1. The power behind competitiveness Delta UPS Amplon Family N Series Single Phase 1 2 3 kVA User Manual IN NELTA www deltapowersolutions com Smarter Greener Together Save This Manual This manual contains important instructions and warnings that you should follow during the installation operation storage and maintenance of this product Failure to heed these instructions and warnings will void the warranty Copyright 2015 by Delta Electronics Inc All Rights Reserved All rights of this User Manual Manual including but not limited to the contents information and figures are solely owned and reserved by Delta Electronics Inc Delta The Manual can only be applied to the operation or the use of this product Any disposition duplication dissemination reproduction modification translation extraction or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta Given that Delta will continuously improve and develop the product changes may be made to the information in this Manual at any time without obligation to notify any person of such revision
2. 18 Chapter 5 Operation Modes 19 5 1 Standby Mode 19 5 2 On line Mode 19 5 3 Bypass Mode 19 5 4 Battery Mode 19 5 5 Setup Mode 20 Chapter 6 Turn on Cold Start amp Turn off Procedures 22 6 1 Turn on Procedures 22 6 2 Cold Start Procedures 22 6 3 Turn off Procedures 22 Chapter 7 Alarm 23 Chapter 8 Optional Accessories 24 TT A DELTA Chapter 9 Troubleshooting 0 00 0 25 Chapter 10 Maintenance 0 0 28 10 1 UPS 28 10 2 Batteries 28 10 3 Fan econ 29 Appendix 1 Technical Specifications 30 Appendix 2 Warranty 32 Amplon N Series IV Chapter 1 Important Safety Instructions Chapter 1 Important Safety Instructions
3. 1 1 Safety Instructions Installation Warnings e Before installation and usage please read this User Manual thoroughly This helps you to use the product correctly and safely e Install the UPS in a well ventilated area away from excess moisture heat dust flammable gas or explosives e To avoid fire accidents and electric shock please install the UPS in a temper ate and humidity well controlled indoor area free of conductive contaminants For the temperature and humidity specifications please refer to Appendix 1 Technical Specifications e Leave adequate space at least 15cm around all sides of the UPS for proper ventilation Connection Warnings e The UPS must be well grounded due to a possible risk of current leakage e The installation of upstream and downstream protective devices is highly recom mended when the UPS is connected to the mains and the loads e The protective devices connecting to the UPS must be installed near the UPS and must be easily accessible for operation e Do not use extension cords to connect the UPS to an AC outlet e Do not plug the UPS s input power cord provided into its own output sockets e If you need to move the UPS or perform re wiring please turn off the AC input power and ensure that the UPS has been safely shutdown Otherwise the out put end might still be energized which might cause electric shock e The UPS output cable should be shorter than 10m 1 A NELTA Usage
4. noe Press the button for 0 1 second to view the next display IN OUT RUNTIME SET TEST BATT LOAD ap CC Press the button for 0 1 second to view the next display IN OUT RUNTIME SET TEST BATT LOAD e 17 A NELTA Chapter 4 Rear Panel gt a a a 2 3 kVA No Functions e manae or mini TVSS card optional Connect to your loads Connects to your computer You can monitor the UPS s status via your computer by installing the USB Port Virtual COM Port Driver and the UPSentry 2012 software please download from http 59 125 232 140 Amplon N Series 18 Chapter 5 Operation Modes Chapter 5 Operation Modes NOTE 1 Please refer to Chapter 3 Operation Panel to learn how to operate the operation panel and understand the display meaning 2 Each of the display diagrams shown in this chapter is for reference only Actual display depends on the operation of the UPS 5 1 Standby Mode After the UPS is connected to the AC utility it will supply power to the UPS and the batteries will be charged The default setting of the UPS is set in STANDBY mode 5 2 On line Mode In online mode the connected loads are supplied by the inverter which derives its power from the utility AC power and the UPS charges the batteries and provides power protection to its connected loads 5 3 Bypass Mode In bypass mode the critical l
