1. 9 2 Additional Power Supply The basic configuration with one ACC and two DRls includes one power supply with a capacity of 150 W If this should not be sufficient for additional DRIs an ad ditional 150 W power supply has to be installed The system then can provide an output power of 300 W in total Load UB UB Battery mal function NTC 4k7 X11 9 Seit B A 3 2 1291 2 76 5 43 2 1 X11 9 MIA 9 8765 43 2 1 eed urre at Sensor Ba Sensor B_N WG of we ion Er Ge NC ptt Inte D 24 V ov F2 B F2 B T6 3A T6 3A B B 3 2 PE DUNN PE L1 LIN N 1 Protect battery with external fuse min 12 A max 20 A 2 Power supply 24 V 150 W V24230 Z6 A1 set to slave 3 Power supply 24 V 150 W V24230 Z6 A1 set to master Fig 4 Additional power supply In case of parallel power supply connections an external protection fuse is neces sary for the battery connection that matches the conductor cross section For example Protect line with 4 mm with a max of 12 A Protect line with 6 mm with a max of 20 A The lines to the connections battery battery UB and UB should be at least 2 5 mm External loads have to be protected with a fuse that matches the conductor cross section For example a line with a cross section of 2 5 mm can be protected with max 20A 19 Siemens Building Technologies Fire Safety amp Secu
2. gt one more entry Choose in the field lt Status gt the event Tamper Switch inactive Add in lt Status Description gt gt a unique status description Choose in lt Alarm Restore gt Restore If required choose in lt Symbol Name gt a symbol for display a plan or create a special symbol Save alarm class gt The minimal configuration of alarm class is done Assign alarm class Follow these steps to assign an alarm class to a tamper switch input of the device housing 1 Choose menu System authority Components ACC controller 2 Choose the device which is connected to the tamper switch 3 Choose and save in lt Alarm Class gt the alarm class created in the steps above 23 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Cables and Lines 10 Cables and Lines 10 1 Calculation Tool for Cable Cross Sections D 24 If remote SiPass components are to be connected to the ACC the following calculation tool might be helpful Use a shielded weak current cable type IY St Y for all bus lines The cross sections of the leads have to be chosen by considering the following criteria power consumption of the connected system components modules e Line length e ntermittently needed switching current e g relay exits However a min diameter of 0 6 mm per lead is required The supply voltage in all system components modules may not fall
3. 0000000000000nnnnnnnnnnnnnnnn 10 5 1 SR lee E EE ae 10 5 2 a lo OH eo Sete ee a A AA E AEEA AEA A AA 11 6 A e EE 12 7 AC5160 Structure uuuu 0uu 000adanaaannnnananannnaudnn anna nnan anna nn aaea aii 13 7 1 Dimensio NSn aa a a er a aan en nf nel 13 7 2 Mechanical SIrUCtU re oii ieccsdiccctesavetcactaiac conta a aaa a aa aa akaaka 13 7 3 Expansion Options nn 14 8 JEC UE de BEE 15 8 1 PrOCCOUNG 22 200 Seis et A ee E ae Rae talc A 15 8 2 Installing Optional DRIS ursnsessseennsnennnnnennnnnnnnnnnnnnnnnnnnnnannnn 16 8 3 AFI5100 or AFO5100 Installaton 16 9 IEN CU de Vu WEN 17 9 1 Power Supply Overview sseessessssessessseessisesrtrntttnstnsnnutnnnnnsnn neen neen 18 9 2 Additional Power Supply ccccccccsseeeeeceeceeeeeeeaeeeeeeeseeeeseaeeeeaeeeeeeeeaas 19 9 3 Installing the Battery cececcceeeeseceeeeeeeceeeeeeeeeeeeneeeeeeeneeaeeeeeteeeeeeenenaes 20 9 4 PE Grounding Concept 20 9 5 Power Supply Connechon nen 21 9 6 AGG GONNCCHON EE 22 9 7 RISIKEN 22 9 8 AFI5100 AFO5100 Connection ccccccccccccceeccceeeeeeeeeeeeeeeeeeeeeeeeeeneneeeess 22 9 9 Configuration of ACC Tamper Switch Input 23 10 Cablessand LION ee ees AN Ae EEN 24 10 1 Calculation Tool for Cable Cross Gechons seen een 24 3 Siemens Building Technologies Fire Safety amp Security Products 04 2008 4 Siemens Building Technologies Fire Safety amp Security Products 04 2008 1 Important Information il O
4. 4V 150 W power pack V24230 Z6 A1 1 2 Covers for battery poles C24243 A100 C12 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Scope of Delivery 3 Scope of Delivery 8 Installation Instructions ACC 010 Advanced Central Contr RIM 010 DRI 24VDC 24V 150 W power pack Enclosure base plate Enclosure shell Installation kit a aa sch NM sch sch Siemens Building Technologies Fire Safety amp Security Products 04 2008 Technical Specifications 4 Technical Specifications Electric Power supply connection 230 V AC 10 to 15 50 Hz Supply voltage 24 V DC System incl battery charging current Max 5 A per 150 W power pack Battery capacity Max 25 Ah per battery Power consumption ACC Max 10 W DRI Max 25 W AFI5100 Max 50 W AFO5100 Max 10 W Power pack Fastener DIN rail mount TS35 Power supply connection Spring loaded clips max 1 5 mm Output and signal clips Spring loaded clips pluggable max 2 5 mm Operating conditions Max permissible ambient temperature 10 to 55 C Protection rating EN60529 IP30 Rel humidity F lt 95 Design Cabinet dimensions W x H x D in mm 500 x 750 x 200 Color RAL 7035 light gray Material Steel sheet EN 50133 Identification class 2 with AR6181 MX Identification class 3 with AR6182 MX Access class B Environmental class 2 IP class IP30 for AC5160 IP65 for AR618n MX IK class IK04 card reader Siemen
