Home

FUS1 Controler

image

Contents

1. Gasket Unit mm Panel thickness 1 to 8 mm wdalalBlc io lElrl ea n PXWS 52 5 100 590 5 114 5 45 0 9 92 PXW7 765 785 67 91 68 68 0 PXWe 1005 100 5 90 5 114 5 92 0 2 92 120min 92min 96min 116min 120min 140min m Panel cutout size when installing n number of units heH n INSTALLATION NEMA 4X Integrity The front side of this instrument conforms to NEMA 4X To ensure the waterproofness between the instrument and the panel use the gasket that is provided with the unit according to the installation procedure described below How to install the unit For PXW 5 7 9 install the two metal brackets one on the top and the other on the bottom and tighten the screws to a torque of about 14 7N cm 1 5kg cm For PXWA install the unit in the panel as shown below and tighten the screws on the mounting bracket until the unit is secure Make sure there is no space between the front side of the unit and the gasket and between the gasket and the panel Figure 1 Unit Figure 2 Unit Po I Front Gasket Case Panel Panel Mounting bracket Screw Caution After the mounting bracket is installed check the gasket for displacement and detachment as shown in Figure 3 Gasket Figure 3 Gasket Case Case Bad Good WIRING
2. Autotune Point Process Variable 100 ON jOFF ON OFF ON Time Output 096 Time I Autotune Period gt The controller then reads the reaction of these test signals on the process Keep in mind that every process is different and therefore every reaction to the test signals is different This is why PID parame ters are not the same for all processes The amplitude L or lag time which is the overshoot and undershoot of the system when autotun ing and the time constant T which is the time the process takes to go through one On Off cycle are measured See diagram below lt Time Constant Overshoot Amplitude Undershoot gt The measurements are then used with the Autotune algorithm for cal culation of the proper PID parameters for the system as shown below where K is the proportionality constant and S is the Laplace operator APPENDIX B Manual Tuning Tune the controller if any of the following occurs The controller is installed in a new system The controller is used as a replacement in an existing system e The input sensor is relocated or changed The output device is relocated or changed The setpoint is significantly changed Any other condition that will alter the dynamics of the system Proportional Band The proportional band is a band around the setpoint of the PXW where the output is between 0 and 100 The percentage of output is pro p
3. Indicator 4 digit 7 segment LED green SELF DIAGNOSIS Method Program error is monitored with a watchdog timer PROTECTION FROM POWER FAILURE Memory protection Non volatile memory Parameter values remain unchanged with disruption of power Ramp soak function has to be re initiated OPERATING AND STORAGE CONDITIONS Operating temperature 10 to 50 C 14 to 122 F Operating humidity 90 RH or less non condensing Storage temperature 20 to 60 C 4 to 140 F nstallation category Pollution degree 2 GENERAL SPECIFICATIONS Rated voltage 85 264V AC or 24V AC DC Power consumption 5VA or less 100V AC 8VA or less 240V AC nsulation resistance 20MQ or more 500V DC Withstand voltage Power source Earth 1500V AC 1 min Power source input terminal 1500V AC 1 min Earth relay output 1500V AC 1 min Earth Alarm output 1500V AC 1 min Between other terminals 500V AC 1 min Input impedance Thermocouple 1MQ or more Voltage 450KQ or more Current 250Q external resistor Allowable signal source resistance Thermocouple 100Q or less Voltage 1KQ or less Allowable wiring resistance RTD 10Q or less per wire Reference junction compensation accuracy 1 C at 23 C Process variable offset 10 FS Setpoint variable offset x 5096 FS nput filter
4. Deadband Overlap X Input Range nN e e E Deadband Overlap The Deadband Overlap is that per centage of the heating side of the proportional band where the heating output 1 and the cooling output 2 outputs are separated by a Deadband or where they Overlap on a heat cool controller A value greater than zero establishes a Deadband area where neither the heating nor cooling outputs are energized for more powerful heating and cooling loads A value less than zero establishes an Overlap area where both the heat 13 P n2 Deadband Overlap of units in the Proportional Band for Heating Prop Band for Heating X Input Range 100 of units in the Proportional Band for Cooling Prop Band for Cooling X Input Range 100 of units in the Deadband Overlap X Input Range peadband Overlap 100 Input Range P S minus P 5 100 _Heating Side Coolng Side output P 0 2 TEMP Setpoint 100 Heating Side Coolng Side OUTPUT 0 Deadband TEMP Setpoint Heating Side Coolng Side 100 OUTPUT 0 Overlap TEMP Setpoint ing and cooling outputs are energized at the same time for less powerful heating and cooling loads Enter a value based on the power of your heating and cool ing loads as well as the application s efficiency in maintaining tight heat cool control Setting range 50 0 to 50 0 of the heating proportion al band Not indicated with
5. Input Range Example 3 QI V X 100 100 C Proportional Band as a percentage Proportional Band Range X 1000 C 100 Example 0j 30 C X 1000 C 10096 Integral Time With the proportional band alone the process tends to reach equilib rium at some point away from the main setpoint This offset is due to the difference between the output needed to maintain setpoint and the output of the proportional band at setpoint SInce the proportional band is equidistant from the main setpoint the output is around 5096 If anything more or less than 50 output is required to maintain set point an offset error will occur Integral action eliminates this offset See the diagrams below Integral action eliminates offset by adding to or subtracting from the output of the proportional action alone This increase or decrease in output corrects for offset error within the proportional band in estab lishing steady state performance at setpoint It is not intended to cor rect for process disturbances See the following diagram Main Setpoint 100 N Output N 0 PV Integral Time is the speed at which the controller corrects for offset A short integral time means the controller corrects for offset quickly If the integral time is too short the controller would react before the effects of previous output shifts due to lead or lag time could be sensed causing oscillation A long Integral time means the control corrects for offs
6. 0 cece eee eee 21 Appendix D Heat Cool Option 0 c cece eee eee ee 22 QUICK Referent eoi obe EE EME E ne aes e v YT se 24 Free Technical Support 1 800 884 4967 U S amp CANADA 802 863 0085 INT L 802 863 1193 Fax 8 30 A M 6 00 P M E S T V298 8 INTRODUCTION Thank you for purchasing the Fuji Electric temperature process controller All of these controllers are PID Autotune controllers that employ Fuji Electric s patented fuzzy logic algorithms It is a fully programmable temperature process controller incor porating many user friendly features The following easy to use instructions are intended to help you understand set up effectively operate and achieve optimal performance from your controller When programmed and operated within the guidelines set up for them in this manual your controller will give you years of precise reliable control If needed we will provide free technical support throughout the life of the controller The first section of this manual details the specifications and general description for the PXV3 controller The second section will cover the PXW controller followed by a detailed description of the programming parameters which are common to both the controllers Several appendices describe some of the controlling techniques Finally a Quick Reference guide gives a listing of all the parameters and their default values FEATURES Fuzzy Logic Control PID Auto
7. Add Integral Time Start with a large Integral Time value which gives very sluggish response to process offset and tighten by decreasing the value in half Analyze the process variable If the response to process offset is still sluggish tighten by decreasing the value in half again Continue with the same procedure until the process starts to oscillate at a con stant rate Increase the Integral Time value by 5096 or multiply the setting 1 5 times From a cold start test and verify that the Integral Time allows maximum elimination of offset with minimum overshoot If not completely satisfied fine tune the value up or down as needed and test until correct The Integral Time is now tuned Add Derivative Time Do not add Derivative Time if the system is too dynamic Start with a small Derivative Time value which gives sluggish response to process upsets and double the value Analyze the process variable If the response to process upsets is still sluggish double the value again Continue with the same procedure until the process starts to oscillate at a quick constant rate Decrease the Derivative Time value by 25 From a cold start test and verify that the Derivative Time value allows maximum response to process disturbances with minimum overshoot If not completely satisfied fine tune the value up or down as needed and test until correct Note that the Derivative Time value is usually somewhere around 25 of the Integral Time value The d
8. Default DSP settings settings dSP6 2 dSP6 4 Description Default DSP settings settings Parameter Range Description P n1 0 19 Control Action code P dF 0 0 900 0sec Input Filter Constant roFF rHLd roFF rrUn rHLd Ramp soak command roFF dSP1 1 AH 0 100 FS High Alarm Setpoint dSP1 2 AL 0 100 FS Low Alarm Setpoint dSP1 4 Hb 0 0 50 0A Heater break alarm S P dSP1 8 AT 0 2 Auto tuning dSP1 16 LoC 0 2 Lock out dSP1 32 Secondary Menu P 0 0 999 9 FS Proportional band dSP1 128 0 3200sec Integral time dSP2 1 D 0 0 999 9sec Derivative time dSP2 2 TC 1 150sec Cycle Time output 1 dSP2 4 HYS 0 50 FS Hysteresis dSP2 8 TC2 1 150sec Cycle Time output 2 dSP2 16 CooL 0 0 100 0 Proportional band 1 0 coefficient for cooling dSP2 32 db 50 0 50 0 FS Deadband Overlap 0 0 dSP2 64 0 100 Balance 0 0 50 0 dSP2 128 Ar 0 100 FS Anti reset wind up 100 FS dSP3 1 P n2 0 16 Input type code t dSP3 2 P SL 1999 9999 Lower range of input O FS dSP3 4 P SU 1999 9999 Upper range of input 100 FS dSP3 8 P dP 0 2 Decimal point position 0 dSP3 16 P AH 0 11 Alarm Type 1 code 5 dSP3 32 P AL 0 15 Alarm Type 2 code
