row in the list below and then click the image ml amj reitt iim Site information Name Plantvisor PRO Identifier supervisori Telephone L i O Password ge _ Confirm password fC O O List of lines A i ds Code 030220491 rel 2 1 11 12 06 7 Quick Guide PlantVisorPRO Locale In the Name field ent
3. Commento alla pagina Rule Description Enabled Iv Actions Time bands Condition Delay minutes The Enabled field is used to enable or disable a certain rule if the field is checked the rule will be enabled for the supervisor Code 030220491 rel 2 1 11 12 06 36 Quick Guide PlantVisorPRO Locale 4 4 Managing the scheduled activities The PlantVisorPRO scheduler not only ensures alarm management but also allows a number of actions to be performed at certain times To set a scheduled activity in the supervisor proceed as follows Select the item Scheduled activities management from the Scheduler menu The following page will be displayed admin 1 19 06 2006 17 19 12 Global Scheduled activites management Rules Time bands Actions Rule Description Enabled W Time bands Actions Select the Actions tab The following page will be displayed admin 1 19 06 2006 17 26 30 Global Scheduled activities management Time bands Actions Rules Description Fax SS Email Relays Variable Remote Print window af 10 To add a new action enter the description then click the image Then double click the new row entered in the list highlighted in red Al Description gt To add a new action enter the cue name in the Name field for example Alarm action click The settings will
4. device configuration Main amp larm variables Variables Descriptions list Main variables In 3320 1 SE List of all variables that can be logged to HACCP standards and or to monitor the operation of the installation ml Besa eae fe Measurement stability CD CD E months E o E 3 Probe display slowdown CD CD E months E 0 f4 Virtual probe CD C E months G O amp e a a Sse e D o E months E 6 Decimal point 0 YES 1 NO T D E months E FAZ Probe 2 configuration CD CD E months E o 743 Probe 3 configuration Fal CD E months E 0 rd Frobe 4 configuration DI DI E months E o rF Select probe type CD CD E months Ef O fol Probe 1 calibration C i IE canto A n E The log refers to the recording of a series of values of such variables over time The Variable column indicates the description of the logged variable The HACCP column if selected for an item indicates that that variable will be logged according to the HACCP standards EN 12830 Temperature recorders for the transport storage and distribution of chilled frozen deep frozen quick frozen food and ice cream The variables marked HACCP are automatically logged for more than one year every 30 minutes The log column is used to enable the variable log function once selected this item the columns Log duration Minimum Variation and Frequency The Log duration column allows to select for each va
5. Numbers configured for the action gt Verifing Code 030220491 rel 2 1 11 12 06 34 Quick Guide PlantVisorPRO Locale Then select the Print Window tab The following page will be displayed admin 1 19 06 2006 17 08 00 Global Alarms and events management gt action configuration Remote Print Window v Fax SMS Email Relays Variable Action Act 1 Print Enable print on alarm Window Enable the alarm window N Z pipe f PATTIE peri itaas L f gt Sisti To set the alarm window check the item corresponding to Enable the alarm window in the Window section To save the settings click To return to the page for setting the actions click the Alarms and events management link located above the tab i Alarms and events management gt action configuration Fax CI F admin P PRO locale 3 2006 12 18 15 49 35 Global Alarms and events management Time bands Actions Event conditions Alarm conditions Rules To edit an action double click the corresponding row in the list below OE Description Fax SMS E mail Relays Variable Remote Print Window act 1 x v a s n na n aa or ed Ra co R pr 143 no il 4 To add a new action enter the description then click the image Then double click the new row entered in the
6. SMTP server the sender and the type of connection used to send EMAIL messages and enter the details of possible recipients in the address book Configuration SMTP 192 168 0 30 Connection Can Dialup Sender industry industry com Provider Telez a Number of attempts zo Try again after E minutes Address book Reference Referenc Riferimento Indirizzo Address Reference reference cam x Then click gt The address book will be updated admin 1 19 06 7006 16 27 31 Global I O configuration Fax E mail gt Vv Select the SMTP server the sender and the type of connection used to send EMAIL messages and enter the details of possible recipients in the address book Configuration SMTP 192 168 0 30 i Connection CLAN Dialup Sender lindustry industry com t Provider Telez aj Number of attempts fio Try again after E minutes Address book Referenc Reference reference com Reference Address To save the settings click Vv Code 030220491 rel 2 1 11 12 06 26 Quick Guide PlantVisorPRO Locale Changing an item in the e mail Address book To change an item in the Address book select the desired item by double clicking it and then edit the desired fields admin 1 19 06 7006 16 29 06 Global 1 0 configuration Fax E mail Window Relay gt V Select the SMTP server the sender and the type of connect
7. case clean management Highest i Vv Defrost interrupted for timeout signalling Highest a mia ta Vv Valve driver LAN error Highest 10 Vv Alarm SH temperature probe Highest J Vv Alarm evaporation pressure probe Highest Vv Alarm duty setting from digital input signalling Highest El i Vv External delay alarm from dig input signalling Highest a 3 Vv External alarm from dig input signalling Highest al F HACCP alarm HA Highest a 7 HACCP alarm HF Highest A f The table shows all the alarms managed by the specific device The Frequency for checking the alarms field is used to decide how often PlantVisorPRO will check whether the device has at least one active alarm from those selected in the Active column The alarm can be selected deselected in this column The Priority column indicates the priority of the alarm when more than one alarm is active at the same time The alarms with Highest priority are the first to be managed while those with the lower priority are placed in the queue By default all the alarms have Highest priority To save the settings click Code 030220491 rel 2 1 11 12 06 13 Quick Guide PlantVisorPRO Locale 3 2 Changing the activation of the variable log To enable disable or change the variable log click the Variables tab The following page will be displayed admin PVYPRO locale 3 2006 12 18 11 57 56 Global Site configuration gt line configuration gt
