DCP552B Mark II - Azbil Corporation
Contents
1. General Operating conditions Ambient temperature O to 50 C ambient temperature at the bottom side of case when gang mounted specifications range Ambient humidity 10 to 90 RH condensation not allowed range Rated power 100 to 240V AC voltage Allowable power 90 to 264V AC voltage Power frequency 50 2 Hz or 6042 Hz Vibration resistance 0 to 1 96 m s Shock resistance 0 to 9 80 m s Mounting angle Reference plane vertical 10 Transport storage Ambient temperature 20 to 70 C conditions range Ambient humidity 10 to 95 RH condensation not allowed range Vibration resistance 0 to 4 90 m s 10 to 60 Hz for 2 hours each in X Y and Z directions Shock resistance 0 to 490 m s 3 times vertically Package drop test Drop height 60 cm 1 angle 3 edges and 6 planes free fall Terminal screw M3 5 self tapping screws Terminal screw 0 78 to 0 98 N m tightening torque Mask case materials Mask Multilon Case Multilon Mask case color Mask Dark gray Munsell 5Y3 5 1 Case Light gray Munsell 2 5Y7 5 1 Installation Specially designed mounting bracket Weight Approx 1 5 kg Standard Item Model No Q ty Auxiliary parts Item Model No Q ty accessories Unit indicating label 1 sold separately Soft dust proof cover set 81446141 001 Mounting bracket 81446044 001 1 s
2. system Data line Bit serial Signal line 5 transmit receive lines 3 wire connection also possible Transmission 1200 2400 4800 9600 bps speed Transmission 500 m max total distance 300 m max for MA500 DIM connection Other Conforming to RS 485 interface specifications Communications RS 485 Char bit count 11 bits character Format 1 start bit even parity 1 stop bit or 1 start bit no parity and 2 stop bits Data length 8 bits Isolation All inputs and outputs are completely isolated except external switch inputs RS 485 communication s can be performed b y connecting to a computer equipped with an RS 485 interface or to Azbil Corporation MX200 MA500 DK link II DIM or CMA50 controllers RS 232C Network 1 1 Connected This controller is provided with only slave instrument functionality Data flow Half duplex Synchronization Start stop synchronization Transmission Unbalanced type system Data line Bit serial Signal line 3 transmit receive lines Transmission 1200 2400 4800 9600 bps speed Transmission 15 m max distance Other Conforming to RS 232C interface specifications Char bit count 11 bits character Format 1 start bit even parity 1 stop bit or 1 start bit no parity and 2 stop bits Data length 8 bits Isolation All inputs and outputs are completely isolated except external switch inputs
3. 89 Oz sensor input Q 4 gt Oz sensor If voltage mode signals are input to PV input CH1 terminal Nos 6 and input CH2 terminal Nos 6 for current input by mistake a large current might flow and cause the controller to malfunction Before wiring to the current input terminals on the DCP552B make sure that current input signals are output correctly within the range 4 to 20 mA Control output and auxiliary output Control output Current output CH1 control output current output CH2 control output current output Open collector output CH1 control output voltage output CH2 control output current output 6 5 Load 12 to 24V DC Load 12 to 24V DC e Auxiliary output Receiver Receiver 10 Voltage output CH1 control output voltage output a a a SSR CH2 control output voltage output 6 SSR Internal circuit of external switch input External switch Internal circuit 5 V separate 5 V from internal voltage Dw 7 of Internal GND Separate GND in addition to internal ground GND for above 5 V Communications I O option RS 485 3 wire type Slave instrument DCP552B SDA SDB RDA RDB Slave instrument DCP552B SG SDA SDB RDA RDB SG RS 232C DCP5
4. General specifications Memory backup Battery life Control Control Memory Battery backed up RAM ler power OFF Approx 5 years under standard conditions ler power ON Approx 10 years under standard conditions Rated power voltage 100 to 240V AC 50 60 Hz Power consumption 40 VA max Power ON rush current 50 A max Power ON operation Reset time 10 seco nds max time until normal operation is possible under normal operating conditions Allowable transient power loss 20 ms max under operating conditions Insulation resistance Min 50 MQ across power terminal or and FG terminal 62 or 6 by 500V DC megger Dielectric strength 1500V AC 50 60 Hz Note The primary secondary s test is carrie for 1 minute between power terminal and FG terminal side and secondary side capacities are joined inside the product For this reason when carrying out a withstand voltage test disconnect the wiring of the grounded ide terminals e g when grounding type thermocouple is used from that terminal If the d out with the wiring as it is this might result in malfunction Standard conditions Ambient temperature 2322 C Ambient humidity 6025 RH Rated power voltage 105V AC 1 Power frequency 50 1 Hz or 60 1 Hz Vibration resistance 0 m s Shock resistance 0 m s Mounting angle Reference plane vertical 3
