VersaMax Micro-20/40/64 PLC Ethernet Option Module, GFK
Contents
1. MAC address is located on the front of the Ethernet module The IP address is only temporary and when Micro PLC is power cycled the IP address will be lost Once Set IP is clicked you will get confirmation that temporary IP has been set At this point you can go on line with Machine Edition via Ethernet and do any function that you would do with a serial connection Setting the Permanent IP Address 1 Go to C Prompt on your computer and type Ping IP address and press the Enter key This step is required to establish the ARP table by creating an entry in the table The address pinged should reply with Pinged data example c Ping 10 10 0 5 and return data Type arp a space between p and a You should see at least one entry in the ARP table example c arp a Type arp s IP address including dots MAC Address of the Ethernet module including dashes You will not see any reply on the screen example c arp s 10 10 0 5 00 20 4a ff ff e9 Type telnet IP address 1 leave space between IP address and 1 and press the Enter key You will be prompted that the connection failed This is normal example c telnet 10 10 0 5 1 Type telnet IP address 9999 leave space between IP address and 9999 and press the Enter key You will be prompted to Press Enter to go into Setup Mode You have two seconds to press the Enter key again If you get the message Connection to host lost re en
2. included To download a driver perform the following procedure Only one driver can be present at one time After the driver has been downloaded you will have to re configure the port using Telnet To download Ethernet drivers 1 Open the PumpKIN Utility M Ae Ae Ae Ae Ae Ae Ae Ae Ae Ae Ae PumpkIN started ms Mii Miia Ti Bi BR TB BB BB BB BB 2 Click on Put File and Local file to be downloaded Modbus_TCP 3 4 VersaMax Micro 20 40 64 PLC Ethernet Option Module IC200UEMOO1 Enter password G5 case sensitive must be upper case Q in Remote file For Remote host enter the IP address of the Micro PLC for example 10 10 0 2 Ss x Local file ox Micro 64 EthernettModbus TCP Modbus TCP Type octet Block 1024 Remote file G5 Remote host 10 10 0 2 00 Ad a When the file is downloaded the utility will respond with the following i PumpKIN x MESO A amp B 6S RSO O RASOR A P he he AS E e IMMM zej GetFile Put Fil lt a a ea f tw r NANN NNNNN fh PumpkiN started Sending G5 to 10 10 0 2 Transfer of G5 has successfully completed 7 7 2 When the transfer is accomplished go back to Telnet and configure the settings by following the procedure listed under Setting the Permanent IP Address on page 2 Refer to GFK 1852 for more information on configuration options Settings are now complete Verify that Port 2 matches above configur
3. 2 485 settings the WARNING RS 422 485 I F Modes Not Supported message displays WF Mode Option 7 6 5 4 3 2 1 0 Rs 232c ofo 7st Sidni a E TE No Parity lofo If Even Parity itt I Odd Party lopi If 1Stopbit Joja 2stopBit ihj tf Common Interface Mode Settings RS 232C 7 bit Even Parity 1 0111 1000 78 stop bit Flow Flow control sets the local handshaking method for stopping serial input output This should be set to zero always VersaMax Micro 20 40 64 PLC Ethernet Option Module IC200UEMOO01 Port Number The setting represents the source port number in TCP connections It identifies the channel for remote initiating connections The range is 1 65535 except for the following 1 1024 Reserved well known ports 9999 TELNET Setup 14000 14009 Reserved for Redirector 30704 Reserved 77FOh 30718 Reserved 77FEh Warning Do not use the reserved port numbers for this setting because incorrect operation may result Connect Mode Connect Mode defines how the unit makes a connection and how it reacts to incoming connections over the network Connect Mode Option 7 6 s a s 2 1 0 a Incoming Connection Never accept incoming o 0 0 Aways Accept i ti fo b Response Nothing quiet FO Character response C Ly Connect c Active Startup With any character 0 0 jo Remote IP Address This setting specifie
4. C Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Note This Class A digital apparatus complies with Canadian ICES 003 Changes or modifications not expressly approved by GE could void the user s authority to operate the equipment SRTP Server pomo O Mode Port PortType sid 19 2 38 4 or 175 0 kbps default a ae VersaMax Micro 20 40 64 PLC Ethernet Option Module IC200UEMOO1 Configuration Use of the Port Option module as Port 2 and the protocol selection must be set up in the configuration software After making those selections the communications parameters can also be configured The option port should be configured for Ethernet If the configuration and hardware do not match the PLC logs a System Configuration Mismatch fault in the PLC Fault Table The configuration a are ee ed ae Pet ede pu PortType 19 2 38 4 or 175 0 kbps default Parity Odd default Even None Station Address Valid range 0 247 Default 1 Modbus TCP Client Di
