A T S – 1 1 5 USER`S MANUAL

image

Contents

1. 4 Menu Enter Knob turned for 12 Output socket No 2 LCD menu page selection and 13 Output socket No 1 pressed for enter confirmation 14 Input socket for Line 2 5 Intelligent slot 15 Trip Breaker for Line 2 6 USB interface port for ATS 16 Input socket for Line 1 7 RS232 for UPS interface port 17 Trip Breaker for Line 1 8 Output socket No 6 4 Cable connection 4 1 Inspection 1 When installing the electrical wiring please note the nominal amperage of your incoming feeder 2 Please note if the specification of input voltage branch is correct or not 4 2 connection 1 ATS input connection Please ensure the correct AC source on input socket 2 ATS output connection Simply connect the load to the ATS output sockets 5 Operation 5 1 Check before starting 1 Ensure the ATS is in a suitable position 2 Ensure the input output cords are completely connected 5 2 Operation and setup 5 2 1 Operation 1 Input power UNE No A is the primary power source input power LINE2 No B is the reserve power 2 When the LINE1 has AC power ATS will start up automatically 4 ATS can automatically detect for 110VAC or 220VAC 5 2 2 LCD Menu 1 Main Menu a This main menu indicates the input power source is from No A Line 1 or No B Line 2 and all the output socket ON OFF status Like the above case it shows the input power source is from No A Line 1 primary source Now the output sockets No 2 amp 4 amp 6 are on th
2. ATS 115 USER S MANUAL ay BON The British Power Conversion Company Contents 1 pute ele Re Le DEEN 2 2 Safety instruction aanrennen 3 3 Outline description cece eee eee es 4 4 Cable connection cece ee ees 5 E el e EE 5 6 Communication Imterlace 12 7 Trouble shooting guide 13 8 Specifications nennen 14 1 Introduction 1 1 General description For valuable equipments the continuity of electrical power is an essential requirement Therefore the uninterruptible power system is the basic equipment But in case the uninterruptible power system is failure and needed to remove for maintenance It won t continue to supply power to any equipment In order to supply power to the equipment continually we designed the ATS Automatic Transfer Switch which offer dual AC power source input When the primary power supply from UPS or other power source is in failure the ATS can automatically transfer to secondary power source to keep power output for the valuable equipments work normally 1 2 Feature 1 Multiple microprocessor design 2 LED and LCD display for status and data of ATS 3 Output sockets can be independently controlled ON OFF and scheduling 4 To given a name for output socket and to delay setting switch 5 Output sockets can be set to priority 6 Remote monitoring with SNMP intelligent slot and RS 232 interface 7 To get UPS cu
3. e case there is UPS installed on the input power source Line1 or Line 2 All the setting procedure is like the menu of UPS Overload Off 10 a In this menu setting is required if the input AC source wave form is not stable as pure sine wave because it may increase the transfer time of LINE1 amp 2 b Press Menu Enter Knob to enter wave form selection 8 1 Turn the knob to select Pure Sine when the input AC is pure sine wave and stable Select Not Pure Sine for when AC wave form is not sine wave a In this Date Time setting menu press Menu Enter Knob to enter each date and time Then turn the knob for correct number b Press ESC key for main menu 6 Communication interface 6 1 UPS communication interface 1 ATS provides two sets of RS232 communication port for the case UPS installed as input power Both of the RS232 port for ATS and UPS must be connected for the priority setting of UPS Overload Off and Battery Low Off 2 LINE1 RS232 port should be connected to the RS232 port of UPS installed for power LINE1 3 LINE2 RS232 port should be connected to the RS232 port of UPS installed for power LINE2 4 Megatec s protocol is used for communication interface 6 2 Computer software interface 1 USB is used for ATS software communication 2 ATS software offer more function setting status and ON OFF schedule 6 3 Internet Communication 1 ATS provides intelligent slot for optional SNMP ca