5. Load Load Load Remote program No selection by external switch input Common A BCD External switch swg ot swio 206 swii oo swi2 8 oo swi3 4 2 oo swi4 420 oo sw15 CH1 cancel lt sw16 CH2 cancel 4 Common Input e PV input CH1 Thermocouple input T C e PV input CH2 Thermocouple input T C Note EV7 EV8 EV9 EV10 EV11 EVi2 EV13 EVi4 EVi5 EVi6 Fol fe fe el fal Fel fel Tel sl fel f ER ERB HEERE 8 3 g External External power power supply supply 12 to 24V DC 12 to 24V DC Noise filter 4 1 Instrument GND 3 a power supply 90 to 264V AC 900 QO 00 0000 CH1 control output I CH2 control output Auxiliary Auxiliary output 1 output 2 FG 00 00e oA Input CH1 RTD input 9 Cc A B RTD RTD input Cc A B RTD Input CH2 Communications I O Current input Frame ground terminals 6 and 63 are common Voltage input C Current Voltage mA mV V oscillator oscillator Current input Voltage input Current mA oscillator Voltage mV V oscillator
6. 5V DC Burnout Detection selectable Over range detection threshold 110 FS min Upscaled 10 FS max Downscaled Note that F50 range is not downscaled Cold junction compensation accuracy 0 5 C under standard conditions Cold junction compensation system Internal external 0 C only compensation selectable Scaling 19999 to 20000 U possible in case of linear input only Inverse scaling possible Decimal point position settable at any point Square root extraction Possible Dropout 0 2 to 10 0 in case of DC current or DC voltage range PV equalizer PV1 9 segments 10 points set linearization table PV2 9 segments 10 points set approximation CP 9 segments 10 points set Input bias 1000 to 1000 U variable Digital filter 0 0 to 120 0 seconds variable 0 0 filter OFF External switch inputs Number of inputs 16 Types of connectable outputs Dry contacts relay contact and open collector current sink to ground Terminal voltage open 8 5 V 0 5 V between common terminals terminals 2 and each input terminal under operating conditions Terminal current short circuit Approx 6 mA between each terminal under operating conditions Allowable contact resistance dry contact ON 250 max under operating conditions OFF 100 kQ min under operating conditions Voltage drop at open collector ON 2 V ma
7. General Electric Data Gold iron chromel Hayashidenko Data e Resistance temperature detector RTD Input type Input range FS Accuracy under standard conditions Symbol Code Range No C ce JIS 89Pt100 F50 64 200 0 to 500 0 300 0 to 900 0 0 1 FS IEC Pt100 O F46 65 200 0 to 200 0 300 0 to 400 0 0 1 FS F32 66 100 0 to 150 0 150 0 to 300 0 0 1 FS F36 67 50 0 to 200 0 50 0 to 400 0 0 1 FS F33 68 40 0 to 60 0 40 0 to 140 0 0 15 FS F01 69 0 0 to 100 0 0 0 to 200 0 0 15 FS F03 70 0 0 to 300 0 0 0 to 500 0 0 1 FS F05 71 0 0 to 500 0 0 0 to 900 0 0 1 FS JIS 89JPt100 P50 96 200 0 to 500 0 300 0 to 900 0 0 1 FS P46 97 200 0 to 200 0 300 0 to 400 0 0 1 FS P32 98 100 0 to 150 0 150 0 to 300 0 0 1 FS P36 99 50 0 to 200 0 50 0 to 400 0 0 1 FS P33 100 40 0 to 60 0 40 0 to 140 0 0 15 FS PO1 101 0 0 to 100 0 0 0 to 200 0 0 15 FS P03 102 0 0 to 300 0 0 0 to 500 0 0 1 FS P05 103 0 0 to 500 0 0 0 to 900 0 0 1 FS Resistance temperature detector RTD Pt100 JPt100 JIS C 1604 1989 DC current DC voltage Input type Input range FS Accuracy under standard conditions Symbol Code Range No mA linear co1 48 4to 20 mA Programmable range 0 1 FS Z51 52 2 4to 20 mA_ 19999 to 20000 0 1 FS mV linear M0
