Home

SmartOnline 6kVA On-Line Double-Conversion UPS

image

Contents

1. e Full time active power conditioning provides clean continuous dual conversion AC output free of voltage fluctuations power interruptions and line noise e Double conversion operation converts raw input from AC to DC then re synthesizes output power back to perfect sine wave AC with enhanced protection from harmonic distortion fast electrical impulses and other hard to solve power problems not addressed by other UPS types e Accepts input voltages between 156 and 276 regulating output within 2 of selectable 208 240 and 120V AC output e Standard included 3U battery pack provides 20 minutes runtime at half load 3000VA and 8 minutes at full load 6000VA e Expandable runtime is supported with optional BP240V10RT3U BP240V557C 1PH BP240V787C 1PH BP240V1037C 1PH BP240V1407C 1PH external battery packs e Highly efficient operation in optional economy mode significantly reduces BTU heat output and operating energy costs e PowerAlert monitoring software offers detailed site power and UPS updates with support for safe auto shutdown of connected systems as UPS batteries become depleted e Includes Free PowerAlert monitoring software packages PowerAlert LOCAL for desktops and small business networks PowerAlert NSA Network Shutdown Agent for larger networks and PowerAlert NMS Network Management System for monitoring up to 250 SNMP enabled UPS PDU and other networking devices e Supports detailed monitoring of equipment load levels self test da
2. user replaceable batteries Online double conversion power conditioning 2 output voltage regulation during overvoltages to 276 2 output voltage regulation during undervoltages to 156 LEDS ALARMS amp SWITCHES LED Indicators 6 LEDs indicate line power online mode economy bypass mode on battery charger and AC output status LCD screen offers additional information and control options Front panel LCD display Alarms Alarm cancel operation Switches Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options LED LCD panel rotates for viewing in rack tower formats see manual Unique audible alarms for all major UPS environmental and power conditions see manual Alarm cancel switch 2 Switches control off on power status and alarm cancel self test operation 2 additional switches support set and execute scrolling LCD functions bundled transformer includes bypass switch to enable hot swap UPS power module replacement SURGE NOISE SUPPRESSION UPS AC suppression response time EMI RFI AC noise suppression ISOLATION Output isolation transformer PHYSICAL Installation form factors supported with included accessories Included mounting accessory description Installation form factors supported with optional accessories Optional mounting accessory notes Primary form factor UPS Power Module dimensions in primary form factor height x
3. 10 with less than 1 millisecond transfer time between modes High availability UPS Automatic inverter bypass Manual bypass switch Hot swappable UPS power module Hot swappable batteries features Green amp high High efficiency economy mode operation Schedulable daily hours of economy mode operation efficiency features CERTIFICATIONS UPS Certifications Tested to UL1778 USA Tested to CSA Canada Tested to NOM Mexico Tested to CE EU Tested to GOST Russia Tested to SASO Saudi Arabia Tested to IRAM Argentina Meets FCC Part 15 Category A EMI WARRANTY Product Warranty 2 year limited warranty Period U S Canada amp Puerto Rico Connected 250 000 Ultimate Lifetime Insurance Equipment Insurance U S Canada amp Puerto Rico Related Items Optional Products Product Type Related Model Description Qty Backplates Backplates Backplates Backplates Extended Warranties Extended Warranties External Battery Packs External Battery Packs External Battery Packs External Battery Packs External Battery Packs Power Cables Rackmount Wallmount Kits Shutdown Cable Kits SNMP Accessories SNMP Accessories Surge Protectors Surge Protectors Surge Protectors Tower Stands SUPDM12 SUPDM13 SUPDM15 SUPDM16 WEXT3 SU6000 WEXT5 SU6000 BP240V1037C 1PH BP240V10RT3U BP240V1407C 1PH BP240V557C 1PH BP240V787C 1PH SU30ACORD 2POSTRMKITHD AS400CABLE KIT ENVIROSENSE
