1 Fire Detection Control Panels Series BC06

image

Contents

1. Specifications Operating voltage 20 to 31VDC Current consumption at 24V typ 22mA per activated circuit Control current typ 1 2mA per input Switching power per contact 1A 60V 30W Contact life unloaded approx 5m switching cycles at 24VDC 1A approx 300 000 switching cycles 169 BB072001 SAM 0720 01 0100 222010 169 BB072001 SAM 0720 01 0100 Chapter 6 Additional Modules for Fire Detection Control Panels 63 Ambient temperature 5 C to 50 C Dimensions L x W x H 85 x 65 x 37 mm Weight 130g Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 41 214128 Battery Bracket BK216 1CE 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 42 212034 Module Carrier 19 3HU MPL17 3 Relay Module 4 Fold 230VAC RL58 2 Componentry for the switching of consumer loads with increased power dema
2. 253 Lid for Detector Base Sounder White 45681 292 252 Lid for Sounder DBS Red DBSLIDR 252 Lid for Sounder DBS White DBSLIDW 252 Limit Switch Anal 500 SS EDS500 1 103 Line Monitoring Module TUM805 1 000 284 Linear Heat Detection Unit Alarmline Conv LWM 1 202 Lithium Battery 3 6V 2 2Ah Lithium Battery 9V 1 2Ah 04 Long Distance Modem BCnet216 MOD 1 56 Loop Interface LIF64 1 2 eee eee cee eee eee eee 35 249096 261008 261003 261009 261010 261005 261011 261006 261004 261019 261017 261018 245014 245395 245429 245372 245415 245352 245417 245021 245023 245402 245302 245389 245042 245040 245043 245041 245362 245356 245020 245022 245396 245392 245355 249078 249076 249102 249077 212034 249115 249100 249101 249060 249046 249061 249072 249091 244629 214029 244630 250606 250608 212031 359049 359022 249092 249095 244025 223032 214027 214033 214031 Product List M MCP Coding Module MCM1 1 Magnetic Clamp 1000N 1340 Magnetic Clamp 500N 1330 0 ee eee eee e ee ee Magnetic Clamp Reset 1000N 1360 Magnetic Clamp Reset 150mm 1000N 1380 15 Magnetic Clamp Reset 150mm 500N 1370 15 Magnetic Clamp Reset 300mm 1000N 1380 30 Magnetic Clamp Reset 300mm 500N 1370 30 Magnetic Clamp Reset 500N 1350 0 00 Magnetic Lock Clamp 2750N 1
3. 70 Chapter 8 Display and Operating Devices 250050 250009 250015 250016 Remote Display and Operating Panel ABF216 1 HR1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Croatian language Remote Tableau SG58 2 A1 Remote display panel for the monitored optical and acoustic display of all operating conditi ons of Fire Detection Control Panels Series BC016 BC216 and LBC The most important operating conditions are displayed by LED indicators In addition the integrated 4 line event text display provides the same information as the fire detection and the burglar alarm control panel The Remote Tableau SG58 2 A1 is actuated via the INFO bus of the control panel A Serial Interface Module SIM016 3 is required for connection to the Fire Detection Control Panel Series BC016 The connection to the Fire Detection Control Panel Series BC016 is possible without any additional devices Features 4 line event text display to provide clear information LED indicators for operation alarm fault transmitting device activation and fault Integrated buzzer with silence function Setable baudrate LED and LCD test functions Wall mount steel sheet cabinet Specifications Supply voltage 20 31VDC Current consumption at 24V 40mA quiescent 55mA active Amb
4. 19 Fire Detection Control Panel BC216 1S SLO1 19 Fire Detection Control Panel BCnet216 Description 20 Fire Detection Control Panel Module BCM216 3E 32 Fire Detection Control Panel Module LG BCM216 3ELG ccc cece ccc e nec ee tenes 32 Fire Detection Control Panel Module PS BCM2163BPS peer eee eg 31 Fire and Evacuation Panel BC016 2 D1 8 Fire and Evacuation Panel BCO16 2 INT1 7 Flame Detector IR Conv IR 10 00008 195 Flame Detector UV Conv NFD 68 P SOCKEL 194 Flame Detector UV Conv UV 03 00 000 cee eee 195 Flat Cable 1700mm 10 Pole FBK17 1 64 Flush Mounting Frame for FSK700 2 EZ700 2 D1 259 Flush Mounting Frame with Drilling Protection for FSK700 2 EZBS700 2 Front Foil FW TP 1A Front Foil FW TP 2 Front Foil FW TT 1 Front Foil for Evacuation Circuit FFEV06 1 5 G Gas Detector 230V GM MEIBU 230V 0 208 Gas Detector Methane GM METHAN 207 Gas Detector Propane GM PROPAN 06 207 Gateway IEC870 5 101 104 BC216 IEC870 BC216 GW 20 20 00 cece eee 56 Glass for MCP Series 10pcs G21140 173 Glue Tangit 0 12kg KLEB RAS 01 24 223 Glue Tangit 0 25kg KLEB RAS 02 025 224 Glue Tangit 0 5kg KLEB RAS 05 Glue Tangit Ikg KLEB RAS 169 BB072001 SAM 0720 01 0100 212028 359023 246027 246090 246023 240025
5. Optical Smoke Detector Anal 200 SS ND2251EM Addressable smoke detector operating on the light scatter principle for application on the ADM loop using System Sensor 200 protocol with an optical sensing chamber and of flat design suitable for indoor mounting Intelligent evaluation algorithms in the respective LST fire de I tection control panels compensate for the impact of contamina tion of the optical sensing system Thereby the response oN sensitivity of the detector is kept constant for a long time thus constituting another effective measure for preventing false r alarms 169 BB072001 SAM 0720 01 0100 Chapter 12 Analogue Detectors and Modules Series 200 500 91 Features Constant sensitivity 2 decadic rotary switches for setting the physical address from 01 to 99 Output for external remote indicator Mechanical theft protection Insect screen Functionality check by means of test activation with magnet Specifications Operating voltage supplied through loop voltage Current consumption max 200uA quiescent Ambient temperature 20 C to 60 C Relative humidity 10 to 93 no condensation Dimensions x H 102 x 45 mm Colour cream Weight 102g Approval VdS G200052 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 1
6. Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 47 2189990 Extinguishing Control Panel Series LC216 Description 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Multi Module Panel Mounting MEA244 1 E The addressable module MEA244 1 E provides 4 inputs and 4 outputs and is connected to a Fire Detection Control Panel Series BC216 via the ADM loop with System Sensor 200 pro tocol The inputs allow for the connection of contact detectors e g manual call points sprinkler system contacts supervising contact and are monitored for wire breakage and short circuit The outputs serve for the connection of control devices e g solenoid valves relay coils and provide a separate monitoring of line resi stance and load resistance The reference value of both resistances is determined by means of an automatic calibration procedure initiated with a keystroke during commissioning If one of the two resistance values differs from the refe rence value by more than 25 during operation the output is indicated as faulty The method of multiple monitoring patent pending provides a reliable detection of line faults or load faults The multi module is therefore ideally suitable for the application in extin guishing systems An optional accessory board allows for the hardware redundant actuation of solenoid valves according to EN 12094 1
7. Product Guide Fire Detection Systems Export 2007 2008 0720 01 SICHERHEITSSYSTEME Il Trademarks All brand names and product names used in this Product Guide are trade names service marks trademarks or registered trademarks of their respective owners 169 BB072001 SAM 0720 01 0100 HI Introduction 169 BB072001 SAM 0720 01 0100 Supported by the quality management system certified according to ISO9001 our products are developed manufactured and accurately tested in accordance to national and international standards as well as to our own strict regulations The planning of systems as well as the installation commissioning and maintenance of the products and of the systems combined thereof require specific expert knowledge and therefo re may only be made by trained expert personnel The product specific training of the expert personnel must be made by LST or by persons explicitly authorized by LST All valid country specific regulations and guidelines for the use of the products must be obeyed This Product Guide is under no circumstances a substitute for the detailed documentation of the individual products or for the product specific training of the expert personnel on proper and professio nal installation connection programming and operation of our products and of systems com bined thereof This Product Guide contains general information on the use for each product Descriptions pictures an
8. 0 cece eee ee ee eee ee 169 2171619 Replacement Glass for Manual Call Point Yellow ET SCH HM GE 0c cece eee ee eee 169 249024 Special Designation for Manual Call Point HM BESCH 0 cece eee ee eee e ect ee eee e eee 170 245040 Manual Call Point Red 200 Glass MCP5A RPOTFG 0 cee cece c eee eee t eee e een nn nee ees 170 245041 Manual Call Point Red 200 ISM Glass MCP5A RPO8FG 0 c cece cece eee eect e nee e eee eee 170 245042 Manual Call Point Red 200 Flexi MCPSA RPOTFF 0 0 cece cee ence ee eet e eee ten eee e ee 171 169 BB072001 SAM 0720 01 0100 18 19 20 169 BB072001 SAM 0720 01 0100 245043 245014 245019 245012 249213 Manual Call Point Red 200 ISM Flexi MCPSA RPO8FF resnvanuannavnennennvrnennernernenneen 172 Manual Call Point Anal XP95 Apo 55000 905 orrvvnanennnvennnennnnennnenarnennrennenenneer 172 Surface Mount Box MCPSA SR r nnenenanannaneneenenenenneneneneneenenerueneneneeneneneneene 173 Surface Mount Box MCP5A SR3T oo cece cn nnn te teen ence nese tees en EErEE ens 173 Glass for MCP Series 1Opcs G21140 oo cece nent teen ee tnn nee e ee nn ene eeene 173 Devices for Hazardous Areas 240015 242015 241090 240023 246090 246023 228003 240025 241024 242036 246027 228004 228005 241025 228006 228007 245680 IS Ionisation Smoke Detector Conv 100 SS 1151EIS aaavvavanavnnennnnnvvvrnanrvvrrnnnreveeenr 174 IS The
9. 0 0 cc ccc cece cence nee eee n ence nen eben en eee en eens 9 Fire Detection Control Panels Series BC216 2149999 214008 214000 214610 214006 214015 214007 214009 214017 214049 214080 214084 214086 214088 214308 214300 214304 214306 214315 214307 214309 214317 214349 214384 214388 2199998 214056 214004 214612 214060 214064 214062 214058 214066 Available Variants Series BEZIG synuan e ceca A eves sas rea cet edeaed cecweaceeseeveceees 10 Fire Detection Control Panel BC216 1 INT1 2 n ence nent e een een ens 12 Fire Detection Control Panel BC216 1 Al 0 occ ccc cece nnn e nent n nen e ee teen en eeee 14 Fire Detection Control Panel BC216 1 D1 0 occ cnn ce cence n nen e te eee nen eens 14 Fire Detection Control Panel BC216 1 B1 0 ccc cnn cence e nen ene n eee eee nen eens 14 Fire Detection Control Panel BC216 1 CZ1 oo ccccccecec cence nen e eee tn ene nn eens 14 Fire Detection Control Panel BC216 1 H1 0 ccc cnn ne cece cnet n enn eee eeen teens 15 Fire Detection Control Panel BC216 1 NL1 oo ccc cence cence nen e eee ene e nn enees 15 Fire Detection Control Panel BC216 1 SK1 oo ccc ccc cece cence center e nents 15 Fire Detection Control Panel BC216 1 HR1 2 ccc cece ence ence een ene nn ents 15 Fire Detection Control Panel BC216 1 RUS1 2 0 occ cece ce cece ence eee n cence ens 15 Fire Detection Control Panel BC216 1 SLO1 0 0 0 cence cnn cnet e teen eneenens 15 Fire Dete
10. 9V block battery included GP Super Alkaline 1604 A Eveready Alkaline 522 Duracell MN 1604 approx 85dB at 3m distance 0 C to 50 C 10 to 95 no condensation 110 x 40 mm signal white RAL 9003 150g VdS G200054 210 Chapter 21 Aspiration Smoke Detection Systems 21 Aspiration Smoke Detection Systems 244030 Aspiration Smoke Detection System A211E LSR The Aspiration Smoke Detection System A211E LSR aspirates air from the monitored room via the connected sensor pipe network and directs the air to a highly sensitive laser smoke de tector If the smoke concentration exceeds the permissible value an alarm is activated which is optically displayed on the system and can be further transmitted to a fire detection control panel The system can be used for early fire detection in room and equipment monitoring due to the high response sensitivity of the laser smoke detector Connection to the fire detection control panel is possible either in conventional technology via dry relay contacts or via an ADM loop using System Sensor 200 protocol The preferred mode of operation must be parameterised at the aspiration smoke detection system The converter module which is integrated in the aspiration smoke detection system constitu tes the interface for communication via the ADM loop It has one address assigned for both the detector and the control module A dual isolator disconnects the loop at short circuit
11. Address Module Conv Apo NG60 1 Electronic component for the application in addressable conventional technology used for in dividual or group identification of System Sensor Series 60 and 65 or Orbis automatic con ventional detectors as well as manual call points special detectors and other contact activating devices S Features Double digit indication of the detector number and text assignment on the display of a fire detection control panel Detector number setting from 0 to 63 Open collector output for triggering a remote indicator Alternatively applicable for individual detector addressing or identification of a detector group Specifications Current consumption at 24V 18mA active Ambient temperature 5 C to 50 C Dimensions L x W x H 38 x 19 x 5 mm without leads Weight 50g 156 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY Cross references Page Art Nr Name Type 35 214020 Conventional Detector Interface GIF8 1 149 246035 Detector Base Conv 60 65 Apo 45681 251 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 249039 Address Cards 100pcs Anal XP95 Disc Apo CK 38531 771 The address card is used for setting the physical address in the detector base of an automatic fire detector Series XP
12. Features Connection of manual call points automatic detectors conventional detector modules control modules and signalling devices in ADM technology ADM loop wiring can be realised as ring branch or any given combination of sectional rings and branches using unscreened cables Two isolator modules at the beginning and the end of the ADM loop are integrated on the componentry Connection of 198 physical address points 99 detectors and 99 modules using System Sensor 200 protocol Connection of 126 physical address points detectors or modules using Apollo Discovery protocol Full function of all elements in case of wire breakage on the ADM loop line 36 Chapter 3 Fire Detection Control Panels Series BC216 214022 At short circuit all elements not affected are fully operable thanks to the installed isolator modules Independent CMOS processor to ensure the alarming capability even at system failure of the control panel Specifications Current consumption at 24V typ 25mA without detectors modules Idle loop current typ 300uA per detector module Total loop current max 300mA at reduced line resistance Idle loop voltage typ 26V Apollo Discovery or typ 29V System Sensor 200 Loop line resistance max 50 Ohm per core Ambient temperature 5 C to 50 C Dimensions L x W x H 132 x 74 x 10 mm Weight 80g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25
13. KJK Specifications Operating voltage Current consumption from loop Sound level Easy address setting via DIL switch Long lifespan of strobe due to the use of LEDs Integrated dual isolator with yellow status LED indicator supply through the loop voltage max 1 2mA quiescent max 9mA sounder and strobe on 100dB A 1m distance Flash frequency 1Hz Ambient temperature 20 C to 70 C Relative Humidity max 95 no condensation Protection class IP66 Dimensions x D 110 x 113 mm Colour red Weight 305g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Strobe FB XP95 White Red 55000 877 The addressable loop powered strobe 55000 877 with a red cap is integrated in a white pla stic housing It is triggered and supplied like a module via the ADM loop using Apollo Disco Features Low power consumption Suitable for surface mounting very protocol The strobe is designed to be inserted into a detector base Series XP95 Discovery and is suitable for indoor mounting Long life span due to use of LEDs Specifications Operating voltage Current consumption supply through the loop voltage typ 150A quiescent max 3mA active Ambient temperature 10 C to 60 C Protection class IP42 Dimensions x H 100 x 52 mm
14. Light emitting diode for indicating operation and fault Integrated mains fuse Specifications Operating voltage 90 to 260VAC 48 to 63Hz Output voltage 24VDC 3 Nominal output current 2A Ambient temperature 5 C to 40 C Relative humidity max 90 no condensation Dimensions L x W x D 140 8 module units x 93 x 66 mm Colour light grey RAL 7035 Weight 355g Power Supply 24V 4Amp Stabilized NG4 1S Electronically controlled compact power supply unit for the supply of external devices with increased current consumption The power supply unit provides constant output voltage and is therefore not suitable for loading stand by batteries 169 BB072001 SAM 0720 01 0100 317020 169 BB072001 SAM 0720 01 0100 Chapter 31 Batteries and Power Supply Devices 291 The componentry is mounted in a plastic housing for DIN rail mounting in 45mm standard grid Features Switch mode power supply unit current limited and short circuit proof Stabilised output voltage Light emitting diode for indicating operation and fault Integrated mains fuse Specifications Operating voltage 90 to 260VAC 48 to 63Hz Output voltage 24VDC 3 Nominal output current 4A Ambient temperature 5 C to 40 C Relative humidity max 90 no condensation Dimensions L x W x D 140 8 module units x 93 x 66 mm Colour light grey RAL 7035 Weight 400g Power Supply Module NTM2402 1 The Power Supply Module NTM2402 1
15. Operating instructions by means of symbols European standard Integrated dual isolator Reverse polarity protection Built in microcontroller Operating instructions by means of symbols European standard Optical activation indication by means of LED Easy to replace standardised glass plate Button in combination with LED for setting the physical address Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 Specifications Operating voltage Current consumption Ambient temperature Protection class Dimensions W x H x D Colour Weight Approval supplied through loop voltage 300uA quiescent 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm flame red RAL 3000 400g VdS G202035 169 BB072001 SAM 0720 01 0100 245372 245415 169 BB072001 SAM 0720 01 0100 Chapter 17 Manual Call Points 161 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249633 Protective Cover V2A for Manual Call Point Red WG ROT E 1 169 2171612 Replacement Glass for Manual Call Point ET SCH HFM Manual Call Point Blue Anal SS HM
16. Special Detectors 242010 242012 Thermal Max Detector IP67 Conv SWM 1KL 57 The maximum heat detector SWM 1KL 57 uses a bimetal element as thermal sensor If the alarm temperature is reached the bimetal contact is closed Addressable conventional techno logy is used for alarm transmission to the fire detection control panel The activated condition of the detector is indicated by an LED The detector can be connected to an ADM loop by using a conventional zone module so Gwe The detector is integrated in an aluminium die cast housing o that is suitable for application in moist areas e g loading A e ramps _ i Features ii D Individual detector addressing by connecting an optional ad dress module Alarm LED on detector housing Output for external remote indicator Metal PG screws for water proof insertion of the connecting cables Specifications Operating voltage supplied through detector line voltage Alarm current at 24VDC max 100mA Alarm temperature typ 57 C Protection class IP67 Dimensions L x W x H 110 x 90 x 54 mm Colour white Weight 250g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacua
17. The module provides an integrated dual isolator and is designed to be mounted into a fire de tection control panel Features Separate status LED for each input and output Surveillance of terminal connecting lines for wire breakage and short circuit Monitoring of the internal resistance of the control devices as well as the line resistance of the supply line with a method pending as patent integrated self calibration by measuring the line resistance and load resistance initiated at a keystroke Monitoring of the supply voltage for low voltage Button and LED for setting the physical address from 01 to 99 Mounting in LST standard grid by means of supplied mounting spacers Specifications Operating voltage 20 to 30VDC Current consumption 35mA quiescent max 160mA no load Current consumption on the loop 500uA Number of outputs 4 Load current per output max 1 5A Number of inputs 4 End of line resistance 5 6kOhm Alarm threshold typ 1kOhm Ambient temperature 5 C to 60 C Ambient temperature control devices 5 C to 50 C to ensure the functioning of the fault detection Dimensions L x W x H 194 x 93 x 20 mm Weight 150g Approval VdS G205120 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 47 2189990 Extinguishing Control Panel Series LC216 Description 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Inter
18. 1m distance high sound level Examples at 24V Continuous tone 660Hz typ 4 4mA at 90dB A 1m distance DIN tone 1200 500Hz typ 5 6mA at 89dB A 1m distance Slow Whoop tone 500 1200Hz typ 5 7mA at 86dB A 1m distance 169 BB072001 SAM 0720 01 0100 355166 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 247 Ambient temperature 25 C to 70 C Relative Humidity 10 96 no condensation Dimensions x H 112 x 42 mm without detector incl Base LPB W Colour cream RAL 9001 Weight 134g Approval VdS G206076 Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 254 359043 Base Sounder amp Strobe IP44 White SDBW 255 359044 Base Sounder amp Strobe IP65 White WDBW 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Sounder Strobe WB 200 White Red Multitone IBSST DR P01 The addressable sounder with strobe red cap is accommodated in a round white plastic hou sing and is prepared for indoor surface mounting The integrated base is suitable for accom modation of fire detectors Series 200 The unit is mounted on a base for signalling devices not provided The componentry is actuated using System Sensor 200 protocol and is powered via the ADM loop The sounder is always activated together with the strobe Depen
19. 242010 242012 242013 242014 243002 243005 243004 244022 244023 244020 244021 244024 244025 244026 244610 244637 244628 244622 Thermal Max Detector IP67 Conv SWM 1KL 57 2 0 0 0 0 cc ccc cece ene tenn enn tnt n eee eeenes 192 Thermal Max Detector IP67 Conv SWM 1KL 80 20 0 0 00 c ccc ccc cence cence nent ne eeeeenes 192 Thermal Max Detector IP67 Conv SWM 1KL 100 0 ccc cence cece crete teen eens 193 Thermal Max Detector IP67 Conv SWM 1KL 140 oo ccc ccc ccc cece ence teen eens 194 Flame Detector UV Conv NFD 68 P SOCKEL 00 c ccc cece cence cece een ence nee enenes 194 Flame Detector UV Conv UV 03 rannanananenenannenenenanennenenenennennnenenenunnenenennner 195 Flame Detector IR Cony TR10 sus sles Ais hae Bares Ss ba PRN Ok a re ak ae a wR hb es 195 Beam Smoke Detector Conv SS 6500R 2 0 0 0 0c cece cence eee n nnn tenet eset ne ne ee eeenes 196 Beam Smoke Detector Test Conv SS 6500RS ccc cece ecece ncn eee n ence teen eens 197 Beam Smoke Detector Anal SS 6500 2 0 0 0 ccc ccc cece cence cence cece ence eee seen ene teenes 198 Beam Smoke Detector Test Anal SS 6500S 2 00 00 ccc ccc cece cece ence nen e een ene e eee enes 199 Reflector 6500 75 100M BEAMLRK 00 c ccc ccc cence ce cece nent e nen e nent ne eeenes 200 Multi Mount Kit 6500 BEAMMMK 00 c ccc ccc cc cen e eee ence nen eee e en en eeeenenes 200 Surface Mount Kit 6500 BEAMSMK 0 0 ccc ccc cence
20. 25mm for an aspiration smoke detection system All joints of the piping system need to be glued toge ther The sensor pipe is provided in 5m long tubes Sensor Tube PVC 25 SCHL PVC 25 Flexible grey tube made of PVC nominal width 20mm outer diameter 25mm for in stalling sections of the sensor pipe network of an aspiration smoke detection system under difficult conditions The connection with the sensor duct is established via bushings The sen sor tube can be used in all systems which contain an individual setting for the actual air flow conditions Pipe Fitting BOW90L BOGEN 90 Pipe elbow long radius made of grey PVC nominal width 20mm with a bending radius of 90 designed for sensor pipes of aspiration smoke detection systems Pipe Fitting BOW90S WINKEL 90 Pipe elbow short radius made of grey PVC nominal width 20mm with a bending radius of 90 designed for sensor pipes of aspiration smoke detection systems Pipe Fitting BOW45 WINKEL 45 Pipe elbow short radius made of grey PVC nominal width 20mm with a bending radius of 45 designed for sensor pipes of aspiration smoke detection systems Pipe Fitting T90 T STUCK 90 Pipe T piece made of grey PVC nominal width 20mm for a 90 junction designed for sensor pipes of aspiration smoke detection systems Pipe Fitting T45 T STUCK 45 Pipe T piece made of grey PVC nominal width 20mm for a 45 junction designed for sensor pipes of aspirat
21. 266 Fire Brigade Key Deposit Surface Mount FASB AP 265 Fire Brigade Keysafe Adapter AD900 1 D1 260 Fire Brigade Map Box FPKCLR900 1 273 Fire Brigade Map Box FPKPHZR900 1 274 Fire Brigade Map Box FWP 1 2 eee eee 273 250717 250902 210100 210102 210200 210205 210204 210208 210209 214000 214006 214015 214610 214007 214049 214086 214008 214009 214088 214080 214017 214084 214100 214164 214611 214109 214108 214158 214300 214306 214315 214304 214307 214349 214308 214309 214388 214317 214384 2199998 214205 214234 214204 210120 210122 243004 243002 243005 229008 265751 265818 244184 244185 244305 210212 244619 244620 244621 223060 249213 244128 244129 244130 244126 Fire Brigade Orientation Panel FOTR900 1 D1 Fire Brigade Orientation Panel FOTR900 2 D1 Fire Detection Control Panel BCO16 1 D1 7 Fire Detection Control Panel BCO16 1 INT1 6 Fire Detection Control Panel BC06 1 D1 2 Fire Detection Control Panel BCO6 1 INT1 1 Fire Detection Control Panel BC06 1A D1 2 Fire Detection Control Panel BC06 2 D1 3 Fire Detection Control Panel BC06 2 INT1 3 Fire Detection Control Panel BC216 1 Al 14 Fire Detection Control Panel BC216 1 B1 14 Fire Detection Control Panel BC216 1 CZ1 14
22. 98 Chapter 12 Analogue Detectors and Modules Series 200 500 Alarm threshold typ 22kOhm Ambient temperature 0 C to 50 C Dimensions L x W x H 172 x 147 x 25 mm Weight 500g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 118 249117 Surface Mounting Box for Multimodule SS M200 SMB MM 249103 Control Module 1xSurv Out Anal 200 SS M201E Addressable module for the activation of an external device via the bi directional communica tion on the ADM loop using System Sensor 200 protocol The external device can be trigge red by means of either a line monitored output or a dry contact The trigger mode can be set via DIL switches The integrated dual isolator can be acti vated or deactivated by choosing the appropriate terminals Features Status LED 2 decadic rotary switches for setting the address from 01 to 99 Installation alternatively in module box or by means of mounting pedestal Specifications Operating voltage supplied through loop voltage Current consumption approx 510uA quiescent Contact rating 2A 30VDC Ambient temperature 20 C to 60 C Dimensions L x W x H 93 x 94 x 23 mm Colour cream Weight 110g Approval VdS G202141 Cross references Page Art Nr Name Type 117 249110 Base for Carrier Rail for M200 SS M200E DIN 116 249109 Base for Mounting Plate for M200 S
23. Colour white red Weight 85g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359023 Housing IP67 for Strobe FB XP95 29600 318 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 241 356022 Strobe FB XP95 White Clear 55000 878 The addressable loop powered strobe 55000 878 with a clear cap and red LEDs is integrated in a white plastic housing It is triggered and supplied like a module via the ADM loop using Apollo Discovery protocol The strobe is designed to be inserted into a detector base and is suitable for indoor mounting Features Low power consumption z Suitable for surface mounting s Long life span due to use of LEDs Specifications Operating voltage supply through the loop voltage Current consumption typ 150uA quiescent max 3mA active Ambient temperature 10 C to 60 C Protection class IP42 Dimensions x H 100 x 52 mm Colour white clear Weight 85g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Bas
24. Features G Top side and lateral rain protection Mechanical protection Cable entry from back side or alternatively bottom side through the cable gland of the manual call point Specifications Dimensions W x H x D 130 x 145 x 55 mm Colour rape yellow RAL 1021 Weight 250g Cross references Page Art Nr Name Type 166 245396 Manual Call Point Yellow Anal Apo HM 1 32 05 02 162 245392 Manual Call Point Yellow Anal SS HM 1 22 05 02 159 245355 Manual Call Point Yellow Conv HM 1 1 1 05 02 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 The accessory kit is used for increasing the protection class of manual call points according to EN 54 11 B to IP54 The kit includes gasket elements a cable gland M20x1 and a mounting instruction OO mm Cross references Page Art Nr Name Type 164 245395 Manual Call Point Blue Anal Apo HM 5 32 02 02 165 245429 Manual Call Point Blue Anal Apo HM 5 32 18 02 161 245372 Manual Call Point Blue Anal SS HM 5 22 02 02 161 245415 Manual Call Point Blue Anal SS HM 5 22 18 02 158 245352 Manual Call Point Blue Conv HM 5 1 1 02 02 159 245417 Manual Call Point Blue Conv HM 5 11 18 02 164 245402 Manual Call Point EN 54 Red Anal Apo HFM 3 32 02 157 245302 Manual Call Point EN 54 Red Conv HFM 3 11 02 163 245389 Manual Call Point Grey Anal SS HM 7 22 03 02 160 245362 Manual Call Point Red Anal SS HFM 3 22 02 157 245356 Manual Call Point Red Conv HM 3 11 01 02 166 24539
25. Specifications Material plastics Dimensions W x H x D 180 x 230 x 50 mm Beam Smoke Detector Conv FR2000 Beam smoke detector operating on the infra red principle for the surveillance of open areas with a range of 10m to 100m consisting of separate sender and receiver units and a control unit in a sheet steel housing suitable for indoor mounting Slow changes of the operating conditions e g contamination of the optics do not result in false alarms but are compensated by the automatic amp drift compensation Connection in conventional technology via terminals inside the control unit hou f o tl e sing Connection to an ADM loop is achieved via Pr auxiliary modules A separate power supply is required Features Detection of clear and dark smoke Sender projects a modulated infra red beam to the receiver Received signal is analysed and compared with the stored reference value Automatic calibration of sensitivity to compensate for ageing and contamination LED display on the receiver for operation alarm and fault LED display on sender and receiver serve as adjusting aid for amplification signal inter ruption signal high and signal low Relays for reporting to the superior fire detection control panel Mounting brackets for wall and ceiling mounting Test filter for easy commissioning Specifications Supply voltage 11 5 to 28VDC Current consumption at 24V 8mA quiescent 16mA active Contact
26. Supply voltage input 19 to 36VDC Supply voltage output 24VDC 42 Output power max 10W Efficiency approx 80 Output current min 50mA max 410mA Ambient temperature 5 C to 50 C Relative humidity max 95 no condensation Dimensions L x W x H 75 x 40 x 15 mm Weight 50g Cross references Page Art Nr Name Type 56 223030 Long Distance Modem BCnet216 MOD 1 JET av E 169 BB072001 SAM 0720 01 0100 32 Chapter 32 Software 295 Software 218008 218041 169 BB072001 SAM 0720 01 0100 Parameter Setup Software PARSOFT 2 The Parameter Setup Software PARSOFT 2 allows for the creation download modification and upload of the site specific parameters of a Fire Detection Control Panel Series BC216 and Series BC016 an Extinguishing Control Panel Series LC216 as well as the Remote Ta bleau Drive Unit PTU288 1 in a clear and timesaving way In addition you can use PARSOFT 2 to load a firmware update into the connected device or read the event memory of the control panel and display it on a monitor The software is delivered in several languages on a CD ROM and can be used on any IBM compatible PC with operating system Windows 95 98 NT4 0 2000 XP provided that the fol lowing minimum requirements are met Pentium 100MHz processor 32MB RAM At least 1OMB free hard disk space CD ROM drive Free serial interface with 9 pin connector or TCP IP connection USB 2 0 interface for PTU288 1 Windows 2000 XP is however r
27. Weight approx 350g Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 Dummy Cover 19 3HU AD8C 3H Powder coated 19 front panel of 3 height units for covering non populated pivoting frame areas of a 19 cabinet Specifications Dimensions W x H x D 478 x 133 3 height units x 3 mm Colour grey white RAL 9002 Weight approx 500g Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 Dummy Cover 19 6HU AD8C 6H Powder coated 19 front panel of 6 height units for covering non populated pivoting frame areas of a 19 cabinet 44 Chapter 3 Fire Detection Control Panels Series BC216 214129 212031 227009 Dimensions W x H x D 478 x 266 6 height units x 15 mm Mounting thickn of front panel 3mm Colour grey white RAL 9002 Weight approx 800g Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 Decoration Foil for BC216 3CE FF216 3CE Self adhesive foil to adjust the colour of the BC216 3CE control panel front by default in grey white RAL 9002 to the front foil of the BC216 1CE light grey RAL 7035 Specifications Dimensions W x H x D 478 x 266 x 1 mm Colour light grey RAL 7035 Weight approx 30g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 43 212033 Dummy Cover 19 6HU AD8C 6H Mounting Kit 19 3HU EW8C E Sheet steel mounting kit designed a
28. 1000N 100kg 5 C to 50 C magnet 125 x 125 x 150 180 mm armature plate 60 x 60 x 48 mm 1 45kg 261011 Magnetic Clamp Reset 300mm 1000N 1380 30 The magnetic clamp is used for fixing fire doors or smoke compartments and is suitable for surface mounting on floors ceilings or walls It consists of a 300mm bracket adjustable to 330mm with interrupt button and an armature plate with a tilt joint as counterpart Specifications Operating voltage Power consumption Adhesive force Working temperature Dimensions L x W x H 24VDC 2 4W approx 1000N 100kg 5 C to 50 C magnet 125 x 125 x 300 330 mm armature plate 60 x 60 x 48 mm 169 BB072001 SAM 0720 01 0100 261017 261018 261019 169 BB072001 SAM 0720 01 0100 Chapter 29 Fire Controls 279 Weight 1 8kg Magnetic Lock Clamp 4900N 1390 Magnetic lock clamp with extra high magnetic force for locking doors emergency exits ac cess control systems etc during normal operation The lock is released through an optional Control Device For Magnetic Lock Clamp 2498 Suitable for surface mounting in dry rooms Com plete with counter plate and mounting accessories Specifications Operating voltage 24VDC Current consumption at 24V 250mA Adhesive force approx 4900N 490kg Working temperature 5 C to 50 C Dimensions L x W x D 270 x 67 x 41 mm Weight 4 2kg Cross references Page Art Nr Name Type 275 260002 Control Device fo
29. 120mA Current consumption from stand by battery in case of supply voltage failure 65mA quiescent Ambient temperature 150mA alarm condition and actuation output activated 5 C to 50 C VdS environmental class 2 Colour grey white RAL 9002 Dimensions W x H x D 215 x 325 x 85 mm Weight 2 3kg Approvals ICT D800451K VdS G199801 Cross references Page Art Nr Name Type 285 329014 Dialogue Module DPM805 1 284 329013 Line Monitoring Module TUM805 1 285 329016 Plug in Power Supply STN805 1 283 329012 Relay Module RL404 1 287 310010 Stand by Battery 6V 1 2Ah 285 329015 Telephone Speaker Set TEL805 1 329012 Relay Module RL404 1 Snap on board for extension of Automatic Telephone Dialling Devices Series TWG805 by 4 control inputs and 4 actuation outputs The control lines react to changes in resistance and can be programmed for connection of normally open and normally closed contacts Each 169 BB072001 SAM 0720 01 0100 284 Chapter 30 Telephone Dialling Devices 329013 Specifications actuation output is designed as dry relay contact and can be con figured as pulse output or continuous output Inputs 4 control lines Activation criteria 30 change in resistance Outputs 4 actuation outputs with dry change over contacts con tact load max 60V 1A Supply voltage internal voltage supply of the TWG805 1 Current consumption at 12V 5mA quiescent 310mA all actuation outputs activated Current cons
30. 173 245019 Surface Mount Box MCP5A SR 173 245012 Surface Mount Box MCP5A SR3T 245041 Manual Call Point Red 200 ISM Glass MCP5A RP08FG The manual call point according to EN 54 11 A is accommodated in a red plastic housing and is activated by breaking the glass pane The detector contains a dual isolator and is de signed for use on the ADM loop ring bus technology using System Sensor 200 protocol 169 BB072001 SAM 0720 01 0100 245042 169 BB072001 SAM 0720 01 0100 Chapter 17 Manual Call Points 171 Features Operating instructions by using symbols European Standard Activation by breaking glass pane Glass pane easy to replace Detector housing can be opened only with a special key provided 2 decadic rotary switches for setting the address from 01 to 99 Specifications Operating voltage Current consumption Ambient temperature Relative humidity Protection class Dimensions W x H x D Colour Weight Dual loop isolator supplied through loop voltage 360uA quiescent 10 C to 55 C 0 95 no condensation IP24 89 x 93 x 28 mm flame red RAL 3000 160g Approvals LPCB 166b 45 166b 46 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 173 249213 Glass for MCP Series 10pces G21140 35 214021 Loop Interface LIF64 1 173 245019 Surface Mount Box MCP5A SR 173 245012
31. 214034 BCnet Sectional Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 249029 Isolator Module Anal Apo ISM 1 3 214021 Loop Interface LIF64 1 Monitor Module Anal XP95 Apo UMS 55000 841 Addressable compact module with integrated dual isolator used for the line monitored inte gration of special detectors e g beam smoke detectors into the bi directional communicati on on the ADM loop using Apollo Discovery protocol The module provides a reset output Specifications Operating voltage Current consumption Line termination Alarm threshold Ambient temperature Dimensions L x W x H for resetting the connected detectors Features Switch for setting the physical address from 01 to 126 supplied through loop voltage 1 2mA quiescent 20kOhm typ 1kOhm 20 C to 70 C 150 x 90 x 48 mm white 240g VdS G201033 Art Nr Name Type Colour Weight Approval Cross references Page 26 32 35 214034 BCnet Sectional Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 Module 1xSurv In 1xRel Out Apo 55000 847 Addressable module for the line monitored integration of contact detectors e g manual call points sprinkler system contacts supervising contacts as well as for triggering external devi ces via the bi directional communication on the ADM loop using Apollo Discovery protocol 144 Chapte
32. 3 Fire Detection Control Panels Series BC216 2149999 Available Variants Series BC216 The term Series BC216 combines both stand alone control panels for small and medium si ze fire detection systems and fire detection control panels that consist of a variety of networ ked sectional control panels for medium to very large fire detection systems The Fire Detection Control Panels BC216 1 and BC216 1CE are designed as compact stand alone control panels for use in small and medium size fire detection systems Due to their modular structure and their free to set parameters they can be easily adapted to various requi rements and can therefore be used in a wide range of applications The control panels set new standards in operating comfort functional variety as well as security in the fire alarm technology which benefit both the user and the installer of a fire detection system The Fire Detection Control Panel BC216 1S is a modular compact panel for small fire de tection systems with a single ADM loop It constitutes an already pre assembled unit that contains all basic components which are required for the operation of a 1 loop fire detection control panel In a Fire Detection Control Panel BCnet216 individual decentrally located BCnet sectional control panels are combined in the Global Security System network GSSnet to form a virtual control panel for medium size to very large or far flung fire detection systems The sectional co
33. 50 C Relative humidity 5 to 95 no condensation Dimensions L x W x H 128 x 58 x 20 mm Weight 100g Cross references Page Art Nr Name Type 82 241041 Optical Thermal Detector Conv 300 SS 2351TEM 81 241040 Optical Smoke Detector Conv 300 SS 2351E 84 242041 Thermal Max Detector Conv 300 SS 4351E 84 242042 Thermal Max Detector Conv 300 SS 5351TE 83 242040 Thermal ROR Detector Conv 300 SS 5351E Satellite Unit for Remote Programming Conv 300 SS S300SAT The Satellite Unit for Remote Programming is used to exchange data between the Remote Program and Test Unit S3OORPTU and System Sensor Series 300 detectors and is attached to the ready to operate detector The Satellite Unit for Remote Programming can be applied with a Telescopic Pole Prior to first operation the Satellite Unit for Remote Programming must be synchronised with the Remote Program and Test Unit Features Locks onto the detector in a defined position Outside located switch and status LED Batteries included in the device Specifications Operating voltage 18VDC 2 x 9V block batteries Ambient temperature 10 C to 50 C Relative humidity 5 to 95 no condensation Dimensions x H 106 x 105 mm Colour black Weight 230g incl batteries Cross references Page Art Nr Name Type 82 241041 Optical Thermal Detector Conv 300 SS 2351TEM 81 241040 Optical Smoke Detector Conv 300 SS 2351E 84 242041 Thermal Max Detector Conv 300 SS 4351E 84 2
34. ADM Series XP95 200 355160 Sounder WM 200 Red Multitone 100dB WMSOU RR P01 The addressable multitone sounder is accommodated in a red plastic housing and is prepared for outdoor and indoor mounting The unit is mounted on a base for signalling devices not provided The sounder is actuated as a module using System Sensor 200 protocol and is po wered via the ADM loop Depending on the parameter setup of the Fire Detection Control Pa nel Series BC216 and the system condition the panel can activate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combinations The sound level is adjustable in 3 steps but depends also on the chosen tone type The power consumption is dependent on the tone type and the adjusted sound level Features 32 different tone type combinations selectable via DIL switch e g continuous tone 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Sound level adjustable in 3 steps low medium high Low power consumption 2 decadic rotary switches for setting the address from 01 to 99 Different base versions available 9 Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 450uA sounder off max 2 5mA low sound level max 4 4mA medium sound level max 7 1mA high sound level Sound level typ 82dB A 1m distance low sound level typ 90dB A 1m distance medium
35. Apo ASA 4568 1 210 Detector Base Conv 1000 SS ECO1000BR1000 107 Detector Base Conv 400 100 300 SS B401RM 105 Detector Base Conv 60 65 Apo 45681 251 149 Detector Base Conv 60 65 Apo GSA 45681 200 149 Detector Base Conv ORBIS Apo MB 00001 150 Detector Base Conv RF 215 27D 00 cece eee 187 Detector Base FC600 FC600 BR 2 cece eee 79 Detector Heater Base Anal 500 SS B524HTR 111 Detector Heater Anal 500 200 SS MH500 1 119 Detector Heater Anal Apo MH95 1 04 155 Detector Heater Conv 60 65 Apo MH60 1 154 Detector Label BME BEZ 000eee eee e eee 226 Detector Label Large BME GR 000 eee ee 227 Detector Label Large Sheet 8pcs BME GR BOG 225 303 304 Product List 249211 249042 249242 244183 244182 244186 244304 244303 244302 249044 246016 246037 246141 246102 246101 246100 246041 246142 246143 246072 249052 222013 210110 329014 229006 214200 214615 214208 214209 244008 246031 244005 244010 244011 244012 244009 212030 212029 212033 229005 218023 223025 249054 210216 2189991 2189990 218024 222011 250008 250740 250741 250707 250900 214023 210111 214022 265740 265742 268010 268009 265900 250709 250713 268007 Detector Label Sheet 8pcs BME BEZ BOG 225 Detector Label Small BME KL 08 227 Detector Lab
36. BC216 1CE the latter can be integrated as BCnet sectional control panel with display and operating field into a Fire Detection Control Panel BCnet216 For further information please refer to the description of the Fire Detection Control Panel BCnet216 Art No 2199998 Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 28VDC Output peak current max 1 8A Connection of external devices typ 0 8A site specific Current consumption at 24V typ 90mA without optional componentries Ambient temperature 5 C to 50 C Dimensions W x H x D 478 x 266 6 height units x 95 mm Colour grey white RAL 9002 Weight without batteries approx 6kg Approval FT 14 147 3 99 Austria VdS G201017 Cross references Page Art Nr Name Type 41 214128 Battery Bracket BK216 1CE 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 50 223009 Control Zone Module SLM1 2 35 214020 Conventional Detector Interface GIF8 1 58 218023 ESPA 4 4 4 Interface License ESPA SS 47 218024 Extinguishing Control 8 Area License LC216 8LB 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2 1 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 51 214027 Network Cable NWK2 1 51 214033 Network Interface Module NIF5 1M 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU4
37. Fire Detection Control Panel BC216 1 D1 14 Fire Detection Control Panel BC216 1 H1 15 Fire Detection Control Panel BC216 1 HR1 15 Fire Detection Control Panel BC216 1 I _ 15 Fire Detection Control Panel BC216 1 INT1 12 Fire Detection Control Panel BC216 1 NL1 15 Fire Detection Control Panel BC216 1 PL1 15 Fire Detection Control Panel BC216 1 RUS1 15 Fire Detection Control Panel BC216 1 SK1 15 Fire Detection Control Panel BC216 1 SLO1 15 Fire Detection Control Panel BC216 1CE AI 29 Fire Detection Control Panel BC216 1CE CZ1 29 Fire Detection Control Panel BC216 1CE D1 29 Fire Detection Control Panel BC216 1CE H1 29 Fire Detection Control Panel BC216 1CE INT1 27 Fire Detection Control Panel BC216 1CE NL1 29 Fire Detection Control Panel BC216 1S Al 18 Fire Detection Control Panel BC216 1S B1 18 Fire Detection Control Panel BC216 1S CZ1 18 Fire Detection Control Panel BC216 1S D1 18 Fire Detection Control Panel BC216 1S H1 18 Fire Detection Control Panel BC216 1S HR1 19 Fire Detection Control Panel BC216 1S INT1 16 Fire Detection Control Panel BC216 1S NL1 18 Fire Detection Control Panel BC216 1S PL1 19 Fire Detection Control Panel BC216 1S SK1
38. Interconnector LWM ZV22 11800 103 Interface Adapter Module IAM216 1E Ionisation Smoke Detector Anal 200 SS 1251E 90 Ionisation Smoke Detector Anal Disc Apo AI 58000 500 2 2 eee eee e eee eens 138 Ionisation Smoke Detector Anal XP95 Apo AT55000 520 r det wes canes gnirede ERACLE CAROLA ES 136 Ionisation Smoke Detector Conv 65 Apo GI 55000 217 Isolator Detector Base Anal 500 200 SS B524IEFT 1 110 Isolator Detector Base Anal Apo AISA 45681 321 151 Isolator Module Anal 500 200 SS ISM1 2 103 Isolator Module Anal Apo ISM1 3 00 00 147 Isolator Module Board Apo 43781 552 65 148 K Key for Fire Brigade Key Deposit 882AML102 266 Key for Manual Call Point SCH HFM HM 169 Kit 19 3HU for Printer DPU414 DPU2 1E 44 L LBC Sub Unit License LBC UZ 055 60 LED Assembled Green 10pces LED GN 10 74 LED Assembled Red 10pcs LED RT 10 75 LED Assembled Yellow 1Opcs LED GE 10 75 LED Connection Module LAM48 1 4 74 LED Display Field LAB48 1 2 cee eee eee eee 37 LED Display Field LAB48 2 00 c eee ee eee eee 38 LED Display Field LAB48 3 LED Display Field LAB484 0 ee eee eee 39 LED Display Tableau LAT288 1 louessense 72 LED Display Tableau LAT288 1CE 4 72 Lid for Detector Base Sounder Red 45681 293
39. LA max 2A 9600Baud 900 1800MHz 0 C to 45 C 85 x 40 x 25 mm 70g Art Nr Name Type 52 295 214231 Interface Adapter Module IAM216 1E 218008 Parameter Setup Software PARSOFT 2 169 BB072001 SAM 0720 01 0100 223041 169 BB072001 SAM 0720 01 0100 Chapter 5 Interfaces 55 52 214025 Serial Interface Module SIM216 1 SMS E Mail Transmitter Module SMS2 1 D1 The Transmitter Module SMS2 1 D1 can send SMS messages or e mails to a maximum of 8 different users in order to provide a recipient with specific information The module can either receive event text messages from a Fire Detection Control Panel Se ries BC216 via serial ESPA data protocol and forward it without change or it can transmit messages according to the parameterisation if the condition of ER SAN one of the six inputs changes In addition the module contains 6 e 4 outputs that can be activated by SMS text messages for remo tely controlling certain system functions A GSM antenna the serial connection cable to the control panel and the options circuit for activation of the ESPA interface on the control panel are provided together with the module The required SIM card has to be provided by the customer The following parameters can be set Events to be transmitted alarm fault etc Transmission priority of events Transmission parameters of users telephone number e mail address disable time etc Disable times or disabl
40. Relative humidity Dimensions x H Colour Weight 10 to 15VDC typ 20uA quiescent 30mA active 1A at 30VDC 30 C to 70 C 5 to 93 no condensation 102 5 x 33 mm white 70g 169 BB072001 SAM 0720 01 0100 246002 246015 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 109 Detector Base Anal 500 200 SS B501 Mounting base for automatic fire detectors Series 500 and 200 suitable for indoor surface mounting Features Connection to the ADM loop using System Sensor 200 a 3 malt protocol lt gt Multi useable terminals with secure screw fitting Dr Terminal for external remote indicator Mechanical theft protection Specifications Ambient temperature 30 C to 70 C Relative humidity 0 to 95 no condensation Dimensions x H 102 x 20 mm Colour cream Weight 53g Cross references Page Art Nr Name Type 114 246006 Base Adapter SS MZP500 1 226 249011 Detector Label BME BEZ 120 249044 Detector Mounting Bracket MMW 1 1 90 240013 Ionisation Smoke Detector Anal 200 SS 1251E 181 241025 IS Optical Smoke Detector Anal 200 SS 225 1EIS 92 241020 Optical Thermal Detector Anal 200 SS 2251TEM 91 241050 Optical Laser Detector Anal 200 SS 7251 90 241010 Optical Smoke Detector Anal 200 SS ND2251EM 121 249640 Protective Cage BWS 1 D1 115 246010 Recessed Mounting Kit SS RMK400 71 251001 Remote Indicator PA58 1 115 246009 Surface Mounting Kit SS SM
41. Suitable for surface mounting Exchangeable cap for different colours Long lifespan Specifications Operating voltage 20 28VDC Current consumption at 24V 300mA Flash frequency 1Hz Ambient temperature 25 C to 40 C Protection class IP54 Dimensions W x H x D 88 x 88 x 81 mm Colour red RAL 3000 Weight 240g Approval VdS G28714 Strobe 24V Orange BE A S 2 0 24VBMT The strobe BE A S 2 0 24VBMT is mounted in a white plastic housing with an orange cap and is suitable for indoor and outdoor mounting 169 BB072001 SAM 0720 01 0100 356672 351650 169 BB072001 SAM 0720 01 0100 Chapter 24 Optical and Acoustic Devices conventional Features Very high flash energy Low power consumption Suitable for surface mounting Easy to mount due to bayonet lock Exchangeable cap for different colours Long lifespan Specifications Operating voltage 20 30VDC Current consumption at 24V 155mA Flash frequency 1Hz Ambient temperature 20 C to 55 C Protection class IP54 Dimensions x D 93 x 75 mm Colour yellow orange RAL 2000 Weight 240g Approval VdS G296014 Strobe 24V Red BE R S 2 0 24VBMT The strobe BE R S 2 0 24VBMT is mounted in a red plastic housing with a red cap and is suitable for indoor and outdoor mounting Features Very high flash energy Low power consumption Suitable for surface mounting Easy to mount due to bayonet lock Exchangeable cap for differ
42. Therefore the thermal detection system is ideally suited for g Fan et monitoring of garages cold storage houses tunnels depots false floors and all areas and rooms which are difficult to ac cess or are in difficult environmental conditions The activation temperature of the maximum alarm can be set with a 15 step switch whereas the activation threshold of the differential alarm can be adjusted with two switches in 16 steps Thereby the heat detection unit can be easily adapted to the respective application Four LEDs operation maximum alarm differential alarm fault indicate the actual condition of the heat detection unit The unit can be reset either by interruption of the supply voltage actuation of the external reset input or via the internal Reset button Two test buttons alarm and fault test as well as LED test allow an electrical system test The heat detection unit is accommodated in a plastic housing The connection to the fire de tection control panel is carried out in conventional technology via one dry contact for alarm and one for fault Features Length of sensing cable up to 300m Detection of exceeding temperatures at any point of the sensing cable High security against false alarms also in difficult environmental conditions Simple mounting commissioning and maintenance Heat detection unit can be mounted up to 500m away from sensing cable 99 Specifications Operating voltage 10 30VDC
43. for every data point Any status change in the system implicates also that the colour of the re spective symbol changes Additional functions such as display of users logged on the event dependent display of screen windows event driven time programs catalogue of measures etc can be defined if required By using sample symbols the parameters for similar functions can be set easily and quickly during a new installation as well as in the course of enhancements or modifications Specifications Operating system at least Windows 2000 Professional Minimum requirements PC Pentium 512MB RAM RS232 interface for the con nection of the fire detection control panel mouse key board USB interface for Dongle 1GB HDD graphics card for 2 monitor Cross references Page Art Nr Name Type 296 218045 Alarm Monitoring Interface Licence ALVIS LBC1000 296 218044 Alarm Monitoring Interface License BC216 ALVIS BC216 52 214025 Serial Interface Module SIM216 1 I eam nd 296 Chapter 32 Software 218044 218045 58 218022 ZLT Interface License ZLT SS Alarm Monitoring Interface License BC216 ALVIS BC216 The alarm monitoring interface license allows for the operation of the DDE server which controls the event driven communication between the operation control system and the Fire Detection Control Panel Series BC216 The DDE server runs as independent task in parallel to the visualisation user interface of the alarm monitoring system
44. free air Ambient temperature 10 C to 55 C JET av E 188 Chapter 19 RF Devices Relative humidity 10 93 no condensation Dimensions W x H x D 210 x 270 x 70 mm Colour white black Weight 930g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 190 245023 Manual Call Point Blue RF M400DKMB AS 189 245022 Manual Call Point Red RF M400DKMR AS 189 241036 Optical Thermal Detector RF complete 2100RFT AS 249203 RF Interface 4Rel M400RFE AS The radio linked interface M400RFE AS serves for the connection of up to 32 automatic or non automatic radio linked detectors The interface provides 2 separate alarm and fault de tection relays Each of these two groups can be assigned up to 16 detectors The two zones are reported as collective messages to the fire detection control panel either in addressable conventional technology or by me ans of auxiliary modules via the ADM loop In addition an LED for the individual display for each detector is provided by the RF interface Features High transmission capacity 9966 Specifications Mains voltage Connection power external supply voltage Up to 32 detectors can be memorised Radio linked detectors assigned to 2 zones integrated power unit expandable with stand by battery Individual detector identification via 3
45. thereby creating two loops Both loops are permanently monitored An interruption or a short circuit in one of the two loops causes a fault message in the evaluation unit The black sensing cable with a stainless steel meshwork has a high resistance against chemi cal and biological agents and is additionally protected against rough mechanical strains Features Length of sensing cable up to 300m Detection of exceeding temperatures at any point of the sensing cable Resistant against chemical and biological agents as well as mechanical strains Easy to install Specifications Outer diameter Wire gauge Temperature resistance 5 8mm 0 46mm up to 100 C unlimited up to 150 C 350 hours up to 175 C 25 hours Cross references Page Art Nr Name Type 202 244637 Linear Heat Detection Unit Alarmline Conv LWM 1 Interconnector LWM ZV22 11800 103 Interconnector for temperature resistant sensing cables consists of a white black and red shrink tube and is used for connection of two sensing cables or for integration of an additio nal cable section Cross references Page Art Nr Name Type 203 244622 Sensing Cable Black LWM SK180001 1 203 244628 Sensing Cable Blue LWM SK1800010 204 244624 Sensing Cable Stainless Steel LWM SK11800013 Termination Connector LWM AV22 11800 102 Termination connector for temperature resistant sensing cables consists of a white inner layer and a black end cap for hermetic seal
46. used for operating and displaying all events of a Fire Detection Control Panel BCnet216 Functions specifications and cross references corre spond to the Remote Display and Operating Panel ABF216 1 INT1 The labels of display and operating elements as well as the displayed texts are in German language 169 BB072001 SAM 0720 01 0100 250036 250033 250038 250035 250037 250046 250047 250048 250049 169 BB072001 SAM 0720 01 0100 Chapter 8 Display and Operating Devices 69 Remote Display and Operating Panel ABF216 1 B1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in French language Remote Display and Operating Panel ABF216 1 CZ1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Czech language Remote Display and Operating Panel ABF216 1 H1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Hungarian language Remote Display and Operating Panel ABF216 1 NL1 Functions specifications and cross references correspond to the Remote Display and Opera ting P
47. 1 4 210210 Zone Extension Board ZEB2 1 Thermal ROR Detector Conv ORBIS Apo HT 11001 Heat detector operating on the rate of rise heat detection principle in addressable conventio nal technology combined maximum rate of rise detector classified as AIR maximum room height 7 5 m in extra flat design suitable for indoor mounting For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire de tection control panel provided that these functions are suppor ted by the control panel If the detector is faulty the multicolour status LED on the detector will flash for approx 4 minutes in yellow colour after the detector line has been enabled Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional address module NG60 1 Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 65uA quiescent Alarm temperature 57 C maximum heat component Operating temperature max 50 C Ambient temperature 40 C to 70 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 50 mm Colour white Weight 130g Approval VdS G
48. 1 JET av E 56 Chapter 5 Interfaces 223060 223030 Gateway lEC870 5 101 104 BC216 IEC870 BC216 GW The Gateway IEC870 BC216 GW serves as interface between the Fire Detection Control Panel Series BC216 and a primary control centre according to the international interface standard IEC870 5 101 RS232 or alternatively IEC870 5 104 ethernet For this purpose the control panel has to be equipped with a ZLT interface not provided On the one hand events from the control panel can be transmitted to the primary control centre via the gateway on the other hand operations at the control panel can be performed depending on the parameterisation of the gateway The system specific list of IEC data points and the assignment of detector zones have to be loaded into the gateway This list can be easily created with the provided setup program for Windows Please note the IEC Gateway can only be operated with a Central Processing Board ZTB216 2 using hardware version V4 or newer versions The type of the central proces sing board can be found on a label The version number is the last digit of the PCB version which is printed in the left bottom corner of the printed circuit board e g PN5233S4 for V4 For operation of the gateway a firmware version PL149 Vx 20 or higher is required for parameterisation a PARSOFT version V1 20 or higher is necessary Features 4000 IEC data points free to define Transmission of events from
49. 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 216 244183 Detector Module DM TP 05 L 215 244182 Detector Module DM TP 25 L 215 244186 Detector Module DM TP 80L 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 216 244185 Front Foil FW TP 2 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 4 210210 Zone Extension Board ZEB2 1 Detector Module DM TP 80L The Detector Module DM TP 80L is used for analysis and evaluation of air which is sampled from the monitored area by the aspiration smoke detection system housing TP x The light obscuration and the air flow are measured by the detector module The response thresholds for the light obscuration and the air flow are separately adju stable Dry contacts in the evaluation electronics of the aspiration smoke detection system housing signal the exceeding of alarm and fault thresholds Specifications Response threshold Light obscuration 1 6 0 8 m Air flow monitoring 4 levels Cross references Page Art Nr Name Type 213 244180 Aspiration Smoke Detection System Housing TP 1 214 244181 Aspiration Smoke Detection System Housing TP 2 Detector Module DM TP 25 L The Detector Module DM TP 25 L is used for analysis and evaluation of air which
50. 12VDC 250ma active at 24VDC Outer door heating 24VAC DC SVA Resistance of alarm circuit 2 2kOhm 5 Ambient temperature 25 C to 70 C Protection class IP44 Dimensions W x H x D 290 x 275 x 145 mm Weight 12 7kg Approval VdS G199055 Cross references Page Art Nr Name Type 260 265900 Fire Brigade Keysafe Adapter AD900 1 D1 259 265751 Flush Mounting Frame for FSK700 2 EZ700 2 D1 259 265818 Flush Mounting Frame with Drilling Protection for FSK700 2 EZBS700 2 261 265752 Inner Door for FSK700 2 A ITA 2 261 265753 Inner Door for FSK700 2 DBUK ITB 2 262 265757 Inner Door for FSK700 2 DBUM ITF 2 260 237700 Power Supply for FSK Heating NT700 1 259 249650 Protective Cover for FSK700 2 WSD FSK 263 265762 Steel Column V2A for F0345 Strobe HSFSK700 2 D3 263 265761 Steel Column V2A for F0345 HSFSK700 2 D2 262 265765 Steel Column V2A for FSE MP1 Strobe HSFSK700 2 D6 264 265764 Steel Column V2A for FSE MP1 HSFSK700 2 D5 264 265763 Steel Column V2A for Strobe HSFSK700 2 D4 262 265760 Steel Column V2A Standard HSFSK700 2 D1 265 265660 Unblocking Element F0345 Jer av E 258 Chapter 27 Fire Brigade Key Boxes and Accessories 265 265661 Unblocking Element for Half Cylinder FSE MP1 265742 Fire Brigade Key Box FSK700 2S2 D1 The Fire Brigade Key Box FSK700 2S2 D1 is tested according to VdS 2105 and serves for theft save and copy protected keeping of two keys of a building which enable the fire brigade to a fast and non violent access
51. 174 242015 IS Thermal ROR Detector Conv 400 SS 5451EIS IS lonisation Smoke Detector Anal XP95 Apo AIEX 55000 540 Addressable smoke detector for hazardous areas operating on the ionisation principle for application on the ADM loop using Apollo Discovery protocol consisting of sensing and re ference chamber dual chamber principle for automatic compensation of environmental in fluences and of extra flat design suitable for indoor mounting The detector must always be connected via a Safety Barrier Anal XP95 Apo approved for the respective detector and a Protocol Interface Anal XP95 Apo Particular attention must a be paid to the compliance with country specific regulations y pE C Daseera not Features Permanent evaluation of environmental conditions Continuous transmission of the current measured value to the fire detection control panel Constant sensitivity Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Mechanical theft protection Insect screen 6069 Specifications Operating voltage supplied through loop voltage Ex classification EEx ia IIC TS Current consumption typ 280uA quiescent Ambient temperature 20 C to 40 C no condensation or icing Relative humidity 0 to 95 no condensation Radioactive compound Am241 0 9uCi 33 3kBq Dimensions x H 100 x 42 mm Colour white Weight 105g Appro
52. 200 SS B524IEFT 1 Base for Mounting Plate for M200 SS M200E PMB Attachable mounting base for plate mounting of System Sensor Series M200 modules The module can thus be mounted upright on every even surface Specifications Ambient temperature 20 C to 60 C Dimensions L x W x H 85 x 25 x 22 mm Colour cream Weight 10g Cross references Page Art Nr Name Type 98 249103 Control Module 1xSurv Out Anal 200 SS M201E 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 97 249102 Module 2xSurv In 1xRel Out Anal 200 SS M221E 96 249100 Monitor Module 1xSurv In Anal 200 SS M210E 169 BB072001 SAM 0720 01 0100 249110 249108 249111 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 117 96 249101 Monitor Module 2xSurv In Anal 200 SS M220E Base for Carrier Rail for M200 SS M200E DIN Attachable mounting base for DIN rail mounting of System Sensor Series M200 modules The module can thus be mounted snapped on upright on standardised 35mm top hat rails Specifications Ambient temperature 20 C to 60 C Dimensions L x W x H 85 x 25 x 22 mm Colour cream Weight 10g Cross references Page Art Nr Name Type 98 249103 Control Module 1xSurv Out Anal 200 SS M201E 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 97 249102 Module 2xSurv In 1xRel Out Anal 200 SS M221E 96 249100 Monitor Module 1xSurv In Anal 200 SS M210E 96 249101 Monitor Module 2
53. 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249633 Protective Cover V2A for Manual Call Point Red WG ROT E 1 169 2171612 Replacement Glass for Manual Call Point ET SCH HFM Manual Call Point Blue Anal Apo HM 5 32 02 02 Manual call point according to EN 54 11 B with dual isolator module integrated in an ele gant blue aluminium die cast housing designed for application on the ADM loop using Apol lo Discovery protocol The manual call point is tested in accordance with the standards EN 54 11 B and EN 54 17 Features Robust aluminium die cast housing with a door aperture ang le of more than 180 Function marking HAUSALARM replaceable Integrated dual isolator Reverse polarity protection Built in microcontroller Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Button in combination with LED for setting the physical address Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 169 BB072001 SAM 0720 01 0100 Specifications Operating voltage Current consumption Ambient temperature Protection class Dimensions W x H xD Chapter 17 Manual Call Points 165 supplied through loop voltage 180uA quiescent 20 C to 60 C continuou
54. 24VDC Power consumption 1 5W Adhesive force approx 500N 50kg Working temperature 5 C to 50 C Dimensions L x W x H magnet 95 x 95 x 40 mm armature plate 60 x 60 x 48 mm Weight 700g Magnetic Clamp Reset 150mm 500N 1370 15 The magnetic clamp is used for fixing fire doors or smoke compartments and is suitable for surface mounting on floors ceilings or walls It consists of a 150mm bracket adjustable to 180mm with interrupt button and an armature plate with a tilt joint as counterpart 169 BB072001 SAM 0720 01 0100 261006 261008 261009 169 BB072001 SAM 0720 01 0100 Chapter 29 Fire Controls 277 Specifications Operating voltage 24VDC Power consumption 1 5W Adhesive force approx 500N 50kg Working temperature 5 C to 50 C Dimensions L x W x H magnet 125 x 125 x 150 180 mm armature plate 60 x 60 x 48 mm Weight 1 2kg Magnetic Clamp Reset 300mm 500N 1370 30 The magnetic clamp is used for fixing fire doors or smoke compartments and is suitable for surface mounting on floors ceilings or walls It consists of a 300mm bracket adjustable to 330mm with interrupt button and an armature plate with a tilt joint as counterpart Specifications Operating voltage 24VDC Power consumption 1 5W Adhesive force approx 500N 50kg Working temperature 5 C to 50 C Dimensions L x W x H magnet 125 x 125 x 300 330 mm armature plate 60 x 60 x 48 mm Weight 1 55kg Magnetic Cl
55. 332 233 355133 Sounder WB XP95ISM White Alert 45681 277 234 355132 Sounder WB XP95ISM White DIN 45681 300 233 355131 Sounder WB XP95ISM White Slow Whoop 45681 290 Mounting Plate for Sounder WB XP95 38531 810 White mounting plate for surface mount cabling of an addressable detector base sounder Se ries XP95 Specifications Dimensions x H 116 x 11 mm Weight 28g Colour white Cross references Page Art Nr Name Type 236 355134 Sounder Strobe WB XP95ISM White Clear Alert 45681 330 238 355136 Sounder Strobe WB XP95ISM White Clear DIN 45681 334 237 355135 Sounder Strobe WB XP95ISM White Clear Slow Whoop 45681 332 233 355133 Sounder WB XP95ISM White Alert 45681 277 234 355132 Sounder WB XP95ISM White DIN 45681 300 233 355131 Sounder WB XP95ISM White Slow Whoop 45681 290 236 355130 Sounder WB XP95RI White Alert 45681 276 Housing IP67 for Strobe FB XP95 29600 318 The protection housing 29600 318 consists of a grey bottom part made of plastic and a trans parent cover The housing protects an addressable loop powered strobe Series XP95 from dust and humidity 254 Chapter 26 Accessories for Optical and Acoustic Devices 359040 359043 Specifications Ambient temperature 40 C to 80 C Protection class IP67 Dimensions W x H x D 125 x 125 x 100 mm Weight 292g Cross references Page Art Nr Name Type 241 356022 Strobe FB XP95 White Clear 55000 878 241 356023 Strobe FB XP95 White Orange 55000 879
56. 5 22 02 02 Manual call point according to EN 54 11 B in an elegant blue aluminium die cast housing designed for application on the ADM loop ring bus technology using System Sensor 200 protocol with integrated dual isolator module HAUSALARM N Knopf tio dr cken Features Robust aluminium die cast housing with a door aperture angle of more than 180 9 Call Point HFM HM ZS IP54 Specifications Operating voltage Current consumption Ambient temperature Protection class Dimensions W x H x D Colour Function marking HAUSALARM replaceable Integrated dual isolator Reverse polarity protection Built in microcontroller Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Button in combination with LED for setting the physical address Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual supplied through loop voltage 300uA quiescent 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm sky blue RAL 5015 Weight 400g Approval VdS G202035 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit
57. 5 years battery life span Sabotage message when door is open 3 6V Lithium battery approx 1 5 years Ambient temperature 0 C to 60 C Dimensions W x H x D 125 x 125 x 37 mm Colour blue Approval VdS G105508 Cross references Page Art Nr Name Type 191 310021 Lithium Battery 3 6V 2 2Ah 184 249201 RF Interface 4Rel FUIF5 1 1 27D ic nd 169 BB072001 SAM 0720 01 0100 246040 249202 169 BB072001 SAM 0720 01 0100 Chapter 19 RF Devices Detector Base Conv RF 215 27D Two piece detector base with radio linked communication module for automatic fire detec tors The base is suitable for indoor mounting For easy installation and for changing the bat teries the bottom part can be removed and is provided with a bayonet coupling for the detector base The detector base is delivered with battery a Features a Continuous status messages High transmission capacity v 2 frequency ranges 434MHz and 868MHz 24 bi directional data channels Unique code made up out of several million options Channels are checked for availability Room for 2 x 9V block battery Surveilled battery voltage Approx 1 5 years life span of lithium block battery Sabotage message when detector is removed 9 Specifications 187 Ambient temperature 0 C to 60 C no condensation Dimensions x H 100 x 50 mm Colour white Weight 160g without batteries Approvals VdS G206016 VdS G206017 Cross
58. ADFAT900 2 D1 270 Reflector 6500 75 100M BEAMLRK Relay Module 4 Fold 230VAC RL58 2 Relay Module 8 Fold 60VDC RL58 1 Relay Module RL404 1 Remote Access Module GSM GPRS FZG2 1 54 Remote Access Module PSTN FZP2 1 Remote Display Panel SG48 2 2 eee eee Remote Display and Operating Panel ABF216 1 A1 68 Remote Display and Operating Panel ABF216 1 B1 69 Remote Display and Operating Panel ABF216 1 CZ1 69 Remote Display and Operating Panel ABF216 1 D1 68 Remote Display and Operating Panel ABF216 1 H1 69 Remote Display and Operating Panel ABF216 1 HR1 70 Remote Display and Operating Panel ABF216 1 I1 69 Remote Display and Operating Panel ABF216 1 INT1 68 Remote Display and Operating Panel ABF216 1 NL1 69 Remote Display and Operating Panel ABF216 1 PL1 69 Remote Display and Operating Panel ABF216 1 RUS1 69 Remote Display and Operating Panel ABF216 1 SK1 69 Remote Display and Operating Panel ABF216 1 SLO1 69 Remote Indicator PAS8 1 0 cece 71 Remote Program and Test Unit Conv 300 SS S300RPTU EREE REEE EEEE cease stewie eee Remote Tableau Drive Unit PTU288 1 Remote Tableau SG58 2 A1 Remote Tableau SG58 2 B 1 Remote Tableau SG58 2 CZ1 Remote Tableau SG58 2 NL1 Remote Test Unit Conv 300 1000 SS ECO1000RTU 113 Replacement Filter for Filtrex RF FTX 124 Replacement Glass for Manual Call Point ET SCH HEM tt
59. ADM loop using System Sensor 200 protocol and is of extra flat design suitable for indoor mounting The alarm evaluation is based on the analysis of both detection units if only one characteristic of fire occurs false alarms can be mostly avoided Please note that the detector must not be used if the room height exceeds 7 5m in the thermal only mode The sensitivity of the detector can be preset individually in 5 steps between 2 m and 5 m depending on the application Three levels show a fixed sensitivity whereas two levels provide an automatic adaption of the sensi tivity thus enabling the detector to ideally adapt to the environment The optical detection unit can also be totally disabled for a thermal only mode Intelligent evaluation algorithms compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept constant for a long time thus constituting another effective measure for preventing false alarms Features Permanent evaluation of environmental conditions Constant sensitivity 5 different operation modes optical thermal as well as thermal only can be set via Fire Detection Control Panel Series BC216 2 decadic rotary switches for setting the physical address from 01 to 99 Sealed electronics prevents false alarms caused by the environment Output for external remote indicator Mechanical theft protection Insect screen 9 Specifi
60. B524RTE 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 116 Chapter 13 Acessories for Series 300 ECO1000 200 500 249012 246017 249109 Wet Base Shroud SS WB1 Accessory for mounting B401RM B501 B501DG B524IEFT 1 B524FTXE B524HTR or B524RTE detector bases in damp locations prepared for PG screw connections Specifications Dimensions x H 105 x 70 mm Colour cream Weight 200g Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 105 246008 Detector Base Conv 400 100 300 SS B401RM 111 246012 Detector Base Filtrex Anal 500 SS B524FTXE 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 110 246013 Isolator Detector Base Anal 500 200 SS B524IEFT 1 Cover Plate for Base Bx01 Bx24 BC Bx01 The plate serves for covering detector base Series 100 200 300 400 or 500 if the detector is permanently removed Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 105 246008 Detector Base Conv 400 100 300 SS B401RM 111 246012 Detector Base Filtrex Anal 500 SS B524FTXE 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 105 246100 Detector Relay Base Conv 300 SS B324RL 110 246013 Isolator Detector Base Anal 500
61. BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 42 212034 Module Carrier 19 3HU MPL17 3 64 Chapter 6 Additional Modules for Fire Detection Control Panels 229008 Flat Cable 1700mm 10 Pole FBK17 1 Flat cable with a length of 1 7m for the connection of modules which are connected via a 10 pole flat cable e g Relay Modules RL58 1 RL58 2 if a longer cable than the supplied 300mm cable is required Cross references Page Art Nr Name Type 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 61 223026 Siren Connection Module SZ58 3 169 BB072001 SAM 0720 01 0100 4 Protocol Printers Chapter 7 Protocol Printers 65 227003 227004 169 BB072001 SAM 0720 01 0100 Protocol Printer Thermal DPU414 30B Desktop printer used as protocol equipment to be connected to a Serial Interface Module SIM216 1 of a Fire Detection Control Panel Series BC216 or Series BCO16 or to a Serial In terface Module SIM06 1 of a Fire Detection Control Panel Series BC06 Depending on the control panel the logging includes the location of the activated detectors detector zone number date and time and any change in the operating condition of the fire detection control panel at the beginning and the end of the event The events are printed as plain text wit
62. BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 138 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 241030 240026 35 214021 71 251001 Loop Interface LIF64 1 Remote Indicator PAS8 1 Optical Thermal Detector Anal XP95 Apo AMS 55000 885 The addressable Multisensor Detector AMS 55000 885 comprises one detection unit opera ting on the principle of scattered light and one detection unit operating on the rate of rise heat principle The alarm evaluation is based on the analysis of measured values from both detecti on units false alarms are mostly avoided if only one of the cha racteristics of fire like smoke or heat appears Communication with the fire detection control panel is established via the ADM loop using Apollo Discovery protocol m N a Intelligent evaluation algorithms compensate for the impact of contamination of the optical sensing system Thereby the re sponse sensitivity of the detector is kept constant for a long time another effective measure for avoiding false alarms The detector is accommodated in a flat white plastic housing and is designed for indoor mounting Features Constant sensitivity o Insect screen Specifications Operating voltage Current consumption Ambient temperature Permanent evaluation of environmental conditions Code card in detector base for setting of physical address from 01 to 126 Sealed electro
63. CK2385312771 oct sense spe Fs eae Address Module Conv NG58 1 Address Module Conv Apo NG60 1 Air Filter for ASDS complete LF RAS Alarm Monitoring Interface Licence ALVIS LBC1000 296 Alarm Monitoring Interface License BC216 ALVIS BC216 oo cece ee cece cece eee teen eee 296 Alarm Monitoring Software License ALVIS F 295 Aspiration Hole Reduction Foils Overview 223 Aspiration Smoke Detection System A211E LSR 210 Aspiration Smoke Detection System A222E LSR 211 Aspiration Smoke Detection System Housing A310E 212 Aspiration Smoke Detection System Housing A320E 213 Aspiration Smoke Detection System Housing TP 1 213 Aspiration Smoke Detection System Housing TP 2 214 Aspiration Smoke Detection System Housing TT 1 217 Aspiration Smoke Detection System T SS_ 219 Aspiration Smoke Detection System VLS 304 220 Aspiration Tube DN 12x9 2 2 eee eee eee ee ee 222 Automatic Telephone Dialling Device TWG805 1A 281 Automatic Telephone Dialling Device TWG805 1D 282 Auxiliary Case for BC216 GEH216 4 Available Variants Series BC216 00 B BCnet Sectional Control Panel Extension BCE216 3LG 26 BCnet Sectional Control Panel No Op BC216 3CE 29 BCnet Sectional Control Panel No Operation BC216 3 25 BCnet Sectional Control Panel OP BC216 2 A1 24 BCnet Sectional Control Panel OP BC216 2 B1 24 BCne
64. Control 8 Area License LC216 8LB 7 and 24 Chapter 3 Fire Detection Control Panels Series BC216 214004 214612 214060 214064 214062 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2 1 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 35 214021 Loop Interface LIF64 1 51 214027 Network Cable NWK2 1 39 214031 Network Redundant Alarm Converter NNUS5 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Module SZ58 3 287 310002 Stand by Battery 12V 18Ah 58 218022 ZLT Interface License ZLT SS BCnet Sectional Control Panel OP BC216 2 A1 The BCnet Sectional Control Panel BC216 2 A1 is a modularly designed sectional control panel with display and operating field in the version for Austria for application in a Fire De tection Control Panel BCnet216 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating ele ments as well as the displayed and printer texts are in German language Approval FT 14 147 3 99 Austria VdS G201017 BCnet Sectional Control Panel OP BC216 2 D1 The BCnet Sectional Control Panel BC
65. Current consumption Alarm temperature Operating temperature Ambient temperature Functionality check by means of test activation with Remote Test Unit ECO1000RTU supplied through detector line voltage typ 80uA quiescent 58 C maximum heat component max 45 C 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 x 40 5 mm Colour white Weight 75g Approval VdS G201067 169 BB072001 SAM 0720 01 0100 242047 242045 169 BB072001 SAM 0720 01 0100 Chapter 11 Conventional Detectors Series 300 ECO1000 87 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 107 246140 Detector Base Conv 1000 SS ECO1000BR 1000 107 246141 Detector Relay Base Conv 1000 SS ECO 1000BREL24L 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PAS8 1 113 246150 Remote Test Unit Conv 300 1000 SS ECO1000RTU 4 210210 Zone Extension Board ZEB2 1 Thermal Max Detector Conv 1000 SS ECO1004T Thermal detector operating on the maximum heat detection principle classified BS in ad dressable conventional technology flat design suitable for indoor mounting in buildings with a maximum room height of 6m For quic
66. D1 Fire Brigade Control Unit FBF900 2 D1 for standard connection to fire detection systems ac cording to DIN 14661 The control unit provides an optical display of the most important operating conditions of the fire detection control panel to facilitate and standardise the opera tion of a fire detection system for the fire brigade The Fire Brigade Control Unit FBF900 2 D1 can be directly con nected to the Fire Detection Control Panels Series BC216 via a Fire Brigade Interface FWI2 1 whereas a connection to the Fire Detection Control Panels Series BC016 is established via the Fire Brigade Interface FWI016 1 Features Green LED indicator for Operation Red LED indicator for Panel summary alarm Red LED indicator for Extinguishing systems activated Yellow LED indicator for Acoustic signals off Yellow LED indicator for Transmitting device disabled Yellow LED indicator for Transmitting device activated Yellow LED indicator for Fire control off Switch Acoustic signals off Button Panel reset with safety cover Switch Transmitting device off Button Test transmitting device Metal case with glass door Prepared for a half cylinder locking mechanism oo ooo o o Specifications Operating voltage 20 30VDC Current consumption lt 12mA quiescent lt 80mA alarm Environmental class II Protection class IP30 169 BB072001 SAM 0720 01 0100 250707 169 BB072001 SAM 0720 01 0
67. DE oe dew ei ove oe date suber ad 285 Telephone Speaker Set TEL805 1 ananununnnnnnvnrnnvnuenannnuenenananuenennnenenananuunenenr 285 Plug in Power Supply STN805 1 sssuunvnenannnnenennvanennnnnueuenannuvernnnanuenennsuusennen 285 Batteries and Power Supply Devices 310010 Stand by Battery OV 122AN Sa San eaaa eee ste rene pease ee eta esa 287 310006 Stand by Battery 12V 2 3Ahe oi coal oe se ak teal snapser eee ear e Ee EA 287 310001 Statid by Battery I2V TAR 3 says dte a E E oe BNP eet ae eS SEE ee Ree eee tet 287 310002 Stand by Battery I2V 18Ah nineye in aa e sea evas aa 287 310012 Stand by Battery 12V 20Ah 2 0 e eect e eee ee tenet tenn nee e enn e nee e ned 288 310003 Stand by Battery 12V 26Ah 1 0 0 ccc cece ee eee renee teen ects ten ene e eben ee ees 288 310004 Stand by Battery 12V 45Ah occ cece cnet eee t bene eee tne e nee nen ee eee 289 310005 Stand by Battery 12V 65Ah nai cece E E ene ee cee eee e eet AEE ence enn ee ees 289 317001 Power Supply 24V 3A MT3400L 0 0 0 cece ccc ene ect e ee eee teen eect n bees ee enneeees 289 317100 Power Supply 24V 1Amp Stabilized NG1 1S 00 0 cece ccc e eect nen e ee nen nee e ees 290 317101 Power Supply 24V 2Amp Stabilized NG2 1S 2 0 c eee cette ence een ee eeeee 290 317102 Power Supply 24V 4Amp Stabilized NG4 1S 0 0 c eee e nent ee nen nee e ees 290 317020 Power Supply Module NTM2402 1 oo cece ec ct nent eee n ee tnt neces nnn ne ee 291 317021 Power Suppl
68. Detection Control Panel BC216 1S SLO1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in Slovenian language Approval 02012 C 709P3 Fire Detection Control Panel BC216 1S PL1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in Polish language Approval CNBOP 2238 2006 20 Chapter 3 Fire Detection Control Panels Series BC216 2199998 Fire Detection Control Panel BCnet216 Description The Fire Detection Control Panel BCnet2 16 is a decentrally located control panel for medi um size to very large or far flung fire detection systems and consists of individual sectional control panels The sectional control panels are normally installed on the spot adapted to the object and distributed across the building they can however be combined at one or several locations All sectional control panels are connected via a redundant high security network the Global Security System network GSSnet and conjointly form the decentralised Fire De tection Control Panel BCnet216 The decentralised structure not only reduces the cabling work for connecting fire detectors it above all significantly improves the failure safety of the entire system com
69. Display of active and fault state of each circuit Separate fault detection output for each siren circuit with direct response to a conventional detector zone an input on the central processing board or an input on the fire brigade interface Activation via external switches or open collector outputs of the control panel connection either with terminals or flat cable Monitoring of the supply voltage of siren circuits Monitoring of signalling device lines by negative surveillance voltage thereby the activa tion of signalling devices is avoided by the monitoring quiescent current 62 Chapter 6 Additional Modules for Fire Detection Control Panels 222007 222004 Specifications Supply voltage 21 30VDC Sirens supply voltage 21 30VDC Current consumption at 24V typ 15mA all siren output quiescent Load current per siren circuit max 500mA Output voltage sirens quiescent typ 1 2VDC Output voltage sirens activated external supply voltage minus typ 1V End of line resistor 5 6kOhm Ambient temperature 5 C to 50 C Dimensions L x W x H 98 x 74 x 18 mm Weight 60g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 1 210205 Fire Detection Control
70. Fire Brigade Key Deposit Surface Mount FASB AP 266 268012 Key for Fire Brigade Key Deposit 882AML102 268012 Key for Fire Brigade Key Deposit 882AML102 The Key 882AML102 fits the magnetic lock cylinder for steel sheet mounting which is used for installation into the Fire Brigade Key Deposit FASB Cross references Page Art Nr Name Type 266 265019 Cylinder for Steel Sheet Mounting FASB LST102 169 BB072001 SAM 0720 01 0100 28 Chapter 28 Fire Brigade Control and Display Devices 267 Fire Brigade Control and Display Devices 250008 250740 169 BB072001 SAM 0720 01 0100 Fire Brigade Control Unit FBF58 2 The operating panel FBF58 2 is designed according to Variant B of NORM F 3031 It provides an optical indication of the most important operating conditions of the fire detection control panel via light emitting diodes and an additional text display as well as easy and uni Features form operation of a fire detection system by the fire brigade person nel The Fire Brigade Control Unit is controlled via the INFO bus of the control panel Connection to a Fire Detection Control Panel Se ries BC216 can be achieved without additional modules For con nection to a Fire Detection Control Panel Series BCO16 a Serial Interface Module SIM016 3 is required 2 line LC display for clear information Scroll buttons for the display Green LED for operation Red LED for alarm Button for silencing the s
71. Fire De tection Control Panel Module BCM216 3EPS or BCM216 3E with a spe cial cable with a length of 1 5m Note The ABP216 1E INT1 must be installed in the same housing with the device that controls it the original connection cable must not be extended Specifications Current consumption at 24V typ 35mA Connection cable 1 5m Ambient temperature 5 C to 50 C Dimensions W x H x D 478 x 266 6 height units x 40 mm Weight approx 2kg Approval VdS G201017 Cross references Page Art Nr Name Type 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 Display and Operating Front Panel ABP216 1E A1 The Display and Operating Front Panel ABP216 1E A1 in the version for Austria is used as display and operating unit in BCnet sectional control panels which are composed of fire de tection control panel modules Functions specifications and cross references correspond to the Display and Operating Front Panel ABP216 1E INT1 The labels of display and opera ting elements are in German language Approvals FT 14 147 3 99 Austria VdS G201017 Display and Operating Front Panel ABP216 1E D1 The Display and Operating Front Panel ABP216 1E D1 in the version for German
72. Fire Detection Control Panel BC216 1CE INT 1 287 310002 Stand by Battery 12V 18Ah 1 am and 42 Chapter 3 Fire Detection Control Panels Series BC216 214029 Mounting Bracket BW216 1 The Mounting Bracket BW216 1 is made of zinc coated sheet steel and provides mounting holes in LST standard grid It allows for easy mounting of auxiliary modules e g 4 Relay Modules RL58 1 or RL58 2 or 4 Siren Connection Modules SZ58 3 in the Auxiliary Case GEH216 4 q Specifications Dimensions W x H x D 380 x 20 x 100 mm Net weight 340g Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 50 223009 Control Zone Module SLM1 2 102 249095 Multi Module Panel Mounting MEA244 1 E 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 61 223024 Siren Connection Module SZ58 2 214230 Control Panel Rack 8HU RACK216 1E The Control Panel Rack 8HU RACK216 1E serves as a mounting frame and allows for the installation of a maximum of 7 Fire Detection Control Panel Modules BCM216 3E or BCM216 3ELG or 1 Fire Detection Control Panel Module with power supply BCM216 3EPS and 6 Fire Detection Control Panel Modules BCM216 3E or BCM216 3ELG or 2 Fire Detection Control Panel Modules with power supply BCM216 3EPS and 4 Fire Detection Control Panel Modules BCM216 3E or BCM216 3ELG The rack is normally installed on the back pla te of a 19 wall mount cabinet or 19 floor ty pe cabine
73. H Colour Weight Approval Cross references Page 0 C to 60 C 0 to 95 no condensation Am241 0 9uCi 33 3kBq 176 177 100 x 42 mm white 102g EECS ATEX 0073 LPCB 010b Art Nr Name Type 246023 IS Detector Base Conv 60 Apo GSEX 45681 207 228003 Safety Barrier Conv ES58 2 IS Detector Base Conv YBN R 4IS Detector base for hazardous areas for an intrinsically safe smoke detector Series SLR suitable for indoor surface mounting An E e Specifications Ambient temperature Features No electronics contained Multi useable terminals with secure screw fitting 10 C to 55 C no condensation or icing 10 to 95 no condensation 100 x 15 mm Relative humidity Dimensions x H Colour Weight Cross references Page 175 71 white 45g Art Nr Name Type 241090 IS Optical Smoke Detector Conv SLR E IS 251001 Remote Indicator PAS8 1 IS Detector Base Conv 60 Apo GSEX 45681 207 Detector base used in hazardous areas for an intrinsically safe Series 60 automatic smoke de tector suitable for indoor surface Specifications Ambient temperature mounting Features No electronics contained Multi useable terminals with secure screw fitting Terminal for external remote indicator Mechanical theft protection 20 C to 60 C no condensation or icing Relative humidity 10 to 95 no condensation Dimensions x H 100 x 15 mm Colour white Weigh