5. SIEMENS SiPass AC5160 Installation Instructions Building Technologies Fire Safety amp Security Products Lieferm glichkeiten und technische nderungen vorbehalten Data and design subject to change without notice Supply subject to availability 2008 Copyright by Bewator AB a Siemens company Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor Der Empfanger erkennt diese Rechte an und wird dieses Dokument nicht ohne unsere vorgangige schriftliche Ermachtigung ganz oder teilweise Dritten zuganglich machen oder auBerhalb des Zweckes verwenden zu dem es ihm Ubergeben worden ist We reserve all rights in this document and in the subject thereof By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him Contents 1 Important Information nreenssernenneennnnnnennnnnnnnnnnnnnnnnnnnnnn nennen anne en 5 2 Ordering Information 2244440044000nnnnannnnnnnnnannnnnnannnnnnnnnnnnnnnannnnnnnnnn 7 3 Scope of Delivery 2 ana 8 4 Technical Specifications uer242n4ennn0nnnennnnnnnennnnnnnnn nnmnnn nnmnnn nnn 9 5 Standards and Guidelines 222000000000000
6. be connected to the DRI 24 V power supply e FLN connection to ACC e One or more card readers e Door monitoringcontacts e Door latch A detailed description of the connections is listed in the DRI installation and user manual document number A24205 A335 B246 98 AFI5100 AFO5100 Connection A detailed description of connecting the AFI5100 and AFO5100 is listed in the fol lowing documents e IPM User Manual document number A24205 A335 B245 e OPM User Manual document number A24205 A335 B244 22 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Installation 9 9 Configuration of ACC Tamper Switch Input Create alarm class Follow these steps to create the new alarm classes BOO Sr Su bg Nas Choose menu system alarm classes Enter a unique name Choose type Controller Choose in lt Alarm Handling gt the option Requires Acknowledging Choose alarm priority and alarm sound Activate in lt Alarm Options gt Restorable Alarm Add in lt Current Defined Alarm Status gt an alarm Choose in the field lt Status gt the event Switch tamper active Add in lt Status Description gt a unique status description e g The housing tamper is triggered Choose in lt Alarm Restore gt Alarm If required choose in lt Symbol Name gt a symbol for display a plan or create a special symbol Add in lt Current Defined Alarm Status
7. below 18 V DC With a min permissible battery voltage of 21 V this yields a max voltage drop of 3V DC pertaining to the entire line length Caution Total length line to and back Resistance values for the conductor cross section calculation Line length 100 m Wire 0 6 mm 0 28 mm gt 6 5 Ohm Wire 0 8 mm 0 56 mm gt 3 6 Ohm Calculation formulae Voltage drop with applied current L I L Line length of line leading to unit and xA back in meters I Current in ampere Conductor cross section with applied current x spec conduct value for copper and 0 5 V voltage drop along line a Q mm2 A Lead cross section in mm U Voltage in V Siemens Building Technologies Fire Safety amp Security Products 04 2008 25 Siemens Building Technologies Fire Safety amp Security Products 04 2008 26 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Issued by Bewator AB SE 171 24 Solna Sweden www buildingtechnologies siemens com 2008 Copyright by Bewator AB a Siemens company Data and design subject to change without notice Supply subject to availability Document no A24205 A335 B219 Edition 04 2008
8. bient temperature of the central control unit must be between 10 and 55 C humidity should not exceed 75 if possible 95 for very short periods no condensation e Use a separate electrical circuit with a specially marked fuse red to supply a c voltage to the unit e Please ensure that switching off other tools or devices does not disconnect the electrical circuit to the unit Attach a note in the cabinet about the location of the power supply fuse low voltage distributor number mains fuse number Please ensure that the fuse is easy to access Please ensure that the cable duct covers the cable entry opening e Use only shielded cables with extra low voltage for all lines leading to the inside of the controller Connect the cable shielding to all connection points Ground cable shielding only on one side e The precautions applicable for C MOS technology are to be applied to activities involving server circuit boards and soldering e Never install a live circuit board Siemens Building Technologies Fire amp Security Products 04 2008 2 Ordering Information Ordering Information Hem AC5160 cabinet with ACC 2 x DRI and 24V 150 W power pack Accessories not included in delivery scope RIM 010 DRI 24 V DC Order No 6FL7820 8BA16 6FL7820 8CA10 Weight approx kg 21 3 AF1I5100 6FL7820 8CB10 AFO5100 6FL7820 8CC10 Battery 12 V 25 Ah GBI 13013 9 6 Battery 12 V 6 5 Ah GBI 13206 2 3 2