4. SNMPWEBCARD DCATV DNET1 DTEL2 2 9USTAND Corded UPS Backplate Outlet Kit Adds AC plug in connection and AC output receptacles to SUBNDD0RT3U and SU6000RT3UXR UPS for use with 208V UPS output voltage configurations Corded UPS Backplate Outlet Kit Adds AC plug in connection and AC output receptacles to SUBNDD0RT3U and SUG000RT3UXR UPS for use with 240V UPS output voltage configurations Corded UPS Backplate Outlet Kit Adds AC plug in connection and AC output receptacles to SUBNDD0RT3U and SUG000RT3UXR UPS for use with 240V UPS output voltage configurations Corded UPS Backplate Outlet Kit Adds AC plug in connection and AC output receptacles to SUBND0RT3U and SU6000RT3UXR UPS for use with 208V UPS output voltage configurations 3 Year Extended Warranty For SU6000 models 5 Year Extended Warranty For SU6000 models External battery pack for use with select Tripp Lite UPS Systems External Battery Pack and Cable 3U Expandable Black 3 Point Connector External battery pack for use with select Tripp Lite UPS Systems External battery pack for use with select Tripp Lite UPS Systems External battery pack for use with select Tripp Lite UPS Systems SU30ACORD Optional Input Cord for UPS System Enables 2 Post Rackmount Installation of 3U and Larger UPS Transformer and Battery Pack Components Power Management Tools UPS Communication Cable Kit for System i AS400 iSeries Servers Monitors temperature humidity and contact
5. Tripp Lite i A 1111 West 35th Street Chicago IL 60609 USA POWER PROTECTION Telephone 773 869 1234 E mail saleshelp tripplite com Model SU6000RT3U SmartOnline 6kVA On Line Double Conversion UPS 9U Rack Tower 208 120V or 240 120V Hardwire output Highlights e 6000VA 6kVA 4200W on line double conversion UPS e 208 120V or 240 120V 50 60Hz output Economy mode option e 9U Rack Tower compatible Hot swap power and battery modules e RS232 amp EPO ports support for SNMP WEB card options e Front panel LEDs with detailed LCD monitoring and control screen e Expandable runtime with optional external battery packs e Hardwire input 3 wire Hardwire output Description Tripp Lite SUGOOORT3U on line double conversion UPS protects server networking or telecommunications equipment from blackouts voltage fluctuations and surges in a compact tower rackmount housing In a rack configuration the power module step down transformer and battery pack occupy only 3 rack spaces each 9U total Upright tower placement of entire system supported with included tower stands Large capacity 6000VA 4200 watt power module double conversion technology converts raw input AC to DC then resynthesizes it back to perfect sine wave AC output within 2 of user selectable 208V 240V and 120V AC output voltages Frequency regulation locks output power to 50 60Hz 0 2 Hz removing harmonic distortion fast electrical impulses and other hard to solve powe
6. closure inputs Requires SNMPWEBCARD or switched PDU For remote monitoring and control via SNMP Web or Telnet Network Surge Suppressor Essential protection for TV VCR coaxial lines Network Surge Suppressor Essential protection for data and communication lines Network Surge Suppressor Essential protection for data and communication lines Enables Tower Placement of Rackmount UPS Systems More information including related products owner s manuals and additional technical specifications can be found online at www tripplite com en products model cfm txtModellD 32 Copyright 2011 Tripp Lite All rights reserved All trademarks are the sole property of their respective owners Tripp Lite has a policy of continuous improvement Specifications are subject to change without notice Photos may differ slightly from final products
7. hr full load Battery mode BTU hr full load 43 8 19 9 Includes 3U power module 3U stepdown transformer and 3U battery pack 5 2 x 17 5 x 26 13 3 x 44 4 x 66 90 40 9 5 2 x 17 5 x 25 13 3 x 44 4 x 63 5 136 5 62 380 172 5 Steel Fan 32 to 104 degrees Fahrenheit 0 to 40 degrees Celsius 5 to 122 degrees Fahrenheit 15 to 50 degrees Celsius 0 to 95 non condensing 1412 3 911 5 1586 7 AC economy mode 96 efficiency rating 100 load Operating Elevation 0 3000m 0 to 10 000 ft ft Audible Noise 53dBA At Front Side 1 Meter COMMUNICATIONS Communications DB9 Serial Contact closure EPO emergency power off Slot for SNMP Web interface interface Network monitoring RS232 and contact closure communications are located on two separate DB9 ports port description PowerAlert software Included Communications DB9 cable included cable LINE BATTERY TRANSFER Transfer time No transfer time 0 ms in online double conversion mode Low voltage transfer 156 to battery power setpoint High voltage transfer 276 to battery power setpoint SPECIAL FEATURES Cold Start startup in Cold start operation supported battery mode during a power failure Economy mode Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of operation 10 Double conversion mode is automatically restored as mains voltage varies beyond
