Safety Manual
Contents
1. Aged L L Circuit principle of output modules with integrated safety shutdown a l The F 3330 F 3331 F 3333 F 3334 F3335 F 3348 F3349 Safety related Digital Output Modules Test routines The modules are tested automatically during operation The main test functions are the follow ing 1 Reading back of the output signal The operating point for a O signal read back is 6 5V In the event of an error the value of the O signal may rise up to this value and this may not be detected 2 Reading of the line diagnosis of the switched on channels F 3331 F 3334 and F 3349 only 3 Application of test patterns and testing for crosstalk walking bit test within the multiple fault occurrence time 4 Reading of the line diagnosis of all channels F 3331 F 3334 and F 3349 only 5 Test of the integrated safety shutdown Principles of Function Chapter 4 Output Modules 3 1 2 3 2 3 2 1 3 2 2 3 2 3 Response of the System on Failures Detected at Safety related Digital Output Modules e If errors are detected on the module it is put to the safe de energized state i e the module is switched off e In the event of external short circuits which cannot be distinguished from internal fail ures the module is also switched off e Line failures are only signalled They do not result in the module being switched off The F 3430 Safety
2. 7 16 PES H41q H51q 8 Flow chart function of the safety tool Program Identification Possibilities The user program can be clearly identified by its code version number This way the associated backup can be clearly determined If the user is not sure which backup is the correct one the backup in question has to be com piled with download option and then the target code is to be compared with the code version 62 106 Safety Aspects ELOP Il Chapter 5 Software of the loaded program But for reloadable code this is only possible if the code had been generated in the following way Do the last change Generate reloadable code compile results in code version A Load control device with code version A Generate reloadable code results in code version B may be iden tical to code version A Load Control device with code version B Each additional code generation without change results in code version B Pah Oo Modification management With the help of modification management the user can administrate his program versions With the help of document administration and the version check the user can document the modifications indicated by the C code comparator Using document administration you can collect various ELOP II objects in one document ob ject in order to commonly print out these documents and to e have a common revision maintenance The supplementary produ
3. connection of input modules output modules Programming Parallel IO modules for increasing the availability Redundant Non safety related Sensors Hardware Depending on the type of the control signal mechanical contact proximity switch intrinsically safe not intrinsically safe input modules type F 3236 F 3237 or F 3238 are used The two sensors operate in a 1002 configuration e g after the response of one of the sensors the safe ty related circuit is switched off at once A discrepancy is indicated after a preset time This function can be included in a function for the input module F 3236 For input modules type F 3237 or F 3238 the block HB RTE 3 is available 77 106 Chapter 5 Software Safety Aspects User Program User program input module F 3236 1002e 311 f Sensor1 control signal 01 12 Sensor2 1002 discrepancy signal m 02 P T 15s discrepancy time current discrep time input signals signals to logic annunciation Sensorl control signal the contol signal is TRUE if both gt _ Sensor amp of the sensors are TRUE ee A IN Q4 discrepancy signal 4 1 TON discrepancy time Pr ET discrepancy signal is TRUE if the sensor signals differ after the discrepancy time has elapsed Function block 1002 and logic of the function block 78 106 Safety Aspects User Program Chapter 5 Software 4 3 3 5 User prog
4. F 3237 8 channel input module HB RTE 3 F 3238 8 channel input module e HB RTE 3 F 3240 8 channel input module F 3248 16 channel input module F 5203 14 bit ring counter F 5220 2 channel counter module HF CNT 3 4 Analog input modules F 6208 Signal converter F 6213 4 channel analogue input module HA RTE 3 F 6214 4 channel analogue input module HA RTE 3 F 6215 8 channel analogue input module F 6216A 8 channel analogue input module with transmitter power source F 6217 8 channel analogue input module F 6220 8 channel thermocouple input mod e HF TMP 3 ule F 6221 8 channel analogue input module HF AIX 3 17 106 Chapter 3 Input modules Safety and availability 2 2 1 18 106 Safety and Availability of Safety related Input Modules General notes on safety related input modules Safety related input modules can be used for both safety related and non safety related inputs Due to their increased complexity some types of the analogue and digital inputs modules have their own 1002 microprocessor system which automatically performs safety related online tests and provides the verified data for the safety related processing module The safety related input modules allow the use of a diagnostic display and thus improved error detection and localization In safety related systems safety related and non interacti
5. 8 Is a supervision of the transmitter voltage supply be implemented 9 Is the building block HF AIX 3 been used in the program see data sheet see data sheet Created by 36 106 Overview of the modules Chapter 4 Output Modules Chapter 4 Output Modules 1 Overview of Output Modules for the H41q H41qc and H51q Systems Module safety non inter loadabil related SW related acting ity function block Digital output modules F 3322 16 channel lt 0 5A digital output module F 3325 6 channel supply module Ex 22 V lt 0 02 A F 3330 8 channel lt 0 5A digital output module F 3331 8 channel lt 0 5A HB BLD 3 digital output module HB BLD 41 F 3332 4 channel lt 2A digital output module F 3333 4 channel lt 2A digital output module F 3334 4 channel lt 2A HB BLD 3 digital output module HB BLD 41 F 3335 4 channel 22 V digital output module Ex lt 0 053 A F 3348 8 channel lt 0 5A digital output module F 3349 8 channel lt 0 5A HB BLD 3 digital output module lt 48 V HB BLD 41 F 3422 8 channel relay module lt 2A lt 60 V F 3430 4 channel relay module lt 4A lt 250 V Analog output modules F 6705 2 channel D A converter k 0 20mMA HZ FAN 32 F 6706 2 channel D A converter 0 20 mA 1 For error display and parameterization of other modes of operation excluding closed circ
6. Chapter 5 Software Safety Aspects User Program 80 106 2 3 User program F 6213 or F 6214 input module Use of HA RTE 3 function block HA RTE 3 Monitoring Analog Testable Input Modules 1305 w dBus No Rack Pos e g 1305 Value le al 4 14Ub feed Bus No Rack Pos red BG Error Value lu TERE p Jused Channels Value 24 i Error Value 24 50 ed TOlerated Differ red Values in 0 1 Value 34 d 0 no Damping 1 Damping Error Value 34 SU ed Tolerated Time Differ red Inputs in ds Value 4a dTest Switch Module Error Value 44 HA RTE 3 dTest Switch red Module aMaximal Test Time in min dTest 4 Channels with 1 Switch 1 0 Other Error Code Pulseu 1 p __dDavailable 1 Safe Reaction Other Error Code Pulsey Eere y_i Cutput Value on Error Error error Code gt O 4 1 feed L 4 20mA O 0 20ma P u ef O Converts in 0 1 l No Conversion Error Code Mod ua qLower Out of range Alarm in 0 1 Error Code red Mod 4 The signals T1 and T2 are directly connected to the first channels of the module F 6213 and F 6214 No other hardware allocation 1 e g 50 2 e g 50 3 7777 if physical value becomes larger in case of danger all four channels of the module 0000 if physical value becomes smaller in case of danger all four channels of the module 4 Values 0 1066 Note numerical values are parameter values at the function block not absolute quantities Comparing element for al
7. F 3236 Safety related Check list No SDIGE F3236 E digital input module 16 channel Version 2 0 32 05 Project data File name of check list Project designation archiving number Position in subrack IOSR Requirements for the project planning of the module and the user program Reci i fulfilled r i equiremen ommen 1 Are the inputs of this module named which perform a safety related function 2 Does a redundant module exist for this module 3 If yes is the redundant module of the same type 27 106 Chapter 3 Input modules Check lists 4 2 F 3237 Safety related Digital Input Module 8 channel F 3237 Safety related digital input module Check list No SDIGE F3237 E 8 channel Version 2 0 32 05 k Project data File name of the check list archiving number Project designation Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment no Are the inputs of this module named which perform a safety related function Is each safety related input evaluated by the HB RTE 3 building block Does a redundant module exist for this module Does an HB RTE building block exist in the user programme for each module or for two redundant modules respectively Are safety related proximity switches connected to the module Are the contacts equipped with resistors 1 k 10 k according to the data sheet Is the line mon
8. gMode Channel 1 0 1 2 Error Channel 1 3 BOOL UINT gMode Channel 2 0 1 2 Error Channel 24 BOOL UINT gMode Channel 3 0 1 2 Error Channel 34 BOOL UINT gMode Channel 4 0 1 2 Error Channel 44 BOOL UINT gMode Channel 5 0 1 2 Error Channel 54 BOOL UINT dMode Channel 6 0 1 2 HB BLD 4 Error Channel 6 BOOL UINT gMode Channel 7 0 1 2 Error Channel 74 BOOL UINT gMode Channel 8 0 1 2 Error Channel 84 BOOL UINT gMax Time Inrush Current in ms Mod Pulse on Error BOOL UINT gMax Time Inrush Current in ms red Mod Pulse on Error BOOL Error BOOL Error Code Mod UINT Error Code red Mod UINT Inputs Bus No Rack Pos e g 1305 Bus No Rack Pos red mod Position of the safety related digital output module and if existing the redundant module des ignated by a four digit decimal number Example 1305 means Cabinet 1 subrack 3 module position 05 Mode Channel n 0 1 2 Allocation by 1 Normal operation Detected error is signalized by H sig nal at corresponding output Error Channel n The out put circuit of the module is closed Allocation by 0 Error evaluation error messages are suppressed Allocation by 2 Only applicable if permitted by the plant specifications Inverted operation i e the output circuit is to be open In safety related control circuits the closed circuit principle must always be appli
9. Chapter 2 Central Modules 1 2 8 106 Overview of the modules Overview of the Central Modules for the H41q H41qc and H51q Systems Module Safety Non interact Kit related ing The H41q and H41qc System Families F 8652 Central module F 8652A double processor 1002 F 8652E F 8653 Central module F 8653E B 4231 Central device kit H41q MS B 4233 1 Central device kit H41q HS B 4233 2 Central device kit H41q HRS B 4235 Central device kit H41qc MS B 4237 1 Central device kit H41qc HS B 4237 2 Central device kit H41qc HRS The H51q System Family F 8650 Central module F 8650A double processor 1002 F 8650E F 8651 Central module F 8651E B 5231 Central device kit H51q MS B 5233 1 Central device kit H51q HS B 5233 2 Central device kit H51q HRS B 9302 IO subrack Overview of the modules 1 2 1 Chapter 2 Central Modules Other Modules for the H41q H41qc and H51q Systems in the Central Device Area Module Kit Safety related Non interact ing Power distribution modules F 7132 4fold power distribution mod e ule F 7133 4fold power distribution mod ule with fuse monitoring Supplementary modules F 7126 Power supply module e F 7130A Power supply module F 7131 Power supply module monitoring with back up batteries for H51q F 8621A Cop
10. e Writing of the user program e Verification of the user program by an offline simulation e Compilation of the user program with the C code generator e The C code is compiled twice by the proven C compiler GNU CC the target code and the comparison code are generated e The target code comparator compares the target code with the comparison code Errors caused by a non safety related PC are detected and signalized e The program thus generated is error free and ready to run It is loaded into the H41q H51q system There the program can be tested by the user and the PES can start safety related operation Use of Standard Function Blocks for Safety related Applications The following list shows the HIMA standard function blocks for safety related applications The description of the function of these function blocks can be found on the internet site www hima com and on the CDROM Standard Function Blocks Independent of the IO Level TUV test Type Function safety non related interacting H8 UHR 3 Date and time HK AGM PES master monitoring 3 HK COM Monitoring of communication module 3 HK LGP 3 LGP evaluation and configuration HK MMT 3 MODBUS master HA LIN 3 Temperature linearization e HA PID 3 PID controller HA PMU 3 Measuring transducer capable of being parameterized 71 106 Chapter 5 Software 4 2 2 4 3 72 106 Standard F
11. However the fol lowing items have to obeyed when the user program is created The resource name in ELOP II must have eight characters of which the last two must be numbers Numbers between 0 and 64 can be used The numbers must be unique so that they can be used without the risk of collision to determine the IP address in the communication module Safety related communication with HIPRO S in NORMAL mode is to be designed in a way that each automation device is configured for safety related data exchange with every other automation device i e exchange of dummy data if no user data are exchanged If using HIPRO S DIRECT mode this is not necessary no dummy data have to be exchanged To check the HIPRO S configuration the PES master program is to be compiled If errors have occurred they are to be corrected afterwards For the safety related communication the transmission data Zero must be the safe state Remove all force markers before starting the safety related operation and before certification by an authority 84 106 Central Fire Alarm Systems Chapter 5 Software 6 Use for Central Fire Alarm Systems according to DIN EN 54 2 and NFPA 72 The H41q H41qc and H51 systems can be used for central fire alarm systems according to DIN EN 54 2 and NFPA 72 For this purpose the user program must comply with the functions of central fire alarm systems according to the menti
12. 1 Allocation by 0 Allocation by 2 In safety related control circuits the closed circuit principle must always be applied Max Time Inrush Current in ms Determination of the delay time for the detection of a line break or time allowed for the tolerat ing of the current limit During this time the error display is suppressed An increase of the de lay time results in an increase of the cycle time Normal operation Detected error is signalized by H signal at corresponding output Error channel n The output circuit of the module is closed Error evaluation error messages are suppressed Only applicable if permitted by the plant specifications Inverted operation i e the output circuit is to be open The outputs Pulse on Error 2x Error and Error code are for information purposes only and no safety related action in the user program must be derived from them 97 106 Appendix Allocation of Standard Building Blocks 2 7 Function Block HB BLD 4 This function block is used for channel related error evaluation and display for safety related digital output modules types F 3331 F 3334 and F 3349 in redundant operation It must be used only once for a pair of redundant modules HB BLD 4 Testable red Outp Modules with Line Diagnostic UINT gBus No Rack Pos e g 1305 Channel Fault Mask Mod 1 UINT UINT sBus No Rack Pos red Mod Channel Fault Mask Mod 2 UINT UINT
13. E E ra 1 Safety and Availability aoaaa aaa 2 Safety TIMES sia iea a ya ade cx eS a E a ES AIEE Raped E a dn Rg hes aus Aa 3 Offline Proof Testii 3 55 208 cn EA e eE E a a a tae Arar A oa a tg eek a A aE 4 Execution of the Offline Proof Test 000 0c cece 4 Periodic Proof Testings 25 ante ks Soh heise aa eta we Ma ald Wee at rs 4 Safety Conditions on iai ec a ae eae We ek i ee ee ee ee a 5 Hardware Project Planning Product Independent Conditions aaas aaaea eee 5 Hardware Project Planning Product Dependent Conditions5 Programming Product Independent Conditions 2005 5 Programming Product Dependent Conditions 2000505 5 Communication Product Dependent Conditions 2 205 6 Special Operating Modes Product Independent Conditions 6 Central Modules Overview of the Modules in the Central Area of the H41q H41qc and H51q Systems 000 e ee eee ees 7 Central Area of HIMA Automation Devices of the H41q H41qc and H51q Systems 0002 ee 7 Overview of the Central Modules for the H41q H41qc and POG SyStEMS a 2404 2 chat anh Meee y ann IE EEE him eee ewe uli aha ee 8 Other Modules for the H41q H41qc and H51q Systems in the Central Device Area 2 eee eens 9 General Notes on the Safety and Availability of safety related Central Modules 0200 c cece eee eee ees 10
14. MOdUIeS s s 2 hese ead or es ee Ai ess eee eae e tees ce tes 25 Check Lists for Project Planning Programming and Commissioning safety related Input Modules 26 F 3236 Safety related Digital Input Module 16 channel 27 F 3237 Safety related Digital Input Module 8 channel 28 F 3238 Ex i Safety related Digital Input Module 8 channel 29 F 3240 Safety related Digital Input Module 16 channel 30 F 3248 Safety related Digital Input Module 16 channel 31 F 5220 Safety related Counter Module 2 channel 0000 eee 32 F 6213 F 6214 Safety related Analogue Input Module 4 Chanel acide we ova ge dared asda nd Raed e Meee ates a eaween eee es 33 F 6217 Safety related Analog Input Module 8 channel 0 4 34 F 6220 Ex i Safety related Analog Thermocouple Input Module 8 channel Pils Vacs ana dnes es by e448 eo Dee eee Ahets 35 F 6221 Ex i Safety related analogue input module 8 echannel ik debe wien arse eee cow arte AT ces Stele oil ay eee nae near lus napa A 36 Output Modules Overview of Output Modules for the H41q H41qc and H51q Systems 222020202 eee eee 37 Table of Contents Chapter 5 2 2 1 2 2 1 2 2 1 2 2 2 3 General Notes on the Safety and Availability of Safety related Output Modules 000 cece eee eee eee 38 Safety related
15. Power Supply Modules 000 0c cece tee e teens 10 Functional Description of the Safety related F 8652 A E F 8650 A E Central Modules for the H41q H41qc and H51q Systems iso edhe aes ble ee Han ean Ae Rech Soa eas 11 The Principles of Function of Safety related Central Modules 000 c cece eee ee eee eee 13 Self Test ROUES masant 664 cin ee etd See eee anon Peels o E E tin eae der dye Be 13 Response on Errors Detected in Central Modules 0000005 13 Diagnostic Display sete 2041s haw tage hee Si ae eer a ead Pee 14 Response on Errors Detected in the IO Bus Area 200000ees 15 Instructions for the Replacement of Central Modules 5 3203 cerdwa cies eee ee oe eo 8 ees 16 Chapter 3 1 2 2 1 2 1 1 2 2 2 2 1 2 2 2 2 3 2 3 1 2 3 2 2 4 2 4 1 2 4 2 2 4 3 2 5 2 5 1 2 5 2 2 6 2 6 1 2 6 2 Chapter 4 1 Table of Contents Input Modules Overview of the Input Modules for the H41q H41qc and H51q Systems 2 022 17 Safety and Availability of Safety related Input Modules ois ke inca oaa elec Wie wees dee di slew wa eles SE eS bs 18 General notes on safety related input modules 00 000 ees 18 Safety of Sensors Detectors Transmitters 000000 19 The F 3236 F 3237 F 3238 F 3240 and F 3248 Safety related Digital Input Modules 00 00 19 TOSUROULNGS 22 ait Mahle ke heh be ee See a Ea ara Sant eb eg
16. S communication Master systems with 3964R protocol Variable declaration 3964R Logic plan controlled logging Variable declaration event controlled proto col texts Safety Aspects Operating System Chapter 5 Software 2 2 1 2 2 Safety Aspects concerning the Operating System Designation Current Approved Version for Safety related Applications CRC Signature Each new operating system is identified by its designation The signature of the operating sys tem serves to further identify the operating system This signature can be retrieved on the di agnostic display during operation of the automation device The current applicable versions of the operating system TUV approved for safety related automation devices and their corre sponding signatures CRCs can be found in the report enclosed in the certificate for the HIMA H41q H51q automation system Signatures of the User Program Code version number The code version number is generated via the functions of the programmed logic The function of the control can be viewed on a PC only if the code version of the program in the control and in the programming device are the same The following actions have no influence on the code version number e Writing or deleting of comments e Setting or deleting of online test fields OLT fields i e of forced information e Shifting of lines or modules respectively but only if the sequence of operation is not