8. modem to the service provider or for checking the availability of the analogue GSM modem as the effective delivery to destination of the SMS message cannot be checked e Try again after This field is used to set the number of minutes that must elapse between one failed attempt and the next Once all the settings have been completed add the numbers to the address book for sending the SMS messages The Address book area is used to set the numbers that the supervisor will use to send the SMS messages in the same was as for the faxes To save the settings click Vj Code 030220491 rel 2 1 11 12 06 24 Quick Guide PlantVisorPRO Locale 4 1 3 Setting the e mail configuration To set the data used to send e mails select the E Mail tab admin 1 19706 2006 16 21 27 Global I O configuration Fax E mail Window Hiv Select the SMTP server the sender and the type of connection used to send EMAIL messages and enter the details of possible recipients in the address book Configuration SMTP E Connection Lam Dialup Sender I 5 Provider Number of attempts fo Try again after minutes Address book Reference o Riferimento sIndirizzo Address DI al The Configuration section features 6 fields SMTP Name of the mail server or the IP address supplied by the Internet service provider Sender e mail address of the sender Important some mail service
9. settings click Code 030220491 rel 2 1 11 12 06 38 Quick Guide PlantVisorPRO Locale To return to the page for setting the actions click the Scheduled activities management link above the tabs Scheduled activities management gt action configuration Then select the Time bands tab The following page will be displayed admin 1 19 06 2006 17 34 56 Global Scheduled activities management Rules Time bands Actions Always Daily al e Time bands Description Type from 00 oo Daily to oo 00 x Enter the text Workdays in the Description field From the Type selection field select the item Weekly admin 1 19 06 2006 17 37 26 Scheduled activities management Rules Time bands Actions ov Daily br Time bands Description value vo e We dea alle w kO t Bi D oo l mon l Tue l wed l thu Type Corri D sat D sun GO Weekly gt from 00 00 to oo oo Code 030220491 rel 2 1 11 12 06 39 Quick Guide PlantVisorPRO Locale Select the days from Monday to Friday Time bands im Always admin 1 19 06 2006 17 37 26 Actions Daily Mi R RZRnNNNSSUM Time bands Description WorkDays n Type Weekly T mon tue wed Thu a Fri a Sat a Sun CHE from 00 00 to oo 00 S
10. signal Code 030220491 rel 2 1 11 12 06 19 Quick Guide PlantVisorPRO Locale 4 Scheduler 4 1 Configuring the I O peripherals PlantVisorPRO using the scheduler can monitor the alarms on the installation and depending on the type of alarm the alarm device the time period and the peripherals available for signalling the alarm can warn the users The I O peripherals must be configured to set all the functions that allow PlantVisorPRO to communicate with the outside world These are Fax Set a fax modem for sending any alarms or reports SMS Set a modem GSM or analogue for sending any alarms via an SMS message E mail Set an e mail address for sending any alarms or reports via e mail RAS Remote Access Service Set a connection to a remote computer Window Set the type of sound that the computer where the PlantVisorPRO supervisor is installed will make when the alarm window is displayed Relay see the Full user manual for configuring the relays Important note for Fax SMS and E mail using the button on these pages an action can be created for sending the schedule alarm via the peripheral to all the numbers or addresses set in the address book Example If the fax modem has two numbers in the address book pressing creates the Fax Action in the scheduler meaning the alarm fax will be sent via the modem to these 2 numbers To set the configuration of the supervisor Input Output peripher
11. the user N B guardianPRO must be configured with at least one alarm signal even simply Alarm window to avoid restarting the unit if guardianPRO cannot signal the alarm situation 7 1 guardian bl To access the general configuration of the guardian function from the Configuration menu select the System pages item and then the guardian tab the following page will be displayed an Global w admin PUPRO locale 3 2006 12 16 16 21 48 System pages Information System quardianPRO Notifications GUARDIAN configuration page Configuration Computer localhost Port 1974 Guardian status Working Enable active alarms verification Variables configuration ba Available variables Monitored variables a Gy fin 33 C 1 gt Virtual probe F Li 4 Check frequency imin agg Number of consecutive constant values to notify an error 214748 In the Configuration section set the computer and the port where guardianPRO is connected e Computer name or IP address where the guardianPRO is installed leave localhost e Port number of the port on the computer where guardianPRO is connected leave 1974 Consult the Full User Manual and contact the network administrator if guardianPRO is installed on another computer in the network Code 030220491 rel 2 1 11 12 06 43 Quick Guide PlantVisorPRO Locale In the Variables configuration sec
12. 36 04 Global I O configuration Fax SMS E mail Window The WAY file played when displaying the alarm window can be selected Warning the file must reside on the computer where the supervisor is installed Configuration Current Sound Sfoglia The Configuration section features 2 fields Current identifies the currently configured audio file Sound used to select with the Browse button an audio file resident on the PC where the supervisor is installed The file must have the wav extension Mp3 or file formats other than wav cannot be used N B The audio file selected must be resident on the computer where PlantVisorPRO is running and will only be played on this computer To save the settings click VI Code 030220491 rel 2 1 11 12 06 29 Quick Guide PlantVisorPRO Locale 4 1 6 Relay configuration To configure the relays select the Relay tab The following page will be displayed ant T i sor gt admin PYPROlocale 3 2006 12 19 15 37 07 Global 1 0 configuration Window LO Module 2 gt ON OFF relayi from serial Active status Resettype Resettime fi Manual seconds IR 33 0 1 gt 4U enabling command Active status Reset type Reset time a Manual aj seconds For further information on this function see the Full user manual Locale For each relay select the field Active status to chose in which status 0 or 1 the relay is cons
13. PlantVisorPRO Locale CAREL CAREL PlantVisorPRO all you need Where you need It Quick guide LEGGI E CONSERVA ce ISTRUZIONI lt READ AND SAVE THESE INSTRUCTIONS Technology amp Evolution Contents 1 Accessingthesupervisor 1 11 10r0rre rire 5 I I SySt6Mautneniicalolyssecal lella iene 6 2 Configuring the devices in the Site cccccsssesseseeceeseseesseeeeseeseeneesenseesonseeseneeesonsees 7 3 Changing the device SettinGS cccssccessccesseeesseseeseeesseceaeenensenensesensenensennsenaeeoeaees 11 3 1 Changing the activation Of the alarMS 13 3 2 Changing the activation of the variable lO 14 3 3 Changing the description of the variableS 16 A 2 00 6 1 MOIO ere ae ee ere reo ei een ea ere ee ee ee eS 17 SS cAlNi gGiridiol bialbero 18 d SChedule il cccaaa 20 4 12 Configuringthe lO peripheralsS Leila aisi 20 4 2 Testing the operation of the I O peripheralS 30 4 3 Configuring the alarms and events iii 31 4 4 Managing the scheduled activities i 37 5 Groups and Areas if included in the version s11 ssrsireiiii iii 42 6 Registering the Product iscitati antiaerei Eee Ana eCa ARa Aae AC AACA 42 7 Configuring guardianPRO ssssssnnsnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnmnnn nnmnnn 43 Pa
