Home
Wireless Temperature Transmitter
Contents
1. 00 00 01 left Link Quality gt gt gt gt gt gt gt Figure 3 6 Wireless Data Loss Test In the top of the window you can configure the test to run for a specified amount of time The longer the test the more data the test will have to do an evaluation Type the length of time that you want to run the test and click BEGIN to start After the test has completed 1t will restore the previously configured Transmit Rate During the test the communications reliability 1s evaluated while the Trans mitter is running under normal operating conditions As the test runs a link strength will be shown in the lower right hand corner of the window gt gt gt gt gt indicates the strongest link while gt indicates the weakest link The Link Test will continue to be evaluated and the rating on the screen may adjust itself for the specified amount of time User Manual 11 Honeywell Process Solutions 3 2 Electrical Installation A Caution Remember to turn off all power BEFORE hook ing up any wires 3 2 1 Electrical Specifications A Warning A Explosions may result in death or serious injury Do not remove the instrument cover or open wir ing housing in explosive atmospheres when power and communications are on 3 2 2 Wiring the Thermocouple RTD Input For Dual T C installations the inputs share a common ground Use Ungrounded T C s or ensure that both T C s are at the same ground pote
2. TRIM IS RESET IF NO S PRESSED NEW TRIM IS CANCELLED This resets all the trim points to the factory settings Not the OFFSET ENTER amp NEXT _ AT ANY TIME 4 36 User Manual Rev 4 May 2012 Honeywell Process Solutions Wireless Temperature Transmitter Rev 4 User Manual 37 May 2012 16981 Honeywell Process Solutions 1860 West Rose Garden Lane Phoenix Arizona 85027 34 XY 25 52 Tel 1 800 423 9883 or 001 215 641 3610 May 2012 Email support ask ssc honeywell com 2008 12 Honeywell International Inc www honeywellprocess com
3. XX XXIN2 5 UNITS Er a EEE see ses O da NO Wireless Temperature Transmitter If enabled RF ERR SEN ERR LOW BAT YES If enabled RF ERR SEN ERR LOW BAT RF OFF NO RE Figure 4 1 Transmitter Power Up and Operations LCD Sequences 4 2 1 The Read Only Sequence Once the Transmitter is in the Operations Sequence a user may access the Read Only Sequence without a password by simply pressing the ENTER button at any time The Read Only Sequence as shown in Figure 4 2 dis plays extra information about the current settings of the Transmitter that is not seen during the Operations Sequence but does not allow any changes to be made to these settings If enabled ERROR MSG RF ERR SEN ERR LOW BAT RF OFF NO RF Rev 4 May 2012 Figure 4 2 The Read Only Sequence User Manual 15 Honeywell Process Solutions 4 3 Overall Configuration Menu Map The user must enter a four digit password to enter the CONFIG and DIAGNSE The FACTORY menu is for factory use only The default user password is 0000 For more information on the password see Section 4 5 Once WMT has been used to configure the Trans mitter this menu option will be disabled on the Transmitter LCD menu See Section 4 1 for more details 4 4 Setting the Transmitter Tag Name 16 May 2012 Wireless Temperature Transmitter A complete Transmitter Menu Map is shown in Appendix C Below is an overall view of the c
4. After selecting the point you will have the option to trim the device or reset the trim If NEW TRIM is selected you will be prompted to enter the lower point first Type the value and press ENTER The Transmitter will prompt you to apply the indicated process value to the Transmitter Apply the process value and press EN TER Repeat the process for the higher point After both points have been trimmed you can choose to save or discard the new trim Disable Sensor Offset Curve Enable Sensor Offset Curve Curve Parameters Indicated Actual Indicated Actual Value Value Value Value LO PNT 0000 00 NTER APPLY NTER pean nnn nnn nnn nnn nnn nnn nono ENTER _ HIPNT sf 0000 00 lentes APPLY ENTER l E a E ee Se ee a ss ee ee L IF YES IS OPERATIONS SEQUENCE I NEXT CONFIG PL SAVE ur SELECTED NEW b a a ENTER NEXT TRIM IS SAVED Y IF NO IS NEW TRIM NO NTER gt SELECTED TRIM POINT IS PROMPTED i i DISCARDED N FOR s NEXT PASSWORD y Keine iF YES 1S RESET NTER ENTERS PRESSED TRIM IS e Su ENTER RESET NEXT iria IF NO IS NEXT 4 PRESSED NEW EET EXIT NO _ ENTER TRIM IS CANCELLED NEXT Y NTER Figure 7 5 Setting a 22 Point Curve Using Wireless Management Toolkit INPUT 2 NEXT If entering a two point trim via the NEXT and ENTER buttons Point 2 MUST be greater than Figure 7 4 Menu Map to Trim Set
5. Enable SmartRate for the correct input The user will then be allowed to enter a delta or amount changed value which will trigger a transmission Once a value has been entered click OK to save and download the con figuration changes to the Transmitter Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A User Manual 25 Honeywell Process Solutions 6 6 Selecting the Normal Up per and Lower Values Input Volts 10 Normal Lower Value set to 2 5 Volts Abnormal Condition Normal Upper Value set to 6 5 Volts Normal Condition Figure 6 10 Normal Upper and Lower Value Example Input Volts Abnormal Condition Abnormal Condition Abnormal Condition Abnormal Condition 2 Normal Upper Value set to 7 5 Volts Normal Condition 0 1 00 2 00 3 00 Time min sec Figure 6 12 Condition Chatter Without Time Deadband Input Volts 10 2 Normal Upper Value set to 7 5 Volts Normal Condition 0 1 00 2 00 3 00 Time min sec Figure 6 13 Condition Chatter Elimina tion Due to Time Deadband Using Wireless Management Toolkit 26 Wireless Temperature Transmitter Each Temperature Transmitter is equipped with an temperature level up per and lower value As the temperature is measured it is compared to a set threshold value Depending upon the setting of that value whether it is enabled or not and what the time deadband is the Tra
6. Use 3 1 3 Testing Communications 3 1 4 Link Test 3 2 Electrical Installation 3 2 1 Electrical Specification 3 2 2 Wiring the Thermocouple RTD Input 3 2 3 Wiring the Input Switches Section 4 General Configuration 4 1 Navigating User Menus 4 2 Transmitter Displayed Messages 4 2 1 The Read Only Sequence 4 3 Overall Configuration Menu Map 4 4 Setting the Transmitter Tag Name 4 5 Resetting a User Password 4 6 Resetting All Transmitter Settings Section 5 Configuring the RF Communications 5 1 RF Channel Selection 5 2 RF Baud Rate Selection 5 3 RF Identification Selection Section 6 Configuring the Sampling and Transmission Rates 6 1 Selecting the Normal Transmission Rate 6 2 Selecting the Normal Sampling Rate 6 3 Selecting the Abnormal Transmission Rate 6 4 Selecting the Abnormal Sampling Rate 6 5 Setting the Smart Rate Threshold 6 6 Selecting the Normal Upper and Lower Values 6 7 Selecting Rates Thresholds and Deadbands via the Software Section 7 Configuring the Process Variable 7 1 Selecting the Units of Measure 7 2 Selecting the Sensor Type 7 3 Setting a Measurement Offset 7 4 Trimming the Measurement 7 5 Entering a 22 Point Curve Section 8 Maintaining the Transmitter 8 1 Changing the Battery Section 9 Technical Specifications Dimensioned Mechanical Drawing Appendix A Navigating User Menus Appendix B Displayed Message Definitions Appendix C Menu Map Rev 4 User Manual May 2012 ossos A Rss P
7. can also be entered via WMT To do so when the software is in the Transmitter view See Appendix A right click the Transmitter icon select Rename and then enter the Tag Name you wish the Transmitter to have This Tag Name will then be uploaded to the Transmitter and can be dis played by pressing the ENTER button when the unit is in the Operations Sequence See Section 4 2 1 of this manual Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A User Manual Rev 4 Honeywell Process Solutions 4 5 Setting a User Password NOTE Once WMT has been used to configure the Trans mitter this menu option will be disabled on the Transmitter LCD menu See Section 4 1 for more details Dual 0 10 V Input Properties 1 47 Output Switches Sampling Rates Sampling Bands Alarms General Inputs Range Sensor Offset Description Location Date Installed Comments General Monitored Equipment Field Unit Password 0000 Units Input Units Volts Figure 4 6 Password Setting Using Wireless Management Toolkit 4 6 Resetting All Transmitter Settings Resetting the Transmitter by using the DEFAULT menu option will not reset the TRIM or OFFSET values Rev 4 May 2012 Wireless Temperature Transmitter Each Transmitter has a password that will lock out undesired users from making changes to the Transmitter Any u
8. of 15 Seconds Figure 6 3 Correct Sampling Rate orcas SeOUENGE era TOR Using Wireless Management Toolkit PE E Eaton cas ums jus us nr co am a If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details An CESPE eres CHORE explanation of how to select the Normal Sampling Rate using the Wire NEXT Default of 1 Second NORSK Jeo 1 5 sec 10sec 15sec so sec cosec um Tess Management Toolkit software can be found in section 6 7 Figure 6 4 Menu Map to Normal Sampling Rate Setting Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix 4 22 User Manual Rev 4 May 2012 Honeywell Process Solutions 6 3 Selecting the Abnormal Transmission Rate NOTE If the device is not configured to check for abnor mal process conditions using the Sampling Bands the Abnormal Transmission Rate is not used and this section can be ignored Input Volts 10 Abnormal Condition Abnormal Transmission Normal Transmission Normal Upper Normal Transmit Rate of 1 Min Abnormal Transmit Rate of 10 Sec Normal Upper Value of 2 5 Figure 6 5 Example of Abnormal Transmission Rate Setting p e e Using Wireless Management Toolkit Wireless Temperature Transmitter The Abnormal Transmission Rate is identical to
9. the Normal Transmis sion Rate with one exception The Abnormal Transmission Rate only ap plies while the Transmitter is in an abnormal condition see Section 6 6 Selecting the Normal Upper and Lower Values This allows an increase or decrease in the frequency of information you receive depending on the operating conditions of the process being monitored In order to properly set the Abnormal Transmission Rate determine how often updates are needed from the Transmitter when the process being monitored is operating under normal conditions The Transmitter has a selectable range of 5 10 15 20 40 seconds and 1 minute Figure 6 5 is an example of how the device switches transmission rates from Normal Transmission Rate to Abnormal Transmission Rate Note how the first abnormal transmission is sent immediately when the Normal Upper Value set point is exceeded The next transmission will then follow this immedi ate transmission by 10 seconds or whatever the Abnormal Transmission Rate is set to The transmissions will continue at this interval until the process value drops below the Normal Upper Value set point Once the process value drops below this set point another transmission is sent to the Base Radio The transmissions will then be sent at the Normal Transmission Rate of one minute the current setting for the Normal Transmission Rate from the time of the last abnormal transmission The user should also note that the transmission time de