17. Use of Standard Function Blocks for Safety related Applications 0 0 0 eee 71 Standard Function Blocks Independent of the IO Level 71 Standard Function Blocks Depending on the IO Level nnau nunana 72 Prerequisites and Rules for the Use in Safety Applications Requirements from Prototype Certificates etc 0 0 ee ee 72 Basic Programm aa siii ea te attack Gti S da e Sod Sak ad BGs see nape A ada ph ants mes cae 73 Variable Declaration and Entering of Process I amp C Names 4 73 Allocation of Process I amp C Names with Variable Names 0 74 Types of Variables sihacela ee woh La nd Baa Siena Bee Ageia 75 Digital Inputs and Outputs for Boolean Variables 200050 75 Analogue lO MOdUIGS lt lt e215 4 3 22 ou b s aie ween g dg Race Oa Se COME See D BD Se 75 Imported or Exported Variables 0 0 0 0 0c eee 75 Functions of the User Program lt 9 s o04 ses dwau eww ieee de evel eee Me wet 76 Group SHUTCOWN 3 6 oak is Heri Ba clave eine eh echoes 76 Function Blocks for Individual Safety related IO Modules 76 Redundant lO Modules 0000 cece ee 77 Redundant Non safety related Sensors 000000 00 e eee ee 77 Analog Redundant Transmitters 0 0 0 ee 79 Input Modules with 2003 Circuit 0 0 0 0 0 00s 81 Program Documentation for Safety related Applications 82 Safety
18. ae aS 19 Response of the System on Failures Detected at Safety related Digital Input Modules 0 000000 c eee ees 20 The F 5220 Safety related Counter Module 0 00000 21 Test ROUES reon ea Catto ates cin ss aan aha daca gia eee 21 Response of the System on Failures Detected at Safety related F 5220 Counter Modules 0000 0c cece eens 21 The F 6213 F 6214 and F 6217 Safety related Analogue Input Modules 0000 cee eee ees 21 TOSHIROUUNGES aie hai eae a dra Ted Gale ie aE ale wed ee race 21 Response of the System on Failures Detected at Safety related F 6213 F 6214 Analogue Input Modules 22 Response of the System on Failures Detected at Safety related F 6217 Analogue Input Modules 0 005 22 The F 6220 Safety related and Intrinsically Safe Thermocouple Input Module 2 0000 eens 23 TeSt ROUNE Sia fy vies tran shames ethene geod eae touts E a e N tenet aya hagd ee 23 Response of the System on Failures Detected at Safety related F 6220 Thermocouple Input Modules 23 The F 6221 Safety related Analogue and Intrinsically Safe Input Modulens Ssss soneta dada uara ko ee eek dale BOOM GS Ce eat es 24 TLeStiROUUNGS ins pews ee eed Sans hb thar T hein s eT eae asa 24 Response of the System on Failures Detected at Safety related F 6221 Analogue Input Modules 0 005 24 Instructions for the Replacement Of Input
19. also be used for monitoring the sense of rotation If the Gate time is modified the correct measuring value is available at the output only after three Gate times as currently set 2 3 1 Test Routines The module has its own 1002 microprocessor system which automatically performs safety re lated online tests The safe data for the safe signal processing are available through the HF CNT 3 function block 2 3 2 Response of the System on Failures Detected at Safety related F 5220 Counter Modules Type of failure Response of system Comment Module failure Switching off of the safety In the event of an error the related outputs only possible response is switching to the safe state Channel failure Switching off of the assigned In the event of an error the safety related output only possible response is switching to the safe state Line break or short circuit Switching off of the assigned After fault recovery reset in the initiator circuit or safety related output signal at the input of the HF other failures CNT 3 function block required 2 4 The F 6213 F 6214 and F 6217 Safety related Analogue Input Modules In parallel operation of safety related analogue input modules the average value for F 6213 F 6214 generated by the appertaining function block for F 6217 by the user program of oper ative modules is processed only within the range of permissible deviations In the event of
20. amp C Names with Variable Names 74 106 The measuring point list or a list of the sensors and actuators should serve as the basis of the allocation of Process I amp C names with variable names Variable names are allocated to the hardware used in the notebook for the resources under Process cabinet The desired subrack position 1 1 to 1 8 or 2 1 to 2 8 respectively and type the slot and type of the required module as well as the Process I amp C names to be allocated to the variable names are entered into the notebook For practical reasons the variable name and the Process I amp C name should be the same The number of channels names per module depends on the type of module used The re quired test routines for safety related IO modules are performed automatically by the operating system We recommend assembling the input and output modules used in the IO subracks into func tional groups Groups may be formed under the following aspects a Grouping according to plant parts e the same way of arranging the modules in the groups e g 1 digital analogue plant parts 2 safety related non safety related IO modules e redundant grouping in the various IO subracks in the same order b Spare modules or spare channels for later reloads reloadable code Safety Aspects User Program Chapter 5 Software 4 3 2 2 Types of Variables Depending on the program organization unit POU program function block or fu
21. and cold withstand test 70 C 25 C 96 h EUT power supply unconnected 6 3 4 3 Change of temperature withstand and immunity test 25 C 70 C and 0 C 55 C EUT power supply unconnected 6 3 4 4 Cyclic damp heat withstand test 25 C 55 C 95 relative humidity EUT power supply unconnected 88 106 Mechanical conditions 2 3 Chapter 6 Operating Conditions Mechanical Conditions The most important tests and limits for mechanical conditions are listed in the table below EN 61131 2 Chapter 6 3 5 Mechanical Tests Vibration test operating 5 9 Hz 3 5 mm 9 150 Hz 1g 6 3 5 1 Immunity vibration test 10 150 Hz 1 g EUT operating 10 cycles per axis 6 3 5 2 Immunity shock test 15 g 11 ms EUT operating 2 cycles per axis EMC Conditions The most important tests and limits for EMC conditions are listed in the table below EN 61131 2 Noise Immunity Tests Chapter 6 3 6 2 6 3 6 2 1 ESD test 4 kV contact 8 kV air discharge IEC EN 61000 4 2 6 3 6 2 1 RFI test 10 V m 26 MHz 1 GHz 80 AM IEC EN 61000 4 3 6 3 6 2 1 Burst test 2 kV power supply 1 kV signal lines IEC EN 61000 4 4 6 3 6 2 1 Damped oscillatory wave immunity test 1 kV IEC EN 61000 4 12 IEC EN 61000 6 2 Noise Immunity Tests IEC EN 61000 4 6 Radio frequency common mode 10 V 150 kHz 80 MHz AM IEC EN 61000 4 3 900 MHz pul
22. causing disturbances or impairments of safety functions severe personal injuries property or environmental damage may occur for which we cannot take liability HIMA Automation Devices are developed manufactured and tested ac cording to the relevant safety standards They must only be used for the applications described in the instructions and with specified environmental conditions and only in connection with approved external devices Intended readership This manual addresses on system planners configuration engineers and programmers as well as persons authorized for the start up and for ope ration of the devices and systems Presupposed is knowledge in the area of the safety technology The reproduction of the contents of this publication either in its entirety or in a part is not permitted without the written permission of HIMA All rights and technical modifications reserved HIMA Paul Hildebrandt GmbH Co KG P O Box 1261 D 68777 Bruehl near Mannheim Phone 49 6202 709 0 Fax 49 6202 709 107 E mail info hima com Internet http www hima com Table of Contents Table of Contents Chapter 1 Chapter 2 aaakR wr Pon i a Aa ma om 3 3 N gt 1 1 1 1 2 1 2 1 2 1 2 2 3 1 3 3 The Safety Philosophy and Conditions Introd ction iesi aea aE ia ha ek a R E R ERNE AS 1 Definitions eresi es ev eee A EE E EEE EE AED etn ae aaa a 1 Certifications ieee e a a n wed ae dle I A E E E T
23. cf chapter 4 item 3 2 Introduction Chapter 1 Safety Philosophy 1 4 To increase the availability by using redundant modules three essential points must be con sidered e Defective modules must be detected and switched off so that they do not block the sys tem e Inthe event of an fault the operator must receive a message indicating that the module must be replaced e Automatic restart of operation after the replacement of a module must be ensured The HIMA Automation devices meet all these requirements in the respective configurations To program the devices a PADT programmer unit PC is used running with the programming tool ELOP Il according to IEC 61131 3 It supports the user during creating safety related programs and op eration of the automation devices The automation devices are designed for the closed circuit principle i e for the peripheral equipment and for the function of the control the de energized state is to see as the safe state In case of faults input and output signals are switched to the safe state they are free of voltage or current Safety Times Single faults which may lead to a dangerous state of operation are detected by the self test equipment within the fault tolerance time min 1 s The fault tolerance time is preset as safety time in the menu properties in the resource Fault tolerance time Process value which is very often called safety time in guidelines for users Safety tim
24. e g graphical modifications or modifications of initial values changes have been incorrectly adopted The new C code new and the comparison file new are compiled by the proven C com piler GNU CC points 6 and 13 The target code and the comparison code are gen erated The target code comparator must be activated point 14 It compares the target code with the comparison code Errors caused by a non safety related PC are detected and signalized This so generated program free of errors is now ready to run and it is loaded into the H41q H51q system All modified parts of the program must now be tested by the user By testing the changes the user can verify whether the target code is correct If there is no malfunction a backup of the new current program must be generated The PES can start safety related operation 61 106 Chapter 5 Software Safety Aspects ELOP Il Binding System Specification 2 Screen FB SFC J 3 i 9 Co o Input data Backup data 17 18 Print out FB SFC FB SFC 4 FB SFC C Code ad Generator A 10 Off line Simulation C Code VGL file new Library GNU C compiler Hitean pind C Code comparator Library GNU C compiler rranaentas Comparison code Target code comparator Modifications Target code H41q H51q
25. fault value must be defined in the user program which is used in case of a failure In safety related applications according to SIL 3 the value for the reference temperature is to be taken from two different modules this is also true for the thermocouples For the detection of the environmental conditions of the module such as temperature an au tomatic recalibration is performed in intervals of 5 minutes During this procedure also the in ternal failure messages of the module are reset This function can also be started by applying a TRUE signal to the Recalibration input via the user program This TRUE signal may only be applied for one cycle With a TRUE signal at the MOS input Maintenance Override Switch the Value and Chan nel error outputs of function block are held for the duration of the test operation See also doc ument Maintenance Override by T V Bayern and T V Rheinland 103 106 Appendix Allocation of Standard Building Blocks 2 13 Function Block HK LGP 3 This function block is used for the evaluation and configuration of event recording and the switch over between BUSCOM and LCL logic plan controlled logging If more than one au tomation device is connected to one printer the function block also enables printing HK LGP 3 LCL Configuration 1 Printout Active BOOL BoOoL Stop Printout Printer Error BOoOL BOOL ri FALSE LCL TRUE MODBUS Printer Offline ji BOOL BYTE 14E
26. functions of the user program are freely programmable When programming make sure that the closed circuit current princi ple at the inputs and outputs is obeyed A line break will e g result in the shutdown of the cor responding actuator e Unlike in the case of hard wired safety related controls line breaks do not have to be considered in the logic functions user program in programmable logic controls e Any negations are permissible e Active signals for triggering an action e g shift clock pulse for a shift register can be used for safety related applications If an error occurs in a safety related analogue input module a defined value will be processed For further information see the description of the function blocks in the Manual ELOP II Re source Type If an error occurs in a safety related digital input output module an input will be set to safe 0 and the digital output module will be switched off by the integrated safety shutdown For further information see the description of the function blocks in the Manual ELOP II Resource Type Unlike hard wired controls programmable logic controls are provided with a more extensive range of functions especially with byte and word processing Group Shutdown The safety related modules used for a certain plant area e g a burner can be assembled in a group For this purpose the H8 STA 3 function block is entered in the user program for each group In this
27. in chapter 3 1 2 The offline simulation verifies the user program against the specification but without influence to the process 59 106 Chapter 5 Software Safety Aspects ELOP Il 3 1 1 60 106 Application of the Safety Tool of ELOP II for the Creation of the Program 1 The user program is generated according to a binding specification e g according to IEC 61508 DIN V VDE 0801 or a corresponding user standard in the flow chart the points 1 to 4 2 The modified user program is compiled into the C code by the C code generator and ad ditionally a comparison file is generated point 5 For the user program a cross reference list has to be generated and checked for correct use of the variables It has to be verified that all variables are used only in those places provided by the specification 4 The C code and the comparison file are compiled by the proven compiler GNU CC points 6 and 13 The target code and the comparison code are generated The target code comparator must be activated point 14 It compares the target code and the comparison code Errors caused by a non safety related PC are detected and signalized 6 The program generated in this way is now ready to run and it is loaded into the H41q H51q system point 7 There the program must be tested completely by the user and accepted point 8 7 A backup of the target code is generated and the PES starts safety related operati
28. influenced e Changing of the SIO parameters themselves but not activating deactivating the SIO parameters Bus parameters Changes of the basic addresses for external MODBUS coupling may but do not necessarily have to result in a change of the code version number With all other changes the code ver sion number changes as well Run version number The run version number is generated during operation by the control itself By comparing it with a currently valid and documented run version number you can see whether the program in the control has been influenced in the meantime see by calling it on the diagnostic display The run version number will be changed if there is a different code version number not at all types of modifications e modules are inserted or deleted e system parameters change e VAR_CONST is inserted or deleted e VAR_CONST values are changed e the resource type is changed e settings are changed online e force values of IO variables in the online test field are changed e the position of the force mains switch is changed 57 106 Chapter 5 Software Safety Aspects Operating System 2 3 58 106 Data version number The data version number refers to the definition of non safety related imported or exported variables It will change if the name of a variable with attributes for HIPRO not safety related changes e these variables are compressed at the generation of a non reloada
29. module input module Storage of the FALSE signal for all channels in logic pro cessing This ensures the safe func tion of the system depend ing on the selected system configuration Wire break in the sensor circuit Reading of the FALSE sig nal in the corresponding channel With modules having line monitoring a line fault is sig nalised For safety related inputs this signal must be evaluated by the HB RTE 3 function block see chapter 5 to ensure a safe response of the system Short circuit in the sensor circuit Reading of the TRUE signal in the corresponding chan nel With modules having line monitoring a line fault is sig nalised For safety related inputs this signal must be evaluated by the HB RTE 3 function block see chapter 5 to ensure a safe response of the system General The position of the defective module is shown on the diag nostic display If input modules with line break and short cir cuit monitoring of the sensor circuit are used the diagnostic display also shows the faulty channel of the defective mod ule Safety and availability Chapter 3 Input modules 2 3 The F 5220 Safety related Counter Module This 2 channel counter module has its own dual processor system with one safety related out put per channel It can be used for pulse counting or with its adjustable gate interval for fre quency measurements or rotational speed measurements It can
30. properties General notes Chapter 4 Output Modules 2 2 Safety related Analog Output Modules The safety related analogue output modules can be used in current source mode or in current sink mode In current source mode the safe state output voltage 0 mA is achieved by the integrated safe ty shutdown in the event of a failure In current sink mode the safe state can only be achieved by additional measures The supply voltage for the current loop must be safely shut down by the user program For the evaluation of errors the HZ FAN 3 function block is to be used In parallel operation redundancy of safety related analogue output modules the operational modules process the mean value In the event of a failure only the value of the operational module is processed 39 106 Chapter 4 Output Modules Principles of Function 3 3 1 40 106 The Principles of Function of Safety related Output Modules In safety related output modules three testable semiconductor switches are connected in se ries Due to this the required independent second way of shutdown is integrated in the output module This so called integrated safety shutdown switches all channels of the defective out put module safely off if an error occurs de energized state ee ee eee IO Bus WD Fi tt g 1 2 3 4 K _
31. related Digital Relay Output Module Test Routines The modules are tested automatically during operation The main test functions are the follow ing 1 Reading back the output signal of the switching amplifier for the relay switch in 3 chan nel diversity 2 Application of test patterns and testing for crosstalk walking bit test within the multiple fault occurrence time 3 Test of the integrated safety shutdown Response of the System on Failures Detected at Safety related Digital Relay Output Modules e If errors are detected on the module it is put to the safe de energized state i e the module is switched off Inthe event of external short circuits the fuse for the relevant channel blows An error message is not generated Notes for Projecting with F 3430 Relays are electromechanical elements and due to their construction they have a limited life The life of relays depends on the switching capacity of the contacts voltage current and the quantity of switching cycles The life at nominal operating conditions is approx 300 000 cycles at 30 V DC and 4A To meet the requirements according to IEC 61508 PFD PFH cf chapter 1 2 for the modules applies an offline proof test interval of 3 years for use in SIL 3 and 6 years for use in SIL 2 The necessary tests are made by the manufacturer 41 106 Chapter 4 Output Modules Principles of Function 3 3 3 3 1 3 3 2 42 106 The F 6705 Safety related Analog
32. shutdown in the case of an error by their Boolean signal The other outputs are for information purposes only and no safety related action in the user program must be derived from them Allocation of Standard Building Blocks Appendix 2 6 Function Block HB BLD 3 This function block is used for error evaluation and display related to the channels of the safety related digital output modules types F 3331 F 3334 and F 3349 It must be used only once for each module UINT UINT UINT UINT UINT UINT UINT UINT UINT UINT Inputs HB BLD 3 Testh Baugr Leit Diagnose Monobetrieb ewdBus No Rack Pos e g 1305 Channel Fault Mask ba edMode Channel 1 0 1 2 Error Channel 1 su ewdMode Channel Z 0 1 2 Error Channel Z su edMode Charnel 3 0 1 2 Error Channel 3 su edMode Channel 4 0 1 2 Error Channel 4u ewMode Channel 5 0 1 2 Error Channel 5 su edMode Channel 6 0 1 2 HB BLD 3 Error Channel 6 su sdMode Channel 7 0 1 2 rere Error Channel 7 s ewdMode Channel 8 O0 1 2 Error Channel u ewMax Time Inrush Current in ms Pulse on Error pu d Pulse on Error pu Error sd a Error Code pa Bus No Rack Pos e g 1305 UINT BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL BOOL UINT Position of the safety related digital output module designated by a four digit decimal number Example 1305 means Cabinet 1 subrack 3 module position 05 Mode Channel n 0 1 2 Allocation by