8. r problems not addressed by other UPS types Perfectly regulated continuous sine wave output with zero transfer time offers guaranteed uptime and compatibility with all equipment types Hardwire input and output connections support a variety of permanent or PDU style power connections Highly efficient operation in optional economy mode setting saving BTU heat output and energy costs Battery support can be extended through the addition of external battery packs Includes accessory slot for optional monitoring and management cards plus DB9 contact closure and DB9 enhanced serial monitoring ports for unattended shutdown remote control and monitoring of UPS system and power data Package Includes e SU6000RT3UPM 3U power module e SU6000XFMRRT3U 3U step down isolation transformer e 240V 3U external battery pack e Four post compatible rack rail kit 3 sets e PowerAlert software complete data cabling and user manual Features e Tripp Lite SUGOOOORT3U 6kVA 6 000VA 4200 watt on line double conversion UPS system in 9U total rack tower configuration 3U UPS power module 3U external battery pack and 3U step down transformer e Included step down transformer with manual bypass switch enables hot swappable UPS power module replacement with no interruption in output power to connected networking equipment e Fault tolerant electronic bypass maintains utility output during a variety of UPS fault conditions e Hardwire input and output connections
9. ta and utility power conditions via built in RS 232 interfaces e Optional SNMVPWEBCARD offers communications and control via secure remote web and network interfaces e Optional RELAYIOCARD supports six configurable hard contact closure outputs for custom event notification e Supports Emergency Power Off EPO via built in interface e Included rail kit supports 9U 19 inch rackmount installation in 4 post racks e Optional 2POSTRMKITHD supports installation in 2 post 19 inch racks e Front panel LED s and LCD readout with scroll controls and supports visual monitoring of all major UPS functions and advanced UPS settings for nominal voltage selection economy mode and other operational parameters e LED LCD display panel rotates for viewing in rackmount or tower configurations e Network grade AC surge and noise suppression e External battery packs are field replaceable and hot swappable Specifications OUTPUT Output Volt Amp 6000 Capacity VA Output kVA capacity 6 kVA Output Watt Capacity 4200 watts Output kW capacity 4 2 Output power factor 0 7 Crest Factor 3 1 Nominal Output 120V 208V 240V Voltage s Supported Frequency 50 60 Hz compatibility Frequency Output frequency matches input nominal on startup compatibility details Output voltage 2 regulation line mode Output voltage 10 regulation Economy line mode Output voltage 2 regulation Battery mode Built in UPS output recep
10. tacles Output receptacle backplate options Output circuit breaker Output AC waveform AC mode Output AC waveform battery mode INPUT Rated input current at maximum load Nominal Input Voltage s Supported UPS input connection type UPS input connection description Input circuit breaker Recommended Electrical Service BATTERY Full load runtime minutes Half load runtime minutes Expandable battery runtime External battery pack compatibility DC system voltage VDC Battery recharge rate included batteries Battery replacement description VOLTAGE REGULATION Voltage regulation description Overvoltage correction Undervoltage correction Hardwire Optional backplates SUPDM12 for 208v nominal SUPDM14 for 240v nominal SUPDM16 for 208v nominal add low and high voltage outlets plus L6 30P input cord 40A double pole Sine wave Pure Sine wave 30A 208V AC 240V AC Hardwire 3 wire single phase input L1 L2 G optional country specific backplates SUPDM12 for 208v nominal SUPDM14 for 240v nominal SUPDM16 for 208v nominal add low and high voltage outlets plus L6 30P input cord 40A double pole 30A 208V or 240V 8 min 4200w 20 min 2100w Supports extended runtime with optional external battery packs BP240V10RT3U BP240V557C 1PH BP240V787C 1PH BP240V1037C 1PH BP240V1407C 1PH 240 Less than 6 hours from 10 to 80 Hot swappable
11. width x depth inches UPS Power Module dimensions in primary form factor height x width x depth cm Installed whole system maximum rack depth inches Installed whole system maximum rack depth cm Installed whole system total rack space height rack spaces Secondary form factor Instantaneous Yes 120V output includes load isolation transfomer protection Tower 3 sets of adjustable 4 post rack rails included 2 post rackmount 2POSTRMKITHD 3 sets of 2POSTRMKITHD required for 2 post rackmount installation of separate power module transformer and battery pack Rackmount 5 2 x 17 5 x 26 13 3 x 44 4 x 66 26 66 9U Tower requires 2 9USTAND UPS Power Module weight Ibs UPS Power Module weight kg UPS dimensions details Stepdown transformer dimensions height x width x depth inches Stepdown transformer dimensions height x width x depth cm Stepdown transformer weight Ibs Stepdown transformer weight kg Included battery pack dimensions height x width x depth inches Included battery pack dimensions height x width x depth cm Included battery pack weight Ibs Included battery pack weight kg Shipping weight Ibs Shipping weight kg UPS housing material Cooling method ENVIRONMENTAL Operating Temperature Range Storage Temperature Range Relative Humidity AC mode BTU hr full load AC economy mode BTU

Download Pdf Manuals