Rosemount 3051 Pressure Transmitter
Contents
1. Typical Model Number 3051CD 2 A 2 2 A 1 A B4 1 2 3 4 9 6 7 8 9 3051CG lower range limit varies with atmospheric pressure 3051CDO is available only with Output Code A Process Flange Code 0 Alternate Flange H2 H7 HJ or HK Isolating Diaphragm Code 2 O ring Code A and Bolting Option L4 Not available with hazardous locations certification Options Codes I1 N1 E4 K6 and K8 Materials of Construction comply with recommendations per NACE MRO0175 ISO 15156 for sour oil field production environments Environmental limits apply to certain materials Consult latest standard for details Selected materials also conform to NACE MRO0103 for sour refining environments Assemble to items are specified separately and require a completed model number Not available with Low Power code M Not available with Fieldbus output code F or Profibus output code W Local zero and span adjustments are standard unless Option Code J1 or J3 is specified NAMUR Compliant operation is pre set at the factory and cannot be changed to standard operation in the field 10 The V5 option is not needed with the T1 option external ground screw assembly is included with the T1 option 28 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 TABLE 12 3051T Gage and Absolute Pressure Transmitter Model Transmitter Type 3051T Pressure Transmitter Code Pressure Type G Gage A Absolute Code Pr
2. L Eng Units only L Alternate Eng Units amp of Range L of Range only L Alternate Eng Units amp Custom Display L Custom Display only _ Alternate of Range amp Custom Display Custom Display Configuration must be filled out if Custom Display is selected as meter type Decimal Point Position fixed X X X X X indicate decimal point location Enter Lower Range Value Decimal point must be in the same position as specified above circle sig LlLI 1sLlsLlsL e 000 00 x Enter Upper Range Value Decimal point must be in the same position as specified above circle sign Pel eben Ld a 100 00 x Custom Units spaces consume A Z 0 9 96 blank LIE EJ EJ EJ RNGE x Custom Display Transfer Function Independent of Analog Output L Linear L Square Root HARDWARE SELECTABLE INFORMATION Alarm Option O High O Low Transmitter Security O Off O On Note Specify C4 Option in model structure when ordering NAMUR compliant alarm and saturation limits SIGNAL SELECTION Software Selectable L 4 20 mA with simultaneous digital signal based on HART protocol O Burst mode of HART digital process variable 4 Burst mode output options O Primary variable in engineering units E Primary variable in percent of range c All dynamic variables in engineering units and the primary var
3. 12 43 mbar which can be calibrated out No span effect 3051L With liquid level diaphragm in vertical plane zero shift of up to 1 inH2O 2 49 mbar With diaphragm in horizontal plane zero shift of up to 5 inH2O 12 43 mbar plus extension length on extended units All zero shifts can be calibrated out No span effect 3051T CA Zero shifts up to 2 5 inH2O 6 22 mbar which can be calibrated out No span effect Vibration Effect All Models Measurement effect due to vibrations is negligible except at resonance frequencies When at resonance frequencies vibration effect is less than 0 1 of URL per g when tested between 15 and 2000 Hz in any axis relative to pipe mounted process conditions Power Supply Effect All Models Less than 0 005 of calibrated span per volt RFI Effects All Models 0 1 of span from 20 to 1000 MHz and for field strength up to 30 Vim Transient Protection Option Code T1 All Models Meets IEEE C62 41 Category B 6 kV crest 0 5 us 100 kHz 3 kV crest 8 x 20 microseconds 6 kV crest 1 2 x 50 microseconds Meets IEEE C37 90 1 Surge Withstand Capability SWC 2 5 kV crest 1 25 MHz wave form General Specifications Response Time 1 nanosecond Peak Surge Current 5000 amps to housing Peak Transient Voltage 100 V dc Loop Impedance 25 ohms Applicable Standards IEC61000 4 4 IEC61000 4 5 NOTE Calibrations at 68 F 20 C per ASME Z210 1 ANSI Product Data Sheet 00
4. 26 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 TABLE 11 3051C Differential Gage and Absolute Pressure Transmitters Not Applicable Applicable Code Mounting Bracket Options CD CG CA B4 Coplanar Flange Bracket for 2 in Pipe or Panel Mounting all SST B1 Traditional Flange Bracket for 2 in Pipe Mounting CS Bolts B2 Traditional Flange Bracket for Panel Mounting CS Bolts B3 Traditional Flange Flat Bracket for 2 in Pipe Mounting CS Bolts B7 B1 Bracket with Series 300 SST Bolts B8 B2 Bracket with Series 300 SST Bolts B9 B3 Bracket with Series 300 SST Bolts BA SST B1 Bracket with Series 300 SST Bolts BC SST B3 Bracket with Series 300 SST Bolts Code Hazardous Locations Certification Options CD forte 07 E5 FM Explosionproof Approval 15 FM Non incendive and Intrinsic Safety Approval IE FM FISCO Intrinsically Safe for FOUNDATION fieldbus protocol only K5 FM Explosionproof and Intrinsic Safety Approval 118 ATEX Intrinsic Safety G N19 ATEX Type N and Dust Certification E8 ATEX Flame proof and Dust Certification E40 TIIS Flame proof Certification 2 g 14 TIIS Intrinsic Safety Certification Only available with HART Option Code A m C5 Measurement Canada Accuracy Approval Limited availability depending on transmitter type and range 2 E Contact an Emerson Process Management representative C6 CSA E
5. 86 28 1 2 18 NPT on Process Flange for Pressure Connection Without the Use of Mounting Adapters 112 14 NPT on Optional Mounting 23 Adapters Can Be Rotated to Give Adapter Connection Centers of 2 00 51 2 126 54 or 2 25 57 Dimensions are in inches millimeters 21 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 3051H Mounting Brackets for 2 in Pipe and Panel Mount Option Code B5 B6 PIPE MOUNTING CONFIGURATION 0 7 16 44 109 Impulse Piping PANEL MOUNTING CONFIGURATION 746 20x3 4 Bolts Supplied for Attaching Bracket to Transmitter Dimensions are in inches millimeters 22 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 3051L Dimensional Drawings 2 in Flange Configuring Flush Mount Only 3 and 4 in Flange Configuration 4 1 104 4 1 104 Housing Rotation Set Screw A A H A Extension H H 2 4 or 6 51 102 or 152 Flushing Connection Diaphragm Assembly and Mounting Flange Dimensions are in inches millimeters 23 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 TABLE 10 3051L Dimensional Specifications Except where indicated dimensions are in inches millimeters Pipe AEU G Bolt Circl
6. J1 4 Local Zero Adjustment Only Local zero and span adjustments are standard unless Option p Code J1 or J3 is specified J30 No Local Zero or Span Adjustment Local zero and span adjustments are standard unless Option Code J1 or J3 is specified T1 Transient Protection Terminal Block c1 Custom Software Configuration Completed CDS 00806 0100 4001 required with order c20 0 8 3 2 V dc Output with Digital Signal Based on HART Protocol Output Code M only C499 Analog Output Levels Compliant with NAMUR Recommendation NE 43 CN Analog Output Levels Compliant with NAMUR Recommendation NE 43 Alarm Configuration Low P1 Hydrostatic Testing with Certificate P2 Cleaning for Special Service P3 Cleaning for 1 PPM Chlorine Fluorine DF 112 14 NPT flange adapters SST D8 Ceramic Ball Drain Vents v58 External Ground Screw Assembly Typical Model Number 3051HG 2 A 2 2 A H 2 1 A B5 1 Materials of Construction comply with recommendations per NACE MR0175 ISO 15156 for sour oil field production environments Environmental limits apply to certain materials Consult latest standard for details Selected materials also conform to NACE MR0103 for sour refining environments 2 Assemble to items are specified separately and require a completed model number 3 Not available with low power Option Code M 4 Not available with fieldbus output code F or profibus protocols output code W 5
7. Pa 124 545 6227 23 622 723 62160 6 2490 89 249089 20684 3 2068430 137895 13789500 kPa 0 12545 6 2272 0 62272 62 2723 2 49089 249 089 20 6843 2068 43 137 895 13789 5 torr 0 93416 46 7082 4 67082 467 082 18 6833 1868 33 155 145 15514 5 1034 3 103430 atm 0 00123 0 06146 0 00615 0 61460 0 02458 2 458 0 20414 20 4138 1 36092 136 092 When using a HART communicator 5 adjustment is allowed on the sensor limit to allow for unit conversions 3051L 3051H Pressure Transmitter Range Limits Range 2 Span Range 3 Span Range 4 Span Range 5 Span min max min max min max min max inH2O 2 5 250 10 1000 83 040 8304 553 60 55360 inHg 0 18389 18 389 0 73559 73 559 6 1081 610 81 40 720 4072 04 ftH2O 0 20833 20 8333 0 83333 83 3333 6 9198 691 997 46 13 4613 31 mmH35O 63 553 6355 254 25421 2110 95 211095 14073 1407301 mmHg 4 67082 467 082 18 6833 1868 33 155 145 15514 5 1034 3 103430 psi 0 0902 9 03183 0 36127 36 127 3 300 20 2000 bar 0 00623 0 62272 0 02491 2 491 0 20684 20 6843 1 37895 137 895 mbar 6 22723 622 723 24 9089 2490 89 206 843 20684 3 1378 95 137895 g cm 6 33875 633 875 25 355 2535 45 210 547 21054 7 1406 14 140614 kg cm 0 00635 0 635 0 0254 2 54 0 21092 21 0921 1 40614 140 614 Pa 622 723 62160 6 2490 89 249089 20684 3 2068430 137895 13789500 kPa 0 62272 62 2723 2 49089 249 089 20 6843 2068 43 137 895 13789 5 torr 4 67082 467 082 18 6833 1868 33 155 145 15514 5 1034 3 103430 atm 0 00615 0 61460 0 02458 2 458 0 20414 20 4138 1 36092 136 092 When u
8. Rosemount 3051 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Product Certifications Approved Manufacturing Locations Rosemount Inc Chanhassen Minnesota USA Emerson Process Management GmbH amp Co Wessling Germany Emerson Process Management Asia Pacific Private Limited Singapore Beijing Rosemount Far East Instrument Co LTD Beijing China European Directive Information The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www rosemount com A hard copy may be obtained by contacting an Emerson Process Management representative ATEX Directive 94 9 EC All 3051 transmitters comply with the ATEX Directive European Pressure Equipment Directive PED 97 23 EC 3051CA4 3051CG2 3 4 5 3051CD2 3 4 5 also with P9 option 3051HD2 3 4 5 3051HG2 3 4 5 3051PD2 3 and 3051PG2 3 4 5 Pressure Transmitters QS Certificate of Assessment EC No PED H 100 Module H Conformity Assessment All other 3051 3001 Pressure Transmitters Sound Engineering Practice Transmitter Attachments Diaphragm Seal Process Flange Manifold Sound Engineering Practice Electro Magnetic Compatibility EMC 2004 108 EC All 3051 Pressure Transmitters meet all of the requirements of EN61326 1997 A1 A2 and A3 and NAMUR NE 21 Ordinary Location Certification for Factory Mutual As standard the transmitter has been e
9. Rosemount 3051 TG TA Range 1 750 psi 51 7 bar Range 2 1500 psi 103 4 bar Range 3 1600 psi 110 3 bar Range 4 6000 psi 413 7 bar Range 5 15000 psi 1034 2 bar For 3051L or Level Flange Option Codes FA FB FC FD FP and FQ limit is O psia to the flange rating or sensor rating whichever is lower TABLE 3 3051L and Level Flange Rating Limits Standard Type CS Rating SST Rating ANSI ASME Class 150 285 psig 275 psig ANSI ASME Class 300 740 psig 720 psig ANSI ASME Class 600 1480 psig 1440 psig At 100 F 38 C the rating decreases with increasing temperature DIN PN 10 40 40 bar 40 bar DIN PN 10 16 16 bar 16 bar DIN PN 25 40 40 bar 40 bar At 248 F 120 C the rating decreases with increasing temperature Static Pressure Limit Rosemount 3051CD Only Operates within specifications between static line pressures of 0 5 psia and 3626 psig 4500 psig 310 3 bar for Option Code P9 Range 0 0 5 psia and 750 psig 3 4 bar and 51 7 bar Range 1 0 5 psia and 2000 psig 3 4 bar and 137 9 bar Burst Pressure Limits Burst pressure on Coplanar traditional or 3051H process flange is 10000 psig 69 MPa Burst pressure for the 3051T is Ranges 1 4 11000 psi 75 8 MPa Range 5 26000 psig 179 MPa Failure Mode Alarm Output Code A If self diagnostics detect a gross transmitter failure the analog signal will be driven either below 3 75 mA or to 21 75 mA to alert the user NAMUR
