Home
3500 Installation - Protec Fire Detection
Contents
1. N93 586 84 Issue 04 AB Page 9 of 32 Protec Fire Detection plc 2015 c1 Protec Protec Fire Detection ple 5 4 Removal of the Control PCB Housing Before handling the 3500 panel control PCB housing it is important that any operatives discharge themselves of any static charge that may have built up This can be done by momentarily touching a solid earth point a non painted part of a radiator for example The Control PCB housing is a sealed unit and must not be opened Tampering with this unit will invalidate the warranty If the unit becomes faulty it must be returned for repair Unscrew and remove the four mounting screws on the control PCB housing Carefully lift away the control PCB housing from the plastic enclosure See figure 5 2 The 3500 control PCB housing and all screws should be stored in the cardboard carton away from the place of work where they will not get damaged Figure 5 2 Removal of the 3500 Control PCB Housing N93 586 84 Issue 04 AB Page 10 of 32 Protec Fire Detection plc 2015 Prater or Protec Fire Detection plc 5 9 5 6 Tie Wraps must be used to secure the batteries Preparing the Mounting Position and Cable Entries Use the dimensions shown on the interior rear face of the 3500 back box in conjunction with a spirit level to mark out the fixing locations for the panel Drill and plug the mounting holes just marked Using a suitable tool carefully remove the rear panel knockout
2. tA Resistive end of line details 8 2KQ 5 14W Capacitive end of line module details 100uF 35V 5 capacitor in series with a 22Q 14W resistor Maximum number of detectors per zone 25 Protec 3000PLUS OP devices Maximum number of devices per zone 32 combination of Manual Call Points and automatic detectors Must be fitted with a series resistor 1500 to 6800 Manual Call Point requirements A 1800 5 14W resistor must be fitted for the 3500 to distinguish between manual and automatic triggers on zones Alarm circuit specifications Maximum alarm circuit capacitance Resistive end of line details 10kQ 5 YW Alarm circuit device requirements Pulse rate when output set to pulsing Auxiliary circuit specifications 150mA maximum protected by monitored self resetting thermal fuse Any overload must be completely removed to clear a fault condition Class change input Class change triggered when CC input connected to OV with less than 50Q Global fire and fault output contacts Volt free changeover contacts rated at a maximum of 1A 24V dc resistive Security codes User security code 134422 Auxiliary 24V output current Engineer security code 314431 N93 586 84 Issue 04 AB Page 27 of 32 Protec Fire Detection plc 2015 c1 Protec Protec Fire Detection plc Appendix 1 List of 3500 Spares and Accessories Standby battery inter connection lead N 41 796 44 12V
3. cccccsseececcseseecceeseeecseseeeseseeecsueeecsaececsaeeesssseeessageeessageees 22 6 7 Programming the Alarm Activation TyP ccccccsssecccsseeeeeceeseeeeeeeseeseeaeeeeseaueeesaaeeeessaneessnaaeess 22 6 8 Setting Zones to Non Latching Operation ccccccccsssseeeccceeeeceeeeseeeceeeeeseeeeseeeeeeesesaaaneeeeeeees 22 6 9 Setting ZONES into Test MOCEC ccccccccccecesesseeeeeceeeeeaeeseceeeeeeeeeeeseseceeeesssueeseeeeeeeessssaaeseeeeees 23 6 10 Delaying the Alarm Output ACtiIVAtION ccccccccsseeeeeeeeeeeeeeeeeeseeeeeeeesseeeeeeesaaeseeeesseaeeeeeeaaaees 23 6 11 Setting Zones into Coincidence Double Knock Operation ccccccccsseseceeeeeeseeeeeeseeeeeeees 24 6 12 Configuring the Volt Free Contact Normal State ccccccccccccccssssseeeeeeeeeseeeeeeeeeeeeesssueaeeeeeeeess 25 6 13 Configuring Alarm Output Trigger Source ccccecccccceseeeeeeeeeeeeeeeeesaeueeeeeeeseaeeeeeesseaeeeeessaaaeeees 25 6 14 Configuring the Detection Circuit End of Line Type ccccceeeccceecessseeeeeeeeeeeeeeeeseeeeeeessaaaeeees 25 7 0 3500 TECHNICAL SPECIFICATION sist cccisssccctecsnet ess cstsccieascb ecu ssicevincoast sun ssvavawescasi ni vavuedsantessvanoeats 26 APPENDIX 1 LIST OF 3500 SPARES AND ACCESSORIES ccccceeeeeeeeeeeeeeeeeeeeeeesseeeneeeeeeeeeeeees 28 APPENDIX 2 3500 CONTROLS INDICATIONS AND CONNECTIONS cc cccceetteeeeseeeeeeeeeeeneeneeeeeeeenns 28 N93 586 84 Issue 04 AB P
4. to increment delay between 1 and 10 minutes The delay is indicated by the time in minutes number of flashes shown on the Outputs Delayed indicator 5 flashes 5 minutes for example Press button 4 to disable delays Disables the delay on the selected alarm outputs Press Enter button to save and exit Saves current settings into memory and exits the menu N93 586 84 Issue 04 AB Page 23 of 32 Protec Fire Detection plc 2015 PA Protec Protec Fire Detection plc 6 11 Setting Zones into Coincidence Double Knock Operation Two or more zones may be programmed into coincidence groups In this mode two or more of the programmed zones must trigger in order to activate the alarm outputs If only one zone in the coincidence group triggers the 3500 will flash the relevant zone fire indicator sound the internal buzzer and activate the global fire contacts The user may then investigate the cause of the alarm and manually activate the alarms in necessary Operation of a Manual Call Point on a zone programmed as coincidence will immediately activate the alarm outputs Sequence C Enter the access level 3 code Access Level indicator flashes Press button 4 to enter the Zone 1 indicator flashes coincidence menu Any currently coincidence zones illuminate steady Cycles through zones to be programmed into coincidence Press button 2 or 3 to cycle round selected zone flashes relevant indicator Choices are zones
