1. NB For Room sensors with floor temperature limiting sensors please refer to separate instructions included with Room sensors controllers Manifold WLM2 Master If the Room sensors controllers are of wireless type connect the receiver WLRC2 19 using the special cable enclosed with the receiver WLRC 19 o FLOW DIAGRAM Power supply Boiler WLM2 Master 5 Connect the actuators to the channel outputs on the master in accordance with the pipe manifold layout please refer to the area schedule Actuator no 1 on the manifold to output no 1 on the master Actuator no 2 on the manifold to output no 2 on the master etc Thermal Actuators 1128 Manifold Outdoor module WLOC 19 FS Master only Install on north facing wall away from direct sunlight Connect into 2 wire Room sensor bus or direct to master maintaining continuity of positive and negative connections WLM2 Master Connect 230 V AC power UFH circulating pump and boiler in accordance with electrical regulations Fo FS masters connect the mixing valve and water flow temperature sensors lea oe a e 52 SEE Q G second
2. 57718 11 08 DJU Installation Quickguide OJ ELECTRONICS www oj dk taking comfort further Quick Installation Guide Setting up the System Wireless system only Testing the system Troubleshooting Page 5 Page 5 Page 6 QUICKGUIDE This Quickguide is for reference only and is not suitable for networked installations For full installation details please refer to the full Installation manual supplied QUICK INSTALLATION GUIDE We recommend the preparation of an area schedule chart on the backside of the user manual before commencing the installation This identifies piping circuits to specific rooms and enables the correct SR noe allocation of a channel number in the WLM2 system Mount the Master and AO modules in the correct way on the wall in accordance with electrical regulations WLM2 Master AO Module Connect the AO module using the special cable included in the box AO Module Cable Mount the Room sensors controllers in the rooms and set the channel switches to correspond with the number of the actuator controlling that room For hardwired Room sensors controllers now connect the 2 wire bus to the master or the AO module maintaining continuity of positive and negative connections For wireless Room sensors controllers now insert the batteries Channel 1
3. Make sure the power light is fast blinking If not then put DIP 3 to ON position 2 wire bus may be incorrectly connected Voltage at each Room sensor should not be lower than 4 0V check for amp continuity and short circuits For wireless Room sensors please check that the batteries have been inserted correctly For wireless systems has the init button been pressed For wireless Room sensor check that the WLRC2 19 receiver is correctly connected For channel 9 14 is the AO module correctly connected to the Master Make sure the Room sensor in that room is set to the correct channel number The channel selector on the Room sensor may be slightly out of position try rotating and the set it again Master has canceled install mode by itself after 2 hours the master automatically de activates install mode please reset the DIP 1 Make sure the Room sensor in that room is set to the correct channel number two Room sensors could be crossed over The actuator on the manifold has not opened after 3 minutes Check the red channel light is illuminated if not see above The actuator for the room is not connected to the correct output on the master Bad electrical connection between actuator and terminals Actuator may be faulty or manually locked UFH Pump not starting in install mode Bad electrical connection between pump and terminals Install mode is not activated Move dip switch 1 to the off position and
4. is excessively high these problems may be corrected by changing PI settings please refer to the main manual Incorrectly installed refer to the installation instructions supplied with the actuator Room is too cold After running for at least 48 hours Room is too hot After running for at least 48 hours The Room sensor is placed in a position that does not represent the general temperature in the room E g mounted on external wall or near an extraneous heat source If the room is controlled by a WLCT2 Room sensor check that the time and temperatures are set correctly If the Room sensor has got an override switch WLTM or WLTD the switch may be set in the off or night position For rooms with floor sensors the maximum floor limit setting could be preventing the room reaching the desired temperature Insufficient heating capacity of the system Bad insulation creating large heat loss This could be caused by draughts affecting the temperature measuring ability of the sensor this could either internal cavities or external sources such as open doors or windows The Room sensor is placed in a position that does not represent the general temperature in the room If the room is controlled by a WLCT2 Room sensor check that the time and temperatures are set correctly If the Room sensor has got an override switch WLTM or WLTD the switch may be set in the day position For rooms with floor sensors t