33. takes over mono operation with the new user program When the second central module has been loaded it re ceives the current data and both central modules go to redundant operation Offline Test Changes in the user program can be simulated with the offline test in ELOP II This simulation is an excellent means of assessing the effects of a change It is however not sufficient for the validation of the changes made in safety related controls This requires a test in the actual con trol or in a simulator Forcing Forcing is only possible after consultation with the test authority in charge of plant acceptance For the duration of the forcing process the person in charge has to ensure appropriate safety related monitor ing of the process by other technical and organizational measures 69 106 Chapter 5 Software Safety Aspects ELOP Il 3 8 70 106 When forcing is to be done in safety related controls the latest appli cable version of the document Maintenance Override issued by TUV Rheinland and TUV Product Service must be obeyed Forcing possibilities provided to the user e Forcing can be forbidden by the configuration In this case the PES does no longer accept forced values with user specific definition New forced values can only be set after the system has been switched off When the user exits the control panel he will be shown if any and how many forced values are still set e Inputs an
34. the event of a fault the watchdog is put into the safe state and the processor status is signalled Flash EPROMs of the program memories for the operating system and the user program are suitable for at least 100 000 memory cycles Data storage in the SRAM static RAM Multiplexer for the connection of the IO bus the Dual Port RAM DPR and the redundant central module Back up of the SRAMs effected by batteries on the central module with monitoring of the bus PCB Two RS 485 interfaces with electrical isolation baud rate 57600 bps can be set to 9600 bps and 57600 bps via switch or via the software other baud rates are also possible the software values have priority Diagnosis display and 2 LEDs for information from the system the IO area and the user program DPR for fast two way alternate access to the second central module Hardware clock with battery back up IO bus logic for connection with the IO modules Fail safe watchdog Power supply module monitoring testable 5 V system voltage Battery monitoring Principles of function Chapter 2 Central Modules 3 3 1 3 2 The Principles of Function of Safety related Central Modules Self Test Routines The following explanations describe in brief the self test routines of the safety related F 8650 A E and F 8652 A E central modules and the coupling to the IO level e CPU test The types of command and addressing writing property of flags and the commands triggere
35. the user program HF AIX 3 Voltage or Current measurement for F6221 as 4Bus No Rack Pos e g 1305 Value 4Channel No 1 8 HF AIX 3 4Enable configuration Active Mode 1 0 01 2 digits 3 scaling physical Live Zero Scaling minimum value for 0 4 mA Scaling maximum value for 20 mA Monitor transmitter voltage 4 Underflow level in 0 1 mA 32 3 2 mA Underflow Overflow level in 0 1 mA 210 21 mA Overflow 4Recalibration IMOS TRUE test operation Maximum time for test operation in min Remaining time Error 4Value on Error Error code The analogue input module has one safety related output per channel controlled independent ly from the cycle of the central unit The status of this output is indicated at the output of the HF AIX 3 function block and can be processed by the user program Via parameter settings the value of the analogue input module can additionally be converted and spread By entry of a value at the function block input Value on error this value is switched to the out put Value in case of channel or module errors as well as in case of measurement range over flow or underflow and in the user program it can be processed instead of the actual value Allocation of Standard Building Blocks Appendix 2 10 Function Block HF CNT 3 The HF CNT 3 function block is used to configure the two channels of the F 5220 safety relat ed 24 bit resolution counter module and to evaluate
36. tion see data sheet regard switching cycles 5 Is intended to replace the module after end of the relay life 6 Isthe required test by the manufacturer intended for SIL 3 use every 3 years for see data sheet SIL 2 use every 6 years 7 Are cables with double or reinforced insu lation used for the connection wiring according to IEC 61131 2 Ed 2 2003 no longer required if the use of the module meets SELV or PELV conditions yes ro ojo 52 106 Check lists Chapter 4 Output Modules 5 9 F 6705 Safety related Analogue Output Module F 6705 safety related Check list No SANAA F6705 E digital output module Version 2 0 32 05 Project data Project designation File name of check list archiving number Position in subrack OSR Requirements for the project planning of the module and the user program 7 TART fulfilled a i O equiremen ommen 1 Are the outputs of this module named which perform a safety related function 2 Are unused channels bridged to avoid error messages from modules Channel 1 Bridge b6 b8 Channel 2 Bridge b22 b24 3 Are the channels switched in parallel used in the same mode of operation current source mode or current sink mode 4 Incase of redundant connection Are the connected actuators capable of tolerating a current burst to the half or the double value for 2 to 3 cycles 53 106 Chapter 4 Output Modules Check lists For
37. to the EC type examination certificate 6 Is the max resistance in the measuring see data sheet circuits less than 500 Q Does a redundant measuring input exist when used in a higher SIL Where does the value of the comparison temperature come from external from the module from redundant measuring 35 106 Chapter 3 Input modules Check lists 4 10 F 6221 Ex i Safety related analogue input module 8 channel F 6221 Ex i Safety related analog Check list No SANAE F6221 input module 8 channel Version 2 0 32 02 Project data File name of check list archiving number Project designation Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment yes o 1 Are the inputs of this module named which perform a safety related function 2 Does a parallel redundant module exist for this module 3 If YES is the redundant module of the same type 4 Is the transmitter feeding coming from module F 3325 5 Are all recommendations for engineering taken into consideration according the permitted variants see data sheet see data sheet F6221 see data sheets of other device see data sheet H51q above H41q below 6 Is there forced ventilation by means of a fan right above below the module 7 Have the special requirements been met see data sheet for the application of the Ex i module as stated in the data sheet
38. 06 means Cabinet 1 subrack 3 module position 06 All inputs of the function block are for information purposes only and no safety related action in the user program must be derived from them 105 106 Appendix Allocation of Standard Building Blocks 106 106 From Company Name Dept HIMA Paul Hildebrandt GmbH Co KG Address Industrie Automatisierung Documentation P O Box 1261 68777 Bruhl Germany Dear reader we are always eager to keep our manuals up to date and to avoid errors But if you have found an error in this manual or if you want to make suggestions for improvements also for the HIMA pro ducts we would be very grateful to you Please use therefore just this page or a photocopy of it and send it to us by post or by fax Fax No 49 6202 709 299 Sub Safety Manual HI 800 013 0702 HIMA Paul Hildebrandt GmbH Co KG Industrial Automation P O Box 1261 D 68777 Br hl e Germany Telephone 49 6202 709 0 Telefax 49 6202 709 107 E mail info hima com Internet www hima com 96 9905116 HIMA Paul Hildebrandt GmbH Co KG
39. Aspects for Communication Safety related Data Transmission 000 cece eee eee eee eee 83 Safety related Communication 0 000 e tees 83 Time Requirements 000 0c eee nee 83 Instructions for the Creation of the User Program auaa eee eee 84 Use for Central Fire Alarm Systems according to DIN EN 54 2 and NFPA 72 3 000is 6 etete awe eed ivan isis tend Peden 85 Operating Conditions Climatic ConditionsS 0 00 cece eee ee eee eee eee 88 Table of Contents Appendix Vi 2 3 4 Mechanical Conditions o nasi adare dere ees Se ene eae Se 89 EMC Conditions sse ected ae bw had ele ne ele vei ad ideals RS PoP wa ae 89 Power Supply Conditions 0000 cece eee ee eee 90 Standard Function Blocks for the Central Are aie eene tees n OEE EEA es een as ec tear tee apa ae 92 Function Block HK AGM 3 0 0 0 000000 cece ee ee ee ee ees 92 Function Block HK COM 3 rduera aka aah ee ee ee eee 92 Function Block HK MMT 3 0 0 00000 cee ee eee ee ees 92 Function Block H8 UHR 3 0 0 0000 ccc ee ee ee ees 92 Allocation of Standard Function Blocks forthe 1O Area via ee ek ead Blotter Ota HA Se A ES a a a ea Gah A 93 Function Block H8 STA 3 1 0 00 00 0c cc ee ee ee aA 93 Function Block HA LIN 3 0 0 0000000 ccc ce eee ee ee ee eee 94 Function Block HA PID 3 0 00000000 ccc eee ee ee ees 94 Function Block HA PMU 3 1 0 0 0 000 0c cee ee ee ee eee 95 Function
40. Block HA RTE 3 0 0 000 0c cece ee ee ee ees 96 Function Block HB BLD 3 0 000000 ccc ee ee eee 97 Function Block HB BLD 4 0 00 00 ee ee eee 98 Function Block HB RTE 3 erae n e A E ee eee 99 Function Block HF AIX 3 oeiia See RAAE Que bred dale betas wb ewan et 100 Function Block HF CNT 3 0 0 00000 ccc cee eee ee ee eee 101 Function Block HF CNT 4 0 0 0 0 ccc cc ee ee ee eee 102 Function Block HF TMP 3 0 0 000000 cc cece eee eee 103 Function Block HK LGP 3 0 0 0 0 000 ccc ee ee ee eee 104 Function Block HZ DOS 3 0 0 000000 0c ce eee 104 Function Block HZ FAN 3 0 0 0 00000 cc ec ee ee ee eee 105 Introduction Chapter 1 Safety Philosophy Chapter 1 The Safety Philosophy and Conditions 1 Introduction 1 1 Definitions Closed circuit principle A system operating in deenergize to trip mode does not need en ergy to perform its safety function Open circuit principle A system operating in energize to trip mode needs energy for ex ample electrical or pneumatic energy to perform its safety function 1 2 Certification The safety related automation devices PES Programmable Electronic System of the H41q H41qc and H51q system families are certified as follows A T V Rheinland T V Anlagentechnik GmbH Automation Software und Informationstechnologie Am grauen Stein D 51105 K ln 4 Bauart geprift Type approved Certificate and Test Repo
41. CNT 3 counter function block and can be processed by the user program With a TRUE signal at the MOS input Maintenance Override Switch the output of the counter function block may directly be controlled within the time interval for test operation i e the output indicates the value given at the Forcevalue for maintenance input See also doc ument Maintenance Override by T V Bayern and T V Rheinland If the Gate time is modified the correct measuring value is available at the output only after three Gate times as currently set 101 106 Appendix 2 11 102 106 Function Block HF CNT 4 This function block has the same functionality as HF CNT 3 but additionally has an output Er ror for channel error HF CNT 4 Counterblock for F5220 1305 Bus No Rack Pos e g Allocation of Standard Building Blocks Counter channel 1 Enable Configuration Signal type 1 5V Z 24V 3 initiator Preset value Gate in 50ms Maximum deviation at frequency Counting mode l right left Z right 3 left Reset counter Stop counter MOS TRUE testoperation Maximum time for testoperation in min Forcevalue for testoperation HF CNT 4 Counter channel 2 Enable Configuration Signal type 1 5V Z Z4V 3 initiator Preset value Gate in 50ms Maximum deviation at frequency 4 Counting mode l right left Z right 3 left Reset counter Stop counter MOS TRUE testoperation Maximum time
42. Digital Output Modules 0 0000 cee eee ees 38 Safety related Analog Output Modules 0000 c cece eee 39 The Principles of Function of Safety related Output Modules 00 cee eee eee eee 40 The F 3330 F 3331 F 3333 F 3334 F3335 F 3348 F3349 Safety related Digital QUIpULMOdUIES 4 23 3 a BO ace OF tee seh tre Shs cea te a A a a ao a 40 MOESUIFOUTINGS eaen E cegh eee SE ao bee te ee ete eg en a a a Bk 40 Response of the System on Failures Detected at Safety related Digital Output Modules 0 000000 eee ees 41 The F 3430 Safety related Digital Relay Output Module 41 Test ROWINGS e mo aaa a aa a aa a a E a avn N ha 41 Response of the System on Failures Detected at Safety related Digital Relay Output Modules nnana naana aaan 41 Notes for Projecting with F 3430 20 0 0 tees 41 The F 6705 Safety related Analog Output Module 2 005 42 Test ROULUNES e ari Pe ada hike ah ok She Rds dt Seb eat ee Ran ete 42 Response of the System on Failures Detected at Safety related Analogue Output Modules 000 0c eee eee 42 Instructions for the Replacement of Output Modules 2 022 ees 43 Check Lists for Project Planning Programming and Commissioning Safety related Outputi Modules 2 2 cscee ice ae cee SN tees Se eee ee 44 F 3330 Safety related Digital Output Module 2 2020005 45 F 3331 Safety related Digita
43. IX 3 function block is 0 The Channel error output at the HF AIX 3 function The failure indicating value must be set in the user pro gram by using the Error Value input signal of the function block block switches to TRUE The Channel error output at the WHF AIX 3 function block switches to TRUE Channel failure Underflow The Underflow output at the HF AIX 3 function block switches to TRUE Overflow The Overflow output at the HF AIX 3 function switches to TRUE block The limits for underflow or overflow are to be set at the inputs Underflow level or Overflow level depending on the HF AIX 3 function block Additional notes on project planning Voltage inputs 0 1 V not used are to be short circuited on the terminal strip Current inputs not used are terminated by a shunt in the cable connector Only uses mentioned in the data sheet of the F 6221 module are admissible The Ex protection regulations and the Ex connection conditions must be met Instructions for replacement Chapter 3 Input modules 3 Instructions for the Replacement of Input Modules We urgently recommend replacing defective input modules In the event of a module failure or for maintenance purposes please follow the instructions de scribed below e Unscrew the cable connector or pull out the input module with its cable connector plugged in e Insert new input module w
44. Output Module Test Routines The module is automatically tested during operation The main test functions are the following 1 Reading back of the output signal 2 Checking the DA converter for linearity 3 Testing for crosstalk between the outputs 4 Test of the integrated safety shutdown Response of the System on Failures Detected at Safety related Analogue Output Modules In current source mode the module is put to the safe de energized state in case an error is detected i e the modules switches off due to its integrated safety shutdown An external line break cannot be distinguished from internal failures and results in the module being switched off In current sink mode the safe de energized state can only be achieved by external switch off The voltage supply for the current loop must be safely switched off by the user program This is why the HZ FAN 3 function block must be used for error evaluation Instructions for Replacement Chapter 4 Output Modules 4 Instructions for the Replacement of Output Modules We urgently recommend replacing defective output modules In the event of a module failure or for maintenance purposes please follow the steps described below e Unscrew the cable connector or pull out the output module with its cable connector plugged in Insert the new output module without its cable connector and fasten by screwing e Plug in the cable connector and fasten by screwing e Op
45. Pos Error UINT UINT 1jBus No Rack Pos Error e UINT UINT wBus No Rack Pos Error Code UINT UINT idBus No Rack Pos Error Code UINT UINT 4Bus No Rack Pos Error __ UINT All safety related IO modules listed at the HZ DOS 3 function block may not be used for safety related functions 104 106 Allocation of Standard Building Blocks Appendix 2 15 Function Block HZ FAN 3 This function block is used for the evaluation and display of errors in safety related IO modules One function block can monitor up to eight modules This function block can be used several times in the user program UINT UINT UINT UINT UINT UINT UINT UINT Inputs HZ FAN 3 Error Display Test ee dBus No i i wBus No wBus No dBus No wWBus No wBus No iBus No dBus No Rack Rack Rack Rack Rack Rack Rack I0 Modules i Pos e g 1306 Error Code we Error 4 Pos Error Code yi Error 4 Pos Error Code uw Error 1 Pos Error Code wi HZ FAN 3 Teras j Pos Error Code a Error u Pos Error Codes Error 4 Pos Error Code wi Error Pos Error Code u Error s Bus No Rack Pos e g 1306 UINT BOOL UINT BOOL UINT BOOL UINT BOOL UINT BOOL UINT BOOL UINT BOOL UINT BOOL The positions of the safety related IO modules are indicated by a four digit decimal number Example 13
46. Programmable Systems Safety Manual Systems H41q H41qc and H51q Operating System BS 41q 51q V7 0 8 HIMA Paul Hildebrandt GmbH Co KG Industrial Automation HI 800 013 FEA Important Note All HIMA products mentioned in this manual are protected with the HIMA trade mark As not diffe rently noted down this is possibly also valid for other mentioned manufactueres and their products The technology is subject to changes without notice All technical statements and data in this manual have been worked out very carefully and effective checks and inspections have been applied This manual may however contain flaws or typesetting errors Therefore HIMA does not offer any warranties nor assume legal reponsibility nor any liability for the possible consequences of any errors in this manual HIMA would appreciate being informed on possible errors Table of Contents About this Manual This manual contains Information for proper application of the safety rela ted HIMA Automation Devices H41q and H51q The knowledge of regulations and the technically perfect transfer of the safety advices contained in this manual carried out by qualified staff are prerequisites for the safe installation start up and for the safety during operation and maintenance of the HIMA Automation Devices In case of unqualified interventions into the automation devices de acti vating or bypassing safety functions or if advices of this manual are neg lected
47. Value 6 Error 3 BOOL UINT dInput Value 7 Output Value 44 UINT UINT dInput Value 3 HA PMU 3 Error BOOL BYTE 1 4 20 O 0 20mA Output Value Su UINT BYTE Nees Values O Values in 0 1 Error 5 3 BOOL UINT wd8 8 Bit l2 12 Bit Analog Value Output Value 64 UINT BYTE sDamping O none 1 Damping Error 61 BOOL UINT d Output Value 74 UINT UINT Error 74 BOOL Output Value Su UINT Error 81 BOOL 95 106 Appendix Allocation of Standard Building Blocks 2 5 96 106 Function Block HA RTE 3 This function block is used to process values and to indicate errors of safety related analogue input modules in single channel or redundant operation It must be used once in the user pro gram for each safety related analogue input module F 6213 F 6214 If two parallel redundant IO modules are used the function block must exist only once in the user program HA RTE 3 Monitoring Analog Testable Input Modules UINT gBus No Rack Pos e g 1305 Value lw UINT gBus No Rack Pos red BG Error Value 1 BYTE gused Channels Value ZHe 1 Error Value Z l UINT gTolerated Differ red Values in 0 1 Value 3 BYTE y0 no Damping 1 Damping Error Value 34 1 UINT gTolerated Time Differ red Inputs in ds Value 44 MOS A sTest Switch Module HA RTE 3 Error Value 4 1 MOS A Test Switch red Module UINT gMaximal Test Time in min BYTE sgTest 4 Channels
48. Your Notes 54 106 Software for H41q H51q Chapter 5 Software Chapter 5 Software 1 Software for Safety related HIMA H41q H41qc and H51q Automation Devices The software for the safety related HIMA automation devices of the H41q H41qc and H51q system families is subdivided into three blocks operating system user program and programming tool according to IEC 61131 3 ELOP II sys tem software package with integrated safety tool The operating system is to be used in its latest applicable version which is TUV certified for safety related applications This version can be found in the common document List for tracing the version releases pertaining to the modules and Firmware of the Company HIMA Paul Hildebrandt GmbH Co KG This document is created by the common modification service of TUV Product Service GmbH IQSE and HIMA The user program is created with the help of the ELOP II system software package and con tains the plant specific functions which the automation device is to perform The ELOP II sys tem software is the parameterizing platform for operating system functions The user program is compiled into the machine code by a code generator This machine code is transmitted to the Flash EPROMs of the central module of the automation device via a serial interface The main functions of the operating system and the specifications for the user program derived from them are listed in the table below 55 106 Chapter 5 So