14. als select the item I O configuration from the Scheduler menu io The following page will be displayed o lantVisor EZ Global I O configuration Fax Window Select the modem used to send FAXES and enter the details of possible recipients in the address book In addition both the number of attempts to be performed after the failure of the first attempt and the delay between one attempt and the next can be Configuration Modem Switchboard Number of attempts o Try again after fo minutes Address book Reference o M Address x Code 030220491 rel 2 1 11 12 06 20 Quick Guide PlantVisorPRO Locale 4 1 1 Setting the modem to send faxes To set the modem used to send faxes select the Fax tab admin 1 19 07 2006 15 00 08 I 0 configuration Fax Window Select the modem used to send FAXES and enter the details of possible recipients in the address book In addition both the number of attempts to be performed after the failure of the first attempt and the delay between one attempt and the next can be Configuration Modem Switchboard Number of attempts fo Try again after o minutes Address book Foca A PETTINE EER Address 2 uJ The Configuration section features 3 fields e Modem this field is used to select one of the modems installed on the supervisor computer This modem will be used to send faxes e Switch
15. be used by GUARDIAN when errors arise Configuration Address book Notifications list FAX mtd Ih The address book will include all the recipients of the signals from the scheduler One or more recipients in the address book can be used or alternatively again in the Configuring the I O peripherals pages a specific recipient can be entered for the signals from the guardian If a Scheduler address book entry is removed this event will not affect the list in guardianPRO which is managed separately e a DI fi UG E From the Address book list select the addresses or the numbers to send the guardianPRO signals to then click lad to add these to the List of signals In the event of an error when entering select the incorrect item in the List of signals and click uJ To save the settings click Code 030220491 rel 2 1 11 12 06 44 Quick Guide PlantVisorPRO Locale 8 Glossary Active alarm Active alarms are alarms whose causes are still present Alarm Alarms are status signals sent by the devices to the supervisory system and then processed to indicate abnormal situations or faults Alarm report The alarm report is a table that based on a start and end date set by the user displays all the alarms that have occurred over a set period Area Logical set of groups and or devices Daily report The daily report is a table that displays the values of certain logged variables selected by
16. board in this field set the number that allows external calls in case the modem telephone line passes through the switchboard e Number of attempts this field is used to set the number of successive attempts the supervisor will make to send a fax if the first attempt fails e Try again after this field is used to set the number of minutes that must elapse between one attempt and the next The supervisor will try to send a fax and if the modem is busy or there are problems during transmission will wait the set number of minutes and then try to send the fax again If the modem cannot send the fax the supervisor will make the number of attempts set by the user The process for resending the fax ends either when the fax is sent successfully or the number of attempts is completed Note the number of attempts if is set to zero the supervisor will only make on attempt to send the fax The Address book area is used to set the fax numbers for sending the faxes The fax will always be sent to all the recipients on the list Code 030220491 rel 2 1 11 12 06 21 Quick Guide PlantVisorPRO Locale To add an item in the Reference field enter a cue name for the fax number being added then in the Address field enter the fax number R admin 1 19 06 2006 16 11 11 Global 1 0 configuration Fax E mail RAS Window Relay gt vV Select the modem used to send FAXES and enter the details of possible recipients in the ad
17. d the type of serial converter used in the protocol field Note the RS485 protocol is used for the PC485KIT00 converter 98C425C001 the RS485N protocol is used for the PC Gate serial converter CVSTD00000 or for the USB converter CVSTDUMORO Each line contains devices that must each be set with their own address Code 030220491 rel 2 1 11 12 06 9 Quick Guide PlantVisorPRO Locale With reference to the Devices section enter the devices in the serial line select the first address from the From address list the last address from the To address list and the type of device entered within such range from the Description list then click admin 1 19 06 2006 14 14 12 Site configuration Site New line Alarms safety Configuration of serial line no 1 This page is used to configure the devices connected to a line To add devices select the serial address for a range of addresses to add more than one device of the same type define the type of device connected then click the image To remo Connection n port comi Baud rate 19200 Protocol CAREL RS485N Default value Devices Description MasterCase Serial CR en nae SE Device description io al gt To address 5 x From address oOo om oo ow mi the set configuration will be displayed in the list of devices admin 1 19 06 2006 14 15 34 i i w Site confi
18. ddress Yersion Product folder Software folder Installation Type Serial number Activation code admin PYPRO locale 3 2006 12 18 16 30 23 n quardianPRO Notifications Windows XP 5 1 Service Pack 2 US_en Vendor ID IDT Centaur Via Inc CPU Type ID 0 Family ID 6 Model ID 9 Stepping Code 8 Brand ID VIA Nehemiah 490 996 KB SI 2 31 616 MB 6 530 MB 00 90 05 D6 0E F6 PlantVisorPRO version 2 0b C Carel PlantVisorPRO C Carel PlantVisorPRO engine webapps wWebSupervisory Locale Advanced m On the www carel com site click the Request PlantVisorPRO activation code link complete all the fields on the application form Code 030220491 rel 2 1 11 12 06 42 Quick Guide PlantVisorPRO Locale Important The MAC address on the PlantVisorPRO system page is required as well as the Serial Number printed on the CD or on the label at the bottom in the case of PlantVisorPRO Embedded Once the data have been confirmed a page will be displayed showing the activation code to be entered in the system page To save the activation code for the supervisor click Then logout and login to PlantVisorPRO again 7 Configuring guardianPRO guardianPRO is an application that ensures maximum system reliability All the processes are monitored and in the event of hardware or supervision software faults guardianPRO independently generates an alarm signal via SMS fax or e mail to warn