9. HB status indicator is lit This is the maximum current usage of the heater Using the same proce dure find the maximum current usage of the heater minus one zone Set the setpoint in Power Supply between the 99 two current readings In this way the opera tor knows if one or more zones fail because the current sensed will only be below the Heater Break Alarm setting if one or more Current Sensing Transformer zones fail gt Ona iN Alarm Output Main tput ppn 4 Input Sensor APPENDIX D Heat Cool Option With the Heat Cool Option the PXW can control a temperature applica tion with one input at one main setpoint using two outputs a heating output and a cooling output By using a heating and cooling output a process is able to quickly bring the temperature to setpoint in both directions and to limit the amount of overshoot The larger the deviation from setpoint the more output applied to the system on both the heat ing and cooling sides Heat Cool control is a very effective way of con trolling exothermic processes processes that generate their own heat or processes where ambient temperature is not adequate or fast enough in returning a process back to setpoint The two outputs on the PXW are independent and sent to two different output devices The PXW can be equipped with two of the same or two different output types Outpu
10. acting If using two outputs in a heat cool type control please refer to Appendix D for more details Relay Connecting a load to full capacity of the relay will shorten the relay life especially if itis operated at a rapid rate To protect the output relay an external relay or a contactor should be used If a higher current rating is required a solid state relay driver type output is recommended Connect the load between the normally opened contacts of the relay This way if power to the controller is disrupted the output cir cuit would open preventing the load from running out of control Set the proportional time cycle parameter TC to 30 secs or more Use of Z trap manufacturer Fuji Electric Co is recommended to protect the relay against switching surges and to ensure the prod uct s long life Connect it between the contacts of the relay as shown in the example below Part No ENC241D 05A power supply voltage 100V ENC471D 05A power supply voltage 200V PXWA4 PXW9 PXV3 8 pin 5 6 456789 7 4loooooo 545 aL cege Hel SSR SSC Driver Pulsed DC Voltage The non isolated DC output is used to drive an external load han dling device such as Solid State Relay SSR or Solid State Contactor SSC The total current drawn for both single and dual outputs should be within the allowed value Make sure th
11. and process variable PV and setpoint variable SV will be displayed PV is the variable that is being controlled and it is not programmable When setting the parameters turn off the power to the load operating equipment to ensure safety Since it takes 30 minutes for the unit to stabilize in terms of temperature all measure ments should be carried out at least 30 minutes after the power is turned on Option related features are displayed only when the options are used Viewing and Setting Parameters The data is automatically registered in 3 seconds after the setting It can also be registered by pressing the SEL key How to set Setpoint value SV Operation Display 1 Power on Operational mode 2 Press UP or DOWN key SV value changes accordingly PRIMARY SETPOINT MENU Operation Display 1 Operational mode PV SV 2 Press SEL key for 3 seconds H LED blinks AH data for units with alarm option AH data changes L LED blinks 3 Press UP or DOWN key 4 Press SEL key to access the next parameter 5 Press SEL key for 3 secs SECONDARY SYSTEM MENU Operation Display Operational mode PV SV 2 Press SEL key for 7 seconds 3 seconds later H LED blinks 7 seconds later P Operational mode 3 Release and press SEL key again P data 4 Press UP or DOWN key P data changes accordingly 5 Press SEL key once p 6 Press DOWN key to scroll d
12. INSTRUCTIONS A Warning Be sure to use the rated power supply voltage and polarity viewing from the back PXW4 socket type standard aft instf ment e pac Current output SSR SSC driving output 1 j output i Voltage current 8 pas Power supply T DE iS T Thermocouple input When no alarms are provided PXW4 socket type with alarm viewing from the back of instrument Current output SSR SSC driving output Contact output Alarm output Voltage s current EM 1 Power supply Ts A T RTD Thermocouple input When alarms are provided For current input install the 250Q precision 2500 resistor accessory before using the unit 3 PXW7 RTD Voltage A Current 010 Current output 9 SSR SSC driving output Alarm 1 Upper limit alarm TC Control output 1 l E Lomo lint alarm ma e 8 Heater break OH Zo alarm output 9 Common I CT input cem Ye els Power supply j Control output 2 on the cooling side Current output SSR SSC driving output PXW5 PXW9 Voltage Current Current output SSR SSC input RTD T C driving output 9 B lt Control output 2 co ga E on the cooling side Current output B 0p SSR SSC driving output ro o Alarm 1 upper limit alarm leo Alarm 2 lower limit a
13. If the derivative time is too short the controller would not react quickly to process disturbances A long derivative time means more derivative action If the derivative time is too large the con troller would react too dramatically to process disturbances creating rapid process oscillation A process which is very dynamic such as pressure and flow applications is more efficiently controlled if the derivative action is turned off because of the oscillation problem which would result Tuning Tuning as with any PID loop requires tuning each parameter sepa rately and in sequence To achieve good PID control manually you can use the trial and error method explained below Tune the Proportional Band Set Integral Time 0 off Set Derivative Time 0 off Start with a large Proportional Band value which gives very sluggish control with noticeable offset and tighten by decreasing the value in half Analyze the process variable If the control is still sluggish tight en by decreasing the value in half again Continue with the same pro cedure until the process starts to oscillate at a constant rate Widen the Proportional Band by 5096 or multiply the setting 1 5 times From a cold start test and verify that the Proportional Band allows maximum rise to setpoint while maintaining minimum overshoot and offset If not completely satisfied fine tune the value up or down as needed and test until correct The Proportional Band is now tuned
14. Operation 1 Power on 2 Press SEL key 3 Press UP or DOWN key 4 Press SEL key to go back to the operational mode Display Process value PV SV value SV lamp is lit SV value changes accordingly Process value PV SV lamp off PRIMARY SETPOINT MENU Operation 1 Operational Mode 2 Press SEL key for 3 seconds Display Process value PV ALM LED blinks AH data for units with alarm option 3 Press UP or DOWN key AH data changes 4 Press SEL key to access the AT 0 next parameter 5 Press SEL key for 3 secs Operational mode SECONDARY SYSTEM MENU Operation 1 Operational Mode 2 Press SEL key for 7 seconds Display Process value 3 seconds later ALM LED blinks 7 seconds later P 3 Release and press SEL key again P data 4 Press UP or DOWN key P data changes accordingly 5 Press SEL key once p 6 Press DOWN key to scroll down i d Mod the menu 7 Press SEL key for 3 secs Operational mode FACTORY PRESET MENU Operation 1 Operational Mode 2 Press SEL key for 9 seconds Display Process value 3 seconds later ALM LED blinks 7 seconds later P 9 seconds later P n1 3 Release and press SEL key again P n1 data 4 Press UP or DOWN key P n1 data changed 5 Press SEL key P n1 6 Press DOWN key to scroll down P dF dsp7 the menu 7 Press SEL key for 3 se
15. Stand by mode Stand by mode No Yes 1 Power on Start 2 Output on END 3 Output on OFF 4 Repeat function Stand by mode Going on Control FACTORY Pat Pent Stand by mode Stand by mode Yes Program starts from the current PV value Output condition at the end of the program rEnd Output condition when program is terminated roFF Ramp soak program operates repeatedly If the repeat function is off the SV value on the last step is maintained Output 3 Alarm off When program ends rEnd control is at the SV value on the last step When program is terminated roFF control is at the main SV value PRESET MENU Control Action amp Sensor Burn out Protection The Control Action is the direction of the output relative to the process variable The controller can be pro grammed for either reverse or direct control action In a reverse acting controller the output decreases as the process variable increases A heating application would require reverse acting control In a direct acting controller the output increases as the process vari able increases A cooling application would require direct acting control Enter the code from the Table of Output Type Codes which establishes either a reverse or direct control action The Sensor Burn out Protection is the intended direc tion of the output in the event of a thermocouple or RTD sensor break or a break in the analog input The controller can b
16. Time a gt Neg memory Autotuning will also automatically set anti essary to eliminate overshoot without over damping reset wind up Ar There are two types of Autotuning the process resulting in process oscillation that can be performed by the controller Autotuning at Setting Range 0 0 to 999 9 secs main setpoint or Autotuning at 10 of full scale below main setpoint The latter may yield slightly different val ues not as precise but the process overshoot encoun tered during the autotuning procedure would not be as Genet etpoint much Enter the value for the type of autotuning you TEMP would like to run on your particular application based on overshoot tolerances and the precision of the PID parameters needed For more information on principles S ES iin of Autotuning refer to Appendix A elon Derivative 0 Autotuning off Action 1 Autotuning performed at setpoint TIME 2 Autotuning performed at 10 of ES below setpoint TL TC Cycle Time Output 1 The Cycle Time for output 1 is Standard type AT 1 Low PV type AT 2 that time cde output is on for a percentage of TUS ae Sencha ee that time and off for a percentage of that time creating V ATinoperationV V AT in operation a proportioning effect The Cycle Time is only used Set value SV bl L ids when P PI PD or PID control action is used and when rare id FM MET ONU the output is time proportional as with the relay or SSR he d i D pv Measured vate driver outputs T
17. band x Cooling proportional band coefficient ooling proportional band coefficient 0 100 ntegral time 3200 sec for heating and cooling Differential time C 0 2 position action 0 0 999 9 sec for heating and cooling PI D 0 2 position action without dead band for heating and cooling D 0 Proportional action Proportional cycle 1 150 sec for relay contact output and SSR SSC drive output only Hysteresis width 2 position action for heating and cooling 0 5 FS 2 position action for cooling 0 5 FS Anti reset wind up 0 100 FS setting in 1 E U steps auto setting with auto tuning Overlap dead band 50 of heating proportional band Input sampling cycle 0 5 sec Control cycle 0 5 sec OUTPUT Relay contact output SPST 220V AC 30V DC 2A resistive load Mechanical life 10 times under no load Electrical life 10 times under the rated load SSR driver output On 5V DC typ 5 5V 1V 20mA max Off 0 5V or less Alarm output 2nd control output SPST 220V AC 30V DC 2A resistive load Alarm Configurable from the front panel keys as Absolute Deviation Zone or Combination alarms with or without the hold feature SETTING AND INDICATION Accuracy 0 5 of FS 1 digit 1 C for thermocouple R T C 0 400 C 1 FS 1 digit 1 C B T C 0 500 C 5 FS 1 digit 1 C Setting method 3 key operation
