Contents
1. STEP 4 750 1000 1500VA D i d e Ar Pe oS J Dag Li 2 i 27 2200 3000VA LA 6 3 Recycling the Used battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery 28 7 Communication 7 1 DB 9 Connector The UPS has a DB 9 9 pin female connector on the rear to allow UPS status communications with a computer running UPS software The connection provides serial communication On Battery and Low Battery signals Table 4 DB 9 pin assignment DB 9 Pin Assignment Description 1 Low Battery open collector 2 UPS TxD 3 UPS RxD 4 N C 5 Common 6 N C T Low Battery open emitter 8 Utility Fail open emitter 9 Utility Fail open collector Pin Assignment Collector to Emitter 29 8 Optional Communication Cards 8 2 SNMP Web Card Ethernet 8 1 DCE Dry Contact card based to UPS 8 2 1 For installation please refer to the user s manual attached with the card 8 2 2 Installation Position Optional Slot 8 1 1 The pin assignments of 10 Pin Terminal 1 2 3 4 4 5 6 7 8 9 10 1 gt N A 2 gt Utility Abnormal 3 gt Utility Normal 4 gt AVR On 5
2. d S o Z o lel LEI ege SSS e Ka CG St YT op sx First connect the UPS with utility power then plug the loads into the 4 a Se a IESSEN f N outlets on the rear of the UPS To use the UPS as a master On Off 2 a JOG E EI 5 E switch make sure that all of the loads are switched on These UPS outlets provide battery backup and surge protection to the equipment when utility voltage is out of specification 6 1 6 2 i hen utility voltage i f specificati Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 5 1 10A Output Circuit Breaker for 6 1 5 2 10A Output Circuit Breaker for 6 2 6 1 IEC 320 C13 Output Receptacles 6 2 IEC 320 C13 Output Receptacles 6 3 IEC 320 C19 Output Receptacles 7 Cooling Vents 15A Input Circuit Breaker 2200 model only 20A Input Circuit Breaker 3000 model only 9 IEC 320 C20 Input Socket 10 REPO 11 Intellislot Port Caution Do not connect a laser printer to the UPS outlets 18
3. UNION A Power Systems Network Pro Series Tower and Rack Mount Convertible UPS User Manual 1000 1500 2200 3000 2 Table of Contents Introduction 2 IMPORTANT SAFETY INSTRUCTION 3 2 1 An Important Notice 3 2 2 Storage Instruction 5 SET UD 6 3 1 Inspection 6 3 2 Place the UPS Properly 6 3 3 Unpacking 7 3 4 Selecting Installation Position 8 3 5 UPS Setup 8 3 6 Tower Setup 9 3 7 Rack Mount Setup 10 3 8 UPS Front Panel 12 3 9 LCD Display Panel 13 3 10 UPS Rear Panel 14 INSTALLATION
4. Input Circuit Breaker 9 NEMA 5 20P Input Power Core 10 REPO 11 Intellislot Port 15 3000VA 120V Now A Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 5 1 15A Output Circuit Breaker for 6 1 5 2 20A Output Circuit Breaker for 6 2 6 1 NEMA 5 15R Output Receptacles 6 2 NEMA 5 20R Output Receptacles 6 3 NEMA 5 30R Output Receptacles 7 Cooling Vents 8 30A Input Circuit Breaker 9 NEMA L5 30P Input Power Core 10 REPO 11 Intellislot Port 16 750 1000 1500VA 230V 11 ata ch ES Bie DI 6 1 Item Description Data Line Connectors Voltage Configuration Switch USB Port RS232 DB 9 Port IEC 320 C13 Output Receptacles Cooling Fan INID AIIN 7A Input Circuit Breaker 750 model only 8A Input Circuit Breaker 1000 model only 10A Input Circuit Breaker 1500 model only IEC 320 C14 Input Socket 10 REPO 11 Intellislot Port 17 2200 3000VA 230V 4 INSTALLATION 9 6 3 8 5 15 2 4 1 Connect Utility and Load 1
5. LED A On Switch Off Switch O Battery Replacement Battery Backup LED Battery Low Go Bypass Utility Low UPS Boost gt 10 Utility High UPS Buck gt 11 UPS Output Indicator LOAD 12 Polarity Error or Ground Fault 13 Overload 9 14 Load Battery Level AN 15 Load Battery Level Indication Control Button ONMNOOKRWH 13 750 1000 1500VA 120V 11 3 10 UPS Rear Panel 1 9 6 1 e el D 0 EWE S oe e a a a a S 0 Cum WQars o Ba o 3 s o ia II II a 8 Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 6 1 NEMA 5 15R Output Receptacles 7 Cooling Fan 8 12A Input Circuit Breaker 750 and 1000 model only 15A Input Circuit Breaker 1500 model only 9 NEMA 5 15P Input Power Core 10 REPO 11 Intellislot Port 14 2200VA 120V 1920VA 1920W for UL 4 3 0 2 8 5 1 5 2 Item Description 1 Data Line Connectors 2 Voltage Configuration Switch 3 USB Port 4 RS232 DB 9 Port 5 1 15A Output Circuit Breaker for 6 1 5 2 20A Output Circuit Breaker for 6 2 6 1 NEMA 5 15R Output Receptacles 6 2 NEMA 5 20R Output Receptacles 7 Cooling Vents 8 30A
