Home
        Centaurus Prime P1 Gateway
         Contents
1.        9600 or 19200  possibly  newer or non Siemens         0     lt means that nothing is on that trunk gt      BAUD1  4800     BAUD2  4800     BAUDS  4800     BAUD4  0   77   e e   m   _    IP  ADDR  is used for the IP address of what you want this box to be            Andit MUST match the SOCKET CFG IP Address               IP ADDR  192 168 0 204               BACNET NETWORK  is used for what BACnet network number we are on    e 1042          BACNET OFFSET  is what we will add to the local device numbers  1  240         to yield the BACnet object ID instances of each mapped BACnet    device     ues 1042000    10    Creating and Downloading the SOCKET CFG file    The following is an example of the SOCKET CFG file that must be edited to match your particular  installation  if you are using the Modbus TCP or BACnet IP protocols  If you ate not doing an Ethernet  connection  this text file is irrelevant  and can be ignored and left as it comes from the factory     ONLY ONE LINE SHOULD BE CHANGED    the line that begins with    ip address   Here is an  example           CTUyP cig      SOCKET CFG is the configuration file to be executed by SOCKETP EXE    ip address 192 168 0 204      interface pdr if0 dix 1500 10 0x60       The following line will just display the info for easy verification      ip address   _  The following lines set TCP IP parameters  commented out in this case      Hip ttl 15      tcp mss 1460      tcp window 2920    The    ip address 192 168 0 204  line sho
2.    8 2006 VERSION 1 2       Centaurus Prime             CENTAURUS PRIME  Integrations  Custom Programming  Consulting          p 1 22  Gateway Guide    8 2006 VERSION 1 2    INTEGRATIONS  CUSTOM PROGRAMMING  AND CONSULTING       P1    Gateway Guide       2006 by Centaurus Prime  4425 Cass Street   Suites B C  San Diego  CA  Phone 858 270 4452   Fax 858 270 7769    www centaurusprime com    Table of Contents    Introduction i    CHAPTER 1    Gateway Installation  Basic Information 1    Summary 1  Single Board Computer Basics 2  Connecting Power to the Gateway 3  Connecting Siemens P1 Trunks to the  Gateway 3  Connecting To the Modbus Master 4  Configuring the CS485 5  RS485 Communications 6  RS422 Communications 6  RS232 Communications 7  Note about Removing the CS485 7  Connecting to a BACnet IP Network 7  Gateway Overview and Identification 8  CHAPTER 2   Commissioning the Gateway with the   Local user Interface 9  Creating and Downloading the  GATEWAY INI file 10  Creating and Downloading the  SOCKET CFG File 11  Local Mode Menu Options 11    Auto Discovery and Database Generation 12       Summary    Menu Options 14       Devices    Menu Options      Point    Menu Options      Control    Menu Options      Watch    Menu Options   Uploading and Downloading files to the  Gateway   Setting Up The Modbus Driver   Setting Up The BACnet System    TEMPLATE Files    Index    15  17  20  24    25   26   27  28    32    CENTAURUS PRIME Ci i    Gateway Installation Basic  Information  
3.    AO   AO   AO   AO   AI   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   AO   BO   AO   AO   AO   BO   AO     4  ROOM TEMP n 48  0 25  DEG F   Room Temperature    5  HEAT COOL   COOL  HEAT       Heating Cooling Status     6  DAY CLG STPT  48   25  DEG F  W Occupied Cooling Setpoint    7  DAY HTG STPT  48  0 25  DEG F  W Occupied Heating Setpoint    8  NGT CLG STPT  48  0 25  DEG F  W Unoccupied Cooling Setpoint   9  NGT HTG STPT  48  0 25  DEG F  W Unoccupied Heating Setpoint   15  SUPPLY TEMP   37 5  0 5  DEG F     Supply Temperature     29  DAY NGT   DAY  NIGHT    W Occ Unocc Control   31  CLG FLOW MIN  0  4  CFM  W Cooling Flow Minimum    32  CLG FLOW MAX   33  HTG FLOW MIN   34  HTG FLOW MAX   35  AIR VOLUME    37  MTR3 COMD                 CFM  W Cooling Flow Maximum     w Heating Flow Minimum i  CFM  W Heating Flow Maximum          d       co  m     x    CFM     Air Volume  PCT WO Motor3 Command    61  COOL TEMP  62  HEAT TEMP  63  CLG P GAIN  64  CLG I GAIN  67  HTG P GAIN  68  HTG I GAIN  71  FLOW P GAIN  72  FLOW I GAIN    DEG F  W Heat to Cool Switch Temp  Ref  DA temp  DEG F  W Cool to Heat Switch Temp  Ref  DA temp  0 25  P GAIN  W Cooling P Gain    0 001  I GAIN  W Cooling I Gain j  0 25  P GAIN  W Heating P Gain A  I GAIN  W Heating I Gain      0 05  P GAIN  W Flow P Gain    0 001  I GAIN  W Flow I Gain F    UYUP EPEPPPPP PPP    0  38  MTR3 POS 0 PCT   Motor3 Position Use as AI  48  DMPR COMD 0 PCT WO Damper Command  
4.   Summary    Th section will help to give a basic overview and quick summary of the procedures needed to install  the    P1    Gateway Panel  Detailed instructions are also provided later in this guide  The Centaurus  Prime    P1    Gateway allows any front end system  Modbus Master or BACnet IP  that communicates  using the either industry standard Modbus or BACnet protocols to communicate to Siemens  also known as  Staefa  Landis  amp  Staefa  Landis  amp  Gyr  Powers  or even MCC Mark Controls  for real old timers  P1 trunk  field equipment  The P1 trunk field devices supported  MPU  DPU and TEC devices  will appear to the  front end system as a series of Modbus SLAVE devices or BACnet Devices  Real time point data from the  Siemens P1 trunk controllers is then mapped to equivalent registers  coils  and bits on the Modbus system  or  as AL  BI  AO  and BO objects on the BACnet system  All operations are transparent to the user and host  computet        ICON  REN Connections to the    P1    Gateway are simple and clearly marked  They consist of       7 Valuable information  poser Supply  120 Volts AC  optionally  220 or 240 Volts AC   e Siemens P1 trunks  up to four  these are RS 485 multi drop trunks   e Modbus RTU Network   RS 485 or IP   or BACnet IP Network      Local Mode Port for commissioning via Laptop Computer    All Hardware necessary to connect the Gateway to the P1 devices is included in the 16  X 14  X 8  plastic  cabinet that is easily mounted in a convenient 
5.  121 is field device  subdevice  type 42 0 52     BACnet ID  15  AI  AUX TEMP UNRELIABLE       Devices    Menu Options    The Devices menu is used to display all of the configured devices  A  or to    target    a specific device and get  data about it      S elect  Target a specific device  This allows you to work with ONE device  rather than them all  This is the  FIRST thing you do when you want to look at one point  on one device  or control a point  First  you select  the device  then go to the POINT menu  to select the point   And if you want to control it  then go to the  CONTROL menu  and issue controls to it     Here   s how you would select device  2  the second device on trunk  1        DEV   S elect   A ll   D etail   O ff line   C omm Stats   X  it  S       DEV  You may select a DEVICE to target into     Enter a DEVICE number  1  240 or 0 for all   2      Device  2 is now the targeted device      A ll  View all configured devices  This is just a summary of the current status of all devices  In the following  example  Device  62 is dead  but all the others are doing just fine       DEV   S elect   A ll   D etail   O ff line   C omm Stats   X  it  A      41 TagID   P1411  TRUNK 1  is ON LINE  amp  RELIABLE    2 TagID   P1 42  TRUNK 1  is ON LINE  amp  RELIABLE    15    _  61TagID   P1  1  TRUNK 2  is OFF LINE    MUST INIT gt   SlowScan       62TagID   P1  2  TRUNK 2  is ON LINE  amp  RELIABLE      121 TagID   P1  4  TRUNK 3  is ON LINE  amp  RELIABLE    122 TagID   
6.  Z 0 5  DEG F  W Heat to Cool Switch Temp  Ref  DA temp  62  HEAT TEMP    S   0 5  DEG F  W Cool to Heat Switch Temp  Ref  DA temp  63  CLGP GAIN   0 25  P GAIN  W Cooling P Gain    64  CLG I GAIN   0 001  I GAIN  w Cooling I Gain  65  CLG D GAIN   2  D GAIN  W Cooling D Gain  66  CLG BIAS 5 0 4  PCT  W Cooling Bias                                        eOOOOOOOOOOOcoOooooooouuwuocoocoooooo       74  FLOW BIAS 0 4  PCT  W Flow Bias    75  FLOW 0 25  PCT   Flow  Use as AI  76  CTL FLOW MIN  4  CFM     Control Flow Min Calc  Use as AI  77  CTL FLOW MAX  4  CFM     Control Flow Max Calc  Use as AI  78  CTL TEMP   4 0 25  DEG F  W Control Temp Calc  Use IFF Rm Tmp fails  79  CLG LOOPOUT   3 0 4  PCT   Cooling Loop Output Calc  Use as AI  80  HTG LOOPOUT   j 0 4  PCT   Heating Loop Output Calc  Use as AI  84  DMPR STATUS   CAL  RECAL       Calibration Adjustment  Use as BI  87  CAL MODULE   NO  YES 5    Calibration Mode  Autozero enabled  91  TOTAL VOLUME  4  CFM  W  Total Volume  Totalized  Reset to 0  92  CTL STPT 5 48  0 25  DEG F   Control Setpoint Calc  Use as AI  93  FLOW STPT   0  0 25  PCT     Flow Setpoint Calc  Use as AI  94  CAL AIR g NO  YES    W Calibration Air  Calibrates velocity  95  CAL SETUP   0  i CODE     Calibration Setup  Danger  Config ONLY  96  CAL TIMER 3 0  d HRS     Calibration Timer  Danger  Use as AI  97  DUCT AREA   0  0 025  SQ  FT   Duct Area  Danger  Config ONLY  98  LOOP TIME 0  SEC   Loop Time  Use as AI  99  ERROR STATUS  0  1 CODE   Error Stat