18. control action and input type code Refer to page 12 and Appendix A for additional details The PID parameters calculated by autotuning will be retained even if the power is lost However if the power is turned off during the auto tuning process you must restart Autotuning To abort the autotune procedure set AT to 0 Auto tuning has to be repeated if there is a significant change in SV P SL or P SU or in the controlled process Autotuning can also be performed while fuzzy control is selected PRIMARY SETPOINT MENU PARAMETER DESCRIPTION roFF rhLd Ramp Soak Command The Ramp Soak program auto matically changes the setpoint value with time according to a preset pattern Setting roFF Normal operation is performed rrUn Ramp Soak operation is performed rhLd Ramp Soak operation is suspended rEnd indicates that the operation is terminated High Alarm Setpoint The High Alarm Setpoint is that point of the process above which the high alarm out put relay is energized If the alarm type programmed in the secondary menu includes an absolute value for the High Alarm Setpoint enter the actual value you want the alarm to be activated at regardless of what the main setpoint is set for If the alarm type includes a deviation value for the High Alarm Setpoint enter the number of units above main setpoint in which you want the alarm to be activated at the deviation alarm tracks main setpoint Settable within the Input Range No
19. dSP3 64 PVOF 10 10 FS PV offset dSP3 128 SVOF 50 50 FS SV offset dSP4 1 P F C F 9 0 0 T C F selection dSP4 2 STAT Ramp soak status oFF dSP4 4 SV 1 0 100 FS 1st S P dSP4 8 TM1r 0 99hr 59min 1st ramping time dSP4 16 TM1S 0 99hr 59min 1st soaking time dSP4 32 SV 2 0 100 FS 2nd S P dSP4 64 TM2r 0 99hr 59min 2nd ramping time dSP4 128 TM2S 0 99hr 59min 2nd soaking time dSP5 1 SV 3 0 100 FS 3rd S P dSP5 2 TM3r 0 99hr 59min 3rd ramping time dSP5 4 TM3S 0 99hr 59min 3rd soaking time dSP5 8 SV 4 0 100 FS Ath S P dSP5 16 TM4r 0 99hr 59min 4th ramping time dSP5 32 TM4S 0 99hr 59min 4th soaking time dSP5 64 MOD 0 15 Ramp soak Mode code dSP5 128 24 P An 0 50 FS Alarm Hysteresis dSP6 8 rCJ N A dSP6 16 PLC1 N A dSP6 32 PHC1 N A dSP6 64 PLC2 N A dSP6 128 PHC2 N A dSP7 1 PCUT N A dSP7 2 FUZY OFF ON Fuzzy control dSP7 4 GAIN N A dSP7 8 ADJO Zero calibration dSP7 16 C ADJS Span calibration dSP7 32 N A dSP7 64 Not applicable to PXV3 t Based on the model Parameter mask
20. 0 900 0 sec setting in 0 1 sec steps primary lagging filter Noise rejection ratio Normal mode noise 50 60Hz 50dB or more Common mode noise 50 60Hz 140dB or more STRUCTURE ounting method Panel mounting Enclosure Plastic housing Protection NEMA 4X IEC IP66 front panel External terminal Pluggable terminal w screw connection External dimensions 48 W x 24 5 H x 99 D mm Weight Approx 100 g Finish color Black front panel DELIVERY Controller panel mounting bracket waterproof gasket 250Q precision resis tor when necessary instruction manual OUTER DIMENSIONS amp PANEL CUTOUT SIZE Outer Dimensions GASKET PANEL thickness imm MOUNTING BRACKET m 9 4 E g 5 9 E o amp ka o amp z 4 8 c E E a Seay 5 S d I E i 48 1 9 al 98 3 86 48 1 9 5 MOUNTING BRACKET D 3 Unit mm in Panel thickness 1 to 8 mm 0 04 to 0 31 Panel Cutout When installing n number of a SE units NEMA4X IP66 compatible 34 ormore e 40 5 45 0 M x INSTALLATION NEMA 4X Integrity The front side of this instrument conforms to NEMA 4X To ensure the waterproofness between the instrument and the panel use the gasket that is provided with the unit according to the installation procedu
21. 85 264V AC or 24V AC DC Power consumption 10VA or less 100V AC 15VA or less 240V AC Insulation resistance 50MQ or more 500V DC Withstand voltage Power source Earth 1500V AC 1 min Power source input terminal 1500V AC 1 min Earth relay output 1500V AC 1 min Earth Alarm output 1500V AC 1 min Between other terminals 500V AC 1 min Input impedance Thermocouple 1MQ or more Voltage 450KQ or more Current 250Q external resistor Allowable signal source resistance Thermocouple 100Q or less Voltage 1KQ or less Allowable wiring resistance RTD 10Q or less per wire Reference junction compensation accuracy 1 C at 23 C Process variable offset 10 FS Setpoint variable offset 50 FS Input filter 0 900 0 sec setting in 0 1 sec steps primary lagging filter Noise rejection ratio Normal mode noise 50 60Hz 50dB or more Common mode noise 50 60Hz 140dB or more POWER FAILURE PROTECTION Memory protection Non volatile memory Parameter values remain unchanged with disruption of power Ramp soak function has to be re initiated SELF CHECK Method Watchdog timer monitors program error OPERATION AND STORAGE CONDITIONS Operating temperature 10 to 50 C 14 to 122 F Operating humidity 9096 RH or less non condensing Storage temperature 20 to 60 C 4 to 140 F Installation category Pollution degr
22. C at ON 0 5V DC or less at OFF Current 60mA or less 3 4 20mA DC Allowable load resistance 600 or less OUTPUT Dual Output Control output For dual output type one of the following three ypes is selected on both heating and cooling types Not available on PXW 4 type 1 Relay contact SPDT 220V AC 30V DC 3A resistive load 2 SSR SSC drive voltage pulse 15 30V DC at ON 0 5V DC or less at OFF Current 60mA or less 3 4 20mA DC Allowable load resistance 600 or less Note When SSR SSC drive output for heating cooling side is selected the total current should be less than 60mA SETTING AND INDICATION Parameter setting method PXW digital setting with three keys PV SV display method PV SV individual LED display 4 digits each PV red SV green Status display Control output alarm output heater break alarm out put Setting accuracy 0 1 FS Indication accuracy at 23 C Thermocouple 0 5 FS 1 digit x 1 C R thermocouple 0 400 C 1 FS 1 digit 1 C B thermocouple 0 500 C 5 FS 1 digit 1 C RTD voltage current 0 5 FS 1 digit ALARM Alarm output Relay contact SPST 220V AC 30V DC 1A resistive load PXW 4 type 1 point Other types 2 points Heater break alarm output Relay contact SPST 220V AC 30V DC 1A resistive load PXW 4 type not available GENERAL SPECIFICATIONS Rated voltage
23. D input is to limit set point settings Making the input range smaller does not increase the accuracy The primary purpose of the Upper Limit of Input range when used with 1 5 0 5V DC or 4 20 0 20mA DC signal input is to scale the range so that 5V DC on a 1 5 0 5VDC signal and 20mA DC on a 4 20 0 20mA DC signal equals the high limit of the engineering unit range used The engineering unit range could be 96 PSI PH or any range which can be scaled between 1999 and 9999 units Enter a value to set Upper Limit of Input range based on the type of input used SCALING THERMOCOUPLE AND RTD Pt100 INPUT RANGES Example Program a J thermocouple for 50 to 500 F Input Type Minimum Maximum Range J Thermocouple 32 eee 1472 F Program m 5 L to 50 L 4 1 to 500 Full Range 500 50 450F 27 5 50 500 522 5 Setpoint Range 5 5 I lt gt SCALING DC CURRENT VOLTAGE INPUT RANGES Indicating Range Example Program a 4 20mA DC signal for 0 to 100 E U Input Type Minimum Maximum Range 4 20mA DC 1999 9999 Enginerring Units Program i 5 L to 0 E t to 100 Full Range 100 0 100 Engineering Units 5 0 100 105 Setpoint Range 596 gt Indicating Range P dP Decimal Point Position Resolution The Decimal Point Position is the resolution at which the controller displays the process variable and other parameter val ues The display can indic
24. FUJI ELECTRIC PXV3 PXW SERIES Operation Manual PID Autotune Controllers Featuring Fuzzy Logic TABLE OF CONTENTS l Gat i6S cenena x max eU RDDAXUUCU VUL UEUERRDip ES 2 Safety PreCautions i c c202ccedan ere e d e deve da ee eee 2 PXV3 Model Config ration 1 neck thee ehh RR 3 SpBCITICatIODS us rires scies eee see ni Res 3 Outer Dimensions and Panel Cutout Size 000 4 Installation etin eeepc eem wires 4 Wiring InSttUCtiols icio codanna reges qebeihiEREPS RR 5 Front Panel Description 0 eee cece eee eee ees 5 Front Panel Operation 2sccsiies tes eased ddae eddies 5 PXW Model Configuration cece eee eee I 6 Specifications inier necosso rre etes eb ohana 6 Outer Dimensions and Panel Cutout Size 0 8 IristallatioD utere mcnvuruxIS US VUCUREEPPPUPSS 8 Wiring Instructions i eonoceocr e re ERR AX RPEULEREPPEEES 9 Front Panel Description 0 cece eee eee tiiit 10 System Wiring Diagrams 10 Front Panel Operation sssssseseeess 11 AUEOLUTIFIQ 25e Rire te emn ed REC LR ot RARO nibus 11 Programming Primary Mem sse vest T DO PPS WWE qwe wt TNI ah 11 Secondary Menu sssssssesssseeee eene 12 Factory Preset Menu ssssessssseeeeee ee 16 Error Messages zur REPERIO EERERE RES 18 Appendix A Autotuning sls 18 Appendix B Manual Tuning 0 eee eee eee eee 19 Appendix C Heater Break Option
25. Range Remarks C F Thermocouple J 0 800 32 1472 Cold Junction K 0 1200 32 2192 compensating R 0 1600 32 2912 function built in B 0 1800 32 3272 S 0 1600 32 2912 T 199 200 328 392 T 150 400 238 752 E 199 800 328 1472 N 0 1300 32 2372 PL2 0 1300 32 2312 RTD Pt100 150 850 238 1562 Allowable wiring resistance 10 ohms max per wire DC Voltage Current 1 5V Scaling Range 1999 to 9999 For current input 0 5V use the 2500 Engineering Units resistor to obtain 4 20mA 1 5V or 0 5V DC 0 20mA input CONTROL FUNCTION SINGLE OUTPUT Control action PID control with auto tuning Fuzzy control with auto tuning Proportional band P 0 999 9 of full scale FS setting in 0 196 steps ntegral time I 0 3200 sec setting in 1 sec steps Differential time D 0 999 9 sec setting in 0 1 sec steps PID 0 2 position action D 0 Proportional action Proportional cycle 1 150 sec setting in 1 sec steps for relay contact output and SSR SSC drive output only Hysteresis width 0 50 FS setting in 1 E U Engineering Unit steps 2 position action only Anti reset wind up 0 100 FS setting in 1 E U steps auto setting with auto tuning Input sampling cycle 0 5 sec Control cycle 0 5 sec CONTROL FUNCTION DUAL OUTPUT Heat Cool Type Heating Proportional band P x 1 2 P 0 999 9 Cooling Proportional band Heating proportional
