Optigo OP10 - MWA Technology
Contents
1. e Language independent e Simple configuration via the backlit display e Input for external setpoint device Optigo OP10 is a pre programmed controller that can be used for control of temperature CO pressure and humidity in air handling and heating applications It is a stand alone controller for simpler applications Optigo is extremely easy to install commission and control Optigo uses a display with an encoder knob making its built in menu system very easy to use Settings are entered by turning the encoder knob to a desired parameter value A value is then approved by pressing the knob Models The Optigo series comprises two different models OP5U and OP10 OP5U has 5 in outputs and OP10 has 10 in outputs OP10 is available in two models e OP10 with 24 V AC supply voltage e OP10 230 with 230 V AC supply voltage Applications for OP 10 and OP 10 230 Optigo OP10 is pre programmed with a choice of five different control modes 1 Supply air control Supply air control with outdoor compensation Cascaded room extract air temperature control Radiator circuit control mm A U N Domestic hot water control revision 10 2013 OP10 Pre programmed configurable controller for simple applications The Optigo OP10 range of controllers can be set to handle everything from temperature or humidity control to control of CO or pressure They are intended for DIN rail mounting e Pre loaded with sev
2. 0 Polycarbonate PC Disconnectable so called lift type for cable cross section 2 5 mm OP10 230 370 g OP10 215 g including terminals Casing Silver Bottom part Dark grey Low Voltage Directive LVD standards OP10 230 conforms to the requirements of the European Low Voltage Directive LVD 2006 95 EC through product standard 60730 1 and EN 60730 2 9 EMC emissions amp immunity standards This product conforms to the requirements of the EMC Directive 2004 108 EC through standards EN 61000 6 1 and EN 61000 6 3 RoHS This product conforms to the Directive 2011 65 EU of the European Parliament and of the Council Three PT1000 sensor working range 0 84 C accuracy 0 5 C PT1000 sensor working range 30 54 C accuracy 0 5 C PT1000 setpoint device working range 0 40 C accuracy 0 5 C One analogue or digital input PT1000 sensor working range 0 84 C accuracy 0 5 C Potential free closing contact Reference for AI and for UI when used as analog input Reference for UI Closing potential free contact Reference for DI Two analogue and three digital outputs 0 10 V DC 8 bit D A short circuit protected Triac controlled 24 V AC 0 5 A continuous Change over SPDT relay 230 VAC 5 A OP10 OP10 230V 24V AC 230 V AConly only Optigo 10 230 Optigo 10 Reference for AI2 PT1000 temperature sensor input Input PT1000 setpoint device k 120 Product documentation Optigo
3. LI Ga AO2 Graphic output signal Control mode only AOI Graphic output signal Control mode only Bargraph AO I output level Bargraph AO2 output level Configuration All configuration menus lie in the 10 seconds level This level is accessed from the Base Display by pressing and holding the encoder button for 10 seconds There are numerous configuration menus covering all available options and combinations In some cases making a certain choice in one menu will mean that you will only see certain other menus For example the menu for setting the damper minimum limit is only shown if you have configured AO2 to be a damper control output Function overview Selectable control functions 1 Supply air control 2 Supply air control with outdoor compensation 3 Cascade connected room extract air temperature control Radiator circuit control with outdoor curve 5 Domestic hot water control Optigo is capable of handling the following control modes Ventilation According to points 1 2 and 3 above e P or Pl control e Can control two analogue outputs in sequence or one 3 position actuator via two digital outputs e Damper control with settable minimum supply air amount e Control of frost protection or frost protection thermostat with manual reset e High temperature limit switch e Electric heater cool down function e Digital scheduler e Start stop of fan via built in relay for 230 V AC e Digital inpu
4. OP10 manual Optigo OP10 user manual The product documentation is available for download from www regincontrols com ay Phone 46 31 720 02 00 Web www regincontrols com Mail info regin se THE CHALLENGER IN BUILDING AUTOMATION
5. eral application modes e 24V or 230 V AC supply voltage e Week based clock calendar function Inputs and outputs Optigo OP10 has e 2 analogue inputs PT1000 e SPI input for an external setpoint device e universal input PT1000 or digital e 2 digital inputs e 3 digital outputs e 2 analogue outputs 0 10 V DC Internal clock Optigo OP10 has a built in week based real time clock with a number of different scheduler alternatives Easy to install Optigo is suitable for DIN rail or cabinet mounting Since the terminals are detachable all connections can be made before Optigo is installed Optigo has been developed in accordance to our Ready Steady Go concept simplifying every step from installation to management REGIN THE CHALLENGER IN BUILDING AUTOMATION Display and encoder knob All setting and configuration is performed using the display and encoder knob on the front of the controller The menu information shown on the display is organised in a tree fashion By using the knob you can move in between menus set values etc In any of the configuration menus pressing the encoder knob will activate change mode You can then turn the knob to move between choices or set values A second press of the knob will accept the choice Turn move up down in the menus Press enter new menu or accept new setting Press for 3 seconds for time menu or 10 seconds for configuration menu The menu system