5. 3 3Ah VRLA battery Online OL3 3 12 N 13 120 24 3500 8 zone spares kit N 62 807 SPARES 3500 user manual N 93 571 87 3500 Installation amp commissioning manual this manual N 93 586 84 Appendix 2 3500 Controls Indications and Connections The diagram below shows the 3500 Control PCB housing and highlights the main connections and controls Global fire Detection zones contacts Main Global fault Class Change conventional ains cable restraint Monitored RS485 Monitored Communications Auxiliary 24V contacts input alarm outputs output J o h ac mains input supply connections MIAIIIIDI DMA DDDDDDDDODDODAA 00000000 ID I ihe li en Place l Pla leila tl bl te biti yl ol ee ne aOR aaa ela Tol9 gt pramelol Tol Te Fat ARE cuass RELAY RELAY CHANGE ZONE CONNECTIONS ALARM RS485 3508 Fire Alarm Control Panel Configuration links RON Firemans access level 2 keyswitch input Specific models only N93 586 84 Issue 04 AB Page 28 of 32 Protec Fire Detection plc 2015 C1 Protec Protec Fire Detection plc Eee N93 586 84 Issue 04 AB Page 29 of 32 Protec Fire Detection plc 2015 C1 Protec Protec Fire Detection plc Eee N93 586 84 Issue 04 AB Page 30 of 32 Protec Fire Detection plc 2015 C1 Protec Protec Fire Detection plc Eee N93 586 84 Issue 04 AB Page 31 of 32 Protec Fire Detection plc 2015 Protec Fire Dete
6. Individual zones gt all zones Press button 1 to enable Relevant indicator changes to steady coincidence mode Press button 4 to disable Relevant indicator turns off coincidence mode Press Enter button to save and exit Saves current settings into memory and exits the menu N93 586 84 Issue 04 AB Page 24 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 6 12 Configuring the Volt Free Contact Normal State The quiescent state of the 3500 Volt free contacts may be configured to be Normally Open or Normally Closed Table 6 0 shows how setting the configuration links changes the operation The Volt free contact configuration is setup by setting the front panel configuration links as follows Sequence Remove panel door see section 5 2 Reveals configuration link aperture See figure 5 0 Jumper 1 or 2 in ON position to configure normally closed Using an appropriate tool alter contacts jumper 1 or 2 see figure 5 0 Jumper 1 or 2 in OFF position to configure normally open contacts i ri Ee palengeor tees ecellel Hides configuration link aperture Table 6 0 Aux fault contact state configuration Global Fire Contacts Link J2 Global Fault Contacts Link J1 Jumper Link Configuration In Fire Not In Fire In Fault Not in Fault 6 13 Configuring Alarm Output Trigger Source The 3500 can be configured to activate the alarm outputs differently depending on the type of zon
7. spares kit 2 0 Introduction and Key Features The 3500 is a conventional fire alarm control panel available in 2 4 and 8 zone models The 3500 incorporates an integrated power supply two fully monitored alarm circuits and a facility for an optional repeat panel connection The 3500 includes many programming and configuration features making it easy to integrate to a variety of site conditions The 3500 is primarily designed to drive Protec 3000PLUS detection devices The 3500 has been designed and manufactured in the United Kingdom and complies fully with current standards dictating fire alarm system design practice EN54 parts 2 and 4 The integrity and reliability of a fire alarm system is paramount and consequenily the 3500 continually monitors all critical paths for faults The fire detection zones and wiring are constantly monitored to check for faults The integrated power supply regularly performs self checks to ensure it is fully working and that the stand by batteries are in a good state Any alarms or faults detected are reported clearly on the front panel display Key Features e 2 4 or 8 detection zones available e Two fully monitored conventional alarm outputs rated at 400mA per circuit e Integrated on board power supply e Internal standby batteries e Attractive enclosure e Comprehensive range of engineering functions including Programmable zone disablements Programmable alarm output disablement Programmable non latching zone o
8. C1 pote 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION AND COMMISSIONING MANUAL 3500 Fire Alarm Control Panel q CoC 9 OC 9 6 _9 O 9 C 9 6 O C oO 6 8 A Prote Se Protec Fire Detection PLC Protec House Churchill Way Nelson Lancashire BB9 6RT Telephone 44 0 1282 717171 Fax 44 0 1282 717273 Web www protec co uk Email sales protec co uk y Protec Protec Fire Detection plc Document Revision Details issue Modification Detail Author Date 22 11 2013 Refer to ECN3503 14 05 2014 Refer to ECN3549 05 08 2014 Refer to ECN3615 01 12 2014 Refer to ECN3715 07 04 2015 N93 586 84 Issue 04 AB Page 2 of 32 Protec Fire Detection plc 2015 Prote J C Protec Fire Detection plc Table of Contents IMPORTANT NOTES PLEASE READ CAREFULLY sssssssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnen 4 1 0 ITEMS SUPPLIED WITH THE 3500 csecsccsvacensccssesccsevreeesennstoast ve cutovoseevccurenguevueusussenrecuduosesmenieeeuveueusaws 5 2 0 INTRODUCTION AND KEY FEATURES nonaaannnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nn nnnnnnnnn nnmnnn 5 3 0 3500 GENERAL CABLING REQUIREMENT cccccccsssssssseeeeesscccesssseeeeeseeceensseeeeeeesecoesnnseeeneseaoes 6 3 1 Zone Alarm and Auxiliary Circuit Wiring cccccccccccseseeeceeeeeeeeeeseeeseeeeeeseeseeesaaeeeeseaeeeessaeeeesaaes 6 3 2 Alarm Circuit Wiring ete sere seri dicate Mecrmenstdea