8. No PID sets output limiter sets Event configuration 2 Thermocouple RTD DC current and DC voltage Events PV start PID parameter can be selected on models not supporting CP G Soak Cycle Setup Models supporting CP become Oz sensors PV shift Pattern link Constant value operation Repeat Specifications Program Number of programs 49 programs x 2 channels Number of segments 99 per program total 2000 Segment setting system RAMP X Set by set points SP and time RAMP T Set by set points SP and ramp 8 RAMP E Set by set points SP and ASP per external switch input 1 pulse Segment time 0 to 500 hours 0 minute O to 500 minutes 0 second 0 0 to 3000 0 seconds time unit selectable Segment ramp 1 to 10000 U hour 1 to 10000 U minute 1 to 10000 U second time unit selectable Segment ASP 1 to 10000 U 1 pulse Number of sub 4000 functions Sub function action Events PID set output limiter set G Soak PV shift repeat Events 16 Set operating point corresponding to event type PID set No Set 0 continuation of previous segment 1 to 9 Aset automatically switched and ON OFF control Output limiter set Set 0 continuation of previous segment 1 to 9 G Soak Set type start end points and overall and G Soak width O to 1000 U PV shift 10000 to 10000 U Repeat Set return destination segment No and repeat count PV start Set type rising
9. falling or both for each program Cycle Set cycle count for each program Pattern link Set program No 0 to 49 0 no link for each program Tag Set 8 alphanumerics or symbols for each program Basic time accuracy 0 01 segment time setting 0 with 0 1 second delay for each repeat and cycle Inputs Input type Thermocouple resistance temperature detector RTD DC voltage DC current multi range See pages 6 7 Sampling cycle 0 1 seconds Input bias current Thermocouple DC voltage input Max 1 3 yA at peak value and reference conditions 1 V or higher range Max 3 yA Input impedance DC current input approx 50 Q under operating conditions Measuring current RTD input Approx 1 mA current flow from terminal A under operating conditions Influence of wiring resistance Thermocouple DC voltage input Thermocouple 0 5 wV Q DC voltage max 1 V range 0 5 wV O DC voltage 5 V range 3 pV Q DC voltage 10 V range 6 yV Q RTD input Max 0 01 FS Q in wiring resistance range 0 to 10 Q Range of F01 F33 P01 and P33 0 02 FS Q max RTD input allowable wiring resistance Ranges other than F01 F33 P01 and P33 85 Q max Ranges of F01 F33 PO1 and P33 10 Q max Allowable parallel resistance Thermocouple disconnection detection allowable parallel resistance 1 MQ min Max allowable input Thermocouple DC voltage input 5 to 15V DC DC current input 50 mA DC 2
10. 1 49 0 to 10 mV i positon can be i aaeses L02 50 10 to 10 mV 0 1 FS 51 O to 100 mV 0 15 FS mA linear c01 128 4 to 20 mA Programmable range 0 15 FS Z51 134 2 4to 20 mA_ 19999 to 20000 0 1 FS V linear 129 Oto1V ear i position canbe ag Agere 130 1to 1V 0 1 FS vol 131 1to5V 0 1 FS 132 Oto5V 0 1 FS 133 Oto10V 0 1 FS O sensor 135 0 to 1250 mV 0 1 FS When converted to mV value Carbon potential CP value indication range 0 000 to 4 000 C Note that PID control is calculated in input range 0 000 to 2 000 C O partial pressure PO indication range 0 000 to 1 500 x 10 atm e Any O sensor made by Japan Glass Co Ltd Marathon Monitors Cambridge Corning AACC Advanced Atmosphere Control Corpora tion Barber Colman and Furnace Control can be used e PV2 is fixed for the O sensor in the case of models supporting carbon potential C Handling Precautions The unit of code Z06 is Kelvin K The PV lower limit alarm does not occur with codes F50 and P50 The number of digits past the decimal point for DC current and DC voltage is programmable within the range 0 to 4 The PV upper limit alarm is output by the O sensor when the voltage exceeds 1375 mV The PV lower limit alarm however is not output Model selection guide External dimensions 144 PROG SEG 8 8 8 8 B2
11. 240 seconds variable Event outputs Open collector output External supply voltage 12 to 24V DC Max load current 70 mA load Max common current 500 mA OFF leakage current 0 1 mA max ON residual voltage 2 V max Event types PV type PV deviation w deviation standby absolute value deviation w absolute value deviation standby PV rate of change SP MV G Soak absolute value deviation w G Soak absolute value deviation standby PV1 constant operation PV2 constant operation Time type Time events RAMP E time monitor segment time program time Code type Code event code event w timer program No binary code segment No binary code program No BCD code segment No BCD code Mode type Unique segment RUN HOLD END FAST HOLD READY READY FAST END G Soak standby MANUAL AT executing FAST READY FAST console operation in progress RUN advance all alarms PV range alarm controller alarm O sensor error low battery voltage Event hysteresis In case of PV type set 0 to 1000 U Event ON delay 0 0 to 3000 0 can be set to four events Communications RS 485 Network Multidrop This controller is provided with only slave instrument functionality except when connected to ST221 dedicated display device 1 to 16 units max DIM 1 to 31 units max CMA SCM Data flow Half duplex Synchronization Start stop synchronization Transmission Balanced differential
