1. 4 Under the Comb Ins tab change the DIG INPUT 1 format by pressing EDIT and then 1 Alternate I O Formats to Con 026 1709 Rev 1 10 NOV 2010 troller Application Property from the Board Point format 5 For the Controller property press LOOK UP to select the Eaton Breaker Panel for the Application property select Lighting Panel and for the Inputs property select the breaker numbers that are included in the group 10 06 09 CX 466 Unit 1 OAT 83 OH 59 18 59 54 Use Ctrl X to Select CX Tabs SETUP FULL xALARM Ci General C2 Comb Ins C3 Ctrl Ins C4 Outputs CS Digital Combiners 76 LGHT PROOF Comb Ins Area Ctrl Application Output DIG INPUT EER 1TN BRKRPNLOG1 BREAKER_2 DIG INPUT2 CK 4 ETN BRKRPNL881 BREAKER_6 DIG INPUT3 s GX 4 ETN BRKRPNL881 BREAKER_8 DIG INPUT4 s GX 4 ETN BRKRPNL881 BREAKER_18 DIG INPUTS 5 GX 4 ETN BRKRPNL881 BREAKER_12 F4 PREU TAB F2 NEXT TAB F3 EDIT Fa LOOK UP FS CANCEL Figure 4 9 Grouping Inputs in Digital Combiner 6 Gobacktothe Lighting application under the More tab and associate the Lighting group Figure 4 10 with the Digital Combiner ap plication 8 86 689 CX 488 Unit 1 OAT 83 OH 59 19 62 19 se Ctr1 X to Select CX Tabs SETUP FULL ALARM C1 Setup C2 C3 Min On Off C4 C5 Std Events c 6 C7 Maint Our C8 Inputs C9 Outputs C6 MORE Lighting Control 76 LIGHTS Proof Area Ctrl Application Output Proof Type ON Only PROOF IN
2. Eaton Breaker Panel System i D Terminate NOTE POLARITY ON BCB MODBUS CONNECTORS IS THE INVERSE OPE2 WIRE on E2 Connect the MODBUS to LAN on BCBS shield to the chassis WIRE on E2 ground earth bus of to LAN on BCBs each panel 7 18 5 6 Panel 4 Panel 3 Panel 2 Figure 3 1 E2 and Eaton Breaker Panel Layout with Example Left Right Rail Numbering 4 Eaton Panel Breaker Breaker Control Bus Address ing Assign a unique address for each BCB on the LAN address switches before the E2 can communicate reli ably In the case of a two rail panel each rail has a separate MODBUS physical address used for com munication the physical address of the first rail will be the device address visible to the user in Network Services The physical address of the second rail is determined by taking the address of the first rail and adding one Always set the left rail as an odd number and the right rail as an even number odd 1 or left rail 1 in order for it to display correctly in the E2 3 2 For example if the physical address of panel 1 is 1 deft rail 1 right rail 2 yo
3. Enter your license key to activate the Eaton Breaker 5 Panel 1 Press WA System Configuration Log in to the E2 with Level 4 access 6 Press lt p followed by Gener al Controller Info BX 466 Unit 1 13 58 29 7 Add License Ctrl Press a to open the Serial tab of the General Controller Info setup screens Licensed Features 09 06 2805 13 58 24 Rev 2 28B12 For controller model type BX 488 Maximum In Use License 67 14 16 RX 388 Unit 3 OAT 78 Use Ctr1 X to Select CX Tabs SETUP NAMES BFULL C3 Serial C4 TCP IP jcs 13 44 82 GEN LON Demand Limit Cont Flexible Combiner Time Schedule Log Group CarrierOne x C5 Peer Netwrk Activate Feature General Setup GENERAL SERV Enter License key to activate a Feature serial Value Connection Serial Baud 115 2 Kbaud Connection Baud 9666 baud Data Size 8 Parity None Stop Bits 1 Connection Modem Baud 115 2 Kbaud Modem Port No Modem Modem Type CPC 33 6K Internal Modem Init ATEGU1S 6 1S16 468D2205 NOZC O amp K GRY 02118 Fax Init ATUIEGSG 1S16 462D2205 NOZC O amp K GRY 02118 DTHF Dur 166 Pause Dur 2 ARTC RTU Nose5 HUAC Zone Analog Sensor Ctr Loop Sequence Ctr Digital Sensor Ct RCB Lighting Control Trane SCC Air Handling Unit Digital Import Point Analog Import Point F5 CANCEL Figure 3 5 Enter Your Unique License Key 4 Reboot the controller and open the License Cra PREU tap