9. age 3 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc Important Notes PLEASE READ CAREFULLY e Both the 3500 user manual and this manual should be thoroughly read and understood before installation and commissioning is undertaken e The 3500 and its associated connections must be installed commissioned and maintained by a suitably trained skilled and competent person e It is assumed that the person commissioning the system is aware of Protec Fire Detection equipment terminology and terms of reference e This equipment must be earthed and earth continuity must be preserved on broken segments of screened cable used anywhere in the system installation e This equipment is not guaranteed unless installed and commissioned in accordance with current national standards e This equipment is not suitable as part of an I T type power distribution system as defined in IEC60364 3 e It is perfectly normal for sealed lead acid batteries to vent small amounts of hydrogen when being charged The 3500 is vented to dissipate any build up of hydrogen The 3500 enclosure must not be sealed in any way e A competent person trained to undertake such work MUST carry out any internal maintenance There are no user serviceable parts inside the 3500 Opening the PCB housing will immediately invalidate the warranty Protec Fire Detection plc Nelson Lancashire England BB9 6RT 13 PFD CPR 0075 3502 Fire Alarm Contro
10. ally Open 3 Configure Sounder Activation Global Sounder 1 Call Point Sounder 2 Detector Configure Zone EOL N93 586 84 Issue 04 AB Page 19 of 32 Protec Fire Detection plc 2015 Protec Fire Detection plc 6 2 Programming Zone and Alarm Disablements This menu allows the user to disable any or all of the detection zones and or both of the alarm circuits activations and faults are inhibited when the circuit is disabled Sequence C Enter the access level 2 code Access Level indicator illuminates steady Disablement indicator flashes Zone 1 indicator flashes Any currently disabled zones or alarms illuminate steady Press button 1 to enter the disablement menu Cycles through disablement choices selected choice flashes the relevant indicator Choices are Individual zones gt all zones gt alarms iia 1 to disable current Relevant indicator changes to steady Press button A to enable current Relevant indicator turns off choice Press Enter button to save and exit Saves current settings into memory and exits the menu 6 3 Enabling Weekly Test Mode The 3500 allows all zones to be programmed into weekly test mode this permits rapid verification of device operation on zones Press button 2 or 3 to cycle round disablement choices In this mode activations from zones sound the alarms for 10 seconds for verification purposes after which the 3500 automatically resets and exits weekly test mo
11. atteries must be connected in series with the battery link provided Observing correct polarity red lead to the positive of one battery and black lead to the negative of the other battery carefully push the spade connectors of the 3500 battery leads onto the battery terminals illustrated in figure 5 4 Please note that at this point the 3500 will not power up until the mains supply is connected Figure 5 4 Standby battery connections BLACK battery lead RED battery lead Observe polarity when connecting the battery leads N93 586 84 Issue 04 AB Page 12 of 32 Protec Fire Detection plc 2015 Proteg Pld Protec Fire Detection plc 5 8 5 9 Refitting the Control PCB Housing Ensure that all cable earth connections are sleeved to insulate them and then securely connect them to the brass earth terminals in the back box Carefully route the battery leads from the rear of the control PCB housing down between the two batteries If the 3500 is equipped with a fire brigade panel controller ensure the ribbon cable connected to the back of the control PCB housing is located over the top of the control PCB housing when refitting into the back box Replace the control PCB housing a reversal of removal ensuring it is pushed flush to the back box and that the battery leads do not get trapped Secure with the four screws removed previously taking care not to over tighten the screws Connecting the Detection Zone Wi
12. ction PLC Protec House Churchill Way Nelson Lancashire BB9 6RT Telephone 44 0 1282 717171 Fax 44 0 1282 717273 Web www protec co uk Email sales protec co uk
13. de If no zone activations are detected for 10 minutes weekly test mode is automatically exited Sequence C Enter the access level 2 code Access Level indicator illuminates steady Activates weekly test mode Test indicator illuminates Zone test indicators illuminate Press button 2 to activate weekly test mode Exits weekly test mode Test indicator extinguishes Zone test indicators extinguish Press button 2 to exit weekly test mode 6 4 Testing the Panel Indications and Internal Buzzer The 3500 allows the front panel indications and internal buzzer to be tested In this mode all indicators are momentarily illuminated and the internal buzzer sounded If any indicators fail to illuminate or the buzzer does not sound note this in the system log and get the fault rectified immediately Sequence fet SSCS Enter the access level 2 code Access Level indicator illuminates steady Press button 3 to activate the lamp All indicators momentarily illuminate and the internal buzzer and buzzer test sounds N93 586 84 Issue 04 AB Page 20 of 32 Protec Fire Detection plc 2015 PA Protec Protec Fire Detection plc 6 5 Clearing System Faults In general faults on the 3500 are non latching and will clear automatically when the fault is rectified Some faults however are latched on the system and require clearing manually Sequence C Enter the access level 2 code Access Level indicator illumi
