Home
FX3G-2EYT-BD USER`S MANUAL
Contents
1. Output form Transistor Sink Source External power supply 5 to 30 VDC Resistance load 0 5 A 1 point Max load Inductive load 12 W 24 V DC Response time CER IOON 0 2 ms or less Open circuit leakage current 0 1 mA or less 30 V DC ON voltage 1 5 V or less Output circuit insulation Photocoupler insulation Output operation display LED lighting when photocoupler is driven 0 point This number is not related to the maximum number of input output points of the PLC Number of occupied I O points This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties A For safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life
2. e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN
3. European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed 3 1 Applicable Cable and Terminal Tightening Torque 3 1 1 Terminal block European type 1 Wire size Wiring to input device should use 22 to 20 AWG wire 2 Applicable cable Type Wire size Single wire 0 3 to 0 5 mm AWG22 to 20 2 wire 2 pieces of 0 3 mm AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrule with insulating sleeve lt Reference gt Model Manufacturer Caulking tool CRIMPFOX 6 AL0 5 8WH Cor CRIMPFOX 6T F 2 Phoenix Contact Co Ltd 1 Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Strand wire single wire Stick terminal with insulating s
4. 3 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be performed for best results When independent grounding is not performed perform shared grounding of the following figure For details refer to the following manual FX3s Series User s Manual Hardware Ed FX3G Series User s Manual Hardware Ed Other Other Other PLC equipment PLC equipment PLC equipment Independent grounding Shared grounding Common grounding Best condition Good condition Not allowed The grounding wire size should be AWG 22 to 20 0 3 to 0 5 mm e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Device allocation and program example 4 1 Device allocation Each output of 2EYT BD is allocated a special auxiliary relay The ON OFF state of each output is reflected in its corresponding special auxiliary relay Input terminal Special auxiliary relays BYO M8116 BY1 M8117 4 2 Program example Turn the special auxiliary relay allocated to each output ON and OFF by program X000 M8116 When X000 is ON drive BYO M8116 MO BTID M8117 When M0 is ON drive BY1 M8117 ee nee 4 3 Caution on Creation of Programs e When the END instruction of the program is executed the output process is completed The interruption output processi
5. MODEL CODE at i Hardware Edition 09R535 wiring installation and maintenance Explains FX3G Series PLC FX3G Series User s Manual J 997D31301 specification details for I O sat MODEL CODE fae i s Hardware Edition 09R521 wiring installation and maintenance FX3S FX3G FX3GC FX3U FX3UC Series JY997D16601 Describes PLC programming Programming Manual MODEL CODE for basic applied instructions Basic amp Applied Instruction 09R517 and devices Edition How to obtain manuals For the necessary product manuals or documents consult with the Mitsubishi Electric dealer from where you purchase your product 1 2 External Dimensions and Part Names Unit mm inches E 5 Connector cover is 3 O removed x S 7 Ss ars D A 2 1 MASS Weight 20 g 0 05 Ibs 35 1 38 15 1 14 1 0 6 10 56 Terminal Layout 5 poles 1 Terminal block mounting screws 2 Output LED BYO LED The LED is lit when BYO is on BY1 LED The LED is lit when BY1 is on LEDs correspond to each output terminal Co Co BYO BY1 3 Mounting holes 2 3 2 4 Connector cover 5 Main unit connector 6 Terminal block for output European 7 Memory cassette Display module connector 1 represents vacant terminals Do not wire vacant terminals externally PRECAUTIONS NWARN ING e Make s
6. Series User s Manual Hardware E 3 Wiring DESIGN PRECAUTIONS 7 WARN ING e Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure Otherwise malfunctions may cause serious accidents 1 Most importantly have the following an emergency stop circuit a protection circuit an interlock circuit for opposite movements such as normal vs reverse rotation and an interlock circuit to prevent damage to the equipment at the upper and lower positioning limits 2 Note that when the PLC CPU detects an error such as a watchdog timer error during self diagnosis all outputs are turned off Also when an error that cannot be detected by the PLC CPU occurs in an input output control block output contro may be disabled External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 3 If an overload of the 24 V DC service power supply occurs the voltage automatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 4 Note that when an error occurs in a transistor output device the output could be held either on or off For output signals that may lead to serious accidents external circuits and mechanisms should be designed to ensure safe machinery operation in such