26. XW con troller Autotune will work for the heating PID parameters but not on the cooling parameters You must manually tune the cooling para meters 6 With the heat side tuned manually set the COOL parameter or Proportional Band Coefficient for Cooling If the cooling output is less powerful than the heating output the Cooling Proportional Band must be narrower than the Heating Proportional Band the COOL parameter would be less than 1 If the cooling output is more powerful than the heating output the Cooling Proportional Band must be wider than the Heating Proportional Band the COOL parameter would be more than 1 See the programming section for more details Heating Side Cooling Side Heating Proportional Band Cooling Proportional Band P 2 P 2 COOL l same as for heating D D same as for heating 7 Finally you can add a Deadband Overlap The programmed Deadband Overlap parameter can be within 50 to 50 of the Heating Proportional band To establish a Deadband parameter db is set somewhere between 0 and 50 of the Heating Proportional band To establish an Overlap db is set somewhere between 50 and 0 of the Heating Proportional Band 8 Manually fine tune the parameters CooL and db until just the right amount of cooling is achieved Refer to the programming section for more details on these parameters 23 Factory Preset Menu Parameter Range PXW PXV3 QUICK REFERENCE Primary Menu
27. alog input wiring is open or short When the burn out control output is set for lower limit standard OFF or 4mA or less When the burn out control output is set for upper limit ON or 20mA or less LL d When PV value goes below 1999 Control is continued until the value reaches 5 FS or less after which burn out condition will occur HB lamp ON Heater break condition Normal control output for heating is continued Z When the setting of P SL P SU is improper OFF or 4mA or less cor Fault in the unit Undefined Stop use immediately APPENDIX A Autotuning By autotuning the controller selects what it calculates to be the opti mal PID control parameters for a particular process and then stores them in EEPROM memory for future use The PID parameters are stored so that when the controller is powered up after being shut down the controller does not need to be autotuned again The con troller uses the same autotuned PID parameters until the Autotune function is again initiated The Autotune parameters are only good for the process the Autotune function was used on If the setpoint is sig nificantly changed the input sensor is changed the load or output device is changed or relocated or any other disturbances occur which might change the dynamics of the system the Autotune func tion should be performed again The autotuned control parameters are not always perfect for every applicat
28. an alarm relay when such conditions exist In most cases the option is used to detect the failure of one or more zones in a multi zoned heater where all individual resistive heater zones are wired in parallel Failed heater zones would create cold spots in a system which could hamper the process and even ruin the product If cold spots in a system are a problem the Heater Break option is an effective way of alerting the operator of a heater break condition a cause of cold spots The PXW controller is able to detect a heater problem by analyzing the current used by the heater The actual sensing is done by a current sensing transformer sold separately which is placed around the hot lead going to the heater and connected to the controller The signal sent by the current sensing transformer is timed with the output of the PXW When the output is energized the signal sent from the current sensing transformer is analyzed When the output is de energized the signal sent from the current sensing transformer is not analyzed This eliminates the alarm condition turning on and off due to the output con dition of the controller If the signal sent when the output is energized indicates that the current level is below what the Heater Break alarm is set for the alarm is energized The alarm is non latching Notes 1 The Heater Break Option is available on the PXW 5 7 and 9 controllers only 2 The Heater Break Option cannot be used on the PXW contr
29. and then by correcting the errors The user calibration function is an independent function and the instrument can easily be reset to conditions prior to delivery Example Input range 0 400 C Indication at 0 C 1 C Indication at 400 C 402 C P gdfF P dF Input Filter Constant The Input Filter is used to filter Change ADJO to 1 and ADJS to 2 to correct the error out the quick changes that occur to the process vari The instrument can be set back to factory values by able in a dynamic or quick responding application setting ADJO and ADJS to 0 which causes erratic control By slowing down the cSt dSP1 Parameter Mask function This function is used to indi response time the PXW controller averages out the to to vidually mask the display of parameters that are not peaks and valleys of a dynamic system which in turn a5 dSP7 used for your application or parameters that are not stabilizes the control The digital filter also aids in con trolling processes where the electrical noise is affect ing the input signal The larger the value entered the more filter added and the slower the controller reacts to process variable changes The smaller the value entered the less filter added and the quicker the con troller reacts to process variable changes Enter as small a value as possible that provides accurate and stable control Setting range 0 0 900 0 secs Fma P An Alarm Hysteresis The Alarm Hyste
30. ate integers tenths or hun dredths of a unit The Decimal Point Position does not increase the accuracy of the controller it only increases the resolution For a thermocouple integers are usually sufficient due to the accuracy rating and the pro grammed input range For a RTD Pt100 integers or tenths of a degree may be entered because of the increased accuracy of these sensors depending on the programmed input range For a 1 5 0 5V DC or 4 20 0 20mA DC signal integers tenths or hundredths of a unit may be entered depending on the programmed input range Setting 0 None 1 Tenths of a unit 2 Hundredths of a unit tt P AH Alarm Type 1 P AL Alarm Type 2 These functions set the control action for the optional alarm output relays They can be pro grammed for absolute deviation combination or zone alarm configuration The high and low alarm setpoints are set with primary menu parameters AH and AL AL is not applicable in the case of PXV3 The absolute alarm configurations are independent of main setpoint The alarm output relays are energized when the process variable exceeds the alarm setpoint an absolute value The deviation alarm configuration is main setpoint tracking The alarm output relays are energized when the process variable exceeds the main setpoint by a deviation value set by AL or AH The combination alarm configurations are a mixture of both the deviation and absolute value settings for the high and low a
31. bsolute upper limit Absolute lower limit Absolute upper limit with hold Absolute lower limit with hold Deviation imit deviation alarm Upper Lower limit deviation Upper and lower limit deviation imit deviation Upper with hold Lower limit deviation with hold Upper and lower limit deviation with hold Range 11 Deviation from upper and alarm lower limit of a range PVOF Process Variable Offset The Process variable Offset is the amount by which the indicated process variable is shifted in a positive or negative direction Both the indicated as well as the measured process variable will be changed This parameter can be used to cor rect for differences in sensors sensor placement and standardization problems Enter a value which is the difference between the measured process value and the actual process value of the system Setting range 10 10 of full scale set in Eng units UGF SVOF Setpoint Variable Offset The Setpoint Variable Offset is that amount of offset which shifts the measured set point variable in a positive or negative direction The measured setpoint variable is changed but the indicat ed setpoint variable remains unchanged Be careful when using this variable because what you see as the setpoint variable may be very different from the actual setpoint variable Setting range 50 50 of full scal
32. cs Setpoint value PXW MODEL CONFIGURATION PIUXIWI 7 i PXW SPECIFICATIONS INPUT RANGE TABLE oH 4 Front panel size 1 16 DIN 1 8 DIN 72mm 1 4 DIN e osBS Q Type of input 3 Thermocouple C Thermocouple F RTD Pt100 C RTD Pt100 F 4 20mA DC 1 5V DC 0 20mA DC 0 5V DC mc zomaA amp c mmooconrS Control Output 1 Relay contact reverse action Relay contact direct action SSR SSC driver reverse action oO SSR SSC driver direct action 4 to 20mA DC reverse action 4 to 20mA DC direct action Control Output 2 C e None Relay contact reverse action Relay contact direct action SSR SSC driver reverse action SSR SSC driver direct action 4 to 20mA DC reverse action 4 to 20mA DC direct action mnmocogr amp a not available on PXW 4 type Alarm Options Code Heater break alarm 2 Process alarm amp Heater break alarm 3 None 4 Process alarm 5 not available on PXW 4 or with 4 20mA output Power Supply Option Code 24V AC DC D ACCESSORIES Sockets only for PXW4 and sold separately 8 pin sockets for PXW 4 without H L Alarm Option ATX1NS Solder Type Socket PG 08 Screw down type terminals on back ATX2PSB Screw down type terminals on back UL TP28X Screw down ty
33. ctly After the appropriate physical changes have been made the controller still needs the correct code for the Input Type to be used Enter the appropriate code from the Table of Input Type Codes Table of Input Type Codes Input Signal Code Range of Range of With With measurement measurement aint eo ont ee pom point Pt100Q 0 a5 z to x Pt100Q 0 to 300 32 to 572 Pt1000 0 to 500 32 to 932 Pt1000 0 to 600 3210 1112 Pt1000 50 to 100 58 to 212 Pt1000 100 to 200 148 to 392 Pt1000 150 to 600 23810 1112 Pt1000 150 to 850 238 to 1562 0 to 400 32 to 752 0 to 800 32 to 1472 0 to 400 32 to 752 0 to 800 32 to 1472 0 to 1200 32 to 2192 0 to 1600 32 to 2912 0 to 1800 32 to 3272 0 to 1600 32 to 2912 199 to 200 328 to 392 150 to 400 238 to 752 0 to 800 32 to 1472 199 to 800 328 to 1472 0 to 1300 32 to 2372 0 00 amp ROOGOINI XOOOOXxXxxoooo xooooooo J J K K K R B S T T E E N N X XXXXXXXXXXOXO xxooxoool z 0 to 1300 32 to 2372 x 1999 to 9999 O Enabled Scaling is possible x Disabled P SL Lower Limit of Input Range The Lower Limit of Input Range is that value which establishes the desired low limit for the type of input used The value must be greater than or equal to the input type s lowest limit Setpoint settings are restricted to values greater than the low limit Parameters which are calculated as a percentage of full scale are affected by this settin