4. Setup screen and locate your E2 s MAC address circled in Figure 3 4 69 61 65 BX 488 Unit 1 Use Ctr1 X to Select CX Tabs SETUP INS C1 General C2 Eng Units C3 Modem C8 Peer Netwrk C9 Web Server CO System General Setup GENERAL SERV 18 83 17 xALARM TCP IP Value DHCP Enabled z No IP Address 18 18 64 39 Subnet Mask 255 255 248 0 DNS Server 1 DNS Server 2 DNS Server 3 E Default Gateway 18 18 64 1 Domain Name MAC Address 7_ 66 6A F6 66 66 AF F4 PREU TAB F2 NEXT TAB F3 EDIT F4 STATUS F5 CANCEL Figure 3 4 TCP IP Screen Locating the Mac Address 4 Call Retail Solutions Customer Service at 770 425 2724 and have your MAC Address ready in order to obtain your unique license key Once you have received your unique license key from Customer Service you can now activate the Eaton Breaker Panel application from the License Re port screen The License Report screen displays that E2 controller s unit type and firmware version the list of all licensed features on that E2 the current number and maximum number of each of those applications allowed and which additional features that require a license key have been enabled From the Main Menu Networking 5 3 4 2 Set Up Network Ports Before setting up an Eaton Breaker Panel the port 2 P L AD jena nn Licensing on the E2 that has the MODBUS cable connected 3 Press Add Feature must be set up as a MODBUS port
5. Above PIB RS485 COM Card 2 Connectors Serial Device RS232 Port POWER INTERFACE BOARD PIB COM4 Serial Device RS485 COM Port 2 Connectors COM2 Figure 3 3 Location of E2 COM Ports E2 PIB Board An E2 has up to three COM ports that can be as signed for MODBUS communication COM2 an RS485 port on the E2 power interface board and COM4 and COM6 which are optional ports requiring expansion cards COM ports can only be used for one function in other words if COM2 is set up as the I O network you cannot connect MODBUS devices to COM2 Ensure your E2 is equipped with an RS485 COM Card P N 637 4890 and configured in E2 General Services BN Serial tab to en able COM4 or an E2 Expansion COM Card P N 637 4871 to enable COMO Connect the MODBUS network cable to the three terminal connector on the COM port you wish to as sign as MODBUS Wire RS485 to the BCB LAN terminal and RS485 to the BCB LAN terminal Network Connection to E2 using MODBUS 3 3 1 If the E2 will be the first device in the network set the port s termination jumpers to the TERMINATED amp BIASED position all three jumpers UP other wise set all jumpers DOWN if not the first device E2 Termination 3 4 E2Setup of Eaton Breaker Pan els 3 4 1 Licensing the Eaton Breaker Panel 1 Press WA System Configuration cas 2 Press KW Remote Communications 3 Press TCP IP Setup to open the TCP IP
6. F2 next rap FB EDIT Fa Lookup Fs CANCEL Report screen again to see the license key appear next to the ETN Breaker Panel Figure 3 6 Figure 3 7 Serial Communications Manager Screen 8 This screen will have a Connection field for all COM ports on the E2 Highlight the COM port connection field that will be used and press LOOK UP From the list RX 366 Unit 3 LICENSE REPORT Perf Alert CtrlLink ACC CtrlLink RSC Suction Control Condenser Control Area Controller Standard Circuit 16AI ISD 2 8 CtrlLink CD Enhanced Suction IRLDS 8R0 XJ Scroll Unit h h h h h h h h b d Mb i oM o N Loop Sequence Ctrl MultiFlex PAK MultiFlex CUB Holiday Schedule Heat Cool Control F1 ADD FEATURE Figure 3 6 License Report Screen 91ED 7EFE 36BD 441B The Eaton Breaker Panel application is now li censed 6 Eaton Panel Breaker of network types select MODBUS 1 MOD BUS 2 or MODBUS 3 Four fields will become visible underneath the COM port connection field which pertain to the way the device communicates eBaud Change Default setting to 9600 Data Size Leave this field at the default value 8 eParity Leave this field at the default value None eStop Bits Leave this field at the default value 1 10 Press gt to save changes and exit 026 1709 Rev 1 10 NOV 2010 3 4 3 Addand Connect Eaton Breaker Panels To enable communications between E2 an