7. a case DESIGN PRECAUTIONS Z CAUTION e Do not bundle the control line together with or lay it close to the main circuit or power line As a guideline lay the control line at least 100 mm 3 94 or more away from the main circuit or power line Noise may cause malfunctions WIRING PRECAUTIONS Z WARNING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product e Connect the DC power supply to the dedicated terminals specified in the manual of the PLC main unit If an AC power supply is connected to a DC input output terminal or DC power supply terminal the PLC will burn out When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not wire vacant terminals externally Doing so may damage the product Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise Do not bundle the power line or input line together with or lay it close to the main circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take lace AS a guideline lay the control line at least 100mm 3 94 or more away from the main circuit or high voltage lines Make sure to properly wire to the terminal block
8. disposal of your device TRANSPORTATION AND STORAGE PRECAUTIONS Z CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 5 1 Applicable PLC Model name Applicability FX3s Series PLC Ver 1 10 or later FX3G Series PLC Ver 2 20 or later The version number can be checked by monitoring D8001 D8101 as well the last three digits indicate the version number e Only one 2EYT BD can be used per main unit Never stack up two or more expansion boards For details on the system configuration refer to the following manual FX3s Series User s Manual Hardware Edition FX3G Series User s Manual Hardware Edition 5 2 General Specifications The general specifications are equivalent to the PLC main unit For general specifications refer to the following manuals FX3s Series User s Manual Hardware Edition FX3G Series User s Manual Hardware Edition 5 3 Performance Specification Item Specification Number of output points 2 points Output connecting type Terminal block European type Output form Transistor Sink Source External power supply 5 to 30 V DC AEA Resistance load 0 5 A 1 point Inductive load 12 W 24 V DC Response time OFF f0 ON 0 2 ms or less Open circuit leakage current 0 1 mA or less 30 V DC ON volta
9. major accidents or losses could occur if the product fails install appropriate backup or failsafe functions in the system MITSUBISHI ELECTRIC CORPORATION HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN JY997D51401B MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS MELSEGAF JAPANESE ENGLISH FX3G 2EYT BD USER S MANUAL Manual Number JY997D51401 Revision B 3 G Date April 2015 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies Effective April 2015 Specifications are subject to change without notice 2013 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classify the safety precautions into two categories A WARNING and A CAUTION Indicates that incorrect handling may cause hazardous conditions resulting in death or severe injury Z WARNING
10. 16 Liane MO 18117 When M0 is ON drive BY1 M8117 M8117 4 3 Caution on Creation of Programs e When the END instruction of the program is executed the output process is completed The interruption output processing of HSCS and HSCR etc are not carried out Output refreshing by REF instruction can not be done e Do not use the special auxiliary relay for an instruction by which the bit device is of three points or more such as comparison result of the CMP instruction and comparison result of the ZCP instruction is occupied Do not use the special auxiliary relays for the operand of each application instruction as data K1M8116 and K2M8116 etc 5 Specification STARTUP AND MAINTENANCE PRECAUTIONS Z WARNING e Do not touch any terminal while the PLC s power is on Doing so may cause electric shock or malfunctions Before cleaning or retightening terminals cut off all phases of the power supply externally Failure to do so may cause electric shock Before modifying or disrupting the program in operation or running the PLC carefully read through this manual and the associated manuals and ensure the safety of the operation An operation error may damage the machinery or cause accidents STARTUP AND MAINTENANCE PRECAUTIONS CAUTION e Do not disassemble or modify the unit Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubi
11. Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Z CAUTION Depending on circumstances procedures indicated by A CAUTION may also be linked to serious results In any case it is important to follow the directions for usage Associated Manuals Manual name Manual No Description Explains FX3S Series PLC FX3S Series User s Manual JY997D48601 specification details for I O Fan MODEL CODE at i Hardware Edition 09R535 wiring installation and maintenance Explains FX3G Series PLC FX3G Series User s Manual J 997D31301 specification details for I O sat MODEL CODE fae i s Hardware Edition 09R521 wiring installation and maintenance FX3S FX3G FX3GC FX3U FX3UC Series JY997D16601 Describes PLC programming Programming Manual MODEL CODE for basic applied instructions Basic amp Applied Instruction 09R517 and devices Edition How to obtain manuals For the necessary product manuals or documents consult with the Mitsubishi Electric dealer from where you purchase your product Applicable standards FX3G 2EYT BD units made in September 2013 or later comply with the EC Directive EMC Directive Further information can be found in the following manual FX3s Series User s Manual Hardware Edition FX36 Series User s Manual Hardware Edition Regarding the standards that relate to the
12. JY997D51401B A MITSUBISHI ELECTRIC PROGRAMMABLE CONTROLLERS JAPANESE ENGLISH Applicable standards 2 Installation 3 is WIRING FX3G 2EYT BD units made in September 2013 or later comply with the EC Directive INSTALLATION PRECAUTIONS Z CAUTION MELSEGF FX3G 2EYT BD USER S MANUAL Manual Number JY997D51401 Revision B 3 G Date April 2015 This manual describes the part names dimensions mounting and specifications of the product Before use read this manual and the manuals of all relevant products fully to acquire proficiency in handling and operating the product Make sure to learn all the product information safety information and precautions Store this manual in a safe place so that it can be taken out and read whenever necessary Always forward it to the end user Registration The company and product names described in this manual are registered trademarks or the trademarks of their respective companies EMC Directive Further information can be found in the following manual FX3s Series User s Manual Hardware Edition FX36 Series User s Manual Hardware Edition Regarding the standards that relate to the main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Elec
13. V DC BYO E BYO Load Fuse BY1 3 jl BY1 Source output wi 5 to 30 V DC 3 3 Grounding Grounding should be performed as stated below e The grounding resistance should be 100 Q or less e Independent grounding should be performed for best results When independent grounding is not performed perform shared grounding of the following figure For details refer to the following manual FX3s Series User s Manual Hardware Edition FX3G Series User s Manual Hardware Edition Other Other Other PLC equipment PLC equipment PLC equipment I 1 Common grounding Not allowed Shared grounding Good condition Independent grounding Best condition e The grounding wire size should be AWG 22 to 20 0 3 to 0 5 mm2 e The grounding point should be close to the PLC and all grounding wire should be as short as possible 4 Device allocation and program example 4 1 Device allocation Each output of 2EYT BD is allocated a special auxiliary relay The ON OFF state of each output is reflected in its corresponding special auxiliary relay Input terminal BYO M8116 BY1 M8117 Special auxiliary relays 4 2 Program example Turn the special auxiliary relay allocated to each output ON and OFF by program of PLC x000 e116 i i M8116 When X000 is ON drive BYO M81
14. e with insulating sleeve lt Reference gt Manufacturer Model Caulking tool CRIMPFOX 6 Phoenix Contact Co Ltd or CRIMPFOX 6T F 2 Al 0 5 8WH 1 Old model name CRIMPFOX ZA 3 2 Old model name CRIMPFOX UD 6 Strand wire single wire Stick terminal with insulating sleeve Insulation sleeve Contact area Crimp area CSS mm 8mm 0 35 0 31 2 6mm 0 1 14mm 0 55 es When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 N m Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions 4 Tool For tightening the terminal use a commercially available small screwdriver having a straight form that is not widened toward the end as shown right With straight tip Caution 0 4mm 2 5mm If the diameter of screwdriver grip is too 0 02 gt PASA small tightening torque will not be able to be achieved Use the following recommended screwdriver or an appropriate replacement grip diameter approximately 25 mm 0 98 lt Reference gt Manufacturer Model Phoenix Contact Co Ltd SZS 0 4x2 5 3 2 Wiring of output For the terminal configuration refer to Section 1 2 2EYT BD Sink output wiring I Load Fuse 5 to 30