34. e set in Eng units Indicated Setpoint Variable is Unchanged Measured Setpoint Variable is Changed E P F C FSelection The C F Selection allows choosing either the Celsius or the Fahrenheit scale If using the controller to control a process other than temperature using the current voltage input model the C F Selection is not important because the scaling is done using the lower limit of the input range and upper limit of input range parameters If using the thermocouple RTD Pt100 input model however the C F Selection is important in scaling the controller s parameters Setting C or F H1 STAT Ramp Soak Status The Ramp Soak program automati cally changes the setpoint value with time in accordance with a preset pattern as shown in the fig ure This device allows a maximum of four ramp and four soak segments Ramp is the region in which SV changes toward the target value Soak is the region in which the target value is maintained STAT displays the current ramp soak status No setting can be made oFF Not in operation 1 rP 4 rP Executing 1st 4th ramp 1 St 4 St Executing 1st 4th soak End End of program a i SV 1 Ramp Target Value Sets the target value for each ramp to to segment n7 SV 4 Setting range 0 100 of full scale iiic TMir Ramp Segment Time Sets the duration of each ramp to to segment E 4r TM4r Setting range 00 00 to 99hrs 59mins 11113 TMIS Soak Segment Time Sets the du
35. e Heater Break Alarm option Time entered the faster the action Enter a value that Not available on PXWA or with 4 20 mA DC outputs would eliminate offset without overcompensating Detection is made only on a single phase heater This d dne RED function cannot be used when controlling a heater etting Range 0 to secs with SCR phase angle control i me Proportional Band The proportional band is that area around main setpoint where the control output is nei ther fully on nor fully off Setting range 0 0 to 999 9 of full scale For On Off control set to 0 Cycle Time TC must be set at 6 secs or higher a d Derivative Time Rate The Derivative Time is that time used in calculating rate of change and thermal lag in Optimal Qurrent of helping eliminate overshoot which results in response minus Optimal Current of Heater to process upsets This overshoot usually accompanies gd eee ee of Marie d Pies proportional only and proportional integral processes less One Zone Setpoint The derivative action dampens proportional and inte EC IR ED gral action as it anticipates where the process should 2 Hb be The more Derivative Time entered the more damp H1 AT Autotuning Autotuning is the automatic calculation ing action The less Derivative Time entered the less and entering of the control parameters P and D into damping action Enter as much Derivative
36. e polarity is correct e Set the proportional time cycle parameter TC to 1 sec or more 4 to 20mA DC The output is a non isolated analog signal used to drive a variety of output devices such as SCRs and valve actuators The load resistance must be less than 60022 Make sure the polarity is correct The proportional time cycle parameter TC is set to 0 and is not displayed on the programming menu Wiring Alarms Make sure the load does not exceed the rated capacity of the relay Several types of alarm configurations can be programmed and does not require a change in the wiring Refer to parameters AL AH P AH P AL P An For details on Heater Break alarm please refer to Appendix D and the Heater Break Alarm Setpoint parameter Hb in the program ming section SYSTEM WIRING DIAGRAMS Example 1 L 120V AC l N PXV3 RCY1 5V pus eL E i INPUT OUTPUT ALARM POWER TYE A PDISENE OUTPUT2 8510264 VAC 50 60Hz 1 DC Input SSR i E e mm EV ox 1 T 2 o 9 9 O DENEN 6 00 Q lt QAO Heater Thermocouple N Example 2 L 120V AC N Fuse Heater 3A or less o E g S Fuse PXW4 RAY1 4V Power 85 to 264 VAC 50 60Hz Thermocouple FRONT PANEL DESCRIPTION o Model PXW4 Model PXW5 Model PXW7 9 Name Function CD Process Value PV display Displays th
37. e process value PV Set value SV indication lamp Stays on while a set value is on the display Set value SV and Displays set value SV or parameter symbol or parameter display code when setting various parameters SELECT key Key for switching between the parameter blocks and for scrolling within the block 5 UP key For incrementing the numerical value or scrolling up the the menu Numerical value changes contin uously when held pressed DOWN key For decrementing the numerical value or scrolling down the menu Numerical value is decremented continuously when held pressed Auto tuning indicator The indicator blinks while the PID auto tuning is being performed Control Output indication lamp C for PXW4 Stays on while control output is ON C1 Stays on while control output 1 is ON C2 Stays on while control output 2 is ON 9 Upper limit alarm Comes on when the upper limit alarm is activated indication lamp optional Blinks while the alarm value is being set 0 Lower limit alarm Comes on when the lower limit alarm is activated indication lamp optional Blinks while the alarm value is being set Ib Heater break alarm Comes on when the heater break alarm is output indication lamp FRONT PANEL OPERATION The PXW controller programming menu consists of three blocks PRIMARY SETPOINT MENU SECONDARY SYSTEM MENU and FACTORY PRESET MENU At power up the controller will be in the operational mode
38. e programmed with either upper limit or lower limit burn out direction With Upper limit Burn out a 100 output will be delivered in the event of a sensor burn out With Lower limit Burn out 0 output will be delivered in the event of a sensor burn out Enter the appropriate code from the Table of Output Type Codes Refer to Error Messages for more details Table of Output Type Codes tc FUZY Fuzzy Logic Control Employing Fuzzy Logic Control in addition to PID control eliminates system overshoot ade Control action Burn out direction put typ Output 1 Output 2 Output 1 Output 2 and effectively suppresses fluctuation of the process Reverse variable due to external disturbances This function action may be enabled even during auto tuning Note that Single Direct fuzzy control is not effective in units with dual outputs action due to the complexity of the process Fuzzy control is also inhibited while the Ramp Soak function is in oper ation Reverse action ji Temperature Direct ie Setpoint Z action Direct action imit Warm Up Load Disturbance Dual Time Beverse imit PID control action 2 PID Fuzzy control R imit Mida Hd ADJO Input Calibration This function is used for input cali f imit bra Direct Hout ADJS tion by the user in a simple manner Calibration is action imit effected by first applying the appropriate signal for zero and span points of the input range being used
39. ee 2 OTHER FUNCTIONS Parameter mask function Parameter display is disabled by software Ramp soak function 4 ramp 4 soak STRUCTURE Mounting method Panel flush mounting or surface mounting Surface mounting PXW 4 type only External terminal PXW 4 type 8 pin or 11 pin socket Other types screw terminal M3 5 screw Enclosure Black ABS plastic Dimensions PXW 4 48 x 48 x 85 7mm 1 16 DIN PXW 5 52 5 x 100 5 x 95 8mm 1 8 DIN PXW 7 76 5 x 76 5 x 95 8mm 72 mm PXW 9 100 5 x 100 5 x 95 8mm 1 4 DIN Weight PXW 4 approx 150g PXW 5 approx 300g PXW 7 approx 300g PXW 9 approx 400g Protective structure Front panel water proof structure EMA 4X equivalent to IEC standards IP66 Rear case IEC IP20 DELIVERY PXW 4 type controller panel mounting bracket socket when specified water proof gasket 250Q precision resistor when required instruction manual Other types controller panel mounting bracket water proof gasket 250Q resistor when required instruction manual OUTER DIMENSIONS amp PANEL CUTOUT SIZE 857 De 48 Gasket _ PEER Unit mm 5 Panel thickness 1 to 8 mm se or Mounting Bracket 63 or more Panel cutout size when installing n number of units r 63 or more I 40 5 45 0 mt 30 5 45 0 PXW 5 7 9
40. erivative Time is now tuned Another tuning method is the closed loop cycling or Zeigler Nichols method According to J G Zeigler and N B Nichols optimal tuning is achieved when the controller responds to a difference between set point and the process variable with a 1 4 wave decay ratio That is to say that the amplitude of each successive overshoot is reduced by 3 4 until stabilizing at setpoint The procedure is explained below 1 Integral Time 0 Derivative Time 0 2 Decrease the Proportional Band to the point where a constant rate of oscillation is obtained This is the response frequency of the system The frequency is different for each process 3 Measure the Time Constant which is the time to complete one cycle of the response frequency The Time Constant will be defined as T when calculating Integral and Derivative Times Time Constant gt PV Time 4 Widen the Proportional Band until only slightly unstable This is the Proportional Band s Ultimate Sensitivity The Proportional Band s Ultimate Sensitivity width will be defined as P when calculating the actual Proportional Band 5 Use the following coefficients in determining the correct PID set tings for your particular application Control P l D Action Setting Setting Setting P Only PI 2 2P PID 2P i 83T 167P 5T 21 APPENDIX C Heater Break Option The Heater Break Option is used to detect heater break conditions and to energize
41. et over a long time If the integral time is too long the offset will remain for some time causing a slow responding or slug gish control See the diagram below PV _ Setpoint Offset Time Short Integral Time Long Integral Time Proportional Action Only Output Time Derivative Time In the case of a process upset proportional only or proportional inte gral action cannot react fast enough in returning a process back to setpoint without overshoot The derivative action corrects for distur bances providing sudden shifts in output which oppose the diver gence of the process from setpoint See the diagram below 20 The derivative action changes the rate of reset or integration propor tional to the rate of change and lag time of the system By calculating the rate of change of the process and multiplying it by the lag time which is the time it takes the controller to sense an output change the controller can anticipate where the process should be and change the output accordingly This anticipatory action speeds up and slows down the effect of proportional only and proportional integral actions to return a process to setpoint as quickly as possible with minimum overshoot See the diagram below Rate of Change X Lag Time Anticipated Process Variable PV Time Derivative time is the amount of anticipatory action needed to return a process back to setpoint A short derivative time means little deriva tive action