7. 5 No Port No port is set up in the E2 Serial Configuration Manager to be a MODBUS port Follow the instructions in Section 3 4 2 Networking 7 4 Eaton Breaker Panel Application Setup in E2 4 1 Press lt HHH select ETN Breaker Panel then to access the Device tab Device Setup Rails Present must be set by the end user Access C6 Device and select Rails Present choose the number of rails and press to save C RX 366 Unit 3 OAT 78 15 66 19 OPTION LOOKUP NAMESBFULL xALARM C1 General 1 kr Names C7 Brkr Cfg 66 28 16 Device Physical Addr Ct a m m Option List Selection Select Description Select L and R Rails o i 1 L Rail R Rail 2 Rails Present F4 SELECT F5 CANCEL Figure 4 1 Device Setting for number of rails 4 2 Eaton Breaker Panel Applica tion Setup in E2 Single Break er 4 2 1 Add a Lighting Schedule Applica tion For each group of breakers to be controlled sepa rately set up a Lighting Schedule application from the Add New Application screen Press the D Key to access the Main Menu then il Add Delete Application 2 Add New Application Press LOOK UP to select Lighting Schedule Enter the number of desired applications in the How Many field 8 Eaton Panel Breaker 4 2 2 Light Outputs and Proof Inputs Set up Once the Lighting Schedule applications have been added set up the light output and proof input for ea
8. be OFF Verify that the cir cuit breaker 1s functional and check wiring to ensure that the BCB is receiving power 026 1709 Rev 1 10 NOV 2010 LAN The LAN LED blinks one second intervals when the E2 is communicating with the BCB and the BCB is receiving data If the LAN LED is not blinking or is non functional verify the PWR LED is ON and the power wiring 1s correct no crossed wires and no wir ing connections that have shorted out RUN The RUN LED blinks one second intervals when the BCB is wired correctly and communicating with the E2 If the RUN LED blinks twice consecu tively and turns OFF for three seconds this indicates that the BCB is not communicating properly 2 2 2 BCB Network Termination Use Retail Solutions standard third party termina tion e Terminate at E2 with all three jumpers at one end of the network e At the other end of the network terminate at the last BCB module with 150 ohm resistor or CPC P N 537 2711 MODBUS Termination Block e Standard Belden 8761 RS485 I O Net cable recom mended Power ON Indicators Wiring 3 3 Networking 3 1 The relationship between the E2 and the Eaton Panel Breaker can be seen in Figure 3 1 The diagram shows four Eaton Breaker Panels with two BCB mod ules per panel with a maximum of eight BCB modules allowed per MODBUS port If the panel contains a single rail or only one BCB module per panel up to eight panels can be controlled by an E2
9. is ee e OS 12 5 1 TROUBLESHOOTING EATON BREAKER PANELS AND THE MODBUS NETWORK cscceccscceccecceccecceccucceccuseeseuses 12 5 2 PANELS WITH UNSUPPORTED USC 1000 CONTROLLERS INSTALLED c ccsccecceccecceccecceccecceccsccsccecceceecencensens 12 Table of Contents i 1 Introduction E2 can communicate directly with Eaton s Breaker Control Bus BCB modules Eaton Breaker Panel Communication with the E2 will enable the user to use features such as Time Schedules Enhanced Lighting and Logging In addition the user will gain the added capabilities of dial out on failure and off site remote connection specifically with UltraSite32 and Site Manager to the breaker panel The Eaton Breaker Panel controller is a licensed application available in the E2 300 and 400 model controllers with a maximum of 8 breaker panel rails allowed 1 1 Eaton Breaker Panel Each Eaton Breaker Panel consists of up to a total of 42 breakers that are divided into 2 rails up to 21 breakers per rail identified as breakers 1 through 42 In addition to being identified by number the user will have the ability to give each breaker a unique name Figure 1 1 Eaton Panel Breaker Eaton Breaker Panel 1 2 Breaker Control Bus The Breaker Control Bus BCB module is de signed to fit in each rail of the Eaton Breaker Panel and provides the interface between the E2 and the re mote controllable breakers using MODBUS Refer to