10. to Section 3 1 2 1 for the RSSI Diagnostic or Section 3 1 3 for the Link Test User Manual 7 Honeywell Process Solutions Wireless Temperature Transmitter 3 1 3 1 Transmitter RSSI Diagnostic The Transmitter should be placed in RSSI Diagnostic mode to determine the signal strength at the location of the equipment to be monitored The RSSI Diagnostic located in the Transmitter s diagnostic menu dis plays the RF signal strength in one of seven ranges The signal strength is displayed on the LCD using a combination of gt and characters Full signal strength is displayed as gt gt gt gt gt gt gt while minimum signal strength is displayed as gt lt lt If the Transmitter is not communi cating with the Base Radio 1 e NO RF all underscore characters will be displayed o The RSSI s measured every time the Transmitter receives a message from the Base Radio The signal strength of the received message from the Base Radio is calculated during this time The actual signal strength in dBm for each range 1s shown below Er 105 dBm amp 100 dBm amp 95 dBm amp 90 dBm amp 85 dBm amp 105 dBm 100 dBm 95 dBm 90 dBm 85 dBm 80 dBm 80 dBm To place the Transmitter in RSSI Diagnostic mode follow the menu map shown in Figure 3 2 Note that the RSSI menu is under the DIAGNSE menu and not the CONFIG menu EE Eo eee OPERATIONS SEQUENCE eee eee NEXT na NEx
11. to three different RF IDs between 1 and 42 The Transmit ters in this example could be set to RF IDs 1 2 and 3 First determine the RF ID s you d like to give each unit Then follow the menu map shown in Figure 5 3 to configure the RF ID The factory de fault is RF ID 0 which disables the RF communication of the unit I l ENTER RF CHAN NEXT NEXT ENT ID euer Default of 000 Figure 5 3 Menu Map to RF ID Setting Once you have selected the RF ID you wish to use for this particular Transmitter exit the menus and return to the Operations Sequence The Transmitter should now be successfully configured to the Base Radio To check this press ENTER while the Transmitter is in the Operations Sequence for the Read Only Sequence to be displayed You may see an RF SYNC message displayed on the Transmitter LCD This means that the Transmitter and Base Radio are attempting to synchronize communica tions If this is successful the RF Status will display an RF OK message If this is unsuccessful the RF Status will display a NO RF message Also notice the two small arrows on either side of the LCD if they are fluctuating up and down that indicates the Transmitter and Base Radio are successfully communicating If only one or none of the arrows are moving then they are not communicating successfully 20 User Manual Rev 4 May 2012 Section 6 Wireless Temperature Transmitter Configuring the Sampling and Transmissi
12. 0 15 20 40 seconds and 1 minute The factory default is 10 seconds Fe eee ee am Default of 10 Seconds SAMPING HENTER NORM KR HENTER 5 SEC 10 SEC 15 SEC 20 SEC 40 SEC 1 MIN Figure 6 1 Menu Map to Normal Transmission Rate Setting Using Wireless Management Toolkit If all of the data does not get through the data is resent the following second This prevents data from being lost Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A Rev 4 User Manual 21 May 2012 Honeywell Process Solutions Wireless Temperature Transmitter 6 2 Selec ting the Normal The Normal Sampling Rate is the interval in which the Transmitter reads vas the monitored process value As previously mentioned the Transmitter is Sampling Rate in sleep mode to save power during the operations sequence This mode turns off most of the electronics on the unit with the exception of the LCD in order to preserve battery life The Transmitter will then wake up for every Normal Sampling Period and take the necessary process value readings Notice that the minimum speed of the Normal Sampling Rate is dependent on the Normal Transmission Rate setting selected earlier see section 6 1 The Sampling Rate cannot be slower than Normal Sampling Rate Thus if you set the Normal Transmit Rate setting to be 10 seconds the Normal Sampling Rate must be set to 10 seconds or faster A complete table of these p
13. 2 Point Curve The Transmitter can be used in many different types of applications To accommodate these various options there are various engineering units that can be selected Please note that the units selected apply to both Input 1 and Input 2 Each input may not use different units To select units of measurement follow the Transmitter menu map shown in Figure 7 1 The factory default units is Degrees C If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details The process variable units should be entered using the Wireless Management Toolkit software To do so enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the General tab to bring up the general information To select the units click the drop down box labeled Input Units Select units you wish to use from the available list Once a valued has been entered click OK to save and download the con figuration changes to the Transmitter Depending on the type of thermocouple or RTD the user intends to em ploy for temperature measurement the sensor setting must be set to the corresponding sensor type For a Thermocouple Transmitter the factory default is a J thermocouple In the case of a WT531T this setting refers to both thermocouple inputs Th
14. 4 May 2012 Wireless Temperature Transmitter The Link Test measures the wireless link performance of a Transmitter run ning in its normal operating mode Messages are sent from the Transmitter to the Base Radio at a predefined interval called the Transmit Rate see Sec tion 6 1 Each message contains data for the previous time period since the last transmit The Link Test looks at the wireless performance going in both directions from the Transmitter to the Base Radio and vice versa and comes up with a rating The result that appears on the display shows the determined link strength In order to perform this test the Transmitter must be communicating on the same channel and baud rate as the Base Radio See Section 5 to configure communications The Link Test may be conducted from the Transmitter Base Radio or through WMT Running the Link Test from WMT is ideal for testing com munications for an installation with remote or hard to get to Transmitters To conduct the Link Test from a Base Radio see Section 3 1 3 2 To con duct the Link Test from WMT see Section 3 1 3 3 The Link Test is located in the Transmitter s diagnostic menu see Figure 3 3 ENTER gt gt gt gt gt gt gt NEXT gt gt gt gt gt gt ext gt _TEST_ sc gt gt gt gt gt gt gt NO LINK NTER Figure 3 3 Transmitter Link Test Using the NEXT and ENTER buttons navigate to Link Test and press the ENTER button to begin the te
15. C T4 Ga Ta 40 C to 65 C O Intrinsically Safe ic HON 06 0201 II 3G Ex ic IC T4 Ge Ta 40 C to 65 C Rev 4 User Manual 31 May 2012 Honeywell Process Solutions Wireless Temperature Transmitter Technical Specifications continued e Specification Modification RF Immunity EN 61000 4 3 Modified Accuracy for RING AoA Petar Performance Criteria A per EN 61326 WT531R xx 3X 230 250 MHz 1 WT534R xx 3X 0 1 of Full Scale 450 MHz 3 32 User Manual Rev 4 May 2012 Honeywell Process Solutions Wireless Temperature Transmitter 97 82 3 85 Split Architecture WTS531R and WT531T gas cue m H M IL 312 9 12 2 Integrated Architecture WT532R and WT532T 174 9 6 9 LEN GTH DETERMINED BY CUSTOMER Dimensioned Mechanical Drawings Rev 4 User Manual 33 May 2012 Appendix A Wireless Temperature Transmitter Navigating User Menus Pressing either the NEXT or ENTER buttons located on the front of the Transmitter or Base Radio just below the Liquid Crystal Display LCD screen 1s all that is needed to navigate the respective menus Pressing both of these buttons for one second will turn the unit on Pressing the NEXT button at any time while the Transmitter is cycling through the normal messages causes the Transmitter to enter the setup mode The NEXT button is then used to step through menu options and the ENTER button is used to enter a sub menu of what is disp
16. Honeywell Wireless Temperature Transmitter User Manual Europe 868 MHz Band XYR 5000 Line 34 XY 25 52 Rev 4 May 2012 il User Manual Rev 4 May 2012 User Manual Wireless Temperature Transmitter Models WT531 and WT532 Versions 1 70 or later Important Information to the User A Changes or modifications not expressly approved by the manufacturer may void the user s authority to operate the equipment This device is for mobile and fixed use only not portable or body worn A separation distance of 20cm must be maintained at all times between the antenna and the body of the user and bodies of nearby persons If the Wireless Management Toolkit RF Server software is shutdown the RS 485 network MUST be physically disconnected from the PC as the serial port is no longer being controlled by the software and may disrupt communications between the Base Radio s and Analog Digital Output Module s This device has been designed to operate with an antenna having a maximum gain of 9 dBd Antenna having a higher gain is strictly prohibited per regulations of Industry Canada The required antenna impedance is 50 ohms To reduce potential radio interference to other users the antenna type and its gain should be so chosen that the equivalent isotropically radiated power EIRP is not more than that required for successful communication The installer of this radio equipment must ensure that the antenna is located or pointed s
17. MHz frequency range with power levels ranging up to 500 W Part 3 Harmonized EN covering essential requirements under article 3 2 of the R amp TTE Directive EN 300 489 1 2005 Electromagnetic compatibility and Radio spectrum Matters ERM Electromagnetic Compatibility EMC standard for radio equipment and services Part 1 Common technical requirements EN 300 489 3 2002 Electromagnetic compatibility and Radio spectrum Matters ERM Electromagnetic Compatibility EMC standard for radio equipment and services Part 3 Specific conditions for Short Range Devices SRD operating on frequencies between 9 kHz and 40 GHz and EN 61326 1997 A1 A2 Electrical Equipment for Measurement Control and Laboratory Use EMC Requirements Conformity of this product with any other CE Mark Directive s shall not be assumed Specification Modification RF Immunity EN 61000 4 3 Modified Accuracy for PLAN Cara ACCURACY Performance Criteria A per EN 61326 WT531R xx 3X 230 250 MHz 1 WT534R xx 3X 79 1 of Full Scale 450 MHz 3 2 User Manual Rev 4 May 2012 Honeywell Process Solutions Wireless Temperature Transmitter 1 4 UNPACKING Remove the Packing List and check off the actual equipment received If you have any questions about your shipment please call your Honeywell Representative Upon receipt of the shipment inspect the container for any signs of damage in transit Especially take note of any evidence of rough handl