74. H x D 300 x 400 x 100 mm Colour grey white RAL 9002 Protection class IP30 Weight 6 4kg Power Supply 24V 1Amp Stabilized NG1 1S Electronically controlled compact power supply unit for the supply of external devices with increased current consumption The power supply unit provides constant output voltage and is therefore not suitable for loading stand by batteries The componentry is mounted in a plastic housing for DIN rail mounting in 45mm standard grid Features Switch mode power supply unit current limited and short circuit proof Stabilised output voltage Light emitting diode for indicating operation and fault Integrated mains fuse JR Specifications Operating voltage 90 to 260VAC 48 to 63Hz Output voltage 24VDC 3 Nominal output current 1A Ambient temperature 5 C to 40 C Relative humidity max 90 no condensation Dimensions L x W x D 87 5 module units x 93 x 66 mm Colour light grey RAL 7035 Weight 185g Power Supply 24V 2Amp Stabilized NG2 1S Electronically controlled compact power supply unit for the supply of external devices with increased current consumption The power supply unit provides constant output voltage and is therefore not suitable for loading stand by batteries The componentry is mounted in a plastic housing for DIN rail mounting in 45mm standard grid Features Switch mode power supply unit current limited and short circuit proof Stabilised output voltage
75. HSFSK700 2 D5 264 265763 Steel Column V2A for Strobe HSFSK700 2 D4 ion and 169 BB072001 SAM 0720 01 0100 265751 265818 249650 169 BB072001 SAM 0720 01 0100 Chapter 27 Fire Brigade Key Boxes and Accessories 259 262 265760 Steel Column V2A Standard HSFSK700 2 D 1 265 265660 Unblocking Element F0345 265 265661 Unblocking Element for Half Cylinder FSE MP1 Flush Mounting Frame for FSK700 2 EZ700 2 D1 The flush mounting frame made of galvanised sheet steel serves as a joint between the Fire Brigade Key Box FSK700 2 and the wall and enables an easy installation in the construction stage of the building a Specifications Dimensions W x H x D 275 x 245 x 160 mm Colour silver grey Weight 3 3kg Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 Flush Mounting Frame with Drilling Protection for FSK700 2 EZBS700 2 The flush mounting frame made of galvanised sheet steel with all side drilling protection ser ves as joint between the Fire Brigade Key Box FSK700 2 D1 or FSK700 2S2 D1 and the wall or the hol low column without concrete filling Specifications Dimensions W x H x D 275 x 245 x 160 Weight 3 5kg Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 Protective Cover for FSK700 2 WSD FSK The protective cover WSD FSK for t
76. IP54 for Manual Call Point HFM HM ZS IP54 167 249634 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 169 2171621 Replacement Glass for Manual Call Point Blue ET SCH HM BL 170 249024 Special Designation for Manual Call Point HM BESCH Manual Call Point Blue Anal SS HM 5 22 18 02 The Manual Call Point HM 5 22 18 02 operates as electrical emergency hold device for gas extinguishing systems and is designed for use on the ADM loop using System Sensor 200 protocol An integrated dual isolator module disconnects the loop at short circuit The manual 162 Chapter 17 Manual Call Points 245392 o o o call point is accommodated in a blue aluminium die cast housing and is tested in accordance with the standards EN54 11 B EN 54 17 and EN 12094 3 Features Robust aluminium die cast housing with an door aperture angle of more than 180 Knopt tief drucken Inscription field STOPP TASTER Gasl schanlage exchangeable Integrated dual isolator Reverse polarity protection Integrated microcontroller Optical indication of activation by LED indicator Push button non latching Standardised glass pane easy to replace Setting of physical address with button in combination with LED indicator Plenty of space for cabling Increase of protection class to IP54 via optional Protection Kit for Manual Call Points HFM HM ZS IP54 Specifications Operating voltage supplied through loop voltage Current consu
77. Name Type 119 249020 Address Module Conv NG58 1 114 246006 Base Adapter SS MZP500 1 226 249011 Detector Label BME BEZ 120 249044 Detector Mounting Bracket MMW1 1 174 240015 IS Ionisation Smoke Detector Conv 100 SS 1151EIS 174 242015 IS Thermal ROR Detector Conv 400 SS 5451EIS 82 241041 Optical Thermal Detector Conv 300 SS 2351TEM 81 241040 Optical Smoke Detector Conv 300 SS 2351E 121 249640 Protective Cage BWS 1 D1 115 246010 Recessed Mounting Kit SS RMK400 71 251001 Remote Indicator PAS8 1 115 246009 Surface Mounting Kit SS SMK400 84 242041 Thermal Max Detector Conv 300 SS 4351E 84 242042 Thermal Max Detector Conv 300 SS 5351TE 83 242040 Thermal ROR Detector Conv 300 SS 5351E 121 249635 Trapezoid Steel Bracket TBH800 1 116 249012 Wet Base Shroud SS WB1 246100 Detector Relay Base Conv 300 SS B324RL Mounting base for automatic fire detectors Series 300 with integrated relay output suitable for indoor surface mounting The mounting base is designed for the connection to control pa nels with a 24VDC operating voltage The relay output is activated by the alarm condition of the inserted detector and remains in the activated status as long as the alarm is not reset on the fire detection control panel Application must comply with the LST Connection of Detectors Features Multi useable terminals with secure screw fitting Auxiliary contact for the through connection of the detector line when the detector is removed Relay outpu
78. Protection class IP21 Dimensions x H 115 x 38 mm Colour white Weight 140g Approval VdS G207009 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG JET mv E 169 BB072001 SAM 0720 01 0100 355124 355125 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 235 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359021 Lid for Detector Base Sounder Red 45681 293 252 359020 Lid for Detector Base Sounder White 45681 292 35 214021 Loop Interface LIF64 1 253 359022 Mounting Plate for Sounder WB XP95 38531 810 Sounder WM XP95 Red Alert 100dB 55000 278 The addressable loop sounder 55000 278 is integrated in a red plastic housing and is de signed for indoor wall mounting The sounder base is included The sounder is activated and supplied via the ADM loop using Specification Operating voltage Current consumption from loop Sound level Ambient temperature Protection class Dimensions x D Apollo Discovery protocol Features Alternating tone 510 610Hz Low power consumption Adjustable sound level supply through the loop voltage max 1 1mA sounder off max 4 5mA sounder on 100dB A 1m distance 20 C to 60 C IP21 106 x 95 mm red 215g according to EN 54 3 Art Nr Name Type Colour Weight Approval Cross references Page 26 32 35 214034 BCnet Sectional Control Pane
79. Series BC016 and BC216 on a remote site The standardised and clear design is user friendly and allows the fire brigade a quick overview of all relevant informati on and an easy operation The Fire Brigade Display Panel FAT900 2 D1 is connected to the INFO bus of the Fire D Detection Control Panels BC016 or BC216 The optional componentry ADFAT900 2 D1 has to be installed in the control panel to guarantee redundant data transfer The Z power is supplied by the control panel and is therefore backed up by stand by batteries Event text messages from the control panel are displayed by default Additional text messages can be programmed using the FatProgWin software The case is equipped with a lock for half cylinders The cylinder lock has to be installed in compliance with the local fire brigade Features Green LED indicator for Operation Red LED indicator for Alarm Yellow LED indicator for Fault Yellow LED indicator for Disablement Button Display level Button Buzzer off Button Scroll forwards Button Scroll backwards 4 line by 20 character backlit display Metal case with glass door Lock for half cylinders Features Operating voltage 10 30VDC Current consumption at 24V 30mA quiescent 90mA alarm Baudrate 1200Baud can be changed with FatProgWin Ambient temperature 0 C to 50 C Dimensions W x H x D 225 x 180 x 58 mm Colour grey white RAL 9002 Weight 3 5kg Approval V
80. Smoke Detector Anal 200 SS ND2251EM Duct Detector Pipe 0 3 0 6M SS ST 1 5 Air inlet pipe with standard air intake drills suitable for Duct Detector Housing Conv 400 SS DH400P and Duct Detector Housing Anal 500 200 SS DH500 applicable for ventilation ducts with a depth of 0 3 to 0 6m Cross references Page Art Nr Name Type 122 244009 Duct Detector 400 OM DH400P 123 244008 Duct Detector Housing Anal 500 200 SS DH500 z am nd 124 Chapter 13 Acessories for Series 300 ECO1000 200 500 244010 244011 244012 249047 Duct Detector Pipe 0 6 1 2M SS ST 3 Air inlet pipe with standard air intake drills suitable for Duct Detector Housing Conv 400 SS DH400P and Duct Detector Housing Anal 500 200 SS DH500 applicable for ventilation ducts with a depth of 0 6 to 1 2m Cross references Page Art Nr Name Type 122 244009 Duct Detector 400 OM DH400P 120 244018 Liiftungsleitungsmeldergeh use DH400 E Duct Detector Pipe 1 2 2 4M SS ST 5 Air inlet pipe with standard air intake drills suitable for Duct Detector Housing Conv 400 SS DH400P and Duct Detector Housing Anal 500 200 SS DH500 applicable for ventilation ducts with a depth of 1 2 to 2 4m Cross references Page Art Nr Name Type 122 244009 Duct Detector 400 OM DH400P 123 244008 Duct Detector Housing Anal 500 200 SS DH500 Duct Detector Pipe 2 4 3 7M SS ST 10 Air inlet pipe with standard air intake drills suitable for Duct Detecto
81. Unblocking Element F0345 265763 Steel Column V2A for Strobe HSFSK700 2 D4 The Steel Column V2A is made of 3mm stainless steel and provides a platform for mounting the Fire Brigade Key Box FSK700 2 and a strobe if installation of the key box in the building front is not possible due to technical or structural reasons or due to special requirements by the fire safety authority Specifications Reinforcement iron cage for anchoring Low net weight Surface made of polished stainless steel Specifications Dimensions W x H x D Weight Art Nr Cross references Page Installation of FSK700 2 possible with flush mounting frame Column prepared for installation of a strobe Flexible armoured tube for different types of cables 400 x 1250 x 300 mm approx 60kg Name Type 257 258 259 230 265740 265742 265751 356671 Fire Brigade Key Box FSK700 2 D 1 Fire Brigade Key Box FSK700 2S2 D1 Flush Mounting Frame for FSK700 2 EZ700 2 D 1 Strobe 24V Orange BE A S 2 0 24VBMT 265764 Steel Column V2A for FSE MP1 HSFSK700 2 D5 The Steel Column V2A is made of 3mm stainless steel and provides a platform for mounting the Fire Brigade Key Box FSK700 2 and an Unblocking Element for half cylinders if instal lation of the key box in the building front is not possible due to technical or structural reasons or due to special requirements by the fire safety authority Specifications Reinforcement iron c
82. Wiring of the ADM loop across several fire areas Full operation of all standard loop elements not affected by the short circuit Installation in commercially available installation boxes on a mounting bracket or a modu supplied through loop voltage max 0 2mA 5 C to 50 C 70 x 24 x 15 mm Weight 20g Approval VdS G296011 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 105 1 3 Acessories for Series 300 ECO1000 200 500 246008 Detector Base Conv 400 100 300 SS B401RM Mounting base for automatic fire detectors Series 400 300 and 100 in addressable conven tional technology suitable for indoor surface mounting a Features Multi useable terminals with secure screw fitting 5 Auxiliary contact for the through connection of the detector Ke Me H line when the detector is removed Terminal for external remote indicator Mechanical theft protection Individual detector addressing by installing an optional ad dress module NG58 1 Specifications Ambient temperature 20 C to 70 C Relative humidity 10 to 93 no condensation Dimensions x H 102 x 20 mm Colour cream Weight 57g Cross references Page Art Nr
83. activated status as long as the alarm is not reset on the fire detection control panel Application must comply with the LST Con nection of Detectors Features Multi useable terminals with secure screw fitting Auxiliary contact for the through connection of the detector line when the detector is removed Relay output with dry changeover contact Specifications Operating voltage Current consumption supplied through detector line voltage 1pA quiescent 30mA active Contact rating 1A at 30VDC Ambient temperature 30 C to 70 C Relative humidity 5 to 93 no condensation Dimensions x H 102 5 x 33 mm Colour white Weight 70g Cross references Page Art Nr Name Type 226 249011 Detector Label BME BEZ JEF av E 108 Chapter 13 Acessories for Series 300 ECO1000 200 500 120 249044 Detector Mounting Bracket MMW 1 1 86 241046 Optical Thermal Detector Conv 1000 SS ECO1002 85 241045 Optical Smoke Detector Conv 1000 SS ECO1003 121 249640 Protective Cage BWS 1 D1 87 242047 Thermal Max Detector Conv 1000 SS ECO1004T 88 242046 Thermal Max Detector Conv 1000 SS ECO1005T 87 242045 Thermal ROR Detector Conv 1000 SS ECO1005 121 249635 Trapezoid Steel Bracket TBH800 1 246142 Detector Relay Base Conv SS ECO1000BREL12L Mounting base for automatic fire detectors Series ECO1000 with integrated relay output sui table for indoor surface mounting The mounting base is designed for the connection to con trol panels wi
84. address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Display of activated condition via 2 LED indicators that are visible from all angles Output for external remote indicator Mechanical theft protection supplied through loop voltage typ 500uA quiescent 20 C to 60 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 50 mm Colour white Weight 105g Approval VdS G299038 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 CO Detector Anal Disc Apo AC 58000 300 Addressable CO detector operating on the electro chemical principle for application on the ADM loop using Apollo Discovery protocol in extra flat design suitable for indoor EN mounting Features Permanent evaluation of environmental conditions Continuous transmission of the current measured value to the fire detection control panel Sensitivity can be set in 5 steps via the Fire Detection Control Panel Series BC216 Address card in the detector base for setting the physical ad
85. an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire detection con trol panel provided that these functions are supported by the control panel If the detector is faulty the multicolour status LED on the detector will flash for approx 4 minutes in yellow colour after the detector line has been enabled Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional address module NG60 1 169 BB072001 SAM 242033 169 BB072001 SAM 0720 01 0100 Chapter 14 Conventional Detectors Series 65 ORBIS 133 Output for external remote indicator Mechanical theft protection Specifications Operating voltage Current consumption Alarm temperature Operating temperature Ambient temperature supplied through detector line voltage typ 65uA quiescent 75 C maximum heat component max 65 C 40 C to 80 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 50 mm Colour white Weight 130g Approval VdS G204035 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Eva
86. and out door mounting The base is not included in the delivery Thanks to a built in serial diode the sounder can be connected directly to a line monitored output with negative surveillance voltage Adjustable sound level Suitable for surface mounting Specifications Operating voltage Current consumption at 24V Sound level Tones Ambient temperature Dimensions W x H x D Features 4 different tones Continuous tone 800Hz Alternating tone 800Hz 1000Hz Slow whoop DIN 33404 tone Wide operating voltage range Low power consumption 15 to 33VDC 4 5 to 12mA 87 to 103dB A at Im distance 800Hz 800 1000Hz Slow Whoop DIN 33404 tone 30 C to 70 C 120 x 90 x 60 mm flame red RAL 3000 155g according to EN 54 3 Art Nr Name Type Colour Weight Approval Cross references Page 251 251 251 359003 Base for Sounder amp Strobe IP44 Red EMA ELPBR 359004 Base for Sounder amp Strobe IP55 Red EMA ESBR 359008 Base for Sounder amp Strobe IP66 Red EMA ESBRS Sounder FB 12 24V White Multitone DBS1224B4W The multitone sounder DBS1224B4W in a round white plastic housing for indoor mounting underneath a standard System Sensor or Apollo detector base or independent of a base An additional front lid DBSLID is needed if the sounder is used independently Thanks to a built in serial diode the sounder can be connected _ directly to a line monitored output with negative surv
87. and output Surveillance of terminal connecting lines for wire bre akage and short circuit z DIL switch for setting the physical address between J 01 and 126 Specifications Operating voltage supplied through loop voltage Current consumption approx 1 25mA quiescent Contact rating 2A 48VDC or 5A 230V AC Line termination 20kOhm Alarm threshold typ IkOhm Ambient temperature 20 C to 70 C Dimensions L x W x H 150 x 90 x 48 mm Colour white Weight 240g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Control Module Anal XP95 Apo SMU 55000 852 Addressable compact module with integrated dual isolator used for the line monitored activa tion of external devices e g fire controls acoustic and optical signalling devices via the bi directional communication on the ADM loop using Apollo Discovery protocol A monitored output can be used as actuation output An external supply voltage has to be applied for the power supply of the external devices Features Monitoring of the external supply voltage Switch for setting the physical address from 01 to 126 146 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY Specifications Operating voltage Current consumption External consumer voltage Output current Monitoring voltage End of line resist
88. are connected to an evalua tion unit or a junction box On the other side they are connected with each other and are hermetically sealed thereby creating two loops Both loops are permanently monitored An interrupti on or a short circuit in one of the two loops causes a fault messa ge in the evaluation unit The blue sensing cable is used in monitored zones where an in creased exposure to dust and humidity can be expected Features Length of sensing cable up to 300m Detection of exceeding temperatures at any point of the sensing cable Resistant against dust and humidity Easy to install Specifications Outer diameter 3 2mm Wire gauge 0 46mm Temperature resistance up to 100 C unlimited up to 150 C 350 hours up to 175 C 25 hours Cross references Page Art Nr Name Type 202 244637 Linear Heat Detection Unit Alarmline Conv LWM 1 Sensing Cable Black LWM SK1800011 The black Alarmline sensing cable with nylon coating consists of four copper wires each of them being coated with a colour coded material with a negative temperature coefficient The wires are twisted and isolated with an outer layer made of temperature resistant and fire retar dant plastic On one side of the cable the four wires are connected to an evaluation unit or a junction box On the other side they are connected with each other and are hermetically sea led thereby creating two loops Both loops are permanently monitored An interru
89. as CS maximum room height 6m in extra flat design suitable for indoor mounting Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional ad gt dress module NG60 1 Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 45uA quiescent Alarm temperature typ 90 C Operating temperature max 80 C continuous operation Ambient temperature 20 C to 90 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 80g Approval VdS G200062 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 149 246035 Detector Base Conv 60 65 Apo 45681 251 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 Optical Smoke Detector Conv ORBIS Apo OP 12001 Smoke detector operating on the light scatter principle in addressable conventional technolo gy with an optical sensing chamber and of extra f
90. bon monoxide sensor slowly developing smouldering fires can x ut be easily detected The infrared sensor reacts to the flicker of fla mes and supports the detection of fires with little smoke forma tion e g alcohol fire All typical fire patterns are detected due to intelligent analysis of measured values obtained from all four detection units Thereby on one hand deceptive alarms can be almost entirely excluded when noise levels occur caused for example by solde ring or a dusty environment On the other hand a real fire is quickly and reliably detected The detector is therefore highly resistant to external influences and can effectively be used in virtually any environmental conditions The response sensitivity of the optical detector can be individually adjusted in 5 steps betwe en 3 2 m and 12 8 m depending on the application In addition the alarm activation of the detector can be accelerated or delayed by intelligent evaluation algorithms that analyse the measured values obtained from all sensors A thermal only mode is also available An automatic drift compensation minimises the influence of contamination on the optical sensing chamber and the CO cell Thereby the response sensitivity of the sensing units is kept constant a further effective measure for avoiding false alarms The carbon monoxide sensor has with 6 years a long lifespan The upcoming end of the life span can be evaluated during maintenance of the fire d
91. by Battery 12V 45Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for emergency power supply of electronic security systems in stand by operation For 24V applications 2 batteries of identical type must be connected in series Due to techno logical progress the stated specifications may differ Specifications Nominal voltage 12V Capacity 45Ah min at 20 hours discharge Dimensions L x W x H 197 x 165 x 170 mm max Weight max 14 8kg Approval approved by VdS Cross references Page Art Nr Name Type 291 317020 Power Supply Module NTM2402 1 Stand by Battery 12V 65Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for emergency power supply of electronic security systems in stand by operation For 24V applications 2 batteries of identical type must be connected in series Due to techno logical progress the stated specifications may differ Specifications Nominal voltage 12V Capacity 65Ah min at 20 hours discharge Dimensions L x W x H 350 x 166 x 175 mm max Weight max 23 7kg Approval approved by VdS Cross references Page Art Nr Name Type 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 292 317021 Power Supply Module NTM2408 1 Power Supply 24V 3A MT3400L The power supply allows for the supply of devices which requir
92. by Buyer shall be borne by the latter Delivery does not however include unloading and subsequent handling Packaging materials will be taken back only by express agreement Seller reserves the right to modify prices if the order placed is not in accordance with the offer submitted Prices are based on costs obtaining at the time of the first quotation In the event that the costs have increased by the time of delivery Seller shall have the right to adjust prices accordingly In carrying out repair orders Seller shall provide all services deemed expedient and shall charge Buyer for the same on the basis of the work input and or expenditures required The same holds for any services or additional services the expediency of which becomes apparent only as the repair order is executed In such an event spe cial notification of Buyer shall not be required Expenses for estimates of costs of repair and maintenance or for expert valuations shall be invoiced to Buyer Delivery The period allowed for delivery shall commence at the latest of the following dates a the date of order confirmation by Seller b the date of fulfillment by Buyer of all the conditions technical commercial and other for which he is responsible c the date of receipt by Seller of a deposit or security due before delivery of the goods in question Buyer shall obtain whatever licences or approvals may be required from authorities or third parties for the constructi
93. condition via green LED indicator Fault display via yellow LED indicator Alarm display via red LED indicator Integrated sounder Push button for detector test and silencing of sounder Additional output for the connection of an external relay max 50mA Specifications Operating voltage Power consumption Ambient temperature Response threshold Sound level of signal Dimensions L x W x H Approvals 230V AC 10 10 50Hz 2 6W 0 C to 40 C lt 25 of lower explosion limit 85dB 1m distance 156 x 80 x 51 mm tested according to BS 7348 1990 EN 60335 1 ERG GS Detector Reset Module MQZ1000 1 Componentry for the connection of special detectors with separate power supply e g RF in terfaces aspiration smoke detection systems beam smoke detectors to detector lines in ad dressable conventional technology The componentry allows for the resetting of an activated special detector directly from the fire detection control panel by Features resetting the corresponding detector zone Depending on the con nection both detectors with integrated reset input and detectors which are reset by disconnecting the power supply can be reset Integrated processing logic for the detector line signal LED display for signalling the activation Specifications Operating voltage Supply current Current consumption at 24V Reset contact rating Ambient temperature Dimensions W x H x D 20 to 31VDC max
94. detector module The response thresholds for the light obscuration and the air flow can be selected in 4 steps Dry contacts in the evaluation electronics of the aspiration smoke detection system housing signal the excee ding of alarm and fault thresholds Specifications Response threshold Light obscuration 2 1 0 5 0 25 m Air flow monitoring 4 levels Cross references Page Art Nr Name Type 217 244300 Aspiration Smoke Detection System Housing TT 1 244304 Detector Module DM TT 05 L The Detector Module DM TT 05 L is used for analysis and evaluation of air which is sampled from the monitored area by the aspiration smoke detection system housing TT 1 The light obscuration and the air flow are measured by the detector module The response thresholds for the light obscuration and the air flow can be selected in 4 steps Dry contacts in the evaluation electronics of the aspiration smoke detection system housing signal the excee ding of alarm and fault thresholds Specifications Response threshold Light obscuration 0 4 0 2 0 1 0 05 m Air flow monitoring 4 levels Cross references Page Art Nr Name Type 217 244300 Aspiration Smoke Detection System Housing TT 1 244305 Front Foil FW TT 1 For Aspiration Smoke Detection System Housing TT 1 WAGNER 169 BB072001 SAM 0720 01 0100 244155 169 BB072001 SAM 0720 01 0100 Chapter 21 Aspiration Smoke Detection Systems 219 Cross references Page Art Nr Na
95. detectors Series ECO1000 suitable for indoor surface mounting i Features Multi useable terminals with secure screw fitting Ce Tie a Auxiliary contact for the through connection of the detec tor line when the detector is removed Terminal for external remote indicator Individual detector addressing by installing an optional ad dress module NG58 1 Specifications Ambient temperature 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 5 x 21 mm Colour white Weight 44g Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 226 249011 Detector Label BME BEZ 120 249044 Detector Mounting Bracket MMW1 1 86 241046 Optical Thermal Detector Conv 1000 SS ECO1002 85 241045 Optical Smoke Detector Conv 1000 SS ECO1003 121 249640 Protective Cage BWS 1 D1 71 251001 Remote Indicator PAS8 1 87 242047 Thermal Max Detector Conv 1000 SS ECO1004T 88 242046 Thermal Max Detector Conv 1000 SS ECO1005T 87 242045 Thermal ROR Detector Conv 1000 SS ECO1005 121 249635 Trapezoid Steel Bracket TBH800 1 Detector Relay Base Conv 1000 SS ECO1000BREL24L Mounting base for automatic fire detectors Series ECO1000 with integrated relay output sui table for indoor surface mounting The mounting base is designed for the connection to con trol panels with a 24VDC operating voltage The relay output is activated by the alarm condition of the inserted detector and remains in the
96. drift compensation according to the degree of contamination of individual smoke detectors on the ADM loop Therefore smoke detectors maintain the same sensitivity over long periods of time and deceptive alarms are avoided ADM alarm logic analyses detector data above the alarm threshold to increase immunity against deceptive alarms comparison of fire patterns ADM multi alarm logic increases the effect of the standard alarm logic through interde pendencies of two or more detectors freely parameterisable in many variants ADM individual detector identification by assignment of a software address to each physical address of a loop element ADM detector text with a two line site specific text that can be easily assigned to every software address ADM individual detector disablement for every single element on the ADM loop or for pre defined groups of elements ADM maintenance prognosis by processor based data interpolations of contamination tendencies of individual smoke detectors on the ADM loop This allows the prediction of a maintenance prognosis Thereby enormous savings in service costs over the product life time are possible ADM detector test each ADM detector can be checked for alarming capability from the control panel ADM actuations on the ADM loop by freely parameterisable control elements and alarm sirens that can be individually activated by the control panel ADM address adjusting to be carried out individual
97. each other by isolator modules Features Wiring of the ADM loop across several fire areas Full operation of all loop elements not affected by the short circuit supplied through loop voltage max 0 2mA Ambient temperature 5 C to 50 C Dimensions L x W x H 70 x 24 x 15 mm Weight 20g Approval VdS G296012 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 z am kand 148 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 249070 Isolator Module Board Apo 43781 552 Isolator module board for the installation in the housing of a detector e g of a manual call point If a short circuit appears between two isolator modules the defective area is separated from the ADM loop and operation of all other connected detectors and modules is guaran teed For optimum availability the detection zones on the ADM loop should be separated from each other by isolator modules Features Connection to the ADM loop using Apol lo Discovery protocol Wiring of the ADM loop across several fire areas Full operation of all loop elements not affected by the short circuit LED activation display Installation in devices manual call points etc Specifications Operating voltage supplied through loop voltage Current consumption max 0 2mA Ambient temperatur
98. ean teen hein as fa AE hrs Ae 60 Programming Cable BC216 RS232 PK216 1 evovnanannnnnvnnannnenrnanvevvernauevennnsnuenrenn 60 Additional Modules for Fire Detection Control Panels 223024 223026 222007 222004 222010 229008 Siren Connection Module SZ58 2 10 0 0 ccc ccc cen en nee eee nen nee bene nee e ee enes 61 Siren Connection Module SZ58 3 eroris rerata Eroe en enn ee cece nen nee een ORELE EEEF 61 Terminal Converter Module 16 Fold SUB58 2 0 0 0 ccc ccc ccc cence eee cece ene ne ete ene neene 62 Relay Module 8 Fold 60VDC RLS8 1 21 0 0 cece ccc cece ee ene n eect eee e eee tn eee eeneaes 62 Relay Module 4 Fold 230VAC RL58 2 ee ccc cece cece ne eee etn eee eect ne ete een nn eens 63 Flat Cable 1700mm 10 Pole FBK17 1 10 0 0 0c ccc ccc cence cece nnn ene nen ene nent eenennene 64 Protocol Printers 227003 227004 227005 227007 227008 227010 227006 Protocol Printer Thermal DPU414 30B 0 ccc cece nnn nee e nent nee e teen een ens 65 AC Adapter for DPU414 PW4007 E1 eeonuunnnennenennnennenennernneenanenennernnennnneneneeenr 65 Battery for DPU414 BT4005 errevnnnenanennnnennenennnennenennenennennnenennernnennnnennnener 66 Printer Cable for DPU414 1 8m 9POL D SUB VERL 0 0 ccc cece cece cece e cence cence ens 66 Protocol Printer Dot Matrix LX300 2 00 0 ccc ccc ccc eee een en ene nee e eben ete ent n beeen eens 66 Printer Cable for LX300 3m 25POL D SUB VERL 0 ccc cece ccc cence ence
99. eee nen enens 67 Spare Paper for DPU414 1Roll MM112 402 N ooo ccc ccc eee ee teen et tne nee e ee 67 Display and Operating Devices 250039 250030 250705 250036 250033 250038 250035 250037 250046 250047 250048 250049 250050 250009 250015 250016 250018 250013 251001 252010 252011 252012 252013 259011 259010 259012 Remote Display and Operating Panel ABF216 1 INT1 oovsmamnnnannnnnnnvnrnnnvevenrnnverennner 68 Remote Display and Operating Panel ABF216 1 A1 oo eee cect eee cen eee eens 68 Remote Display and Operating Panel ABF216 1 D1 1 0 eee cence teen eee eens 68 Remote Display and Operating Panel ABF216 1 B1 oo cece eee cence eens 69 Remote Display and Operating Panel ABF216 1 CZ1 0 cece cece eee nee eeeeee 69 Remote Display and Operating Panel ABF216 1 H1 1 0 cece eee teen eee eens 69 Remote Display and Operating Panel ABF216 1 NL1 ccc c teen eee n eee e teens 69 Remote Display and Operating Panel ABF216 1 SK1 02 0 c eect teen ee ene e eee eeee 69 Remote Display and Operating Panel ABF216 1 RUS1 0 eee cece eect eee eects 69 Remote Display and Operating Panel ABF216 1 SLOL 0 0 0 eee ete ene e eee ees 69 Remote Display and Operating Panel ABF216 1 I1 oo cece cece eee cnet n eens 69 Remote Display and Operating Panel ABF216 1 PL1 0 2 0 oe cece eect nee e eens 69 Remote Display and Operating Panel ABF216 1 HR1 0 ec c cee cette eee ee enee 70 Remote Tableau SG58
100. external devices typ 6A site specific Current consumption at 24V typ 90mA without optional componentries Ambient temperature 5 C to 50 C Dimensions W x H x D 233 x 355 x 104 mm Weight approx 2 8kg Approvals FT 14 147 3 99 Austria VdS G201017 Cross references Page Art Nr Name Type 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 42 214230 Control Panel Rack 8HU RACK216 1E 50 223009 Control Zone Module SLM 1 2 35 214020 Conventional Detector Interface GIF8 1 33 214208 Display and Operating Front Panel ABP216 1E INT 1 58 218023 ESPA 4 4 4 Interface License ESPA SS 47 218024 Extinguishing Control 8 Area License LC216 8LB 37 214023 Fire Brigade Interface Additional Board FWZ2 1 32 Chapter 3 Fire Detection Control Panels Series BC216 36 214022 Fire Brigade Interface FWI2 1 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 32 214205 Fire Detection Control Panel Module BCM216 3E 52 214231 Interface Adapter Module IAM216 1E 35 214021 Loop Interface LIF64 1 51 214027 Network Cable NWK2 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 62 222004 Relay Module 8 Fold 60VDC RL58 1 61 223026 Siren Connection Module SZ58 3 289 310005 Stand by Battery 12V 65Ah 58 218022 ZLT Interface License ZLT SS 214205 Fire Detection Control Panel Module BCM216 3E The Fire Detection Control Panel Module BCM216 3E is a BCnet sectional control panel in slide in unit design with
101. faults or load faults The multi module is therefore ideally suitable for the application in extin guishing systems An optional accessory board allows for the hardware redundant actuation of solenoid valves according to EN 12094 1 The module provides an integrated dual isolator and is designed to be mounted on a DIN rail Features Separate status LED for each input and output Surveillance of terminal connecting lines for wire breakage and short circuit Monitoring of the internal resistance of the control devices as well as the line resistance of the supply line with a method pending as patent integrated self calibration by measuring the line resistance and load resistance initiated at a keystroke Monitoring of the supply voltage for low voltage Button and LED for setting the physical address Mounting on a DIN rail Specifications Operating voltage 20 to 30VDC Current consumption 35mA quiescent max 160mA no load Current consumption on the loop 500uA Number of outputs 4 Load current per output max 1 5A Number of inputs 4 End of line resistance 5 6kOhm Alarm threshold typ 1kOhm Ambient temperature 5 C to 60 C Ambient temperature control devices 5 C to 50 C to ensure the functioning of the fault detection Dimensions L x W x H 196 x 97 x 56 mm Weight 310g Approval VdS G205120 Jer 169 BBO72001 SAM ani 0720 01 0100 102 Chapter 12 Analogue Detectors and Modules Series 200 500 249095
102. for M500 SS SMB500 IS Manual Call Point Red Conv DC21 Manual call point in an elegant red plastic housing with door and standardised glass plate re placeable function marking FEUERWEHR for application in hazardous areas in conven tional technology providing a changeover contact optionally with 2 sealed resistors alarm Latching push button replaceable glass plate Plenty of room for cabling Specifications Operating voltage Ambient temperature Protection class Dimensions W x H xD and end of line resistor The desired resistance value must be specified when ordering The detector can be connected to an ADM loop by using a conventional zone module A safety barrier is not required therefor Features Robust dust proof and water proof plastic housing with a door aperture angle of more than 160 Low flammability and UV resistant Function marking FEUERWEHR replaceable supplied through detector line voltage 20 C to 60 C IP66 135 x 145 x 70 mm 169 BB072001 SAM 0720 01 0100 Chapter 18 Devices for Hazardous Areas 183 Colour flame red RAL 3000 Weight 800g Approval VdS G295026 ATEX 1729 Ex classification II 2 G EEx dme IIC T6 169 BB072001 SAM 0720 01 0100 184 Chapter 19 RF Devices 19 RF Devices 249201 RF Interface 4Rel FUIF511 27D Radio linked interface for the connection of up to 32 automatic or non automatic radio linked detectors The interfa
103. for monitoring and control of the fire brigade key box The adapter is accommodated in a grey white steel sheet case suitable for surface indoor mounting The optical indicators Power Key Box 1 alarm Key Box unlocked and Key removed are clearly arranged and ya indicate the operating conditions of the system The AD900 1 D1 is FSK Adapler able to monitor two separately stored keys in the Fire Brigade Key Box AD 9001 FSK700 2S2 D1 for proper storage and removal and to optically indi ons cate the corresponding key The operating voltage of 10 30VDC en om ables the connection to all commercial control panels without Omen O adjustment Numerous adaptations to specific system conditions actuation with High or Low signal static or dynamic transmission of key box alarm to the fire detection or burglar alarm control panel 169 BB072001 SAM 0720 01 0100 265752 265753 169 BB072001 SAM 0720 01 0100 Kapitel 27 Feuerwehr Schliisselk sten und Zubeh r 261 open circuit or closed circuit operation are possible by means of the DIL switch Opening of the adapter is monitored by a door contact Features Easy adaptation to different system configurations via DIL switch Function testing of box monitoring with button Reset of alarm memory with button Temporary unlocking for testing with button Operating voltage 10 30VDC Current consumption lt 20mA without box locking system
104. g in inser ted ceilings inserted floors or for marking other devices of the fire detection system e g distribution boxes Specifications Dimensions 45mm Marking area W x H 40 x 20 mm Indicating Label FDCP BME BMZ Standardised adhesive label for indication of the fire detection control panel White sign with red border and black inscription Brandmelderzentrale according to the standard DIN 4066 Brandmelderzentrale Specifications Dimensions L x W 298 x 104 mm Cross references Page Art Nr Name Type 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 s am and 228 Chapter 24 Optical and Acoustic Devices conventional 24 Optical and Acoustic Devices conventional 355001 Sounder WM 12 24V Red Multitone 106dB MS1R The multitone sounder MSIR is integrated in a red plastic housing and is suitable for indoor and outdoor mounting Due to the built in serial diode the sounder can be directly connected to a line monitored output with negative monitoring voltage Features 32 differ
105. has been specified by means of S300RPTU the detector number is not displayed on the control panel itself but on an additio nal Zonal Display Unit S300ZDU one of which must be integrated in every detector line Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept con stant for a long time thus constituting an effective measure for preventing false alarms If the contamination of the sensing system is too heavy for further compensation or if the sensing system is defective the status LED on the detector will flash yellow The degree of contamination can be scanned by the maintenance engineer via the Remote Program and Test Unit S3OORPTU Furthermore the SSOORPTU is used to adjust the re sponse sensitivity to the local requirements Features Individual detector addressing via Address Module NG58 1 or programming of the detector Response sensitivity can be set to 3 levels low medium high Functionality check by means of test activation with Remote Program and Test Unit S300RPTU or Remote Test Unit ECO1000RTU Detector status degree of contamination detector address response sensitivity as well as date of latest maintenance can be scanned and edited via Remote Program and Test Unit S300RPTU Output for external remote indicator Mechanical theft protection Insect screen Specificat
106. indication of summary alarm and fault si gnals from fire detection control panels The Remote Display Panel can be surface or flush mounted in dry rooms Features a Optical indication via LEDs _ s gt Acoustic indication by means of integrated buzzer with e silence function lt Display unit and reset button for the buzzer integrated in front panel Alternative buzzer connection options for fault and alarm indication Specifications Supply voltage 20 to 31VDC Current consumption at 24V per LED 20mA buzzer 17mA Number of wires for connection 4 Ambient temperature 5 C to 50 C Dimensions L x W x D 86 x 86 x 40 mm Colour white Weight 170g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E Remote Indicator PA58 1 Remote Indicator for quick identification of alarm
107. indicator Mechanical theft protection Specifications Operating voltage Current consumption Alarm temperature Ambient temperature Relative humidity Dimensions x H Colour Weight Approval Cross references supplied through detector line voltage typ 85uA quiescent 78 C 30 C to 70 C continuous operation 5 to 95 no condensation 102 x 43 mm cream 75g VdS G202016 Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 105 246008 Detector Base Conv 400 100 300 SS B40IRM 105 246100 Detector Relay Base Conv 300 SS B324RL 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PAS8 1 112 246111 Remote Program and Test Unit Conv 300 SS S300RPTU 113 246150 Remote Test Unit Conv 300 1000 SS ECO1000RTU 113 246112 Satellite Unit for Remote Programming Conv 300 SS S300SAT 112 246113 Zonal Display Unit Conv 300 SS S300ZDU 4 210210 Zone Extension Board ZEB2 1 Optical Smoke Detector Conv 1000 SS ECO1003 Smoke detector operating on the light scatter principle in addressable conventional technolo gy with an optical sensing chamber and of flat design suitable for indoor mounting For quick localisation in the event of an alarm each detector c
108. is an autonomous componentry for the supply of devices which require a failure safe power supply with a nominal voltage of 24VDC The module complies with EN 544 2006 In case of mains voltage failure the module continues to provide current from optionally connected stand by batteries The mains voltage is transformed by the in tegrated switched mode power supply to the current limited and short circuit protected output voltage that is required for connected loads and optional stand by batteries The maximum load current varies depending on the battery capacity For a theoretical charging time of 24 hours stand by batteries with a maximum capacity of 45Ah can be charged Battery monitoring includes periodic measurements of the final charge voltage and of the in ternal resistance of the batteries according to EN 54 4 2006 The optional earth leakage mo nitoring of the module can be activated by inserting a jumper The power supply module is prepared for installation in the Power Supply Housing Series NTG Features High efficiency through modern switched mode power supply technology current limited and short circuit protected Long lifespan of stand by batteries through temperature compensated final charge voltage Seven LED indicators for display of causes of fault and operation Integrated mains fuse Specifications Mains voltage 185 to 255VAC 47 to 53Hz Output voltage typ 28VDC Output peak current 2
109. literature as well as written or oral statements which have not be en included in the agreement no warranty obligations may be deduced Unless special warranty periods operate for individual items the warranty period shall be 12 months These conditions shall also apply to any goods supplied or ser vices rendered in respect of goods supplied that are firmly attached to buildings or the ground The warranty period begins at the point of passage of risk acc to para graph 6 The foregoing warranty obligations are conditional upon the Buyer giving immedia te notice in writing of any defects that have occurred Buyer shall prove immediate ly the presence of a defect in particular he shall make available immediately to Seller all material and data in his possession Upon receipt of such notice Seller shall in the case of a defect covered by the warranty under 8 1 above have the opti on to replace the defective goods or defective parts thereof or else to repair them on Buyer s premises or have them returned for repair or to grant a fair and reasonable price reduction Any expenses incurred in connection with rectifying defects e g expenses for as sembly and disassembly transport waste disposal travel and site to quarters time shall be borne by Buyer For warranty work on Buyer s premises Buyer shall make available free of charge any assistance hoisting gear scaffolding and sundry supp lies and incidentals that may he required Replaced
110. load 32V 1A Ambient temperature 20 C to 55 C Protection class IP50 Dimensions Sender unit x L 60 x 102 mm Receiver unit x L 60 x 102 mm Control unit W x H x D 210 x 265 x 85 mm Weight sender 0 5kg Weight receiver 0 5kg Weight control unit 2 1kg Approval VdS G297058 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 208 222013 Detector Reset Module MQZ1000 1 rer p E 202 Chapter 20 Special Detectors 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 4 210210 Zone Extension Board ZEB2 1 Linear Heat Detection Unit Alarmline Conv LWM 1 The heat detection unit LWM 1 forms together with the sensing cable a linear thermal de tection system The sensing cable consist of 4 copper wires which are isolated with a materi al with a negative temperature coefficient The resistance of the sensor wires is permanently monitored Thereby an exceeding of the maximum temperature thermal maximum function or a sudden temperature rise rate of rise function at any point of the sensing cable can be detected
111. marking of every double LED Specifications Current consumption at 24V typ 2mA no active LED 0 25mA per LED Ambient temperature 5 C to 50 C Dimensions L x W x H 176 x 120 x 15 mm Weight 60g Jer ani 169 BBO72001 SAM 0720 01 0100 214036 214031 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 39 Cross references Page Art Nr Name Type 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 33 214208 Display and Operating Front Panel ABP216 1E INT1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 72 252010 LED Display Tableau LAT288 1 72 252011 LED Display Tableau LAT288 1CE 73 252012 Remote Tableau Drive Unit PTU288 1 LED Display Field LAB48 4 The LED Display Field LAB48 4 contains 48 freely parameterisable double LEDs 24 pairs red yellow 24 pairs green yellow for the individual display of events of the detector zones actuations transmitting devices or alarming devices at Fire Detection Control Panels Series BC216 and of events of the flooding zones and extin guishing systems at the Extinguishing Control Panel Series LC216 The double LEDs are arranged in two rows each with 24 pairs In addition the LED Display Field can be installed in to an LED Display Tableau LAT288 that serves as a freely programmable display for the events of a F
112. maximum of 2 ADM loops or to a maximum of 16 detector lines in addressable conventional technology or to a combination of both The sectional control panel is designed as 19 slide in unit with 6 height units to be mounted in an optional 19 cabinet The slide in unit is prepared for 2 function modules Conventional Detector Interface GIF8 1 or Loop Interface LIF64 1 a Fire Brigade Interface FWI2 1 a Fire Brigade Interface Additional Board FWZ2 1 an LED Display Field LAB48 1 a Serial Interface Module SIM216 1 and 30 Chapter 3 Fire Detection Control Panels Series BC216 2149997 additional optional componentries as well as a Battery Bracket BK216 1CE for the installati on of a stand by battery with 2 x 12V max 22 Ah The extensive functions and features are summarised in the description of the Fire Detection Control Panel BCnet216 No 2199998 Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 28VDC Output peak current max 1 8A Connection of external devices typ 0 8A site specific Current consumption at 24V typ 90mA without optional componentries Ambient temperature 5 C to 50 C Dimensions W x H x D 478 x 266 6 height units x 95 mm Colour grey white RAL 9002 Weight without batteries approx 6kg Approvals FT 14 147 3 99 Austria VdS G201017 Cross references Page Art Nr Name Type 41 214128 Battery Bracket BK216 1CE 50 223009 Control Zone Module SLM 1 2 35 214
113. measure for preventing false alarms Permanent evaluation of environmental conditions Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Output for external remote indicator Mechanical theft protection supplied through loop voltage typ 280uA quiescent 20 C to 60 C no condensation or icing 0 to 95 no condensation Am241 0 9uCi 33 3kBq Dimensions x H 100 x 42 mm Colour white Weight 105g Approval VdS G294037 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 4568 1 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PA58 1 Optical Smoke Detector Anal XP95 Apo AO 55000 620 Addressable smoke detector operating on the light scatter principle for application on the ADM loop using Apollo Discovery protocol with an optical sensing chamber and of extra flat design suitable for indoor mounting 4 i CTY Intelligent evaluation algorithms in the respective LST fire de tection control panels compensate for the impact of contaminati on of the optical sensing system Thereby th
114. messages from detector zones or single detectors respectively Collective reset of all current alarms via button Panel reset Hierarchized authorisation levels for operation and parameterisation secured via numeric codes Alarm delay with dead man s handle controlled by internal timer which can be set separa tely for each day of the week Start and end date of Daylight Saving Time according to EU directive or freely parameterisable 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 13 One man test condition Non resetable electronic alarm counter Two integrated serial interfaces Integrated INFO bus for the connection of fire brigade control units and intelligent remote indication units Connection of a serial protocol printer via an optional data interface Control panel recognises all control panel components and loop elements by means of au to setup during first commissioning Connection of detectors via unshielded 2 wire cabling Stand by battery 2 x 12V 22Ah can be installed in the control panel s housing Additional features and functions when operating in analogue ADM loop technology provi ded that Loop Interfaces LIF64 1 are used in the control panel ADM loop supports 198 elements 99 detectors and 99 modules using System Sensor 200 protocol or 126 elements detectors and or modules using Apollo Discovery protocol Each ADM loop can be split in up to 128 d
115. of electric welding at larger distances The response delay can be adju sted in 3 levels between 3 and 12 seconds Application limits occur in the field of IR emitting rapidly changing light sources dust and contamination of the IR filter glass on the detector Features Applicable in conventional technology Connection to an ADM loop via a conventional zone module possible Specifications Operating voltage supplied through detector line voltage Current consumption 350uA quiescent Surveillance angle approx 110 Spectral sensitivity 4 4um Ambient temperature 20 C to 60 C Dimensions L x W x D 98 x 64 x 35 mm Protection class IP65 Weight 110g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 4 210210 Zone Extension Board ZEB2 1 Beam Smoke Detector Conv SS 6500R Beam smoke detector for the surveillance of open areas with a range of 5m to 70m with ac cessories up to 100m consisting of a combined transmitter receiver unit integrated into
116. of aspiration holes and pipe burst as fault The velocity of air flow is indicated separately for each channel via 10 step LED displays The conditions for operation summary fault and ventilator fault are signalled by one com bined LED Smoke detector detector base and sensor pipe network are not provided with the aspira tion smoke detection system housing Specifications Supply voltage Current consumption ext supply Pipe length Ambient temperature Humidity Protection class Dimensions W x H x D 18 30VDC 80 500mA at 24V depending on tube length and ven tilator speed max 100m 10 C to 60 C max 95 non condensing IP50 optionally IP65 258 x 194 x 145 mm 1 67kg VdS pending Art Nr Name Type Weight Approval Cross references Page 91 90 241050 Optical Laser Detector Anal 200 SS 7251 241010 Optical Smoke Detector Anal 200 SS ND2251EM Aspiration Smoke Detection System Housing TP 1 The Aspiration Smoke Detection System Housing TP 1 samples air via the connected sensor pipe network from a monitored room and directs it to the detector module not provided which analyses the air samples If the smoke concentration exceeds the permissible value an alarm is activated which is optically displayed on the system and further transmitted to a fire detection control panel The alarm can be reset at the control panel The system can be used for ear ly fire detection in room and equipment m
117. panel Activation via selectable detector zone outputs Activation via an external switch Surveilled voltage at external and internal supply of the signalling devices Separately fused outputs Monitoring of the signalling device lines through negative monitoring voltage thereby the interfering activation of the signalling devices by the quiescent surveillance current is prevented Specifications Operating voltage 20 to II VDC External supply voltage 20 to 36VDC Current consumption at 24V 10mA quiescent Load current per output max 500mA externally supplied Output voltage siren circuit idle 1 1VDC Output voltage siren circuit active approx equal to supply voltage End of line resistor 5 6kOhm Quiescent surveillance current 0 2mA Ambient temperature 5 C to 50 C Dimensions L x W x H 95 x 75 x 15 mm Weight 50g Siren Connection Module SZ58 3 The Siren Connection Module SZ58 3 is designed with four siren circuits for activation of re mote signalling devices e g sirens strobes to expand control panels Series BC216 BC016 and BC06 All four siren circuits have separately actua table individually fused and monitored outputs In additi on each circuit contains a separate fault detection output Monitored signalling devices may either be supplied by the control panel or at higher current demand by an external power supply Features 4 individually fused and monitored siren circuits
118. permanently moni tored A failure of the ventilator blocking of aspiration holes or a pipe burst are optically displayed on the system and transmitted to the control panel as fault message The aspiration smoke detection system housing is provided with the entire evaluation electro nics However the detector module the front foil and the sensor pipe network are not provided A serial interface is installed in the system for communication with a PC software Operation fault alarm areal and alarm area2 are indicated on the front side of the system via LEDs 169 BB072001 SAM 0720 01 0100 244186 244182 169 BB072001 SAM 0720 01 0100 Chapter 21 Aspiration Smoke Detection Systems 215 Features Applicable in addressable conventional technology with the optional Detector Reset Mo dule MQZ1000 1 Individual detector identification through connection of an optional address module NG58 1 Connection to an ADM loop is possible via optional modules Specifications Supply voltage 14 30VDC Current consumption at 24V max 295mA quiescent 315mA alarm incl detector module Pipe length 2 x max 180m Number of aspiration holes 2 x max 20 Ambient temperature 20 C to 60 C Dimensions W x H x D 200 x 292 x 113 mm Colour white RAL 9018 Weight 1 45kg Approval VdS G202064 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1
119. radio transmitted to the RF Interface M500RFE AS System Sensor 200 protocol or M400RFE AS in conven tional technology The radio linked detector is particularly suited for applications where cabling is not possible or inefficient Batteries are provi ded with the detector which is suited for indoor mounting Features Operating instructions by symbols European Standard Optical indication of activation via LED Latching push button Standardised glass pane easy to replace Continuous status messages 24 bi directional data channels Unique code generated out of several million options Channels are checked for availability Monitored battery voltage Sabotage message when door is open Oo o Specifications Supply voltage 2 lithium batteries 3 6V type LS14500 Battery lifespan approx 1 5 years rer nd 190 Chapter 19 RF Devices 245023 249215 Frequencies Radio transmission range Ambient temperature 434MHz and 868MHz max 300m free air 0 C to 40 C Relative humidity 10 93 no condensation Dimensions W x H x D 125 x 125 x 36 mm Colour flame red RAL 3000 Weight 250g without batteries Approval VdS G204103 Cross references Page Art Nr Name Type 191 310021 Lithium Battery 3 6V 2 2Ah 188 249203 RF Interface 4Rel M400RFE AS 187 249202 RF Interface Anal SS M500RFE AS Manual Call Point Blue RF M400DKMB AS The radio linked manual call point according to EN 54 1
120. rating Line termination Alarm threshold Ambient temperature Dimensions L x W x H Colour Weight Approval Apollo Discovery protocol The module provides an integrated dual isolator and is integrated into a pla stic housing Features Separate status LED for each input and output Surveillance of terminal connecting lines for wire breakage and short circuit DIL switch for setting the physical address bet ween 01 and 126 supplied through loop voltage approx 3mA quiescent 1A 30VDC or AC 20kOhm typ 4 7kOhm 20 C to 70 C 250 x 175 x 75 mm white 621g VdS G202052 169 BB072001 SAM 0720 01 0100 249078 249073 169 BB072001 SAM 0720 01 0100 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 145 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Module 1xSurv In 1xRel Out 230 Apo 55000 875 Addressable module for the line monitored integration of a contact detector e g manual call point sprinkler system contact supervising contact as well as a dry relay contact for trigge ring external devices via the bi directional communication on the ADM loop using Apol lo Discovery protocol The module provides an integrated pp dual isolator and is integrated into a plastic housing Features Separate status LED for input
121. references Page Art Nr Name Type 191 310020 Lithium Battery 9V 1 2Ah 185 241029 Optical Smoke Detector RF 55000 680 184 249201 RF Interface 4Rel FUIF5 1 1 27D 185 242029 Thermal ROR Detector RF 55000 480 RF Interface Anal SS M500RFE AS The RF Interface MSOORFE AS constitutes a gateway between radio linked detectors and a fire detection control panel Communication with the control panel is established via the ADM loop using System Sensor 200 protocol Up to 99 automatic detectors and up to 98 manual call points can be addressed by the RF interface One module address on the ADM loop is assigned to the gateway In the teach in phase the detector addresses have to be configured either automatically or manually via the operating menu Features Operation via keypad and alphanumeric display Multilingual operation menu Automatic teach in process for configuration of detectors Protection against unauthorised access by 6 digit code Display of signal level of each detector Status display via 3 LED indicators operation alarm fault Integrated dual isolator Automatic change over between the two frequencies 434MHz and 868MHz 24 bi directional data channels Channels checked for availability wwe w u 9 69 Specifications Supply voltage 10 30VDC Current consumption ext supply max 80mA at 24V Current consumption from loop 325uA quiescent Frequencies 434MHz and 868MHz Radio transmission range max 300m
122. sound level typ 96dB A 1m distance high sound level max 100dB A Im distance high sound level Examples at 24V Continuous tone 660Hz typ 4 6mA at 98dB A 1m distance DIN tone 1200 500Hz typ 6 5mA at 100dB A 1m distance Slow Whoop tone 500 1200Hz typ 6 6mA at 96dB A 1m distance Ambient temperature 25 C to 70 C Relative humidity 10 96 no condensation Dimensions x D 115 x 68 mm incl Base LPBW Colour red Weight 204g Approval VdS G206072 Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 255 359041 Base Sounder amp Strobe IP44 Red SDBR 256 359042 Base Sounder amp Strobe IP65 Red WDBR 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 355161 Sounder WM 200ISM Red Multitone 100dB WMSOU RR P02 The addressable multitone sounder is accommodated in a red plastic housing and is prepared for outdoor and indoor mounting The unit is mounted on a base for signalling devices not provided The sounder is actuated as a module using System Sensor 200 protocol and is powered via the ADM loop A dual isolator is integrated in the sounder At short circuit it main tains the function of ADM elements that are not affected by the short circuit 169 BB072001 SAM 0720 01 0100 355162 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devi
123. supply of the Optical Thermal Detector 2100RFT AS Features High quality lithium battery Low self discharge Long lifespan of typ 1 5 years in an automatic radio linked detector 169 BB072001 SAM 0720 01 0100 310020 310021 169 BB072001 SAM 0720 01 0100 Chapter 19 RF Devices Shelf life min 5 years Cross references Page Art Nr Name Type 191 189 241036 Optical Thermal Detector RF complete 2100RFT AS Lithium Battery 9V 1 2Ah Spare battery for radio linked detector base 215 27D Each detector base requires 2 batteries both batteries have to be replaced at the same time Features High quality lithium battery Low self discharge Long life span of typ 1 5 years when used in radio linked detector base 215 27D Shelf life min 5 years Cross references Page Art Nr Name Type 187 246040 Detector Base Conv RF 215 27D Lithium Battery 3 6V 2 2Ah Spare battery for radio linked manual call points Features High quality lithium battery Low self discharge Long life span of typ 1 5 years when used in radio linked manual call point Shelf life min 5 years Cross references Page Art Nr Name Type 186 245021 Manual Call Point Blue RF HM 152 27D 190 245023 Manual Call Point Blue RF M400DKMB AS 185 245020 Manual Call Point Red RF HFM 153 27D 189 245022 Manual Call Point Red RF M400DKMR AS Jer _ 192 Chapter 20 Special Detectors 20
124. the power supply housing The bottom side of the housing is recommended as cable en try point otherwise stand by batteries are standing on the flange plate and prevent a cable entry Specifications Dimensions W x H x D 800 x 1000 x 300 mm 294 Chapter 31 Batteries and Power Supply Devices 317033 229010 Colour light grey RAL 7035 Weight without installations approx 57kg Cross references Page Art Nr Name Type 294 317033 Battery Bracket BK24 1 291 317020 Power Supply Module NTM2402 1 292 317021 Power Supply Module NTM2408 1 Battery Bracket BK24 1 The Battery Bracket BK24 1 is prepared for simple and secure installation of stand by batte ries in the Power Supply Housing NTG24 2 or in an 19 cabinet The stable steel sheet de sign can accommodate a maximum of either one stand by battery 12V 65Ah or 12V 85Ah or two stand by batteries 12V 45Ah Specifications Dimensions W x H x D 370 x 195 x 209 mm Colour light grey RAL 7035 Weight approx 1 8kg Cross references Page Art Nr Name Type 293 317032 Power Supply Housing NTG24 2 Voltage Stabiliser 24VDC STAB24 1 By using the Voltage Stabiliser STAB24 1 the voltage fluctuations of the output voltages that are conditional upon the charging logic of the fire detection control panels are kept to a minimum which guarantees optimum operation of the supplied modules Features High efficiency Easy installation Small dimensions Specifications
125. the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 Specifications Operating voltage Ambient temperature Protection class Dimensions W x H xD supplied through detector line voltage 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm Colour flame red RAL 3000 Weight 400g Approval VdS G202034 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 169 219006 Key for Manual Call Point SCH HFM HM 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249633 Protective Cover V2A for Manual Call Point Red WG ROT E 1 169 2171620 Replacement Glass for Manual Call Point Red ET SCH HM RT 170 249024 Special Designation for Manual Call Point HM BESCH 4 210210 Zone Extension Board ZEB2 1 245352 Manual Call Point Blue Conv HM 5 11 02 02 Universal manual call point according to EN 54 11 B in an elegant blue aluminium die cast housing designed for application in addressable conventional technology HAUSALARM Scheibe einschlagen e Knopi tiet driicken Fe
126. those of an 18Ah accumulator Specifications Nominal voltage 12V Capacity 20Ah at 20 hours discharge Dimensions L x W x H 181 x 76 x 167 mm max Weight 6 4kg max Approval approved by VdS Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT 1 27 214108 Fire Detection Control Panel BC216 1CE INT1 16 214308 Fire Detection Control Panel BC216 1S INT1 72 252010 LED Display Tableau LAT288 1 Stand by Battery 12V 26Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for emergency power supply of electronic security systems in stand by operation For 24V applications 2 batteries of identical type must be connected in series Due to techno logical progress the stated specifications may differ Specifications Nominal voltage 12V Capacity 26Ah min at 20 hours discharge Dimensions L x W x H 167 x 175 x 125 mm max Weight max 9 6 kg Approval approved by VdS 169 BB072001 SAM 0720 01 0100 310004 310005 317001 169 BB072001 SAM 0720 01 0100 Chapter 31 Batteries and Power Supply Devices 289 Stand
127. typ 7 9mA at 86dB A 1m distance Flash frequency 1Hz Ambient temperature 25 C to 70 C Relative humidity 10 96 no condensation Dimensions x H 112 x 42 mm without detector incl Base LPB W Colour red cream RAL 9001 Weight 136g Approval VdS G206076 Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 254 359043 Base Sounder amp Strobe IP44 White SDBW 255 359044 Base Sounder amp Strobe IP65 White WDBW 169 BB072001 SAM 0720 01 0100 356140 356141 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 249 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Strobe WM 200 Red WMSTR WR P01 The addressable strobe is accommodated in a red plastic housing and is prepared for outdoor and indoor mounting The unit is mounted on a base for signalling devices not provided The strobe is actuated as a module using System Sensor 200 protocol and is powered via the ADM loop mpe Features Long lifespan of strobe due to the use of LEDs Low power consumption 2 decadic rotary switches for setting the address from 01 to 99 Different base versions available Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 450uA strobe off max 3 8mA strobe activ
128. 0 1 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 Mounting base for fire detectors Series XP95 and Discovery with integrated relay output sui table for indoor surface mounting The relay output is active as long as the detector remains in the alarm state Application must comply with the LST Connection of Detectors Features Multi useable terminals with secure screw fitting Relay output with dry changeover contact Specifications Current consumption max I UA quiescent 40uA active Contact rating 1A at 30VDC Ambient temperature 20 C to 70 C Relative humidity 0 to 95 no condensation Dimensions x H 100 x 24 mm Colour white Weight 100g Cross references Page Art Nr Name Type 153 246030 Backplate Apo SZPL 4568 1 233 141 243100 CO Detector Anal Disc Apo AC 58000 300 153 246029 Conduit Box Apo SZA 4568 1 204 120 249044 Detector Mounting Bracket MMW 1 1 138 240026 Ionisation Smoke Detector Anal Disc Apo AI 58000 500 136 240024 Ionisation Smoke Detector Anal XP95 Apo AI 55000 520 141 241022 Optical Thermal Detector Anal Disc Apo AMS 58000 700 138 241030 Optical Thermal Detector Anal XP95 Apo AMS 55000 885 139 241027 Optical Smoke Detector Anal Disc Apo AO 58000 600 136 241023 Optical Smoke Detector Anal XP95 Apo AO 55000 620 121 249640 Protective Cage BWS 1 D1 140 242028 Thermal Detector Anal Disc Apo AD 58000 400 137 242023 Thermal Detector Anal XP95 Apo AW 55000 420 121 249635 Trapezoid Ste
129. 0 845 Addressable compact module with integrated dual isolator for the integration of conventional detectors into the bi directional communication on the ADM loop using Apollo Discovery protocol 169 BB072001 SAM 0720 01 0100 249029 169 BB072001 SAM 0720 01 0100 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 147 Specifications Operating voltage Current consumption Line termination Detector current Ambient temperature Dimensions L x W x H Features Switch for setting the physical address from 01 to 126 supplied through loop voltage 4mA quiescent 6 2kOhm max ImA 20 C to 70 C 150 x 90 x 48 mm white 230g VdS G201094 Art Nr Name Type Colour Weight Approval Cross references Page 26 32 35 214034 BCnet Sectional Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 Isolator Module Anal Apo ISM1 3 Isolator module for the connection to the ADM loop using Apollo Discovery protocol If a short circuit appears between two isolator modules the defective area is separated from the ADM loop and operation of all other connected detectors and modules is guaranteed For op LED activation display Installation in commercially available installation sockets Specifications Operating voltage Current consumption timum availability the detection zones on the ADM loop should be separated from
130. 0 BRD 80 246072 Detector Relay Base FC600 FC600 BREL 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 169 BB072001 SAM 0720 01 0100 10 Chapter 10 Acessories for Series FC600 79 Acessories for Series FC600 246070 246071 169 BB072001 SAM 0720 01 0100 Detector Base FC600 FC600 BR The Detector Base FC600 BR is used for mounting of automatic fire detectors Series FC600 in conventional technology The base is suitable for indoor surface mounting s oraa med Features Multi wire terminal with secure screw fitting Terminal for external remote indicator A Individual detector addressing by installing an optional address module NG58 1 Mechanical theft protection of detectors Specifications Ambient temperature 30 C to 70 C Relative humidity 5 95 no condensation Dimensions x H 110 x 16 mm Colour white Weight 32g Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 76 241070 Optical Smoke Detector Conv FC600 FC600 O 71 251001 Remote Indicator PAS8 1 77 242071 Thermal Max Detector Conv FC600 FC600 TMAX 78 77 242070 Thermal ROR Detector Conv FC600 FC600 TDIFF 57 Detector Base with Diode FC600 F
131. 0 BREL 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 169 BB072001 SAM 0720 01 0100 242070 242071 169 BB072001 SAM 0720 01 0100 Chapter 9 Conventional Detectors Series FC600 77 Thermal ROR Detector Conv FC600 FC600 TDIFF 57 The Thermal Rate of rise Detector FC600 TDIFF 57 reacts to temperature changes in de fined time intervals or to a maximum temperature of 57 C Due to the intelligent evaluation of these data an early detection of expanding fires is possible The alarm is transmitted to the fire detection control panel in A i conventional technology For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG58 1 to the mounting base The address of the detector in alarm condition as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are supported by the control panel An LED indicator visible from all angles displays the activated condition of the detector The detector is accommodated in a white housing complies with class A1R and can be in stalled in rooms that do not exceed a height of 7 5m Several base versions ar
132. 001 SAM 0720 01 0100 30 Chapter 30 Telephone Dialling Devices 281 Telephone Dialling Devices 320007 169 BB072001 SAM 0720 01 0100 Automatic Telephone Dialling Device TWG805 1A The Automatic Telephone Dialling Device TWG805 1A serves for transmission of alarm messages and fault messages and for the reception of switching commands in public telepho ne networks Alarm messages and fault messages are transmitted as voice messages to tele phone connections mobile phones or voice mail boxes Switching commands are transmitted by the caller via DTMF tones to the actuati on output of the telephone dialling device If a dialogue module is used the TWG805 1 can be remotely operated from every telephone connection with an authorisation code In case of an alarm activation the reply of the called participant is recorded Thereby the receipt of alarm information is documented In the basic version the Telephone Dialling Device TWG805 1A is equipped with 4 control inputs and one actuation output The control lines react to changes in resistance and can be programmed for connection of normally open and normally closed contacts The actuation output is designed as dry relay contact and can be configured as pulse output with freely settable pulse duration or as continuous output Ten different voice announcement messages can be recorded the total length of all messages is 64 seconds Up to four messages can be assigned to eac
133. 020 Conventional Detector Interface GIF8 1 58 218023 ESPA 4 4 4 Interface License ESPA SS 47 218024 Extinguishing Control 8 Area License LC216 8LB 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2 1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 35 214021 Loop Interface LIF64 1 51 214027 Network Cable NWK2 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Module SZ58 3 287 310002 Stand by Battery 12V 18Ah 58 218022 ZLT Interface License ZLT SS BCnet Sectional Control Panel OP BC216 2EPS The BCnet Sectional Control Panel BC216 2EPS is the basic set of a Fire Detection Control Panel BCnet216 in 19 slide in unit design It consists of One Control Panel Rack 3HU RACK216 1E One Fire Detection Control Panel Mo dule PS BCM216 3EPS and One Display and Operating Front Pa nel ABP216 1E This basic unit provides space for up to 6 additional BCnet sectional control panels Fire Detection Control Panel Modules BCM216 3E or BCM216 3ELG which are supplied by the power unit of the module BCM216 3EPS If the power does not suffice to supply all sectional control panels you can install an additional module BCM216 3EPS in stead of 2 modules BCM216 3E or BCM216 3ELG The extensive functi
134. 04 The Aspiration Smoke Detection System VLS 304 samples air from the monitored room via up to four separate piping networks and directs it to the smoke evaluation unit which opera tes using a laser light source on the principle of scattered light Each sampling pipe represents an identifiable area that can be individually evaluated If the smoke concentration exceeds the permissible value an alarm is activated which is optically displayed on the sy stem and further transmitted to a fire detection control pa nel Two pre alarms can be activated by exceeding two lower thresholds before reaching the alarm threshold The alarm can be reset at the fire detection control panel The continuous air flow which is generated by a ventilator in the interior of the evaluation unit is permanently monitored A failure of the ventilator blocking of the aspiration holes or a pipe breakage are optically displayed on the system and transmitted to the control panel as fault message The sensitivity and the delay time of the air flow monitoring can be individually adjusted The aspiration smoke detection system is provi ded including the entire evaluation and detection unit However the sensor pipe network is not provided Features Applicable in addressable conventional technology with the optional Detector Reset Mo dule MQZ1000 1 Individual detector identification through connection of an optional address module NG58 1 Connection to an ADM lo
135. 09 210208 210210 210215 210212 Fire Detection Control Panel BCO6 1 INT1 vanamaannanarnananav eee cence ene e nent een enenees 1 Fire Detection Control Panel BCO6 1 D1 oo ccc cece nee n cence eee ee teen enn ents 2 Fire Detection Control Panel BCO6 LA D1 oo cence eee n enn eee e eset en enenens 2 Fire Detection Control Panel BCO6 2 INT1 2 ccc cence eee cece ence eee en een een teenies 3 Fire Detection Control Panel BC06 2 D1 nuananenunuanannenenenenernenenennenenernenenenennenene 3 Zone Extension Board ZEB 2 1 ups sva 4 Serial Interface Module SIMO6 1 2 0 0 0 ccc ccc eee enn eee e nen een n beeen en eee ees 4 Front Foil for Evacuation Circuit FFEV06 1 2 0 0 ccc cence nen e nen eee ene e ante tees 5 Fire Detection Control Panels Series BC016 210102 210100 210122 210120 210110 210111 210112 Fire Detection Control Panel BCO16 1 INT1 6 occ nce n ence een ee een een eens 6 Fire Detection Control Panel BCO16 1 D1 0 6 ccc ccc ce ene cence ene e nen en een ens 7 Fire and Evacuation Panel BCO016 2 INT1 2 0 00 ccc ccc ccc cece ev nan av avnanavevevneneneneneenenr 7 Fire and Evacuation Panel BCO16 2 D1 rannanananuananarneneneneaneneneauanenennenenenenernenene 8 Detector Zone Extension MGE8 1 renenuanenenunuenenuanenennanenenuenenenenernenenenneneneneen 8 Fire Brigade Interface FWI016 1 2 oi cee eee ete ere ee te ce tne eee varene cteteseeteegtveterdensbes 9 Serial Interface Module SIM016 3
136. 0VAC Output current SA Ambient temperature 5 C to 50 C Dimensions W x H x D 200 x 300 x 155 mm Colour light grey RAL 7035 Weight 9kg Cross references Page Art Nr Name Type 119 249027 Detector Heater Anal 500 200 SS MH500 1 155 246033 Detector Heater Anal Apo MH95 1 154 246032 Detector Heater Conv 60 65 Apo MH60 1 249027 Detector Heater Anal 500 200 SS MH500 1 Mounting base with included heating for the application of System Sensor Series 500 or 200 automatic smoke detectors in extremely moist areas e g loading ramps cable ducts A de tector base with area heater and connection terminals with a remote indicator are mounted to gether on a mounting plate Features Connection terminals for all incoming and out going cables Detector base pre wired on the terminals Additional remote indicator on the connection terminals Specifications Operating voltage max 48V AC Power consumption 12W Dimensions L x W x H 310 x 175 x 120 mm Weight 1 3kg Cross references Page Art Nr Name Type 90 240013 Ionisation Smoke Detector Anal 200 SS 1251E 91 241050 Optical Laser Detector Anal 200 SS 7251 90 241010 Optical Smoke Detector Anal 200 SS ND2251EM 119 249014 Power Supply Unit for Detector Heater MH TR1 249020 Address Module Conv NG58 1 Electronic component for the application in addressable conventional technology used for in dividual or group identification of System Sensor Series FC600 100 300 or ECO1000
137. 1 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 52 214231 Interface Adapter Module IAM216 1E 35 214021 Loop Interface LIF64 1 51 214027 Network Cable NWK2 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 61 223026 Siren Connection Module SZ58 3 58 218022 ZLT Interface License ZLT SS 214234 Fire Detection Control Panel Module LG BCM216 3ELG The Fire Detection Control Panel Module LG BCM2 16 3ELG allows for the extension of a Fire Detection Control Panel BCnet216 with two ADM loops for detectors and modules using System Sensor 200 or Apollo Discovery protocols The module is mounted as slide in 169 BB072001 SAM 0720 01 0100 214208 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 33 unit on a sheet steel carrier and is used in a Control Panel Rack 83HU RACK216 1E It is integrated into the BCnet216 by connecting it to the GSSnet wiring via the GSSnet interface on the module The functions of the loop elements at the Fire Detection Control Panel Module LG BCM216 3ELG fully correspond to the functions of a BCnet Sectional Control Panel BCM216 3E equipped with 2 Loop Interfaces LIF64 1 with the limitation that apart from the BCnet redundant alarm function no additional control panel functio
138. 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 113 246150 Remote Test Unit Conv 300 1000 SS ECO 1000RTU 4 210210 Zone Extension Board ZEB2 1 241046 Optical Thermal Detector Conv 1000 SS ECO1002 Multisensor detector with a detection element operating on the light scatter principle and a detection element operating on the rate of rise heat principle classified ATR in addressable conventional technology with an optical sensing chamber and of flat design suitable for in door mounting in buildings with a maximum room height of 7 5m The alarm evaluation is based on the analysis of both de tection units if only one characteristic of fire occurs false alarms can be mostly avoided For quick localisation in the event of an alarm each detector can be assigned an address by adding an Address Module NG58 1 to the mounting base The address of the detector in alarm condition as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are supported by the control panel Features Individual detector addressing by installing an optional address module NG58 1 Drift compensation Output for external remote indicator Insect screen Specifications Operating voltage
139. 1 The labels of display and operating elements as well as the displayed and printer texts are in Czech language Approval EZU 7 105034 00 00 Fire Detection Control Panel BC216 1S H1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in Hungarian language Approval EMILABS 85 2000 Fire Detection Control Panel BC216 1S NL1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in Dutch language Approval VdS G201017 169 BB072001 SAM 0720 01 0100 214317 214349 214384 214388 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 19 Fire Detection Control Panel BC216 1S SK1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in Slovak language Approval EVPU 03323 101 1 2002 Fire Detection Control Panel BC216 1S HR1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in Croatian language Fire
140. 1 B is accommodated in a blue pla stic housing The antenna is integrated in the detector housing The alarm is radio transmitted to the RF Interface MSOORFE AS System Sensor 200 protocol or M400RFE AS in con ventional technology HAUSALARM The radio linked detector is particularly suited for applications Features Inscription field HAUSALARM Optical indication of activation via LED indicator Latching push button where cabling is not possible or inefficient Batteries are provi ded with the detector which is suited for indoor mounting Standardised glass pane easy to replace Continuous status messages Monitored battery voltage Oo Specifications Supply voltage Battery lifespan Frequencies Radio transmission range Ambient temperature Relative humidity Dimensions W x H x D Colour Weight 24 bi directional data channels Unique code generated out of several million options Channels are checked for availability Sabotage message when door is open 2 lithium batteries 3 6V type LS14500 approx 1 5 years 434MHz and 868MHz max 300m free air 0 C to 40 C 10 93 no condensation 125 x 125 x 36 mm sky blue RAL 5015 250g without batteries Cross references Page Art Nr Name Type 191 310021 Lithium Battery 3 6V 2 2Ah 188 249203 RF Interface 4Rel M400RFE AS 187 249202 RF Interface Anal SS MSOORFE AS Battery for 2100RFT AS CR123 The 3V battery is used for
141. 1 SAM 0720 01 0100 214058 214066 214079 214081 214085 214087 214089 214005 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 25 BCnet Sectional Control Panel OP BC216 2 NL1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Dutch language Approval VdS G201017 BCnet Sectional Control Panel OP BC216 2 SK1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Slovak language Approval EVPU 03323 101 1 2002 BCnet Sectional Control Panel OP BC216 2 HR1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Croatian language BCnet Sectional Control Panel OP BC216 2 RUS1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Russian language with cyrillic characters Approval B 01832 BCnet Sectional Control Panel OP BC216 2 SLO1 Functions specifications and cross references co
142. 100 Chapter 28 Fire Brigade Control and Display Devices 269 Dimensions W x H x D 225 x 180 x 57 mm Colour grey white RAL 9002 Weight 2kg Approval VdS G200091 Cross references Page Art Nr Name Type 9 210111 Fire Brigade Interface FW1016 1 36 214022 Fire Brigade Interface FWI2 1 Fire Brigade Display Panel FAT900 1 D1 The Fire Brigade Display Panel FAT900 1 D1 is according to DIN 14662 an ancillary de vice for fire detection systems and provides acoustic and optic display of events from detec tors detector zones and system conditions of Fire Detection Control Panels Series BC016 and BC216 on a remote site The standardised and clear design is user friendly and allows the fire brigade person nel a quick overview of the relevant information and an easy operation The Fire Brigade Display Panel FAT900 1 D1 is directly connected to the INFO bus of D the Fire Detection Control Panel Series BC216 A Serial Interface Module SIM016 3 is required for connection to a Fire Detection Control Panels Series BCO16 The power is supplied by the control panel and is therefore backed up by stand by batteries Event text messages from the con trol panel are displayed by default Additional texts can be programmed using the FatProgWin software The case is equipped with a lock for half cylinders The cylinder lock has to be in stalled in compliance with the local fire brigade Features Green LED indicator for operation Red LED
143. 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 151 246025 Detector Base Anal Apo ASA 45681 210 107 246140 Detector Base Conv 1000 SS ECO 1000BR 1000 105 246008 Detector Base Conv 400 100 300 SS B40IRM 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 79 246070 Detector Base FC600 FC600 BR 111 246012 Detector Base Filtrex Anal 500 SS BS24FTXE 79 246071 Detector Base with Diode FC600 FC600 BRD 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 107 246141 Detector Relay Base Conv 1000 SS ECO1000BREL24L 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 80 246072 Detector Relay Base FC600 FC600 BREL 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 116 249012 Wet Base Shroud SS WB1 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 121 249635 Trapezoid Steel Bracket TBH800 1 The steel sheet bracket is used for the mounting of fire detectors on trapezoid ceilings Specifications Dimensions L x W x H 35 x 95 x 95 mm Weight 150g Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 151 246025 Detector Ba
144. 11 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 241050 Optical Laser Detector Anal 200 SS 7251 Addressable smoke detector operating on the laser light principle for application on the ADM loop using System Sensor 200 protocol with an optical sensing chamber and of flat design suitable for indoor mounting Its high response sensitivity which can be individually set in 9 steps according to the requirements of the detection task en ables this detector to realise a wide range of specific tasks com gt mon optical smoke detectors cannot cope with An optional oly pre alarm can be activated 2 sensitivity levels before reaching 4 the alarm level sr Intelligent evaluation algorithms compensate for the impact of contamination of the optical sensing system Thereby the re sponse sensitivity of the detector is kept constant for a long time thus constituting an effecti ve measure for preventing false alarms The individual response sensitivity of the detector is set via the fire detection control panel Features Continuous transmission of the current measured value to the fire detection control panel Constant sensitivity Response sensitivity can be set in 9 levels between 0 06 m an
145. 113 246150 Remote Test Unit Conv 300 1000 SS ECO 1000RTU 113 246112 Satellite Unit for Remote Programming Conv 300 SS S300SAT 112 246113 Zonal Display Unit Conv 300 SS S300ZDU 4 210210 Zone Extension Board ZEB2 1 84 Chapter 11 Conventional Detectors Series 300 ECO1000 242042 Thermal Max Detector Conv 300 SS 5351TE The conventional addressable thermal detector 5351TE in flat design operates on the maxi mum heat principle class A2S The device is suitable for mounting in buildings with rooms that do not exceed a height of 6m Each detector can be assigned an address for rapid localisation 77 A ae in case of an alarm either by installation of an Address Module NG58 1 in the detector base or by programming of the detector G with the Remote Program and Test Unit S300RPTU In case the detector is addressed by the NG58 1 the detector address and an assigned detector text are displayed directly at the fire detection control panel provided that the control panel supports these functions If the detector address has been specified by means of S300RPTU the detec tor number is not displayed on the control panel itself but on an additional Zonal Display Unit S300ZDU one of which must be integrated in every detector line KJ Features Individual detector identification with the Address Module NG58 1 or the Remote Pro gram and Test Unit S3OORPTU Function testing possible by test activation via the Remote Program and T
146. 14 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Module SZ58 3 287 310002 Stand by Battery 12V 18Ah 58 218022 ZLT Interface License ZLT SS Jer FT 169 BB072001 SAM 0720 01 0100 214100 214611 214158 214164 214109 214105 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 29 Fire Detection Control Panel BC216 1CE A1 The Fire Detection Control Panel BC216 1CE A1 is a modularly designed compact control panel in 19 slide in technology in the version for Austria for small and medium size fire de tection systems Functions specifications and cross references correspond to the Fire Detecti on Control Panel BC216 1CE INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language Approval FT 14 147 3 99 Austria VdS G201017 Fire Detection Control Panel BC216 1CE D1 The Fire Detection Control Panel BC216 1CE D1 is a modularly designed compact control panel in 19 slide in technology in the version for Germany for small and medium size fire detection systems Functions specifications and cross references correspond to the Fire De tection Control Panel BC216 1CE INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language Approval VdS G201017 Fire De
