        DAM-E3043 User`s Manual
         Contents
1.          DAM E3043 User s Manual       V6 10                               Domain Name Data  hex   Domain Name Data  hex   Function Code 01 Function Code 01  Start Address H  byte  00 Byte Count 03  Start Address L  byte  13 27 h  20 status CD  Read Amount H  byte  00 35 h  28 status 6B  Read Amount L  byte  13 38 h  36 status 05             Read Holding Register    Function Code  03    Note  Read the holding register value    Data Description                                                                                                        Address Description Note  40001 Ch01 Pulse Output L Level 16 bits  40002 Ch01 Pulse Output H Level 16 bits  Reservation  40065 Ch01 Switch Pulse Count L Level 16 bits  40066 Ch01 Switch Pulse Count H Level 16 bits  Reservation  40129 For Pulse Output Enable Register Set bit  Enabled  Space  Disabled  Reservation  40257 For Chl Analog Input Mode De a   code   ee E a A G A  the range of Chl is OK   40259 For Ch3 Analog Input Mode  Reservation  40289 For Chl Lower Limit Alarm Value L 16 bits  40290 For Chl Lower Limit Alarm Value H 16 bits  40291 For Ch2 Lower Limit Alarm Value L 16 bits  40292 For Ch2 Lower Limit Alarm Value H 16 bits  40293 For Ch3 Lower Limit Alarm Value L 16 bits  40294 For Ch3 Lower Limit Alarm Value H 16 bits  Reservation  40321 For Chl Upper Limit Alarm Value L 16 bits  40322 For Chl Upper Limit Alarm Value H 16 bits  40323 For Ch2 Upper Limit Alarm Value L 16 bits  40324 For Ch2 Upper Limit Alarm Value H 16 bits  
2.    Wiring  amp  Installation    Power supply requirements  unregulated  10 Vpc    30 Vpc    Vs  is a positive  and  GND  is ground   The Ethernet interface is connected to a computer switch directly via network cable  If the wiring and  power is ok  then the power indicator should be stop flash and keep on  The module initialization is  completed  The indicator flashes according to the transmitted data when the module is working     DAM E3043       DAM E3043 can be installed in standard DIN rail inside the cabinet  it also can be installed by stacking  mode        Fig 2 DAM E3043 standard DIN installation    DAM E3043 User s Manual V6 10       Application Wiring       Fig 5 3 wire RTD wiring diagram    DAM E3043 User s Manual V6 10       Fig 7 collector output wiring diagram    Default Setting    If the module s network configuration is wrong  or forget the last modified value  the module can be reverted to default  settings  Steps  short circuit the    INIT     and    GND    when there is no power  power on for 3 seconds  power off     disconnect    INIT     and    GND     The module is reverted to the default settings     IP Address  192 168 2 80  Subnet Mask  255 255 255 0  Default Gateway  192 168 2 1  TCP Port  502   HTTP Port  80    a B GR    Code configuration table  RTD Input Range Configuration Code Table                                     Tvpe Range Code   200  C 600  C 20  Pt100 385   100  C 100  C 21  0  C 100  C 22  0  C 200  C 23  0  C 600  C 24  Cu50  50  C 15
3.  You can only read and write one file at one time                             Request  Domain Name Byte Value  Function Code 1 byte 0x 14  Byte Count 1 byte 0X07 to 0 XF5  Sub Function Code Ibvte 0X 06  File Number 2 bytes 0x0000 to OxFFFF  Record Number 2 bytes 0x0000 to 0x270F  Read Length 2 bytes n  Sub Function Code 1 byte 0x06                         Response   Domain Name Byte Value  Function Code 1 byte 0X14   Byte Count 1 byte 0x07 to OxF5  Sub Function Byte Count 1 byte 0x07 to OxF5  Sub Function Code 1 byte 0x06       Data          2n bytes             V6 10    DAM E3043 User s Manual V6 10                                                                                                                                                    Exception  Domain Name Byte Value  Function Code 1 byte 0x 14  0X80  Error Code Ibvte OX1oroOXx2  Example  Request Response  Domain Name Data hex  Domain Name Data hex    Function Code 14 Function Code 14  Byte Count 07 Byte Count 06  Sub Function Code 06 Respond Count 05  File Number High  byte  00 Sub Function Code 06  File Number Low bvte  04 Record Data High bvte  0D  Record Number High byte  00 Record Date Low byte  FE  Record Number Low byte  01 Record Data High bvte  00  Read Length High byte  00 Record Date Low byte  20  Read Length Low byte  02  Write File Record  Function Code  15 06  Request  Domain Name Byte Value  Function Code 1 byte 0X15  Byte Count 1 byte 0X07 to 0XF5  Sub Function Code 1 byte 0X06  File Number 2 bytes 