49. acks for the H41q H41qc and H51q systems Systems H41q H41qc System H51q The input modules are plugged into The input modules are plugged into the system subrack IO subracks IOSR having 16 IO Kits with 12 slots H41q or 13 slots module slots each H41qc for IO modules are avail The required basic components for able IOSRs are assembled in kits If a plant operates in deenergized to trip mode the reaction to a fail ure of an input module has to be if no redundancy exists e Transition into safe state if necessary shutdown e Annunciation of the failure If a plant operates in energized to trip mode e g fire alarm systems see Chapter 6 Operating Conditions then if no redundancy exists the PES has to do e Annunciation of the failure of the input module e No further reaction necessary Safety of Sensors Detectors Transmitters Safety related signals are only given if the external sensors detectors or transmitters have a related proof of safety Safety related operation of external sensors detectors or transmitters can also be ensured by special wiring see below If the transmitters have no proof of safety the detectors have to be wired in a 1002 2003 or NooM circuit Remark 1002 means 1 out of 2 The safety and availability of the sensor technology can be increased by a 1002 2003 or NooM circuit of the sensors Methods of implementing various ways of sen
50. an error only the value from the operative module is processed 2 4 1 Test Routines Via the test DA converter the test values are applied and tested via the AD converter which also digitizes the input signal 21 106 Chapter 3 Input modules 2 4 2 Response of the System on Failures Detected at Safety related F 6213 F 6214 Analogue Input Modules Safety and availability Type of failure Response of system Comment Module or channel failure with single channel ana logue inputs The configured value is pro cessed by the HA RTE 3 function block see appen dix In the event of an error the only possible response is switching to the safe state Module or channel failure with redundant analogue input modules and redun dant transmitters If an input module fails the value coming from the redundant module or the configured error value is pro cessed Either min max or mean value generation via the HA RTE 3 function block see appendix Short circuit in the trans mitter circuit Display of the module posi tion and the faulty channel on the diagnostic display only when using 4 20 mA 2 4 3 Response of the System on Failures Detected at Safety related F 6217 Analogue Input Modules 22 106 Type of failure Response of system Comment Channel failure Analog value 0000 Channel error bit TRUE Channel error bit must be processed in a safety rela
51. and by supply is to be carried out fast enough to ensure uninterrupted duty Voltage drops up to 10 ms are admissible During malfunctions of the system the system variables defined in the user program are writ ten by the operating system So an error signalling for the failures detected by the system can be programmed Safety related inputs and outputs are switched off in the case of an error i e processing of Low signals in all channels of the faulty input module and switch off of all channels of the faulty output module Central Fire Alarm Systems Chapter 5 Software For Your Notes 87 106 Chapter 6 Operating Conditions Climatic conditions Chapter 6 Operating Conditions The safety related controls H41q H41qc and H51q are developed to observe the requirements of the following standards for EMC climate and environmental conditions IEC 61131 2 Programmable Controllers Part 2 Equipment Requirement and Tests IEC 61000 6 2 EMC Generic Standard Part 6 2 Immunity for Industrial Environments IEC 6100 6 4 Electromagnetic compatibility EMC Generic Emission Standard Industrial Environment 1 Climatic Conditions The most important tests and limits for climatic conditions are listed in the table below EN 61131 2 Climatic Tests Chapter 6 3 4 Temperature operating 0 60 C Test limits 10 70 C Storage temperature 40 80 C with battery only 30 C 6 3 4 2 Dry heat
52. arm or shutdown if the permissible limit value is achieved al eR Oo or fT Of jimit limit Safety aspects If one of the transmitters responds or if a component inside the system fails output A has L signal As normal transmitters are used we recommend checking the sensor circuits at regu lar intervals e g after a couple of months if the signals are not switched through the process within shorter periods of time In addition to this we recommend monitoring to verify whether the signals are equal parameterization of the HA RTE 3 function block Availability aspects No availability as each component failure or the response of a sensor results in a shutdown Safety Aspects User Program Chapter 5 Software 4 3 3 6 Input Modules with 2003 Circuit control ead i A A discrepancy signal A2 ly 2003 g f current discrep time P signals of 3 different function block 2003 signals to logic annunciator input modules the control signal is TRUE if sensori s gt j sensorz i gt E sensors 2 or 3sensors are TRUE l IN TON ggg signal 4 Jaiscrepancy te PT BT s discrepancy signal is TRUE if 1 or 2 sensors differ from the control signal and after the discrepancy time has elapsed m control signal a Function block 2003 and logic of the function block For practical reasons the circuits shown above are combined to form the function block 2003 In a PES
53. aster and a separate bus for safety related data transmission with a baud rate of 57 6 kbit s The data transmission time T7 taken from the point of time a sensor at a PES changes up to the point of time an output responds at another PES is the following Ty 2 22 2 Tp 222 ZZ cycle time of PES 1 ZZ cycle time of PES 2 Tp data transmission time between two PES depending on the type of data connection used Serial data connection use the value of the bus cycle time To determine the bus cycle time refer to the operating system manual section Safety related data transmission via HIPRO S Ethernet connection assume the maximum transmission time refer to the datasheet of the F 8627 X section Calculating the Monitoring Time for HIPRO S HIPRO S DI RECT Connections As the import variables are updated at regular intervals a monitoring time can be set via the SIO parameters in the dialog for resource properties The relevant factor is the applicable safe ty delay time of the plant PESs If no imported safety related variables are written within the defined period of time this fact is annunciated by setting a system variable Moreover the user can parameterize that all those variables in the automation device are set to 0 in this case 83 106 Chapter 5 Software Safety Aspects for Communication 5 3 Instructions for the Creation of the User Program The Ethernet network in ELOP II for HIPRO S is configured automatically
54. ble code if memory gaps exist Area version number The area version number records all variables defined in a project It will change if modules are deleted or new modules are set e if more variables are allocated to the attributes of the following types than are deleted HIPRO N HIPRO S BUSCOM event 3964R the memory has to be reorganized This may occur when the capacity limit of the mem ory is reached and if gaps have formed in memory allocation due to prior repeated gen eration of codes Changes of the basic addresses for external MODBUS coupling may but do not necessarily have to result in a change of the area version number Procedures and Functions of the Operating System The operating system processes the user program in cycles The following shows this se quence in simplified form e Reading of input data e Processing of the logic functions according to IEC 61131 3 Section 4 1 3 e Writing of output data The cycle also comprises the following essential functions e Extensive self tests e Tests of the IO modules during operation e Data transfer and data comparison A cycle is processed in seven stages These stages are shown in detail in the operating system manual HI 800 105 Safety Aspects ELOP Il Chapter 5 Software 3 3 1 Safety Aspects Concerning Programming with ELOP Il For implementing the application program the programming tool ELOP II is used It can be used on standard PCs runni
55. check list archiving number Position in subrack OSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment 1 Are the inputs of this module named which perform a safety related function 2 Does a redundant module exist for this module 3 If yes is the redundant module of the same type 4 Are the input leads correctly connected and laid considering safe electric isolation 5 Is the connection wiring done by using cables with safety isolation according to IEC 61131 2 Ed 2 2003 no longer required if the use of the module meets SELV or PELV conditions 31 106 Chapter 3 Input modules Check lists 4 6 F 5220 Safety related Counter Module 2 channel F 5220 Safety related counter module Check list No SDIGE F5220 E 2 channel Version 2 0 32 05 Project data Project designation File name of the check list archiving number Position in subrack OSR Requirements for the project planning of the module and the user program ease i fulfilled equiremen ommen Are the inputs of this module named which perform a safety related function 2 Is each safety related module evaluated by the HF CNT 3 4 building block 3 Are the pulse inputs for proximity See data sheet switches correctly connected 4 Are the pulse inputs for mechanical con See data sheet tacts correctly connected 5 Has the HF CNT 3 4 building block See Safety Manual been parameter
56. cially true for fire detectors without mechanical contacts but electronic outputs The alarm output circuits for controlling lamps and audible alarms etc are also carried out in the open circuit principle Therefore output modules with monitoring for line break and short circuit must be used for instance the F 3331 or F 3334 output modules The control of visualization systems indicator light panels LED displays alphanumeric dis plays audible alarms etc can be realized with an according user program For this purpose other products can be used The transmission of fault signals via input output modules or to transmission modules for fault signals must be made in the closed circuit principle The transmission of fire alarms between HIMA systems can be realized by using the commu nication standards available such as MODBUS HIPRO S or OPC Ethernet Monitoring of the communication is part of the user program It is recommended using redundant communi cation to ensure transmission even if a transmission component line hardware fault etc fails The failure of a component must be indicated and it should be possible to replace or repair the faulty component during operation The H41q H41qc or H51q systems used as control and indicating equipment must have redun dant power supplies Precautions must be taken in case the electricity supply system fails for example battery operated alarm horns The switch over between mains supply and st
57. ct Version Management of ELOP Il is used to store and manage ELOP II objects in an archive These data may be copied from the archive any time for further processing For the time being the data of the following objects can be stored and administrated in an ar chive e POU program type function type of function block e data type e global variable program type instance e task e document object The following possibilities are provided Saving of the working version of the object as a version in the archive e Copying an object version from the archive Note In project management you can further process the current object version after archiving one As all versions of the object are stored in the archive you can copy a version from the archive other than that most recently saved If an object version is copied from the archive it will replace the work ing version in project management For further explanations see the online help of the ELOP II program 63 106 Chapter 5 Software Safety Aspects ELOP Il 3 1 4 3 2 3 3 3 3 1 64 106 Check of the User Program to Meet the Specified Safety related Function The user has to perform a number of suitable test cases covering the specification It is not necessary to perform 220 test cases for a 20 channel AND gate Normally the independent test of each input and the most important logic circuits should be sufficient This extent of test case is s
58. cumentation is freely adjustable The documentation is part of the function acceptance of a plant subject to approval by an in spection authority TUV The function acceptance only applies to the user function but not to the safety related HIMA automation devices H41q MS H51q MS H41q HS H51q HS H41q HRS H51q HRS These devices have a prototype certificate For plants subject to approval we recommend for the project planning to engage the authority in charge as soon as possible Safety Aspects for Communication Chapter 5 Software 5 5 1 5 2 Safety Aspects for Communication Safety related Data Transmission The communication protocol HIPRO S is certified for SIL 3 Safety related Communication In the notebook Resource properties the data exchange with safety related allocated resourc es can be monitored via the PES master For this purpose a monitoring time can be set as Time Interval parameter and the command delete imported variables can be activated as soon as the monitoring time is exceeded The monitoring time to be set depends on the process and must be agreed with the acceptance authority The safety related communication can also be effected via the F 8625 F 8626 F 8627 X and F 8628 X Ethernet communication modules They use the protocol safeethernet certified by TUV Time Requirements In order to achieve a constant transmission time we recommend providing a separate PES m
59. d by flags the writing property and the crosstalk of the registers and the ALU are tested e Test of the memory areas The operating system the user program the constants and parameters as well as the variable data are stored in the central module in a direct and an inverted version By a hardware comparator they are checked for antivalence e Permanent memory areas The operating system the user program and parameter area are each stored in a Flash EPROM and they are assured by a CRC test e RAM test The RAM areas are tested by a read write test especially for crosstalk e Watchdog test The watchdog signal is switched off unless it is triggered within a determined period of time by both CPUs with antivalent bit patterns or if the hardware comparator between the two memories direct and inverted detects a difference A fur ther test checks the switch off capability of the watchdog signal Test of the connection to the IO level within the central module With redundant central modules in the systems H41q HS H41qc HS H51q HS and a single channel IO bus the interlock of the IO access of the central module is protected via an arbiter circuit The arbiter circuit is checked by self tests With a two channel IO level HRS system the right to IO access is read back and checked With a single channel IO level MS system single channel IO modules and single channel CPU the right to IO access is read back and checked Test o
60. d outputs may be reset by two separate force main switches For further details on the forcing procedure are stated in the User Manual Before starting the safety related operation all force markers must be removed from the application program Details of force markers are described in the online help of ELOP II Protection against Manipulations The user must determine the measures for the protection of the sys tem against manipulation in co operating with the test authority in charge Protective mechanisms are integrated in the PES and in the programming system ELOP Il which prevent unintentional or unauthorized changes to the safety system 1 In the PES the system parameters can be set in way that a change of the program is not possible without reloading 2 The ELOP II programming system has a hardlock and can additionally be protected against unauthorized access by the password mechanisms provided in Windows The requirements for the safety and application standards concerning protection against manipulation have to be obeyed The operator is responsible for the authorization of employees and the necessary pro tective measures Safety Aspects User Program Chapter 5 Software 4 4 1 4 2 4 2 1 Safety Aspects Concerning the User Program General Programming Procedure for Automation Systems of the H41q H51q Families for Safety related Applications e Specification of the control function
61. e application of the Ex i module as stated in the data sheet and the appendix to the EC type examination certificate been met 29 106 Chapter 3 Input modules Check lists 4 4 F 3240 Safety related Digital Input Module 16 channel F 3240 safety related digital input module Check list No SDIGE F3240 16 channel Version 2 0 32 05 inhi Project data File name of check list archiving number Project designation Position in subrack OSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment 1 Are the inputs of this module named which perform a safety related function 2 Does a redundant module exist for this module If yes is the redundant module of the same type Are the input leads correctly connected and laid considering safe electric insula tion 5 Are cables with double or reinforced insu lation used for the connection wiring 6 Can it be made sure that the input signals lead up to 127 V AC 7 Can it be made sure that the input signals lead up to 110 V DC according to IEC 61131 2 Ed 2 2003 no longer required if the use of the module meets SELV or PELV conditions ie ro 30 106 Check lists Chapter 3 Input modules 4 5 F 3248 Safety related Digital Input Module 16 channel F 3248 Safety related digital input module Check list No SDIGE F3248 16 channel Version 2 0 32 05 Project data Project designation File name of
62. e in the PES Value depending on the system capability Failures whose effects may be critical for safety only in combination with additional faults are detected by background tests within the Multiple Fault Occurrence Time The Multiple Fault Occurrence Time is determined with the setting of the safety time fault tolerance time In the operating system it is defined as 3600 times that value Two types of tests are distinguished e Tests performed during the safety time They are performed within the safety time foreground tests Response time immediate response at the latest within the safety time e Tests performed during the multiple fault occurrence time They are performed during the multiple fault occurrence time and are subdivided into many cycles background test Response time immediate response upon detection of the fault at the latest within the multiple fault occurrence time Example for the response time maximum double the cycle time If a fault tolerance time safety time of 1s is required for the process the cycle time may not exceed 500 ms Fault response time The fault response time of an automation device corresponds to the safety time S 1s defined in the properties for the resource Special attention should be paid to the fact that the cycle time does not exceed half of the safety time as the response to faults in the input modules comes within max 2 cycles The cycle itself depends on the safety time which determine
63. ed Max Time Inrush Current in ms Mod and Max Time Inrush Current in ms red Mod Determination of the delay time for the detection of a line break or time allowed for the tolerat ing of the current limit During this time the error display is suppressed An increase of the de lay time results in an increase of the cycle time The outputs Pulse on Error 2x Error Error Code Mod and Error Code red Mod are for information purposes only and no safety related action in the user program must be de rived from them 98 106 Allocation of Standard Building Blocks Appendix 2 8 Function Block HB RTE 3 This function block is used for evaluating and displaying errors of safety related digital input modules in single channel or redundant operation It must be used once in the user program for each input module type F 3237 or F 3238 or respectively for two input modules type F 3237 or F 3238 working in parallel HB RTE 3 Monitoring Digital Testable Input Modules Output 1 BOOL UINT wBus No Rack Pos e g 1305 Output zs BOOL Output 34 BOOL UINT dBus No Rack Pos red Mod Output 4 4 BOOL Output 5 BOOL BYTE dused Channels Output 6 4 BOOL HB RTE3 Output a BOOL oie Output 8 BOOL i Channel Error Mask WORD BYTE t41 1002 2 2002 Trip Other Error Code Pulse y BOOL UINT aTolerated Fault Time in min Other Error Code Pulse BOOL UINT sTole