7.  devices in a very simple fashion  Devices 1 through 60 on trunk 1  Devices 61 through 120 on  trunk 2  Devices 121 through 180 on trunk 3  and Devices 181 through 240 on trunk 4  But you might not  want to use those as your Device    Instance numbers   if you have some other addressing scheme  or a  number of these gateways  on a system  The BACNET OFFSET allows you to have these devices show up    as a different set of Instances rather than just 1 to 240  The number that you specify is added to the internal  device number  Hence  if your offset is 5000  and you are interested in  local  device  84  the fourth gizmo  on trunk  2   the BACnet system sees this device as Instance   5084     Also  if you have multiple gateways on one system  you will need to have each of them be a different Network  Number  set via the BACNET NETWORK parameter in the Gateway ini file   This is so that there is no  confusion between the devices on one gateway and any others  they all could have local device numbers be  the same  by having different Network Numbers for each gateway  they become unique  as far as the  underlying BACnet protocol works     _C   gt type gateway ini           BAUDO  is used for the HOST CHANNEL Baud Rate  the Modbus RTU   Protocol  and Parity       settings N None  O Odd  E Even   oi     BAUDO  9600 N   UH   pa            Required for 4 ports  Set the baud rate  set to 0 if channel unused                 Valid baud rates are  4800     standard Siemens Landis baud rate 
8.  gt    AI  4  ROOM TEMP   48  0 25  DEG F   Room Temperature i   BO  5  HEAT COOL   COOL  HEAT       Heating Cooling Status     AO  6  DAY CLG STPT  48   25  DEG F  W Occupied Cooling Setpoint     AO  7  DAY HTG STPT  48  0 25  DEG F  W Occupied Heating Setpoint     AO  8  NGT CLG STPT  48  0 25  DEG F  W Unoccupied Cooling Setpoint    AO  9  NGT HTG STPT  48  0 25  DEG F  W Unoccupied Heating Setpoint    AO  11  RM STPT MIN   48  0 25  DEG F  W Room Setpoint Minimum  If dial exists   AO  12  RM STPT MAX   48  0 25  DEG F  W Room Setpoint Maximum  If dial exists   AI  13  RM STPT DIAL  48  0 25  DEG F     Setpoint Dial Setting  If dial exists   BO  14  STPT DIAL 5 NO  YES    W Setpoint Dial Control  If dial exists   AI  15  SUPPLY TEMP   37 5  0 5  DEG F     Supply Temperature     BO  18  WALL SWITCH   NO  YES    W Wall Switch Control  if DI2 used this way  BI  19  DI OVRD SW   OFF  ON       Override Switch Status  if existant   AO  20  OVRD TIME 5 0  L  HRS  W Override Time  if existant   BO  21  NGT OVRD   DAY  NIGHT       Night Override Control  Use as BI   BI  24  DI 7   OFF  ON 2c DE 2  If not used for   18  BO  29  DAY NGT i DAY  NIGHT    W Occ Unocc Control j   AO  31  CLG FLOW MIN  0  4  CFM  W Cooling Flow Minimum     AO  32  CLG FLOW MAX  0  4  CFM  W Cooling Flow Maximum i   AO  33  HTG FLOW MIN  0  4  CFM  W Heating Flow Minimum      AO  34  HTG FLOW MAX  0  4  CFM  W Heating Flow Maximum H   AI  35  AIR VOLUME   0  4  CFM   Air Volume f   AO  36  FLOW COEFF   0  
9.  is different in the two protocol systems  register  addresses versus object type instances              MB Reg 30099  AT          MB Reg 30098  AT          MB Reg 30097  AT          MB Reg 30096  AT          MB Reg 30095  AT          MB Reg 10394  BI           MB Reg 30092  AT         MB Reg 10387  BI          MB Reg 30059  AT         MB Reg 30058  AT          MB Reg 30057  AD     _   MB Reg 30056  AT          MB Reg 30055  AI          MB Reg 30053  AI          MB Reg 30052  AT          MB Reg 30051  AT          MB Reg 30049  AT          MB Reg 30048  AT        MBReg 446  BO       MBReg 429  BO         MB Reg 10325  BI           MB Reg 10324  BI           MB Reg 40120  AO           MB Reg 10319  BI            MB Reg 10318  BI          MBReg 414 BO          MB Reg 40112  AO          MB Reg 40111  AO          MB Reg 40109  AO          MB Reg 40108  AO          MB Reg 40107  AO          MB Reg 40106  AO          MB Reg 5  BO         MB Reg 30004  AI          MB Reg 30002  AT         MB Reg 30001  AT                   DEVICE  2 is field device subdevice type 42 0 2023    TagID   TEC  42   has 41 objects under it  Ist one at  55    ERROR STATUS  Fld   LOOP TIME  Fld   DUCT AREA  Fld    CAL TIMER  Fld     CAL SETUP   Fld     CAL AIR  Fld     CTL STPT  Fld     CAL MODULE   Fld     DO DIR REV   Fld   MTR SETUP   Fld     DPR2 ROT ANG  Fld   DPR1 ROT ANG  Fld   MTR2 TIMING   Fld     MTR2 POS   Fld   MTR2 COMD   Fld     MTR1 TIMING   Fld     MTR1 POS  Fld   MTR1 COMD   Fld     DO 6  Fl
10.  or RS 485 half duplex  COM2  address  0x2F8  IRQ 3 115200 baud maximum   Serial Port 3 6   RS 232 with handshake lines  16554 UART COM3 6 115200 baud  maximum 16 byte Rx and Tx FIFO   Digital I O   5 Bits  P1 4 P1 7  amp  P3 1  Pin configurable as input or  output  8mA souce sink   Watchdog   Hardware  1 6 second timeout Generates board wide Reset   Clock Calendar   Hardware  battery backup   Supply Power   7 34V unregulated DC  10   3 Watts   Humidity   5    90   non condensing   Temperature    4 to  158   F   20 to  70   C    Weight   53 oz  1 5 kg    Dimensions   8 30  x 6 76  x 2 28   210 8mm x 171 7mm x 57  9mm     Connecting Power to the Gateway    Power connections are made by first removing the 2 screws on either side of the power terminal block  enclosure  Then  you remove the temporary power cord  supplied for you  actually left in from our internal  burn in testing   Connect your PERMANENT power source to the HOT  Black   NEUTRAL  white  and  GROUND  green  wires  Follow the diagram below for proper terminations         120 Volt Neutral  Picture 1 0  Connecting the power  Ground       120 Volt Hot    Connecting Siemens P1 Trunks to the Gateway    Typically  Siemens P1 trunks  possibly several trunks  are connected to  building level  Siemens controllers   MBC  SCU  MEC  or the like  Most of these devices have up to three P1 trunks  labeled FLN1  FLN2  and  FLN3  the    FLN    stands for    Floor Level Network   The se are RS 485 multi drop trunks  These trunks  fr
11.  to your PC  edit it to add a line about the missing controller  and then upload the modified file  back into the Gateway  See    Uploading and Downloading files to the Gateway       12     7 Note 3  MPU and DPU devices only know about addresses 1 to 32  They will respond to  commands at MULTIPLES of 32  i e   an MPU at address  1 also responds at address  33   65   and  97      The auto discover mode understands this  and if it finds an MPU or DPU at any  address higher than 32  it flags it as being a    duplicate    and ignores it ever more      7 Files that are in the Gateway on drive C   and their purpose  are     STARTUP  BAT   Startup Batch file   GATEWAY  INI   Sets all baud rates  IP Address  BACnet parameters  SOCKET CFG   IP Configuration file   SOCKETP  EXE   TCP IP Socket stack   NE2000 COM   Ethernet Driver    TRN GWAY EXE  Does all the magic  DATABASE DAT   Database that is created from Save Discovery    DISC_1 TXT   Trunk  1 Auto Disc File   DISC 2  TXT   Trunk  2 Auto Disc File   DISC  gt   TXT   Trunk  3 Auto Disc File   DISC 4  TXT   Trunk  4 Auto Disc File   CONFIG  TXT   Device configuration file created when the  Auto Discovery files are merged   XPING EXE   Test program to verify Ethernet connectivity       Help   S ummaty   D evice   P oint   C ontrol   W atch   A utoDisc   X  it  A  AUT   A uto Discovety   S ave Discovery   X  it  S      AUTODISCOVERY  You may SAVE and MERGE all trunk auto discovery maps   i o ARE YOU SURE  If so  enter  Y  for YES  an
12.  value of the object will be   0    Adding to Control Queue  at  2  Device  6  AO  114    Queued Control  Trunk  1  Device  6  AO 4114    to  70 000 pri   4     R elease  This option will let you release control for the selected point at your selected priority level  valid for  the BACnet variant of the Gateway  only        RLS  Are you sure that you want to RELEASE this object     ARE YOU SURE  If so  enter Y for Yes  and then the ENTER key    or any other keys if you do NOT want to RELEASE the object    Y      The object AO  114 has been released from Priority  4      D etail  will display details associated with the selected point  Let s first look at a Modbus version of an  object   s detail       CTL   S elect   P riority   C ontrol   R elease   D etail   X  it  D    MB Address  30001  Type   AL  Zone Temperature   Field Unit   Subunit  4  0 Field Address  30001  Object Flags  bits     0 Error Counter  0  Field In   Out Counts  0  0 Field Value  0 000  i Field Hi   Lo Range  255 000   0 000 Eng  Units   Deg F     s And this is what is displayed for an example BACnet controllable object that has been released from all  controls  note the line that says    No elements in priority control array          CTL   Select   P riority   C ontrol   R elease   Detail   X  it  D    BACnet Obj ID 113  Type   AO    Object Name     COOL FLOW MAX SPT     Description     Maximum Cooling Flow SPT        No elements in priority control array     BACnet Relinquish Default Value  65 000  Fiel