5. ary pump SETTING UP THE SYSTEM 1 a Turn on the power and complete a full reset of the master by holding the tick button in for 16 seconds until all the area light alternately flash 2 Set the clock on any WLCT2 room controller a If the hour digit is not flashing press the small pinhole button with the clock symbol otherwise b Adjust the hours and press OK c Adjust the minutes and press OK d Adjust the day number 1 Monday and press OK 3 In addition to its own room the WLCT2 room controller can be used to set the operating times and temperatures of other Room sensors channels To achieve this do the following on the WLCT2 Room Controller a If the WLCT2 Room controller already shows CH 1 in the display please go directly to step b Enter the InFo menu by pressing the up and down button simultaneously for 4 seconds c Find the ArEA menu with the down button and press OK d The display now shows CH 1 channel 1 Press OK button Select On if this channel Room sensor should be controlled by the WLCT2 room controller by pressing the down button or OFF if not Now press OK button to get to the next channel CH 2 and repeat this step until all required channels have been selected On e After all channels are set up find the ESC menu entry and press OK NB If different times and temperatures are required for other channels Room sensors within the syst
6. e that during the Install mode the boiler will not fire unless dipswitch 2 is also activated this is to reduce energy consumption and boiler cycling during the test process Turn the temperature setting on the adjustable Room sensor in room 1 to maximum The red channel 1 light should be lit and the actuator on output nr 1 will be activated and will open after 1 3 minutes depending on the type of actuator Important If the Room sensor is of a wireless type a delay of up to 5 minutes may occur before the channel light becomes illuminated Check that the UHF pump is running and the mixing valve only FS master opens Repeat step 6 on all rooms Boiler test function Switch on DIP 2 This closes the boiler start relay contacts for 1 minute 10 To end all tests Switch off DIP 1 to deactivate install mode Switch off DIP 2 to deactivate boiler test Set all temperature knobs to default positions Room sensors WLTA WLTD WLTM WLTP to zero center position Room controllers WLCT2 recommended to 21 C Set all override switches on WLTM and WLTD Room sensors to automatic position clock symbol 11 the system is now operating automatically Other important settings can be found in the User Manual TROUBLESHOOTING Problem Channel light is not coming on When in Learn mode Channel light is not coming on When in Install mode when the Room sensor is activated set to maximum Possible cause amp solution
7. em more than one WLCT2 room controller can be used Care must be taken to ensure that the action of selecting a channel On is not made on more than one WLCT2 room controller ADDITIONAL STEPS FOR WIRELESS SYSTEM BRQeANTE 4 Switch on DIP 3 to activate learn mode BR965A30c COMMON UHF PUMP 5 All wireless Room sensors now have to be initialized X RELAY TE Analogue Room sensor WLTA WLTD WLTM WLTP by pressing the COMMISSION MODE JE internal init button Button learning mode until a beep is heard LEARN MODE Digital Room sensor WLCT2 by pressing the pin hole button with the BOILER TEST clock symbol until a beep is heard INSTALL MODE When communication has been established the area LED on the master will illuminate oo N si en ic o 6 Switch off DIP 3 to de activate learn mode Button learning mode TESTING THE SYSTEM Switch on DIP 3 to activate learn mode power light will blink quickly Each red channel light on the master should now be lit if a Room sensor is present on that channel Switch off DIP 3 to de activate learn mode again power light stops blinking Turn all adjustable temperature settings on the Room sensors to minimum Switch on DIP 1 on the master to activate install mode Install mode will be active for 2 hours Pumps boiler mixing valve and actuators should now be off Please not
8. he minimum floor limit setting could be increasing the room temperature above the desired setting Solar gain or extraneous heat source son Sum SDINOALIIID FO d SDINOWLOG I3CO MMM 0 O0I8Y T6 OCC 8r Y T6 Occv 8b L 104 ADIZGOGSIMS O9T 8S VMOZOZ38 IN DIO31319 193904 0 2 S Y SIINOY19313 fO 009 IntO MMM AN OIANLODSTIVS OTE ET 48610 00 ETZ S86T0 WOGSND 458 CIVA FUIHSITIM VHILSNINUYM avd uadvsnu AN SOINOuIOTT13 ACTO MMM q tooro ET ET CT El Spt VI ET CI EL SPEL AYVIANZO DYOAYIANDS 0099 3 SET YIDVNILS S Y SDINOYLII1I fO
9. then back to the on position Pump may be faulty Output relay for Main pump Cooling High limit valve or other attached device Boiler does not fire LED lit LED not lit Incorrect connection to device X output relay has volt free contacts see master wiring diagram for correct connection Bad electrical connection between terminals and attached device Install mode not activated set dipswitch to off and then on again to commence install mode for 2 hours Attached device may be faulty Dip switches may be incorrectly set see Installation Manual Free relay Function X output for details Incorrect connection to device output relay has volt free contacts see master wiring diagram for correct connection Bad electrical connection between terminals and attached device During Install mode the boiler relay will not operate Attached device may be faulty Timing sequence delay is activated FS master only mixing valve not open above 20 No heat demand from Room sensors Master is in cooling mode Mixing valve does not operate correctly When in install mode Valve cycles between open and closed in normal operating mode Incorrect connection see master wiring diagram for correct connection Valve actuator assembly is incorrect Actuator is faulty Check what happens if sensor and or outdoor module is missing EIA Supply Limit sensor may be subject to heat migration Upstream water temperature

Download Pdf Manuals

image

Related Search

Related Contents

Omega 208H Network Card User Manual  American DJ Verti-Pro User's Manual  Scantech ID MICA M-9030 Laser Barcode Scanner  ダウンスキャン[DSE-002] マニュアル  KRAUS FUS-13801ORB Installation Guide  2014 Sportage Owner`s Manual  Samsung MIM-E03AN Manual de utilizare  折りたたみ自転車の安全性[PDF形式]  Pelican Work Light 2720 User's Manual  