42. g An underscale error message is indicated on the process variable display when the process variable goes below the Lower Limit of Input Range setting by 5 of full scale The primary purpose of the Lower Limit of Input Range when used with a thermocouple or RTD sensor input is to limit setpoint settings Making the input range smaller does not increase the accuracy The primary purpose of the Lower Limit of Input range when used with 1 5 0 5V DC or 4 20 0 20mA DC signal input is to scale the range so that 1 0V DC on a 1 5 0 5V DC signal and 4 0mA DC on a 4 20 0 20mA DC signal equals the low limit of the engineering unit range used The engineering unit range could be PSI GPM PH or any range which can be scaled between 1999 and 9999 units Enter a value to set Lower Limit of Input range based on the type of input used Upper Limit of Input Range The Upper Limit of Input Range is that value which establishes the desired high limit for the type of input used The value must be less than or equal to the input type s highest limit Setpoint settings are restricted to values less than the high limit Parameters which are calculated as a percent age of full scale are affected by this setting An over scale error message is indicated on the process vari able display when the process variable goes above the Upper Limit of Input Range setting by 596 of full scale The primary purpose of the upper limit when used with a thermocouple or RT
43. he shorter the Cycle Time the higher e ox TON OW the proportioning resolution is and better is the con E ox LFF OFF E o L LFF OFF trol but there will be an increased strain on the output ON OFF action PID congo ON OFF acion PP con device Enter a value that is based on the limitations of your controller s output type Setting range 1 to 150 secs For relay output Set to 30 secs or more L CL LoC Lock out This function enables or disables changing For SSR SSC driver output Set to 1 sec or mone For current output Set to 0 normally not indicated the settings of parameters Code 0 All parameter settings are changeable mos OFF e OFF 1 All parameter settings are locked cannot be 30 sec Cycle Time 30 sec Cycle Time changed 25 Output 75 Output 2 Only the main setpoint can be changed all other parameter settings are locked and cannot be changed HYS Hysteresis Hysteresis is that area around the main setpoint where the output does not change condition That area or deadband is intended to eliminate relay chatter at setpoint for On Off control applications The wider the Hysteresis the longer it takes for the con troller to change output condition The narrower the Hysteresis the less time the controller takes to change output condition When the Hysteresis is narrow the On Off control is more accurate but the wear on the output relay is increased Enter a value which is small e
44. ion but almost always give the operator a good starting point from which further refinement of the control parameters can be performed manually The autotuning algorithm used here is particularly suited for tempera ture control applications and may not always autotune effectively for other processes Here are cases where the Autotune function does not perform well or does not perform at all 1 The system is affected by process disturbances external to the con trol loop Adjacent heater zones changing material levels exother mic reactions are examples of process disturbances which are external to the control loop The controller would never be able to autotune such an unstable process 2 The system is very dynamic The process variable changes very quickly Certain pressure and flow applications would be charac terized as very dynamic Because of how the Autotune function is performed a very dynamic system would create very large over shoots which could damage the process 3 The system is very insulated and cannot cool down in a timely man ner With such heating systems the autotuning function would take a long time to complete with questionable results During autotuning test signals are sent to the process The test sig nals are 100 output and 0 output at the Autotune point The Autotune point can either be at setpoint or 10 of full scale below setpoint The controller performs as an On Off controller See diagram below
45. irst second or third block parameters are selected 4 UP key Pressing the key once will increase the value by one By pressing it in succession the value is continuously incremented DOWN key Pressing the key once will decrease the value by one By pressing it in succession the value is continuously decremented B Autotuning indication Blinks while the PID autotuning is being lamp performed T Control output indication lamp 8 Alarm indication lamp Comes on when the control output is ON Comes on when the alarm is activated Blinks while the alarm is being set FRONT PANEL OPERATION The PXV3 controller programming menu consists of three blocks PRIMARY SETPOINT MENU SECONDARY SYSTEM MENU and FACTORY PRESET MENU At power up the controller will be in the operational mode and process variable PV will be displayed This is the variable that is being controlled and it is not programmable When setting the parameters turn off the power to the load operating equip ment to ensure safety Since it takes 30 minutes for the unit to stabilize in terms of temperature all measurements should be carried out at least 30 minutes after the power is turned on Option related features are displayed only when the options are provided Viewing and Setting Parameters The data is automatically registered in 3 seconds after the setting It can also be registered by pressing the SEL key How to set Setpoint value SV
46. larm l le7o 9 Heater break alarm output Common Control output 1 Power supply gt EE Q 660900090 el CT input Wiring Power to Controllers Be sure to use the rated power supply voltage and polarity for the unit to protect it against damage and to prevent the occurrence of failure Keep the power off until all of the wiring is completed to prevent electric shock and abnormal operation Keep the power supply wires separated from the input and output wires Power connections should be made with 18 gauge or larger insulated wire Stranded wire improves noise immunity Noise filters and isolation transformers are recommended in case of noisy power lines When the Heater Break option is selected use the same power line for both the controller and the heater Wiring Inputs There are two input categories available Thermocouple RTD or current voltage Make sure you have the right type before wiring the inputs Refer to Table of Input Type Codes and set the parameter P n2 accordingly Note In order to minimize the risk of high frequency noise induced by coils and windings in relays solenoids and transformers use leads which have braided sheath and ground one end of the sheath Keep your input leads separate from power and output leads If you have to bring the input signal from a long distance a signal transmitter might be needed to maintain an accurate reading in
47. larms With zone alarm configurations the alarm output is energized between the range set by AL and AH One of the alarm types is Alarm with Hold In this case the alarm is not turned on the first time the measured value is in the alarm band Instead it turns on only when the measured value goes out of the band and enters it again This type is useful when using devia tion alarm with step type input Enter the code for P AH and P AL from the Table of Alarm Action Type Codes See Figues below P AL is not applicable in the case of PXV3 Note 1 A change of alarm action type can cause the alarm set value to change but this is not a malfunction Note 2 After the alarm type is changed turn off the power to the unit once Table of Alarm Action Type Codes PXW d Pca pom Alarm type Action diagram Absolute value alarm High alarm Low alarm High alarm with hold Low alarm with hold Deviation alarm High alarm Low alarm High Low alarm High alarm with hold Low alarm with hold High Low alarm with hold High Low deviation Zone alarm alarm ALM 1 2 independent action High Low absolute alarm High Low deviation alarm High absolute Low deviation alarm High deviation Low absolute alarm Table of Alarm Action Type Codes PXV3 Cod EN oe MEINE Absolute value alarm A
48. nough to meet the control tolerance of the application but large enough to eliminate relay chatter Setting range 0 to 50 of FS set in E U for output 1 Hysteresis for On Off action for dual outputs heating and cooling is fixed at 0 5 of FS Output OFF Output OFF Output ON Output ON z Setpoints Narrow Wide Hystersis Hystersis Cycle Time Output 2 The Cycle Time for output 2 is similar in function to Cycle Time for output 1 Output 2 is the cooling side of a heat cool PXW controller Enter a value that is based on the limitations of your controller s output type Setting Range 1 to 150 secs Not indicated without the control output 2 option For current output Set to 0 normally not indicated Proportional Band Coefficient for Cooling The Proportional Band Coefficient for Cooling is a multiplier for the proportional band on the cooling side of a heat cool controller It varies the width of the propor tional band on the cooling side A large value would establish a larger proportional band for more powerful cooling loads A small value would establish a smaller Lime proportional band for less powerful cooling loads Enter a value based on the power of your cooling load Setting Range 0 0 to 100 0 Not indicated without control output 2 option Set to 0 for On Off control P Prop Band for Heating X Input Range N Prop Band for Cooling X Input Range x Lool n
49. oller with a 4 20mA DC output The current sensing transformer would pick up current changes due to fluctuating power output between 0 and 100 which would result in a heater break alarm condition even though no such condition existed 3 The Cycle Time must be set at 6 secs or higher in order for the controller to correctly analyze the signal sent by the current sensing transformer 4 The power supply used should be the same for the PXW and heater to eliminate current fluctuations due to power differences between different power supplies Wiring and Setting 1 Choose the correct current sensing transformer based on the maxi mum current usage of the heater 0 30 Amps part CTL 6 SF 20 50 Amps part CTL 12 S36 8F 2 Thread the hot lead going to the heater through the donut of the cur rent sensing transformer Connect the wires of the current sensing trans former to the current sensing transformer input terminals in the back of the controller Connection to PXW Polarity not important Hot lead to Heater 3 Set Heater Break alarm setpoint parameter Hb With the current sensing transformer connected and the heater in operation output energized change the Heater Break Alarm set ting from the maximum current setting for the particular current sensing transformer being used to a lower value Allow 3 secs or more between setting changes Continue lowering the setting until the relay is energized and the