147. 140 Strobe WM 200 Red WMSTR WR PO1 249 356141 Strobe WM 200ISM Red WMSTR WR P02 Base Sounder amp Strobe IP44 White SDBW The Base SDBW serves for mounting of sounders detector base sounders and strobes Series WMS and IBS Due to the design of the base cable entry is possible from the back or from the side a The base contains an integrated spring contact for through con i nection of the loop if the signalling device has been removed a g Features pi Cable entry possible from the back or from the side in case of surface mount installation Multi wire terminals with secure screw fitting Through connection of loop line via spring contact Mechanical theft protection 169 BB072001 SAM 0720 01 0100 359044 359041 169 BB072001 SAM 0720 01 0100 Specifications Ambient temperature Protection class Dimensions x D Chapter 26 Accessories for Optical and Acoustic Devices 255 25 C to 70 C IP44 107 x 61 mm Additional depth of signalling devices 43mm Colour white Weight 110g Cross references Page Art Nr Name Type 247 355166 Sounder Strobe WB 200 White Red Multitone IBSST DR PO1 248 355167 Sounder Strobe WB 200ISM White Red Multitone IBSST DR P02 245 355164 Sounder WB 200 White Multitone IBSOU DD PO1 246 355165 Sounder WB 200ISM White Multitone IBSOU DD P02 Base Sounder amp Strobe IP65 White WDBW The Base WDBW serves for the indoor and outdoor wall mounting of sounders and str
148. 15 Serial Interface Module SIM06 1 52 214025 Serial Interface Module SIM216 1 Printer Cable for LX300 3m 25POL D SUB VERL Serial data cable for the connection of a Protocol Printer of type LX300 to a Fire Detection Control Panel Series BC216 BC016 or BCO6 The cable is configured with a 9 pole D SUB socket and a 25 pole D SUB connector Specifications Cable length 3m Cross references Page Art Nr Name Type 52 214231 Interface Adapter Module IAM216 1E 66 227008 Protocol Printer Dot Matrix LX300 4 210215 Serial Interface Module SIM06 1 52 214025 Serial Interface Module SIM216 1 Spare Paper for DPU414 1Roll MM112 402 N One roll of thermal paper for the Protocol Printer Thermal DPU414 30B Cross references Page Art Nr Name Type 65 227003 Protocol Printer Thermal DPU414 30B z am im 68 Chapter 8 Display and Operating Devices 8 Display and Operating Devices 250039 250030 250705 Remote Display and Operating Panel ABF216 1 INT 1 Remote panel used for operating and displaying all events of a Fire Detection Control Panel BCnet216 The remote panel provides the same operation convenience and the same infor mation LED displays and 4 line text display as any operatable sectional control panel The remote panel is installed in a wall mount cabinet The labels of display and operating elements as well as the displayed texts are in English language Features Connection as GSSnet member to the GS
149. 169 BB072001 SAM 0720 01 0100 120 Chapter 13 Acessories for Series 300 ECO1000 200 500 249044 automatic conventional detectors as well as manual call points special detectors and other contact activating devices Features Double digit indication of the detector number and text assignment on the display of a fire detection control panel Detector number setting from 0 to 63 Open collector output for triggering a remote indicator Alternatively applicable for individual detector addressing or identification of a detector group Specifications Current consumption at 24V 18mA active Ambient temperature 5 C to 50 C Dimensions L x W x H 32 x 19 x 5 mm without leads Weight 50g Cross references Page Art Nr Name Type 35 214020 Conventional Detector Interface GIF8 1 107 246140 Detector Base Conv 1000 SS ECO1000BR 1000 105 246008 Detector Base Conv 400 100 300 SS B401RM 79 246070 Detector Base FC600 FC600 BR 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 Detector Mounting Bracket MMW1 1 Metal bracket for the lateral mounting e g false floors elevator shafts shelves of an auto matic fire detector The bracket is provided with all necessary thread holes for easy mounting of a detector base Specifications Dimensions L x W x H 130 x 120 x 40 mm Weight 225g Cross references Page Art Nr Name Type
150. 169 BBO72001 SAM 0720 01 0100 244008 244005 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 123 Dimensions x H 103 x 42 mm Colour cream Weight 104g Approval 0832 CPD 0058 Cross references Page Art Nr Name Type 122 244009 Duct Detector 400 OM DH400P Duct Detector Housing Anal 500 200 SS DH500 Elegant plastic housing with detector base for application on the ADM loop using System Sensor 200 protocol but without detector for the surveillance of ventilation ducts The built in detector base is suitable for Series 500 smoke sensors The air escape pipe is integrated into the plastic housing The air inlet pipe is not provi ded with the duct detector and has to be selected according to the duct size see cross references Features Inspection window for optical identification of a detector activation Terminal for external remote indicator Approved for wind speeds of 2 5m s to 2 5m s Specifications Ambient temperature 10 C to 60 C Dimensions W x H x D 367 x 127 x 102 mm Colour grey Weight 1 9kg Cross references Page Art Nr Name Type 123 244005 Duct Detector Pipe 0 3 0 6M SS ST 1 5 124 244010 Duct Detector Pipe 0 6 1 2M SS ST 3 124 244011 Duct Detector Pipe 1 2 2 4M SS ST 5 124 244012 Duct Detector Pipe 2 4 3 7M SS ST 10 90 240013 Ionisation Smoke Detector Anal 200 SS 1251E 91 241050 Optical Laser Detector Anal 200 SS 7251 90 241010 Optical
151. 2 If stand by batteries 2 x 12V max 22Ah are installed a Multi Module MEA244 1 E can additionally be installed The operating and display board on the front side of the housing includes LED indicators for display of operating conditions and fault conditions and allows for the reset of the internal 169 BB072001 SAM 0720 01 0100 317031 317032 169 BB072001 SAM 0720 01 0100 Chapter 31 Batteries and Power Supply Devices 293 buzzer For the labelling of the LED indicators and the button insertable labelling strips in various languages are provided Cable entry can either be on the top side bottom side or back side of the housing Specifications Dimensions W x H x D 442 x 382 x 203 mm Colour light grey RAL 7035 Weight without installations approx 5 7kg Cross references Page Art Nr Name Type 291 317020 Power Supply Module NTM2402 1 292 317021 Power Supply Module NTM2408 1 Power Supply Housing NTG24 1 CE The Power Supply Housing NTG24 1 CE accommodates one Power Supply Module Series NTM The housing is made of powder coated steel sheets and can due to its intelligent de sign either be accommodated in a pivoting frame in 19 design or mounted on a mounting plate of a 19 cabinet In both cases the optional stand by batteries are accommodated in the interior of the 19 cabinet Besides the power supply module it provides space for the installation of one Relay Module RL58 1 or RL58 2 The oper
152. 2 A1 oo cece cnn eee eee ee eee e eee eee b een eee n eens 70 Remote Tableau SGS8 2 N EI 2 tun eek cee eds TS a es 70 Remote Tableau SG98 2 B Vierra tann E ga ey Sica eg Meas oe AN eG FON ee eee RS set 70 Remote Tableau SG582 CZ vasre ely Pee he Se es ey NG 71 Remote Display Panel SG482 ix serves ere Ate SNA SY pee eae Se ee es 71 Remote Indicator PAS 8 1 naust beate ak ad a ae 71 LED Display Tableau LAT288 1 2 0 00 cece eee cnet eee e nnn eee eenn eee eenenes 72 LED Display Tableau LAT288 1CE eronnonevevnnnanennanannerennnreneenennenernnnerevenenese 72 Remote Tableau Drive Unit PTU288 1 2 0 0 cece ccc nent teen eect nn eee eeaee 73 LED Connection Module LAM48 1 2 eect c ene c nee e eee tent eee tnen eee eeaes 74 LED Assembled Green 10pcs LED GN 10 o oo cece cece ete een n een e enn eens 74 LED Assembled Red 10pcs LED RT 10 2 0 0 cece cece cece nee c cnet nt nee e ee nn ene eeeeaee 75 LED Assembled Yellow 10pcs LED GE 10 svovvananavavvvnnanvenennnneverennvenenanasuerenner 75 VII vill 10 11 12 13 259013 Cord 2 Wire for LED Connection 1Opcs LED LEITUNG 10 2 0 0 2 cece e eee c cece cece eee ee 75 Conventional Detectors Series FC600 241070 242070 242071 Optical Smoke Detector Conv FC600 FC600 O svvrnnnnnvnennnanvenrnnnvvenenanuerenananueeen 76 Thermal ROR Detector Conv FC600 FC600 TDIFF 57 000 c ccc cc cece cece eee e nee n ences TT Thermal Max Detector Conv FC600
153. 2 LEDs Input for remote reset Programming via built in buttons Automatic shift between the two frequency ranges 434MHz and 868MHz 24 bi directional data channels Channels are checked for availability 230VAC 10 15 50Hz 12VA 10 to 30VDC Current consumption at power failure from 12V stand by battery Ambient temperature Dimensions W x H x D Colour Weight without batteries Approval Cross references Page max 110mA quiescent 120mA alarm 0 C to 60 C 300 x 390 x 140 mm white RAL 9018 35 100 146 208 8 7kg VdS G204104 Art Nr Name Type 214020 Conventional Detector Interface GIF8 1 249104 Conventional Zone Module Anal 200 SS M210E CZ 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 222013 Detector Reset Module MQZ1000 1 210110 Detector Zone Extension MGE8 1 210122 Fire and Evacuation Panel BC016 2 INT 1 210102 Fire Detection Control Panel BC016 1 INT1 210205 Fire Detection Control Panel BC06 1 INT1 210209 Fire Detection Control Panel BC06 2 INT 1 245023 Manual Call Point Blue RF M400DKMB AS 245022 Manual Call Point Red RF M400DKMR AS 241036 Optical Thermal Detector RF complete 2100RFT AS 210210 Zone Extension Board ZEB2 1 169 BB072001 SAM 0720 01 0100 241036 245022 169 BB072001 SAM 0720 01 0100 Chapter 19 RF Devices 189 Optical Thermal Detector RF complete 2100RFT AS The radio linked detector 2100RFT AS contains an optical sensing chamber on the principle
154. 204033 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 132 Chapter 14 Conventional Detectors Series 65 ORBIS 242031 Thermal Max Detector Conv ORBIS Apo HT 11002 Heat detector operating on the heat detection principle in addressable conventional technolo gy maximum heat detector classified as A2S maximum room height 6m in extra flat de sign suitable for indoor mounting For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire detection con trol panel provided that these functions are supported by the control panel If the detector is faulty the multicolour status LED on the detector will flash for approx 4 minutes in yellow colour after the detector line has been enabled Features Sealed electronics prevents false alarms caused by the environ
155. 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT 1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 103 249003 Isolator Module Anal 500 200 SS ISM 1 2 147 249029 Isolator Module Anal Apo ISM1 3 Fire Brigade Interface FWI2 1 By means of dry contacts the Fire Brigade Interface FWI2 1 allows for the connection of two independent transmitting devices for the direct interconnection to a designated alarm respon dent e g the fire brigade as well as the connection of a country specific fire brigade control unit to Fire Detection Control Panels Series BC216 Features Two independent relays with one dry changeover contact each Nine inputs and eight outputs freely parameterisable for the connection of a country specific fire brigade control unit and other devices All inputs and outputs are available on screw terminals Specifications Current consumption at 24V typ 4mA Switching power per contact 60V LA 30W Contact life 3x10 Ambient temperature 5 C to 50 C Dimensions L x W x H 132 x 74 x 10 mm Weight 70g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056
156. 216 1 H1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Hungarian language Approval EMILABS 85 2000 Fire Detection Control Panel BC216 1 NL1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Dutch language Approval VdS G201017 Fire Detection Control Panel BC216 1 SK1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Slovak language Approval EVPU 03323 101 1 2002 Fire Detection Control Panel BC216 1 HR1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Croatian language Fire Detection Control Panel BC216 1 RUS1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Russian language with cyrillic characters Approval B 01832 Fire Detection Control Panel BC216 1 SLO1 Function
157. 216 2 D1 is a modularly designed sectional control panel with display and operating field in the version for Germany for application in a Fire Detection Control Panel BCnet216 Functions specifications and cross references corre spond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and opera ting elements as well as the displayed and printer texts are in German language Approval VdS G201017 BCnet Sectional Control Panel OP BC216 2 B1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in French language Approval ANPI BFS DE 1096 2003 03 20 BCnet Sectional Control Panel OP BC216 2 CZ1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Czech language Using the optional interface Serial Interface Module SIM216 1 the connection to the Ra dom transmitting system can be realised Approval EZU 7 105034 00 00 BCnet Sectional Control Panel OP BC216 2 H1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Hungarian language Approval EMILABS 85 2000 169 BB07200
158. 22 1 2 cece ete e eee eee nee n ees 127 242025 Thermal ROR Detector Conv 65 Apo GD 55000 127 oo cece cece eee eee eee ete en ence eens 127 242026 Thermal ROR Detector Conv 65 Apo GD 55000 132 0 cee ec cece eee ete ene eee e ene 128 242027 Thermal Max Detector Conv 65 Apo GM 55000 137 1 0 0 cece ce cece cette eee ect eee eee eeees 129 241060 Optical Smoke Detector Conv ORBIS Apo OP 12001 1 2 2 cece cece eee teen ee cece een e es 129 241061 Optical Thermal Detector Conv ORBIS Apo OH 13001 cece cece cece eee ec eee eee e eee ee 130 242030 Thermal ROR Detector Conv ORBIS Apo HT 11001 0 cee cece eee cece eect teen eens 131 242031 Thermal Max Detector Conv ORBIS Apo HT 11002 1 0 0 cee cece cee eee ee 132 242032 Thermal ROR Detector Conv ORBIS Apo HT 11003 cece cece cee eee ee teen eens 132 242033 Thermal Max Detector Conv ORBIS Apo HT 11004 0 cece cence eee 133 242034 Thermal ROR Detector Conv ORBIS Apo HT 11005 cece eee c eee eee e eee e ee 134 242035 Thermal Max Detector Conv ORBIS Apo HT 11006 1 00 0 cece cece cence cee e eee e eee 134 Analogue Detectors and Modules Series XP95 DISCOVERY 240024 Ionisation Smoke Detector Anal XP95 Apo AI 55000 520 1 0 0 ce eee cece ccc eee e teen eens 136 241023 Optical Smoke Detector Anal XP95 Apo AO 55000 620 1 00 0 2c cece cece cence cece eee e ee ene 136 242023 Thermal Detector Anal XP95 Apo AW 55000 420 0 cece e
159. 224 Cleaner Tangit 0 121 REIN RAS O01 essuunnnvnnnannerennnanvernnnnenenananuenenananuerennusner 224 Cleaner Tangit I REIN RAS 2 2 22 ccc c cee cece cece conc nese ceecnerscsceeeecreeterereerereerens 224 169 BB072001 SAM 0720 01 0100 23 24 25 26 169 BB072001 SAM 0720 01 0100 Labels 249211 249240 249242 249011 249040 249042 249041 Detector Label Sheet 8pcs BME BEZ BOG ovsunnnnunennnnnnenrnnnunvennnnuenennnanuenennr 225 Detector Label Large Sheet 8pcs BME GR BOG ananunennnnnnenrnnnunvennnnnenennnanuenennr 225 Detector Label Small Sheet 20pcs BME KL BOG 0 cc cece cece eee cent eee e teen eee nene 226 Detector Label BME BEZ bocs sited ste Seki ghia tiene sede Ardea uren Bis SSH SET ee vert oe ae teed 226 Detector Label Large BME GR viss cian cadet E Selb ade estniels fee kr Soe knee aa es 227 Detector Label Small BME KL 0 cece cece cree eee tenn eet nee e cette nee e eben eeeeenes 227 Indicating Label FDCP BME BMZ ccc cece eee cece eee cee e eee tne e nee enen nee eees 227 Optical and Acoustic Devices conventional 355001 355014 355101 355102 356001 356650 356671 356672 351650 Sounder WM 12 24V Red Multitone 106dB MSIR 6 cece ccc cece ence nee nent enes 228 Sounder WM 12 24V White Multitone 106dB MS1IW 2 ccc cece ccc cence e cece en een ees 228 Sounder WM 12 24V Red Multitone 103dB EMA1224B4R oo ccc ccc ccc cnn ne
160. 230V AC RL58 2 222004 Relay Module 8 Fold 60VDC RL58 1 210215 Serial Interface Module SIM06 1 223026 Siren Connection Module SZ58 3 310001 Stand by Battery 12V 7Ah 210210 Zone Extension Board ZEB2 1 Fire Detection Control Panel BC06 2 D1 Functions specifications and cross references are equal to the Fire Detection Control Panel BC06 2 INT I but the manual comes in German language 4 Chapter I Fire Detection Control Panels Series BC06 210210 Zone Extension Board ZEB2 1 The Zone Extension Board ZEB2 1 extends the Fire Detection Control Panel Series BC06 by 2 detector zones in conventional technology Features 2 detector lines in conventional technology that can be indi vidually configured as detector zone for manual call points automatic fire detectors with or without alarm verification and fault detectors with or without self resetting property By means of the optional MCP Coding Module MCM1 1 alarms from automatic detec tors and manual call points which are both connected to the same detector line can be distinguished The type of line terminator end of line resistor or end of line capacitor can be selected separately for both zones of the Zone Extension Board ZEB2 1 via parameterisation at the control panel Monitoring of detector lines for wire breakage short circuit and earth fault The assignment of detector lines for activation of alarming devices can be set at the Fire Detection Control Panel BC06
161. 234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 118 249004 Surface Mounting Box for M500 SS SMB500 Conventional Zone Module Anal 200 SS M210E CZ Addressable module for the integration of conventional detectors into an ADM loop using Sy stem Sensor 200 protocol The address is set in a straightforward manner by means of two decadic rotary switches located on the module itself The integrated dual isolator can be acti vated or deactivated by choosing the appropriate terminals The module can be powered alternatively through the loop or by an external supply with 24VDC The conventional zone module provides a reset output for resetting special detectors ee M Attention Due to the capacitive line termination the conventional zone module must not be used for connecting intrinsically safe devices Features Status LED Surveillance of detector connecting line for wire breakage and short circuit 2 decadic rotary switches for setting the address from 01 to 99 Installation alternatively in module box or by means of mounting pedestal Specifications Operating voltage 15 to 30VDC Current consumption on loop typ 500uA quiescent external voltage supply typ 1 5mA quiescent loop supplied Line termination typ 47uF Capacitance line incl detectors max 2 2uF Current consumption of detectors max 3mA Ambient temperature 20 C to 60 C 169 BB072001 SAM 0720 01 0100 Chap
162. 240 356020 Strobe FB XP95 White Red 55000 877 Base Sounder amp Strobe IP24 White LPBW The Base LPBW serves for mounting of sounders detector base sounders and strobes Series WMS and IBS Due to the design the base is covered by the signalling device and therefore cannot be seen nor is the height of devices increased Kg A mounting plate is available for surface cabling of the base ea Va J The base contains an integrated spring contact for through con 4 Ke nection of the loop if the signalling device has been removed Features md Cable entry from back side Multi wire terminals with secure screw fitting Through connection of loop line via spring contact Mechanical theft protection Specifications Ambient temperature 25 C to 70 C Protection class IP24 Dimensions x D 107 x 21 mm Colour white Weight 48g Cross references Page Art Nr Name Type 256 359049 Mounting Plate for Sounder 200 Spcs DBSPD 5 247 355166 Sounder Strobe WB 200 White Red Multitone IBSST DR PO1 248 355167 Sounder Strobe WB 200ISM White Red Multitone IBSST DR P02 243 355162 Sounder Strobe WM 200 Red Multitone 100dB WMSST RR POI 244 355163 Sounder Strobe WM 200ISM Red Multitone 100dB WMSST RR P02 245 355164 Sounder WB 200 White Multitone IBSOU DD PO1 246 355165 Sounder WB 200ISM White Multitone IBSOU DD P02 242 355160 Sounder WM 200 Red Multitone 100dB WMSOU RR PO1 242 355161 Sounder WM 200ISM Red Multitone 100dB WMSOU RR P02 249 356
163. 240015 240023 245680 241025 241024 241090 242036 242015 249041 265752 265753 265757 244638 214231 240013 240026 240024 240027 246013 246036 249003 249029 249070 268012 219006 227009 218021 259011 259010 259012 252013 214024 214030 214032 214036 252010 252011 359021 359020 359005 359006 249090 329013 244637 310021 310020 223030 214021 169 BB072001 SAM 0720 01 0100 H Housing 19 36HU GEH19 STAND ooavvvnvvnvvnnr 46 Housing IP67 for Strobe FB XP95 29600 318 253 I IS Detector Base Anal Apo ASEX 45681 215 179 IS Detector Base Conv YBN R 4IS 2 2 0 eee 176 IS Detector Base Conv 60 Apo GSEX 45681 207 176 IS Ionisation Smoke Detector Anal XP95 Apo ATEX 55000 540 2 2 0 e eee eee 177 IS Ionisation Smoke Detector Conv 100 SS 1151EIS 174 IS Ionisation Smoke Detector Conv 60 Apo GIEX 55000 212 sara esta owner ones 175 IS Manual Call Point Red Conv DC21 IS Optical Smoke Detector Anal 200 SS 2251EIS 181 IS Optical Smoke Detector Anal XP95 Apo AOEX 55000 640 2 0 cece cece cece eee eee eens IS Optical Smoke Detector Conv SLR E IS IS Thermal Detector Anal XP95 Apo AWEX 55000 440 1 0 0 cee cc cece e eee teens 178 IS Thermal ROR Detector Conv 400 SS 5451EIS 174 Indicating Label FDCP BME BMZ Inner Door for FSK700 2 A ITA 2 Inner Door for FSK700 2 DBUK ITB 2 Inner Door for FSK700 2 DBUM ITF 2
164. 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 169 BB072001 SAM 0720 01 0100 5 Chapter 5 Interfaces 51 Interfaces 214033 214027 169 BB072001 SAM 0720 01 0100 Network Interface Module NIF5 1M The Network Interface Module NIF5 1M allows for the connection of BCnet sectional con trol panels of a Fire Detection Control Panel BCnet216 or other GSSnet members to the Glo bal Security System network GSSnet it is installed in all BCnet sectional control panels by default The componentry is required to upgrade a 19 Compact Control Panel BC216 1CE to a BCnet sectional control panel Note the Network Interface Module NIF5 1M can only be operated with a central processing board ZTB216 2 The type of the board is printed on a label Features Galvanically isolated RS485 interface sisizisie ise see ess Specifications Current consumption at 24V typ 25mA Cab
165. 250g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 Thermal Max Detector IP67 Conv SWM 1KL 100 The maximum heat detector SWM 1KL 100 uses a bimetal element as thermal sensor If the alarm temperature is reached the bimetal contact is closed Addressable conventional techno logy is used for alarm transmission to the fire detection control panel The activated condition of the detector is indicated by an LED The detector can be con 0 AS nected to an ADM loop by using a conventional zone module K The detector is integrated in an aluminium die cast housing that e is suitable for application in moist areas e g loading ramps VI T Features D Individual detector addressing by connecting an optional ad dress module Alarm LED on detector housing Output for external remote indicator Metal PG screws for waterproof insertion of the connecting cables Specifications O
166. 2A Connection of external devices typ 0 8A system specific Ambient temperature 5 C to 50 C Relative humidity max 90 no condensation Dimensions L x W x H 230 x 150 x 52 mm Weight approx 0 5kg Approval VdS pending Cross references Page Art Nr Name Type 292 317030 Power Supply Housing NTG24 1 293 317031 Power Supply Housing NTG24 1 CE 289 310004 Stand by Battery 12V 45Ah ier mee E 292 Chapter 31 Batteries and Power Supply Devices 317021 317030 Power Supply Module NTM2408 1 The Power Supply Module NTM2408 1 is an autonomous componentry for the supply of devices which require a failure safe power supply with a nominal voltage of 24VDC The module complies with EN 544 2006 In case of mains voltage failure the module continues to provide current from optionally connected stand by batteries The mains vol tage is transformed by the integrated switche d mode power supply to the current limited and short circuit protected output voltage that is required for connected loads and optio nal stand by batteries The maximum load current varies depending on the battery capacity For a theoretical charging time of 24 hours stand by batteries with a maximum capacity of 130Ah can be charged Battery monitoring includes periodic measurements of the final charge voltage and of the in ternal resistance of the batteries according to EN 54 4 2006 The optional earth leakage mo nitoring of the module can be activated by insertin
167. 31 Duct Detector Housing Anal Apo LG 53546 016 0 cece cece cece eee ec ee eee e cette ee ee ene 154 246032 Detector Heater Conv 60 65 Apo MH60 1 0 cece ccc cence cece eee tne e eee e nn en eens 154 246033 Detector Heater Anal Apo MH95 1 avvsnuvvnnnnennvnnnnernnvnnnennnnenanennrenanennnnennnen 155 249028 Address Module Conv Apo NG60 1 oo eee eect tenet eee e ee tet eect ee nnn ee eeeee 155 249039 Address Cards 100pcs Anal XP95 Disc Apo CK 38531 771 10 0 cece cece e ec ee teen teen ence es 156 Manual Call Points 245302 Manual Call Point EN 54 Red Conv HFM 3 11 02 0 0 oe c eect tenet et een eee eee 157 245356 Manual Call Point Red Conv HM 3 11 01 02 20 cece cece teen eect nee e tenn eee es 157 245352 Manual Call Point Blue Conv HM 5 11 02 02 1 0 c eee cece nee eten een e tenes 158 245417 Manual Call Point Blue Conv HM 5 11 18 02 1 0 0 cece cece ccc n eee ee een en cent eeneeee 159 245355 Manual Call Point Yellow Conv HM 1 11 05 02 1 0 0 cee c cece cence teen ee nenn eee eene 159 245362 Manual Call Point Red Anal SS HFM 3 22 02 12 0 ccc cece cence cee ee tence eee nn eee ees 160 245372 Manual Call Point Blue Anal SS HM 5 22 02 02 0 0 cece cece cee e eect ene en nen e es 161 245415 Manual Call Point Blue Anal SS HM 5 22 18 02 0 0 c cece eee ee tte eet en nen e es 161 245392 Manual Call Point Yellow Anal SS HM 1 22 05 02 0 0 0 cece eee cece eect tence een en eee e ee 162 245389 Manua
168. 351E 83 Thermal ROR Detector Conv 65 Apo GD 55000 122 127 Thermal ROR Detector Conv 65 Apo GD 55000 127 127 Thermal ROR Detector Conv 65 Apo GD 55000 132 128 Thermal ROR Detector Conv FC600 FC600 TDIFF S7 1 2 2 0 cee e eee ee eee eee 77 Thermal ROR Detector Conv ORBIS Apo HT 1 1001 131 Thermal ROR Detector Conv ORBIS Apo HT 11003 132 Thermal ROR Detector Conv ORBIS Apo HT 11005 134 Thermal ROR Detector RF 55000 480 185 Three way Ball Valve 3MKH 02 ee eee 222 Transparent Door 19 36HU SIT19 STAND 46 Trapezoid Steel Bracket TBH800 1 121 U Unblocking Element F0345 0 eee e eee eee 265 Unblocking Element for Half Cylinder FSE MPI 265 V Voltage Stabiliser 24VDC STAB24 1 294 W Wet Base Shroud SS WBI 000 eee eee 116 Z ZLT Interface License ZLT SS 00 00005 58 Zonal Display Unit Conv 300 SS S300ZDU 112 Zone Extension Board ZEB2 1 0 ee eee 4 307 308 Product List 169 BB072001 SAM 0720 01 0100 309 Last but not least 169 BB072001 SAM 0720 01 0100 We hope that this product survey enabled an easy search for and selection of articles suitable for you If you are in need of further special documentation or if you are interested in special products not contained in the Product Guide please do not hesitate to contact us We a
169. 359022 Mounting Plate for Sounder WB XP95 38531 810 Sounder Strobe WB XP95ISM White Clear Slow Whoop 45681 332 The addressable sounder with integrated strobe 45681 332 is installed in a round white pla stic housing The unit is actuated using Apollo Discovery protocol and powered via the ADM loop The sounder is always activated together with the strobe The integrated detector base is suitable for accommodation of fire detectors Series XP95 and i ea LT Sigge Discovery The unit is prepared for indoor surface mounting p A dual isolator is integrated in the componentry At short circuit i it maintains the function of ADM elements that are not affected by the short circuit Depending on the parameter setup of the Fire Detection Control Panel Series BC216 and the system condition the panel can activate the sounder with tone A or B The address of the sounder and strobe as well as the sound level are set via the DIL switch Features Tone A Slow Whoop tone NEN 2575 500 1200Hz over 3 5s 1s pause Tone B continuous tone 870Hz Sound level adjustable in two steps via DIL switch Simple address setting of inserted detector by code card in detector base Low power consumption Integrated dual isolator Specifications Operating voltage Current consumption from loop Sound level Flash frequency Ambient temperature Protection class Relative humidity Dimensions x H Long lifespan of str
170. 388 00 Magnetic Lock Clamp 4900N 1390 2 06 Magnetic Lock Clamp LED 4900N 1392 Manual Call Point Anal XP95 Apo 55000 905 Manual Call Point Blue Anal Apo HM 5 32 02 02 Manual Call Point Blue Anal Apo HM 5 32 18 02 Manual Call Point Blue Anal SS HM 5 22 02 02 Manual Call Point Blue Anal SS HM 5 22 18 02 Manual Call Point Blue Conv HM 5 11 02 02 Manual Call Point Blue Conv HM 5 11 18 02 Manual Call Point Blue RF HM 152 27D Manual Call Point Blue RF M400DKMB AS Manual Call Point EN 54 Red Anal Apo HEM 3 32 02 s ers reren genene pels ois Manual Call Point EN 54 Red Conv HFM 3 11 02 Manual Call Point Grey Anal SS HM 7 22 03 02 Manual Call Point Red 200 Flexi MCPSA RPO7FF Manual Call Point Red 200 Glass MCP5A RPO7FG Manual Call Point Red 200 ISM Flexi MCPSA RPO8FF Manual Call Point Red 200 ISM Glass MCPSA RPO8FG 0 2 0 eee eee eee eee Manual Call Point Red Anal SS HFM 3 22 02 Manual Call Point Red Conv HM 3 11 01 02 Manual Call Point Red RF HFM 153 27D Manual Call Point Red RF M400DKMR AS Manual Call Point Yellow Anal Apo HM 1 32 05 02 Manual Call Point Yellow Anal SS HM 1 22 05 02 Manual Call Point Yellow Conv HM 1 11 05 02 Module 1xSurv In 1xRel Out 230 Apo 55000 875 Module 1xSurv In 1xRel Out Apo 55000 847 Module 2xSurv In 1xRel Out Anal 200 SS M221E Module 3xSurv In 3xRel Out Apo 55000
171. 40 x 165 mm Material powder coated steel sheet 1 5mm Colour grey white RAL 9002 Weight approx 3 1kg Cross references Page Art Nr Name Type 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT1 12 214008 Fire Detection Control Panel BC216 1 INT1 16 214308 Fire Detection Control Panel BC216 1S INT1 212027 Cabinet 19 18HU GEH19 18 169 BBO72001 SAM 19 wall mount cabinet in robust sheet steel design with pivoting frame of 18 height units for housing equipment in 19 design e g a Fire Detection Control Panel Series BC216 in slide in technology Features Pivoting frame of 18 height units and an aperture angle of 105 Integrated back wall 19 grid for additional system components Removable flange covers for cable entry on top and bottom sides of the cabinet Mounting rails for additional components 46 Chapter 3 Fire Detection Control Panels Series BC216 212028 212032 Specifications Dimensions W x H x D 620 x 920 x 350 mm Colour grey white RAL 9002 Weight approx 30kg Housing 19 36HU GEH19 STAND 19 housing in robust steel sheet design with integrated 36 height units pivoting frame The housing is suitable for installing devices in 19 design e g a Fire Detection Control Panel Series BC216 gt r Features Pivoting frame with 36 height units and an aperture angle of 120 Side walls back wall and top cover r
172. 42042 Thermal Max Detector Conv 300 SS 5351TE 83 242040 Thermal ROR Detector Conv 300 SS 5351E Remote Test Unit Conv 300 1000 SS ECO 1000RTU Hand held laser test unit for easy test activation of System Sensor Series 300 and ECO 1000 detectors Features rome Range of several metres Simple handling due to visible laser beam Specifications Operating voltage 6VDC battery type V11GA Dimensions L x W x H 82 x 30 x 15 mm Weight 30g Cross references Page Art Nr Name Type 114 249212 Battery for ECO1000RTU 6V V11GA 86 241046 Optical Thermal Detector Conv 1000 SS ECO1002 82 241041 Optical Thermal Detector Conv 300 SS 2351TEM 85 241045 Optical Smoke Detector Conv 1000 SS ECO1003 81 241040 Optical Smoke Detector Conv 300 SS 2351E z am kand 114 Chapter 13 Acessories for Series 300 ECO1000 200 500 249212 249214 246006 87 242047 Thermal Max Detector Conv 1000 SS ECO1004T 88 242046 Thermal Max Detector Conv 1000 SS ECO 1005T 84 242041 Thermal Max Detector Conv 300 SS 4351E 84 242042 Thermal Max Detector Conv 300 SS 5351TE 87 242045 Thermal ROR Detector Conv 1000 SS ECO1005 83 242040 Thermal ROR Detector Conv 300 SS 5351E Battery for ECO1000RTU 6V V11GA The 6V battery is used for supply of the Remote Test Unit ECO1000RTU ATTENTION the remote test unit exists in two different designs which require diffe rent types of batteries Please pay attention to the type and dimensions of the battery when yo
173. 44116 244115 244234 329016 317100 317101 317001 317102 317030 317031 317032 317020 317021 249014 237700 227007 227010 219010 249631 249640 249634 249633 249636 249650 228007 228005 227008 227003 O Optical Battery Smoke Detector FL10022H 209 Optical Filtrex Smoke Detector Anal 500 SS FTX P1 94 Optical Laser Detector Anal 200 SS 7251 Optical Smoke Detector Anal 200 SS ND2251EM 90 Optical Smoke Detector Anal Disc Apo AO 58000 600 0 cece cece cece eee eee tees 139 Optical Smoke Detector Anal XP95 Apo A0 55000 620 ac ceciscreeis ener peker kvensk kna ke 136 Optical Smoke Detector Conv 100 SS 2151E LC 122 Optical Smoke Detector Conv 1000 SS ECO1003 85 Optical Smoke Detector Conv 300 SS 2351E 81 Optical Smoke Detector Conv 65 Apo GO 55000 317 126 Optical Smoke Detector Conv FC600 FC600 0 76 Optical Smoke Detector Conv ORBIS Apo OP 12001 129 Optical Smoke Detector RF 55000 680 185 Optical Thermal Detector Anal 200 SS 2251TEM 92 Optical Thermal Detector Anal Disc Apo AMS 58000 700 2 0 0 s sce ee eect eee eee teens 141 Optical Thermal Detector Anal XP95 Apo AMS 55000 885 00 e eee c cece teen eee intine 138 Optical Thermal Detector Conv 1000 SS ECO1002 86 Optical Thermal Detector Conv 300 SS 2351TEM 82 Optical Thermal Detector Conv ORBIS Apo OHRTS OOD end heksene EEE 130 Optical Thermal Detect
174. 48 1 contains 48 freely parameterisable double LEDs red yel low for the individual display of events of the detector zones actuations transmitting devi ces or alarming devices at Fire Detection Control Panels Series BC216 and of events of the flooding zones and extinguishing systems at the Extinguishing Control Panel Series LC216 The double LEDs are arranged in two rows each with 24 pairs In addition the LED Display Field can be installed into an LED Display Tableau LAT288 that serves as a freely programmable display for the events of a Fire Detection Control Panel Series BC016 or BC216 as well as an Extinguishing Control Panel Series LC216 Features 48 double LEDs left hand side red right hand side yellow freely parameterisable accor ding to individual events Display of activation as well as deactivation or fault condition of the parameterised event Designation labels provide for individual marking of every double LED Specifications Current consumption at 24V typ 2mA no active LED 0 25mA per LED Ambient temperature 5 C to 50 C Dimensions L x W x H 176 x 120 x 15 mm Weight 60g Cross references Page Art Nr Name Type 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 33 214208 Display and Operating Front Panel ABP216 1E INT1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 72 252010 L
175. 50 C VdS environmental class 2 grey white RAL 9002 215 x 325 x 85 mm 2 3kg VdS G199801 VSO 990629 11 Austrian Telecommunication Authority 105340ZB9705 Art Nr Name Type 285 284 285 283 287 285 329014 Dialogue Module DPM805 1 329013 Line Monitoring Module TUM805 1 329016 Plug in Power Supply STN805 1 329012 Relay Module RL404 1 310010 Stand by Battery 6V 1 2Ah 329015 Telephone Speaker Set TEL805 1 Automatic Telephone Dialling Device TWG805 1D The Automatic Telephone Dialling Device TWG805 1D serves for transmission of alarm messages and fault messages and for the reception of switching commands in public telepho ne networks Alarm messages and fault messages are transmitted as voice messages to tele phone connections mobile phones or voice mail boxes Switching commands are transmitted by the caller via DTMF tones to the actuation output of the telephone dialling device If a dialogue module is used the TWG805 1 can be remotely operated from every telephone connection with an authorisation code In case of an alarm activation the reply of the called participant is recorded Thereby the receipt of alarm information is documented In the basic version the Telephone Dialling Device TWG805 1D is equipped with 4 control inputs and one actuation output The control lines react to changes in resistance and can be programmed for connection of normally open and closed contacts The actuation output is designed a
176. 588 Module Carrier 19 3HU MPL17 3 Monitor Module 10xSurv In Anal 200 SS IM 10 Monitor Module 1xSurv In Anal 200 SS M210E Monitor Module 2xSurv In Anal 200 SS M220E Monitor Module Interrupt Anal XP95 Apo UMI 55000 832 Monitor Module Anal 500 SS MS03ME Monitor Module Anal XP95 Apo UMM 55000 833 Monitor Module Anal XP95 Apo UMS 55000 841 Monitor Module Box Anal 500 SS UMB500 1 Mounting Base TC358 Mounting Bracket BW216 1 00 c eee eee eee eee Mounting Clip 3040 LSK 0 cece eee eee Mounting Frame 19 6HU RAHMEN Mounting Frame 19 6HU RAHMEN FBF Mounting Kit 19 3HU EW8C E Mounting Plate for Sounder 200 Spcs DBSPD S Mounting Plate for Sounder WB XP95 38531 810 Multi Module Mounting Rail MEA244 1 TR Multi Module Panel Mounting MEA244 1 E Multi Mount Kit 6500 BEAMMMK Multimode Fibre Gateway BCnet216 LWL MM 2 N Network Cable NWK2 1 Network Interface Module NIF5 1M 55 Network Redundant Alarm Converter NNUS 1 305 164 157 163 171 170 172 170 160 157 185 189 166 162 159 145 143 144 42 97 96 142 142 306 Product List 241603 241019 241050 241010 241027 241023 241038 241045 241040 241026 241070 241060 241029 241020 241022 241030 241046 241041 241061 241036 241051 218008 244125 244118 244114 244112 244113 244119 2
177. 6 3LG 0 0 cc cece ccc cece cece nee e ences 26 Fire Detection Control Panel BC216 1CE INT1 20 0 0 c ccc cece cece ccc cen n eee ene een eens 27 Fire Detection Control Panel BC216 1CE A1 oo ccc cence cece nee eee een en teens 29 Fire Detection Control Panel BC216 I1CE D1 oo ccc ccc cence cece entre teen teens 29 Fire Detection Control Panel BC216 1CE NL1 0 ccc ccc ccc cence cece ence en enens 29 Fire Detection Control Panel BC216 1CE CZ1 oo ccc ccc ccc cence eect ne an en enees 29 Fire Detection Control Panel BC216 1CE H1 oo occ ccc ccc nec e eee e een en eeens 29 BCnet Sectional Control Panel No Op BC216 3CE 2 0 0 eee eee eect ee eee e ene e eee nene 29 BCnet Sectional Control Panel OP BC216 2EPS 00 ccc nce n ence nen e eee een ens 30 Fire Detection Control Panel Module PS BCM216 3EPS 0 0 c cece cece cence ener e nen enees 31 Fire Detection Control Panel Module BCM216 3E oo ccc ccc cece cc cence ence ene e en en teens 32 Fire Detection Control Panel Module LG BCM216 3ELG 00 c ccc cece cece eee nen e ences 32 Display and Operating Front Panel ABP216 1E INT1 2 0 0 cece eee e cece cence eee e eee 33 Display and Operating Front Panel ABP216 1E Al 1 0 0 eee eee eee ee ene e teens 34 Display and Operating Front Panel ABP216 1E D1 2 0 0 0 eee cee ccc eee ete ene eee e ene 34 Display and Operating Front Panel ABP216 1E NL1 0 e nec ee ene e eee eeee 34 Conventional Detector Inter
178. 6 Manual Call Point Yellow Anal Apo HM 1 32 05 02 162 245392 Manual Call Point Yellow Anal SS HM 1 22 05 02 159 245355 Manual Call Point Yellow Conv HM 1 11 05 02 169 BB072001 SAM 0720 01 0100 219006 2171612 2171620 2171621 2171619 169 BB072001 SAM 0720 01 0100 Chapter 17 Manual Call Points 169 Key for Manual Call Point SCH HFM HM Standard key for opening doors of various components of fire alarm technology e g manual call points Fire Brigade Control Units FBF58 1 FBF58 2 Fire Brigade Key Safe Adapters AD800 1 and Fire Brigade Map Boxes FWP 1 gt Replacement Glass for Manual Call Point ET SCH HFM Standardised replacement glass for manual call points without marking Specifications Dimensions W x H x D 80 x 80 x 0 7 mm Cross references Page Art Nr Name Type 164 245402 Manual Call Point EN 54 Red Anal Apo HFM 3 32 02 157 245302 Manual Call Point EN 54 Red Conv HFM 3 11 02 163 245389 Manual Call Point Grey Anal SS HM 7 22 03 02 160 245362 Manual Call Point Red Anal SS HFM 3 22 02 Replacement Glass for Manual Call Point Red ET SCH HM RT Standardised replacement glass for manual call points with red marking Specifications Dimensions W x H x D 80 x 80 x 0 7 mm Cross references Page Art Nr Name Type 157 245356 Manual Call Point Red Conv HM 3 11 01 02 Replacement Glass for Manual Call Point Blue ET SCH HM BL Standardised replacement glass for manual call po
179. 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Sound level adjustable in 3 steps low medium high Long lifespan of strobe due to the use of LEDs 244 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 355163 Low power consumption 2 decadic rotary switches for setting the address from 01 to 99 Different base versions available Specifications Operating voltage Current consumption from loop Sound level Examples at 24V Continuous tone 660Hz DIN tone 1200 500Hz Slow Whoop tone 500 1200Hz supply through the loop voltage typ 450uA sounder and strobe off max 4 7mA low sound level max 6 6mA medium sound level max 9 3mA high sound level typ 82dB A 1m distance low sound level typ 90dB A 1m distance medium sound level typ 96dB A 1m distance high sound level max 100dB A 1m distance high sound level typ 6 8mA at 98dB A 1m distance typ 8 8mA at 100dB A 1m distance typ 9 3mA at 96dB A 1m distance 1Hz 25 C to 70 C 10 96 no condensation 115 x 68 mm incl Base LPBW Flash frequency Ambient temperature Relative Humidity Dimensions x D Colour Weight Approval Cross references Page 254 255 256 26 32 35 red 204g VdS G206072 Art Nr Name Type 359040 Base Sounder amp Strobe IP24 White LPBW 359041 Base Sounder amp Strobe IP44 Red SDBR 359042 Base Sounder amp Strobe IP65 Red WDBR 214034 BCnet Section
180. 720 01 0100 214056 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 23 ADM actuations on the ADM loop by means of actuation elements as well as alarm si rens which are freely parameterisable and are controlled individually by the control panel ADM address setting is carried through separately at each loop element ADM flexibility provides for the possibility to connect conventional detectors and special detectors via a Conventional Detector Module Specifications See individual description of the BCnet sectional control panel and Fire Detection Control Pa nel Module Approvals P BST FT 14 147 3 99 Austria VdS G201017 VKF 13400 2007 EMILABS 85 2000 ANPI BFS DE 1096 2003 03 20 EZU 7 105034 00 00 EVPU 03323 101 1 2002 ABA S 059 01 UNIIPO B 01832 FEL 02012 C 709P3 CNBOP 2238 2006 BCnet Sectional Control Panel OP BC216 2 INT1 The BCnet Sectional Control Panel BC216 2 INT1 with its modular design and integrated display and operating field is suitable for use in a Fire Detection Control Panel BCnet216 Fi re fault and status detectors as well as control elements and alarming devices can be con nected to up to 2 ADM loops in analogue technology or to a maximum of 16 detector zones in addressable conventional technology or to a combination thereof depending on the optional modules used The Sectional Control Panel is installed in a wall mount case made of powder co
181. 74 Control Module Anal XP95 Apo SMK 55000 849 arnvvvnennnnnvevrnnnrnerennnvevennnanveeenr 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 oo eee cece eee eee eee teens 146 249029 Isolator Module Anal Apo ISM1 3 2 0 0 0c ec ccc cee cece cee cee e tee een ence eee n eens 147 249070 Isolator Module Board Apo 43781 552 2 0 cece cece cence eee e teen e eee e nnn n eect nen e eens 148 Acessories for Series 65 ORBIS XP95 DISCOVERY 246021 Detector Base Conv 60 65 Apo GSA 45681 200 0 cece eee cence cc ee nee e ee enne ee eeene 149 246035 Detector Base Conv 60 65 Apo 45681 251 navrnunnnnnnvnennnannenennnanvenrnnvevennnaauevennnr 149 246042 Detector Base Conv ORBIS Apo MB 00001 2 0 cee cee cee tee ete eens 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 2 0 00 ccc cee cence eee ees 150 246025 Detector Base Anal Apo ASA 45681 210 aauvvavanavnvenennnnevennnnuvernnnrevenrnrnevennner 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 0 cece cece eee cette eee e teen ence ee 151 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 1 0 0 cece cece e cence tte eee e ees 152 246034 Detector Base Anal Apo 45681 250 1 0 ieee cece nec c cnet ene e nett bene ee een nee e es 153 246029 Conduit Box Apo SZA 45681 204 00 eee cnn cece ee ett n nett et nn neces nee e eens 153 246030 Backplate Apo SZPL 45681 233 2 0 00 cece cee cence cece eee eect nent tte n eee nnen eee es 153 2460
182. 8 Surface Mounting Kit SS SMK400 255 115 T Telephone Speaker Set TEL805 1 00005 285 Telescopic Pole SOLO100 0 cece eee eee 298 Terminal Converter Module 16 Fold SUB58 2 62 Terminal Set CE AKS216 1 Terminal Set E AKS216 2 Termination Connector LWM AV22 11800 102 204 Test Gas Can SOLOA3 001 0 eee eee eee eee ee 297 Test Module 100 200 SS MOD400R 5 297 Test Set Conv S60 Apo TS 53832 020 0 298 Thermal Detector Anal 200 SS 5251EM 94 Thermal Detector Anal Disc Apo AD 58000 400 140 Thermal Detector Anal XP95 Apo AW 55000 420 137 Thermal Max Detector IP67 Conv SWM 1KL 100 193 Thermal Max Detector IP67 Conv SWM 1KL 140 194 Thermal Max Detector IP67 Conv SWM 1KL 57 192 Thermal Max Detector IP67 Conv SWM 1KL 80 192 Thermal Max Detector Conv 1000 SS ECO1004T 87 Thermal Max Detector Conv 1000 SS ECO1005T 88 Thermal Max Detector Conv 300 SS 4351E 84 Thermal Max Detector Conv 300 SS 5351TE 84 Thermal Max Detector Conv 65 Apo GM 55000 137 129 Thermal Max Detector Conv FC600 FC600 TMAX 78 seitei tineia weien eee eee 77 Thermal Max Detector Conv ORBIS Apo HT 11002 132 Thermal Max Detector Conv ORBIS Apo HT 11004 133 Thermal Max Detector Conv ORBIS Apo HT 11006 134 Thermal ROR Detector Conv 1000 SS ECO1005 87 Thermal ROR Detector Conv 300 SS 5
183. 81 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 Optical Smoke Detector Anal Disc Apo AO 58000 600 Addressable smoke detector operating on the light scatter principle for application on the ADM loop using Apollo Discovery protocol with an optical sensing chamber and of extra flat design suitable for indoor mounting 3 Intelligent evaluation algorithms in the respective LST fire de A tection control panels compensate for the impact of contaminati F on of the optical sensing system Thereby the response sensitivity of the detector is kept constant for a long time thus constituting another effective measure for preventing false alarms What is more the response sensitivity of the detector can be adju sted via the fire detection control panel to adapt the detector optimally to the application environment Features Permanent evaluation of environmental conditions Constant sensitivity Response sensitivity can be set in 5 steps via the Fire Detection Control Panel Series BC216 1 4 to 2 8 m Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Display of activated condition via 2 LED indicators that are visible from all angles Output for external remote indicator Mechanical thef
184. 95 or Discovery or a loop strobe 100 pieces of unprogrammed address card are included in the packing unit Note an address card is included in each detector base Features No electronics contained Easy programming Easy to replace Specifications Address range Dimensions L x W x H Colour Weight per card 01 to 126 55 x 20 x 4 mm white 2g 169 BB072001 SAM 0720 01 0100 Chapter 17 Manual Call Points 157 1 T Manual Call Points 245302 Manual Call Point EN 54 Red Conv HFM 3 11 02 Universal manual call point according to EN 54 11 B in an elegant red aluminium die cast housing designed for application in addressable conventional technology Features Robust aluminium die cast housing with a door aperture angle of more than 180 Operating instructions by means of symbols European standard Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Individual detector addressing by connecting an optional address module Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 Specifications Operating voltage supplied through detector line voltage Ambient temperature 20 C to 60 C continuous operation 25 C to 70 C max 12 hours Protection class IP43 Dimensions W x H x D 125 x 125 x 34 mm Colour flame red R
185. 99 Installation alternatively in module box or by means of mounting pedestal Specifications Operating voltage supplied through loop voltage Current consumption approx 510uA quiescent Line termination 56kOhm Alarm threshold typ 22kOhm Ambient temperature 20 C to 60 C Dimensions L x W x H 93 x 94 x 23 mm Colour cream Weight 110g Approval VdS G202140 Cross references Page Art Nr Name Type 117 249110 Base for Carrier Rail for M200 SS M200E DIN 116 249109 Base for Mounting Plate for M200 SS M200E PMB 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 117 249108 Surface Mounting Box for M200 SS M200SMB Monitor Module 2xSurv In Anal 200 SS M220E Addressable module for the line monitored integration of 2 contact detectors e g manual call points sprinkler system contacts supervising contacts into the bi directional communi cation on the ADM loop using System Sensor 200 protocol The integrated dual isolator can be activated or deactivated by choosing the appropriate terminals Features Status LED for every input gt T Surveillance of terminal connecting lines for wire bre akage and short circuit emere 2 decadic rotary switches for setting the address from 01 to 99 Installation alternatively in module box or by means of mounting pedestal Specifications Operating voltage supplied through l
186. A ESBRS 251 Battery Bracket BK216 1 00 cece eee eee eee 41 Battery Bracket BK216 1CE 0 cece eee e eee 41 317033 249215 227005 249214 249212 244020 244610 244022 244021 244023 243100 212027 244240 244235 244131 244127 244236 246029 260002 249106 249105 249103 249116 249074 249073 214230 223009 214020 249104 249045 249075 259013 214601 246017 265019 214129 246012 246071 246002 246015 246034 246025 246140 246008 246035 246021 246042 246040 246070 246018 249027 246033 246032 249011 249040 249240 Product List Battery Bracket BK24 1 2 02 00 eee cee eee eee eee eee 294 Battery for 2100RFT AS CR123 0e eee 190 Battery for DPU414 BT4005 eee e eee ee 66 Battery for ECO1000RTU 6V 476A 2 055 114 Battery for ECO1000RTU 6V VI IGA 114 Beam Smoke Detector Anal SS 6500 05 198 Beam Smoke Detector Conv FR2000 45 201 Beam Smoke Detector Conv SS 6500R 196 Beam Smoke Detector Test Anal SS 6500S 199 Beam Smoke Detector Test Conv SS 6500RS 197 C CO Detector Anal Disc Apo AC 58000 300 141 Cabinet 19 18HU GEH19 18 20 22 0 cece eee cece 45 Ceiling Duct complete DDF KOMPL 222 Check Valve Spring loaded R25 RVFED 25 222 Cleaner Tangit 0 12I REIN RAS 01 0 0005 224 Cleaner Tangit 1 RE
187. AL 3000 Weight 400g Approval VdS G202034 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT I 6 210102 Fire Detection Control Panel BC016 1 INT 1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT I 169 219006 Key for Manual Call Point SCH HFM HM 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249633 Protective Cover V2A for Manual Call Point Red WG ROT E 1 169 2171612 Replacement Glass for Manual Call Point ET SCH HFM 4 210210 Zone Extension Board ZEB2 1 245356 Manual Call Point Red Conv HM 3 11 01 02 Universal manual call point according to EN 54 11 B in an elegant red aluminium die cast housing designed for application in addressable conventional technology Features Robust aluminium die cast housing with a door aperture ang le of more than 180 Function marking FEUERWEHR replaceable Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Individual detector addressing by connecting an optional ad dress module Scheibe einschlagen 91 Knopf tief dr cken 99 Plenty of room for cabling 169 BB072001 SAM 0720 01 0100 158 Chapter 17 Manual Call Points Increasing
188. ASTER Gasl schanlage exchangeable Integrated dual isolator Reverse polarity protection Optical indication of activation by LED indicator Push button non latching Standardised glass pane easy to replace Setting of physical address with button in combination with LED indicator Plenty of space for cabling Increase of protection class to IP54 via optional Protection Kit for Manual Call Points supplied through loop voltage 180uA quiescent 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm Colour sky blue RAL 5015 Weight 400g Approval VdS G206128 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249634 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 169 2171621 Replacement Glass for Manual Call Point Blue ET SCH HM BL ion 169 BBO72001 SAM im 0720 01 0100 166 Chapter 17 Manual Call Points 245396 249096 170 249024 Special Designation for Manual Call Point HM BESCH Manual Call Point Yellow Anal Apo HM 1 32 05 02 Manual call point according to EN 54 11 B with dual isolator module integrated in an ele gant yellow aluminium die cast housing designed for application on the ADM loo
189. Accessories Cross references Page Art Nr Name Type 266 265019 Cylinder for Steel Sheet Mounting FASB LST 102 266 268012 Key for Fire Brigade Key Deposit 882AML102 268010 Fire Brigade Key Deposit Flush Mount FASB UP The Fire Brigade Key Deposit FASB for flush mounting is used for storage of additional buil ding keys The key deposit is delivered without a lock It provides authorised access for the fire brigade or secured access for service personnel e g technicians for elevator or heating On fire brigade access rou tes the key deposit is only allowed on demand by the fire bri N gade e g when the access to the fire brigade key box is secured by a barrier The door and the stored key are not moni tored The door is opened and locked simply by means of the cylinder lock pt e Features Key deposit made of powder coated steel sheet Easy to mount Specifications Colour pebble grey RAL 7032 Dimensions W x H x D 150 x 150 x 57 mm Cross references Page Art Nr Name Type 266 265019 Cylinder for Steel Sheet Mounting FASB LST102 266 268012 Key for Fire Brigade Key Deposit 882AML102 265019 Cylinder for Steel Sheet Mounting FASB LST102 The cylinder for steel sheet mounting with the new magnetic lock system customised for LST is designed for installation into the Fire Brigade Key Deposit FASB Cross references Page Art Nr Name Type 266 268010 Fire Brigade Key Deposit Flush Mount FASB UP 265 268009
190. Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 216 244183 Detector Module DM TP 05 L 215 244182 Detector Module DM TP 25 L 215 244186 Detector Module DM TP 80L 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 216 244184 Front Foil FW TP 1A 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 4 210210 Zone Extension Board ZEB2 1 Aspiration Smoke Detection System Housing TP 2 The Aspiration Smoke Detection System Housing TP 2 samples air from two monitored rooms via two connected sensor pipe networks and directs it to two detector modules not provided which analyse the air samples If the smoke concentration exceeds the permissible value an alarm is activated which is optically displayed on the system and further transmitted to a fire detection control panel The alarm can be reset at the control panel The system can be used for early fire detection in room and equipment monitoring due to the high response sensitivity of detector modules and is designed for the monitoring of two independent areas Loch The continuous air flow which is generated by a ventilator in the aspiration smoke detection system housing is
191. Alarm Monitoring Interface Licence ALVIS LBC1000 The Alarm Monitoring Interface Licence ALVIS LBC1000 enables the service of the DDE server which controls the event dependent communication between the alarm monitoring sy stem and the Fire Detection Control Panel Series LBC1000 The DDE server operates as an independent task parallel to the user interface of the alarm monitoring system 169 BB072001 SAM 0720 01 0100 33 Chapter 33 Tools 297 Tools 249059 249036 249051 169 BB072001 SAM 0720 01 0100 Test Module 100 200 SS MOD400R Measuring adapter to read out measured values from optical or ionisation smoke detectors Se ries 100 and 400 The test module transforms the measured value into a direct current volta ge signal which is measured by a multimeter Thereby the sensitivity of a detector can be assessed during maintenance A sufficient sensitivity is one of the most important criteria for avoiding false alarms Features Terminals for multimeter Easy readout of measured values without an alarm activation of the detector Battery lifespan approx one year Specifications Operating voltage 9VDC block battery Ambient temperature 0 C to 50 C Dimensions L x W x H 114 x 79 x 31 mm Connection 4mm sockets Colour black Weight 238g Test Gas Can SOLOA3 001 Canned non polluting test gas for checking the function of automatic smoke detectors Can be used with Smoke Detector Test Tools FPD05 an
192. Ambient temperature 10 C to 50 C Protection class IP30 Dimensions W x H x D 137 x 180 x 57 mm Colour grey white RAL 9002 Weight 1 2 kg Approval VdS G105045 Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 Inner Door for FSK700 2 A ITA 2 Inner door for the Fire Brigade Key Box FSK700 2 made of 5mm stainless steel with a lock for a profile half cylinder Dimensions W x H x D 108 x 150 x 5 mm Weight 0 5kg Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D 1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 Inner Door for FSK700 2 DBUK ITB 2 Inner door for Fire Brigade Key Boxes made of 5mm stainless steel sheet for installation of the double bit lock manufactured by Kruse or KABA Bauer including door stop and accessories Dimensions W x H x D Weight 0 4kg 108 x 150 x 5 mm 262 Chapter 27 Fire Brigade Key Boxes and Accessories 265757 265765 265760 Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 Inner Door for FSK700 2 DBUM ITF 2 Inner door for Fire Brigade Key Boxes made of 5mm stainless steel sheet for installation of the double bit lock manufactured by Mauer type 70091 92 including door stop and accessories Specifications Dimensions W x H x D 108 x 150 x 5 mm Weig
193. Apo GO 55000 317 121 249640 Protective Cage BWS 1 D1 71 251001 Remote Indicator PAS8 1 129 242027 Thermal Max Detector Conv 65 Apo GM 55000 137 127 242024 Thermal ROR Detector Conv 65 Apo GD 55000 122 127 242025 Thermal ROR Detector Conv 65 Apo GD 55000 127 128 242026 Thermal ROR Detector Conv 65 Apo GD 55000 132 121 249635 Trapezoid Steel Bracket TBH800 1 Detector Base Conv 60 65 Apo 45681 251 Mounting base in flush mounting design for automatic fire detectors Series 65 incl cover plate in particular for mounting in inserted ceiling made of mineral fibre ko E 232 2 Specifications Dimensions x H 150 x 15 mm Colour white Weight 70g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 126 240027 Ionisation Smoke Detector Conv 65 Apo GI 55000 217 126 241026 Optical Smoke Detector Conv 65 Apo GO 55000 317 71 251001 Remote Indicator PA58 1 129 242027 Thermal Max Detector Conv 65 Apo GM 55000 137 127 242024 Thermal ROR Detector Conv 65 Apo GD 55000 122 127 242025 Thermal ROR Detector Conv 65 Apo GD 55000 127 150 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY 246042 246041 128 242026 Thermal ROR Detector Conv 65 Apo GD 55000 132 Detector Base Conv ORBIS Apo MB 00001 Mounting base for automatic fire detectors Series Orbis in addressable conventional technolo gy suitable for indoor surface mounting Features Multi useable terminals with secure s
194. B072001 SAM 0720 01 0100 Chapter 30 Telephone Dialling Devices 285 Dialogue Module DPM805 1 Module for extension of Automatic Telephone Dialling Devices Series TWG805 1 with the functions for remote control remote enquiry and recording of the alarm receipt It consists of a voice message memory with pre programmed dialogue texts and an integrated circuit for control of additional functions The remote control and authorisation code enquiry is establis hed via the telephone network with DTMF tones Features Remote control of actuation outputs with the dialogue menu Condition enquiry of actuation outputs Condition enquiry of control lines Remote enquiry of the event memory of the telephone dialling device Enquiry of alarm receipt Activation of a time window for remote maintenance by manufacturer Remote disablement of control lines Remote enquiry of voice announcement messages test function Alarm test call back simulation HEG Specifications Supply voltage internal voltage supply of the TWG805 1 Current consumption at 12V 8mA Current consumption at 24V 4mA Current consumption from stand by battery in case of supply voltage failure 10mA Ambient temperature 5 C to 50 C Weight 6g Cross references Page Art Nr Name Type 281 320007 Automatic Telephone Dialling Device TWG805 LA 282 320008 Automatic Telephone Dialling Device TWG805 1D Telephone Speaker Set TEL805 1 For recording of voic
195. BC216 1 INT 1 27 214108 Fire Detection Control Panel BC216 1CE INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 103 249090 Limit Switch Anal 500 SS EDS500 1 101 249092 Multi Module Mounting Rail MEA244 1 TR 295 218008 Parameter Setup Software PARSOFT 2 Extinguishing Control Function Series BC06 Description In the basic version the Fire Detection Control Panel Series BC06 is equipped with 4 con ventional detector lines Automatic and non automatic fire detectors as well as numerous spe cial detectors with contact output can be connected The control panel provides a mounting position for extension modules for installation of eit her the Zone Extension Board ZEB2 1 or the Extinguishing Board EXB1 1 The Fire De tection Control Panel Series BC06 can be used as extinguishing control panel according to EN 12094 1 for one flooding zone in combination with the Extinguishing Board EXB1 1 In combination with the extinguishing module the control panel provides suitable inputs and outputs for actuation and monitoring of the following components of the extinguishing system Input for activation devices for manual activation of the extinguishing system Input for emergency hold devices delaying the flooding process Input for fault detectors e g monitoring the pressure of the extinguishing agent Input to switch into manual only mode Output for signalling devices to
196. BC216 2EPS and allows for the relocation of the terminals between fire detection control panel and the outgoing lines It includes terminals for the 230V AC supply and the power unit outputs and the outputs of the first fire detection control panel module as well as a pre assembled cable harness of 1 7m length Cross references Page Art Nr Name Type 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS Battery Bracket BK216 1 The Battery Bracket BK216 1 allows for the installation of 2 stand by batteries 12V max 22Ah in the Auxiliary Case GEH2164 Specifications Dimensions W x H xD 380 x 175 x 90 mm Material powder coated sheet steel Colour grey white RAL 9002 Weight approx 900g Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 287 310002 Stand by Battery 12V 18Ah Battery Bracket BK216 1CE The Battery Bracket BK216 1CE allows for the installation of 2 stand by batteries 12V max 22Ah and auxiliary modules e g 2 Relay Modules RL58 1 or RL58 2 or 2 Siren Connection Modules SZ58 3 at the back side of the Fire Detection Control Panels BC216 1CE and BC216 3CE Specifications Dimensions W x H x D 437 x 175 x 90 mm Complete Control Panel BC216 xCE with battery bracket Dimensions W x H x D 478 x 266 x 181 mm Material zinc coated sheet steel Weight approx 950g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 27 214108
197. BCnet Sectional Control Panel OP BC216 2 INT1 37 214023 Fire Brigade Interface Additional Board FWZ2 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT1 16 214308 Fire Detection Control Panel BC216 1S INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 39 214031 Network Redundant Alarm Converter NNUS5 1 169 BB072001 SAM 0720 01 0100 214023 214024 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 37 Fire Brigade Interface Additional Board FWZ2 1 The Fire Brigade Interface Additional Board FWZ2 1 that is attached to the Fire Brigade In terface FWI2 1 allows for the connection of two independent line monitored transmitting de vices for the direct interconnection to a designated alarm respondent e g fire brigade Features Two independent line monitored outputs that functionally correspond to the relay outputs of the Fi re Brigade Interface FWI2 1 3 different levels of surveillance current can be set Specifications Current consumption at 24V typ 4mA both outputs not connected max 28mA both outputs connected Ambient temperature 5 C to 50 C Dimensions L x W x H 117 x 74 x 10 mm Weight 70g Cross references Page Art Nr Name Type 36 214022 Fire Brigade Interface FWI2 1 LED Display Field LAB48 1 The LED Display Field LAB
198. Brigade Orientation Panel FOTR900 1 D1 The Fire Brigade Orientation Panel FOTR900 1 D provides the fire brigade on site quickly with precise information It contains the Fire Brigade Control Unit FBF900 1 D1 for operati on of Fire Detection Control Panels Series BC016 and BC216 by the fire brigade according to DIN 14661 and the Fire Brigade Dis play Panel FAT900 1 D1 according to DIN 14662 for information retrieval Both devices are accommodated in a powder coated steel sheet case coloured in flame red RAL 3000 or in a colour requested by the operator A lock for half cylinders is mounted in the case of the Fire Brigade Orientation Panel FOTR900 1 D The Fire Brigade Orientation Panel FOTR900 2 D1 can be com bined with the Fire Brigade Map Box FPKCLR900 1 D1 DOM CL1 lock or FPKPHZR900 1 D1 lock for half cylinders to a compact unit Features Integrated Fire Brigade Display Panel FAT900 1 D1 Integrated Fire Brigade Control Unit FBF900 1 D1 Lock for half cylinders Specifications Operating voltage 10 30VDC Current consumption at 24V 50mA quiescent 150mA alarm Ambient temperature 0 C to 50 C Dimensions W x H x D Colour 230 x 360 x 95 mm flame red RAL 3000 Weight 3 7kg Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT1 30 2149997 BCn
199. C600 BRD The Detector Base FC600 BRD is used for mounting of automatic fire detectors Series FC600 in conventional technology If no detector is mounted in the base the connection to the following detectors is maintained by the integrated Schottky diode The base is suitable for indoor surface mounting Features re gt Multi wire terminal with secure screw fitting ss Schottky diode to maintain through connection of the es detector line on removal of the detector Terminal for external remote indicator Mechanical theft protection of detectors Specifications Ambient temperature 30 C to 70 C Relative humidity 5 95 no condensation Dimensions x H 110 x 16 mm Colour white Weight 36g Cross references Page Art Nr Name Type 76 241070 Optical Smoke Detector Conv FC600 FC600 O 71 251001 Remote Indicator PA58 1 77 242071 Thermal Max Detector Conv FC600 FC600 TMAX 78 77 242070 Thermal ROR Detector Conv FC600 FC600 TDIFF 57 z am and 80 Chapter 10 Acessories for Series FC600 246072 Detector Relay Base FC600 FC600 BREL The Detector Base FC600 BREL is used for mounting of automatic fire detectors Series FC600 in conventional technology The integrated relay output is active as long as the detec tor remains in alarm condition The base is suitable for indoor surface mounting Features p Multi wire terminal with secure screw fitting Zur gt Relay output with dry change over c
200. Cable NWK2 1 232 h eee a e stede beer Seg 51 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 214025 214231 223025 223027 223028 223041 223060 223030 223032 223033 218022 218023 214176 218021 219010 Serial Interface Module SIM216 1 ramaanananvavavenvav ee cence rece tn nee bene beeen ene neens 52 Interface Adapter Module IAM216 1E ooo eee cee cence cette tee ne nee e ee enen eens 52 Ethernet Module ENM2 1 i pen ccc cence cn cee enn en ene eee e debe ent a een en T 53 Remote Access Module PSTN FZP2 1 oo 0c ccc ccc ccc cnet cece ence ene n eee eben teenies 53 Remote Access Module GSM GPRS FZG2 1 2 0 0 0 ccc ccc cnn cee cence een n teense ene ne ees 54 SMS E Mail Transmitter Module SMS2 1 D1 0 ccc ce cence ene e nen ene eeeeenes 55 Gateway IEC870 5 101 104 BC216 IEC870 BC216 GW arnnannnnennnnennnennnnennnnennrnener 56 Long Distance Modem BCnet216MOD 1 essuunnnnnnnnnnenennnanuenennnanennnanuenenananuener 56 Multimode Fibre Gateway BCnet216 LWL MM 2 essuunnnvvnnnnnenennnanverrnnnnnerenanuevener 57 Singlemode Fibre Gateway BCnet216 LWL SM 2 osrennnnnnenenannnvennnnvanenananuerenasaneer 57 ZET Interface License ZCT SS oyri A R e AAO E ges bere a es 58 ESPA 4 4 4 Interface License ESPA SS anrnuuuenenernenenenernenernenenenenenenueuaneneneener 58 BCnet LBC Gateway N OP 6HU BCNET LBC GW annennnnvnnnennenennnennerennerenenenneer 59 LBC Sub Unit License LBC UZ vas och 2
201. Control Panel OP BC216 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT 1 27 214108 Fire Detection Control Panel BC216 1CE INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E ESPA 4 4 4 Interface License ESPA SS ESPA interface license for the communication of Fire Detection Control Panels Series BC216 with pager systems DECT systems visual call systems etc which provide an ESPA 4 4 4 interface for the transmission of display texts You can define the text length as well as the type of the messages alarms technical messages etc for up to 2 receiver groups at the fire detection control panel The ESPA interface license is required in the sectional control panel that is connected to the respective system Note the ESPA interface can only be operated on a central processing board ZTB216 2 with at least hardware version V4 The type of the board is printed on a label The version num ber is the last digit of the PCB version that is printed in the left bottom corner of the PCB e g PN5233S4 for V4 Furthermore a firmware version PL149 Vx 20 or newer and a 169 BB072001 SAM 0720 01 0100 Chapter 5 Interfaces 59 PARSOFT version V1 20 or newer are required for the operation and the setup of the inter face respectively Cross references Page Art Nr Name Type 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet
202. Control Panel Series BC216 and the system condition the panel can activate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combinations The sound level is ad justable in 3 steps but depends also on the chosen tone type The power consumption is de pendent on the tone type and the adjusted sound level Features 32 different tone type combinations selectable via DIL switch e g continuous tone 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Sound level adjustable in 3 steps low medium high Low power consumption Long lifespan of strobe due to the use of LEDs Integrated dual isolator Integrated detector base 2 decadic rotary switches for setting the sounder strobe address from 01 to 99 Different base versions available o I Specifications Operating voltage Current consumption from loop supply through the loop voltage typ 450uA sounder and strobe off max 4 3mA low sound level max 5 6mA medium sound level max 9 2mA high sound level typ 70dB A 1m distance low sound level typ 79dB A 1m distance medium sound level typ 87dB A 1m distance high sound level max 95dB A 1m distance high sound level Sound level detector mounted Examples at 24V Continuous tone 660Hz DIN tone 1200 500Hz Slow Whoop tone 500 1200Hz typ 6 6mA at 90dB A 1m distance typ 7 8mA at 89dB A 1m distance
203. Current consumption at24VDC 25mA quiescent and active Ambient temperature 20 C to 50 C Protection class IP65 Dimensions W x H x D 200 x 120 x 80 mm Material ABS Colour light grey RAL 7035 Weight 550g Approval VdS G205066 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 203 244622 Sensing Cable Black LWM SK180001 1 203 244628 Sensing Cable Blue LWM SK1800010 169 BB072001 SAM 0720 01 0100 244628 244622 169 BB072001 SAM 0720 01 0100 Chapter 20 Special Detectors 203 204 244624 Sensing Cable Stainless Steel LWM SK11800013 4 210210 Zone Extension Board ZEB2 1 Sensing Cable Blue LWM SK1800010 The blue Alarmline sensing cable consists of four copper wires each of them being coated with a colour coded material with a negative temperature coefficient The wires are twisted and isolated with an outer layer made of temperature resistant and fire retardant plastic On one side of the cable the four wires
204. D 249201 RF Interface 4Rel FUIF511 27D Thermal ROR Detector RF 55000 480 Radio linked heat detector operating on the rate of rise heat detection principle combined maximum rate of rise detector classified as AIR maximum room height 7 5 m suitable for mounting in radio linked detector bases Features Extremely low quiescent current Sealed electronics prevents false alarms caused by the page environment Specifications Operating voltage Battery life span Alarm temperature Operating temperature Ambient temperature Dimensions x H Alarm indication on detector supplied through detector base approx 1 5 years batteries are located in the detector base 57 C maximum heat component Colour Weight Approval Cross references Page 187 184 max 50 C 0 C to 60 C no condensation 100 x 42 mm white 80g VdS G206016 Art Nr Name Type 246040 Detector Base Conv RF 215 27D 249201 RF Interface 4Rel FUIF511 27D Manual Call Point Red RF HFM 153 27D Radio linked manual call point according to EN 54 11 B in elegant red plastic housing with integrated antenna The manual call point is delivered with battery 186 Chapter 19 RF Devices 245021 Features Operating instructions by means of symbols European standard Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Continuous status messages High transmission ca
205. D indicator pairs 478 x 266 6 height units x 55 mm light grey RAL 7035 approx 1 6kg Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 27 214108 Fire Detection Control Panel BC216 1CE INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 169 BB072001 SAM 0720 01 0100 252012 169 BB072001 SAM 0720 01 0100 Chapter 8 Display and Operating Devices 73 73 252012 Remote Tableau Drive Unit PTU288 1 Remote Tableau Drive Unit PTU288 1 The Remote Tableau Drive Unit PTU288 1 allows to optically signal events of a Fire Detecti on Control Panel Series BC016 or BC216 or of an Extinguishing Control Panel Series LC216 on an LED display tableau or a synoptic remote tableau Further an integrated buzzer indicates the alarm condition and fault condition of the control panel Up to three LED Display Fields LAB48 x or LED Con nection Modules LAM48 1 can be connected to the remote tableau drive unit A remote tableau with up to 144 para meterisable LED indicators can be created in combination with an optional LED Display Tableau LAT288 1 or LAT288 1CE To design synoptic re mote tableaus the Remote Tableau Drive
206. Detection Control Panel Series BC216 Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Display of activated condition via 2 LED indicators that are visible from all angles Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through loop voltage Current consumption typ 500uA quiescent Alarm temperature typ 58 C with AIR typ 61 C with A2 and A2S typ 90 C with CR and CS Operating temperature max 50 C with AIR A2 and A2S max 80 C with CR and CS Ambient temperature 20 C to 80 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 105g Approval VdS G299039 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 169 BB072001 SAM 0720 01 0100 241022 243100 169 BB072001 SAM 0720 01 0100 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 141 Optical Thermal Detec
207. Detector Base Conv 60 65 Apo GSA 4568 1 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 111 246012 Detector Base Filtrex Anal 500 SS B524FTXE 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 169 BB072001 SAM 0720 01 0100 122 Chapter 13 Acessories for Series 300 ECO1000 200 500 244009 241038 107 246141 Detector Relay Base Conv 1000 SS ECO1000BREL24L 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 Duct Detector 400 OM DH400P The Duct Detector DH400P monitors ventilation ducts or air conditioning channels A small amount of air is conducted into the detector housing via the air inlet pipe directed to the opti cal smoke detector and is released into the ventilation duct again via the air escape pipe The duct detector consists of a plastic housing with transparent cover and the Optical Smoke Detector 2151E LC The air escape pipe is al ready integrated in the plastic housing The air inlet pipe is not provided with the duct detector and has to be selected according to the duct si ze see cross references The alarm is trans mitted in addressable conventional technology Features Transparent cover for optical recognition of detector activation Individual detector identification through connection of an optional Address Module NGS58 1 Approved for win
208. Dimensions W x H x D Weight Cross references Page sections of the high security network GSSnet can be interconnected in this Each sectional control panel requires one gateway each for in and output The ends of multimode fibres have to be fit with an ST connector not provided for optical fibres A 5m long and already pre assembled data cable is provided to enable an easy connection between the gateway and the Network Interface Module NIF5 1 18 30VDC typ 200mA max 4km with 62 5 125um multimode fibre max 3km with 50 125um multimode fibre 50um or 62 5um 8 50nm 8dB 10 C to 55 C 61 x 115 x 113 mm 500g Art Nr Name Type 20 2199998 Fire Detection Control Panel BCnet216 Description Singlemode Fibre Gateway BCnet216 LWL SM 2 The gateway LWL SM 2 interconnects sectional control panels of the Fire Detection Control Panel BCnet216 via singlemode optical fibres An optical fibre cable with at least 2 free 58 Chapter 5 Interfaces 218022 218023 singlemode fibres is needed for the connection If required only specific sections of the high security network GSSnet can be interconnected in this way Each sectional control panel requires one gateway each for in and output The ends of singlemode fibres have to be fit with an ST connector not provided for optical fibres A 5m long and already pre assembled data cable is provided to enable an easy connection between the gateway and the Network Interfa
209. E 79 246071 Detector Base with Diode FC600 FC600 BRD 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 107 246141 Detector Relay Base Conv 1000 SS ECO1000BREL24L 105 246100 Detector Relay Base Conv 300 SS B324RL 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 80 246072 Detector Relay Base FC600 FC600 BREL 110 246013 Isolator Detector Base Anal 500 200 SS B524IEFT 1 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 Detector Label Small Sheet 20pcs BME KL BOG The inscribable adhesive label serves for the marking of fire detectors not directly visible e g in inserted ceilings inserted floors or for marking other devices of the fire detection sy stem e g distribution boxes An A4 size sheet contains 20 adhesive labels ST LABOR STRAUSS SOEUNGSANAGENEAU avan Specifications Dimensions 45mm Marking area W x H 40 x 20 mm Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 151 246025 Detector Base Anal Apo ASA 45681 210 107 246140 Detector Base Conv 1000 SS ECO 1000BR 1000 105 246008 Detector Base Conv 400 100 300 SS B401RM 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 79 246070 Detector Base FC600 FC600 BR 111 246012 Detector Base Fi
210. E 43 Dummy Cover 19 3HU AD8C3H lt s sisine ait aa o s si in os N EErEE ITANE EEEE 43 Dummy Cover 19 6HUAD8C 6H xit aa ee hata E Sea Ses TE eee eee E 43 Decoration Foil for BC216 3CE FF216 3CE 20 0 ccc n cece e tener ene n teenies 44 Mounting Kit 19 3HU EW8C E eoonenanennanennneennnennenenanennnnennerennennnennnnennnener 44 Kit 19 3HU for Printer DPU414 DPU2 1E 2 0 ccc cnet e teen een en eeeenes 44 Cover IP54 for BC216 GEH IP54 BC 1 D1 0 ccc ccc cence ne nee n nee een teenie ees 45 Cabinet 19 I8HU GEHI IAS samba ve 45 Housing 19 36HU GEH19 STAND s e aia e EE e E E EET E a IST E 46 Transparent Door 19 36HU SIT19 STAND suvnvvevvnnvavvvnnnnnevevnnanuevennnannennnnsuueeen 46 Extinguishing System Controls 2189990 Extinguishing Control Panel Series LC216 Description 0 0 cece ee cc eee e cece nee e eens 47 218024 Extinguishing Control 8 Area License LC216 8LB 2 eee cence eee e ene e ee ene 47 2189991 Extinguishing Control Function Series BC06 Description 00 0 cece cece ence eee eee eee 48 210216 Extinguishing Board BC06 EXB1 1 ccc cnet eee ee teen eee nen ee eeene 49 222011 Extinguishing System Interface LSS1000 1 1 0 20 c eee t ene e ee cnn ene eeaee 49 223009 Control Zone Module SLM1 2 psani net etater che ede eee ad bee bena vag Web embeds same EA 50 Interfaces 214033 Network Interface Module NIF5 1M oo eo cece ete e nee e et tee een e ee ntn ne eeene 51 214027 Network
211. ED Display Tableau LAT288 1 72 252011 LED Display Tableau LAT288 1CE 73 252012 Remote Tableau Drive Unit PTU288 1 z am and 38 Chapter 3 Fire Detection Control Panels Series BC216 214030 214032 LED Display Field LAB48 2 The LED Display Field LAB48 2 contains 48 freely parameterisable double LEDs yello w yellow for the individual display of events of the detector zones actuations transmitting devices or alarming devices at Fire Detection Control Panels Series BC216 and of events of the flooding zones and extinguishing systems at the Extinguishing Control Panel Series LC216 The double LEDs are arranged in two rows each with 24 pairs In addition the LED Display Field can be installed into an LED Display Tableau LAT288 that serves as a freely programmable display for the events of a Fire Detection Control Panel Series BC016 or BC216 as well as an Extinguishing Control Panel Series LC216 Features 48 double LEDs left and right hand side yellow freely parameterisable according to indi vidual events Display of activation as well as deactivation or fault condition of the parameterised event Designation labels allow for individual marking of every double LED Specifications Current consumption at 24V typ 2mA no active LED 0 25mA per LED Ambient temperature 5 C to 50 C Dimensions L x W x H 176 x 120 x 15 mm Weight 60g Cross references Page Art Nr Name Type 23 214056 BCnet Sectional Control Pan
212. Evacuation Circuit FFEV06 1 Self adhesive plastic foil for labelling of three additional function keys in the display and ope rating field of the Fire Detection Control Panel Series BC06 These keys are used for the function Alarming device configured as Evacuation Circuit NEN 2575 o o Specifications Dimensions W x H 56 x 42 mm Colour light grey RAL 7035 Cross references Page Art Nr Name Type 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 6 Chapter 2 Fire Detection Control Panels Series BCO16 2 Fire Detection Control Panels Series BC016 210102 Fire Detection Control Panel BC016 1 INT1 The Fire Detection Control Panel BC0O16 1 INT1 is a compact control panel for small and medium size fire detection systems in conventional technology Depending on the boards inserted you can connect fire detectors fault detectors and condition detectors to a maximum of 16 detector lines in addressable conventional technology Further more up to 16 actuations 9 alarming devices and 3 transmitting devi is ces can be connected Thanks to its wide range of possible logic ji combinations for alarming and transmitting devices as well as for actuations the control panel can realise even extensive and complex alarming and control tasks in the fire alarm technology It complies with all requirements of the European Standards EN 54 2 and EN 54 4 including all options for
213. FC600 TMAX 78 20 0 cece ccc cece ncn e nent een en tees TT Acessories for Series FC600 246070 246071 246072 Detector Base FC600 FC600 BR 6 ccc ccc ce cece nen nee e nent beet een tn enens 79 Detector Base with Diode FC600 FC600 BRD 0 ccc ccc cece cence ncn e eee n ene en en enens 79 Detector Relay Base FC600 FC600 BREL 1 eee c cece eee c teen eee en eens eenae 80 Conventional Detectors Series 300 ECO1000 241040 241041 242040 242042 242041 241045 241046 242047 242045 242046 Optical Smoke Detector Conv 300 SS 2351E cece cece cece eee cnet een e eee enn e ne ee 81 Optical Thermal Detector Conv 300 SS 2351TEM 2 0 0 0 eee cece cee e eect nent ne nee e eee 82 Thermal ROR Detector Conv 300 SS 5351 Eo ccc ccc ccc ence e nee ete ne ten tn ee nenens 83 Thermal Max Detector Conv 300 SS 5351TE 0 0 ccc ccc ccc cece cece ence een ene nn en enens 84 Thermal Max Detector Conv 300 SS 4351 Eo 0 cece ccc cence cece ence nent renee teenies 84 Optical Smoke Detector Conv 1000 SS ECO1003 1 0 0 eee cece eee e eee ett t eee en nen e ee 85 Optical Thermal Detector Conv 1000 SS ECO1002 2 0 occ e cece teen e ene e eens 86 Thermal Max Detector Conv 1000 SS ECO1004T 2 0 ccc cece ccc ncn cece cece nen ee nenens 87 Thermal ROR Detector Conv 1000 SS ECO1005 2 0 ccc ccc cece e cece nen en ee nenens 87 Thermal Max Detector Conv 1000 SS ECO1005T 2 0 00 ccc ccc ccc cece nce cece cenc
214. Fibreglass telescopic pole used to adjust the Smoke Detector Test Tool SOLO330 or the De tector Removal Tool SOLO200 to the individual room height The pole measures 1 2m in retracted condition The total length in extracted condition is 4 5m you can therefore reach detectors mounted to approx 7m height Cross references Page Art Nr Name Type 298 249052 Detector Removal Tool SOLO200 113 246112 Satellite Unit for Remote Programming Conv 300 SS S300SAT 297 249051 Smoke Detector Test Tool SOLO330 Extension Pole SOLO101 Fibreglass extension pole with a length of 1 2m for Smoke Detector Test Tool SOLO330 and Detector Removal Tool SOLO200 for application with room heights of up to approx 4m Together with the Telescopic Pole SOLO100 it is possible to reach detectors which are mounted in rooms of up to 9m height Cross references Page Art Nr Name Type 298 249052 Detector Removal Tool SOLO200 113 246112 Satellite Unit for Remote Programming Conv 300 SS S300SAT 297 249051 Smoke Detector Test Tool SOLO330 Test Set Conv S60 Apo TS 53832 020 Measuring device for electrical testing of automatic detectors Series 60 and 65 in conventio nal technology on site during maintenance Each test set is provided with a continuity tester mains adapter and a portable case with shoulder straps Features Easy to handle Menu controlled test program Automatic execution of a series of tests for selected detector types Two buttons fo
215. Foil BA AREDF The banderole is used for reliable fixation of the aspiration hole reduction foil to the sensor pipe network of an aspiration smoke detection system 244234 Plastic Clip for Aspiration Hole Reduction Foil DF KC AREDF TK The plastic clip is used for reliable fixation of an aspiration hole reduction foil in deep free zing areas to the sensor pipe network of an aspiration smoke detection system 244128 Glue Tangit 0 12kg KLEB RAS 01 Glue for the connection of individual components of a sensor pipe network One packing unit contains 0 125kg which is sufficient for gluing approx 50 junctions 169 BB072001 SAM 0720 01 0100 224 Chapter 22 Accessories for Aspiration Smoke Detection Systems 244129 244130 244126 244131 244127 Glue Tangit 0 25kg KLEB RAS 02 Glue for the connection of individual components of a sensor pipe network One packing unit contains 0 25kg which is sufficient for gluing approx 100 junctions Glue Tangit 0 5kg KLEB RAS 05 Glue for the connection of individual components of a sensor pipe network One packing unit contains 0 5kg which is sufficient for gluing approx 200 junctions Glue Tangit 1kg KLEB RAS Glue for the connecting individual components of a sensor pipe network One packing unit contains 1kg which is sufficient for approx 400 junctions Cleaner Tangit 0 121 REIN RAS 01 Cleaning liquid for removal of dirt residual fat etc which is used before gluing individu
216. Humidity max 95 no condensation Protection class IP21 Dimensions x D 106 x 95 mm Colour red Weight 209g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Sounder Strobe WM65 XP95ISM Red Multitone 100dB 55000 298 The addressable multitone sounder with integrated strobe 55000 298 is installed in a red pla stic housing and is prepared for outdoor surface mounting The unit is actuated using Apol lo Discovery protocol and powered via the ADM loop The sounder is always activated together with the strobe A dual isolator is integrated in the sounder In case of a short circuit on the loop it maintains the function of ADM elements that are not affected by the short circuit A short circuit on the loop is indicated via a yellow status LED Depending on the parameter setup of the Fire Detection Control Panel Series BC216 and the system condition the panel can acti vate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 3 combinations 240 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 356020 Features 3 different tone type combinations selectable via DIL switch e g continuous tone 900Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Sound level 100dB
217. IN RAS eee eee e eee 224 Condensate Separator DN25 KABS 25 222 Conduit Box Apo SZA 4568 1 204 e eee 153 Control Device for Magnetic Lock Clamp 2498 275 Control Module 1xRel Out DIN Anal 200 SS M201E 240 DIN cece cece cece ee cee eee eens 99 Control Module 1xRel Out Anal 200 SS M201E 240 98 Control Module 1xSurv Out Anal 200 SS M201E 98 Control Module 6xRel Out Anal 200 SS CR 6 99 Control Module Anal XP95 Apo SMK 55000 849 146 Control Module Anal XP95 Apo SMU 55000 852 145 Control Panel Rack 8HU RACK216 1E Control Zone Module SLM1 2 Conventional Detector Interface GIF8 1 Conventional Zone Module Anal 200 SS M210E CZ 100 Conventional Zone Module Anal 500 SS MS12ME 100 Conventional Zone Module Anal XP95 Apo GWM 55000 845 oo eee e ccc eee nee enee 146 Cord 2 Wire for LED Connection 10pcs LED LEITUNG 10 2 00 0 ccc cece cece ccc oneni 75 Cover IP54 for BC216 GEH IP54 BC 1 D1 45 Cover Plate for Base Bx01 Bx24 BC Bx01 116 Cylinder for Steel Sheet Mounting FASB LST102 266 D Decoration Foil for BC216 3CE FF216 3CE 44 Detector Base Filtrex Anal 500 SS B524FTXE 111 Detector Base with Diode FC600 FC600 BRD 79 Detector Base Anal 500 200 SS B501 4 Detector Base Anal 500 200 SS B501DG Detector Base Anal Apo 45681 250 Detector Base Anal
218. K400 94 242002 Thermal Detector Anal 200 SS 525 1EM 121 249635 Trapezoid Steel Bracket TBH800 1 116 249012 Wet Base Shroud SS WB1 Detector Base Anal 500 200 SS B501DG The Detector Base B501DG is used for mounting of automatic fire detectors Series 500 and 200 The base is suitable for indoor surface mounting The height of the Detector Base B501DG is increased compared to the Base B501 and is therefore suitable for thicker cables with a diameter of up to 12mm 5 Features Connection to the ADM loop using System Sensor 200 protocol Multi wire terminal with secure screw fitting Terminal for external remote indicator Mechanical theft protection Specifications Ambient temperature 30 C to 70 C Relative humidity 0 to 95 no condensation Dimensions x H 102 x 26 mm Colour cream Weight 57g Cross references Page Art Nr Name Type 114 246006 Base Adapter SS MZP500 1 226 249011 Detector Label BME BEZ 120 249044 Detector Mounting Bracket MMW1 1 90 240013 Ionisation Smoke Detector Anal 200 SS 1251E 92 241020 Optical Thermal Detector Anal 200 SS 2251TEM 91 241050 Optical Laser Detector Anal 200 SS 7251 90 241010 Optical Smoke Detector Anal 200 SS ND2251EM 121 249640 Protective Cage BWS 1 D1 115 246010 Recessed Mounting Kit SS RMK400 71 251001 Remote Indicator PAS8 1 110 Chapter 13 Acessories for Series 300 ECO1000 200 500 246016 246013 115 246009 Surface Mounting Kit SS SMK400 94 242002 Th
219. K700 2 DBUM ITF 2 0 s eee cee e eee cect EEEE EE E EEEE a 262 Steel Column V2A for FSE MP1 Strobe HSFSK700 2 D6 0 0 eee cece c eee teen eee ee 262 Steel Column V2A Standard HSFSK700 2 D1 oo ccc cette nett been ete nn eee e ee 262 Steel Column V2A for F0345 HSFSK700 2 D2 2 0 cect eet te nee e enn nnn e eas 263 Steel Column V2A for F0345 Strobe HSFSK700 2 D3 oo cece cece eee tte eee e ees 263 Steel Column V2A for Strobe HSFSK700 2 D4 2 c ete eet ee tne e ee nnn neces 264 Steel Column V2A for FSE MP1 HSFSK700 2 D5 0 cece cece cee cette eee nen nee e ee 264 Unblocking Element FO345 si p2202 och yi cee et ok ee dee s OY Bene eee deed 265 Unblocking Element for Half Cylinder FSE MP1 ornnnnnennnnnnenennnannenrnnnauvnnnanuevenenr 265 Fire Brigade Key Deposit Surface Mount FASB AP oorvvvennnnnvenannvvrrnananvennnnvevennner 265 Fire Brigade Key Deposit Flush Mount FASB UP esuvvananannnvervnnvnnenanavuvennnanuenener 266 Cylinder for Steel Sheet Mounting FASB LST102 2 0 0 0 eee tenet tenn en eee 266 Key for Fire Brigade Key Deposit 882AML102 20 0 0 cece eect eee n eee tnn eee eee 266 Fire Brigade Control and Display Devices 250008 250740 250741 250707 250900 250901 250717 250902 250606 250608 268007 250709 250713 Fire Brigade Control Unit FBF58 2 0 2 0 0 cece cece cence cent e ene e tence tenn ee eennes 267 Fire Brigade Control Unit FBF900 1 D1 0 cece cen