10. 33 7 65 194 DIN 2501 PN 10 40 DN 50 2 4 61 0 97 25 1 31 33 5 65 143 DIN 2501 PN 25 40 DN 80 3 6 91 0 97 25 1 31 33 5 65 143 DN 100 3 6 91 0 97 25 1 31 33 5 65 143 DIN 2501 PN 10 16 DN 100 3 6 91 0 97 25 1 31 33 5 65 143 1 Tolerances are 0 040 1 02 0 020 0 51 24 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Ordering Information TABLE 11 3051C Differential Gage and Absolute Pressure Transmitters Not Applicable Applicable Model Transmitter Type Select One cD CG CA 3051CD Differential Pressure Transmitter 3051CG Gage Pressure Transmitter 3051CA Absolute Pressure Transmitter Code Pressure Ranges Range Min Span CD CG CA 3051CD 3051CG 3051CA 0 3to3inH40 0 1 inH2O Not Applicable Not Applicable 7 5 to 7 5 mbar 0 25 mbar 1 25 to 25 inH2O 0 5 inH2O 25 to 25 inH20O 0 5 inH2O 0 to 30 psia 0 3 psia 762 2 to 62 2 mbar 1 2 mbar 62 1 to 62 2 mbar 1 2 mbar 0 to 2 1 bar 20 7 mbar 2 250 to 250 inH20 2 5 inH2O 250 to 250 inH20 2 5 inH2O 0 to 150 psia 1 5 psia 623 to 623 mbar 6 2 mbar 621 to 623 mbar 6 2 mbar 0 to 10 3 bar 0 1 bar 3 1000 to 1000 inH 0 10 inH O 393 to 1000 inH 0 10in H20 0 to 800 psia 8 psia 2 5 to 2 5 bar 25 mbar 0 98 to 2 5 bar 25 mbar 0 to 55 2 bar 0 55 bar 4 300 to 300 psi 3 psi 14 2 to 300 psi 3 psi 0 to 4000 psia 40 psia 20 7 to 20
11. 6 4 12 of EN50020 1994 This must be taken into account when installing the apparatus ATEX Type n and Dust Certification No BAS 98ATEX3356X Il 3 GD Ui 40 Vdc max EEx nL IIC T5 T4 40 C to 70 C Dust rating T80 C Tamb 20 to 40 C IP66 Special Conditions for Safe Use X The device is not capable of withstanding the 500V insulation test required by Clause 6 4 12 of EN50020 1994 This must be taken into account when installing the apparatus ATEX Flame Proof and Dust Certification No KEMA 00ATEX2013X II 1 2 GD EEx d IIC T6 Tamb 50 to 65 C Dust rating T90 C IP66 ce 1180 Vmax 55 V dc Special Conditions for Safe Use X This device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime 15 Rosemount 3051 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Japanese Certifications E4 TIIS Flame Proof Ex d IIC T6 Certificate Description C15852 3051C D 1 FOUNDATION Fieldbus no display C15853 3051C D 1 FOUNDATION Fieldbus with display C15858 3051T G 1 FOUNDATION Fieldbus SST Silicon no display C15859 3051T G 1 FOUNDATION Fieldbus Hastelloy C276 Silicon no display C15860 3051T G 1 FOUNDATIO
12. 7 bar 0 2 bar 0 98 to 20 7 bar 0 2 bar 0 to 275 8 bar 2 8 bar 5 2000 to 2000 psi 20 psi 14 2 to 2000 psig 20 psi Not Applicable 7137 9 to137 9 bar 1 4 bar 70 98 to 137 9 bar 1 4 bar Code Output cD CG CA A 4 20 mA with Digital Signal Based on HART Protocol M Low Power 1 5 V dc with Digital Signal Based on HART Protocol See Option C2 for 0 8 3 2 V dc F FOUNDATION fieldbus Protocol Ww Profibus PA g Code Materials of Construction cD CG CA Process Flange Type Flange Material Drain Vent 2 Coplanar SST SST 3 0 Coplanar Alloy C Hastelloy C276 4 Coplanar Monel Monel 5 Coplanar Plated CS SST 7 Coplanar SST Hastelloy C276 84 Coplanar Plated CS Hastelloy C276 0 Alternate Flange See Options on page 26 0707o 2M ETT EET TESTS AT ET LLL e 9 e C 07 2V 316L SST 3 0 Hastelloy C276 4 Monel 5 Tantalum Available on 3051CD and CG Ranges 2 5 only Not available on 3051CA 6 Gold plated Monel Use in combination with O ring Option Code B 7 Gold plated SST A Glass filled PTFE B Graphite filled PTFE Code Fill Fluid cD exe CA 1 Silicone 2 Inert fill Halocarbon 2 a Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 TABLE 11 3051C Differential Gage and Absolute Pressure Transmitters Not Applicable Applicable Code Housing Material Cond
13. Code T3C Explosion Proof for Class Division 1 Groups B C and D Dust Ignition Proof for Class II and Class III Division 1 Groups E F and G Suitable for Class Division 2 Groups A B C and D hazardous locations Enclosure type 4X factory sealed For input parameters see control drawing 03031 1024 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 European Certifications 1 N1 E8 ATEX Intrinsic Safety and Dust Certification No BAS 97ATEX1089X 9 Il 1 GD EEx ia IIC T4 60 lt T lt 70 C Dust Rating T80 C 20 lt T4 lt 40 C IP66 ce 1180 TABLE 5 Input Parameters U 30V l 200 mA Pj 0 9W Ci 0 012 uF Special Conditions for Safe Use X When the optional transient protection terminal block is installed the apparatus is not capable of withstanding the 500V insulation test required by Clause 6 4 12 of EN50020 1994 This must be taken into account when installing the apparatus ATEX Type n and Dust Certification No BAS OOATEX3105X 9 II 3 GD U 55 Vdc max EEx nL T5 40 C lt Tamb lt 70 C Dust rating T80 C 20 lt T4 lt 40 C IP66 ce Special Conditions for Safe Use X When the optional transient protection terminal block is installed the apparatus is not capable of withstanding a 500V r m s test to case This must be taken into account on any installation in which it is used for example by assuring that the supply to
14. D01 The 3051C FOUNDATION fieldbus Diagnostics provide Abnormal Situation Prevention ASP indictation The integral statistical process monitoring SPM technology calculates the mean and standard deviation of the process variable 22 times per second The 3051C ASP algorithm uses these values and highly flexible configuration options for customization to many user defined or application specific abnormal situations The detection of plugged impulse lines is the first available predefined application Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Low Power Output Code M Output Three wire 1 5 V dc or 0 8 3 2 V dc Option Code C2 user selectable output Also user selectable for linear or square root output configuration Digital process variable superimposed on voltage signal available to any host conforming to the HART protocol Low power transmitter operates on 6 12 V dc with no load Power Consumption 3 0 mA 18 36 mW Minimum Load Impedance 100 KQ Vout wiring Indication Optional 5 digit LCD display Overpressure Limits Rosemount 3051CD CG Range 0 750 psi 51 7 bar Range 1 2000 psig 137 9 bar Ranges 2 5 3626 psig 250 bar 4500 psig 310 3 bar for option code P9 Rosemount 3051CA Range 1 750 psia 51 7 bar Range 2 1500 psia 103 4 bar Range 3 1600 psia 110 3 bar Range 4 6000 psia 413 7 bar Rosemount 3051H All Ranges 3626 psig 25 MPa
15. Inert 50 to 350 F 45 to 177 C Neobee M 20 0 to 375 F 18 to 191 C 3051T Process Fill Fluid Silicone Fill Sensor 40 to 250 F 40 to 121 C Inert Fill Sensor 22 to 250 F 30 to 121 C 3051L Low Side Temperature Limits Silicone Fill Sensor 40 to 250 F 40 to 121 C Inert Fill Sensor 0 to 185 F 18 to 85 C 2 3051L High Side Temperature Limits Process Fill Fluid Syltherm XLT 100 to 300 F 73 to 149 C D C Silicone 704 32 to 400 F 0 to 205 C D C Silicone 200 40 to 400 F 40 to 205 C Inert 50 to 350 F 45 to 177 C Glycerin and Water 0 to 200 F 18 to 93 C Neobee M 20 0 to 400 F 18 to 205 C Propylene Glycol and Water 0 to 200 F 18 to 93 C 1 Process temperatures above 185 F 85 C require derating the ambient limits by a 1 5 1 ratio 0 6 1 ratio for the 3051H 2 220 F 104 C limit in vacuum service 130 F 54 C for pressures below 0 5 psia 3 3051CDO process temperature limits are 40 to 212 F 45 to 100 C 4 160 F 71 C limit in vacuum service 5 Not available for 3051CA Humidity Limits 0 100 relative humidity Turn On Time Performance within specifications less than 2 0 seconds 10 0 s for Profibus protocol after power is applied to the transmitter Volumetric Displacement Less than 0 005 in 0 08 cm Damping Analog output response to a step input chan
16. Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Rosemount 3051L Process Wetted Parts Flanged Process Connection Transmitter High Side Process Diaphragms Including Process Gasket Surface 316L SST Hastelloy C276 or Tantalum Extension CF 3M Cast version of 316L SST material per ASTM A743 or Hastelloy C276 Fits schedule 40 and 80 pipe Mounting Flange Zinc cobalt plated CS or SST Reference Process Connection Transmitter Low Side Isolating Diaphragms 316L SST or Hastelloy C276 Reference Flange and Adapter CF 8M Cast version of 316 SST material per ASTM A743 Non Wetted Parts Electronics Housing Low copper aluminum or CF 3M Cast version of 316L SST material per ASTM A743 NEMA 4X IP 65 IP 66 Coplanar Sensor Module Housing CF 3M Cast version of 316L SST material per ASTM A743 Bolts ASTM A449 Type 1 zinc cobalt plated carbon steel ASTM F593G Condition CW1 Austenitic 316 SST ASTM A193 Grade B7M zinc plated alloy steel Monel K 500 Sensor Module Fill Fluid Silicone oil D C 200 or Fluorocarbon oil Halocarbon or Fluorinert FC 43 for 3051T Process Fill Fluid 3051L and 3051H only 3051L Syltherm XLT D C Silicone 704 D C Silicone 200 inert glycerin and water Neobee M 20 or propylene glycol and water 3051H inert Neobee M 20 or D C Silicone 200 Paint Polyurethane Cover O rings Buna N Shipping Weights Refer to Shipping Weights on page 38 11
17. proof and Intrinsic Safety Approvals combination of K5 and C6 K7 SAA Flame proof and Intrinsic Safety Approvals combination of I7 N7 and E7 K8 ATEX Flame proof and Intrinsic Safety Approvals combination of 11 and E8 KD CSA FM and ATEX Explosion proof and Intrinsic Safety Approval combination of K5 C6 11 and E8 I7 SAA Intrinsic Safety Certification E4 TIIS Flame proof Certification E7 SAA Flame proof Certification N7 SAA Type N Certification I1 ATEX Intrinsic Safety and Dust Certification N1 ATEX Type N and Dust Certification E8 ATEX Flame proof and Dust Certification DW NSF drinking water approval IA ATEX Intrinsic Safety for FISCO for FOUNDATION fieldbus protocol only Code Other Options Q4 Calibration Data Sheet Q8 Material Traceability Certification per EN 10204 3 1 B NOTE This option applies to the process connection only Q16 Surface finish certification for sanitary remote seals Qz Remote Seal System Performance Calculation Report QP Calibration certification and tamper evident seal QS Certificate of FMEDA Data J196 ocal Zero Adjustment Only J3 X No Local Zero or Span Adjustment M5 LCD display for Aluminum Housing Housing Codes A B C and D only M6 LCD display for SST Housing Housing Codes J K L and M only T1 Transient Protection Terminal Block C16 Custom Software Configuration Completed CDS 00806 0100 4001 required with order C20 0 8 3 2 V dc Output with Digital Signal Based on HART Protocol Outp