10. 026 1709 Rev 1 10 NOV 2010 E2 and Eaton Breaker Panel Installation and Operation Manual EMERSON EMERSON Retail Solutions 3240 Town Point Drive NW Suite 100 Kennesaw GA 30144 Phone 770 425 2724 Fax 770 425 9319 ALL RIGHTS RESERVED The information contained in this manual has been carefully checked and is believed to be accurate However Com puter Process Controls Inc assumes no responsibility for any inaccuracies that may be contained herein In no event will Computer Process Controls Inc be liable for any direct indirect special incidental or consequential damages resulting from any defect or omission in this manual even if advised of the possibility of such damages In the interest of continued product development Computer Process Controls Inc reserves the right to make improvements to this manual and the products described herein at any time without notice or obligation The Eaton Breaker Panel is manufactured by the Eaton Corporation and is a registered trademark of that company Table of contents LL INTRODUCTION tt re o tT OC RR nt Se ee eRe a Een 1 Lal AOI AC ha a a cash Sar em eet e do ley eae ats 1 1725 BREAKER CON PRO BUS ss ee eee O seems cor matinee ee 1 2 AN e en nee aT er A le URES Med ee Rao ee 2 Als sey Ce WV MMR DIN tei NI lt do ae an tae Aus hes T ee 2 Deda be AGAIN POWER CORNELSEN ee 2 22 gt BOWERSON INDIEATORSZr 2 22 o e A er eb e ee ee rl 2 Frl 0 SER AM AN EE EAT O ee Ds IN
11. 8V Red 240V Orange Grey Table 2 1 Transformer lead Colors Supply Voltage 2 Eaton Panel Breaker Transformer Model TR75V A003 277V Brown COM Yellow White Table 2 1 Transformer lead Colors Supply Voltage The secondary leads of the 24 VAC transformer should have one wire connected to the 24 V terminal of the BCB modules and the other secondary wire connected to the 24 Com terminal of the BCB mod ules The side of the 24VAC secondary connected to the 24 Com terminals of the BCB should also be con nected to the chassis ground earth bus of the panel It is recommended to use 16 AWG wire with 600 V isolation jacket for interconnecting BCB modules 24V AC power with a maximum length of 150 feet If the BCB modules are mounted in closer proximity such that the total power length is 50 feet or less then 18 AWG conductors may be substituted Figure 2 2 BCB LAN and Power Connectors 2 2 Power ON Indicators 2 2 1 BCB Status LEDs Once power 1s applied to the Eaton Breaker Panel and each connected BCB the PWR Power LED on each BCB should be illuminated red If the Power LED does not illuminate verify the power supply and the proper wiring terminations on each BCB Confirm all four pin connectors are properly wired PWR The PWR LED is illuminated ON solid when the BCB is powered up 24VAC If the PWR LED is OFF the other LEDs will
12. A 2 2 2 2 BEB NCIWOME T CHININGTTON 6 ke ae ss ee Be le a ig Eh el Uli O 5 Sy NETWORKING ecco ec a u Eee sa ee OE lea dl 4 SA EATON BREAKER PANELS STE M 2 2 2222 esse 4 5 2 e BREAKER CONTROL BUS ADDRESSING O ee a eee ad A 3 3 NETWORK CONNECTION TO E2 USING MODB US 2 22 22 oct ea ees ahi ei ee 5 Ile BROCAS A ed 5 54 gt EZ SETUP OF BATON BREAKER PANEUCS 2222er 5 34 4 Dicensing the Eaton Breaker Panel ne toes ade Sees iad tig edie 5 AZ ASCE INCI WOIK TOTES ae AAA AA A A A ee 6 3 4 5 Add and Connect Eaton Breaker Panal a o 6 4 EATON BREAKER PANEL APPLICATION SETUP IN El cescccccccccccccccccccccccccccccccccccccccccccccccecs 8 Al DEVICE SETUP aussi hen de ed ct eae et aie shee Een ett o aS tel de ct tates ae aa ae ig ETETE 8 4 2 EATON BREAKER PANEL APPLICATION SETUP IN E2 SINGLE BREAKER cccescesccscecccscesccecesccscescescencescescesceucesees 8 42 1 ADAL Schedule APP CTO aueh das 8 4 2 2 ion Opus and Proof INPUS SETUD mirre Ee ee nee A NAE e 292 1 ASM Outputs Setup Dutputs Tabs dd A E A A oda 8 A SPOOL Inpuls SEU SCP AD di tit delle 9 4 3 EATON APPLICATION SETUP IN E2 MULTIPLE BREAKER GROUPING ccscescecccccscecceccceccsceccsccscescscescscscscesescescecs 9 43 4 gt CRE LA ECOS dica 9 4 3 2 Proof Inputs Setup for Multiple Breaker Grouping ooooncccccnncnnnnnnnnnanononononnnnnnnnnnnnnanenonnnnnnnnnnnnnnnnnnannnnnnnnnnnnnnnnnnnns 10 gt ITROUBLESHOOTING 32 23 a o aoe