13. 0 01  CFM     Flow Coeff   Calib    Danger  Config ONLY  AO  37  MTR3 COMD   0  0 4  PCT WO Motor3 Command      AO  38  MTR3 POS   0  0 4  PCT   Motor3 Position  Use as AI   AO  39  MTR3 TIMING   0  iL  SEC   Motor3 Timing Setup  Danger  Config ONLY  BO  41  DO1 A OFF  ON   WO DO 1  Usually w DO2  Motor1   BO  42  DO2   OFF  ON   WO DO 2  Usually w DO1  actuator   BO  43  DO 3    i OFF  ON   WO DO 3    Usually w DO4  Motor2   BO  44  DO 4   OFF  ON   WO DO 4  Usually w DO3  actuator   BO  45  DO 5   OFF  ON   WO DO 5  Usually w DO6  Motor3   BO  46  DO 6 n OFF  ON   WO DO 6  Usually w DO5  actuator     67  HTG P GAIN  68  HTG I GAIN  69  HTG D GAIN  70  HTG BIAS  71  FLOW P GAIN  72  FLOW I GAIN  73  FLOW D GAIN    0 25  P GAIN  W Heating P Gain   0 001  I GAIN  W Heating I Gain   2  D GAIN  W Heating D Gain  0 4  PCT   W Heating Bias  0 05  P GAIN  W Flow P Gain  0 001  I GAIN  W Flow I Gain  2  D GAIN  W Flow D Gain    48  DMPR COMD   0 4  PCT WO Damper Command     49  DMPR POS   0 4  PCT     Damper Position  Use as AI  51  MTR1 TIMING  L SEC   Motorl Timing Setup  Danger  Config ONLY  52  MTR2 COMD P 0 4  PCT WO Motor2 Command    53  MTR2 POS s 0 4  PCT   Motor2 Position  Use as AI  55   MTR2 TIMING  1  SEC   Motor2 Timing Setup  Danger  Config ONLY  56  DMPR ROT ANG  l DEGREES    Damper Rotation Angle  Danger  Config ONLY  58  MTR SETUP 5 E  CODE   Motor Setup  Danger  Config ONLY  59  DO DIR  REV   1 0 DIRCT   Forward Reverse Setup  Danger  Config ONLY  61  COOL TEMP s  
14. 3  25   Watch  i  11  24    32    
15. 49  DMPR POS 0 PCT     Damper Position  Use as AI  52  MTR2 COMD 0 PCT WO Motor2 Command y  53  MTR2 POS L PCT   Motor2 Position  Use as AI  0    UJUJ  NN    Soon or Ooooooooooouuocooooooooo    e  ce  eo  nd    75  FLOW 0 25  PCT     Flow  Use as AI  76  CTL FLOW MIN  4  CFM     Control Flow Min Calc  Use as AI  77  CTL FLOW MAX  4  CFM   Control Flow Max Calc  USe as AI  79  CLG LOOPOUT   0 4  PCT   Cooling Loop Output Calc  Use as AI  80  HTG LOOPOUT   0 4  PCT   Heating Loop Output Calc  Use as AI  84  DMPR STATUS   CA RECAL       Calibration Adjustment  Use as BI  91  TOTAL VOLUME  4  CFM  W Total Volume  Totalized  Reset to 0  92  CTL STPT   4 0 25  DEG F     Control Setpoint Calc  Use as AI  93  FLOW STPT g 0 25  PCT     Flow Setpoint Calc  Use as AI  94  CAL AIR 5 N YES    W Calibration Air  Calibrates Velocity  99  ERROR STATUS  uM CODE   Error Status Code  Use as AI    The advantage here is that it   s only about half the number of points  Thus  the scan is twice as fast  This is  important  for a system that gets new values from the TECs only for those points that have COS COV  enabled on them  a closely kept Siemens secret  as far as we can tell   Those that don t send COS COV  values up when data changes must be scanned  and that may take many minutes  The faster the scan  the  faster you will get these scanned  non COS COV point  values  Keep this in mind     30    Another thing that you can do is to send down    custom    templates for a particular device  Say t
16. AI    Now  let s say that you know a lot about this device  Turns out there is no room t   stat  AI  4  where the  Room Temperature normally is   is actually used for the Supply temperature  and AI  3 is used for the return  temperature  DO  2 and DO  3 are unused  and the direct reverse setup point is irrelevant  We can modify  this template to be    special     for whatever TEC device that it is for  and download it to the Gateway  We  might have modified this for TEC  15 on Trunk  2  and we would create a special    custom template  called     TPL 2 15 CSV   the    2    being for trunk  2  the    15    being for TEC  15   Our custom file would be  modified to look like this        Application  2384   TPL 2 15 CSV   for TEC  15 on Trunk  2       Type Point Siemens Name 0 Units Int  1 Units Slope Ana  Units Action Sensible Name  Comments    AI   AI   BI   BI   BO   AO   AO   BO   BO   BO   AI   AI   AO     4  SUPPLY TEMP     15  RETURN TEMP   24  FAN PRF   26  LO TMP DET   29  DAY  NGT   40  HT VLV   41  MIX DMPR   44  STG1 DX   45  STG  DX   46  FAN   47  DISCH TEMP   48  MA TEMP   99  ERROR STATUS     48   34 534  OFF   OFF   DAY    0   OFF   OFF   OFF   OFF   3755  Dr   0     0 25   0 5   ON   ON   NIGHT   0 01   ON   ON   ON   ON   0 5   0 5   i     DEG F   DEG F         J    VOLTS WO Heating Valve Output     Supply Temperature   Return Temperature   Fan Status Proof   Low Temp Detection  W Occ Unocc Control     WO Mixing Damper   WO Stage 1 DX Cooling   WO Stage 2 DX Co
17. Discovery  on Trunk  1  P1 Device  1          Device Found   1 Type MPU      State    AutoDiscovery  on Trunk  1  P1 Device  2        Device Found   1 Type  VV11   i    Device Found   1 APP   2023     State    AutoDiscovery  on Trunk  1  P1 Device  3        Device Found   1 Type  FC10        Device Found   1 APP   2090     State    AutoDiscovery  on Trunk  1  P1 Device  4    State    AutoDiscovery  on Trunk  1  P1 Device  5    State    AutoDiscovery  on Trunk  1  P1 Device  6       Etc   up to Device  99    State   AutoDiscovery  on Trunk  1  P1 Device  99  _ State   AutoDiscovery  on Trunk 1  COMPLETED     When Auto Discover is invoked the Gateway will scan for all VAV device addresses possible on the requested  trunk     As you can see in the example above     P1    Device address  1 was discovered  which was a MPU type device   Two TEC devices were found  one VAV gizmo  with application  2023  and another Fan Coil device  using  application  2090      This process should be completed for all trunks that have    P1    devices  When all trunks have been Auto  Discovered  you can then use the  S ave Discovery option      lt 7 Note 1  This is a lengthy process  taking 3 4 minutes per trunk on a 4800 baud trunk  Be patient     wait for it to complete   Coffee is always good  here      lt 7 Note 2  If a controller is dead  unplugged  or not communicating when Auto Discover is done   you can manually add the controller to the discovered data file  You must download the data file 
18. E  Fld  1   gt  1 00  DI OVRD SW  Fld  0    gt  OFF  WALL SWITCH  Fld  0    gt  NO  STPT DIAL  Fld  0    gt  NO    RM STPT MAX  Fld  124    gt  79 00  RM STPT MIN  Fld  28    gt  55 00  NGT HTG STPT  Fld  68    gt  65 00  NGT CLG STPT  Fld  136    gt  82 00  DAY HTG STPT  Fld  92   gt  71 00  DAY CLG STPT  Fld  104    gt  74 00  HEAT COOL  Fld  0    gt  COOL    ROOM TEMP  Fld     0    gt   lt UNREL BAD gt     APPLICATION  Fld  2023    gt  2023 00   CTLR ADDRESS  Fld  42    gt  42 00  Analog Value 1  user   Fld  0       gt  0 00  Analog Value 2  user   Fld  0       gt  0 00       18      BACnet ID 204  AV    TX Error Rate  Fld  0              S elect  With Select  you can target a specific point for the Device that you have targeted using the    Devices     menu  This  along with the DEVICE that you have selected  now uniquely defines a point of interest to you   Here is what the MODBUS version of select looks like       PNT   Select   AYI   D etail   X  it S      PNT  You may select an OBJECT ID to target into   Enter a valid  existing  Object ID  1 to 49999    30001      The object at ID  30001 is now selected     The BACnet version is slightly different  You have to select the object TYPE and ID for BACnet  to  uniquely specify an object  Here is what the BACnet version of select looks like       PNT   S elect   A ll   Detail   X  it  S      PNT  You may select an OBJECT ID to target into         Enter an existing BACnet Object TYPE ID  0 to 4  1 to 1000    0  1      The ob