19. dress Alarm high temperature virtual probe HI Alarm low temperature virtual probe LO amp larm case clean management Defrost interrupted for timeout signalling Valve driver LAN error Alarm SH temperature probe amp larm evaporation pressure probe Alarm duty setting from digital input signalling External delay alarm from dig input signalling Description Default description Italiano Multilanguage English description peo d re The tab contains the descriptions of all the variables Double clicking an item loads the Description section allowing the user to change the description both in the default language Default description field and in any other languages an description tab installed when setting up the supervisor To save the changes click Code 030220491 rel 2 1 11 12 06 16 Quick Guide PlantVisorPRO Locale 3 4 Adding notes Notes can be entered for device To do this click the Notes tab the following page will be displayed admin 1 19 07 2006 14 49 40 Global Site configuration gt line configuration gt device configuration Main Alarm variables Variables Descriptions list Main variables n V Enter date ca iii eS mu EE In the Note field enter the desired text To save the note entered click i The note will be saved with the date and time it was entered and the author admin 1 19 07 2006 14 52 58 Site confi
20. dress book In addition both the number of attempts to be performed after the failure of the first attempt and the delay between one attempt and the next can be Configuration Modem Agere Systems 40 97 Modem aj Switchboard Number of atternpts io Try again after 5 minutes Address book Reference verify Address 15564448351346 fermento Indirizzo uJ Then click gt The address book will be updated admin 1 19 06 2006 16 12 51 Global 1 0 configuration Fax E mail RAS Window Relay 2 Select the modem used to send FAXES and enter the details of possible recipients in the address book In addition both the number of attempts to be performed after the failure of the first attempt and the delay between one attempt and the next can be Configuration Modem Agere Systems AC 97 Modem Switchboard Mumber of attempts fo Try again after E minutes Address book Reference Address x O Riferimento SS A Verity 15564445351346 Click VI The settings will then be saved Code 030220491 rel 2 1 11 12 06 22 Quick Guide PlantVisorPRO Locale Changing an item in the fax Address book To change an item in the Address book section select the desired item by double clicking it and then edit the desired fields admin 1 197 Global 1 0 configuration Fax Window Select the modem used to send FAXES and ente
21. e name of the site is used to indicate a PlantVisorPRO installation that is accessible via a remote connection Supervisor Program that can manage the hardware connected to the computer Its main task is to check the status of the devices and implement actions according to the rules set by the user keeping trace of such actions User A user is a subject who is approved and authorised to access the supervisor Variable Each device has a number of variables which are configuration parameters and or status conditions of the device Code 030220491 rel 2 1 11 12 06 45 Technology amp Evolution CAREL S p A Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 http www carel com e mail carel carel com Agenzia Agency Code 030220491 rel 2 1 dated 11 12 06
22. er a name that identifies the installation where PlantVisorPRO Locale is installed This site will be listed under this name on any Remote supervisors for example Supermarket Refrigeration The Identifier field allows the PlantVisorPRO Remote supervisor to distinguish a local installation from other local sites As a result in the Identifier field enter a different number from those used for the other sites This field is used together with the password to control access when communicating with PlantVisorPro Remote For the connection between the local and remote sites to be successful the Identifier and Password must coincide on both supervisors Consequently enter a different string of characters and or numbers in the Identifier field for each installation One useful suggestion is to use the phone number of the site being configured as the identifier The Telephone field is a useful piece of information when the site is connected to a Remote supervisor via a dedicated modem Enter the phone number of the line that the modem is connected to The Password field is required to protect access to the supervisory system when this is connected to a dedicated modem The password is then required to access this site via a remote connection The minimum number of characters is 6 and the maximum is 16 and distinction is made between upper and lower case In the Confirm password field repeat the same passwo
23. et the time from 8 00 to 9 00 Scheduled activities management Rules sta it i Always Time bands Description WorkDays ha Type Weekly Time bands Actions Daily ne M mon M Tue M Wed Mi Thu Iv Fri a Sat LI Sun CE from 00 00 to oo w 00 Then click Finally click to save the changes made Now to set the rules click the Rules tab The following page will be displayed Code 030220491 rel 2 1 11 12 06 40 Quick Guide PlantVisorPRO Locale admin 1 19 06 2006 17 44 39 Scheduled activites management Actions Rules Time bands Commento alla pagina Rule Description weekly relay di Enabled W Time bands WorkDays aj di Actions Allar Action aj B In the Rules section enter a cue name in the Description field for the rule being created for example Weekly fax Check the Enabled field Select the desired time band for example Workday Select the action you want to set for example Alarm action LTES Click The settings will then be saved and become operational Code 030220491 rel 2 1 11 12 06 41 Quick Guide PlantVisorPRO Locale 5 Groups and Areas if included in the version Groups are logical groupings of devices These are displayed in the form of lists in the menu with the icon Groups are useful for identifying a set of devices with the
