2711P-IN004J-EN-P - Rockwell Automation

image

Contents

1. equipment and hard wired electromechanical devices Because of this difference and also because of the wide variety of uses for solid state equipment all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable In no event will Rockwell Automation Inc be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative purposes Because of the many variables and requirements associated with any particular installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is p Throughout this man ohibited al when necessary we use notes to make you aware of safety considerations Identifies information about practices or circumstances that can cause an explosion in a hazardous environment which may lead to personal injury or death property damage or economic loss IMPORTANT Identifies information that is critical for successful application and understanding of the
2. if attached from the logic module by removing the four screws 4 Loosen the six captive screws that attach the logic module to the display module Communication Module Screw Logic Module f Captive Display Module 5 Carefully lift the logic module away from the terminal and turn over to expose the circuit board Publication 2711P IN004J EN P September 2009 10 Logic Module Internal CompactFlash and RAM 6 Locate the battery on the circuit board Lift up the edge of the battery indicated by the arrow 7 Remove the battery by lifting up the side of the battery 8 Insert the new battery 9 Reattach the logic module by aligning the two connectors on the bottom of the module with the connectors on the terminal 10 Push down on the logic module until it is firmly seated 11 Tighten the six captive screws that secure the logic module to a torque of 0 58 Nem 5 7 Ibsin 12 Reattach the communication module if necessary and tighten the four screws to a torque of 0 58 Nem 5 7 Ibein Publication 2711P INOO4J EN P September 2009 Logic Module Internal CompactFlash and RAM 11 Ethernet Cable Use Belden 7921A shielded Ethernet Category 5e cable according to TIA 568 B 1 and RJ45 connector according to IEC 60603 7 for compliance with Marine emissions limits and European Union 89 336 EEC EMC Directive The maximum cable length between the terminal s Ethernet port and a 10
3. logic module with 128 MB flash 128 MB RAM DC input 2711P RP3 Logic module with 256 MB flash 256 MB RAM DC input 2711P RP3A Logic module with 256 MB flash 256 MB RAM AC input 2711P RP3D Logic module 256 MB flash 256 RAM isolated DC input PanelView Plus CE 700 to 1500 Logic Modules 2711P RP6 PanelView Plus CE logic module with 128 MB flash 128 MB RAM DC inpu 2711P RP6A PanelView Plus CE logic module with 128 MB flash 128 MB RAM AC input 2711P RP6D PanelView Plus CE logic module with 128 MB flash 128 MB RAM isolated DC input 2711P RP6K PanelView Plus CE conformal coated logic module with 128 MB Flash 128 MB RAM DC input 2711P RP6DK PanelView Plus CE conformal coated logic module with 128 MB flash 128 MB RAM isolated DC input 2711P RP7 PanelView Plus CE logic module with 256 MB flash 256 MB RAM DC inpu 2711P RP7A PanelView Plus CE logic module with 256 MB flash 256 MB RAM AC input 2711P RP7D PanelView Plus CE logic module with 256 MB flash 256 MB RAM isolated DC input 1 2 These logic modules are compatible with any of the 2711P RWx internal CompactFlash cards These logic modules are approved for marine applications Publication 2711P INOO4J EN P September 2009 Logic Module Internal CompactFlash and RAM 5 Required Tools The following tools are required for installation e 1 and 2 Phillips screwdriver e Electrostatic discharge ESD wristband Component Compatibility fo
4. not functioning and needs to be returned follow these procedures United States Contact your distributor You must provide a Customer Support case number see phone number above to obtain one to your distributor in order to complete the return process Outside United Please contact your local Rockwell Automation representative for the return States procedure PanelView Plus PanelView Plus CE RSView ME FactoryTalk View Allen Bradley Rockwell Automation and TechConnect are trademarks of Rockwell Automation Inc Trademarks not belonging to Rockwell Automation are property of their respective companies www rockwellautomation com Power Control and Information Solutions Headquarters Americas Rockwell Automation 1201 South Second Street Milwaukee WI 53204 2496 USA Tel 1 414 382 2000 Fax 1 414 382 4444 Europe Middle East Africa Rockwell Automation Vorstlaan Boulevard du Souverain 36 1170 Brussels Belgium Tel 32 2 663 0600 Fax 32 2 663 0640 Publication 2711P INOO4J EN P September 2009 PN 54637 Supersedes Publication 2711P INOO4I EN P September 2008 Copyright 2009 Rockwell Automation Inc All rights Printed in the U S A
