Home
        2046916 R1 - Flatpack2 User Manual (300A-1200A)
         Contents
1.       W ELTEK VALERE    alwayson    Installat  on Guide    Flatpack2 Power Systems                  en Powe t Sys stem S    ee          Flatpack2 48V 24V 300A   1200A Systems    2046916 R1    Information in this document is subject to change without notice and does not  represent a commitment on the part of Eltek Valere     No part of this document may be reproduced or transmitted in any form or by any  means   electronic or mechanical  including photocopying and recording   for any  purpose without the explicit written permission of Eltek Valere     Copyright    2008 Eltek Valere  W ELTEK VALERE    alwayson       1303 E Arapaho Rd  Richardson  TX 75081  USA    Phone   1  469  330 9100  Fax   1  469  330 9101    Technical Support   1  866  240 6614    www eltekvalere com    2046916 R1  June 2008  Published 17 June 2008    2 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Table of Contents    1  Safety and ComplianCe     ax  rnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnennnnennnnnnnnnnennnnennnnnr 5  FCC COMDPIANCE SLOME ee e Eea en ees 5   2 AEP OGUGCUION ne AEE Ea 7  TE ME 7  About This Revision  2  u     eeeecceceseecceceeeeeceecesseneeecesenceeeeesnceeeesseneeeseseaneeesesnaceesesseneeeeerstacers 7   3  Standard SYSTEMS sere Dann aan een ER een 8  TN OR ee ee 8  Flatpack2  48V 600A and  24V 600A    eaneesnnsnensnnsnnannnnnnnnnnnennnnsnennensnnannnnnnnnnennnnnnnnnennnnn 8  EE EE EO 9   4  Mechanical Instala eee 10  SETE NE 0800 1 EEE 10  TESS a EE In rer Eee een Ene
2.      Figure 2   Flatpack2  48V 300A    Flatpack2  48V 600A and  24V 600A    The  48V and  24V systems output a maximum of 32kW at  48V and 16kW at   24V  There is a dedicated 19    alarm and control section with room for up to two  Smartpack controllers and alarm cards  These systems typically make use of the  same 23    wide  4U high distribution unit  This distribution features twenty four  plug in breaker positions  eight bulk battery landings  an emergency power off   EPO  circuit  and a service bypass switch     Mil mm    FLATPACK Power System       2 DIG Ss EDEN Figure 4   Flatpack2  24V 600A  Figure 3   Here  48V 600A    3 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Flatpack2  24V 1200A    This system outputs a maximum of 32kW  It is designed for a 23    rack  The 23      wide  6U high distribution unit features twenty four plug in breaker positions   eight bulk battery landings  room for up to two Smartpack controllers and alarm  cards  an emergency power off  EPO  circuit  and a service bypass switch     ed       w   VE    AA NO ANT I       Figure 5   Flatpack2  24V 1200A    Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 9    4  Mechanical Installation        A  A    USE OF FULLY INSULATED TOOLS IS REQUIRED WHEN WORKING WITH ANY POWERED AC OR DC  CIRCUITS         THE SYSTEM IS TO BE MOUNTED OVER A CONCRETE SURFACE ONLY AND INSTALLED IN  RESTRICTED ACCESS LOCATIONS  RAL   ACCESS MUST BE LIMITED BY USE OF TOOL  I E  LOCK  A
3.     2  Use rack screws to connect the system brackets to the desired positions  of the rack     Anchoring the Cabinet    If the system is delivered installed in a mounting rack  anchor the cabinet before  installing rectifiers and batteries  Refer to the accompanying system installation  guide for rack feet diagrams and floor loading concerns     Equipment Rack    Frame Ground       Connections are located at rear of the rectifier rack with chassis studs  provided in the AC input chamber  Refer to the NEC and any local codes  practices to determine the appropriate wire size  Use of paint penetrating  washers  abrasive compounds  or other means to achieve a reliable frame  ground is recommended     Converter Shelf Installation    If Flatpack DC DC converters are to be installed  refer to the manual  accompanying the converters for instructions on mounting and making system  connections     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 1 1    5  Electrical Installation  Flatpack2 rectifiers have an operating input voltage range of 85 to 300 VAC  rated    for 100   250 VAC   with a frequency range between 45 and 66 Hz  See the User   s  Guide   Flatpack2 Rectifier Modules  350002 013  for further details       The AC junction box of each rectifier shelf contains a  knockout hole for a standard trade size conduit with a  diameter of 0 75        To wire the AC input terminal block     CAUTION  VERIFY THAT ALL AC CIRCUIT BREAKERS FEEDING THE SYSTEM ARE IN THE O
4.    Secondary load breakers        LVLD       The 1200A system Is very similar  except that the top bus Is unused        Unused       Secondary load breakers       Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 1      18    Converter Bus Configuration    The top bus can be used to distribute converter output  Converters are Is  typically fed directly from the main bus on the same side of the LVBD  contactor as other loads  this arrangement makes converters act as load  to the native power of the DC system  Thus  the converter bus may  continue powering dependent devices during an AC supply failure     Converter           Converter Distribution    LVLD     gt  m Secondary load breakers  YA     Critical load breakers                t  DK       Rectifier Battery       Bus Configurations for Secondary Distributions    A second distribution unit can be added atop 23    distributions to double the  number of distribution positions from 24 to 48  The configuration of the  second distribution panel typically mirrors the primary panel   s configuration   unless indicated otherwise  Always verify the exact configuration prior to  landing any connections  The following examples illustrate standard  configurations and a common variation     Standard Secondary Bus Configuration    The standard bus configuration for the 600A system uses the bottom bus  for critical load termination points in both distribution panels  Each of the  individual bus bars are rated at 600A  ye