24. guration Site New line amp larms safety Notes Vv To add devices select the serial address for a range of addresses to add more than one device of the same type define the type of device connected then click the image To remo Connection n port comi a Baud rate 19200 Protocol CAREL RS485N Default value Devices Description mastercase O N Serial address Device description 1 Masterlase 1 2 Masterlase 2 From address fi DI a MasterCase 3 4 MasterCase 4 5 Masterlase 5 To address 5 x 6 7 q 10 zi Clicking saves the settings and returns to the Site configuration page Code 030220491 rel 2 1 11 12 06 10 Quick Guide PlantVisorPRO Locale 3 Changing the device settings admin 1 19 07 2006 14 21 59 Site configuration Site New line Alarms safety This page is used to set the site information To edit a configured line double click the row in the list below To remove a line select the its row in the list below and then click the image Site information Mame supermarket Identifier far Telephone 390493298985 Password evens si Confirm password essene List of line CAREL RS435M To change the settings for a device such as name displayed in PlantVisorPRO remote select the Site configuration item from the Configuration menu Then double click the line that the device belongs to and the following page will be disp
25. guration gt line configuration gt device configuration Main Alarm variables Variables Descriptions list Main variables 19 07 2006 02 52 19 07 2006 02 52 admin First note This is a single note Enter date Last update User Note Code 030220491 rel 2 1 11 12 06 17 Quick Guide PlantVisorPRO Locale When clicking a note in the list of notes cy y admin 1 19 07 2006 14 55 02 9 T Site configuration gt line configuration gt device configuration Main Alarm variables Variables 19 07 2006 02 52 19 07 2006 02 54 admin First note This is a single note First note This is a single note admin 1 19 07 2006 14 56 24 Global Site configuration gt line configuration gt device configuration Main Alarm variables Variables Descriptions list Main variables n DET T rs Pini y j j Clicking saves the changes made N B Only the author has the right to edit or delete their own notes 3 5 Alarm guardian This function ensures that all the alarms are acknowledged and failure of the scheduler to signal an alarm is notified Code 030220491 rel 2 1 11 12 06 18 Quick Guide PlantVisorPRO Locale Click the site configuration link Site configuration gt line configuration gt device configuration Then select the Alarm guardian tab the following window will be displayed admin P YPRO locale 3 2006 12 18 12 08 22 S
26. he address book In addition both the number of attempts to be performed after the failure of the first attempt and the delay between one attempt and the next Configuration Switchboard Type g Analogico GSM Number of attempts fa Provider GREAT BRITAIN Vodafone Try again after o minutes Call Nazionale Modem Address book Reference a ius ee Sddress x The Configuration section features 6 fields e Modem this field is used to select one of the modems analogue or GSM installed on the supervisor computer This modem will be used to send the SMS messages e Switchboard in this field set the number that allows external calls in case the modem telephone line passes through the switchboard e Type this field is used to set the type Analogue or GSM of modem that is selected in the modem field e Provider this field is used to select the provider used to send the SMS messages If a GSM modem is used select Direct SMS xxx where xxx is the model of GSM modem supported Currently the following are supported Falcom Twist Siemens T35 Wavecom e Call select whether or not the call is international National or International Number of attempts this field is used to set the number of successive attempts the supervisor will make when sending an SMS if the first attempt fails N B This function is only valid for managing the calls made by the analogue
27. ick Here To add a new action enter the description then click the image Then double click the new row entered in the list highlighted in red Description eee Ze Ze ZZZ Z Z Ze Ze Ze TZ TZ TZ ZZZ ZZZZZZZZZZZZZZZZZZZlZ Ze Ze ZZZ ZZZZZZZZZZZZZA cr Code 030220491 rel 2 1 11 12 06 33 Quick Guide PlantVisorPRO Locale Double click the red row in the list of actions and the following page will be opened Miele RI admin 1 19 06 2006 17 04 16 i i ig Global Alarms and events management gt action configuration Fax SMS Email Relays Variable Remote Print window Action Act 1 ziz mi Fax Address book numbers Numbers configured for the action Verifing gt El ba Assuming the desired actions are to send a fax and display the alarm window for the explanation of all the other settings see the PlantVisorPRO Full User Manual The Address book numbers tab in the Fax section contains the address book that has been set when configuring the fax modem see the chapter Configuring the I O peripherals sub chapter Setting the modem to send faxes Add the desired address book items by selecting them and then click To save the settings click admin 1 19 06 2006 17 06 16 Global Alarms and events management gt action configuration SMS Email Relays Variable Remote Print Window Action Act 1 Fax Address book numbers
28. idered active The relay is energised to provide an alarm signal Reset type can have three settings e Manual only the user via a special page in PlantVisorPRO Alarms Events Relay management can reset the relay e Automatic managed directly by PlantVisorPRO when the alarm passes the relay is automatically reset e Timed the relay remains energised for the time set in the Reset time field N B the relays can always be reset manually even when Timed and Automatic management is set To save the settings click i 4 2 Testing the operation of the I O peripherals To test the operation of the supervisor Input Output peripherals select the item I O test page from the Scheduler menu The following page will be displayed Code 030220491 rel 2 1 11 12 06 30 Quick Guide PlantVisorPRO Locale admin PYPRO locale 3 2006 12 16 15 38 52 Global 1 0 test page Test IZO To execute the test select an action type and its recipient then click the button S Action types Fax sms E mail Remote connection we Print Relay Alarm window e Inthe Action type section select the I O peripheral to be tested e Select the recipient e Click The I O peripheral will be activated so as to test its operation 4 3 Managing the alarms and events After having configured all the I O peripherals the list of alarms managed by the scheduler needs to be set By defau
29. ion used to send EMAIL messages and enter the details of possible recipients in the address book Configuration SMTP fisz168 0 30 ii Connection Lam Dialup Sender industry industry com a Provider Mee El Number of attempts fio Try again after 5 minutes Address book Reference Reference da MEV siIndirizzo Address Reference reference com Xx Referenc Reference reference com admin 1 19706 2006 16 30 50 Global 1 0 configuration Fax E mail Window Relay gt V Select the SMTP server the sender and the type of connection used to send EMAIL messages and enter the details of possible recipients in the address book Configuration SMTP fisz168 0 30 Connection C Lan Dialup Sender industry industry com Provider Teee El Number of attempts fo Try again after E minutes Address book Reference Address fF Riferimento Indize Reference Reference reference cam amp UG To save the settings click Vj Code 030220491 rel 2 1 11 12 06 27 Quick Guide PlantVisorPRO Locale 4 1 4 Setting the remote calls To set the possibility of calling a remote computer select the RAS tab i admin 1 19 06 7006 16 33 21 Global I O configuration Fax SMS E mail Window Relay Select the modem used for the calls to the Remote Supervisor and enter the details of possible recipients of the call in the address book In addi