5. product ATTENTION Identifies information about practices or circumstances that can lead to personal injury or death property damage or economic loss Attentions help you identify a hazard avoid a hazard and recognize the consequences SHOCK HAZARD BURN HAZARD 2 a a PDE Labels may be on or inside the equipment for example a drive or motor to alert people that dangerous voltage may be present Labels may be on or inside the equipment for example a drive or motor to alert people that surfaces may reach dangerous temperatures Publication 2711P IN004J EN P September 2009 Logic Module Internal CompactFlash and RAM 3 Safety Precautions Before installing or replacing components and modules disconnect power from the terminal During the installation be careful not to touch any of the exposed electronic components SHOCK HAZARD Disconnect all power from the terminal before installing or replacing any components Failure to disconnect power may result in electrical shock or damage to the terminal ATTENTION Be careful when touching any of the exposed electronic components to prevent damage from electrostatic discharge ESD Work in a static free environment and wear a properly A grounded ESD wristband About the Logic Module The logic module has these features e Status indicators e Input power DC or AC e Ethernet port serial port two USB ports CompactFlash card slot e RA
6. 09 Logic Module Internal CompactFlash and RAM 15 Notes Publication 2711P INOO4J EN P September 2009 Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products At http support rockwellautomation com you can find technical manuals a knowledge base of FAQs technical and application notes sample code and links to software service packs and a MySupport feature that you can customize to make the best use of these tools For an additional level of technical phone support for installation configuration and troubleshooting we offer TechConnect support programs For more information contact yout local distributor or Rockwell Automation representative or visit http support rockwellautomation com Installation Assistance If you experience a problem within the first 24 hours of installation please review the information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running United States 1 440 646 3434 Monday Friday 8 a m 5 p m EST Outside United Please contact your local Rockwell Automation representative for any States technical support issues New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility However if your product is
7. 100 Base T port on an Ethernet hub without repeaters or fiber is 100 m 328 ft For additional information refer to the EtherNet IP Media Planning and Installation Manual publication ENET INO001 Marine Applications Isolated DC logic modules require a line filter for use in marine applications Use Corcom 6VW1 or equivalent filter type PanelView Plus Marine Terminal GND DC DC Earth ground 1 m 39 in max GND to ground bus DC Earth ground GND to ground bus DC Publication 2711P INOO4J EN P September 2009 12 Logic Module Internal CompactFlash and RAM Install a Logic Module If the display module and logic module are ordered as separate components attach the logic module to the display module before panel installation 1 Disconnect power from the terminal 2 Set the display module of the terminal display side down on a clean flat stable surface to avoid scratches 3 Position the logic module over the back of the display module until the two connectors on the bottom of the logic module align with the connectors on the display module 4 Push down on the logic module until firmly seated 5 Tighten the six captive screws that secure the logic module to the display module to a torque of 0 58 Nem 5 7 Ibein Logic Module Captive Screws on Top and Bottom Publication 2711P INOO4J EN P September 2009 Logic Module Internal CompactFlash and RA
8. Installation Instructions Logic Module Internal CompactFlash and RAM Catalog Numbers 2711P Rxxxx Topic Page About the Components 1 Important User Information 2 Safety Precautions 3 About the Logic Module 3 Electrostatic discharge ESD wristband 5 Install or Replace RAM 7 Install or Replace the Internal CompactFlash 8 Marine Applications 11 Install a Logic Module 12 Replace a Logic Module 13 Additional Resources 14 About the Components This document provides information on how to install these components e Logic module on a PanelView Plus or PanelView Plus CE device e Memory RAM and internal CompactFlash in the logic module For complete information on installing wiring and troubleshooting the terminals refer to the publications listed under Additional Resources This document refers to FactoryTalk View ME software that was previously named RSView ME software Rockwell ALLEN BRADLEY e ROCKWELL SOFTWARE Automation 2 Logic Module Internal CompactFlash and RAM Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment Safety Guidelines for the Application Installation and Maintenance of Solid State Controls Publication SGI 1 1 available from your local Rockwell Automation sales office or online at http literature rockwellautomation com describes some important differences between solid state