5. GFK 2436F February 2012 Module Description This datasheet describes the Ethernet Option module for a VersaMax Micro 20 40 or 64 PLC CPU This module cannot be used with other types of VersaMax Nano or Micro PLCs For more information about Option Modules and about VersaMax Micro 20 40 and 64 PLCs please refer to the VersaMax Nano and Micro PLCs User s Manual GFK 1645J or later Ordering Information RJ 45 10 100 Mbit Ethernet Communications AROSE MOOH board supporting SRTP Ethernet Option Module Ethernet Module IC200UEMO001 can be used with a Micro 20 40 or 64 Point PLC to provide an Ethernet Port Connector for Memory Pack Module Port Connector When installed on the Micro 20 40 or 64 PLC the Ethernet Port Option Module becomes Port 2 It supports the following communications protocols SRTP Modbus Server and client separate download and pass through port separate download Protocol options are available online at www ge ip com support FCC and ICES Requirements for the US and Canada This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Note This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FC
6. Intelligent Platforms SNP 1 Network IP Settings IP Address Default Gateway 10 10 0 5 10 10 0 1 Netmask 255 000 000 000 2 CH1 Serial amp Protocol Settings Protocol Mode Mode 1 SRTP Ethernet to Serial SNP Slave 175000 8 0 1 00002 msec 09000 msec Serial Interface T1 Turn Around Delay T2 ACK NAK Timeout T3 Link Idle Timeout 10000 msec T4 After Break Delay 00400 msec 3 SNP ID to IP mapping table not used in this mode D efault settings S ave Q uit without save Select Command or parameter set 1 3 to change Press 2 2 CH1 Serial amp Protocol Settings Mode 1 SRTP Ethernet to Serial SNP Slave Mode 2 Serial SNP Master to Remote VMSE Select desired operating mode 1 Enter serial parameters 175000 8 0 1 38400 8 N 2 New T1 Line Turn Around Delay 2 1280 msec 1ms resolution 2 Press Enter New T2 ACK NAK Timeout 50 12 950 msec 50ms resolution 9000 Press Enter New T3 Link Idle Timeout 1000 60 000 msec 250ms resolution 10000 Press Enter New T4 After lt BREAK gt Delay 5 1280 msec 5ms resolution 400 Press Enter After configuring all the parameters telnet will display the configured parameters Press S to save the configuration to the Ethernet module You will see the messages Parameters saved Restarting and then Connection to host lost
7. Unit Id Source Modbus TCP header Modbus Serial Broadcasts Disabled Id 0 auto mapped to 1 MB TCP Exception Codes Yes return OOAH and OOBH Char Message Timeout 00050msec 05000msec D efault settings S ave Q uit without save Select Command or parameter set 1 4 to change Press 2 Attached Device 1 Slave 2 Master 1 Press Enter Modbus TCP Client Enabled N Y Close Idle TCP sockets after 3 60 sec O leave open 10 Enter Serial Protocol 1 Modbus RTU 2 Modbus ASCII 1 Enter Enter serial parameters 38400 8 0 1 175000 8 0 1 After configuring all the parameters telnet will display the configured parameters Press S to save the configuration to the Ethernet module You will see the messages Parameters saved Restarting and then Connection to host lost VersaMax Micro 20 40 64 PLC Ethernet Option Module IC200UEMOO01 To change the Serial Parameter Settings in SRTP Protocol Connect PLC with IC200UEM001 on port2 in the Network For this example the current protocol is SRTP and serial settings are 175000 8 0 1 The following procedure explains how to change the existing serial parameters to 38400 8 N 2 For this example the IP address of the IC200UEMO01 is 10 10 0 5 Type TELNET 10 10 0 5 9999 at command prompt Follow the below procedure to configure the parameters of the Ethernet Option Module MAC address XXXXXXXXXXXX Software version 01 8 090618 XPTEX Press Enter to go into Setup Mode VMSE GE