4.  timer length  millisecond    Note 2  When power on  the highest bit ofthe watchdog control register is 1  can be done to do determine whether the  module is rested or not     Read Input Register  Function Code  04    Description   Read input data    Data Description                          Address Description Note  30257 For Chl Analog Input Value L 16 bits  30258 For Chl Analog Input Value H 16 bits  30259 For Ch2 Analog Input Value L 16 bits  30260 For Ch2 Analog Input Value H 16 bits  30261 For Ch3 Analog Input Value L 16 bits                DAM E3043 User s Manual V6 10                                                                                                                                                       30262 For Ch3 Analog Input Value H 16 bits  Reservation  30289 For Ch1 Alarm Status 0 for normal  1 for lower limit  2 for upper  limit  30290 For Ch2 Alarm Status 0 for normal  1 for lower limit  2 for upper  limit  30291 For Ch3 Alarm Status 0 for normal  1 for lower limit  2 for upper  limit  Reservation  Request  Domain Name Byte Value  Function Code 1 byte 0X04  Start Address 2 bytes 0 x 0000 to 0 X FFFF  Read Amount 2 bytes 1 to 125  0X 7D   Response  Domain Name Byte Value  Function Code 1 byte 0x04  Byte Count 1 byte 2n  Input State 2n bytes  Exception  Domain Name Byte Value  Function Code 1 byte OX 04 0 X 80  Error Code 1 byte 0X1 or0X2  Example  Request Response  Domain Name Data  hex  Domain Name Data  hex   Function Code 04 Function Code 04  St
5. 0  C 40  Cul00  50  C 150  C 41  BAI  200  C 650  C 42  BA2  200  C 650  C 43  G53  50  C 150  C 44                   DAM E3043 User s Manual V6 10       Communication Protocol    At present  Ethernet Distributed Acquisition Modules of our companv use MODBUS TCP mode  Supported function  codes include the following categories     01 READ COIL STATUS   02 READ INPUT STATUS   03 READ HOLDING REGISTERS  04 READ INPUT REGISTERS   05 FORCE SINGLE COIL   06 PRESET SINGLE REGISTER   15 FORCE MULTIPLE COILS   16 FORCE MULTIPLE REGISTERS  20 READ FILE RECORD   21 WRITE FILE RECORD    Address Mapping Table  Read Relay Status    Function Code  01  Description   Read the status of the output relay    Data Description                                                                                                              Address Description Note  00001 Ch01 For Switch Output Current Status  1 for H Level 0 for L level  Reservation  00033 Ch01 For Switch Output Power on Status  1 for H Level 0 for L level  Reservation  00065 Ch01 For Switch Output Safe Status  1 for H Level 0 for L level  Reservation  Request  Domain Name Byte Value  Function Code 1 byte 0X01  Start Address 2 bytes 0 X 0000 to 0X FFFF  Read Amount 2 bytes 1 to 2000  0 X 7D0   Response  Domain Name Byte Value  Function Code 1 byte 0x01  Byte Count 1 byte n   Read Amount 7  8  Coil Status n bytes  Exception  Domain Name Byte Value  Function Code 1 byte 0 X02 0 X 80  Error Count 1 byte 0X1or0x2  Example  Request Response 
6. 0x0000 to OxFFFF  Record Number 2 bytes 0x0000 to 0x270F  Read Length 2 bytes u  Data 2n bytes  Response  Domain Name Byte Value  Function Code 1 byte 0x15  Byte Count 1 byte 0x07 to OxE5  Sub Function Code 1 byte 0x06  File Number 2 bytes 0x0000 to OxFFFF  Record Number 2 bytes 0x0000 to 0x270F  Write Length 2 bytes n  Data 2n bytes  Exception  Domain Name Byte Value  Function Code 1 byte 0X 15 0X80  Error Code 1 byte 0X1or0X2                   DAM E3043 User s Manual V6 10                                                          Example  IRequest Response  Domain Name Data hex  Domain Name Data hex   Function Code 15 Function Code 15  Byte Count 0B Byte Count 0B  Sub Function Code 06 Sub Function Code 06  File Number High  byte  00 File Number High  byte  00  File Number Low byte  04 File Number Low  byte  04  Record Number High byte  00 Record Number High byte  00  Record Number Low byte  01 Record Number Low byte  0l  Read Length High byte  00 Write Length High byte  00  Read Length Low byte  02 Write Length Low byte  02  Write Data 4 bytes Write Data 4 bytes  EEPROM assignment     file 0    define MODULE_NET ADDR 0x0000    define MODULE VER ADDR 0x0020    define ADC_ZERO_ADDR 0x0080    define ADC_SLOPE ADDR 0x0084     file 1    define NET CONFIG ADDR 0x0000     file 3    define ADC_CONTRL_ADDR 0x0000    define ADC ALARMC ADDR 0x00A0      file 4 to file 7  Note   EEPROM is 8kbyte capacity  divide to 8 file blocks  every block Ikbvte   1  MODULE NET ADDR  Restore to factor