50. ortional to the amount of error between the setpoint variable SV and the process variable PV Outside of the proportional band the output is either 096 or 10096 The proportional band on PXV3 PXW is equidistant from the main set point as illustrated below Reverse Action Direct Action lt PB PB gt 100 Output 100 Output 0 PV 0 Main Setpoint Main Setpoint An example of proportioning would be a vehicle approaching a stop sign at an intersection If the driver were traveling at 50mph and only applied his brakes once at the intersection his car would skid through the intersection before coming to a full stop This illustrates how On Off control acts If however the driver started slowing down some distance before the stop sign and continued slowing down at some rate he could conceivably come to a full stop at the stop sign This illustrates how proportional control acts The distance where the speed of the car goes from 50 to 0 MPH illustrates the proportional band As you can see as the car travels closer to the stop sign the speed is reduced accordingly In other words as the error or distance between the car and the stop sign becomes smaller the output or speed of the car is proportionally diminished Figuring out when the vehicle should start slowing down depends on many variables such as speed weight tire tread and braking power of the car road condi tions and weather much like figuring out the propo
51. osive gases sulfide and ammonia gas in particular or combustible gases are emitted e the unit is subject to vibration or shock the unit is likely to come in contact with water oil chemicals steam or vapor the unit is exposed to dust salt or air containing iron particles the unit is subject to interference with static electricity mag netism or noise e the unit is exposed to direct sunlight heat may be accumulated due to radiation Maintenance 1 Do not use organic solvents such as alcohol or benzene to wipe this unit Use a neutral detergent 2 Three year warranty is guaranteed only if the unit is properly used PXV3 MODEL CONFIGURATION PH XIV 3 1 l V Type of Input Code Thermocouple C Thermocouple F R RTD Pt100 C N RTD Pt100 F S 4 20mA DC 1 5V DC B 0 20mA DC 0 5V DC A Control Output 1 Code Relay contact reverse action A Relay contact direct action B SSR SSC driver reverse action C SSR SSC driver direct action D Control Output 2 Code None Y Relay contact reverse action A Relay contact direct action B Alarm Option Code None 4 High Low alarm SPST 5 Available with single output only Power Supply Option Code 85 264 VAC 24V AC DC D PXV3 SPECIFICATIONS INPUT RANGE TABLE Input Signal Input Range Input
52. out control output 2 option Balance Balance is used to pre position the propor tional band with respect to setpoint With Balance MV Offset set at 50 the proportional band will be cen tered around setpoint To move the band left or right decrease or increase the balance setting respectively Setting range 0 100 Ar Anti Reset Wind up Anti Reset is used to limit the range where integration occurs This helps in stabiliz ing a system With Anti Reset at 100 integration will occur throughout the proportional band With Anti Reset set to 90 integration will occur at 90 of the band above the setpoint and 90 of the band below the setpoint Autotuning automatically sets Ar Setting range 0 100 of full scale set in E U Input type The Input Type is the type of sensor to be used with the controller in sensing the process vari able The Input Type must be correctly programmed into the controller in order for the controller to perform with the selected sensor type Depending on the type of sensor to be used the controller comes in two mod els One model accepts J K R B S T E N thermo couples and RTDs Pt100 The other model accepts 1 5 0 5V DC and 4 20 0 20mA DC signals The current voltage model comes with a 250Q preci Thermocouple sion resistor Wired directly to the controller it would convert a current signal into a voltage signal There is no need to use the resistor if a voltage signal is applied dire
53. own i d Mod the menu 7 Press SEL key for 3 secs Operational mode FACTORY PRESET MENU Operation Display 1 Operational mode PV SV 2 Press SEL key for 9 seconds 3 seconds later H LED blinks 7 seconds later P 9 seconds later P n1 3 Release and press SEL key again P n1 data 4 Press UP or DOWN key P n1 data changed 5 Press SEL key once P n1 6 Press DOWN key to scroll down P df dsp7 the menu 7 Press SEL key for 3 secs Operational mode Blinking H LED AH Blinking Aj L LED AUTOTUNING Before initiating the autotune function first decide if you would like to autotune at setpoint or 1096 of full scale below setpoint Setthe set point SV alarms AL AH and the cycle time TC Bring your process near setpoint before starting the autotune procedure Set the parameter AT to either 1 to auto tune at setpoint or 2 to auto tune at 10 of full scale below setpoint and press SEL key to start auto tuning The point indicator at lower right will then start blink ing When the auto tuning is completed the point indicator stops blink ing and the parameter AT will automatically be set to 0 Duration of the autotune process varies with every application The auto tuning process may take between 1 and 30 minutes to complete If it fails to complete an abnormality may be suspected In this case recheck the wiring
54. pe terminals on front UL 11 pin sockets for PXW 4 with H L Alarm Option PG 11 Screw down type terminals on back TP311SB Screw down type terminals on back UL TP3118 Screw down type terminals on front UL Heater Break Current Sensing Transformer CTL 6 SF For heater current 1 to 30 amps CTL 12 S36 8F For heater current 20 to 50 amps Input Signal Input Range Input Range Remarks C F Thermocouple 0 80 0 12 0 16 32 1472 Cold Junction 32 2192 compensating 32 2912 function built in 0 18 32 3272 0 16 32 2912 199 200 328 392 150 400 238 752 199 800 328 1472 0 1300 32 2372 0 1300 32 2372 C39 C9 c5 C9 Ce ccc TUzermm c00020 rC N RTD Pt100 150 850 238 1562 Allowable wiring resistance 10 ohms max per wire DC Voltage Current 1 5V Scaling Range 1999 to 9999 For current input use 0 5V Engineering Units the 250Q resistor 4 20mA to obtain 1 5 V or 0 20mA 0 5V DC input CONTROL FUNCTION SINGLE OUTPUT Control action PID control with auto tuning Fuzzy control with auto tuning Proportional band P 0 999 9 of full scale FS setting in 0 1 steps ntegral time I 0 3200 sec setting in 1 sec steps Differential time D 0 999 9 sec setting in 0 1 sec steps PID 0 2 position action D 0 Proportional action Proportional cycle 1 150 sec setting in 1 sec steps for relay contact o
55. quirements are classified as either warning or caution according to the following explanations Warning suggesting that the user s mishandling can result in personal death or serious injury A Caution suggesting that the user s mishandling can result in personal injury or damage to the property A Warning Wiring 1 If there is danger of serious accident resulting from a failure or defect in this unit provide the unit with an appropriate external protective circuit to prevent an accident 2 The unit is normally supplied without a power switch or a fuse Use power switch and fuse as required Rating of the fuse 250V 1A Power supply 1 Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure 2 Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented General 1 Never attempt to disassemble modify or repair this unit Tampering with the unit may result in malfunction electric shock or fire 2 Do not use the unit in combustible or explosive gaseous atmos pheres A Caution Installation 1 Avoid installing the unit in places where the ambient temperature may reach beyond the range of 10 to 50 C 14 to 122 F while in operation e the ambient humidity may reach higher than 90 RH while in operation e a change in the ambient temperature is so rapid as to cause condensation corr
56. ration of each soak i to to segment 11135 TM4S Setting range 00 00 to 99hrs 59mins Set Value SV3 sv2 svi Fourth Ramp 4 p r r I PV Time TMIR TM1S TM2R TM2S TM3R TM3S TM4R TM4S Ramp Region in which the setpoint changes toward the target value Soak Region in which the setpoint stays unchanged at the target value Note 1 SV cannot be changed while the operation is running or suspended Note 2 The use of fuzzy control is inhibited while Ramp Soak operation is being performed mo oo eee Mod Ramp Soak Mode Up to 16 different modes of ramp soak operations are possible Choose the appro priate code from the Table of Ramp Soak Modes Setting 0 15 Table of Ramp Soak Modes MOD Power on start Output on END Output on OFF Repeat function No Going on control Going on control No No Going on control Going on control Yes No Going on control Stand by mode No No Going on control Stand by mode Yes No Stand by mode Going on control No No Stand by mode Going on control Yes No Stand by mode Stand by mode No No Stand by mode Stand by mode Yes Yes Going on control Going on control No Yes Going on control Going on control Yes Yes Going on control Stand by mode No Yes Going on control Stand by mode Yes Yes Stand by mode Going on control No Yes Stand by mode Going on control Yes Yes
57. re described below 1 Install the gasket over the enclosure and insert the unit into the panel as shown in Figure 1 2 Slide the mounting bracket and tighten the screws as shown in Figure 2 Figure 1 unit N Figure 2 unit oc o I o oo n d 3 D Bezel Gasket Case Panel Panel Mounting Bracket Screw Caution After the mounting bracket is installed check the gasket for displacement and detachment as shown in Figure 3 Figure 3 Gasket Case Case A Bad Good Gasket WIRING INSTRUCTIONS Terminal connection A Warning Be sure to use the rated power supply voltage and polarity OUTPUT AARW L V PULSE OUTPUT2 i I l INPUT o o o o POWER I 3 Power supply For current input install the 250Q precision pone resistor accessory before using the unit Wiring material 1 For terminals 1 2 3 use 18 26 gauge wire 2 For terminals 4 to 9 use 14 24 gauge wire Please refer to Page 9 for further instructions on wiring power input and output to the controller FRONT PANEL DESCRIPTION NAME FUNCTION D Set value SV Comes on when a set value SV indication lamp is displayed 2 Process value PV Process value PV Setpoint value SV Set value SV or parameter symbols and codes are parameter display displayed 3 Select key To be used when the f