9. J EN P September 2009 6 Logic Module Internal CompactFlash and RAM Component Compatibility for PanelView Plus Terminals It is important that you match the series of the internal CompactFlash card with the correct series of the logic module and software version The series of the CompactFlash determines the version of FactoryTalk View ME software The logic module is available with or without memory installed Logic Module Compatibility Internal CompactFlash FactoryTalk View ME 2711P RPx 2711P RP1x 2711P RW1 2711P RW2 Software Version 2711P RP2x 2711P RP3x 2711P RW3 Series A 2711P RPx A Series B 2711P RWx B FactoryTalk View ME 3 0 Series B 2711P RPx B Series C 2711P RWx C FactoryTalk View ME 3 10 Series B 2711P RPx B Series D 2711P RWx D FactoryTalk View ME 3 20 Series C 2711P RPx C Series E 2711P RWx E Series D 2711P RPx D Series F 2711P RWx F FactoryTalk View ME 4 0 Series E 2711P RPxx E Series G 2711P RWx G Series F 2711P RPxx F Series H 2711P RWx H Series G 27 P RPxxx G 2 Series J 2711P RWx J FactoryTalk View ME 5 0 or 5 1 1 Series A logic modules are compatible with series B CompactFlash cards When upgrading from FactoryTalk View ME software version 3 0 to 3 10 or later the Firmware Upgrade Kit is required 2 Series F and later logic modules work with PanelView Plus and PanelView Plus CE CompactFlash cards Compatibility After Upgrade Factory
10. M 13 Replace a Logic Module Before replacing the logic module you must remove the communication module if attached Remove the internal CompactFlash card and RAM from the logic module if you want to reuse the memory in the new logic module Follow these steps to replace the logic module 1 Disconnect power from the terminal 2 Disconnect all power and communication cables WARNING Do not connect or disconnect any communication cable with power applied to this device or any device on the network An electrical arc could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding 3 Set the terminal display side down on a clean flat stable surface to prevent scratches if the terminal is removed from a panel 4 Remove the four screws that secure the communication module if attached to the logic module and carefully lift the communication module away from the logic module Screw Display Module 5 Loosen the six captive screws that secure the logic module 6 Carefully lift the logic module away from the back of the display module Publication 2711P IN004J EN P September 2009 14 Logic Module Internal CompactFlash and RAM 7 If reusing the memory in the new logic module e remove the RAM and CompactFlash from the logic module e insert the RAM and CompactFlash in the new logic module To verify component compatibility
11. M and internal CompactFlash with firmware or operating system Display Module Logic modules are available as separate catalog numbers for field installation and are shipped with or without memory installed If RAM and internal CompactFlash are ordered separately you must install these components before attaching the logic module to the display module Publication 2711P INOO4J EN P September 2009 4 Logic Module Internal CompactFlash and RAM PanelView Plus and PanelView Plus CE Logic Modules Cat No Description PanelView Plus or PanelView Plus CE 700 to 1500 Logic Modules 1 2711P RP Logic module without flash RAM memory DC input 2711P RPA Logic module without flash RAM memory AC input 2711P RPD Logic module without flash RAM memory isolated DC input PanelView Plus 700 to 1500 Logic Modules 2711P RP1 Logic module with 64 MB flash 64 MB RAM DC input 2711P RPIA Logic module with 64 MB flash 64 MB RAM AC input 2711P RP1D Logic module with 64 MB flash 64 MB RAM isolated DC input 2711P RP2 Logic module with 128 MB flash 128 MB RAM DC input 2711P RP2A Logic module with 128 MB flash 128 MB RAM AC input 2711P RP2D Logic module with 128 MB flash 128 MB RAM isolated DC input 2711P RP2DK Conformal coated logic module with 128 MB flash 128 MB RAM isolated DC input 2711P RP2K Conformal coated
12. Talk View ME terminals are compatible with MER applications that are the same or a previous revision For example FactoryTalk View ME 3 20 terminals can run MER applications for FactoryTalk View ME software versions 3 0 3 10 and 3 20 For PanelView Plus CE devices the appropriate changes are made to the OS from Windows CE software version 3 0 to 4 1 when upgrading from FactoryTalk View ME software version 3 0 to 3 10 or later Publication 2711P INOO4J EN P September 2009 Logic Module Internal CompactFlash and RAM 7 Install or Replace RAM The logic module is available with or without RAM installed If ordered separately you must install the RAM before attaching the logic module to the display module RAM Memory Modules Cat No Description 2711P RR64 64 MB SODIMM RAM for PanelView Plus and PanelView Plus CE terminals 2711P RR128 128 MB SODIMM RAM for PanelView Plus and PanelView Plus CE terminals 2711P RR128K Conformal coated 128 MB SODIMM RAM for PanelView Plus and PanelView Plus CE terminals 2711P RR256 256 MB SODIMM RAM for PanelView Plus and PanelView Plus CE terminals Follow these steps to install or replace RAM 1 Turn the logic module over to expose the circuit board 2 Locate the RAM module on the circuit board 3 Pull the metal retaining clips away from the module and slide out the RAM module 4 Insert the new RAM module at a 45 angle and snap down Retaining Cli Siew CompactF