14. e silenced and reset manually Activations from a zone programmed as non latching automatically reset the 3500 when the zone returns from fire to non fire condition Activations from non latching zones DO NOT operate the global fire contacts Sequence C Enter the access level 3 code Access Level indicator flashes Press button 1 to enter the Zone 1 indicator flashes non latching menu Any currently non latching zones illuminate steady Cycles through zones to be programmed into non latching Selected zone flashes relevant indicator Choices are Individual zones gt all zones Press button 2 or 3 to cycle round zones Press button 1 to enable non latching mode Press button 4 to disable non NP Relevant indicator turns off latching mode Press Enter button to save and exit Saves current settings into memory and exits the menu Relevant indicator changes to steady N93 586 84 Issue 04 AB Page 22 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 6 9 Setting Zones into Test Mode The 3500 permits zones to be programmed into walk test mode Activations from zones in walk test mode activate the alarm outputs for 10 seconds after which the 3500 automatically resets Activations from a zone not in test mode will operate as normal Activations from zones programmed as walk test DO NOT operate the global fire contacts Sequence Efet OSS Enter the access level 3 code Acc
15. e trigger manual or automatic The settings are changed by altering the jumper link configuration as follows Sequence C Ect Remove panel door see section 5 2 Reveals configuration link aperture See figure 5 0 Jumper 3 in ON position to configure global activations U AAPPO prag jeokanet Jumper 3 in OFF position to configure separate automatic jumper 3 see figure 5 0 a and manual activations i vn Ee Pane AOO eee SERLO Hides configuration link aperture 6 14 Configuring the Detection Circuit End of Line Type The 3500 can accommodate resistive or capacitive end of line EOL termination This applies to all zones of the panel and cannot be configured on a zone by zone basis The EOL type is setup by setting the front panel configuration links as follows Sequence Remove panel door see section 5 2 Reveals configuration link aperture see figure 5 0 Using an appropriate tool alter Jumper 4 in ON position to configure capacitive EOL jumper 4 see figure 5 0 Jumper 4 in OFF position to configure resistive EOL E Ee Panevaney EEREN Hides configuration link aperture N93 586 84 Issue 04 AB Page 25 of 32 Protec Fire Detection plc 2015 Protec Protec Fire Detection plc 7 0 3500 Technical Specification General Specification Ambient Temperature Range 5 to 40 degrees Celsius Humidity Limit 95 RH no condensation or icing EP HVicaninent Meets IP30 if mount
16. ed in a dry position that does not exceed the temperature and humidity limits given above 3 points surface mount or flush no extra bezel required when flush mounting 72 hours typical Standby Time 8 zones loaded with 25 3000PLUS OP devices 800mA alarm load for 30 minutes Power Supply Specification Rated Voltage 100 to 240V acrms Rated Frequency 50 to 60 Hz Rated Current 600mA rms Maximum Inrush Current 20A at 240V from cold 452mA 22mA panel 5mA zones 150mA Aux 24V 275mA battery charge Maximum Quiescent Load Imax_a 177MA 22mA panel 5mA zones 150mA Aux 24V 1026mA 48mA panel 28mA zones 800mA alarm 150mA Aux 24V PEELA Esteli Lee ie e Note Batteries are not charged during an alarm condition a E EA 22mA panel normal 30 seconds after a mains failure i P y 48mA panel in alarm 30 seconds after a mains failure Mains Input Fuse 1 6A time delay not user or engineer replaceable Se ere Battery Under Voltage Fault Level 22V dc Battery Monitoring Charger dip battery load and internal impedance Maximum Battery Resistance Ri 2Q battery internal resistance lead and connection resistances Note 1 5mA comprises 8 fully loaded zones of Protec 3000PLUS OP detectors N93 586 84 Issue 04 AB l Page 26 of 32 Protec Fire Detection plc 2015 Protec Protec Fire Detection plc Detection circuit specifications Number of detection zones 2 3502 4 3504 8 3508
17. eeeeeeeeaeeeeeessaaeeeeessaaeeeessaaaeeees 14 5 10 Connecting the Auxiliary WIriINQ cccccsseeeceeeceeeeeeeeeceeeeeeeeesaeaeeceeeesaeseeeeesseaeeeeeessaaeeeeessaaaeeeess 14 5 11 Connecting the 3500 Repeat Panel cccccccccccccecccseesseeeeeeeeeseeeeeeeceeesessaaesseeeeeeesssaaeeeeeeeees 15 5 12 Connecting the Mains Cabling ccccccccsssssssseeceeeeseeeeeeeceeeeeeseeeeseeceeeesssuaeaeeeeeeesseaaaeeeeeeees 16 5 13 Connecting the Fire Brigade Panel Controller cccccccccccccccseesseesseeeceeeeeeeeeeeeeeeeeeesssaeaeseeeeess 16 5 14 FSH UNS LI OOM rE A EE N EE E EAE TE T E A E T 17 5 15 Switching the Mains Power ON ccccccsseeceececeeseeeeecceeesecececaeaseceeeeaaeeeeeessaaeeeesesseeeeeessaaageeess 17 6 0 COMMISSIONING THE 3500 nnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn nnn nnnnnnnn nnmnnn nnmnnn mnnn 18 6 1 PCC SS EEVEE E E E E A E 18 6 2 Programming Zone and Alarm Disablements cccccccccsseeeeceeeeeeeeeeeeeesaeseeeseeeeeessaneeesaaeeees 20 6 3 Enabling Weekly Test MOd ccccccccccccseeeeeeeeeeeeeeeeeeeeeeeeeesessaesceeesseaeeeeeesaaaseeeessaaeseeessaaaes 20 6 4 Testing the Panel Indications and Internal BUZZEef cccccseeeeceeeeeeeeceeeeeseeeeeeeaeeeeesaaeeeenaees 20 6 5 Clearing System Faults ciwsevinsinosucwaicanscnvveraunanes conse adiueay svsdvawbiud doxatdswoaanaitunwentveieant twadamcotdvaneny 21 6 6 Disabling the Internal BUZZEM