18. the apparatus is galvanically isolated ATEX Flame Proof and Dust Certification No KEMA 00ATEX2013X II 1 2 GD EEx d IIC T6 50 lt T4 lt 65 C Dust rating T90 C IP66 ce 1180 Vmax 55 V dc Special Conditions for Safe Use X This device contains a thin wall diaphragm Installation maintenance and use shall take into account the environmental conditions to which the diaphragm will be subjected The manufacturer s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime Japanese Certifications E4 TIIS Flame Proof Ex d IIC T6 Certificate Description C15850 3051C D 1 4 20 mA HART no display C15851 3051C D 1 4 20 mA HART with display C15854 3051T G 1 4 20 mA HART SST Silicon no display C15855 3051T G 1 4 20 mA HART Hastelloy C276 Silicon no display C15856 3051T G 1 4 20 mA HART SST Silicon with display C15857 3051T G 1 4 20 mA HART Hastelloy C276 Silicon with display TIIS Intrinsic Safety Ex ia IIC T4 Certificate Description C16406 3051CD CG Australian Certifications I7 SAA Intrinsic Safety Certification No AUS Ex 1249X Ex ia IIC T4 Tamb 70 C IP66 When connected per Rosemount drawing 03031 1026 TABLE 6 Input Parameters U 30V l 200 mA lj 160 mA output code A with T1 Pj 0 9W Cj 0 01 uF Cj 0 042 pF output code M Lj 10 uH L 1 05 mH output co
19. 008 3051T Dimensional Drawings 112 414 NPT Conduit Certification Connection Two Label Places Other 4 1 105 Sizes Available Sa ras EN o 0 75 20 Clearance for Cover Removal 0 75 20 Clearance for P Cover Removal i Transmitter Circuitry 183 Housing Rotation Set Screw 3051T Typical Mounting Configurations with Optional Mounting Bracket Pipe Mounting Panel Mounting Arn wwe za mi Hum Z O rm p 6 GY 156 O E ju g h 6 3 G 3 5 160 o f 4 8 120 gt 6 9 175 Dimensions are in inches millimeters 20 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 3051H Pressure Transmitter Exploded View and Dimensional Drawings Secondary Filled System Low Side Process Flan Drain Vent Valve Flange Bolts Process Isolating Diaphragm ge High Side Process Flange for Cover Removal Transmitter 0 75 19 Clearance otf 1 2 14 NPT 5 0 127 Conduit Connection 4 3 110 0 75 19 Clearance for Cover Removal Circuitry iA Nameplate _ Terminal Connections Housing Rotation Set Screw Drain Vent Valve Two Places Other Sizes Available 1 2 Certification Label 3 4 1 1 30
20. 3051CD Low Draft Range Ranges 0 1 0 2 of URL for 1 year 3051T Ranges 1 4 0 125 of URL for 5 years 50 F 28 C temperature changes and up to 1000 psi 6 9 MPa line pressure Rosemount 3051H Ranges 2 3 0 1 of URL for 1 year Ranges 4 5 0 2 of URL for 1 year Dynamic Performance 4 20mA Fieldbus HART protocol protocol Typical HART Transmitter Response Time Total Response Time Tg T 3051C Ranges 2 5 100 ms 152 ms Range 1 255 ms 307 ms Range 0 700 ms 752 ms Transmitter Output vs Time 3051T 100 ms 152 ms Pressure Released 3051H L Consult factory Consult factory T Dead Time Dead Time Td 45 ms nominal 97 ms am Time Constant Update Rate 22 times per second 22 times per second 100 sponse Time T4 T 1 Dead time and update rate apply to all models and ranges analog output only 2 Nominal total response time at 75 F 24 C reference conditions 36 8 pow 3 Transmitter fieldbus output only segment macro cycle not included 83 276 of Total Step Change 0 Time Line Pressure Effect per 1000 psi 6 9 MPa For line pressures above 2000 psi 13 7 MPa and Ranges 4 5 see user manual Rosemount publication number 00809 0100 4001 Models Line Pressure Effect 3051CD Zero Error Range 0 0 125 of URL 100 psi 6 89 bar Range 1 0 25 of URL 1000 psi 68 9 bar Ranges 2 3 0 05 of URL 1000 psi 68 9 bar for line pressures from 0 to 2000 psi 0 to 13 7 M
21. 80 Tantalum Flush Mount Only FO 4 in DN 100 Tantalum Flush Mount Only 31 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 TABLE 13 3051L Flange Mounted Liquid Level Transmitter e 51 Mounting Flange Size ASME B 16 5 ANSI or DIN Flange Rating Material M 2in Class 150 CS A 3 in Class 150 CS B 4 in Class 150 CS N 2 in Class 300 CS C 3 in Class 300 CS D 4 in Class 300 CS P 2 in Class 600 CS E 3 in Class 600 CS X 2 in Class 150 SST F 3 in Class 150 SST G 4 in Class 150 SST Y 2 in Class 300 SST H 3 in Class 300 SST J 4 in Class 300 SST Z 2 in Class 600 SST L 3 in Class 600 SST Q DN 50 PN 10 40 CS R DN 80 PN 40 CS S DN 100 PN 40 CS V DN 100 PN 10 16 CS K DN 50 PN 10 40 SST T DN 80 PN 40 SST U DN 100 PN 40 SST Ww DN 100 PN 10 16 SST e 1 Process Fill High Pressure Side Temperature Limits A Syltherm XLT 100 to 300 F 73 to 135 C C D C Silicone 704 60 to 400 F 15 to 205 C D D C Silicone 200 40 to 400 F 40 to 205 C H Inert Halocarbon 50 to 350 F 45 to 177 C G Glycerine and Water 0 to 200 F 17 to 93 C N Neobee M 20 0 to 400 F 17 to 205 C P Propylene Glycol and Water 0 to 200 F 17 to 93 C Low Pressure Side Code Configuration Flange Adapter Diaphragm Material Sensor Fill Fluid Gage 316L SST Silicone 21 Differential SST 316L SST Silicone 22 Differential SST Hastelloy C276 Silicone 2A Diff
22. 813 0100 4001 Rev HA March 2008 Rosemount 3051 FUNCTIONAL SPECIFICATIONS Range and Sensor Limits TABLE 1 3051CD 3051CG 3051L and 3051H Range and Sensor Limits Range and Sensor Limits Minimum Span Lower LRL 3051CD 1 Upper 3051C 3051C 3051L 3051L 3051H CG L H 0 318 Differential Gage Differential Gage Differential 0 0 1inH2O 3 0 inH2O 3 0 inH2O NA NA NA NA NA 0 25 mbar 7 47 mbar 7 47 mbar 1 0 5 inH2O 25 inH2O 25 inH2O 25 inH2O NA NA NA NA 1 2 mbar 62 3 mbar 62 1 mbar 762 1 mbar 2 2 inH2O 250 inH2O 250 inH2O 250 inH2O 250 inH2O 250 inH2O 250 inH2O 250 inH2O 6 2 mbar 0 62 bar 70 62 bar 70 62 bar 0 62 bar 0 62 bar 0 62 bar 70 62 bar 3 10 inH2O 1000 inH2O 1000 inH2O 0 5 psia 1000 inH2O 0 5 psia 1000 inH2O 0 5 psia 24 9 mbar 2 49 bar 2 49 bar 34 5 mbar abs 2 49 bar 34 5 mbar abs 2 49 bar 34 5 mbar abs 4 3 psi 300 psi 300 psi 0 5 psia 300 psi 0 5 psia 300 psi 0 5 psia 0 20 bar 20 6 bar 20 6 bar 34 5 mbar abs 20 6 bar 34 5 mbar abs 20 6bar 34 5 mbar abs 5 20 psi 2000 psi 2000 psi 0 5 psia NA NA 2000 psi 0 5 psia 1 38 bar 137 9 bar 137 9 bar 34 5 mbar abs 137 9 bar 34 5 mbar abs 1 Range 0 only available with 3051CD Range 1 only available with 3051CD or 3051CG TABLE 2 Range and Sensor Limits 3051CA 3051T Range and Sensor Limits Range and Sensor Limits Minimum Upper Lo
23. 841 136 092 680 46 When using a HART communicator 5 adjustment is allowed on the sensor limit to allow for unit conversions 3051C Absolute Pressure Transmitter Range Limits Range 1 Span Range 2 Span Range 3 Span Range 4 Span min max min max min max min max inH2O 8 30397 831 889 41 5198 4151 98 221 439 22143 9 1107 2 110720 inHg 0 61081 61 0807 3 05403 305 403 16 2882 1628 82 81 441 8144 098 ftH2O 0 69199 69 3241 3 45998 345 998 18 4533 1845 33 92 2663 9226 63 mmH2O 211 10 21130 6 35308 635 308 5634 66 563466 28146 1 2814613 mmHg 15 5145 1551 45 1055 47 105547 413 72 41372 2068 6 206860 0 psi 0 3 30 1 5 150 8 800 40 4000 bar 0 02068 2 06843 0 10342 10 342 0 55158 55 1581 2 75791 275 7905 mbar 20 6843 2068 43 103 421 10342 1 551 581 55158 1 2757 91 275790 5 g cm 21 0921 2109 21 105 27 105 27 561 459 56145 9 2807 31 280730 6 kg cm 0 02109 2 10921 0 10546 10 546 0 56246 56 2456 2 81228 281 228 Pa 2068 43 206843 10342 1 1034210 55158 1 5515811 275791 27579054 kPa 2 06843 206 843 10 3421 1034 21 55 1581 5515 81 275 791 27579 05 torr 15 5145 1551 45 77 5726 7757 26 413 721 413721 2068 6 206859 7 atm 0 02041 2 04138 0 10207 10 207 0 54437 54 4368 2 72184 272 1841 When using a HART communicator 5 adjustment is allowed on the sensor limit to allow for unit conversions 40 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 HART Protocol C1 Option Configuration Data Sheet x Default Value CONFIGURATION DATA
24. Blocks Processes the measurements for input into other function blocks The output value is in engineering units or custom and contains a status indicating measurement quality PID Block Contains all logic to perform PID control in the field including cascade and feedforward Backup Link Active Scheduler LAS The transmitter can function as a Link Active Scheduler if the current link master device fails or is removed from the segment Advanced Control Function Block Suite Option Code A01 Input Selector Block Selects between inputs and generates an output using specific selection strategies such as minimum maximum midpoint average or first good Arithmetic Block Provides pre defined application based equations including flow with partial density compensation electronic remote seals hydrostatic tank gauging ratio control and others Signal Characterizer Block Characterizes or approximates any function that defines an input output relationship by configuring up to twenty X Y coordinates The block interpolates an output value for a given input value using the curve defined by the configured coordinates Integrator Block Compares the integrated or accumulated value from one or two variables to pre trip and trip limits and generates discrete output signals when the limits are reached This block is useful for calculating total flow total mass or volume over time FOUNDATION fieldbus Diagnostics Suite Option Code
25. C Stainless Steel B3 Bracket with SST Bolts B3 bracket in stainless steel with Series 300 stainless steel bolts 38 Shipping Weights TABLE 15 Transmitter Weights without Options Transmitter Add Weight In Ib kg 3051C 6 0 2 7 3051L Table 16 on page 38 3051H 13 6 6 2 3051T 3 0 1 4 TABLE 16 3051L Weights without Options Flush 2 in Ext 4 in Ext 6 in Ext Flange Ib kg Ib kg Ib kg Ib kg 2 in 150 12 5 5 7 3 in 150 17 5 7 9 19 5 8 8 20 5 9 3 21 5 9 7 4 in 150 23 5 10 7 26 5 12 0 28 5 12 9 30 5 13 8 2 in 300 17 5 7 9 3 in 300 22 5 10 2 24 5 11 1 25 5 11 6 26 5 12 0 4 in 300 32 5 14 7 35 5 16 1 37 5 17 0 39 5 17 9 2 in 600 15 3 6 9 3 in 600 25 2 11 4 27 2 12 3 28 2 12 8 29 2 13 2 DN50 PN40 13 8 6 2 DN 80 PN40 19 5 8 8 21 5 9 7 22 5 10 2 23 5 10 6 DN 100 17 8 8 1 19 8 9 0 20 8 9 5 21 8 9 9 PN 10 16 DN 100 23 2 10 5 25 2 11 5 26 2 11 9 27 2 12 3 PN 40 EN a TABLE 17 Transmitter Options Weights Add Code Option Ib kg J K L M Stainless Steel Housing T 3 9 1 8 J K L M Stainless Steel Housing C L H P 3 1 1 4 M5 LCD display for Aluminum Housing 0 5 0 2 M6 LCD display for SST Housing 1 25 0 6 B4 SST Mounting Bracket for Coplanar Flange 1 0 0 5 B1B2B3 Mounting Bracket for Traditional Flange 2 3 1 0 B7 B8 B9 Mounting Bracket for Traditional Flange 2 3 1 0 BA BC SST Br
26. N Fieldbus SST Silicon with display C15861 3051T G 1 FOUNDATION Fieldbus Hastelloy C276 Silicon with display Australian Certifications I7 16 SAA Intrinsic Safety Certification No AUS Ex 1249X Ex ia IIC T4 Tap 60 C IP66 When connected per Rosemount drawing 03031 1026 TABLE 9 Input Parameters U 30 V li 300 mA Pj213W C 20 pF L 2 0 uH Special Conditions for Safe Use X The apparatus may only be used with a passive current limited power source Intrinsic Safety application The power Source must be such that Po x Uo lo 4 Modules using transient protection in the terminal assembly T1 transient protection models the apparatus enclosure is to be electrically bonded to the protective earth The conductor used for the connection shall be equivalent to a copper conductor of 4 mm2 minimum cross sectional area E7 SAA Explosion Proof Flame Proof Certification No AUS Ex 1347X Ex d IIC T6 Tamb 40 C DIP A21 T6 Tag 40 C IP66 Special Conditions for Safe Use X It is a condition of safe use for transmitter enclosures having cable entry thread other than metric conduit thread that the equipment be utilized with an appropriate certified thread adaptor N7 SAA Type n Non sparking Certification No AUS Ex 1249X Ex n IIC T4 Tamb 70 C IP66 Special Conditions for Safe Use X Where the equipment is installed such that there is an unused conduit entry it must b