18. NY Ma ma AQ Go Ro No m NO m JNNA WD gt B pd u NO O NO NO ho NAN AND MN NO MO dO ima YO NM BON mm ho DB SD m nm nm X 0O OCC hd w WW w An BY 09 vi User Manual Rev 4 May 2012 Section 1 Wireless Temperature Transmitter Introduction 1 1 USING THIS MANUAL This manual is designed to assist in installing operating and maintaining Honeywell Model WT531T and WT531R Temperature Transmitters The manual is broken into sections as follows Section 2 Quick Start This section summarizes what must be done in order to get the device in stalled configured and in operation quickly However it does not provide detailed or how to information to perform the tasks outlined Section 3 Installation This section explains how to correctly wire the Thermocouple RTD In puts Input Switches and ground the Transmitter Also covered in this section are mechanical installation considerations such as Transmitter placement Section 4 General Configuration In this section general configuration options such as password protection and selecting a user password are discussed Also covered is the setting of a Transmitter tag name resetting of all Transmitter settings and a discus sion of the various messages that are displayed on the Transmitter LCD Section 5 Configuring the RF Communications This section covers the setup of the Transmitter RF Communications that allow the Transmitter to achie
19. Properties 00001047 1 47 The SmartRate feature causes the field unit to transmit its data immediately any time the primary value changes by the amount set C Enable SmartRate on Input 1 C Enable SmartRate on Input 2 Smart Smoothing The Smart Smoothing feature rejects noise and glitches by averaging samples within the deadband and ignoring the first sample outside the deadband _ Enable Smart Smoothing Load from File General Inputs Range Sensor Offset Output Switches Sampling Hates SamplingBands Alarms Update Rates Normal Transmit Rate 1 Sec v Abnormal Transmit Rate 1 Sec ix Normal Sampling 1 Sec v Abnormal Sampling 1 Sec SmartRate Figure 6 9 Smart Rate Configuration Using Wireless Management Toolkit Rev 4 May 2012 Wireless Temperature Transmitter The Smart Rate is a feature used to trigger radio transmission of the meas ured data sooner than the normal or abnormal rate specified by the user This feature is used to construct a more accurate graph of the measured process value vs time than is possible with the fixed transmission rates while using less battery power To configure the Smart Rate Threshold follow the user menu to the SMART R menu and press the ENTER button The user is then asked to enter the amount that the process variable must change since the last data sample in order to trigger a new transmission of the process variable I
20. T gt DIAGNSE NExT FACTORY next gt EXIT ENTER ee ee r 1 USER PROMPTED FOR PASSWORD UF Figure 3 2 Menu Map to RSSI Mode Now that the Transmitter is in the RSSI mode bring the Transmitter close to the equipment you wish to monitor Look at the LCD notice the gt will constantly fluctuate One should estimate an average value based on these fluctuations The ideal signal integrity 1s seven arrows Once you have verified that you are receiving a signal you should check to make sure the Transmitter 1s communicating properly with the Base Radio To do so exit the RSSI by pressing ENTER and then navigate to EXIT of the diagnostic menu and return to the Operations Sequence shown in Figure 4 1 in Section 4 2 If you see a NO RF message then you do not have satisfactory RF com munication with the Base Radio If your application allows move the Transmitter to a different position and check again for communications One final solution is to reposition the Base Radio However this may af fect communications with previously installed Transmitters and if so may require the use of a second Base Radio for your application To select a better spot for the Base Radio see Section 3 1 1 of the Base Radio User Manual 8 User Manual Rev 4 May 2012 Honeywell Process Solutions 3 1 4 Link Test 3 1 4 1 Conducting a Link Test from the Trans mitter 3 1 4 2 Conducting a Link Test from the Base Radio Rev
21. arameters is shown below Baud Rate Input communication range 600 m 2000 ft Volts speed of updates 10 8 Transmit Rates Greater Normal and Abnormal 6 Normal Sampling Rates Rate or Less Sample In order to properly set the Normal Sampling Rate determine how often updates are needed from the Transmitter when the process being moni tored 1s operating under normal conditions The Transmitter has a select Time min With a Normal able range of 1 5 10 15 20 30 and 60 seconds depending on the Normal Sampling Rate of 30 Seconds Transmission Rate The factory default 1s 1 second However the more Figure 6 2 Incorrect Sampling Rate frequently the Transmitter wakes up to check the monitored device the faster you will use up the battery life of the Transmitter hoond Figure 6 2 is an example of what happens when the Normal Sampling Rate 10 is too slow for the process being monitored Notice how the rise in the voltage level falls between two normal samples and thus goes completely E undetected 6 Normal Figure 6 3 1s an example of what happens when the Normal Sampling Rate is correctly set for the device that s being monitored Notice how this set ting makes it possible to sample the rise in the voltage level 0 1 00 2 00 Once you have decided on the proper Normal Sampling Rate follow the Time min With a Normal Transmitter menu map shown in Figure 6 4 to select this setting The fac Sampling Rate
22. at it requires no peri odic calibration or system checks The Transmitter has a self diagnostic which is constantly checking the internal system If any errors are found they are reported via the LCD Base Radio or the software A simple yearly visual inspection for the following is all that is needed e Is the Transmitter still securely fastened to the equipment being monitored e Are there any visible corrosions cracks or residue build ups on the unit e Has anything about the application changed from the original intended use The battery will need to be changed within one month of seeing a LOW BAT message on either the Transmitter or in WMT This is a simple process 1 Make sure you have the correct replacement battery Lithium Inorganic Battery non rechargeable Size C 3 6Volts Tadiran TL 2200 Tadiran TL 5920 Tadiran GmbH SL 2770 2 Simultaneously press and hold the NEXT and ENTER buttons to power down the Transmitter Then enter the password 3 Remove the 4 set screws on the sides of the Transmitter housing with a standard screwdriver 4 Remove the housing and locate the battery Warning When removing the housing do not twist or bend the green flex cable Doing so may cause the tether to improperly seat next to the antenna and greatly reduce operable RF distances Do not allow the housing to flop around while hanging by the tether 5 Remove the old battery and replace it with the new bat
23. b menu of what is displayed on the LCD at that time If no button is pressed within a 30 second period the unit goes back to the normal display mode If you enter a sub menu that requires a numerical input such as 001 the leftmost 0 will be blinking This indicates that pressing the NEXT button will increment this value with each press from 0 to 9 and back to 0 again Pressing the ENTER button will move to the next available value If the last value is blinking pressing ENTER will save the entered values and return from the sub menu If both the NEXT and ENTER buttons are depressed at the same time a message on the LCD displaying OFF will appear If both buttons are re leased upon appearance of this message the user will be returned to the scrolling main screen If both buttons are not released for the duration of the OFF message you will be prompted for the password Upon entering the correct password the unit will power down and turn off To turn the Transmitter on press and hold both the NEXT and ENTER buttons for a few seconds Upon power up the Transmitter will display the Power Up Sequence and then go into the Operations Sequence These sequences are shown n Figure 4 1 User Manual Rev 4 Honeywell Process Solutions 4 2 Continued jg f POWERUPSEOUNE During configuration and testing keep Transmit ters at least six feet from the Base Radio and other Transmitters MRS es D 1 OPERATIONS SEQUENCE Hei XX XXIN1
24. be on the same RF Channel and must be transmitting at the same Baud Rate While all Transmitters and Base Radios are set to default con figurations at the factory if any configuration differences are present the Base Radio will not be able to communicate with the Transmitters The subsections are as follows 5 1 RF Channel Setup 5 2 RF Baud Rate Setup 5 3 RF Identification Setup Warning If the Transmitters have been running for an extended period of time with no signal from the Base Radio the Base Radio 1s off or not present the Transmitters will only search for the Base Radio every one hour or so Turning the Transmitters off and back on will cause them to begin searching immediately e The RF Channel defines a set of frequencies on which communication 5 1 RF Channel Selection takes place between the Base Radio and the Transmitter Each RF Channel has a different set of frequencies thus allowing the user to have multiple different wireless networks co existing throughout the same facility All Base Radios and Transmitters can be set to one of 4 different RF chan nels The only Transmitters recognized by a particular Base Radio are the The RF Channel defines a set of frequencies on units that are on the same RF Channel as that Base Radio This allows the which communication takes place between the user to decide which Transmitters communicate with each Base Radio Base Radio and the Transmitter Each RF Channe
25. d ENTER buttons The Wireless Man agement Toolkit requires a user login password to gain access to all con figuration parameters However user accounts are available and can be set with different access levels and restrictions For more information on user accounts see the Wireless Management Toolkit User Manual Section 8 4 To reset all Transmitter settings to their default state you must navigate to the DEFAULT menu option in the CONFIG menu via the keypad Once at the default menu option pressing the ENTER button will display RESET on the LCD which asks if you are sure you want to reset the device to its default configuration You will then be prompted with NO on the LCD Pressing the ENTER button while NO is being displayed will NOT reset the device Pressing the NEXT button will display YES on the LCD If you press the ENTER button while YES is being dis played the device will be reset Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A User Manual 17 Honeywell Process Solutions 4 6 Continued 18 May 2012 Wireless Temperature Transmitter re e e e e e ee ee rm en 1 ENTER Figure 4 7 Menu Map to Reset All Transmitter Settings User Manual Rev 4 Section 5 Wireless Temperature Transmitter Configuring the RF Communications IN Warning IN In order for the Transmitter and the Base Radio to communicate they must