19. ID   P1  4  TRUNK 3  is ON LINE  amp  RELIABLE      122 TagID   P1  5  TRUNK 3  is ON LINE  amp  RELIABLE                  A larms  Not available with Modbus  does not support alarm states   With BACnet  this does have meaning   but only for points that have alarm states or limits  intrinsic alarms  defined  At the present time  the  Centaurus Prime gateways do NOT support BACnet alarming  either    intrinsic    or    algorithmic         Controlled  This command will display all controlled points for all Modbus or BACnet devices       SUM   D evices   A larms   C ontrolled   U nreliable   X  it  C      Internal Global Controls Queue  Head   987 Tail   987  Controls Today   1529    14    This is the usual condition of the gateway  If you have a bunch of controls that happen at a particular time   you may be able to catch the gateway with some controls that it needs to do  In that case  it will list all the  objects in the queue that need to be controlled  and what those controls are  The    head and tail  numbers will  then be different  too  If you find that the gateway has lots of controls to do  ot the number of controls keeps  building up  you have some run away logic external to the gateway which is over controlling      U nreliable  This will display all unreliable points for all devices       SUM   D evices   A larms   C ontrolled   U nreliable   X  it  U       DEVICE  1 is field device  subdevice type 4 0 2092      BACnet ID 4  AI  ROOM TEMP is UNRELIABLE       DEVICE 
20. Operator Control     Critical Equipment Control Commonly  Demand Limiting  Minimum On Off Commonly     Minimum on off     5   10   11 Usually  Area Control  non  VAV    2   B       Minos SS   14 Overrides a    standard    schedule   E  6   pou    N A Relinquish Default Relinquish Default  Note in the    Comments    we have given what the majority of control systems use for their    Default    was for  the priorities in question  This is informational only  but might help     1       Each controllable point in BACnet  that is  an AO or a BO  has a    priority array  which is generally sparsely  populated  Nothing in a particular priority level is specified by    Null     which means that priority level is    unused     21    As an example  consider a warehouse exhaust fan which is turned on and off by a time schedule at priority 15   In a demand limiting situation  this point may also have control at priority 5  shut down ancillary systems in  energy peak situations   But programmatically  a logic block that detects a fire might want to override  everything and keep the fan on in order to pressurize an area and keep the fire from spreading  so that might  be at priority 2  When control is    released    from the higher levels  the next lowest control is issued  Hence   after the fire is over  the fan that was overridden ON might go OFF from its priority 7 demand limiting  shutdown  But if that priority 7 control had been released  then the control descends to the priority 15 t
21. P1  5  TRUNK 3  is ON LINE  amp  RELIABLE      123 TagID   P1  6  TRUNK 3  is ON LINE  amp  RELIABLE         DEVICE  2 is field device  subdevice type 42 0 2092     Device Name  TEC  99     Device Description  TEC  99    Insurance Company     Location  West Conference Room VAV    2 TagID   P1 42  TRUNK 1  is ON LINE  amp  RELIABLE     I O Trunk  1  had last COMM at 17 13 12 on Mar 28  2006     Scan time  secs   142  Device has 41 objects under it  First link    54     O ffline  This will display the Offline status of devices  Hopefully none are  but if any are  they will be  displayed in a list       DEV   Select   AYI   D etail   O ff line   C omm Stats   X  it  O      E 61TagID   P1  1  TRUNK 2  is OFF LINE    MUST INIT gt   SlowScan       DEV   S elect   Al   D etail   O ff line   C omm Stats   X  it  C       2 TagID   P1  42statistics    Packets Today  101902  RX Errors Today  92   Error  0 090  TX Errors Today  509   Error  0 499  Last Comm at  17 13 26 on Mar 28  2006       Point    Menu Options    The  Point  menu has three options  Select  All  and Detail     NT   Select   Al   D etail   X  it       16     A   This will display all points and their current values for the targeted device  What follows below is an  example from a Modbus gateway  A BACnet gateway will display the BACnet object type and Instance  number in the first part of each line  rather than the Modbus register number   Data is the same for both  gateway  flavors   it is just the object mapping which
22. ata you want  the bad  news is that if you want to add points in the future  you will need to download modified TEMPLATE files to  the Gateway in order to add those points  Our personal opinion is that the speed improvement far outweighs  the minor inconvenience of downloading new templates  if ever they are needed     So let s go with philosophy  2 and follow it for awhile  Let s say that we only wanted a few  very important  points out of this template  We might trim it to remove the setup parameters  the D GAIN and BIAS terms   generally unused in Siemens systems  anyway   and the timing polarity rotation parameters  Perhaps the  T   stat does NOT have a setpoint dial  so you can of course remove the points 11  12  13  and 14 that deal with  it   nor does it have a button for night override  so you can remove points 18  19  20  and 21 that handle this    Say you do NOT want them to twiddle the digital output points directly  but you WILL let them control the  heating cooling valves and damper with the AO control point   and thus points 41 through 46 you don   t need  at all  Perhaps it does have an auto zero module  so you WILL keep the related point  but only the point that  lets you do the calibration  point  94   This then will whittle the template file down considerably  as shown  below        Application  2021  reduced  for speed        Type Point Siemens Name O Units Int  1 Units Slope Ana  Units Action Sensible Name  Comments    AI   BO   AO   AO   AO   AO   AI   BO
23. ay about several network options of BACnet     The    BAUDO  9600 N  line may be modified for different Baud rates and parity for your Modbus RTU  connection  The valid baud rates you can use are only     4800  9600  19200    The parity specification should only be    N     O     or    E     This will set the Parity to None  Odd  or Even  if  you are using the Modbus RTU protocol  If you are using Modbus IP or BACnet IP  then the    BAUDO     line is irrelevant     The lines for BAUD1  BAUD2  BAUD3  and BAUDA must be set for the respective Device baud rates  which will be    4800    usually  but may be    9600     newer devices are rumored to even be 19200 baud   If you  have unused trunks  then the baud rate should be set to    0    as seen in the example below for BAUD3 and  BAUD4  See    Uploading and Downloading files to the Gateway    for information on accomplishing the  upload download procedures     The line for IP_LADDR is required only if you have the Ethernet in use  i e   Modbus TCP or BACnet IP  protocols in operation  You have to set up the FIXED IP Address of this gateway computer in two places   here in the GATEWAY INI file  and also in the SOCKET CFG file  more on that later   But just be aware  that they MUST match  If the SOCKET CFG specifies a different IP address from the GATEWAY INI file   you will never receive anything from the Gateway     For the BACnet IP  Annex J  protocol  a couple other global parameters ate necessary  Internally the  gateway maps
24. d    DAY NGT  Fld    DI 3  Fld    DI 2  Fld    OVRD TIME   Fld   DI OVRD SW  Fld   WALL SWITCH   Fld   STPT DIAL   Fld     RM STPT MAX  Fld   RM STPT MIN   Fld   NGT HTG STPT  Fld   NGT CLG STPT  Fld   DAY HTG STPT  Fld   DAY CLG STPT  Fld   HEAT COOL   Fld   ROOM TEMP   Fld        PNT   Select   A ll   Detail   X  it  A                gt   20    gt   12        12 00  1   gt  1 00  0    gt  NO  136    gt  82 00  0    gt  NO  0   gt  0 00  5   gt  5 00  90    gt  90 00  90    gt  90 00  90    gt  90 00  0   gt  0 00  0   gt  0 00  90    gt  90 00  250    gt  100 00  250    gt  100 00  0    gt  OFF  1    gt  NIGHT  0    gt  OFF  0    gt  OFF  1   gt  1 00     gt  OFF  0    gt  NO    0 00  5 00  0 50       124    gt  79 00  28    gt  55 00  68    gt  65 00  136    gt  82 00  92    gt  71 00  104    gt  74 00    0    gt  COOL  0    gt   lt UNREL BAD gt     APPLICATION  Fld  2023    gt  2023 00    CTLR ADDRESS  Fld     17    42    gt  42 00    The display is slightly different for the BACnet flavor of this gateway  because BACnet uses Object  Type Instances rather than registers  The order is slightly different  but the data is identical  Here is the same    display  in    BACyap    format     NT   Select   AYI   D etail   X  it  A         DEVICE 722 is field device subdevice type 42 0 2023    l TagID   TEC  42   has 41 objects under it  1st one at  55       BACnet ID 99  AI        BACnet ID 98  AI        BACnet ID 97  AI        BACnet ID 96  AI        BACnet ID 95  AT        BACn