6. allows not only the control of the UPS and graceful shutdown when the Utility Fails but also allows the user to remotely test the major operating functions of the UPS communicate via SNMP web network optional card access UPS functions via the web and alert users via SMS messages against specific events User friendly design can easily be installed by end user Plug and play USB RS232 interface conveniently offers a USB or RS232 port for connecting to a computer or other hardware 2 IMPORTANT SAFETY INSTRUCTION 2 1 An Important Notice a The UPS has its own internal energy source battery If the UPS is switched on when no AC power is available there could be voltage at the output receptacles 2 Make sure that the AC Utility outlet is correctly grounded 3 Do not open the case as there are no serviceable parts inside Your warranty will be voided if the case is opened 4 Do not try to repair the unit yourself contact your local supplier or Orion Power Systems Technical support if the unit needs repair o Please make sure that the input voltage of the UPS matches the supply voltage 6 To eliminate any overheating of the UPS keep all ventilation openings free from obstruction 7 Make sure the UPS is installed within the proper environment as specified 0 40 C and 30 90 non condensing humidity 8 Do not install the UPS in direct sunlight 9 The UPS is designed for indoor installation only Do not inst
7. of electrical shock if the UPS is moved while in use 18 SAVE THESE INSTRUCTIONS This Manual Contains Important Instructions that should be followed during Installation and Maintenance of the UPS 19 Symbol for ON Off is displayed and defined 20 Intended for installation in a temperature controlled indoor area free of conductive contaminants 21 Maximum ambient temperature 40 C or 0 40 C for ambient Operating 22 For Model 3000 CAUTION To reduce the risk of fire connect only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code ANSI NFPA 70 23 For Models 2200 1500 1000 and 750 CAUTION To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code ANSI NFPA 70 24 CAUTION RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE DISPOSE OF USED BATTERIES ACCORDING TO THE INSTRUCTIONS 25 Replacement of batteries located ina SERVICE ACCESS AREA A Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions B When replacing batteries replace with the same type and number of batteries or battery packs C CAUTION Do not dispose of batteries in a fire The batteries may explode D CAUTION Do not open or mutilate batteries Released e
8. there is nothing on the LCD go to step 3 2 Press the On Switch on the front panel for approximately 3 seconds until the audible alarm beep sounds then release the On Switch to start the UPS Both the LCD and Utility LED Green are lit The start up procedure is completed and the connected devices are protected by the UPS 3 To cold start the UPS press the On Switch on the front panel for approximately 3 seconds until the LCD lights up and audible alarm beep sounds then release the On Switch The UPS starts operating and the Battery Backup LED Amber lights up The cold start up procedure is completed and the loads are supplied by the UPS 4 The UPS will run under Backup mode with the audible alarm beep sounding every 2 seconds in case of blackout or over under voltage Once normal utility power is restored the UPS will run under Utility mode and the audible alarm will be silenced 5 2 Turn Off the UPS 1 Press the Off Switch for at least 3 seconds to turn off the UPS If you press the Off Switch less than 3 seconds the UPS will not execute the shutdown command The UPS will automatically shut off the output and beep for 5 seconds then completely shut itself down 2 The UPS will automatically shut itself down in case of overload short circuited output or a low battery condition when in Battery Backup mode 5 3 Plug in Charge 1 If the Input Power Cord is connected to the wall receptac
9. 19 4 2 Connect Network Surge protection Connect a 10 base T 100 base T network cable to the RJ 45 network surge protection IN jack on the rear of the UPS Connect from the OUT jack with network cabling to network equipment z fo a 8 SN NEN NON JOH OOOO 4 3 Connect Computer Interface Port Connect the supplied interface cable RS 232 or USB Optional between the interface port on the rear of the UPS and the computer interface port See software installation guide in the CD ROM Optional for installation purpose 20 4 4 REPO Switch The UPS is equipped with an Emergency Power Off EPO switch The user must supply a means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder breaker to interrupt all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations 1 REPO 2 Ground Short Pin 1 and Pin 2 to enable the REPO function 21 5 OPERATION 5 1 Turn on the UPS 1 Connect the UPS to the wall receptacle LCD will display OFF when Utility is normal If