5.   4  Make a note for each position on the label provided on the distribution door     2 2 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Load  Return  Landings    Load  Output    Landings  Distribution    Device    Holders       Figure 14   Configurable Protected Load Connections    Plug in Breakers    Auxiliary contact circuit breakers are the standard over current protection  devices used in the distribution section  Breakers are connected to system  alarming through the holder so that an open breaker  whether tripped or  manually placed in the OFF position  triggers a    Load Distribution Alarm    in the  Smartpack controller  Breakers should be removed from any unused positions  to prevent nuisance alarms  Single pole circuit breakers rated up to 100A can  be installed  Straps are available to make use of two pole breakers rated up  to 175A and three pole breakers rated up to 250A     Plug in Fuse Holders    Plug in fuse modules may also be installed  The same considerations  regarding insertion and removal of breakers should be observed     A plug in fuse assembly consists of three main parts  A fuse  an alarm fuse  indicator  and a plug in module  If the main fuse element opens  the alarming  fuse also opens  giving a visible indication of a fault condition  a signal is then  sent via the Smartpack alarm board that activates the remote system  monitor  The alarming fuse must be replaced whenever a new main fuse IS  required  A fuse holder may be r
6.  In    dialog box Is displayed by selecting   Access  gt  Login    from the menu  pressing the  shortcut key F4  or using the  Log In    button on the  toolbar     Security    Please  enter the password to login             For further info on controller operation and  adjustment  refer to the User s Guide   Smartpack SS  Monitoring  amp  Ctrl Unit  Es    3 6 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    10  Startup Checklists    This section includes basic checklists to assist the user in verifying proper  installation and starting system operation     Pre Start Check Power is OFF     CHECK THE FOLLOWING POINTS  OK    1  Flatpack2 system installation is completed  The Flatpack2 Installation Check List is filled in   All cabling is securely terminated with correct polarity    2  All battery and load Breakers   fuses are disconnected oO    3  AC input cable s  and AC earth wire  Ground  are terminated    4  Site specific parameters and settings are known oO  5  AC supply and all Breakers   fuses are switched OFF oO    Start up  No Load  amp  Load Adjustments Power is ON   CARRY OUT FOLLOWING  OK    om JE   Ewes sem  EG      4  Verify all rectifier modules are working  Green power LEDs are ON Verify  m   OOOO 0    7  Verify DC output voltage  Measure and adjust as needed    8  Measure battery voltage  confirm level  and close disconnect if present Verify correct polarity     9  Verify System Setup is in accordance with desired configuration Enter site sp
7.  can be shut down to increase  available backup time  Each bus bar is rated at 600A for a total  distribution capacity of 2400A  The top bus of the primary  bottom   distribution panel is configured to accept battery input  the corresponding  bus in the secondary panel is unused  Load output for the secondary  distribution is configured identically to the main section     Secondary load breakers  Critical load breakers           Battery breakers    The 1200A system is similar to the 600A except for the top bus of the  primary distribution section  Batteries can only connect through the rear  bulk terminal points     Unused Bus    Secondary load breakers    Critical load breakers       Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Breaker and Fuse Installation    CAUTION  SIGNIFICANT EXTRACTION FORCE IS REQUIRED TO REMOVE DISTRIBUTION   AN DEVICES DUE TO THE CONTACT PRESSURE REQUIRED FOR HIGHLY RELIABLE  LOW   TEMPERATURE RISE CONNECTIONS    AN USE INSULATED TOOLS  ESPECIALLY WHEN WORKING ON LIVE SYSTEMS     NOTE  Do not use any type of clamps  pliers  or similar tools to remove over   current protection devices as the housing can be cracked by excessive force   Damaged devices represent an operational hazard and should never be used     Flatpack2 three bus distributions feature a moveable distribution device holder  that accepts a breaker or fuse holder with 5 10    plug in bullets  It is designed to  align the device to one of the three buses by screw
8.  to  loosen the bottom bullet receptacle of the holder  See Figure 11     4           Select the appropriate bus based on system configuration  Buses are  numbered 1 to 3 from top to bottom and are labeled by function on the    right and left walls  e g      Primary        Battery     etc    See the sections on bus  configurations beginning on page 16 for details          Hook the device holder into the position that lines up with the bus  selected in the above step  The holder   s hooks  Figure 11  correspond to  each bus  NOTE  Holders set to higher buses sit higher than those at  lower buses  See Figure 10 on page 15     6  Lower the holder into position against the bus     7  Screw the receptacle into the bus using an insulated 7 16    or 11 mm nut  driver  Torque between 20   25 in lbs     TEE a  EG   gt  elie ce  amp     4         ce KEREI RET HA  m sd EEE ae    tm A EE ss mb CC EI 0   2   040 M   name En eee G      ti ds   ma  A PA  lag 9         Figure 12   Distribution Device Holder Installation  To make load connections     1  Make connections with a maximum  1 AWG cable with two hole lugs having  1 4    diameter holes on 5 8    centers  1 4    20 fastening hardware is provided   Do not connect batteries until system turn up     2  Torque connections to 51 58 in Ibs     3  Land each return lug to the corresponding position on the return bus  directly  behind the load buses   Return landings are closer together than the output  landings and are offset to the right   
9. 6916 R1  June 2008 5    dass die Cirquite Breaker in der aus position sind  Benutzen Sie ein  Spannungsmesser um sicher zu sein das keine Netzspannung mehr vorhanden ist   Vergwissern Sie sich das alle Schalter an Ihrem Gereat und in der Vesorgung beim  Anschluss abgeschaltet sind  Unsachgemaesse Verdrahtung kann koerperliche  Verletzung und an der Ausstattung Schaeden verursachen  Vor Wartungsarbeiten  am Ger  t s  nd alle Netzkabel vom Stromnetz zu trennen  um die Gefahr eines  elektrischen Schlages oder andere m  gliche Gefahren zu reduzieren     6 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    2  Introduction    The Flatpack2 power system consists of 19    rectifier shelves  one or more  Smartpack controllers  and a distribution section  It can be mounted in a standard  19    or 23    telecommunications equipment rack  Systems are available in 48VDC and  24VDC versions  with maximum outputs of 8kW to 32kW     Distribution Section                        Controller  Expansion  Slot       J 1   ON INNS NSNSNS NNN NNN Smartpack  f   p      f f N    V     aT     4 f    f i El    g i      Controller    ae i pY r Sg i  T PT FP Ae RF       la Dp De I A ahaha I  fi       EEE ii F  f f A             f   f        4 4     4 f 4 4             r       A    y   A       r  4    4  ree WU UYVU WU WU a a g kr Ar bred    Alarm Connections       Flatpack2  Power  Shelves    hide ln         ae          Figure 1   Flatpack2  24V 600A System  About This Guide    This manu