64. ee 59 Application of the Safety Tool of ELOP II for the Creation OL ING FOOraM sve nre oR atau ee ated ta ae eas A ae see he Re eae Meee 60 Application of the Safety Tool of ELOP II for Program Mo difiGations sds kamers ew ede Sie eels oes Pelee eth ety aae We Slee Soe arene o ah 60 Program Identification Possibilities 0 0000 eee 62 Check of the User Program to Meet the Specified Safety related Function 64 Guidelines for the ELOP Il User 0 0 0 0 c cece es 64 Parameterization of the Automation Device 00 002 c eee ees 64 Safety eia sath E weed ae RA aed dS ence eat hee A Lee as 64 Failures in Safety related Output Amplifiers 202000005 65 Check list Measures Required for the Creation of a User Program cereos pe ee ee ee e nba heal oe het Oe ee eRe a 66 Reload Reloadable Code 4 ossazeoieddenatzecteatet 42 Med ower bea ove ak 68 Systems with one Central Module 0000 cee eee 69 Systems with Redundant Central Modules 0000 0c eee eee eee 69 Offline TeSt e Sroine stewie eal aa ea E T wigan et dee Saeed 69 FOrCINg ssh te acetone nae Sadan dh BLAS Seo HAS Eo ee Ra ada Gos Lats Eae 69 Protection against Manipulations 00 0c cece eee 70 Safety Aspects Concerning the User Program 000e ee eee eens 71 General Programming Procedure for Automation Systems of the H41q H51q Families for Safety related Applications 71
65. ent Conditions For safety related operation only the fail safe hardware modules and software compo nents approved for such use are to be used The approved hardware modules and soft ware components are listed in the List for tracing the version releases pertaining to the modules and Firmware of the Company HIMA Paul Hildebrandt GmbH Co KG Certificate No 968 EZ 129 00 02 Each running version is to take from this list which is commonly managed with the certifica tion authority The conditions of use specified in chapter 6 regarding EMC mechanical and climatic effects must be observed Non fail safe but interaction free hardware modules and software components may only be used for the processing of signals not relevant to safety but not for the processing of safety related tasks The closed circuit principle has to be applied to all safety circuits connected externally to the system Hardware Project Planning Product Dependent Conditions Safe electrical isolation from the mains supply must be ensured for all devices connected to the system The safe electrical isolation of the power supply must be performed in the 24 V supply of the system Only PELV or SELV version power supplies may be used Programming Product Independent Conditions In safety relevant applications there must be regarded carefully the correct setting of the system parameters which have an effect on safety Possible parameteri
66. er program Are functionally independent parts of the PES encapsulated by the use of function and function building blocks Is it taken into consideration that after a change of variable names and subsequent reload a re initialization of the variables is performed Is it taken into consideration that after a reload set outputs will remain set although these set outputs are not assigned a value after the deletion of parts of the user logic If the online change of a constant is to be retained after reload Has this constant been adapted accordingly in the program prior to the generation of the code 66 106 Safety Aspects ELOP Il Chapter 5 Software After modification Notes verifications Comments Prior to loading Have all force markers been removed from the application pro gram Has a review of the user program against the binding specifica tion been performed by a person not involved in the implemen tation of the program Has the result of the review been documented and released date signature Has an off line test been performed After loading Is the RUN version of the program which can be changed online identical to the RUN version of the program adapted after an on line change of constants Check at the diagnostic display Has the desired program been loaded Check at the diagnostic display Does the error display show non existing modules
67. er program is to be used or the reference temperature is to be determined via comparison of the reference temperatures of two modules All possible deviations have to be considered and have to be regarded in the evaluation of the measuring values For use in SIL 3 the input temperature is to be determined via comparison of the temperatures of two different thermocouples 23 106 Chapter 3 Input modules Safety and availability 2 6 2 6 1 2 6 2 24 106 The F 6221 Safety related Analogue and Intrinsically Safe Input Module The analogue input module has eight channels for the direct connection of analogue transmit ters from the Ex area The transmitter supply voltage can be delivered from the output module F 3325 or other generators according the data sheet standards This transmitter supply volt age is to connect via the module F 6221 for monitoring Each used channel is parameterized via a separate function block HF AIX 3 Test Routines The module has its own 1002 microprocessor system which automatically performs safety re lated online tests The safe data for the safe signal processing are available through the HF AIX 3 function block Each of the eight channels supplies safe input values and a safe error status Response of the System on Failures Detected at Safety related F 6221 Analogue Input Modules Type of failure Response of system Comment Module failure The Value output INT at the HF A
68. erate the acknowledgement button push button marked ACK on the central mod ule 43 106 Chapter 4 Output Modules 5 44 106 Check lists Check Lists for Project Planning Programming and Commissioning Safety related Output Modules For each safety related output module used in a system a check list must be completed to en sure that all relevant requirements are met This is to be done during project planning or com missioning This is the only way to make sure that the requirements are recorded clearly and completely At the same time the check lists serve as evidence that project planning has been carried out carefully The check lists of this Safety Manual are available as MS Word files doc on a data medium SDIGA F3330 SDIGA F3331 SDIGA F3333 SDIGA F3334 SDIGA F3335 SDIGA F3348 SDIGA F3349 SDIGA F3430 e SANAA F6705 for safety related analogue modules for safety related digital modules for safety related digital modules for safety related digital modules for safety related digital modules for safety related digital modules for safety related digital modules for safety related digital modules for safety related digital modules Check lists Chapter 4 Output Modules 5 1 F 3330 Safety related Digital Output Module F 3330 safety related Check list No SDIGA F3330 E digital output module 8 channel Version 2 0 32 05 Project data Project designation File name of c
69. escribed below are approved for operation in safety related automation de vices The special programming instructions described in this section must be adhered to For more detailed information on the functions of these function blocks and the allocation of the inputs and outputs please refer to the Manual ELOP II Resource Type Function Block H8 STA 3 This function block is used to configure group shutdown It is used once in the user program for each shutdown group H8 STAi 3 Grouping of Safety Related Outp Modules UINT dBus No Rack Pos e g 1306 UINT dBus No Rack Pos UINT dBus No Rack Pos UINT dBus No Rack Pos UINT wdBus No Rack Pos UINT wdBus No Rack Pos H8 STAS UINT dBus No Rack Pos UINT dBus No Rack Pos UINT dBus No Rack Pos UINT dBus No Rack Pos UINT dBus No Rack Pos Group Amplifier Control Group Relays BOOL UINT dBus No Rack Pos red Group Amplif Cont red Group Rel 1 BOOL Function block inputs The positions of the modules belonging to a shutdown group are designated by a four digit decimal number according to the determination in the selected resource Example 1306 means Cabinet 1 subrack 3 module position 06 For one of the inputs Bus No Rack Pos Group Amplif or Bus No Rack Pos red Group Am plif a possible but non existent slot has to be entered Module outputs Names of the group amplifier channels Further programming in the logic o
70. f the connection module on the IO subracks The addressing is tested in cycles each time a safety related IO module has been pro cessed The addresses of all agreed IO module positions are read back and tested The safety switches of the F 7553 module are tested Response on Errors Detected in Central Modules The test routines ensure that errors are detected and that the defective central module is switched off At the same time the diagnostic display indicates the errors and enters them into the system diagnosis For a central module MS system this means a complete shut down of the automation device In case of redundant central modules HS and HRS systems the defective central module is switched off and the second one continues operation If in redundant systems the defective central module is replaced by a new one having the same user program the new central module receives the current data from the running central mod ule and the system returns to redundant operation 13 106 Chapter 2 Central Modules Principles of function 3 3 14 106 Diagnostic Display The diagnostic display is part of the central module It consists of a 4 digit alphanumeric display for the representation of texts and values of an LED for the general display of central module faults and an LED for the general display of faults in safety related IO modules An acknowl edgement push button ACK and two push buttons for calling further system informa
71. f the user program is not necessary Output modules having integrated safety shutdown do not need group shutdown However group shutdown may be configured for these A modules In this case all modules belonging to a group are switched off if one output module fails according to the settings in function block H8 STA 3 93 106 Appendix Allocation of Standard Building Blocks 2 2 2 3 94 106 Function Block HA LIN 3 This function block is used to linearize temperature measurements with thermocouples and Pt 100 resistance thermometers Correct parameterization must be verified if the values are to be used for circuits relevant to safety see Manual ELOP Il Resource Type HA LIN 3 Temperature Evaluation UINT Value 1 Value 1 0 1000 UINT BOOL Error Value 1l Value 1 in 0 1 Deg C UINT UINT dValue Z Sigm Value 14 BOOL BOOL wWJjError Value Z Error Value Lau BOOL UINT WValue 3 Value 2 0 1000 UINT BOOL jError Value 3 Value Z in 0 1 Deg C i UINT UINT wV alue 4 Sign Value Zu BOOL BOOL HError Value 4 HA LIN 3 Error Value 2 BOOL UINT wInit Val in 0 1Deg Cent Value 3 0 1000 sw UINT UINT wSign Initial Value Sensor Type Value 3 in 0 1 Deg C y UINT UINT WdMeasuring Span in 0 1Deg Cent Sign Value 3 4 BOOL UINT 1Digital Initial Value Error Value 33 BOOL UINT wDigital End Value Value 4 0 1000 a UINT UINT tdPermissible Analog Value Unde
72. for testoperation in min Forcevalue for testoperation TRUE right Counter 24 BINT Output state Rotation direction FALSE left Line break Short circuit Active Error Remaining time Counter Z4 bit Output state Rotation direction TRUE right FALSE Line break Short circuit Active Error Remaining time Module error code u Allocation of Standard Building Blocks Appendix 2 12 Function Block HF TMP 3 One HF TMP 3 function block is used for each channel of the F 6220 thermocouple module A channel without proper configuration via HF TMP 3 doesn t work i e the output values are 0 or FALSE respectively There is no default functionality or setting A type 1 sensor may only be assigned to channel 9 HF TMP 3 Ternperature measurement for F6220 The signal Enable external comparison temperature will only be evaluated if the mode is set to temperature measurement values 2 8 at the Senor type input If the above mentioned input Enable external comparison temperature is TRUE the value given at the External ref erence temperature input is taken as reference value If the input is FALSE the value of the resistance temperature detector located on the module will be processed as reference temper ature The Value output of the function block indicates 0 in case of a channel or module failure Therefore the Channel error output must be evaluated by the user program and a special
73. ftware Software for H41q H51q 56 106 Functions of the operating system Specification in user program Cyclical processing of the user program Function blocks functions variables HIMA standard function blocks included in the operating system Standard function blocks variables Configuration of the automation device 1 or 2 IO buses number of power supply modules etc Determination by the resource type Reload of the user program possible adherence to restrictions see ELOP II Resource Type H41q H51q Manual Tests in the central area and in the IO bus Tests of IO modules depending on the type Type of IO module Response in the event of a failure in parts specified in other parts configurable Diagnostic display Diagnosis mode for testable IO modules HZ DOS 3 function block diagnosis not safety related Communication via serial interfaces with personal computer permissible actions during operation ELOP II Determination in the resource type External coupling to master system Variable declaration Variable names BUSCOM External coupling to slave systems Variable declaration HK MMT 3 function block Event transmission Variable names event controlled PES master not safety related Variable declaration HIPRO N communica tion PES master Ethernet communication safety related Variable declaration safety related HIPRO
74. function block all the positions of the output amplifiers belonging to one group are set If one output module fails all the output amplifiers belonging to this group are shut down For the safety of the system the integrated safety shutdown of the output modules alone is sufficient 4 3 3 2 Function Blocks for Individual Safety related IO Modules 76 106 Input module Output module digital digital Function Block Function Block F 3237 HB RTE 3 F 3331 HB BLD 3 4 F 3238 HB RTE 3 F 3334 HB BLD 3 4 F 5220 HF CNT 3 4 F 3349 HB BLD 3 4 analogue analogue F 6213 HA RTE 3 F 6705 HZ FAN 3 F 6214 HA RTE 3 F 6220 HF TMP 3 Safety Aspects User Program Chapter 5 Software 4 3 3 3 connection of 4 3 3 4 Input module Output module F 6221 HF AIX 3 For the safety related IO modules the associated function blocks must be entered into the user program For further information see Appendix check list and description of the function blocks in the Manual ELOP II Resource Type Redundant IO Modules To increase availability without affecting safety safety related input or output modules can be switched in parallel as shown in the sketch below Maximum availability is achieved if in this case also automation devices with 2 IO buses are used and if the redundant IO signals are input into separate IO modules sc Ho o Logic
75. h risk potential it has and which standards for operation are applied and form the bases for the approval by the test authority in charge According to the standards IEC 61508 1 7 IEC 61511 1 3 IEC 62061 and VDI VDE 2180 sheet 1 to 4 in case of safety related systems the operating company has to arrange for proof tests Periodic Proof Testing The HIMA PES can be proof tested by executing the full safety loop In practice the input and output field devices have a more frequent proof test interval e g ev ery 6 or 12 months then the HIMA PES If the end user tests the complete safety loop because of the field devices then the HIMA PES is automatically included in these tests No additional periodic tests are required for the HIMA PES If the proof test of the field devices does not include the HIMA PES then the PES needs to be tested as a minimum once in 10 year This can be done by executing a reset of the HIMA PES In case there are periodic proof test requirements for specific modules then the end user should refer to the data sheets of these modules Safety Requirements Chapter 1 Safety Philosophy 2 2 1 2 2 2 3 2 4 Safety Conditions The operating company is responsible for operating a plant safely according to the relevant application standards For use of the safety related PES of the systems H41q H41qc and H51q the following safety requirements are valid Hardware Project Planning Product Independ
76. he Process I amp C technology concept of the plant must contain the analysis of the field circuits i e the kind of sensors and actuators Sensors digital or analogue e Signal in normal operation closed circuit current principle for digital sensors life zero for analogue sensors e Signal in the event of an error or failure e Determination of redundancies required for safety related operation 1002 2003 e Monitoring of discrepancies and response Actuators e Position and activation during normal operation e Safe response position in the event of a shutdown or power failure The created user program should be e easy to understand e easy to trace e easy to change Variable Declaration and Entering of Process I amp C Names With the help of the variable declaration editor the variables and their data types are defined Symbolical names are allocated to all variables of the user program These symbolical names may have up to 256 characters For physical inputs and outputs symbolical Process I amp C names are used which also may have up to 256 characters For the user the use of symbolical names instead of the physical address has two essential advantages e Inthe user program the plant names of inputs and outputs are used e Changes of the allocation of the signals in the input and output channels do not affect the user program 73 106 Chapter 5 Software Safety Aspects User Program 4 3 2 1 Allocation of Process I
77. heck list archiving number Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment yes no 1 Are the outputs of this module named which perform a safety related function 2 Does a redundant module exist for this module 3 Are at most 10 output modules energized with rated load assembled within one IOSR 4 Has a supplementary circuit with a 4 7 Q series resistor been implemented for lamp wattages from 4 W to 10 W 5 Are free wheeling circuits provided at the actuators 45 106 Chapter 4 Output Modules Check lists 5 2 F 3331 Safety related Digital Output Module F 3331 safety related Check list No SDIGA F3331 E digital output module 8 channel Version 2 0 32 05 Project data Project designation File name of check list archiving number Requirements for the project planning of the module and the user program fulfilled Requirement Comment 1 Are the outputs of this module named which perform a safety related function 2 In case of line monitoring Does an HB BLD 3 building block exist for each module in the user program in case of non redundant operation 4 Incase of line monitoring Does one HB BLD 4 building block exist in the user program for two redundant mod ules 5 Is each safety related output evaluated by the HB BLD 3 or HB BLD 4 building block 6 Has the HB BLD 3 or HB BLD 4 building block been
78. his Safety Manual must be applied At present the transfer of safety related data via public networks e g Internet is not admissible Ifthe data are transferred via internal networks of a company or factory a sufficient pro tection against manipulation must be reached by administrative or technical actions e g blocking of the safety related part of the network against access from others with a fire wall To the communication interfaces may only be connected equipment providing a save elec trical isolation Special Operating Modes Product Independent Conditions Online modifications in safety applications are only permitted after consultation with the test authority responsible for plant acceptance and with the aid of certified tools approved for this purpose ELOP II version 3 5 During the entire online modification the person responsible for the online modification must ensure that there is sufficient safety monitoring of the process through other techni cal and organizational measures Prior to each online modification the version changes against the application software cur rently running are to be determined with the aid of a certified tool approved for this pur pose With ELOP II version 3 5 this tool is to be the C code comparator Inthe case of mono online modifications the duration of the entire modification plus twice the cycle time may not exceed the failure tolerance time of the
79. ilures in Safety related Output Amplifiers Parameter Display only Switch off by means of the integrated safety shutdown inside the output amplifier If not possible then shutdown of the watchdog signal in the IO rack by means of the coupling module only in systems H51q No shut down of the watchdog signal of the appertaining central unit This parame ter is permissible only up to SIL 1 Parameter Emergency off Switch off of the watchdog signal of the appertaining central unit and thus shutdown of the output amplifiers Parameter Normal operation Reaction as with parameter Display only additionally switch off of the watchdog signal of the appertaining central unit if necessary Parame terization required from SIL 2 Normal and recommended parameter 65 106 Chapter 5 Software Safety Aspects ELOP Il 3 4 Check list Measures Required for the Creation of a User Program Measures required for the creation of a user programme Checklist No MEAP 0001 E Version 2 1 02 07 Project data Project designation File name of checklist archiving number Notes verifications Comments Prior to change Is the configuration and the user program based on a safety assessment Are programming guidelines used to create a user program Are only tested and approved programming organization units functions function blocks program used to create the us