27. NAMUR Compliant operation is pre set at the factory and cannot be changed to standard operation in the field 6 The V5 option is not needed with the T1 option external ground screw assembly is included with the T1 option wo 6 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 OPTIONS Standard Configuration Unless otherwise specified transmitter is shipped as follows ENGINEERING UNITS Differential Gage inH4O Range 0 1 2 and 3 psi Range 4 and 5 Absolute 3051T psi all ranges 4 mA 1 V dc 0 engineering units above 20 mA 5 V dc Upper range limit Output Linear Flange type Specified model code option Flange material Specified model code option O ring material Specified model code option Drain vent Specified model code option Integral meter Installed or none Alarm Upscale Software tag Blank 1 Not applicable to fieldbus Custom Configuration HART protocol only If Option Code C1 is ordered the customer may specify the following data in addition to the standard configuration parameters Output Information Transmitter Information LCD display Configuration Hardware Selectable Information Signal Selection Refer to the HART Protocol C1 Option Configuration Data Sheet document number 00806 0100 4001 Tagging 3 options available Standard SST hardware tag is wired to the transmitter Tag character height is 0 125 in 3 18 mm 56 cha
28. Pa Span Error Range 0 0 15 of reading 100 psi 6 89 bar Range 1 0 4 of reading 1000 psi 68 9 bar Ranges 2 3 x0 196 of reading 1000 psi 68 9 bar 3051HD Zero Error All Ranges 0 1 of URL 1000 psi 68 9 bar for line pressures from 0 to 2000 psi 0 to 13 7 MPa Span Error All Ranges 0 1 of reading 1000 psi 68 9 bar 1 Can be calibrated out at line pressure Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 Ambient Temperature Effect per 50 F 28 C Models Ambient Temperature Effect 3051CD CG Range 0 0 25 URL 0 05 span Range 1 0 1 URL 0 25 span Ranges 2 5 0 0125 URL 0 0625 span from 1 1 to 5 1 0 025 URL 0 125 span from 5 1 to 100 1 3051T Range 1 0 025 URL 0 125 span from 1 1 to 10 1 0 05 URL 0 125 span from 10 1 to 100 1 Range 2 4 0 025 URL 0 125 span from 1 1 to 30 1 0 035 URL 0 125 span from 30 1 to 100 1 Range 5 0 1 URL 0 15 span 3051CA All Ranges 0 025 URL 0 125 span from 1 1 to 30 1 0 035 URL 0 125 span from 30 1 to 100 1 3051H All Ranges 0 025 URL 0 125 span 0 35 inH2O from 1 1 to 30 1 0 035 URL 0 125 span 0 35 inH2O from 1 1 to 30 1 3051L See Rosemount Inc Instrument Toolkit software Mounting Position Effects Models Mounting Position Effects 3051C Zero shifts up to 1 25 inH2O 3 11 mbar which can be calibrated out No span effect 3051H Zero shifts up to 5 inH2O
29. Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Rosemount 3051 Pressure Transmitter THE PROVEN INDUSTRY LEADER IN PRESSURE MEASUREMENT Best in Class performance with 0 0496 High Accuracy option Industry first installed five year stability Unmatched Dynamic Performance Coplanar platform enables integrated pressure flow and level solutions Advanced PlantWeb Functionality to increase plant productivity CE FOUNDATION Contents Product Offering isses su ee Ea oe eee bone Ron aG page 3 Specifications mantre scere E E RAD eM ea tcs s E ee dura etos RR d page 4 Product Certifications a a aa nsaan nuana es page 12 HART Protocol is erecta eer ENR RES ENG ERG NA Ea page 12 Fieldbus Protocol ocs esarri 00 0 cee ee eee page 15 Dimensional Drawings leslie RII page 17 Ordering Information 0 000 eee eae page 25 HART Protocol C1 Option Configuration Data Sheet page 41 ROSEMOUNT EMERSON www rosemount com Process Management Rosemount 3051 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Setting the Standard for Pressure Measurement Industry s best total performance a flexible Coplanar platform and installed five year stability has made the Rosemount 3051 the standard in pressure measurement Industry s best in class total performance of 0 15 Total performance is the true me
30. SHEET Customer P O No Model No Line Item SST Tag No Software Tag __ bL bL bL I OUTPUT INFORMATION Software Selectable 4 mA 1 0 8 Volts O 20 mA 5 3 2 Volts Upper Range Limit x Pressure Units L inH 0O x L psi x L Pa L ftH2O L inHg L bar C kPa g cm L mbar L Torr L mmH O L inH5O at 4 c L Atm L kg cm C mmHg L mmh at 4 c Output L Linear x L Square Root For DP transmitters only Damping 0 00 sec 0 05 sec L 0 10 sec C 0 20 sec _ 0 40 sec L 0 80 sec L 1 60 sec L 3 20 sec L 12 8 sec L 25 6 sec TRANSMITTER INFORMATION Software Selectable Descriptor 4 LL LL I I L I IL I 16 characters Message J I ee pez esp T Ens spp e e pes s e pipe nf nnne pe pe es hg 32 characters Date L LL O OL Day Month Year Local Span and Zero Enabled L Disabled 1 Default values may be different outside the U S A Consult an Emerson Process Management Representative for details 2 inH20 for CD CG ranges 1 3 3 psi for CD CG range 4 and 5 all CA ranges 4 C1 option required for configuration of this parameter 5 Not available with low power output Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 LCD display CONFIGURATION Software Adjustable M5 or M6 option must be specified in model number Meter Display Type
31. acket for Traditional Flange 2 3 1 0 B5B6 Mounting Bracket for 3051H 2 9 1 3 H2 Traditional Flange 2 4 1 1 H3 Traditional Flange 2 7 1 2 H4 Traditional Flange 2 6 1 2 H7 Traditional Flange 2 5 1 1 FC Level Flange 3 in 150 10 8 4 9 FD Level Flange 3 in 300 14 3 6 5 FA Level Flange 2 in 150 10 7 4 8 FB Level Flange 2 in 300 14 0 6 3 FP DIN Level Flange SST DN 50 PN 40 8 3 3 8 FQ DIN Level Flange SST DN 80 PN 40 13 7 6 2 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 3051C Differential Gage Pressure Transmitter Range Limits Range 1 Span Range 2 Span Range 3 Span Range 4 Span REU os EU min max min max min max min max min max inH2O 0 5 25 2 5 250 10 1000 83 040 8304 553 60 55360 inHg 0 03678 1 8389 0 18389 18 389 0 73559 73 559 6 1081 610 81 40 720 4072 04 ftH2O 0 04167 2 08333 0 20833 20 8333 0 83333 83 3333 6 9198 691 997 46 13 4613 31 mmH 0 12 7 635 5 63 553 6355 254 25421 2110 95 211095 14073 1407301 mmHg 0 93416 46 7082 4 67082 467 082 18 6833 1868 33 155 145 15514 5 1034 3 103430 psi 0 01806 0 903 0 0902 9 03183 0 36127 36 127 3 300 20 2000 bar 0 00125 0 06227 0 00623 0 62272 0 02491 2 491 0 20684 20 6843 1 37895 137 895 mbar 1 2454 62 2723 6 22723 622 723 24 9089 2490 89 206 843 20684 3 1378 95 137895 g cm 1 26775 63 3875 6 33875 633 875 25 355 2535 45 210 547 21054 7 1406 14 140614 kg cm 0 00127 0 0635 0 00635 0 635 0 0254 2 54 0 21092 21 0921 1 40614 140 614
32. ansmitter Type Select One HD HG 3051HD Differential Pressure Transmitter for High Temperature Processes 3051HG Gage Pressure Transmitter for High Temperature Processes Code Pressure Ranges Range Min Span 3051HD 3051HG 2 250 to 250 inH20 2 5 inH2O 250 to 250 inH20 2 5 inH2O 0 62 to 0 62 bar 6 2 mbar 0 62 to 0 62 bar 6 2 mbar 3 1000 to 1000 inH2O 10 inH2O 407 to 1000 inH2O 10in H20 2 5 to 2 5 bar 25 mbar 71 01 to 2 5 bar 25 mbar 4 300 to 300 inH2O 3 psi 14 7 to 300 psi 3 psi 747 to 747 mbar 0 2 bar 71 01 to 20 7 bar 0 2 bar 5 2000 to 2000 psi 20 psi 14 7 to 2000 psig 20 psi 7138 to 138 bar 1 4 bar 71 01 to 138 bar 1 4 bar NOTE 3051HG lower range limit varies with atmospheric pressure Code Output HD HG A 4 20 mA with Digital Signal Based on HART Protocol M Low Power 1 5 V dc with Digital Signal Based on HART Protocol See Option Code C2 for 0 8 3 2 V dc Output Not available with hazardous certification Option Codes I1 N1 E4 K6 and K8 F FOUNDATION fieldbus Protocol WwW Profibus PA Code Process Connection HD HG Process Flange Material Drain Vent 2 SST SST 7 SST Hastelloy C276 Code Process Isolating Diaphragm HD HG 2 316L SST 3 Hastelloy C276 5 Tantalum Code O ring Material HD HG A Glass Filled PTFE Code Process Fill Fluid HD HG D D C 200 Silicone H Inert N Neobee M 20 Code Sensor Module Isolator Mater
33. asure of real world transmitter performance Using superior sensor technology and engineered for optimal performance the 3051 delivers unprecedented 0 04 reference accuracy resulting in total operating performance of 0 15 Superior total performance equates to reduced variability and improved plant safety Installed five year stability of 0 125 Transmitter stability is a critical measure of transmitter performance over time Through aggressive simulation testing beyond standard IEC 770 testing the 3051 has proven its ability to maintain performance over a five year period under the most demanding process conditions Superior transmitter stability reduces calibration frequency to save operation and maintenance costs Unmatched dynamic performance In dynamic applications speed of measurement is as important as repeatability The 3051 responds up to eight times faster than the typical pressure transmitter to detect and control variations quickly and efficiently Superior dynamic response yields more accurate measurements to reduce variability and increase profitability Coplanar platform enables complete point solutions The versatile Coplanar platform design enables the best process connection for pressure flow and level applications Right out of the box the solution arrives factory calibrated pressure tested and ready to install Only the 3051 has a flexible design to reduce engineering and inventory costs Advanced Pla
34. compliant values are available option code C4 High or low alarm signal is user selectable by internal jumper Output Code M If self diagnostics detect a gross transmitter failure the analog signal will be driven either below 0 94 V or above 5 4 V to alert the user below 0 75 V or above 4 4 V for Option C2 High or low alarm signal is user selectable by internal jumper Output Code F and W If self diagnostics detect a gross transmitter failure that information gets passed as a status along with the process variable Temperature Limits Ambient 40 to 185 F 40 to 85 C With LCD display 4 to 175 F 20 to 80 C Storage 50 to 230 F 46 to 110 C With LCD display 40 to 185 F 40 to 85 C Process At atmospheric pressures and above See Table 4 1 LCD display may not be readable and LCD updates will be slower at temperatures below 4 F 20 C Rosemount 3051 Product Data Sheet 00813 0100 4001 Rev HA March 2008 TABLE 4 3051 Process Temperature Limits 3051CD 3051CG 3051CA Silicone Fill Sensor 40 to 250 F 40 to 121 C with Coplanar Flange 40 to 300 F 40 to 149 C 2X9 with Traditional Flange with Level Flange 40 to 300 F 40 to 149 C with 305 Integral Manifold 40 to 300 F 40 to 149 C O Inert Fill Sensor 0 to 185 F 18 to 85 C 9 3051H Process Fill Fluid D C Silicone 200 40 to 375 F 40 to 191 C