10. AU  distribution does not contain alarm boards  rather  a 1U alarm and controller  section installed between the distribution and power shelves houses up to two  front access boards  depending on the number of Smartpack controllers used    just to the left of the controller slots  The 23    6U distribution contains front   access boards just to the left of the integrated controller slots     The alarm interface board provides an equal number of configurable input alarms  and form C output relays  The Smartpack Extended version has six input alarms  and six output relays  the Smartpack Web has two inputs and outputs       2  ACMainAlarm    High Voltage Alarm  Low Voltage Alarm  6   Rectifier Fail Alarm    Closure to Alarm          put 2B    e    Common    Open to Alarm          MOI Conf in       To install an alarm wire to the board   1  Strip the alarm wire end 3 8        2  Press the white terminal clamp  above the desired wire location     3  Insert the alarm wire  and release  the terminal clamp        Alarm terminals are designed to accept a wire range of  26 AWG solid or stranded  to  18 AWG  The Form C contacts provided in the system have a rating of 1A at 60  VDC  Please refer to the User s Guide   Smartpack Monitoring  amp  Ctrl Unit for further  details of alarm relay designations and assignment procedures     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 2 9    Configurable Inputs    The configurable alarm inputs of  the Smartpack alarm board ca
11. Device _ Open the handles before inserting modules into shelves    Flatpack2 rectifiers incorporate an AC mains fuse In each line   Double Pole   Neutral Fusing       M    Both the Smartpack controller and the Flatpack2 rectifier utilize the same locking  mechanism to keep the module fixed in place when installed into a system shelf   Typically  the Smartpack controller is delivered installed in the system  If it is not  pre installed  make required connection to the back of the controller before  installing  see Section 8      To install modules     1  Release the handles by inserting a small flat blade screwdriver into the  release slots and pressing the tip upward  extend each handle     2  Slide the module firmly into the shelf   3  Latch the handles to lock the rectifier in place     Handle  Release       To remove modules     1  Release the handles by inserting a small flat blade screwdriver into the  release slots and pressing up     2  Use the handles to pull the module out just far enough to where the body  can be held     3  Slide the module out the rest of the way  Do not carry it by the handles   Flatpack2 rectifiers weigh just over 4 lbs  1 9 kg  each     1 4 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    7  Distribution    Flatpack2 system distributions range in size from 19    to 23    in width and AU to 6U in  height  Although each distribution design is intended for a specific system  configuration  distributions have inherent flexibili
12. FF  POSITION  KEEP ALL AC BREAKERS OFF UNTIL ALL APPROPRIATE SYSTEM CONNECTIONS  HAVE BEEN MADE AND VERIFIED  REFER TO SECTION 9 FOR STARTUP CHECKLISTS             WARNING  FoR SAFETY REASONS  HIGH LEAKAGE CURRENT AND HIGH TOUCH CURRENT   ALWAYS CONNECT THE AC EARTH WIRE  PE  TO THE TERMINALS BEFORE CONNECTING AC  INPUT CABLE S            1  Remove the cover located at the  rear of each rectifier shelf using a  Phillips screwdriver  two screws         2  Unscrew and remove the green AC  connector using either a Phillips or  flat blade screwdriver     3  Use a small flat blade screwdriver to er  open each terminal and install AC Mana  wiring  See the sections    Individual Ru  Feed    on page 13 and    Dual Feed    on Al lin   page 13 for wiring details           p  S   iaia       4  Pull a green safety wire in the AC  mains conduit and terminate it to Figure 6   AC Input Cover  the ground terminal of the  connector  It should be longer in length than the black and white AC wires     5  Double check that each connection is secure and replace the connector     6  If necessary  terminate additional safety wires to the  shelf ground termination stud located to the right of  the connector  see Figure 8 and Figure 9      7  Replace the cover after AC terminations are  complete  Make sure to line up the bottom plate    between the guides on the bottom of the shelf        Figure 7   AC Terminal  Block    1 2 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Indivi
13. ND KEY     The following tools are required for the installation     O    O    O    Standard wrench and or socket set  1 4    to 1       Torque wrench  10 40 Ft lb range    Torque screwdriver  5 10 in lb range    Small flat blade screwdriver  3 32    wide    Standard blade screwdriver and Phillips tip screwdriver   Wire cutters   strippers   Fork lift truck or similar heavy equipment handling transport   Hoist with lifting straps   Electric drill and appropriate bits  a hammer drill may be required for concrete  flooring     System Unpacking    An individual Flatpack2 unit is typically pre installed in a cabinet or rack  wrapped    with a shroud of high strength plastic  and bolted to a wooden pallet with four  anchors  Rectifier modules and expansion options are packed in separate  cartons  Exercise care when unpacking and setting the equipment in place     Rack Mounting    Flatpack2 systems can be installed in a rack or an enclosure  The mounting  brackets are pre installed at the factory and designed to be mounted within a  standard EIA 19    or 23    rack  depending on the width of the distribution box   Systems are designed to be mid mounted  Other mounting configurations may  require additional support brackets     Rack Installation    1  Use proper lifting equipment to position the Flatpack2 system so that the  holes in the support bracket are aligned with the correct mounting holes in  the rack     1 O Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008