10. 19 4 1 Connect Utility and Load 19 4 2 Connect Network Surge protection 20 4 3 Connect Computer Interface Port 20 4 4 REPO Switch 21 OPERATION 22 5 1 Turn on the UPS 22 5 2 Turn Off the UPS 22 5 3 Plug in Charge 22 5 4 Auto Restart 24 5 5 Alarm Silence 24 5 6 Self Test 24 UPS MAINTENANCE 25 6 1 Battery Replacement 25 6 2 How to Replace Battery 26 6 3 Recycling the Used battery 28 Communication 29 7 1 DB 9 Connector
11. 29 Optional Communication Cards 30 8 1 DCE Dry Contact card 30 8 2 SNMP Web Card Ethernet 31 SPECIFICATIONS 32 9 1 120V 32 1 The Network Pro UPS features a rack tower convertible design single Introduction AVR boost and single buck pure sine wave output user friendly LCD display built in customer option slot hot swappable battery and USB RS232 communications interface The Network Pro provides a flexible rack tower form factor for use with critical file servers minicomputers network switches hubs and other business critical equipment Sine wave output provides clean output power to connected equipment User friendly LCD panel displays system status including load level battery level AVR Boost Buck and fault status for easy monitoring and service 90 high efficiency design when used in Normal mode meets high efficiency energy saving standards and reduces noise and heat User replaceable hot swappable battery design saves time and money by allowing quick battery changes without downtime Cold start function enables UPS to power up without connecting to incoming utility power Optional Communication Software
12. Relative Humidity 0 to 95 non condensing Unit 45 48 77 85 Operating Altitude Up to 10 000 ft 3000m at 95 F 35 C without derating Input AC Parameters Audible Noise lt 40 dBA internal fan s Off lt 40 dBA internal fan s Off Surge Protection 570J lt 45 dBA internal fan s On lt 45 dBA internal fan s On Voltage Range Agency Without 83 159 configurable Safety UL 1778 c UL Listed Battery Operation Surge ANSI C62 41 CatA Lev3 surges Frequency Range 45 65Hz 0 5Hz IEC61000 4 5 Input Power Cord 10ft 3m 10ft 3m 10ft 3m 1 Oft 3m attached ESD IEC61000 4 2 attached attached attached W NEMA L5 30P Susceptibility IEC61000 4 3 w NEMA 5 15P_ w NEMA 5 15P_ w NEMA 5 20P Electrical Fast IEC61000 4 4 Output Receptacles 8 NEMA 5 15R 8 NEMA 5 15R 6 NEMA 5 15R_ 6 NEMA 5 15R Transient 2 NEMA 5 20R 2 NEMA 5 20R Emissions FCC Part 15 Class A 1 NEMA L5 30R Conducted Immunity EN61000 4 6 Voltage Normal 110 120 127 VAC configurable 10 Harmonics ENG10003 2 mode Network surge UL 497 B Voltage Battery 110 120 127 VAC configurable Transportation ISTA Procedure 1A Certification Mode 5 before low battery warning Tanter Time a8 ms typica Runtimes reflect 7 power factor and are approximate Run times may vary depending on aveform Sinewave Frequency battery age temperature etc Normal Mode 45 65Hz 0 5Hz Frequency Battery Mode 50 60Hz 0 5Hz auto sensing Overload Warning Nor
13. UPS will not provide power to the outlets if the if the start up operation is not completed properly Important Notice Plug the UPS onto the wall receptacle to charge the UPS for at least 8 hours after initial installation Storage Store at 15 to 30 C 5 to 86 F charge the UPS battery every three months Store at 30 to 45 C 86 to 113 F charge the UPS battery every two months 24 6 UPS MAINTENANCE 6 1 Battery Replacement When the UPS is started up or a self test is executed the Battery Replacement LED may be illuminated due to a weak or dead internal battery 1 When the Battery Replacement RED LED is illuminated leave the UPS to re charge the battery for at least 8 10 hours Run the self test procedure again to re test the battery 2 If the Battery Replacement RED LED remains illuminated the internal batteries should be replaced Replace batteries following the procedure in Section 6 2 then push the On Switch to reset the UPS and turn off the Battery Replacement light Caution The UPS will not provide power to the outlets if the if the start up operation is not completed properly Caution The battery is heavy pull the battery out onto flat stable surface Caution DO NOT DISCONNECT the batteries while the UPS is operating in Backup mode 25 6 2 How to Replace Battery STEP 2 26 STEP 3