220. LED for setting the physical address Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 Specifications Operating voltage supplied through loop voltage 169 BB072001 SAM 0720 01 0100 Current consumption Ambient temperature Protection class Dimensions W x H x D Chapter 17 Manual Call Points 163 300uA quiescent 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm Colour rape yellow RAL 1021 Weight 400g Approvals VdS G202035 VdS G206129 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 168 249636 Protective Cover V2A for Manual Call Point Yellow WG GELB E 1 169 2171619 Replacement Glass for Manual Call Point Yellow ET SCH HM GE 170 249024 Special Designation for Manual Call Point HM BESCH 245389 Manual Call Point Grey Anal SS HM 7 22 03 02 The manual call point according to EN 54 11 B is accommodated in a robust grey alumini um die cast housing The detector is designed for use on the ADM loop ring bus technolo gy using System Sensor 200 protocol An integrated dual isolator module disconnects the loop at short ci
221. LIF64 1 51 214027 Network Cable NWK2 1 39 214031 Network Redundant Alarm Converter NNUS5 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Module SZ58 3 287 310002 Stand by Battery 12V 18Ah 58 218022 ZLT Interface License ZLT SS BCnet Sectional Control Panel Extension BCE216 3LG The BCnet Sectional Control Panel Extension BCE216 3LG allows for the extension of a Fi re Detection Control Panel BCnet216 with two ADM loops for detectors and modules using System Sensor 200 or Apollo Discovery protocols The extension is integrated into the Fire Detection Control Panel BCnet216 by installing it in a BCnet Sectional Control Panel BC216 2 or BC216 3 and connecting it to the GSSnet wiring via the GSSnet interface on the extension The 24V supply of the BCnet Sectional Control Pa nel Extension BCE216 3LG is shared with the BCnet sectional control panel in whose cabi net it has been installed it does not have a power supply or battery charger of its own The extension is designed as compact unit and mounted on a pivoting sheet steel carrier 169 BB072001 SAM 0720 01 0100 214108 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 27 The loop processing functions of the BCE216 3LG fully correspond to t
222. NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 136 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 15 Analogue Detectors and Modules Series XP95 DISCOVERY 240024 241023 lonisation Smoke Detector Anal XP95 Apo Al 55000 520 Addressable smoke detector operating on the ionisation principle for application on the ADM loop using Apollo Discovery protocol consisting of a sensing and reference chamber dual chamber principle for automatic compensation of environmental influences and a extra flat design suitable for indoor mounting EN Font Features Constant sensitivity OO o Insect screen Specifications Operating voltage Current consumption Ambient temperature Relative humidity Radioactive compound Intelligent evaluation algorithms in the respective LST fire detection control panels compensate for the impact of contamination of the sensing system Thereby the response sensitivity of the detector is kept constant for a long time thus constituting an effective
223. O bus address Features Operating voltage 20 31VDC Current consumption at 24V typ 15mA without LED componentries Ambient temperature 5 C to 50 C USB connection USB plug socket type B Dimensions L x W x H 150 x 75 x 20 mm Weight 76g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 74 252013 LED Connection Module LAM48 1 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 72 252010 LED Display Tableau LAT288 1 72 252011 LED Display Tableau LAT288 1CE 74 Chapter 8 Display and Operating Devices 252013 259011 9 210112 Serial Interface Module SIM016 3 LED Connection Module LAM48 1 The LED Connection Module LAM48 1 is connected to the Remote Tableau Drive Unit PTU288 1 and indicates events from a Fire Detection Control Panel Series BC016 or BC216 or from an Extinguishing Control Panel Series LC216 via 48 LED indicators or relay out puts The LED connect
224. O8FF The manual call point according to EN 54 11 A is accommodated in a red plastic housing and is activated by pressing in the plastic pane without breaking it The pane can be placed again into the idle position with a special key thereby resetting the detector The detector contains a dual isolator and is designed for use on the ADM loop ring bus technology using System Sensor 200 protocol Features Operating instructions by symbols European Standard Activation by pressing in plastic pane without breaking it Plastic pane easy to reset Detector housing can be opened only with a special key provided 2 decadic rotary switches for setting the address from 01 to 99 Dual loop isolator Specifications Operating voltage supplied through loop voltage Current consumption 360uA quiescent Ambient temperature 10 C to 55 C Relative humidity 0 95 no condensation Protection class IP24 Dimensions W x H x D 89 x 93 x 28 mm Colour flame red RAL 3000 Weight 160g Approvals LPCB 166b 45 166b 46 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 173 245019 Surface Mount Box MCP5A SR 173 245012 Surface Mount Box MCP5A SR3T 245014 Manual Call Point Anal XP95 Apo 55000 905 Manual call point according to EN 54 11 A in an elegant red plastic housing for application on the ADM loop ring b
225. P95 200 239 Sounder Strobe WM XP95ISM Red Multitone 100dB 55000 293 The addressable multitone sounder with integrated strobe 55000 293 is installed in a red pla stic housing and is prepared for indoor surface mounting The unit is actuated using Apol lo Discovery protocol and powered via the ADM loop The sounder is always activated together with the strobe A dual isolator is integrated in the sounder In case of a short circuit on the loop it maintains the function of ADM elements that are not affected by the short circuit A short circuit on the loop is indicated via a yellow status LED Depending on the parameter setup of the Fire Detection Control Pa nel Series BC216 and the system condition the panel can activate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 3 combinations Features 3 different tone type combinations selectable via DIL switch e g continuous tone 900Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Sound level 100dB Easy address setting via DIL switch Long lifespan of strobe due to the use of LEDs Integrated dual isolator with yellow status LED indicator 96 Specifications Operating voltage supply through the loop voltage Current consumption from loop max 1 2mA quiescent max 9mA sounder and strobe on Sound level 100dB A 1m distance Flash frequency 1Hz Ambient temperature 10 C to 55 C Relative
226. Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E Terminal Converter Module 16 Fold SUB58 2 Componentry used for the easy conversion of a 10 pole flat cable connector to screw termi nals The cabling of two times 8 open collector outputs as well as the triggering of relay mo dules of type RL58 1 and RL58 2 in this way can be realised flexibly and according to the individual requirements Specifications Connection technology two 10 pole flat cable connectors 16 screw terminals Ambient temperature 5 C to 50 C Dimensions L x W x H 85 x 30 x 20 mm Weight 100g Relay Module 8 Fold 60VDC RL58 1 Componentry for the switching of consumer loads via eight dry changeover contacts which can be triggered separately The componentry can be installed in Fire Detection Control Pa nels Series BC216 Series BC016 Series BC06 Series LBC and in the Burglar Alarm Con trol Panel LAC1000 1 Features Eight independent relays with one dry changeover contact each Galvanically isolated switch contacts on separate terminals Separate LED display for each relay Common positive supply Connection of trigger inputs via terminals or flat cable
227. Red WMSTR WR PO1 oo occ cece cece nee eet e eben en ene eet n en eneens 249 Strobe WM 200ISM Red WMSTR WR P02 1 cece cece cence eee eee n ene e eet eeennene 249 Accessories for Optical and Acoustic Devices 359003 359004 359008 359005 359006 359020 359021 359022 359023 359040 359043 359044 Base for Sounder amp Strobe IP44 Red EMA ELPBR 0c cece cece cece nen ene ee ne eens 251 Base for Sounder amp Strobe IP55 Red EMA ESBR 0 0 c cece cece ence ence ene neeeeeenes 251 Base for Sounder amp Strobe IP66 Red EMA ESBRS 0 0 c cc cece cen e cece ence tne ne eens 251 Lid for Sounder DBS Red DBSLIDR 0 ccc ccc ene eee n eee n tne ne teenies 252 Lid for Sounder DBS White DBSLIDW 0 cc ccc cence cence nen eee ene n enn eeenenes 252 Lid for Detector Base Sounder White 45681 292 2 0 ccc cece teen cence eee een enes 252 Lid for Detector Base Sounder Red 45681 29300 cece ccc ccc ccc ce nee een e renee ene eens 253 Mounting Plate for Sounder WB XP95 38531 810 1 0 0 cece ccc e cece eee e eee en en eee eens 253 Housing IP67 for Strobe FB XP95 29600 318 2 0 ccc cece eee teen eee een nen eeenae 253 Base Sounder amp Strobe IP24 White LPBW 0000s ccc cece cece e ene eee ence ent n eee eeenenes 254 Base Sounder amp Strobe IP44 White SDBW 0 cece ccc ccc e teen ence n ene eeeeenenes 254 Base Sounder amp Strobe IP65 White WDBW 0 cece cece cence cenc
228. Remote Test Unit Conv 300 1000 SS ECO 1000RTU 4 210210 Zone Extension Board ZEB2 1 Thermal ROR Detector Conv 1000 SS ECO1005 Thermal detector operating on the rate of rise heat detection principle in addressable conven tional technology combined maximum rate of rise detector classified as AIR maximum room height 7 5 m suitable for indoor mounting 88 Chapter 11 Conventional Detectors Series 300 ECO1000 For quick localisation in the event of an alarm each detector can be assigned an address by adding an Address Module NG58 1 to the mounting base The address of the detector in alarm condition as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are supported by the control panel Features Individual detector addressing by installing an optional address module NG58 1 Output for external remote indicator Functionality check by means of test activation with Remote Test Unit ECO 1000RTU Specifications Operating voltage Current consumption Alarm temperature Operating temperature Ambient temperature supplied through detector line voltage typ 75uA quiescent 58 C maximum heat component max 45 C 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 x 40 5 mm Colour white Weight 70g Approval VdS G201016 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventio
229. S M200E PMB 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 117 249108 Surface Mounting Box for M200 SS M200SMB 249105 Control Module 1xRel Out Anal 200 SS M201E 240 Addressable module in wall mount cabinet for the activation of external devices by means of a changeover contact suitable for 230V AC via the bi directional communication on the ADM loop using System Sensor 200 protocol The integrated dual isolator can be activated or deactivated by choosing the appropriate terminals Features Status LED 2 decadic rotary switches for setting the address from 01 to 99 Module delivery includes module box wall mount cabinet Specifications Operating voltage Current consumption Contact type Switching power per contact supplied through loop voltage approx 510uA quiescent changeover contact SA 30VDC or 5A 230V AC 169 BB072001 SAM 249106 249116 169 BB072001 SAM 0720 01 0100 Chapter 12 Analogue Detectors and Modules Series 200 500 99 Ambient temperature 20 C to 60 C Dimensions L x W x H 132 x 137 x 40 mm Colour cream transparent smoke coloured Weight 235g Approval VdS G202141 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Contr
230. SS 2351 TEM 81 241040 Optical Smoke Detector Conv 300 SS 2351E 84 242041 Thermal Max Detector Conv 300 SS 4351E 84 242042 Thermal Max Detector Conv 300 SS 5351TE 83 242040 Thermal ROR Detector Conv 300 SS 5351E Remote Program and Test Unit Conv 300 SS S300RPTU Hand held programming device for setting and reading the parameters of System Sensor Se ries 300 detectors The device can exchange data with Series 300 detectors either over short distances or combined with the Satellite Unit for Remote Programming S300SAT over di stances up to 4 5m In the Satellite Unit for Remote Programming data and time can be set This date information can be stored as timestamp of the latest maintenance date in the maintained detector Features Setting of date and time in the device Setting of the detector address Setting of the response sensitivity only with 2351E and 2351TEM Setting of the maintenance date Display of the detector contamination only with 2351E and 2351TEM Display of the detector status separately for smoke and temperature value with 2351TEM Display of the latest maintenance date Function test test activation of Series 300 detectors Specifications Operating voltage 4 5VDC 3 x 1 5V type AAA batteries 169 BB072001 SAM 0720 01 0100 246112 246150 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 113 Ambient temperature 10 C to
231. Sectional Control Panel OP BC216 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT I 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 214176 BCnet LBC Gateway N OP 6HU BCNET LBC GW The BCnet LBC Gateway allows for the integration of an LBC Fire Detection Control Panel or the main control panel of an LBC Control Panel Compound into the Global Security Sy stem network GSSnet of a Fire Detection Control Panel BCnet216 The LBC Fire Detection Control Panel is connected to the RS232C interface of the BCnet LBC Gateway which deals with the conversion between the LBC data protocol and the GSSnet data protocol Therewith the detector zones actuations alarming devices and transmitting devices connected to the LBC Fire Detection Con trol Panel can be displayed and operated by the superior Fire Detection Control Panel BCnet216 the same way as those from the BCnet216 This way up to 9700 detector zones as well as 9700 actuations can be combined in a conjoint fire detection control panel The BCnet LBC Gateway already includes the basic license for the integration of the LBC1000 main control panel If further sub control panels exist in the LBC Fire Detection Control Panel the additionally required LBC Sub Unit Licenses LBC UZ have to be ordered separately The LBC texts can be conveniently and efficiently importe
232. Snet of the Fire Detection Control Panel BCnet216 Operation and display of all events of the fire detection control panel 4 line display texts Menu controlled operation Menu controlled programming Continuous supervision of the data exchange with the j 7 control panel Power supply via the fire detection control panel Specifications Supply power 15 31VDC Current consumption at 24V 140mA normal GSSnet line length max 1200m on each side to the adjacent GSSnet mem ber with Cat 5 cable Ambient temperature 5 C to 50 C Dimensions W x H x D 200 x 300 x 65 mm Colour grey white RAL 9002 Weight 1 4kg Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 27 214108 Fire Detection Control Panel BC216 1CE INT1 Remote Display and Operating Panel ABF216 1 A1 Remote panel in the version for Austria used for operating and displaying all events of a Fire Detection Control Panel BCnet216 Functions specifications and cross references corre spond to the Remote Display and Operating Panel ABF216 1 INT1 The labels of display and operating elements as well as the displayed texts are in German language Remote Display and Operating Panel ABF216 1 D1 Remote panel in the version for Germany
233. Specifications Current consumption at 24V typ 14mA end of line resistor 5 6kOhm typ 7mA end of line capacitor 47uF Line voltage typ 20V end of line resistor 5 6kOhm typ 23V end of line capacitor 47uF Line current typ 3 7mA end of line resistor 5 6kOhm typ 0 35mA end of line capacitor 47uF Line termination 5 6kOhm or 47uF Line resistance max 50 Ohm per core Ambient Temperature 5 C to 50 C Dimensions L x W x H 103 x 58 x 15 mm Weight 34g Cross references Page Art Nr Name Type 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 166 249096 MCP Coding Module MCM 1 1 210215 Serial Interface Module SIM06 1 The Serial Interface Module SIM06 1 extends the Fire Detection Control Panel Series BC06 by one galvanically isolated RS232C interface for the connection of a serial protocol printer un Specifications Current consumption at 24V typ 15mA Interface RS232C galvanically isolated Data transfer lines RxD TxD Baudrate 1200 2400 4800Baud Type of connection D SUB connector 9 pin Ambient temperature 5 C to 50 C Dimensions L x W x H 88 x 35 x 17 mm Weight 32g Cross references Page Art Nr Name Type 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 Jer ka 169 BB072001 SAM 0720 01 0100 210212 169 BB072001 SAM 0720 01 0100 Kapitel 1 Brandmelderzentralen Serie BC06 5 Front Foil for
234. Surface Mount Box MCP5A SR3T Manual Call Point Red 200 Flexi MCP5A RP07FF The manual call point according to EN 54 11 A is accommodated in a red plastic housing and is activated by pressing in the plastic pane without breaking it The pane can be placed again into the idle position with a special key thereby resetting the detector The detector is designed for use on the ADM loop ring bus technology using System Sensor 200 protocol Features Operating instructions by symbols European Standard Activation by pressing in plastic pane without breaking it Plastic pane easy to reset Detector housing can be opened only with a special key provided 2 decadic rotary switches for setting the address from 01 to 99 Specifications Operating voltage supplied through loop voltage Current consumption 260uA quiescent Ambient temperature 10 C to 55 C Relative humidity 0 95 no condensation Protection class IP24 Dimensions W x H x D Colour 89 x 93 x 28 mm flame red RAL 3000 Weight 160g Approvals LPCB 166b 45 166b 46 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 173 245019 Surface Mount Box MCP5A SR 173 245012 Surface Mount Box MCP5A SR3T s m and 172 Chapter 17 Manual Call Points 245043 Manual Call Point Red 200 ISM Flexi MCP5A RP
235. Surv Out Anal 200 SS M201E oo ccc ccc cc cece cece ener n ene n eee eeenes 98 Control Module 1 xRel Out Anal 200 SS M201E 240 2 0 ccc c cece cece eee eee e eee ee en eeee ees 98 Control Module 1xRel Out DIN Anal 200 SS M201E 240 DIN 0 00 ccc cece eee e ene eeeeaes 99 Control Module 6xRel Out Anal 200 SS CR 6 2 0 0 ccc ccc cece cece cece net e ener e een ene eeeenes 99 Conventional Zone Module Anal 500 SS MS12ME 0 0 c cece cece cece nee e een en een eens 100 Conventional Zone Module Anal 200 SS M210E CZ 0 0 ccc cece cnn nee e een en een ens 100 Multi Module Mounting Rail MEA244 1 TR 0 0 2 c eect eee c teen et ene nee ee ene 101 Multi Module Panel Mounting MEA244 1 E oo cece cece nent e teen et ene eee ee ene 102 Limit Switch Anal 500 SS EDS500 1 2 0 0 ccc cece cee nce een e eee nee n ene eee e nee eenees 103 Monitor Module Box Anal 500 SS UMB500 1 0000 ccc ecccceceeee cece cess eeeeeeeeeeeees 103 Isolator Module Anal 500 200 SS ISM1 2 0 cece cece ene ee ne eee nee e tenet eee tenn eee 103 Acessories for Series 300 ECO1000 200 500 246008 246100 246101 246102 246140 246141 246142 246143 Detector Base Conv 400 100 300 SS B401RM oo cece cee cnet een ees 105 Detector Relay Base Conv 300 SS B324RL oo ccc ce cece cen nee nee es 105 Detector Relay Base Conv 300 SS B312RL oo cece cece cect e ene e een es 106 Detector Relay Base Conv 300 SS B312NL oo cece cece ccc nent e nee
236. T STUCK 45 aa laS aA OE AENA PUTER EA EPE AESA T ERKSA 221 Pipe Fitting ADA MUFFE 32245026220 eige ee Ser 221 Pipe Fittinig CAP KAPPE drepe el E Cawbintia oe Lee er redere 2 222 Pipe Connector 25 RKL25 museene ee hates baa Oe Le seated tak De Ste ee GE 222 Check Valve Spring loaded R25 RVFED 25 annonuenenannnnennnnnenenananunennnnnuenennnusner 222 Ceiling Duct complete DDF KOMPL 0c cee cece eee ene e ett eee n ee eee nent enn nee eee 222 Aspitation Tube DN 1259 uns 52s eae rer EN Bed oe AE es DE 222 Air Filter for ASDS complete LF RAS 2 2 0 0 ccc cece cence cece e eee tenn eee ten tenet ee nn ene eeaee 222 Three way Ball Valve 3MKH o23 o 5c keen hee Ube Fed cee een Paes ened SAVANNE Besa D 222 Condensate Separator DN25 KABS 25 1 2 0 cece ccc neee een eee e eet bn nee e enn nese ee 222 Aspiration Hole Reduction Foils Overview 0 cece eee c eee ee eee e ec ee nett enn nn ne eee 223 Banderole for Aspiration Hole Reduction Foil BA AREDF 0 cece cece cc ee eee e eee 223 Plastic Clip for Aspiration Hole Reduction Foil DF KC AREDF TK cece ee eens 223 Glu Fangit 0 12kg KLEB RAS 01 so 20 aa sted ek oa ine Set dees bee teen cabo bedi esac teva 223 Glue Tangit 0 25kg KLEB RAS 02 ornononeanannenevnnnerernenerenvenenrereeneneueereneereve 224 Glu Tangit 0 5kg KLEB RAS 05 eder bakes area 224 Glu Tangit Iks KEEB RAS von un skiten sjekka Ft SRG pened Bee ee does ae
237. The de vice key is placed on a label on the bottom side of the module Parameterisation and maintenance can be accomplished without limitations with PARSOFT once control panel and PC are connected There is no difference between local or remote ac cess of the control panel 169 BB072001 SAM 0720 01 0100 54 Chapter 5 Interfaces 223028 Features Remote parameterisation and maintenance via analogue telephone line Specifications Operating voltage plug in adapter Supply voltage FZP2 1 Current consumption at SV Transfer rate Ambient temperature Dimensions L x W x H Weight without plug in adapter Cross references Page Status LED indicators for supply voltage and data transfer Includes pre assembled serial data cable for SIM216 1 length approx 1 8m Includes pre assembled telephone cable length approx 2m Plug in power adapter provided 100 240V AC 50 60Hz 52 295 52 SVDC max 120mA 38400Baud 0 C to 45 C 85 x 40 x 25 mm 70g Art Nr Name Type 214231 Interface Adapter Module IAM216 1E 218008 Parameter Setup Software PARSOFT 2 214025 Serial Interface Module SIM216 1 Remote Access Module GSM GPRS FZG2 1 The Remote Access Module FZG2 1 is designed for the transmission of configuration data of Fire Detection Control Panel Series BC016 or BC216 via a GSM connection Remote access of control panels with parameter setup software PARSOFT 1 and PARSOFT 2 can be established in t
238. Unit PTU288 1 can be installed in combination with LED connection modules in any housing This componentry is prepared for mounting in the LST standard grid and comes with the required mounting material The remote tableau drive unit is actuated via the INFO bus of the control panel A Serial In terface Module SIM016 3 is required to connect the PTU288 1 to a Fire Detection Control Panel Series BC016 whereas connection to the Fire Detection Control Panel Series BC216 does not require any additional modules Up to 6 Remote Tableau Drive Units PTU288 1 can be connected to one control panel Features 5 parameterisable inputs for control functions Possible connection of up to three LED Display Fields LAB48 x or LED Connection Mo dules LAM48 1 in any combination LEDs can be used to indicate the conditions of detectors detector zones actuations actuation elements alarming devices transmitting devices extinguishing systems or floo ding zones and the most important system conditions e g summary alarm fault or dis abled condition depending on the parameter setup Individual or summary display of events from detectors detector zones actuations actua tion elements alarming devices and transmitting devices depending on the parameter setup USB interface for parameter setup using the parameter setup software PARSOFT PARSOFT version V1 21 or higher is required for parameterisation of the PTU288 1 Setable baudrate and INF
239. WG GELB E 1 169 2171619 Replacement Glass for Manual Call Point Yellow ET SCH HM GE 170 249024 Special Designation for Manual Call Point HM BESCH MCP Coding Module MCM1 1 The MCP Coding Module MCM1 1 enables the combined connection of automatic detectors and manual call points to one detector line of a Fire Detection Control Panel Series BC06 The control panel can distinguish activation of an automatic detector and of a manual call point with the help of the coding module and can react accordingly The coding module is optionally installed in every manual call point on the respective zone Specifications Current consumption at 24V typ 20mA detector activated Ambient temperature 5 C to 50 C Dimensions L x W x H 30 x 18 x 4 mm without leads Weight 6g Jer as 169 BBO72001 SAM 0720 01 0100 249633 249634 169 BB072001 SAM 0720 01 0100 Chapter 17 Manual Call Points 167 Cross references Page Art Nr Name Type 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 Protective Cover V2A for Manual Call Point Red WG ROT E 1 Red powder coated protective cover made of V2A stainless steel used as supplement for ma nual call points installed in open areas Features Top side and lateral rain protection Mechanical protection Cable entry from back side or alternatively bottom side through the cable gland of the manual call point Dimensions W
240. WK2 1 can be provided by the customer 169 BB072001 SAM 0720 01 0100 223032 223033 169 BB072001 SAM 0720 01 0100 Features Chapter 5 Interfaces Status LED for display of the data flow Automatic adaptation to the transfer rate of the GSSnet Easy DIN rail mounting Connection of the cables to terminals Specifications Supply voltage Current consumption at 24V Line length Number of wires required Cable diameter Line capacity Ambient temperature 21 6 to 26 4VDC typ 150mA max 4000m 4 min 0 3mm max 42pF m 5 C to 50 C max 95 no condensation 75 x 129 x 169 mm 250g Art Nr Name Type 57 Relative humidity Dimensions W x H x D Weight Cross references Page 20 294 2199998 Fire Detection Control Panel BCnet216 Description 229010 Voltage Stabiliser 24VDC STAB24 1 Multimode Fibre Gateway BCnet216 LWL MM 2 The gateway LWL MM 2 interconnects sectional control panels of the Fire Detection Con trol Panel BCnet216 via multimode optical fibres An optical fibre cable with at least 2 free multimode fibres is needed for the connection If required only specific way Features Status LED indicator to display data transfer All parameters to be set via a DIL switch Small dimensions To be mounted on a DIN rail Specifications Operating voltage Current consumption at 24V Length of optical fibre Type of fibre Optical budget Ambient temperature
241. a plastic housing for application in conventional technology designed for indoor mounting A pulsed infrared beam emitted from the transmitter receiver unit is reflected by a reflector mirror Alarm evaluation is achieved by false alarms detection of a reduced intensity of the light beam Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system There by the response sensitivity of the detector is kept constant for a long time thus constituting an effective measure for preventing ee p The response sensitivity of the detector can be set to 6 different levels Four levels show a fixed alarm threshold 2 other levels provide an adaption of the detector to changing ambient conditions by means of a variable alarm threshold The detector is delivered with a reflector which can be used for ranges from 5 to 70m A three part accessory is available to extend the range of the detector from 70 to 100m Features Detection of clear and dark smoke Sender and receiver integrated in a single housing Sealed detector housing Receiver LED display for alarm and fault as well as display for preset values and commis sioning support Adjustment screws for an easy alignment of the detector 169 BB072001 SAM 0720 01 0100 244023 169 BB072001 SAM 0720 01 0100 Chapter 20 Special Detectors 197 Test filter for optimal commissioning incl
242. age for anchoring Low net weight Surface made of polished stainless steel Specifications Dimensions W x H x D Installation of FSK700 2 possible with flush mounting frame Column prepared for installation of the Unblocking Element FSE MP1 half cylinders Flexible armoured tube for different types of cables 400 x 1250 x 300 mm Name Type Fire Brigade Key Box FSK700 2 D1 Fire Brigade Key Box FSK700 2S2 D1 Flush Mounting Frame for FSK700 2 EZ700 2 D 1 Weight approx 60kg Cross references Page Art Nr 257 265740 258 265742 259 265751 265 265661 Unblocking Element for Half Cylinder FSE MP1 169 BB072001 SAM 0720 01 0100 265660 265661 268009 169 BB072001 SAM 0720 01 0100 Chapter 27 Fire Brigade Key Boxes and Accessories 265 Unblocking Element F0345 VdS approved unblocking element made of stainless steel with micro switch as change over contact for activation of a detector zone and a 1m long connection cable Drill protected design pre pared with a special cylinder Specifications Dimensions x L 42 x 80 mm Approval VdS G192034 Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 263 265762 Steel Column V2A for F0345 Strobe HSFSK700 2 D3 263 265761 Steel Column V2A for F0345 HSFSK700 2 D2 Unblocking Element for Half Cylinder FSE MP1 VdS approved unblocking element made of stainl
243. ain operating unit or an optionally connected Display and Ope rating Front Panel ABP216 1E 3 The functions and features of the Fire Detection Control Panel Module BCM216 3LG are restricted to the processing of 2 ADM loops the connection of conventional detector lines is not possible control panel functions are not supported either please see also the detailed product description in the catalogue Additional features and functions when operating in analogue ADM loop technology provi ded that Loop Interfaces LIF64 1 are used in the sectional control panel Note The Fire De tection Control Panel Module BCM216 3LG integrates 2 loop interfaces ADM loop supports 198 elements 99 detectors and 99 modules using System Sensor 200 protocol or 126 elements detectors and or modules using Apollo Discovery protocol Each ADM loop can be split in up to 128 detector zones the control panel can support a total of 144 detector zones ADM loop wiring can be accomplished as ring branch or any given combination of sectional rings and branches using two core unscreened cables ADM communication is achieved by means of bi directional data exchange between the fire detection control panel and every single element on the ADM loop ADM failure strategy secures full functionality of all elements connected to the ADM loop in case of wire breakage At short circuit all elements not affected by the short circuit thanks to the installed isolator modules a
244. al components of the sensor pipe network One packing unit contains 0 125 litre Cleaner Tangit 1l REIN RAS Cleaning liquid for removal of dirt residual fat etc which is used before gluing individual components of the sensor pipe network One packing unit contains I litre 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 Chapter 23 Labels 225 23 Labels 249211 Detector Label Sheet 8pcs BME BEZ BOG The labels serve for the marking of an automatic fire detector with detector zone and detector number It consists of a sturdy white plastic card to which an adhesive label can be sticked and signed Direct marking of the plastic card is also an option An A4 size sheet with 8 la bels and 8 plastic cards are included in the delivery LST LABOR STRAUSS SOBRUNGSANAGENIAG GEELSOMET wh Specifications Marking area W x H 80 x 40 mm Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 151 246025 Detector Base Anal Apo ASA 45681 210 107 246140 Detector Base Conv 1000 SS ECO1000BR1000 105 246008 Detector Base Conv 400 100 300 SS B401RM 149 246021 Detector Base Conv 60 65 Apo GSA 45681 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 79 246070 Detector Base FC600 FC600 BR 111 246012 Detector Base Filtrex Anal 500 SS B524FTXE 79 246071 Detector Base with Diode FC600 FC600 BRD 111 246018 Detector Heater Ba
245. al Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 Sounder Strobe WM 200ISM Red Multitone 100dB WMSST RR P02 The addressable multitone sounder with strobe is accommodated in a red plastic housing and is prepared for outdoor and indoor mounting The unit is mounted on a base for signalling de vices not provided The sounder is actuated as a module using System Sensor 200 protocol and is powered via the ADM loop The sounder is always activated La together with the strobe A dual isolator is integrated in the componentry At short circuit it maintains the function of ADM elements that are not affected by the short circuit Depending on the parameter setup of the Fire Detection Control Panel Series BC216 and the system condition the panel can activa te the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combinations The sound level is adjustable in 3 steps but depends also on the chosen tone type The power consumption is dependent on the tone type and the adjusted sound level Features 32 different tone type combinations selectable via DIL switch e g continuous tone 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Low power consumption Integrated dual isolator Sound level adjustable in 3 steps low medium high Long lifespan of strobe d
246. al LPCB 1991 01 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 110 246013 Isolator Detector Base Anal 500 200 SS B524IEFT 1 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PA58 1 242002 Thermal Detector Anal 200 SS 5251EM Addressable thermal detector operating on the heat principle for application on the ADM loop using System Sensor 200 protocol suitable for indoor mounting The detector can be classi fied AIS AIR or BS parameterisation in a compatible fire detection control panel determi nes the class to be used as AT Specifications Operating voltage Current consumption Alarm temperature Class A1S Class AIR Class BS Operating temperature Features Continuous transmission of the current measured value to the fire detection control panel 2 decadic rotary switches for setting the physical address from 01 to 99 Output for external remote indicator Mechanical theft protection supplied through loop voltage max 200A quiescent 58 C maximum detector max room height 7 5m 58 C rate of rise detector max room height 7 5m 78 C maximum detector max room height 6m Classes AIS and AIR max 45 C Class BS max 68 C Ambie
247. all Point Blue Conv HM 5 11 18 02 163 245389 Manual Call Point Grey Anal SS HM 7 22 03 02 157 245356 Manual Call Point Red Conv HM 3 11 01 02 166 245396 Manual Call Point Yellow Anal Apo HM 1 32 05 02 162 245392 Manual Call Point Yellow Anal SS HM 1 22 05 02 159 245355 Manual Call Point Yellow Conv HM 1 11 05 02 245040 Manual Call Point Red 200 Glass MCP5A RP07FG The manual call point according to EN 54 11 A is accommodated in a red plastic housing and is activated by breaking the glass pane The detector is designed for use on the ADM lo op ring bus technology using System Sensor 200 protocol Features Operating instructions by symbols European Standard Activation by breaking glass pane Glass pane easy to replace Detector housing can be opened only with a special key provided 2 decadic rotary switches for setting the address from 01 to 99 Specifications Operating voltage supplied through loop voltage Current consumption 260uA quiescent Ambient temperature 10 C to 55 C Relative humidity 0 95 no condensation Protection class IP24 Dimensions W x H x D 89 x 93 x 28 mm Colour flame red RAL 3000 Weight 160g Approvals LPCB 166b 45 166b 46 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 173 249213 Glass for MCP Series 10pcs G21140 35 214021 Loop Interface LIF64 1
248. alling devices 43mm Colour red Weight 112g Cross references Page Art Nr Name Type 243 355162 Sounder Strobe WM 200 Red Multitone 100dB WMSST RR POI 244 355163 Sounder Strobe WM 200ISM Red Multitone 100dB WMSST RR P02 242 355160 Sounder WM 200 Red Multitone 100dB WMSOU RR PO1 242 355161 Sounder WM 200ISM Red Multitone 100dB WMSOU RR P02 249 356140 Strobe WM 200 Red WMSTR WR PO1 249 356141 Strobe WM 200ISM Red WMSTR WR P02 Mounting Plate for Sounder 200 5pcs DBSPD 5 The white mounting plate enables the surface cabling of sounders detector base sounders and strobes Series WMS and IBS in conjunction with the Base Sounder amp Strobe IP24 white LPBW gt gt Specifications Dimensions x D 107 x 17 mm Additional depth of signalling devices 10mm Weight 24g Colour cream Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 169 BB072001 SAM 0720 01 0100 27 Chapter 27 Fire Brigade Key Boxes and Accessories Fire Brigade Key Boxes and Accessories 257 265740 169 BB072001 SAM 0720 01 0100 Fire Brigade Key Box FSK700 2 D1 The fire brigade key box FSK700 2 D1 is certified according to VdS 2105 and serves for the theft proof and copy protected safekeeping of a key which allows the fire brigade fast and non violent access to the building in the event of fire Housing and blind frame are made of F 5mm stainless steel and therefore provide not only
249. amming Cable BC216 RS232 PK216 1 60 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 oo cece ccc eee cence enn e eee 168 Protective Cage BWS 1 D1 2 0 eee eee eee eee ee 121 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 0 0 0 0 ccc cece eee ee eee nneeeee 167 Protective Cover V2A for Manual Call Point Red WG ROTET ec Sd5 c ccaaredeies ariere tenance 167 Protective Cover V2A for Manual Call Point Yellow WG GELB E 1 0 cece cece eee p ERRERA TIRES 168 Protective Cover for FSK700 2 WSD FSK 259 Protocol Interface Anal 200 SS IST200 182 Protocol Interface Anal XP95 Apo API 55000 855 180 Protocol Printer Dot Matrix LX300 005 66 Protocol Printer Thermal DPU414 30B 65 249202 249201 249203 246010 250901 244024 222010 222004 329012 223028 223027 250013 250030 250036 250033 250705 250038 250050 250048 250039 250035 250049 250046 250037 250047 251001 246111 252012 250009 250016 250018 250015 246150 249047 2171612 2171621 2171620 2171619 229004 223041 228006 228004 228003 246112 244622 244628 244624 244632 244631 244634 244111 244248 210112 210215 214025 223033 223024 223026 249051 249023 217001 R RF Interface Anal SS MSOORFE AS RF Interface 4Rel FUIF511 27D RF Interface 4Rel M400RFE AS Recessed Mounting Kit SS RMK400 Redundant Transmission Adapter
250. amp 1000N 1340 The magnetic clamp is used for fixing fire doors or smoke compartments It consists of a base plate for wall mounting and flexible wires for con nection as well as an armature plate with a tilt joint as counterpart Specifications Operating voltage 24VDC Power consumption 2 4W Adhesive force approx 1000N 100kg Working temperature 5 C to 50 C Dimensions L x W x H magnet 65 x 65 x 38 mm armature plate 60 x 60 x 48 mm Weight 650g Magnetic Clamp Reset 1000N 1360 The magnetic clamp is used for fixing fire doors or smoke compartments It consists of a sur face wall mount housing with lateral interrupt button and an armature plate with a tilt joint as counterpart 278 Chapter 29 Fire Controls w Specifications Operating voltage Power consumption Adhesive force Working temperature Dimensions L x W x H Weight 24VDC 2 4W approx 1000N 100kg 5 C to 50 C magnet 95 x 95 x 40 mm armature plate 60 x 60 x 48 mm 930g 261010 Magnetic Clamp Reset 150mm 1000N 1380 15 The magnetic clamp is used for fixing fire doors or smoke compartments and is suitable for Specifications Operating voltage Power consumption Adhesive force Working temperature Dimensions L x W x H Weight surface mounting on floors ceilings or walls It consists of a 150mm bracket adjustable to 180mm with interrupt button and an armature plate with a tilt joint as counterpart 24VDC 2 4W approx
251. an be assigned an address by adding an Address Module NG58 1 to the mounting base The address of the detector in alarm condition as well as the as signed text is displayed directly on the fire detection control pa nel provided that these functions are supported by the control panel Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept constant for a long time thus constituting an effective measure for pre venting false alarms 86 Chapter 11 Conventional Detectors Series 300 ECO1000 Features Individual detector addressing by installing an optional address module NG58 1 Drift compensation Output for external remote indicator Insect screen Specifications Operating voltage Current consumption Ambient temperature Functionality check by means of test activation with Remote Test Unit ECO1000RTU supplied through detector line voltage typ 65uA quiescent 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 x 32 5 mm Colour white Weight 75g Approval VdS G201060 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 107 246140 Detector Base Conv 1000 SS ECO1000BR 1000 107 246141 Detector Relay Base Conv 1000 SS ECO 1000BREL24L 8 210110 Detector Zone Extension MGE8
252. ananeennnner 276 Magnetic Clamp Reset 150mm 500N 1370 15 sevannnnnennnnnvnvenannverrnnrrvvenrnrvevennner 276 Magnetic Clamp Reset 300mm 500N 1370 30 sevennnnvvnnnnnnnvenanaveernnrrvvenrnrvevennner 277 M gn tic Clamp 1000N 1340 vii sce si toate nesa to ede ped sed GTV SE ES 277 Magnetic Clamp Reset 1000N 1360 orvenennnnnvnnnnnverrnnnanvvnnnnuevennnanuennnnsauenener 277 Magnetic Clamp Reset 150mm 1000N 1380 15 snsunnvnennnnnnenennvnvvrnnnnvevenanaveerrnner 278 Magnetic Clamp Reset 300mm 1000N 1380 30 aoroavvvvnananvenennvrvvrennnvevenanavverenner 278 Magnetic Lock Clamp 4900N 1390 oooovenennnnnvnnnnnvevenanavvernanuevenananuuennnanuenennnr 279 Magnetic Lock Clamp LED 4900N 1392 eronvnvevennvnnerennnvevenannveervanauvennnanevennner 279 Magnetic Lock Clamp 2750N 1388 aooovananananvnnnanvevenanavverrnnuevenanaueuennnanuenrnnr 279 169 BB072001 SAM 0720 01 0100 30 31 32 33 34 169 BB072001 SAM 0720 01 0100 Telephone Dialling Devices 320007 320008 329012 329013 329014 329015 329016 Automatic Telephone Dialling Device TWG805 1A arsruannnnnenennnnnuennnnnavernnnnvevennner 281 Automatic Telephone Dialling Device TWG805 1D 2 eee ence eee t eee e eee eee 282 Relay Module RIA04 1 nedenfra ett ao ke eee Vielen be vue Mek epee SE 283 Line Monitoring Module TUM805 1 0 0 ccc ccc ce cece e cece ences eee EEEE S 284 Dialogue M dule DPM805 1 pek airneo n ei ioe set dk nia
253. anel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Dutch language Remote Display and Operating Panel ABF216 1 SK1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Slovak language Remote Display and Operating Panel ABF216 1 RUS1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Russian language Remote Display and Operating Panel ABF216 1 SLO1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Slovenian language Remote Display and Operating Panel ABF216 1 I1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Italian language Remote Display and Operating Panel ABF216 1 PL1 Functions specifications and cross references correspond to the Remote Display and Opera ting Panel ABF216 1 INT1 The labels of display and operating elements as well as the dis played texts are in Polish language
254. anel OP BC216 2 D1 6 ccc cece nce e ee en tenn en ees 24 BCnet Sectional Control Panel OP BC216 2 B1 oo ccc cece ccc e cnet tenets 24 BCnet Sectional Control Panel OP BC216 2 CZ1 oo ccc cece cece cence eee n een een ens 24 BCnet Sectional Control Panel OP BC216 2 H1 0 cece cece nce nent enn ents 24 BCnet Sectional Control Panel OP BC216 2 NL1 oo cece cnn enn eee nent nenneee 25 BCnet Sectional Control Panel OP BC216 2 SK1 0 ccc cece cece ncn e cence een ens 25 VI 214079 214081 214085 214087 214089 214005 214034 214108 214100 214611 214158 214164 214109 214105 2149997 214204 214205 214234 214208 214200 214615 214209 214020 214021 214022 214023 214024 214030 214032 214036 214031 214003 214130 214232 214028 214128 214029 214230 212034 212030 212029 212033 214129 212031 227009 214601 212027 212028 212032 BCnet Sectional Control Panel OP BC216 2 HR1 oo ccc nee e ener e teen enens 25 BCnet Sectional Control Panel OP BC216 2 RUS1 0 ccc cece cnet e nen e nen teens 25 BCnet Sectional Control Panel OP BC216 2 SLO1 0 ccc cence ener cence eee eeenes 25 BCnet Sectional Control Panel OP BC216 2 T1 oo ccc cece cence nnn ee ee ene ene ees 25 BCnet Sectional Control Panel OP BC216 2 PL1 oo ccc cc ccc cc cece tenet nen teenies 25 BCnet Sectional Control Panel No Operation BC216 3 1 0 cece cece cece eee eect eee e eens 25 BCnet Sectional Control Panel Extension BCE21
255. anual Call Points MCP5A RP07Fx and MCP5A RPO08Fx The box is designed with 3 auxiliary terminals for simple wiring Specifications Protection class IP24 Dimensions W x H x D 87 x 87 x 32 mm Colour flame red RAL 3000 Weight 60g Cross references Page Art Nr Name Type 171 245042 Manual Call Point Red 200 Flexi MCP5A RPO7FF 170 245040 Manual Call Point Red 200 Glass MCP5A RPO7FG 172 245043 Manual Call Point Red 200 ISM Flexi MCP5A RPO8FF 170 245041 Manual Call Point Red 200 ISM Glass MCP5A RPO8FG 249213 Glass for MCP Series 10pcs G21140 The printed glass pane for replacement is inserted for resetting a manual call point MCP5A RP07FG MCP5A RPO8FG or 55000 905 after activation Cross references Page Art Nr Name Type 172 245014 Manual Call Point Anal XP95 Apo 55000 905 170 245040 Manual Call Point Red 200 Glass MCP5A RP07FG 170 245041 Manual Call Point Red 200 ISM Glass MCP5A RPO8FG z am ad 169 BB072001 SAM 0720 01 0100 174 Chapter 18 Devices for Hazardous Areas 1 8 Devices for Hazardous Areas 240015 IS lonisation Smoke Detector Conv 100 SS 1151EIS Smoke detector for hazardous areas operating on the ionisation principle in conventional technology unipolar chamber in a dual system consisting of a sensing and reference chamber for automatic compensation of environmental influences and of flat design suitable for in door mounting The detector 1151EIS must always be con nected via a safety barrier
256. approved for the respective detector Particular attention must be paid to the compliance with country specific regulations Features Output for external remote indicator Mechanical theft protection Insect screen Functionality check by means of test activation with magnet Service plug sockets for testing with the Detector Testing Device MOD400R Specifications Ignition protection intrinsically safe Ex classification EEx ia IIB T5 Current consumption at 24V typ 40uA quiescent Ambient temperature 0 C to 50 C Relative humidity 10 to 93 no condensation Radioactive compound Am241 0 5uCi 18 5kBq Dimensions x H 103 x 42 mm Colour cream Weight 104g Approval BASEEFA03ATEX0156X VdS G296051 Cross references Page Art Nr Name Type 105 246008 Detector Base Conv 400 100 300 SS B40IRM 177 228003 Safety Barrier Conv ES58 2 242015 IS Thermal ROR Detector Conv 400 SS 5451EIS Heat detector for hazardous areas operating on the rate of rise heat detection principle in conventional technology combined maximum rate of rise detector assigned to class I maxi mum room height 7 5 m suitable for indoor mounting The detector 5451EIS must always be connected via a safety barrier approved for the respective Per detector Particular attention must be paid to the compliance 4 2 A E with country specific regulations KF Features Output for external remote indicator Mechanical theft protection Functionality c
257. as des 216 Front FOLEWETP 2 yian anen eea orae bias avarter Gr o E E EE a E a A sin gree svidd 216 Aspiration Smoke Detection System Housing TT 1 2 0 0 0 occ eee cece ee ee eee n eee e ee 217 Detector Module DM TT 80 L irreg nea keert net e EEn abie Ki ahihi as BER ee ah egei E 217 Detector Mod le DM TT 25 L rraren a E E E E eo ER nr NE 218 Detector Module DM ET 05 E irer fer ea E E Mak soe eee Se ae eh EE 218 Front Fol FW PT nse Anar A E E EEEL APA EER REE el E ER EEE E N a all 218 Aspiration Smoke Detection System T SS aanunuenenannnnennnnnenenananuenenaanuenennnuunenner 219 Aspiration Smoke Detection System VLS 304 srvvnnnnnenennnannenrnnevevrnnnnuenenasaueenner 220 Accessories for Aspiration Smoke Detection Systems 244111 244248 244112 244113 244114 244115 244116 244118 244119 244125 244235 244240 244201 244241 244237 244236 2449999 244233 244234 244128 244129 244130 244126 244131 244127 Sensor Pipe PV C ROHR PY C 2 4s sed sd speed das esse o A na T Gee kake Geeks 221 Sensor Tube PVC 25 SCHL PVC 25 nnvnnnevnnnvanenananvenenanauverennuanenannnuueennnnueeer 221 Pipe Fitting BOW90L BOGEN 90 aooouennnnvnnenananvennnnnnuvernanuenenannuuuennnanuenenner 221 Pipe Fitting BOW90S WINKEL 90 rsi a a RE E A EEE E EE a 221 Pipe Fitting BOW45 WINKEL 45 eoooouenunnnnanenananuennnnnnuuernnnunnenannuunennnanuenennnr 221 Pipe Fitting 190 T STUCK90 oxic24 a crcunte dn rede Lan eet end GS ned 221 Pipe Fitting T45
258. ase is suitable for accommodation of fire detectors Series XP95 and Discovery v GER j The sounder is actuated using Apollo Discovery protocol and X powered via the ADM loop Depending on the parameter setup gt of the Fire Detection Control Panel Series BC216 and the sy N pus RE stem condition the panel can activate the sounder with tone A or B The unit contains a dual isolator Features Tone A alternating tone 581Hz for 1s 870Hz for 1s Tone B interrupted tone 870Hz 1s ON 1s OFF Low power consumption maintained Specifications Operating voltage Current consumption from loop Sound level Sound level adjustable via DIL switch Simple address setting of inserted detector by code card in detector base At short circuit the function of loop elements that are not affected by the short circuit is supply through the loop voltage typ 200uA quiescent typ 5mA sounder on 55 75dB A or 75 91dB A Im distance Ambient temperature 20 C to 60 C Protection class IP21 Dimensions x H 115 x 38 mm Colour white Weight 140g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359021 Lid for Detector Base Sounder Red 45681 293 252 359020 Lid for Detector Base Sounder White 45681 292 35 214021 Loop Interface LIF64 1 253 359022 Mounting Plate for Soun
259. ase of wire breakage on the ADM loop line At short circuit all elements not affected are fully operable thanks to the installed isolator modules In addition to the main processor an independent CMOS processor per ADM loop is in stalled to ensure the alarming capability even at system failure Transmission of an alarms via BCnet redundant alarm line even in case of multiple line faults in the GSSnet or at system failure of the BCnet sectional control panel Specifications Supply voltage 21 to 30VDC Current consumption at 24V Idle loop current Total loop current Idle loop voltage Loop line resistance Number of ADM loops Number of detector zones Ambient temperature Dimensions W x H x D Weight Cross references Page 140mA without detectors typ 300uA per detector module max 300mA at reduced line resistance typ 26V Apollo Discovery or typ 29V System Sensor 200 max 50 Ohm per core 2 max 128 per loop max 144 in total 5 C to 50 C 248 x 222 x 28 mm approx 675g Art Nr Name Type 25 23 214005 BCnet Sectional Control Panel No Operation BC216 3 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 Fire Detection Control Panel BC216 1CE INT1 The Fire Detection Control Panel BC216 1CE INT1 is a modularly designed compact con trol panel in 19 slide in technology for small and medium size fire detection systems Depen ding on the boards inserted you can connect fire detectors faul
260. ated steel sheet which is prepared for ac commodating 2 function modules Conventional Detector Interface GIF8 1 or Loop Interface LIF64 1 one Fire Briga de Interface FWI2 1 one Fire Brigade Interface Additional Board FWZ2 1 one LED Display Field LAB48 x a Serial Interface Module SIM216 1 and further optional modules as well as a stand by battery of 2 x 12V max 22Ah A summary of the extensive functions and features are provided in the description of the Fire Detection Control Panel BCnet216 No 2199998 The labels of display and operating ele ments as well as the displayed and printer texts are in English language Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 28VDC Output peak current max 1 8A Connection of external devices typ 0 8A site specific Current consumption at 24V typ 125mA without optional modules Ambient temperature 5 C to 50 C Dimensions W x H x D 420 x 520 x 120 mm Colour grey white RAL 9002 Weight without batteries approx 6kg Approval VdS G201017 Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 25 214005 BCnet Sectional Control Panel No Operation BC216 3 50 223009 Control Zone Module SLM1 2 35 214020 Conventional Detector Interface GIF8 1 45 214601 Cover IP54 for BC216 GEH IP54 BC 1 D1 58 218023 ESPA 4 4 4 Interface License ESPA SS 47 218024 Extinguishing
261. ating and display board on the front side of the housing includes LED indicators for the display of operating conditions and fault conditions and allows for the reset of the internal buzzer For the labelling of the LED indicators and the button insertable labelling strips in various languages are provided Specifications Dimensions W x H x D 478 x 266 x 20 mm without power supply module Colour light grey RAL 7035 Weight without installations approx 1 4kg Cross references Page Art Nr Name Type 291 317020 Power Supply Module NTM2402 1 292 317021 Power Supply Module NTM2408 1 Power Supply Housing NTG24 2 The Power Supply Housing NTG24 2 accommodates one Power Supply Module Series NTM The housing in a stable powder coated steel sheet design is prepared for wall moun ting Besides the power supply module it provides space for the installation of stand by batte ries 4 x 12V max 85Ah one Relay Module RL58 1 or RL58 2 and one Multi Module MEA244 1 E The operating and display board on the front side of the housing provides LED indicators for display of operating conditions and fault conditions and allows for the reset of the internal buzzer For the labelling of the LED indicators and the button insertable labelling strips in various languages are provided Cable entry can either be on the top side or bottom side of the housing One flange plate with apertures to break out and two Battery Brackets BK24 1 are provided with
262. ations Operating voltage 8 5 to ISVDC Current consumption typ 20uA quiescent 50mA active Contact rating 1A at 30VDC Ambient temperature 20 C to 70 C Relative humidity 5 to 93 no condensation Dimensions x H 127 x 29 mm Colour cream Weight 96g 246102 Detector Relay Base Conv 300 SS B312NL Mounting base for automatic fire detectors Series 300 with integrated relay output suitable for indoor surface mounting The mounting base is designed for the connection to control pa nels with a 12VDC operating voltage and must therefore not be connected to Fire Detection Control Panels Series BC06 BC016 and BC216 The relay output is activated by the alarm condition of the inserted detec tor both the detector and the relay output are automatically re set several seconds after the fire alarm detection Features Multi useable terminals with secure screw fitting Relay output with dry changeover contact Mechanical theft protection Specifications Operating voltage 8 5 to ISVDC Current consumption typ 20uA quiescent 50mA active Contact rating 1A at 30VDC Ambient temperature 20 C to 70 C Relative humidity 5 to 93 no condensation Dimensions x H 127 x 29 mm 169 BB072001 SAM 246140 246141 169 BB072001 SAM 0720 01 0100 Colour Weight Chapter 13 Acessories for Series 300 ECO1000 200 500 107 cream 96g Detector Base Conv 1000 SS ECO1000BR1000 Mounting base for automatic fire
263. attery for ECO1000RTU 6V 476A 2 0 cece cece ect t nee ett n tne e een nen e ee 114 246006 Base Adapter SS MZP500 1 0 cece ccc erent eee t nnn e ee etn eee e tenn ee eee 114 246009 Surface Mounting Kit SS SMK400 0 eee eect e ene e ec tee eect enn e ne eeeannes 115 246010 Recessed Mounting Kit SS RMK400 2 02 02 eee e eee cet c ene e eee tenet ee nnn nee e ees 115 249012 Wet Base Shroud SS WBT arnnnnnenanannenennnnnvrnrnnnnnvennnnuenennnanuenennnanenananuener 116 246017 Cover Plate for Base Bx01 Bx24 BC Bx01 1 0 0 c cent cnt n nee e enn ene e ees 116 249109 Base for Mounting Plate for M200 SS M200E PMB cece eee ee eee ee eee e eee en eee e es 116 249110 Base for Carrier Rail for M200 SS M200E DIN 2 0 eee cece eee teen eee etn ee ne eee 117 249108 Surface Mounting Box for M200 SS M200SMB cece cece eee cee e ee eet e eee eeeenn ees 117 249111 Surface Mounting Box for MS200 SS M200SMB KO 20 ee cece cece eee cette eee ee enn ees 117 249117 Surface Mounting Box for Multimodule SS M200 SMB MM 0e ee ee cence eee eee eee e es 118 249004 Surface Mounting Box for M500 SS SMB500 oo c cee cence cette nen e nnn n ee ees 118 249014 Power Supply Unit for Detector Heater MH TR1 occ cece cee e eect nee n eens 119 249027 Detector Heater Anal 500 200 SS MH500 1 0 2 eee cece eee nent ete en eee e enn en ees 119 249020 Address Module Conv NG58 1 isesi innorari eee eile Sed eee
264. ature 25 C to 70 C Relative humidity 10 96 no condensation Dimensions x D 115 x 68 mm incl Base LPB W Colour red Weight 204g Approval VdS G206076 Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 255 359041 Base Sounder amp Strobe IP44 Red SDBR 256 359042 Base Sounder amp Strobe IP65 Red WDBR 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Sounder Strobe WM 200 Red Multitone 100dB WMSST RR P01 The addressable multitone sounder with strobe is accommodated in a red plastic housing and is prepared for outdoor and indoor mounting The unit is mounted on a base for signalling de vices not provided The sounder is actuated as a module using System Sensor 200 protocol and is powered via the ADM loop The sounder is always activated together with the strobe Depending on the parameter setup of the Fire Detection Control Pa nel Series BC216 and the system condition the panel can activate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combinations The sound level is adjustable in 3 steps but depends also on the chosen tone ty pe The power consumption is dependent on the tone type and the adjusted sound level Features 32 different tone type combinations selectable via DIL switch e g continuous tone
265. atures Robust aluminium die cast housing with a door aperture angle of more than 180 Function marking HAUSALARM replaceable Optical activation indication by means of LED Latching default or non latching push button Easy to replace standardised glass plate Individual detector addressing by connecting an optional ad dress module Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 Specifications Operating voltage Ambient temperature Protection class Dimensions W x H x D supplied through detector line voltage 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm Colour sky blue RAL 5015 Weight 400g Approval VdS G202034 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 8 210110 Detector Zone Extension MGE8 1 49 210216 Extinguishing Board BC06 EXB1 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 169 BB072001 SAM 0720 01 0100 245417 245355 169 BB072001 SAM 0720 01 0100 Chapter 17 Manual Call Points 159 169 219006 Key for Manual Call Point SCH HFM HM 168 249631 P
266. automatic fire detectors Series 500 and 200 with integrated dual isolator suitable for indoor surface mounting If a short circuit appears between two isolator modules the defective area is separated from the ADM loop and operation of all other connected detec tors and modules is guaranteed For optimum availability the de DR tei tector zones on the ADM loop should be separated from each Ae RS ie oy other by isolator modules KG de Features Connection to the ADM loop using System Sensor 200 protocol Multi useable terminals with secure screw fitting Terminal for external remote indicator Mechanical theft protection Specifications Current consumption max 100A quiescent Ambient temperature 30 C to 70 C Relative humidity 10 to 93 no condensation Dimensions x H 102 x 26 mm Colour cream Weight 70g 169 BB072001 SAM 0720 01 0100 246018 246012 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 111 Approval VdS G200100 Cross references Page Art Nr Name Type 114 246006 Base Adapter SS MZP500 1 226 249011 Detector Label BME BEZ 120 249044 Detector Mounting Bracket MMW 1 1 90 240013 Ionisation Smoke Detector Anal 200 SS 1251E 92 241020 Optical Thermal Detector Anal 200 SS 2251TEM 91 241050 Optical Laser Detector Anal 200 SS 7251 90 241010 Optical Smoke Detector Anal 200 SS ND2251EM 121 249640 Protective Cage BWS 1 D1 115 246010 Recessed Mounti
267. auxiliary modules or Four stand by batteries 12 V max 22Ah two batteries at the cabinet bottom two batteries in an optional Battery Bracket BK216 1 and a Mounting Bracket BW216 1 for auxiliary modules Specifications Dimensions W x H x D 420 x 520 x 120 mm Colour grey white RAL 9002 Net weight 6 4kg Cross references Page Art Nr Name Type 41 214028 Battery Bracket BK216 1 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 16 214308 Fire Detection Control Panel BC216 1S INT 1 42 214029 Mounting Bracket BW216 1 287 310002 Stand by Battery 12V 18Ah 214130 Terminal Set CE AKS216 1 The terminal set is used in a 19 cabinet with a Fire Detection Control Panel BC216 xCE and allows for the relocation of the terminals between fire detection control panel and the outbound lines It includes terminals for the 230VAC supply and the power unit outputs as well as a pre assembled cable harness of 1 7m length Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 27 214108 Fire Detection Control Panel BC216 1CE INT 1 169 BB072001 SAM 0720 01 0100 214232 214028 214128 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 41 Terminal Set E AKS216 2 The terminal set is used in a 19 cabinet with a Fire Detection Control Panel
268. be installed in Fire Detection Control Panels Se ries BC216 Series BC016 BC06 LBC1000 and LBC32 Features Extinguishing system control according to VdS specifications System neutral design for all extinguishing systems Processing logic for the actuation and confirmation of the extin guishing system Specifications Operating voltage 20 to 31 VDC Current consumption at 24VDC OmA quiescent 20mA active Ambient temperature 5 C to 50 C Dimensions L x W x H 70 x 45 x 20 mm Weight 50g JET av E 50 Chapter 4 Extinguishing System Controls 223009 Control Zone Module SLM1 2 Componentry for the installation in Fire Detection Control Panels Series BC216 Series BCO16 Series BC06 or Series LBC which allows for the line monitored triggering of exter nal devices with increased current demand e g signalling devices solenoid valves Features Hardware controlled activation via control line Activation delay can be set from 0 to 90 seconds Electronically limited load current Line monitored output with fault reporting Specifications Operating voltage 20 to 31 VDC Current consumption at 24V 30mA quiescent Load current max 1 4A Monitoring voltage 1 2V End of line resistor 5 6kQ Activation delay 0 to 90s Ambient temperature 5 C to 50 C Dimensions L x W x H 75 x 75 x 30 mm Weight 120g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE
269. but can be by passed when connected accordingly The aspiration smoke detection system can be parameterised with 3 response thresholds for the conditions ALERT ACTION and FIRE The reaching of the ALERT threshold can be transmitted via the ADM loop to the fire detection control panel and be displayed as technical message The relay ACTION is activated once the ACTION threshold is exceeded Reaching the FIRE threshold activates a fire alarm If the aspiration smoke detection system is con nected to an ADM loop the relay FIRE has to be activated by the control panel through para meterisation of the relevant control module In this case the relays ACTION and FIRE can be used for general control tasks If the aspiration smoke detection system is connected in conventional technology via the relay contacts the relay ACTION can activate a technical message for the indication of a pre war ning The fire alarm is activated via the relay FIRE which in this case is auto activated by the aspiration smoke detection system The continuous air flow which is generated by a ventilator in the aspiration smoke detection system housing is permanently monitored The system identifies the failure of the ventilator blocking of aspiration holes and pipe burst as fault Disturbance of air flow or fault of power supply is signalled via the loop address of the con trol module whereas fault of the laser smoke detector is transmitted via the detector address Ev
270. c jacket It is therefore acid and alkaline resistant and can be used in harsh environmental conditions It comprises an in ternal and an external conductor the external conductor is designed as wire mesh synthe tic material with a negative temperature coefficient is used for isolation i e the isolator resistance decreases with increasing temperature At the end of the sensor cable the conduc tor is connected to a termination box with a defined end of line resistance The entire line is continuously monitored for wire breakage and short circuit Features Sensor cable length up to 300m Detection of exceeding temperatures at any point of the sensing cable Easy installation Specifications Outer diameter 4mm Tensile strength lt 200N Cable type Synthetic coaxial cable with nylon jacket Weight of sensor cable 3 0kg per 100m Cross references Page Art Nr Name Type 206 244632 Sensor Cable Monitoring System Anal XP95 Apo SKM 95 205 244631 Sensor Cable Monitoring System Conv SKM 03 Gas Detector Methane GM METHAN Compact gas detector for the detection of methane natural gas below the explosion limit The detector is suitable mainly for the application in private households and for the surveil lance of gas pipes gas fireplaces and gas valves in any facilities where gas leaks can occur The gas detector signals pre alarm at 10 of the lower explosion limit and alarm at 20 of the lower ex plosion limit 9 Feat
271. calisation in the event of an alarm each detector can be assigned an ad dress by adding an address module NG58 1 to the mounting 3 base The address of the detector in alarm condition as well as the assigned text is displayed directly on the fire detection con trol panel provided that these functions are supported by the control panel ae An LED indicator visible from all angles displays the activated condition of the detector The detector is accommodated in a white housing complies with class BS and can be installed in rooms that do not exceed a height of 6m Several base versi ons are available for mounting the detector 78 Chapter 9 Conventional Detectors Series FC600 Features Individual detector addressing by installing an optional address module NG58 1 Output for external remote indicator Mechanical theft protection Simple function testing using a magnet Specifications Operating voltage Current consumption supplied through detector line voltage typ 40uA quiescent Alarm temperature typ 78 C Operating temperature max 60 C Ambient temperature 30 C to 80 C Relative humidity max 95 no condensation Dimensions x H 106 x 46 mm Colour white Weight 80g Approval LPCB 603b 01 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 79 246070 Detector Base FC600 FC600 BR 79 246071 Detector Base with Diode FC600 FC60
272. cation of all locking systems possible due to a variety of optional inner doors Buzzer for signalling inappropriate storage of keys Heating device for outer door Optional flush mounting frame enables preparation for installation also available with all side drilling protection Adjustment possible for flush mounting of the key box Installation in an optional stainless steel key box column possible 9 Specifications Operating voltage 12 24VDC 15 Duty cycle electromagnet 100 Current consumption 500mA active at 12VDC 250mA active at 24VDC Outer door heating 24VAC SVA Resistance of the alarm circuit 2 2kOhm 5 Ambient temperature 25 C to 70 C Protection class IP44 Dimensions W x H x D 290 x 275 x 145 mm Weight 12 7kg Approval VdS G199055 Cross references Page Art Nr Name Type 260 265900 Fire Brigade Keysafe Adapter AD900 1 D1 259 265751 Flush Mounting Frame for FSK700 2 EZ700 2 D 1 259 265818 Flush Mounting Frame with Drilling Protection for FSK700 2 EZBS700 2 261 265752 Inner Door for FSK700 2 A ITA 2 261 265753 Inner Door for FSK700 2 DBUK ITB 2 262 265757 Inner Door for FSK700 2 DBUM ITF 2 260 237700 Power Supply for FSK Heating NT700 1 259 249650 Protective Cover for FSK700 2 WSD FSK 263 265762 Steel Column V2A for F0345 Strobe HSFSK700 2 D3 263 265761 Steel Column V2A for F0345 HSFSK700 2 D2 262 265765 Steel Column V2A for FSE MP1 Strobe HSFSK700 2 D6 264 265764 Steel Column V2A for FSE MP1
273. cations Operating voltage supply through the loop voltage Current consumption typ 250uA quiescent Alarm temperature 57 C maximum heat component Operating temperature max 45 C Ambient temperature 20 C to 60 C no condensation or icing Relative humidity 10 to 93 no condensation Dimensions x H 102 x 45 mm Colour cream Weight 115g Approval VdS G201041 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 169 BB072001 SAM 0720 01 0100 Chapter 12 Analogue Detectors and Modules Series 200 500 93 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PA58 1 241051 Optical Thermal CO IR Detector Anal 200 SS 2251CTLE The multi criteria detector 2251CTLE contains four separate detection units for the four es sential characteristics of fire smoke temperature carbon monoxide and infrared radiation The optical smoke sensor works on the principle of scattered light and detects visible smoke particles The thermal element reacts to changes in temperature Sy in defined time intervals up to the alarm temperature of 58 C rate of rise heat principle class A1R Due to the long living car Ng ay
274. ce Module NIF5 1 Features Status LED indicator to display data transfer All parameters to be set via a DIL switch Small dimensions To be mounted on a DIN rail Specifications Operating voltage 18 30VDC Current consumption at 24V typ 200mA Length of optical fibre max 15km Type of fibre 9 125um 1300nm Optical budget 17dB Ambient temperature 10 C to 55 C Dimensions W x H x D 61 x 115 x 113 mm Weight 500g Cross references Page Art Nr Name Type 20 2199998 Fire Detection Control Panel BCnet216 Description ZLT Interface License ZLT SS ZLT interface license for the communication of Fire Detection Control Panels Series BC216 with superior alarm monitoring systems According to requirements the superior operation control system can display only the states of the fire detection control panel or additionally al low for the operation of zones actuations etc The ZLT interface license is required in the sectional control panel that is connected to the operation control system Note the ZLT Interface can only be operated on a central processing board ZTB216 2 with at least hardware version V4 The type of the board is printed on a label The version num ber is the last digit of the PCB version that is printed in the left bottom corner of the PCB e g PN5233S4 for V4 Cross references Page Art Nr Name Type 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional
275. ce cet n eee etnenn eee eene 267 Fire Brigade Control Unit FBF900 2 D1 0 0 0 cece ene cece eect e nee t ee enn eee eene 268 Fire Brigade Display Panel FAT900 1 D1 oo cece cence eet e ene e ee een nen eeenee 269 Fire Brigade Display Panel FAT900 2 D1 oo ccc eee cece eee teen e eee en nen e tenes 270 Redundant Transmission Adapter ADFAT900 2 D1 oe cece cece cece eee teen eee eeenae 270 Fire Brigade Orientation Panel FOTR900 1 D1 2 0 cece cet n ene en nen eeenee 271 Fire Brigade Orientation Panel FOTR900 2 D1 1 0 cece cence cette nee eeen een eeenee 271 Mounting Frame 19 6HU RAHMEN 0 c cece cece e teen teen e eee enn ene e nnn nee e ned 272 Mounting Frame 19 6HU RAHMEN FBF 000 cece cc cece cee e ee eet eee eee nen eee eeenes 273 Fire Brigade Map Box FWP unitarer free Se 273 Fire Brigade Map Box FPKCLR900 1 osreuannnvevnnavnnennnnnuevenannuenrnnnueuenenanuusenner 273 Fire Brigade Map Box FPKPHZR900 1 ves aaie EARE EIE AEE EEE EEEE E e 274 Fire Controls 217001 260002 261003 261004 261005 261006 261008 261009 261010 261011 261017 261018 261019 Smoke Switch RS24 saksa geek ae snodde Bld E E AE E AS Rk 275 Control Device for Magnetic Lock Clamp 2498 eovvvanananvnvrnnnnnerrnanvevvevannenennnanveeer 275 Magnete Clamp SOON 13830 222 skrssense sekt pakka ash cud seige peler dete pene arsen dreide 276 Magnetic Clamp Reset SOON 1350 aorovannnnvnnenananverrnnnnnenenanvuvnnnanuenen
276. ce provides 2 separate alarm and fault detection relays Each of these two groups can be assigned up to 16 detectors The two zones are reported as collective mes sages to the fire detection control panel either in addressable conventional technology or by means of auxiliary modules via the ADM loop In addition an LED for the individual display for each detector is provided by the RF interface Features Up to 32 detectors can be memorised Radio linked detectors assigned to 2 zones integrated power supply unit with optional stand by battery Individual detector identification via 32 LEDs Input for remote reset High transmission capacity Programming via built in buttons Automatic shift between the two frequency ranges 434MHz and 868MHz 24 bi directional data channels Channels are checked for availability o o o Specifications Mains voltage 230V AC 10 15 50Hz Connection power 12VA external supply voltage 10 to 30VDC Current consumption at power failure from 12V stand by battery max 110mA quiescent 120mA alarm Ambient temperature 0 C to 60 C Dimensions W x H x D 300 x 390 x 140 mm Colour white RAL 9018 Weight without battery 8 7kg Approval VdS G206015 Cross references Page Art Nr Name Type 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 187 246040 Detector Ba
277. cece nent e ene e eben een tneeeneens 201 Beam Smoke Detector Conv FR2000 0 0 ccc cece cence ence nen eee ener e etn eneeeenes 201 Linear Heat Detection Unit Alarmline Conv LWM 1 0 ccc ccc cece cece nen e cece en enes 202 Sensing Cable Blue LWM SK1800010 2 2 0 cco cence cee e nent ene ene e etn n ene e ee 203 Sensing Cable Black LWM SK1800011 2 0 0 0 cee cece eee cence nent en een eeenen ne eeeee 203 XI XII 21 22 244624 244638 244639 244629 244630 244631 244632 244633 244634 244620 244621 244619 222013 241603 Sensing Cable Stainless Steel LWM SK11800013 eremnnnnvnrnnnnenennnavvernnranvenrnrnvvere 204 Interconnector LWM ZV22 11800 103 ovvuunnnennrvnnveennnnnnveennrennernrnenanennusenanen 204 Termination Connector LWM AV22 11800 102 21 0 0 eee e ee cee eee e ee eenn eee e ene 204 Mounting Base TC358 pre are a ae bees Beg an gas shine mr beth 205 Mounting Clip 3040 LSK ie e e cece cece a pee e saer ue eee nen e ee ete nese eed 205 Sensor Cable Monitoring System Conv SKM 03 00 e cece eee cece ee cect eee e tne en eees 205 Sensor Cable Monitoring System Anal XP95 Apo SKM 95 ooo cece cece eee eee eee nee n ees 206 Standard Sensor Cable Red SKM SK ROT 20 0 0 0 cece cece cence tence eee e eect etn en eee ee 206 Sensor Cable Black SKM SK SCHWARZ 00 c ccc ce cece eect eee t een e ete eens etnn ene e ee 207 Gas Detector Methane GM METHAN esuunenanennnnen
278. ces ADM Series XP95 200 243 Depending on the parameter setup of the Fire Detection Control Panel Series BC216 and the system condition the panel can activate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combinations The sound level is ad justable in 3 steps but depends also on the chosen tone type The power consumption is de pendent on the tone type and the adjusted sound level Features 32 different tone type combinations selectable via DIL switch e g continuous tone 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Sound level adjustable in 3 steps low medium high Low power consumption Integrated dual isolator 2 decadic rotary switches for setting the address from 01 to 99 Different base versions available Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 450uA sounder off max 2 7mA low sound level max 4 6mA medium sound level max 7 3mA high sound level Sound level typ 82dB A 1m distance low sound level typ 90dB A 1m distance medium sound level typ 96dB A 1m distance high sound level max 100dB A Im distance high sound level Examples at 24V Continuous tone 660Hz typ 4 8mA at 98dB A Im distance DIN tone 1200 500Hz typ 6 7mA at 100dB A 1m distance Slow Whoop tone 500 1200Hz typ 6 8mA at 96dB A 1m distance Ambient temper
279. co ver In the basic version the control panel contains 4 conventional detector zones 2 parameterisable inputs and 2 relay outputs The Fire Detection Control Pa nel Series BC06 can be extended to 6 detector zones by the installation of the Zone Extensi on Board ZEB2 1 As an alternative to a zone extension board the control panel can be equipped with the Extinguishing Board EXB1 1 to create a combined fire detection and ex tinguishing control panel for single zone extinguishing systems according to the European standard EN 12094 1 In addition the wall mount cabinet can accommodate an optional componentry Relay Module RL58 1 or RL58 2 Siren Connection Module SZ58 3 etc as well as stand by batteries 2 x 12V max 7Ah The initial commissioning of the control panel is significantly facilitated by the practical facto ry settings The system specific parameterisation of the control panel can be directly accom plished via the keypad of the integrated display and operating field without the requirement of any additional support Essential features RISC microprocessor technology Administration of up to 6 detector zones for manual call points automatic fire detectors with or without alarm verification and fault detectors with or without self resetting property With the help of the optional MCP Coding Module MCM1 1 alarms from automatic de tectors and manual call points which are both connected to the same detector line can b
280. contamination of the glass pane on the detector front Features Applicable in conventional technology Connection to an ADM loop via a conventional zone module possible Specifications Operating voltage supplied through detector line voltage Current consumption 50uA quiescent Surveillance angle approx 110 Spectral sensitivity 185 to 235nm Ambient temperature 20 C to 60 C Dimensions L x W x H 98 x 64 x 35 mm Protection class IP65 Weight 110g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 4 210210 Zone Extension Board ZEB2 1 Flame Detector IR Conv IR 10 Flame detector operating on the IR principle in conventional technology The detector re sponds to the flickering infrared radiation of flames and is therefore very well applicable for the detection of open flames even with smoke formation The detector does not respond to 196 Chapter 20 Special Detectors 244022 sunlight incandescent lamps fluorescent lamps and light arcs
281. control panel is nor mally passive and only takes over the function of the active sectional control panel in case of its failure The function of the extinguishing control panel is enabled in the LC216 1 or LCnet sectional control panels once an options circuit with the correct setting is installed The options circuit is part of the Extinguishing Control 8 Area Licence LC216 8LB The parameterisation of the Extinguishing Control Panel Series LC216 can be most easily ac complished via PC by means of the Windows parameter setup software PARSOFT The clear user interface allows an almost self explanatory definition of system configurations and there by minimises the requirement for training Entered parameters are loaded into the control pa nel after automatic verification In case of redundant extinguishing control panels PARSOFT guarantees the synchronisation of parameters from active and redundant LCnet sectional con trol panels Specifications see description of BC216 1 the BCnet sectional control panels and of the fire detection con trol panel modules Approvals VdS G206046 as extinguishing control panel only VdS G206089 as combined fire detection and extin guishing control panel Extinguishing Control 8 Area License LC216 8LB License for extinguishing control panel for the administration of up to 8 flooding zones at the Fire Detection Control Panel Series BC216 This license allows you to manage up to 8 floo ding zones on on
282. crew fitting Terminal for external remote indicator Specifications Ambient temperature 40 C to 70 C Relative humidity 0 to 98 no condensation Dimensions x H 100 x 23 mm Colour white Weight 60g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 153 246030 Backplate Apo SZPL 45681 233 153 246029 Conduit Box Apo SZA 45681 204 120 249044 Detector Mounting Bracket MMW 1 1 130 241061 Optical Thermal Detector Conv ORBIS Apo OH 13001 129 241060 Optical Smoke Detector Conv ORBIS Apo OP 12001 121 249640 Protective Cage BWS 1 D1 71 251001 Remote Indicator PA58 1 132 242031 Thermal Max Detector Conv ORBIS Apo HT 11002 133 242033 Thermal Max Detector Conv ORBIS Apo HT 11004 134 242035 Thermal Max Detector Conv ORBIS Apo HT 11006 131 242030 Thermal ROR Detector Conv ORBIS Apo HT 11001 132 242032 Thermal ROR Detector Conv ORBIS Apo HT 11003 134 242034 Thermal ROR Detector Conv ORBIS Apo HT 11005 121 249635 Trapezoid Steel Bracket TBH800 1 Detector Relay Base Conv ORBIS Apo RB 10004 Mounting base for automatic fire detectors Series Orbis with integrated relay output suitable for indoor surface mounting The relay output is active as long as the detector remains in the alarm state Application must comply with the LST Connection of Detectors Features Multi useable terminals with secure screw fitting Relay output with dry changeover contact Specifications Current consum
283. ction Control Panel BC216 1 I1 20 ccc ccc nce n eee e nee eee tn en enn eee 15 Fire Detection Control Panel BC216 1 PL1 0 0 cece cence cece n eee een een eens 15 Fire Detection Control Panel BC216 1S INT1 0 0 0 e nen e nen eee een en enn ene 16 Fire Detection Control Panel BC216 1S A1 oo ccc cence een e ene n eee eee enn eens 18 Fire Detection Control Panel BC216 1S D1 oo ccc nce n ence nen c eee ene e nn enees 18 Fire Detection Control Panel BC216 1S B1 oo ccc ccc ence ence cence teen e ene eee 18 Fire Detection Control Panel BC216 1S CZ1 oo ccc nce een n ence eee ee ene tenes 18 Fire Detection Control Panel BC216 1S H1 o oo ccc ccc nce cece nee eee e ean eens 18 Fire Detection Control Panel BC216 1S NL1 2 2 2 ccc cee cece en cnn ence een ens 18 Fire Detection Control Panel BC216 1S SK1 2 ccc cence cece nen nent n een eenens 19 Fire Detection Control Panel BC216 1S HR1 0 0 ccc cee cece nen e een e nen een ens 19 Fire Detection Control Panel BC216 1S SLOL oo c ccc cence ence ene n eee ee nen eens 19 Fire Detection Control Panel BC216 1S PL1 0 ccc cence ence ence een ene een ens 19 Fire Detection Control Panel BCnet216 Description 00 0 cece eee ee eee e ec ee eee e een nee 20 BCnet Sectional Control Panel OP BC216 2 INT1 2 0 00 ccc ccc ccc ccc ccc ence nce veven teen eee 23 BCnet Sectional Control Panel OP BC216 2 A1 0 ccc cence nce eet een enn enees 24 BCnet Sectional Control P
284. ction Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 206 Chapter 20 Special Detectors 244632 244633 3 210209 Fire Detection Control Panel BC06 2 INT1 207 244634 Sensor Cable Black SKM SK SCHWARZ 206 244633 Standard Sensor Cable Red SKM SK ROT 4 210210 Zone Extension Board ZEB2 1 Sensor Cable Monitoring System Anal XP95 Apo SKM 95 Linear heat detection system according to EN 54 5 class C max room height 6m for the secure detection of maximum temperature exceedances over the entire length of the sensor cable Direct connection and supply through the ADM loop using Apollo Discovery protocol Thanks to the integrated dual isolator the loop is disconnected at short circuit SENSORKABELMELDER Features Sensor cables up to 300m length can be connected Detection of exceeding temperatures at any point of the sen sing cable Easy to maintain system Separate alarm and fault indication Integrated dual isolator Direct connection to the ADM loop with Apollo Discovery protocol Alarm indication according to DIN 14623 Easy commissioning Specifications Operating voltage supplied through loop voltage Current consumption at 24VDC 2mA quiescent 3 2mA alarm Ambient temperature 25 C to 50 C Protection class IP65 Dimensions W x H xD 105 x 105 x 65 mm Material polycarbonate Colour grey white RAL 9002 Weight 300g Approval VdS G203077 Cross references Pag
285. ctor Base Anal 500 200 SS B501 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 91 241050 Optical Laser Detector Anal 200 SS 7251 244031 Aspiration Smoke Detection System A222E LSR The two channel Aspiration Smoke Detection System A222E LSR contains two separate sensing chambers for monitoring two independent areas Air from a monitored room is aspi rated by each of the sensor pipe networks that are connected to the housing and is directed to the respective highly sensitive laser smoke detector If the smoke concentration exceeds the permissible value an alarm is activated which is optically displayed on the system and can be further transmitted to a fire detection control panel The alarm can be reset at the control panel The system can be used for early fire detection in room and equipment monitoring due to the high response sen sitivity of the laser smoke detector Connection to the fire detection control panel is possible either in conventional technology via dry relay contacts or via an ADM loop using System Sensor 200 protocol The preferred mode of operation must be parameterised at the aspiration smoke detection system The converter module which is integrated in the aspiration smoke detection system constitu tes the interface for communication via the ADM loop For each channel it has one address assigned for both the detector and the control module A dual isolator disconnects t
286. cuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 Thermal Max Detector Conv ORBIS Apo HT 11004 Heat detector operating on the heat detection principle in addressable conventional technolo gy maximum heat detector classified as BS maximum room height 6m in extra flat design suitable for indoor mounting For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are supported by the control panel If the detector is faulty the multicolour status LED on the detector will flash for approx 4 minutes in yellow colour after the detector line has been enabled Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional address module NG60 1 Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 65uA quiescent Alarm temperature typ 75 C Operating temperature max 65 C continuous operation Ambient te
287. d 2 Wire for LED Connection 10pcs LED LEITUNG 10 The two pin connection cable connects light emitting diodes or relays to the LED Connection Module LAM48 1 The cable is required if non assembled LEDs are used or if more than two Relay Modules RL58 1 or RL58 2 which can be directly connected to the LED Con nection Module via a flat cable are being actuated In this case the cable connects two addi tional actuation inputs of a further Relay Module RL58 1 or RL58 2 One side of the cable has a connector assembled fitting to the pin strip header of the LED connection Module LAM48 1 the other side has flying leads Specifications Length of cable 2m Cross references Page Art Nr Name Type 74 252013 LED Connection Module LAM48 1 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 ion im 76 Chapter 9 Conventional Detectors Series FC600 9 Conventional Detectors Series FC600 241070 Optical Smoke Detector Conv FC600 FC600 0 The optical smoke detector FC600 O operates with an optical sensing chamber on the princi ple of scattered light The alarm is transmitted to the fire detection control panel in addressab le conventional technology For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG58 1 to the mounting base The address of the detector in alarm condition as well as the assigned text is displayed directly on t
288. d 6 4 m 2 decadic rotary switches for setting the address from 01 to 99 Output for external remote indicator Mechanical theft protection Insect screen Functionality check by means of test activation with magnet o o o Specifications Operating voltage supplied through loop voltage Current consumption max 330uA quiescent Ambient temperature 10 C to 50 C Relative humidity 10 to 93 no condensation Air velocity max 20m s Dimensions x H 103 x 42 mm Colour cream 169 BB072001 SAM 0720 01 0100 92 Chapter 12 Analogue Detectors and Modules Series 200 500 241020 Weight 159g Approval VdS G202051 Cross references Page Art Nr Name Type 210 244030 Aspiration Smoke Detection System A211E LSR 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 110 246013 Isolator Detector Base Anal 500 200 SS B524IEFT 1 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PA58 1 Optical Thermal Detector Anal 200 SS 2251TEM Addressable multisensor detector with a detection element operating on the light scatter prin ciple and a detection element operating on the rate of rise heat principle classified AIR for application on the
289. d SOLO300 Cross references Page Art Nr Name Type 297 249051 Smoke Detector Test Tool SOLO330 Smoke Detector Test Tool SOLO330 Smoke detector test tool for checking automatic smoke detectors by means of non polluting test gas The transparent head of the test tool provides intervisibility with c the detector activation LED indicator and thus saves test gas The con ee struction of the test tool thanks to its pivoting head allows reaching even mounting places which can be accessed only with difficulty With the op tional Telescopic Pole SOLO100 it is possible to check detectors which are mounted in rooms of up to 7m height Cross references Page Art Nr Name Type 298 249054 Extension Pole SOLO101 298 249053 Telescopic Pole SOLO100 297 249036 Test Gas Can SOLOA3 001 s am nd 298 Chapter 33 Tools 249052 249053 249054 249058 Detector Removal Tool SOLO200 Universal detector removal tool for removing and reinstalling punctiform automatic fire de tectors of various dimensions The clamping mechanism is flexibly mounted on a pole of 0 65 m length and can the refore be used even for mounting places that are difficult to access With the optional Telescopic Pole SOLO100 it is possible to reach detectors which are mounted in rooms of up to 7m height Cross references Page Art Nr Name Type 298 249054 Extension Pole SOLO101 298 249053 Telescopic Pole SOLO100 Telescopic Pole SOLO100
290. d from the It files of the LBC se tup by using PARSOFT 2 So in the event of an alarm or fault the detector text of the LBC detectors is displayed on the display and operating field of the BCnet216 members The BCnet LBC Gateway is designed as BCnet sectional control panel in 19 slide in tech nology with 6 height units without display and operating field Black Box control panel The BCnet LBC Gateway allows for the installation of up to 2 Conventional Detector Inter faces GIF8 1 for the connection of optional redundant alarm lines to the LBC control panels or conventional detector lines but no loop Interfaces LIF64 1 The extensive functions and features are summarised in the description of the Fire Detection Control Panel BCnet216 No 2199998 Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 28VDC Output peak current max 1 8A Connection of external devices typ 0 8A site specific Current consumption at 24V typ 90mA without optional componentries Ambient temperature 5 C to 50 C Dimensions W x H x D 478 x 266 6 height units x 95 mm Colour grey white RAL 9002 Weight without batteries approx 6kg Cross references Page Art Nr Name Type 20 2199998 Fire Detection Control Panel BCnet216 Description 169 BB072001 SAM 0720 01 0100 60 Chapter 5 Interfaces 218021 219010 LBC Sub Unit License LBC UZ License for a sub control panel for the integratio