18. er information on cables wiring and other interconnections please consult clause 26 of BS5839 part 1 Alarm Circuit Wiring Two alarm circuits are provided on the 3500 Each alarm output can provide 400mA of current and must be terminated with the correct value end of line resistor even if the alarm output is not used The gauge of the alarm circuit wiring must be chosen such that the volt drop along the wiring does not exceed specified limits The maximum wiring resistance may be calculated using the following formula Rwiring_ max 20 5 V device min ldevice max Where Rwiring max iS the maximum resistance of the alarm circuit wiring both conductors Vievice min IS the minimum Voltage the alarm circuit devices are specified to work down to ldevice max IS the maximum total current that will be drawn on the alarm circuit For example if alarm devices are specified to work to a minimum of 16V and the maximum alarm circuit current is 80mA the maximum alarm cable resistance is 56 250 28 130 per conductor Alarm devices must not be connected on spurs from the main alarm circuit wiring as All devices connected to the alarm circuits must be polarised and suppressed A a spur will not be monitored for open circuit faults Mains Input Rating Label The mains rating label is located on the inner door of the 3500 and should be consulted before starting installation The label details the working voltage frequency and maximum cur
19. ess Level indicator flashes Test indicator flashes Zone 1 indicator flashes Any current walk test zones illuminate steady Press button 2 to enter the walk test menu Cycles through zones to be programmed into walk test Selected zone flashes relevant indicator Choices are Individual zones gt all zones Press button 1 to enable walk test Relevant indicator changes to steady mode Press button 4 to disable walk test p elevant indicator turns off mode Press Enter button to save and exit Saves current settings into memory and exits the menu 6 10 Delaying the Alarm Output Activation Press buttons 2 or 3 to cycle round zones An output delay may be programmed if required In this mode a delay is introduced from detection of a zone activation to activating the alarm outputs The delay DOES NOT apply to the global fire contacts which will operate immediately Sequence C Enter the access level 3 code Access Level indicator flashes Outputs Delayed indicator illuminates Zone 1 indicator flashes to show Alarm output 1 is selected Any currently delayed alarms illuminate steady Press button 3 to enter the delays menu Cycles through delay choices Selected alarm flashes the relevant zone indicator Choices are Individual alarms gt all alarms Press button 2 or 3 to cycle round the alarm outputs to be delayed Repeated presses of this button increase the delay Press button 1
20. etector circuits e Disablement of alarm circuits e Programming weekly test mode all Zones in walk test mode e Testing the front panel indications and internal buzzer e Clearing of system faults Access Level 3 Engineer Controls Only engineers are permitted access to level 3 functions these are e Silencing an alarm condition e Resetting the panel after an alarm activation e Disablement of the internal buzzer e Programming pulsing or continuous alarm activation e Programming of non latching zones e Programming of test zones one or more zones may be programmed e Programming of output delays e Programming of coincidence zones N93 586 84 Issue 04 AB Page 18 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc Access Level 4 3500 cover removed tool required e Configuration of global fire relay contact state normally closed or normally open e Configuration of global fault relay contact state normally closed or normally open e Configuration of alarm output activation type e Global configuration of End of Line type capacitive or resistive Configuration of panel at access level 4 is carried out using the locations of 4 links accessible with the panel door removed shown in figure 6 0 see appendix 2 Figure 6 0 Panel Configuration Links ON OFF ROD Configure Aux Fault Relay Contacts Normally Closed Normally Open Configure Aux Fire Relay Contacts Normally Closed Norm