15. ge 1 5 V or less Output circuit insulation Photocoupler insulation Output operation display LED lighting when photocoupler is driven 0 point Number of occupied I O points This number is not related to the maximum number of input output points of the PLC This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual Warranty Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi opportunity loss or lost profits caused by faults in the Mitsubishi products damage secondary damage accident compensation caused by special factors unpredictable by Mitsubishi damages to products other than Mitsubishi products and to other duties A For safe use e This product has been manufactured as a general purpose part for general industries and has not been designed or manufactured to be incorporated in a device or system used in purposes related to human life e Before using the product for special purposes such as nuclear power electric power aerospace medicine or passenger movement vehicles consult with Mitsubishi Electric e This product has been manufactured under strict quality control However when installing the product where
16. in circuit high voltage line or load line Otherwise noise disturbance and or surge induction are likely to take place As a guideline lay the control line at least 100mm 3 94 or more away from the main circuit or high voltage lines Make sure to properly wire to the terminal block European type in accordance with the following precautions Failure to do so may cause electric shock equipment failures a short circuit wire breakage malfunctions or damage to the product The disposal size of the cable end should follow the dimensions described in the manual Tightening torque should follow the specifications in the manual Twist the end of strand wire and make sure that there are no loose wires Do not solder plate the electric wire ends Do not connect more than the specified number of wires or electric wires of unspecified size Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed 3 1 Applicable Cable and Terminal Tightening Torque 3 1 1 Terminal block European type 1 Wire size Wiring to input device should use 22 to 20 AWG wire 2 Applicable cable Type Wire size Single wire 0 3 to 0 5 mm AWG22 to 20 2 wire 2 pieces of 0 3 mm AWG22 3 Termination of cable end Strip the coating of strand wire and twist the cable core before connecting it or strip the coating of single wire before connecting it An alternative connection is to use a ferrul
17. l block mounting screws 2 Output LED BYO LED The LED is lit when BYO is on BY1 LED The LED is lit when BY1 is on LEDs correspond to each output terminal Co Co BYO BY1 3 Mounting holes 2 3 2 4 Connector cover 5 Main unit connector 6 Terminal block for output European 7 Memory cassette Display module connector 1 represents vacant terminals Do not wire vacant terminals externally For installation uninstallation details refer to the following manual e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur Make sure to affix the expansion board with tapping screws Tightening torque should follow the specifications in the manual Loose connections may cause malfunctions Use screwdrivers carefully when performing installation work thus avoiding accident or product damage When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the p
18. leeve Insulation sleeve Contact area Crimp area CSS mm 8mm 0 35 0 31 2 6mm 0 1 14mm 0 55 i When using a stick terminal with insulating sleeve choose a wire with proper cable sheath referring to the above outside dimensions or otherwise the wire cannot be inserted easily The tightening torque must be 0 22 to 0 25 N m Do not tighten terminal screws exceeding the specified torque Failure to do so may cause equipment failures or malfunctions 4 Tool For tightening the terminal use a commercially available small screwdriver having a straight form that is not widened toward the end as shown right With straight tip Caution 0 4mm 2 5mm If the diameter of screwdriver grip is too 0 02 gt lt 01 small tightening torque will not be able to be achieved Use the following recommended screwdriver or an appropriate replacement grip diameter approximately 25 mm 0 98 lt Reference gt Manufacturer Model Phoenix Contact Co Ltd SZS 0 4x2 5 3 2 Wiring of output For the terminal configuration refer to Section 1 2 Sink output wiring 2EYT BD I Load Fuse 5t030VDC BYO _ a _ BYO I Load Fuse BY1 BY1 Source output wiring 2EYT BD I 5 to 30 VDC BYO 1 aca I Load Fuse BYO I BY1 aca Load Fuse BY1 Ea 3