5. Battery The audible alarm beeps once every 2 1 seconds Missing Weak Battery Battery Replacement Overload Overload_105 125 The audible alarm beeps once every 2 1 seconds Overload_125 150 The audible alarm beeps once every 0 6 seconds Fault The audible alarm beeps continuously for 5 seconds when the UPS detects an internal fault NOTE After reconnecting or replacing the batteries it might take a while for the UPS to switch off the alarm automatically If after a period of time the audible alarm still exists the user must manually initiate a battery test press and hold the button for 3 seconds and release it after you hear one beep to clear the alarm 23 A DELTA Chapter 8 Optional Accessories aE Function Dust Filter Prevents dust from entering into the UPS to ensure UPS reliability and to prolong product life Mini SNMP Card Monitors and controls the status of the UPS via a network system Mini Relay I O Card Increases the quantity of dry contacts Mini ModBus Card Lets the UPS have ModBus communication function Mini TVSS Card Lets the UPS have surge protection function NOTE 1 For detailed installation and operation of any accessory mentioned above please refer to the Quick Guide User Guide or Installation amp Operation Guide included in the package of the relevant optional accessory 2 If you want to buy any accessory mentioned above please contact your local dealer or c
6. bypass range and is not sufficient to let the unit operate in on line mode Output Icon Indicates the output status 1 ON There is output 2 OFF There is no output Battery Indicates the battery power status Power Icon 14 ON Battery power is on 2 OFF Output is not supplied by the battery power Standby llluminates when the UPS is operating in stand Mode Graph by mode Online Mode Illuminates when the UPS is operating in on line Graph mode 11 A NELTA Icon Naming Description No _ Battery llluminates when the UPS is operating in battery Mode Graph mode q Bypass llluminates when the UPS is operating in bypass Mode Graph mode 8 wtf Buzzer icon llluminates when the buzzer is disabled A Warning Icon 1 ON The unit is shut down due to an internal fault or an environmental fault The error code will appear on the 7 segment display Please refer to the following table for each error code and refer to 3 4 7 Segment Display for relevant 7 segment display information Error Code meanings Voltage E21 O P Short 2 Flashing When the icon is flashing it would be accom panied with other icon s to show you the according warning message s a There is no battery or battery replace ment is needed The UPS is overloaded Amplon N Series 12 Chapter 3 Operation Panel Description Load Level Indicates the status of load level Bar Graph 4 ON
7. OIT sre x v NOTE 1 If there is any damage or anything missing please immediately contact the dealer from whom you purchased the unit 2 If the UPS needs to be returned carefully repack the UPS and all of the accessories using the original packing material that came with the unit 7 A NELTA Chapter 3 Operation Panel AA NELTA BR LED Indicators 3 3 LCD Display inclduing 3 4 7 Segment Display 3 2 Multi function Buttons Description Indicates the output status ON green There is output OFF There is no output ON red The UPS detects an internal fault or an environmental fault You could refer to 3 3 LCD Display No 9 for more infor mation Flashing red The UPS has the following warning message s a g There is no battery or battery replacement is needed b A The UPS is overloaded Amplon N Series 8 Chapter 3 Operation Panel 3 2 Multi function Buttons Multi No function Button Description The button has multi function Please refer to the following for de tailed information 1 Turn on e In standby mode press and hold the button for 3 seconds release it after you hear one beep and the UPS will run in on line mode e Cold start When there is no AC input press and hold the but ton for 3 seconds release it after you hear one beep and the UPS will start up in battery mode 2 Battery Test Battery test can only be executed in on
8. circuit issue 2 Contact service persomnel RPO Remote shutdown After the remote shutdown Shutdown is executed from dry events are eliminated follow contact the turn on procedures to start up the UPS Battery Low The UPS transfers to Check the main AC source Shutdown run in battery mode and the input power cord s due to AC utility status abnormality however Contact service personnel the battery power is almost used up Amplon N Series 26 Chapter 9 Troubleshooting B About other problems that might happen Problem Possible Cause Solution Overload The UPS is Decrease your connected overloaded loads Battery Missing Internal battery cables 1 Contact service are not connected or personnel not firmly connected 2 Connect the internal battery cables and connect them firmly Weak Battery Batteries are Contact service personnel Battery damaged or battery Replacement life time is due Abnormal Input The AC input voltage 1 Check whether the when the AC icon or frequency is out of AC input voltage or A is flashing the acceptable bypass frequency is abnormal range 2 Contact service personnel NOTE If all possible causes are eliminated but the alarm still appears please contact your local dealer or customer service 27 A DELTA Chapter 10 Maintenance 10 1 UPS e UPS Cleaning Regularly clean the UPS especially the slits and openings to ensure that the air freely flows int