7. 40325 For Ch3 Upper Limit Alarm Value L 16 bits  40326 For Ch3 Upper Limit Alarm Value H 16 bits  Reservation  40273 For Chl Analog Alarm Level Normal Status  0x0000  Lower Limit Alarm  0x0001  40274 For Ch2 Analog Alarm Level Upper Limit Alarm  0x0002  All the analog channels share one alarm output  so  40275 For Ch3 Analog Alarm Level just set Chl is OK              DAM E3043 User s Manual V6 10                                                                                                                   40513 For Watchdog Control Register bit0 1 for enabled  0 for disabled  bitl  0 for normal  1 for overflow  bit2  0 for normal  1 for reset   40514 For Watchdog Overflow Register Watchdog Overtime Constant   40515 For Watchdog Reset Registered OxSSAA   Reservation  Request  Domain Name Byte Value  Function Code 1 byte 0X03  Start Address 2 bytes 0 X 0000 to 0 X FFFF  Read Amount 2 bytes 1 to 125  0X7D   Response  Domain Name Byte Value  Function Code 1 byte 0X03  Byte Count 1 byte 2n  Input State 2n bytes  Exception  Domain Name Byte Value  Function Code 1 byte 0X 03 0 X 80  Error Code 1 byte 0X1or0x2  Example  Request Response  Domain Name Data  hex  Domain Name Data  hex   Function Code 03 Function Code 03  Start Address H  byte   00 Byte Count 02  Start Address L  byte  08 Input Registers High 00  Read Amount H  byte  00 Input Register Low 0A  Read Amount L  byte  01                Note 1  The unit of the pulse output level width  millisecond  The unit of the watchdog
8. DAM E3043    User   s Manual    W Beijing ART Technology Development Co   Ltd     DAM E3043 User s Manual V6 10       DAM E3043 Module    Introduction    Features   3 ch Resistance Temperature Input and 1 ch Isolated Digital Output Module  General   Power Supply  unregulated  10    30 Vpc   Power Consumption  2W   24Vpc   Support 10 100Mbps Ethernet    Provide the default Web page or pages can be customized    VV VV V    Built in Watchdog   Analog Input    Channel  3 channels   Input type  Pt100 385   Cu50  Cul00  BA1  BA2  G53  Sampling Frequency  10Hz  Resolution  16 bit  Accuracy   0 1    Input Impedance  10KQ  Zero Drift    3uV  C   CMR   50 60Hz  150dB  Isolation Voltage  3000V    VV VV VV VV V WV    Wiring Method  2 wire  3 wire and 4 wire  Digital Output    Channel  1   Open collector 30V  maximum load100mA   Isolation Voltage  3750V    Independent channel disconnection detection function    VV VV V    Programmable alarm status output    Easy to operate    DAM E3043 utility software can help you to select input configuration  set the operating parameter for  your process control needed     Industrial Design    DAM E3043 was designed to use in industrial environment  It can be installed in standard DIN rail inside  the cabinet  And it can be powered by unregulated 10 30Vpc to meet the various power supplied source  in field  It also withstands ambient temperature up to 60  C and resists the effects of vibration and  mechanical shock     DAM E3043 User s Manual V6 10    
9. art Address H  byte   00 Byte Count 02  Start Address L  byte  08 Input Register H  9  00  Read Amount H  byte  00 Input Register L  9  0A  Read Amount L  byte  01  Write Single Relay  Function Code  05  Request  Domain Name Byte Value  Function Code 1 byte 0x05  Address Setting 2 bytes 0 X 0000 to 0 X FFFF  Content Setting 2 bytes 0x0000 or OxFFOO  0x0000 release relay  OxFFO00 engage relay  Response  Domain Name Byte Value  Function Code 1 byte 0x05                   DAM E3043 User s Manual V6 10                                                                            Address Setting 2 bytes 0x0000 to OxFFFF  Content Setting 2 bvtes 0x0000 or OxFFOO  Exception  Domain Name Byte Value  Function Code lbyte 0x05 0x80  Error Code lbyte 0x1 or 0x2  Example  Request Response  Domain Name Data  hex  Domain Name Data  hex   Function Code 05 Function Code 05  Set Address H  byte  00 Set Address H  byte  00  Set Address L  byte  05 Set Address L  byte  05  Set Content H  byte  FF Set Content H  byte  FF  Set Content L  byte  00 Set Content L  byte  00                Set Single Holding Registers  Function Code  06                                                                                                       Request   Domain Name Byte Value   Function Code 1 byte 0X06   Setting Address 2 bytes 0 X 0000 to 0 X FFFF   Setting Content 2 bytes 0X 0000 to 0 X FFFF  Response   Domain Name Byte Value  Function Code 1 byte 0X06  Address Setting 2 bytes 0 X 0000 to 0 X FFFF  Content Se