21. indaudhoainaicte codec nelnceena nies nied aaa Sineiaeninsqiediebelsiuionemeacielamanhaemaaisanenicadatend 6 3 3 Mains Input Rating Label cc ceccccccceccssseeeeeeeeeseceeeeeeeseceeeeeeeeseeeeeseeueeeeessaeseeeeessaeeeeeeessaeeeees 6 3 4 IT UUNS VV MAA POPA 6 4 0 INSULATION TESTING OF CABLING PRIOR TO CONNECTION cccccsssssssseeseeeesecceesseneeeeeseeees 7 50 INSTALLING THE 3500 cscs crc tases cee eee coronene aee aa aiaa 8 5 1 Binjo AGM p E E E S PE T E E E E A E 8 5 2 Removal of the DOOP cccccccseseeeeceeeeeeeceeeeeeeseeeeeeseaseeessaeeeeeseaeeeeseaueeessaeeeesaneeeesseeeesseseeesaageees 8 5 3 Removal of the Control PCB HOUSING ccccccccsseeeceeeeaeeeeceeeeaeeseeeeesaeeeeeeeeeaaaeeeeesaaeeeeeesaaees 10 5 4 Preparing the Mounting Position and Cable Entries ccccccsccecececseseeeeeeeeeeeeeeeeeeeeeeeeeseaaaees 11 5 5 Installing the Standby Batteries cccccseccceeecseeeeceeeeaeeeeeeeesaeeeeeeeeseeaeeeeesaeaeeeesseeeeeesesaaaes 11 5 6 Connecting the Standby Batteries cccccccccccssseeeceeceeeeeeeeeeeeeeeeeeeeeeeeeeeeseaeeeeeeeseaeeeeeesaaaeeeees 12 5 7 Refitting the Control PCB Housing ccccsseeecceeceeeseceeeeeeeeeeeeeeaeeeeeeeeseaaeseeeesuaeseeeeesuaeeeeesssaaaes 13 5 8 Connecting the Detection Zone WILING ccccccseeeeccccceeeeeeeeeeseeeeceeeesaeseeeeeeseaeeeeessaaeeeeesssaaeeees 13 5 9 Connecting the Alarm Circuit Wiring ccccccccesseeceeeceeeeeceeeceees
22. l Panel PFD CPR 0076 3504 Fire Alarm Control Panel PFD CPR 0077 3508 Fire Alarm Control Panel BS EN 54 2 1997 A1 2006 BS EN 54 4 1997 A1 A2 2006 Control Indicating and Power Supply equipment for fire detection and fire alarm systems for buildings 3500 Fire Alarm Control Panel Control amp Indicating Performance under fire conditions Pass Response delay response time to fire Pass Operational reliability Pass Durability of operational reliability Temperature resistance Pass Durability of operational reliability Vibration resistance Pass Durability of operational reliability Electrical stability Pass Durability of operational reliability Humidity resistance Pass Power supply Performance of power supply Pass Durability of operational reliability Temperature resistance Pass Durability of operational reliability Vibration resistance Pass Durability of operational reliability Electrical stability Pass Durability of operational reliability Humidity resistance Pass The policy of Protec Fire Detection plc is one of continuous improvement and as such we reserve the right to make changes to product specifications at any time and without prior notice Errors and omissions excepted N93 586 84 Issue 04 AB Page 4 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 1 0 Items Supplied with the 3500 e User manual e Installation and commissioning manual this manual e 3500
23. lush mounted no extra bezel is required when flush mounting The 3500 circuit board is fully enclosed within a sealed control PCB housing The control PCB housing must not be opened If the 3500 requires repair it must be sent back to the distributor from where it was purchased The standby batteries are fully accessible with the control PCB housing removed from the enclosure The 3500 must be located internally in an area that is not subject to dampness extremes of temperature or physical abuse The environmental limits are given in section 7 0 5 1 Unpacking Carefully open the cardboard carton do not use a sharp object and remove the packing fitments manuals and spares pack 5 2 Removal of the Door Remove the 3500 from the packaging then using a T15 Torx type security tool unscrew but do not withdraw the fixing screw from the bottom of the panel housing front as shown in figure 5 0 stage 1 Slide the door upward from the bottom and pull away as shown in figure 5 0 stages 2 and 3 Put all removed parts in a safe dry place Figure 5 0 Removing the 3500 door N93 586 84 Issue 04 AB Page 8 of 32 Protec Fire Detection plc 2015 c1 Protec ttt 5 3 Disconnection of the Fire Brigade Panel Controller If the 3500 is equipped with the optional fire brigade controller ensure that the ribbon cable and earth cable are disconnected from the rear of the controller as shown in figure 5 1 Figure 5 1 Removing the 3500 door
24. nates steady Press button 4 to clear any latched Any latched faults are cleared If the fault remains it will be faults re generated N93 586 84 Issue 04 AB Page 21 of 32 Protec Fire Detection plc 2015 Protec Fire Detection plc 6 6 Disabling the Internal Buzzer The internal buzzer of the 3500 may be disabled to suit local site requirements Sequence efet SS Enter the access level 3 code Access Level indicator flashes Press Mute Buzzer button to toggle n a between buzzer disabled enabled Disablement indicator illuminates if buzzer is disabled 6 Programming the Alarm Activation Type The alarm outputs of the 3500 can be configured to turn on continuously or pulse when the 3500 is activated The alarm activation type is configured as follows Sequence C Enter the access level 3 code Access Level indicator flashes The Alarm Fault indicator will illuminate steady if the alarms are set to continuous or flashing if the alarms are set to pulse P ma button 1 to program Alarm Fault indicator illuminates steady continuous alarms Pee O ate OAT pulsing Alarm Fault indicator flashes alarms Press Enter button to save and exit Saves current settings into memory and exits the menu 6 8 Setting Zones to Non Latching Operation Press Sound Alarms button to enter the menu Standard zone operation is latching activations from latching zones require the 3500 to b