291. d specifications correspond to the conditions and intentions at the time of printing of the Product Guide We reserve the right for modifications of any type especially when on account of technological progress and do not take on any liability for misprints and obvious mistakes The values stated in the specifications generally represent nominal values by me ans of sample variations product modifications or site specific conditions these values may differ from the actually measured values LST always tries to provide information as comprehensive and as accurate as possible Ne vertheless all information on suitability and use of our products are non binding and do not liberate the introducer in a market from doing own tests The buyer is responsible for himself for obeying legal and official regulations in connection with the use With the publication of this Product Guide all previous Product Guides and if prices are con tained in this Product Guide all previous price lists of the corresponding subject and sales area lose their validity The charge for the products is made on basis of the prices valid on the day of delivery All delivery contracts are concluded on the basis of the General Terms of Delivery issued by the Austrian Electrical and Electronics Association Special delivery times or export limitations may exist for some products listed in the Product Guide Also country specific variants of products may be listed in the Product G
292. d speeds from 1 5m s to 20m s Specifications Operating voltage supplied through detector line voltage Current consumption at 24V typ 100uA quiescent Ambient temperature 0 C to 50 C Relative humidity 10 93 no condensation Dimensions W x H x D 380 x 125 x 100 mm Colour grey Weight 2 0kg Cross references Page Art Nr Name Type 123 244005 Duct Detector Pipe 0 3 0 6M SS ST 1 5 124 244010 Duct Detector Pipe 0 6 1 2M SS ST 3 124 244011 Duct Detector Pipe 1 2 2 4M SS ST 5 124 244012 Duct Detector Pipe 2 4 3 7M SS ST 10 Optical Smoke Detector Conv 100 SS 2151E LC The Optical Smoke Detector 2151E LC operates with an optical sensing chamber on the principle of scattered light The alarm is transmitted to the fire detection control panel in ad dressable conventional technology The optical smoke detector is accommodated in a flat pla stic housing and is exclusively designed for the installation in the Duct Detector DH400P oe Features 4 Individual detector identification through connection of an g optional Address Module NG58 1 Nr Mechanical theft protection Insect screen Function testing possible by test activation via magnet Service connector for testing with the Test Module MOD400R Specifications Operating voltage supplied through detector line voltage Current consumption typ 100uA quiescent Ambient temperature 0 C to 50 C Relative humidity 10 93 no condensation Jer ani
293. dS G205090 Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 270 250901 Redundant Transmission Adapter ADFAT900 2 D 1 9 210112 Serial Interface Module SIM016 3 Redundant Transmission Adapter ADFAT900 2 D1 Module for redundant operation of the Fire Brigade Display Panel FAT900 2 D1 and the Fire Brigade Orientation Panel FOTR900 2 D1 to Fire Detection Control Panels BC016 and OP BC216 For installation in control panels the module is mounted in the corresponding mounting bracket by using the provided printed circuit board spacers made of PVC co oceoeocooG 169 BB072001 SAM 0720 01 0100 250717 250902 169 BB072001 SAM 0720 01 0100 Specifications Operating voltage Current consumption at 24V Ambient temperature Chapter 28 Fire Brigade Control and Display Devices 271 10 30VDC 20mA 0 C to 50 C Dimensions W x H x D 72 x 65 x 25 mm Weight 100g Approval VdS G200079 Cross references Page Art Nr Name Type 270 250900 Fire Brigade Display Panel FAT900 2 D1 271 250902 Fire Brigade Orientation Panel FOTR900 2 D1 Fire
294. der WB XP95 38531 810 Sounder WB XP95ISM White Slow Whoop 45681 290 The addressable loop sounder is installed in a round white plastic housing and is prepared for indoor surface mounting The integrated detector base is suitable for accommodation of fire detectors Series XP95 and Discovery gt The sounder is actuated using Apollo Discovery protocol and po 5 wered via the ADM loop Depending on the parameter setup of j the Fire Detection Control Panel Series BC216 and the system r condition the panel can activate the sounder with tone A or B inn E 4 The unit contains a dual isolator 234 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 Features Tone A Slow Whoop tone NEN 2575 500 1200Hz over 3 58 1s pause Tone B continuous tone 870Hz Low power consumption Sound level adjustable via DIL switch Simple address setting of inserted detector by code card in detector base At short circuit the function of loop elements that are not affected by the short circuit is maintained Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 200uA quiescent typ 5mA sounder on Sound level 55 75dB A or 75 91dB A Im distance Ambient temperature 20 C to 60 C Protection class IP21 Dimensions x H 115 x 38 mm Colour white Weight 140g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Cont
295. detector line voltage Current consumption typ 40uA quiescent Ambient temperature 20 C to 60 C no condensation or icing Relative humidity 0 to 95 no condensation Jer ani 169 BBO72001 SAM 0720 01 0100 242024 242025 169 BB072001 SAM 0720 01 0100 Chapter 14 Conventional Detectors Series 65 ORBIS 127 Dimensions x H 100 x 42 mm Colour white Weight 100g Approval VdS G200017 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 149 246035 Detector Base Conv 60 65 Apo 45681 251 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 Thermal ROR Detector Conv 65 Apo GD 55000 122 Heat detector operating on the rate of rise heat detection principle in addressable conventio nal technology combined maximum rate of rise detector classified as AIR maximum room height 7 5 m in extra flat design suitable for indoor mounting JE Features aD Sealed electronics prevents false alarms caused by the 1 environment ze Individual detector addressing by installing an optional ad gt dress module NG60 1 Output for
296. detectors detector zone number date and time and any change in the operating condition of the fire detection control panel at the beginning and the end of the event The events are printed as plain text with 80 characters per line In combination with Fire yt Detection Control Panels Series BC216 or pr Series BCO16 the entire event memory and the parameterised system configuration can also be printed If used in analogue technology the current measured values of the detectors the measured values of the previous 6 months as well as a maintenance recommendation for every single detector can be printed once or periodically as well Note Replacement ribbon cartridges are available in specialised stores 169 BB072001 SAM 0720 01 0100 227010 227006 169 BB072001 SAM 0720 01 0100 Features Use of continuous paper High printing speed Low noise printing Easy operation via three buttons Three optical displays Specification Mains voltage Nominal current Power consumption Ambient temperature Chapter 7 Protocol Printers 67 9 dot matrix printer with 80 characters per line 230VAC 10 15 50Hz 0 5A approx 30W 5 C to 35 C Relative humidity 5 to 85 no condensation Dimensions W x H x D 366 x 147 x 275 mm Weight approx 4kg Cross references Page Art Nr Name Type 52 214231 Interface Adapter Module IAM216 1E 67 227010 Printer Cable for LX300 3m 25POL D SUB VERL 4 2102
297. ding on the parameter setup of the Fire Detection Control Pa nel Series BC216 and the system condition the panel can activate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combinations The sound level is adjustable in 3 steps but depends also on the chosen tone type The power consump tion is dependent on the tone type and the adjusted sound level Features 32 different tone type combinations selectable via DIL switch e g continuous tone 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Low power consumption Integrated detector base 99 Specifications Operating voltage Current consumption from loop Sound level detector mounted Examples at 24V Continuous tone 660Hz DIN tone 1200 500Hz Slow Whoop tone 500 1200Hz Flash frequency Ambient temperature Relative humidity Dimensions x H Colour Weight Approval Sound level adjustable in 3 steps low medium high Long lifespan of strobe due to the use of LEDs 2 decadic rotary switches for setting the sounder strobe address from 01 to 99 Different base versions available supply through the loop voltage typ 450uA sounder and strobe off max 4 1mA low sound level max 5 4mA medium sound level max 9 0mA high sound level typ 70dB A 1m distance low sound level typ 79dB A 1m distance medium sound level typ 87dB A 1m distance high sound leve
298. display activated condition e g sirens warning signs Output for signalling devices to display released condition e g sirens warning signs Extinguishing output for the line monitored actuation of an activation device for extin guishing medium e g solenoid valve HK The practical factory settings enable an easy commissioning of the extinguishing control pa nel The required functions of the extinguishing system and the delay times for the flooding process are set during commissioning depending on the employed extinguishing agent gas water etc and on country specific regulations The Fire Detection Control Panel BC06 fulfils in combination with the Extinguishing Board EXB1 1 all compulsory functions and the most important options according to EN 12094 1 The control panel is tested according to EN 54 2 EN 544 and EN 12094 1 by VdS 169 BB072001 SAM 0720 01 0100 210216 222011 169 BB072001 SAM 0720 01 0100 Chapter 4 Extinguishing System Controls 49 Extinguishing Board BC06 EXB1 1 The Extinguishing Board EXB1 1 enables the design of small single zone extinguishing sy stems The general parameters of the flooding zone e g pre discharge warning time floo ding time connection of detector zone s for activation of extinguishing output can be set Features Zone input for activation devices for manual activation of the flooding process Zone input for emergency hold devices fo
299. dividual ADM detector disablement for every single element on the ADM loop or for predefined groups of elements ADM maintenance prognosis by means of processor aided interpolation of data concer ning the trend of contamination for every single smoke detector on the ADM loop This way it is possible to predict the next maintenance date with a high degree of probability which in turn results in major cost savings in maintenance during the lifetime of the fire detection system ADM detector test checks the alarming capability of every ADM detector from the fire detection control panel ADM actuations on the ADM loop by means of actuation elements as well as alarm si rens which are freely parameterisable and are controlled individually by the control panel ADM address setting is carried through separately at each loop element ADM flexibility provides for the possibility to connect conventional detectors and special detectors via a Conventional Detector Module Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 28VDC Output peak current max 1 8A Connection of external devices typ 0 8A site specific Current consumption at 24V typ 90mA without optional componentries Ambient temperature 5 C to 50 C Dimensions W x H x D 420 x 520 x 120 mm Colour grey white RAL 9002 Weight without batteries approx 6kg Approval VdS G201017 Jer 169 BBO72001 SAM as 0720 01 0100 14 Cha
300. dress from 01 to 126 Sealed electronics prevents false alarms caused by the environment 142 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY Display of activated condition via 2 LED indicators that are visible from all angles Output for external remote indicator Mechanical theft protection Specifications Operating voltage Current consumption Ambient temperature supplied through loop voltage typ 400A quiescent 0 C to 40 C no condensation Relative humidity 15 to 90 no condensation Dimensions x H 100 x 42 mm Colour white Weight 105g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 249061 Monitor Module Anal XP95 Apo UMM 55000 833 Addressable compact mini module for the line monitored integration of contact detectors e g sprinkler system contacts supervising contact into the bi directional communication on the ADM loop using Apollo Discovery protocol Features Output for an optional LED indicator tt Switch for setting the physical address from 01 to 126 Specifications Op
301. e Flash frequency 1Hz Ambient temperature 25 C to 70 C Relative humidity 10 96 no condensation Dimensions x D 112 x 37 mm incl Base LPB W Colour red Weight 80g Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 255 359041 Base Sounder amp Strobe IP44 Red SDBR 256 359042 Base Sounder amp Strobe IP65 Red WDBR 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Strobe WM 200ISM Red WMSTR WR P02 The addressable strobe is accommodated in a red plastic housing and is prepared for outdoor and indoor mounting The unit is mounted on a base for signalling devices not provided The strobe is actuated as a module using System Sensor 200 protocol and is powered via the ADM loop A dual isolator is integrated in the strobe At short circuit it maintains the function of ADM elements that are not affected by the short circuit Features Long lifespan of strobe due to the use of LEDs Integrated dual isolator Low power consumption 2 decadic rotary switches for setting the address from 01 to 99 Different base versions available Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 450uA strobe off max 4 0mA strobe active Flash frequency 1Hz Ambient temperature 25 C to 70 C Relative humidity 10 96 no c
302. e 5 C to 50 C 330 x 330 x 90 mm grey white RAL 9002 approx 3kg tested to EN 54 2 4 EN 12094 1 by VdS Fire Detection Control Panel BC06 2 INT1 Same design as Fire Detection Control Panel BC06 1 but includes a 4 digit non resettable alarm counter in the display and operating field according to EN 54 2 Specifications Mains voltage Connection power Output voltage Output peak current Output current siren output Connection of external devices Current consumption at 24V without optional devices Line voltage Line current Line termination Line resistance Ambient temperature Dimensions W x H x D Colour Weight without batteries 230VAC 10 15 50Hz 60VA typ 27 6VDC max 1 8A max 1A typ 0 8A system specific typ 70mA end of line resistor 5 6kOhm typ 55mA end of line capacitor 47uF typ 20V end of line resistor 5 6kOhm typ 23V end of line capacitor 47uF typ 3 7mA end of line resistor 5 6kOhm typ 0 35mA end of line capacitor 47uF 5 6kOhm or 47uF max 50 Ohm per core 5 C to 50 C 330 x 330 x 90 mm grey white RAL 9002 approx 3kg Approval tested to EN 54 2 4 EN 12094 1 by VdS Cross references Page Art Nr Name Type 50 49 166 223009 Control Zone Module SLM 1 2 210216 Extinguishing Board BC06 EXB1 1 249096 MCP Coding Module MCM1 1 227008 Protocol Printer Dot Matrix LX300 227003 Protocol Printer Thermal DPU414 30B 222010 Relay Module 4 Fold
303. e 151 246025 Detector Base Anal Apo ASA 45681 210 149 246021 Detector Base Conv 60 65 Apo GSA 45681 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 179 246027 IS Detector Base Anal Apo ASEX 45681 215 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 246030 Backplate Apo SZPL 45681 233 Supplement base used in addition to detector bases Series 65 XP95 or Discovery for surface mounting to protect the mounting area against dust or dirt 169 BB072001 SAM 0720 01 0100 154 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY Specifications Dimensions x H 100 x 8 mm Colour white Weight 50g Cross references Page Art Nr Name Type 151 246025 Detector Base Anal Apo ASA 45681 210 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 4568 1 242 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 179 246027 IS Detector Base Anal Apo ASEX 45681 215 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 246031 Duct Detector Housing Anal Apo LG 53546 016 Elegant plastic housing for the surveillance of ventilation ducts including a detector base for mounting Apollo Series XP95 or Discovery smoke detectors The air escape pipe as well as the air inlet pipe is includ
304. e 5 C to 50 C Dimensions L x W x H approx 30 x 24 x 8 mm Weight 20g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 em nd 169 BB072001 SAM 0720 01 0100 16 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY 149 Acessories for Series 65 ORBIS XP95 DISCOVERY 246021 246035 169 BB072001 SAM 0720 01 0100 Detector Base Conv 60 65 Apo GSA 45681 200 Mounting base for automatic fire detectors Series 65 in addressable conventional technology suitable for indoor surface mounting Features Ege No electronics contained gt Multi useable terminals with secure screw fitting j Terminal for external remote indicator od Individual detector addressing by installing an optional ad dress module NG60 1 Mechanical theft protection AT h Ny Specifications Ambient temperature 209C to 60 C no condensation or icing Relative humidity 10 to 95 no condensation Dimensions x H 100 x 15 mm Colour white Weight 50g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 153 246030 Backplate Apo SZPL 4568 1 233 153 246029 Conduit Box Apo SZA 4568 1 204 120 249044 Detector Mounting Bracket MMW 1 1 126 240027 Ionisation Smoke Detector Conv 65 Apo GI 55000 217 126 241026 Optical Smoke Detector Conv 65
305. e distinguished by the Fire Detection Control Panel Series BC06 The type of line terminator end of line resistor or end of line capacitor can be selected via parameterisation Administration of alarming devices with the possibility of individual activation via an an d or combination Summary LED indicators for information about all current events 8 LED pairs are automatically assigned to parameterised zones or the conditions of the ex tinguishing module and display the activation disablement and fault condition of the zones Displays can be labelled individually with labelling strips which are inserted into the front foil Event memory for the last 50 events in chronological order to be output via the serial interface Monitored output for connection of external signalling devices with display of activation fault or disablement 2 dry contact outputs These outputs are pre set in the factory settings according to EN 54 standards summary alarm and summary fault 8 open collector outputs that automatically signal the activated condition of each zone and one summary output each for fault condition and disabled condition of the zones Button Panel reset for common reset of all current events 3 authorisation levels for operation and parameterisation secured by numeric codes A mounting position for a Serial Interface Module SIM06 1 for connection of a serial protocol printer Control panel case provides spac
306. e Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359023 Housing IP67 for Strobe FB XP95 29600 318 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 356023 Strobe FB XP95 White Orange 55000 879 The addressable loop powered strobe 55000 879 with an orange cap is integrated in a white plastic housing It is triggered and supplied like a module via the ADM loop using Apol lo Discovery protocol The strobe is designed to be inserted into a detector base and is sui Features Low power consumption Suitable for surface mounting table for indoor mounting Long life span due to use of LEDs Specifications Operating voltage Current consumption supply through the loop voltage typ 150A quiescent max 3mA active Ambient temperature 10 C to 60 C Protection class IP42 Dimensions x H 100 x 52 mm Colour white orange Weight 85g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359023 Housing IP67 for Strobe FB XP95 29600 318 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 169 BB072001 SAM 0720 01 0100 242 Chapter 25 Optical and Acoustic Devices
307. e Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 207 244634 Sensor Cable Black SKM SK SCHWARZ 206 244633 Standard Sensor Cable Red SKM SK ROT Standard Sensor Cable Red SKM SK ROT The sensor cable comprises an internal and an external conductor the external conductor is designed as wire mesh A synthetic material with a negative temperature coefficient is used for isolation i e the isolator resistance decreases with increasing temperature At the end of the sensor cable the conductor is connected to a termination box with a defined end of line resistance The entire line is continuously moni tored for wire breakage and short circuit Features Sensor cable length up to 300m Detection of exceeding temperatures at any point of the sensing cable Easy installation Specifications Outer diameter 3 25mm Tensile strength lt 200N 169 BB072001 SAM 0720 01 0100 244634 244620 244621 169 BB072001 SAM 0720 01 0100 Chapter 20 Special Detectors 207 Cable type plastic coaxial cable Weight of sensor cable 1 6kg per 100m Cross references Page Art Nr Name Type 206 244632 Sensor Cable Monitoring System Anal XP95 Apo SKM 95 205 244631 Sensor Cable Monitoring System Conv SKM 03 Sensor Cable Black SKM SK SCHWARZ The Sensor Cable Black is provided with an additional syntheti
308. e Detection System Housing TP 1 214 244181 Aspiration Smoke Detection System Housing TP 2 244184 Front Foil FW TP 1A For Aspiration Smoke Detection System Housing TP 1 Cross references Page Art Nr Name Type 213 244180 Aspiration Smoke Detection System Housing TP 1 244185 Front Foil FW TP 2 For Aspiration Smoke Detection System Housing TP 2 Cross references Page Art Nr Name Type 214 244181 Aspiration Smoke Detection System Housing TP 2 169 BB072001 SAM 0720 01 0100 244300 244302 169 BB072001 SAM 0720 01 0100 Chapter 21 Aspiration Smoke Detection Systems 217 Aspiration Smoke Detection System Housing TT 1 The Aspiration Smoke Detection System Housing TT 1 samples air from a monitored room via a connected sensor pipe network and directs it to a detector module not provided which analyses the air samples If the smoke concentration exceeds the permissible value an alarm is activated which is optically displayed on the system and further transmitted to a fire detection control panel The alarm can be re set at the control panel The system can be used for early fire de tection in room and equipment monitoring due to the high response sensitivity of detector modules SOS The continuous air flow which is generated by a ventilator in the i aspiration smoke detection system housing is permanently moni tored A failure of the ventilator blocking of aspiration holes or a pipe burst are op
309. e Dialling Device TWG805 1A 282 320008 Automatic Telephone Dialling Device TWG805 1D Stand by Battery 12V 2 3Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for emergency power supply of electronic security systems in stand by operation For 24V applications 2 batteries of identical type must be connected in series Due to techno logical progress the stated specifications may differ Specifications Nominal voltage 12V Capacity 2 3Ah min at 20 hours discharge Dimensions L x W x H 178 x 34 x 65 mm max Weight max 1 1kg Approval approved by VdS Stand by Battery 12V 7Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for emergency power supply of electronic security systems in stand by operation For 24V applications 2 batteries of identical type must be connected in series Due to techno logical progress the stated specifications may differ Specifications Nominal voltage 12V Capacity 7Ah min at 20 hours discharging time Dimensions L x W x H 152 x 65 x 100 mm max Weight max 2 4kg Approval approved by VdS Cross references Page Art Nr Name Type 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 Stand by Battery 12V 18Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for em
310. e Extension Board ZEB2 1 210200 Fire Detection Control Panel BC06 1 D1 Functions specifications and cross references are equal to the Fire Detection Control Panel BC06 1 INT1 but the manual comes in German language 210204 Fire Detection Control Panel BC06 1A D1 Same design as Fire Detection Control Panel BC06 1 but with two separately monitored and individually actuated independent alarming devices with maximum 0 5A continuous output current per device For each alarming device separate parameters for and or combinations can be set Specifications Mains voltage Connection power Output voltage Output peak current Output current siren outputs Connection of external devices Current consumption at 24V without optional modules Line voltage Line current without fire detector Line termination 230VAC 10 15 50Hz 60VA typ 27 6VDC max 1 8A 2 x max 0 5A typ 0 8A system specific typ 70mA end of line resistor 5 6kOhm typ 55mA end of line capacitor 47H F typ 20V end of line resistor 5 6kOhm typ 23V end of line capacitor 47uF typ 3 7mA end of line resistor 5 6kOhm typ 0 35mA end of line capacitor 47uF 5 6kOhm or 47uF 169 BB072001 SAM 0720 01 0100 210209 210208 169 BB072001 SAM 0720 01 0100 Line resistance Ambient temperature Dimensions W x H x D Colour Weight without batteries Approval Chapter 1 Fire Detection Control Panels Series BC06 3 max 50 Ohm per cor
311. e PS BCM216 3EPS is a BCnet sectional control panel in slide in unit design with a powerful power supply but without display and operating field It is mounted on a sheet steel carrier and designed for use in a Control Panel Rack 8HU RACK216 1E The module is prepared for 2 function modules Conventional Detector Interface GIF8 1 or Loop Interface LIF64 1 a Fire Brigade Interface FWL 1 a Fire Brigade Interface Additional Board FWZ2 1 and an Interface Adapter Module IAM216 1E By connecting a Display and Operating Front Panel ABP216 1E to the Fire Detection Con trol Panel Module PS BCM216 3EPS the BCnet Sectional Control Panel can be operated directly The power supply unit of the fire detection control panel module meets all requirements of the European Standard EN 54 4 and is designed to supply additional Fire Detection Control Panel Modules installed in the RACK216 1E to provide power supply for the connected ex ternal devices of the fire detection system and to charge an optional stand by battery If se veral BCM216 3EPS are used in a fire detection control panel they must be used independently from each other and with separate stand by batteries The extensive functions and features are summarised in the description of the Fire Detection Control Panel BCnet216 No 2199998 Specifications Mains voltage 230V AC 10 15 50Hz Connection power 300VA Output voltage typ 27 6VDC Output peak current typ 8 4A Connection of
312. e a fail safe supply with a no minal voltage of 24VDC During a mains power failure the optional stand by batteries provi de uninterrupted current for the consumer loads The compact power supply consists of a fully electronic stabilised mains charging unit for stand by operation and is installed in a ro bust sheet steel wall mount housing The housing provides room for 2 stand by batteries with 12V max 22Ah Depending on the stand by battery that is used the required values maxi mum charging current maximum express charging time battery test interval and battery test length can be set within a wide range With a given charging period of 24 hours stand by batteries with a maximum capacity of 65Ah can be charged Features Linear controlled mains charging unit current limited and short circuit proof Optimised charging process of the stand by battery by means of fast charging and trickle charging Electronically reverse polarity protected 3 light emitting diodes for clear indication of all status conditions 3 relay outputs for transmitting the fault conditions battery DC output or mains supply Specifications Operating voltage 230VAC 10 15 50Hz Connection power 150VA Nominal voltage typ 24VDC Nominal output current max 3A JET av E 290 Chapter 31 Batteries and Power Supply Devices 317100 317101 317102 Ambient temperature 5 C to 50 C Relative humidity max 90 no condensation Dimensions W x
313. e announcement messages into the digital voice message memory and for checking the recorded texts in Automatic Telephone Dialling Devices Series TWG805 Specifications Connection 4 pin Western connector Cable length approx 1 4m Ambient temperature 0 C to 50 C Dimensions L x W x H 200 x 50 x 40 mm Weight 200g Plug in Power Supply STN805 1 Power supply unit for supply of 12V devices with low power demand e g an Automatic Te lephone Dialling Device Series TWG805 286 Chapter 30 Telephone Dialling Devices Specifications Mains voltage Connection power Output voltage Output current Ambient temperature Dimensions W x H x D Weight 230VAC 10 15 50Hz SVA 12VDC 400mA 5 C to 50 C 50 x 75 x 80 mm 300g 169 BB072001 SAM 0720 01 0100 31 Chapter 31 Batteries and Power Supply Devices 287 Batteries and Power Supply Devices 310010 310006 310001 310002 169 BB072001 SAM 0720 01 0100 Stand by Battery 6V 1 2Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for emergency power supply of electronic security systems in stand by operation Due to technological progress the stated specifications may differ Specifications Nominal voltage 6V Capacity 1 2Ah min at 20 hours discharge Dimensions L x W x H 97 x 25 x 55 mm max Weight max 310g Cross references Page Art Nr Name Type 281 320007 Automatic Telephon
314. e available for mounting the detector Features Individual detector addressing by installing an optional address module NG58 1 Output for external remote indicator Mechanical theft protection Simple function testing using a magnet Specifications Operating voltage Current consumption Alarm temperature supplied through detector line voltage typ 40uA quiescent typ 57 C maximum heat component Operating temperature max 45 C Ambient temperature 30 C to 70 C Relative humidity max 95 no condensation Dimensions x H 106 x 46 mm Colour white Weight 80g Approval LPCB 603b 02 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 79 246070 Detector Base FC600 FC600 BR 79 246071 Detector Base with Diode FC600 FC600 BRD 80 246072 Detector Relay Base FC600 FC600 BREL 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT I 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 Thermal Max Detector Conv FC600 FC600 TMAX 78 The Thermal Max Detector FC600 TMAX 78 identifies a maximum temperature of 78 C as a sign of fire The alarm is transmitted to the fire detection control panel in conventional tech nology For quick lo
315. e brigade maps and building specific technical data Powder coated ST 37 steel sheet case with security lock Specifications Lock DOM CLI1 Dimensions W x H x D 500 x 360 x 95 mm Colour flame red RAL 3000 274 Chapter 28 Fire Brigade Control and Display Devices 250713 Weight 6 1kg Cross references Page Art Nr Name Type 271 250717 Fire Brigade Orientation Panel FOTR900 1 D1 271 250902 Fire Brigade Orientation Panel FOTR900 2 D1 Fire Brigade Map Box FPKPHZR900 1 Document case for storage of approx 100 fire brigade alarm plans in DIN A4 and A3 format fire brigade maps and building specific technical data Pow der coated steel sheet case with lock for half cylinders Specifications Lock bolt lock for half cylinder Dimensions W x H x D 500 x 360 x 95 mm Colour flame red RAL 3000 Weight 6 1kg Cross references Page Art Nr Name Type 271 250717 Fire Brigade Orientation Panel FOTR900 1 D1 271 250902 Fire Brigade Orientation Panel FOTR900 2 D1 169 BB072001 SAM 0720 01 0100 29 Chapter 29 Fire Controls 275 Fire Controls 217001 260002 169 BB072001 SAM 0720 01 0100 Smoke Switch RS24 In normal condition the Smoke Switch RS24 provides the holding current for the fire con trols that is needed to keep the fire doors etc open In the event of a fire the Smoke Switch RS24 recognises the alarm of a fire detector connected to the detector line and disconnects the supply of the c
316. e control panel or sectional control panel Setup of the required parameters is accomplished using PARSOFT 1 or PARSOFT 2 The functions are specifically adapted to the requirements of EN 12094 1 48 Chapter 4 Extinguishing System Controls 2189991 If the system size or country specific regulations require redundant operation of the extinguis hing control panels additional licenses are required for the redundant control panels Each sectional control panel that is used for extinguishing control in the network requires a license Note the Extinguishing Control Panel Series LC216 can only be operated on a central processing board ZTB216 2 with at least hardware version V4 The type of the board is printed on a label The version number is the last digit of the PCB version that is printed in the left bottom corner of the PCB e g PN5233S4 for V4 Furthermore a firmware version PL149 Vx 20 or newer and a PARSOFT version V1 20 or newer are required for the operati on and the setup of the extinguishing control panel respectively Specifications Approvals VdS G206046 as pure extinguishing control panel VdS G206089 as combined fire detection and extin guishing control panel Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 12 214008 Fire Detection Control Panel
317. e controls or extinguishing system controls 99 transmitting devices e g to the fire brigade 999 alarming devices e g zones of acoustic or optical signalling devices 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 11 The following figure shows the available variants of panel housings BC216 x compact wall mount design display and operating field with BC216 1 BC216 1S and BC216 2 520mm depth 120mm BC216 xCE compact 19 design depth 95mm depth 181mm SHU 266mm display and operating field with BC216 1CE BC216 xE 19 slide in unit design 478mm 478mm EM i E E E der T8 ao depth 40mm ABP216 1E depth 233mm BOM216 3xx RACK216 1E Control Panel Modules max 7 pcs per RACK216 1E s 169 BB072001 SAM and 0720 01 0100 12 Chapter 3 Fire Detection Control Panels Series BC216 214008 Fire Detection Control Panel BC216 1 INT1 The Fire Detection Control Panel BC216 1 INT 1 is a modularly designed compact control panel for small and medium size fire detection system Depending on the boards inserted you can connect fire detectors fault detectors and condition detectors as well as actuation ele ments and alarming devices to a maximum of 2 ADM lo ops or to a maximum of 16 detector lines in addressable conventional technology or to a combination of both Thanks to its wide ran
318. e ee ene eee rece E ence ren S E E a aa a E ot aaah 298 249058 Test Set Conv S60 Apo TS 53832 020 2 0 ccc eect eee cnt e eee tenn eee e en en eee 298 249023 Smoke Sticks 1O pcs REZ ersen arnei ori eene TER Base ving HE bee amp ihe DE Heh Ae ped ae derma eas 299 Miscellaneous 229005 E O L Resistor 100pcs 5 6K 0 33W cece cece cece eee cet e eee cette eect etn nee e eee nn en eee 300 229004 Resistor LOOpes 1K 0 33W sorrisos rat ot ay backed aod Se ee farve tote core 300 229006 Diode 100pcs IN4004 0 cece ence cece ee eee cee e eee e nnn e KEE S Aa 300 180001 Banknote Contact 12V 24V GK1224 oo cece ccc nee ect e eben eben eect bene eeeee 300 XV XVI 169 BB072001 SAM 0720 01 0100 Chapter 1 Fire Detection Control Panels Series BC06 1 1 Fire Detection Control Panels Series BC06 210205 Fire Detection Control Panel BC06 1 INT 1 The Fire Detection Control Panel BC06 1 INT1 is a compact control panel for small conven tional fire detection systems Depending on the level of expansion fire detectors fault detec tors and condition detectors can be connected to a maximum of 6 conventional detector lines An output for an alarming device is provided as well The control panel was tested by VdS for compliance according to the European standards EN 54 2 and EN 54 4 The control panel is integrated in a wall mount cabinet The cabinet con sists of powder coated steel sheet base and a removable plastic cabinet
319. e eee 124 Duct Detector Pipe 2 4 3 7M SS ST 10 4 124 Duct Detector 400 OM DH400P 5 122 Dummy Cover 19 2HU AD8C 2H 4 43 Dummy Cover 19 3HU AD8C 3H 00 43 Dummy Cover 19 6HU AD8C 6H 4 43 E E O L Resistor 100pcs 5 6K 0 33W 00e eee 300 ESPA 4 4 4 Interface License ESPA SS 58 Ethernet Module ENM2 1 0 eee cece eee 53 Extension Pole SOLO1O1 0 0c eee 298 Extinguishing Board BC06 EXB1 1 49 Extinguishing Control Function Series BC06 Description eis nisser See dence chaste See loses ions 48 Extinguishing Control Panel Series LC216 Description 47 Extinguishing Control 8 Area License LC216 8LB 47 Extinguishing System Interface LSS1000 1 49 F Fire Brigade Control Unit FBF58 2 267 Fire Brigade Control Unit FBF900 1 D1 _ 267 Fire Brigade Control Unit FBF900 2 D1 268 Fire Brigade Display Panel FAT900 1 D1 269 Fire Brigade Display Panel FAT900 2 D1 270 Fire Brigade Interface Additional Board FWZ2 1 37 Fire Brigade Interface FWIO16 1 onnavvnnnannnvrr 9 Fire Brigade Interface FWI2 1 0 cece eee ee 36 Fire Brigade Key Box FSK700 2 D1 4 257 Fire Brigade Key Box FSK700 2S2 D1 258 Fire Brigade Key Deposit Flush Mount FASB UP
320. e ence teen eee eeenenes 255 XIII XIV 27 28 29 359041 359042 359049 Base Sounder amp Strobe IP44 Red SDBR 2 ccc cece cece nent e een ene n teen teen eneene 255 Base Sounder amp Strobe IP65 Red WDBR 0 ccc ccc cece cece nce e tence ene n eee eeenenenne 256 Mounting Plate for Sounder 200 5pcs DBSPD 5 1 0 2 eect eee eee e eee eeenn eee e ene 256 Fire Brigade Key Boxes and Accessories 265740 265742 265751 265818 249650 237700 265900 265752 265753 265757 265765 265760 265761 265762 265763 265764 265660 265661 268009 268010 265019 268012 Fire Brigade Key Box FSK700 2 D1 oo ccc ccc e eect nee e ee tee ence ee nnn ne eeeee 257 Fire Brigade Key Box FSK700 2S2 D1 sssuunnnnvnnnnnvnennnnnnenennnanuennnnuuuenanasuerennnr 258 Flush Mounting Frame for FSK700 2 EZ700 2 D1 eee cee cee e eee e tenn ence eens 259 Flush Mounting Frame with Drilling Protection for FSK700 2 EZBS700 2 0 cee eee ee 259 Protective Cover for FSK700 2 WSD FSK 2 ccc eee ccc ene eee teen eee nenn eee eenee 259 Power Supply for FSK Heating NT700 1 0 0 0 c cence cence cect eect ee nnn nee eees 260 Fire Brigade Keysafe Adapter AD900 1 D1 1 02 0 cece cece eee e ete e eee tne nee eeeenee 260 Inner Door for FSK700 2 AITA 2 0 ccc cece ne eect eee tt nee e ee nen ee eeenee 261 Inner Door for FSK700 2 DBUK ITB 2 1 0 0 0 cece cece eee teen eect nen e eee teen eeeee 261 Inner Door for FS
321. e for accommodating stand by batteries max 2 x 12V 7Ah 169 BB072001 SAM 0720 01 0100 2 Chapter I Fire Detection Control Panels Series BC06 Specifications Mains voltage Connection power Output voltage Output peak current Output current siren output Connection of external devices Current consumption at 24V without optional modules Line voltage Line current Line termination Line resistance Ambient temperature Dimensions W x H x D 230VAC 10 15 50Hz 60VA typ 27 6VDC max 1 8A max 1A typ 0 8A system specific typ 70mA end of line resistor 5 6kOhm typ 55mA end of line capacitor 47uF typ 20V end of line resistor 5 6kOhm typ 23V end of line capacitor 47uF typ 3 7mA end of line resistor 5 6kOhm typ 0 35mA end of line capacitor 47uF 5 6kOhm or 47uF max 50 Ohm per core 5 C to 50 C 330 x 330 x 90 mm Colour grey white RAL 9002 Weight without batteries approx 3kg Approval tested to EN 54 2 4 EN 12094 1 by VdS Cross references Page Art Nr Name Type 50 223009 Control Zone Module SLM 1 2 49 210216 Extinguishing Board BC06 EXB 1 1 166 249096 MCP Coding Module MCM 1 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 4 210215 Serial Interface Module SIM06 1 61 223026 Siren Connection Module SZ58 3 287 310001 Stand by Battery 12V 7Ah 4 210210 Zon
322. e inputs for demand orientated transmission to selected users System name Please note the Transmitter Module SMS2 1 can only be operated with a Central Processing Board ZTB216 2 using hardware version V4 or newer versions The type of the central processing board can be found on a label The version number is the last digit of the PCB version which is printed in the left bottom corner of the printed circuit board e g PN5233S4 for V4 For operation of the transmitter module a firmware version PL149 Vx 20 or higher is required for parameterisation a PARSOFT version V1 20 or higher is necessary Features Integrated web server with menu in German language Parameterisation via ethernet or dial up connection RS232C interface prepared for data transfer of event text messages from Fire Detection Control Panel Series BC216 Six inputs galvanically isolated Four outputs galvanically isolated Specifications Operating voltage 10 29 5VDC Current consumption at 24V typ 160mA max 330mA Input voltage range 10 29 5VDC Output voltage range 10 29 5VDC Max output voltage 0 5A per output GSM modem 900 1800MHz Ethernet interface RJ45 10BaseT Serial interface RJ11 9600Baud Ambient temperature 5 C to 50 C Dimensions W x H x D 105 6 module units x 85 x 58 mm Weight 225g Cross references Page Art Nr Name Type 52 214231 Interface Adapter Module IAM216 1E 52 214025 Serial Interface Module SIM216
323. e made of polished stainless steel Specifications Dimensions W x H x D 400 x 1250 x 300 mm Weight approx 60kg Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D 1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 259 265751 Flush Mounting Frame for FSK700 2 EZ700 2 D1 265 265660 Unblocking Element F0345 Steel Column V2A for F0345 Strobe HSFSK700 2 D3 The Steel Column V2A is made of 3mm stainless steel and provides a platform for mounting the Fire Brigade Key Box FSK700 2 the Unblocking Element F0345 and a strobe if installa tion of the key box in the building front is not possible due to technical or structural reasons or due to special requirements by the fire safety authority Specifications Installation of FSK700 2 possible with flush mounting frame Column prepared for installation of the Unblocking Element F0345 and a strobe Reinforcement iron cage for anchoring Flexible armoured tube for different types of cables Low net weight Surface made of polished stainless steel Specifications Dimensions W x H x D 400 x 1250 x 300 mm Weight approx 60kg 264 Chapter 27 Fire Brigade Key Boxes and Accessories Name Type Cross references Page Art Nr 257 265740 258 265742 259 265751 230 356671 265 265660 Fire Brigade Key Box FSK700 2 D1 Fire Brigade Key Box FSK700 282 D1 Flush Mounting Frame for FSK700 2 EZ700 2 D1 Strobe 24V Orange BE A S 2 0 24VBMT
324. e protected steel sheet case Power supply from a danger detection system 12V and 24V or optional plug in adapter Integrated charger for an optional stand by battery Optional extension to 8 control line inputs and 5 actuation outputs Optional extension for continuous monitoring of phone line Optional extension for remote control by an acoustic dialogue menu remote inquiry of the system conditions and remote maintenance by the installer o o ooo ooo Specifications Inputs 4 control lines with free assignment expandable to 8 282 Chapter 30 Telephone Dialling Devices 320008 Activation criteria Outputs Dialling mode Supply voltage Current consumption at 12V Current consumption at 24V Stand by battery Charging current Current consumption from stand by battery in case of supply voltage failure Ambient temperature Colour Dimensions W x H x D Weight Approvals Cross references Page 30 change in resistance 1 actuation output dry change over contact contact load max 60V 1A 1 dry fault detection output max load 30V 50mA 1 dry confirmation output max load 30V 50mA pulse dialling mode DTMF mode 10 31VDC 60mA quiescent 140mA alarm condition and actuation output activated 35mA quiescent 70mA alarm condition and actuation output activated optional 6V 1 2Ah max 120mA 65mA quiescent 150mA alarm condition and actuation output activated 5 C to
325. e response sensitivity of the detector is kept constant for a long time thus constituting another effective measure for preventing false alarms 169 BB072001 SAM 0720 01 0100 242023 169 BB072001 SAM 0720 01 0100 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 137 Features Permanent evaluation of environmental conditions Constant sensitivity Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Output for external remote indicator Mechanical theft protection Insect screen HK HK I Specifications Operating voltage supplied through loop voltage Current consumption typ 340uA quiescent Ambient temperature 20 C to 60 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 105g Approval VdS G294028 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 Thermal Detector Anal XP95 Apo AW 55000 420 Addressable thermal detector opera
326. e teen nenens 88 Analogue Detectors and Modules Series 200 500 240013 241010 241050 241020 241051 242002 241019 249046 249100 249101 249102 249115 249103 249105 249106 249116 249045 249104 249092 249095 249090 249091 249003 Ionisation Smoke Detector Anal 200 SS 1251 Eo ccc ccc cece cc cence tener ene n ene eeees 90 Optical Smoke Detector Anal 200 SS ND2251EM 00 c ccc c cece eee e eee teen teen nen e ee 90 Optical Laser Detector Anal 200 SS 7251 0 cece cece eee cece eee cee E ete ene e teen nee e ee 91 Optical Thermal Detector Anal 200 SS 2251TEM eee eee cece cece eee eee eee en nen e ee 92 Optical Thermal CO IR Detector Anal 200 SS 2251CTLE 2 0 0 cece cece cece eee eee cee eee e eee 93 Thermal Detector Anal 200 SS 5251EM 2 0 0 0 ccc cc ccc cece cence cece cence nen terete nen eenenene 94 Optical Filtrex Smoke Detector Anal 500 SS FTX P1 oo cece eect eee eet e eee eeeee 94 Monitor Module Anal 500 SS MS03ME 0 00 ccc cc ccc e cence eee cece n eee n een e ene een ean ens 95 Monitor Module I xSurv In Anal 200 SS M210E 2 cc cece ccc cece cence ence een e renee ens 96 Monitor Module 2xSurv In Anal 200 SS M220E 0c c cece ence cece een ence een een teens 96 Module 2xSurv In 1xRel Out Anal 200 SS M221E oo ccc cc ccc cence centre nen enees 97 Monitor Module 10xSurv In Anal 200 SS IM 10 2 0 0 cece ccc cece cece n ence ete ne nn eens 97 Control Module 1x
327. ece cence eee een cannes 236 Sounder Strobe WB XP95ISM White Clear Slow Whoop 45681 332 0 cece eee eee een es 237 Sounder Strobe WB XP95ISM White Clear DIN 45681 334 2 0 0 cece cece cece eee eee eeeee 238 Sounder Strobe WM XP95ISM Red Multitone 100dB 55000 293 6 cece cece cece eee e eae 239 Sounder Strobe WM65 XP95ISM Red Multitone 100dB 55000 298 ccc cee cece eee eens 239 Strobe FB XP95 White Red 55000 877 2 0 0 ccc ccc ccc cece eenn cee ten ence nent eee en en ennene 240 Strobe FB XP95 White Clear 55000 878 0 6 c ccc cece cece nee eee ence teen eee eee nen eens 241 Strobe FB XP95 White Orange 55000 879 2 0 00 cece cece cence ee eee ene ee etn been een eneneee 241 Sounder WM 200 Red Multitone 100dB WMSOU RR PO1 0c e ccc ccc cece n ence eee 242 Sounder WM 200ISM Red Multitone 100dB WMSOU RR PO2 00sec ccc cee een ene ee ees 242 Sounder Strobe WM 200 Red Multitone 100dB WMSST RR PO1 0 0 cece cece eee e ene eee 243 Sounder Strobe WM 200ISM Red Multitone 100dB WMSST RR P02 0 0 c cece cee ee ees 244 Sounder WB 200 White Multitone IBSOU DD PO1 0 0 cece ncn nee een tenes 245 Sounder WB 200ISM White Multitone IBSOU DD P02 occ ccc cnn ence ene eees 246 Sounder Strobe WB 200 White Red Multitone IBSST DR PO1 0 0 ccc cece ccc cece ene e eens 247 Sounder Strobe WB 200ISM White Red Multitone IBSST DR P02 0 0 c cece eee e ences 248 Strobe WM 200
328. ector housing Direct connection to the ADM loop with System Sensor 200 protocol without external po wer supply except for powering the test unit Integrated dual isolator activation by removal of two jumpers Receiver LED display for alarm and fault as well as display for preset values and commis sioning support Adjustment screws for an easy alignment of the detector Test filter for optimal commissioning included in delivery Specifications Operating voltage Current consumption supplied through loop voltage 2mA quiescent 8mA active 200 Chapter 20 Special Detectors 244024 244025 Operating voltage test filter 15 to 32VDC Current consumption test filter max 500mA Ambient temperature 30 C to 55 C Relative humidity max 95 no condensation Dimensions W x H x D 190 x 254 x 84 mm Smoke Detector 6500 Dimensions W x H x D 200 x 230 x 10 mm Reflector 5 to 70m Protection class IP54 Colour cream Weight 1 8kg Approval VdS G205033 EN 54 12 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 200 244025 Multi Mount Kit 6500 BEAMMMK 200 244024 Reflector 6500 75 100M BEAMLRK 201 244026 Surface Mount Kit 6500 BEAMSMK Reflector 6500 75 100M BEAMLRK Reflector mirror for joint application with the Beam Smoke Detector Series 6500 for exten ding the surv
329. ed channel whereas fault of the laser smoke detector is transmitted via the according detector address Every fault condition of a channel also causes the deacti vation of the relay FAULT This relay serves for transmission of fault messages when con nected in conventional technology 169 BB072001 SAM 0720 01 0100 212 Chapter 21 Aspiration Smoke Detection Systems 244032 The conditions for detector fault ventilator fault ALERT ACTION and FIRE of each chan nel are signalled via LEDs The conditions for operation and summary fault are signalled by one combined LED The velocity of air flow or alternatively the smoke density of each chan nel can be indicated via 10 step LED displays The aspiration smoke detection system is provided with the entire evaluation electronics and the laser smoke detector but without the sensor pipe network Specifications Supply voltage 18 30VDC Current consumption ext supply 80 500mA at 24V depending on tube length and ven tilator speed Current consumption by loop max 390uA quiescent Response sensitivity of detector 0 03 m to 3 33 m Pipe length max 50m per channel Ambient temperature 10 C to 60 C Humidity max 95 non condensing Protection class IP50 optionally IP65 Dimensions W x H x D 258 x 194 x 145 mm Weight 1 9kg Approval VdS pending Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire D
330. ed in delivery Features Mounting base for Series XP95 Discovery detectors Applicable in ventilation ducts of 300mm to 1500mm width Suitable for wind speeds of 1 0m s to 25m s Transparent cover for optical identification of a de tector activation No electronics contained No impact on the operation of the ventilation system Included drilling template for easy mounting Specifications Ambient temperature 0 C to 60 C Dimensions L x W x H 245 x 110 x 92 mm Colour grey Weight 1 5kg Cross references Page Art Nr Name Type 138 240026 Ionisation Smoke Detector Anal Disc Apo AI 58000 500 136 240024 TIonisation Smoke Detector Anal XP95 Apo AI 55000 520 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 139 241027 Optical Smoke Detector Anal Disc Apo AO 58000 600 136 241023 Optical Smoke Detector Anal XP95 Apo AO 55000 620 246032 Detector Heater Conv 60 65 Apo MH60 1 Mounting base with included heating for the application of an Apollo Series 65 optical smoke detector in extremely moist areas e g loading ramps cable ducts A detector base with area heater and an installation box with connection terminals and a remote indicator are mounted to gether on a mounting plate Features Connection terminals for all incoming and outgoing cables 169 BB072001 SAM 0720 01 0100 246033 249028 169 BB072001 SAM 0720 01 0100 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY 155 D
331. ed with the control panel due to numerous possible combinations to alarming devices and transmitting devices and combinations for actuations The control panel complies with to the European standards EN 54 2 and EN 54 4 in all points including all options for hig hest safety demands The control panel is integrated in a wall mount cabinet made of powder coated steel sheet and is equipped with a Loop In terface LIF64 1 by default In addition the control panel is prepared for accommodation of one Fire Brigade Interface FWI2 1 one Fire Brigade Interface Additional Board FWZ2 1 one LED Display Field LAB48 a Serial Interface Module SIM216 1 and further optional compo nentries as well as of stand by batteries 2 x 12V max 22Ah The mounting position for function module 2 is non functional The labelling of operating and display elements display texts and text printouts come in English language The configuration parameters of the control panel can be quickly and reliably created on a PC by means of the Windows parameter setup software PARSOFT 1 and transferred to the con trol panel In addition parameter data can be directly entered either on the control panel via the keyboard of the integrated display and operating field or via a standard PC keyboard Essential features Micro processor technology with diverse redundant processing logic Administration of up to 128 detector zones for manual call points aut
332. edium sound level max 6 8mA high sound level typ 70dB A 1m distance low sound level typ 79dB A 1m distance medium sound level 246 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 355165 Examples at 24V Continuous tone 660Hz DIN tone 1200 500Hz Slow Whoop tone 500 1200Hz Ambient temperature typ 87dB A 1m distance high sound level max 95dB A 1m distance high sound level typ 4 2mA at 90dB A 1m distance typ 5 4mA at 89dB A Im distance typ 5 5mA at 86dB A 1m distance 25 C to 70 C 10 96 no condensation 112 x 42 mm without detector incl Base LPB W cream RAL 9001 Relative Humidity Dimensions x H Colour Weight Approval Cross references Page 254 254 255 26 32 35 134g VdS G206072 Art Nr Name Type 359040 Base Sounder amp Strobe IP24 White LPBW 359043 Base Sounder amp Strobe IP44 White SDBW 359044 Base Sounder amp Strobe IP65 White WDBW 214034 BCnet Sectional Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 Sounder WB 200ISM White Multitone IBSOU DD P02 The addressable sounder is accommodated in a round white plastic housing and is prepared for indoor surface mounting The integrated base is suitable for accommodation of fire detec tors Series 200 The unit is mounted on a base for signalling devices not provided The so under is actuated as a module usin
333. ee e ee eens 263 Steel Column V2A for F0345 HSFSK700 2 D2 263 Steel Column V2A for FSE MP1 Strobe HSFSK700 2 D6 0 eee cee cence neces 262 Steel Column V2A for FSE MP1 HSFSK700 2 D5 264 Steel Column V2A for Strobe HSFSK700 2 D4 Strobe 24V Orange BE A S 2 0 24VBMT Strobe 24V Red BE R S 2 0 24VBMT 55 Strobe FB XP95 White Clear 55000 878 Strobe FB XP95 White Orange 55000 879 Strobe FB XP95 White Red 55000 877 Strobe WM 200 Red WMSTR WR POI 55 Strobe WM 200ISM Red WMSTR WR P02 Strobe WM 24V Red Orange MS2RA Strobe WM 24V Red Red MS2RR 24V Surface Mount Box MCPSA SR Surface Mount Box MCP5A SR3T Surface Mount Kit 6500 BEAMSMK Surface Mounting Box for M200 SS M200SMB 117 Surface Mounting Box for M500 SS SMB500 118 249111 249117 246009 329015 249053 222007 214130 214232 244639 249036 249059 249058 242002 242028 242023 242013 242014 242010 242012 242047 242046 242041 242042 242027 242071 242031 242033 242035 242045 242040 242024 242025 242026 242070 242030 242032 242034 242029 244237 212032 249635 265660 265661 229010 249012 218022 246113 210210 Product List Surface Mounting Box for MS200 SS M200SMB KO 117 Surface Mounting Box for Multimodule SS M200 SMB MM 00cceecceeee eee rrene 11
334. eee seb eres 119 249044 Detector Mounting Bracket MMW1 1 0 c cece cece eee cen e eee tcnn eect enn eneeeene 120 249635 Trapezoid Steel Bracket TBH800 1 aroonenennnanvnnnnnvenenananuenennnnuenenanuenenananuueenn 121 249640 Protective Cage BWS 1 D1 aonaouanunnnnnennnnnnevenananenennnnnuvernnnuenennnnnuueennanueeer 121 244009 Duct Detector 400 OM DH400P runnnvvnnnannenennnanvernnnvevenanreverennanuenrnnnuueseren 122 241038 Optical Smoke Detector Conv 100 SS 2151E LC aannnnvnnenannnvernanvevenrnnevvernranvenennr 122 244008 Duct Detector Housing Anal 500 200 SS DH500 aaruuvenenananvernnnuenenrnnnvvernrrnvenrnnr 123 244005 Duct Detector Pipe 0 3 0 6M SS ST 1 5 0 eee cece eee ene e eee e teen eee e enn ene ee 123 244010 Duct Detector Pipe 0 6 1 2M SS ST 3 cece cece nent t nent eee enn ence enen eee ee 124 244011 Duct Detector Pipe 1 2 2 4M SS ST 5 oo cece ect eee cnt e eee tet nee e enn ene e eens 124 244012 Duct Detector Pipe 2 4 3 7M SS ST 10 oo eee cece cette eee teen ee ett een eee e enn e ne ee 124 249047 Replacement Filter for Filtrex RF FTX 2 0 00 cece cece ccc cece e een eet nee n ee nnn nee e es 124 Conventional Detectors Series 65 ORBIS 240027 _Ionisation Smoke Detector Conv 65 Apo GI 55000 217 2 0 0 cece cece eee ct eee ee nee n eee 126 241026 Optical Smoke Detector Conv 65 Apo GO 55000 317 1 2 cece cee eee ete eect eee e nee n ees 126 242024 Thermal ROR Detector Conv 65 Apo GD 55000 1
335. eillance voltage A Features 4 different tones Continuous tone 800Hz Alternating tone 800Hz 1 000Hz Slow whoop DIN 33404 tone Wide operating voltage range Low power consumption Adjustable sound level Suitable for surface mounting OO Specifications Operating voltage 9 to 33VDC Current consumption at 24V 4 5 to 12mA Sound level 86 to 93dB at 1m distance Ambient temperature 30 C to 70 C Dimensions x H 117 x 30 mm Colour cream RAL 9001 Weight 150g Approval according to EN 54 3 230 Chapter 24 Optical and Acoustic Devices conventional 356001 356650 356671 Cross references Page Art Nr Name Type 252 359005 Lid for Sounder DBS Red DBSLIDR 252 359006 Lid for Sounder DBS White DBSLIDW Strobe WM 24V Red Orange MS2RA The beacon MS2RA is mounted in a red plastic housing with an orange cap and is suitable for indoor and outdoor mounting Features Very high flash energy Suitable for surface mounting Coloured cap can be changed Long life span Specifications Operating voltage 24VDC Current consumption at 24V 300mA active Flash frequency 1Hz Ambient temperature 25 C to 40 C Protection class IP54 Dimensions W x H x D 88 x 88 x 81 mm Weight 240g Approval VdS G28714 Strobe WM 24V Red Red MS2RR 24V The Strobe MS2RR is accommodated in a red plastic housing with red cap and is prepared for indoor and outdoor mounting Features Very high flash energy
336. eillance range from 70 to 100m The reflector consists of 3 parts which are mounted together with the mirror that comes enclosed with the detector Specifications Material plastics Dimensions W x H x D 200 x 230 x 10 mm single unit Dimensions W x H 400 x 460 mm total reflecting area Cross references Page Art Nr Name Type 198 244020 Beam Smoke Detector Anal SS 6500 196 244022 Beam Smoke Detector Conv SS 6500R 199 244021 Beam Smoke Detector Test Anal SS 6500S 197 244023 Beam Smoke Detector Test Conv SS 6500RS Multi Mount Kit 6500 BEAMMMK Mounting accessory used to install the Beam Smoke Detector Series 6500 or the reflector for application under difficult conditions slope of the ceiling etc Depending on the applicati on the Multi Mount Kit may be required for both the beam smoke detector and for the reflector If the reflector must be used in connection with the Multi Mount Kit the surveillance gt range is limited to 70 meters j Features I Three dimensional adjustment of the bracket possible gt Mounting alternatively on ceiling or wall E 169 BB072001 SAM 0720 01 0100 244026 244610 169 BB072001 SAM Chapter 20 Special Detectors 201 Surface Mount Kit 6500 BEAMSMK The Surface Mount Kit BEAMSMK allows for the surface mounting of the Beam Smoke Detector Series 6500 or for the mounting of the detector in combi nation with the Multi Mount Kit BEAMMMK gt
337. el Bracket TBH800 1 169 BB072001 SAM 0720 01 0100 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY 153 246034 Detector Base Anal Apo 45681 250 Mounting base in flush mounting design for automatic fire detectors Series XP95 and Disco very with programmable address card incl cover plate in particular for mounting in inserted ceiling made of mineral fibre Sa Ory ud Specifications Dimensions x H 150 x 15 mm Colour white Weight 70g Cross references Page Art Nr Name Type 141 243100 CO Detector Anal Disc Apo AC 58000 300 138 240026 Ionisation Smoke Detector Anal Disc Apo AI 58000 500 136 240024 TIonisation Smoke Detector Anal XP95 Apo AI 55000 520 141 241022 Optical Thermal Detector Anal Disc Apo AMS 58000 700 138 241030 Optical Thermal Detector Anal XP95 Apo AMS 55000 885 139 241027 Optical Smoke Detector Anal Disc Apo AO 58000 600 136 241023 Optical Smoke Detector Anal XP95 Apo AO 55000 620 71 251001 Remote Indicator PA58 1 140 242028 Thermal Detector Anal Disc Apo AD 58000 400 137 242023 Thermal Detector Anal XP95 Apo AW 55000 420 246029 Conduit Box Apo SZA 45681 204 Supplement base used in addition to detector bases Series 65 XP95 or Discovery for surface mounting and insertion of installation tubes or thick cables prepared for PG screw connections Specifications Dimensions x H 100 x 30 mm Colour white Weight 60g Cross references Page Art Nr Name Typ
338. el OP BC216 2 INT1 33 214208 Display and Operating Front Panel ABP216 1E INT1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT1 16 214308 Fire Detection Control Panel BC216 1S INT1 72 252010 LED Display Tableau LAT288 1 72 252011 LED Display Tableau LAT288 1CE 73 252012 Remote Tableau Drive Unit PTU288 1 LED Display Field LAB48 3 The LED Display Field LAB48 3 contains 48 freely parameterisable double LEDs 24 pairs red yellow 24 pairs yellow yellow for the individual display of events of the detector zones actuations transmitting devices or alarming devices at Fire Detection Control Panels Series BC216 and of events of the flooding zones and extinguishing systems at the Extinguishing Con trol Panel Series LC216 The double LEDs are arranged in two rows each with 24 pairs In addition the LED Display Field can be instal led into an LED Display Tableau LAT288 that serves as a freely programmable display for the events of a Fire Detection Control Panel Se ries BCO16 or BC216 as well as an Extinguishing Control Panel Series LC216 Features 24 double LEDs left hand side red right hand side yellow freely parameterisable accor ding to individual events 24 double LEDs yellow freely parameterisable according to individual events Display of activation as well as deactivation or fault condition of the parameterised event Designation labels allow for individual
339. el Small Sheet 20pcs BME KL BOG 226 Detector Module DM TP 05 L Detector Module DM TP 25 L Detector Module DM TP 80L Detector Module DM TT 05 L Detector Module DM TT 25 L Detector Module DM TT 80 L Detector Mounting Bracket MMWI 1 120 Detector Relay Base Anal 500 200 SS B524RTE 110 Detector Relay Base Anal XP95 DISC Apo ASR45681 242 asrieriroierirrit rotori er os kle ens 152 Detector Relay Base Conv 1000 SS ECOI000BREL24L 2 2 0 cece cece cece 107 Detector Relay Base Conv 300 SS B312NL 106 Detector Relay Base Conv 300 SS B312RL 106 Detector Relay Base Conv 300 SS B324RL 105 Detector Relay Base Conv ORBIS Apo RB 10004 150 Detector Relay Base Conv SS ECO1000BREL12L 108 Detector Relay Base Conv SS ECO1000BREL12NL 108 Detector Relay Base FC600 FC600 BREL Detector Removal Tool SOLO200 Detector Reset Module MQZ1000 1 Detector Zone Extension MGE8 1 Dialogue Module DPM805 1 Diode 100pcs 1N4004 Display and Operating Front Panel ABP216 1E A1 Display and Operating Front Panel ABP216 1E D1 34 Display and Operating Front Panel ABP216 1E INT1 33 Display and Operating Front Panel ABP216 1F NL1 34 Duct Detector Housing Anal 500 200 SS DH500 Duct Detector Housing Anal Apo LG 53546 016 Duct Detector Pipe 0 3 0 6M SS ST 1 5 123 Duct Detector Pipe 0 6 1 2M SS ST 3 04 124 Duct Detector Pipe 1 2 2 4M SS ST 5 1 2 ee
340. emovable Mounting rails for additional components Side by side mounting with or without side wall Cable duct Built in lighting Mounting plate 10cm or 20cm base optional Specifications Dimensions W xH x D without base 800 x 1800 x 500 mm Colour light grey RAL 7035 Weight approx 150kg Transparent Door 19 36HU SIT19 STAND Transparent door for Housing 19 36HU GEH19 STAND with acrylic glass pane double bit insert for closure and mounting accessories Features Frame made of aluminium profiles Locking rod with double bit insert equipped with 180 hinges as standard Exchangeable 3mm thick acrylic glass pane Special sealing for protection class increase of housing equipped with transparent door Specifications Dimensions W x H x D 800 x 1800 x 40 mm Colour frame light grey RAL 7035 Protection class housing door IP54 169 BB072001 SAM 0720 01 0100 4 Chapter 4 Extinguishing System Controls 47 Extinguishing System Controls 2189990 218024 169 BB072001 SAM 0720 01 0100 Extinguishing Control Panel Series LC216 Description The Extinguishing Control Panel Series LC216 is an extended Fire Detection Control Panel BC216 with electrical control equipment for extinguishing systems All functions of the fire detection control panel remain intact after the extension A combined use as fire detection and extinguishing control panel is possible without furt
341. ent colours Long lifespan Specifications Operating voltage 20 30VDC Current consumption at 24V 155mA Flash frequency 1Hz Ambient temperature 20 C to 55 C Protection class IP54 Dimensions x D 93 x 75 mm Colour flame red RAL 3000 Weight 240g Approval VdS G296014 Sounder Strobe 24V Red Red MS5RR Strobe and sounder combined together on a housing frame installed in a red plastic housing with red cap for outdoor and indoor mounting Features Very high flash energy 32 different tones programmable Adjustable sound level Suitable for surface mounting Exchangeable cap for different colours Long lifespan Oo Specifications Operating voltage 20 28VDC Current consumption at 24V 350ma active 231 232 Chapter 24 Optical and Acoustic Devices conventional Flash frequency Sound level Ambient temperature Protection class Dimensions W x H x D Colour Weight Approval 1Hz max 108dB 25 C to 40 C IP54 160 x 88 x 81 mm flame red RAL 3000 460g according to EN 54 3 169 BB072001 SAM 0720 01 0100 25 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 233 Optical and Acoustic Devices ADM Series XP95 200 355133 355131 169 BB072001 SAM 0720 01 0100 Sounder WB XP95ISM White Alert 45681 277 The addressable loop sounder is installed in a round white plastic housing and is prepared for indoor surface mounting The integrated detector b
342. ent consumption Alarm temperature Operating temperature Ambient temperature typ 75uA quiescent typ 58 C max 45 C 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 x 40 5 mm Colour white 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 Chapter 11 Conventional Detectors Series 300 ECO1000 89 Weight 70g Approval VdS G201073 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 107 246140 Detector Base Conv 1000 SS ECO1000BR 1000 107 246141 Detector Relay Base Conv 1000 SS ECO 1000BREL24L 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PAS8 1 113 246150 Remote Test Unit Conv 300 1000 SS ECO 1000RTU 4 210210 Zone Extension Board ZEB2 1 90 Chapter 12 Analogue Detectors and Modules Series 200 500 12 Analogue Detectors and Modules Series 200 500 240013 241010 lonisation Smoke Detector Anal 200 SS 1251E Addressable smoke detector operating on the ionisation principle for application on the ADM loop using System Sensor 200 protocol unipolar chamber in a dual system consisting of a sensing and reference chamber for automatic compensation of environmental
343. ent freely programmable tones Large operating voltage range Adjustable sound level Suitable for surface mounting Specifications Operating voltage 10 to 32VDC Current consumption at 24V 20 to 110mA depending on the tone type Sound level max 106dB Ambient temperature 25 C to 50 C Protection class IP54 Dimensions W x H x D 88 x 88 x 81 mm Colour flame red RAL 3000 Weight 250g Approval VdS G28702 355014 Sounder WM 12 24V White Multitone 106dB MS1W The multitone sounder MS1W is integrated in a white plastic housing and is suitable for in door and outdoor mounting Due to the built in serial diode the sounder can be directly con nected to a line monitored output with negative monitoring voltage Features 32 different freely programmable tones Large operating voltage range Adjustable sound level Suitable for surface mounting Specifications Operating voltage 10 to 32VDC Current consumption at 24V 20 to 110mA depending on the tone type Sound level max 106dB Ambient temperature 25 C to 50 C Protection class IP54 Dimensions W x H x D 88 x 88 x 81 mm Colour white RAL 9003 Weight 250g Approval VdS G28702 169 BB072001 SAM 0720 01 0100 355101 355102 169 BB072001 SAM 0720 01 0100 Chapter 24 Optical and Acoustic Devices conventional 229 Sounder WM 12 24V Red Multitone 103dB EMA1224B4R The multitone sounder EMA1224B4R is integrated in red plastic housing for indoor
344. entification for up to 64 addresses per detector line in conjunction with optional address modules Detector lines monitored for wire breakage short circuit and earth fault Freely parameterisable allocation of the detector lines for activating transmitting devices actuations and alarming devices Independent CMOS processor to ensure the alarming capability even at system failure of the control panel Specifications Current consumption at 24V typ 50mA 8 zones terminated without detectors Line voltage typ 20 0V Line current typ 3 7mA End of line resistance 5 6kOhm Line resistance max 50 Ohm per core Ambient temperature 5 C to 50 C Dimensions L x W x H 132 x 74 x 10 mm Weight 80g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E Loop Interface LIF64 1 The Loop Interface LIF64 1 supports one ADM loop with bi directional data exchange Sy stem Sensor 200 or Apollo Discovery protocol with up to 198 loop elements in Fire Detecti on Control Panel Series BC216
345. equired therefor PC keyboard mouse One of the serial interfaces of the BCnet sectional control panel that has been parameterised as main operating unit of a Fire Detection Control Panel BCnet216 or of the Fire Detection Control Panel BC216 1 BC216 1CE BC216 1S BC016 respectively must be provided with a Serial Interface Module SIM216 1 so that the PC can be connected Alarm Monitoring Software License ALVIS F Control center license for using an operation control system for alarm reporting systems The software allows for a concise depiction of the ground plans as well as detailed views of the facility The alarm monitoring software is a modular system with a modern user interface and can be configured according to your individual needs The system allows for a comfortable uniform operation and control of the alarm reporting system Depending on the configuration of the user interface overview screens and photos of the facility can be displayed at any time thus providing an optimal and quick overview in any situation Detail screens inform about all im portant events and report them chronologically as well as by type Each event triggered by a detector can be located with the respective detector on the corresponding screen window by a simple mouse click Depending on the authorisation level operations regarding the fire de tection system disablement of detectors operating units actuations etc can be carried out
346. er a ventilator po wered by an external 24VDC power supply is integrated in the detector in order to convey enough air into the sensing cham ber The ventilator works in a 15 duty circle 5s on 30s off o Intelligent evaluation algorithms compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept constant for a long time thus constituting another effective measure for preventing false alarms Features Constant sensitivity 2 decadic rotary switches for setting the physical address from 01 to 99 Removable filter Specifications Operating voltage detector Current consumption detector Operating voltage ventilator Current consumption ventilator Ambient temperature supply through the loop voltage max 230uA quiescent 15 to 30VDC 6mA 30s stand by 60mA 5s duty 10 C to 55 C 10 93 no condensation 102 x 89 mm cream 207g DIFT 0845 CPD 232 1427 Art Nr Name Type Relative humidity Dimensions x H Colour Weight Approval Cross references Page 26 111 32 35 124 214034 BCnet Sectional Control Panel Extension BCE216 3LG 246012 Detector Base Filtrex Anal 500 SS B524FTXE 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 249047 Replacement Filter for Filtrex RF FTX Monitor Module Anal 500 SS M503ME Addressable compact module for the line monitored
347. erating voltage supplied through loop voltage Current consumption 1mA quiescent Ambient temperature 20 C to 70 C Dimensions L x W x H 76 x 47 x 14 mm Connection technology six flexible wires of 150mm length Colour white Weight 46g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 147 249029 Isolator Module Anal Apo ISM 1 3 35 214021 Loop Interface LIF64 1 249060 Monitor Module Interrupt Anal XP95 Apo UMI 55000 832 Addressable compact mini module used for the line monitored integration with prioritised alarm transmission of contact detectors e g manual call points into the bi directional com munication on the ADM loop using Apollo Discovery protocol Features sae Prioritised quick alarm transmission to the fire detection control panel Output for an optional LED indicator Switch for setting the physical address from 01 to 126 169 BB072001 SAM 249072 249076 169 BB072001 SAM 0720 01 0100 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 143 Specifications Operating voltage Current consumption Ambient temperature Dimensions L x W x H Connection technology supplied through loop voltage 1mA quiescent 20 C to 70 C 76 x 47 x 14 mm six flexible wires of 150mm length white 46g Art Nr Name Type Colour Weight Cross references Page 26 32 147 35
348. ergency power supply of electronic security systems in stand by operation 288 Chapter 31 Batteries and Power Supply Devices 310012 310003 For 24V applications 2 batteries of identical type must be connected in series Due to techno logical progress the stated specifications may differ Specifications Nominal voltage 12V Capacity 18Ah min at 20 hours discharge Dimensions L x W x H 181 x 76 x 167 mm max Weight max 6 3kg Approval approved by VdS Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT 1 27 214108 Fire Detection Control Panel BC216 1CE INT1 16 214308 Fire Detection Control Panel BC216 1S INT1 72 252010 LED Display Tableau LAT288 1 Stand by Battery 12V 20Ah Maintenance free sealed accumulator with fixed electrolyte and low self discharge suitable in particular for emergency power supply of electronic security systems in stand by operation For 24V applications 2 batteries of identical type must be connected in series Due to techno logical progress it was possible to achieve a still higher energy density The dimensions of this type series correspond to
349. ermal Detector Anal 200 SS 5251EM 121 249635 Trapezoid Steel Bracket TBH800 1 116 249012 Wet Base Shroud SS WB1 Detector Relay Base Anal 500 200 SS B524RTE The Detector Base is used for mounting of fire detectors Series 500 and 200 and includes an integrated relay output The relay output is active as long as the detector remains in alarm condition The application has to be in compliance with the LST Connection of Detectors The base is suitable for indoor surface mounting Features Connection to the ADM loop using System Sensor 200 protocol Multi wire terminal with secure screw fitting Relay output with dry changeover contact Specifications Contact rating 1A at 30VDC Ambient temperature 10 C to 60 C Relative humidity 10 93 no condensation Dimensions x H 102 x 36 mm Colour cream Weight 110g Cross references Page Art Nr Name Type 114 246006 Base Adapter SS MZP500 1 226 249011 Detector Label BME BEZ 120 249044 Detector Mounting Bracket MMW 1 1 90 240013 Ionisation Smoke Detector Anal 200 SS 1251E 92 241020 Optical Thermal Detector Anal 200 SS 225 ITEM 91 241050 Optical Laser Detector Anal 200 SS 7251 90 241010 Optical Smoke Detector Anal 200 SS ND2251EM 115 246010 Recessed Mounting Kit SS RMK400 115 246009 Surface Mounting Kit SS SMK400 94 242002 Thermal Detector Anal 200 SS 5251EM 116 249012 Wet Base Shroud SS WB1 Isolator Detector Base Anal 500 200 SS B524IEFT 1 Mounting base for
350. ermanent evaluation of environmental conditions Continuous transmission of the current measured value to the fire detection control panel Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Mechanical theft protection supplied through loop voltage EEx ia IIC TS typ 340uA quiescent 20 C to 40 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 100g Approval EECS ATEX 0073 LPCB 010q Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 179 246027 IS Detector Base Anal Apo ASEX 45681 215 35 214021 Loop Interface LIF64 1 180 228005 Protocol Interface Anal XP95 Apo API 55000 855 180 228004 Safety Barrier Anal XP95 Apo AES 29600 098 IS Thermal Detector Anal XP95 Apo AWE X 55000 440 Addressable heat detector for hazardous areas operating on the heat detection principle for application on the ADM loop using Apollo Discovery protocol in extra flat design suitable for indoor mounting The detector is assigned to class 2 maximum room height 6m Which 169 BB072001 SAM 0720 01 0100 246027 169 BB072001 SAM 0720 01 0100 Chapter 18 Devices for Hazardous Areas 179 principle is used for the evaluation of the measured values maxi mum
351. ery fault condition also causes the deactivation of the relay FAULT This relay serves for transmission of fault messages when connected in conventional technology The conditions for operation summary fault detector fault ventilator fault ALERT ACTI ON and FIRE are signalled via LEDs The velocity of air flow or alternatively the smoke den sity can be indicated via a 10 step LED display The Aspiration Smoke Detection System A211E LSR can be equipped with an optional se cond laser smoke detector which is in interdependence with the first detector if fire alarm sy stems require a double knock function The aspiration smoke detection system is provided with the entire evaluation electronics and the laser smoke detector but without the sensor pipe network Specifications Supply voltage 18 30VDC Current consumption ext supply 80 500mA at 24V depending on tube length and ven tilator speed Current consumption from loop max 390A quiescent ior ami 169 BBO72001 SAM 0720 01 0100 Chapter 21 Aspiration Smoke Detection Systems 211 Response sensitivity of detector 0 03 m to 3 33 m Pipe length max 75m Ambient temperature 10 C to 60 C Humidity max 95 non condensing Protection class IP50 optionally IP65 Dimensions W x H x D 258 x 194 x 145 mm Weight 1 9kg Approval VdS pending Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Dete
352. ess steel with micro switch as change over contact and a 10m long connection cable Suitable for flush mounting or for installation in a Standard Column V2A for FSK700 2 The Unblock ing Element FSE MP1 is prepared for the integration of a half cylinder kj 3 oTe Specifications Dimensions x L 62 x 70 mm Approval VdS G199083 Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D 1 258 265742 Fire Brigade Key Box FSK700 2852 D1 262 265765 Steel Column V2A for FSE MP1 Strobe HSFSK700 2 D6 264 265764 Steel Column V2A for FSE MP1 HSFSK700 2 D5 Fire Brigade Key Deposit Surface Mount FASB AP The Fire Brigade Key Deposit FASB for surface mounting is used for storage of additional building keys The key deposit is delivered without a lock It provides authorised access for the fire brigade or secured access for service personnel e g technicians for elevator or hea ting On fire brigade access routes the key deposit is only allo wed on demand by the fire brigade e g when the access to the t fire brigade key box is secured by a barrier The door and the stored key are not monitored The door is opened and locked D simply by means of the cylinder lock Features Key deposit made of powder coated steel sheet Easy to mount Specifications Colour pebble grey RAL 7032 Dimensions W x H x D 150 x 150 x 57 mm rer nd 266 Chapter 27 Fire Brigade Key Boxes and
353. est Unit S300RPTU or the Remote Test Unit ECO1000RTU Detector condition detector address and date of the last maintenance can be read out with the Remote Program and Test Unit SJOORPTU Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 85uA quiescent Alarm temperature 58 C Operating temperature max 45 C Ambient temperature 30 C to 70 C continuous operation Relative humidity 5 to 95 no condensation Dimensions x H 102 x 43 mm Colour cream Weight 75g Approval LPCB 199n Issue9 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 105 246008 Detector Base Conv 400 100 300 SS B401RM 105 246100 Detector Relay Base Conv 300 SS B324RL 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 112 246111 Remote Program and Test Unit Conv 300 SS S300RPTU 113 246150 Remote Test Unit Conv 300 1000 SS ECO 1000RTU 113 246112 Satellite Unit for Remote Programming Conv 300 SS S300SAT 112 246113 Zonal Display Unit Conv 300 SS S300ZDU 4 210210 Zone Extension Board ZEB2 1 242041 Thermal Max Detector Conv 300 SS 4351E T
354. et Sectional Control Panel OP BC216 2EPS 9 210111 Fire Brigade Interface FW1016 1 36 214022 Fire Brigade Interface FWI2 1 273 250709 Fire Brigade Map Box FPKCLR900 1 274 250713 Fire Brigade Map Box FPKPHZR900 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT1 9 210112 Serial Interface Module SIM016 3 Fire Brigade Orientation Panel FOTR900 2 D1 The Fire Brigade Orientation Panel FOTR900 2 D1 in redundant design according to DIN 14662 provides the fire brigade on site quickly with the first precise information on the con dition of the fire detection system It includes the Fire Brigade Control Unit FBF900 1 D1 as 272 Chapter 28 Fire Brigade Control and Display Devices operating panel for Fire the case of Fire Brigade Detection Control Panels BC016 and BC216 according to DIN 14661 and the Fire Brigade Display Panel FAT900 2 D1 for information retrieval according to DIN 14662 Both devices are accommodated in a powder coated ST 37 steel case coloured in flame red RAL 3000 or in a colour requested by the ope rator To establish a redundant connection to a Fire Detection Control Panel BCO16 or BC216 the ADFAT900 2 D1 module has to be in stalled in the control panel A lock for half cylinders is mounted in Orientation Panel FOTR900 2 D 1 The Fire Brigade Orientation Panel FOTR900 2 D1 can be com bined with the Fi
355. etection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Aspiration Smoke Detection System Housing A310E The Aspiration Smoke Detection System Housing A3 10E can accommodate one or two smo ke detectors of any manufacturer Air from the monitored room is aspirated by the sensor pipe network that is connected to the housing and is directed to the detector Evaluation of the characteristics of smoke and the detection of alarm and fault depends on the applied detector The use of a sensitive detector is recommended such as a laser smoke detector to effectively detect a fire in an early stage The continuous air flow which is generated by a ventila tor in the aspiration smoke detection system housing is permanently monitored The system identifies the failure of the ventilator blocking of aspiration holes and pipe burst as fault The conditions for operation summary fault and ventilator fault are signalled via LEDs The velocity of air flow is indicated via a 10 step LED display The Aspiration Smoke Detection System Housing A310E can be equipped with an optional second smoke detector and set in interdependence with the first detector if fire alarm systems require a double knock function Smoke detector detector base and sensor pipe network are not provided with the aspira tion smoke detection system housing Specifications Supply voltage 18 30VDC Current consumption ext supply 80 500mA at 24V depe
356. etection Control Panels Series BC216 9 Hierarchized authorisation levels for operation and parameterisation secured via numeric codes 1 2 3 Alarm delay with dead man s handle controlled by internal timer which can be set up se parately for each day of the week Start and end date of Daylight Saving Time according to EU directive or freely parameterisable One man maintenance function 1 2 3 Non resetable electronic event counter One freely usable serial interface 3 Integrated INFO bus for the connection of a fire brigade control unit and an intelligent re mote indication unit 3 Connection of a serial protocol printer via optional data interface 3 Control panel recognises all control panel components and loop elements by means of au to setup during first commissioning Connection of detectors via unshielded 2 wire cabling Stand by battery 2 x 12V 22Ah can be integrated in control panel housing only with BC216 2 BC216 3 BC216 1CE BC216 3CE 1 Sectional Control Panels BC216 3 and BC216 3CE have no display and operating field installed these sectional control panels are operated by and the events are displayed on an operatable sectional control panel e g the main operating unit 2 Fire Detection Control Panel Modules have no display and operating field installed these sectional control panels are operated by and the events are displayed on an operatable sectio nal control panel e g the m
357. etection control panel The end of the lifespan is indicated with a fault message The detector is designed for use on the ADM loop using System Sensor 200 protocol and is suitable for indoor mounting Importantly operation in thermal mode only is only allowed in rooms that do not exceed a height of 7 5m For operation of the detector a firmware version PL149 Vx 21 or higher is required for para meterisation a PARSOFT Version V1 21 or higher is necessary Features Constant sensitivity of the optical sensing chamber Response sensitivity adjustable in 6 steps at the Fire Detection Control Panel Series BC216 2 decadic rotary switches for setting the address from 01 to 99 Sealed electronics prevents false alarms caused by environmental influences Output for external remote indicator Display of activated condition via 2 LED indicators that are visible from all angles Mechanical theft protection Insect screen Features Operating voltage supplied through loop voltage Current consumption max 300A quiescent Alarm temperature 58 C maximum temperature Wave length infrared sensor 800 1200nm Measurement range CO sensor 0 500ppm Ambient temperature 20 C to 55 C no condensation or icing Relative humidity 15 90 no condensation Dimensions x H 102 x 60 mm Colour cream Weight 130g 169 BB072001 SAM 0720 01 0100 94 Chapter 12 Analogue Detectors and Modules Series 200 500 Approv
358. etector base pre wired on the terminals Additional remote indicator on the installation box Specifications Operating voltage max 48VAC Power consumption 12W Dimensions L x W x H 310 x 175 x 120 mm Weight 1 3kg Cross references Page Art Nr Name Type 126 240027 Ionisation Smoke Detector Conv 65 Apo GI 55000 217 126 241026 Optical Smoke Detector Conv 65 Apo GO 55000 317 119 249014 Power Supply Unit for Detector Heater MH TR1 Detector Heater Anal Apo MH95 1 Mounting base with included heating for the application of an Apollo Series XP95 or Disco very optical smoke detector in extremely moist areas e g loading ramps cable ducts A de tector base with area heater and an installation box with connection terminals and a remote indicator are mounted together on a mounting plate Features Connection terminals for all incoming and outgoing cables Detector base pre wired on the terminals Additional remote indicator on the installation box Specifications Operating voltage max 48VAC Power consumption 12W Dimensions L x W x H 310 x 175 x 120 mm Weight 1 3kg Cross references Page Art Nr Name Type 138 240026 Ionisation Smoke Detector Anal Disc Apo AI 58000 500 136 240024 Ionisation Smoke Detector Anal XP95 Apo AI 55000 520 139 241027 Optical Smoke Detector Anal Disc Apo AO 58000 600 136 241023 Optical Smoke Detector Anal XP95 Apo AO 55000 620 119 249014 Power Supply Unit for Detector Heater MH TR1
359. etector zones the control panel can support a total of 144 detector zones ADM loop wiring can be accomplished as ring branch or any given combination of sectional rings and branches using two core unscreened cables ADM communication is achieved by means of bi directional data exchange between the fire detection control panel and every single element on the ADM loop ADM failure strategy secures full functionality of all elements connected to the ADM loop in case of wire breakage At short circuit all elements not affected by the short circuit thanks to the installed isolator modules are fully operable ADM alarm threshold tracing for every single smoke detector on the ADM loop accor ding to its individual contamination The sensitivity of every smoke detector is thus held constant over a very long period of time and deceptive alarms are avoided ADM alarm logic analyses the measured values above alarm threshold comparison of fire patterns to increase immunity against deceptive alarms ADM multi alarm logic increases the effect of the standard alarm logic by making use of the broad variety of freely parameterisable 2 detector or multi detector interdependencies ADM individual detector identification by assigning each physical address of an ele ment on the ADM loop a logical address that consists in a zone number and element number 2 line ADM detector text can be assigned to every logical address on the ADM loop In
360. everal fire areas Easy detector addressing through address card in mounting base Full operation of all loop elements not affected by the short circuit Multi useable terminals with secure screw fitting Terminal for external remote indicator Mechanical theft protection 152 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY 246037 Specifications Operating voltage supplied through loop voltage Current consumption max 43uA Ambient temperature 20 C to 60 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 24 mm Colour white Weight 100g Cross references Page Art Nr Name Type 153 246030 Backplate Apo SZPL 4568 1 233 141 243100 CO Detector Anal Disc Apo AC 58000 300 153 246029 Conduit Box Apo SZA 4568 1 204 120 249044 Detector Mounting Bracket MMW 1 1 138 240026 Jonisation Smoke Detector Anal Disc Apo AI 58000 500 136 240024 Ionisation Smoke Detector Anal XP95 Apo AI 55000 520 141 241022 Optical Thermal Detector Anal Disc Apo AMS 58000 700 138 241030 Optical Thermal Detector Anal XP95 Apo AMS 55000 885 139 241027 Optical Smoke Detector Anal Disc Apo AO 58000 600 136 241023 Optical Smoke Detector Anal XP95 Apo AO 55000 620 121 249640 Protective Cage BWS 1 D1 71 251001 Remote Indicator PA58 1 140 242028 Thermal Detector Anal Disc Apo AD 58000 400 137 242023 Thermal Detector Anal XP95 Apo AW 55000 420 121 249635 Trapezoid Steel Bracket TBH80
361. exible aspiration tube can be installed per ceiling duct Aspiration Tube DN 12x9 The Aspiration Tube DN 12x9 is used for the connection of system components of the cei ling duct Due to the flexible design of the aspiration tube aspiration elements can be precise ly fit in the false ceiling and can be connected with the sensor pipe network Air Filter for ASDS complete LF RAS The air filter is placed in the sensor pipe network outside the aspiration smoke detection sy stem housing to protect the detector module against rapid contamination The filter consists of 3 layers one filter each course medium fine which guarantee to reliably clean the aspira ted air but simultaneously allow smoke particles to pass in case of fire The filter is connected to the sensor pipe network via two PG 25 screw connections Three way Ball Valve 3MKH The three way ball valve enables the manual supply of compressed air to the sensor pipe net work During the change from normal mode to blow out mode the destruction of the aspira tion smoke detection system is avoided due to the leak proof centre position Specifications Input pressure max 16bar Connection 3 4 Weight 450g Condensate Separator DN25 KABS 25 The condensate separator is for installation in the sensor pipe network and guarantees that air samples which are directed to the aspiration smoke detection system are dry This is an 169 BB072001 SAM 0720 01 0100 Chapter 22 Acces
362. external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 45uA quiescent Alarm temperature 57 C maximum heat component Operating temperature max 50 C Ambient temperature 20 C to 90 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 80g Approval VdS G200059 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 149 246035 Detector Base Conv 60 65 Apo 45681 251 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT I 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 Thermal ROR Detector Conv 65 Apo GD 55000 127 Heat detector operating on the rate of rise heat detection principle in addressable conventio nal technology combined maximum rate of rise detector classified as BR maximum room height 6m in extra flat design suitable for indoor mounting 128 Chapter 14 Conventional Detectors Series 65 ORBIS 242026 Features Specifications Operating voltage Current consumption Alarm temperature Operatin