10. t Content Low  byte  01                   Set Multiple Holding Registers  Function Code  10                               Request  Domain Name Byte Value  Function Code 1 byte OX10   Start Address Setting 2 bvtes 0 X 0000 to OX FFFF  Length Setting 2 bvtes 0 X 0000 to OX 07B0  Byte count 1 byte 2n   Content Setting 2n bytes   Response  Domain Name Byte Value  Function Code 1 byte 0X10                   DAM E3043 User s Manual                                                                                                       Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF  Length Setting 2 bytes 0 X 0000 to 0X 07B0  Exception  Domain Name Byte Value  Function Code 1 byte 0X 10 0xX 80  Error Code 1 byte 0X1 or 0X2  Example  IRequest Response  Module address Data hex  Module address Data hex   Function Code 10 Function Code 10  Set Address High  byte  00 Set Address High  byte  00  Set Address Low  byte  01 Set Address Low  byte  01  Set Amount High byte  00 Set Amount High byte  00  Set Amount Low  byte  02 Set Amount Low  byte  02  Byte count 04  Set Content High  byte  00  Set Content Low  byte  0A  Set Content High  byte  01  Set Content Low  byte  02  Read File Record    Function Code  14 06    Read file record  in MODBUS  file is considered to be 16 bit array  addressing according to address  Read file  set the  start address and read length and change the Start Address and Read Length can traverse the entire file  The file does not    have a name  it has number only 
11. tting 2 bytes 0 X 0000 to 0 X FFFF   Exception   Domain Name Byte Value   Function Code 1 byte 0X 06 0 X 80   Error Code 1 byte 0X1 or 0X2  Example  IRequest IResponse  Domain Name Data hex  Domain Name Data hex   Function Code 06 Function Code 06  Set Address High  byte  00 Set Address High  byte  00  Set Address Low  byte  08 Set Address Low  byte  08  Set Content High  byte  00 Set Content High  byte  00  Set Content Low  byte  19 Set Content Low  byte  19                   DAM E3043 User s Manual V6 10                                                                                                                            Set Multiple Relay  Function Code  OF  Request  Domain Name Byte Value  Function Code 1 byte OXOF  Start Address Setting 2 bvtes OX0000 to 0 X FFFF  Length Setting 2 bytes 0X 0000 to 0X 07B0  Byte count 1 byte n  Content Setting n bytes  Response  Domain Name Byte Value  Function Code 1 byte 0 X0OF  Start Address Setting 2 bytes 0 X 0000 to 0 X FFFF  Length Setting 2 bytes 0 X 0000 to 0 X 07B0  Exception  Domain Name Byte Value  Function Code 1 byte 0 X OF 0 X 80  Error Code 1 byte 0X1 or 0X2  Example  IRequest IResponse  Domain Name Data hex  Domain Name Data hex   Function Code OF Function Code OF  Set Address High  byte  00 Set Address High  byte  00  Set Address Low  byte  13 Set Address Low  byte  13  Set Amount High  byte  00 Set Amount High  byte  00  Set Amount Low  byte  0A Set Amount Low  byte  0A  Byte count 02  Set Content High  byte  CD  Se
12. y defaults network configuration parameter     Byte 4 4 4 6  Content IP Address Default Gateway   Subnet Mask   MAC Address                               2  MODULE_VER_ADDR    Module Version Information        Byte 42byte  Content DAM E3043 V6 20 2006 09 01 ID  DAME123456    3  ADC_ZERO_ADDR                   Analog input zero point calibration factor  4 bytes float  Calibrate method  function code is 3 and calibrates register  address is from 432772 to 432773  Change the register to complete zero point calibration  Note  the changes can not be  saved to EEPROM  so it is necessary to clear the write protect of file 0 via function code 3  address 432769  Then write    DAM E3043 User s Manual V6 10  ss SSS SSS SSS SSS   _ EEE Ee U a    zero point calibration data to file 0  address ADC ZERO ADDR     4  ADC SLOPE ADDR  Analog input slope calibration factor  4 bvtes  Calibrate method  function code is 3 and calibrates register address is from    432770 to 432771  The same method as zero point calibration   5 NET CONFIG ADDR   Network configuration parameter  call table 1 for structures    6 ADC CONTRL ADDR   Analog input control register  2 bvtes  high bvte is 0     7 ADC LIMITU ADDR    
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
ASUS STRIX-GTX750TI-OC-2GD5 1 User's Manual  Nature2® Fusion Inground  Bombas de baja presión  RL78 Data Flash Access Library Type T02 (Tiny), European Release  Worldwide Lighting W83101C28-AM Installation Guide    DuraLabel 4TTP Manual - DuraLabel Sign and Label Printers    Copyright © All rights reserved. 