26. e Base Radio entirely This proce dure is easy to implement but please read carefully for a full understand ing The Base Radio synchronizes with the Transmitters in Synch Groups of 7 organized by their RF ID numbers If you want to place two Transmit ters closer than 6 feet make sure that you have set them in different groups Note that this only applies to Transmitters that are communicat ing with the same Base Radio The groups are defined in the table to the left For example if two Transmitters are placed one foot apart and the first Transmitter has an RF ID number of 027 that means it is in the 4th group 22 28 The second Transmitter must have an RF ID number that is in another group less than 22 or greater than 28 Setting the RF IDs of two closely spaced Transmitters so that the RF ID numbers are greater than 7 apart ensures that the Transmitters are in different Base Radio sync groups This allows the closely spaced Transmitters to properly receive their synchronization signal from the Base Radio and maintain their proper communication and range You can also ensure that closely spaced Transmitters maintain their syn chronization with their Base Radio by simply assigning each of the two closely spaced Transmitters to talk to a different Base Radio Parts of the enclosure are non conducting and may generate an ignition capable level of electrostatic charge under certain extreme conditions The user should ensure that the e
27. ement of the Transmitter will optimize your RF communication range and capabilities Perhaps the best test to perform before mechanically mounting the unit is a quick hand held test There are two types of tests you can conduct the RSSI Received Signal Strength Indicator Diagnostic and the Link Test The RSSI Diagnostic measures the strength of the signal at the Transmitter The Link Test measures the throughput of data sent to and from the Transmitter The Link Test may be conducted from the Transmitter Base Radio or through WMT The RSSI Diagnostic should be conducted first to determine if the Base Radio is communicating with the Transmitter Then the Link Test may be performed to test the validity of the installation To perform these tests you should have a good idea of where the Base Radio will be placed for more information see Section 3 of the Base Radio User Manual Put the Base Radio in this area and power it up Make sure that the Base Radio and Transmitter are on the same RF Chan nel and Baud Rate See Section 5 You may also have to increment the number of Transmitters with which the Base Radio is communicating See the Base Radio User Manual Section 4 3 Once both the Base Radio and Transmitter are set up to be on the same network make sure communication is established by looking at the Transmitter LCD for the RF OK message in the Read Only Sequence see Section 4 2 1 After communications have been established go
28. er set to the above listed settings e Is the Base Radio on Do the Transmitter and Base Radio settings match See Section 5 of Transmitter and Base Radio User Guides e Are the Base Radio and Transmitters unable to communicate due to obstructions or distance See Section 3 1 1 Trans mitter Positioning Warning X Warning If the Transmitters have been running for an extended period of time with no signal from the Base Radio the Base Radio is off or not present the Transmitters will only search for the Base Radio every one hour or so Turning the Transmitters off and back on will cause them to begin searching im mediately User Manual Rev 4 Section 3 Wireless Temperature Transmitter Installation 3 1 Mechanical Installation In this section mechanical installation instructions are discussed for the various setup capabilities of the Temperature Transmitters Each Temperature Transmitter a rugged device but it provides much bet ter performance if installed with careful consideration as noted in this manual It may be utilized in any Temperature measurement service so long as care is exercised to prevent exposing the sensing elements to ex cess stress or temperature Installation practices have a lot to do with these service parameters and the life that you can expect from your Temperature Warning IN Transmitter s Warning During installation do not Give careful consideration to the environment where you wil
29. eral Configuration 4 1 Navigating User Menus NOTE If the unit is turned off while entering values in a sub menu those values will NOT be saved There are several menu options that will automati cally turn off if you are using WMT All changes to these Transmitter menu options should then be made through WMT instead This is to prevent simultaneous changes from taking place If you wish to discontinue use of the software and want these menus re instated you must contact your Honeywell Sales Representative 4 2 Transmitter Displayed Messages 14 May 2012 This section discusses the generalities for configuring the Transmitter via the NEXT and ENTER buttons The subsections are as follows 4 1 Navigating User Menus 4 2 Transmitter Displayed Messages 4 2 1 The Read Only Sequence 4 3 The Overall Configuration Menu Map 4 4 Setting the Transmitter Tag Name 4 5 Setting a User Password 4 6 Resetting All Transmitter Settings Pressing either the NEXT or ENTER buttons located on the front of the Transmitter or Base Radio just below the LCD screen is all that is needed to navigate the respective menus Pressing both of these buttons for one second will turn the unit on Pressing the NEXT button at any time while the Transmitter 1s cycling through the normal messages causes the Transmitter to enter the setup mode The NEXT button is then used to step through menu options and the ENTER button is used to enter a su
30. es it difficult to measure parameters that have an economic impact on your plant opera tion but the Temperature Transmitter allows you to quickly and accu rately monitor those devices at a fraction of the cost which gives you big ger and faster returns on your instrumentation investments The Transmitters communicate in a secure digital protocol over a band of frequencies from 869 4 MHz to 869 65 MHz This data communication technique has been the backbone of the military s secure communications protocols for many years These devices require no wires permits or li censes and they are easily set up and installed right out of the box You can use this device for long term monitoring in remote locations for short term data gathering on process conditions or to quickly test the eco nomic viability of a new installation The purpose of this manual is to help you install and maintain your Hon eywell Temperature Transmitter BEFORE setting up and installing the Transmitter please setup and configure the Base Radio 1 3 CE Conformity These models are in conformity with the protection Tequirements of European Council Directives 89 336 EEC the EMC Directive Generic Immunity Standard for industrial environments and 1999 5 EC the Telecommunications Directive in accordance with EN 300 220 3 2000 Electromagnetic compatibility and Radio spectrum Matters ERM Short Range Devices SRD Radio equipment to be used in the 25 MHz to 1 000
31. f the process value changes by more than the entered Smart Rate amount within the normal or abnormal sampling rate whichever is active then the process variable is transmitted immediately The normal abnormal transmit clock is then reset upon this transmission If no Smart Rate amount exceeding change takes place in the next normal abnormal sample then the next transmission will be the normal abnormal transmit rate pe riod The amount entered is in the same units as were selected by the user to be displayed on the Transmitter If the measured process value does not change by more than the entered Smart Rate amount within the time be tween the sampling rate whichever is active then the process value is transmitted on the next transmit rate If changes in the process value which exceed the Smart Rate Amount continue to occur the process value is transmitted repeatedly If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software s being used See Appendix A for more details The Smart Rate should be enabled using the Wireless Management Toolkit software To do so enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the Sampling Rates tab to bring up the sampling rate information as shown in Figure 6 9 To enable the Smart Rate click the check box labeled
32. gnored Abnormal Condition Abnormal Normal Upper Value Normal Sampling Rate of 15 Sec Abnormal Sampling Rate of 5 Sec Normal Upper Value of 2 5 Figure 6 7 Example of Abnormal Sampling Rate Setting Using Wireless Management Toolkit Wireless Temperature Transmitter The Abnormal Sampling Rate is identical to the Normal Sampling Rate with one exception The Abnormal Sampling Rate only applies while the Transmitter is in an abnormal condition see 6 6 Selecting the Normal Upper and Lower Values This allows an increase or decrease of the fre quency of information you receive depending on the operating conditions of the process being monitored In order to properly set the Abnormal Sampling Rate determine how often updates are needed from the Transmitter when the process being moni tored is operating under normal conditions The Transmitter has a select able range of 1 5 10 15 20 40 seconds and 1 minute Figure 6 7 is an example of how the device switches sampling methods from Normal Sam pling Rates to Abnormal Sampling Rates Note how the first abnormal sample is taken a few seconds after the Normal Upper Value set point is exceeded The next sample will then follow this sample by 5 seconds or whatever the Abnormal Sampling Rate is set to These samples will con tinue at this interval until the process value drops below the Normal Upper Value set point Once the process value drops below this set point the sam
33. ing Report any apparent damage immediately to the shipping agent Please note that sometimes units are assembled with accessories when shipped Inspect the shipment carefully if you think that something 1s missing This is rare as we take considerable care to pack units for ship ment but 1t does sometimes happen Please give us a call and we may be able to resolve this matter quickly over the phone Please note that the carrier will not honor any claims for damage unless all shipping materials are saved for their examination If damage is found during examining and removal of the contents save the packing material and the carton 1 5 SOFTWARE Software for Honeywell is revised periodically Internal device software may contain portions that are not compatible with previous versions of the COMPATIBILITY Wireless Management Toolkit software To ensure software compatibility Wireless Management Toolkit software version 1 70 138 or later must be used If you believe you are experienc ing software compatibility issues please call your local representative or email bill europe Honeywell com e mail Rev 4 User Manual 3 May 2012 Section 2 i 4 May 2012 Quick Start Contact Closure Device Wireless Temperature Transmitter This section summarizes what must be done in order to get the device in stalled configured and in operation quickly However it does not provide detailed or how to information to perform the tas