13. ARM Status RX386 Refrig Ethernet This Controller LonMark Device LonMark Device 16AI IONet 8RO IONet 8D0 IONet 4A0 IONet IRLDS IONet CtrlLink RSC No Network CtrlLink CD No Network CtrlLink ACC MODBUS 1 ISD 2 6 Comp MODBUS 1 Perfnrmanre Alert HNNRUIS 1 ETN Breaker Panel MODBUS 1 AJ SCFOLL UNIT MUDBUS 1 Status Display Ethernet Status Display Ethernet No Port No Port No Port No Port No Port Unknown Unknown Unknown Unknown Iinknnun unknown F2 STATUS F5 SETUP F COMMISSION Figure 3 9 Network Summary Screen 6 To set the address and begin communication press and select MN Select Address In the list of MODBUS devices choose the address number corresponding to the Eaton Breaker Panel s address switch Figure 3 2 setting and press to select it For a two rail system the user will select the left rail ad dress and the right rail address will automati cally be addressed as the left rail address 1 Locate the Eaton Breaker Panels you set up and look at each device s status in the Status field You will see one of the following mes sages Online The Eaton Breaker Panel is com municating normally Offline The Eaton Breaker Panel is not communicating has not been commis sioned is not functional or is not powered up Verify the Eaton Breaker Panel is pow ered up wired correctly and has the proper network address baud rate and parity see Section
14. CX 1 5 LGHT PROOF 0uTPUT Proof Delay 8 88 38 Proof Latch 8 88 88 Clear Any Match No Pr Fail Ady Pri 28 Figure 4 10 The Digital Combiner Used To Group Inputs When using the Digital Combiner method above the Proof Type must be set to ON Only 7 Under the More tab change the PROOF IN Eaton Application Setup in E2 Multiple Breaker Grouping format by pressing EDIT and then 1 Alternate I O Formats to Area Ctrl Appli cation Property from the Board Point for mat 8 For the Area Ctrl property press LOOK UP to select the E2 Name for the Ap plication property select the Digital Combin er that you created and for the Output property select OUTPUT For more information on setting up Lighting Schedules refer to the Lighting Schedules section in the E2 User Manual P N 026 1610 Eaton Breaker Panel Application Setup in E2 11 5 Troubleshooting 5 1 Troubleshooting Eaton Break er Panels and the MODBUS Network Problem Eaton Breaker Panel is Offline l Check Wiring Verify the Eaton Breaker Panel is properly connected to the MODBUS cable Verify the network polarity is correct MODBUS 485 to BCB LAN terminal MODBUS 485 to BCB LAN terminal and there are no loose wires If none of the Eaton Breaker Panels are online check wiring con nections on the E2 Check the cable jackets to make sure all network cable is Belden 8761 or equivalent 2 Verify MODBUS Port Setup Press AM on t
15. Figure 1 2 for proper orientation of the BCB rails s A Figure 1 2 BCB installed on an Eaton Breaker Panel The BCB rails attach to the Eaton Breaker Panel interior without any special connectors or modifica tions Note how the rails are positioned Figure 1 2 in side each panel Observe the correct orientation of the BCBs for correct breaker numbering and control with the E2 Introduction 1 2 Wiring 2 1 BCB Wiring Two four pin combination LAN Power Connec tors are located on each BCB Figure 2 1 It also has the Breaker Terminations for plugging into the Eaton Breaker Panel and the LAN Address Switch es used to set the MODBUS address 1 to 8 for com munication with E2 Three recessed LEDs RUN LAN PWR are located on the BCB that indicate the communication and power status of the BCB LAN Power Connectors LAN Address Switches RUN LAN PWR Breaker Status LEDs Termination Figure 2 1 BCB Connectors 2 1 1 LAN Power Connectors A 24VAC transformer is needed to power the BCB modules see Table 2 1 One 75VA transformer can power up to four panels eight BCB modules if they are in the same area or one 75VA transformer can be used per panel Transformer Model TR75VA005 COM Black 24 VAC 120V White COM Yellow White 20