9. or changes Delta will make all possible efforts to secure the accuracy and the integrity of this Manual Delta disclaims any kinds or forms of warranty guarantee or undertaking either expressly or implicitly including but not limited to the completeness faultlessness accuracy non infringement merchantability or fitness for a particular purpose of the Manual Amplon N Series Il Table of Contents Table of Contents Chapter 1 Important Safety Instructions 1 1 1 Safety Instructions 1 1 2 Standard Compliance 4 1 3 Storage 4 Chapter 2 Introduction 5 2 1 General Overview 5 2 2 Exterior amp Dimensions 5 2 3 Package List 6 Chapter 3 Operation Panel 8 3 1 LED Indicators 8 3 2 Multi function Buttons 9 3 3 LCD Display 11 3 4 7 Segment Display 14 3 5 Flow Chart of the 7 Segment Display 16 Chapter 4 Rear Panel
10. 20 C 25 C or 68 F 77 F for at least one hour to avoid moisture condensing inside the UPS Amplon N Series 4 Chapter 2 Introduction Chapter 2 Introduction 2 1 General Overview The N series UPS is a single phase on line UPS providing reliable and consistent sine wave quality power to your electronic equipment It adopts the latest technol ogy and the highest quality components providing output power factor up to 0 9 and its efficiency in on line mode can reach at maximum 93 The UPS not only pro vides safe reliable and uninterrupted power to your sensitive electronic equipment at all times but also produces greater electronic power efficiency at less cost lts compact design does not occupy much space and is easy to use There are three different ratings 1kKVA 2kVA and 3kVA for your selection 2 2 Exterior amp Dimensions oO N 3 N 3 a 3 3 Y A SN E 45 3 79 M In Figure 2 1 1 kVA Figure 2 2 2 3 kVA Exterior 8 Dimensions Exterior amp Dimensions 5 A DELTA 2 3 Package List e For models UPS102N2000B035 1kVA UPS202N2000B035 2kVA 8 UPS302N2000B035 3kVA 1 kVA 2 3 kVA Item Q ty 1kVA 2 3KVA ole ey fo twin fare v TT Le comune 0 Lo omaromoraron Amplon N Series 6 Chapter 2 Introduction For models UPS102N2000B0B6 1kVA UPS202N2000B0B6 2kVA 8 UPS302N2000B0B6 3kVA Q ty 1kVA 2 3KVA 3 foe vl CA uw fre vy
11. 26701
12. 3 Fan Higher temperatures shorten fan life When the UPS is running please check if each fan works normally and make sure if the ventilation air can move freely around and through the UPS If not contact service personnel NOTE Please ask your local dealer or customer service for more maintenance information Do not perform maintenance if you are not trained for it 29 A NELTA Appendix 1 Technical Specifications Model N 1K N 2K N 3K Power Rating 1kVA 0 9KW 2kVA 1 8KW 3kVA 2 7KW Waveform Pure Sine Wave Nominal Voltage 220 230 240 Vac 175 280 Vac 100 load 80 175 Vac 50 100 load ETICO Voltage 99 Regulation 2 linear load 50 60 Hz 0 05 Hz lt 9 linear load Overload lt 105 continuous 105 125 1 minute Capability 125 150 30 seconds Cress Factor IEC C13x4 IEC C13x6 C19x1 Efficiency Online Mode Up to 93 Battery Voltage 24 Vdc 48 Vdc 72 Vdc Backup Time Standard Recharge Time Ahrs to 90 Amplon N Series 30 Battery Up to 7 Min Appendix 1 Technical Specifications Model N 1K N 2K N 3K Audible Noise lt 45 dBA lt 48 dBA lt 48 dBA Display LED indicators amp LCD display Communication Interfaces MINI Slot x 1 USB Port x 1 Dimensions 145 x 320 x 190 x 390 x 190 x 390 x WxDxH 225 mm 325 mm 325 mm Weight 18 6 Kg 24 4 Kg Operating Environment Temperature Relative Humidity 5 95 non condensing Phys