9. cessing is done in the AC5100 ACC e Power supply That part of an access control system which provides power for the operation of the systems or any part thereof e Self protection The AC5160 is tamper protected Methods used to protect an access control system or part thereof against deliberate interference e Programmability The Controller AC5100 is the ability to receive and store pre set rules e Access Point Control An access point is the location at which access can be controlled by a door turnstile or other secure barrier The access point control is in this system done with the combination of the AC5100 the DRI ADD5100 and the reader AR618x MX or AR618x RX e Recognition Done with a unique card presented to the reader AR618x MX or AR618x RX Display for the User The display for the user are the LED s of the readers AR618x MX and AR618x RX Annunciation Presentation of the information to the management or other systems The Sys tem provides this information to the SiPass integrated PC SW can be seen in the SiPass integrated clients e Communication with other systems Interfaces to other systems are described in the SiPass integrated User Manu als 11 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Description 6 Description 12 The AC5160 is a cabinet for the basic components of the SiPass access control system This cabinet can be expanded with additional componen
10. ction Strain relief Fig 6 Power supply connection mains cable strain relief WARNING The EC Conformity is invalid if the mains power line 230 V is not equipped with a strain relief clamp e Insert the mains power supply lines to the battery from the bottom into the cen tral controller unit e Attach all cables and lines using cable ties at the provided cable entries to relief the strain e Remove the sheath of the cable one centimeter behind the cable tie e Connect the cable leads to the corresponding terminals of the power supply without too much slack black to L blue to N Protect both cables by tying both with a cable tie approx 1 cm in front of the connection terminals reason If a cable breaks contact with metal parts has to be prevented The green yellow lead is attached to the grounding terminal on the rail mount From there a cable leads to the PE connection of the power supply 21 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Installation 9 6 ACC Connection The following have to be connected to the ACC 24 V power supply e Ethernet TCP IP cable pin designation 10 100 e Tamper contact pin designation tamper e FLN devices to one or several FLN inputs Beginning with FLN 4 A detailed description of the connections is listed in the ACC installation and user manual document number A24205 A335 B243 9 7 DRI Connection The following have to
11. dure Installation Follow these steps to install the unit and check off items you finished IT OF OOO UC OOO OO OOOO OT U Determine installation location for controller Pay close attention to the cable entry points Unpack the AC5160 Remove enclosure shell from the base plate The enclosure shell is attached to the base plate with a screw Mark drill holes for the base plate Drill 6 plug holes 8 mm for the base plate and insert plugs Screw in both upper screws until only approx 10 mm are visible Attach base plate to both upper screws Screw in the two lower and center screws to fasten the base plate and then tighten all 6 screws Insert cable Strip the insulation from the peripheral cable and attach the cable ties to the indicated positions to ease the strain on the cables Place sheath wires of shielding on grounding screws Place peripheral cables directly on components Strip power cable 230 V and connect to power supply see section 9 5 Power Supply Connect ground Check wiring Connect cover contact to ACC Insert battery and connect to the power supply Turn on system Connect PC to TCP IP interface of ACC Configure ACC Connect FLN components of FLN bus to a PC by using a RS232 485 converter Configure FNL components with the FLN Configurator program Start up the system Check all system functions If necessary analyse and eliminate errors troubleshooting Place
12. er supply from the unit using the intended disconnecting device when replacing the power pack and when working on 230 V parts Also clamp off the battery at its connection poles 17 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Installation 9 1 Power Supply Overview 1 1 In case of several parallel connected power ryt supplies always use an external fuse between 12 d ri meer 1 i N and 20 A Se 5 fat 1 To loads Slavet X8 7 Slave1 X8 2 Slave1 X11 6 i Slave2 X8 7 Slave2 X11 77 Slave2 X8 2 Joll gt 2 22 deis Vgl Aak RSB 9 8 7 6 5 4 3 2 1 1 9 8 7 6 15 4 3 2 1 X11 H x8 3 Interference Rest Power OK gn oO Battery malfunction yl Sensor malfunction yl O Slave Master 1 Battery temperature sensor Siemens Matsushita NTC K164 4 7k K B57164 K472 K PE FPE L N 2 Maintenance free lead gel batteries 2 x 12 V 3 Battery fuse F2 for output X8 10 T6 3AH250V 5 x 20 4 Mains fuse F1 T4AL250V 5 x 20 5 Batterie with external fuse Fig 3 Power supply 18 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Installation