35. de A with T1 Lj 0 75 mH output code M with T1 Special Conditions for Safe Use X The apparatus may only be used with a passive current limited power source Intrinsic Safety application The power Source must be such that Po x Uo lo 4 Modules using transient protection in the terminal assembly T1 transient protection models the apparatus enclosure is to be electrically bonded to the protective earth The conductor used for the connection shall be equivalent to a copper conductor of 4 mm minimum cross sectional area 13 Rosemount 3051 Product Data Sheet 00813 0100 4001 Rev HA March 2008 E7 SAA Explosion Proof Flame Proof Certification No AUS Ex 03 1347X Ex d IIC T6 Tamb 40 C DIP A21 T6 Tamb 40 C IP66 Special Conditions for Safe Use X It is a condition of safe use for transmitter enclosures having cable entry thread other than metric conduit thread that the equipment be utilized with an appropriate certified thread adaptor N7 SAA Type n Non sparking Certification No AUS Ex 1249X Ex n IIC T4 Tamb 70 C IP66 Special Conditions for Safe Use X Where the equipment is installed such that there is an unused conduit entry it must be sealed with a suitable blanking plug to maintain the IP66 degree of protection Any blanking plug used with the equipment shall be of a type which requires the use of a tool to effect its removal Voltage source shall not exceed 55V dc Combinatio
36. e Outside No of Bolt Hole Extension O D Gasket Size Thickness A DiameterB Diameter C Bolts Diameter Diameter D Surface E ASME B16 5 ANSI 150 2 51 0 69 18 4 75 121 6 0 152 4 0 75 19 NA 3 6 92 3 76 0 88 22 6 0 152 7 5 191 4 0 75 19 2 58 66 5 0 127 4 102 0 88 22 7 5 191 9 0 229 8 0 75 19 3 5 89 6 2 158 ASME B16 5 ANSI 300 2 51 0 82 21 5 0 127 6 5 165 8 0 75 19 NA 3 6 92 3 76 1 06 27 6 62 168 8 25 210 8 0 88 22 2 58 66 5 0 127 4 102 1 19 30 7 88 200 10 0 254 8 0 88 22 3 5 89 6 2 158 ASME B16 5 ANSI 600 2 51 1 00 25 5 0 127 6 5 165 8 0 75 19 NA 3 6 92 3 76 1 25 32 6 62 168 8 25 210 8 0 88 22 2 58 66 5 0 127 DIN 2501 PN 10 40 DN 50 20 mm 125 mm 165 mm 4 18 mm NA 4 0 102 DIN 2501 PN 25 40 DN 80 24 mm 160 mm 200 mm 8 18 mm 65 mm 5 4 138 DN 100 24 mm 190 mm 235 mm 8 22 mm 89 mm 6 2 158 DIN 2501 PN 10 16 DN 100 20 mm 180 mm 220 mm 8 18 mm 89 mm 6 2 158 Pipe Process Lower Housing G Class Size Side F 1 4 NPT 1 2 NPT H ASME B16 5 ANSI 150 2 51 2 12 54 0 97 25 1 31 33 5 65 143 3 76 3 6 91 0 97 25 1 31 33 5 65 143 4 102 3 6 91 0 97 25 1 31 33 5 65 143 ASME B16 5 ANSI 300 2 51 2 12 54 0 97 25 1 31 33 5 65 143 3 76 3 6 91 0 97 25 1 31 33 5 65 143 4 102 3 6 91 0 97 25 1 31 33 5 65 143 ASME B16 5 ANSI 600 2 51 2 12 54 0 97 25 1 31 33 7 65 194 3 76 3 6 91 0 97 25 1 31
37. e of the art fifth generation Rosemount 485 Annubar combined with the 3051S or 3095MV MultiVariable transmitter creates an accurate repeatable and dependable insertion type flowmeter Compact Orifice Flowmeter Series Rosemount 3051SFC 3095MFC and 405 Compact Orifice Flowmeters can be installed between existing flanges up to a Class 600 PN100 rating In tight fit applications a conditioning orifice plate version is available requiring only two diameters of straight run upstream ProPlate Flowmeter Series Rosemount ProPlate Mass ProPlate and 1195 These integral orifice flowmeters eliminate the inaccuracies that become more pronounced in small orifice line installations The completely assembled ready to install flowmeters reduce cost and simplify installation Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Product Offering Rosemount 3051C Differential Gage and Absolute See ordering information on page 25 Performance up to 0 0496 accuracy Installed five year stability of 0 12596 Coplanar platform enables integrated manifold primary element and diaphragm seal solutions Calibrated spans ranges from 0 1 inH5O to 4000 psi 0 25 mbar to 276 bar 316L SST Hastelloy C276 Monef Tantalum Gold plated Monel or Gold plated 316L SST process isolators Rosemount 3051T Gage and Absolute See ordering information on page 29 Performance up to 0 0496 accuracy Installed fiv
38. e sealed with a suitable blanking plug to maintain the IP40 degree of protection Any blanking plug used with the equipment shall be of a type which requires the use of a tool to effect its removal Voltage source shall not exceed 35V dc Combinations of Certifications Stainless steel certification tag is provided when optional approval is specified Once a device labeled with multiple approval types is installed it should not be reinstalled using any other approval types Permanently mark the approval label to distinguish it from unused approval types K5 E5 and I5 combination KB K5 and C6 combination KD K5 C6 11 and E8 combination K6 C6 11 and E8 combination K8 E8 and I1 combination K7 ET I7 and N7 combination Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Dimensional Drawings 3051 Exploded View Certification Label Span and Zero Adjustments Standard Electronics Housing fs d Terminal Block Cover O ring Cover lectronics Board a Housing Rotation Set Screw 180 Maximum Housing Rotation without Further Disassembly Coplanar Flange Drain Vent Valve Flange 1 Span and Zero Adjustments are not available with fieldbus or profibus protocols Flange Adapter O Ring Flange Alignment Screw Not Pressure Retaining 17 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 3051C Coplanar Flange Dimensional Drawi
39. e year stability of 0 12596 Calibrated spans from 0 3 to 10000 psi 10 3 mbar to 689 bar Multiple process connections available 316L SST and Hastelloy C276 process isolators Rosemount 3051L Liquid Level See ordering information on page 31 e Performance up to 0 075 accuracy e Welded fill fluid system provides best in class system reliability Flush and extended diaphragms Multiple fill fluids and wetted materials available Rosemount 3051 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Specifications PERFORMANCE SPECIFICATIONS Total Performance is based on combined errors of reference accuracy ambient temperature effect and static pressure effect This product data sheet covers both HART and fieldbus protocols unless specified Conformance To Specification 30 Sigma Technology leadership advanced manufacturing techniques and statistical process control ensure specification conformance to at least 30 Reference Accuracy Models 3051CD 3051CG Range 0 CD 0 10 of span For spans less than 2 1 accuracy 0 05 of URL Range 1 0 10 of span For spans less than 15 1 accuracy s o 025 0 oos SR Standard of Span Ranges 2 5 0 065 of span For spans less than 10 1 accuracy YRL fo 015 0 oos of Span 3051T Ranges 1 4 0 065 of span For spans less than 10 1 accuracy o 0075 85 J of Span Range 5 0 075 of span For spa
40. erential SST 316L SST Inert Halocarbon 2B Differential SST Hastelloy C276 Inert Halocarbon 31 Remote Seal SST 316L SST Silicone Requires Option Code S1 Code O ring Material A Glass filled PTFE Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 TABLE 13 3051L Flange Mounted Liquid Level Transmitter Code Housing Material Conduit Entry Size A Polyurethane covered Aluminum 72 14 NPT B Polyurethane covered Aluminum M20 x 1 5 CM20 C Polyurethane covered Aluminum PG 13 5 D Polyurethane covered Aluminum Gh J SST 72 14 NPT K SST M20 x 1 5 CM20 L SST PG 13 5 M SST GR Code PlantWeb Functionality Optional A01 Advanced Control Function Block Suite D01 FOUNDATION fieldbus Diagnostics Suite e 1 Diaphragm Seal Assemblies Optional S1 One Diaphragm Seal requires low pressure side Option Code 31 capillary connection type Code Hazardous Locations Certification Options E5 FM Explosion proof Approval 15 FM Non incendive and Intrinsic Safety Approval IE FM FISCO Intrinsically Safe for FOUNDATION fieldbus protocol only K5 FM Explosion proof and Intrinsic Safety Approval 14 ATEX Intrinsic Safety and Dust Certification N10 ATEX Type N and Dust Certification E8 ATEX Flame proof and Dust Certification E40 TIIS Flame proof Certification C6 CSA Explosion proof and Intrinsic Safety Approval Ke CSA and ATEX Explosion proof and Intrinsic Safety Approval combination of C6 and K8 KB FM and CSA Explosio
41. essure Ranges Range Min Span 3051TG 3051TA 1 14 7 to 30 psi 0 3 psi 1 01 to 2 1 bar 20 7 mbar 0 to 30 psia 0 3 psia 0 to 2 1 bar 20 7 mbar 2 14 7 to 150 psi 1 5 psi 1 01 to 10 3 bar 103 4 mbar 0 to 150 psia 1 5 psia 0 to 10 3 bar 103 4 mbar 3 14 7 to 800 psi 8 psi 1 01 to 55 2 bar 0 55 bar 0 to 800 psia 8 psia 0 to 55 2 bar 0 55 bar 4 14 7 to 4000 psi 40 psi 1 01 to 275 8 bar 2 8 bar 0 to 4000 psia 40 psia 0 to 275 8 bar 2 8 bar 5 14 7 to 10000 psi 2000 psi 1 01 to 689 5 bar 138 bar 0 to 10000 psia 2000 psia 0 to 689 5 bar 138 bar Code Output A 4 20 mA with Digital Signal Based on HART Protocol M Low Power 1 5 V dc with Digital Signal Based on HART Protocol See Option Code C2 for 0 8 3 2 V dc Output Not available with hazardous certification Option Codes I1 N1 E4 K6 or K8 F FOUNDATION fieldbus Protocol WwW Profibus PA Code Process Connection Style 2B 2 14 NPT Female 2C G A DIN 16288 Male Available in SST for Range 1 4 only 2F Coned and Threaded Compatible with Autoclave Type F 250 C Only available in SST for Range 5 Code Isolating Diaphragm Process Connection Wetted Parts Material 2 316L SST 316L SST 30 Hastelloy C276 Hastelloy C276 Code Fill Fluid 1 Silicone 2 Inert Fluorinert FC 43 Code Housing Material Conduit Entry Size A Polyurethane covered Aluminum 12 14 NPT B Polyurethane covered Aluminum M20 x 1 5 CM20 C Polyurethane covered Alum
42. evel Transmitter Model Transmitter Type 3051L Flange Mounted Liquid Level Transmitter Code Pressure Ranges Range Min Span 2 250 to 250 inH20 2 5 inH2O 0 6 to 0 6 bar 6 2 mbar 3 1000 to 1000 inH2O 10 inH2O 2 5 to 2 5 bar 25 mbar 4 300 to 300 psi 3 psi 20 7 to 20 7 bar 0 2 bar Code Output A 4 20 mA with Digital Signal Based on HART Protocol M Low Power 1 5 V dc with Digital Signal Based on HART Protocol See Option Code C2 for 0 8 3 2 V dc Output Not available with hazardous certification Option Codes I1 N1 E4 K6 and K8 F FOUNDATION fieldbus Protocol Ww Profibus PA High Pressure Side e 1 Diaphragm Size Material Extension Length GO 2 in DN 50 316L SST Flush Mount Only HO 2 in DN 50 Hastelloy C276 Flush Mount Only JO 2 in DN 50 Tantalum Flush Mount Only AO 3 in DN 80 316L SST Flush Mount A2 3 in DN 80 316L SST 2 in 50 mm A4 3 in DN 80 316L SST 4 in 100 mm A6 3 in DN 80 316L SST 6 in 150 mm BO 4 in DN 100 316L SST Flush Mount B2 4 in DN 100 316L SST 2 in 50 mm B4 4 in DN 100 316L SST 4 in 100 mm B6 4 in DN 100 316L SST 6 in 150 mm CO 3 in DN 80 Hastelloy C276 Flush Mount C2 3 in DN 80 Hastelloy C276 2 in 50 mm C4 3 in DN 80 Hastelloy C276 4 in 100 mm C6 3 in DN 80 Hastelloy C276 6 in 150 mm DO 4 in DN 100 Hastelloy C276 Flush Mount D2 4 in DN 100 Hastelloy C276 2 in 50 mm D4 4 in DN 100 Hastelloy C276 4 in 100 mm D6 4 in DN 100 Hastelloy C276 6 in 150 mm EO 3 in DN
43. ge is user selectable from 0 to 36 seconds for one time constant This software damping is in addition to sensor module response time 10 PHYSICAL SPECIFICATIONS Electrical Connections 1 2 14 NPT PG 13 5 G1 2 and M20 x 1 5 CM20 conduit HART interface connections fixed to terminal block Process Connections All Models except 3051L and 3051T 14 18 NPT on 2 e in centers 1 2 14 NPT on 2 21 s or 21 4 in centers Rosemount 3051L High pressure side 2 3 or 4 in ASME B 16 5 ANSI Class 150 300 or 600 flange 50 80 or 100 mm PN 40 or 10 16 flange Low pressure side 1 4 18 NPT on flange 2 14 NPT on adapter Rosemount 3051T 1 2 14 NPT female A DIN 16288 Male available in SST for Range 1 4 transmitters only or Autoclave type F 250 C Pressure relieved 16 18 gland thread 1 4 OD high pressure tube 60 cone available in SST for Range 5 transmitters only Process Wetted Parts Drain Vent Valves 316 SST Hastelloy C276 or Monel material Monel not available with 3051L or 3051H Process Flanges and Adapters Plated carbon steel SST cast CF 8M cast version of 316 SST material per ASTM A743 C Type cast alloy CW12MW or Monel cast alloy M30C Wetted O rings Glass filled PTFE or Graphite filled PTFE Process Isolating Diaphragms o 9 a 9 Isolating Diaphragm Material S 316L SST Hastelloy C276 Monel Tantalum Gold plated Monel Gold plated SST Product Data