80. ion is deleted in a reload e g a function controlling a physical output the process image remains unchanged Therefore all the out puts affected by a reload must be deleted That means the outputs to be deleted by a reload have to be reset before the reload If an input variable VAR_INPUT of a function block is no longer writ ten after a reload e g because the variable or assignment left of the function block has been deleted the input variable keeps its former value and is not reset automatically to FALSE 0 This behaviour concerns all function blocks but not the functions The cause of this behaviour is the fact that during reload all values of all variables are stored to make possible a continuous operation Inputs of standard and user defined function blocks are processed internally as variables Remedy such an input must be connected to a new variable set to the desired value All variables with the attribute const are set to their initial value again during a reload even if they were assigned other values online All system parameters are set to their configured value again during a reload even if they were assigned other values online This may have influence on watchdog safety time baud rate of the interfaces and many other things If a reload of the user program of the central module s is possible this is indicated by the mes 68 106 Safety Aspects ELOP Il Chapter 5 Sof
81. ithout its cable connector and fasten by screwing e Plug in the cable connector and fasten by screwing e Operate the acknowledgement button push button marked ACK on the central mod ule 25 106 Chapter 3 Input modules Check lists 4 26 106 Check Lists for Project Planning Programming and Commissioning safety related Input Mod ules For each safety related input module used in a system a check list must be completed to en sure that all relevant requirements are met This is to be done during project planning or com missioning It is the only way to make sure that the requirements are recorded clearly and completely At the same time the check lists serve as evidence that project planning has been carried out carefully The check lists of this Safety Manual are available as MS Word files doc on a data medium e SDIGE F3236 for safety related digital modules e SDIGE F3237 for safety related digital modules e SDIGE F3238 for safety related digital modules e SDIGE F3240 for safety related digital modules e SDIGE F3248 for safety related digital modules e SANAE F5220 for safety related analogue modules e SANAE F6213 6214 for safety related analogue modules e SANAE F6217 for safety related analogue modules e SANAE F6220 for safety related analogue modules e SANAE F6221 for safety related analogue modules Check lists Chapter 3 Input modules 4 1 F 3236 Safety related Digital Input Module 16 channel
82. itoring of the sensor channels evaluated Has the building block HB RTE 3 building block been parameterised according to the requirements stated in the manual See Safety Manual appendix Are the unused inputs of the module wired accordingly E Created by 28 106 Check lists Chapter 3 Input modules 4 3 F 3238 Ex i Safety related Digital Input Module 8 channel F 3238 Safety related Check list No SDIGE F3238 E digital input module 8 channel Version 2 0 32 05 i Project data File name of check list archiving number Project designation Position in subrack OSR Requirements for the project planning of the module and the user program ey i fulfilled i equiremen ommen Are the inputs of this module named which perform a safety related function 2 Is each safety related input evaluated by the HB RTE 3 building block Does a redundant module exist for this module Does an HB RTE 3 building block exist in the user program for each module or for two parallel redundant modules 5 Are safety related proximity switches connected to the module 6 Are the contactors equipped with resistors 1 k 10 k Is the line monitoring of the sensor channels evaluated Has the HB RTE 3 building block been parameterized according to the requirements stated in this manual See Safety Manual appendix Are the unused inputs of the module wired accordingly 10 Have the special requirements for th
83. ized according to the appendix for building blocks requirements stated in the Safety Man ual 32 106 Check lists Chapter 3 Input modules 4 7 F 6213 F 6214 Safety related Analogue Input Module 4 channel F 6213 F 6214 safety related analogue Check list No SANAE F6213 14 E input module 4 channel Version 2 0 32 05 t Project data File name of check list archiving number Project designation Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment yes no Are the inputs of this module named which perform a safety related function Is each safety related input evaluated by the HA RTE 3 building block Does a redundant module exist for this module 3 4 Does an HA RTE 3 building block exist in the user program for each module or for two redundant modules respectively Has the HA RTE 3 building block been parameterized according to the requirements stated in the manual 6 Are the unused inputs of the module wired accordingly See safety manual appendix See data sheet 33 106 Chapter 3 Input modules Check lists 4 8 F 6217 Safety related Analog Input Module 8 channel F 6217 safety related Check list No SANAE F6217 E analogue input module 8 channel Version 2 0 32 05 Project data Project description File name of check list archiving number Position in subrack IOSR Require
84. l ure of an output module has to be if no redundancy exists e Transition into safe state if necessary shutdown e Annunciation of the failure If a plant operates in energized to trip mode e g fire alarm systems see Chapter 6 Operating Conditions then if no redundancy exists the PES has to do e Annunciation of the failure of the output module e No further reaction possible Therefore a plant specific solution must exist to enable the transi tion into the safe state e g by providing a redundant output mod ule or by monitored operation Safety related Digital Output Modules The test routines detect an error by comparing the back read output signals with the internal output data The module in the module position detected as defective is put to the safe state by the operating system and indicated on the diagnostic display With modules having output circuit monitoring a detected line break is signalized by the indi cation of the faulty channel of the module on the diagnostic display By the integrated safety shutdown the defective module is safely switched off In addition to this one or more shutdown groups can be defined via the H8 STA 3 function block If one output module in an output group fails all other output modules belonging to this group are switched off Depending on the safety requirements of the system a complete shutdown of the control can be configured via the IO parameters in the resource
85. l Output Module 202020005 46 F 3333 Safety related Digital Output Module 202000005 47 F 3334 Safety related Digital Output Module 02000005 48 F 3335 Safety related Digital Output Module 202020005 49 F 3348 Safety related Digital Output Module 2 202000505 50 F 3349 Safety related Digital Output Module 02 2020005 51 F 3430 Safety related Digital Output Module 2020200050 52 F 6705 Safety related Analogue Output Module 2 2005 53 Software Software for Safety related HIMA H41q H41qc and H51q Automation Devices 00 00 eee eee eee eee eee eee 55 Safety Aspects concerning the Operating System okie dw G46 sala ete Wee NE a ee Sas Oe eres ha ea 57 Designation Current Approved Version for Safety related Applications CRC Signature 000 eee 57 Signatures of the User Program 066200 e eee eee eee 57 Procedures and Functions of the Operating System 00 055 58 4 2 4 2 1 4 2 2 4 3 4 3 1 4 3 2 4 3 2 1 4 3 2 2 4 3 2 3 4 3 2 4 4 3 2 5 4 3 3 4 3 3 1 4 3 3 2 4 3 3 3 4 3 3 4 4 3 3 5 4 3 3 6 4 4 5 1 5 2 5 3 Chapter 6 1 Table of Contents Safety Aspects Concerning Programming Wi ELOP I grenann aaa on ea Katee aah Roe mae ae aa mete eae 59 The ELOP Il Safety CONCEP es e ncns 9 24 053 2 26 BSS ye Dali ad See nea nernne t
86. le and the user program fulfilled Requirement Comment no 1 Are the outputs of this module named which perform a safety related function 2 Does a redundant module exist for this module 3 Are there at most 10 output modules ener gized with rated load assembled within one IOSR 4 Are free wheeling circuits provided at the actuators 5 Are the output leads correctly connected and laid considering safe electric insula tion AEE 6 Are cables with double or reinforced insula tion used for the connection wiring lt n oO oO r l Qa o lt according to IEC 61131 2 Ed 2 2003 no longer required if the use of the module meets SELV or PELV conditions 50 106 Check lists Chapter 4 Output Modules 5 7 F 3349 Safety related Digital Output Module Check list No SDIGA F3349 E Version 2 0 32 05 F 3349 safety related digital output module 8 channel Project data File name of check list archiving number Project designation Position in the subrack OSR Requirements for the project planning of the module and the user program fullfilled No Requirement Comment no Are the outputs of this module named which perform a safety related function 1 2 Incase of line monitoring Does an HB BLD 3 building block exist for each module in the user program in case of non redundant operation 3 Does a redundant module exist for this mod
87. ments for the project planning of the module and the user program fulfilled Requirement Comment yes no Are the inputs of this module named which perform a safety related function Is the channel error bit digital input processed in a safety related way at each analogue input Does a redundant module exist for this iS module Does a function building block exist in the user program for each channel or for two redundant channels respectively 5 Are the unused inputs of the module wired accordingly L See data sheet 34 106 Check lists Chapter 3 Input modules 4 9 F 6220 Ex i Safety related Analog Thermocouple Input Module 8 channel F 6220 Ex i Safety related analog Check list No SANAE F6220 thermocouple input module 8 channel Version 2 0 32 05 Project data Project designation File name of check list archiving number Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment Are the inputs of this module named which perform a safety related function 2 Is each safety related input evaluated by the HF TMP 3 building block 3 Are the errors of the module and channel overflow and underflow evaluated in the user program by an error value Are the unused input circuits short circuited Are the special requirements met for the see data sheet application of the Ex i module as stated in the data sheet and the appendix
88. message For an extended diagnosis we recommend to use only safety related IO modules Analogue IO Modules Analogue input modules convert analogue values voltages currents into digital values with a 12 bit resolution Analogue output modules convert 12 bit digital values into currents 0 20 mA or 4 20 mA For the most safety related and non safety related analogue IO modules HIMA function blocks are to be used in the user program see Appendix Imported or Exported Variables The data of the variables to be imported or exported are transmitted by the serial interfaces to either HIMA communication via HIPRO PES master or to external systems Available proto cols for external systems are MODBUS Profibus DP and 3964R The data can also be trans mitted to an OPC server via an Ethernet protocol The variables for import and export are processed in the user program like normal input and output signals They are defined in the 75 106 Chapter 5 Software Safety Aspects User Program 4 3 3 4 3 3 1 variable declaration of the program instance It is possible to provide Boolean variables with the event attribute Events are signal changes of Boolean variables with additional information about the point of time date and time The time stamp of an event corresponds to the time of the automation device with millisecond pre cision Functions of the User Program Programming is not restricted in any way by the hardware The
89. module 4 channel i Project data Project designation File name of check list archiving number Requirements for the project planning of the module and the user program Are the outputs of this module named which perform a safety related function In case of line monitoring Does an HB BLD 3 building block exist for each module in the user program in case of non redundant operation 3 Does a redundant module exist for this module 4 Incase of line monitoring Does one HB BLD 4 building block exist in the user program for two redundant mod ules 5 Is each safety related output evaluated by the HB BLD 3 or HB BLD 4 building block 6 Has the HB BLD 3 or HB BLD 4 building block been parameterized according to the specified values 7 Are there at most 10 output modules ener gized with rated load assembled within one IOSR 8 Has it been made sure that at maximum load 2 A only two channels have the max current 9 Has it been ensured that the minimum load for line break monitoring is 10 mA 10 Has it been made sure that the signal line break must only be evaluated up to SIL 1 in the user program 11 Has atime between 1 ms and 50 ms been set at the input MAKING CURRENT IN ms of the HB BLD 3 or HB BLD 4 building block 12 Are free wheeling circuits provided at the actuators See safety manual appendix lt no QO oO r el Q e lt 48 106 Check lists Chapter 4 Outpu
90. nction var ious variables can be defined The following table gives an overview Type User program Function block Function FUN Used as of variable PROG FB VAR X X X local variable CONST RETAIN CONST RETAIN CONST VAR_ X X input INPUT variable VAR_ X X output OUTPUT RETAIN variable VAR_ X externally from EXTERNAL CONST to an other POU VAR_ X globally from to GLOBAL CONST RETAIN other POUs VAR_ X X X in the action ACTION block of the sequential function chart 4 3 2 3 4 3 2 4 4 3 2 5 For some types of variables additional attributes can be defined CONST constant which can be changed in online operation without having to compile the user program again It cannot be written by the user program RETAIN non volatile variable i e its value is retained after a power fail ure and resumption of power Digital Inputs and Outputs for Boolean Variables When the resource is defined digital inputs and outputs and safety related digital inputs and outputs are distinguished For safety related functions only safety related IO modules must be used For most safety related IO modules HIMA standard function blocks are to be provided in the user program see appendix Non safety related IO modules are only read or written by the operating system They are not subject to further test routines Therefore a defect is not recognized by the operating system and there is no error
91. ng input modules can be mixed We recommend equipping the system with the highest possible degree of safety related input modules Safety related input modules in the H41q H41qc and H51q system are automatically subject ed to a high quality cyclical self test during operation The input modules contain circuit parts which allow the online test of the input module function via special test routines integrated into the operating system These test routines are TUV tested and ensure the correct function of the corresponding modules Whenever an error is detected an error message is generated These error messages automatically trigger the safety related function of the system and dis play diagnostic information for the system operator This allows the design of a flexible diag nosis system in the planning and realization stage of the plant Due to the safety concept of the H41q H41qc and H51q systems a single channel solution for safety related input modules is possible up to SIL 3 in the input area To increase availability or for other system related reasons the safety related input modules can also be used in parallel redundantly The safety of the system will not be affected in any way by redundant input modules Safety and availability Chapter 3 Input modules 2 2 2 2 1 The following rules have to be obeyed concerning the permissible slots for input modules on the system subracks and the IO subr
92. ng the operatin system Windows The current version of the tool is applicable on Windows 2000 and Windows XP The ELOP II Safety Concept The ELOP II safety concept ensures that e the programming system PS works correctly i e programming system errors are detected e the user uses the PS correctly i e user errors are detected When a Safety related control is commissioned the safety of the complete system is checked by an overall function test The two above points will be verified Until now after a modification of a user program another complete function test had to be performed to ensure the safety related function of the system The safety tool of ELOP II according to IEC 61131 3 is now designed to check only to the mod ifications in the user program This safety tool detects user errors and programming system errors The safety tool of ELOP II consists of three sections which are important for safety e C code comparator e target code comparator proven GNU C compiler With the C code comparator modifications made to the user program are identified The target code comparator compares two target codes subsequently generated by the GNU C compiler GNU CC This method prevents errors caused by a non safety related PC Non safety related tools are e The revision management in ELOP II This can only be used for the identification of the relevant project versions The offline simulation shown in the flow chart
93. nputs may not be allo cated Any deviations from this must be approved by the authority in charge of acceptance Online changes of parameters and constants are only permissible upon permission of the re sponsible acceptance authority and in monitored operation The allocation of the function block inputs with non safety related imported variables is not al lowed Allocation of Standard Building Blocks Appendix 2 4 Function block outputs A safety shutdown is only permissible via Y Maximum Value Reached and Y Diff Maximum Reached Any deviations from this must be approved by the responsible acceptance authority The safe state of a plant cannot be achieved in every case by the con trol algorithm of the function block alone In the specific case addi tional measures may become necessary Function Block HA PMU 3 This building is used for both the conversion of digitized measuring values into o values and the conversion of o values into digitized analogue values Correct parameterization has to be verified if these values are used for the shutdown of safety relevant circuits see Manual ELOP II Resource Type HA PMU 3 Input Conve rter with Parametrizat ic on UINT dInput Value 1 Output Value l UINT UINT dInput Value Z Error 1s BoOoL UINT dInput Value 3 Output Value Zs UINT UINT dInput Value 4 Error 24 BOoOL UINT dInput Value 5 Output Value 34 UINT UINT dInput
94. ntered into the PC via ELOP II programming system This program is suitable for computers with the Windows operating system In addition to this the PC must be equipped with a HIMA hardlock module The essential parts of the ELOP II programming system are the following e Entry function block editor monitoring and documentation e Variables with symbolical names and type of variable BOOLEAN UINT etc e Allocation of the resource type HIMA automation systems H41q H51q e Code generator compilation of the user program into the machine code with C code generator and GNU C compiler Safety Aspects User Program Chapter 5 Software 4 3 1 4 3 2 Basic Programming The task to be performed by the control is to be laid down in the form of a specification This documentation is the basis of correct implementation into the program How this task is actually specified depends on the kind of task This may be Combinatorial logic e Cause effect scheme e Logic of the combination with functions and function blocks e Function blocks with specified characteristics Sequential controls sequence control systems e Verbal description of the steps with step enabling conditions and actuators to be con trolled e Sequence diagrams according to DIN EN 60848 e Matrix or chart form of the step enabling conditions and the actuators to be controlled e Definition of the marginal conditions such as operation modes EMERGENCY OFF etc T
95. ogram for the central modules will be loaded one after the other One central module will always be in operation MONO and the system will not be stopped The outputs of a PES having only one central module will be held during the reload process The reload mode requires the prior generation of a reload able code Parameterization of the Automation Device The parameters listed below determine the reaction of the automation device during operation They are set in the menu for resource properties Safety Here the permissible actions of the automation device in safety related operation are deter mined and the safety related parameters are given Safety Aspects ELOP Il Chapter 5 Software Safety related parameter Safety time ins Depending on process Watchdog in ms Maximum half the change of safety parameters safety time Test operation reset Start Restart reset Change of constants reset Change of variables reset forcing of variables in the OLT Forcing reset main switch and individual switches Reload reset Change of configuration reset The safety time must not be set to the value 255 s Only the value range 1 to 254 is permitted The allocations possible during safety related operation are not rigidly bound to one SIL They have to be coordinated with the test authority in charge for each application of the automation system 3 3 2 Fa