30. ite configuration Site New line Alarms safety Notes Page for setting the alarm forwarding control system This function can be used to notify any alarms the scheduler fails to signal within the set time Remember that this time period is not the same as the delay set for each rule in the scheduler configuration In addition the function for viewing the alarms for each type of priority can also be enabled on this page Vv Del Highest Minutes High Minutes fiso iso Medium jio Minutes zao Minutes For each level of alarm priority see Chap 3 1 there are two fields e Maximum time to manage the alarms this function notifies the failure of the scheduler to signal an alarm within the set time Remember that this time is not the same as the delay set for each rule when configuring the scheduler see Chap 4 4 e Can be acknowledged function for acknowledging the alarms with different levels of priority Acknowledgement simply highlights that the alarm has formally been read by a registered and authorised user Example The high priority alarms have a maximum management time of 180 minutes For a certain type of high priority alarm the scheduler is programmed to send a fax When the high priority alarm is activated the scheduler attempts to send a fax but due to technical problems e g line disconnected these attempts fail After 180 minutes the guardianPRO notifies the failure to send the alarm
31. l OUNd aesa aaa Errore Il segnalibro non definito AEREE E AO E E Le 44 E E O h indici E E E E E EEE E E 45 1 Accessing the supervisor To access PlantVisorPRO Locale open the following page in the browser User Password Language Quick Guide PlantVisorPRO Locale admin levees English SERS to do this select the link called Supervisor login page under Program Files PlantVisorPRO from the Windows Supervisor login page menu F Impostazioni accesso ai programmi HE Program Updates t windows Update Accessori im Accessories CAREL Esecuzione automatica m PlantvisorPRO PostgreSQL 8 1 aP Software activation at Supervisor login page Fa DpernDffice org 2 0 Trend Micro OfficeScan Client F Adobe Reader 7 0 li Assistenza remota E Internet Explorer ea Outlook Express Tutti i programmi amp Windows Media Player A Disconnetti Chiudi sessione Code 030220491 rel 2 1 11 12 06 Quick Guide PlantVisorPRO Locale 1 1 System authentication To access PlantVisorPRO type User admin Password admin only use lower case and click Login to confirm access the following page will be displayed admin 1 19 06 2006 13 57 24 Globale Main Parameters Alarms HACCP graph Log graph Conf Graph Notes S a X aama _ _ __ _ __ i Devices non presenti S Tabs Menu Icon
32. layed with the details of the line R admin 1 19 07 2006 14 25 27 P Site configuration line configuration Display line Edit line Notes Configuration of serial line no 1 me To access the configuration of a device double click the corresponding row in the list below tao Configured devices Serial address Device description MasterCase MasterCase MasterCase MasterCase Master ase MasterCase MasterCase MasterCase Masterlase Masterlase Connection Baud rate 19200 aj Protocol T RS Default value Double click the device being modified thus entering the device configuration section and accessing the page for changing the description Code 030220491 rel 2 1 11 12 06 11 Quick Guide PlantVisorPRO Locale admin il 19 07 2006 14 27 13 Site configuration gt line configuration gt device configuration Main Alarm variables Variables Descriptions list Main variables The description of the device can be changed and the device disabled S Description A Default Sen Multilanguage di SA description MasterCase 1 ni maahi English MasterCase 1 E Lr Italiano Aoo La Status Ir Disable the device alarms configured in SCHEDULER section will not be managed In the Description section the descriptions can be changed for each of the various languages installed In the Default descri
33. list highlighted in red a Name l je ita ug The row in the list of the actions that was previously highlighted is no longer red and shows the ticks corresponding of the types of action set in this example in the Fax and Window columns Code 030220491 rel 2 1 11 12 06 35 Quick Guide PlantVisorPRO Locale Rules Now select the Rules tab The following page will be displayed admin 1 19 06 2006 16 49 15 Global Alarms and events management Rules Alarm conditions Event conditions Time bands Actions Rule Description s Enabled Iv p i i Condition gt Delay minutes Actions Time bands In the Rules section enter a cue name in the Description field for the rules being created for example General rules Then select the previously created condition to be used for example All Select the time band for example Always N B the Always time band is the default and this therefore does not need to be set in the Time bands section Select the action for example Alarm action Enter the delay in minutes for the implementation of the rules in response to an alarm click The settings will then be saved The following page will be displayed admin 1 19 06 2006 17 16 56 Global Alarms and events management Rules Alarm conditions Event conditions Time bands Actions
34. lt a list is included with all the alarms for all the instruments Below are the instructions on using this default setting See the Full user manual for the instruction on how to set different lists of alarms The scheduler is made up of a set of Rules that are continuously checked and updated A rule includes a alist of alarm conditions alarms deriving from the field devices b a series of time bands that determine the periods when the alarm is valid c a series of actions for signalling the alarm to the outside world Before defining a Rule therefore first its components need to be defined To signal all the alarms proceed as follows Alarm condition Configure the management of alarms and events in the supervisor selecting the Alarm and event management item from the Scheduler menu io The following page will be displayed Code 030220491 rel 2 1 11 12 06 31 Quick Guide PlantVisorPRO Locale admin 1 19 06 2006 16 49 15 Global Alarms and events management Actions Time bands Event conditions Rules alarm conditions F Rule Description i Enabled Ca i Actions Condition Time bands Delay minutes Select the Conditions tab The following page will be displayed admin 1 19 06 2006 16 51 34 Global Alarms and events management Actions Time bands Rules Alarm conditions Event conditions