34. input wires should be routed into the back of the enclosure and threaded through the center of the circuit board RTD Input Red Wi Positive Wire White vive Negatve vire White Aire Ground Ground Bonding Bonding Wire Wee Wires should z be routed through hole and out the condun opening on the back of the housing Zn O Figure 3 8 RTD Input Wiring Diagrams User Manual Rev 4 Honeywell Process Solutions Wireless Temperature Transmitter 3 2 3 Wiring the Input Switches To properly wire a switch input device to the Temperature Transmitter Op tional simply follow the wiring diagram provided below Please note that loop power does NOT need to be supplied as the Transmitter supplies the moni toring power The Temperature Transmitter has the capability of monitor ing two input switches The most common application for the switch inputs 1s to monitor a contact NOTE closure However the input switches must only be attached to simple de The RTD Temperature Transmitter WT531R has vices A simple device is one that meets the conditions set forth in the In only ONE INPUT SWITCH trinsic Safety Control Drawing which can be found in the Technical Specifications section of this manual The diagram shown below in Figure 3 9 refers to the circuit board found at the base of the Transmitter within the junction box Before connecting wires to the terminal blocks the input wires should be routed into the back of the enclo
35. ition To select a proper Time Deadband consider the example in Figure 6 12 Notice that the Transmitter continues to cycle from Normal to Abnormal Conditions due to the fact that the input value is fluctuating around the 7 5 Volt Normal Upper Value This is undesired The addition of a few second delay before the Transmitter switches conditions will eliminate this chatter as seen in Figure 6 13 If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software 1s being used See Appendix A for more details An explanation of how to select the Abnormal Sampling Rate using the Wireless Management Toolkit software can be found in section 6 7 Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A User Manual Rev 4 Honeywell Process Solutions Wireless Temperature Transmitter 6 7 Selecting Rates Thresh If you have the Wireless Management Toolkit software the Normal and Abnormal Sampling and Transmission menu options will not be accessi olds and Deadbands via ble via the Transmitter once the Transmitter detects that the software is the Software being used See Appendix A for more details These settings should be entered using the Wireless Management Toolkit software To do so enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration me
36. ks outlined Ignore steps 1 thru 5 and 16 if you do not have the split architecture Transmitter 1 Install the Transmitter in the desired location of operation Note Trimming of the measurement may be necessary before the device can be placed in service If trimming is required perform steps 1 and 6 16 prior to placing device in service 2 Wire the channel input s as shown in top left figure 3 Wire input switches as shown in middle left figure optional 4 Ground the Transmitter via grounding screw provided in enclosure 5 Close enclosure and secure enclosure via set screw 6 Turn on the Transmitter by simultaneously pressing and holding the ENTER and NEXT buttons the until unit powers up 7 Set the RF CHAN setting equal to the Base Radio s RF Channel 8 Set the BAUD RT setting equal to the Base Radio s Baud Rate 9 Set the RF ID number to be a unique value between 1 and 42 10 Select normal transmission rate 11 Select normal sampling rate 12 Select abnormal transmission rate 13 Select abnormal sampling rate 14 Set normal upper and lower values 15 Select engineering measurement units 16 Select the thermocouple RTD sensor type If the RF OFF message is being displayed on the Transmitter LCD per form the following e Set the RF CHAN setting equal to the Base Radio s RF Channel If a NO RF message is being displayed on the Transmitter LCD check the following e Is the Transmitt
37. l has a different set of frequencies thus allowing the user to have multiple different wireless net The RF Channel can be thought of as a set of walkie talkies If both works co existing throughout the same facility walkie talkies are on channel one they can communicate If a walkie talkie is on channel one and the other is on channel two they cannot com municate Likewise if two walkie talkies are on channel one and two other walkie talkies are on channel two the walkie talkies on channel one cannot hear what is being transmitted by the walkie talkies on channel two Each Transmitter comes from the factory with the RF Channel set to OFF This means the Transmitter will not communicate to any Base Radio To set the Transmitter for communication first determine the channel that you want to use Then follow the Transmitter menu map shown in Figure 5 1 to configure the RF Channel Fa mE eee ee m 1 OPERATIONS SEQUENCE NEXT ee eee es am Y USER PROMPTED FOR PASSW Figure 5 1 Menu Map to RF Channel Setting Once in the RF Channel menu increment it by pressing the NEXT button When selecting this value do not choose an RF Channel that is currently being used by other Honeywell Wireless Systems as this can cause com munication problems 5 2 RF Baud Rate Selection The RF Baud Rate refers to the speed at which the Base Radio and Transmitters communicate The Baud Rate is not configurable It is set at 4 8K This allow
38. l be installing apply force to the instrument housing or your instrument Avoid installations that expose the device to excess tem antenna Use a proper wrench for all perature high vibration considerable shock or exposure to dripping con installations Failure to use correct in densate or corrosive materials Also avoid installing the device in an un stallation procedures can cause damage serviceable location to the Transmitter Most often these problems can be avoided with some thought at the time of installation The practices noted below are generally recommended but they can only act as a guideline and cannot cover all possible variations The final installation must be made at the discretion and approval of the user You must be the judge of the actual installation Dimensioned mechanical drawings for aid in mechanical installation are located in Section 9 Technical Specifications 3 1 1 Transmitter Positionin g Correct positioning of the Transmitter will ensure the best performance of the device When planning the positioning of the Transmitters there are a few parameters that must be paid attention to e The top of the Transmitter should point in an upward fashion The bottom of the Transmitter should NOT point directly at the Base Ra dio and the Transmitter LCD should point away from the Base Radio e All Transmitters should maintain an approximate spacing of at least six feet apart from one another Should you need t
39. layed on the LCD at that time If no button is pressed within a 30 second period the unit goes back to the normal display mode If you enter a sub menu that requires a numerical input such as 001 the left most O will be blinking This indicates that pressing the NEXT button will increment this value with each press from O to 9 and back to O again Pressing the ENTER button will move to the next available value If the last value is blinking pressing ENTER will save the entered values and return from the sub menu If both the NEXT and ENTER buttons are depressed at once a message on the LCD displaying OFF will appear If both buttons are released upon appearance of this message the user will be returned to the scrolling main screen If both buttons are not released for the duration of the OFF message the unit will power down and turn off Note If the unit is turned off while entering values in a sub menu those values will NOT be saved As shown throughout the document this mark indicates that these menu options will automatically turn off if the Wireless Management Toolkit Software is used All changes to these Transmitter menu options should be made through software instead This is to prevent simultaneous changes from taking place If you wish to discontinue use of the software and want these menus re instated you must contact your Honeywell Sales Repre sentative 34 User Manual Rev 4 May 2012 Appendix B Wireless Temperatu
40. ling transmission rates when the primary values are within the bands When the value is outside of the bands it is considered Abnormal and Abnormal rates are used Figure 6 15 Normal Upper and Lower Value Selection Using the Software Rev 4 User Manual 27 May 2012 Section 7 Wireless Temperature Transmitter Configuring the Process Variable 7 1 Selecting Unit of Measure ISEB DEPOMDTEN END NEXT Thermocouple Menu UNIT NTER DEG C DEG F KELVIN RANKIN MV Default of DEG C RTD Menu ENTER DEG C DEG F KELVIN RANKIN Default of DEG C Figure 7 1 Menu Map to Units Setting 7 2 Selecting the Sensor Type Se ae os eos as ee sl R T __ N amp T Thermocouple Menu IC B TIC C TIC E TIC J TIC K T C L TIC N kENTER INFUT A ENTER PHT CR TES T C T TIC CSPE RTD Menu SENSOR VENTER NPUTT J ENTER gt 4W DINP 4W SAMP 4W SPEC IK DINP NEXT Figure 7 2 Menu Map to Sensor Selection Setting 28 May 2012 Default of 4W DINP This section helps the user n the selection of engineering units as well as discussing the setting of a measurement offset selecting the sensor type and trimming the process measurement The subsections are as follows 7 1 Selecting Units of Measure 7 2 Selecting the Sensor Type 7 3 Setting a Measurement Offset 7 4 Trimming the Measurement 7 5 Entering a 2
41. n User Manual 9 Honeywell Process Solutions Wireless Temperature Transmitter 3 1 4 2 Continued Next enter the RF ID for the Transmitter that you want to test Then select the Normal Transmit rate that matches that of the Transmitter If the Trans mitter is transmitting at a different rate than the one you select in this menu your results will be invalid Once the Normal Transmit Rate is selected the Link Test will immediately start The Base Radio will begin to test the link from the Transmitter Dur ing this time the word TEST will appear on the LCD display When the test is complete the Base Radio will display the quality of the link Be aware that the length of time it takes to perform this test is dependent upon how fast the Transmitter is normally transmitting Figure 3 4 Base Radio Link Test When enough messages have been observed a link strength will be shown on the display gt gt gt gt gt indicates the strongest link while gt indicates the weakest link The Link Test will continue to be evaluated and the rating on the screen may adjust itself Keep in mind that the longer the Link Test runs the more data the Transmitter will have to evaluate The Transmitter installation site should strive to place the Transmitter in a location where it receives the highest number possible A stronger link means less data re transmits and better battery life 3 1 4 3 Conducting a Link Test from WMT To conduct a Link Test fr