8. ation by connecting to the Micro PLC serial port and checking hardware configuration GFK 2436F February 2012 Security Settings Security settings are provided to prevent unauthorized access to the Ethernet Option Module configuration mode Two security settings are supported for the Ethernet Option Module firmware version 2 0 and later Password support for Telnet configuration and SNMP Enable Disable configuration Security settings are provided for the three protocols SNP SRTP Modbus TCP and Tunneling For Modbus TCP and SRTP protocols these security settings options are present in the Network IP Settings menu For Tunneling Passthrough these security settings are present in basic parameters server menu By default there is no password and Simple Network Management Protocol SNMP is enabled Disabling or Enabling the SNMP is configurable The maximum password length is 16 characters These characters can be alphanumeric or special characters The password requires a minimum length of 8 characters A password set on a particular protocol s firmware remains in effect if the firmware is changed to that of a different protocol For example if a password is set on Modbus TCP firmware and later the firmware is changed to SNP SRTP the same password set on Modbus TCP firmware will still apply Status LEDs Link LED Amber Solid Amber Connection to Micro PLC established and network is connected Acti
9. l to avoid contact with the exposed components in the module Connector for Option Module Screws for Option Module Press the Option Module downward until it clicks into place Install the screws provided with the Option Module into the corners indicated above Connector for mete aes odule Port lt Connector If a Memory Pack Module is being installed orient the connector on the back of the Memory Pack Module with the connector on the Micro PLC or port type Option Module Press the Memory Pack down until it clicks into place Install the protective cover s If only the Memory Pack Module is used both covers may be installed If a port module is used the right hand cover is not installed and the port connector remains accessible Setting the IP Address Key items to remember when setting the IP address on the VersaMax Micro Ethernet Board IC200UEMO001 When connecting via Ethernet point to point a crossover cable is required IP address setting must be saved to the Flash on the Ethernet board or it will be lost during power cycle The second port of the Micro PLC must be configured for Ethernet IC200UEMOO1 Setting the Temporary IP Address First set up a temporary IP address using Proficy Machine Edition Logic Developer 1 Open your project Click on Utility on the Navigator box 2 3 Click on Set Temporary IP Address 4 Enter a Temporary IP address and MAC address for the Ethernet module
10. o functions features or compatibility Functional Compatibility The default data rate with Ethernet option module firmware version 2 0 is 175000 bps Micro firmware versions below 3 83 do not support 175000 bps If firmware version 2 0 is to be used with Micro firmware versions prior to 3 83 the data rate on Ethernet Option module should be changed to 38400 bps or less as per the requirement GFK 2436F February 2012 Telnet Configuration Note The Ethernet option module will be power cycled and reset under the following conditions A connection to the Ethernet option module is established through TELNET and disconnected immediately A connection to the Ethernet option module through is established through TELNET the configuration is edited and you press Q Quit without Save Description of Serial IO configurable parameters Baud Rate The supported baud rates are 19200 38400 and 175000 This baud rate should match the baud rate of the configuration software I F Mode Interface Mode The Interface I F Mode is a bit coded byte entered in hexadecimal notation The following table displays available I F Mode options Note All bit positions in the table that are blank represent don t care bits for that particular option which can be set to either a 0 or 1 value Only RS 232C is supported and hence Bit 0 and Bit 1 always should be zeros If you attempt to select an I F Mode bit that pertains to RS 42
11. s the remote IP address through which the communication needs to be established D disconnect N Unreachable Remote Port The setting represents the destination port number in TCP connections It is the number that identifies the channel for remote initiating connections Note See the reserved port numbers from the table specified in Port Number section DisConn Mode Set to zero FlushMode Set to zero DisConnTime Set to zero SendChar 1 Set to zero SendChar 2 Set to zero GFK 2436F February 2012 Examples User entries are shown in bold To configure the Modbus TCP Client in IC200UEMO01 through TELNET Connect PLC with IC200UEM001 on port2 in the Network For this example the IP address of the IC200UEMO01 is 10 10 0 5 Load the Ethernet Option Module firmware upgrade kit 82A1588 MS10 000 BO Type TELNET 10 10 0 5 9999 at command prompt Configure the parameters of the Ethernet Option Module as follows Modbus TCP to RTU Bridge MAC address XXXXXXXXXXXX Software version 02 5 090526 XCARD Press Enter to go into Setup Mode Model Device Server OEM Firmware Code G5 Modbus TCP to RTU Bridge Setup 1 Network IP Settings IP Address Default Gateway 10 10 0 5 10 10 0 1 Netmask 255 000 000 000 SNMP is enabled 2 Serial amp Mode Settings Protocol Modbus TCP Client Serial Interface Modbus RTU Slave s attached disabled 38400 8 0 1 4 Advanced Modbus Protocol settings Slave Addr