16. S IS THE INVERSE sa F E2 a DE MODBUS connected GONNESTOR WIRE on E2 to on BCBs N WIRE onE2 A to on BCBs Belden 8761 or equiv To other AR NOR BC 5 u 12 E Jl N Ly Eaton Panel Figure 5 1 E2 and Unsupported USC 1000 Panel Layout p Wire colors are subject to change 026 1709 Rev 1 10 NOV 2010
17. ch Lighting application Proof input setup may be optional The outputs of a Lighting Schedule cell control the breakers on the Eaton Breaker Panels and the proof inputs of the Lighting Schedule cell are the Eaton panel breaker status outputs 4 2 2 1 Light Outputs Setup Outputs Tab If on the E2 Home screen press or to access the Lighting Schedule depending on whether a BX or CX E2 controller is being used 1 Under the Lighting Outputs tab change the LIGHTS OUTPUT format by pressing EDIT and then 1 Alternate I O Formats to Area Ctrl Application Property from the Board Point format 2 For the Area Ctrl property use LOOK UP to select the Eaton Breaker Panel for the Application property select lighting panel and for the Input property select the breaker input number BREAKER_IN_X CX 488 Unit 1 OAT 84 OH 59 18 48 22 ALARH 16 66 69 Use Ctr1 X to Select CX Tabs SETUP FULL C1 Setup C2 C3 Min On Off C4 C5 Std Events c G Maint Our C8 Inputs C9 Outputs CO MORE Lighting Control 36 LIGHTS Outputs Area Ctrl Application Input LIGHTS OUTPUT 1 E n BRKRPNLOG1 BREAKER_IN_1 PROOF STATUS IN BYPASS F4 PREU TAB F2 NEXT TAB F3 EDIT F4 LOOK UP F5 CANCEL Figure 4 2 Single Breaker Lighting Output Setup in E2 Lighting 026 1709 Rev 1 10 NOV 2010 4 2 2 2 Proof Inputs Setup Setup Tab To enable proofing set Enable Proofing to Yes for each Lighting application under
18. ched No Llev Logic Mode LOGIC ONLY Alt Lt Lgc Mode LOGIC ONLY Schedif Mode SCHED ONLY Alt Schdif Mode LLEV LOGIC ONLY Schedule Type MASTER Num Std Events 1 Num Date Ranges 8 Show Sched Show LLev Show Logic Enable Dimming KW Load Enter State Y Yes N NO YES to enable proofing F4 PREU TAB F2 NEXT TAB F3 EDIT Fa STATUS F5 CANCEL Figure 4 7 Enable Proofing on Setup Tab When grouping multiple breakers to a Lighting ap plication add a Digital Combiner application for proofing inputs To add an application follow the steps for adding an application in Section 4 2 1 Once added go to the Digital Combiner application 16 86 69 7 m CX 488 Unit 1 OAT 83 OH 59 18 58 39 Use Ctr1 X to Select CX Tabs SETUP FULL ALARM Ci General C2 Comb Ins C3 Ctrl Ins C4 Outputs CS Digital Combiners 76 LGHT PROOF General Value Name 76 LGHT PROOF Num Inputs 5 Eng Units ON OFF Comb Method ALT Comb Hethod VOTE Emerg Out Output On Fail ENABLE Scroll using Next Prev keys Normal input combination method A_F2 NEXT TAB F3 EDIT F4 LOOK UP F5 CANCEL Figure 4 8 Digital Combiner For Input Proof Grouping 2 For grouping set the combination method to AND under the Comb Method parameter in the General Setup and add a name that will associate the proof input group to the Light ing application 3 Set the number of inputs to the number of breakers in the group