42. nalog Input sensor If the measurement goes above 150 full range the unit will go into Sensor Fault mode In over range mode the measurement continues to be displayed with the OVERRNG message to remind the user that the specified range of the sensor and the calibrated range of the device is being exceeded Fatal error messages will replace the normal cycling message sequence and will flash A fatal message indicates the Transmitter is no longer oper ating normally and requires repair These are e RFERR fatal error within RF communications e SENERR fatal error within the sensor electronics e SYSERR fatal error within the microprocessor system e RFCAL fatal error within the RF calibration system Rev 4 User Manual 35 May 2012 Appendix C Wireless Temperature Transmitter Transmitter Menu Map EXT fe me o ENTER Factory passwords will be hard coded User password will be 0000 from factory NEXT Note The Baud Rate determines the maximum speed of the Transmission Rates Rates determine the minimum speed of the Sample Rates If a user enters a value that is not within these bounds the value of entered bound will be changed automatically to allow proper Default of 1 en NAB e EMIS Svs gt R NEXT 0 300 SEC Defaults of Disabled Default of 0 ENS a oo ISABLE IF YES IS SELECTED NEW TRIM IS SAVE IF NO IS SELECTED TRIM POINT IS DISCARDED IF YES IS PRESSED
43. nsmitter will enter an Abnormal condition as seen in Figure 6 10 The Normal Upper Value would be an indication that the temperature is high and the Normal Lower Value would be an indication that tempera ture is low Thus the normal operating condition for the temperature application would be found n between the two Normal Values To config ure the adi follow the Transmitter menu map shown in Figure 6 11 Veep DDAMDTEN EoD 1 DISABLED 0 300 SEC ENABLED Conia es A DISABLED Defaults of Disabled Default ot O Default of both ENTERS EN DIS JENABLE eal x here enabled E oisaBLeD VA e XX XX NEXT Figure 6 11 Menu Map to Normal Upper and Lower Value Settings When configuring the Normal Values you will first be prompted to enable the input You should only disable an input if it will not be used Once an input has been enabled the user may enter a Normal Upper Value Normal Lower Value and the Smart Rate Threshold see Section 6 5 If for example the Normal Upper Value is enabled the next prompt you will receive is XX XX for the process variable value Increment this value to the desired value and press the ENTER button The may be toggled on and off as well The final prompt you will receive is the Time Deadband prompt The Time Deadband refers to the number of seconds that the measured reading must stay n a certain condition before the Transmitter will actually switch to that cond
44. ntial to avoid ground loop effects Thermocouple Input 1 Positive Mro Negative Wire Wires should be routed through hole and out the condunt opening on the back of the housing gt 7 0 Figure 3 7 Thermocouple Input Wiring Diagrams If using two thermocouples remember to enable both thermocouple inputs otherwise the measure ment of the disabled thermocouple will not be made 12 May 2012 Wireless Temperature Transmitter In this section wiring instructions are discussed for the various setup capa bilities of the Temperature Transmitter This section only applies if you have ordered the WT531T or WT531R If the integrated architecture ver sion of the Temperature Transmitter has been purchased then skip the electrical installation section The subsections are as follows 3 2 1 Electrical Specifications 3 2 2 Wiring the Thermocouple RTD Input 3 2 3 Wiring the Input Switches Input Switch Characteristics e For simple device monitoring only 1 e contact closures e Input switches share common ground To properly wire a thermocouple RTD to the Temperature Transmitter follow the wiring diagram provided below Please note that a thermocou ple CANNOT be wired to a WT531R unit and a RTD CANNOT be wired to a WT531T unit The diagram shown in Figure 3 7 below refers to the circuit board found at the base of the Transmitter within the junction box Before connecting wires to the terminal blocks the
45. nu click on the Sam Dual 0 10 V Input Properties 00001047 1 47 General Inputs Range Sensor Offset Output Switches Sampingates Sampling Bands Alems pling Rates tab to bring up the sampling rate information as shown in er Figure 6 14 Normal Transmit Rate 10 Sec v a m To select the Normal Transmission Rate select one of the time periods EN TEE from the drop box Next select an Abnormal Transmission Rate in the m SS same manner Note that the Normal and Abnormal Transmission Rate can be the same The SmartRate feature causes the field unit to transmit its data immediately any time the primary value changes by the amount set L Enable Smartflate on Input 1 Once the transmission rates have been selected the user should select the desired sampling rates Note that the sampling rate must be equal to or faster than the associated transmit rate For example in Figure 6 14 the Normal Transmission Rate s set to 10 seconds and the Normal Sampl ng Rate is also set to 10 seconds This is a valid configuration Another ex ample in Figure 6 14 is the Abnormal Transmission Rate being set to 3 seconds and the Abnormal Sampling Rate being set to 1 second C Enable SmartRate on Input 2 Smart Smoothing The Smart Smoothing feature rejects noise and glitches by averaging samples within the deadband and ignoring the first sample outside the deadband Enable Smart Smoothing If you incorrectly enter
46. o put Transmitters i tere closer than six feet please see Section 3 1 1 1 Technique for Close Positioning of Transmitters e The line of sight range between a Transmitter and Base Radio is 600 m 2000 ft Note that this range is reduced by the amount of RF Noise present obstructions and the material properties of the obstruc tion Obstruction e Only place the Transmitter in ambient operating temperatures of 40 F to 185 F 40 C to 85 C Figure 3 1 Examples of Incorrect Transmitter Positioning Figure 3 1 gives examples of incorrect setups according to the previously mentioned parameters Because there are so many setup possibilities we cannot cover them all A correct setup would make sure that the above warnings are heeded and that the Transmitter and Base Radio are capable of communication The Testing Communications section will help you to determine if you have selected the correct installation points and orientations for your applica tion Rev 4 User Manual 5 May 2012 Honeywell Process Solutions 3 1 1 1 Technique for Close Positioning of Transmitters 29 35 a 3 1 2 Special Conditions for Safe Use 6 May 2012 Wireless Temperature Transmitter Transmitters may be placed closely together by carefully following this procedure If this procedure is not followed the communication range of the Transmitters will be significantly reduced and the Transmitters may eventually lose communication with th
47. om WMT make sure that WMT is running on the PC attached to the Base Radio Then go to the Transmitter view and right click on the Transmitter you want to test Received data transmission from p Honeywell Wireless Management Toolkit Connected File View Help Field Units All Field Units dee Total Field Units 2 I Alarming Field Units er h 7 Alarming Field Units 1 S pa Field Units Warming Field Units 1 a ield Unit Groups J L Base Radios Field Unit Types Selected Field Unit Honeywell Dual 4 20 m Input Field Units All Field Units TagName Monitored Equipment 1D__ DeviceType Status eet amen 14 009 Temperature ATD ISENSOR FAULT 1 0 Devices AMME Rename 14 041 Dual 4 20 mA Input OK IN1 35 00 mA 1 0 Tasks View Field Unit Data Tasks Configuration Export Data Accounts 7 13 2006 11 12 10 AM Device discovery completed 0 new devices found 0 devices removed 2 Total Field Units Alarming Field Unit Figure 3 5 WMT Transmitter View 10 User Manual Rev 4 May 2012 Honeywell Process Solutions 3 1 4 3 Continued Rev 4 May 2012 Wireless Temperature Transmitter Select Wireless Data Loss Test from the popup menu The Wireless Data Loss Test window appears Figure 3 6 The name of the Transmitter being tested appears in the title bar in parenthesis Wireless Link Test Unit 14041 Configure Test Hours Minutes Seconds Progress Restoring old configuration
48. on Rates The Temperature Transmitter is very versatile with many programmable features and can be used in numerous different applications Because no two applications are the same some configuration is required for each unit This section will walk you through the initial configuration of these sample and transmit settings The subsections are as follows 6 1 Selecting the Normal Transmission Rate 6 2 Selecting the Normal Sampling Rate 6 3 Selecting the Abnormal Transmission Rate 6 4 Selecting the Abnormal Sampling Rate 6 5 Setting the Smart Rate Threshold 6 6 Selecting the Normal Upper and Lower Values 6 7 Selecting Rates Thresholds and Deadbands via the Software 6 1 Selecting the Normal The Normal Transmission Rate is the interval in which the Transmitter a P transmits data to the Base Radio The Transmitter is in a sleep mode to Transmission Rate save power during the operations sequence This mode turns off most of the electronics on the unit with the exception of the LCD in order to pre serve battery life The Transmitter will then wake up every Normal Sam pling Period and take the necessary process value readings The Transmit ter will then transmit these readings to the Base Radio on an interval deter mined by the Normal Transmission Rate In order to properly set the Normal Transmission Rate you must first de termine how often you need updates from the Transmitter You have a selectable range of 5 1
49. on assistance current specifications pricing or name of the nearest Authorized Distributor contact one of the offices below ASIA PACIFIC EMEA NORTH AMERICA SOUTH AMERICA TAC Honeywell Process Solutions Honeywell Process Solutions Honeywell do Brasil amp Cia hfs tac Phone 80012026455 or 44 Phone 1 800 423 9883 Phone 55 11 7266 1900 support honeywell com ln Or 1 800 343 0228 FAX 55 11 7266 1905 a FAX 44 0 1344 655554 ustralia o Email Sales Honeywell Limited ease E o Email Sales Email Sales Phone 61 7 3846 1255 ask ssc honeywell com ask ssc honeywell com salespa62 honeywell com FAX 61 7 3840 6481 salespa62 honeywell com Toll Free 1300 36 39 36 or Toll Free Fax TAC TAC TAC 1300 36 04 70 hfs tac hfs tac hfs tac support honevwell com support honeywell com support honeywell com China PRC Shanghai Honeywell China Inc Phone 86 21 5257 4568 Fax 86 21 6237 2826 Singapore Honeywell Pte Ltd Phone 65 6580 3278 Fax 65 6445 3033 South Korea Honeywell Korea Co Ltd Phone 822 799 6114 Fax 822 792 9015 iv User Manual Rev 4 May 2012 Table of Contents Section 1 Introduction 1 1 Using This Manual 1 2 About the Device 1 3 CE Conformity 1 4 Unpacking 1 5 Software Compatibility Section 2 Quick Start Section 3 Installation 3 1 Mechanical Installation 3 1 1 Transmitter Positioning 3 1 2 Special Conditions for Safe