363. f green LED indicators on a synoptic remote tableau Specifications 8 On one end each cable has attached a bright green 5mm LED indicator and on the other end a 2 pin connector which fits the 2 54mm grid of the pin strip header on the LED Connection Module LAM48 1 For each LED indicator a black plastic LED clip is provi op ded to guarantee a time saving installation of LEDs No soldering required Specifications Operating voltage supply via LED Connection Module LAM48 1 Length of LED cable 2m LED 5mm Drilling for LED clip 6 3 6 5mm Thickness of front panel max 2mm Cross references Page Art Nr Name Type 74 252013 LED Connection Module LAM48 1 169 BB072001 SAM 0720 01 0100 259010 259012 259013 169 BB072001 SAM 0720 01 0100 Chapter 8 Display and Operating Devices 75 LED Assembled Red 10pcs LED RT 10 Functions specifications and cross references are equal to the packing unit of LED Assem bled Green 10pcs Pre assembled lines though are equipped with bright red LED indicators Cross references Page Art Nr Name Type 74 252013 LED Connection Module LAM48 1 LED Assembled Yellow 10pcs LED GE 10 Functions specifications and cross references are equal to the packing unit of LED Assem bled Green 10pcs Pre assembled lines though are equipped with bright yellow LED indicators Cross references Page Art Nr Name Type 74 252013 LED Connection Module LAM48 1 Cor
364. f industrial property rights raised against him if Seller manufactures an article pursuant to any design data design drawings models or other specifications made available to him by Buyer 13 2 Design documents such as plans and drawings and other technical specifications as 14 15 well as samples catalogues prospectuses pictures and the like shall remain the in tellectual property of Seller and are subject to the relevant statutory provisions go verning reproduction imitation competition etc The provisions of 2 2 above shall also cover design documents General Should individual provisions of the contract or of these provisions be invalid the va lidity of the other provisions shall not be affected The invalid provision shall be re placed by a valid one which comes as close to the target goal as possible Jurisdiction and applicable law Any litigations arising under the contract including litigations over the existence or non existence thereof shall fall within the exclusive jurisdiction of the competent court at Sellers domicile the competent court of the Bezirksgericht Innere Stadt Vienna shall have exclusive jurisdiction if Seller is domiciled in Vienna The con tract is subject to Austrian law excluding the referral rules Application of the UN Convention on Contracts for the International Sale of Goods is renounced 169 BB072001 SAM 0720 01 0100
365. face GIF8 1 2 ccc nec e ene nen een eee nen eeenees 35 Loop Interface LIFG4 1 usa cease duvet as Udo des vars Y E a ete ey eee ah eee ods 35 Fire Brigade Interface FWDA1 235s se esk oer ake idae Seen cee dengan SS 36 Fire Brigade Interface Additional Board FWZ2 1 1 0 0 2 cece cece cece eet c teen ee eeen nee eeenee 37 LED Display Field EAB4ST ra iroa e kes 37 LED Display Field LAB48 2 erenenevnanevennenanennnnennnennenennnennenennennnenennennneenenener 38 LED Display Field LAB48 3 seneneenanenennenanennenennnennnnennnenneeennennnenenneneneenenener 38 LED Display Field LAB48 4 enenuvnnnennnnennnennnnennnennnnennnennnnennenennnennenennennnener 39 Network Redundant Alarm Converter NNUS 1 2 0 0 0 ccc ccc cence cece cece ence een ene nn en enens 39 Auxiliary Case for BC216 GEH2164 0 cece cence eect eee e ec ten eect ee nnneeeeees 40 Terminal Set GBE AKS216 1 un ess Bed he BRAN a BAR NSA OS desse a Nie BEA Be en GEG Ae Sh ee 40 Terminal S t E AKS2162 ci sas che v rens eee bien vdnolanvods dus caused eke 41 Battery Bracket BKQ 16 1 vred Pee ate 41 Battery Bracket BK216 1CE Ls Asser salts 41 Mounting Bracket BW216 1 1 0 cece cence cece eee cnt e nee tet nese enn eneeeaee 42 Control Panel Rack 8HU RACK216 1E 2 0 0 ccc ccc ccc cee cence nen enn e een en eeenees 42 Module Carrier 19 3HU MPL17 3 s nn nee A nen e teen ene aran ees 42 Dummy Cover 19 2HU AD8C 2H x aeee er ies eraa estes EAEE esse EEE O E ERISA PEER ESEE E
366. face LIF64 1 ier av E 169 BB072001 SAM 0720 01 0100 249090 249091 249003 169 BB072001 SAM 0720 01 0100 Chapter 12 Analogue Detectors and Modules Series 200 500 103 Limit Switch Anal 500 SS EDS500 1 The addressable module EDS500 1 allows for the monitoring of the position of slides valves and similar mechanical appliances The bi directional communication on the ADM loop use the System Sensor 200 protocol The module is located in a plastic housing and is especially durable and fail safe due to the use of opto electronic components Features Status LED Button in combination with LED for setting the physical address Mounting terminals according to DIN912 M5 Specifications Operating voltage Current consumption supplied through loop voltage approx 300uA quiescent Ambient temperature 20 C to 60 C Dimensions L x W x H 59 x 32 x 63 mm Colour red black Protection class IP65 Weight 80g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 47 2189990 Extinguishing Control Panel Series LC216 Description 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Monitor Module Box Anal 500 SS UMB500 1 The addressable module UMB500 1 allows for the integration of a contact detector e g pressure switch temperature monitor into the bi directional communication on the ADM lo op with System Sen
367. for preventing false alarms If the contamination of the optical sensing system is too heavy or if it is defective the multicolour status LED on the detector will flash for approx 4 minutes in yellow colour after the detec tor line has been enabled Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional address module NG60 1 Output for external remote indicator Mechanical theft protection Insect screen Specifications Operating voltage supplied through detector line voltage Current consumption typ 65uA quiescent Ambient temperature 40 C to 70 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 60 mm 169 BB072001 SAM 0720 01 0100 242030 169 BB072001 SAM 0720 01 0100 Chapter 14 Conventional Detectors Series 65 ORBIS 131 Colour white Weight 140g Approval VdS G204040 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PAS8
368. g System Sensor 200 protocol pe Dew and is powered via the ADM loop A dual isolator is integrated in the sounder At short circuit it maintains the function of ADM elements that are not affected by the short circuit Depending on the parameter setup of the Fire Detection Control Panel Series BC216 and the system condition the panel can acti vate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combinations The sound level is adjustable in 3 steps but depends also on the chosen tone type The power consumption is dependent on the tone type and the adjusted sound level Features 32 different tone type combinations selectable via DIL switch e g continuous tone 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz Sound level adjustable in 3 steps low medium high Low power consumption Integrated dual isolator Integrated detector base 2 decadic rotary switches for setting the sounder address from 01 to 99 Different base versions available Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 450uA sounder off max 2 1mA low sound level max 3 3mA medium sound level max 7 0mA high sound level Sound level detector mounted typ 70dB A 1m distance low sound level typ 79dB A 1m distance medium sound level typ 87dB A 1m distance high sound level max 95dB A
369. g a jumper The power supply module is prepared for installation in the Power Supply Housing Series NTG Features High efficiency through modern switched mode power supply technology current limited and short circuit protected Long lifespan of stand by batteries through temperature compensated final charge voltage Seven LED indicators for display of causes of fault and operation Integrated mains fuse Specifications Mains voltage 185 to 255VAC 47 to 53Hz Output voltage typ 28VDC Output peak current 8A Connection of external devices typ 3 5A system specific Ambient temperature 5 C to 50 C Relative humidity max 90 no condensation Dimensions L x W x D 290 x 220 x 70 mm Weight approx 1 5kg Approval VdS pending Cross references Page Art Nr Name Type 292 317030 Power Supply Housing NTG24 1 293 317031 Power Supply Housing NTG24 1 CE 289 310005 Stand by Battery 12V 65Ah Power Supply Housing NTG24 1 The Power Supply Housing NTG24 1 accommodates one Power Supply Module Series NTM The housing in a stable powder coated steel sheet design is prepared for wall mounting If a Power Supply Module NTM2402 1 is mounted the housing provides space for the installation of stand by batteries 2 x 12V max 45Ah and of one Relay Module RL58 1 or RL58 2 If a Power Supply Module NTM2408 1 is integrated the housing accommodates stand by batteries 2 x 12V max 22Ah and of one Relay Module RL58 1 or RL58
370. g false alarms Features Constant sensitivity 2 decadic rotary switches for setting the physical address from 01 to 99 Mechanical theft protection Insect screen Functionality check by means of test activation with magnet Specifications Operating voltage Ignition protection supplied through loop voltage intrinsically safe Ex classification EEx ia IIB TS Current consumption 330uA at 24V Ambient temperature 25 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 103 x 43 mm Colour cream Weight 110g Approval BASEEFA03ATEX0157X LPCB 199m Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Detector Base Anal 500 200 SS B501 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 182 228007 Protocol Interface Anal 200 SS IST200 181 228006 Safety Barrier Anal 200 SS Y72221 Safety Barrier Anal 200 SS Y72221 Zener barrier with galvanic separation used for the build up of an intrinsically safe circuit for the connection of analogue fire detectors in hazardous areas to ADM loops using System Sensor 200 protocol The relevant regulations for installations in hazardous areas must be observed Features Connection of up to 15 automatic detectors of type 2251EIS Limitation of the possible short circuit current Limitation of the idle voltage Limitation of the energy stored in the i
371. g temperature Ambient temperature Relative humidity Dimensions x H Colour Weight Approval Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional ad dress module NG60 1 Output for external remote indicator Mechanical theft protection supplied through detector line voltage typ 45uA quiescent 78 C maximum heat component max 65 C 20 C to 90 C no condensation or icing 0 to 95 no condensation 100 x 42 mm white 80g VdS G200060 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 149 246035 Detector Base Conv 60 65 Apo 45681 251 149 246021 Detector Base Conv 60 65 Apo GSA 45681 200 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 Thermal ROR Detector Conv 65 Apo GD 55000 132 Heat detector operating on the rate of rise heat detection principle in addressable conventio nal technology combined maximum rate of rise detector classified as CR maximum room height 6m in extra flat design suitable for indoor mounting Features Dan Specifications Operating voltage Current consumpt
372. ge of possible logic combinations for alarming and transmitting devices as well as for actuations the control panel can realise even extensive and complex alarming and control tasks in the fire alarm technology It complies with all requirements of the European Standards EN 54 2 and EN 54 4 including all options for the highest safety demands If required the Fire Detection Control Panel BC216 1 can be expanded to become an Extinguishing Control Panel LC216 1 This panel can control and monitor up to 8 flooding zones The extensive functi ons and features are summarised in the description of the Extinguishing Control Panel Series LC216 No 2189990 The control panel is installed in a wall mount cabinet made of powder coated sheet steel and prepared for 2 function modules Conventional Detector Interface GIF8 1 or Loop Interface LIF64 1 a Fire Brigade Interface FWI2 1 a Fire Brigade Interface Additional Board FWZ2 1 an LED Display Field LAB48 1 a Serial Interface Module SIM216 1 and additio nal optional componentries as well as a stand by battery with 2 x 12V max 22Ah The labels of the display and operating elements as well as the displayed and printer texts are in English language The parameters of the control panel can be set up and transmitted to the control panel quickly and reliably by means of a PC and the Windows Parameter Setup Software PARSOFT 1 Ad ditionally the parameter setup can be realised also without any furthe
373. ges and fault detectors with or without self resetting property Administration of 3 transmitting devices 9 alarming devices and 16 actuations INFO field with a 2 line by 16 character text display providing information about all cur rent events Info button for additional information on the current events 16 double LEDs left hand side red right hand side yellow automatically assigned to the parameterised zones and displaying the activation as well as the disablement or fault condition of the zones Designation labels allow for individual marking of every double LED The event memory stores the latest 200 events in chronological order Display of activation fault disablement alarm delay call fire brigade and confirmation of the transmitting device to the fire brigade Monitored output for the connection of external signalling devices with display of activati on fault or disablement 3 dry freely parameterisable contact outputs default setup includes two outputs preset for EN 54 requirements summary alarm and summary fault 16 open collector outputs which can be freely parameterised as transmitting devices alar ming devices actuations or other output functions and or combinations for actuations transmitting devices or alarming devices Collective reset of all current alarms via button Panel reset Hierarchized authorisation levels for operation and parameterisation secured via numeric code
374. h 80 characters per line In combination with Fire Detection Control Panels Series BC216 or Series BCO16 the entire event memory and the parameteri sed system configuration can also be printed If used in analogue technology the current measured values of the detectors the measured values of the previous 6 months as well as a maintenance recommendation for every single detector can be printed once or periodically as well The protocol printer is supplied through the AC Adapter PW4007 E1 not included in the delivery Features Thermal printer with 80 characters per line Power LED Paper feed button Space for optional stand by battery Specifications On line OFF line switching with separate LED display Power supply external AC Adapter PW4007 E1 not included in deli very of the protocol printer Ambient temperature 0 C to 40 C Relative humidity 30 to 80 no condensation Dimensions W x H x D 160 x 170 x 66 5 mm Weight 580g Cross references Page Art Nr Name Type 65 227004 AC Adapter for DPU414 PW4007 E 1 66 227005 Battery for DPU414 BT4005 52 214231 Interface Adapter Module IAM216 1E 66 227007 Printer Cable for DPU414 1 8m 9POL D SUB VERL 4 210215 Serial Interface Module SIM06 1 52 214025 Serial Interface Module SIM216 1 67 227006 Spare Paper for DPU414 1Roll MM112 402 N AC Adapter for DPU414 PW4007 E1 Power unit for the supply of the Protocol Printer Thermal DPU414 30B i Specificat
375. h connection of loop line via spring contact Mechanical theft protection Specifications Ambient temperature Protection class IP44 25 C to 70 C Dimensions x D 107 x 61 mm 256 Chapter 26 Accessories for Optical and Acoustic Devices 359042 359049 Additional depth of signalling devices 43mm Colour red Weight 110g Cross references Page Art Nr Name Type 243 355162 Sounder Strobe WM 200 Red Multitone 100dB WMSST RR PO1 244 355163 Sounder Strobe WM 200ISM Red Multitone 100dB WMSST RR P02 242 355160 Sounder WM 200 Red Multitone 100dB WMSOU RR PO1 242 355161 Sounder WM 200ISM Red Multitone 100dB WMSOU RR P02 249 356140 Strobe WM 200 Red WMSTR WR PO1 249 356141 Strobe WM 200ISM Red WMSTR WR P02 Base Sounder amp Strobe IP65 Red WDBR The Base WDBR serves for the indoor and outdoor wall mounting of sounders and strobes Series WMS Due to the design of the base cable entry is possible from the back or the side The base contains an integrated spring contact for through connection of the loop if the si gnalling device has been removed Features Cable entry possible from the back or the side in case of surface mount installation Multi wire terminals with secure screw fitting Through connection of loop line via spring contact Mechanical theft protection Specifications Ambient temperature 25 C to 70 C Protection class IP65 Dimensions x D 107 x 61 mm Additional depth of sign
376. h control line or to special system conditions of the device For operation and programming the integrated keyboard and the two line LC display or the acoustic dialogue menu via the telephone line can be used Hierarchical codes for user and manufacturer avoid unauthorised access The Automatic Telephone Dialling Device TWG805 1A is accommodated in a sabotage pro tected steel sheet housing which also provides space for the optional stand by battery and a telephone socket Features Four control inputs that are activated by a change in resistance One actuation output for remote control commands programmable as pulse output or continuous output Up to eight users can be called on activation of a control input Dial possible also when control inputs are reset to inactive state DTMF or pulse dialling mode Trunk seizure via code for connection in remote systems Digital voice memory for the recording of announcement and communication texts Ten different voice announcement messages with a the total length of 64 seconds can be recorded Recording of announcement messages directly on the device via a telephone receiver All functions freely programmable without the need for an additional programming device Programmable time delay for transmission of fault messages Real time clock with calendar pre programmable shifting date of summer time period Event memory for the last 200 events Outputs for transmission of system conditions Sabotag
377. he FSK700 2 is made of stainless steel V2A and serves for additional protection against moisture in the area of the outer door when raining water 260 Chapter 27 Fire Brigade Key Boxes and Accessories 237700 265900 penetrates this area from the top or from the side The protective cover is placed from the top behind the trim frame of the FSK700 2 Specifications Dimensions W x H x D 300 x 275 x 55 mm silver grey Colour Weight Cross references Page 257 258 500g Art Nr Name Type 265740 Fire Brigade Key Box FSK700 2 D 1 265742 Fire Brigade Key Box FSK700 2S2 D1 Power Supply for FSK Heating NT700 1 The power supply unit NT700 1 provides the voltage supply for the exterior door heating of the Fire Brigade Key Boxes FSK700 2 D1 and FSK700 2S2 D1 and for the Fire Brigade Key Safe FSS800 1 The power supply unit is integrated in a surface mounting box that is al so suitable for DIN rail mounting A circuit breaker is installed for over load and short circuit protection Specifications Operating voltage Output voltage Protection class Ambient temperature Dimensions W x H x D Cross references Page 230V AC 10 15 50Hz 12 24V AC IP30 0 C to 70 C 90 x 160 x 80 mm Art Nr Name Type 257 258 265740 Fire Brigade Key Box FSK700 2 D 1 265742 Fire Brigade Key Box FSK700 2S2 D1 Fire Brigade Keysafe Adapter AD900 1 D1 The Fire Brigade Key Safe Adapter AD900 1 D1 according to VdS 2105
378. he fire detection control panel provided that these functions preventing false alarms An LED indicator visible from all angles displays the activated condition of the detector The detector is accommodated in a white housing and is designed for indoor mounting Se are supported by the control panel Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system Thereby the response sensiti vity of the detector is kept constant for a long time thus constituting an effective measure for veral base versions are available for mounting the detector Features Drift compensation Insect screen Double dust trap OO Specifications Operating voltage Current consumption Output for external remote indicator Mechanical theft protection Individual detector addressing by installing an optional address module NG58 1 Simple function testing using a magnet or test gas supplied through detector line voltage typ 75uA quiescent Ambient temperature 30 C to 70 C Relative humidity max 95 no condensation Dimensions x H 106 x 46 mm Colour white Weight 80g Approval LPCB 603a 01 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 79 246070 Detector Base FC600 FC600 BR 79 246071 Detector Base with Diode FC600 FC600 BRD 80 246072 Detector Relay Base FC600 FC60
379. he functions of a BCnet Sectional Control Panel BC216 2 equipped with 2 Loop Interfaces LIF64 1 with the limitation that apart from the BCnet redundant alarm function no additional control panel functions are supported The extensive functions and features are summarised in the description of the Fire Detection Control Panel BCnet216 No 2199998 Features Per ADM loop a maximum of 128 detector zones in ADM technology for the connection of manual call points automatic detectors conventional detector modules control modu les and signalling devices The BCnet Sectional Control Panel Extension can support a to tal of 144 detector zones ADM loop wiring is realised as ring branch or any given combination of sectional rings and branches using unscreened cables Two isolator modules at the beginning and the end of every ADM loop are integrated on the componentry Connection of 198 physical address points 99 detectors and 99 modules per ADM loop using System Sensor 200 protocol Connection of 126 physical address points detectors or modules per ADM loop using Apollo Discovery protocol Every physical address is assigned an organisational address individual detector identification Free assignment of detector zones or individual detectors for the activation of transmitting devices actuations or alarming devices Maintenance prognosis for every single connected smoke detector Full function of all loop elements in c
380. he key box in the building 169 BB072001 SAM 0720 01 0100 265761 265762 169 BB072001 SAM 0720 01 0100 Chapter 27 Fire Brigade Key Boxes and Accessories 263 front is not possible due to technical or structural reasons or due to special requirements by the fire safety authority Specifications Installation of FSK700 2 possible with flush mounting frame Reinforcement iron cage for anchoring Flexible armoured tube for different types of cables Low net weight Surface made of polished stainless steel Specifications Dimensions W x H x D 400 x 1250 x 300 mm Weight approx 60kg Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D 1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 259 265751 Flush Mounting Frame for FSK700 2 EZ700 2 D1 Steel Column V2A for F0345 HSFSK700 2 D2 The Standard Column V2A is made of 3mm stainless steel and provides a platform for mounting the Fire Brigade Key Box FSK700 2 and the Unblocking Element F0345 if instal lation of the key box in the building facade is not possible due to technical or structural reasons or due to special requirements by the fire safety authority Specifications Installation of FSK700 2 possible with flush mounting frame Column prepared for installation of the Unblocking Element F0345 Reinforcement iron cage for anchoring Flexible armoured tube for different types of cables Low net weight Surfac
381. he loop at short circuit but can be by passed when connected accordingly The aspiration smoke detection system can separately for both channels be parameterised with 3 response thresholds for the conditions ALERT ACTION and FIRE The reaching of the ALERT threshold can be transmitted via the ADM loop to the fire detection control panel and be displayed as technical message The relay ACTION is activated once the ACTION threshold is exceeded Reaching the FIRE threshold activates a fire alarm If the aspiration smoke detection system is connected to an ADM loop the relay FIRE has to be activated by the control panel through parameterisation of the relevant control module In this case the re lays ACTION and FIRE can be used for general control tasks If the aspiration smoke detection system is connected in conventional technology via the relay contacts the relay ACTION can activate a technical message for the indication of a pre war ning The fire alarm is activated via the relay FIRE which in this case is auto activated by the aspiration smoke detection system The continuous air flow in both channels which is generated by a ventilator in the aspiration smoke detection system housing is permanently monitored The system identifies the failure of the ventilator blocking of aspiration holes and pipe burst as fault Disturbance of air flow or fault of power supply is signalled via the loop address of the con trol module of the affect
382. heck test activation with magnet possible Specifications Ignition protection Ex classification intrinsically safe EEx ia IIB T5 typ 100uA quiescent 60 C maximum heat component 10 C to 43 C continuous operation 10 to 93 no condensation 104 x 54 mm Current consumption Alarm temperature Ambient temperature Relative humidity Dimensions x H 169 BB072001 SAM 0720 01 0100 241090 240023 169 BB072001 SAM 0720 01 0100 Colour Weight Approval Cross references Page Chapter 18 Devices for Hazardous Areas 175 105 177 cream 80g BASEEFAO3ATEX0155X VdS G296050 Art Nr Name Type 246008 Detector Base Conv 400 100 300 SS B40IRM 228003 Safety Barrier Conv ES58 2 IS Optical Smoke Detector Conv SLR E IS Smoke detector operating on the light scatter principle in conventional technology for hazar dous areas and of flat design suitable for indoor mounting The detector SLR E IS must al ways be connected via a safety barrier approved for the respective detector Particular attention must be paid to the compliance with country specific regulations a gn Features n Output for external remote indicator 2 Connection to a System Sensor 200 loop via auxiliary mo dules possible Specifications Ignition protection Insect screen intrinsically safe Ex classification EEx ia IIC T5 Current consumption at 24V typ 50u A quiescent Ambient temperature 10 C t
383. heft protection Insect screen Specifications Operating voltage supplied through detector line voltage Current consumption typ 28uA quiescent Ambient temperature 20 C to 60 C Relative humidity 0 to 95 no condensation Radioactive compound Am241 Dimensions x H 100 x 42 mm Colour white Weight 102g Approval VdS G200075 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 149 246035 Detector Base Conv 60 65 Apo 45681 251 149 246021 Detector Base Conv 60 65 Apo GSA 45681 200 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 241026 Optical Smoke Detector Conv 65 Apo GO 55000 317 Smoke detector operating on the light scatter principle in addressable conventional technolo gy with an optical sensing chamber and of extra flat design suitable for indoor mounting Features Sealed electronics prevents false alarms caused by the lt a environment 4 J l N A Individual detector addressing by installing an optional nl address module NG60 1 Output for external remote indicator Mechanical theft protection Insect screen Specifications Operating voltage supplied through
384. her options The Extinguishing Control Panel Family Series LC216 includes the following types of con trol panels The Extinguishing Control Panel LC216 1 for an extinguishing system with one flooding zone according to EN 12094 1 or with up to 8 flooding zones without compliance with EN 12094 1 The networked Extinguishing Control Panel LCnet216 with up to 127 extinguishing sy stems The Control Panel LCnet216 consists of several sectional control panels which are interconnected via the Global Security System Network GSSnet and thereby form a decentralised extinguishing system Each extinguishing system can control up to 32 floo ding zones and each LCnet sectional control panel is able to administrate up to 8 flooding zones A maximum of 127 flooding zones can be controlled by the networked Extinguis hing Control Panel LCnet216 The Extinguishing Control Panel Series LC216 fulfils all compulsory requirements and the options for highest safety demands according to EN 12094 1 EN 54 2 EN 54 4 and is VdS certified The networked Extinguishing Control Panel LCnet216 can be easily implemented with a redundant design of the extinguishing system control which is required if several floo ding zones are to be actuated from one sectional control panel In this case 2 LCnet sectional control panels are identically parameterised at a time and all inputs outputs and ADM loops of the extinguishing system are interconnected The redundant sectional
385. hermal detector operating on the maximum heat detection principle classified BS in ad dressable conventional technology in flat design suitable for indoor mounting in buildings with a maximum room height of 6m 169 BB072001 SAM 0720 01 0100 241045 169 BB072001 SAM 0720 01 0100 AN cans Chapter 11 Conventional Detectors Series 300 ECO1000 85 For quick localisation in the event of an alarm each detector can be assigned an address either by adding an address module NG58 1 to the mounting base or by programming the detector with an optional Remote Program and Test Unit S300RPTU If the detector is addressed using NG58 1 the detector address as well as the assigned text is displayed directly on the fire de tection control panel provided that these functions are suppor ted by the control panel If the detector address has been specified by means of SJOORPTU the detector number is not displayed on the control panel itself but on an additional Zonal Display Unit S300ZDU one of which must be integrated in every detector line Features Individual detector addressing via Address Module NG58 1 or Remote Program and Test Unit S300RPTU Functionality check by means of test activation with Remote Program and Test Unit S300RPTU or Remote Test Unit ECO1000RTU Detector status detector address as well as date of latest maintenance can be read out via Remote Program and Test Unit SJOORPTU Output for external remote
386. his way The serial interface of the module is connected to the Serial In terface Module SIM216 1 of the control panel via the provided cable The telephone connection between the module and the mobile phone network is established with the provided external antenna The module has to be equipped with a SIM card acti vated for data transfer The SIM card is not provided The device key of the module and the mobile phone number of the integrated SIM card have to be entered in PARSOFT the first time a connection is established These parameters are stored in the parameter file The device key is placed on a label on the bottom side of the module Parameterisation and maintenance can be accomplished without limitations with PARSOFT once control panel and PC are connected There is no difference between local or remote ac cess of the control panel Features Remote parameterisation and maintenance via a mobile phone network Specifications Operating voltage plug in adapter Supply voltage FZG2 1 Current consumption at SV Transfer rate GSM interface Ambient temperature Dimensions L x W x H Weight without plug in adapter Cross references Page Status LED indicators for supply voltage and data transfer Includes pre assembled serial data cable for SIM216 1 length approx 1 8m Includes GSM antenna with magnetic base cable length approx 3m Plug in power adapter provided 100 240V AC 50 60Hz SVDC typ
387. ht 0 4kg Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 Steel Column V2A for FSE MP1 Strobe HSFSK700 2 D6 The Steel Column V2A is made of 3mm stainless steel and provides a platform for mounting the Fire Brigade Key Box FSK700 2 an Unblocking Element for half cy linders and a strobe if installation of the key box in the building front is not possible due to technical or structural reasons or due to special require ments by the fire safety authority Specifications Installation of FSK700 2 possible with flush mounting frame Column prepared for installation of a strobe and the Unblocking Ele ment FSE MPI half cylinders Reinforcement iron cage for anchoring Flexible armoured tube for different types of cables Low net weight Surface made of polished stainless steel Specifications Dimensions W x H x D 400 x 1250 x 300 mm Weight approx 60kg Cross references Page Art Nr Name Type 257 265740 Fire Brigade Key Box FSK700 2 D1 258 265742 Fire Brigade Key Box FSK700 2S2 D1 259 265751 Flush Mounting Frame for FSK700 2 EZ700 2 D1 230 356671 Strobe 24V Orange BE A S 2 0 24VBMT 265 265661 Unblocking Element for Half Cylinder FSE MP1 Steel Column V2A Standard HSFSK700 2 D1 The Steel Column V2A Standard is made of 3mm stainless steel and provides a platform for mounting the Fire Brigade Key Box FSK700 2 if installation of t
388. i leie 169 Replacement Glass for Manual Call Point Blue ET SCH HM BL seseiscomiinernesi rr eip Ein Ein Enn 169 Replacement Glass for Manual Call Point Red ET SCH HM RT 20 0 eee e eee eee 169 Replacement Glass for Manual Call Point Yellow ET SCH HMGE e raaire naval 169 Resistor 100pcs 1K 0 33W aarrannnnenanernnnnenr 300 S SMS E Mail Transmitter Module SMS2 1 D1 55 Safety Barrier Anal 200 SS Y72221 005 181 Safety Barrier Anal XP95 Apo AES 29600 098 180 Safety Barrier Conv ES58 2 00 cece eee ee 177 Satellite Unit for Remote Programming Conv 300 SS S300SAT terest pus ard eho onto 113 Sensing Cable Black LWM SK1800011 203 Sensing Cable Blue LWM SK1800010 203 Sensing Cable Stainless Steel LWM SK11800013 204 Sensor Cable Monitoring System Anal XP95 Apo SKM IS AEE cal aan baat tates 206 Sensor Cable Monitoring System Conv SKM 03 205 Sensor Cable Black SKM SK SCHWARZ 207 Sensor Pipe PVC ROHR PVC 00 cece eee eee 221 Sensor Tube PVC 25 SCHL PVC 25 Serial Interface Module SIM016 3 Serial Interface Module SIM06 1 Serial Interface Module SIM216 1 Singlemode Fibre Gateway BCnet216 LWL SM 2 57 Siren Connection Module SZ58 2 0 ce eee 61 Siren Connection Module SZ58 3 orvonvannrnnrenr 61 Smoke Detector Test Tool SOLO330 Smoke Sticks 10pcs RE2 Smoke Switch RS24 ccs sak aod aed ood sey ka
389. ia the ADM loop and activated by the re mote indicator output of the detector Sa Features ES Alternating tone 630 990Hz amp Signal sequence 0 5Hz en Low power consumption Specifications Operating voltage 17 to 28VDC Current consumption from loop typ 10uA sounder off max 3mA sounder on Sound level 85dB A 1m distance Ambient temperature 20 C to 60 C Protection class IP23 Dimensions x H 115 x 38 mm Colour white Weight 140g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 253 359022 Mounting Plate for Sounder WB XP95 38531 810 Sounder Strobe WB XP95ISM White Clear Alert 45681 330 The addressable sounder with integrated strobe 4568 1 330 is installed in a round white pla stic housing The unit is actuated using Apollo Discovery protocol and powered via the ADM loop The sounder is always activated together with the strobe The integrated detector base is suitable for accommodation of fire detectors Series XP95 and Discovery The unit is prepared for indoor surface mounting A dual isolator is integrated in the componentry At short circuit it maintains the function of ADM elements that are not affected ae P Sr mecest by the short circuit Depending on the parameter setup of the Fire Detecti
390. ial data transfer e g a remote serial protocol printer a PC EN Specifications Current consumption at 24V typ 10mA Interface RS232C galvanically isolated up to 57 6kBaud Signal lines RxD TxD CTS DTR Connection type D SUB plug 9 pole Ambient temperature 5 C to 50 C Dimensions L x W x H 70 x 45 x 20 mm Weight 50g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT1 7 210122 Fire and Evacuation Panel BC016 2 INT1 6 210102 Fire Detection Control Panel BC016 1 INT1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT1 16 214308 Fire Detection Control Panel BC216 1S INT1 Interface Adapter Module IAM216 1E The Interface Adapter Module IAM216 1E allows for the extension of a Fire Detection Con trol Panel Module BCM216 3EPS or BCM216 3E with a galvanically isolated RS232 inter face for the connection of devices with serial data transfer e g a remote serial protocol printer a PC The functional unit consists of a Serial Interface Module SIM216 1 and an adapter board with flat cable for reloca ting the D SUB plug of the SIM216 1 to the connection surface of the fire detection control panel modules Specifications Current consumption at 24V typ 10mA Interface RS232C galvanically isolated up
391. ient temperature 5 C to 50 C Dimensions W x H x D 162 x 209 x 34 mm Colour grey white RAL 9002 Weight 1 4kg Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 24 214004 BCnet Sectional Control Panel OP BC216 2 A1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 7 210122 Fire and Evacuation Panel BC016 2 INT1 6 210102 Fire Detection Control Panel BC016 1 INT1 14 214000 Fire Detection Control Panel BC216 1 A1 29 214100 Fire Detection Control Panel BC216 1CE A1 16 214308 Fire Detection Control Panel BC216 1S INT1 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E Remote Tableau SG58 2 NL1 Functions and specifications correspond to the Remote Tableau SG58 2 A1 The labels and the displayed texts are in Dutch language Remote Tableau SG58 2 B1 Functions and specifications correspond to the Remote Tableau SG58 2 A1 The labels and the displayed texts are in French language 169 BB072001 SAM 0720 01 0100 250018 250013 251001 169 BB072001 SAM 0720 01 0100 Chapter 8 Display and Operating Devices 71 Remote Tableau SG58 2 CZ1 Functions and specifications correspond to the Remote Tableau SG58 2 A1 The labels and the displayed texts are in Czech language Remote Display Panel SG48 2 Remote indication unit for the optical and acoustic
392. indicator for alarm Yellow LED indicator for fault and disablement Button display level Button buzzer off Button scroll forwards Button scroll backwards 4 line by 20 character backlit display Metal case with glass door Lock for half cylinders o ooo oo Specifications Operating voltage 10 30VDC Current consumption at 24V 30mA quiescent 90mA alarm Baudrate 1200Baud can be changed with FatProgWin Ambient temperature 0 C to 50 C Dimensions W x H x D 225 x 180 x 58 mm Colour grey white RAL 9002 Weight 3 5kg Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 9 210112 Serial Interface Module SIM016 3 s am kand 270 Chapter 28 Fire Brigade Control and Display Devices 250900 250901 Fire Brigade Display Panel FAT900 2 D1 The Fire Brigade Display Panel FAT900 2 D1 in redundant design is according to DIN 14662 an ancillary device for fire detection systems and provides acoustic and optic display of events from detectors detector zones and system conditions of the Fire Detection Control Panels
393. influences and of flat design suitable for indoor mounting a Intelligent evaluation algorithms in the respective LST fire de oN tection control panels compensate for the impact of contamina x gt tion of the sensing system Thereby the response sensitivity of az the detector is kept constant for a long time thus constituting e an effective measure for preventing false alarms Features Constant sensitivity 2 decadic rotary switches for setting the physical address from 01 to 99 Output for external remote indicator Mechanical theft protection Insect screen Specifications Functionality check by means of test activation with magnet Operating voltage supplied through loop voltage Current consumption max 200A quiescent Ambient temperature 10 C to 60 C Relative humidity 10 to 93 no condensation Radioactive compound Am241 0 5uCi 18 5kBq Dimensions x H 102 x 43 mm Colour cream Weight 102g Approval VdS G295010 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 110 246013 Isolator Detector Base Anal 500 200 SS B524IEFT 1 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PA58 1
394. ing A pulsed infrared beam emitted from the transmitter receiver unit is reflected by a reflector mirror For easy functional testing the detector can be remotely activa ted during maintenance by the fire detection control panel This test simulates a light obscuration by means of an integrated test filter ww a er Alarm evaluation is achieved by detection of a reduced intensity of the light beam Intelligent evaluation algorithms in the detec tor compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept constant for a long time thus constituting an effective measure for preventing false alarms The response sensitivity of the detector can be set to 6 different levels Four levels show a fi xed alarm threshold 2 other levels provide an adaption of the detector to changing ambient conditions by means of a variable alarm threshold The detector is delivered with a reflector which can be used for ranges from 5 to 70m A three part accessory is available to extend the range of the detector from 70 to 100m Features Detection of clear and dark smoke Sender and receiver integrated in a single housing Sealed detector housing Receiver LED display for alarm and fault as well as display for preset values and commis sioning support Adjustment screws for an easy alignment of the detector Test filter for optimal commissioning included in deli
395. ing of sensing cable ends Cross references Page Art Nr Name Type 203 244622 Sensing Cable Black LWM SK180001 1 203 244628 Sensing Cable Blue LWM SK1800010 204 244624 Sensing Cable Stainless Steel LWM SK11800013 169 BB072001 SAM 0720 01 0100 244629 244630 244631 169 BB072001 SAM 0720 01 0100 Chapter 20 Special Detectors 205 Mounting Base TC358 Mounting base for mounting of temperature resistant sensing cables to concrete ceilings For installation the mounting base is fixed in a hole with a 6mm diameter that has to be drilled into the ceiling and is mounted in a distance of 1cm to the ceiling The sensing cable is mounted to the base via a cable tie Cross references Page Art Nr Name Type 203 244622 Sensing Cable Black LWM SK1800011 203 244628 Sensing Cable Blue LWM SK1800010 204 244624 Sensing Cable Stainless Steel LWM SK11800013 207 244634 Sensor Cable Black SKM SK SCHWARZ 206 244633 Standard Sensor Cable Red SKM SK ROT Mounting Clip 3040 LSK Insulating grip saddle for mounting of temperature resistant sensing cables to concrete cei lings Please note that the mounting clip has a limited resistance against acids and solvents Therefore it is not recommended for use in environments where sensing cables either with black nylon coating or stainless steel meshwork are usually applied Cross references Page Art Nr Name Type 203 244628 Sensing Cable Blue LWM SK1800010 207 244634 Senso
396. integration of contact detectors e g ma nual call points sprinkler system contacts supervising contact into the bi directional com munication on the ADM loop using System Sensor 200 protocol Specifications Operating voltage Features Output for an optional LED indicator 2 decadic rotary switches for setting the address from 01 to 99 supplied through loop voltage Current consumption 300uA quiescent Line termination 56kOhm Alarm threshold typ 22kOhm Ambient temperature 10 C to 60 C Dimensions L x W x H 48 x 40 x 13 mm Colour cream Weight 33g Approval VdS G296025 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG JEF av E 96 Chapter 12 Analogue Detectors and Modules Series 200 500 249100 249101 35 214021 Loop Interface LIF64 1 Monitor Module 1xSurv In Anal 200 SS M210E Addressable module for the line monitored integration of a contact detector e g manual call point sprinkler system contact supervising contact into the bi directional communication on the ADM loop using System Sensor 200 protocol The integrated dual isolator can be activa ted or deactivated by choosing the appropriate terminals Features W name Status LED a 7 Surveillance of terminal connecting line for wire brea kage and short circuit 2 decadic rotary switches for setting the address from 01 to
397. ints with blue marking Specifications Dimensions W x H xD 80 x 80 x 0 7 mm Cross references Page Art Nr Name Type 164 245395 Manual Call Point Blue Anal Apo HM 5 32 02 02 165 245429 Manual Call Point Blue Anal Apo HM 5 32 18 02 161 245372 Manual Call Point Blue Anal SS HM 5 22 02 02 161 245415 Manual Call Point Blue Anal SS HM 5 22 18 02 158 245352 Manual Call Point Blue Conv HM 5 11 02 02 159 245417 Manual Call Point Blue Conv HM 5 11 18 02 Replacement Glass for Manual Call Point Yellow ET SCH HM GE Standardised replacement glass for manual call points with yellow marking Specifications Dimensions W x H x D 80 x 80 x 0 7 mm Cross references Page Art Nr Name Type 166 245396 Manual Call Point Yellow Anal Apo HM 1 32 05 02 162 245392 Manual Call Point Yellow Anal SS HM 1 22 05 02 z am Fr 170 Chapter 17 Manual Call Points 159 245355 Manual Call Point Yellow Conv HM 1 11 05 02 249024 Special Designation for Manual Call Point HM BESCH Allows you to modify the labelling of a manual call point The desired wording has to be spe cified upon order Cross references Page Art Nr Name Type 164 245395 Manual Call Point Blue Anal Apo HM 5 32 02 02 165 245429 Manual Call Point Blue Anal Apo HM 5 32 18 02 161 245372 Manual Call Point Blue Anal SS HM 5 22 02 02 161 245415 Manual Call Point Blue Anal SS HM 5 22 18 02 158 245352 Manual Call Point Blue Conv HM 5 1 1 02 02 159 245417 Manual C
398. ion Alarm temperature Operating temperature Ambient temperature Relative humidity Dimensions x H Colour Weight Approval Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional ad dress module NG60 1 Output for external remote indicator Mechanical theft protection supplied through detector line voltage typ 45uA quiescent 90 C maximum heat component max 80 C 20 C to 90 C no condensation or icing 0 to 95 no condensation 100 x 42 mm white 80g VdS G200061 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 149 246035 Detector Base Conv 60 65 Apo 45681 251 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 8 210110 Detector Zone Extension MGE8 1 169 BB072001 SAM 0720 01 0100 242027 241060 169 BB072001 SAM 0720 01 0100 Chapter 14 Conventional Detectors Series 65 ORBIS 129 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 Thermal Max Detector Conv 65 Apo GM 55000 137 Heat detector operating on the heat detection principle in addressable conventional technolo gy maximum heat detector classified
399. ion Control Panels Series BC216 can be established via a Fire Brigade Interface FWI2 1 whereas a Fire Detection Control Panels Series BCO16 can be connected via a Fire Brigade Interface FWI016 1 Para meters for in and outputs are set at the control panel 268 Chapter 28 Fire Brigade Control and Display Devices 250741 Features Green LED indicator for Operation Red LED indicator for Panel summary alarm Red LED indicator for Extinguishing systems activated Yellow LED indicator for Acoustic signals off Yellow LED indicator for Transmitting device disabled Yellow LED indicator for Transmitting device activated Switch Acoustic signals off Metal case with glass door o oo ooo ooo o Specifications Operating voltage Current consumption at 12V DC Current consumption at 24V DC Environmental class Protection class Dimensions W x H x D Yellow LED indicator for Fire controls off Button Panel reset with safety cover Switch Transmitting device off Button Testing transmitting device Prepared for a half cylinder locking mechanism 10 30VDC lt 20mA quiescent lt 50mA alarm lt 20mA quiescent lt 50mA alarm II IP30 225 x 180 x 57 mm grey white RAL 9002 Colour Weight Approval Cross references Page 9 36 2kg VdS G200079 Art Nr Name Type 210111 Fire Brigade Interface FW1016 1 214022 Fire Brigade Interface FWI2 1 Fire Brigade Control Unit FBF900 2
400. ion module is therefore ideal for the design of synoptic remote tableaus Each of the 48 outputs can be used for actuation of one light emitting diode or of one relay output of a Relay Module RL58 1 or RL58 2 The signals are available at a pin strip header which is prepared for the connection of pre assembled LED cables The first 16 outputs are available in addition at two ten pin connectors each for the connection of one Relay Module RL58 1 or one RL58 2 via a flat cable If more than 16 relay outputs are required further actuation inputs of additional relay modules can be connected to the LED connection module via suitable connection cables This componentry is prepared for mounting in the LST standard grid and comes with the re quired mounting material Specifications Operating voltage 20 31 VDC Current consumption at 24V typ 3mA quiescent max 80mA lamp test 48 LEDs connected Ambient temperature 5 C to 50 C Dimensions L x W x H 135 x 75 x 15 mm Weight 62g Cross references Page Art Nr Name Type 75 259013 Cord 2 Wire for LED Connection 10pcs LED LEITUNG 10 74 259011 LED Assembled Green 10pcs LED GN 10 75 259010 LED Assembled Red 10pcs LED RT 10 75 259012 LED Assembled Yellow 10pcs LED GE 10 73 252012 Remote Tableau Drive Unit PTU288 1 LED Assembled Green 10pcs LED GN 10 The packing unit contains 10 light emitting diodes with an assembled connection cable for simple and quick wiring and mounting o
401. ion smoke detection systems Pipe Fitting ADA MUFFE Pipe adapter made of grey PVC nominal width 20mm for the connection of sensor pipes of aspiration smoke detection systems 222 Chapter 22 Accessories for Aspiration Smoke Detection Systems 244119 244125 244235 244240 244201 244241 244237 244236 Pipe Fitting CAP KAPPE Pipe end cap made of grey PVC nominal width 20mm for sensor pipes of aspiration smoke detection systems Pipe Connector 25 RKL25 Pipe junction made of grey PVC including screw nut for fixation of rigid sensor pipes of as piration smoke detection systems Check Valve Spring loaded R25 RVFED 25 The check valve is a safety device to protect the sensor pipe network and reduction foils du ring cleaning The pressure is kept constant in the entire pipe network during the blow out process by the check valve thereby ensuring that all aspiration holes are cleaned equally The check valve is installed at the end of the sensor pipe network Ceiling Duct complete DDF KOMPL The ceiling duct enables a barely noticeable integration of aspiration holes in areas with inser ted ceilings and in special applications when air has to be sampled from closed rooms e g 19 cabinets The ceiling duct consists of an aspiration element including knurled nut for easy installation and a duct reducer The Tube Fitting T90 and the required reduction foil ha ve to be ordered separately A 2 meter long fl
402. ions Mains voltage 230V AC 50Hz 66 Chapter 7 Protocol Printers 227005 227007 227008 Output voltage 6 5VDC Output current 2 0A Dimensions W x H xD 114 x 75 x 61 mm Cable length 1 8m Weight approx Ikg Cross references Page Art Nr Name Type 65 227003 Protocol Printer Thermal DPU414 30B Battery for DPU414 BT4005 Stand by battery suitable for installation in the Protocol Printer Thermal DPU414 30B Specifications Type Ni MH Voltage 4 8VDC Output voltage 2 0A Weight approx 120g Cross references Page Art Nr Name Type 65 227003 Protocol Printer Thermal DPU414 30B Printer Cable for DPU414 1 8m 9POL D SUB VERL Cable for the connection of the Protocol Printer Thermal DPU414 30B to the serial interface module of a Fire Detection Control Panel of Series BC216 Series BC016 or BC06 Specifications Cable length 1 8m Cross references Page Art Nr Name Type 52 214231 Interface Adapter Module IAM216 1E 65 227003 Protocol Printer Thermal DPU414 30B 4 210215 Serial Interface Module SIM06 1 52 214025 Serial Interface Module SIM216 1 Protocol Printer Dot Matrix LX300 Desktop printer used as protocol equipment to be connected to a Serial Interface Module of a Fire Detection Control Panel Series BC216 or Series BCO16 or to a Serial Interface Module SIM06 1 of a Fire Detection Control Panel Series BC06 Depending on the control panel the logging includes the location of the activa ted
403. ions Operating voltage Current consumption Ambient temperature supplied through detector line voltage typ 75uA quiescent 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 x 32 5 mm Colour cream Weight 75g Approval VdS G202012 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 105 246008 Detector Base Conv 400 100 300 SS B40IRM 105 246100 Detector Relay Base Conv 300 SS B324RL 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PAS8 1 112 246111 Remote Program and Test Unit Conv 300 SS S300RPTU z am 169 BB072001 SAM im 0720 01 0100 82 241041 Chapter 11 Conventional Detectors Series 300 ECO1000 113 113 112 246150 246112 246113 210210 Remote Test Unit Conv 300 1000 SS ECO 1000RTU Satellite Unit for Remote Programming Conv 300 SS S300SAT Zonal Display Unit Conv 300 SS S300ZDU Zone Extension Board ZEB2 1 Optical Thermal Detector Conv 300 SS 2351TEM Multisensor detector with a detection element operating on the light scatter principle and a detection element operating on the heat principle classified AIR in addressable conventio nal technology and of flat design s
404. ire Detection Control Panel Series BC016 or BC216 as well as an Extinguis hing Control Panel Series LC216 Features 24 double LEDs left hand side red right hand side yellow freely parameterisable accor ding to individual events 24 double LEDs left hand side green right hand side yellow freely parameterisable ac cording to individual events Display of activation as well as deactivation or fault condition of the parameterised event Designation labels allow for individual marking of every double LED Specifications Current consumption at 24V typ 2mA no active LED 0 25mA per LED Ambient temperature 5 C to 50 C Dimensions L x W x H 176 x 120 x 15 mm Weight 60g Cross references Page Art Nr Name Type 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 33 214208 Display and Operating Front Panel ABP216 1E INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 72 252010 LED Display Tableau LAT288 1 72 252011 LED Display Tableau LAT288 1CE 73 252012 Remote Tableau Drive Unit PTU288 1 Network Redundant Alarm Converter NNU5 1 The Network Redundant Alarm Converter NNU5 1 analyses the data on the BCnet redun dant alarm line which runs in addition to the GSSnet line and transmits an alarm message to the designated transmitting and alarming device even at multiple line failure in the GSSnet or at s
405. iren Button for testing the lamps HK o Specifications Supply voltage Current consumption at 24V DC Ambient temperature Dimensions W x H x D Colour Weight Cross references Page Button for silencing the FDCP Button for resetting the FDCP Elegant metal case with glass door Yellow LED for fault disablement 2 LEDs for FDCPs with extinguishing system 20 to 31VDC 40mA quiescent 55mA active 5 C to 50 C 200 x 300 x 50 mm flame red RAL 3000 1 4kg Art Nr Name Type 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 2149997 BCnet Sectional Control Panel OP BC216 2EPS 214008 Fire Detection Control Panel BC216 1 INT1 214108 Fire Detection Control Panel BC216 1CE INT 1 214308 Fire Detection Control Panel BC216 1S INT 1 210112 Serial Interface Module SIM016 3 Fire Brigade Control Unit FBF900 1 D1 Fire Brigade Control Unit FBF900 1 D 1 for standard connection to fire detection systems ac cording to DIN 14661 The control unit provides an optical display for the most important operating conditions of the fire detection control panel to facilitate and standardise the opera tion of a fire detection system for the fire brigade The Fire Brigade Control Unit FBF900 1 D 1 can be connected to control panels of different manufacturers due to the indivi dual actuation of indicators with an inverted or non inver ted signal and an operating voltage of 10 30V A direct connection to Fire Detect
406. is sampled from the monitored area by the aspiration smoke detection system housing TP x 216 Chapter 21 Aspiration Smoke Detection Systems The light obscuration and the air flow are measured by the detector module The response thresholds for the light obscuration and the air flow can be selected in 4 steps Dry contacts in the evaluation electronics of the aspiration smoke detection system housing signal the excee ding of alarm and fault thresholds Specifications Response threshold Light obscuration 2 1 0 5 0 25 m Air flow monitoring 4 levels Cross references Page Art Nr Name Type 213 244180 Aspiration Smoke Detection System Housing TP 1 214 244181 Aspiration Smoke Detection System Housing TP 2 244183 Detector Module DM TP 05 L The Detector Module DM TP 05 L is used for analysis and evaluation of air with particularly high sensitivity which is sampled from the monitored area by the aspiration smoke detection system housing TP x The light obscuration and the air flow are measured by the detector module The response thresholds for the light obscuration and the air flow can be selected in 4 steps Dry contacts in the evaluation electronics of the aspiration smoke detection system housing signal the exceeding of alarm and fault thresholds Specifications Response threshold Light obscuration 0 4 0 2 0 1 0 05 m Air flow monitoring 4 levels Cross references Page Art Nr Name Type 213 244180 Aspiration Smok
407. ith diverse redundant processing logic Administration of up to 144 detector zones for manual call points automatic fire detectors with of without alarm verification technical messages and fault detectors with or without self resetting property 3 Administration of 10 transmitting devices 99 alarming devices 128 actuations and 199 sectors Easy control panel operation thanks to freely parameterisable sectors INFO field with a 4 line by 20 character backlit text display providing information about all current events 1 2 3 Info button for additional information on the current events 1 2 3 Event memory with quick search filter displays the latest 500 events in chronological order Display of activation fault disablement delay operation call fire brigade and confirmati on for the transmitting device to the fire brigade 1 2 3 Monitored output for the connection of external signalling devices with display of activati on fault or disablement 3 Dry contact outputs for summary alarm and summary fault 16 open collector outputs which can be freely parameterised as transmitting devices alar ming devices actuations or other output functions 3 and or combinations for the activation of actuations transmitting devices or alarming devices depending on messages from detector zones or single detectors respectively Collective reset of all current alarms via button Panel reset 1 2 3 22 Chapter 3 Fire D
408. itter receiver unit integrated into a plastic housing for application on the ADM loop using System Sensor 200 protocol de pe panene signed for indoor mounting A pulsed infrared beam emitted from the transmitter receiver unit is reflected by a reflector mirror Alarm evaluation is achieved by detection of a reduced intensity of the light beam The Beam Smoke Detector 6500 can be con nected directly to the ADM loop with System Sensor 200 protocol without external power supply Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system There by the response sensitivity of the detector is kept constant for a long time thus constituting an effective measure for preventing false alarms The response sensitivity of the detector can be set to 6 different levels Four levels show a fi xed alarm threshold 2 other levels provide an adaption of the detector to changing ambient conditions by means of a variable alarm threshold The detector is delivered with a reflector which can be used for ranges from 5 to 70m A three part accessory is available to extend the range of the detector from 70 to 100m Features Detection of clear and dark smoke Sender and receiver integrated in a single housing Sealed detector housing Direct connection to the ADM loop with System Sensor 200 protocol without external po wer supply Integrated dual isolator activati
409. ividually configured as detector zone for manual call points automatic fire detectors with of without alarm ve rification technical messages and fault detectors with or without self resetting property Individual detector identification for up to 64 addresses per detector line in conjunction with optional address modules Detector lines monitored for wire breakage short circuit and earth fault Freely parameterisable allocation of the detector lines for activating transmitting devices actuations and alarming devices J Specifications Current consumption at 24V typ 32mA 8 zones terminated without detectors Line voltage typ 20 0V Line current typ 3 8mA End of line resistance 5 6kOhm Line resistance max 50 Ohm per core Ambient temperature 5 C to 50 C Dimensions L x W x H 100 x 65 x 15 mm 169 BB072001 SAM Chapter 2 Fire Detection Control Panels Series BCO016 9 Weight 80g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 7 210122 Fire and Evacuation Panel BC016 2 INT1 6 210102 Fire Detection Control Panel BCO16 1 INT1 210111 Fire Brigade Interface FWI016 1 The Fire Brigade Interface FWI016 1 allows for the connection of two independent transmit ting devices for direct interconnection to a designated alarm respondent e g the fire brigade as well as the connection of a country specific fire brigade control unit to Fire Detec
410. k localisation in the event of an alarm each detector can be assigned an address by adding an Address Module NG58 1 to the mounting base The address of the detector in ER alarm condition as well as the assigned text is displayed directly on the fire detection control panel provided that these functi ons are supported by the control panel Features Individual detector addressing by installing an optional address module NG58 1 Output for external remote indicator Functionality check by means of test activation with Remote Test Unit ECO1000RTU Specifications Operating voltage Current consumption Alarm temperature Operating temperature Ambient temperature supplied through detector line voltage typ 75uA quiescent typ 78 C max 60 C 30 C to 70 C continuous operation Relative humidity 5 to 95 no condensation Dimensions x H 102 x 40 5 mm Colour white Weight 70g Approval VdS G204042 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 107 246140 Detector Base Conv 1000 SS ECO1000BR1000 107 246141 Detector Relay Base Conv 1000 SS ECO1000BREL24L 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PAS8 1 113 246150
411. l max 95dB A 1m distance high sound level typ 6 4mA at 90dB A 1m distance typ 7 6mA at 89dB A 1m distance typ 7 7mA at 86dB A 1m distance 1Hz 25 C to 70 C 10 96 no condensation 112 x 42 mm without detector incl Base LPB W red cream RAL 9001 136g VdS G206072 248 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 254 359043 Base Sounder amp Strobe IP44 White SDBW 255 359044 Base Sounder amp Strobe IP65 White WDBW 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Sounder Strobe WB 200ISM White Red Multitone IBSST DR P02 The addressable sounder with strobe red cap is accommodated in a round white plastic hou sing and is prepared for indoor surface mounting The integrated base is suitable for accom modation of fire detectors Series 200 The unit is mounted on a base for signalling devices not provided The componentry is actuated using System Sensor 200 protocol and is powered via the ADM loop The soun N der is always activated together with the strobe 355167 A dual isolator is integrated in the componentry At short circuit it maintains the function of ADM elements that are not affected by the short circuit Depending on the parameter setup of the Fire Detection
412. l Call Point Grey Anal SS HM 7 22 03 02 0 cece ccc c eee e eee eet en eee en nen e ee 163 245402 Manual Call Point EN 54 Red Anal Apo HFM 3 32 02 2 0 0 cece eee cence tee teen eet ten eee e ee 164 245395 Manual Call Point Blue Anal Apo HM 5 32 02 02 1 0 0 cece cece ccc nent ee teen eee nen nee e es 164 245429 Manual Call Point Blue Anal Apo HM 5 32 18 02 1 0 0 cece cece cece eee eee t eee e nen e eee es 165 245396 Manual Call Point Yellow Anal Apo HM 1 32 05 02 oo eee eee cece eee nen eee e eens 166 249096 MCP Coding Module MCM1 1 cece cece eect tenet cen eee e etn tne e eee nn eee es 166 249633 Protective Cover V2A for Manual Call Point Red WG ROT E 1 0 cece cence eee eee e eee 167 249634 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 00 cece e cece eee eee 167 249636 Protective Cover V2A for Manual Call Point Yellow WG GELB E 1 2 cee eee eee eee 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 0 c cece e eee e ene e eee eens 168 219006 Key for Manual Call Point SCH HFM HM 0 c cece c cece ect eee e ete t nee e ee nnn neces 169 2171612 Replacement Glass for Manual Call Point ET SCH HFM 0 cece ee eee ee ee eee eee eens 169 2171620 Replacement Glass for Manual Call Point Red ET SCH HM RT 0 cece eee ce eee eee 169 2171621 Replacement Glass for Manual Call Point Blue ET SCH HM BL
413. l Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 Sounder WM XP95 Red Slow Whoop 100dB 55000 276 The addressable loop sounder 55000 276 is integrated in a red plastic housing and is de Specifications Operating voltage Current consumption from loop Sound level Ambient temperature signed for indoor wall mounting The sounder base is included The sounder is activated and supplied via the ADM loop using Apollo Discovery protocol Features Tone A Slow Whoop tone NEN 2575 500 1200Hz over 3 5s 1s pause Tone B continuous tone 870Hz Low power consumption Adjustable sound level Supply by loop voltage max 1 2mA sounder off max 5mA sounder on 100dB A 1m distance 20 C to 60 C 236 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 355130 355134 Protection class IP21 Dimensions x D 106 x 95 mm Colour red Weight 215g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Sounder WB XP95RI White Alert 45681 276 The base sounder 45681 276 is integrated in a round white plastic housing and is designed for indoor mounting The integrated detector base accommodates automatic fire detectors Se ries XP95 or Discovery The sounder is supplied v
414. l Points 245402 245395 Manual Call Point EN 54 Red Anal Apo HFM 3 32 02 Manual call point according to EN 54 11 B in an elegant red aluminium die cast housing de signed for application on the ADM loop using Apollo Discovery protocol with integrated dual isolator module The manual call point is tested in accordance with the standards EN 54 11 B and EN 54 17 Features Robust aluminium die cast housing with a door aperture angle of more than 180 Operating instructions by means of symbols European standard Integrated dual isolator Reverse polarity protection Built in microcontroller Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Button in combination with LED for setting the physical address Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 Specifications Operating voltage supplied through the loop voltage Current consumption 180uA quiescent Ambient temperature 20 C to 60 C continuous operation 25 C to 70 C max 12 hours Protection class IP43 Dimensions W x H x D 125 x 125 x 34 mm Colour flame red RAL 3000 Weight 400g Approval VdS G204003 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169
415. l mount cabinet made of powder coated sheet steel and prepared for 2 function modules Conventional Detector Interface GIF8 1 or Loop In terface LIF64 1 a Fire Brigade Interface FWI2 1 a Fire Bri gade Interface Additional Board FWZ2 1 a Serial Interface Module SIM216 1 and additional optional componentries as well as a stand by battery with 2 x 12V max 22Ah The extensive functions and features are summarised in the description of the Fire Detection Control Panel BCnet216 No 2199998 Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 28VDC Output peak current max 1 8A Connection of external devices typ 0 8A site specific Current consumption at 24V typ 90mA without optional componentries Ambient temperature 5 C to 50 C Dimensions W x H x D 420 x 520 x 120 mm Colour grey white RAL 9002 Weight without batteries approx 6kg Approvals FT 14 147 3 99 Austria VdS G201017 Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 50 223009 Control Zone Module SLM 1 2 35 214020 Conventional Detector Interface GIF8 1 58 218023 ESPA 4 4 4 Interface License ESPA SS 47 218024 Extinguishing Control 8 Area License LC216 8LB 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2 1 35 214021 Loop Interface
416. lA 1mA quiescent 20mA active 1A 60V 30W 5 C to 50 C 70 x 45 x 17 mm 169 BB072001 SAM 0720 01 0100 241603 169 BB072001 SAM 0720 01 0100 Weight Cross references Chapter 20 Special Detectors 209 approx 40g Page Art Nr Name Type 213 244180 Aspiration Smoke Detection System Housing TP 1 214 244181 Aspiration Smoke Detection System Housing TP 2 217 244300 Aspiration Smoke Detection System Housing TT 1 219 244155 Aspiration Smoke Detection System T SS 220 244170 Aspiration Smoke Detection System VLS 304 196 244022 Beam Smoke Detector Conv SS 6500R 201 244610 Beam Smoke Detector Conv FR2000 197 244023 Beam Smoke Detector Test Conv SS 6500RS 202 244637 Linear Heat Detection Unit Alarmline Conv LWM 1 184 249201 RF Interface 4Rel FUIF511 27D 188 249203 RF Interface 4Rel M400RFE AS 205 244631 Sensor Cable Monitoring System Conv SKM 03 Optical Battery Smoke Detector FL10022H Photo optical 9V smoke detector with included mounting base in flat design suitable for application in houses apartments bedrooms nurseries and halls Specifications Operating voltage Recommended batteries Sound level Ambient temperature Relative humidity Dimensions x H Colour Weight Approval Features Integrated sounder Test button for testing the battery Battery removal protection Possible network with up to 30 additional detectors Easy installation Compact appealing design oO
417. lat design suitable for indoor mounting G For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire detection con trol panel provided that these functions are supported by the control panel Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept con stant for a long time thus constituting an effective measure for preventing false alarms If the contamination of the sensing system is too heavy or if it is defective the multicolour status 130 Chapter 14 Conventional Detectors Series 65 ORBIS 241061 LED on the detector will flash for approx 4 minutes in yellow colour after the detector line has been enabled Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional address module NG60 1 Output for external remote indicator Mechanical theft protection Insect screen Specifications Operating voltage supplied through detector line voltage Current consumption typ 65uA quiescent Ambient temperature 40 C to 70 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 50 mm C
418. le length between two NIF5 1 max 1200m Connection type Screw terminals Ambient temperature 5 C to 50 C Dimensions L x W x H 95 x 70 x 25 mm Weight 50g Cross references Page Art Nr Name Type 27 214108 Fire Detection Control Panel BC216 1CE INT 1 20 2199998 Fire Detection Control Panel BCnet216 Description Network Cable NWK2 1 Network cable 4x2xAWG24 1 S FTP category 5 twisted pair for the connection of GSSnet members e g of BCnet sectional control panels which form a decentral Fire De tection Control Panel BCnet216 in the Global Security System network GSSnet Specifications Loop resistance max 16 8Q 100m at 20 C Operating capacitance 4 9nF 100m at 1kHz Capacitance interference max 59pF at 1MHz to 200MHz Impedance 100 15Q at 1kHz Attenuation SOMHz max 14dB 100m Outer coat FR PVC FR I S H Outer diameter 6 5mm Min bend radius 52mm Max tensile strength 25kg Core diameter 0 51mm Shield Al polyester foil Cu braid shield Weight 51kg km Temperature range 20 C to 75 C Colour grey RAL 7032 52 Chapter 5 Interfaces 214025 214231 Cross references Page Art Nr Name Type 20 2199998 Fire Detection Control Panel BCnet216 Description Serial Interface Module SIM216 1 The Serial Interface Module SIM216 1 allows for the extension of a Fire Detection Control Panel Series BC216 or Series BC016 with a galvanically isolated RS232 interface for the connection of devices with ser
419. le terminals with secure screw fitting Terminal for external remote indicator Mechanical theft protection Specifications Ambient temperature Relative humidity Dimensions x H Colour Weight 20 C to 60 C no condensation or icing 10 to 95 no condensation 100 x 15 mm white 50g Cross references Page Art Nr Name Type 153 246030 Backplate Apo SZPL 45681 233 141 243100 CO Detector Anal Disc Apo AC 58000 300 153 246029 Conduit Box Apo SZA 4568 1 204 120 249044 Detector Mounting Bracket MMW 1 1 138 240026 Ionisation Smoke Detector Anal Disc Apo AI 58000 500 136 240024 Ionisation Smoke Detector Anal XP95 Apo AI 55000 520 141 241022 Optical Thermal Detector Anal Disc Apo AMS 58000 700 138 241030 Optical Thermal Detector Anal XP95 Apo AMS 55000 885 139 241027 Optical Smoke Detector Anal Disc Apo AO 58000 600 136 241023 Optical Smoke Detector Anal XP95 Apo AO 55000 620 121 249640 Protective Cage BWS 1 D1 71 251001 Remote Indicator PA58 1 140 242028 Thermal Detector Anal Disc Apo AD 58000 400 137 242023 Thermal Detector Anal XP95 Apo AW 55000 420 121 249635 Trapezoid Steel Bracket TBH800 1 Isolator Detector Base Anal Apo AISA 45681 321 Mounting base with integrated dual isolator for automatic fire detectors Series XP95 and Dis covery with programmable address card suitable for indoor surface mounting Features Connection to ADM loop using Apollo Discovery protocol Wiring of the ADM loop across s
420. llance angle Ambient temperature supplied through detector line voltage Relative humidity Dimensions x H Colour Weight Cross references Page 155 119 35 120uA quiescent 100 10 C to 50 C 10 to 93 no condensation 120 x 40 mm white 230g Art Nr Name Type 249028 Address Module Conv Apo NG60 1 249020 Address Module Conv NG58 1 214020 Conventional Detector Interface GIF8 1 169 BB072001 SAM 0720 01 0100 243005 243004 169 BB072001 SAM 0720 01 0100 Chapter 20 Special Detectors 195 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 4 210210 Zone Extension Board ZEB2 1 Flame Detector UV Conv UV 03 Flame detector operating on the UV principle in conventional technology The detector re sponds to the ultraviolet parts contained in the outer zone of the flames and is therefore very well applicable for the detection of open flames light arcs on isolators etc The detector does not respond however to sunlight incandescent lamps fluorescent lamps and flying sparks Application limits occur in the field of UV emitting lamps halogen mercury vapour lamps etc dust and
421. ltage typ 20 0V Line current typ 3 8mA End of line resistance 5 6kOhm Line resistance max 50 Ohm per core Ambient temperature 5 C to 50 C Dimensions W x H x D 380 x 480 x 83 mm Colour grey white RAL 9002 Weight without batteries approx 5kg Approval VdS G205023 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 50 223009 Control Zone Module SLM 1 2 8 210110 Detector Zone Extension MGE8 1 9 210111 Fire Brigade Interface FW1016 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 9 210112 Serial Interface Module SIM016 3 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Module SZ58 3 287 310002 Stand by Battery 12V 18Ah 210120 Fire and Evacuation Panel BC016 2 D1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC016 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language Approval FT 14 439 04 Austria VdS G205023 210110 Detector Zone Extension MGE8 1 The Detector Zone Extension MGE8 1 is used to extend a Fire Detection Control Panel Se ries BCO16 by 8 detector zones in addressable conventional technology Features 8 detector lines in addressable conventional technology that can be ind
422. ltrex Anal 500 SS B524FTXE 79 246071 Detector Base with Diode FC600 FC600 BRD 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 107 246141 Detector Relay Base Conv 1000 SS ECO 1000BREL24L 105 246100 Detector Relay Base Conv 300 SS B324RL 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 80 246072 Detector Relay Base FC600 FC600 BREL 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 Detector Label BME BEZ Label for marking an automatic fire detector with detector zone and detector number It con sists of a sturdy white plastic card to which an adhesive label can be sticked and signed Di rect marking of the plastic card is also an option Specifications Marking area W x H 80 x 40 mm 169 BB072001 SAM 0720 01 0100 249040 249042 249041 169 BB072001 SAM 0720 01 0100 Chapter 23 Labels 227 Detector Label Large BME GR Single inscribable adhesive label for marking fire detectors not directly visible e g in inser ted ceilings inserted floors or for marking other devices of the fire detection system e g distribution boxes Specifications Dimensions 70mm Marking area W x H 60 x 30 mm Detector Label Small BME KL Single inscribable adhesive label for marking fire detectors not directly visible e
423. ly on each loop element ADM flexibility enables the connection of standard conventional detectors and special detectors to the ADM loop via a conventional zone monitor module Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 28VDC Output peak current max 1 8A Connection of external devices typ 0 8A system specific Current consumption at 24V typ 115mA incl LIF64 1 without detectors modules Ambient temperature 5 C to 50 C Dimensions W x H x D 420 x 520 x 120 mm Colour grey white RAL 9002 Weight without batteries approx 6kg Approval VdS G201017 Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 50 223009 Control Zone Module SLM 1 2 45 214601 Cover IP54 for BC216 GEH IP54 BC 1 D1 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2 1 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 295 218008 Parameter Setup Software PARSOFT 2 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 18 Chapter 3 Fire Detection Control Panels Series BC216 214300 214304 214306 214315 214307 214309 62 222004 Relay Module 8 Fold 60VDC RL58 1 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Mod
424. m Colour sky blue RAL 5015 Weight 400g Approval VdS G205018 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 49 210216 Extinguishing Board BC06 EXB1 1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 169 219006 Key for Manual Call Point SCH HFM HM 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249634 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 169 2171621 Replacement Glass for Manual Call Point Blue ET SCH HM BL 170 249024 Special Designation for Manual Call Point HM BESCH Manual Call Point Yellow Conv HM 1 11 05 02 Universal manual call point according to EN 54 11 B in an elegant yellow aluminium die cast housing designed for application in addressable conventional TOSCHANLAGE technology Scheibe einschlagen Features Ve R Robust aluminium die cast housing with a door aperture angle amp of more than 180 Function marking LOSCHANLAGE replaceable Keon fol A Optical activation indication by means of LED Latching default or non latching push button 160 Chapter 17 Manual Call Points Call Point HFM HM ZS IP54 Specifications Operating voltage Ambient temperature Protection class Dimensions W x H xD Easy to replace standardised glass plate Individual detector addre
425. matic hold up detectors for the surveillance of banknote packages in cash desks of financial institutions The Banknote Contact GK1224 works noise lessly due to the use of the principle of light reflection without any physical contacts At with drawal of the surveilled banknote package the gt detector switches to the state of alarm Specifications Supply voltage 10 30VDC Current consumption quiescent 15mA 12V 30mA 24V Switching distance 5 20mm Alarm delay 2 5sec Alarm contact change over contact 30VDC 0 5A Connection cable 5 wire 2m Ambient temperature 0 C to 50 C Colour black Dimensions W x L x H 30 x 45 x 16 mm Weight 60g Approval VSO 961021 27 169 BB072001 SAM 0720 01 0100 301 Notes Notes 169 BB072001 SAM 0720 01 0100 302 Notes 169 BB072001 SAM 0720 01 0100 227004 249039 249020 249028 244241 218045 218044 218041 2449999 244030 244031 244032 244033 244180 244181 244300 244155 244170 244201 320007 320008 214003 2149999 214034 214105 214005 214004 214060 214064 214612 214062 214079 214087 214056 214058 214089 214081 214066 214085 2149997 214176 246030 244233 180001 246006 359040 359041 359043 359042 359044 249110 249109 359003 359004 359008 214028 214128 169 BB072001 SAM 0720 01 0100 Product List A AC Adapter for DPU414 PW4007 E1 65 Address Cards 100pcs Anal XP95 Disc Apo
426. me Type 217 244300 Aspiration Smoke Detection System Housing TT 1 Aspiration Smoke Detection System T SS The Aspiration Smoke Detection System T SS continuously samples air from a monitored room via a sensor pipe network and directs it to an automatic smoke evaluation unit A venti lator in the interior of the aspiration smoke detection system housing generates a negative pressure to continuously aspirate air through the sensor pipe network to the evaluation unit Thereby the system which ope rates on the principle of scattered light always obtains new air samples from the monitored area If the smoke concentration exceeds the permissible value an alarm is activated which is optically displayed on the system and further transmitted to a fire detection control panel There is also the possibility of acti vating 2 different pre alarms The alarm can be reset at the fire detection control panel The air flow in the sensor pipe network is continuously monitored The operational safety of the aspira tion smoke detection system depends to a large extent on the permanent air supply of the detector Therefore a failure of the ventilator blocking of aspiration holes or a pipe burst are imme diately identified and transmitted to the control panel as fault message The sensitivity and the delay time of the air flow monitoring can be selected with two switches in 4 steps each The aspiration smoke detection system housing is provided in cludi
427. mechanical stability but also high corrosion resistance A standard built in heating device SW guarantees unhindered opening of the outer door even at low temperatures The key box can be connected to an existing burglar alarm system without any additional items The electric components of the key box are designed for an ope rating voltage of 12 to 24VDC which allows the Fire Brigade Key Box FSK700 2 D 1 to be connected via Control Unit for FSK700 AD700 1 D1 and AD900 1 D1 to any fire detection control panel even from other manufacturers Features High mechanical safety due to use of strong materials and intelligent design High corrosion resistance entire body construction made of stainless steel V2A Burglar alarm surveillance for the following componentries and functions Outer door protected against drilling and forced opening Correct deposit of the key in the cylinder of the console Application of all locking systems possible due to a variety of optional inner doors Buzzer for indication of incorrect deposit of key Heating device for outer door Optional flush mounting frame enables preparation for installation also available with all side drilling protection Adjusting options for even alignment of the key box Installation in optional Key Box Column possible Specifications Operating voltage 12 24VDC 15 Duty cycle of electromagnet 100 Current consumption 500ma active at
428. ment Individual detector addressing by installing an optional address module NG60 1 Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 65uA quiescent Alarm temperature typ 61 C Operating temperature max 50 C Ambient temperature 40 C to 70 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 50 mm Colour white Weight 130g Approval VdS G204034 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 242032 Thermal ROR Detector Conv ORBIS Apo HT 11003 Heat detector operating on the rate of rise heat detection principle in addressable conventio nal technology combined maximum rate of rise detector classified as BR maximum room height 6m in extra flat design suitable for indoor mounting For quick localisation in the event of an alarm each detector can be assigned an address by adding
429. mperature 40 C to 80 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 50 mm Colour white Weight 130g Approval VdS G204036 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 134 Chapter 14 Conventional Detectors Series 65 ORBIS 242034 242035 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 Thermal ROR Detector Conv ORBIS Apo HT 11005 Heat detector operating on the rate of rise heat detection principle in addressable conventio nal technology combined maximum rate of rise detector classified as CR maximum room height 6m in extra flat design suitable for indoor mounting For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are supported by the control panel If the detector i
430. mption 300uA quiescent Ambient temperature 20 C to 60 C continuous operation 25 C to 70 C max 12 hours Protection class IP43 Dimensions W x H x D 125 x 125 x 34 mm Colour sky blue RAL 5015 Weight 400g Approval VdS G206130 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249634 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 169 2171621 Replacement Glass for Manual Call Point Blue ET SCH HM BL 170 249024 Special Designation for Manual Call Point HM BESCH Manual Call Point Yellow Anal SS HM 1 22 05 02 Manual call point according to EN 54 11 B in an elegant yellow aluminium die cast housing designed for application on the ADM loop ring bus technology using System Sensor 200 protocol with integrated dual isolator module KJK Features LOSCHANLAGE Robust aluminium die cast housing with a door aperture angle of more than 180 a Function marking LOSCHANLAGE replaceable amp Integrated dual isolator Reverse polarity protection Knop tie dr cken Built in microcontroller st r Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Button in combination with
431. n e eee n eee 229 Sounder FB 12 24V White Multitone DBS1224B4W 6c cence ene e ence en ens 229 Strobe WM 24V Red Orange MS2RA 2 1 eee cece c eee n nnn e een b beet tenn ne eee 230 Strobe WM 24V Red Red MS2RR 24V 0 0 ccc cece ne ete ence een beeen enenn ees 230 Strobe 24V Orange BE A S 2 0 24VBMT resnnennnnennnennnnenanenaanenanenaanenarenannennne 230 Strobe 24V Red BE R S 2 0 24VBMT 00 ccc ccc cece cece nent e eee raven ene e teen eneenens 231 Sounder Strobe 24V Red Red MS5RR 6 cece ccc cece ccc een nen eee een ene n beeen een eenene 231 Optical and Acoustic Devices ADM Series XP95 200 355133 355131 355132 355124 355125 355130 355134 355135 355136 355137 355138 356020 356022 356023 355160 355161 355162 355163 355164 355165 355166 355167 356140 356141 Sounder WB XP95ISM White Alert 45681 277 00 ccc ccc ccc cece nen e een en ean teens 233 Sounder WB XP95ISM White Slow Whoop 45681 290 eee cece cece cence nee e ee eee 233 Sounder WB XP95ISM White DIN 45681 300 0 cece ccc cece cence ence een ene ae teens 234 Sounder WM XP95 Red Alert 100dB 55000 278 1 0 cece cece cece cence ene ence nee ee en eeeees 235 Sounder WM XP95 Red Slow Whoop 100dB 55000 276 00 e cece eee cece cnet eee e ees 235 Sounder WB XP95RI White Alert 45681 276 2 0 0 cece ccc cence ete ence ene n eee eeeneneens 236 Sounder Strobe WB XP95ISM White Clear Alert 45681 330 2 0 0 0 cece c
432. n ee enee ne eeene 106 Detector Base Conv 1000 SS ECO1000BR1000 2 0 cece cee eee eee een es 107 Detector Relay Base Conv 1000 SS ECO1000BREL24L cece c cence eee 107 Detector Relay Base Conv SS ECO1000BREL12L cece cence ee ee ees 108 Detector Relay Base Conv SS ECO1000BRELI2NL 1 cece cee ete 108 169 BB072001 SAM 0720 01 0100 14 15 169 BB072001 SAM 0720 01 0100 246002 Detector Base Anal 500 200 SS B501 srvauanannennnnannenrnnnvvernrnnvevennnaverernnnevener 109 246015 Detector Base Anal 500 200 SS B5S01DG oo ccc cece eee e ene n beeen nnn n eens 109 246016 Detector Relay Base Anal 500 200 SS BS24RTE 0 cece cece eee tte nee en nen e ee 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 0 cee cece cece eens 110 246018 Detector Heater Base Anal 500 SS BS24HTR ccc cee cee cee nent e een ees 111 246012 Detector Base Filtrex Anal 500 SS BS24FTXE 1 cece eee cnt e eee n nen e eens 111 246113 Zonal Display Unit Conv 300 SS S300ZDU o oo ccc cee cence eee tn nn eect en nen e ee 112 246111 Remote Program and Test Unit Conv 300 SS S300RPTU 0 cece cece cece ee eee eee e eee 112 246112 Satellite Unit for Remote Programming Conv 300 SS S300SAT 0 cece cece eee eens 113 246150 Remote Test Unit Conv 300 1000 SS ECO1000RTU cece eee cee ce teen eens 113 249212 Battery for ECO1000RTU 6V V11GA 0 0 cece e cc e reece e nee n eens eee 114 249214 B
433. n nnn e enn nen eeae 182 RF Devices 249201 241029 242029 245020 245021 246040 249202 249203 241036 245022 245023 249215 310020 310021 RF Interface 4Rel FUIF511 27D 2 0 ccc cee nnn een nen e een e beeen ene eeenes 184 Optical Smoke Detector RF 55000 680 2 2 0 0 coe e eee cece eee ene e ee een ene eee etn nee eens 185 Thermal ROR Detector RF 55000 480 2 0 0 ccc ccc ccc cence cence nen ence tenn en tneenenenes 185 Manual Call Point Red RF HFM 153 27D oo occ cence nce e nen e nent nee eeenenes 185 Manual Call Point Blue RF HM 152 27D 2 0 0 ccc ccc ccc cence nee een erent nen eeeeees 186 Detector Base Conv RF 215 27D 2 0 0 ccc ne cence nen nen n ene e bene n teen ene n teen tenes 187 RF Interface Anal SS MSOORFE AS 2 0 0 0 ccc ccc cece nee n nen nen e eet n eee teen eeenens 187 RF Interface 4Rel M400RFE AS 2 0 0 0 ccc cece cece nen ene nen nen n nee e etn tne ne teenies 188 Optical Thermal Detector RF complete 2100RFT AS 2 02 0 0 cece ec ee cece cece eect eee e ees 189 Manual Call Point Red RFM400DKMR AS 0 cece cence ene e nen e nent ne eeeeenes 189 Manual Call Point Blue RF M400DKMB AS 0 ccc cence nce e teen ence nen eeeeeenes 190 Battery for 270ORFI AS CRI23 sa das eh SARC EAN LAE IE 190 Lithium Battery 9V 2AM viss oe Rito ca sine pica cin tie alee sel dle clk win Bolte bie Ue Sad Se tiden area 191 Lithium Battery 3O V Z 2AB sv jesus sie eg VANE ISG Ya Saga arven 191 Special Detectors
434. n of an LBC sub control panel LBC1000 or LBC32 into the Global Security System network GSSnet The license must be ordered toge ther with the BCnet LBC Gateway Cross references Page Art Nr Name Type 59 214176 BCnet LBC Gateway N OP 6HU BCNET LBC GW Programming Cable BC216 RS232 PK216 1 Cable for connecting a COM interface of a PC with the Serial Interface Module SIM216 1 of a Fire Detection Control Panel of Series BC216 Specifications Cable length 1 8m Connection type 9 pole D SUB socket on both sides Cross references Page Art Nr Name Type 52 214231 Interface Adapter Module IAM216 1E 295 218008 Parameter Setup Software PARSOFT 2 52 214025 Serial Interface Module SIM216 1 s eam and 169 BB072001 SAM 0720 01 0100 6 Chapter 6 Additional Modules for Fire Detection Control Panels 61 Additional Modules for Fire Detection Control Panels 223024 223026 169 BB072001 SAM 0720 01 0100 Siren Connection Module SZ58 2 The Siren Connection Module SZ58 2 is installed particularly in Fire Detection Control Pa nels Series LBC to allow for the connection of acoustic signalling devices e g sirens to two separately controlled line monitored electric circuits The signalling devices can be supplied either directly by the fire detection control panel or at in creased current demand by an external power supply Features Connection to a monitored siren output of the fire detection control
435. nal Detector Interface GIF8 1 107 246140 Detector Base Conv 1000 SS ECO1000BR1000 107 246141 Detector Relay Base Conv 1000 SS ECO1000BREL24L 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PA58 1 113 246150 Remote Test Unit Conv 300 1000 SS ECO 1000RTU 4 210210 Zone Extension Board ZEB2 1 242046 Thermal Max Detector Conv 1000 SS ECO 1005T Thermal detector operating on the maximum heat detection principle classified A2S in ad dressable conventional technology in flat design suitable for indoor mounting in buildings with a maximum room height of 6m For quick localisation in the event of an alarm each detector can 4 be assigned an address by adding an Address Module NG58 1 i D a E a to the mounting base The address of the detector in alarm con ae dition as well as the assigned text is displayed directly on the fire _ detection control panel provided that these functions are sup ported by the control panel Features Individual detector addressing by installing an optional address module NG58 1 Output for external remote indicator Functionality check by means of test activation with Remote Test Unit ECO1000RTU Specifications Operating voltage supplied through detector line voltage Curr