19. main unit please refer to either the FX series product catalog or consult with your nearest Mitsubishi product provider Attention e This product is designed for use in industrial applications Note e Authorized Representative in the European Community Mitsubishi Electric Europe B V Gothaer Str 8 40880 Ratingen Germany 1 Outline The FX3G 2EYT BD output expansion board hereinafter called 2EYT BD is an expansion board to be installed in the FX3S FX3G series programmable controller hereinafter referred to as PLC to add two transistor outputs 1 1 Incorporated Items Verify that the following product and items are included in the package Product FX3G 2EYT BD output expansion board 2 Installation INSTALLATION PRECAUTIONS NWARN ING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAUTIONS CAUTION e M3x8 tapping screws for installation 2 pcs e Side cover e USER S MANUAL This manual Accessories 1 2 External Dimensions and Part Names Unit mm inches a 5 Connector cover is 3 O removed a S 7 Ss er ey A 2 1 MASS Weight 20 g 0 05 Ibs 35 1 38 15 1 14 1 0 6 10 56 6 Terminal Layout 5 poles 1 Termina
20. ng of HSCS and HSCR etc are not carried out Output refreshing by REF instruction can not be done e Do not use the special auxiliary relay for an instruction by which the bit device is of three points or more such as comparison result of the CMP instruction and comparison result of the ZCP instruction is occupied Do not use the special auxiliary relays for the operand of each application instruction as data K1M8116 and K2M8116 etc 5 Specification STARTUP AND MAINTENANCE PRECAUTIONS N WARNING e Do not touch any terminal while the PLC s power is on Doing so may cause electric shock or malfunctions Before cleaning or retightening terminals cut off all phases of the power supply externally Failure to do so may cause electric shock Before modifying or disrupting the program in operation or running the PLC carefully read through this manual and the associated manuals and ensure the safety of the operation An operation error may damage the machinery or cause accidents STARTUP AND MAINTENANCE PRECAUTIONS NCAUTION e Do not disassemble or modify the unit Doing so may cause fire equipment failures or malfunctions For repair contact your local Mitsubishi Electric representative e Do not drop the product or exert strong impact to it Doing so may cause damage DISPOSAL PRECAUTIONS Z CAUTION e Please contact a certified electronic waste disposal company for the environmentally safe recycling and
21. roduct directly Doing so may cause device failures or malfunctions Connect expansion board securely to their designated connectors Loose connections may cause malfunctions FX3s Series User s Manual Hardware Edition FX3c Series User s Manual Hardware Edition 3 Wiring DESIGN PRECAUTIONS 7 WARN ING e Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure Otherwise malfunctions may cause serious accidents 1 Most importantly have the following an emergency stop circuit a protection circuit an interlock circuit for opposite movements such as normal vs reverse rotation and an interlock circuit to prevent damage to the equipment at the upper and lower positioning limits 2 Note that when the PLC CPU detects an error such as a watchdog timer error during self diagnosis all outputs are turned off Also when an error that cannot be detected by the PLC CPU occurs in an input output control block output contro may be disabled External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 3 If an overload of the 24 V DC service power supply occurs the voltage automatically drops inputs in the PLC are disabled and all outputs are turned off External circuits and mechanisms should be designed to ensure safe machinery operation in such a case 4 Note that