19. d the Eaton Breaker Panels the devices must be added and addressed in E2 1 Log in to the E2 with Level 4 access 2 Press lt HHL Connected I O Boards and Controllers 8 13 88 xALARM 67 12 16 Cb RX 368 Unit 3 2 Use Ctrl X to Select CX Tabs SETUP C1 This Unit C2 IO Network C3 ECT C4 Third Partys A Num Network Ctrls NetSetup Third Party Board Type Quantity Max 1 ETN Breaker Panel 1 2 Open Echelon 2 2 FA PREU TAB F2 NEXT TAB F3 EDIT F5 CANCEL Figure 3 8 Connected I O Screen 3 Onthe Connected I O screen in a box labeled Third Party Devices enter the number of Eaton Breaker Panels in the Eaton Breaker Panel number field 4 Press gt to return to the Network Setup menu then select M EN Network Summary Figure 3 9 ou added to the network list press Up and Dom to scroll through the list and highlight with the cursor The default name for a Eaton Breaker Panels begins with a three letter designator of the model type ETN for Eaton Press Bo Setup 5 Locate the Eaton Breaker Panels E2 Setup of Eaton Breaker Panels 67 12 18 THIS 63 1 LONMARK_ 661 LONHARK 662 16AI_881 8RO_ 661 8D0_ 661 4AD 661 LEAK DETECT881 CL RSC_661 CL CD_661 CL acceet ISD2 COMP_ 661 PFRF ALERT _ A4 ETN BRKRPNL 881 AJ SCRULL UI STATUS DSP_661 STATUS DSP_ 662 F41 DELETE RCRD b RX 366 Unit 3 OAT 78 Network Summary NAMES FULL Network Address 8 21 23 AL
20. he E2 front panel Verify COM2 COM4 or COM6 is set up as a MODBUS port If so verify that the MODBUS cable is connected to the proper connectors Verify the COM port fields Figure 3 7 are properly set for ECT MODBUS 9600 baud data size 8 bits Parity NONE stop bits 1 3 Check Eaton Breaker Panel Selector Num bering Verify that the selector matches the address selector parameter under the De vices tab in E2 4 Check Network Termination The two de vices on either end of the MODBUS network should be terminated with all other devices in the daisy chain unterminated Check jump er settings for all devices on the network 5 Verify BCB power connections It 1s 1m portant to observe proper orientation of the BCB to facilitate both physical place ment and logical performance The BCB also has three status LEDs used to indicate its activity and operation Refer to Section 2 2 1 BCB Status LEDs 12 Eaton Panel Breaker 5 2 Panels with UNSUPPORTED USC 1000 Controllers In stalled Connecting to panels with integrated USC 1000 controllers is not supported If using this type of pan el disconnecting the USC 1000 from the BCB and connecting the BCB to the E2 controller is required 1 Disconnect and remove the MODBUS con nections between the USC 1000 and the BCB modules Lan and Lan 2 Connect the Lan and Lan wires to the E2 RS485 MODBUS network NOTE POLARITY ON BCB MODBUS CONNECTOR
21. on Breaker Panel Application Setup in E2 9 CX 466 Unit 1 OAT 83 OH 59 18 54 53 SETUP FULL ALARM Multiple Output Setup 10 06 89 Output CX 1 78 LIGHTS LIGHTS OUTPUT Area Ctrl Application Property Inputs Using Output 1 E n BRKRPNLOG1 BREAKER_IN_2 ox 4 ETN BRKRPNL881 BREAKER_IN_6 ex 1 ETN BRKRPNL881 BREAKER_IN_18 Cx 1 ETN BRKRPNL881 BREAKER_IN_12 Cx 1 ETN BRKRPNL881 BREAKER_IN 8 Enter Board Controller F41 ADD RECORD F2 DELETE RCRD F3 ALT FORMATS F4 LOOK UP F5 CANCEL Figure 4 6 Multiple Output Setup View 2 For the Area Ctrl property press LOOK UP to select the Eaton Breaker Panel for the Application property select lighting panel and for the Property output select the breaker input number BREAKER_IN_X Repeat for each breaker you wish to group to this Lighting application 4 3 2 Proof Inputs Setup for Multiple Breaker Grouping Press or to access the Lighting Schedule from the Home screen depending on whether a BX or CX E2 controller is being used 1 To enable proofing set Enable Proofing to Yes for each Lighting application under the Setup tab 10 Eaton Panel Breaker 10 06 09 7 im CX 466 Unit 1 a OAT 83 OH 59 18 57 14 Use Ctr1 X to Select CX Tabs SETUP FULL ALARIM Ci Setup C3 Min On Off C4 CS Std Events C C7 Maint Our C8 Inputs C9 Outputs CO MORE Lighting Control 36 LIGHTS Value 36 LIGHTS Alt Control No Enable Proofing RB Use Ext S