14. Rete 10  ROCK AS eel Vee IO ee ee en Re 10  PMWM MN INS ANN EE een 11  Equipment Rack    Frame Ground    nee 11  Converter Shelf He alla One 11   5  Electrical INS AWE Ol ncesannsewesanccsesmacevauseneeserseowsccscuazacansnasenaneeasccene  12  fy  6 175100 19 Fee ee ee 13  DUIE T  EEE ee 13   6  Module Installation          asernnnnnnnonnnnnnnnnnnnnennnnennnnnnnnennnnennnnnnnnennnnennnne 14  PET DUNN xe ae ae meer een 15  ACEBO DIE FH DEE OM  Se ee 15  BES eo ee ee 15   Bus Configurations for Single Distributions          uucuusursunnennennnnnnennennennennennonennennennnnnnn 16   Bus Configurations for Secondary Distributions       uneesessnsenesnesnesensennennennennennenennennn 18  Breaker and Fuse se ON een 21  PUB IN BES OS ee 23   PIUS USE OL CTS nennen 23   Device Installation and Extraction       sornennonnrennrnnvennvennvennvennvrnnennvennvennrsnnennvennvenvennnennnenne 24   BUK DIS NN 24  Bulk Battery CONNEL LION et ea ee ee 24  Fh ALOE SL IM VG OE een een 27   Other Features and ODUONS een ei een 27  DISTNOULON COVER re ea 27  Emergency Power Off  EPO  and Service Bypass Switch    rrnnrnnrnnvnnvnnvnnvrnvrnververnennenn 28   LYD ODON JE er 28    Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 3    8  Alarm and Control Terminations       aravannnvavavannnnnvannvnnnnnavavnvnnnnvaneve 29    AE da CORE IC ee ee 29   CF ONEIgUrODIEINPURS zei inter neers meant ete 30  Temperature Probe Terminations             ccscsscsssssessscsessessessesseessesseeseesee
15. al provides a comprehensive overview of and installation guidelines for  Flatpack2 power systems with 300A to 1200A DC output  Additional information  regarding system components is found in the following documents     o 350002 013  User s Guide   Flatpack2 Rectifiers  o 350003 013  User   s Guide   Smartpack Monitoring  amp  Control Unit    Information for the Flatpack2  48V 150A system and distribution configurations  is contained in the following document     o 2029242  Installation Guide   Flatpack2 150A DC System  About This Revision  2     A new document format was adopted for this revision to reflect the transition to  the Eltek Valere brand  In addition  information from individual Flatpack2 system  manuals was incorporated into this manual     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008      3  Standard Systems    Standard Flatpack2 systems are defined by voltage and output current  Asa  general guideline  each larger system outputs about two times the current of the  preceding system  The smallest system   Flatpack2  48V 150A   is discussed in  detail in another manual   2029242  because of Its unique and highly configurable  1U distribution section     Flatpack2  48V 300A    This system outputs a maximum of 14kW  It is designed for a 19    rack  There is  room for a single Smartpack controller and up to seven Flatpack2 rectifiers  The  typical 19    distribution unit features twenty plug in breaker positions and four  bulk battery landings   
16. cts    Smartpack with Controller Blank            SmMARTPACK         Because the 600A and 1200A Flatpack2 systems can accommodate up to two Smartpack  controllers  a blank faceplate may be installed if the expansion slot is not populated     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 3 3    Local Keypad Access    The Smartpack controller is typically pre configured at the factory according to  customer requirements  If operational adjustments are required refer to the  PowerSuite Help menu or Smartpack manual for further details  The Smartpack  digital controller is located in the distribution section and provides system    control and monitoring functions  Features include    e Local user interface via a three button keypad on the front panel   e 2line x 16 character  high contrast backlit LCD display   e Digital Communication over CAN bus with  each Flatpack2 rectifier   e Storage of setup parameters  alarm  configuration and system history in non   volatile memory   e Realtime clock with battery backup   e Advanced battery monitoring and protection    SMARTPACK       Display Modes  Status Mode  displays the system   s status  or Menu Mode   displays the menu structure      Operation  Press the  4   key to change from Status Mode to Menu Mode  Press  thel I  orl I   keys to scroll up or down and navigate to find menu options   Function or parameter   Press the key to select functions             Graphical Display Alarm  16 character x 2 lines LCD dis
17. dual Feed    An individual feed shelf is fed by four  4  AC feeds  each feed supplies one  rectifier  Systems operating at 48VDC and should have 15A breakers on each AC    feed  24VDC systems should have 20A breakers on      each AC fat a AWG wire Is recommended  but Pin  Description  up to  10 AWG may be used for each feed  termination position  The figure below illustrates 2  LineZ Rectifier1    the 9 pin AC input connector  Termination points  for Line 1  Line 2  and Ground are listed in the table   4   Line 2  Rectifier 2    at right       6  Line 2 Rectifier3      8  line2 Rectifiera      o feron         e    d     2  e ms   g       Figure 8   Individual Feed Connector  Cover Removed     Dual Feed    A dual feed shelf is fed by two  2  AC feeds  each feed supplies two rectifiers   Systems operating at 48VDC and should have 30A breakers on each AC feed  with  10 AWG wire  24VDC systems should have 40A breakers on each AC feed  with  8 AWG wire  The figure below illustrates the 5 pin AC input connector   Termination points for Line 1  Line 2  and Ground are listed in the table at right     in  Description      a Line 2  Rectifier 1  amp  2      2   Line 2  Rectifier 3  amp  4          Line 1  Rectifier 1  amp  2  Ft _ Line 1  Rectifier 3  amp  4  Figure 9   Dual Feed Connector  Cover Removed        Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 1 3    6  Module Installation    CAUTION   AN   Do not carry modules by the handles  even if they are warm    
18. ead only        To make changes to the settings   enter the Service Options menu  and enter the password     Default password  0003    When the front keys are not in  operation  the display Is in Status  Mode  The upper line continuously  displays the battery voltage  The  lower line scrolls the following  Information     o Battery Current  o Load Current  o Active alarms    o Other messages    35    Local Computer Access    PowerSuite software must be installed on the PC to be used before connecting  to the Smartpack controller  Do not connect USB prior to installation process  In  most cases  FrameNet  also provided  must be installed prior to Powersuite        Z Eikhaugen   Eltek PowerSuite  Access Tools Windows View Help             el     m configuration EventLog Alarm su mmary                  23                     240    En   Battery Voltage   57 52 vorne                                            Power System     amp  Refresh S Cancel AY Apply   Close          eneral   Security   Summary                 Company  Eltek       Site  Eikhaugen          Model  SmartPack Controler          Date time     Serial    123456789          Message 1     Module  3 has been changed                   Message 2    Battery test OK                                                             Vi  04 11 2005 16 19 5 VS          Interface with a PC requires a standard A B USB cable      To make changes to the settings enter the Service Options menu Default  password  lt 0003 gt     The  Log