12. 52B 8 1 SD RD SG Master instrument terminal type connection 4 5 6 8 20 1 RS 485 5 wire type Slave instrument Slave instrument DCP552B DCP552B x Attach a terminator 1 2 W or more 150 Q to both ends of the communications path meu SDA SDB RDA RDB SG RS 232C Note 1 In the case of a modem type connected master instrument connect terminals 2 and 61 and 3 and 63 in reverse to the above figure 2 The RS 232C terminals 4 5 and 6 8 20 on the computer must be short circuited as shown in the figure on the left 3 In the case of a computer whose RS 232C terminals 1 and 7 are for the same signal do not connect the leads as shown in the above figure Also do not connect the sleeve marked FG to any terminal at all 11 E Wiring precautions 1 Isolating inputs and outputs inside the controller Solid lines show isolated items Dotted lines show non isolated items PV input CH1 i Control output CH1 PV input CH2 Auxiliary output CH1 Loader communications pe Control output CH2 oo External switch input Auxiliary output CH2 Communications Event output 2 Noise countermeasures for Instrument power supplies 1 Reducing noise Connect the DCP552B to a single phase power supply for instruments and take measures to prevent the influence of electrical noise Instrumen
13. 88A PROFILE RUN AT HLD S 2 BAT 8888A MESSAGE MAN EGI meL Z S Jee A aen PROG RUNHOLD DISP FESET MESSAGE AM PID PARA CLR FUNC AT SETUP ENTER i cD LOAD LAE SAVE Panel cutout 138 9 185 l I IV V VI Example DCP552B20100 l II Ili IV v VI Specifications Basic Number Carbon Option Additions model No of potential PV inputs DCP552 Digital Programmable Controller 2 loop model B Mark II 2 PV input CH2 0 None 1 Available 0 None 1 Auxiliary output CH1 2 Auxiliary output CH2 communications 00 None DO Inspection certificate Yo Complying with the traceability certification 138 9 T450 min Unit mm 3 A A T Qe 24f g g Q A O O o m el O S Ol 6j a L T Unit mm Wiring External switches Operation mode selection by external switch input Event outputs 16 SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 e e e EV1 Ev2 EV3 EV4 EV5 EV6 se HOLD gt a lt b sso RESET ae Load
14. No CP SS 1853E Specification DCP552B Mark Il DIGITRONIK Programmable Controller Overview The DIGITRONIK DCP552B Mark II is a high function programmable controller supporting two channels up to 49 program patterns per channel to which thermocouple resistance temperature detector RTD DC voltage DC current and other signals can be input The DCP552 Mark II supports 16 event outputs 16 external switch inputs and a wide range of other functions as part of the standard specification Features e Accuracy of 0 1 FS Easy to view large display characters Compact design e Any input type can be selected by console key operation e Easy operation aided by guidance messages e 16 external switch inputs allow the control of remote Up to 49 program patterns can be stored to each channel selection of program Nos or operation on each channel and up to 99 segments can be programmed to each separately or both channels simultaneously pattern e CE marking compatible e Any event can be selected to each channel and set for Applicable standards EN61010 1 EN61326 the 16 event outputs and code events comprising a combination of two or more points can be set Basic function blocks of DCP552B Mark II Control operation block Thermocouple Root extraction Output 1 Resistance temperature Linearization table Output change limiter Current proportional detector RTD ap