4. e status of ON and 1 amp 38 amp 5 OFF b Under main menu by turning the Menu Enter Knob clockwise or anti clockwise the other menus 2 9 can be browsed c Press Menu Enter Knob to enter the following displays for output load status and sockets setting Display for the input power source voltage frequency and of loading By turning the Menu Enter Knob clockwise or anti clockwise each of the output sockets status can be browsed 1 2 Display for output socket ON OFF status name of the load which connected to this socket and load current Press the knob to the following socket ON OFF setting The Load name can be only edited by the software attached 1 3 Turn the knob to select ON or OF F then press to confirm setting Press ESC key to main menu In main menu to turn right enter next screen Display for input No A Line 1 voltage frequency and status Display for input No B Line 2 voltage frequency and status For convenience press Menu Enter Knob to enter output socket setting for all ON and all OFF in one time 4 4 Turn the knob to select ON or OFF then press to confirm setting Press ESC key to main menu a This menu the function of AC Overload Off is for the load shutdown priority setting in case of AC input overload By the way of turning off the output socket the load connected to output socket can be shutdown by priorit
5. rd internet remote control Please contact your supplier for special details 2 The optional RS232 interface card is available if there is no USB port in computer 12 7 Trouble Shooting 1 In case no LCD and LED indication output socket without output Action Please check if input power source LINE1 has power and if inout breaker is tripped 2 Panel LINE1 LED or LINE2 LED is blinking Action Please check if the input power voltage frequency and phase polarity L N for LINE 1 amp LINE 2 are correct 3 There is has AC input but the ATS still can t work normally Action Please remove power source then reconnect it If you still can t solve the troubles please contact your supplier Do not open case to avoid any danger 13 8 Specifications tem Input Display data for each output socket lt current name gt USB 1pcs Intelligent slot 1pcs Operation Temperature O 40 C Relative Humidity lt 95 Non condensing Altitudes Dimension W H D 440mm 44mm 250mm weight Jeng 3 2kg x Specification are subject to change without notice 14
6. rrent state through exclusive interface connects UPS 8 Light weight compact size easy to transport and installation 2 Safety instruction 2 1 Transport 1 Please use original packaging to transport 2 Be careful not to impact it while transporting 3 Before removing please turn off the ATS and disconnect the power 2 2 Positioning 1 Do not put it on rugged or declined position 2 Do not put it near water or in environments of excessive humidity 3 Do not put it in volatile gases or solutions environment 4 Do not put it under direct sunshine or close to heat emitting sources 5 Do not block air vents to keep good ventilation 6 Do not put anything on the machine 2 3 Installation 1 Please install the current is larger than the local socket 2 To ensure connect the power cord 3 Do not bundle the power cord 2 4 Maintenance and service 1 There are high voltage in inside do not open the case to avoid electric shock 2 Please contact professional service personnel if failure 3 Outline description Front t TT 2 Rear Panel with IEC Socket BEST 3 i ES E ie r He e NNN OD Om YD o O Cl O O Rear Panel with NEMA Socket e TR em fig cee fo f fF ft fF 4 ff Fo of fF Ff OU 3 5 4 1 LCD 9 Output socket No 5 2 LED for AC input Line1 amp 2 10 Output socket No 4 3 ESC key for LCD menu 11 Output socket No 3
7. y b Press Menu Enter Knob to enter the priority setting Only when this function is ON activated the output socket will be automatically turned off as per priority until the load is less than 100 5 1 Turn the knob to select ON or OFF for this AC overload protection function then press to confirm the setting Only the ON is selected this function is activated it can enter the following sub menu 5 2 a Turn the knob to select the output socket Number digital for the first priority Then press to confirm setting and go to the second priority setting Please select one by one b There is no limit for the total quantity of priority setting But maximum is 6 pieces because there is only 6pcs of output socket c Press ESC key for main menu a This menu the function of UPS Overload Off is only used for the case there is UPS installed on the input power source Line1 or Line 2 And both of the UPS and ATS should be connected by RS232 interface port When UPS is under overload it can send out the alarm signal to ATS which can shutdown the loads as per priority b Press Menu Enter Knob to enter the priority setting Only when this function is ON activated the output socket will be automatically turned off as per priority until the load is less than 100 The other setting procedure is like the menu of AC Overload Off 7 This menu the function of Battery Low Off is only used for th