44. iable mA value L Muttidrop Communication Choose transmitter address 1 15 4 C1 option required for configuration of this parameter 5 Not available with low power output 6 This option fixes the transmitter analog output at 4mA 7 Default address is 1 if multidrop communication is selected Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 43 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 Standard Terms and Conditions of Sale can be found at www rosemount comMerms of sale The Emerson logo is a trade mark and service mark of Emerson Electric Co Rosemount Annubar ProPlate and the Rosemount logotype are registered trademarks of Rosemount Inc PlantWeb is a registered trademark of one of the Emerson Process Management group of companies Instrument Toolkit is a registered trademark of Emerson Process Management Complete Point Solutions Coplanar and Multivariable are trademarks of Rosemount Inc HART is a registered trademark of the HART Communications Foundation Hastelloy is a registered trademark of Haynes international Inc Monel is a registered trademark of the Special Metals Corporation group of Companies Syltherm 800 Dow Corning and D C are registered trademarks of Dow Corning Co Neobee M 20 is a registered trademark of Stephan Chemical Co The 3 A symbol is a registered trademark of the 3 A Sanitary Standards Symbol Council FOUNDATION f
45. ial HD HG 2 SST Code Sensor Module Fill Fluid HD HG 1 Silicone 2 Inert Halocarbon Code Housing Material Conduit Entry Size HD HG A Polyurethane covered Aluminum 72 14 NPT B Polyurethane covered Aluminum M20 x 1 5 CM20 C Polyurethane covered Aluminum PG 13 5 D Polyurethane covered Aluminum G J SST 72 14 NPT K SST M20 x 1 5 CM20 L SST PG 13 5 M SST G Code PlantWeb Functionality Optional A01 Advanced Control Function Block Suite D01 FOUNDATION fieldbus Diagnostics Suite Code Integral Mount Primary Elements Optional HD HG S4 Factory Assembly to Rosemount Primary Element Rosemount Annubar or Rosemount 1195 Integral Orifice With the primary element installed the maximum operating pressure will equal the lesser of either the transmitter or the primary element Option is available for factory assembly to range 1 4 transmitters only 35 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 TABLE 14 3051H Pressure Transmitter for High Temperature Processes Not Applicable Applicable Code Mounting Bracket Options HD HG B5 Universal Mounting Bracket for 2 in Pipe or Panel Mount CS Bolts B6 Universal Mounting Bracket for 2 in Pipe or Panel Mount SST Bolts Code Hazardous Locations Certification Options HD HG E5 FM Explosion proof Approval I5 FM Non incendive and Intrinsic Safety Approval K5 FM Explosion proof and I
46. ieldbus is a registered trademark of the Fieldbus Foundation Fluorinert is a registered trademark of 3M Company All other marks are the property of their respective owners Rosemount Model 3051 Smart Pressure Transmitters may be protected by one or more of the following U S Patent Nos 4 370 890 4 466 290 4 612 812 4 791 352 4 798 089 4 818 994 4 833 922 4 866 435 4 926 340 4 988 990 and 5 028 746 Mexico Patentado No 154 961 May depend on model Other foreign patents issued and pending Emerson Process Management Rosemount Inc Emerson Process Management Emerson Process Management Asia 8200 Market Boulevard Heath Place Pacific Private Limited Chanhassen MN 55317 USA Bognor Regis 1 Pandan Crescent T U S 1 800 999 9307 West Sussex PO22 9SH Singapore 128461 T International 952 906 8888 England T 65 6777 8211 F 952 949 7001 T 44 0 1243 863121 F 65 6777 0947 F 44 0 1243 867554 Enquiries AP EmersonProcess com www rosemount com UIT EMERSON 2008 Rosemount Inc All rights reserved Process Management
47. inless steel housing option housing codes J K and L Local Span and Zero Adjustment Transmitters ship with local span and zero adjustments standard unless otherwise specified Non interactive external zero and span adjustments ease calibration Magnetic switches replace standard potentiometer adjustments to optimize performance J1 Local Zero Adjustment Only J3 No Local Zero or Span Adjustment Transient Protection T1 Integral Transient Protection Terminal Block Integral transient protection terminal block Meets IEEE Standard 587 Category B 1 kV crest 10 x 1 000 microseconds 3 kV crest 8 X 20 microseconds 6 kV crest 1 2 x 50 microseconds Meets IEEE Standard 472 Surge Withstand Capability SWC 2 5 kV crest 1 MHz wave form Applicable standards IEC 801 4 801 5 Bolts for Flanges and Adapters Options permit bolts for flanges and adapters to be obtained in various materials Standard material is plated carbon steel per ASTM A449 Type 1 L4 Austenitic 316 Stainless Steel Bolts L5 ASTM A 193 Grade B7M Bolts L6 Monel Bolts 2 Not applicable to fieldbus 37 Rosemount 3051 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051C Coplanar Flange and 3051T Bracket Option B4 Bracket for 2 in Pipe or Panel Mounting e For use with the standard Coplanar flange configuration Bracket for mounting of transmitter on 2 in pipe or panel Stainless steel construction with s
48. inum PG 13 5 D Polyurethane covered Aluminum G J SST 72 14 NPT K SST M20 x 1 5 CM20 L SST PG 13 5 M SST G Code PlantWeb Functionality Optional A01 Advanced Control Function Block Suite D01 FOUNDATION fieldbus Diagnostics Suite Code Integral Mount Manifold Optional S5 Assemble to Rosemount 306 Integral Manifold specified separately see the Rosemount 305 and 306 Integral Manifolds PDS document number 00813 0100 4733 Requires 1 2 in process connection code 2B Code Remote Diaphragm Seals Assemblies Optional S1 One remote diaphragm seal Direct Mount or Capillary Connection Type Requires Process Connection Style code 2B Code Mounting Brackets Optional B4 Bracket for 2 in Pipe or Panel Mounting All SST N o Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 TABLE 12 3051T Gage and Absolute Pressure Transmitter Code Hazardous Locations Certifications Optional E5 FM Explosion proof Approval I5 FM Non incendive and Intrinsic Safety Approval IE FM FISCO Intrinsically Safe for FOUNDATION fieldbus protocol only K5 FM Explosion proof and Intrinsic Safety Approval C5 Measurement Canada accuracy approval Limited availability depending on transmitter type and range Contact an Emerson Process Management representative C6 CSA Explosion proof and Intrinsic Safety Approval K6 CSA and ATEX Explosion proof and Intrinsic Safety Approval combination of C6 and K8 KB FM and CSA Explosion
49. n proof and Intrinsic Safety Approvals combination of K5 and C6 K7 SAA Flame proof and Intrinsic Safety Approvals combination of I7 N7 and E7 Ka ATEX Flame proof and Intrinsic Safety Approvals combination of 11 and E8 Kp CSA FM and ATEX Explosion proof and Intrinsic Safety Approval combination of K5 C6 11 and E8 I7 SAA Intrinsic Safety Certification E7 SAA Flame proof Certification N7 SAA Type N Certification IA ATEX Intrinsic Safety for FISCO for FOUNDATION fieldbus protocol only Code Bolt for Flange and Adapters Optional L5 ASTM A 193 Grade B7M Bolts e 1 Display Options M5 LCD display for Aluminum Housing Available with Housing codes A B C and D only M6 LCD display for SST Housing Available with Housing codes J K L and M only Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 TABLE 13 3051L Flange Mounted Liquid Level Transmitter Code Q4 Q8 QZ QP JAGU Ja T1 c1 c2 c4QG0 CNOX5 D8 V5 6 Code F1 F2 F30 F40 Other Options Calibration Data Sheet Material Traceability Certification per EN 10204 3 1 B Available with the diaphragm upper housing Coplanar flange adapter sensor module housing lower housing flushing connection and extension Remote Seal System Performance Calculation Report Calibration certification and tamper evident seal Local Zero Adjustment Only No Local Zero or Span Adjustment Transient Protection Terminal Block Cus
50. ng Differential Pressure Transmitter Shown 5 0 127 1 2 14 NPT Certification 4 3 110 Conduit Connection 4 1 Label C Two Places Other P 105 0 75 20 Clearance 0 75 20 Clearance i i CE FN for Cover Removal for Cover Removal eae Terminal Transmitter 1 i Circuitry i amp r o Connections Nameplate gt Y Drain Vent Valve 7 1 181 8 2 209 Housing Rotation Set Screw Coplanar Flange y Process Connection 9 0 0 i Y Per IEC 61518 2 126 54 10 012 in 74 18 NPT on Coplanar Flange 6 4 163 Connection Centers for Pressure Connection without the Use He f Flange Adapt 112 14 NPT on Optional Flange Adapters Adapters can be rotated Shenae snap to give connection centers of 2 00 51 2 126 54 or 2 25 57 Coplanar Flange Mounting Configurations with Optional Bracket B4 for 2 in Pipe or Panel Mounting 2 8 3 J aat 9 7 5 4 x 11 2 Bolts 4 1 1 28 71 9 for Panel Mounting o aa ee Not Supplied z EC 7 4 j E gt 181 ali 5 31 16 x 1 14 Bolts y e E s for M ti z LJH y or Mounting V m td id to Transmitter Lu 6 EE Y E oO 156 F 2g 1 1 28 P SY Go m 3 4 E s 4 8 120 2 inch U Bolt for Pipe Mounting o
51. ns less than 10 1 accuracy 0 0075 URL o of Span Spa 3051CA Ranges 1 4 0 065 of span For spans less than 10 1 accuracy o 0075 YRL se of Span 3051H 3051L All Ranges 0 075 of span For spans less than 10 1 accuracy fo 025 0 005 URL soe of Span High Accuracy Option Ranges 2 4 High Accuracy Option P8 0 04 of span For spans less than 5 1 accuracy SRL 2 0 015 0 oos SE of Span Ranges 2 4 High Accuracy Option P8 0 04 of span For spans less than 5 1 accuracy o 007s 8 of Span Ranges 2 4 High Accuracy Option P8 0 04 of span For spans less than 5 1 accuracy 0 0075 Z846 J of Span 1 For FOUNDATION fieldbus transmitters use calibrated range in place of span For zero based spans reference conditions silicone oil fill SST materials Coplanar flange 3051C or 1 2 in 18 NPT 3051T process connections digital trim values set to equal range points Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Total Performance For 50 F 28 C temperature changes up to 1000 psi 6 9 MPa line pressure CD only from 1 1 to 5 1 rangedown Models Total Performance 3051C Ranges 2 5 0 15 of span 3051T Ranges 1 4 0 15 of span Long Term Stability Models Long Term Stability 3051C Ranges 2 5 0 125 of URL for 5 years 50 F 28 C temperature changes and up to 1000 psi 6 9 MPa line pressure
52. ns of Certifications Stainless steel certification tag is provided when optional approval is specified Once a device labeled with multiple approval types is installed it should not be reinstalled using any other approval types Permanently mark the approval label to distinguish it from unused approval types K5 E5 and I5 combination KB K5 and C6 combination KD K5 C6 I1 and E8 combination K6 C6 11 and E8 combination K8 E8 and 11 combination K7 ET I7 and N7 combination 14 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 FIELDBUS PROTOCOL Hazardous Locations Certifications North American Certifications IA FM Approvals E5 Explosion Proof for Class Division 1 Groups B C and D Dust Ignition Proof for Class II Division 1 Groups E F and G Dust Ignition Proof for Class III Division 1 Intrinsically Safe for use in Class I Division 1 Groups A B C and D Class II Division 1 Groups E F and G Class lll Division 1 when connected per Rosemount drawing 03031 1019 Non incendive for Class Division 2 Groups A B C and D Temperature Code T4 Ta 60 C T3 Ta 85 C Enclosure Type 4X For input parameters see control drawing 03031 1019 Canadian Standards Association CSA E6 C6 Explosion Proof for Class Division 1 Groups B C and D N1 Dust Ignition Proof for Class II and Class III Division 1 Groups E F and G Suitable for Class Division 2 Group