22. the Setup tab 6 66 69 3 m CX 488 Unit 1 2 OAT 83 0H 59 18 56 21 se Ctr1 X to Select CX Tabs SETUP FULL ALARI1 E Min On Off CS Std Events Lighting Control 36 LIGHTS Value 36 LIGHTS Use Alt Control No Enable Proofing Y es Use Ext Sched No Llev Logic Mode LOGIC ONLY Alt Lt Lgc Mode LOGIC ONLY Schedif Mode SCHED ONLY Alt Schdif Mode LLEU LOGIC ONLY Schedule Type MASTER Num Std Events 1 Num Date Ranges 8 Show Sched Show LLeu Show Logic Enable Dimming KW Load Enter State Y Yes F1 PREU TAB YES to enable proofing NEXT TAB F3 EDIT F4 STATUS F5 CANCEL Figure 4 3 Enable Proofing on Setup Tab If using a single Eaton breaker associate the proof input PROOF IN with the Eaton panel Figure 4 4 and status of the breaker number from the More tab in the Lighting application 16 66 69 CX 466 Unit 1 OAT 84 OH 59 18 52 13 Use Ctrl X to Select CX Tabs SETUP FULL xAL ARM C3 Min On Off C4 CS Std Events Haint Our C8 Inputs C9 Outputs Lighting Control 36 LIGHTS Proof Area Ctrl Proof PROOF CX aia aCe BREAKER 1 Proof 88 Proof Latch 8 88 88 Clear Any Match No Pr Fail Adu Pri 26 Application Output Enter Property Proof input F4 PREU TAB F2 NEXT TAB F3 EDIT Fa Look UP Fs CANCEL Figure 4 4 Single Breaker Proof Input Setup in E2 Lighting l Change the PROOF IN format by pressing EDIT and then 1 Alternate I O Formats to Area C
23. trl Application Property from the Board Point format 2 For the Area Ctrl property use LOOK UP to select the Eaton Breaker Panel for the Application property select lighting panel and for the Output property select the breaker number BREAKER X Eaton Application Setup in E2 Multiple Breaker Grouping 4 3 Eaton Application Setup in E2 Multiple Breaker Grouping www NOTE A Group can contain one or more breakers as defined by a user Assigning multiple breakers to a group allows an en tire group of breakers to be turned on or off si multaneously instead of each individual breaker being turned on or off separately 4 3 1 Setting Light Outputs 1 To group multiple breakers to a single Light ing application press EDIT and se lect 2 Set Multiple Outputs 19 06 89 7 m CX 488 Unit 1 a OAT 84 OH 59 18 53 46 Use Ctr1 X to Select CX Tabs SETUP FULL ALARM Ci Setup C3 Min On Off CS Std Events TE Haint Our C8 Inputs CRIT Outputs CG MORE Lighting Control 76 LIGHTS Outputs LIGHTS OUTPUT PROOF STATUS ACTIVE SCHED SCHED TUCOS SCHED TSCOS ALG STATUS IN BYPASS Area Ctrl Application Input ct BOUN M Enter Board Controller Lights output F2 NEXT TAB F3 EDIT F LOOK UP F5 CANCEL Figure 4 5 Set Multiple Breakers in E2 Lighting The Multiple Output Setup screen opens Figure 4 6 where you can set up the Area Ctrl Ap plication and Property Lighting outputs Eat
24. u will see the address of the left rail in the Network Summary screen In Figure 3 1 the odd panel numbers 1 3 5 and 7 will be visible on the Network Summary screen Figure 3 2 BCB Address Configuration CAUTION The same BCB model is used A for both Left and Right rails there are not separate BCB models for each rail In Figure 1 2 the BCB module for the Right rail is mounted upside down from the Left rail therefore the address switch numbering and ON OFF posi tions are reversed for Left and Right rail BCB modules Check the labeling on each BCB module for the correct address switch numbering and ON OFF positions 026 1709 Rev 1 10 NOV 2010 Network Connection to E2 us ing MODBUS Connecting an Eaton Breaker Panel to an E2 unit using MODBUS requires the E2 to be version 2 82 or above Contact Retail Solutions for upgrade informa tion if the controller is a version prior to 2 82 3 3 E2 PIB COM PORT ASSOCIATIONS E2 Enclosure Right Side COM Card Mounted _
Download Pdf Manuals
Related Search
Related Contents
Pioneer BDP-52FD Blu-ray Player User Manual Panasonic KX-T7625B Corded Phone sommaire - Expelec MODE D`EMPLOI DU BON DE RESERVATION - Over-blog Manual de Usuario User's Guide to CLShanCommands HUILE DURE fiche Document Technique d`Application Rock Up C Soudable Samsung USB메모리 16GB MANUALE UTENTE - Icon Heath & Fitness Copyright © All rights reserved.