25. d Unit   Subunit   4   0 Field Address  30051  Object Flags   Errors   0  0  Field In   Out Counts   67  67 Field Value  67 000  Field Hi   Lo Range  0 000   1 000  Engineering Units  o Percnt  E Had any priorities have controls in them  it would have displayed the priority and the control value  for EACH  priority level        Watch    Menu Options    The    Watch    menu will let you select various methods for monitoring the real time data from the field    Q uiet  Use the  Q  key to halt any of the following monitoring options      1   2  3   4  to Watch Trunks  Enter the number of a P1 trunk to monitor  1 4   This will display the field  scan of all Trunk devices and the status of their points in real time  What is displayed below is the Modbus    23    variant  it shows the register numbers in the second column   the BACnet variation is the same except it  shows the BACnet object instances in the second column     DS TRUNK 1 is now being MONITORED           POLL  Trunk  1  Device  1  P1 Unit  4 Type  MPU   1       SCAN  Trunk  1  Device  1  P1 Unit  4 Point  4   P121  AI 4 KWH Usage Counts   128   524 15 KWH      POLL  Trunk  1  Device  2  P1 Unit  42 Type  2023       SCAN  Trunk  1  Device  2  P1 Unit  42 Point  20     P1  1  AI 120 Override Time Counts   1   1 00 Hours       POLL  Trunk  1  Device  3  P1 Unit  65 Type  2092       SCAN  Trunk  1  Device  3  P1 Unit  65 Point  19     P1  1  BI 319 DI Override Switch Counts   0   Off     V erbose  When  V  is pressed whil
26. d then the ENTER key    or any other keys if you do NOT want to merge the maps  Y      Discovery File Merging  trunk  1     Merging P1 unit  1  Trunk  1  Type   MPU     Merging P1 unit  2  Trunk  1  Type   TEC  2023     Merging P1 unit  3  Trunk  1  Type   TEC  2090     Discovery File Merging  trunk  2     Merging P1 unit  1  Trunk  1  Type   TEC  53     Merging P1 unit  50  Trunk  1  Type   TEC  714   _ Discovery File Merging  trunk  3     Merging  P1 unit  44  Trunk  3  Type   TEC  2218    Merging  P1 unit  67  Trunk  3  Type   TEC  2052    No Discovery File on trunk  4    This option will merge all of the discovery files for each trunk thereby giving you a completed database for the  Siemens P1 devices on all    FLN    trunks     After the merge is complete  the Gateway will have created a file called CONFIG TXT  When the Gateway is  rebooted  this new Database Configuration file will be initialized and communications to the field devices will  commence     13    The Save Discovery option automatically assigns Modbus device numbers  slave addresses  or BACnet device  numbers to the Siemens Landis devices it finds  in order  First  devices on trunk  1 are assigned  in order of  Modbus slave devices  or BACnet devices  1 through 60  note that there are a maximum of 60 P1 devices for  EACH trunk     this is a    reasonable    limit  and 95  of Siemens installations will not have more than 60  devices on any trunk  However  we offer an option that does allow for more devices p
27. e in monitor mode  the full protocol data packets will be displayed as well  for each scanned device           Now in VERBOSE MODE  full packets  for monitored trunks                          POLL  Trunk  1  Device  1  P1 Unit  4 Type  MPU   1      TO Trunk 1  16 04 04 02 EC B8      FRM Trunk 1  16 05 01 15 FB 57 7C   Valid       SCAN  Trunk  1  Device  1  P1 Unit  4 Point  4  _  TO Trunk 1  16 05 04 06 08 BE 77   _ FRM Trunk 1  16 06 04 06 88 00 1C B3  lt Valid gt    P121  AI 4 KWH Usage Counts     128     524 15 KWH      POLL  Trunk  1  Device  2  P1 Unit  1 Type  2023      TO Trunk 1  16 04 01 02 C5 D8      FRM Trunk 1  16 05 01 15 FB 57 DC  lt Valid gt        SCAN  Trunk  1  Device  2  P1 Unit  1 Point  20       TO Trunk 1  16 04 63 02 EC B8      TIMEOUT on Trunk  1  error count   0        M odbus  When  M  is pressed while in monitor mode  the full Modbus RTU data packets will be displayed  as well for each scanned device  Modbus version only       B ACnet  When  B  is pressed while in monitor mode  the full BACnet protocol data packets  addressed  globally or to this gateway only  will be displayed in real time  Note that this significantly slows down the  BACnet channel  and we recommend that this mode NOT be utilized for any length of time     24    Uploading and Downloading files to the Gateway    In order to upload download files to the Gateway  you will need to use a VI 100 Terminal emulator   Hyperterminal or the like   You will need to set it up to use a Comm Por
28. ed the    P1    Gateway as the standard Modbus IP configuration  then it is simple  You plug  in an 8 pin Category 5 or Category 6 cable into the Ethernet connection on the top right hand corner of the  PC  You must set the IP address of the Gateway to a static  fixed address  on the segment that you are in   This is done with the CONFIG TXT file  described in the next chapter      2  Serial Link     If you have ordered the    P1    Gateway with the Modbus RTU protocol option  then the Modbus connection  is made with the CS485 line driver included in the Gateway cabinet  if the product has been ordered with a  Modbus RTU front end  The CS485 line driver is an RS 232 to RS 485 interface converter  It allows an RS   232 device to reliably transmit data over long distances  up to 4000 feet   The CS485 has many features not  normally found in typical line drivers  and is intended for operation in harsh industrial environments     You must also modify the GATEWAY INI file to specify the baud rate and parity of the Modbus RTU  connection  All Centaurus Prime Gateways act as a series of Modbus slaves  and can be a large number of  logical devices  but it acts as only one electrical device on the Modbus RTU trunk  The    P1    Gateway can act  at any baud rate from 4800 baud to 19200 baud  19200 baud is not recommended except for very short  distances   Even  Odd  and None are the valid parity options     The CS485 may be used in point to point applications as well as multi drop appl
29. egular    and    custom    templates that will be used in your  building  Say that you had a system with a couple DPUs and many TECs  Perhaps you have several VAV  box types  like this     Many Application 2021 TECs  cooling only VAV for internal zones    Many Application 2022 TECs  VAVs with baseboard or electric reaheat    A few 2051 TECs  Blower coils    One Application 2384  I O only  to handle a rooftop unit with it   s own controls     You would have to download  at least  the following templates to the Gateway  TPL_2021 CSV   TPL_2022 CSV  TPL_2051 CSV  and TPL_2384 CSV  Note the extension  CSV means    comma separated  variable   which is a standard text type spreadsheet file  Because it is a text file  you can edit these files with  either a simple text editor or a spreadsheet program  If you do edit it with a spreadsheet  some spreadsheets   like Excel  will give you the option to save the file in their own internal format  e g   XLS format   DO NOT  DO THIS  Keep the file in text format   CSV   so that it is transferable and readable by the Gateway     Centaurus Prime supplies these TEMPLATE files  You can obtain them by contacting us  either by e mail or  telephone  and we will e mail any that you need back to you     Let   s look at one of these template files  for example  TPL_2021 CSV       Application  2021      Type Point Siemens Name O Units Int  1 Units Slope Ana  Units Action Sensible Name  Comments    AO  2  APPLICATION   0  T  APP     Application Number 
30. er trunk  but it  sacrifices the fourth trunk  If this is your situation  please consult the factory for the one additional file you  will have to download into the P1 Gateway to do any non standard device assignments  this file is called   PARTITION TXT    because it partitions the three trunks in a particular fashion to accommodate your  installation      Similarly  the P1 devices found on Trunk   2 are assigned  in the order that they are discovered  to Modbus  slave devices 61 through 120  same BACnet device numbers  And of course  Modbus slave  addresses BACnet device numbers 121 to 180 are for the P1 devices found on Trunk  3  and finally Modbus  slave addresses BACnet device numbers 181 to 240 ate assigned to P1 devices on Trunk  4  in order of  discovery         Summary    Menu Options  SUM   D evices   A larms   C ontrolled   U nreliable   X  it                  After the  S ave Discovery has been completed  you can then reboot and the Gateway will begin to poll the  discovered devices  The summary menu option will display further options detailed below      D evices   Devices will display all the status of all devices configured for the Gateway     I SUM   D evices   A latms   C ontrolled   U nreliable   X  it  D      4   1 TagID   P1241  TRUNK 1  is ON LINE  amp  RELIABLE    2 TagID   P1242  TRUNK 1  is ON LINE  amp  RELIABLE       61TagID   P1  1  TRUNK 2  is OFF LINE    MUST INIT gt   SlowScan       G2TagID   P1  2  TRUNK 2  is ON LINE  amp  RELIABLE      121 Tag