15. d operation Profile display 7 orange LEDs Displays program pattern rise soak and fall trends Status displays 22 round LEDs Modes RUN HLD MAN PRG green Display details PV SP OUT TM CYC SYN DEV green EG1 EG2 red Battery voltage BAT red blinks at low voltage Status AT green Operation keys 18 rubber keys Loader connector port 1 dedicated cable with stereo miniplugs Modes Program operation modes READY Ready to run program control stop program No selectable RUN Program run HOLD Program hold FAST Program fast forward END Program end READY FAST Ready to run and fast forward program AUTO Automatic operation MANUAL Manual operation output can be controlled on console Constant value operation modes READY Ready to run program control stop RUN Program run AUTO Automatic operation MANUAL Manual operation output can be controlled on console Controller PID controls Proportional band P 0 0 to 1000 0 0 0 ON OFF control Reset time I 0 to 3600 seconds 0 seconds PD control Rate time D 0 to 1200 seconds 0 seconds PI control MV limit Lower limit 5 0 to upper limit Upper limit Lower limit to 105 0 Manual reset 0 0 to 100 0 Controller PID controls Number of PID sets 16 sets for program operation 9 segment unique sets 7 sets for automatic zone selection PID
16. et 2 p ces User s manual CP UM 5017E 1 Lithium battery set 81446140 001 Approx 200 g Terminal cover 81446176 001 1 Table 1 Input types and ranges selectable in setup Thermocouple Input type Input range FS Accuracy under standard conditions Symbol Code Range No c or K CA K46 16 200 0 to 200 0 300 0 to 400 0 0 1 FS K CA K09 0 0 0 to 1200 0 0 to 2400 0 1 FS K CA KO8 1 0 0 to 800 0 0 to 1600 0 1 FS K CA K04 2 0 0 to 400 0 0 to 750 0 1 FS E CRC E08 3 0 0 to 800 0 0 to 1800 0 1 FS J IC J08 4 0 0 to 800 0 0 0 to 1600 0 1 FS T CC T44 5 200 0 to 300 0 300 to 700 0 1 FS 0 3 FS between 200 C to 45 C B PR30 6 B18 6 0 0 to 1800 0 0 to 3300 0 1 FS 4 0 FS between 0 to 260 C 0 15 FS between 260 to 800 C R PR13 R16 7 0 0 to 1600 0 0 to 3100 0 1 FS S PR10 S16 8 0 0 to 1600 0 0 to 3100 0 1 FS W WRe5 26 W23 9 0 0 to 2300 0 0 to 4200 0 1 FS W WRe5 26 W14 10 0 0 to 1400 0 0 to 2552 0 1 FS PR40 20 D19 11 0 0 to 1900 0 0 to 3400 0 2 FS 0 9 FS between 0 to 300 C 0 5 FS between 300 to 800 C N U13 12 0 0 to 1300 0 32 to 2372 0 1 FS PLII Y13 13 0 0 to 1300 0 32 to 2372 0 1 FS Ni Ni Mo Z13 14 0 0 to 1300 0 32 to 2372 0 1 FS Golden iron Z06 15 0 0 to 300 0 K K Kelvin 0 4 FS chromel Thermocouple K E J T B R S JIS C 1602 1981 WRe5 26 Hoskins Data PR40 20 Johnson Matthey Data N N B S Monograph 161 PLII Engelhard Industries Data IPTS68 Ni NiMo
17. le occurs Pay attention to this when providing a varister on a controller Recommended varister Azbil Corporation Model No 81446366 001 for 100V AC 81446367 001 for 200V AC 4 Ground Use only the FG terminal or on the DCP552B for grounding Do not ground across other terminals When it is difficult to ground shielded cable prepare a separate GND terminal plate earth bar Ground type 100 Q max Ground cable 2 mm min annealed copper wire AWG14 Cable length Max 20 m Shielded GND Dre E GND terminal plate GND 100 Q min earth bar DCP552 5 Precautions during wiring 1 After providing anti noise measures do not bundle primary and secondary power leads together or pass them through the same piping or wiring duct 2 Maintain a distance of at least 50 cm between I O signal leads or communications leads and the power lead Also do not pass these leads through the same piping or wiring duct 6 Inspection after wiring After wiring is completed be sure to inspect and check the wiring state Wrong wiring may cause controller malfunction or accidents azbil 1st Edition Issued in May 2008 3rd Edition Issued in Dec 2013 No part of this publication may be reproduced or duplicated without the prior written permission of Azbil Corporation
18. proximation Upper lower limiter Voltage time proportional DC current Input bias Open collector time proportional DC volta Filter Output 2 Output change limiter Current proportional Thermocouple Root extraction Upper lower limiter Voltage time proportional Resistance temperature Linearization table Open collector time proportional detector RTD approximation 4 FIER Input bias 16 event outputs voltage Filter as Time event Modes O2 sensor Mode transition lt PV Alarm m SP Segment No code 12 external switch inputs Z PID control Deviation Unique segments RUN Program No Auto tuning MV Program No code HOLD CH1 operation cancel Code PV rate of change RESET CH2 operation cancel Direct reverse action Code w timer O2 sensor error ADV ON OFF control 1 2 auxiliary outputs 4 external switch inputs SP limit FAST G Soak cancel SP bias RAMP E Direct reverse action AUTO MANUAL Autoload AT Oz sensor check Key operation RS 485 RS 232C communications VO Display selection FAST Display channel AUTO MANUAL salen aii AT e Loader communications 1 0 Program No Program setup RUN HOLD Parameter setup RESET Memory card ADV operation PV SP Deviation MV Program Parameter 2 channels x 49 patterns x 99 segments Variable parameters 1 Option according to model