19. ec  info in  PowerSuite       11  Verify the rectifiers output current  and load function    12  Verify System Alarm Setup is in accordance with desired configuration Configure alarm mapping in PowerSuite    13  Use PowerSuite to simulate Alarm Relay conditions Verify all alarm relays are working correctly       10  Connect all load Breakers   fuses  and verify no alarms are displayed  m     14  This completes the basic system start up and configuration    Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 3      W ELTEK VALERE    alwayson       www eltekvalere com    Headquarters   Eltek Valere Eltek Valere  1303 E  Arapaho Rd  Richardson  TX  75081  USA Gr  terudv  8  Pb 2340 Stramsg  3003 Drammen  Norway    Phone   1  469  330 9100 Fax   1  469  330 9101 Phone   47 32 20 32 00 Fax   47 32 20 32 10       
20. emoved and inserted into the plug in module  at any time  it is not necessary to remove the plug in module to replace the  fuse     0 305  Dia   Bullet Terminal    SF  Alarm pin 0 02  x 0 11  a       Biown Fuse  Indicator       Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 23    Device Installation and Extraction  To install plug in breakers or fuse holders in device holder   1  Remove fuses and turn breaker actuators OFF until system turn up     2  Orient the device correctly to the device holder  line is the bottom  receptacle  load is the top   securely insert device into the receptacles     A distribution device extraction tool is installed on the  distribution door  It is shaped like a handle and has two  Phillips head screws  This item is provided for convenience  and should not be necessary for all extractions     To remove plug in breakers or fuse holders     1  Align the extraction tool to the device to be  removed     2  Use a Phillips screwdriver to secure the  device     3  Firmly pull the device out from the holder   Avoid using excessive force or motion to    extract an over current protection device       Bulk Distributions    CAUTION  IT IS STRONGLY RECOMMENDED THAT EXTERNAL BREAKERS OR FUSES BE     INSTALLED BETWEEN BULK SYSTEM TERMINALS AND EQUIPMENT AND OR BATTERIES        A bulk distribution unit Is usually a 23    section that features large  front access  copper buses  Each polarity has two landings that accept up to 535MCM cable  wi
21. ilding a total distribution capacity  of 1200A  The critical buses are fed through the low voltage battery  disconnect contactor  The LVBD contactor disconnects the battery from  the system when it reaches a user defined setpoint during discharge  The  top bus of the bottom distribution section is configured to accept battery  input  the top bus of the secondary distribution panel is not used  Load  output for the secondary distribution panel is configured identically to the  primary distribution panel     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Critical load breakers             Battery breakers    Critical load breakers         Rectifier    The 1200A system uses both the bottom bus and middle bus of each  distribution section for critical load termination points  yielding a total  distribution capacity of 2400A  The top buses are unused  Batteries may  only connect to the rear bulk termination points     Critical load breakers   i Critical load breakers                       Battery       Rectifier       Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 1 9    Load shedding with Secondary Distribution    The load shedding bus configuration for the 600A system with secondary  distribution uses the bottom buses for critical loads that need the longest  available backup time  Both critical buses are fed through the LVBD  contactor  The middle busses are fed through an LVLD contactor and  used for peripheral or redundant loads that
22. ing the bottom bullet  receptacle directly into the desired bus  A single cable landing on top accepts up  to  1 AWG cable with a two hole 1 4    lug on 5 8    centers  The holder also  connects the distribution device to the system alarm circuit     a    Cable Landing  Top Bullet  Receptacle    Alarm Contact    Bottom Bullet  Receptacle            Hooks for Bus 3  Hooks for Bus 2  Hooks for Bus 1    Bus Screw tand    Figure 11   Distribution Device Holder    il    NOTE  The distribution device holders must be installed in the desired bus before  plugging over current protection devices Into the holders     NOTE  Breakers and other over current protection devices must be modified in  order to alarm correctly  If using breakers other than those provided by Eltek  Valere  contact technical support for more Information about the modifications  necessary for using the breaker fuse alarming of the three bus distribution     Distribution device holders are pre installed to Bus 3  the lowest bus  at the  factory  To properly access and reassign the distribution device holders refer to  Figure 11 and Figure 12 when following these instructions     1  Open the distribution cover using the two thumbscrews     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 2 1    2  Use a Phillips screwdriver to remove the two screws on the front that hold  the Lexan cover at the top of the distribution box     3  Toremove a device holder  use an insulated 7 16    or 11 mm nut driver
23. irectly at the battery post    s   Ron The best termination point may vary   depending on the type of battery     kLoekWasher Used  The probe itself is not polarity   Flat Washer Sensitive  so it can be installed at         SensingLug either a     or     battery post  The   voltageortemp  hardware configuration at left is   Power Cable Lugor fecommended  This allows the probe   _ Inter module Strap tO monitor the temperature   accurately without interfering with     Battery Post the current carrying terminations on  the battery              3 O Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    NOTE  IF USING EXTERNAL BATTERY CONNECTIONS BOARDS  SUCH AS THOSE PROVIDED WITH A  SYMMETRY MONITORING KIT  DO NOT CONNECT MORE THAN ONE TEMPERATURE PROBE TO EACH OF  THE BOARDS  CONNECT A SINGLE PROBE EITHER TO THE 15 PIN SERIAL PORT CON6 CON7 or TO  THE SENSE INPUTS TO TERMINALS 9 AND LO OF THE TERMINAL BLOCK     Symmetry Terminations    Symmetry capability is facilitated by a symmetry monitoring kit  A battery  connection board is mounted near the batteries using a bracket  The serial port  connector  DE15  connects the board to either CON3 or CON4 on the rear of the  Smartpack controller  Up to two battery boards may be installed for each  controller  In this case  temperature probes must connect to the battery  connection board  one per board   Battery symmetry harness connections will  vary depending on the desired configuration  Refer to the symmetry kit manua