25. panels supplied from an external EN54 4 power supply unit The connections for the repeat panel are optional and if not used do not require any termination The 3500 repeat panel is mounted using the same process followed for mounting a 3500 control panel Ensure that the correct polarity is observed when wiring the 24V supply to the 3500 repeat panel The RS485 is connected from the A terminal of the host panel to the A terminal of the repeat panel and the B terminal of the host panel to the B terminal of the repeat panel The connections are shown in figure 5 8 Figure 5 8 Typical wiring diagram To further repeat panels Ce A fap Eea 24V OV A B 24V OV A B 24V OV A B 3500 3500 3500 Control Repeat Repeat Panel Panel Panel When carrying out commissioning of the 3500 control panel ensure that the 3500 repeat panels mimic the display of the 3500 Ensure that if the if the repeat panel is locally muted the buzzer resounds upon the activation of an additional fault or fire For further details regarding a 3500 repeat panel refer to DEL2129 supplied with the unit N93 586 84 Issue 04 AB Page 15 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 5 13 Connecting the Mains Cabling Isolate the incoming mains supply by ensuring the fused double pole isolator is in the OFF position Pay particular atten
26. peration Programmable coincidence zone operation Programmable output delay per alarm 0 to 10 minutes in 1 minute steps Weekly test feature Zonal walk test feature Pulsing or continuous alarm output activation Manual or automatic detection alarm output activation e Keypad user code or fireman s key switch access options correct model must be ordered e Ability to distinguish if a zone activation is from an automatic detector or a Manual Call Point e Class Change input e Global fault and fire Volt free contacts e UK designed and manufactured Note 1 The MCP must contain a series 180Q resistor for this feature to operate N93 586 84 Issue 04 AB Page 5 of 32 Protec Fire Detection plc 2015 Proteg Pid Protec Fire Detection plc 3 0 3 1 3 2 3 3 3 4 3500 General Cabling Requirements Zone Alarm and Auxiliary Circuit Wiring All wiring associated with the system must conform to the current I E E Regulations and cabling must conform to the relevant BS specifications ECA recommended cable separation for electromagnetic compatibility in buildings must be followed To comply with EMC regulations Protec recommends the use of screened cabling throughout the installation Where screened cables are used it is important to ensure that screen continuity is maintained between cable segments Any screen wiring in the 3500 panel enclosure must be sleeved and securely bonded to the earth terminals provided For furth
27. rent of the 3500 Mains Wiring The 3500 requires a mains supply exclusive to the panel that uses fixed three core wiring between 0 75mm and 2 5mm which is fed from a double pole isolating fused spur fused at 3A Unauthorised operation of the mains supply must not be allowed and the fused spur should be labelled FIRE ALARM PANEL DO NOT SWITCH OFF Mains wiring must be segregated from all other system wiring The wiring clamp must be used to secure the incoming cables N93 586 84 Issue 04 AB Page 6 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 4 0 Insulation Testing of Cabling Prior to Connection Before connecting any external cables to any field device or the 3500 tests should be carried out using a 500V DC insulation tester Megger If tests are performed the insulation readings between each cable core and each cable core and earth must be greater than 10MQ The 3500 or associated devices must not be connected to any cables when high voltage insulation tests are being performed on the cabling The cabling must be completely discharged prior to connection to the 3500 Equipment connected to the cabling during insulation tests will be damaged by the high voltages used invalidating any warranty N93 586 84 Issue 04 AB Page 7 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 5 0 Installing the 3500 The 3500 may be surface or f
28. ring Ensure the detection circuit wiring conforms to the specifications in section 7 0 of this manual Figure 5 5 shows typical connections for the detection zone wiring Connect the end of line EOL device resistor or capacitor depending on requirements across the terminals of the last device on the zone circuit Wiring spurs must not be connected from the main zone wiring as the spur WILL NOT be monitored for open circuit faults To ensure compliance with BS5839 part 1 each detector base must include a series low voltage drop diode This ensures that Manual Call Points following a removed detector still function correctly Protec 3000PLUS BASE and 3000PLUS FFBASE products incorporate the diode as standard Figure 5 5 Typical 3500 Detection Zone Connection Zone Connection Manual Call Point N93 586 84 Issue 04 AB Page 13 of 32 Protec Fire Detection plc 2015 Protec or Protec Fire Detection plc t 5 10 Connecting the Alarm Circuit Wiring 5 11 The 3500 has two alarm circuit outputs each output is rated for continuous use at 400mA and protected from over load by an auto resetting thermal fuse The fuse will reset when the cause of overload has been removed and the alarm output has been de activated Ensure the alarm circuit wiring conforms to the specifications in section 7 0 of this manual Figure 5 6 shows typical connections for the alarm circuit wiring Connect the end of line EOL resistor acros