96. on Application of the Safety Tool of ELOP II for Program Modifications 1 The user program is modified according to a mandatory specification e g according to IEC 61508 DIN V VDE 0801 or corresponding user standard in the flow chart this re fers to points 1 to 4 2 For the modification the backup of the running user program is used This backup con tains e the VGL file e the target code input data 3 The modifications of the user program are entered 4 The modified user program is newly compiled into the C code by the C code generator point 5 5 The C code comparator must be activated point 12 It compares the new C code with the old C code of the previous program version point 11 The backup must be indicat ed as the comparison file old C code Safety Aspects ELOP Il Chapter 5 Software 11 12 The result of the comparison point 15 is documented The user checks whether the C code comparator indicates all the changes made to the user program Only code relevant changes are indicated If the C code comparator a indicates changes which the user does not recognize this may have the follow ing reasons the modification made by the user results in further modifications which were not planned there is an internal error b does not indicate modifications made by the user this may be due to the follow ing there are changes which the C code comparator does not recognize
97. oned standards The maximum cycle time for central fire alarm systems of 10 seconds as it is required in DIN EN 54 2 can easily be fulfilled by the H41q H41qc and H51q systems as the cycle times of these systems are in a range lt 0 5 seconds also the possibly requested safety time of 1 sec ond fault response time The connection of the fire alarm boxes call points is carried out in the open circuit principle with monitoring for line break and short circuit Here the F 3237 F 3238 input modules can be used for boolean connections or the F 6217 F 6221 for analogue connections with the follow ing external wiring boolean connections F 3237 F 3238 Reor M l l S ee eae eee analogue connections Reor Analogue pepas input F 6217 Signal loop l E 6221 i Resnunt Reference pole L Wiring of fire alarm boxes M Fire alarm box call point Reo Termination resistor at the last sensor of the loop RL Limitation of the maximum admissible current of the loop Rshunt Measuring shunt 85 106 Chapter 5 Software Central Fire Alarm Systems 86 106 For the application the resistors Reo_ Rq and Rshunt Must be dimensioned depending on the sensors and their quantity in a loop Therefore also the data sheets of the sensor manufactur ers must be regarded Additionally the specified current values of the F 3237 and F 3238 modules cf data sheets must be considered This is espe
98. ons Central modules for single channel automation devices with integrated back up battery must be stored without the user program if this program contains non volatile variables retain variables These variables are not set to their initial value while the system is booting e Central modules for redundant automation devices with integrated back up battery can be stored containing the user program even if this program includes non volatile vari ables retain variables During system booting these variables are taken over by the central device already in operation The diagnostic display of the central module signalizes BATI in case the battery of the central module is discharged A recommendation for replacing the batteries on the modules can be found in the datasheet When there is both a battery and a power failure the RETAIN vari ables are newly initialized during system booting and thus loose the stored values Overview of the modules Chapter 3 Input modules Chapter 3 Input Modules 1 Overview of the Input Modules for the H41q H41qc and H51q Systems Module Safety Non Ex i Related SW related inter function block acting Digital input modules F 3221 16 channel input module F 3222 8 channel input module F 3223 4 channel input module e F 3224A 4 channel input module F 3236 16 channel input module
99. or other error messages Has a backup of the complete program been made after the program has been loaded into the PES Has an online test been performed Has a sufficient number of tests been performed for all safety related logical circuits including inputs and outputs and for all mathematical calculations intermediate results limits etc After the rejection of a modification of an online constant Has the program been reloaded or has the constant been reset online to its original value Has the correct data transmission to other systems been tested Has forced information been reset prior to safety related opera tion Date Created by 67 106 Chapter 5 Software Safety Aspects ELOP Il 3 5 Reload Reloadable Code The formerly used term online changes has been replaced by reload Reload is only possible after consultation with the test authority in charge of plant acceptance For the duration of the reload the person in charge has to ensure appropriate safety related monitoring of the process by other technical and organizational measures Prior to each reload the changes in the user program as compared to the user program still running have to be determined using the C code comparator contained in the safety tool ELOP Il Before they are transmitted to the PES the reloads have to be tested carefully using simulators If a funct
100. parameterized according to the specific values 7 Are at most 10 output modules energized with rated load assembled within one IOSR 8 Has it been ensured that the minimum load for line break monitoring is 10 mA 9 Has it been made sure that the signal line break must only be evaluated up to SIL 1 in the user program 10 Are free wheeling circuits connected to the actuators Created by 46 106 Check lists Chapter 4 Output Modules 5 3 F 3333 Safety related Digital Output Module Check list No SDIGA F3333 E Version 2 0 32 05 F 3333 safety related digital output module 4 channel Project data Project designation File name of check list archiving number Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment Are the outputs of this module named which perform a safety related function 2 Does a redundant module exist for this module 3 Are there at most 10 output modules ener gized with rated load assembled within one IOSR 4 Has it been made sure that at maximum load 2 A only two channels have the maximal current 5 Are free wheeling circuits provided at the actuators D n oO D a o lt 47 106 Chapter 4 Output Modules Check lists 5 4 F 3334 Safety related Digital Output Module Check list No SDIGA F3334 E Version 2 0 32 05 F 3334 safety related digital output
101. process For the use of Maintenance Override the relevant current version of the document Maintenance Override written by T V Rheinland and T V Product Service is to be observed With ELOP II version 3 5 a static offline test of the logic is possible The offline simulation was not subject to a safety relevant testing Therefore the simulation cannot replace a functional test of the plant If required the operator must determine administrative measures for access protection to the PES in accordance with the test authority responsible for the application 6 106 1 Due to the proprietary protocols and interfaces of the operating system only HIMA products can be used Overview of the modules Chapter 2 Central Modules Chapter 2 Central Modules 1 1 Overview of the Modules in the Central Area of the H41q H41qc and H51q Systems Central Area of HIMA Automation Devices of the H41q H41qc and H51q Systems The components required for the central area of the different types of HIMA automation devic es are assembled in a kit The kit of an operative central module consists of the following com ponents e Central module rack e Central modules e Power supply modules e Accessories The exact scope of supply as well as the cabling of the of the supply voltage and the connection of the IO level are described in the data sheets of the catalogue Programmable Systems Sys tem Families H41q H51q 7 106
102. ram F 3237 or F 3238 input module Use of the HB RTE 3 function block HB RTE 3 Monitoring Digital Testable Input Modules Output 1 tts 4 1305 HBus No Rack Pos e g 1305 Output 23 Output 34 1405 Bus No Rack Pos red Mod Output 4 4 Output 5 18H W usea Channels Output 6 f HB RTE 3 Output 7 t 4 Output 8 Channel Error Mask E J1 1002 2 2Z002 Trip Other Error Code Pulse 4 Tolerated Fault Time in min Other Error Code Pulse 150 k Tolerated Time Difference red Inputs in ds Error i i Error Code Mod g Error Code red Mod The signals S 1 and S 2 are directly connected to the first channels of the module F 3237 or F 3238 No other hardware allocation Safety aspects If one of the sensors responds or if a component inside the system fails the system is switched off As normal sensors are used we recommend checking the sensor circuits at regular inter vals e g after a couple of months if the signals are not switched through the process within shorter periods of time In addition to this we recommend monitoring to verify whether the sig nals are equal logic with F3236 input module or parameterization of the HB RTE 3 function block F 3237 F 3238 input modules Availability aspects No availability as each component failure results in a shutdown Analog Redundant Transmitters Hardware wiring 4 20 mA Transmitter 1 T1 4 20 MA Transmitter 2 T2 79 106
103. rated Time Difference red Inputs in ds Error 4 BOOL Error Code Mod UINT Error Code red Mod 3 UINT Inputs Bus No Rack Pos e g 1305 Bus No Rack Pos red Mod Position of the safety related digital output module and if existing the redundant module given as a four digit decimal number Example 1305 means Cabinet 1 subrack 3 module position 05 1 1002 2 2002 Trip Allocated by 1 Tolerated Fault Time in min No effect on the shutdown within the indicated time after a sensor test component failure or line error Must be approved by the acceptance authority in charge Tolerated Time Difference red Inputs in ds Time difference of the switching points between two redundant sensors The time depends on the sensors Must be approved by the acceptance authority in charge The outputs Channel Error Mask Other Error Code Pulse 2x Error Error Code Mod and Error Code red Mod are for information purposes only and no safety related action in the user program must be derived from them 99 106 Appendix Allocation of Standard Building Blocks 2 9 100 106 Function Block HF AIX 3 The function block HF AIX 3 is used for parameterization and evaluation of one channel of the safety related analogue Ex i input module F 6221 with a resolution of 0 10 000 For each channel of the F 6221 module one HF AIX 3 function block is required in
104. rflow Value 4 in 0 1 Deg C UINT UINT dPermissible Analog Value Overflow Sign Value 4i BOOL UINT Reference Junct Temp Circuit Resist Error Value 4 4 BoOOoL Function Block HA PID 3 This function block contains a digital control which can be operated in the following modes P D Pl PD and PID The mode must be determined by parameterisation Ha amp A PID 3 PID Controller UINT dControlled Variable Manipulated Variable Yu UINT UINT dRe ference Variable Indication of Ys UINT UINT 4PID Structure PID 111 PD 101 Y Diff Signs BOOL UINT dP Gain in k Y Diff Value s UINT UINT 4dI Reset Time in ds TN UINT dD Rate Time in ds TV X Diff Signs BOOL UINT adSampling Period in ds TA X Diff Value s UINT BOOL JjRead in k TN TV TA HA PID 3 P Component Signs UINT UINT iProcessing Pulse P Component Value w UINT BYTE dParameter for Y 0 1 2 3 I Component Sign UINT UINT d Value Manual I Component Value s BOOL BOOL jJTRUE Manual PID 0 D Component Signs BOOL BOOL jJTRUE Manual Compensating D Component Value s UINT UINT d Diff Minimum UINT d Y Maximum Y Maximum Value Reacheds BOOL UINT d Diff Maximum Y Diff Maximum Reacheds BOOL Function block inputs H signal manual PID 0 and H signal manual Compensating If this control function block is used in safety related operation these i
105. rforms safety re lated online tests The safe data for the safe signal processing are available through the HF TMP 3 function block Each of the 8 1 input channels supplies safe input values and a safe error status 2 5 2 Response of the System on Failures Detected at Safety related F 6220 Thermocouple Input Modules Type of failure Response of system Comment Module failure The Value output INT at the HF TMP 3 function block is 0 The Channel error output at the HF TMP 3 function block switches to TRUE The error indication value must be set in the user pro gram by using the Channel error output signal Channel failure The Channel error output at the HF TMP 3 function block switches to TRUE The failure indicating value must be set in the user pro gram HF TMP 3_ function switches to TRUE block Underflow The Underflow output at The failure indicating value the HF TMP 3 function block must be set in the user pro switches to TRUE gram Overflow The Overflow output at the The failure indicating value must be set in the user pro gram The limits for underflow or overflow are to be set at the inputs Underflow level or Overflow level depending on the HF TMP 3 function block Additional notes on project planning Not used inputs have to be short circuited When using the module in SIL 3 the reference temperature from the us
106. rocessor module for H51q F 8625 Communication module for Ethernet F 8626 Communication module for e Profibus DP Slave F 8627 Communication module for Ethernet Bus connections F 7553 IO bus connection module for H51q Bus connection modules for the configuration of HIPRO F 7505 Interface converter RS 485 V 24 20mA 2 wire 4 wire HIPRO F 7506 Bus connection terminal for the configuration of 2 wire buses 9 106 Chapter 2 Central Modules General notes 2 General Notes on the Safety and Availability of safety related Central Modules For the system allocation of the central modules and power supply module components as well a bus components of the H41q H41qc and H51q system families the following requirements apply Systems H41q H41qc System H51q On the H41q system subrack On the central module subrack e two central modules e two central modules e 12 IO modules e three F 8621 A coprocessor modules or e two power supply modules five F 8625 F 8626 F 8627 F 8628 com e three fuse modules munication modules per central module can be used can be plugged in On the H41qc system subrack The basic components for IO subracks are e two central modules assembled in kits e two communication modules e 13 IO modules e two power supply modules can be used Fusing of the inputs outputs by automatic circuit breakers 2 1 Power Supply Modules In safet
107. rt No 968 EZ 129 06 05 Safety related Automation Systems H41q MS H41q HS H41q HRS H41qc MS H41qc HS H41qc HRS H51q MS H51q HS H51q HRS The safety related HIMA automation devices of the H41q H41qc and H51q system families are tested and certified for their functional safety according to the important standards as listed below IEC 61508 Parts 1 7 2000 up to SIL 3 IEC 61511 2004 EN 954 1 1996 up to Category 4 DIN VDE 0116 1989 EN 50156 1 2004 EN 120672 2004 EN 298 2003 EN 230 1990 NFPA 85 2001 EN 61131 2 2003 EN 61000 6 2 2001 EN 61000 6 4 2001 EN 54 2 1997 NFPA 72 2002 The Chapter 6 Operating Conditions contains a detailed listing of all applied environ ment and EMC tests 1 106 Chapter 1 Safety Philosophy Introduction 1 3 Safety and Availability Due to the 1002D microprocessor structure on one central module already as mono systems the system families H41q H41qc and H51q are designed for use up to SIL 3 Cat 4 Depending on the required availability the HIMA Automation devices can be equipped with re dundant modules in the central and IO areas Redundant modules increase availability as in the event of the failure of one module the failed module is automatically switched off and the redundant module maintains operation without interruption According to IEC 61508 the PFD Probability of Failure on Demand and PFH Probability of Failure per Hour calculations were made for the safe
108. s the period of time during which all foreground tests are performed 3 106 Chapter 1 Safety Philosophy Introduction 1 5 1 5 1 1 5 2 4 106 A short safety time therefore increases the cycle time and vice versa With long safety times some tests are distributed to several cycles Example 1 safety time 1s Cycle time for user program 450 ms Time required for tests 100 ms Two cycles are possible during the safety time 100 ms 2 50 ms cycle time required for tests Total cycle time 500 ms Example 2 safety time 2 s Cycle time for user program 450 ms Time required for tests 100 ms Four cycles are possible during the safety time 100 ms 4 25 ms cycle time required for tests Total cycle time 475 ms The safety time must not be set to the value 255 s Only the value range 1 to 254 is permitted Offline Proof Test The offline proof test recognizes dangerous concealed faults that would affect the safe func tion of the plant HIMA safety systems have to be subjected to an offline proof test in intervals of 10 years By an analysis using the HIMA calculation tool SlLence the interval often may be extended For relay modules the proof test for the relays has to be carried out in intervals defined for the respective plant Execution of the Offline Proof Test The execution of the offline proof test depend on the configuration of the plant EUC equip ment under control whic
109. ses IEC EN 61000 4 5 Surge 1 kV 0 5 kV Noise Emission Tests EN 61000 6 4 EN 50011 Class A Emission test radiated conducted 89 106 Chapter 6 Operating Conditions Power supply conditions 4 Power Supply Conditions The most important tests and limits for the power supply conditions are listed in the table be low EN 61131 2 Verification of DC Power Supply Characteristics Chapter 6 3 7 The power supply must meet alternatively the following standards IEC 61131 2 or SELV Safety Extra Low Voltage EN 60950 or PELV Protective Extra Low Voltage EN 60742 The fusing of the systems H41q H41qc and H51q must be in accordance to the statements of the data sheets 6 3 7 1 1 Voltage range test 24 V DC 20 25 19 2 30 0 V DC 6 3 7 1 2 Momentary interruption immunity test of the external power supply DC PS 2 10 ms 6 3 7 4 1 Reversal of DC power supply polarity test see application note in the concerning chapter of the system manual or in the data sheet of the power supply module 6 3 7 5 1 Backup duration withstand test Test B 1000 h Lithium battery is used for backup 90 106 Power supply conditions Chapter 6 Operating Conditions For Your Notes 91 106 Appendix Standard Software Building Blocks Appendix 1 1 1 2 1 3 1 4 92 106 Standard Function Blocks for the Central Area For functions of the central modules
110. sor wiring under the aspect of safety and availability are described in detail in Chapter 5 Software The user pro gram has to be designed accordingly Based on the IEC 61508 standard according safety proof is possible by the determination of offline prove test intervals Detailed determinations are to be made for the specific application The F 3236 F 3237 F 3238 F 3240 and F 3248 Safety related Digital Input Modules Test Routines The online test routines check whether the input channels are able to switch through both sig nal levels L and H signals irrespective of the applied input signals This function test is per formed each time the input signals are read Each time an error occurs in the input module the user program processes the 0 signal safe state 19 106 Chapter 3 Input modules 2 2 2 20 106 The modules for initiators and for contact makers with line monitoring additionally test the line up to the contact maker A safety related initiator can be connected to these modules Due to the self tests all requirements concerning the detection of the thresholds of the safety related initiators are fulfilled The monitoring of the power supply of a sensor contact requires the connection of two resistors according to the data sheet Response of the System on Failures Detected at Safety related Digital Input Modules Safety and availability Kind of failure Response of system Comment Defective