13. The bar graph illuminates according to the load level 2 Flashing The bar graph flashes when there is an overload situation Battery Level Indicates the status of battery level Bar Graph 1 ON The bar graph illuminates according to the re maining battery capacity 2 Flashing The bar graph flashes when a low battery situation occurs NOTE means that lt 10 no segment will illuminate 10 29 the 1 segment will illuminate 30 49 the first two segments will illuminate 50 69 the first three segments will illuminate 70 89 the first four segments will illuminate 90 100 all segments will illuminate 13 A NELTA 3 4 7 Segment Display Column A 7 Segment Display Column B NOTE You might need to read the word shown in Column A together with that in Cloumn B to understand the display meaning Icon Description IN 8 V When the above two words illuminate together it means input voltage IN 8 Hz When the above two words illuminate together it means input frequency OUT amp V When the above two words illuminate together it means output voltage OUT amp Hz When the above two words illuminate together it means output frequency RUN TIME RUNTIME amp MIN Mia When the above two words illuminate together it means the estimated remaining backup time Amplon N Series 14 Chapter 3 Operation Panel Description When the word SET illum
14. Warnings This is a class A product In a domestic environment this product may cause ra dio interference in which case the user is required to take adequate measures The UPS can be used to power computers and associated peripheral devices such as monitors modems cartridge tape drives external hard drives etc It is strictly forbidden to connect the UPS with 1 any regenerative type loads 2 any asymmetrical loads ex half wave rectifier To ensure reliable operation of the UPS and to protect the UPS from overheat ing the slits and openings in the UPS must not be blocked or covered Before usage you must allow the UPS to adjust to room temperature for at least one hour to avoid moisture condensing inside the UPS Do not pour and splash any liquid on the UPS Do not insert any object into the UPS s slits and openings Do not put beverage containers on or around the UPS When an emergency occurs press the OFF button E and release it after you hear one beep to turn off the UPS Cut off the input power to completely shut down the UPS Do not use any cleaning liquid or cleaning spray to clean the UPS Before clean ing please make sure that the UPS has been completely shut down the UPS s input power cord has been unplugged and the built in batteries have been dis connected All maintenance services must be performed by qualified service personnel Forbid opening or removing the cover of the UPS to avoid high voltage e
15. essed To fully turn off the UPS it is advised to unplug the input power cord In battery mode press and hold the button for 3 seconds re lease it after you hear one beep and the UPS will turn off its output Fault Clear When the UPS has a fault condition press and hold the button for 3 seconds release it after you hear one beep and the UPS will clear the fault condition and return to standby mode Besides the LCD will show the relevant error code For error code infor mation please refer to 3 3 LCD Display No 9 un The button has multi function Please refer to the following for de serue tailed information 1 Scrolling down Press the button for 0 1 second to go to the next display 2 Entering into the setup mode Press the button for 3 seconds and the UPS will enter into the setup mode For more information please refer to 5 5 Setup Mode Please note that only qualified service personnel can per form setup action NOTE When the backlight of the LCD is off you can press any button mentioned above to wake up the display and enable each button function Amplon N Series 10 Chapter 3 Operation Panel 3 3 LCD Display Description AC Icon Indicates the input source status 1 ON The AC input is within the acceptable bypass range 2 Flashing The AC input is out of the accep table bypass range but is still sufficient to let the unit operate in on line mode 3 OFF The AC input is out of the acceptable
16. ical 0 40 C NOTE 1 When the total load reaches 75 2 Please refer to the rating label for the safety rating 3 All specifications are subject to change without prior notice 31 A DELTA Appendix 2 Warranty Seller warrants this product if used in accordance with all applicable instructions to be free from original defects in material and workmanship within the warranty period If the product has any failure problem within the warranty period Seller will repair or replace the product at its sole discretion according to the failure situation This warranty does not apply to normal wear or to damage resulting from improper installation operation usage maintenance or irresistible force i e war fire natural disaster etc and this warranty also expressly excludes all incidental and consequential damages Maintenance service for a fee is provided for any damage out of the warranty period If any maintenance is required please directly contact the supplier or Seller WARNING The individual user should take care to determine prior to use whether the environment and the load characteristic are suitable adequate or safe for the installation and the usage of this product The User Manual must be carefully followed Seller makes no representation or warranty as to the suitability or fitness of this product for any specific application Amplon N Series 32 A NELTA Smarter Greener Together A 50132