436. nd via four dry changeover contacts which can be triggered separately The componentry can be installed in Fire Detection Control Panels Series BC216 Series BC016 Series BC06 and in the Burglar Alarm Control Panel LAC1000 1 Features Four independent relays with one dry changeover contact each Galvanically isolated changeover contacts on terminals Separate LED display for each relay Common positive supply Connection of trigger inputs via terminals or flat cable Specifications Operating voltage 20 to 31VDC Current consumption at 24V typ 22mA per activated circuit Control current typ 1 2mA per input Switching power per contact 3A 30VDC or 5A 230V AC Contact life unloaded approx 20m switching cycles at 230VAC 3A approx 400 000 switching cycles Ambient temperature 5 C to 50 C Dimensions L x W x H 98 x 74 x 28 mm Weight 120g Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 41 214128 Battery Bracket BK216 1CE 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel
437. nding on tube length and ven tilator speed Pipe length max 100m Ambient temperature 10 C to 60 C Humidity max 95 non condensing Protection class IP50 optionally IP65 Dimensions W x H x D 258 x 194 x 145 mm Weight 1 67kg Approval VdS pending Jer as 169 BBO72001 SAM 0720 01 0100 244033 244180 169 BB072001 SAM 0720 01 0100 Cross references Page Chapter 21 Aspiration Smoke Detection Systems Art Nr Name Type 91 90 241050 Optical Laser Detector Anal 200 SS 7251 241010 Optical Smoke Detector Anal 200 SS ND2251EM Aspiration Smoke Detection System Housing A320E The two channel Aspiration Smoke Detection System Housing A320E contains two separate sensing chambers for monitoring of two independent areas Each sensing chamber can ac commodate one smoke detector of any manufacturer Air from the monitored room is aspira ted by each of the sensor pipe networks that are connected to the housing and is directed to the respective detector Evaluation of the characteristics of smoke and the detection of alarm and fault depends on the applied detector The use of sensitive detectors is recommended such as a laser smoke detector to effectively detect a fire in an early stage The continuous air flow in both channels which is gene rated by a ventilator in the aspiration smoke detection sy stem housing is permanently monitored The system identifies the failure of the ventilator blocking
438. ne eee eet e eee ee nen nee ees 137 241030 Optical Thermal Detector Anal XP95 Apo AMS 55000 885 2 0 20 cece cece cece eee eee e eee e ee 138 240026 _Ionisation Smoke Detector Anal Disc Apo AI 58000 500 1 0 2 0 cece cece ee tence ett e eee e eee 138 241027 Optical Smoke Detector Anal Disc Apo AO 58000 600 0 cece cece cece eee e ee ence een e ee 139 Ix 16 17 242028 Thermal Detector Anal Disc Apo AD 58000 400 orovvenenananvernnnvevenanavvvernranveerenr 140 241022 Optical Thermal Detector Anal Disc Apo AMS 58000 700 1 0 2 0 0 cece eee cece eee eect eee e eens 141 243100 CO Detector Anal Disc Apo AC 58000 300 1 0 2 0 cece cece c cece eee e eee et ten eect enn ene es 141 249061 Monitor Module Anal XP95 Apo UMM 55000 833 c0ccecceee eee eee eee t eaten eeeeeeeenas 142 249060 Monitor Module Interrupt Anal XP95 Apo UMI 55000 832 cccceceeee eee eee eee eeee ences 142 249072 Monitor Module Anal XP95 Apo UMS 55000 841 ccc ccc cec cece eee eee eee e eae eaeeeeeenees 143 249076 Module 1xSurv In 1xRel Out Apo 55000 847 1 0 0 cece cece eee n nen e cette eee e es 143 249077 Module 3xSurv In 3xRel Out Apo 55000 588 2 2 0 cece eee cece ec eee eect eee e ee een nee e es 144 249078 Module 1xSurv In 1xRel Out 230 Apo 55000 8750 eke cece cence ee eet eee e een nee e es 145 249073 Control Module Anal XP95 Apo SMU 55000 852 ccc ccceee cece ences eee teat este tenes 145 2490
439. ng Kit SS RMK400 71 251001 Remote Indicator PA58 1 115 246009 Surface Mounting Kit SS SMK400 94 242002 Thermal Detector Anal 200 SS 525 1EM 121 249635 Trapezoid Steel Bracket TBH800 1 116 249012 Wet Base Shroud SS WB1 Detector Heater Base Anal 500 SS B524HTR Mounting base with heating elements for optical smoke sensors Series 500 and 200 suitable for indoor surface mounting in extremely moist areas e g loading ramps cable ducts The heating elements are powered by an external power supply Features Connection to the ADM loop using System Sensor 200 protocol Multi useable terminals with secure screw fitting Terminal for external remote indicator Mechanical theft protection Specifications Operating voltage for heating 20 to 30VAC DC Current consumption at 24V typ 80mA Ambient temperature 30 C to 60 C Relative humidity 10 to 95 no condensation Dimensions x H 102 x 35 mm Colour cream Weight 90g Cross references Page Art Nr Name Type 90 240013 Ionisation Smoke Detector Anal 200 SS 1251E 91 241050 Optical Laser Detector Anal 200 SS 7251 90 241010 Optical Smoke Detector Anal 200 SS ND2251EM 71 251001 Remote Indicator PA58 1 Detector Base Filtrex Anal 500 SS B524FTXE Mounting base for Filtrex detector FTX P1 suitable for indoor surface mounting Features Connection to the ADM loop using System Sensor 200 protocol 24VDC terminal for supplying the detector s ventilato
440. ng the entire evaluation and detection unit However the sensor pipe network is not provided bo EELETEE Features Applicable in addressable conventional technology with the optional Detector Reset Mo dule MQZ1000 1 Individual detector identification through connection of an optional address module NG58 1 Connection to an ADM loop is possible via optional modules Specifications Sensitivity 0 025 to 0 2 m adjustable in 4 steps Maximum pipe length 360m Max number of aspiration holes 72 Supply voltage 14 30VDC Current consumption at 24V approx 400mA quiescent 450mA active Ambient temperature 10 C to 60 C standard version Dimensions W x H x D 366 x 240 x 132 mm Colour white RAL 9018 Weight 2 8kg Protection class IP20 Approval VdS G201035 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 4 210210 Zone Extension Board ZEB2 1 220 Chapter 21 Aspiration Smoke Detection Systems 244170 Aspiration Smoke Detection System VLS 3
441. nics prevents false alarms caused by environmental influences Output for external remote indicator Mechanical theft protection supplied through loop voltage typ 500uA quiescent 20 C to 60 C no condensation or icing Relative humidity 0 95 no condensation Dimensions x H 100 x 50 mm Colour white Weight 105g Approval VdS G299080 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 lonisation Smoke Detector Anal Disc Apo Al 58000 500 Addressable smoke detector operating on the ionisation principle for application on the ADM loop using Apollo Discovery protocol consisting of a sensing and reference chamber dual chamber principle for automatic compensation of environmental influences and of extra flat design suitable for indoor mounting C2 nar Intelligent evaluation algorithms in the respective LST fire de tection control panels compensate for the impact of contamina tion of the sensing system Thereby the response sensitivity of the detector is kept constant for a long time thus constituting an effective measure for
442. nnection to the ADM loop using Apollo Discovery of oo a protocol Qo E7 Easy detector addressing through address card in moun Se if ting base No electronics contained Multi useable terminals with secure screw fitting Mechanical theft protection Specifications Ambient temperature 20 C to 60 C no condensation or icing Relative humidity 10 to 95 no condensation Dimensions x H 100 x 15 mm Colour white Weight 50g Cross references Page Art Nr Name Type 153 246030 Backplate Apo SZPL 45681 233 153 246029 Conduit Box Apo SZA 4568 1 204 177 240025 IS Ionisation Smoke Detector Anal XP95 Apo AIEX 55000 540 178 241024 IS Optical Smoke Detector Anal XP95 Apo AOEX 55000 640 178 242036 IS Thermal Detector Anal XP95 Apo AWEX 55000 440 180 Chapter 18 Devices for Hazardous Areas 228004 228005 Safety Barrier Anal XP95 Apo AES 29600 098 Safety barrier with galvanic separation used for the build up of an intrinsically safe circuit for the connection of analogue fire detectors in hazardous areas to ADM Part No 71997 Part No 72157 or 107496 Features loops using Apollo Discovery protocol Due to the galvanic separation the earth fault surveillance of the fire detection control panel can re main active The relevant regulations for installations in hazardous areas must be observed The number of detectors that can be connected to the safety barrier depends on the hardware version
443. nnenaanennneenanenareennnenannennnenner 207 Gas Detector Propane GM PROPAN 0 cece cec eee e eee ete ene eet n eee n ee eae 207 Gas Detector 230V GM MEIBU 230V reuunnnnenennvanennnannenenannuenrnanueuennnnuenenenr 208 Detector Reset Module MQZ1000 1 eeununennennnnenanenenenanennnuenanenannenanennnnenaner 208 Optical Battery Smoke Detector FL10022H oonavvnnnanvenennnnvenennnanvenrnneauenananuevennr 209 Aspiration Smoke Detection Systems 244030 244031 244032 244033 244180 244181 244186 244182 244183 244184 244185 244300 244302 244303 244304 244305 244155 244170 Aspiration Smoke Detection System A211E LSR assuunnnnennnnnnenennnnnerernnvrvvennanvevener 210 Aspiration Smoke Detection System A222F LSR sesuunvnenanannenennnnnvrnrnnvannennanuevener 211 Aspiration Smoke Detection System Housing A310E srevonnnnenenananennnnnvevenanavverennnr 212 Aspiration Smoke Detection System Housing A320E srevonnnnenenananennnnnvevenanavverennnr 213 Aspiration Smoke Detection System Housing TP 1 aoooovenannnannvnvnnvvvvvnnanvevenasauvenner 213 Aspiration Smoke Detection System Housing TP 2 aorovvennnnnannennnnnnevrnnanuevenasaueenner 214 Detector Module DM TP 80L r ersero eterra E eE E E EAE EE ENT EE 215 Detector Module DM TP 25 L oenar essen ccc cence EE N E SE 215 Detector Module DM TP 05 L ovnanunnnnenennnanuenennunnennnannenennnnuennnanuenennnnuuerenn 216 Front FOLEWTP TAGAN AS SANE AM AI GA
444. ns are supported Features Per ADM loop a maximum of 128 detector zones in ADM technology for the connection of manual call points automatic detectors conventional modules control modules and si gnalling devices The Fire Detection Control Panel Module LG can support a total of 144 detector zones ADM loop wiring is realised as ring branch or any given combination of sectional rings and branches using unscreened cables Two isolator modules at the beginning and the end of every ADM loop are integrated on the componentry Connection of 198 physical address points 99 detectors and 99 modules per loop using System Sensor 200 protocol Connection of 126 physical address points detectors or modules per loop using Apol lo Discovery protocol Every physical address is assigned an organisational address individual detector identification Free assignment of detector zones or individual detectors for the activation of transmitting devices actuations or alarming devices Maintenance prognosis for every single connected smoke detector Full function of all connected elements in case of wire breakage on the ADM loop line At short circuit all elements not affected are fully operable thanks to the installed isolator modules In addition to the main processor an independent CMOS processor per ADM loop is in stalled to ensure the alarming capability even at system failure Specifications Supply voltage 21 to 30VDC Cu
445. nt temperature 20 C to 60 C continuous operation Relative humidity 10 to 93 no condensation Dimensions x H 102 x 51 mm Colour cream Weight 102g Approval VdS G200094 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PA58 1 241019 Optical Filtrex Smoke Detector Anal 500 SS FTX P1 Addressable smoke detector operating on the light scatter principle for application on the ADM loop using System Sensor 200 protocol with an optical sensing chamber suitable for indoor mounting in dusty environments The detector is equipped with two 32 filters which 169 BB072001 SAM 0720 01 0100 249046 169 BB072001 SAM 0720 01 0100 Chapter 12 Analogue Detectors and Modules Series 200 500 95 prevent the infiltration of dust and water particles One filter is firmly built in the other is demountable and can be cleaned or replaced by the user The filters allow smoke to permeate while particles that can trigger deceptive alarms dust particles water spray tiny insects etc are deterred Since the filters weaken the normal circulation in the sensing chamb
446. ntrinsically safe circuit DIN rail mounting Specifications Ignition protection Ex classification Operating voltage Ambient temperature Dimensions W x H x D intrinsically safe EEx ia IIC T5 supplied through detector line voltage 20 C to 60 C 20 x 110 x 107 5 mm 182 Chapter 18 Devices for Hazardous Areas 228007 245680 Installation Colour Weight Approval Cross references Page 181 182 35mm DIN rail green 100g BASOOATEX7087 Art Nr Name Type 241025 IS Optical Smoke Detector Anal 200 SS 225 1EIS 228007 Protocol Interface Anal 200 SS IST200 Protocol Interface Anal 200 SS IST200 The protocol interface is always used together with the Safety Barrier Anal 200 SS and al lows for the bi directional data exchange of analogue fire detectors in hazardous areas on the ADM loop using System Sensor 200 protocol Features Connection of up to 15 automatic detectors of type KE 2251EIS Sy NE Designed to be integrated into the surface mounting box iy ee SMB500 Specifications Ignition protection Operating voltage intrinsically safe supplied through loop voltage Ambient temperature 0 C to 60 C Relative humidity 5 to 95 no condensation Dimensions W x H x D 70 x 70 x 32 mm Weight 155g Cross references Page Art Nr Name Type 181 241025 IS Optical Smoke Detector Anal 200 SS 2251EIS 181 228006 Safety Barrier Anal 200 SS Y72221 118 249004 Surface Mounting Box
447. ntrol panels consist basically of the same components as the stand alone control panels and consequently share the same clear modular design as well as the individual parameter setup This makes the units clear and easy to handle and the required professional knowledge for planning and commissioning thanks to the use of consistent components remains the same for every system size By the use of network technology the control panel sets new standards for security in fire alarm technology and at the same time reduces costs due to most simple cabling work The following table provides you with an overview of the most important characteristics of the individual control panels sectional control panels or control panel modules respectively of Series BC216 Type Display and Sectional Control BCnet Sectional LED display operating field Panel in the Control Panel field available GSSnet Extension applicable applicable BC216 2 Oos oos ee x weas px feczwscernrom x px feces S S feczeaers x x x fecwmosers dt dT Cd sms dd C 9 The Global Security System network GSSnet allows for the communication of overall 127 GSSnet members i e BCnet sectional control panels control panel modules etc which to gether provide the possibility to connect 254 ADM loops using System Sensor 200 or Apollo Discovery protocol or 2032 detector zones in addressable conventional technology 9700 actuations e g fir
448. nts of the European Standard EN 54 2 The following designs of control panels can be used as sectional control panels within a Net work Fire Detection Control Panel BCnet216 BCnet Sectional Control Panel in standard wall mount cabinet BC216 2 with display and operating field or BC216 3 without display and operating field each of which can be expanded with a BCnet Sectional Control Panel Extension BCE216 3LG BCnet Sectional Control Panel in compact 19 slide in technology BC216 1CE with addi tionally installed Network Interface Module NIF5 1M with display and operating field or BC216 3CE without display and operating field and BCnet Sectional Control Panel BC216 2EPS consisting of a 19 Control Panel Rack RACK216 1E a Fire Detection Control Panel Module with power unit BCM216 3EPS and a Display and Operating Front Panel ABP216 1E which can be expanded with Fire Detection Control Panel Modules BCM216 3EPS BCM216 3E and BCM216 3ELG The administration of the entire fire detection control panel is assigned to a BCnet sectional control panel with display and operating field of your choice which is parameterised as main operating unit and allows for the full operation of all BCnet sectional control panels in the networked control panel This main operating unit also takes care of the setup of site specific parameters for the entire control panel easily and comfortably accomplished by means of PC and Windows Parameter Setup Sof
449. o gy maximum heat detector classified as CS maximum room height 6m in extra flat design suitable for indoor mounting 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 Chapter 14 Conventional Detectors Series 65 ORBIS 135 For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire detection con trol panel provided that these functions are supported by the control panel If the detector is faulty the multicolour status LED on the detector will flash for approx 4 minutes in yellow colour after the detector line has been enabled Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional address module NG60 1 Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 65uA quiescent Alarm temperature typ 90 C Operating temperature max 80 C continuous operation Ambient temperature 40 C to 90 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 50 mm Colour white Weight 130g Approval VdS G204038 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo
450. o 55 C Relative humidity 10 to 95 no condensation Dimensions x H incl base 100 x 46 mm Colour cream Weight 115g Approval BAS01ATEX1281 LPCB 164a Cross references Page Art Nr Name Type 176 246090 IS Detector Base Conv YBN R 4IS 177 228003 Safety Barrier Conv ES58 2 IS lonisation Smoke Detector Conv 60 Apo GIEX 55000 212 Smoke detector for hazardous areas operating on the ionisation principle in conventional technology consisting of a sensing and reference chamber dual chamber principle for auto matic compensation of environmental influences and of extra flat design suitable for indoor 7 mounting The detector is used with the IS Detector E N Base Conv 60 Apo and must always be connected via a safety Vo _ NE barrier approved for the respective detector Particular attention KA must be paid to the compliance with country specific regulations Features Sealed electronics prevents false alarms caused by the environment Output for external remote indicator Mechanical theft protection Insect screen Checking with Testset Conv S60 Apo TS 53832 020 Specifications Ignition protection Ex classification Operating voltage Current consumption at 24V intrinsically safe EEx ia II T5 supplied through detector line voltage typ 45uA quiescent 176 Chapter 18 Devices for Hazardous Areas 246090 246023 Ambient temperature Relative humidity Radioactive compound Dimensions x
451. obe due to the use of LEDs supply through the loop voltage typ 300uA quiescent max 8mA sounder and strobe on 55 75dB A or 75 91dB A 1m distance 1Hz 20 C to 60 C IP21 max 95 no condensation 115 x 38 mm 238 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 355136 Colour white Weight 160g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359021 Lid for Detector Base Sounder Red 45681 293 252 359020 Lid for Detector Base Sounder White 45681 292 35 214021 Loop Interface LIF64 1 253 359022 Mounting Plate for Sounder WB XP95 38531 810 Sounder Strobe WB XP95ISM White Clear DIN 45681 334 The addressable sounder with integrated strobe 4568 1 334 is installed in a round white pla stic housing The unit is actuated using Apollo Discovery protocol and powered via the ADM loop The sounder is always activated together with the strobe The integrated detector base is x Wi 3 ir ait SV suitable for accommodation of fire detectors Series XP95 and Discovery The unit is prepared for indoor surface mounting 4 A dual isolator is integrated in the componentry At short circuit W it maintains the function of ADM elements that are not affected by the short circuit Depending on the parameter setup of the Fire Detection Control Panel Se
452. obes Series WMS Due to the design of the base cable entry is possible from the back or the side The base contains an integrated spring contact for through connection of the loop if the si gnalling device has been removed Features Cable entry possible from the back or the side in case of surface mount installation Multi wire terminals with secure screw fitting Through connection of loop line via spring contact Mechanical theft protection Specifications Ambient temperature 25 C to 70 C Protection class IP65 Dimensions x D 107 x 61 mm Additional depth of signalling devices 43mm Colour white Weight 112g Cross references Page Art Nr Name Type 247 355166 Sounder Strobe WB 200 White Red Multitone IBSST DR P01 248 355167 Sounder Strobe WB 200ISM White Red Multitone IBSST DR P02 245 355164 Sounder WB 200 White Multitone IBSOU DD P01 246 355165 Sounder WB 200ISM White Multitone IBSOU DD P02 Base Sounder amp Strobe IP44 Red SDBR The Base SDBR serves for mounting of sounders detector base sounders and strobes Series WMS and IBS Due to the design of the base cable entry is possible from the back or from the side The base contains an integrated spring contact for through con nection of the loop if the signalling device has been removed Features Cable entry possible from the back or from the side in case of surface mount installation Multi wire terminals with secure screw fitting Throug
453. odule DM TT 80 L 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT I 218 244305 Front Foil FW TT 1 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 4 210210 Zone Extension Board ZEB2 1 Detector Module DM TT 80 L The Detector Module DM TT 80 L is used for analysis and evaluation of air which is sampled from the monitored area by the aspiration smoke detection system housing TT 1 The light obscuration and the air flow are measured by the detector module The response 218 Chapter 21 Aspiration Smoke Detection Systems thresholds for the light obscuration and the air flow can be selected in 4 steps Dry contacts in the evaluation electronics of the aspiration smoke detection system housing signal the exceeding of alarm and fault thresholds Specifications Response threshold Light obscuration 1 6 0 8 m Air flow monitoring 4 levels Cross references Page Art Nr Name Type 217 244300 Aspiration Smoke Detection System Housing TT 1 244303 Detector Module DM TT 25 L The Detector Module DM TT 25 L is used for analysis and evaluation of air which is sampled from the monitored area by the aspiration smoke detection system housing TT 1 The light obscuration and the air flow are measured by the
454. of announcement messages directly on the device via a telephone receiver All functions freely programmable without the need for an additional programming device Programmable time delay for transmission of fault messages Real time clock with calendar pre programmable shifting date of summer time period Event memory for the last 200 events Outputs for transmission of system conditions Sabotage protected steel sheet case Power supply from a danger detection system 12V and 24V or optional plug in adapter Integrated charger for an optional stand by battery Optional extension to 8 control line inputs and 5 actuation outputs Optional extension for continuous monitoring of phone line Optional extension for remote control by an acoustic dialogue menu remote inquiry of the system conditions and remote maintenance by the installer Specifications Inputs 4 control lines with free assignment expandable to 8 Activation criteria 30 change in resistance Outputs 1 actuation output dry change over contact contact load max 60V 1A I dry fault detection output max load 30V 50mA 1 dry confirmation output max load 30V 50mA Dialling mode pulse dialling mode DTMF mode Supply voltage 10 31 VDC Current consumption at 12V 60mA quiescent 140mA alarm condition and actuation output activated Current consumption at 24V 35mA quiescent 70mA alarm condition and actuation output activated Stand by battery optional 6V 1 2Ah Charging current max
455. of scattered light and a maximum heat detector with the alarm temperature set at 58 C The alarm is radio transmitted to the RF Interface M500RFE AS System Sensor 200 protocol or MA400RFE AS in conventional technology The radio linked detector is particularly suitable for appli 4 W D cations where cabling is not possible or inefficient The detector is designed for indoor mounting and is delivered p with a mounting base however batteries are not provided Features Extremely low quiescent current consumption Sealed electronics prevents false alarms caused by environmental influences Insect screen Alarm display on detector Status message at the end of battery lifespan Features Voltage supply 2 lithium batteries 3V type CR123 Battery lifespan approx 1 5 years Alarm temperature 58 C Frequencies 434MHz and 868MHz Radio transmission range max 300m free air Ambient temperature 0 C to 40 C Relative humidity 10 93 no condensation Dimensions x H 140 x 55 mm Colour white Weight 187g without batteries Approval VdS G204105 Cross references Page Art Nr Name Type 190 249215 Battery for 2100RFT AS CR123 188 249203 RF Interface 4Rel M400RFE AS 187 249202 RF Interface Anal SS M500RFE AS Manual Call Point Red RF M400DKMR AS The radio linked manual call point according to EN 54 11 B is accommodated in a red plastic housing The antenna is integrated in the detector housing The alarm is
456. of the building in case of fire The keys have to be kept sepa rately in the fire brigade key box if two separate user areas for the fire detection system or two separate access roads for the fire brigade exist After an alarm an LED in the Fire Brigade Key Box above the mounted half cylinder optically indicates which key has to be taken out for access after rescue forces have ope ned the outer and inner door Both half cylinders are monitored for proper key storage and removal by the Fire Brigade Key Safe Adapter AD900 1 D1 The box and the front plate consist of 5mm stainless steel and hence offer mechanic stability and high resistance against corrosion An integrated heating device SW guarantees the opening of the outer door also in case of low temperatures The electrical components of the key box are de signed for an operating voltage of 12 or 24VDC thus enabling the connection to all fire de tection control panels also products from other manufacturers via the Fire Brigade Key Safe Adapter AD900 1 D1 Features Separate storage of two building keys High mechanical safety through application of strong materials and sophisticated construction High corrosion resistance entire body construction made of stainless steel V2A Burglar alarm surveillance for the following componentries and functions Outer door protected against drilling and forced opening Correct deposit of the keys in the cylinder of the console Appli
457. ol Module 1xRel Out DIN Anal 200 SS M201E 240 DIN Addressable module prepared for mounting on a DIN rail for the activation of external devi ces by means of a changeover contact suitable for 230V AC via the bi directional communi cation on the ADM loop using System Sensor 200 protocol The integrated dual isolator can be activated or deactivated by choosing the appropriate terminals Features Status LED 2 decadic rotary switches for setting the address from 01 to 99 prepared for mounting on a DIN rail Specifications Operating voltage supplied through loop voltage Current consumption approx 510uA quiescent Contact type changeover contact Switching power per contact SA 30VDC or 5A 230V AC Ambient temperature 20 C to 60 C Dimensions L x W x H 127 x 76 x 48 mm Weight 235g Approval VdS G202141 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Control Module 6xRel Out Anal 200 SS CR 6 Addressable module for the activation of external devices by means of 6 independent dry contacts via the bi directional communication on the ADM loop using System Sensor 200 protocol Features Status LED for every input 2 decadic rotary switches for setting the address from 01 to 99 Mounting in a Surface Mounting Box For Multimodule SS Specifications O
458. ol panel Features Activation in conjunction with a fire detection control panel possible Two optical and one acoustic indicator signalise the operating status door CLOSED or OPEN Integrated electronic buzzer activates when emergency button is pushed Surface case suitable for wall mounting in dry rooms Specifications Operating voltage 24VDC Buzzer sound level 100dB Dimensions W x H x D 120 x 170 x 60 mm 276 Chapter 29 Fire Controls 261003 261004 261005 Weight 730g Cross references Page Art Nr Name Type 279 261019 Magnetic Lock Clamp 2750N 1388 279 261017 Magnetic Lock Clamp 4900N 1390 279 261018 Magnetic Lock Clamp LED 4900N 1392 Magnetic Clamp 500N 1330 The magnetic clamp is used for fixing fire doors or smoke compartments It consists of a base plate for wall mounting and flexible wires for con nection as well as an armature plate with a tilt joint as counterpart Specifications Operating voltage 24VDC Power consumption 1 5W Adhesive force approx 500N 50kg Working temperature 5 C to 50 C Dimensions L x W x H magnet 65 x 65 x 35 mm armature plate 60 x 60 x 48 mm Weight 420g Magnetic Clamp Reset 500N 1350 The magnetic clamp is used for fixing fire doors or smoke compartments It consists of a sur face wall mount housing with lateral interrupt button and an armature ES plate with a tilt joint as counterpart L9 Specifications Operating voltage
459. olour white Weight 100g Approval VdS G204039 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 Optical Thermal Detector Conv ORBIS Apo OH 13001 Multisensor detector with a detection element operating on the light scatter principle and a detection element operating on the heat principle in addressable conventional technology and of flat design suitable for indoor mounting For quick localisation in the event of an alarm each detector can be assigned an address by adding an address module NG60 1 to the mounting base In this case the detector address as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are supported by the control panel Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept con stant for a long time thus constituting an effective measure
460. omatic fire detectors with or without alarm verification technical messages and fault detectors with or without self resetting property Administration of 10 transmitting devices 99 alarming devices 128 actuations and 199 sectors Easy operation of the control panel by freely parameterisable sectors INFO field with 4 line by 20 character backlit text display for information on all current events Info button for additional information on current events Event memory displays last 500 events in chronological order with setable filters LED indicators for activation fault disablement alarm delay operation call fire brigade and confirmation for the fire brigade transmitting device Monitored output for activation of external signalling devices with display of activation fault or disablement One dry contact each for summary alarm and summary fault 16 open collector outputs parameterisable as transmission and alarming devices actuati ons or other output types And or combinations for activation of actuations transmitting devices or alarming devi ces in dependence from messages of detector zones or individual detectors Button Panel reset for common reset of all current events 3 authorisation levels for operation and parameterisation secured by numeric codes Alarm delay with dead man s handle programmable for every day of the week by means of the internal timer Automatic shifting between winter and summertime either according to EU di
461. ompleted week of delay an indemnity of at most one half of one per cent a total of no more than 5 however of the value of that part of the goods to be delivered which cannot be used on account of Seller s failure to deliver an essential part thereof provided the Buyer has suffered a damage to the aforesaid extent Assertion of rights of damages exceeding this extent is precluded Passage of risk and Place of performance Enjoyment and risk shall pass to Buyer at the time of departure of the goods ex works or ex warehouse regardless of the terms of quotation such as carriage paid C LF etc agreed upon This provision also includes the case of shipment being ef fected organised and supervised by Seller and the case of delivery being made in connection with assembly work to be undertaken by Seller For services the place of performance shall be the place at which the service is ren dered the risk in respect of such services or any part thereof that may have been ag reed upon shall pass to Buyer at the time the services have been rendered Payment Unless otherwise agreed one third of the purchase price shall fall due at the time of receipt by Buyer of the order confirmation of Seller one third after half the delivery period has elapsed and the balance at the time of delivery Irrespective thereof the turnover tax comprised in the amount of the invoice shall be paid within 30 days of the invoice date In the case of part settlement
462. on Control Panel Series BC216 and the system condition the panel can activate the sounder with tone A or B The address of the sounder and strobe as well as the sound level are set via the DIL switch Features Tone A alternating tone 581Hz for 1s 870Hz for 1s Tone B interrupted tone 870Hz 1s ON 1s OFF 169 BB072001 SAM 0720 01 0100 355135 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 237 Low power consumption Integrated dual isolator Specifications Operating voltage Current consumption from loop Sound level Flash frequency Ambient temperature Protection class Sound level adjustable in two steps via DIL switch Simple address setting of inserted detector by code card in detector base Long lifespan of strobe due to the use of LEDs supply through the loop voltage typ 300uA quiescent max 8mA sounder and strobe on 55 75dB A or 75 91dB A Im distance 1Hz 20 C to 60 C IP21 Relative humidity max 95 no condensation Dimensions x H 115 x 38 mm Colour white Weight 160g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359021 Lid for Detector Base Sounder Red 45681 293 252 359020 Lid for Detector Base Sounder White 45681 292 35 214021 Loop Interface LIF64 1 253
463. on by removal of two jumpers Receiver LED display for alarm and fault as well as display for preset values and commis sioning support Adjustment screws for an easy alignment of the detector Test filter for optimal commissioning included in delivery 169 BB072001 SAM 0720 01 0100 244021 169 BB072001 SAM 0720 01 0100 Chapter 20 Special Detectors 199 Specifications Operating voltage Current consumption Ambient temperature Relative humidity Dimensions W x H x D Dimensions W x H x D supplied through loop voltage 2mA quiescent 8mA active 30 C to 55 C max 95 no condensation 190 x 254 x 84 mm Smoke Detector 6500 200 x 230 x 10 mm Reflector 5 to 70m Protection class IP54 Colour cream Weight 1 8kg Approval VdS G205033 EN 54 12 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 200 244025 Multi Mount Kit 6500 BEAMMMK 200 244024 Reflector 6500 75 100M BEAMLRK 201 244026 Surface Mount Kit 6500 BEAMSMK Beam Smoke Detector Test Anal SS 6500S Beam smoke detector for the surveillance of open areas with a range of 5m to 70m with ac cessories up to 100m consisting of a combined transmitter receiver unit integrated into a plastic housing for application on the ADM loop using System Sensor 200 protocol de signed for indoor mounting A pulsed inf
464. on of plant and equipment If the granting of such licences or approvals is delayed for any reason the delivery period shall be extended accordingly Seller may carry out and charge Buyer for partial or advance deliveries If delivery on call is agreed upon the commodity shall be deemed called off at the latest one year after the order was placed 5 4 5 5 6 2 7 2 7 3 7 4 7 5 7 6 V7 7 8 In case of unforeseeable circumstances or circumstances beyond the parties control such as all cases of force majeure which impede compliance with the agreed period of delivery the latter shall be extended in any case for the duration of such circum stances these include in particular armed conflicts official interventions and prohi bitions delays in transport or customs clearance damages in transit energy shortage and raw materials scarcity labor disputes and default on performance by a major component supplier who is difficult to replace The aforesaid circumstances shall be deemed to prevail irrespective of whether they affect Seller or his subcontractor s If a contractual penalty for default of delivery was agreed upon by contracting par ties when the contract was concluded it shall be executed as follows and any devia tions concerning individual items shall not affect the remaining provisions Where delay in performance can be shown to have occurred solely through the fault of Seller Buyer may claim for each c
465. onal Zonal Display Unit S300ZDU one of which must be integrated in every detector line Features Individual detector addressing via Address Module NG58 1 or Remote Program and Test Unit SJOORPTU Functionality check by means of test activation with Remote Program and Test Unit S300RPTU or Remote Test Unit ECO1000RTU Detector status detector address as well as date of latest maintenance can be scanned via Remote Program and Test Unit SJOORPTU Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 80uA quiescent Alarm temperature 58 C maximum heat component Operating temperature max 45 C Ambient temperature 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 x 43 mm Colour cream Weight 75g Approval VdS G202014 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 105 246008 Detector Base Conv 400 100 300 SS B40IRM 105 246100 Detector Relay Base Conv 300 SS B324RL 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 71 251001 Remote Indicator PAS8 1 112 246111 Remote Program and Test Unit Conv 300 SS S300RPTU
466. ondensation Dimensions x D 112 x 37 mm incl Base LPBW wa av E 250 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 Colour red Weight 80g Cross references Page Art Nr Name Type 254 359040 Base Sounder amp Strobe IP24 White LPBW 255 359041 Base Sounder amp Strobe IP44 Red SDBR 256 359042 Base Sounder amp Strobe IP65 Red WDBR 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 169 BB072001 SAM 0720 01 0100 26 Chapter 26 Accessories for Optical and Acoustic Devices 251 Accessories for Optical and Acoustic Devices 359003 359004 359008 169 BB072001 SAM 0720 01 0100 Base for Sounder amp Strobe IP44 Red EMA ELPBR The base ELPBR for Series EMA sounders and strobes is used for surface mounting and flush mount or surface mount cabling Features All side cable entry possible Additional terminal on base floor Specifications Ambient temperature 30 C to 70 C Protection class IP44 Dimensions W x H x D 120 x 90 x 22 mm Colour red Weight 40g Cross references Page Art Nr Name Type 229 355101 Sounder WM 12 24V Red Multitone 103dB EMA1224B4R Base for Sounder amp Strobe IP55 Red EMA ESBR The base ESBR for Series EMA sounders and strobes is used for surface mounting and flus h mount or surface mount cabling Features All side cable entry
467. onitoring due to the high response sensitivity of the detector modules The continuous air flow which is generated by a ventilator in the a aspiration smoke detection system housing is permanently moni tored A failure of the ventilator blocking of aspiration holes or a pipe burst are optically displayed on the system and transmitted to the control panel as fault message 214 Chapter 21 Aspiration Smoke Detection Systems 244181 The aspiration smoke detection system housing is provided with the entire evaluation electro nics However the detector module the front foil and the sensor pipe network are not provided A serial interface is installed in the system for communication with a PC software Operation fault and alarm are indicated on the front side of the system via LEDs Features Applicable in addressable conventional technology with the optional Detector Reset Mo dule MQZ1000 1 Individual detector identification through connection of an optional address module NGS58 1 Connection to an ADM loop is possible via optional modules Specifications Supply voltage 14 30VDC Current consumption at 24V max 275mA quiescent 285mA alarm incl detector module Pipe length max 180m Number of aspiration holes max 20 Ambient temperature 20 C to 60 C Dimensions W x H x D 200 x 292 x 113 mm Colour white RAL 9018 Weight 1 35kg Approval VdS G202064 Cross references Page Art Nr Name Type 119 249020
468. onnected fire controls the fire doors close and thereby a prevent the spreading of fire and smoke Features Conventional detector line with surveilled quiescent current for auto matic detectors or manual call points 9 High output power for fire controls m Dry contact for site specific functions q 9 Activation and reset button integrated in the device Specifications Mains voltage 230V AC 10 15 50Hz Connection power 40VA Output voltage 24VDC Output power max 18W in continuous operation Working temperature 5 C to 50 C Contact rating 30VDC 2A 60W Protection class IP43 Dimensions W x H x D 99 x 164 x 67 mm Colour light grey RAL 7035 Weight 1 06kg Cross references Page Art Nr Name Type 107 246140 Detector Base Conv 1000 SS ECO 1000BR 1000 105 246008 Detector Base Conv 400 100 300 SS B40IRM 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 60 241009 Meldereinsatz 100 OM 2151E 86 241046 Optical Thermal Detector Conv 1000 SS ECO1002 82 241041 Optical Thermal Detector Conv 300 SS 2351TEM 85 241045 Optical Smoke Detector Conv 1000 SS ECO1003 81 241040 Optical Smoke Detector Conv 300 SS 2351E 126 241026 Optical Smoke Detector Conv 65 Apo GO 55000 317 Control Device for Magnetic Lock Clamp 2498 Electronic control device for triggering a magnetic lock clamp Activation can result from pushing a button located behind a glass plate by means of an integrated key switch or via a fire detection contr
469. ons and features are summarised in the description of the Fire Detection Control Panel BCnet216 No 2199998 as well as in the description of the individual components Cross references Page Art Nr Name Type 42 214230 Control Panel Rack 8HU RACK216 1E 50 223009 Control Zone Module SLM 1 2 35 214020 Conventional Detector Interface GIF8 1 33 214208 Display and Operating Front Panel ABP216 1E INT1 169 BB072001 SAM 214204 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 31 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2 1 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 52 214231 Interface Adapter Module IAM216 1E 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 35 214021 Loop Interface LIF64 1 51 214027 Network Cable NWK2 1 39 214031 Network Redundant Alarm Converter NNUS5 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 61 223026 Siren Connection Module SZ58 3 289 310005 Stand by Battery 12V 65Ah Fire Detection Control Panel Module PS BCM216 3EPS The Fire Detection Control Panel Modul
470. ontact NG Terminal for external remote indicator Mechanical theft protection of detectors i Specifications Operating voltage 10 to 28VDC Current consumption max 3uA quiescent 17mA active Contact rate 1A at 30VDC Ambient temperature 30 C to 70 C Relative humidity 5 95 no condensation Dimensions x H 111 x 27 mm Colour white Weight 58g Cross references Page Art Nr Name Type 76 241070 Optical Smoke Detector Conv FC600 FC600 O 71 251001 Remote Indicator PAS8 1 77 242071 Thermal Max Detector Conv FC600 FC600 TMAX 78 77 242070 Thermal ROR Detector Conv FC600 FC600 TDIFF 57 TET av E 169 BB072001 SAM 0720 01 0100 11 241040 Chapter 11 Conventional Detectors Series 300 ECO1000 81 Conventional Detectors Series 300 ECO1000 Optical Smoke Detector Conv 300 SS 2351E Smoke detector operating on the light scatter principle in addressable conventional technolo gy and of flat design suitable for indoor mounting For quick localisation in the event of an alarm each detector can be assigned an address eit her by adding an address module NG58 1 to the mounting ba se or by programming the detector with an optional Remote Program and Test Unit SSOORPTU If the detector is addres sed using NG58 1 the detector address as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are supported by the control pa nel If the detector address
471. ontrol Panel Housing 9 14 GEH19 18 GEH19 40 1 or 9 STAND Colour grey white RAL 9002 Weight 1 5kg Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 267 250740 Fire Brigade Control Unit FBF900 1 D1 268 250741 Fire Brigade Control Unit FBF900 2 D1 260 265900 Fire Brigade Keysafe Adapter AD900 1 D1 169 BB072001 SAM 0720 01 0100 250608 268007 250709 169 BB072001 SAM 0720 01 0100 Chapter 28 Fire Brigade Control and Display Devices 46 212028 Housing 19 36HU GEH19 STAND 273 Mounting Frame 19 6HU RAHMEN FBF Mounting frame 19 6HU for accommodation of a Fire Brigade Control Unit FBF900 1 or FBF900 2 in a Fire Detection Control Panel Housing GEH19 14 GEH19 18 GEH19 40 1 or GEH19 STAND Specifications Colour grey white RAL 9002 Weight 1 5kg Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 267 250740 Fire Brigade Control Unit FBF900 1 D1 268 250741 Fire Brigade Control Unit FBF900 2 D1 46 212028 Housing 19 36HU GEH19 STAND Fire Brigade Map Box FWP 1 Metal wall mount box for safekeeping alarm plans for the fire brigade operation at the locati on of the fire detection control panel FEUERWEHRPL NE Specifications Dimensions W x H x D 350 x 400 x 110 mm Colour flame red RAL 3000 Weight 4 2kg Fire Brigade Map Box FPKCLR900 1 Document case for storage of approx 100 fire brigade alarm plans in DIN A4 and A3 format fir
472. oop voltage Current consumption approx 600uA quiescent Line termination 56kOhm Alarm threshold typ 22kOhm Ambient temperature 20 C to 60 C Dimensions L x W x H 93 x 94 x 23 mm Colour cream Weight 110g Approval VdS G202140 Jer ani 169 BBO72001 SAM 0720 01 0100 249102 249115 169 BB072001 SAM 0720 01 0100 Chapter 12 Analogue Detectors and Modules Series 200 500 97 Cross references Page Art Nr Name Type 117 249110 Base for Carrier Rail for M200 SS M200E DIN 116 249109 Base for Mounting Plate for M200 SS M200E PMB 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 117 249108 Surface Mounting Box for M200 SS M200SMB Module 2xSurv In 1xRel Out Anal 200 SS M221E Addressable module for the monitored integration of 2 contact detectors e g manual call points sprinkler system contacts supervising contacts as well as for the integration of a dry relay contact for triggering external devices via the bi directional communication on the ADM loop using System Sensor 200 protocol The integrated dual isolator can be activated or deactivated by choosing the appropriate terminals Features Separate status LED for each input and output See ee Surveillance of terminal connection lines for wire bre A akage and short circuit 2 decadic rotary switches for setting the address from 01 to 99 Ins
473. op is possible via optional modules Specifications Supply voltage 18 30VDC Current consumption at 24V 320 530mA quiescent max 660mA active Sensitivity 0 05 to 20 m Pipe length max 200m Monitored areas max 4 Number of aspiration holes max 100 depending on the design of the pipe network Outputs 12 relays function can be selected Ambient temperature 0 C to 39 C Protection class IP20 Dimensions W x H x D 350 x 225 x 125 mm Colour grey RAL 7012 Weight 4 6kg Approval VdS G298024 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT1 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 4 210210 Zone Extension Board ZEB2 1 1 eam and 169 BB0O72001 SAM 0720 01 0100 22 244111 244248 244112 244113 244114 244115 244116 244118 169 BB072001 SAM 0720 01 0100 Chapter 22 Accessories for Aspiration Smoke Detection Systems 221 Accessories for Aspiration Smoke Detection Systems Sensor Pipe PVC ROHR PVC The sensor pipe is made of grey PVC nominal width 20mm outer diameter
474. or Ambient temperature Dimensions L x W x H Colour Weight Approval VdS G201095 Cross references Page supplied through loop voltage 1 9mA quiescent max 32VDC max 1 A resistive or inductive load 10VDC 10kOhm 20 C to 70 C 150 x 90 x 48 mm white 240g Art Nr Name Type 26 32 35 214034 BCnet Sectional Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 249074 Control Module Anal XP95 Apo SMK 55000 849 Addressable compact module with integrated dual isolator used for the activation of external devices e g fire control acoustic and optical signalling devices via the bi directional communication on the ADM loop using Apollo Discovery protocol A dry chan geover contact can be used as actuation output Features Bm Switch for setting the physical address from 01 to gt tc J N Pes 126 ROA va Specifications Operating voltage supplied through loop voltage Current consumption 720uA quiescent Contact load 30VDC 1A resistive or inductive load Ambient temperature 20 C to 70 C Dimensions L x W x H 150 x 90 x 48 mm Colour white Weight 240g Approval VdS G201032 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 249075 Conventional Zone Module Anal XP95 Apo GWM 5500
475. or Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 Surface Mounting Kit SS SMK400 Supplement base in addition to detector bases B501 B501DG B401RM B524IEFT 1 B524FTXE B524HTR or B524RTE for surface mounting and insertion of installation tu bes or thick cables prepared for PG screw connections OR j i Specifications Dimensions x H 103 x 34 mm Colour cream Weight 90g Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 105 246008 Detector Base Conv 400 100 300 SS B40IRM 111 246012 Detector Base Filtrex Anal 500 SS B524FTXE 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 Recessed Mounting Kit SS RMK400 Mounting accessory for detector bases of type B501 B501DG B401RM B524IEFT 1 B524HTR or B524RTE for flush mounting in false ceilings Specifications Dimensions x H 144 x 40 mm Colour cream Weight 90g Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 105 246008 Detector Base Conv 400 100 300 SS B40IRM 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS
476. or RF complete 2100RFT AS 189 Optical Thermal CO IR Detector Anal 200 SS 2251CTLB pop db db AO 93 P Parameter Setup Software PARSOFT 2 295 Pipe Connector 25 RKL25 cece eee eee ee ee Pipe Fitting ADA MUFFE see cere ee ee Pipe Fitting BOW45 WINKEL 45 Pipe Fitting BOW90L BOGEN 90 2 221 Pipe Fitting BOW90S WINKEL 90 2 221 Pipe Fitting CAP KAPPE 0 cece eee eee 222 Pipe Fitting T45 T STUCK 45 errrararvrnrnnrvvnnr 221 Pipe Fitting T90 T STUCK 90 000 00ce eee 221 Plastic Clip for Aspiration Hole Reduction Foil DF KC AREDF TK sei isesmetdetmetmedne de den ots eta Kle 223 Plug in Power Supply STN805 1 002 0020 285 Power Supply 24V 1Amp Stabilized NG1 1S 290 Power Supply 24V 2Amp Stabilized NG2 1S 290 Power Supply 24V 3A MT3400L 0020 289 Power Supply 24V 4Amp Stabilized NG4 1S 290 Power Supply Housing NTG24 1 0205 292 Power Supply Housing NTG24 1 CE 293 Power Supply Housing NTG24 2 0205 293 Power Supply Module NTM2402 1 02005 291 Power Supply Module NTM2408 1 0 055 292 Power Supply Unit for Detector Heater MH TRI 119 Power Supply for FSK Heating NT700 1 260 Printer Cable for DPU414 1 8m 9POL D SUB VERL 66 Printer Cable for LX300 3m 25POL D SUB VERL 67 Progr
477. or rate of rise heat detection is decided in the fire detection control panel by means of appropriate programming Features Permanent evaluation of environmental conditions Continuous transmission of the current measured value to the fire detection control panel Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Output for external remote indicator Mechanical theft protection gt Specifications Operating voltage supplied through loop voltage Ex classification EEx ia IIC T5 Current consumption typ 300uA quiescent Ambient temperature 20 C to 40 C class T5 20 C to 60 C class T4 no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 100g Approval EECS ATEX 0073 LPCB 010p Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 179 246027 IS Detector Base Anal Apo ASEX 45681 215 35 214021 Loop Interface LIF64 1 180 228005 Protocol Interface Anal XP95 Apo API 55000 855 180 228004 Safety Barrier Anal XP95 Apo AES 29600 098 IS Detector Base Anal Apo ASEX 45681 215 Detector base used in hazardous areas for a Series XP95 intrinsically safe analogue smoke detector suitable for indoor surface mounting Features 22 me Co
478. ounting Box for Multimodule SS M200 SMB MM Powder coated sheet steel mounting box for System Sensor Multi Modules IM 10 or CR 6 On both long sides 7 knock outs 19mm for PG screw connections are available Specifications Dimensions L x W x H 285 x 225 x 62 mm Colour cream Weight 2kg Cross references Page Art Nr Name Type 99 249116 Control Module 6xRel Out Anal 200 SS CR 6 97 249115 Monitor Module 10xSurv In Anal 200 SS IM 10 Surface Mounting Box for M500 SS SMB500 The plastic mounting box is designed for the surface mounting of a module Series 500 Specifications Dimensions W x H x D 125 x 124 x 55 mm Colour cream Weight 155g Cross references Page Art Nr Name Type 100 249045 Conventional Zone Module Anal 500 SS M512ME 182 228007 Protocol Interface Anal 200 SS IST200 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 119 249014 Power Supply Unit for Detector Heater MH TR1 The power supply unit serves for generating the heating voltage for the detector heaters MH500 1 MH60 1 and MH95 1 Features Power supply for up to ten detector heaters Optical indication for operation and fault Surveilled heating voltage malfunction can be forwarded to the fire detection control panel as fault message Wall mount cabinet for surface mounting Specifications Mains voltage 230VAC 10 15 50Hz Power consumption 200VA Heating voltage 4
479. out display and operating field It is mounted on a sheet steel carrier and designed for use in a Control Panel Rack 8HU RACK216 1E The slide in unit is prepared for a maximum of 2 function modules Conventional Detector Inter face GIF8 1 or Loop Interface LIF64 1 a Fire Brigade Interface FWI2 1 a Fire Brigade Inter face Additional Board FWZ2 1 and an Interface Adapter Module IAM216 1E By connecting a Display and Operating Front Panel ABP216 1E to the Fire Detection Con trol Panel Module BCM216 3E the BCnet Sectional Control Panel can be operated directly The extensive functions and features are summarised in the description of the Fire Detection Control Panel BCnet216 No 2199998 Specifications Supply voltage 21 to 30VDC Current consumption at 24V typ 80mA without optional componentries Ambient temperature 5 C to 50 C Dimensions W x H x D 233 x 355 x 42 mm Weight approx 0 9kg Approvals FT 14 147 3 99 Austria VdS G201017 Cross references Page Art Nr Name Type 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 42 214230 Control Panel Rack 8SHU RACK216 1E 50 223009 Control Zone Module SLM1 2 35 214020 Conventional Detector Interface GIF8 1 33 214208 Display and Operating Front Panel ABP216 1E INT1 58 218023 ESPA 4 4 4 Interface License ESPA SS 47 218024 Extinguishing Control 8 Area License LC216 8LB 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2
480. p using Apollo Discovery protocol The manual call point is tested in accordance with the standards EN 54 11 B and EN 54 17 sn Features L SCHANLAGE Robust aluminium die cast housing with a door aperture angle of more than 180 Function marking LOSCHANLAGE replaceable Integrated dual isolator Reverse polarity protection Built in microcontroller sr r Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Button in combination with LED for setting the physical address Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual Call Point HFM HM ZS IP54 Scheibe einschlagen Knopf tief dr cken 96 Specifications Operating voltage supplied through loop voltage Current consumption 180uA quiescent Ambient temperature 20 C to 60 C continuous operation 25 C to 70 C max 12 hours Protection class IP43 Dimensions W x H x D 125 x 125 x 34 mm Colour rape yellow RAL 1021 Weight 400g Approval VdS G204003 VdS G206127 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 168 249636 Protective Cover V2A for Manual Call Point Yellow
481. pacity 2 frequency ranges 434MHz and 868MHz 24 bi directional data channels Unique code made up out of several million options Channels are checked for availability Room for 3 6V lithium battery Surveilled battery voltage Approx 1 5 years life span of lithium battery Sabotage message when door is open Specifications Operating voltage Battery life span Ambient temperature Dimensions W x H x D Colour Approval Cross references Page 3 6V Lithium battery approx 1 5 years 0 C to 60 C 125 x 125 x 37 mm flame red RAL 3000 191 184 VdS G204014 Art Nr Name Type 310021 Lithium Battery 3 6V 2 2Ah 249201 RF Interface 4Rel FUIF511 27D Manual Call Point Blue RF HM 152 27D Radio linked manual call point according to EN 54 11 B in elegant blue plastic housing with integrated antenna The manual call point is delivered with battery HAUSALARM o Room for 3 6V block battery Surveilled battery voltage HK I Specifications Operating voltage Battery life span Features Function marking HAUSALARM Optical activation indication by means of LED Latching push button Easy to replace standardised glass plate Continuous status messages High transmission capacity 2 frequency ranges 434MHz and 868MHz 24 bi directional data channels Unique code made up out of several million options Channels are checked for availability Approx 1
482. pared to conventionally designed fire detection control panels The control panel can easily be adapted to any required system size and provides literally unlimited possi bilities also for future extensions Thanks to its wide range of possible logic combinations for alarming and transmitting devices as well as for actuations the control panel can realise even extensive and complex alarming and control tasks in the fire alarm technology It complies with all requirements of the Euro pean Standards EN 54 2 and EN 54 4 including all options for the highest safety demands The Global Security System network GSSnet allows for the communication of overall 127 GSSnet members which together provide the possibility to connect 254 ADM loops using System Sensor 200 or Apollo Discovery protocol or 2032 detector zones in addressable conventional technology 9700 actuations e g fire controls or extinguishing system controls 99 transmitting devices e g to the fire brigade e 999 alarming devices e g zones of acoustic or optical signalling devices 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 21 The applied network technology warrants top failure safety in case of a fault of the network line and exceeds the redundancy requireme
483. parts shall become the property of Seller If an article is manufactured by Seller on the basis of design data design drawings models or other specifications supplied by Buyer Seller s warranty shall be re stricted to non compliance with Buyers specifications Seller s warranty obligation shall not extend to any defects due to assembly and in stallation work not undertaken by Seller inadequate equipment or due to non com pliance with installation requirements and operating conditions overloading of parts in excess of the design values stipulated by Seller negligent or faulty handling or the use of inappropriate materials nor for defects attributable to material supplied by Buyer Nor shall Seller be liable for damage due to acts of third parties at mospheric discharges Excess voltage and chemical influences The warranty does not cover the replacement of parts subject to natural wear and tear Seller accepts no warranty for the sale of used goods The warranty shall lapse immediately if without written consent of Seller Buyer himself or a third party not expressly authorised undertakes modifications or repairs on any items delivered Claims acc to 933b ABGB are struck by the statute of limitation with lapse of the period mentioned under point 8 2 The provisions of sub paragraphs 8 1 to 8 7 shall apply mutatis mutandis to all ca ses where the obligation to repair defects has to be accepted for other reasons laid down by la
484. parture from the terms and conditions mentioned in 1 1 above shall be valid only if expressly accepted in writing by Seller Submission of offers Seller s offers shall be deemed offers without engagement Tender documents and project documentation must not be duplicated nor made available to third parties without the permission of Seller They may be claimed back at any time and shall be returned to Seller immediately if the order is placed elsewhere Conclusion of contract The contract shall be deemed concluded upon written confirmation by Seller of an order received or upon dispatch of a delivery Particulars appearing in catalog folders etc as well as any oral or written statements shall only be binding if Seller makes express reference to them in the confirmation of the order Subsequent amendments of or additions to the contract shall be subject to written confirmation Prices Prices shall be quoted ex works or ex Seller s warehouse without VAT packing and packaging loading disassembly take back and proper recycling and disposal of waste electrical and electronic equipment for commercial purposes as defined by the Ordinance Regulating the Handling of Waste Electrical Equipment Buyer shall be liable for any and all charges taxes or other duties levied in respect of delivery If the terms of delivery include transport to a destination designated by Buyer trans port costs as well as the cost of any transport insurance desired
485. perating voltage supplied through detector line voltage Alarm current at 24VDC max 100mA Alarm temperature typ 100 C Protection class IP67 Dimensions L x W x H 110 x 90 x 54 mm Colour white Weight 250g Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PAS8 1 4 210210 Zone Extension Board ZEB2 1 194 Chapter 20 Special Detectors Thermal Max Detector IP67 Conv SWM 1KL 140 The maximum heat detector SWM 1KL 140 uses a bimetal element as thermal sensor If the alarm temperature is reached the bimetal contact is closed Addressable conventional techno logy is used for alarm transmission to the fire detection control panel The detector can be connected to an ADM loop by using a conventional zone module The detector is integrated in an aluminium die cast housing that is suitable for application in moist areas e g loading ramps Individual detector addressing by connecting an optional ad dress module Metal PG sc
486. perating voltage supplied through loop voltage Current consumption approx 1 5mA quiescent Switching power per contact 2A 30VDC Ambient temperature 0 C to 50 C Dimensions L x W x H 172 x 147 x 25 mm Weight 500g JET av E 100 Chapter 12 Analogue Detectors and Modules Series 200 500 249045 249104 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 118 249117 Surface Mounting Box for Multimodule SS M200 SMB MM Conventional Zone Module Anal 500 SS M512ME Addressable module for the integration of conventional detectors detectors for intrinsically safe areas and flame detectors into an ADM loop using System Sensor 200 protocol The ad dress is set in a straightforward manner by means of two decadic rotary switches located on the module itself The conventional zone module provides a Ss reset output for resetting special detectors For the moun OG ting of the module a Surface Mounting Box for M500 SS bi See an SMB500 is required t PE 4 ae Specifications Operating voltage 18 to 32VDC Quiescent current cons on loop 300uA Line termination 3 9kOhm Ambient temperature 10 C to 60 C Dimensions L x W x H 70 x 70 x 32 mm Weight 142g Approval VdS G297009 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214
487. possible prepared for optional PG screw connections Additional terminal on base floor Suitable for indoor and outdoor mounting Specifications Ambient temperature 30 C to 70 C Protection class IP54 Dimensions W x H x D 120 x 90 x 35 mm Colour red Weight 70g Cross references Page Art Nr Name Type 229 355101 Sounder WM 12 24V Red Multitone 103dB EMA1224B4R Base for Sounder amp Strobe IP66 Red EMA ESBRS The base ESBRS for surface mounting of Series EMA sounders and strobes suitable for flush mount or surface mount cabling 252 Chapter 26 Accessories for Optical and Acoustic Devices 359005 359006 359020 Features All side cable entry possible Additional terminal on base floor Suitable for indoor and outdoor mounting Specifications Ambient temperature 30 C to 70 C Protection class IP66 Dimensions W x H x D 120 x 90 x 36 mm Colour red Weight 72g Cross references Page Art Nr Name Type 229 355101 Sounder WM 12 24V Red Multitone 103dB EMA1224B4R Lid for Sounder DBS Red DBSLIDR The red cover plate DBSLIDR is used for mounting a sounder Series DBS without detector base Specifications Dimensions x H 103 x 2 mm Colour flame red RAL 3000 Cross references Page Art Nr Name Type 229 355102 Sounder FB 12 24V White Multitone DBS 1224B4W Lid for Sounder DBS White DBSLIDW The white cover plate DBSLIDW is used for mounting a sounder Series DBS
488. pproval FT 14 147 3 99 Austria VdS G201017 Fire Detection Control Panel BC216 1 D1 The Fire Detection Control Panel BC216 1 D1 is a modularly designed compact control pa nel in the version for Germany for small and medium size fire detection systems Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language Approval VdS G201017 Fire Detection Control Panel BC216 1 B1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in French language Approval ANPI BFS DE 1096 2003 03 20 Fire Detection Control Panel BC216 1 CZ1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Czech language Using the optional interface Serial Interface Module SIM216 1 the connection to the Ra dom transmitting system can be realised Approval EZU 7 105034 00 00 169 BB072001 SAM 0720 01 0100 214007 214009 214017 214049 214080 214084 214086 214088 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 15 Fire Detection Control Panel BC
489. preventing false alarms 169 BB072001 SAM 0720 01 0100 241027 169 BB072001 SAM 0720 01 0100 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 139 What is more the response sensitivity of the detector can be adjusted via the fire detection control panel to adapt the detector optimally to the application environment Features Permanent evaluation of environmental conditions Constant sensitivity Response sensitivity can be set in 5 steps via the Fire Detection Control Panel Series BC216 Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Display of activated condition via 2 LED indicators that are visible from all angles Output for external remote indicator Mechanical theft protection Insect screen OO Specifications Operating voltage supplied through loop voltage Current consumption typ 500uA quiescent Ambient temperature 20 C to 60 C no condensation or icing Relative humidity 0 to 95 no condensation Radioactive compound Am241 0 9uCi 33 3kBq Dimensions x H 100 x 42 mm Colour white Weight 105g Approval VdS G200073 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 4568 1 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 456
490. pter 3 Fire Detection Control Panels Series BC216 214000 214610 214006 214015 Cross references Page Art Nr Name Type 40 214003 Auxiliary Case for BC216 GEH216 4 50 223009 Control Zone Module SLM 1 2 35 214020 Conventional Detector Interface GIF8 1 45 214601 Cover IP54 for BC216 GEH IP54 BC 1 D1 58 218023 ESPA 4 4 4 Interface License ESPA SS 47 218024 Extinguishing Control 8 Area License LC216 8LB 37 214023 Fire Brigade Interface Additional Board FWZ2 1 36 214022 Fire Brigade Interface FWI2 1 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 35 214021 Loop Interface LIF64 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Module SZ58 3 287 310002 Stand by Battery 12V 18Ah 58 218022 ZLT Interface License ZLT SS Fire Detection Control Panel BC216 1 A1 The Fire Detection Control Panel BC216 1 A1 is a modularly designed compact control pa nel in the version for Austria for small and medium size fire detection systems Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language A
491. ption max 7mA active Contact rating 1A at 30VDC Ambient temperature 40 C to 70 C Relative humidity 0 to 98 no condensation Dimensions x H 100 x 24 mm Colour white Weight 80g Cross references Page Art Nr Name Type 153 246030 Backplate Apo SZPL 45681 233 153 246029 Conduit Box Apo SZA 4568 1 204 120 249044 Detector Mounting Bracket MMW 1 1 169 BB072001 SAM 0720 01 0100 246025 246036 169 BB072001 SAM 0720 01 0100 Chapter 16 Acessories for Series 65 ORBIS XP95 DISCOVERY 151 130 241061 Optical Thermal Detector Conv ORBIS Apo OH 13001 129 241060 Optical Smoke Detector Conv ORBIS Apo OP 12001 121 249640 Protective Cage BWS 1 D1 132 242031 Thermal Max Detector Conv ORBIS Apo HT 11002 133 242033 Thermal Max Detector Conv ORBIS Apo HT 11004 134 242035 Thermal Max Detector Conv ORBIS Apo HT 11006 131 242030 Thermal ROR Detector Conv ORBIS Apo HT 11001 132 242032 Thermal ROR Detector Conv ORBIS Apo HT 11003 134 242034 Thermal ROR Detector Conv ORBIS Apo HT 11005 121 249635 Trapezoid Steel Bracket TBH800 1 Detector Base Anal Apo ASA 45681 210 Mounting base used for automatic fire detectors Series XP95 and Discovery with pro grammable address card suitable for indoor surface mounting rim JP ANE A Features Connection to ADM loop using Apollo Discovery protocol Easy detector addressing through address card in mounting base No electronics contained Multi useab
492. ption or a short circuit in one of the two loops causes a fault message in the evaluation unit The black sensing cable with nylon coating has a high resistance against chemical and biolo gical agents Therefore it is applied in areas where acidic alkaline or solvent fumes can oc cur In addition the cable is UV resistant and therefore suitable for outdoor application Features Length of sensing cable up to 300m Detection of exceeding temperatures at any point of the sensing cable Resistant against chemical and biological agents Suitable for outdoor application Easy to install Specifications Outer diameter 4 8mm Wire gauge 0 46mm Temperature resistance up to 100 C unlimited up to 150 C 350 hours up to 1759C 25 hours 204 Chapter 20 Special Detectors 244624 244638 244639 Cross references Page Art Nr Name Type 202 244637 Linear Heat Detection Unit Alarmline Conv LWM 1 Sensing Cable Stainless Steel LWM SK11800013 The Alarmline sensing cable with a stainless steel meshwork consists of four copper wires each of them being coated with a colour coded material with a negative temperature coeffi cient The wires are twisted and isolated with an outer layer made of temperature resistant and fire retardant plastic On one side of the cable the four wires are connected to an evalua tion unit or a junction box On the other side they are connected with each other and are her metically sealed
493. r Multi useable terminals with secure screw fitting Specifications Ambient temperature 10 C to 60 C Relative humidity 0 to 95 no condensation Dimensions x H 102 x 35 mm Colour cream 112 Chapter 13 Acessories for Series 300 ECO1000 200 500 246113 246111 Weight 91g Cross references Page Art Nr Name Type 94 241019 Optical Filtrex Smoke Detector Anal 500 SS FTX P1 121 249640 Protective Cage BWS 1 D1 121 249635 Trapezoid Steel Bracket TBH800 1 Zonal Display Unit Conv 300 SS S300ZDU The Zonal Display Unit S300ZDU allows for the numerical display of the activated detectors addresses on a conventional detector line built from Series 300 fire detectors If more than one detector is in the alarm state the addresses are automatically scrolled In addition the zo nal display unit detects and displays wiring errors between control panel and zonal display unit as well Vs as short circuits in the detector line Features Multiple alarm display 4 digit display Remote installation always before the first detector Specifications Operating voltage supplied through detector line voltage Current consumption typ 1004 A own consumption without detector Ambient temperature 10 C to 50 C Relative humidity 5 to 95 no condensation Dimensions W x H x D 137 x 132 x 40 mm Colour cream Weight 170g Cross references Page Art Nr Name Type 82 241041 Optical Thermal Detector Conv 300
494. r Housing Conv 400 SS DH400P and Duct Detector Housing Anal 500 200 SS DH500 applicable for ventilation ducts with a depth of 2 4 to 3 7m Cross references Page Art Nr Name Type 122 244009 Duct Detector 400 OM DH400P 123 244008 Duct Detector Housing Anal 500 200 SS DH500 Replacement Filter for Filtrex RF FTX Replacement filter for the easy replacement of a contaminated filter of an Optical Filtrex Smoke Detector Anal 500 SS 444 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 125 Specifications Dimensions x H 80 x 19 mm Colour cream Weight 10g Cross references Page Art Nr Name Type 94 241019 Optical Filtrex Smoke Detector Anal 500 SS FTX P1 169 BB072001 SAM 0720 01 0100 126 Chapter 14 Conventional Detectors Series 65 ORBIS 1 4 Conventional Detectors Series 65 ORBIS 240027 lonisation Smoke Detector Conv 65 Apo Gl 55000 217 Smoke detector operating on the ionisation principle in addressable conventional technology consisting of a sensing and reference chamber dual chamber principle for automatic com pensation of environmental influences and of extra flat design suitable for indoor mounting Features p Sealed electronics prevents false alarms caused by the i environment i i Individual detector addressing by installing an optional ad pate dress module NG60 1 Output for external remote indicator Mechanical t
495. r 15 Analogue Detectors and Modules Series XP95 DISCOVERY 249077 Specifications Operating voltage Current consumption Contact rating Line termination Alarm threshold Ambient temperature Dimensions L x W x H The module provides a monitored input and a relay output with two dry contacts Furthermore an external voltage can be monitored via an opto coupled input The unit in cludes an integrated dual isolator it is integrated into a plastic housing Features Separate status LED for each input and output Surveillance of terminal connecting lines for wire bre akage and short circuit DIL switch for setting the physical address between 01 and 126 supplied through loop voltage approx 1 5mA quiescent 1A 30VDC or AC 20kOhm typ 4 7kOhm 20 C to 70 C 150 x 90 x 48 mm white 240g VdS G201032 Art Nr Name Type Colour Weight Approval Cross references Page 26 32 35 214034 BCnet Sectional Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop Interface LIF64 1 Module 3xSurv In 3xRel Out Apo 55000 588 Addressable module for the line monitored integration of 3 contact detectors e g manual call points sprinkler system contacts supervising contacts as well as 3 dry relay contacts for triggering external devices via the bi directional communication on the ADM loop using Specifications Operating voltage Current consumption Contact
496. r Cable Black SKM SK SCHWARZ 206 244633 Standard Sensor Cable Red SKM SK ROT Sensor Cable Monitoring System Conv SKM 03 Linear heat detection system according to EN 54 5 class C max room height 6m for the secure detection of maximum temperature exceedances over the entire length of the sensor cable Connection via dry relay contacts to a conventional detector line or in modern ring bus technology via appropriate modules with external power supply fp SENSORKABELMELDER Features Sensor cables up to 300m length can be connected o Detection of exceeding temperatures at any point of the sen sing cable Easy to maintain system Separate alarm and fault indication Alarm indication according to DIN 14623 Easy commissioning Il 9 Specifications Operating voltage 16 to 28VDC Current consumption at 24VDC 28mA quiescent 58mA alarm Ambient temperature 25 C to 50 C Protection class IP65 Dimensions W x H xD 105 x 105 x 65 mm Material polycarbonate Colour grey white RAL 9002 Weight 300g Approval VdS G203076 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Dete
497. r Magnetic Lock Clamp 2498 Magnetic Lock Clamp LED 4900N 1392 Magnetic lock clamp with extra high magnetic force and function indication for locking doors emergency exits access control systems etc during normal operation The lock is re leased through an optional Control Device For Magnetic Lock Clamps 2498 Suitable for sur face mounting in dry rooms Complete with counter plate and mounting accessories Specifications Operating voltage 24VDC Current consumption at 24V 250mA Adhesive force approx 4900N 490kg Working temperature 5 C to 50 C Dimensions L x W x D 270 x 67 x 41 mm Weight 4 2kg Cross references Page Art Nr Name Type 275 260002 Control Device for Magnetic Lock Clamp 2498 Magnetic Lock Clamp 2750N 1388 Magnetic lock clamp with extra high magnetic force for interlocking of doors emergency exits access control systems etc during normal operation The lock is released through an optional Control Device For Magne tic Lock Clamp 2498 Suitable for surface mounting in dry rooms Complete with counter plate and mounting accessories Specifications Operating voltage 24VDC Current consumption at 24V 250mA Adhesive force approx 2750N 275kg Working temperature 5 C to 50 C JET av E 280 Chapter 29 Fire Controls Dimensions L x W x D 268 x 48 x 25 mm Weight 2kg Cross references Page Art Nr Name Type 275 260002 Control Device for Magnetic Lock Clamp 2498 169 BB072
498. r any damage and other financial disadvantages incurred by Seller due to Buyer s failure to meet or ful ly meet his financing commitment or any other obligations according to Article 10 The Buyer shall bear the burden of proof of performance of this obligation Seller s liability Outside the scope of the Product Liability Act Seller shall be liable only if the da mage in question is proved to be due to intentional acts or acts of gross negligence within the limits of statutory provisions Seller shall not be liable for damage due to acts of ordinary negligence nor for consequential damages or damages for economic losses loss of savings or interest or damage resulting from third party claims against buyer 10 2 Seller shall not be liable for damages in case of non compliance with instructions 10 3 12 13 13 1 for assembly commissioning and operation such as are contained in instructions for use or non compliance with licensing requirements Claims that exceed the contractual penalties that were agreed on are excluded from the respective title Assertion of Claims All claims to which Buyer is entitled must be asserted in court within three years from passage of risk as specified under paragraph 6 unless shorter limits of time are prescribed by law otherwise claims shall become forfeited Industrial property rights and copyrights Buyer shall indemnify Seller and hold him harmless against any claims for any in fringement o
499. r manual delay of the extinguishing process Input for fault detectors e g for monitoring the weight and or pressure of the extinguis hing agent A monitored and permanently short circuit protected extinguishing output max 1 A A monitored short circuit proof output signalling the activated condition max 0 5A A monitored short circuit proof output signalling the released condition max 0 5A 8 open collector outputs providing the conditions of the extinguishing module if further control tasks are required All inputs and the three monitored outputs are available on screw terminals the open col lector outputs are available on a flat cable connector Specifications Current consumption at 24V quiescent typ 13mA in and outputs terminated with 5 6kOhm extinguishing output terminated with 560hm Extinguishing output max continuous current 1A Output activated condition max continuous current 0 5A Output released condition max continuous current 0 5A Ambient temperature 5 C to 50 C Dimensions L x W x H 103 x 58 x 15 mm Weight 50g Approval tested to EN 12094 1 by VdS Cross references Page Art Nr Name Type 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 Extinguishing System Interface LSS1000 1 Componentry used for the reactionless connection of an extinguishing system to a fire de tection control panel The componentry can
500. r selection and operation LC display Automatic switching on off Beep option to initiate action HK I 169 BB072001 SAM 0720 01 0100 Chapter 33 Tools 299 Red LED indicator lights up if a detector subjected to a test changes into the alarm condition Cross references Page Art Nr Name Type 126 241026 Optical Smoke Detector Conv 65 Apo GO 55000 317 Smoke Sticks 10pcs RE2 Smoke sticks for test activation of optical smoke detectors 249023 169 BB072001 SAM 0720 01 0100 300 Chapter 34 Miscellaneous 34 Miscellaneous 229005 229004 229006 180001 E O L Resistor 100pcs 5 6K 0 33W 100 resistors per packing unit suitable as line terminator end of line resistor of a detector line in conventional technology of Fire Detection Control Panels Series BC216 BCO16 and BC06 Resistor 100pcs 1K 0 33W 100 resistors per packing unit to be used with contact detectors in conventional technology e g manual call points Resistors limit the line current of the detector line during alarm acti vation of the contact detector and serve to distinguish between a short circuit and an alarm Diode 100pcs 1N4004 100 diodes per packing unit suitable as blocking diode in case of negative monitoring volta ges e g Control Zone Module SLM1 2 Siren Connection Module SZ58 2 and SZ58 3 or as recovery diode for inductive loads Banknote Contact 12V 24V GK1224 Banknote contacts are semi auto
501. r tools using the keypad of the integrated display and operating field of the control panel or by means of a commercial ly available PC keyboard Most important features Micro processor technology with diverse redundant processing logic Administration of up to 144 detector zones for manual call points automatic fire detectors with of without alarm verification technical messages and fault detectors with or without self resetting property Administration of 10 transmitting devices 99 alarming devices 128 actuations and 199 sectors Easy control panel operation thanks to freely parameterisable sectors INFO field with a 4 line by 20 character backlit text display providing information about all current events in English Info button for additional information on the current events Event memory with quick search filter displays the latest 500 events in chronological order Display of activation fault disablement alarm delay call fire brigade and confirmation of the transmitting device to the fire brigade Monitored output for the connection of external signalling devices with display of activati on fault or disablement Dry contact outputs for summary alarm and summary fault 16 open collector outputs which can be freely parameterised as transmitting devices alar ming devices actuations or other output functions and or combinations for the activation of actuations transmitting devices or alarming devices depending on
502. ram and Test Unit S300RPTU Furthermore the S300RPTU is used to adjust the re sponse sensitivity to the local requirements Features Individual detector addressing via Address Module NG58 1 or Remote Program and Test Unit S300RPTU Response sensitivity can be set to 3 levels low medium high Functionality check by means of test activation with Remote Program and Test Unit S300RPTU or Remote Test Unit ECO1000RTU Detector status degree of contamination detector address response sensitivity as well as date of latest maintenance can be scanned and edited via Remote Program and Test Unit S300RPTU Output for external remote indicator Mechanical theft protection Insect screen Specifications Operating voltage Current consumption Alarm temperature Operating temperature Ambient temperature supplied through detector line voltage typ 85uA quiescent 58 C maximum heat component max 45 C 30 C to 70 C Relative humidity 5 to 95 no condensation Dimensions x H 102 x 43 mm Colour cream Weight 75g Approval VdS G202018 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 105 246008 Detector Base Conv 400 100 300 SS B401RM 105 246100 Detector Relay Base Conv 300 SS B324RL 8 210110 Detector Zone Extension MGE8 1 169 BB072001 SAM 0720 01 0100 242040 169 BB072001 SAM 0720 01 0100 Chapter 11 Conven
503. rared beam emitted from the transmitter receiver unit is reflected by a reflector mirror For easy functional testing the detector can be remotely activated during maintenance by the fire detection control panel This test simulates a light obscuration by means of an integrated test filter The test unit requires its own external voltage supply it cannot be supplied by the loop ae p the light beam The Beam Smoke Detector 6500S can be con nected directly to the ADM loop with System Sensor 200 protocol without external power supply except for powering the test unit Alarm evaluation is achieved by detection of a reduced intensity of Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept con stant for a long time thus constituting an effective measure for preventing false alarms The response sensitivity of the detector can be set to 6 different levels Four levels show a fi xed alarm threshold 2 other levels provide an adaption of the detector to changing ambient conditions by means of a variable alarm threshold The detector is delivered with a reflector which can be used for ranges from 5 to 70m A three part accessory is available to extend the range of the detector from 70 to 100m Features Detection of clear and dark smoke Sender and receiver integrated in a single housing Sealed det
504. rcuit knop tief dr cken r Plenty of space for cabling Features Robust aluminium die cast housing with an door aperture angle of more than 180 Inscription field RAUCHABZUG exchangeable Integrated dual isolator Reverse polarity protection Integrated microcontroller Optical indication of activation by LED indicator Latching push button Standardised glass pane easy to replace Setting of physical address with button in combination with LED indicator Increase of protection class to IP54 via optional Protection Kit for Manual Call Points HFM HM ZS IP54 Specifications Operating voltage Current consumption Ambient temperature Protection class Dimensions W x H xD supplied through loop voltage 300uA quiescent 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm Colour light grey RAL 7035 Weight 400g Approval VdS G202035 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 169 2171612 Replacement Glass for Manual Call Point ET SCH HFM 170 249024 Special Designation for Manual Call Point HM BESCH 169 BB072001 SAM 0720 01 0100 164 Chapter 17 Manual Cal
505. re pleased to be of personal assistance to you We can assure you that customer service is of highest value for LST We will do whatever possible to complete your inquiries and your orders as fast as possible and to your convenience We would be pleased to count also you among our ever expanding number of customers LABOR STRAUSS Sicherungsanlagenbau Ges m b H Head Office Vienna A 1231 Vienna Wiegelestrasse 36 Tel 43 1 52114 0 Fax 43 1 52114 27 E mail OFFICE LST AT Homepage WWW LST AT 310 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 General Terms Of Delivery 311 General Terms Of Delivery General Terms of Delivry issued by the Austrian Electrical and Electronics Industry Association 1 2 2 1 2 2 3 2 3 3 42 4 3 4 4 45 5 2 5 3 Scope These General Terms shall govern legal transactions between business enterprises namely the delivery of commodities and mutatis mutandis the rendering of servi ces Software transactions are with precedence governed by the Software Conditions issued by the Austrian Electrical and Electronics Industry Association assembly work by the Terms and Conditions for Assembly Work issued by the Austrian Po wer Current and Light Current Engineering Industry and or where applicable the Terms and Conditions for the Assembly of Electrical Equipment used in Medicine issued by the Austrian Electrical and Electronics Industry Any de
506. re Brigade Map Box FPKCLR900 1 D1 DOM CLI lock or FPKPHZR900 1 D1 lock for half cylinders to a compact unit Features Integrated Fire Brigade Display Panel FAT900 2 D1 Integrated Fire Brigade Control Unit FBF900 1 D1 Lock for half cylinders Specifications Operating voltage 10 30VDC Current consumption at 24V 50mA quiescent 150mA alarm Ambient temperature 0 C to 50 C Dimensions W x H x D 230 x 360 x 95 mm Colour flame red RAL 3000 Weight 3 7kg Approvals VdS G200079 VdS G205090 Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 9 210111 Fire Brigade Interface FW1016 1 36 214022 Fire Brigade Interface FWI2 1 273 250709 Fire Brigade Map Box FPKCLR900 1 274 250713 Fire Brigade Map Box FPKPHZR900 1 12 214008 Fire Detection Control Panel BC216 1 INT1 27 214108 Fire Detection Control Panel BC216 1CE INT1 16 214308 Fire Detection Control Panel BC216 1S INT1 270 250901 Redundant Transmission Adapter ADFAT900 2 D 1 9 210112 Serial Interface Module SIM016 3 250606 Mounting Frame 19 6HU RAHMEN Mounting frame 19 6HU for accommodation of a Fire Brigade Control Unit FBF900 1 or GEH1 GEH1 Specifications FBF900 2 and one Fire Brigade Key Safe Adapter AD900 1 in a Fire Detection C
507. re fully operable ADM alarm threshold tracing for every single smoke detector on the ADM loop accor ding to its individual contamination The sensitivity of every smoke detector is thus held constant over a very long period of time and deceptive alarms are avoided ADM alarm logic analyses the measured values above alarm threshold comparison of fire patterns to increase immunity against deceptive alarms ADM multi alarm logic increases the effect of the standard alarm logic by making use of the broad variety of freely parameterisable 2 detector or multi detector interdependencies ADM individual detector identification by assigning each physical address of an ele ment on the ADM loop a logical address that consists in a zone number and element number 2 line ADM detector text can be assigned to every logical address on the ADM loop Individual ADM detector disablement for every single element on the ADM loop or for predefined groups of elements ADM maintenance prognosis by means of processor aided interpolation of data concer ning the trend of contamination for every single smoke detector on the ADM loop This way it is possible to predict the next maintenance date with a high degree of probability which in turn results in major cost savings in maintenance during the lifetime of the fire detection system ADM detector test checks the alarming capability of every ADM detector from the fire detection control panel 169 BB072001 SAM 0
508. rective or freely setable One man maintenance function Non resetable electronic event counter Two integrated serial interfaces Integrated INFO bus for the connection of a fire brigade control unit and intelligent remo te indication unit Connection of a serial protocol printer via an optional data interface At first commissioning the control panel recognises all componentries and loop elements by means of AUTO setup 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 17 Use of unshielded 2 wire detector cabling Control panel case provides space for accommodating 2 x 12V 22Ah stand by batteries Additional features and functions in analogue ADM technology ADM loop serves 198 elements 99 detectors and 99 modules with protocol System Sensor 200 or 126 elements detectors and or modules with Apollo Discovery protocol An ADM loop and can be divided in up to 128 detector zones ADM loop wiring can be installed in form of a ring branch or an arbitrary combination of sectional rings and branches ADM communication by bi directional data exchange between the fire detection control panel and every single element on the ADM loop ADM failure strategy guarantees full function of all elements connected to the loop in case of wire breakage At short circuit the installed isolator modules protect devices not affected by the short circuit from failure ADM