14. all the UPS outdoors or in an environment that is not climate controlled 10 Dusty corrosive and salty environments can damage the UPS 11 Install the UPS away from objects that give off excessive heat and areas that are excessively wet 12 If liquids are spilled onto the UPS or foreign objects are dropped into the unit the warranty will be void 13 The battery will discharge if the system is disconnected from AC power for long periods gt 3 months If left uncharged the battery may require replacement for the UPS to provide battery backup 14 The battery should be recharged every 2 3 months if the UPS is not in service This can be done by plugging in the UPS for a minimum of 8 hours every 2 3 months If this is not done the batteries will need to be replaced this is not covered under the warranty When the UPS is installed and in use the batteries will be automatically recharged and kept in top condition 15 This UPS supports electronic equipment in offices telecommunications process control and non life support medical and security applications The UPS should not be installed in the following areas a Medical equipment directly related to human life support b Elevator Metro Subway system or any other equipment related to human safety c Nuclear power plants 16 Do not install the UPS in an environment with flammable gases 17 Make sure the UPS is completely powered off before moving There is a risk
15. gt Battery Low 6 gt N A 7 gt N A 8 gt Common 9 gt Shutdown UPS positive signal 10 gt Shutdown UPS Negative signal 8 1 2 The shutdown function will be activated after a 6 25Vdc is put between pin 9 and pin 10 for 5 seconds 8 1 3 The capacity of each relay contact is 40Vdc 25mA 8 1 4 Installation Position Optional Slot 8 1 5 Flexible signal output for N C Normal Close or N O Normal Open contact by shorting pin1 2 or pin2 3 form JP1 5 8 1 6 The shutdown function will be enabled in 1 minute after blackout occurs if the pin1 2 of both CN1 and CN6 are shorted by cap Or the shutdown function can only be enabled by pin9 10 of CN3 if the pin2 3 of both CN1 and CN6 are shorted by cap 30 31 9 SPECIFICATIONS Backup Time 9 1 120V 1000VA 1500VA 2200VA 3000VA Model number 750 1000VA 1500VA 2200VA 3000VA Full Load 7m 5m 5m 5m Power Rating VA W 750VA 750W Half Load 19m 16m 16m 16m 1000VA 900W EE Deeg SE Recharge Time 5 hours to 90 of rated capacity after full discharge into resistive load Dimensions W x D x H in Environmental Unit 3 5 2U H x 3 5 2U H x 3 5 2U H x 3 5 2U H x Operating 32F to 104 F 0 C to 40 C 18 W x 18 W x 18 W x 18 W x Temperature kan 17D 26 D 26 D Storage Temperature 5 F to 104 F 15 C to 40 C Weight Ibs
16. le properly and the utility is normal the UPS will start charging the battery automatically The UPS does not have to be powered on to charge the battery 22 2 If the UPS is not in active use charge the battery for at least 8 12 hours every 3 months to keep the batteries in good working condition 23 5 4 Auto Restart After an extended power outage if the Input Power Cord is properly connected to the wall receptacle and Utility power is normal the UPS will automatically restart and restore power to the connected devices and begin recharging the battery 5 5 Alarm Silence 1 The audible alarm beep can be silenced by pressing the On Switch for approximately 1 second while the UPS is in Backup mode 2 Unless any other warning or fault condition occurs the audible alarm will remain silenced once turned off 5 6 Self Test 1 Under Utility Normal condition press the On Switch for 3 seconds to execute the Battery Self test function 2 If the battery is normal the UPS will enter into Battery Backup Mode for 10 seconds then return to Utility Mode 3 If the battery voltage is detected lower than set limit the Battery Replacement LCD will blink for 5 seconds The self test procedure will not be completed If the battery is detected as weak or dead the Battery Replacement LCD will be illuminated Please contact Orion Power Systems Technical Support for battery replacement information Caution The