24. l    251491 033  for more details and installation instructions     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 3 1    9     Controller Access    Controller Configurations    The Flatpack2 power system can be delivered in several configurations  The  following examples are basic configurations  The 300A power systems use a  single Smartpack controller  the 600A and 1200A systems permit the use of a  master slave configuration for up to two controllers           32       Smartpack Extended    SMARTPACK       Local user interface via a three button keypad on the front panel  2 line x 16 character  high contrast backlit LCD display   Digital communication with each Flatpack2 rectifier   Storage of setup parameters  alarm configuration and system history in non volatile memory  Real time clock with battery backup   Advanced battery monitoring and full symmetry for 2 battery strings   Recording of rectifier serial numbers and other information   Load shedding control   6 digital inputsfor site equipment alarms   6 user definedform C output contacts    Smartpack Extended with Slave    SMARTPACK       Local user interface via a three button keypad on the front panel   2 line x 16 character  high contrast backlit LCD display   Digital communication with each Flatpack2 rectifier   Storage of setup parameters  alarm configuration and system history in non volatile memory  Real time clock with battery backup   Advanced battery monitoring and fullsymmetry for 4 bat
25. n  be used to connect external site  alarms or input devices such as  door sensors  fire alarms  and  generator activation alarms   Each relay circuit can be set to     normally closed    or    normally open     This can be selected through either the  menu or the PowerSuite interface  Some inputs can be used by auxiliary system  components like external or tray mounted battery disconnects and DC DC  converter alarms  Use solid or stranded wire of size 28 16 AWG     Temperature Probe Terminations    put 2B          Re  O Relay 1 CTA  Relay 2 OTA   gt  Relay 2 COM  Relay 2 CTA  inpu  inpu  miConf inpu  ZIConf inpu    1     i   Mia  ele      aia  Qa  a  cc      Gi G  00  OO    ay 1 COM       OlConf input 2A      OlConf in          gt     The standard Smartpack controller is capable of temperature compensated  battery charging  symmetry monitoring  and advanced battery discharge  monitoring  Temperature probes can be connected directly to the controller or  integrated into symmetry monitoring cables     Rear access to the system controller is required in order to connect a single  temperature probe  Unlock the Smartpack controller using the same process  used for the rectifiers  see page 14   Feed the cable through the system as  desired through the wiring ports     The 15 pin serial connector  DE15  of the N3 CO   temperature probe connects to either CON3 OL JOD Q  or CON4 on the rear of the Smartpack   F  controller        SD sg    The probe end is designed to be   installed d
26. o determine which hardware on the return bus fastens it to the  internal system return bus  take care not to disconnect the return bus     To make connections to battery landings     1  After successful system turn up  remove the four screws holding the rear  cover in place     2  Make connections using two hole  3 8    16 lugs on 1    centers  Fastening  hardware is provided     3  Torque connections from 15 to 23 ft  lbs     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 2 5    Do NOT Remove    HHHH TE HEHHEHE       Figure 16   Bulk Battery Landings  23  4U Distribution     Battery Returns Do NOT Remove Battery Hot           2 CO Ground  Figure 17   Bulk Battery Landings  23  6U Distribution     2 6 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Central Office Ground    A dedicated central office  CO  grounding conductor connection is  recommended  This conductor should be of the same or larger gauge than  the largest system conductor so that It can discharge total system current in  a fault condition  A THHN style cable is recommended  Install this cable  between the DC system point and the critical site ground bar  See the figures  on page 26 for the recommended organization of return connections     Other Features and Options    Distribution Covers    Internal Cover    There are two protective  covers supplied with the    power system  The lower    internal cover is positioned  just behind the primary return  bus bar  and   s in
27. oad termination point  During battery discharge the critical  bus is fed from battery input through the low voltage battery disconnect   LVBD  contactor  The contactor is designed to disconnect the battery  from the system when it reaches a user defined setpoint during  discharge  The top bus is configured to accept battery input  Both the  top bus and the rear bulk battery terminals are connected to the LVBD         Battery breakers  Critical load breakers    u    1 6 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008        io    The 1200A system has a different configuration since each bus is rated at  600A  therefore  rectifier output must be divided between at least two  buses  The top bus is unused in this configuration     Unused Bus    Critical load breakers          Critical load breakers         LVBD    RE gj  t WAR   gt   Rectifier Battery    Load Shedding Bus Configuration    The load shedding bus configuration is connected as shown  The bottom  bus is used for critical load termination points  The critical bus is intended  for loads that need to have power for the longest available backup time   The critical bus is fed from the batteries through the low voltage battery  disconnect contactor  The secondary bus powers peripheral or redundant  loads that can be shut down to increase available backup time  The  secondary bus is fed through a low voltage load disconnect contactor   The top bus is configured to accept battery input     Battery breakers 