29. s at the required cable entry positions and mount the enclosure in position whilst feeding the cables into the enclosure via suitable glands The mains cable entry position must be segregated from all other system cabling a reserved knock out is provided specifically for this purpose A four way brass earth block is supplied within the 3500 Three locations are provided for this in the 3500 back box This allows the best location to be selected depending on wiring entry requirements Choose the location then clip the earth block into the back box ensuring it is securely fitted Installing the Standby Batteries The 3500 is designed to house two 12V 3 3Ah Valve Regulated Lead Acid VRLA batteries These fit into the back box and must be secured with the two plastic tie wraps provided as shown in figure 5 3 Only use batteries supplied or recommended by Protec The internal charger has been specifically designed to maintain the charge voltage at an optimum level for these batteries over the entire operating temperature range in order to maximise the life of the batteries Figure 5 3 Installation of 3500 standby batteries shown with the lid and control PCB housing removed N93 586 84 Issue 04 AB Page 11 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 5 7 Connecting the Standby Batteries The two standby b
30. s the terminals of the last device on the alarm circuit Wiring spurs must not be connected from the main wiring as the sour WILL NOT be monitored for open circuit faults Failure to use polarised sounders can result in an alarm circuit fault f Only polarised and suppressed sounders can be used on the 3500 alarm circuits All Protec conventional sounder devices are polarised and suppressed as standard Figure 5 6 Typical 3500 Alarm Circuit Connection Details ALARM1 FOL or Resistor ALARM2 Wiring spurs are not permitted Connecting the Auxiliary Wiring The auxiliary wiring comprises the class change input auxiliary 24V supply output global fire contacts and global fault contacts Note that these connections are optional and if not used do not require any termination Ensure the auxiliary wiring conforms to the specifications in section 7 0 of this manual Figure 5 7 Auxiliary Connection Details 24V P E Maximum 150mA CLASS Load CHANGE OV ovi Auxiliary 24V Output Connection Class Change Input Wiring N93 586 84 Issue 04 AB Page 14 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection plc 5 12 Connecting the 3500 Repeat Panel The 3500 can support additional repeat panels allowing the state of the system to be monitored from alternative locations The 3500 control panel can support up to 5 3500 repeat panels supplied from the auxiliary 24V supply output or up to 10 3500 repeat
31. tion that the incoming mains cable is segregated from all other cables within the 3500 enclosure Ensure the incoming earth cable is firmly connected to the Main PCB see figure 5 9 and the earth cable from the Main PCB is securely connected to the brass earth terminals within the back box The mains wiring must now be restrained using the clamp provided to secure the mains cables to the control PCB housing see figure 5 10 The restraining clamp must be supported at the rear when the two screws are being tightened Figure 5 9 Power Supply Terminal Details Hoo CE Main PCB to earth block cable Figure 5 10 Mains wiring connections Mains wiring clamp 000000044 EE ASI i lt ARI N93 586 84 Issue 04 AB Page 16 of 32 Protec Fire Detection plc 2015 y Protec Protec Fire Detection ple 5 14 Connecting the Fire Brigade Panel Controller If the 3500 is equipped with the optional fire brigade controller ensure that the ribbon cable and earth lead are re connected to the rear of the controller as shown in figure 5 11 Figure 5 11 5 15 Re fitting the Door Before replacing the door ensure all mains zone alarm and auxiliary wiring has been completed and will not foul the door when it is refitted Replace the plastic door by raising the door and placing flush to the back box of the panel figure 5 12 step 1 Slide the door down and ensure it pushes fully home into the back box fig
32. ure 5 12 step 2 Finally screw in the fixing screw taking care not to over tighten the screw figure 5 12 step 3 Figure 5 12 Refitting the 3500 door 5 16 Switching the Mains Power On Switch the fused isolator to the ON position The green Power indicator will illuminate the 3500 is now ready to be programmed and commissioned N93 586 84 Issue 04 AB Page 17 of 32 Protec Fire Detection plc 2015 PA Protec Protec Fire Detection plc 6 0 Commissioning the 3500 The 3500 has many programmable features making it extremely flexible These can be accessed by users at different authorisation levels The features available at the different authorisation levels are detailed below 6 1 Access Levels Access Level 1 User code not entered The panel s front panel display indicators are visible providing a clear status of the 3500 at that time The functions that may be performed at access level 1 are e Entry of the 6 digit user code to access level 2 or level 3 functions e Activation of the front panel fireman s key switch correct model must be ordered Access Level 2 User code entered or fireman s key switch activated Only authorised users are permitted access to level 2 functions these are e Accepting the current state of the panel and Mute the panels internal buzzer e Silencing an alarm condition e Resetting the panel after silencing an alarm activation e Sounding the alarms e Disablement of d
Download Pdf Manuals
Related Search
Related Contents
Manual de Instalação Sissy Bar - Drag Star 650 alarma sin cable multi-zonas Nakamichi -- 481 - Bedienungsanleitung Panasonic KX-UT1XX Quick Start Guide Souffleur électrique sans fil M-BL18Li Copyright © All rights reserved.
Failed to retrieve file