31. et ID 394  BI        BACnet ID 92 AI         BACnet ID 387  BI        BACnet ID 59 AI        BACnet ID 58 AI        BACnet ID 57 AI        BACnet ID 56 AI        BACnet ID 55 AI      BACnet ID 53 AD       BACnet ID 52  AD       BACnet ID 51  AJ        BACnet ID 49  AI        BACnet ID 48  AI         BACnet ID 446  BO         BACnet ID 429  BO        BACnet ID 325  BI      BACnet ID 324  BD        BACnet ID 120  AO        BACnet ID 319  BI         BACnet ID 318  BI         BACnet ID 414  BO          BACnet ID 112  AO        BACnet ID 111  AO        BACnet ID 109  AO        BACnet ID 108  AO        BACnet ID 107  AO        BACnet ID 106  AO         BACnet ID 405  BO        BACnetID 4 AI        BACnetID 2 AI        BACnetID 1 A         BACnet ID 201  AV         BACnet ID 202  AV                ERROR STATUS  Fd  0   gt  0 00  LOOP TIME  Fld  5   gt  5 00  DUCT AREA  Fld  20   gt  0 50   CAL TIMER  Fld  12    gt  12 00  CAL SETUP   Fld  1   gt  1 00  CAL AIR  Fld  0    gt  NO  CTLSTPT  Fld  136    gt  82 00  CAL MODULE  Fld  0    gt  NO  DO DIR REV  Fld  0   gt  0 00  MTR SETUP  Fld  5   gt  5 00  DPR2 ROT ANG  Fld  90    gt  90 00  DPR1 ROT ANG  Fld  90    gt  90 00  MTR2 TIMING   Fld  90    gt  90 00  MTR2 POS  Fld  0   gt  0 00  MTR2 COMD   Fld  0   gt  0 00  MTR1 TIMING   Fld  90    gt  90 00  MTR1 POS  Fld  250    gt  100 00  MTR1 COMD   Fld  250    gt  100 00  DO 6  Fld  0    gt  OFF  DAY NGT  Fld  1    gt  NIGHT  DI 3  Fld  0    gt  OFF  DI 2  Fld  0       gt  OFF  OVRD TIM
32. gateway to be on a separate  network number  e g   ALC   some prefer the gateway to be on the same network  e g   Alerton   and some  don   t cate  most   In the GATEWAY INI you should change the parameter    BACNET NETWORK    to  an appropriate value     Typically  installers have chosen the BACNET NETWORK to be a certain number  and then made the  BACNET OFFSET to be 1000 times that number  so that the BACnet instance numbers of the devices are  all prefixed by the network number  As an example  if you set the BACNET NETWORK number to 333  and the BACNET OFFSET to 333000  then you would end up with BACnet device numbers 333001   333002  333003  etc   on network  333  Makes it simple  no  Just a suggestion     DO NOT over tax the BACnet network  At about 30 BACnet IP packets per second directed TO THE  GATEWAY  the Gateway will saturate  any more packets than that  and they are lost  Any more than that  will cause retries and actually SLOW DOWN the BACnet system  This is because BACnet IP is a     connectionless    system   the requestor sends a packet to the Gateway  and the network gives it a    best  effort    to deliver it  If the network is saturated  and our Gateway does not receive the packet  the requestor  has to time out  and then retries its request packet  This may mean that control logic will    stall     depending  upon the software implementation in the controller  until that retry occurs     27    TEMPLATE Files    You need to download to the Gateway and    r
33. hat you have  a TEC of type 2384  This is a    dumb    TEC that handles things like Roof Top Units  RTUs   that have their  own internal controls  This is the default template for Application 2384  which is file    TEC_2384 CSV           Application  2384      Type Point Siemens Name 0 Units Int  1 Units Slope Ana  Units Action Sensible Name Comments    AD  2  APPLICATION  B d  APP     Application Number     AT    ROOM TEMP  48  0 25  DEG F     Return Temperature   AI  13  RM STPT DIAL  48  0 25  DEGF    Setpoint Dial N  If dial exists  BO  14  STPT DIAL  NO  NES    W Setpoint Dial Contro    if existant  AI  i5  ALIS  Al    0 5  DEG F    AI3  Any usage   BI  19  DI OVRD SW  OFF  ON       Override Switch Status  if existant  BI  24  FAN PRF  OFF  ON       Fan Status Proof   BI  26  LO TMP DET  OFF  ON       Low Temp Detection     BO  29  DAY  NGT  DAY  NIGHT    W Occ Unocc Control     AO  40  HT VLV    QUI  VOLTS  WO Heating Valve Output   AO  41  MIX DMPR  OFF  ON   WO Mixing Damper     BO  42  DO 2  OFF  ON   WO DO 2  Any usage   BO  43  DO 3  OFF  ON   WO DO 3  Any usage   BO  44  STGI DX  OFF  ON   WO Stage 1 DX Cooling   BO  45  STG2 DX  OFF  ON   WO Stage 2 DX Cooling   BO  46  FAN  OFF  ON   WO Fan Control 1   AI  47  DISCH TEMP  37 5  0 5  DEG F   Discharge Air Temp     AI  48  MA TEMP  37 5  0 5  DEG F     Mixed Air Temp i   AO  59  DO DIR  REV   0  1 0 DIRCT   Forward Reverse Setup   Danger  Config ONLY  AO  99  ERROR STATUS  0  i  CODE     Error Status Code  Use as 
34. ications using either 4 wire or  2 wite configurations  Up to 32 devices may be connected together on one communication line     The CS485 has 1500 volt optical isolation between the RS 232 side and the RS 485 side  The RS 485 lines are  protected with 2 stages of surge protection  and jumpers allow complete configuration of terminating and pull  up down functions     Configuring the CS485    The full manual for the CS 485 is available on the Centaurus Prime web site  www centaurusprime com    While it is very lengthy and technical  we recommend that you download and review the full manual if you are  using the Gateway in unusual applications  e g   with radio modems  Ethernet converters  line drivers with  delays  etc   The CS 485 allows for many options  and a unique    data mode  that no other RS 485 converter  on the market has  It is extremely robust and adaptable        The CS485   s default configuration is for 2 wire RS485  Following are setup parameters for RS485  2 wire    RS422  4 wire   and optionally  RS232      RS 485 RX and TX Jumpers 0       J4    Enable pull up resistor for RX  line     J3     Enable pull down resistor for RX  line     J2    Terminate RX pair with 120 ohm resistor     J7     Enable pull up resistor for the TX  line     J6     Enable pull down resistor for the TX  line     J5    Terminate TX pair with 120 ohm resistor   J8 IN Enables 2 wire operation for both RX and TX pairs  i  Dual port operation     OUT Enables 4 wire operation   RX is rece
35. iew Call li Place received file in the following folder     ap   al Send File       CAgateway    Browse                Soe Use receiving protocol   Capture Text            modem   v                     Send Text File       Capture to Printer    ir  Nil Receive Filename    modem never sends a filename  so you must specify a  filename for storing the received file     Folder   C gateway   Filename  filename  txl  gt  l 3          Click Transfer  gt  Receive File  Enter the location to save the file and make sure that Xmodem is selected and  then click the Receive button  The next dialog box will ask you to specify a filename and when you click     OR    the file will be received from the Gateway     Setting up the Modbus Driver    After the Gateway is ready to go and you have your database configured  one of the last steps is to make sure  that you have the Modbus driver settings for the Host Master setup correctly  The following information  should be kept in mind when configuring the driver    Modbus commands that are accepted by the Gateway are     1   Read Coils  0000 s    2   Read Discretes  10000 s   3   Read Holding Registers  40000 s   4   Read Input Registers  30000 s     5   Force Single Coil   6   Preset Single Register   7   Read Exception Status  Status is 0 if OK  o w internal error code   15   Force Multiple Coils   16   Preset Multiple Registers   17   Report Slave ID  Emulates Modicon Micro 84     Most Modbus drivers have many setup options and each vendor is d
36. ifferent  Following are some limits with  the Modbus Gateway that you need to consider when setting up your driver           MAXIMUM number of coils read at once  CMD 41  is 64   MAXIMUM number of discretes read at once  CMD  2  is 64   MAXIMUM number of holding registers read at once  CMD 43  is 32  MAXIMUM number of input registers read at once  CMD 44  is 32  MAXIMUM number of coils forced at once  CMD 415  is 8   MAXIMUM number of registers preset at once  CMD 416  is 8   TIMEOUT for a command should be a minimum of 350 milliseconds  500 ms          recommended                             TIME BETWEEN commands should be a minimum of 50 milliseconds  100 ms  recommended                 NUMBER OF TIMEOUTS before  slow polling  should be a minimum of 3  3  recommended              Setting up the BACnet System    After the Gateway is ready to go and you have your database configured  one of the most important steps is to  make sure that you have your BACnet system configured propetly to communicate with the Centaurus Prime  Gateway     The most important parameter that some BACnet systems need to know is whether a device supports  READ MULTIPLE and WRITE MULTIPLE services  The Centaurus Prime Gateways only support  READ MULTIPLE  not WRITE MULTIPLE services  All Centaurus Prime Gateways conform to the  BACnet    PICS    statement published and available on our web site  www CentaurusPrime com        There is some difference in the way many host systems work  Some require our 