28. play   LED Lamp  red   i per line z rn Warning  utput voltage or lm oo Prac    LED Lamp  yellow  menu options   ee 1    E Piy         Cutualt 1 54  1500 BH Power  Lower line BattCunp   00587A   f     LED Lamp  green     Battery or load current   alarms  or keys to press     4   Down  arrow key   T   Up  arrow key  CAN port  2     4    Enter    key    Battery Connections    Alarm K0 Connections    Rear View        Battery Connections   Alarm   0 Connections    system Connections    3 4 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Adjustment Menu Example     NomVolt         Jt     J Boostvot V       J todattmaj UV    Volt Adjustment  gt  LoBattMin JT       HiBattMaj UT        HiBattMin 1  gt      fivBD 4        gt  S     Change Password  gt  Password JT     Set Boost Time  gt  HE     Start Stop Boost  gt    0000000      Enable Disable JT  amp   Auto Boost Conf   gt  Threshold   Nxt Test Date Time Date  LT Time JT    Pend ott YP  Test Int JT       Guard Timel      Start Stop Test  gt         Enable Disable JT  amp  Max  Charge Curr Lim   gt  C Curr LT    Battery Setup  gt  NumofString LT    Cellcap A nT    Output Control  gt  Voltage Ctrl   u Comp          Change Date Time  gt  Date JT Time LT      fAlamOutputl     gt      BattContactorl  gt   pf toad Contactor TO    Alarm Output 7  gt        Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Menus  When entering Menu Mode   Level 1   access User Options  By  default  it is set to    r
29. sly approved by the  party responsible for the compliance could void the user s authority to operate this  equipment     Protecting personnel against electrical shocks  The power system cabling must be  done by qualified personnel in conformance with local and national electrical codes   Input voltages to rectifiers are at a dangerous level  Ensure that circuit breakers are  locked in the OFF position at the AC service panel before attempting to work on the  power system  Dangerous voltages may still be present at the terminals even if the  rectifiers are OFF  Use a voltmeter to verify the presence of such voltages  Do not  Switch circuit breakers to ON until the entire system has been assembled and you  have been instructed to do so according to the appropriate procedure  Improper  wiring can cause bodily harm and equipment damage  Turn off all power sources  before servicing units     WARNUNG    Schuetzen von Personal gegen elektrische Schocks  Die Spannungsversorgungs    Leitungen darf nur durch qualifiziertes Personal in Anpassung mit Oertlichen und  nationalen elektrischen Codes ausgefuehrt werden  Unsachgemaesse Verdrahtung  kann koerperliche Verletzung und Schaeden verursachen  Eingangsspannungen von  der Netzspannungs   Versorgung Ihrer Hausanlage koennen unter Spannung stehen  beim Anschluss derLeitungen  Vesorgungsspannungen koennen bei  unsachgemaessen Gebrauch gefeahrliche Schaeden verursachen  Sorgen Sie daf  r     Installation Guide Flatpack2 Power Systems   204
30. sseeseessesseeeaess 30  SMET TE MINE NON een ee 31  FEMTE ACCESS eee 32  FE PN 32  SMALLDACK EXTENdEU EE 32  Smartpack Extended with Slave    ea 32  MANN 33  SMAA NET 33  SMarLDack VIN EO OLE BEAN 33   Local ICY PA ER 34  Local Computer NES 36  10  Startup Checklists  csicssansennnanennane nennen 37    Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    1  Safety and Compliance    WARNING  For safety  the power supply Is required to be reliably connected to  PROTECTIVE GROUND  The equipment is to be connected to supply mains by  qualified personnel in accordance with local and national codes  e g   NEC  CEC  etc    Do not disconnect and reconnect I O power connectors during lightning storms   The output of the power supply is not intended to be accessible due to energy  hazards  Rack mounting must be performed in accordance with instructions  provided by the manufacturer to avoid potential hazards     A readily accessible disconnect device shall be incorporated in the building  installation wiring for all AC connections  Select wall breakers according to section  AC input requirements  page 13      FCC Compliance Statement    This device complies with Part 15 of FCC Rules  Operation Is subject to the  following two conditions     1  This device may not cause harmful interference  and    2  This device must accept any interference received  including  interference that may cause undesired operation     WARNING  Changes or modifications to this unit not expres
31. tended to  protect the internal bus  structure  amp  contactors  This  cover can be removed by  loosening the four screws  securing It in position with two on either side  Permanent removal of this  cover is not recommended  and may impact the safety ratings of the  device        Top Cover    The second cover IS positioned  above the main distribution  section  and is intended to protect  the DC load termination points   The cover should be removed  during the installation of load  wiring  Once wiring is complete it       is recommended to replace the  cover during long term use  This   cover is removed by opening the    front door of the system and    loosening the two screws securing  the cover one on either side        Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008 2      Emergency Power Off  EPO  and Service Bypass Switch    The emergency power off circuit and service bypass switch are situated on a  front access circuit board inside the 23    distribution units  In the 23    AU  distribution  the board is located on the far left  in the 23    6U  the board is  near the center of the distribution unit  just to the left of the controller slots   EPO and service bypass are not available in 19    distributions     The emergency power off circuit is a normally closed circuit that stops  system operation when opened  This feature is useful for fires or other  emergencies requiring the immediate shut off of a power system  A jumper  wire Is provided to keep 
32. tery strings   Recording of rectifier serial numbers and other information   Load shedding control   12 digital inputsfor site equipment alarms   12 user definedform C output contacts    Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Smartpack Web       SmMARTPACK    r            USR       Local user interface via a three bu   2 line x 16 character  high contrast backlit LCD display   Digital communication with each Flatpack2 rectifier   TCP   IP or SNMP user interface  Storage of setup parameters  alarm configuration and system history in non volatile memory  Real time clock with battery backup   Advanced battery monitoring and full symmetry for 2 battery strings   Recording of rectifier serial numbers and other information   Load shedding control   2 digital inputs for site equipment alarms   2 user defined form C output contacts    Smartpack Web with Slave            SmMARTPACK       Local user interface via a three button keypad on the front panel  2 line x 16 character  high contrast backlit LCD display   Digital communication with each Flatpack2 rectifier   TCP   IP or SNMP user interface  Storage of setup parameters  alarm configuration and system history in non volatile memory  Real time clock with battery backup   Advanced battery monitoring and full symmetry for 4 battery strings   Recording of rectifier serial numbers and other information   Load shedding control   8 digital inputs for site equipment alarms   8 user definedform C output conta