17. inates it means that the UPS is in the setup mode You can set up the following items via the LCD For how to setup please refer to 5 5 Setup Mode Inverter voltage Inverter frequency Bypass range Buzzer Overload alarm When the word TEST flashes it means that the UPS is under test When the two words TEST and BATT flash together it means that the UPS is under battery test BATT amp When the above two words illuminate together it means the remaining battery capacity BATT amp V When the above two words illuminate together it means battery voltage LOAD amp When the above two words illuminate together it means how much the total load has occupied the rated capacity LOAD amp KVA When the above two words illuminate together it means how much kVA the total load is LOAD amp KW When the above two words illuminate together it means how much kW the total load is LOAD amp 8 A When the above word LOAD unit and icon A flash together it means that the UPS has an overload situation 15 A DELTA No Icon Description Means voltage Means percentage Ha Means frequency Means kVA NOM Means kW wn Means minute Means the UPS s internal temperature 3 5 Flow Chart of the 7 Segment Display The following flow chart helps you to understand how to go through each display sc
18. lectric shock You must contact qualified service personnel if either of the following events oc cur 1 Liquid is poured or splashed on the UPS 2 The UPS does not run normally after this User Manual is carefully observed NOTE If you use the UPS in an area that generates or incurs dust you should install a dust filter in the UPS to ensure normal product life and function Amplon N Series 2 Chapter 1 Important Safety Instructions Battery Warnings Rating Batteries Q ty Type Voltage UPS Built in A Battery Battery 24Vdc 9Ah sealed The UPS cannot battery battery pack 72Vdc EN Yes lead acid connect any external NEC 72Vde e Keep the batteries away from heat sources Do not open or mutilate the batter ies The released electrolyte is harmful to the skin and eyes and may be toxic A battery can present a risk of electric shock and high short circuit current e Servicing of batteries must be performed or supervised by qualified service per sonnel knowledgeable in batteries and the required precautions Keep unauthor ized personnel away from batteries The risk of electric shock and short circuit current is possible when the batteries are connected to the UPS Before maintenance disconnect all batteries to cut off the battery power For battery replacement only use the same number and type of batteries Observe the following before replacing the batteries 1 Remove watches rings or other
19. line mode e For automatic regular battery test you must install the Virtual COM Port Driver and the UPSentry 2012 software please download from http 59 125 232 140 or configure the SNMP card optional or ModBus card optional For manual battery test please press and hold the button for 3 seconds release it after you hear one beep and the UPS will transfer to run in battery mode and perform a 10 second battery test If the test result is ok the LCD will show PAS and the UPS will return to on line mode If the test result is abnormal the LCD will show FAL the LED UN will flash the warning icon A and no battery battery replacement icon will illuminate and the UPS will return to on line mode m 3 Buzzer Off When the buzzer is on press the button for 0 1 second to turn the buzzer off Please note that the buzzer will automatically turn on when a new alarm occurs 4 Confirmation In setup mode press the button for 0 1 second to confirm your parameter setup 9 A DELTA Multi No function Description Button un The button has multi function Please refer to the following for de OFF tailed information 1 Turn off e In on line mode press and hold the button for 3 seconds release it after you hear one beep and the inverter will be off and the UPS will transfer to run in standby mode The UPS will keep charging the batteries when the UPS is in standby mode even though the button has been pr