12. sabled default Support Refer to the or Enabled VersaMax Nano and Enabling Micro PLCs User s j Modbus TCP Client Manual GFK 1645J or Support sets the later a status bit Port Mode Serial I O Data Rate 19 2 38 4 or 175 0 kbps default Flow Control Parity Odd default a None Stop bits default or 2 Bits Characters Station Address Valid range Byte 1 to Byte 8 0 F Default 0 When the Ethernet Option Module is configured for Modbus TCP Client the configured Sequence Number and Command Data addresses should not overlap or conflict with any other variables used in the logic These addresses are reserved exclusively for communications between the CPU and Ethernet module when initiating Modbus TCP commands Modbus TCP Client Server Pass Through or Tunneling GFK 2436F VersaMax Micro 20 40 64 PLC Ethernet Option Module February 2012 Installation Instructions Power to the VersaMax Micro PLC MUST BE TURNED OFF when installing or removing Option Modules 1 Remove the two doors shown below by pressing downward on the latches and lifting them away from the module 7 U gt Press Down__ J Latch and Remove These il Two Doors E If a port type Option Module is being installed orient the connector on the Option Module with the connector in the Micro PLC Be carefu
13. ter telnet IP address and press the Enter key twice to get to the setup screen example c telnet 10 10 0 5 9999 Press 1 to change IP address Enter the desired IP address and Net Mask Press 2 to change Serial Settings For best performance set the baud rate to 175000 Setting should be Mode 1 RS232 175000 8 0 1 Port 2 needs to be configured with Proficy Machine Edition to match these settings Machine Edition should configure Port 2 for Ethernet and baud rate of 175000 When complete press S to save to the Ethernet module You will see a prompt that informs you Parameters saved Display will Restart and then Connection to host lost The data is now stored in the internal Flash of the IC200UEMO001 You can change the settings by repeating the above steps GFK 2436F February 2012 Settings are now complete Verify that Port 2 matches above configuration by connecting to the Micro PLC serial port and checking hardware configuration Status LEDs Connector for Memory Pack Module gt Downloading Ethernet Drivers The Ethernet drivers for the Ethernet Option Module are downloaded from www ge ip com support Files and passwords Function Upgrade Kit for Destination Release 2 0 GE Intelligent 82A1587 MS10 000 B0O Platforms SRTP Modbus TCP 82A1588 MS10 000 BO Client and Server in single firmware Tunneling or Pass 82A1589 MS10 000 BO Thru Downloading is done using the PumpkKIN utility which is
14. vity Green Flashing Green when there is any activity on the network Status Red OFF No errors Red ON Duplicate IP address present or network controller error Red BLINK 2x sec No DHCP response or Setup menu active VersaMax Micro 20 40 64 PLC Ethernet Option Module IC200UEMOO01 Module Specifications Processor Speed DSTni EX CPU 48MHz 256 kByte RAM 512 kByte FLASH Connection Type RJ 45 10Base T 100Base TX Ethernet Entity Type Client Server Bus Speed 10 100Mbaud Protocols SRTP preloaded Supported Modbus TCP Server and Client optional Tunneling optional Supports up to 8 Modbus TCP IP server channels If client configured then 1 client and 7 server channels supported Supports 4 SRTP server channels Number of Connections Supported Supports 1 connection for Tunneling Mode Full Duplex Revision History IC200UEMO001 AA Initial release Compatible with VersaMax Micro 64 firmware release 3 5 and Proficy Machine Edition 5 5 IC200UEM001 AB Improved noise immunity IC200UEM001 BC_ Added support for Modbus TCP Client enhanced data throughput 175 000bps and 16 character password security Firmware requirements Micro 20 40 and 64 firmware versions 3 83 and later Ethernet Option Module firmware versions 2 0 and later Programmer requirements Proficy Machine Edition Logic Developer PLC version 6 0 or later IC200UEMO001 CC_ Labeling change No changes t
Download Pdf Manuals
Related Search
Related Contents
Lincoln Electric IM849 User's Manual Philips HD6110 1000 g Deep-fat fryer AES uScope Manual Mirasys NVR 5.4 Quick Installation and User Guide MANUAL DO USUÁRIO Coifa Vetro Coifa Arketto Sony Contact 1500 Manual de VITO Audio NotesUser`s manual Table des matières Relationship Pricing User Manual Copyright © All rights reserved.