37. ime   schedule control  You have to know what your plant s priority system is  and what each point s capabilities  and control options are   this is not a trivial control philosophy     The    Relinguish Default  value  if any is specified  is the control that is given out to a point if there is  NOTHING in this priority array  that is  all 16 levels of control have been released   If there is no     Relinguish Default  value  i e   NULL      then the point just sits there  at it   s last control     Now  before you can control a point object you must first have selected a device number   a point  type instance  and a priority  Then you can set the control value  and that value will go into the object s  ptiotity atray  That does NOT mean that control will be issued  remember  since you may be at a lower  priority level than what is controlling the point right now      P riority   BACnet ONLY  Use this to select the priority that you will issue subsequent control and release  operations at          PRI  Enter a PRIORITY to do your controls at  1 to 16   4      Control and Release Operations will now be done at Priority 4      C ontrol   BACnet version  This option will let you control the selected point  at whatever priority level you  are currently at       CTL   S elect   P riority   C ontrol   R elease   Detail   X  it  C      CTL  You may enter a new value to set the selected object to   Enter a field value  0 or 1 for digitals  valid number for analogs    70      The new
38. ive pair    TX is transmit pair    JE Connects isolated RS 485 common to bleed resistor and filter cap    RS485 Communications     5Udc  COMMON  EARTH  CHASSIS     U2     o     9  cs485  e  i cl  all LAT  CTS DELAYO    no    Mc       Installed jumpers  2W 4W  Baud0  Baudi  Data DCD  Data RTS  J2  end of line only   J3  end of  line only   J4  end of line only   and J15  static bleed     RS422 Communications     5Udc  COMMON  EARTH  CHASSIS      E  a  E    u2             e  cs485  Lo crs mune  PROGR ese  DELAYO tye    Mr mno    Installed jumpers  Baud0  Baud1  Data DCD  Data RTS  J2  end of line only   J3  end of line only    J4  end of line only   J5  end of line only   J7  end of line only   and J15  static bleed        RS232 Communications    For RS232 communications  you will need to make a cable that will connect to Comm1  RJ45  on the Single  board Computer following the diagram below     RJ45 SIGNAL DIR DBSM       EXT MODEM       NOTE about removing the C5 48      For RS 232 or Ethernet applications  the CS 485 module is not used  and may be removed  if you had  ordered the gateway for RTU communications   While many are tempted to do this  it can be used in other  applications  of coutse   we recommend that you remove the wiring that powers the CS 485 also  if you do   Both the National Electrical Code and local electrical code  generally  do not approve of either    wire nuts  or  electrical tape on exposed wires  As the Gateways are built to UL and CSA standards  we 
39. ject with TYPE 0 and Object ID  lis now selected     You have to remember that BACnet types are an    enumerated value   in BACnet speak   These are  for  those who don t remember such minutae     e 0 AI  e 1 AO  e 2 AV  e 3 BI   e 4  BO     D etail  will display details associated with the selected point  for MODBUS points     PNT   S elect   A ll   D etail   X  it  D    MB Address  30004  Type   AI   Zone Temperature   Field Unit   Subunit  4  0 Field Address  30001   Object Flags   Errors  0   0   Field In   Out Counts  0  0 Field Value  0 000    19    Field Lo   Hi Range  0 000   255 000  Eng  Units   Deg F     NT   Select   Al   D etail   X  it  D       BACnet Object ID   112  Type   AO  Object Name     RM STPT MAX     Description     Room Setpoint Maximum        No elements in priority control array       BACnet Relinguish Default Value  NULL  Field Unit   Subunit  42  0 Field Address  40012  Object Flags   Errors  3   0  Field In   Out Counts  124  0 Field Value  79 000  Field Lo   Hi Range  48 000   0 250  Eng  Units   Deg F        Control    Menu Options    This is slightly different for Modbus and BACnet  In BACnet  you control things at sixteen different priority  levels  and you can    release    control from any particular level     Let   s consider the simpler  Modbus case first  Control just    happens    when you select a point and give it a  new value  No priorities at all  The last control to a point    wins     and stays until some other control is given  t
40. location     The BACnet IP network is a 10 Mbaud Ethernet  only  The Modbus RTU  Network connects to the    P1    Gateway via either  a  a 10 Mbaud Ethernet   b   an RS 422 serial link  a four wire  full duplex connection   an RS 485 serial link     a two wire  half duplex connection   or an  c  RS 232 serial link  a three wire  full duplex connection      Single Board Computer Basics    The Single Board Computer used in Centaurus Prime Gateways is the Ether 6 manufactured by JK  Microsystems  It is made in the United States of America    The controller is based on an Intel 386Ex processor running at 25Mhz  It is equipped with 1 megabyte of  static ram organized as 512K 16 bit words  Also included are 512K bytes of flash memory organized as DOS  drives A and B  A 40 Megabyte M Systems DiskOnChip is added to the 32 pin DIP socket on the controller  board  and acts as drive C  There is a switching power converter on the controller  which can accept 7 34 volts  DC  Nominal current consumption is 250mA at 12 volts with 10Base T Ethernet selected     Specifications for the Ether 6 are                                            Processor   Intel 386Ex  25MHz   Operating System   XDOS  MS PC DOS 3 3 compatible    Memory   IM SRAM  512K Flash  40MB Flash   Ethernet   10BASE T  NE2000 compatible automatic media detection  Link  status and Activity LEDs   Serial Port 1   RS 232 with 5 handshake lines  COM1  address Ox3F8  IRQ4 115200 baud maximum   Serial Port 2   RS 232 no handshaking
41. o that point     Now  before you can control a point object you must first have selected a device number and point number   see Modbus point map  Chapter 3       Select  Use this to select a valid point  Here is the Modbus variant       CTI   Select   Cjontrol   D etail   X  it  S    CTL  You may select an OBJECT ID to target into   Enter a valid  existing  Object ID  0 to 49999    11      The object at ID  1 is now selected          CTL   S elect   P riority   C ontrol   R elease   D etail   X  it  S      CTL  You may select an OBJECT ID to target into     Enter a valid  existing  BACnet Object TYPE ID  0 to 4    1 to 16000   1 114      The object with Type 1 and Instance  114 is now selected      C ontro   MODBUS version   This option will let you control the selected point  Here is a simple  MODBUS example of a digital point control to    off     zero        CTL   Select   Control   D etail   X  it  C       CTL  You may enter a new value to set the selected object to   Enter a field value  0 or 1 for digitals  valid number for analogs    0      The new value of the object will be   0    Adding to Control Queue  at  2  MB  1  Register  1    Queued Control  Trunk  1  MB  1  Register  1     to  0 000    OK   so much for simple  Now let s talk about BACnet  alias BADnet   There ate sixteen priorities  These  are given below     BACnet Default Comments     Miscellaneous OP     Miehwos Ss O    Custom Programming   High Custom Programming   High Pri   Manual Operator Standard    