20. metal objects 2 Use tools with insulated handles 3 Wear rubber gloves and boots 4 Do not lay tools or metal parts on the top of batteries 5 Before battery removal replacement or installation disconnect any circuit connected to the batteries e Do not connect the batteries in reverse otherwise a risk of electric shock or fire accidents might occur WARNING The risk of electric shock and short circuit current is possible when the batteries are still connected to the UPS even though the UPS is disconnected from the mains Do not forget to cut off the battery source before maintenance 3 A NELTA 1 2 Standard Compliance e CE e RCM EN 62040 1 EN 62040 2 Category C2 1 3 Storage e Prior to installation If the UPS needs to be stored prior to installation it should be placed in a dry area The allowable storage temperature is between 15 C and 50 C 5 F 122 F e After usage Press the E button make sure the UPS is shutdown disconnect the UPS from the utility power remove all equipment from the UPS and store the UPS in a dry and well ventilated area at a temperature between 15 C and 50 C 5 F 122 F Idle batteries must be recharged fully approximately every three months if the UPS needs to be stored for an extended period of time The charging time must not be less than 24 hours each time NOTE After storage and before start up of the UPS you must allow the UPS to adjust to room temperature
21. mp Turn off Procedures NOTE Please refer to Chapter 3 Operation Panel to learn how to operate the operation panel and understand the display meaning 6 1 Turn on Procedures After the UPS is connected to the AC utility the AC utility supplies power to the UPS The UPS is initially set in STANDBY mode To turn on the UPS press and hold the button for 3 seconds and release it after you hear one beep 6 2 Cold Start Procedures Even when there is no utility power you can still turn on the UPS Just press and hold the button for 3 seconds release it after you hear one beep and the UPS will start up and run in battery mode 6 3 Turn off Procedures 1 In on line mode if you want to turn off the UPS press and hold the O button for 3 seconds and release it after you hear one beep The inverter will turn off and the UPS will transfer to standby mode The UPS will keep charging the batteries when the UPS is in standby mode even though the button has been pressed To fully turn off the UPS it is advised to unplug the input power cord 2 In battery mode if you want to turn off the UPS press and hold the s button for 3 seconds and release it after you hear one beep The UPS will turn off its output Amplon N Series 22 Chapter 7 Alarm Chapter 7 Alarm No Condition Alarm EN Battery Mode The audible alarm beeps once every 2 1 seconds ea Low Battery The audible alarm beeps once every 0 6 second
22. nd at the same time the LCD will go to the next setup item You can skip to the next setup item by pressing the cancel button for 0 1 second In setup mode press the scrolling button o for more than 3 seconds the LCD will go back to the original display In setup mode if you don t press any button for more than 2 minutes the LCD will exit from the setup mode and go back to the original display automatically For some settings they can t be set in certain operation modes Please refer to the table below for relevant information Standby On line Bypass Battery Setup Item Mode Mode Mode Mode Inverter Voltage Setup Inverter Frequency Setup IrveriseVolegs Setup v Inverter Frequency Setup Y Bypass Range Setup Amplon N Series 20 Chapter 5 Operation Modes Standby On line Bypass Battery Mode Mode Mode Buzzer Setup Overload Alarm Setup NOTE Please note that only qualified service personnel can perform setup action Setup Item Setup Mode Flow Chart Original Display O T gt 3 seconds SETUP Inverter Voltage Setup SETUP i gt a ww T gt 3 seconds SETUP ON T gt 0 1S T 0 1S T gt 0 1S OFF SETUP O C T gt 3 seconds BEE SETUP ON T gt 0 1S T 0 1S T gt 0 1S SETUP T gt 3 seconds O SETUP ON T 0 1S T gt 0 1S SETUP T gt 3 seconds SETUP T gt 3 seconds 21 A NELTA Chapter 6 Turn on Cold Start a
23. o the UPS to avoid overheating If necessary use an air gun to clean the slits and openings to prevent any object from blocking or covering these areas e UPS Regular Inspection Regularly check the UPS every half year and inspect 1 Whether the UPS LEDs and alarm function are operating normally 2 Whether battery voltage is normal If battery voltage is too high or too low find the root cause 10 2 Batteries The N series UPS uses sealed lead acid batteries Though the typical battery life cycle is 3 5 years the battery life depends on the temperature the usage and the charging discharging frequency High temperature environments and high charging discharging frequency will quickly shorten the battery life The UPS does not require maintenance by the user however the batteries should be checked periodically Please follow the suggestions below to ensure a normal battery lifetime e Keep the usage temperature at 20 C 25 C e idle batteries must be fully recharged every three months if the UPS needs to be stored for an extended period of time Please fully charge the batteries internal and external until the Battery Level Bar Graph E shown on the UPS s LCD is fully on NOTE If the UPS s internal batteries need to be replaced please contact qualified service personnel During battery replacement the loads attached to the UPS will not be protected if input power fails Amplon N Series 28 Chapter 10 Maintenance 10