35. providers require a valid sender address accepted by the mail server contact your service provider for details Connection this field is used to set whether the mail server is in the LAN or is accessed via modem DialUp The following fields are only enabled if the DialUp option is selected the Connection field Provider this field is used to select the provider used for the connection This list includes all the providers set in the Windows Control panel under Network connections Number of attempts This field is used to set the number of successive attempts the supervisor will make when sending an email if the first attempt fails N B This function is only valid for managing the calls made by the analogue modem to the service provider or for checking the availability of the analogue GSM modem as the effective delivery to destination of the SMS message cannot be checked Try again after This field is used to set the number of minutes that must elapse between one failed attempt and the next Once all the settings have been completed enter the address book for sending the e mails Code 030220491 rel 2 1 11 12 06 25 Quick Guide PlantVisorPRO Locale To add an item in the Reference field enter a cue name for the recipient being added then enter the e mail address in the Address field admin 1 19 06 2006 16 26 24 Global 1 0 configuration Window Fax E mail w Select the
36. ption field enter the new description in the default language set during installation In the Multilanguage description tab enter the corresponding description of the device for the various languages available In the Status section the status of the device can be changed with reference to the supervisor The Disable the device alarms configured in SCHEDULER section will not be managed check box is used to disable the device for the supervisor that is the device will continue to physically operate but the supervisor will consider it as being disabled and will not show nor manage any alarms A typical application of this is when a refrigeration unit is placed in standby Clicking saves the settings Code 030220491 rel 2 1 11 12 06 12 Quick Guide PlantVisorPRO Locale 3 1 Changing the activation of the alarms To change the activation of the alarms click the Alarm variables tab The following page will be displayed admin 1 19 07 2006 14 30 05 T Main variables Main Alarm variables Variables Descriptions list List of all device alarm variables A To display and record an alarm select it from the list below For each selected alarm the priority can be set Frequency for checking the alarms ao seconds Tr Mr cEi iiiieeleeao e Vv Alarm high temperature virtual probe HI Highest Vv Alarm low temperature virtual probe LO Highest a Vv Alarm
37. r the details of possible recipients in the address book In addition both the number of attempts to be performed after the failure of the first attempt and the delay between one attempt and the next can be Configuration Modem Agere Systems AC 97 Modem aj Switchboard Number of attempts jio Try again after E minutes Address book Reference verifing Address 15564448351346 Te Verify 1556444351346 Oi amp admin 1 19 06 2006 16 16 26 Global I O configuration Fax E mail RAS Window Relay Select the modem used to send FASES and enter the details of possible recipients in the address book In addition both the number ot attempts to be performed after the failure of the first attempt and the delay between one attempt and the next can be Configuration Modem Agere Systems AC 97 Modem aj Switchboard Number of attempts 10 Try again after E minutes Address book Reference gt Address fp Rifenmento Indies Verifing 15564445351346 Ej To save the settings click VI Code 030220491 rel 2 1 11 12 06 23 Quick Guide PlantVisorPRO Locale 4 1 2 Setting the modem to send SMS messages To set the modem used for sending SMS messages select the SMS tab admin 1 19706 2006 16 19 22 Global 1 0 configuration Window Fax Select the modem used to send SMS messages and enter the details of possible recipients in t
38. rd The password will only be accepted if the data in the Password and Confirm password fields are identical To save the settings click VI To set the lines select the New Line tab admin 1 19 06 2006 14 05 56 i i i Tid Global Site configuration This page is used to set the site information To edit a configured line double click the row in the list below To remove a line select the its row in the list below and then click the image Site information Name PlantVisor PRO Identifier supervisori Telephone Password Confirm password List of line Code 030220491 rel 2 1 11 12 06 8 Quick Guide PlantVisorPRO Locale The following page will be opened R i admin 1 19 06 2006 14 11 06 Site configuration Site New line Alarms safety Configuration of serial line no 1 This page is used to configure the devices connected to a line To add devices select the serial address for a range of addresses to add more than one device of the same type define the type of device connected then click the image To remo From address E i To address E x Le Set the serial port on the computer that the converter is connected to usually COM1 in the COM port field e the transmission speed of the port usually 19200 baud in the Baud rate field e the type of communication protocol which depends on the type of device an
39. riable the log duration Once occupied all the log space established by the user the oldest data are over written TL logdeph i E months 301 Code 030220491 rel 2 1 11 12 06 14 Quick Guide PlantVisorPRO Locale The Frequency column allows selecting for each variable the time interval in which the supervisor makes the sampling Ire 300 SEC AN zen The Minimum variation column shows which is the minimum curve definition step In the graph To save the setting click Vj Example If the variable is set with Duration 1 month Minimum variation 0 2 Frequency 5 minutes Log start 19 09 2006 at 11 30 The graph will be the following 0 7 0 5 LO 11 30 00 09 19 11 35 00 11 40 00 Code 030220491 rel 2 1 11 12 06 15 Quick Guide PlantVisorPRO Locale 3 3 Changing the description of the variables The description of the variables relating to a device description of the parameters description of the alarms names of the probes etc can be changed to do this click the Descriptions List tab the following page will be displayed m t Y iIsSor I REE Global Site configuration gt line configuration gt device configuration Main Slarm variables Variables Descriptions list Main variables Notes The descriptions of all the device variables can be edited To edit a description double click the corresponding row in the list below Yariable descriptions Serial ad