509. rew for waterproof insertion of the connecting supply through the detector line voltage max 100mA 140 C IP67 110 x 90 x 54 mm white 250g Art Nr Name Type 249028 Address Module Conv Apo NG60 1 249020 Address Module Conv NG58 1 214020 Conventional Detector Interface GIF8 1 249104 Conventional Zone Module Anal 200 SS M210E CZ 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 210110 Detector Zone Extension MGE8 1 210122 Fire and Evacuation Panel BC016 2 INT 1 210102 Fire Detection Control Panel BC016 1 INT1 210205 Fire Detection Control Panel BC06 1 INT1 210209 Fire Detection Control Panel BC06 2 INT 1 210210 Zone Extension Board ZEB2 1 242014 Features EN s iid cables Specifications Operating voltage Alarm current at 24V DC Alarm temperature Protection class Dimensions L x W x H Colour Weight Cross references Page 155 119 35 100 146 8 7 6 1 3 4 243002 Flame Detector UV Conv NFD 68 P SOCKEL Flame detector operating on the UV principle in addressable conventional technology sui table for indoor mounting The detector can also be connected to an ADM loop by using a conventional zone module Features Optical indication of activation through high power LEDs Electronic theft protection Up to 3 detectors per detector line in conventional technology Upto 5 detectors per conventional zone module on the ADM loop Specifications Operating voltage Current consumption Survei
510. ries BC216 and the system condition the panel can activate the sounder with tone A or B The address of the sounder and strobe as well as the sound level are set via the DIL switch Features 9 Tone A DIN tone DIN 33 404 1200 500Hz over 1s Tone B continuous tone 870Hz Sound level adjustable in two steps via DIL switch Simple address setting of inserted detector by code card in detector base Low power consumption Long lifespan of strobe due to the use of LEDs Integrated dual isolator Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 300uA quiescent max 8mA sounder and strobe on Sound level 55 75dB A or 75 91dB A Im distance Flash frequency 1Hz Ambient temperature 20 C to 60 C Protection class IP21 Relative humidity max 95 no condensation Dimensions x H 115 x 38 mm Colour white Weight 160g Approval according to EN 54 3 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359021 Lid for Detector Base Sounder Red 45681 293 252 359020 Lid for Detector Base Sounder White 45681 292 35 214021 Loop Interface LIF64 1 253 359022 Mounting Plate for Sounder WB XP95 38531 810 169 BB072001 SAM 0720 01 0100 355137 355138 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devices ADM Series X
511. rmal ROR Detector Conv 400 SS 5451EIS rvrvenenannnnvnnnnuerenanavvernnnvevenennr 174 IS Optical Smoke Detector Conv SLR E IS erreuonnnnenennnnnvernnnvenennnauuuennnasuenennnr 175 IS Ionisation Smoke Detector Conv 60 Apo GIEX 55000 212 revnnvvvenennvrvvrnnnrvevenennr 175 IS Detector Base Conv YBN R 4IS sessssssesesssereseseersreersessererseseersesereeerereese 176 IS Detector Base Conv 60 Apo GSEX 45681 207 10 0 c eee ee nee e een ee eee eene 176 Safety Barri r Conv ES58 2rassrfa astra 177 IS Ionisation Smoke Detector Anal XP95 Apo AIEX 55000 540 arvvverenanavverrnnveverennr 177 IS Optical Smoke Detector Anal XP95 Apo AOEX 55000 640 cee eee cece ee cece eee ee eee 178 IS Thermal Detector Anal XP95 Apo AWEX 55000 440 0 cece cece cece eee eee nee e eee 178 IS Detector Base Anal Apo ASEX 45681 215 0 0 ccc ccc cnet teen eee etn eee eeenee 179 Safety Barrier Anal XP95 Apo AES 29600 098 2 0 0 0 coe ccc cece cece eee ete eee e enn ene e eee 180 Protocol Interface Anal XP95 Apo API 55000 855 oo kee cece cect eee ee tence ee enee 180 IS Optical Smoke Detector Anal 200 SS 2251 ETS 2 0 0 c eect cence ete en nee e eens 181 Safety Barrier Anal 200 SS Y72221 1 0 eee ccc cent e ee eee n eee e tenet eet enenneeeees 181 Protocol Interface Anal 200 SS IST200 0 eee cece ccc e eee eect nent eeen eee eeenne ne eeeee 182 IS Manual Call Point Red Conv DC21 0 0 cece cece een nett ee
512. rn 169 BB072001 SAM 0720 01 0100 351650 355166 355167 355134 355136 355135 355162 355163 355137 355138 355102 355164 355165 355133 355132 355131 355130 355101 355001 355014 355160 355161 355124 355125 227006 249024 310002 310006 310012 310003 310004 310005 310001 310010 244633 265760 265762 265761 265765 265764 265763 356671 356672 356022 356023 356020 356140 356141 356001 356650 245019 245012 244026 249108 249004 169 BB072001 SAM 0720 01 0100 Sounder Strobe 24V Red Red MSSRR 5 231 Sounder Strobe WB 200 White Red Multitone IBSST DR PO1 0 0 ec cee ccc eee eat S 247 Sounder Strobe WB 200ISM White Red Multitone IBSST DR P02 0 cc cee ccc eee ce eee cne eee ees 248 Sounder Strobe WB XP95ISM White Clear Alert 45681330 rase diaateosariaais cls slike 236 Sounder Strobe WB XP95ISM White Clear DIN 45681334 sjuke delhnsd lesa thle betes Ge 238 Sounder Strobe WB XP95ISM White Clear Slow Whoop 45681 332 22 2 cee cece cece cece ee eens 237 Sounder Strobe WM 200 Red Multitone 100dB WMSST RR POIL roooonaonnnnevneranvarnvveer 243 Sounder Strobe WM 200ISM Red Multitone 100dB WMSST RR PO2 2 02 ccc ccc eee cence een eee e eee 244 Sounder Strobe WM XP95ISM Red Multitone 100dB 950002293 vu obo darts sect ona E aA En 239 Sounder Strobe WM65 XP95ISM Red Multitone 100 dB55000 298 uvel hee MSRM 239 Sounder FB 12 24V White Multi
513. rol Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 253 359021 Lid for Detector Base Sounder Red 45681 293 252 359020 Lid for Detector Base Sounder White 45681 292 35 214021 Loop Interface LIF64 1 253 359022 Mounting Plate for Sounder WB XP95 38531 810 355132 Sounder WB XP95ISM White DIN 45681 300 The addressable loop sounder is installed in a round white plastic housing and is prepared for indoor surface mounting The integrated detector base is suitable for accommodation of fire detectors Series XP95 and Discovery V the Fire Detection Control Panel Series BC216 and the system eee ee RE condition the panel can activate the sounder with tone A or B The unit contains a dual isolator Features Tone A DIN tone DIN 33 404 1200 500Hz over 1s Tone B continuous tone 870Hz Low power consumption Sound level adjustable via DIL switch Simple address setting of inserted detector by code card in detector base At short circuit the function of loop elements that are not affected by the short circuit is maintained Specifications Operating voltage supply through the loop voltage Current consumption from loop typ 200uA quiescent typ 5mA sounder on S 5 The sounder is actuated using Apollo Discovery protocol and po s wered via the ADM loop Depending on the parameter setup of Sound level 55 75dB A or 75 91dB A Im distance Ambient temperature 20 C to 60 C
514. rotection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249634 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 169 2171621 Replacement Glass for Manual Call Point Blue ET SCH HM BL 170 249024 Special Designation for Manual Call Point HM BESCH 4 210210 Zone Extension Board ZEB2 1 Manual Call Point Blue Conv HM 5 11 18 02 The Manual Call Point HM 5 22 18 02 operates as electrical emergency hold device for gas extinguishing systems and is designed for application in addressable conventional technology The manual call point is accommodated in a blue aluminium die cast housing and is tested in accordance with the standards EN54 11 B and EN 12094 3 Features Robust aluminium die cast housing with an door aperture angle of more than 180 Inscription field STOPP TASTER Gasl schanlage exchangeable Optical indication of activation by LED indicator Push button non latching Standardised glass pane easy to replace Individual detector identification through connection of an optional address module Scheibe einschlagen Knopf tief dr cken 9 Plenty of space for cabling Increase of protection class to IP54 via optional Protection Kit for Manual Call Points HFM HM ZS IP54 Specifications Operating voltage supplied through loop voltage Ambient temperature 20 C to 60 C continuous operation 25 C to 70 C max 12 hours Protection class IP43 Dimensions W x H x D 125 x 125 x 34 m
515. rrent consumption at 24V 140mA without detectors modules Idle loop current typ 300uA per detector module Total loop current max 300mA at reduced line resistance Idle loop voltage typ 26V Apollo Discovery or typ 29V System Sensor 200 Loop line resistance max 50 Ohm per core Number of ADM loops 2 Number of detector zones max 128 per ADM loop max 144 in total Ambient temperature 5 C to 50 C Dimensions W x H x D 233 x 355 x 30 mm Weight approx Ikg Approvals FT 14 147 3 99 Austria VdS G201017 Cross references Page Art Nr Name Type 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 42 214230 Control Panel Rack 8HU RACK216 1E 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E Display and Operating Front Panel ABP216 1E INT 1 The Display and Operating Front Panel ABP216 1E INT1 is used as display and operating unit in BCnet sectional control panels which are composed of fire detection control panel modules It contains all standard display and operating elements of a Fire Detection Control 34 Chapter 3 Fire Detection Control Panels Series BC216 214200 214615 214209 Panel Series BC216 can be equipped with an LED Display Field LAB48 x and is de signed as 19 front panel of 6 height units The labels of display and operating elements are in English language The Display and Operating Front Panel ABP216 E INT I is connected to a
516. rrespond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Slovenian language Approval 02012 C 709P3 BCnet Sectional Control Panel OP BC216 2 I1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Italian language Approval VdS G201017 BCnet Sectional Control Panel OP BC216 2 PL1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 2 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Polish language Approval CNBOP 2238 2006 BCnet Sectional Control Panel No Operation BC216 3 The BCnet Sectional Control Panel BC216 3 is a modularly designed sectional control panel without display and operating field Black Box control panel for application in a Fire De tection Control Panel BCnet216 Depending on the boards inserted you can connect fire 26 Chapter 3 Fire Detection Control Panels Series BC216 214034 detectors fault detectors and condition detectors as well as actuation elements and alarming devices to a maximum of 2 ADM loops or to a maximum of 16 detector lines in addres sable conventional technology or to a combination of both The sectional control panel is installed in a wal
517. s Alarm delay with dead man s handle controlled by internal timer which can be set separa tely for each day of the week 169 BB072001 SAM 0720 01 0100 Chapter 2 Fire Detection Control Panels Series BCO16 7 Start and end date of Daylight Saving Time according to EU directive or freely parameterisable Non resetable electronic event counter 1 mounting position for serial interface SIM216 1 RS232C interface for the connection of a PC with Windows parameter setup software PARSOFT 1 or a serial protocol printer or SIM016 3 INFO bus interface for the connection of fire brigade control units and in telligent remote tableaus Stand by battery max 2 x 12V 22Ah can be installed in the control panel s wall mount case Specifications Mains voltage 230VAC 10 15 50Hz Connection power 60VA Output voltage typ 27 6VDC Output peak current max 1 8A Connection of external devices typ 0 8A site specific Current consumption at 24V typ 70mA without optional componentries Line voltage typ 20 0V Line current typ 3 8mA End of line resistance 5 6kOhm Line resistance max 50 Ohm per core Ambient temperature 5 C to 50 C Dimensions W x H x D 380 x 480 x 83 mm Colour grey white RAL 9002 Weight without batteries approx 5kg Approval VdS G205023 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 50 223009 Control Zone Module SLM 1 2 8 210110 De
518. s specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Slovenian language Approval 02012 C 709P3 Fire Detection Control Panel BC216 1 I1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Italian language Approval VdS G201017 Fire Detection Control Panel BC216 1 PL1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in Polish language Approval CNBOP 2238 2006 16 Chapter 3 Fire Detection Control Panels Series BC216 214308 Fire Detection Control Panel BC216 1S INT1 The Fire Detection Control Panel BC216 1S INT1 is a modularly designed compact control panel for small fire detection systems with a single ADM loop ring bus technology It is an already completely mounted unit which includes all basic components that are needed for the operation of a 1 loop fire detection control panel Fire detec tors fault detectors and condition detectors as well as control elements and alarming devices can be connected to the ADM loop Even extensive and complex alarming and con trol tasks can be accomplish
519. s 19 slide in unit with 3 height units Allows for the as sembly of stand by batteries max 2 x 12V 45Ah or 1 x 12V 65Ah Specifications Dimensions W x H x D 478 x 133 3 height units x 200 mm Mounting thickn of front panel 3mm Colour frontal view grey white RAL 9002 Weight 2kg Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 289 310004 Stand by Battery 12V 45Ah 289 310005 Stand by Battery 12V 65Ah Kit 19 3HU for Printer DPU414 DPU2 1E The mounting kit allows for the quick and easy mounting of a Protocol Printer DPU414 into a control panel that is integrated in a 19 cabinet The mounting kit is designed as a 19 slide in unit with 3 height units and it includes a drawer to accommodate the Protocol Printer DPU414 The slide in unit also provides space for the appropriate AC adapter PW4007 E1 169 BB072001 SAM 0720 01 0100 Specifications Dimensions W x H x D Colour front view Chapter 3 Fire Detection Control Panels Series BC216 45 478 x 133 x 200 mm grey white RAL 9002 Weight 2kg Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 65 227003 Protocol Printer Thermal DPU414 30B 214601 Cover IP54 for BC216 GEH IP54 BC 1 D1 Cover made of powder coated steel sheet for increasing the protection class of Fire Detection Control Panels BC216 1 BC216 1S BC216 2 and BC216 3 to IP54 Specifications Dimensions W x H x D 430 x 5
520. s dry relay contact and can be configured as pulse output with freely settable pulse duration or as continuous output Ten different voice announcement messages can be recorded the total length of all messages is 64 seconds Up to four messages can be assigned to each control line or to special system conditions of the device For operation and programming the integrated keyboard and the two line LC display or the acoustic dialogue menu via the telephone line can be used Hierarchical codes for user and manufacturer avoid unauthorised access The Automatic Telephone Dialling Device TWG805 1D is accommodated in a sabotage pro tected steel sheet housing which also provides space for the optional stand by battery and a telephone socket Features Four control inputs that are activated by a change in resistance 169 BB072001 SAM 0720 01 0100 OO o ooo oeoo Chapter 30 Telephone Dialling Devices 283 One actuation output for remote control commands programmable as pulse output or continuous output Up to eight users can be called on activation of a control input Dial possible also when control inputs are reset to inactive state DTMF or pulse dialling mode Trunk seizure via code for connection in remote systems Digital voice memory for the recording of announcement and communication texts Ten different voice announcement messages with a the total length of 64 seconds can be recorded Recording
521. s faulty the multicolour status LED on the detector will flash for approx 4 minutes in yellow colour after the detector line has been enabled Features Sealed electronics prevents false alarms caused by the environment Individual detector addressing by installing an optional address module NG60 1 Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through detector line voltage Current consumption typ 65u quiescent Alarm temperature 90 C maximum heat component Operating temperature max 80 C Ambient temperature 40 C to 90 C no condensation or icing Relative humidity 0 to 98 no condensation Dimensions x H 100 x 50 mm Colour white Weight 130g Approval VdS G204037 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 35 214020 Conventional Detector Interface GIF8 1 150 246042 Detector Base Conv ORBIS Apo MB 00001 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 Thermal Max Detector Conv ORBIS Apo HT 11006 Heat detector operating on the heat detection principle in addressable conventional technol
522. s operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm Colour sky blue RAL 5015 Weight 400g Approval VdS G204003 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 169 219006 Key for Manual Call Point SCH HFM HM 35 214021 Loop Interface LIF64 1 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 167 249634 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 169 2171621 Replacement Glass for Manual Call Point Blue ET SCH HM BL 170 249024 Special Designation for Manual Call Point HM BESCH 245429 Manual Call Point Blue Anal Apo HM 5 32 18 02 The Manual Call Point HM 5 32 18 02 operates as electrical emergency hold device for gas extinguishing systems and is designed for use on the ADM loop using Apollo Discovery pro tocol An integrated dual isolator module disconnects the loop at short circuit The manual call point is accommodated in a blue aluminium die cast housing Knopf tief dr cken Integrated microcontroller o o HFM HM ZS IP54 Specifications Operating voltage Current consumption Ambient temperature Protection class Dimensions W x H x D Features and is tested in accordance with the standards EN54 11 B EN 54 17 and EN 12094 3 Robust aluminium die cast housing with an door aperture angle of more than 180 Inscription field STOPP T
523. s the individual part payments shall fall due upon receipt of the respective invoices The same shall apply to amounts invoiced for ad ditional deliveries or resulting from additional agreements beyond the scope of the original contract irrespective of the terms of payment agreed upon for the principal delivery Payment shall be made without any discount free Seller s domicile in the agreed currency Drafts and checks shall be accepted on account of payment only with all interest fees and charges in connection therewith such as collection and discoun ting charges to be borne by Buyer Buyer shall not be entitled to withhold or offset payment on the grounds of any war ranty claims or other counterclaims Payment shall be deemed to have been effected on the date at which the amount in question is at Seller s disposal If Buyer fails to meet the terms of payment or any other obligation arising from this or other transactions Seller may without prejudice to his other rights a suspend performance of his own obligations until payments have been made or other obligations fulfilled and exercise his right to extend the period of delivery to a reasonable extent b call in debts arisen from this or any other transactions and charge default interest amounting to 1 25 per month plus turnover tax for these amounts beginning with the due dates unless Seller proves costs exceeding this In any case Seller has the right to invoice all expenses ari
524. se Anal 500 SS BS24HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 4568 1 242 107 246141 Detector Relay Base Conv 1000 SS ECO1000BREL24L 105 246100 Detector Relay Base Conv 300 SS B324RL 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 80 246072 Detector Relay Base FC600 FC600 BREL 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 249240 Detector Label Large Sheet 8pcs BME GR BOG The inscribable adhesive label serves for the marking of fire detectors not directly visible e g in inserted ceilings inserted floors or for marking other devices of the fire detection sy stem e g distribution boxes An A4 size sheet contains 8 adhesive labels L ST LABOR STRAUSS SOMERUNGSANLAGENBAL GMSH Specifications Dimensions 70mm Marking area W x H 60 x 30 mm 226 Chapter 23 Labels 249242 249011 Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 151 246025 Detector Base Anal Apo ASA 45681 210 107 246140 Detector Base Conv 1000 SS ECO1000BR1000 105 246008 Detector Base Conv 400 100 300 SS B40IRM 149 246021 Detector Base Conv 60 65 Apo GSA 45681 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 79 246070 Detector Base FC600 FC600 BR 111 246012 Detector Base Filtrex Anal 500 SS B524FTX
525. se Anal Apo ASA 45681 210 107 246140 Detector Base Conv 1000 SS ECO 1000BR 1000 105 246008 Detector Base Conv 400 100 300 SS B40IRM 149 246021 Detector Base Conv 60 65 Apo GSA 4568 1 200 150 246042 Detector Base Conv ORBIS Apo MB 00001 79 246070 Detector Base FC600 FC600 BR 111 246012 Detector Base Filtrex Anal 500 SS BS24FTXE 79 246071 Detector Base with Diode FC600 FC600 BRD 111 246018 Detector Heater Base Anal 500 SS B524HTR 110 246016 Detector Relay Base Anal 500 200 SS B524RTE 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 4568 1 242 107 246141 Detector Relay Base Conv 1000 SS ECO1000BREL24L 150 246041 Detector Relay Base Conv ORBIS Apo RB 10004 80 246072 Detector Relay Base FC600 FC600 BREL 110 246013 Isolator Detector Base Anal 500 200 SS BS24IEFT 1 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 116 249012 Wet Base Shroud SS WB1 249640 Protective Cage BWS 1 D1 Steel web cage acting as mechanical protection against mechanical impacts e g ball shots and unauthorised removal of detectors Specifications Material steel wire ST37 Dimensions x H 108 x 135 mm Colour white Weight 132g Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 151 246025 Detector Base Anal Apo ASA 45681 210 107 246140 Detector Base Conv 1000 SS ECO 1000BR 1000 105 246008 Detector Base Conv 400 100 300 SS B40IRM 149 246021
526. se Conv RF 215 27D 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 186 245021 Manual Call Point Blue RF HM 152 27D 185 245020 Manual Call Point Red RF HFM 153 27D 185 241029 Optical Smoke Detector RF 55000 680 185 242029 Thermal ROR Detector RF 55000 480 4 210210 Zone Extension Board ZEB2 1 169 BB072001 SAM 0720 01 0100 241029 242029 245020 169 BB072001 SAM 0720 01 0100 Chapter 19 RF Devices Optical Smoke Detector RF 55000 680 Smoke detector operating on the light scatter principle in addressable conventional technolo gy with an optical sensing chamber suitable for mounting in radio linked detector bases lt Features Extremely low quiescent current l Sealed electronics prevents false alarms caused by the environment Insect screen Specifications Operating voltage Battery life span Ambient temperature Dimensions x H Alarm indication on detector supplied through detector base approx 1 5 years batteries are located in the detector base 0 C to 60 C no condensation 185 Colour Weight Approval Cross references Page 187 184 100 x 42 mm white 100g VdS G2060017 Art Nr Name Type 246040 Detector Base Conv RF 215 27
527. sing prior to a lawsuit especially reminder charges and lawyer s fees Discounts or bonuses are subject to complete payment in due time Seller retains title to all goods delivered by him until receipt of all amounts in voiced including interests and charges Buyer herewith assigns his claim out of a resale of conditional commodities even if they are processed transformed or combined with other commodities to Seller to secure the latter s purchase money claim and he undertakes to make a correspon ding entry in his books or on his invoices Upon request Buyer has to notify the as signed claim and the debtor thereof to Seller and to make all information and material required for his debt collection available and to notify the assignment to the third party debtor If the goods are attached or otherwise levied upon Buyer shall draw attention to Sellers title and immediately inform Seller of the attachment or levy 312 General Terms Of Delivery 8 2 8 3 8 4 8 5 8 6 8 7 8 8 8 9 92 9 3 9 4 9 5 9 6 10 Warranty and acceptance of obligation to repair defects Once the agreed terms of payment have been complied with Seller shall subject to the conditions hereunder remedy any defect existing at the time of acceptance of the article in question whether due to faulty design material or manufacture that impairs the functioning of said article From particulars appearing in catalogues fol ders promotional
528. sor 200 protocol The module is integrated in a round transparent plastic box and is connected both with the ADM loop and with the detector via flying leads Since the module has no mounting mechanism of its own it must be installed in the detector housing Features Status LED Button in combination with LED for setting the physical address Specifications Operating voltage Current consumption supplied through loop voltage approx 300uA quiescent Ambient temperature 20 C to 60 C Dimensions x H 45 x 16 mm Colour transparent Weight 80g Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 47 2189990 Extinguishing Control Panel Series LC216 Description 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 Isolator Module Anal 500 200 SS ISM1 2 Isolator module for the connection to the ADM loop using System Sensor 200 protocol If a short circuit appears between two isolator modules the defective area is separated from the ADM loop and operation of all other connected detectors and modules is guaranteed For 104 Chapter 12 Analogue Detectors and Modules Series 200 500 le carrier Specifications Operating voltage Current consumption Ambient temperature Dimensions L x W x H optimum availability the detector zones on the ADM loop should be separated from each other by isolator modules Features
529. sories for Aspiration Smoke Detection Systems 223 effective measure to keep the number of false alarms low in areas with low or varying tempe ratures and in areas with high humidity The condensate separator contains a manual drain valve and should be regularly checked Specification Input pressure max 16bar Ambient temperature 0 C to 50 C 2449999 Aspiration Hole Reduction Foils Overview Aspiration hole reduction foils are used for a precise design of aspiration holes on the sensing pipe network of the aspiration smoke detecting system A separate version is available for deep freezing areas Standard version Version for deep freezing areas Hole diameter Article number Article number C oom ouma Areoran eee aneoraove om ms aneor ne zaze aneorzom C eomm ruz _aneor0 mor AREDFaOTK C omm sums aneors2 ves aneorazm C eamm me ancora em aneoraam O somm aaaane aneorae eo ancora C eomm aaaane ancoras ee AreoraatK C iom mr aneorao oaar AREDFAOTK C amm ou ancora vm AREDEAATK C eamm aaaaae ancoras nazza AREDFAATK C eomm me ancoras aaazae ancoraem C som zum _areor s0 mes AREDFSOMK O omm me _aneors2 naaar AREDFS TK C oom razo ancore een Areorserk C eomm zuza aneors0 aaazze Areoreor C eomm meme ancoros oe ancor eare_ O romm me aneor z0 men ancora 244233 Banderole for Aspiration Hole Reduction
530. ssing by connecting an optional address module Plenty of room for cabling Increasing the protection class to IP54 by using the optional Protection Kit for Manual supplied through detector line voltage 20 C to 60 C continuous operation 25 C to 70 C max 12 hours IP43 125 x 125 x 34 mm Colour rape yellow RAL 1021 Weight 400g Approvals VdS G202034 VdS G205018 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 49 210216 Extinguishing Board BC06 EXB1 1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 169 219006 Key for Manual Call Point SCH HFM HM 168 249631 Protection Kit IP54 for Manual Call Point HFM HM ZS IP54 168 249636 Protective Cover V2A for Manual Call Point Yellow WG GELB E 1 169 2171619 Replacement Glass for Manual Call Point Yellow ET SCH HM GE 170 249024 Special Designation for Manual Call Point HM BESCH 245362 Manual Call Point Red Anal SS HFM 3 22 02 Manual call point according to EN 54 11 B in an elegant red aluminium die cast housing de signed for application on the ADM loop ring bus technology using System Sensor 200 pro tocol with integrated dual isolator module Latching push button Features 9 Robust aluminium die cast housing with an door aperture angle of more than 180
531. t Status LED Pre configured data line to SIM216 1 included length 1 8m Pre configured power supply line included length 1 8m Specifications Supply voltage 21 to 30VDC Current consumption at 24V 45mA Ambient temperature 5 C to 50 C Relative humidity max 95 no condensation Dimensions L x W x H 100 x 90 x 25 mm Weight 150g Cross references Page Art Nr Name Type 52 214231 Interface Adapter Module IAM216 1E 295 218008 Parameter Setup Software PARSOFT 2 52 214025 Serial Interface Module SIM216 1 223027 Remote Access Module PSTN FZP2 1 The Remote Access Module FZP2 1 is designed for the transmission of configuration data of Fire Detection Control Panels Series BCO16 or BC216 via an analogue telephone line Re mote access of control panels with parameter setup software PARSOFT 1 and PARSOFT 2 can be established in this way The serial interface of the module is connected to the Serial In terface Module SIM216 1 of the control panel via the provided cable The telephone connection between the module and the telephone network local loop or extension line is established via the provided telephone cable with RJ11 connectors on both sides The device key of the module and the according telephone number of the telephone extensi on where the Remote Access Module is connected have to be entered in PARSOFT the first time a connection is established These parameters are stored in the parameter file
532. t the modules are wired in the enclosed cable channel Specifications Dimensions W x H x D 478 x 355 x 244 mm incl cable channel H approx 400mm Material zinc coated sheet steel Weight approx 4 4kg Cross references Page Art Nr Name Type 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS 32 214205 Fire Detection Control Panel Module BCM216 3E 212034 Module Carrier 19 3HU MPL17 3 19 mounting plate of 3 height units for 19 cabinets with mounting holes in standardised LST grid for the mounting of auxiliary mo dules The module carrier can hold for in stance 17 Isolator Modules ISM1 x 4 Relay Modules RL58 1 or RL58 2 4 Siren Con nection Modules SZ58 2 or SZ58 3 or 2 Multi Modules MEA244 1 E respectively 169 BB072001 SAM 212030 212029 212033 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 43 Specifications Dimensions W x H x D 478 x 133 3 height units x 10 mm Colour zinc coated steel sheet Weight approx 400g Cross references Page Art Nr Name Type 45 212027 Cabinet 19 18HU GEH19 18 64 229008 Flat Cable 1700mm 10 Pole FBK17 1 Dummy Cover 19 2HU AD8C 2H Powder coated 19 front panel of 2 height units for covering non populated pivoting frame areas of a 19 cabinet Specifications Dimensions W x H x D 478 x 89 2 height units x 3 mm Colour grey white RAL 9002
533. t 50g Cross references Page Art Nr Name Type 175 240023 IS Ionisation Smoke Detector Conv 60 Apo GIEX 55000 212 71 251001 Remote Indicator PAS8 1 z am and 169 BB0O72001 SAM 0720 01 0100 228003 240025 169 BB072001 SAM 0720 01 0100 Chapter 18 Devices for Hazardous Areas 177 Safety Barrier Conv ES58 2 Safety barrier with galvanic separation used for the build up of an intrinsically safe circuit for the connection of fire detectors in hazardous areas Due to the galvanic separation the earth fault surveillance of the fire detection control panel can remain active The relevant regulati ons for installations in hazardous areas must be observed Features Connection of automatic detectors Limitation of the possible short circuit current Limitation of the idle voltage Limitation of the energy stored in the intrinsically safe circuit Plastic surface mount case Specifications Ignition protection intrinsically safe Ex classification EEx ia IIC Operating voltage supplied through detector line voltage Quiescent current approx 5mA Ambient temperature 10 C to 60 C Dimensions W x H x D 120 x 160 x 90 mm Colour light grey similar to RAL 7035 Weight 650g Approval BASEEFA98ATEX7343 Cross references Page Art Nr Name Type 174 240015 IS Ionisation Smoke Detector Conv 100 SS 1151EIS 175 240023 IS Ionisation Smoke Detector Conv 60 Apo GIEX 55000 212 175 241090 IS Optical Smoke Detector Conv SLR E IS
534. t Sectional Control Panel OP BC216 2 CZ1 24 BCnet Sectional Control Panel OP BC216 2 D1 24 BCnet Sectional Control Panel OP BC216 2 H1 24 BCnet Sectional Control Panel OP BC216 2 HR1 25 BCnet Sectional Control Panel OP BC216 2 T1 25 BCnet Sectional Control Panel OP BC216 2 INT1 23 BCnet Sectional Control Panel OP BC216 2 NL1 25 BCnet Sectional Control Panel OP BC216 2 PL1 25 BCnet Sectional Control Panel OP BC216 2 RUS1 25 BCnet Sectional Control Panel OP BC216 2 SK1 25 BCnet Sectional Control Panel OP BC216 2 SLO1 25 BCnet Sectional Control Panel OP BC216 2EPS 30 BCnet LBC Gateway N OP 6HU BCNET LBC GW 59 Backplate Apo SZPL 45681 233 2 eee eee 153 Banderole for Aspiration Hole Reduction Foil BAAREDP cos e retenen tau can niten e EREET Banknote Contact 12V 24V GK1224 Base Adapter SS MZP500 1 44 Base Sounder amp Strobe IP24 White LPBW Base Sounder amp Strobe IP44 Red SDBR Base Sounder amp Strobe IP44 White SDBW Base Sounder amp Strobe IP65 Red WDBR Base Sounder amp Strobe IP65 White WDBW Base for Carrier Rail for M200 SS M200E DIN 117 Base for Mounting Plate for M200 SS M200E PMB 116 Base for Sounder amp Strobe IP44 Red EMA ELPBR 251 Base for Sounder amp Strobe IP55 Red EMA ESBR 251 Base for Sounder amp Strobe IP66 Red EM
535. t detectors and condition 28 Chapter 3 Fire Detection Control Panels Series BC216 detectors as well as actuation elements and alarming devices to a maximum of 2 ADM loops or to a maximum of 16 de tector lines in addressable conventional technology or to a combination of both Thanks to its wide range of possible logic combinations for alarming and transmit ting devices as well as for actuations the control panel can realise even extensive and complex alarming and control tasks in the fire alarm technology It complies with all requirements of the European Standards EN 54 2 and EN 54 including all options for the highest safety demands The control panel is designed as 19 slide in unit with 6 height units to be mounted in an op tional 19 cabinet The slide in unit is prepared for 2 function modules Conventional Detec tor Interface GIF8 1 or Loop Interface LIF64 1 a Fire Brigade Interface FWI2 1 a Fire Brigade Interface Additional Board FWZ2 1 an LED Display Field LAB48 1 a Serial Inter face Module SIM216 1 and additional optional componentries as well as a stand by battery with 2 x 12V max 22Ah The labels of display and operating elements as well as the dis played and printer texts are in English language The extensive functions and features correspond to the full extent to the Fire Detection Con trol Panel BC216 1 INT1 Art No 214008 By installing a Network Interface Module NIF5 1M in the Fire Detection Control Panel
536. t protection Insect screen 140 Chapter 15 Analogue Detectors and Modules Series XP95 DISCOVERY 242028 Specifications Operating voltage supplied through loop voltage Current consumption typ 400A quiescent Ambient temperature 20 C to 60 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 105g Approval VdS G299037 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 151 246036 Isolator Detector Base Anal Apo AISA 45681 321 35 214021 Loop Interface LIF64 1 71 251001 Remote Indicator PAS8 1 Thermal Detector Anal Disc Apo AD 58000 400 Addressable thermal detector operating on the heat principle for application on the ADM loop using Apollo Discovery protocol in extra flat design suitable for indoor mounting The de tector can be classified AIR A2 A2S CR and CS maximum room height with AIR is 7 5m else 6m a E AV dd Features A Permanent evaluation of environmental conditions n Continuous transmission of the current measured value to the fire detection control panel Classification can be set in 5 steps AIR A2 A2S CR and CS via Fire
537. t with dry changeover contact Mechanical theft protection Specifications Operating voltage supplied through detector line voltage 106 Chapter 13 Acessories for Series 300 ECO1000 200 500 Current consumption luA quiescent 25mA active Contact rating 1A at 30VDC Ambient temperature 20 C to 70 C Relative humidity 5 to 93 no condensation Dimensions x H 127 x 29 mm Colour cream Weight 96g Cross references Page Art Nr Name Type 226 249011 Detector Label BME BEZ 82 241041 Optical Thermal Detector Conv 300 SS 2351TEM 81 241040 Optical Smoke Detector Conv 300 SS 2351E 84 242041 Thermal Max Detector Conv 300 SS 4351E 84 242042 Thermal Max Detector Conv 300 SS 5351TE 83 242040 Thermal ROR Detector Conv 300 SS 5351E 246101 Detector Relay Base Conv 300 SS B312RL Mounting base for automatic fire detectors Series 300 with integrated relay output suitable for indoor surface mounting The mounting base is designed for the connection to control pa nels with a 12VDC operating voltage and must therefore not be connected to Fire Detection Control Panels Series BC06 BC016 and BC216 The relay output is activated by the alarm condition of the inserted detec A tor and remains in the activated state as long as the operating 3 voltage has not been shortly interrupted Features Multi useable terminals with secure screw fitting Relay output with dry changeover contact Mechanical theft protection Specific
538. tallation alternatively in module box or by means of mounting pedestal Specifications Operating voltage Current consumption supplied through loop voltage approx 660uA quiescent Contact rating 2A 30VDC or 0 5A 125VAC Line termination 56kOhm Alarm threshold typ 22kOhm Ambient temperature 20 C to 60 C Dimensions L x W x H 93 x 94 x 23 mm Colour cream Weight 110g Approval VdS G202139 Cross references Page Art Nr Name Type 117 249110 Base for Carrier Rail for M200 SS M200E DIN 116 249109 Base for Mounting Plate for M200 SS M200E PMB 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 117 249108 Surface Mounting Box for M200 SS M200SMB Monitor Module 10xSurv In Anal 200 SS IM 10 Addressable module with 10 inputs for the line monitored integration of contact detectors e g manual call points sprinkler system contacts supervising contacts into the bi directio nal communication on the ADM loop using System Sensor 200 protocol Features Status LED for every input Surveillance of terminal connection lines for wire breakage and short circuit 2 decadic rotary switches for setting the ad dress from 01 to 99 Mounting in a Surface Mounting Box For Multimodule SS Specifications Operating voltage supplied through loop voltage Current consumption approx 3 5mA quiescent Line termination 56kOhm
539. tection Control Panel BC216 1CE NL1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1CE INT1 The labels of display and operating elements as well as the displayed and printer texts are in Dutch language A User Manual in English is included in delivery Approval VdS G201017 Fire Detection Control Panel BC216 1CE CZ1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1CE INT1 The labels of display and operating elements as well as the displayed and printer texts are in Czech language A User Manual in English is included in delivery Approval EZU 7 105034 00 00 Fire Detection Control Panel BC216 1CE H1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1CE INT1 The labels of display and operating elements as well as the displayed and printer texts are in Hungarian language A User Manual in English is included in delivery Approval EMILABS 85 2000 BCnet Sectional Control Panel No Op BC216 3CE The BCnet Sectional Control Panel BC216 3CE is a modularly designed sectional control panel in 19 slide in technology without display and operating field Black Box control pa nel for application in a Fire Detection Control Panel BCnet216 Depending on the boards inserted you can connect fire detectors fault detectors and condition detectors as well as actuation elements and alarming devices to a
540. tector Zone Extension MGE8 1 9 210111 Fire Brigade Interface FW1016 1 66 227008 Protocol Printer Dot Matrix LX300 65 227003 Protocol Printer Thermal DPU414 30B 63 222010 Relay Module 4 Fold 230V AC RL58 2 62 222004 Relay Module 8 Fold 60VDC RL58 1 9 210112 Serial Interface Module SIM016 3 52 214025 Serial Interface Module SIM216 1 61 223026 Siren Connection Module SZ58 3 287 310002 Stand by Battery 12V 18Ah 210100 Fire Detection Control Panel BC016 1 D1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC016 1 INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language Approval FT 14 439 04 Austria VdS G205023 210122 Fire and Evacuation Panel BC016 2 INT1 The design of the Fire and Evacuation Panel BC016 2 INT I is identical with the Fire De tection Control Panel BC016 1 INT1 but includes additional 10 buttons in the display and operating field for the direct control i e activation and deactivation of a maximum of 8 evacuation circuits according to NEN 2575 169 BB072001 SAM 0720 01 0100 8 Chapter 2 Fire Detection Control Panels Series BCO16 Specifications Mains voltage Connection power Output voltage Output peak current Connection of external devices Current consumption at 24V 230V AC 10 15 50Hz 60VA typ 27 6VDC max 1 8A typ 0 8A site specific typ 7OmA without optional componentries Line vo
541. ter 12 Analogue Detectors and Modules Series 200 500 101 Dimensions L x W x H 93 x 94 x 23 mm Weight 110g Approval VdS G205144 Cross references Page Art Nr Name Type 117 249110 Base for Carrier Rail for M200 SS M200E DIN 116 249109 Base for Mounting Plate for M200 SS M200E PMB 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 35 214021 Loop Interface LIF64 1 117 249108 Surface Mounting Box for M200 SS M200SMB 249092 Multi Module Mounting Rail MEA244 1 TR The addressable module MEA244 1 TR provides 4 inputs and 4 outputs and is connected to a Fire Detection Control Panel Series BC216 via the ADM loop with System Sensor 200 pro tocol The inputs allow for the connection of contact detectors e g manual call points sprinkler system contacts supervising contact and are monitored for wire breakage and short circuit The outputs serve for the connection of control devices e g solenoid valves relay coils and provide a separate monitoring of line resi stance and load resistance The reference value of both resistances is determined by means of an automatic calibration procedure initiated with a keystroke during commissioning If one of the two resistance values differs from the refe rence value by more than 25 during operation the output is indicated as faulty The method of multiple monitoring patent pending provides a reliable detection of line
542. terface LIF64 1 Sounder WB 200 White Multitone IBSOU DD P01 The addressable sounder is accommodated in a round white plastic housing and is prepared for indoor surface mounting The integrated base is suitable for accommodation of fire detec tors Series 200 The unit is mounted on a base for signalling devices not provided The so A Features under is actuated as a module using System Sensor 200 protocol and is powered via the ADM loop Depending on the parameter setup of the Fire Detection Control HN Panel Series BC216 and the system condition the panel can activate the sounder with tone A or B The tone type of tones A and B is set via a DIL switch with selection out of 32 combina tions The sound level is adjustable in 3 steps but depends also on the chosen tone type The power consumption is dependent on the tone type and the adjusted sound level 32 different tone type combinations selectable via DIL switch e g continuous tone 660Hz DIN 33 404 tone 1200 500Hz Slow Whoop tone 500 1200Hz 9 Sound level adjustable in 3 steps low medium high Low power consumption Integrated detector base 2 decadic rotary switches for setting the address from 01 to 99 Different base versions available Specifications Operating voltage Current consumption from loop Sound level detector mounted supply through the loop voltage typ 450uA sounder off max 1 9mA low sound level max 3 ImA m
543. th a 12VDC operating voltage and must therefore not be connected to Fire Detection Control Panels Series BC06 BCO16 and BC216 The relay output is activated by the alarm condition of the inserted detector and remains in the activated state as long as the operating voltage has not been shortly interrupted Features Multi useable terminals with secure screw fitting Relay output with dry changeover contact Specifications Operating voltage 10 to ISVDC Current consumption typ 1uA quiescent 25mA active Contact rating 1A at 30VDC Ambient temperature 30 C to 70 C Relative humidity 5 to 93 no condensation Dimensions x H 102 5 x 33 mm Colour white Weight 70g 246143 Detector Relay Base Conv SS ECO1000BREL12NL Mounting base for automatic fire detectors Series ECO1000 with integrated relay output sui table for indoor surface mounting The mounting base is designed for the connection to con trol panels with a 12VDC operating voltage and must therefore not be connected to Fire Detection Control Panels Series BC06 BCO16 and BC216 The relay output is activated by the alarm condition of the inserted detector both the detector and the relay output are automatically reset several seconds after the fire detection Features Multi useable terminals with secure screw fitting Relay output with dry changeover contact Specifications Operating voltage Current consumption Contact rating Ambient temperature
544. that is marked in the case max detector can be connected max 5 detectors can be connected Connection of remote indicators to the smoke detectors possible Limitation of the idle voltage DIN rail mounting Specifications Ignition protection Ex classification Operating voltage Ambient temperature Approval Cross references Page Limitation of the possible short circuit current Limitation of the energy stored in the intrinsically safe circuit intrinsically safe 177 178 178 180 EEx ia IIC TS supplied through loop voltage 10 C to 60 C EECS ATEX 0073 Art Nr Name Type 240025 IS Ionisation Smoke Detector Anal XP95 Apo AIEX 55000 540 241024 IS Optical Smoke Detector Anal XP95 Apo AOEX 55000 640 242036 IS Thermal Detector Anal XP95 Apo AWEX 55000 440 228005 Protocol Interface Anal XP95 Apo API 55000 855 Protocol Interface Anal XP95 Apo API 55000 855 The protocol interface is always used together with a Safety Barrier Anal XP95 Apo and al lows for the bi directional data exchange of analogue fire detectors in ha Specifications Ignition protection zardous areas on the ADM loop using Apollo Discovery protocol The number of detectors that can be connected to the protocol interface is limited by the safety barrier The protocol interface is suitable for snap on to a 35mm DIN rail intrinsically safe Ex classification EEx ia IIC T5 Operating voltage supplied through loop
545. the control panel Configurable functions for the operation of the control panel RS232C interface for data transfer to control panel RS232C interface for data transfer to IEC870 5 101 control centre Ethernet interface for data transfer to IEC870 5 104 control centre Individual setting of all IEC parameters using the setup program Separate status LED indicators for each interface To be mounted on a DIN rail o o o o Specifications Operating voltage 20 30VDC Current consumption at 24V typ 125mA Ambient temperature 5 C to 50 C Dimensions L x W x D 168 x 118 x 54 mm Protection class IP30 Weight 820g Cross references Page Art Nr Name Type 52 214231 Interface Adapter Module IAM216 1E 52 214025 Serial Interface Module SIM216 1 58 218022 ZLT Interface License ZLT SS Long Distance Modem BCnet216 MOD 1 The Long Distance Modem BCnet216 MOD 1 allows you to extend the maximum distance between two sectional control panels of the Fire Detection Control Panel BCnet216 to up to 4000m The sectional control panels are connected through a telephone cable with at least 2 free wire pairs Each sectional control panel requires a Long Distance Modem MOD 1 on both the incoming and outgoing side In this way you can also bridge only individual sections of the high security network if required The use of the long distance modem is furthermore recommended if no cabling with the minimum requirement of the Network Cable N
546. the highest safety demands The control panel is installed in a powder coated sheet steel wall mount case The basic version of the control panel includes 8 detector zones in addressable conventional technology 2 freely parameterisable inputs and 3 relay outputs The Fire De tection Control Panel Series BC016 can be extended to 16 detector zones by installing a De tector Zone Extension MGE8 1 and can be provided with a Fire Brigade Interface FWI016 1 The wall mount case furthermore provides for the possible installation of up to 3 optional componentries Relay Module RL58 1 or RL58 2 Siren Connection Module SZ58 3 etc as well as of a stand by battery with 2 x 12V max 22Ah The labels of display and operating elements as well as the displayed and printer texts are in English language The parameters of the control panel can be set up and transmitted to the control panel quickly and reliably by means of a PC and the Windows parameter setup software PARSOFT 1 Ad ditionally the parameter setup can be accomplished without any further tools by using the keypad of the integrated display and operating field of the control panel The fire detection control panel comes with a default setup which allows for a particularly easy commissioning Most important features RISC micro processor technology Administration of up to 16 detector zones for manual call points automatic fire detectors with or without alarm verification technical messa
547. tically displayed on the system and transmitted to AEE Cite control panel as fault message The aspiration smoke detection system housing is provided with the entire evaluation electro nics However the detector module the front foil and the sensor pipe network are not provided A serial interface is installed in the system for communication with a PC software Operation fault info alarm pre alarm and main alarm are indicated on the front side of the system via LEDs In addition for the display of the actual smoke density a 10 step LED dis play is provided Features Applicable in addressable conventional technology with the optional Detector Reset Mo dule MQZ1000 1 Individual detector identification through connection of an optional address module NG58 1 Connection to an ADM loop is possible via optional modules Specifications Supply voltage 14 30VDC Current consumption at 24V max 260mA quiescent 290mA alarm incl detector module Pipe length max 180m Number of aspiration holes max 24 Ambient temperature 20 C to 60 C Dimensions W x H x D 200 x 292 x 113 mm Colour white RAL 9018 Weight 1 35kg Approval VdS G202064 Cross references Page Art Nr Name Type 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 218 244304 Detector Module DM TT 05 L 218 244303 Detector Module DM TT 25 L 217 244302 Detector M
548. ting on the heat principle for application on the ADM loop using Apollo Discovery protocol and of extra flat design suitable for indoor mounting The detector is assigned to class A2S and A2R maximum room height 6m The principle that is applied for the evaluation of the measured values maximum or gt rate of rise heat detection can be selected in the fire detection Cap control panel by means of appropriate programming 1 Features Permanent evaluation of environmental conditions Continuous transmission of the current measured value to the fire detection control panel Constant sensitivity Address card in the detector base for setting the physical address from 01 to 126 Sealed electronics prevents false alarms caused by the environment Output for external remote indicator Mechanical theft protection Specifications Operating voltage supplied through loop voltage Current consumption typ 250uA quiescent Ambient temperature 20 C to 70 C no condensation or icing Relative humidity 0 to 95 no condensation Dimensions x H 100 x 42 mm Colour white Weight 105g Approval VdS G294029 Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 153 246034 Detector Base Anal Apo 45681 250 151 246025 Detector Base Anal Apo ASA 45681 210 152 246037 Detector Relay Base Anal XP95 DISC Apo ASR 45681 242 32 214234 Fire Detection Control Panel Module LG
549. tion Con trol Panels Series BCO16 Features 1 relay output with dry changeover contact 1 line monitored output with selectable surveillance current 8 inputs and 7 outputs freely parameterisable for the connection of a country specific fire brigade control unit and other devices All inputs and outputs are available on screw terminals or flat cable connector Specifications Current consumption at 24V typ 4mA Switching power per contact 60V 1A 30W Contact life 3x 10 Ambient temperature 5 C to 50 C Dimensions L x W x H 130 x 65 x 15 mm Weight 70g Cross references Page Art Nr Name Type 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 210112 Serial Interface Module SIM016 3 The Serial Interface Module SIM016 3 is used to extend a Fire Detection Control Panel Se ries BCO16 with an INFO bus interface for the connection of fire brigade control units and intelligent remote indication units with serial data transmission Specifications Current consumption at 24V typ 22mA Interface 20mA current loop Connection type Screw terminals Ambient temperature 5 C to 50 C Dimensions L x W x H 70 x 45 x 20 mm Weight 50g Cross references Page Art Nr Name Type 7 210122 Fire and Evacuation Panel BC016 2 INT1 6 210102 Fire Detection Control Panel BC016 1 INT1 Jer 169 BBO72001 SAM ai 0720 01 0100 10 Chapter 3 Fire Detection Control Panels Series BC216
550. tion Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 4 210210 Zone Extension Board ZEB2 1 Thermal Max Detector IP67 Conv SWM 1KL 80 The maximum heat detector SWM 1KL 80 uses a bimetal element as thermal sensor If the alarm temperature is reached the bimetal contact is closed Addressable conventional techno logy is used for alarm transmission to the fire detection control panel The activated condition of the detector is indicated by an LED The detector can be con nected to an ADM loop by using a conventional zone module P f rd gt wwe O The detector is integrated in an aluminium die cast housing that NE is suitable for application in moist areas e g loading ramps f P Features kr FEE SEE N Individual detector addressing by connecting an optional ad dress module Alarm LED on detector housing Output for external remote indicator 169 BB072001 SAM 0720 01 0100 242013 169 BB072001 SAM 0720 01 0100 Chapter 20 Special Detectors 193 Metal PG screws for waterproof insertion of the connecting cables Specifications Operating voltage supplied through detector line voltage Alarm current at 24VDC max 100mA Alarm temperature typ 80 C Protection class IP67 Dimensions L x W x H 110 x 90 x 54 mm Colour white Weight
551. tional Detectors Series 300 ECO1000 83 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT 1 3 210209 Fire Detection Control Panel BC06 2 INT 1 71 251001 Remote Indicator PA58 1 112 246111 Remote Program and Test Unit Conv 300 SS S300RPTU 113 246150 Remote Test Unit Conv 300 1000 SS ECO 1000RTU 113 246112 Satellite Unit for Remote Programming Conv 300 SS S300SAT 112 246113 Zonal Display Unit Conv 300 SS S300ZDU 4 210210 Zone Extension Board ZEB2 1 Thermal ROR Detector Conv 300 SS 5351E Heat detector operating on the rate of rise heat detection principle combined maximum rate of rise detector classified as AIR maximum room height 7 5 m suitable for indoor moun ting in addressable conventional technology and in flat design 4 For quick localisation in the event of an alarm each detector oa ae can be assigned an address either by adding an address module p NG58 1 to the mounting base or by programming the detector with an optional Remote Program and Test Unit S300RPTU If the detector is addressed using NG58 1 the detector address as well as the assigned text is displayed directly on the fire de tection control panel provided that these functions are suppor ted by the control panel If the detector address has been specified by means of S300RPTU the detector number is not displayed on the control panel itself but on an additi
552. to 57 6kBaud Signal lines RxD TxD CTS DTR Connection type D SUB plug 9 pole Ambient temperature 5 C to 50 C Dimensions L x W x H SIM216 1 70 x 45 x 20 mm adapter board 73 x 34 x 22 mm Weight 70g Cross references Page Art Nr Name Type 31 214204 Fire Detection Control Panel Module PS BCM216 3EPS Jer as 169 BBOT2001 SAM 0720 01 0100 Chapter 5 Interfaces 53 32 214205 Fire Detection Control Panel Module BCM216 3E 223025 Ethernet Module ENM2 1 The Ethernet Module ENM2 1 is used to convert the setup data which is transmitted via the Serial Interface Module SIM216 1 into an IP protocol You can use the parameter setup soft ware PARSOFT 1 or PARSOFT 2 to realise a convenient remote access to the Fire Detection Control Panel Series BC216 as well as Series BCO16 RI The Ethernet module is integrated into the customer s LAN by the customer s LAN supervisor like any member e g PC network printer The Ethernet Module ENM2 1 is set up by means of the setup software SS ConfigENM2 which is included on the CD ROM for the delivery of the parameter setup software PARSOFT 1 or PARSOFT 2 The Ethernet module is contacted from the remote PARSOFT PC via the spe cified IP address when operating via PARSOFT 1 or PARSOFT 2 there is no difference bet ween on site and remote operation Features Operation in DHCP or BOOTP networks Operation with static or dynamic IP address Remote operation via LAN WAN or Interne
553. tone DBS1224B4W 229 Sounder WB 200 White Multitone IBSOU DD PO1 245 Sounder WB 200ISM White Multitone IBSOU DD P02 2 0 cece eee eens 246 Sounder WB XP95ISM White Alert 45681 277 233 Sounder WB XP95ISM White DIN 45681 300 234 Sounder WB XP95ISM White Slow Whoop 45681290 tei ss drenerer nese alken 233 Sounder WB XP95RI White Alert 45681 276 236 Sounder WM 12 24V Red Multitone 103dB EMA1224BAR favicicaseaieaagxiats patient 229 Sounder WM 12 24V Red Multitone 106dB MSIR 228 Sounder WM 12 24V White Multitone 106dB MSIW 228 Sounder WM 200 Red Multitone 100dB WMSOU RR PO1 oeooooovonvrnnannannansnnnenr 242 Sounder WM 200ISM Red Multitone 100dB WMSOU RR P02 oe ceee eee ee ease okimnekne 242 Sounder WM XP95 Red Alert 100dB 55000 278 235 Sounder WM XP95 Red Slow Whoop 100dB 990002716 cia ae or ob ee ort des 235 Spare Paper for DPU414 IRoll MM112 402 N 67 Special Designation for Manual Call Point HM BESCH 170 Stand by Battery 12V I8Ah 00 cee eee eee ee 287 Stand by Battery 12V 2 3Ah 00 cece ee eee 287 Stand by Battery 12V 20Ah Stand by Battery 12V 26Ah Stand by Battery 12V 45Ah Stand by Battery 12V 65Ah Stand by Battery 12V 7Ah Stand by Battery 6V 1 2Ah Standard Sensor Cable Red SKM SK ROT 206 Steel Column V2A Standard HSFSK700 2 D1 262 Steel Column V2A for F0345 Strobe HSFSK700 2 D3 oo ee cece cece e
554. tor Anal Disc Apo AMS 58000 700 Addressable multisensor detector with a detection element operating on the light scatter prin ciple and a detection element operating on the rate of rise heat principle for application on the ADM loop using Apollo Discovery protocol and is of extra flat design suitable for indoor mounting The alarm evaluation is based on the analysis of both detection units if only one characteristic of fire occurs false alarms can be mostly avoided Please note that the detector must not be used if the room height exceeds 7 5m in the thermal only L N m mode Intelligent evaluation algorithms compensate for the impact of contamination of the optical sensing system Thereby the re sponse sensitivity of the detector is kept constant for a long time thus constituting another ef fective measure for preventing false alarms What is more the response sensitivity of the detector can be adjusted via the fire detection control panel to adapt the detector optimally to the application environment Features Permanent evaluation of environmental conditions Constant sensitivity Response sensitivity and operation mode can be set in 5 steps via the Fire Detection Con trol Panel Series BC216 smoke only heat only 3 levels multisensor Insect screen Specifications Operating voltage Current consumption Ambient temperature Address card in the detector base for setting the physical
555. triggering detectors if the indicator on the detector itself is not visible due to false floors or ceilings etc Depending on the connecti on the remote indicator can indicate the activation of a single detector or multiple detectors Features Elegant surface mount plastic case with red cap High power LEDs Supply via detector line Specifications Operating voltage supply through the detector line or loop voltage Current consumption at 24V typ 12mA active Ambient temperature 5 C to 50 C Dimensions W x H x D 70 x 70 x 35 mm Colour white 72 Chapter 8 Display and Operating Devices Weight 150g 252010 LED Display Tableau LAT288 1 The LED Display Tableau LAT288 1 allows for the design of a display for the optical si gnalling of events of a Fire Detection Control Panel Series BC016 or BC216 and of an Extin guishing Control Panel Series LC216 via parameterisable LED pair indicators The tableau housing consists of a wall mount case made of powder coated steel sheet which accommodates up to three LED Display Fields LAB48 x and the Remote Tableau Drive Unit PTU288 1 The front side of the case is sealed with a light grey plastic foil which has six windows integrated for labelling of LED indicator pairs Besides LED display fields further optional componentries e g relay modules and up to 2 x 12V max 22Ah stand by batteries at the bottom of the case can be accommodated Specifications Dimensions W
556. tware PARSOFT 2 In addition to the main operating unit additional operating units as well as remote display and operating units can be integrated into GSSnet Every BCnet sectional control panel as well as the Fire Detection Control Panel Modules BCM216 3EPS and BC216 3E is prepared for 2 function modules Conventional Detector Module GIF8 1 or Loop Interface LIF64 1 one Fire Brigade Interface FWI2 1 one Fire Bri gade Interface Additional Board FWZ2 1 a Serial Interface Module SIM216 1 as well as ad ditional optional componentries You can thus connect fire detectors fault detectors and condition detectors as well as actuation elements and alarming devices to a maximum of 2 ADM loops or to a maximum of 16 detector lines in addressable conventional technology or to a combination of the both Sectional control panel with display and operating field can be equipped with LED Display Fields If required the Fire Detection Control Panel BCnet216 can be expanded to become an Extin guishing Control Panel LCnet216 Each sectional control panel can control and monitor up to 8 flooding zones the entire panel network controls a maximum of 127 flooding zones The extensive functions and features are summarised in the description of the Extinguishing Control Panel Series LC216 No 2189990 Most important features of each BCnet sectional control panel or fire detection control panel modules respectively Micro processor technology w
557. u order Features High quality alkaline manganese battery Low self discharge Long lifespan Specifications Dimensions L x 16 x 10 mm Cross references Page Art Nr Name Type 113 246150 Remote Test Unit Conv 300 1000 SS ECO1000RTU Battery for ECO1000RTU 6V 476A The 6V battery is used for supply of the Remote Test Unit ECO1000RTU ATTENTION the remote test unit exists in two different designs which require diffe rent types of batteries Please pay attention to the type and dimensions of the battery when you order Features High quality alkaline manganese battery Low self discharge Long lifespan Specifications Dimensions L x 25 x 13 mm Cross references Page Art Nr Name Type 113 246150 Remote Test Unit Conv 300 1000 SS ECO1000RTU Base Adapter SS MZP500 1 Plastic plate used in addition to detector base B501 B501DG B401RM B524IEFT 1 B524HTR or B524RTE for securely covering the mounting area and for compensating an uneven surface Specification Dimensions x H 103 x 5 mm Colour cream Weight 50g 1 am and 169 BB072001 SAM 0720 01 0100 246009 246010 169 BB072001 SAM 0720 01 0100 Chapter 13 Acessories for Series 300 ECO1000 200 500 115 Cross references Page Art Nr Name Type 109 246002 Detector Base Anal 500 200 SS B501 109 246015 Detector Base Anal 500 200 SS B501DG 105 246008 Detector Base Conv 400 100 300 SS B40IRM 111 246018 Detect
558. uded in delivery Specifications Operating voltage 10 2 to 32VDC Current consumption at 24V 17mA quiescent 38 5mA active Ambient temperature 30 C to 55 C Relative humidity max 95 no condensation Dimensions W x H x D 190 x 254 x 84 mm Smoke Detector 6500 Dimensions W x H x D 200 x 230 x 10 mm Reflector 5 to 70m Protection class IP54 Colour cream Weight 1 8kg Approval VdS G205034 EN 54 12 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 208 222013 Detector Reset Module MQZ1000 1 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BCO16 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 200 244025 Multi Mount Kit 6500 BEAMMMK 200 244024 Reflector 6500 75 100M BEAMLRK 201 244026 Surface Mount Kit 6500 BEAMSMK 4 210210 Zone Extension Board ZEB2 1 Beam Smoke Detector Test Conv SS 6500RS Beam smoke detector for the surveillance of open areas with a range of 5m to 70m with ac cessories up to 100m consisting of a combined transmitter receiver unit integrated into a plastic housing for application in conventional technology designed for indoor mount
559. ue to the use of LEDs 2 decadic rotary switches for setting the address from 01 to 99 Different base versions available 169 BB072001 SAM 0720 01 0100 355164 169 BB072001 SAM 0720 01 0100 Chapter 25 Optical and Acoustic Devices ADM Series XP95 200 245 Specifications Operating voltage Current consumption from loop Sound level Examples at 24V Continuous tone 660Hz DIN tone 1200 500Hz Slow Whoop tone 500 1200Hz supply through the loop voltage typ 450uA sounder and strobe off max 4 9mA low sound level max 6 8mA medium sound level max 9 5mA high sound level typ 82dB A 1m distance low sound level typ 90dB A 1m distance medium sound level typ 96dB A 1m distance high sound level max 100dB A 1m distance high sound level typ 7 0mA at 98dB A 1m distance typ 9 0mA at 100dB A 1m distance typ 9 5mA at 96dB A 1m distance 1Hz 25 C to 70 C 10 96 no condensation 115 x 68 mm incl Base LPB W Flash frequency Ambient temperature Relative humidity Dimensions x D Colour Weight Approval Cross references Page 254 255 256 26 32 35 red 204g VdS G206076 Art Nr Name Type 359040 Base Sounder amp Strobe IP24 White LPBW 359041 Base Sounder amp Strobe IP44 Red SDBR 359042 Base Sounder amp Strobe IP65 Red WDBR 214034 BCnet Sectional Control Panel Extension BCE216 3LG 214234 Fire Detection Control Panel Module LG BCM216 3ELG 214021 Loop In
560. uide which may not be used in all sales areas due to different technical requirements or specific approval limitations Please always refer to the article number of the products when making an inquiry or when placing an order IV Example of an article entry 1 2 3 999999 Name Type XX XXX XX Description of the article with basic notes on function design application detailed specifications approval codes and other information Cross references Page Art Nr Name Type XX 999999 Name Type XX XXX XX XX 888888 Name Type XX XXX XX XX 777777 Name Type XX XXX XX XX 666666 Name Type XX XXX XX 1 Article number please always refer to this number on ingiries or orders to avoid mistakes 2 Product name 3 Type the type is a string of alpha numerical characters and symbols without blank cha racters and is separated from the product name by one blank character 4 Price per unit generally per piece 5 Product description details on approvals and examinations specifications 6 Cross references to other products of the Product Guide which are in direct connection with the chosen product These cross references present a list of possibilities which are of exemplary nature only the products listed therein must not necessarily be working altogether 169 BB072001 SAM 0720 01 0100 169 BB072001 SAM 0720 01 0100 Contents Fire Detection Control Panels Series BC06 210205 210200 210204 2102
561. uitable for indoor mounting in buildings with a maximum room height of 7 5m The alarm evaluation is based on the KL analysis of both detection units if only one characteristic of fire occurs false alarms can be mostly avoided For quick localisation in the event of an alarm each detector can be assigned an address either by adding an address module NG58 1 to the mounting base or by programming the detector with an optional Remote Program and Test Unit S300RPTU If the detector is addressed using NG58 1 the detector address as well as the assigned text is displayed directly on the fire detection control panel provided that these functions are suppor ted by the control panel If the detector address has been specified by means of SJOORPTU the detector number is not displayed on the control panel itself but on an additional Zonal Display Unit S300ZDU one of which must be integrates in every detector line Intelligent evaluation algorithms in the detector compensate for the impact of contamination of the optical sensing system Thereby the response sensitivity of the detector is kept con stant for a long time thus constituting another effective measure for preventing false alarms If the contamination of the sensing system is too heavy for further compensation or if the sensing system is defective the status LED on the detector will flash yellow The degree of contamination can be scanned by the maintenance engineer via the Remote Prog
562. ule SZ58 3 287 310002 Stand by Battery 12V 18Ah Fire Detection Control Panel BC216 1S A1 The Fire Detection Control Panel BC216 1S A1 is a modularly designed compact control pa nel in the version for Austria for small size fire detection systems with a single ADM loop Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language Approval FT 14 147 3 99 Austria VdS G201017 Fire Detection Control Panel BC216 1S D1 The Fire Detection Control Panel BC216 1S D1 is a modularly designed compact control pa nel in the version for Germany for small size fire detection systems with a single ADM loop Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in German language Approval VdS G201017 Fire Detection Control Panel BC216 1S B1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT1 The labels of display and operating elements as well as the displayed and printer texts are in French language Approval ANPI BFS DE 1096 2003 03 20 Fire Detection Control Panel BC216 1S CZ1 Functions specifications and cross references correspond to the Fire Detection Control Panel BC216 1S INT
563. umption at 24V 3mA quiescent Current consumption from stand by battery in case of 150mA all actuation outputs activated supply voltage failure 7mA quiescent 350mA all actuation outputs activated Ambient temperature 5 C to 50 C Dimensions L x W x H 70 x 60 x 15 mm Weight 50g Cross references Page Art Nr Name Type 281 320007 Automatic Telephone Dialling Device TWG805 1A 282 320008 Automatic Telephone Dialling Device TWG805 1D Line Monitoring Module TUM805 1 Snap on board for Automatic Telephone Dialling Devices Series TWG805 to continuously monitor the loop voltage of a telephone line The delay time for the fault evaluation can be programmed at the TWG805 1 Specifications Supply voltage Response threshold of the voltage monitoring Current consumption at 12V Current consumption at 24V Current consumption from stand by battery in case of supply voltage failure Current consumption from telephone line Ambient temperature Dimensions L x W x H Weight Approval Cross references Page internal voltage supply of the TWG805 1 20VDC 64mA 32mA 8mA 10uA 5 C to 50 C 35 x 30 x 15 mm 6g together with TWG805 1A Austrian Telecommunication Authority 105340ZB9705 Art Nr Name Type 281 320007 Automatic Telephone Dialling Device TWG805 1A 282 320008 Automatic Telephone Dialling Device TWG805 1D z am im 169 BB072001 SAM 0720 01 0100 329014 329015 329016 169 B
564. ures Alarm indication through red LED Acoustic indication of pre alarm and alarm Relays for pre alarm and alarm Alarm resetting via button WAMU VINN Specifications Operating voltage 8 5 to 14VDC Current consumption max 200mA Contact rating relay 1 amp 2 120VAC 1A 24VDC 1A Ambient temperature 0 C to 60 C Sensor heating power 750mW Dimensions W x H x D 120 x 120 x 30 mm Gas Detector Propane GM PROPAN Compact gas detector for the detection of propane below the explosion limit The detector is suitable mainly for the application in private households where propane gas bottles are used 208 Chapter 20 Special Detectors 244619 222013 The gas detector signals pre alarm at 10 of the lower explosion li NELL Leg In Features Alarm indication through red LED Acoustic indication of pre alarm and alarm Relays for pre alarm and alarm mit and alarm at 20 of the lower explosion limit Alarm resetting via button Specifications Operating voltage Current consumption Contact rating relay 1 amp 2 Ambient temperature Sensor heating power Dimensions W x Hx D 8 5 to 14VDC max 200mA 120VAC 1A 24VDC 1A 0 C to 60 C 750mW 120 x 120 x 30 mm Gas Detector 230V GM MEIBU 230V Compact gas detector with sensor technology for detection of methane natural gas propane and butane available in cylinders in houses or apartments Sy Features Display of operating
565. us technology using Apollo Discovery protocol Specifications Operating voltage Ambient temperature Protection class Dimensions W x H x D Colour Weight Cross references Features Operating instructions by means of symbols European standard Activation by breaking the glass plate Easy to replace glass plate DIL switch for setting the physical address between 01 and 126 supplied through loop voltage 0 C to 60 C IP53 87 x 87 x 52 mm flame red RAL 3000 190g Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 173 249213 Glass for MCP Series 10pcs G21140 35 214021 Loop Interface LIF64 1 169 BB072001 SAM 0720 01 0100 Chapter 17 Manual Call Points 173 245019 Surface Mount Box MCP5A SR The box made of red plastic is used for surface mounting of Manual Call Points MCP5A RP07Fx and MCP5A RPO8Fx Specifications Protection class IP24 Dimensions W x H xD 87 x 87 x 32 mm Colour flame red RAL 3000 Weight 52g Cross references Page Art Nr Name Type 171 245042 Manual Call Point Red 200 Flexi MCP5A RPO7FF 170 245040 Manual Call Point Red 200 Glass MCP5A RPO7FG 172 245043 Manual Call Point Red 200 ISM Flexi MCP5A RPO8FF 170 245041 Manual Call Point Red 200 ISM Glass MCP5A RPO8FG 245012 Surface Mount Box MCP5A SR3T The box made of red plastic is used for surface mounting of the M
566. val EECS ATEX 0073 JET av E 178 Chapter 18 Devices for Hazardous Areas 241024 242036 LPCB 010q Cross references Page Art Nr Name Type 26 214034 BCnet Sectional Control Panel Extension BCE216 3LG 32 214234 Fire Detection Control Panel Module LG BCM216 3ELG 179 246027 IS Detector Base Anal Apo ASEX 45681 215 35 214021 Loop Interface LIF64 1 180 228005 Protocol Interface Anal XP95 Apo API 55000 855 180 228004 Safety Barrier Anal XP95 Apo AES 29600 098 IS Optical Smoke Detector Anal XP95 Apo AOEX 55000 640 Addressable smoke detector for hazardous areas operating on the light scatter principle for application on the ADM loop using Apollo Discovery protocol with an optical sensing cham ber and of extra flat design suitable for indoor mounting The detector must always be con nected via a Safety Barrier Anal XP95 Apo approved for the respective detector and a Protocol Interface Anal XP95 Apo Particular attention must be paid to the compliance with country specific regulations DN ST Features Constant sensitivity HK HK I Insect screen Specifications Operating voltage Ex classification Current consumption Ambient temperature Intelligent evaluation algorithms compensate for the impact of contamination of the optical sensing system Thereby the re sponse sensitivity of the detector is kept constant for a long time thus constituting another effective measure for preventing false alarms P
567. very 198 Chapter 20 Special Detectors Specifications Operating voltage Current consumption at 24V Current consumption test filter Ambient temperature Relative humidity Dimensions W x H x D Dimensions W x H x D Protection class Colour Weight Approval 15 to 32VDC 17mA quiescent 38 5mA active max 500mA 30 C to 55 C max 95 no condensation 190 x 254 x 84 mm Smoke Detector 6500 200 x 230 x 10 mm Reflector 5 to 70m IP54 cream 1 8kg VdS G205034 EN 54 12 244020 Cross references Page Art Nr Name Type 155 249028 Address Module Conv Apo NG60 1 119 249020 Address Module Conv NG58 1 35 214020 Conventional Detector Interface GIF8 1 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 146 249075 Conventional Zone Module Anal XP95 Apo GWM 55000 845 8 210110 Detector Zone Extension MGE8 1 7 210122 Fire and Evacuation Panel BC016 2 INT 1 6 210102 Fire Detection Control Panel BC016 1 INT1 1 210205 Fire Detection Control Panel BC06 1 INT1 3 210209 Fire Detection Control Panel BC06 2 INT 1 143 249072 Monitor Module Anal XP95 Apo UMS 55000 841 200 244025 Multi Mount Kit 6500 BEAMMMK 200 244024 Reflector 6500 75 100M BEAMLRK 201 244026 Surface Mount Kit 6500 BEAMSMK 4 210210 Zone Extension Board ZEB2 1 Beam Smoke Detector Anal SS 6500 Beam smoke detector for the surveillance of open areas with a range of 5m to 70m with ac cessories up to 100m consisting of a combined transm
568. voltage Current consumption at 24V ImA Ambient temperature 10 C to 60 C Relative humidity 10 95 Dimensions L x W x H 93 x 20 x 110 mm Colour green Weight 100g Approval EECS ATEX 0073 Cross references Page Art Nr Name Type 177 240025 IS Ionisation Smoke Detector Anal XP95 Apo AIEX 55000 540 178 241024 IS Optical Smoke Detector Anal XP95 Apo AOEX 55000 640 178 242036 IS Thermal Detector Anal XP95 Apo AWEX 55000 440 180 228004 Safety Barrier Anal XP95 Apo AES 29600 098 z eam and 169 BB072001 SAM 0720 01 0100 241025 228006 169 BB072001 SAM 0720 01 0100 Chapter 18 Devices for Hazardous Areas 181 IS Optical Smoke Detector Anal 200 SS 2251EIS Addressable smoke detector operating on the light scatter principle for application on the ADM loop using System Sensor 200 protocol with an optical sensing chamber and of flat design suitable for mounting in hazardous areas The smoke detector can be mounted in a detector base B501 The detector must always be connected via a Safety Barrier Anal 200 SS approved for the respective detec tor and a Protocol Interface Anal 200 SS Particular attention must be paid to the compliance with country specific regulations Intelligent evaluation algorithms compensate for the impact of contamination of the optical sensing system Thereby the re sponse sensitivity of the detector is kept constant for a long time thus constituting another ef fective measure for preventin
569. w Withdrawal from contract Buyer may withdraw from the contract only in the event of delays caused by gross negligence on the part of Seller and only after a reasonable period of grace has elap sed Withdrawal from contract shall be notified in writing by registered mail Irrespective of his other rights Seller shall be entitled to withdraw from the contract a if the execution of delivery or the inception or continuation of services to be ren dered under the contract is made impossible for reasons within the responsibility of Buyer and if the delay is extended beyond a reasonable period of grace allowed b if doubts have arisen as to Buyer s creditworthiness and if same fails on Seller s request to make an advance payment or to provide adequate security prior to deli very or c if for reasons mentioned in 5 4 the period allowed for delivery is extended by more than half of the period originally agreed or by at least 6 months For the reasons given above withdrawal from the contract shall also be possible in respect of any outstanding part of the delivery or service contracted for If bankruptcy proceedings are instituted against any contracting party or an applicati on for bankruptcy proceedings against that party is not granted for insufficiency of assets the other party may withdraw from the contract without allowing a period of grace Without prejudice to Seller s claim for damages including expenses arising prior to a la
570. without detec tor base Specifications Dimensions x H 103 x 2 mm Colour cream RAL 9001 Cross references Page Art Nr Name Type 229 355102 Sounder FB 12 24V White Multitone DBS 1224B4W Lid for Detector Base Sounder White 45681 292 White plate for covering an addressable detector base sounder Series XP95 if no detector is inserted 169 BB072001 SAM 0720 01 0100 359021 359022 359023 169 BB072001 SAM 0720 01 0100 Chapter 26 Accessories for Optical and Acoustic Devices 253 Specifications Dimensions x H 100 x 9 mm Weight 20g Colour white Cross references Page Art Nr Name Type 236 355134 Sounder Strobe WB XP95ISM White Clear Alert 45681 330 238 355136 Sounder Strobe WB XP9SISM White Clear DIN 45681 334 237 355135 Sounder Strobe WB XP95ISM White Clear Slow Whoop 45681 332 233 355133 Sounder WB XP95ISM White Alert 45681 277 234 355132 Sounder WB XP95ISM White DIN 45681 300 233 355131 Sounder WB XP95ISM White Slow Whoop 45681 290 Lid for Detector Base Sounder Red 45681 293 Red plate for covering an addressable detector base sounder Series XP95 if no detector is inserted Specifications Dimensions x H 100 x 9 mm Weight 20g Colour red Cross references Page Art Nr Name Type 236 355134 Sounder Strobe WB XP9SISM White Clear Alert 45681 330 238 355136 Sounder Strobe WB XP95ISM White Clear DIN 45681 334 237 355135 Sounder Strobe WB XP95ISM White Clear Slow Whoop 45681
571. wsuit upon withdrawal from contract any open accounts in respect of deliveries made or services rendered in whole or in part shall be settled according to contract This provision also covers deliveries or services not yet accepted by Buyer as well as any preparatory acts performed by Seller Seller shall however have the option alternatively to require the restitution of articles already delivered Withdrawal from contract shall have no consequences other than those stipulated above Disposal of waste electrical and electronic equipment 10 1 The Buyer of electrical electronic equipment for commercial purposes incorporated in Austria is responsible for the financing of the collection and treatment of waste electrical and electronic equipment as defined by the Ordinance Regulating the Handling of Waste Electrical Equipment if he is himself the user of the electrical e lectronic equipment If the Buyer is not the end user he shall transfer the full finan cial commitment to his customer by agreement and furnish proof thereof to the Seller 10 2 The Buyer incorporated in Austria shall ensure that the Seller is provided with all 10 3 11 10 1 information necessary to meet the Seller s obligations as manufacturer importer par ticularly according to 11 and 24 of the Ordinance Regulating the Handling of Waste Electrical Equipment and the Waste Management Act The Buyer incorporated in Austria is liable vis a vis the Seller fo
572. x H x D 130 x 145 x 55 mm Colour flame red RAL 3000 Weight 250g Cross references Page Art Nr Name Type 164 245402 Manual Call Point EN 54 Red Anal Apo HFM 3 32 02 157 245302 Manual Call Point EN 54 Red Conv HFM 3 11 02 160 245362 Manual Call Point Red Anal SS HFM 3 22 02 157 245356 Manual Call Point Red Conv HM 3 11 01 02 Protective Cover V2A for Manual Call Point Blue WG BLAU E 1 Blue powder coated protective cover made of V2A stainless steel used as supplement for ma nual call points installed in open areas Features Top side and lateral rain protection Mechanical protection Cable entry from back side or alternatively bottom side through the cable gland of the manual call point Specifications Dimensions W x H x D 130 x 145 x 55 mm Colour sky blue RAL 5015 Weight 250g Cross references Page Art Nr Name Type 164 245395 Manual Call Point Blue Anal Apo HM 5 32 02 02 165 245429 Manual Call Point Blue Anal Apo HM 5 32 18 02 161 245372 Manual Call Point Blue Anal SS HM 5 22 02 02 161 245415 Manual Call Point Blue Anal SS HM 5 22 18 02 158 245352 Manual Call Point Blue Conv HM 5 11 02 02 159 245417 Manual Call Point Blue Conv HM 5 11 18 02 168 Chapter 17 Manual Call Points 249636 249631 Protective Cover V2A for Manual Call Point Yellow WG GELB E 1 Yellow powder coated protective cover made of V2A stainless steel used as supplement for manual call points installed in open areas
573. x H x D 420 x 520 x 120 mm Colour of cabinet grey white RAL 9002 Colour of front foil light grey RAL 7035 Weight 6 2kg without optional componentries Cross references Page Art Nr Name Type 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT1 7 210122 Fire and Evacuation Panel BC016 2 INT I 6 210102 Fire Detection Control Panel BC016 1 INT 1 12 214008 Fire Detection Control Panel BC216 1 INT 1 16 214308 Fire Detection Control Panel BC216 1S INT 1 37 214024 LED Display Field LAB48 1 38 214030 LED Display Field LAB48 2 38 214032 LED Display Field LAB48 3 39 214036 LED Display Field LAB48 4 73 252012 Remote Tableau Drive Unit PTU288 1 287 310002 Stand by Battery 12V 18Ah 252011 LED Display Tableau LAT288 1CE The LED Display Tableau LAT288 1CE allows for the design of a display for the optical si gnalling of events of a Fire Detection Control Panel Series BC016 or BC216 or of an Extin guishing Control Panel Series LC216 via parameterisable LED indicator pairs The tableau Specifications Dimensions W x H xD Colour of front foil Weight incl PTU288 1 housing consists of a 19 rack mount case made of powder coated steel sheet providing space for the instal lation of up to three LED Display Fields LAB48 x and the Remote Tableau Drive Unit PTU288 1 The front side of the case is sealed with a light grey pla stic foil which has six windows integrated for labelling of LE
574. xSurv In Anal 200 SS M220E Surface Mounting Box for M200 SS M200SMB The plastic mounting box is designed for the surface mounting of a module Series M200 The box is prepared for wall mounting Specifications Ambient temperature 20 C to 60 C Dimensions L x W x H 132 x 137 x 48 mm Colour cream transparent smoke coloured Weight 235g Cross references Page Art Nr Name Type 98 249103 Control Module 1xSurv Out Anal 200 SS M201E 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 97 249102 Module 2xSurv In 1xRel Out Anal 200 SS M221E 96 249100 Monitor Module 1xSurv In Anal 200 SS M210E 96 249101 Monitor Module 2xSurv In Anal 200 SS M220E Surface Mounting Box for MS200 SS M200SMB KO The plastic mounting box is designed for the surface mounting of a module Series M200 A protected cable entrance is possible with the help of 5 integrated cable glands Specifications Ambient temperature 20 C to 60 C 118 Chapter 13 Acessories for Series 300 ECO1000 200 500 249117 249004 Dimensions L x W x H 132 x 137 x 48 mm Colour cream transparent smoke coloured Weight 250g Cross references Page Art Nr Name Type 98 249103 Control Module 1xSurv Out Anal 200 SS M201E 100 249104 Conventional Zone Module Anal 200 SS M210E CZ 97 249102 Module 2xSurv In 1xRel Out Anal 200 SS M221E 96 249100 Monitor Module 1xSurv In Anal 200 SS M210E 96 249101 Monitor Module 2xSurv In Anal 200 SS M220E Surface M
575. y Module NTM2408 1 1 0 2 2 cece cece e eee teen eee tn eee e ee een nee eeee 292 317030 Power Supply Housing NTG24 1 esrssunnnnennnannenennnnuenennnannerennnenennnanuenenannueser 292 317031 Power Supply Housing NTG24 1 CE esrennnannennnnnnnennnannenennnanenrnnnuenenannuverensner 293 317032 Power Supply Housing NIGD vrede 293 317033 Battery Bracket BK24 1 nara iee AARE EEA AEE base ere en 294 229010 Voltage Stabiliser 24 VDC STAB24 1 oroonenennnnnvenananenennnnnvvernnnanvenrnaeeveenaanuever 294 Software 218008 Parameter Setup Software PARSOFT 2 srnununvenananvnennnnnuuerennunnenennnuunennnnueerenr 295 218041 Alarm Monitoring Software License ALVIS F erennnnnnennnnnnnennnnnnenenananvenennsaueenner 295 218044 Alarm Monitoring Interface License BC216 ALVIS BC216 occ cece eens 296 218045 Alarm Monitoring Interface Licence ALVIS LBC1000 rerennnnnnnvnnananenennnrnvenrnnsnveenr 296 Tools 249059 Test Module 100 200 SS MOD400R roevennnnenennnnnvernnnvevenanrevevenanauvereanueueneenr 297 249036 Test Gas Can SOLOA3 001 vessavevieketasnetetesee nes vekke geek Mk ees bedere eee 297 249051 Smoke Detector Test Tool SOLO330 rrennnnnnenenanannennnnuanenananuueennnnuenennsuuuennnr 297 249052 Detector Removal Tool SOLO200 avvvenvuvnnveennnreavennnuenrennnnuennennnnernrennnnennneen 298 249053 Telescopic Pole SOLO100 oo onc pene ere eee be the Dede ep lo ey eee 10 298 249054 Extension Pole SOLO101 2 2 0 0 ooo ee
576. y is used as display and operating unit in BCnet sectional control panels which are composed of fire detection control panel modules Functions specifications and cross references correspond to the Display and Operating Front Panel ABP216 1E INT1 The labels of display and opera ting elements are in German language Approval VdS G201017 Display and Operating Front Panel ABP216 1E NL1 Functions specifications and cross references correspond to the Display and Operating Front Panel ABP216 1E INT1 The labels of display and operating elements are in Dutch language Approval VdS G201017 169 BB072001 SAM 0720 01 0100 214020 214021 169 BB072001 SAM 0720 01 0100 Chapter 3 Fire Detection Control Panels Series BC216 35 Conventional Detector Interface GIF8 1 The Conventional Detector Interface GIF8 1 supports 8 detector zones in addressable con ventional technology in Fire Detection Control Panels Series BC216 Features 8 detector lines in addressable conventional technolo gy that can be individually configured as detector zo ne for fire alarm for the connection of manual call points as well as automatic detectors with or without alarm verification detector zone for technical messages for the connection of surveillance and status detectors detector zone for fault messages for the connection of fault detectors and detector zone for special functions e g for con trol commands Individual detector id
577. ystem failure of a BCnet sectional control panel redundant alarm The NNUS5 1 is installed in the BCnet sectional control panel that is connected to the transmitting device to the fire brigade Features Meets the requirements of NORM F3000 con cerning redundancy Line monitored BCnet circular redundant alarm line 40 Chapter 3 Fire Detection Control Panels Series BC216 Surveilles up to 126 BCnet members of a decentralised Fire Detection Control Panel BCnet216 Specifications Current consumption at 24V typ 4mA BCnet redundant alarm line 2 core circular line Line resistance max 1000Q Ambient temperature 5 C to 50 C Dimensions L x W x H 75 x 40 x 15 mm Weight 40g Cross references Page Art Nr Name Type 29 214105 BCnet Sectional Control Panel No Op BC216 3CE 25 214005 BCnet Sectional Control Panel No Operation BC216 3 23 214056 BCnet Sectional Control Panel OP BC216 2 INT 1 30 2149997 BCnet Sectional Control Panel OP BC216 2EPS 36 214022 Fire Brigade Interface FWI2 1 27 214108 Fire Detection Control Panel BC216 1CE INT 1 214003 Auxiliary Case for BC216 GEH216 4 Wall mount cabinet made of powder coated sheet steel for stand by batteries and or auxiliary modules as supplement to Fire Detection Control Panels Series BC216 in standard wall mount cabinets The cabinet is prepared for the installation of Two stand by batteries 12 V max 22Ah at the cabinet bottom and 4 Mounting Brackets BW216 1 for