13. es The module features 16 inputs and 16 outputs and is also connected to the ACC via FLN The AFO5100 is not part of the basic configuration Please refer to the corresponding user guide for a detailed description of these modules The basic configuration consisting of power supply ACC and two DRIs can be expanded by the previously mentioned components The following configurations are possible e Six DRI s in total The AC5160 provides 5 installation slots for simple installation of the DRIs This means that one DRI needs to be installed on top of another DRI when expand ing the basic configuration to the maximum of 6 DRIs e Additional 150 W power power supply see chapter 5 3 e AFI5100 The AFI5100 Input Point Module can be installed on top of the ACC using the included spacer bolts The fully expanded configuration may not exceed the max output power of the power supply e AFO5100 The AFO5100 Output Point Module can be installed on top of the ACC using the included spacer bolts as well The fully expanded configuration may not ex ceed the max ourpur power of the power supply Siemens Building Technologies Fire Safety amp Security Products 04 2008 AC5160 Structure 7 AC5160 Structure 7 1 Dimensions g E Di E J amp amp Gm a H Ei E x Hi SR E S Ze 2 1g cot A g ME rr 500 200 Ba
14. installation instructions inventory list configuration and structure plans into the controller Carry out acceptance procedure Close cabinet and attach seal 15 Siemens Building Technologies Fire Safety amp Security Products 04 2008 Installation 8 2 Installing Optional DRIs The AC5160 is already equipped with two DRIs Three optional installation slots for additional DRIs are available To install an additional DRI screw four spacer bolts to the corresponding installation slot Fasten the DRI to the spacer bolt of the in stallation slot If you would like to stack two DRis use four additional spacer bolts to attach the lower DRI Then attach the second DRI with screws 8 3 AFI5100 or AFO5100 Installation 16 The AFI5100 or the AFO5100 can be installed on top of the ACC Remove the screws used to attach the ACC to the base plate and replace these with the corre sponding spacer bolts Remove the AFI5100 or the AFO5100 from the package and screw to the spacer bolts Siemens Building Technologies Fire Safety amp Security Products 04 2008 Installation 9 Installation Risk of explosion when improperly replacing battery Only use original replace WARNING ment parts or those recommended by the manufacturer Used batteries are hazardous waste and have to be disposed accordingly Only an authorized electrician may connect the system to the 230 V power supply Disconnect the 230 V pow
15. nly authorized personnel may assemble and install the system Your attention is drawn to the fact that the contents of these Installation Instructions are not part ofa previous or existing agreement commitment or statutory right and do not change these All commit ments on the part of Siemens are contained in the respective sales contract which also contains the il complete and solely applicable warranty conditions These warranty conditions in the contract are neither extended nor limited by the contents of this Manual Should you require any further informa tion or should particular problems occur that are not handled in sufficient depth in these Installations Instructions help can be requested through your local Siemens office or representative Please read and comply with the following notes before assembling and installing the unit e Please ensure that the controller is installed in a clean room Please ensure that the central control unit is protected from damaging environmental influences such as direct sun exposure operation dependent vibrations dust etc e Never install the controller close to heaters and sinks Avoid the proximity of sources of electrical or mechanical interferences If the controller is installed in an enclosed space such as behind paneling or in small niches please ensure sufficient ventilation Please use electrically conducting floor coverings to minimize electrostatic charges e The permissible am