24. oads are directly supplied by the utility power and the batteries are charged 5 4 Battery Mode When the UPS is operating during a power outage the batteries provide DC power which maintains inverter operation to support the connected critical loads You can install the Virtual COM Port Driver and the UPSentry 2012 software please download from http 59 125 232 140 or configuare the SNMP card optional or ModBus card optional to monitor and estimate the battery remaining capacity before or during an AC power failure For more information about the SNMP card optional or ModBus card optional please refer to its user manual NOTE You can only enable SHUTDOWN AFTER function in battery mode For information about SHUTDOWN AFTER function please contact service personnel 19 A DELTA 5 5 Setup Mode Press the scrolling button a for more than 3 seconds and the LCD will go into the setup menu Please note that only qualified service personnel can perform setup action In setup mode you can set up the following items 1 2 3 4 5 Inverter voltage Inverter frequency Bypass range Buzzer Overload alarm For setup procedures please refer to the following 1 Press the scrolling button UB for more than 3 seconds to enter into the setup mode Press the scrolling button for 0 1 second to change the parameter SETU Press the confirmation button for 0 1 second to confirm your parameter a
25. reen Here we take Standby Mode as an example Each of the display diagrams shown in below is for reference only Actual display depends on the operation of the UPS After this screen appears around 10 seconds the scrolling function will be active The scrolling button is Y SETUP Amplon N Series 16 IN OUT RUNTIME SET TEST BATT LOAD CUA COLO AN Press the button for 0 1 _ IN OUT RUNTIME SET TEST BATT LOAD c c UI Mowe Press the a button for 0 1 Chapter 3 Operation Panel Press the BS button SET TEST BATT LOAD for 0 1 second to view the next display IN OUT RUNTIME Press the e button for 0 1 SETUP second to view the next display second to view the next display IN OUT RUNTIME SET TEST BATT LOAD a ce gt WI I KW a Press the button for 0 1 second to view the next display second to view the next display IN OUT RUNTIME SET TEST BATT LOAD am eD Vv UTA E QUO Press the 8 button for 0 1 SETUP IN OUT RUNTIME SET TEST BATT LOAD QUA a Press the a button for 0 1 second to view the next display second to view the next display IN OUT RUNTIME SET TEST BATT LOAD Press the BS button for 0 1 IN OUT RUNTIME SET TEST BATT LOAD 2 v ILII Press the Oo button for 0 1 second to view the next display second to view the next display IN OUT RUNTIME SET TEST BATT LOAD UN gt KW
26. ustomer service Amplon N Series 24 1 Chapter 9 Troubleshooting Chapter 9 Troubleshooting When a problem occur please check if the following situation exists before contacting Delta service personnel e ls the main input voltage present Please have the following information ready if you would like to contact the Delta service personnel e Unit information including model serial number etc e An exact description of the problem The more detailed description of the problem the better When you see the following problems occur please follow the solutions shown below A About the error codes shown on the 7 segment Display Error Code a Charger is damaged Contact service personnel Fault Temperature The UPS temperature Check whether the UPS s is out of range ventilation is normal Meaning Possible Cause Solution Decrease the loads 3 Check whether the fan s run s normally Clean the filters if you have installed any DC BUS The UPS has Contact service personnel High Low abnormalities 25 A NELTA Error Gone Meaning Possible Cause Solution Inverter The UPS has Contact service personnel Fault abnormalities DC DC Fault The UPS has Contact service personnel abnormalities Abnormal The UPS has Contact service personnel Output abnormalities Inverter Voltage O P Short Output has a short 1 Check whether the output circuit issue has a short