33. th two hole 3 8    lugs on 1    centers  The recommended torque range is 15 to  23 ft  lbs  When facing the front of the system  the bulk    hot     output  is the left  bus  the bulk return is the right bus     The rear bulk battery terminal specifications are identical to those of the three   bus distributions  See the discussion of bulk battery connections on page 21 for  details     Bulk Battery Connections    AN CAUTION  Do NOT CONNECT BATTERIES UNTIL SYSTEM TURN UP  FOLLOW THE  CHECKLIST PROVIDED FOR THE PROPER PROCEDURE        CAUTION   T IS STRONGLY RECOMMENDED THAT EXTERNAL BREAKERS OR FUSES BE  AN INSTALLED BETWEEN BULK SYSTEM TERMINALS AND BATTERIES     NOTE  UNFASTENING THE HARDWARE MARKED    Do NOT REMOVE    IN THE FIGURES WILL  DISCONNECT THE RETURN BUS FROM THE INTERNAL SYSTEM BUS WORK     2 4 Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    Flatpack2 distributions feature multiple battery termination points at the rear   Landings accept two hole 3 8    16 lugs on 1    centers  Each distribution unit has  different specifications for cable landings  as follows     o 19    AU  Four landings per polarity  maximum wire size of 250 MCM  o 23    AU  Eight landings per polarity  maximum wire size of 250 MCM  o 23    6U  Eight landings per polarity  maximum wire size of 750 MCM    Bulk battery return buses contain an extra landing as a central office  CO   ground  see the section on CO Ground on page 25  Carefully examine the figures  on page 26 t
34. the circuit closed  If desired  an external emergency  device  such as a switch or lever  may be wired to this connection     val    FF Fu    TT         x         iA   ves   1G    7 x    x wS  Figure 19   EPO and Service Bypass Switch in 23  6U Distribution    The service bypass switch forces the LVD  contactor to remain closed  preventing service  disruption during maintenance  In the    Normal     position  DOWN in the 23    AU  UP in the 23    6U    the contactor operates according to the  settings defined in the Smartpack controller  To  activate the bypass  change the switch to     Bypass     UP in the 23    4U  DOWN in the 23    6U    this forces the LVD contactor to close and  prevents controller signals from opening it  A  label is provided on the inside of the distribution  door to illustrate proper switch operation     Additionally  the LED on the board illuminates Figure 18   EPO and Service      when the bypass Is active  Switch in 23  6U Distribution    LVD Options    Up to two low voltage disconnect  LVD  contactors can be installed   Contactor settings are configured through the Smartpack controller     Installation Guide Flatpack2 Power Systems   2046916 R1  June 2008    8  Alarm and Control Terminations    Alarm Contacts    Alarm interface boards differ in location depending on the distribution unit used   The 19    AU distribution has a single rear access board located to the far right   when viewed from the rear  next to the bulk battery hot bus  The 23    
35. tpack2 Power Systems   2046916 R1  June 2008 1 5    23    AU    The 23    wide  AU high distribution section is designed for 600A systems   Load buses have twenty four positions and holders for over current  protection devices  The rear of the distribution has eight bulk battery  landings on each polarity accepting a maximum wire size of 250 MCM  An  additional AU distribution section can be added to double the number of  cable landings for a total of forty eight     23    6U    The 23    wide  6U distribution section Is designed for 1200A systems   Load buses have twenty four positions and holders for over current  protection devices  Because each load bus is rated for 600A  two buses  are strapped together to share the output current  The internal return  bus Is rated for the full 1200A  The rear of the distribution offers eight  bulk battery landings on each polarity  with each landing accepting a  maximum wire size of 750 MCM  An additional 4U distribution section can  be added to double the number of cable landings for a total of forty eight     Bus Configurations for Single Distributions    Three bus distributions can be configured in many ways  The following  examples illustrate standard arrangements and some common variations   Notice that each diagram indicates the presence of a customer supplied  disconnect device between the system and batteries     Standard Bus Configuration    The standard bus configuration is connected as shown  The bottom bus  is the critical l
36. ty that permits them to work with  all configurations  There are three primary designs defined by dimensions     o 19    wide  4U  7 0     high unit  o 23    wide  4U  7 0     high unit  o 23    wide  6U  10 5     high unit    Front views of these distributions and typical system configurations are found  beginning on page 8  Rear views of the distributions are on page 26     Three Bus Distributions    The three bus distribution features a unique  configurable design that allows load  breakers and or fuses to be aligned to any one of the three parallel  front access  buses  see Figure 10   Load landings accept up to  1 AWG cable with two hole  1 4    lugs on 5 8    centers  Rear access battery landings accept two hole 3 8      16 lugs on 1    centers  maximum wire gauge depends on the size of the  distribution section     Jo UV VEVIVPVVBUBHIPBVPBRE BRD   A I 2 2 2 20  he       au N   p i nA 3  BE Sho  oy LN    b  X 3 Vee   ar         Lo    108808       w o  Dumme ee  x       as IAAI    E O bi   A a aj       gd 123  TAR yt aos es eer eet       Figure 10   Three bus Distribution with En Distribution Device Holders  Designations    19    4U    The 19    wide  4U high distribution section Is designed for 300A systems   The parallel load buses have twenty positions and holders for over   current protection devices  The rear of the distribution offers four bulk  battery landings on each polarity  with each landing accepting a maximum  wire size of 250 MCM     Installation Guide Fla
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
SoftBank 101F 取扱説明書  取扱説明書[NE-BS901] (4.78 MB/PDF)  Tripp Lite B119-003 User's Manual  プロペラファン/AC入力 MRシリーズ D180mm ー65mm厚 仕様 風量  NET145LA NET145CL User Manual  TP425C Charger Manual  Cables Direct Cat5e UTP 3m  20 kb Template Preparation Using BluePippin Size    TurboScript™ T7 Transcription Kit    Copyright © All rights reserved. 
   Failed to retrieve file