16. rity Products 04 2008 Installation 9 3 Installing the Battery Install the battery and then connect the battery to the power supply The battery connection wires are not included with the controller Note the following when installing the battery e In case of a parallel connection of two power supplies the battery wire has to be protected with an external fuse e The fuse may not exceed the max value of the total current of 12 A e Be very careful when connecting the batteries Ensure poles are assigned cor rectly Only use battery types intended for this application e Attach the battery pole covers before assembling the enclosure shell To power pack bl Battery 1 Battery 2 12 V 25 Ah 12V 25 Ah Fig 5 Installing and connecting battery 9 4 PE Grounding Concept 20 The AC5160 is a protection class 1 device The measures and actions required by protection class 1 devices specify that the PE is to be connected to the mains cable With the AC5160 the PE is firmly at tached to the grounding terminal The PE is connected with the device via the grounding terminal On the other side of the grounding terminal a green yellow line leads to the power pack This ensures proper protection is provided protecting health and life Siemens Building Technologies Fire Safety amp Security Products 04 2008 Installation 9 5 Power Supply Conne
17. s Building Technologies Fire Safety amp Security Products 04 2008 Standards and Guidelines 5 Standards and Guidelines 5 1 EU Directives This product complies with the requirements of the European Directives 89 336 EEC Directive of Electromagnetic Compatibility and 2006 95 EEC Low Voltage Directive The EU declaration of conformity is available from Siemens Building Technologies Fire amp Security Products GmbH amp Co oHG 76181 Karlsruhe European Directive 2004 108 EC Electromagnetic Compatibility Compliance with the European Directive 2004 108 EC has been proven by testing according to the following standards Emitted interference EN 61000 6 3 EN 55022 Class B Interference resis EN 50130 4 tance European Directive 2006 95 EEC Low Voltage Directive Compliance with the European Directive 2006 95 EEC has been proven by testing according to the following standard Safety EN 60950 1 10 Siemens Building Technologies Fire Safety amp Security Products 04 2008 5 2 EN 50133 Standards and Guidelines The product meets the requirements of the EN 50133 X Basic functions of the access control system according to EN 50133 1 e Processing The comparing of information with pre set rules to make decisions concerning the granting or denying of access to users and or the comparing of events with pre set rules to produce appropriate actions The pro
18. se plate Front of shell Side of shell Fig 1 Controller enclosure 7 2 Mechanical Structure The AC5160 cabinet consists of a two piece sheet steel enclosure e Base plate e Enclosure shell The enclosure shell is detachable for simple installation and equipped with a tam per contact to detect unauthorized access to the cabinet The power supply is mounted on the base plate by a DIN rail mount One ACC and two DRI boards are also installed on the base plate Further installation slots are available for three additional DRIs Two DRIs can be installed on top of each other when using the included spacer bolts An AFO5100 or an AFI5100 can be installed on top of the ACC as well The DIN rail mount is generously dimensioned and thus can accommodate an ad ditional 150 W power supply The cabinet is prepared for max two 12 V 25 Ah batteries 13 Siemens Building Technologies Fire Safety amp Security Products 04 2008 AC5160 Structure 7 3 Expansion Options 14 Possible configurations at max power consumption of the components Power pack s DRIs AFI5100 AFO5100 1 2 0 1 1 2 1 0 1 4 0 0 2 6 0 0 2 6 0 1 2 6 1 0 When making configurations the max power consumption of the system readers door locks must be taken into account Fig 2 Installation plate Siemens Building Technologies Fire Safety amp Security Products 04 2008 8 Installation 8 1 Proce
19. ts The Advanced Central Controller ACC is one of the basic components It is the central analysis unit for the access control system This unit is connected with the input output boards via the field level network FLN The ACC is equipped with four FLNs TCP IP is used to link to the SiPass Server The Dual Reader Interface DRI is a door module including all necessary inputs and outputs Support of up to two card readers door monitoring inputs e g door frame contact and associated outputs e g door latch The FLN connects the DRI to the ACC The AC5160 includes 2 DRIs Four additional DRIs can be installed into the AC5160 cabinet The basic AC5160 model is equipped with a 24V 150 W power supply If neces sary an additional power supply can be placed in the AC5160 and connected in parallel to the existing power pack master slave operation The AC5160 can be equipped with two 12 volt batteries of a capacity up to 25 Ah each These are connected to and charged by the power supply In the event of a power failure the system is kept online by the batteries The Batteries are not in cluded in the delivery scope The Input Point Module AFI5100 is an input board with 32 inputs and 5 outputs This module also connects to the ACC via the FLN The AFI5100 is not part of the basic configuration The Output Point Module AFO5100 is an output board especially designed for elevator access control but can also be used for general purpos