22. shi Electric representative e Do not drop the product or exert strong impact to it Doing so may cause damage DISPOSAL PRECAUTIONS CAUTION e Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device TRANSPORTATION AND STORAGE PRECAUTIONS CAUTION e The product is a precision instrument During transportation avoid any impacts Failure to do so may cause failures in the product After transportation verify the operations of the product 5 1 Applicable PLC Model name Applicability FX3s Series PLC Ver 1 10 or later FX3G Series PLC Ver 2 20 or later The version number can be checked by monitoring D8001 D8101 as well the last three digits indicate the version number e Only one 2EYT BD can be used per main unit Never stack up two or more expansion boards For details on the system configuration refer to the following manual FX3s Series User s Manual Hardware Edition FX3G Series User s Manual Hardware Edition 5 2 General Specifications The general specifications are equivalent to the PLC main unit For general specifications refer to the following manuals FX3s Series User s Manual Hardware Edition FX3G Series User s Manual Hardware Edition 5 3 Performance Specification Item Specification Number of output points 2 points Output connecting type Terminal block European type
23. tric Europe B V Gothaer Str 8 40880 Ratingen Germany 1 Outline The FX3G 2EYT BD output expansion board hereinafter called 2EYT BD is an expansion board to be installed in the FX3S FX3G series programmable controller hereinafter referred to as PLC to add two transistor outputs 1 1 Incorporated Items Verify that the following product and items are included in the package Product FX3G 2EYT BD output expansion board e M3x8 tapping screws for installation 2 pcs e Side cover e USER S MANUAL This manual Accessories Effective April 2015 Specifications are subject to change without notice 2013 Mitsubishi Electric Corporation Safety Precaution Read these precautions before use This manual classify the safety precautions into two categories A WARNING and A CAUTION Indicates that incorrect handling may cause hazardous conditions resulting in death or severe injury Z WARNING Indicates that incorrect handling may cause hazardous conditions resulting in medium or slight personal injury or physical damage Z CAUTION Depending on circumstances procedures indicated by A CAUTION may also be linked to serious results In any case it is important to follow the directions for usage Associated Manuals Manual name Manual No Description Explains FX3S Series PLC FX3S Series User s Manual JY997D48601 specification details for I O Fan
24. ure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product INSTALLATION PRECAUTIONS CAUTION e Use the product within the generic environment specifications described in PLC main unit manual Hardware Edition Never use the product in areas with excessive dust oily smoke conductive dusts corrosive gas salt air Cl2 H2S SO2 or NO2 flammable gas vibration or impacts or expose it to high temperature condensation or rain and wind If the product is used in such conditions electric shock fire malfunctions deterioration or damage may occur Make sure to affix the expansion board with tapping screws Tightening torque should follow the specifications in the manual Loose connections may cause malfunctions Use screwdrivers carefully when performing installation work thus avoiding accident or product damage When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not touch the conductive parts of the product directly Doing so may cause device failures or malfunctions Connect expansion board securely to their designated connectors Loose connections may cause malfunctions For installation uninstallation details refer to the following manual FX3s Series User s Manual Hardware E FX3c
25. when an error occurs in a transistor output device the output could be held either on or off For output signals that may lead to serious accidents external circuits and mechanisms should be designed to ensure safe machinery operation in such a case DESIGN PRECAUTIONS Z CAUTION e Do not bundle the control line together with or lay it close to the main circuit or power line As a guideline lay the control line at least 100 mm 3 94 or more away from the main circuit or power line Noise may cause malfunctions WIRING PRECAUTIONS Z WARN ING e Make sure to cut off all phases of the power supply externally before attempting installation or wiring work Failure to do so may cause electric shock or damage to the product WIRING PRECAUTIONS Z CAUTION e Connect the DC power supply to the dedicated terminals specified in the manual of the PLC main unit If an AC power supply is connected to a DC input output terminal or DC power supply terminal the PLC will burn out When drilling screw holes or wiring make sure cutting or wire debris does not enter the ventilation slits Failure to do so may cause fire equipment failures or malfunctions Do not wire vacant terminals externally Doing so may damage the product Make sure to observe the following precautions in order to prevent malfunctions under the influence of noise Do not bundle the power line or input line together with or lay it close to the ma