111. standard function blocks can be called and allocated You can find a detailed description of these function blocks in the Manual ELOP II Resource Type Function Block HK AGM 3 With this function block the function of an H51q automation device serving as HIPRO master is monitored This function block has no safety relevance Its outputs are for information purposes only and no safety related action in the user program must be derived from it Function Block HK COM 3 With this function block the function of the communication modules in a system H41qc or H51q is monitored This function block has no safety relevance Its outputs are for information purposes only and no safety related action in the user program must be derived from it Function Block HK MMT 3 With this function block an H41q H41qc or H51q automation device can be used as MODBUS master This function block has no safety relevance Its outputs are for information purposes only and no safety related action in the user program must be derived from it Function Block H8 UHR 3 This function block allows external setting or changing of the date and time of the automation device The outputs of this function block are for information purposes only and no safety related ac tion in the user program must be derived from them Allocation of Standard Building Blocks Appendix 2 2 1 Allocation of Standard Function Blocks for the IO Area All function blocks d
112. t Modules 5 5 F 3335 Safety related Digital Output Module F 3335 Ex i Safety related digital output module 4 channel Check list No SDIGA F3335 Version 2 0 32 05 Project data File name of check list archiving number Project designation Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment yes no 1 Are the outputs of this module named re which perform a safety related function 2 Does a redundant module exist for this module see data sheet see data sheet 3 Is there a forced convection for the module with a fan just below 4 Are the electrical data of the connected valves below the output characteristic of the module F 3335 see data sheet see data sheet redundancy 7 Is the engineering made exclusively ac see data sheet cording to the approved modifications 5 Are the special requirements met for the application of the Ex i module as stated in the data sheet 6 Are the special Ex requirements met for use of parallel connections in 49 106 Chapter 4 Output Modules Check lists 5 6 F 3348 Safety related Digital Output Module Check list No SDIGA F3348 Version 2 0 32 05 F 3348 safety related digital output module t Project data File name of check list archiving number Project designation Position in subrack IOSR Requirements for the project planning of the modu
113. ted way in the user pro gram Module failure All analogue values 0000 See channel error applies to All channel error bits all channel error bits TRUE Measuring range Analog value 0000 or Max admissible value must exceeded 4095 be defined in the user pro Channel error bit TRUE gram This module has its own 1002 microprocessor system which automatically performs safety re lated online tests and provides the saved data for the safety related processing module An an alogue value and a related channel error bit exist for each channel Depending on the requirements the necessary function block can be created in the user program A When the channel error bit has been set a safety related response in relation to the corresponding analogue input must be programmed Safety and availability Chapter 3 Input modules 2 5 The F 6220 Safety related and Intrinsically Safe Thermocouple Input Module The thermocouple input module has eight channels for the connection of various types of ther mocouples according to the parameters of the HF TMP 3 function block and one input for the connection of a Pt100 resistance temperature detector as a reference temperature input It has its own dual processor system The parameterization of the module is performed via the HF TMP 3 for each channel used 2 5 1 Test Routines The module has its own 1002 microprocessor system which automatically pe
114. the signals The counter module can be used for pulse counting measuring of frequencies or rotational speeds and for detection of the sense of rotation For each F 5220 counter module one HF CNT 3 function block is required in the user program HF CNT 3 Counterblock for F5220 dBus No Rack Pos e g 1305 Counter channel 1 dEnable Configuration dSignal type 1 5V Z 24V 3 initiator Counter 24 bit a dPreset value Output stated dGate in SOms Rotation directions dMaximum deviation of frequency TRUE right FALSE left dCounting mode l right left Z right 3 left Line break Short circuit J Active J 4iReset counter 4Stop counter 4MO0S TRUE testoperation dMaximum time for testoperation in min Remaining time u 4Forcevalue for testoperation HF CNT 3 Counter channel 2 dEnable Configuration dSignal type 1 5V 2 Z4V 3 initiator Counter 24 bit a dPreset value Output states dGate in 50ms Rotation directions dMaximum deviation of frequency TRUE right FALSE left dCounting mode l right left Z right 3 left Line break Short circuit 4 Active i JReset counter 4Stop counter 4JMOS TRUE testoperation dMaximum time for testoperation in min Remaining time a JForcevalue for testoperation Module error code 4 The counter module has one safety related output per channel which is controlled indepen dent from the cycle time of the central module The Output state is indicated at the output of the HF
115. tion are also provided If errors occur in the central modules STOP is displayed and additionally the error code can be called If errors occur in safety related modules in the IO level the position of the module is displayed and if possible the disturbed channel In addition to this all error codes are provided in the diagnostic system for the visual display on a process control system An error history supports the detection of problems in the system The diagnostic display is not fail safe Therefore no safety related action must be taken based on the information on the diagnostic dis play Error response Chapter 2 Central Modules 4 Response on Errors Detected in the IO Bus Area If errors occur in the IO area between the central module and the connection modules all IO subracks affected by this fault are switched off If an error in the IO bus area occurs within the IO subrack only the connection module switches off the output modules on the IO subrack affected 15 106 Chapter 2 Central Modules Error response 5 16 106 Instructions for the Replacement of Central Modules Defective modules of both the central and the IO areas can be replaced during operation The automation device does not have to be switched off We urgently recommend replacing defective central modules In the event of a fault or for maintenance purposes the module should be replaced obeying the following instructi
116. tware 3 5 1 3 5 2 3 6 3 7 sage Code reloadable during the compilation run of the code generators Reloadability is lost if modules are inserted or deleted in the cabinet more variables are allocated to the attributes of the following types than are deleted HIPRO N HIPRO S BUSCOM event 3964R e the basic addresses for BUSCOM are changed e system variables are inserted or their allocations are changed names of HIPRO S variables are modified Systems with one Central Module If a reload is performed in systems having only one central module this change must be performed within in the fault tolerance time of the process While the user program is being loaded there is no access to the IO level i e IO modules are not read written or tested While the user program is being loaded the interfaces of the automation device are not pro cessed by the user program and imported or exported variables are not routed via the serial interfaces Systems with Redundant Central Modules Reload of automation devices having redundant central modules are possible without adhering to the restrictions relating to the single channel systems mentioned above After the start of the reload the second central module continues processing the user program in mono mode while the first central module is being loaded Then the newly loaded central module receives the current data from the central module in operation and
117. ty related systems H41q H41qc and H51q IEC 61508 1 defines for SIL 3 a PFD of 10 4 10 3 and a PFH of 10 8 10 7 per hour For the control PES are estimated 15 of the standard limit value for PFD and PFH This results in the following limit values for the control part PFD 1 5 10 4 PFH 1 5 10 8 per hour The offline proof test intervals for the for the safety related systems H41q H41qc and H51q is determined to 10 years as The safety functions each consisting of a loop input processing stage output meet the re quirements in all configurations Further information is available on request Overview system designations safety availability and system configurations H41qc MS H41qc HS H41qc HRS H41q MS H41q HS H41q HRS System designation H51q MS H51q HS H51q HRS SIL Category SIL 3 Cat 4 SIL 3 Cat 4 SIL 3 Cat 4 Availability normal high very high Configuration Central module mono redundant redundant IO modules mono mono redundant IO bus mono mono redundant 1 To increase availability individual IO modules may be used as redun dant modules or in a 2003 circuit 2 When using a redundant IO bus we recommend using not only the lO modules but also the peripherals Sensors and actuators as redundant modules Experience shows that these components have higher failure rates than the modules of the PES 2 106 1 Restrictions for the relay output module F 3430
118. ufficient since the measures implemented in the software program ELOP II since version 2 1 and the measures described in the safety manual ensure a sufficient correct semantic and syntactic code containing no undetected errors of the process of the code generation Also for the numeric evaluation of forms a suitable number of tests have to be performed It makes sense to create equivalence class tests That means tests in the defined range of val ues at the limits and in not permitted ranges of values The tests have to be selected in that way that the correctness of the calculation has to be established The necessary number of tests depends on the used formula and has to consider critical pairs of values The online test facility can be used to support the tests e g to enter values or to check inter mediate values However an active simulation with sensors and actuators has to be performed to establish the correct wiring and function of sensors and actuators In addition only this is the way to establish the correctness of the system configuration Guidelines for the ELOP II User Definitions New load This term means that a program is loaded either as down load or reload mode into the PES formerly expression PLC Download If a program is loaded into the PES in download mode all outputs of the PES will be reset and the PES will be stopped Reload If a user program is loaded into a redundant PES in reload mode the modified user pr
119. uit cur rent 2 Required for error evaluation in current sink mode 37 106 Chapter 4 Output Modules General notes 2 2 1 38 106 General Notes on the Safety and Availability of Safety related Output Modules The safety related output modules are written in every cycle the output signals are read back and compared with the output data evaluated by the user logic Additionally a walking bit test over all outputs is performed within the multiple fault occurrence time The test signal is applied for max 200 us Thus the ability of the outputs to switch is tested without affecting the function of the connected actuators Due to this the freezing of each out put is detected even if the output signal is a static one Safety related output modules with line monitoring can detect errors in the lead wires going to the load The line monitoring meets the safety requirements up to SIL 1 The output signal can be used in all applications for safety requirements up to SIL 3 System H41q H41qc System H51q The output modules are plugged into the The output modules are plugged into spe system subrack cially designed IO subracks IOSRs each Kits with 12 slots H41q or 13 slots having a maximum of 16 slots for IO mod H41qc for IO modules are available ules The required basic components for IOSRs are comprised in kits see Chapter 2 If a plant operates in deenergized to trip mode the reaction to a fai
120. ule 4 Incase of line monitoring Does one HB BLD 4 building block exist in the user program for two redundant mod ules 5 Is each safety related output evaluated by the HB BLD 3 or HB BLD 4 building block 6 Has the HB BLD 3 or HB BLD 4 building block been parameterized according to the specific values See safety manual appendix 7 Are there at most 10 output modules ener gized with rated load assembled within one IOSR 8 Has it been ensured that the minimum load for line break monitoring is 10 mA 9 Has it been made sure that the signal line break must only be evaluated up to SIL 1 in the user program 10 Are free wheeling circuits provided at the actuators oO n O oO 2 D 51 106 Chapter 4 Output Modules Check lists 5 8 F 3430 Safety related Digital Output Module Check list No SDIGA F3430 Version 2 0 32 05 F 3430 Safety related digital output module i Project data Project designation File name of check list archiving number Position in subrack IOSR Requirements for the project planning of the module and the user program fulfilled Requirement Comment no 1 Are the outputs of this module named which perform a safety related function 2 Do the relay circuits have fuses with max current of 4 A 3 Are free wheeling circuits provided at the actuators 4 Are the output leads correctly connected and laid considering safe galvanic isola
121. unction Blocks Depending on the IO Level Safety Aspects User Program TUV test Type Function safety non related interacting H8 STA 3 Group formation of safety related testable outputs HA RTE 3 Monitoring of analogue testable input mod ules F 6213 F 6214 HB BLD 3 Module and line diagnosis of testable out puts HB BLD 4 Module and line diagnosis of testable out puts HB RTE 3 Monitoring of binary testable input modules HF AIX 3 Monitoring of analogue testable input modules F 6221 HF CNT 3 Counter function block for F5220 module HF CNT 4 Counter function block for F5220 module HF TMP 3 Configuration function block for F6220 module HZ FAN 3 Error display for testable IO modules HZ DOS 3 Non safety related diagnosis In the T V test column indicates that a T V safety certificate ex ists for the corresponding function block For the safety related ap plication of the function blocks please refer to the documentation of these function blocks The following function blocks can be used in safety related applications but not for safety re lated functions H8 UHR 3 HK AGM 3 HK LGP 3 HK MMT 3 HZ FAN 3 HZ DOS 3 For further notes see the internet site www hima com or the CDROM Prerequisites and Rules for the Use in Safety Applications Requirements from Prototype Certificates etc The user program is e
122. vents without Text 1 0 Buffer Overflow cotati BOOL Paper a BOOL i Printer Cover Open s BOOL No Con to Printer iu BOOL HK LGP 3 Events in Buffer BOOL UINT Reaction on Midnight 0 1 2 Buffer Overflow BOOL UINT UINT UINT UINT Message Counter UINT This function block is not relevant to safety Its outputs are for information purposes only and no safety related action in the user program must be derived from them 2 14 Function Block HZ DOS 3 This function block is used to determine which safety related IO modules are to be operated in the diagnostic mode only Up to sixteen modules can be monitored by one function block The function block can be used several times in the user program This function block is not relevant to safety Its outputs are for information purposes only and no safety related action in the user program must be derived from them HZ DOS 3 Diagnosis without Safety i UINT dBus No Rack Pos fe g 1306 Error Code UINT UINT wdBus No Rack Pos Error codep UINT UINT 1dBus No Rack Pos Error UINT UINT dBus No Rack Pos Error Secs Hi UINT UINT w WBus No Rack Pos Error o E UINT UINT idBus No Rack Pos Error a UINT UINT Bus No Rack Pos Error _ UINT UINT Bus No Rack Pos H7 DOS 3 Error Aer UINT UINT eee Pos Error Code UINT UINT jBus No Rack Pos Error a UINT UINT Bus No Rack Pos Error code UINT UINT mo bade ceca
123. with 1 Switch 1 0 Other Error Code Pulse BYTE s0 available l Safe Reaction Other Error Code Pulse UINT sOutput Value on Error Error error Code gt 0 BYTE yl 4 ZOmA O 0 Z0mA 1 BYTE yO Converts in 0 1 1 No Conversion Error Code Mod UINT yLower Out of range Alarm in 0 1 Error Code red Mod Inputs Bus No Rack Pos e g 1305 Bus No Rack Pos red Mod Position of the safety related analogue input module and if existing the redundant module designated by a four digit decimal number Example 1305 means Cabinet 1 subrack 3 module position 05 for redundant operation the redundant module must be given a different position O no Damping 1 Damping 1 only for redundant operation The difference taken from the current value and the value of the previous cycle is added to the permissible difference in 0 1 Tolerated Differ red Val ues in 0 1 Maximal Test Time in min Limitation of the testing time given in minutes After the testing time elapses the actual value is processed in the user logic See also the Maintenance Override information issued by TUV Bavaria and TUV Rhineland This information is part of the HIMA USD service Outputs Value 4 The use of the values must be checked if these values are used for the shutdown of safety related circuits Error value 1 4 The outputs must be allocated to be able to trigger a
124. with two IO buses the sensor signal of the second sensor is connected to two input channels one at a channel of the 1st IO bus and one at a channel of the 2nd IO bus In the user program these 2 signals are OR gated It is also possible to connect in parallel all the 3 sensor signals to each IO bus and then three times OR gated in the user program Then the function block like shown above is used Notes concerning sensors The user should not only consider the availability of the electronic modules but also the safety of the sensors If no safety related sen sors exist two sensors can be installed in the same measuring point A and combined with a 1002 circuit If safety and availability are required three sensors are installed in one measuring point and com bined with a 2003 circuit In both cases discrepancy monitoring of the two or respectively three sensor signals is required 81 106 Chapter 5 Software Safety Aspects User Program 4 4 82 106 Program Documentation for Safety related Applications The ELOP II programming system allows the automatic printout of the documentation of a project The most important kinds of documentation are the following e Interface declaration e List of variables e Logic e Description of data types Configurations of the cabinet subracks modules and system parameters e Process amp C variables cross reference e Code generator information The layout of the various kinds of do
125. y related applications one more 24 V DC 5 V DC power supply module than is re quired due to power consumption is to be used This applies to the central module subrack and for the additional power supply The power supply modules are decoupled via diodes and are monitored by the central devices 10 106 General notes Chapter 2 Central Modules 2 2 Functional Description of the Safety related F 8652 A E F 8650 A E Central Modules for the H41q H41qc and H51q Systems The F 8652 A E or F 8650 A E central module for safety related applications includes the function blocks shown below displays interfaces requests g g RS 485 setting Fa bus subscriber no i HAABBARE i hardware 1 l clock A mpa ee 2 watchdog Flash _ Flash EPROM EPROM P al a SRAM SRAM voltage m l monitoring Fa U CRC 1 10 bus logic eee eee ee es ee a E eee See rear side bus plane Each central module of type F 8652 A E or F 8650 A E consists of the following function blocks Two microprocessors with synchronized clock Each microprocessor has its own memory The memories of one processor contain the program and the data in non inverted form while the memories of the other processor contain the program and the data in inverted form 11 106 Chapter 2 Central Modules General notes 12 106 Testable hardware comparator for external access by both microprocessors in
126. zation is described in this Safety Manual In particular the definition of the system configuration the maximum cycle time and the safety time must be regarded Programming Product Dependent Conditions The error reaction of the system in the case of errors in the fail safe input and output mod ules must be defined in accordance with the specific safety aspects of the plant by the user program Incase of the use of a not certified tool for the user program the correct compilation and implementation of the program after initial set up or after modifications of the application is 5 106 Chapter 1 Safety Philosophy Safety Requirements 2 5 2 6 to be verified by full functional testing By using ELOP Il from version 3 5 on the verification of the program can be simplified according to the conditions of this safety manual However a sufficient validation of the program is required Function checks verifications after a modification of the user program can be limited to the modified parts The procedure of programming and modification of programming is described in Chapter 5 Software The requirements mentioned there must be regarded Communication Product Dependent Conditions Using the safety related communication between the different devices it must be regarded that the total reaction time of a system does not exceed the fault tolerance time The calcu lation elements mentioned in t