40. same features e g all IRmpx a set of devices with the same type of product stored e g dairy showcases fruit and vegetables frozen food The advantages of using groups derive from the immediateness of the information displayed and the possibility to create different types of management for each group With the groups is possible create variables of group Areas are logical groupings of groups and or of devices These are displayed in the bar at the top If supervising a refrigeration installation in a supermarket areas can be created to identify similar devices and or groups For example the low temperature and the normal temperature devices can be grouped together dairy showcases LT utilities or NT utilities fruit and vegetables frozen foods the groups can be added depending on the type to an area For further information and how to configure these see the chapters on Groups and Areas in the PlantVisorPRO Full User Manual 6 Registering the product To register the product from the Configuration menu select the System pages item the following page will be displayed Information System N 5 Mr ASCIUTTI SLI PERTTI 1 a ii gt hang PiantVisor Global System pages System System language Processor Total physical memory RAM Used physical memory RAM percentage Used CPU percentage Free space Used space MAC a
41. the user for a specific date Device Device refers to an electronic device connected to a supervisory network that can be managed by PlantVisorPRO Event Events are sets of information sent by the devices I O peripherals or generated by the supervisor This information communicates the general operating status of the supervisor Group Logical set of devices Group variables can be created for the groups Group variable logical extension of variables with write access that belong to different devices that have been entered in the same group Instant value report The instant value report is a table that displays the instant values those measured at the moment of printing the report of the variables for a certain device Local supervisor A local supervisor is a system for controlling and managing devices Log report The alarm log report is a table that based on a start and end date set by the user displays the values of certain logged variables selected by the user Network A network is a series of devices connected to and supervised by PlantVisorPRO devices converters etc Remote supervisor A remote supervisor is a centralised system for controlling the local supervisors Report Reports are tables generated according to time that contain the data of the logged variables Reset alarm Reset alarms are alarm events whose causes are no longer present Site A site is any installation managed by PlantVisorPRO Normally th
42. then be saved Code 030220491 rel 2 1 11 12 06 37 Quick Guide PlantVisorPRO Locale Subsequently double click the new row that has been entered in the list highlighted in red This will allow the type of operation to be set for this action admin 1 19 06 2006 17 30 32 Global Scheduled activities management Rules Time bands Actions To edit an action double click the corresponding row in the list below To add a new action enter the description then click the image Then double click the new row entered in the list highlighted in red mia CS LAI Description H m Double click the red row in the list of actions the following page will be opened Q a ae ee admin 1 19 06 2006 17 28 30 Scheduled activities management gt action configuration SMS Email Relays Variable Remote Print Window vi Sts Action Allarm Action Address book numbers Numbers configured for the action i Assuming the desired actions are to send a fax and display the alarm window for the explanation of all the other settings see the PlantVisorPRO Full User Manual The Address book numbers tab in the Fax section contains the address book that has been set when configuring the fax modem see the chapter Configuring the I O peripherals sub chapter Setting the modem to send faxes Enter the desired address book items by selecting them and then click lad To save the
43. tion a number of device probes can be selected that guardianPRO monitors independently of PlantVisorPRO This monitoring process makes sure that reliable values are always received from the field devices Choose the device with the variable to be managed by guardian from the Device list box From the Variables available select the variables to be monitored by guardian Click lad to add these to the Monitored variables list To remove a controlled variable from the list select it and click x Repeat this procedure from point 1 to point 3 for each group of variables on the devices being monitored Set how often to activate the guardian in minutes in the Monitoring frequency min field Set the Monitoring frequency and Number of constant consecutive values to signal an error that is the for how long the probes have a constant value before assuming a communication error with the field devices For a minimum configuration select at least one probe on 2 3 different instruments and leave the two preset values at 10 SRI PT Once the settings have been completed click to save the configuration Then select the Signals tab 7 2 Signals Once having selected the Signals tab the following page will be displayed PlantVisor ee Global System pages Information System guardianPRo Notifications 4 Configuration page for GUARDIAN s notifications Configured notifications will
44. tion both the number of attempts to be performed after the failure of the first attempt and the delay bet sa A Configuration Modem Switchboard E Number of attempts o Try again after o minutes Address book a number ud E Identifier F u a The Configuration section features 6 fields e Modem this field is used to select one of the modems installed on the supervisor computer This modem will be used to make remote calls connection to a PlantVisorPRO Remote supervisor e Switchboard in this field set the number that allows external calls in case the modem telephone line passes through the switchboard e Number of attempts This field is used to set the number of successive attempts the supervisor will make when contacting the remote supervisor e Try again after This field is used to set the number of minutes that must elapse between one failed attempt and the next e Reference Identifying name of the remote site that the local supervisor must connect to Number Telephone number of the remote supervisor VI To save the settings click Code 030220491 rel 2 1 11 12 06 28 Quick Guide PlantVisorPRO Locale 4 1 5 Setting the audio file played when displaying the alarm window Select the Window tab to set the audio file with wav extension to be played by the computer where the local supervisor is installed when displaying the alarm window admin 1 19 06 7006 16
Download Pdf Manuals
Related Search
Related Contents
Bedienungsanleitung Raptor 4all Kompaktbike Istruzioni per l'uso Operating Instructions Mode d'emploi Philips AZ 8030 User's Manual Numark Industries KMX02 Karaoke Machine User Manual ﺞﺋﺎﺗﻧﻟا - Faculté de Médecine et de Pharmacie de Fès Newsroom - Eurocom Cooker King Cooker King Kooker OUTDOOR COOKER User's Manual Approx appNB17B Copyright © All rights reserved.