58. resis is that area on one side of the alarm setpoint where the output does not change condition That area or deadband is intend ed to eliminate relay chatter at alarm setpoint with less wear on the relay With a wide Alarm Hysteresis the controller takes a longer time to change output condi tion With a narrow Alarm Hysteresis the controller takes a short time to change output condition Enter a value which is just large enough to eliminate relay chatter Setting Range 0 to 50 of full scale set in E U Alarm OFF Alarm OFF AlarmON gt Alarm ON a7 S Low Alarm Low Alarm Main High Alarm High Alarm Setpoint Hysteresis Setpoint Hysteresis Setpoint to be accessed by the operator To mask or unmask a parameter appropriate values should be selected from the DSP Assignment table Example 1 To mask parameter P 1 Determine the dSP value for P from Quick Reference P dSP1 128 2 Add 128 to the existing dSP1 value Example 2 To display unmask the parameter P F 1 Determine the dSP value for P F from Quick Reference P F dSP4 2 2 Subtract 2 from the existing dSP4 value ERROR MESSAGES Error Indication Cause Control Output 1 Thermocouple burnt out aiian 2 RTD A leg burnt out 3 PV value exceeds P SU by 5 FS EE ie 1 When RTD B or C is burnt out 2 When RTD between A and B or between A and C is shorted 3 When PV value is below P SL by 5 FS 4 When an
59. rtional band of a control process with its many variables The width of the proportional band depends on the dynamics of the system The first question to ask is how strong must my output be to eliminate the error between the setpoint variable and process vari able The larger the proportional band low gain the less reactive the process A proportional band too large however can lead to process wandering or sluggishness The smaller the proportional band high gain the more reactive the output becomes A proportion al band too small however can lead to over responsiveness leading to process oscillation Proportional Band with Correct Width Proportional Band Too Large Proportional Band Too Small A proportional band which is correct in width approaches main set point as fast as possible while minimizing overshoot If a faster approach to setpoint is desired and process overshoot is not a prob lem a smaller or narrower proportional band may be used This would establish an over damped system or one where the output would change greatly proportional to the error If process overshoot cannot be tolerated and the approach to setpoint does not have to be quick a larger or wider proportional band may be used This would establish an under damped system or one where the output would change little proportional to the error To Calculate Proportional Band Proportional Band Proportional Band as a percentage 5 X 100
60. t 2 can be relay SSR driver or 4 20mA DC regardless of what Output 1 is Both output types must be speci fied when ordering The PXW controls the cooling side with three additional parameters TC 2 COOL and DB as explained in the programming section TC2 Cycle Time Output 2 Because Output 2 is not nec essarily the same as Output 71 the cycle time may be different CooL Proportional Band Coefficient for Cooling Because the cooling power may not necessarily be the same as the heating power the cooling proportional band may be different from that of the heating proportional band 22 db Deadband Overlap Deadband is that area where neither outputs are energized Overlap is that area when both out puts are energized This function lets you decide where you want the heating action to stop and the cooling action to begin Notes 1 The Heat Cool Option is available on the PXW 5 7 and 9 con trollers only Output 2 type can be the same or different than Output 1 type Relay SSR driver or 4 20mA DC 2 Integral and Derivative Times are the same for both the heating and cooling sides of a process with PID control because the response frequency or time constant of the system does not change at main setpoint when cooling is added 3 The Proportional Band for heating and cooling are almost always different Rarely does the same amount of cooling output remove the same percentage of process error as the heating outpu
61. t does The Cooling Proportional Band must be manually and separately tuned 4 f the heating side is set for On Off control the cooling side will be set for On Off control also Regardless of what the COOL parame ter is set for if the Proportional Band is set to zero the Heating Proportional Band and the Cooling Proportional Band will always be zero or On Off 5 If the cycle times of one or both outputs are long and the process dynamic there is a good chance that both outputs will be cycling on and off at the same time around main setpoint This is evident if one or both outputs are relays 6 Autotune is not effective on the cooling side of Heat Cool control Autotune the controller for heat only and then manually tune the cooling parameters Wiring and Setting 1 Make sure that your PXW has the correct output type installed for Output 2 Verify that the TC2 COOL and DB parameters are indi cated in the primary setpoint menu 2 Wire your cooling load to the Output 72 terminals located on the back of your PXW controller 3 In the secondary system menu program the correct code for Heat Cool action See Table of Output Type Codes 4 In the primary setpoint menu program TC2 the cycle time for Output 2 The table below is a general guide to TC2 settings Output 2 Type Setting Secs Relay 30 SSR Driver pulsed DC 2 4 20mA DC Not indicated or 0 5 Autotune or manually tune the PID parameters of your P
62. t indicated without the alarm option Low Alarm Setpoint The Low Alarm Setpoint is that point of the process below which the low alarm output relay is energized Absolute and deviation alarm con figurations are programmable from within the sec ondary menu Settable within the Input Range Not indicated without the alarm option or in PXV3 Blinking Hb Heater Break Alarm Setpoint If the heater s operating HB LED current falls below this setpoint the heater break SECONDARY SYSTEM MENU alarm output relay is energized This option is used in cases where the PXW is controlling a bank of heaters wired in parallel A current transformer around the hot lead going to the heater bank and connected to the controller is tied with the controller s output and sens es the current used by the heater bank If one or more of the zones burnout resulting in cold spots the cur rent used by the defective heater bank is reduced By I IT The Time is th d determining what the optimal current and the optimal 5 ntegral Time reset The Integral Time is the speed at current minus one zone for the heater bank is the which a corrective increase or decrease in output is Heater Break Alarm setpoint can be calculated and made to compensate for offset which usually accom entered panies proportional only processes The more Integral Setting Range 0 0 to 50 0 amps Time entered the slower the action The less Integral Not indicated without th
63. this case a unit that accepts current voltage input would be necessary Thermocouple Connect thermocouples directly to the input terminals whenever possible e If using extension wires make sure they are of the same thermocouple material and grade any dissimilar metal junctions will lead to erroneous readings Ungrounded thermocouples are recommended for optimal performance and to prevent ground loops Make sure the polarity is correct RTD Pt100 e Use a 3 wire Pt100Q RTD whenever possible All three wires must have low lead resistance less than 10Q and no resistance differentials among them If using a 2 wire RTD jumper the two B legs with a wire of equal resis tance Make sure A and B leads are connected to the right terminals Current Voltage The controller accepts 1 5V 0 5V 4 20mA and 0 20mA DC signals If wiring for a voltage input feed the signal directly to the input terminals For current inputs first connect the 250Q precision resistor that comes with the unit Make sure the polarity is correct Wiring Outputs Before wiring the outputs make sure the unit has the right kind of control output and that all the load handling devices conform to the controller specifications Note that it takes 5 seconds for the outputs to activate after the power is turned on Refer to parameter P n1 and to the Table of Output Type Codes to choose the preferred type of control action reverse acting or direct
64. tune with manual override heating or cooling Programmable control action reverse or direct Programmable cycle time Programmable inputs Thermocouple RTD Current Voltage e Sensor burn out protection Input calibration by user Outputs Relay Solid state relay drive or 4 20mA DC 4 20mA not available on PXV3 Secondary output for cooling optional High low alarm outputs optional Heater break alarm optional only on PXW 5 7 9 Menu driven format e Setting touch keys on front panel Programmable 8 segment ramp soak function Digital filtering to suppress factory noise Adjustable setpoint range Selectable F C Offset adjustments Programmable decimal point Programmable lock feature Advanced security options to prevent unauthorized parameter changes 4 digit LED indication Dutput status indication Fault indication Non volatile memory 1 32 1 16 1 8 1 4 DIN and 72mm panel mount package NEMA 4X faceplate ABS plastic housing Termination screw down type PXV3 PXW 5 7 9 or socket with screw down terminals PXW 4 Metal mounting bracket plastic bracket for PXV3 PXW 4 85 to 264V AC free voltage power supply e 24V AC DC power supply optional UL C UL and CE approvals 3 year warranty SAFETY PRECAUTIONS Before using this product the user is requested to read the follow ing precautions carefully to ensure safety The safety re
65. utput and SSR SSC drive output only Hysteresis width 0 50 FS setting in 1 E U Engineering Unit steps 2 position action only Anti reset wind up 0 100 FS setting in 1 E U steps auto setting with auto tuning Input sampling cycle 0 5 sec Control cycle 0 5 sec CONTROL FUNCTION DUAL OUTPUT Heat Cool Type Heating Proportional band P x 1 2 P 0 999 9 Cooling Proportional band Heating proportional band x Cooling proportional band coefficient Cooling proportional band coefficient 0 100 0 2 position action 0 0 ntegral time 3200 sec for heating and cooling Differential time 999 9 sec for heating and cooling PI D 0 2 position action without dead band for heating and cooling D 0 Proportional action Proportional cycle 1 150 sec for relay contact output and SSR SSC drive output only Hysteresis width 2 position action for heating and cooling 0 5 FS 2 position action for cooling 0 5 FS Anti reset wind up 0 100 FS setting in 1 E U steps auto setting with auto tuning Overlap dead band 50 of heating proportional band Input sampling cycle 0 5 sec Control cycle 0 5 sec OUTPUT Single Output Control output One of the following three types is selected 1 Relay contact SPDT 220V AC 30V DC 3A resistive load Mechanical life 10 times under no load Electrical life 10 times under the rated load 2 SSR SSC drive voltage pulse 15 30V D

Download Pdf Manuals

image

Related Search

Related Contents

メッシュタイプ  GM-T106696D  HSA3500 HSA3500 plus Power Supply User Manual  SignalVu-PC Demonstration Guide  BM3001  新事業分野開拓者認定制度 募集要項  change yourlife  C10A / C30A Controller Cable Splitter Kit Installation Manual    classificazione di nizza - Camera di commercio di Benevento  

Copyright © All rights reserved.
Failed to retrieve file