53. ntWeb Functionality The 3051 powers the PlantWeb A architecture by delivering the best JUI sensor and transmitter best installation jaa practices and best in class field Y intelligence One component is the enhanced diagnostic capabilities in FOUNDATION fieldbus that provide an increase in process visibility enabling proactive maintenance improving process availability and plant productivity Rosemount Pressure Solutions Rosemount 3051S Series of Instrumentation Scalable pressure flow and level measurement solutions improve installation and maintenance practices Rosemount 3095MV Mass Flow Transmitter Accurately measures differential pressure static pressure and process temperature to dynamically calculate fully compensated mass flow Rosemount 305 and 306 Integral Manifolds Factory assembled calibrated and seal tested manifolds reduce on site installation costs Rosemount 1199 Diaphragm Seals Provides reliable remote measurements of process pressure and protects the transmitter from hot corrosive or viscous fluids Orifice Plate Primary Element Systems Rosemount 1495 and 1595 Orifice Plates 1496 Flange Unions and 1497 Meter Sections A comprehensive offering of orifice plates flange unions and meter sections that is easy to specify and order The 1595 Conditioning Orifice provides superior performance in tight fit applications 2 Annubar Flowmeter Series Rosemount 3051SFA 3095MFA and 485 The stat
54. ntrinsic Safety Approval 14 ATEX Intrinsic Safety and Dust Certification N19 ATEX Type N and Dust Certification E8 ATEX Flame proof and Dust Certification E40 TIIS Flame proof Certification C6 CSA Explosion proof and Intrinsic Safety Approval p Ke 9 CSA and ATEX Explosion proof and Intrinsic Safety Approval combination of C6 and K8 KB FM and CSA Explosion proof and Intrinsic Safety Approvals combination of K5 and C6 K7 SAA Flame proof and Intrinsic Safety Approvals combination of I7 N7 and E7 KB ATEX Flame proof and Intrinsic Safety Approvals combination of 11 and E8 KD CSA FM and ATEX Explosion proof and Intrinsic Safety Approval combination of K5 C6 11 and E8 I7 SAA Intrinsic Safety Certification E7 SAA Flame proof Certification N7 SAA Type N Certification IA ATEX Intrinsic Safety for FISCO for FOUNDATION fieldbus protocol only IE FM FISCO Intrinsic Safety for FOUNDATION fieldbus protocol only Code Bolt for Flange and Adapter Options HD HG L4 Austenitic 316 SST Bolts G Code Display Options HD HG M5 LCD display for Aluminum Housing Available with Housing codes A B C and D only E D M6 LCD display for SST Housing Available with Housing codes J K L and M only Code Other Options HD HG Q4 Calibration Data Sheet Q8 Material traceability certification per EN 10204 3 1 B QP Calibration certification and tamper evident seal
55. quires Materials of Construction Code 0 S5 Assemble to Rosemount 305 Integral Manifold specified separately see the Rosemount 305 and 306 Integral Manifolds PDS document number 00813 0100 4733 S69 Assemble to Rosemount 304 Manifold or connection system Code Integral Mount Primary Elements Optional cD fete 07 S4 F m actory Assembly to Rosemount Primary Element Orifice With the primary element installed the maximum operating pressure will equal the lesser of either the transmitter or the primary element Option is available for factory assembly to range 1 4 transmitters only 3 Factory Assembly to Rosemount 405 Primary Element M Rosemount Annubar or Rosemount 1195 Integral Diaphragm Seal Assemblies Optional NOTE Standard flange and adapter bolts are austenitic 316 SST 1 One Diaphragm Seal Direct Mount or Capillary Connection Type S20 Two Diaphragm Seals Direct Mount or Capillary Connection Type Optional All Welded Diaphragm Seal Systems for high vacuum applications NOTE Standard flange and adapter bolts are austenitic 316 SST S7 One Diaphragm Seal All Welded System Capillary Connection Type S80 Two Diaphragm Seals All Welded System Capillary Connection Type so One Diaphragm Seal All Welded System Direct Mount Connection Type S99 Two Diaphragm Seals All Welded System One Direct Mount and One Capillary Connection Type
56. r the sensor module housing and low volume Coplanar flange and adapter 3051C with Option Code S1 Q16 Surface finish certification for sanitary remote seals QZ Remote Seal System Performance Calculation Report d QP Calibration certification and tamper evident seal s 7 QS Certificate of FMEDA Data s J18 Local Zero Adjustment Only 3 J308 No Local Zero or Span Adjustment Y Y E T1 Transient Protection Terminal Block g c1 Custom Software Configuration Completed CDS 00806 0100 4001 required with order C2U 0 8 3 2 V dc Output with Digital Signal Based on HART Protocol Output Code M only C3 Gage Calibration 3051CA4 only C4UX9 Analog Output Levels Compliant with NAMUR Recommendation NE 43 CN Analog Output Levels Compliant with NAMUR Recommendation NE 43 Alarm Configuration Low P1 Hydrostatic Testing with Certificate P2 Cleaning for Special Service P3 Cleaning for 1 PPM Chlorine Fluorine P4 Calibrate at line pressure Specify Q48 on order for corresponding certificate E E DF 1 2 14 NPT flange adapter s Material determined by flange material 7 D7 Coplanar Flange Without Drain Vent Ports D8 Ceramic Ball Drain Vents D9 JIS Process Connection RC 74 Flange with RC 72 Flange Adapter P8 0 0496 accuracy to 5 1 turndown Range 2 4 P9 4500 psig Static Pressure Limit 3051CD Ranges 2 5 only V5 9 External Ground Screw Assembly
57. racters maximum Tag may be permanently stamped on transmitter nameplate upon request 56 characters maximum Tag may be stored in transmitter memory 30 characters maximum Software tag is left blank unless specified Commissioning tag fieldbus only A temporary commissioning tag is attached to all transmitters The tag indicates the device ID and allows an area for writing the location Optional Rosemount 304 305 or 306 Integral Manifolds Factory assembled to 3051C and 3051T transmitters Refer to the following Product Data Sheet document number 00813 0100 4839 for Rosemount 304 and 00813 0100 4733 for Rosemount 305 and 306 for additional information 1 Not applicable to fieldbus Optional Diaphragm and Sanitary Seals Refer to Product Data Sheet 00813 0100 4016 or 00813 0201 4016 for additional information Output Information Output range points must be the same unit of measure Available units of measure include inH20 inH20 4 c psi Pa inHg ftH20 bar kPa mmH20 mmH20 4 c mbar torr mmHg g cm2 kg cm2 atm 1 Not available on low power or previous versions LCD display M5 Digital Display 5 Digit 2 Line LCD Direct reading of digital data for higher accuracy Displays user defined flow level volume or pressure units Displays diagnostic messages for local troubleshooting 90 degree rotation capability for easy viewing M6 Digital Display with 316 Stainless Steel Cover e For use with sta
58. s A B C and D for indoor and outdoor hazardous locations Enclosure type 4X factory sealed Explosion Proof and intrinsically safe approval Intrinsically safe for Class I Division 1 Groups A B C and D when connected in accordance with Rosemount drawings 03031 1024 Temperature Code T3C Explosion Proof for Class Division 1 Groups B C and D Dust Ignition Proof for Class II and Class III Division 1 Groups E F and G Suitable for Class Division 2 Groups E8 A B C and D hazardous locations Enclosure type 4X factory sealed For input parameters see control drawing 03031 1024 European Certifications n ATEX Intrinsic Safety and Dust Certification No BAS 98ATEX1355X 9 Il 1 GD EEx ia IIC T4 Tamb 60 to 60 C Dust Rating T70 C Tamb 20 to 40 C IP66 ce 1180 TABLE 7 Input Parameters U 30V 300 mA Pj213W C 20 uF Special Conditions for Safe Use X The device is not capable of withstanding the 500V insulation test required by Clause 6 4 12 of EN50020 1994 This must be taken into account when installing the apparatus ATEX FISCO Intrinsic Safety Certification No BAS 98ATEX1355X II 1 G EEx ia IIC T4 Tamb 60 to 60 C IP66 ce 1180 TABLE 8 Input Parameters U 17 5 V lj 380 mA Pj 5 32 W C lt 5 uF Lj x 10 pH Special Conditions for Safe Use X The device is not capable of withstanding the 500V insulation test required by Clause
59. sing a HART communicator 5 adjustment is allowed on the sensor limit to allow for unit conversions 39 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 3051T Gage and Absolute Pressure Transmitter Range Limits Range 1 Span Range 2 Span Range 3 Span Range 4 Span Range 5 Span min max min max min max min max min max inH O 8 30397 831 889 41 5198 4159 45 221 439 22143 9 1107 2 110720 55360 276799 inHg 0 61081 61 0807 3 05403 305 403 16 2882 1628 82 81 441 8144 098 4072 04 20360 2 ftH2O 0 69199 69 3241 3 45998 345 998 18 4533 1845 33 92 2663 9226 63 4613 31 23066 6 mmH20 211 10 21130 1054 60 105460 3 5634 66 563466 28146 1 2814613 1407301 7036507 mmHg 15 5145 1551 45 77 5723 7757 23 413 72 41372 2068 6 206860 0 103430 517151 psi 0 3 30 1 5 150 8 800 40 4000 2000 10000 bar 0 02068 3 06843 0 10342 10 3421 0 55158 55 1581 2 75791 275 7905 137 895 689 476 mbar 20 6843 2068 43 103 421 10342 11 551 581 55158 1 2757 91 275790 5 137895 689476 g cm 21 0921 2109 21 105 461 10546 1 561 459 56145 9 2807 31 280730 6 140614 703067 kg cm 0 02109 2 10921 0 10546 10 5461 0 56246 56 2456 2 81228 281 228 140 614 701 82 Pa 2068 43 206843 10342 1 1034212 55158 1 5515811 275791 27579054 13789500 68947600 kPa 2 06843 206 843 10 3421 1034 21 55 1581 5515 81 275 791 27579 05 13789 5 68947 6 torr 15 5145 1551 45 77 5726 7757 26 413 721 413721 2068 6 206859 7 103430 517151 atm 0 02041 2 04138 0 10207 10 2069 0 54437 54 4368 2 72184 272 1
60. tainless steel bolts Rosemount 3051H Bracket Options B5 Bracket for 2 in Pipe or Panel Mounting e For use with the 3051H Pressure Transmitter for high process temperatures Carbon steel construction with carbon steel bolts B6 B5 Bracket with SST Bolts Same bracket as the B5 option with Series 300 stainless steel bolts Traditional Flange Bracket Options B1 Bracket for 2 in Pipe Mounting e For use with the traditional flange option Bracket for mounting on 2 in pipe Carbon steel construction with carbon steel bolts Coated with polyurethane paint B2 Bracket for Panel Mounting e For use with the traditional flange option Bracket for mounting transmitter on wall or panel Carbon steel construction with carbon steel bolts Coated with polyurethane paint B3 Flat Bracket for 2 in Pipe Mounting e For use with the traditional flange option Bracket for vertical mounting of transmitter on 2 in pipe Carbon steel construction with carbon steel bolts Coated with polyurethane paint B7 B1 Bracket with SST Bolts Same bracket as the B1 option with Series 300 stainless steel bolts B8 B2 Bracket with SST Bolts Same bracket as the B2 option with Series 300 stainless steel bolts B9 B3 Bracket with SST Bolts Same bracket as the B3 option with Series 300 stainless steel bolts BA Stainless Steel B1 Bracket with SST Bolts B1 bracket in stainless steel with Series 300 stainless steel bolts B