50. onfiguration menu to aid the user in setting up the Transmitter for proper operation 1 OPERATIONS SEQUENCE sca wae E Tim O pes ae a A a NEXT Lon TUE NG A DNS noo FACTOR nox oN ENTER 2 BED e o E a n USER PROMPTED FOR PASSWORD UF NEXT Menus are disabled if use of Wireless Instrumentation Manager is detected NEXT NEXT SAMPLING ENTE NORM XR NEXT NEXT corso mem ABNR XR NEXT NEXT NEXT NEXT EE ore DEFAUCTT NEXT NEXT cnet Figure 4 3 Overall Configuration Menu Map Each Transmitter has a user settable Transmitter Tag Name This Tag Name is displayed upon Transmitter power up and when the Read Only Sequence is selected The Tag Name is a 21 character string that is dis played in three separate 7 character flashes on the Transmitter LCD The user may choose from A Z 0 9 a dash and an underscore _ The underscore has a special meaning to the software inside the Transmit ter For example if you have a Tag Name that is only 5 characters long then you do not want to wait for the rest of the 16 characters to be dis played on the LCD So if your Tag Name was TANK 1 you would want to enter the Tag Name like this TANK1 ee ee ee a ee e ee ol NEXT NEXT ENTERS KKRRRRR ENTERS KKRRKRRF ENTERS XKKKRRR a b o Figure 4 4 Menu Map to Tag Name Setting Using Wireless Management Toolkit The Tag Name
51. pends on the sam pling rate and when the process value is sampled If the Normal Sampling Rate is 30 seconds then the process value may be above the Normal Up per Value for up to 29 seconds before an abnormal condition is detected This means that the transmission could be as late as 29 seconds after the process value exceeded the Normal Upper Value Once you have decided the proper time for the Abnormal Transmission Rate follow the Transmitter menu map shown in Figure 6 6 y USER PROMPTED FOR PASSWORD i Se ahah ns a NEXT NEXT SAMPLNG jenter ENORM XR NEXT NEXT Default of 5 Second ABNR XR HENTER 5 SEC 10 SEC 15 SEC 20 SEC 40 SEC 1 MIN Figure 6 6 Menu Map to Abnormal Transmission Rate Setting If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details An explanation of how to select the Abnormal Transmission Rate using the Wireless Management Toolkit software can be found in section 6 7 Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A Rev 4 May 2012 User Manual 23 Honeywell Process Solutions 6 4 Selecting the Abnormal Sampling Rate If the device is not configured to check for abnor mal process conditions using the Sampling Bands the Abnormal Sampling rate is not used and this section can be i
52. pling rate will return to the Normal Sampling Rate Also the Abnormal Sampling must be equal to or faster than the Abnormal Transmission Rate The user should also note that the transmission time depends on the sam ple rate and when the process variable is sampled If the Normal Sam pling Rate is 30 seconds then the process variable may be above the Nor mal Upper Value for up to 29 seconds before abnormal condition is de tected This means that the transmission could be as late as 29 seconds after the process variable exceeded the Normal Upper Value Once you have decided the proper time for the Abnormal Sampling Rate follow the Transmitter menu map shown in Figure 6 8 en PASSWORD a u eb ENTER NEXT NEXT Default of 1 Second CAEN SR ENTER 1 5 SEC 10 SEC 15 SEC 20 SEC 30 SEC 1 MIN Figure 6 8 Menu Map to Abnormal Sampling Rate Setting If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details An explanation of how to select the Abnormal Sampling Rate using the Wireless Management Toolkit software can be found in section 6 7 Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix A 24 User Manual Rev 4 May 2012 Honeywell Process Solutions 6 5 Setting the Smart Rate Threshold Dual 0 10 V Input
53. quipment is not installed or used in a location where it may be subjected to external conditions such as high pressure steam which might cause a build up of electrostatic charge on non conducting surfaces Additionally the equipment must be cleaned only with a damp cloth As aluminum may be used at the accessible surface of this equipment in the event of rare incidents ignition sources due to impact and friction sparks could occur This shall be considered when the Honeywell XYR 5000 series Transmitters are being installed in locations that specifically require group II category 1G equipment The following Honeywell Transmitter types have flying leads and require installation in suitable conduit The leads shall be terminated such that they are provided with adequate protection appropriate to the intended installation location e WT533R a 3G RTD Temperature Transmitter Split Unit e WYT533T a 3G T C Temperature Transmitter e WW593 3G Dual Switch Input Transmitter e WIS5S5 3G Dual 4 20mA Transmitter e WI556 3G Dual 0 10V Transmitter The Sensor terminals and the Input SW terminals of the following Honeywell XYR 5000 series Transmitter types shall be installed as separate intrinsically safe circuits e WI555 3G Dual 4 20mA Transmitter e WI556 3G Dual 0 10V Transmitter User Manual Rev 4 Honeywell Process Solutions 3 1 3 Testing Communications Rev 4 May 2012 Wireless Temperature Transmitter Remember proper plac
54. re Transmitter Transmitter Displayed Message Definitions This section covers the various messages displayed on the Transmitter LCD that occur during operation of the device Operations Sequence e RF Link Status gt RF OK Transmitter and Base Radio are communicating properly gt RF SYNC Transmitter and Base Radio are attempting to synchronize communications RF OFF Transmitter s RF Channel is set to RF OFF gt NO RF Transmitter and Base Radio have no communica tions e Temperature Input Level XX XX Currently measured Temperature Input level Error Messages If an error is detected with the operation of the Transmitter a message will be displayed on the Transmitter LCD a corresponding message may also appear on the Base Radio LCD There are few types of error messages warning and fatal Warning mes sages are displayed as part of the normal cycling message sequence These are e LOW BAT battery should be replaced as soon as possible e NORF cannot detect Base Radio e S FAULT there is an open sensor or excitation wire detected Also if a sensor value goes above below logical limits The unit will display 9999 99 for measurement sensor fault mode but will con tinue sampling and recover if the problem desists e OVERRNG the device is measuring a value above below sensor dependent bound values For example the Analog Input device will report over range if measurement is above 100 range of the A
55. requency Hopping Spread Spectrum 868 MHz e Up to 600 m 2000 ft range from Base Radio with clear line of sight Operating Temperature Range e 40 F to 185 F 40 C to 85 C electronics e 4 F to 158 F 20 C to 70 C display full visibility e 40 F to 185 F 40 C to 85 C display with reduced visibility Physical Characteristics e Aluminum junction box e GE Lexan cover V 0 rating and UV stable Operating Vibration and Shock Characteristics e Certified per IEC 60068 2 6 vibration and 2 27 shock Random Vibration Characteristics e Certified to withstand 6 g s 15 minutes per Axis from 9 500 Hz Electromagnetic Compatibility CE Compliance e Operates within specification in fields from 80 to 1 000 MHz with Field strengths to 10 V m Meets EN 50082 1 general immunity standard and EN 55011 compatibility emissions standard Random Vibration Characteristics e Certified to withstand 6 g s 15 minutes per Axis from 9 500 Hz CE Conformity e These models are in conformity with the protection requirements of European Council Directives 89 336 EEC the EMC Directive and 1999 5 EC the Telecommunications Directive in accordance with EN 300 220 3 2000 EN 300 489 1 2005 EN 300 489 3 2002 and EN 61326 1997 A1 A2 Conformity of this product with any other CE Mark Directive s shall not be assumed e ATEX Certifications O Intrinsically Safe ia SIRA 06ATEX2021X II 1G Ex ia II
56. s the Transmitter to have a fastest update rate of 5 seconds and a range of 360m to 600m 1200 ft to 2000 ft Line of Sight Rev 4 User Manual 19 May 2012 Honeywell Process Solutions Wireless Temperature Transmitter 3 2 Continued A faster RF Baud Rate allows the user to transmit more information in a given period of time but it will also limit the Transmitter s range If you need more distance out of your Transmitters or are encountering difficulties by frequently losing communications then select a slower baud rate Follow the Base Radio menu map shown in Figure 5 2 to configure the RF Baud Rate OPERATIONS SEQUENCE NEXT LES ES E SEEN BEER SEND PASSWORD dase a pee e r aves a RECT NEXT Figure 5 2 Menu Map to RF Baud Rate Setting 5 3 RF Identification RF ID Each Transmitter is identified by the Base Radio and WMT according to Selection the RF ID given to that particular unit Two Transmitters on the same RF Channel CANNOT have the same RF ID if you do not know the RF Channel see section 5 1 When the Transmitter is in the Operations Se quence pressing the ENTER button displays the Read Only Sequence on the LCD The RF of that unit will be displayed in the format ID 3 All Transmitters in your system are set to a default RF ID number upon shipment For example if you have ordered a Base Radio and three Trans mitters the Transmitters will be configured to ID s 0 0 and 0 You must set these units
57. ser may still view some of the Transmitter settings by pressing the ENTER key during the Operations Sequence and viewing the Read Only Sequence The password 1s a four digit password The factory default is 0000 If you wish to select a different password one may be entered via WMT To do so enter the configuration dialog box See Appendix A From the con figuration dialog box click on the General tab to bring up the general information as shown in Figure 4 6 OPERATIONS SEQUENCE ENEXT ENTER ee F zu 1 USER PROMPTED FOR CSET PWD Jeene XKKKT Defaut of 0000 Figure 4 5 Menu Map to Password Setting If you have the Wireless Management Toolkit software this menu option will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details The pass word should be entered using the Wireless Management Toolkit software To do so enter the configuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the General tab to bring up the general information as shown in Figure 4 6 The Transmitter password for this device can be set by entering a four digit number in the Transmitter Password field Once a password has been entered click OK to save and download the password to the Trans mitter Please note that the password only protects the Transmitter from unauthor ized configuration via the NEXT an