17. lectrolyte is harmful to the skin and eyes It may be toxic E CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries a Remove watches rings or other metal objects b Use tools with insulated handles c Wear rubber gloves and boots d Do not lay tools or metal parts on top of batteries e Disconnect charging source prior to connecting or disconnecting battery terminals f Determine if battery is inadvertently grounded If inadvertently grounded remove source from ground Contact with any part of a grounded battery can result in electrical shock The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance applicable to equipment and remote battery supplies not having a grounded supply circuit 26 CAUTION Lead acid batteries may cause chemical hazard 2 2 Storage Instruction For extended storage the batteries should be charged for 12 hours every 3 months by plugging the UPS power cord into the wall receptacle and turning on the input breaker on the front panel Repeat this procedure every 2 months if the UPS is stored in a high temperature environment 3 SETUP 3 1 Inspection Inspect the UPS upon receipt Notify the carrier and dealer if there is damage to the shipping carton or the UPS If shipping damage is present please keep all packaging materials until the
18. mal Mode gt 100 109 Continuous Overload Alarm and power to the load gt 110 120 Shutdown after 10 minutes gt 120 Shutdown UPS immediately Battery Mode gt 100 119 Continuous Overload Alarm till end of battery discharged gt 120 130 Shutdown after 10 seconds gt 130 Shutdown UPS immediately Battery Parameters Type Valve regulated nonspillable lead acid 32 33 Orion Power Systems Service and Technical Support If you have any problems or questions with the UPS call your local distributor or Orion Power Systems technical support at the following telephone number In the United States 1 877 385 1654 Please have the following information ready when you call Model number and Serial number Description of failure or problem Date of failure or problem Customer contact information and return address If repair is necessary you will be given a Returned Material Authorization RMA number The RMA number must appear on the outside of the box and on the Bill Of Lading Original packaging should be used if available Systems that get damaged in transit as a result of improper packaging are not covered under warranty A replacement or repair unit will be shipped freight prepaid for all units under warranty NOTE For critical applications immediate replacement may be available 34
19. ment or near any flammable objects 5 This UPS is not designed for outdoor use ei N e Wy A ep H Lp Sa 3 5 UPS Setup The UPS offers a flexible form factor enabling integration into a wide variety of environments The UPS uses a 2U rack tower convertible design for 1KVA to 3KVA systems If you are installing the UPS in a tower continue to the following section Tower setup otherwise continue to Rack Mount setup Relative humidity 0 o non condensation 30 90 ES aa aa an am D DS am am aa DS Step3 3 7 Rack Mount Setup B S Ka H Si Step1 Step4 mma D Di D D D D D Di 4 ES aa ERC aS aa aaa Siar Step2 Ko Q Ka 11 10 3 8 UPS Front Panel O O I T OOO es CH DD gt 12 3 9 LCD Display Panel 718 9 10 11612 5 13 2 14 Utility LED Ze LINE Fault
20. shipping claim has been resolved The package is recyclable save it for reuse or dispose of it properly 3 2 Storage and Operation of UPS The UPS should be stored and operated in a well ventilated and climate controlled low humidity environment 3 3 Unpacking 1 Take the UPS out of the packing foam 2 Remove the packing materials 3 Standard Package includes a User Manual b 1pc x AC Input Power Cord Not available for hard wiring connection models c For 230v International models with IEC connectors the UPS should include 1pc for 1k 1 5kVA or 2pcs for 2 2k 3kVA IEC output cables d 1set x UPS communication kit optional Accessories for Tower and Rack Mount 6 0 41 0mm 6 0 1 0mm 5 GI Wu 8 0 1 0mm 3 4 Selecting Installation Position 3 6 Tower Setup In order to minimize the possibility of damage to the UPS and extend Stand alone unit the life of the UPS it is necessary to select a proper environment to install the unit Please follow the instructions below 1 Keep at least 20cm 8 inches clearance from the rear panel of the UPS from the wall or other obstructions 2 Do not block air flow to the ventilation openings on the front and rear of the unit 3 Please ensure the installation site environmental conditions meet the UPS specifications to avoid overheating and excessive moisture and to prolong battery life 4 Do not place the UPS in a dusty or corrosive environ