61. tocol Power Supply External power supply required Standard transmitter 4 20 mA operates on 10 5 to 55 V dc with no load Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply as described by Max Loop Resistance 43 5 Power Supply Voltage 10 5 1935 1500 1000 Operating Region 500 Load Ohms 20 30 40 42 4 Voltage V dc Communication requires a minimum loop resistance of 250 ohms 55 1 For CSA approval power supply must not exceed 42 4 V FOUNDATION fieldbus output code F and Profibus output code W Power Supply External power supply required transmitters operate on 9 0 to 32 0 V dc transmitter terminal voltage Current Draw 17 5 mA for all configurations including LCD display option FOUNDATION fieldbus Function Block Execution Times Block Execution Time Resource Transducer LCD Block Analog Input 1 2 30 milliseconds PID 45 milliseconds Input Selector 30 milliseconds Arithmetic 35 milliseconds Signal Characterizer 40 milliseconds Integrator 35 milliseconds Standard Function Blocks Resource Block Contains hardware electronics and diagnostic information Transducer Block Contains actual sensor measurement data including the sensor diagnostics and the ability to trim the pressure sensor or recall factory defaults LCD Block Configures the local display 2 Analog Input
62. tom Software Configuration Completed CDS 00806 0100 4001 required with order 0 8 3 2 V dc Output with Digital Signal Based on HART Protocol Available with Output code M only Analog Output Levels Compliant with NAMUR Recommendation NE 43 Analog Output Levels Compliant with NAMUR Recommendation NE 43 Alarm Configuration Low Ceramic Ball Drain Vents External Ground Screw Assembly Lower Housing Flushing Connections Options Ring Material Number Size 2in 3in 4 in SST 1 1 4 SST Hastelloy C276 Hastelloy C276 SST SST Hastelloy C276 Hastelloy C276 l2 m NS S Typical Model Number 3051L 2 A AO D 21 A A F1 1 Assemble to items are specified separately and require a completed model number 2 Not available with low power Option Code M 3 Not available with fieldbus output code F or profibus protocols output code W 4 Local zero and span adjustments are standard unless Option Code J1 or J3 is specified 5 NAMUR Compliant operation is pre set at the factory and cannot be changed to standard operation in the field 6 The V5 option is not needed with the T1 option external ground screw assembly is included with the T1 option 7 Not available with Option Codes AO BO and GO Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 TABLE 14 3051H Pressure Transmitter for High Temperature Processes Not Applicable Applicable Model Tr
63. uit Entry Size e 9 e C fey A Polyurethane covered Aluminum 72 14 NPT B Polyurethane covered Aluminum M20 x 1 5 CM20 C Polyurethane covered Aluminum PG 13 5 D Polyurethane covered Aluminum G J SST 12 14 NPT K SST M20 x 1 5 CM20 L SST PG 13 5 M SST G c Code PlantWeb Functionality Optional cD CG CA A01 Advanced Control Function Block Suite D01 FOUNDATION fieldbus Diagnostics Suite Code Alternate Flange Options Requires Materials of Construction Code 0 cD fete CA H2 Traditional Flange 316 SST SST Drain Vent H3 Traditional Flange Alloy C Hastelloy C276 Drain Vent H4 Traditional Flange Monel Monel Drain Vent H7 Traditional Flange 316 SST Hastelloy C276 Drain Vent HJ DIN Compliant Traditional Flange SST 1He in Adapter Manifold Bolting HK DIN Compliant Traditional Flange SST 10 mm Adapter Manifold Bolting HL DIN Compliant Traditional Flange SST 12mm Adapter Manifold Bolting Not available on 3051CD0 FA Level Flange SST 2 in ANSI Class 150 Vertical Mount FB Level Flange SST 2 in ANSI Class 300 Vertical Mount FC Level Flange SST 3 in ANSI Class 150 Vertical Mount FD Level Flange SST 3 in ANSI Class 300 Vertical Mount FP DIN Level Flange SST DN 50 PN 40 Vertical Mount FQ DIN Level Flange SST DN 80 PN 40 Vertical Mount Code Integral Mount Manifold Options Re
64. ut Code M only C47 Analog Output Levels Compliant with NAMUR Recommendation NE 43 27 June 1996 CN 7 Analog Output Levels Compliant with NAMUR Recommendation NE 43 Low Alarm Configuration P1 Hydrostatic Testing with Certificate P2 Cleaning for Special Service P3 Cleaning for 1 PPM Chlorine Fluorine P8 0 0496 accuracy to 5 1 turndown Range 1 4 V5 9 External Ground Screw Assembly Typical Model Number 3051T G 5 F 2A 2 1 A B4 1 3051TG lower range limit varies with atmospheric pressure 2 Materials of Construction comply with recommendations per NACE MR0175 ISO 15156 for sour oil field production environments Environmental limits apply to certain materials Consult latest standard for details Selected materials also conform to NACE MRO0103 for sour refining environments 3 Assemble to items are specified separately and require a completed model number 4 Not available with low power Option Code M 5 Not available with fieldbus output code F or Profibus protocols output code W 6 Local zero and span adjustments are standard unless Option Code J1 or J3 is specified 7 NAMUR Compliant operation is pre set at the factory and cannot be changed to standard operation in the field 8 The V5 option is not needed with T1 option external ground screw assembly is included with the T1 option 30 Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 TABLE 13 3051L Flange Mounted Liquid L
65. wer Minimum Upper Lower Lower Span URL 1 15 Span URL 8318 BB ECCET T 1 0 3 psia 30 psia 0 psia 1 0 3 psi 30 psi 0 psia 14 7 psig 20 6 mbar 2 07 bar 0 bar 20 6 mbar 2 07 bar 0 bar 1 01 bar 2 1 5 psia 150 psia 0 psia 2 1 5 psi 150 psi 0 psia 14 7 psig 0 103 bar 10 3 bar 0 bar 0 103 bar 10 3 bar 0 bar 1 01 bar 3 8 psia 800 psia 0 psia 3 8 psi 800 psi 0 psia 14 7 psig 0 55 bar 55 2 bar 0 bar 0 55 bar 55 2 bar 0 bar 1 01 bar 4 40 psia 4000 psia 0 psia 4 40 psi 4000 psi 0 psia 14 7 psig 2 76 bar 275 8 bar 0 bar 2 76 bar 275 8 bar 0 bar 1 01 bar 5 2000 psi 10000 psi 0 psia 14 7 psig 137 9 bar 689 4 bar 0 bar 1 01 bar 1 Assumes atmospheric pressure of 14 7 psig Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 Zero and Span Adjustment Requirements FOUNDATION fieldbus Parameters HART and Low Power Schedule Entries 7 max Zero and span values can be set anywhere within the range limits Links 20 max stated in Table 1 and Table 2 Virtual Communications Relationships VCR 12 max Span must be greater than or equal to the minimum span stated in Table 1 and Table 2 Service Liquid gas and vapor applications 4 20 mA Output Code A Output Two wire 4 20 mA user selectable for linear or square root output Digital process variable superimposed on 4 20 mA signal available to any host that conforms to the HART pro
66. xamined and tested to determine that the design meets basic electrical mechanical and fire protection requirements by FM a nationally recognized testing laboratory NRTL as accredited by the Federal Occupational Safety and Health Administration OSHA 12 HART PROTOCOL Hazardous Locations Certifications North American Certifications FM Approvals E5 Explosion Proof for Class Division 1 Groups B C and D Dust Ignition Proof for Class II Division 1 Groups E F and G Dust Ignition Proof for Class III Division 1 Factory Sealed Enclosure Type 4X 15 Intrinsically Safe for use in Class I Division 1 Groups A B C and D Class II Division 1 Groups E F and G Class III Division 1 when connected per Rosemount drawing 03031 1019 Non incendive for Class Division 2 Groups A B C and D Temperature Code T4 Ta 40 C T3 Ta 85 C Enclosure Type 4X For input parameters see control drawing 03031 1019 Canadian Standards Association CSA E6 Explosion Proof for Class Division 1 Groups B C and D Dust Ignition Proof for Class II and Class III Division 1 Groups E F and G Suitable for Class Division 2 Groups A B C and D for indoor and outdoor hazardous locations Enclosure type 4X factory sealed C6 Explosion Proof and intrinsically safe approval Intrinsically safe for Class I Division 1 Groups A B C and D when connected in accordance with Rosemount drawings 03031 1024 Temperature
67. xplosion proof and Intrinsic Safety Approval K6 CSA and ATEX Explosion proof and Intrinsic Safety Approval combination of C6 and K8 gt KB FM and CSA Explosion proof and Intrinsic Safety Approvals combination of K5 and C6 K7 SAA Flame proof and Intrinsic Safety Approvals combination of I7 N7 and E7 t K8 ATEX Flame proof and Intrinsic Safety Approvals combination of 11 and E8 9 KD FM CSA and ATEX Explosion proof and Intrinsically Safe combination of K5 C6 11 and E8 E g I I7 SAA Intrinsic Safety Certification y E7 SAA Flame proof Certification s N7 SAA Type N Certification y IA ATEX Intrinsic Safety for FISCO for FOUNDATION fieldbus protocol only t Code Bolting Options 04B fore 07 L4 Austenitic 316 SST Bolts L5 ASTM A 193 Grade B7M Bolts L6 Monel Bolts Code Display Options cD fete 07 M5 LCD display for Aluminum Housing Housing Codes A B C and D only M6 LCD display for SST Housing Housing Codes J K L and M only 27 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2008 TABLE 11 3051C Differential Gage and Absolute Pressure Transmitters Not Applicable Applicable Code Other Options cD fore 07 Q4 Calibration Data Sheet Q8 Material Traceability Certification per EN 10204 3 1 B Only available for the sensor module housing and d l Coplanar or traditional flanges and adapters 3051C and fo
68. z EI 5 z n H o s lu 3 3 83 4 6 0 152 Dimensions are in inches millimeters Product Data Sheet 00813 0100 4001 Rev HA March 2008 Rosemount 3051 Traditional Flange Mounting Configurations with Optional Brackets for 2 in Pipe or Panel Mounting Traditional Flange Panel Mounting Bracket option B2 B8 Traditional Flange 2 in Pipe Mounting Bracket option B1 B7 BA e 10 1 257 4 2 106 27 va Impulse Piping 67 j 1 1 28 2 95 5 6 x 7 8 Bolts for Panel Mounting Not Supplied 9 6 243 i 67 i i v N PANEL MOUNTING BRACKET 1 4 33 4 6 116 112 14 NPT Conduit Connection Two Places Other Sizes Connections Set Screw 0 75 20 Available Clearance for Cover Removal mo Housing Terminal Transmitter J Rotation Circuitry 7 9 202 1 2 14 NPT on 114 18 NPT on i as Traditional Flange for ange 1 7 43 Adapters Pressure Connection Without the Use of Flange Adapters Connection Per IEC 61518 2 126 54 0 12 in Connection Centers Adaptors Can Be Rotated to Give 14 M Connection 28 Centers of 2 00 51 2 126 54 or 2 25 57 Dimensions are in inches millimeters 19 Product Data Sheet 00813 0100 4001 Rev HA Rosemount 3051 March 2
Download Pdf Manuals
Related Search
Related Contents
WX330J E クイックマニュアル - JRC日本無線 JRC PHSサポートサイト VX7 Reference Guide - L - ARC - Honeywell Scanning and Mobility guía del alumno - Comunidad de Madrid 三菱高性能省エネモータ スーパーラインプレミアムシリーズ 7部屋まで、ブロードバンドにつながる。低コストでつながる。 約3万円で téléchargez le manuel d`utilisation Pile Poil PresTop GT Kiosk Slim Universal White Cantus 238 - G. Kisselbach AARIA ONE - Scheda tecnica New iStar ICCD - Andor Technology Copyright © All rights reserved.