6. is divided into three levels e Base level view mode e The 3 second level clock and scheduler program e The 10 second level configuration menus Display information The display can show the following information Outdoor compensation configured Alarm indicator NN NA A A NINN o Cascade control Temperature control Radiator circuit control egsa Domestic hot water control C TH Piij r Fan run indicator eL I Is Active 0 10v Menu holds changable values input signal indicator or 3 position output Display Base level This is an example of the display when in Base level view mode It is normally shown when there is no operator activity nin Pht T lt s 905 p The Base display shows current time and actual value AO ar There are bar graphs showing the current output levels together with symbols showing how the outputs have been configured Heating Cooling or Damper etc There is also a symbol showing which of the five control modes is configured as well as an alarm symbol that is displayed in the event of an alarm condition The fan symbol control modes 1 2 and 3 only is lit as long as the fan indication input is activated To see the values and status of all in and outputs simply turn the knob counter clockwise until the text I O is displayed and then press it To return to the Base display click on the knob and then turn it clockwise Configuration level Menu number A
7. nged according to the outdoor temperature A single PI control loop is used A room temperature sensor can be added to give corrective action if the room temperature differs from the setpoint CV y eS T m This control mode requires two sensors Supply temperature on AIl and Outdoor sensor on AI2 A room temperature sensor can also be connected to UII permitting the room temperature offset to correct the supply temperature Wire UI as an analogue input 3 position control Instead of the analogue outputs Optigo can be configured for 3 position control increase decrease DO1 will then be used for the increase signal and DO2 for the decrease signal This option cannot be combined with an alarm output Domestic hot water control The water temperature is kept constant by controlling the output signal on AOI A single PID control loop is used gt This control mode requires a sensor Supply water temperature on AI Technical data Supply voltage Internal consumption Ambient temperature Storage temperature Ambient humidity Display Protection class Housing material Terminals Weight Colour ce Inputs Analog inputs All AI2 SPI Universal input Al or DI AGND UI Digital inputs DI Outputs AO DO1 and DO2 DO3 OP10 24 V AC 15 50 60 Hz OP10 230 230 V AC 10 15 50 60 Hz 4 VA 0 50 C 20 70 C Max 95 RH Numeric graphic backlit IP2
8. t for extended running via timer e Input for an external setpoint device e Alarm management in the display as well as sum alarm output e Heat maintaining function e As of revision 21 a frost protection thermostat can be connected to UI for control modes 1 3 Radiator circuit control According to point 4 above P or Pl control Output 0 10 V or 3 position 24 V AC Settable outdoor compensation curve Extra correction of outdoor curve increase at approx zero degrees outdoor temp Room sensor can be connected for adaption of outdoor curve Room setpoint can be set via an external setpoint device Pump stop Pump exercise Alarm management in the display as well as sum alarm output Domestic hot water According to point 5 above PID control 0 10 V output Periodic overheating to decrease risk of Legionella Alarm management in the display as well as sum alarm output Application examples Optigo OP10 can be configured to any one of the following control modes The three control modes on this page have much in common and will therefore be treated in a single section Supply air control The supply air temperature is kept at the setpoint value by controlling the output signals on AO and AO2 A single PI control loop is used This control mode requires a sensor Supply air sensor on All Supply air control with outdoor compensation The supply air temperature is kept at the setpoint value by con
9. trolling the output signals on AO and AO2 A single PI control loop is used The setpoint is automatically adjusted according to the outdoor temperature This control mode requires two sensors Supply air sensor on AI and Outdoor sensor on AI2 Cascade connected room extract air temperature control An offset in room temperature which if desired can be set via the external setpoint device will adjust the supply air temperature setpoint so as to eliminate the room temperature offset One PI and one P control loop are used The supply air temperature can be minimum and maximum limited This control mode requires two sensors Supply air sensor on AIl and either Room sensor or Extract sensor on Al2 Analogue outputs The analog outputs can be configured to the following combinations valid for all three examples on this page AO 1 Heating 2 Cooling 3 Heating 4 Heating 5 Cooling 6 Heating 7 Cooling Cooling Heating Cooling Dampers Dampers 3 position control Instead of the analogue outputs Optigo can be configured for 3 position control increase decrease Only the following output choices will then be available e Heating e Cooling DO is used for increase signal and DO2 for decrease This option cannot be combined with alarm output A single PI control loop is used Radiator circuit control with outdoor curve The water temperature setpoint is cha
Download Pdf Manuals
Related Search
Related Contents
VC-10取扱説明書:PDF 約782KB Générateur de fumée Samsung 520DXN Наръчник за потребителя USER'S MANUAL HR Series Portable Rockwell/Superficial Fiche technique Art.-No. 173- Descargar documento con más información: cem-09 YSS 06-07 User Guide - University of Waterloo muller_histoire_5e TRI-Xi Outdoor Bachelor Thesis - FB Informatik Copyright © All rights reserved.