58. st The Transmitter will begin to test the link in both directions to and from the Base Radio During this time the word TEST will appear on the LCD display When the test is complete the Transmitter will display the quality of the link Be aware that the Transmitter uses the configured Baud Rate and transmission rate to per form this test The length of time it will take to perform this test is de pendent upon how fast the device is normally transmitting When enough messages have been observed a link strength will be shown on the display gt gt gt gt gt indicates the strongest link while gt indi cates the weakest link The Link Test will continue to be evaluated and the rating on the screen may adjust itself Keep in mind that the longer the Link Test runs the more data the Transmitter will have to evaluate The Transmitter installation site should strive to place the Transmitter in a location where it receives the highest number possible A stronger link means less data re transmits and better battery life When the Link Test is conducted from a Base Radio it measures the link strength between a selected Transmitter and the Base Radio The Link Test data must be configured to match the communication parameters of the Transmitter from which you want to test The Link Test is located in the Base Radio s diagnostic menu see Figure 3 4 To conduct a Link Test from the Base Radio Navigate to Link Test and press the ENTER butto
59. sure and threaded through the center of the circuit board Wires should be routed through hole and out the conduit opening on the back of the housing E _ A Warning A Wiring the Temperature Transmitter to a non simple device such as an explosion proof device voids the intrinsic safety of the Transmitter A simple device is one that meets the conditions set forth in the Intrinsic Safety Control Drawing found in the Technical Specifications section of Grounding this manual Bonding Wire OJ Positive ge Wire Contact Closure Device Figure 3 9 Input Switch Wiring Diagram Note that the Transmitter may continue to monitor the temperature inputs in addition to the contact closure monitoring Also the contact closure monitoring requires NO POWER to be supplied to the loop nor does the user have to enable or enter any information via the NEXT and ENTER buttons as this is done automatically by the Transmitter No messages indicating the status of a monitored contact closure are dis played on the Transmitter LCD The status of the input switches can be found in the Wireless Management Toolkit under the Transmitter View An open contact closure is indicated as an O and a closed contact closure is indicated as a C on the Transmitter View see Wireless Management Toolkit Manual section 8 1 for each input switch Rev 4 User Manual 13 Section 4 Wireless Temperature Transmitter Gen
60. tery positive end first Note that the positive end of the battery clip is the end with the red wire 6 Replace the housing and screw the housing back on Power up the unit by pressing and holding both the NEXT and ENTER buttons for a few seconds i Properly dispose of the used battery User Manual Rev 4 Section 9 Wireless Temperature Transmitter Technical Specifications T C Input Characteristics e RTD and Thermocouple linearization to 05 C 0 1 of Full scale Reading Plus 1 8 F 1 C for Thermocouple Cold junction e Effect at Reference Conditions unit should be powered for 1 5 minutes for best accuracy 0 002 of reading per C for Ambient Temperature Effect RTD 0 01 of reading per C for Ambient Temperature Effect Thermocouple Stability deviation per year is less than 0 025 T C accepts thermocouple types B C E J K L N R S T U Note For Dual T C installations the inputs share a common ground Use Ungrounded T C s or ensure that both T C s are at the same ground potential to avoid ground loop effects Local Input Switch Characteristics WT531T WT531R only Simple Device Closure Only Optional e Number of Channels TC 2 RT 1 e Max External Switch Impedance Applied 1 KOhm e Isolation 110 KOhms between output and input e Connector Wire size 28 16 AWG e For simple device monitoring only i e contact closures RF Characteristics e 869 4 MHz 869 65 MHz F
61. the Transmission and Sampling Rates a message will be displayed explaining this You will not be allowed to enter an in correct setting Figure 6 14 Sampling and Transmission Rate Selection Using the Software If you have the Wireless Management Toolkit software the Normal and Normal Upper and Lower Value menu options will not be accessible via the Transmitter once the Transmitter detects that the software is being used See Appendix A for more details These settings should be entered Using Wireless Management Toolkit Dual 0 10 V Input Properties 00001047 1 47 General Inputs Range Sensor Offset Output Switches Sampling Rates Sampling Bands Alarms j Upper Limits using the Wireless Management Toolkit software To do so enter the con a A Lini figuration menu See Section 9 2 of the Wireless Management Toolkit o ag User Manual Once in the configuration menu click on the Sampling Time Deadband 3 3 Seconds Bands tab to bring up the sampling band information as shown in Figure C Use Input 2 Limit 6 l 5 To set a limit to the normal condition enable the limit by clicking on the Use Input X Limit check box Then enter the value and time deadband Dee for the limit for more details see Section 6 6 of this manual Use Input 1 Limit Value 1 Volts Time Deadband 2 5 Seconds _ Use Input 2 Limit This tab allows the user to set the Sampling Bands of the field unit The unit uses Normal samp
62. ting Point in order for the trim to work properly If you have the Wireless Management Toolkit software a 22 point sensor offset curve may be entered for the Transmitter To do so enter the con figuration menu See Section 9 2 of the Wireless Management Toolkit User Manual Once in the configuration menu click on the Sensor Offset tab to bring up the offset information as shown in Figure 7 5 7 5 Entering a 22 Point Curve Rev 4 User Manual 29 May 2012 Section 8 Wireless Temperature Transmitter Maintaining the Transmitter 8 1 Changing the Battery A Caution A Explosions may result in death or serious injury Do not remove the instrument cover or open wir ing housing in explosive atmospheres when power and communications are on Instead power down the Transmitter and communications ventilate the atmosphere as much as possible then proceed to open the instrument cover and replace the battery A Warning A The replacement battery MUST be a Lithium Inorganic Battery non rechargeable Size C 3 6Volts Tadiran TL 2200 Tadiran TL 5920 Tadiran GmbH SL 2770 Use of a different battery will VOID the intrinsic safety rating of this device and may result in an explosion A Caution PN When replacing the battery the positive end of the battery clip 1s the end with the red wire Putting the battery in backwards will blow a fuse 30 May 2012 The Transmitter is extremely easy to maintain in th
63. uch that it does not emit RF field in excess of Health Canada limits for the general population consult Safety Code 6 obtainable from Health Canada s website www hc sc gc ca rpb Honeywell Process Solutions Copyright 2008 by Honeywell International Inc 1860 West Rose Garden Lane Rev 4 May 2012 While this information is presented in good faith and believed to be accurate Honeywell disclaims the implied warranties of merchantability and Phoen IX Arizona 85027 fitness for a particular purpose and makes no express warranties except as may be stated in its written agreement with and for its customers In no event is Honeywell liable to anyone for any indirect special or consequential damages The information and specifications in this document are subject to change without notice Honeywell and TotalPlant are U S registered trademarks Of Honeywell International Inc yw Other brand or product names are trademarks of their respective owners Rev 4 User Manual iii May 2012 About This Document Revision Notes The following list provides notes concerning all revisions of this document DoclD RellD Date NM O O o 34 XY 25 52 12 03 1st issue of document 08 06 Updated for version 1 70 software release Contacts The following s a list of Honeywell contacts for including Internet World Wide Web Telephone Fax and Email For Asia Pacific Europe North and South Americas Sales and Service For applicati
64. us two different thermocouple types cannot be wired into the same Transmitter For a RTD Transmitter the factory is a 4 wire DIN platinum sensor To select the sensor type follow the Transmitter menu map shown in Fig _ ure Ea Indicates that Menu is Disabled if Wireless Management Toolkit is detected See Appendix 4 User Manual Rev 4 Honeywell Process Solutions Wireless Temperature Transmitter 7 3 Setting a Measurement For various applications the user may wish to display an offset value rather than the actual value To enter an offset navigate to the OFFSET Offset command as shown in Figure 7 3 select the desired input to be offset Then enter the offset to be added or subtracted from the actual measured value a ne es snp Ten DDALIDTEN EAD NEXT OFFSET Jenter INPUT T Jenter NEXT NOTE Input 2 is only mehr Pier available for a Dual NEXT Input Thermocouple EXIT Figure 7 3 Menu Map to Offset Setting The Transmitter interface allows you to set a two point correction curve 7 4 Trimming the for the sensor This process is often called trimming because the dis Measurement played value is trimmed up or down to reflect the actual value being ap plied Dual 0 10 V Input Properties 00001047 1 47 Vat ie un To set a trim point take the Transmitter offline and navigate to the TRIM menu as shown in Figure 7 4 and select the input to be trimmed Then select the point you wish to enter
65. ve communication with the Base Radio Parameters discussed are the Transmitter RF ID the RF channel setting and Baud Rate Section 6 Configuring the Sampling and Transmission Rates This section aids the user in selecting the amount of time between each sample of the process and the time between each transmission of this sample to the Base Radio Also discussed is the use of setting an abnormal threshold in which sampling and transmission times may change during a period when the process variable is within the abnormal region Section 7 Configuring the Process Variable This section helps the user select engineering units and discusses setting a measurement offset and trimming the process measurement Section 8 Maintaining the Transmitter This section explains how the Transmitter should be cared for once it has been placed into service and how to change the battery Section 9 Technical Specifications This section explains the technical specifications that are associated with this device such as power characteristics accuracy and operating charac teristics Rev 4 User Manual 1 May 2012 Honeywell Process Solutions Wireless Temperature Transmitter 1 2 ABOUT THE DEVICE The Honeywell Temperature Transmitter 1s a reliable Radio Frequency RF transceiver coupled with an temperature input sensor that can be used to monitor a variety of processes in hazardous and hard to reach ar eas The time and expense of running wires often mak
Download Pdf Manuals
Related Search
Related Contents
PTQ-DNET User Manual CONDITION REPORT Dual Force Teclado y Ratَn gaming َptico INSTALACIسN Energy Sistem D2800 VM150 EDITION Sony CDX-GT660UP Marketing Specifications VGN-SR Series ダウンロード(396KB) Le développement durable, risque ou opportunité pour l Manuale d`uso e installazione CLASSE A1-A2 Copyright © All rights reserved.
Failed to retrieve file