42. oling   WO Fan Control    DEG F   DEG F   CODE        Discharge Air Temp   Mixed Air Temp   Error Status Code      SPECIAL usage   SPECIAL usage    Use as AI          J                  Y       By downloading these custom files to the Gateway  you can get the Gateway to use them for a certain P1  device on a particular trunk  instead of the    standard    template for that application  How sweet it is  You can  customize the system to your heart s desire     31    Index     A larms  14  15    C ontrol  11  12  13  21  22  23    C ontrolled  14  15    D etail  15  16  17  18  19  20  21  22  23    D evices  14    H elp  11    M odbus  24  25    S elect  15  16  17  18  19  20  21  22  23    V erbose  24      Devices    Menu Options  15    Point  Menu Options  17      Summary    Menu Options  14   220 or 240 Volts AC  1   Auto Discovery  12   BAUD TXT  i  9   Commissioning  9   communication statistics  16   Creating and Downloading the GATEWAY INI  file  9   CS485 i  4 5   Database Generation  12   Downloading  i  9  11  13  25   Gateway Overview  7   jumpers  5  6    Local Mode  11   Memory 2   Modbus device numbers  14  Modbus Master  i  4  7  Modbus Network  1  Modbus RTU  1 25    Power  2  3   Power Supply  1   Processor 2   Receive File  26   RS232 5 6 7   RS 232  1  2  4 5   RS485  i  5  6   Send File  25   Serial Port 2   Setting up the BACnet System  27  Setting up the Modbus Driver  26  Smart Il Device Buss  1  SOCKET CFG  11   targeted device  17   Uploading  i  9  1
43. om the Siemens building controllers are removed from it and simply re connected to the Centaurus Prime     P1    Gateway     A usual Siemens  Landis controller  such as an MBC or SCU  has three    FLN    trunks  The Centaurus Prime     P1    gateway has four trunks  While this may be    one too many     in many cases several Siemens controllers  are installed in one location  and you can install fewer gateways than simple one to one Siemens controller  replacements  due to the fourth FLN trunk on the    P1    Gateway    The trunk connections ate clearly marked and each trunk is only a two wire connection  The trunks have a     plus    and    minus    side  and also a    shield    connection that goes to cabinet  AC  ground  Be sure that the  polatity is correct  and that the shields are ALL tied together and only connected to ground at ONE place  to  avoid ground loops   This is a two wire trunk  so it does not matter if you land the field trunk wires on  TX  TX   or on RX  RX   Just make sure the polarity is right     The avoidance of    ground    loops is VERY important  especially in long lines  electrically noisy environments   or between buildings on a campus  Also  termination of the RS 485 lines is very critical to good  communications  Follow the RS 485    rules    to the letter     Picture 1 2  Gateway Overview and Identification             Connecting to the Modbus Master    Connecting to the Modbus Master is done one of two ways    1  Ethernet     If you have order
44. suggest you adhere  to these standards  to avoid code issues     Connecting to a BACnet IP Network    This is quite simple  You plug in an 8 pin Category 5 or Category 6 cable into the Ethernet connection on the  top right hand corner of the PC  You must set the IP address of the Gateway to a static  fixed address  on the  segment that you are in  This is done with the GATEWAY INI file  described in the following section  The  same IP address must also be used in the SOCKET CFG file  which is also described later     Gateway Overview    Picture 1 3  Gateway Overview and Identification    2 0905 08       P1 Trunk 4  Single Board  Computer  P1 Trunk 3  P1 Trunk 2  P1 Trunk 1  NOTE  If    connecting to a  Modbus RTU  Master  an    additional z owen  RS485 232 E 9 5520 595 5     converter is 9e e  gt     T    supplied and  mounted on the  backplane     Perr       Remove Cover for  Power Connections       Commissioning the Gateway with  the Local User Interface    Creating and Downloading the GATEWAY INI file    The following is an example of the GATEWAY INI file that must be edited to match your particular  installation   There are several sets of parameters in the INI file  One set of parameters deals with the BAUD  rates on the four P1 trunks  Another parameter sets the Ethernet IP Address of the gateway  it must be a  FIXED IP address   if you ate using either Modbus TCP or BACnet IP as the host protocol  And  if you  are using BACnet  another set of parameters tells the gatew
45. t  Comm  typically  and use the  following settings  Baud 9600  Databits 8  Stop bits 1  Parity None  and no Flow Control     The Gateway has two utilities for transferring files  UP COM is used to send files to the Gateway and  DOWN COM is used to received files from the gateway     When you are connected to the gateway in local mode  hit X it once or twice and you will be asked to type     YES    to quit the program which will take you to DOS prompt     Sending a file to the Gateway  uploading   From the dos prompt  you must type    UP filename   filename being the name of the file to send with  extension   The response will look like the following     C Vup test txt      Ready  start X modem upload now     Press CNTL C to abort       In Hyperterminal  start the file transfer by selecting Transfer Send and follow the following sequence below     Click Transfer  gt  Send File  Browse for file to send and make sure that Xmodem is selected  Click the send  button and the file will be sent to the Gateway                HyperTerminal ME Send File      ami ay Receiving a file from  View Call Meise Folder C  N          a T the Gateway  zs Se Filename  x  l R ive Fil  c gatewayMilename  td   downloading   uice E RU C     From the dos  Capture Text    Protocol   Send Text File  modem    pe Lia adi    m type DOWN    being the name of    In Hyperterminal  start the file transfer by selecting Transfer Send and follow the following sequence below      HyperTerminal lil Receive File    V
46. uld be modified to be whatever static IP address that the    P1     Gateway will have  Note that DHCP is not an option  this device requires a static  fixed  IP address     Local Mode Menu Options    Once connected via the local mode port you may press  lt enter gt  at any time to display this top level menu     When you type    H     lt enter gt  you will get the following     Hit a single key to get to a submenu  Your Options are       H forHelp  which gives you this screen   S  for Summary   which allows you to get various status summaries   D  for Devices   which allows you to manage and get data on devices   P  for Points   which allows you to manage and get data on points   C  for Control   which allows you to control various field objects   W  for Watch   which allows you to watch protocol streams   A  for AutoDisc   which allows you to auto discover trunks   X  for  X it    which exits this gateway program         Melp   S ummaty   D evice   Point   C ontrol   W atch   A utoDisc   X  it      11     7 X     will always take you back to the top level menu options    Auto Discovery and Database Generation    Before you can use any of the other menu options you must first create your database by using the  A  option   which will give you the following text       AUTODISCOVERY  You may select a TRUNK to auto discover     Enter a TRUNK NUMBER  1 through 4    1      Trunk  1 will now be auto discovered      _ AUT   A uto Discovery   S ave Discovery   X  it       State   Auto
47. us Code  Use as AI    This is ALL the valid points that can come from this particular device  using this application number   2021    That does not mean that ALL these points are used  not does it mean that you should map ALL the points   Some can never  or should never change   such as point  2  the application number   points  36  39  97  etc   The calibration only points  rotation travel  motor timing parameters  duct square area  etc   will NOT change   And if they do  it is because the hardware has changed  Then these parameters should be changed by the  hand held calibration device or a laptop with DataMate  the Siemens Landis softwate to setup  calibrate  and  commission the TECs   It is recommended that you NOT put these points in the database  so that the user is  not tempted to try to mess with them from their control room La Z Boy recliner     One philosophy is to put all points in the Gateway  i e   keep these files just as they are and download them to  the Gateway   and just NOT map the ones that you don t want  The other philosophy is to DELETE the  points you will never want to expose from these template files  before you download them to the Gateways   The good point of the first philosophy is that all the points are there  if you ever want to map them latet  the  bad news is that the Gateway has to scan these points  and that affects performance in a bad way  The good  point of the second philosophy is that the scan is quicker  and you are only getting the d
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
TCL-10MW  Samsung 910MP Bruksanvisning  K5000S取扱説明書  Wire your business for success  ARX c.cdr - Prodance  Manual de usuario EZ-2200 / EZ-2300    HDfury 4 (aka 3Dfury) User Manual Rev 1.0  Service and Parts Manual  Télécharger le document en PDF - Bibliothèques municipales de    Copyright © All rights reserved. 
   Failed to retrieve file