19. set selection Segment designation automatic zone selection can be switched by program operation MV change 0 1 to 110 0 0 1 seconds Auto tuning Automatic setting of PID value by limit cycle system ON OFF control differential 0 to 1000 U Direct reverse action switching Possible Outputs Auxiliary output Output types SP1 PV1 deviation 1 MV1 SP2 PV2 deviation 2 O sensor mV value Scaling Possible Current output 5G CH1 CH2 auxiliary outputs CH1 CH2 Output current 4 to 20 mA DC Allowable load resistance 600 Q max under operating conditions Output accuracy 0 1 FS max under standard conditions Output resolution 1 10000 Max output current 21 6 mA DC Min output current 2 4 mA DC Output updating cycle 0 1 seconds Open terminal voltage 25 V max Voltage output 6D CH1 CH2 Allowable load resistance 600 Q max under operating conditions Load current adjustment 2 to 22 mA variable Variable open terminal voltage 25 V max OFF leakage current 100 pA max Output response time At ON OFF 600 load 0 5 ms max At OFF ON 600 load 0 5 ms max Output resolution 1 1000 Time proportional cycle 1 to 240 seconds variable Open collector output 8D CH1 CH2 External supply voltage 12 to 24V DC Max load current 100 mA load OFF leakage current 0 1 mA max ON residual voltage 2 V max Output resolution 1 1000 Time proportional cycle 1 to
20. t power supply Noise filter 100 to 240V AC 2 When there is a lot of noise If there is a lot of electrical noise we recommend inserting an insulating transformer in the power circuit and using a line filter Insulating Line filter transformer Azbil Corporation Instrument 100 100 V Model No 81446364 001 power supply 200 200 V 100 to 240V AC gt aie fe cxf 4 ore Other circuit GND GND 3 Noise generating sources and countermeasures Generally the following generate electrical noise Relays and contacts electromagnetic coils solenoid valves power lines in particular 90V AC min induction loads inverters motor commutators phase angle control SCR radio communications equipment welding equipment high voltage ignition equipment Please read the Terms and Conditions from the following URL before ordering or use http www azbil com products bi order html Specifications are subject to change without notice Azbil Corporation Advanced Automation Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 Japan URL http www azbil com 12 10 1 Fast rising noise CR filters are effective in countering fast rising noise Recommended CR filter Azbil Corporation Model No 81446365 001 2 Noise with a high wave height Varisters are effective in countering noise with a high wave height However note that the varister may become short circuited when troub
21. x under operating conditions Leakage current at open collector OFF 0 1 mA max under operating conditions Parallel connection with other instruments Can be connected to Azbil Corporation SDC40 and SDC10 series Assignments fixed RUN HOLD RESET ADV program No CH1 operation cancel CH2 operation cancel Assignments variable RAMP E FAST AT AUTO MANUAL G Soak cancel auto load O sensor check Input sampling cycle 0 1 seconds ON detection min hold time 0 2 seconds 0 4 seconds for program No Indication programmer Upper display Green 5 digit 7 segment LED This displays PV values in the basic display state Item codes are displayed in the parameter setup Lower display Orange 5 digit 7 segment LED This displays SP and output in the basic display state Setting values are displayed in the parameter setup Program No display Green 2 digit 7 segment LED This displays program No in the basic display state Segment No display Green 2 digit 7 segment LED This displays segment No in the basic display state Item Nos are displayed in parameter setup and alarm No is displayed when alarm occurs Message display This displays output graph deviation graph event state and tags in the basic display state This displays reference messages in the parameter setup and program setup This displays operation details and operation results of memory car