13. d 3 Pull out the internal CompactFlash card 4 Insert the new internal CompactFlash card 5 Reattach the retaining clip Publication 2711P INOO4J EN P September 2009 Logic Module Internal CompactFlash and RAM 9 Battery Precautions WARNING When you connect or disconnect the battery an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding For safety information on the handling of lithium batteries including handling and disposal of leaking batteries see Guidelines for Handling Lithium Batteries publication AG 5 4 Replace the battery only with the indicated catalog number Do not dispose of battery in a fire or incinerator Dispose of used batteries in accordance with local regulations Store batteries in a cool dry environment We recommend 25 C 77 F with 40 60 relative humidity You may store batteries for up to 30 days between 45 85 C 49 185 F such as during transportation To avoid possible leakage do not store batteries above 60 C 140 F for more than 30 days Replace the Battery in PanelView Plus Terminals Follow these steps to replace the battery in the logic module of Panel View Plus or Panel View Plus CE terminals 1 Disconnect power from the terminal 2 Place the terminal display side down on a flat stable surface 3 Detach the communication module
14. lash Card Se RAM Module Retaining Clips Publication 2711P INOO4J EN P September 2009 8 Logic Module Internal CompactFlash and RAM Install or Replace the Internal CompactFlash The logic module is available with or without CompactFlash installed If ordered separately you must install the CompactFlash before attaching the logic module to the display module Internal CompactFlash Cat No Description 2711P RW1 64 MB internal CompactFlash with FactoryTalk View ME software for PanelView Plus ogic modules 2711P RW2 128 MB internal CompactFlash with FactoryTalk View ME software for PanelView Plus ogic modules 2711P RW3 256 MB internal CompactFlash with FactoryTalk View ME software for PanelView Plus ogic modules 2711P RW6 128 MB internal CompactFlash with FactoryTalk View ME software for PanelView Plus CE ogic modules 2711P RW7 256 MB internal CompactFlash with FactoryTalk View ME software for PanelView Plus CE logic modules 2711P RW8 512 MB internal CompactFlash with FactoryTalk View ME software for PanelView Plus CE logic modules 1 The 2711P RP 2711P RPD and 2711P RPA logic modules are compatible with any of the internal CompactFlash options Follow these steps to replace the internal CompactFlash 1 Turn the logic module over to expose the circuit board 2 Unscrew and remove the retaining clip that secures the internal CompactFlash car
15. r PanelView Plus CE Terminals It is important to match the series of the internal CompactFlash card with the correct series of the logic module and software version The series of the CompactFlash determines the version of FactoryTalk View ME software and version of the operating system The logic module is available with or without memory installed Logic Module Compatibility 6189 RPx 6189 RPRHx 6189 RPEHx 2711P RPx 2711P RPx 2711P RP6x 2711P RP7x Internal CompactFlash 6189 RW2 6189 RW3 6189 RW4 2711P RW6 2711P RW7 2711P RW8 FactoryTalk View ME and OS Software Version Series A 6189 RPxH A Series B 6189 RWx B FactoryTalk View ME 3 0 Windows CE 3 0 Series B 6189 RPxH B Series C 6189 RWx C FactoryTalk View ME 3 10 Windows CE 4 1 Series B 6189 RPxH B Series D 6189 RWx D FactoryTalk View ME 3 20 Series C 6189 RPxH C Series E 6189 RWx E Windows CE 4 1 Series D 6189 RPxH D Series F 6189 RWx F FactoryTalk View ME 4 0 Series E 6189 RPxHx E Series G 6189 RWx G Windows CE 4 1 Series F 271 1P RPxx F2 Series H 2711P RWx H Series G 2711P RPxxx G Series J 2711P RWx J FactoryTalk View ME 5 0 or 5 1 Windows CE 4 1 1 When upgrading from FactoryTalk View ME software version 3 0 to 3 10 or later the Firmware Upgrade Kit is recommended 2 Series F and later logic modules work with PanelView Plus and PanelView Plus CE CompactFlash cards Publication 2711P INOO4
16. refer to the tables on page 5 and 6 8 Install the new or used logic module 9 Install the communication module if necessary Additional Resources For additional information on the PanelView Plus and PanelView Plus CE terminals refer to these publications Resource Description PanelView Plus User Manual publication Provides an overview of the PanelView Plus and PanelView 2711P UM001 Plus CE terminals and gives information on how to install operate configure and troubleshoot these devices PanelView Plus Terminals and Display Provides specific guidelines and procedures on how to install Modules Installation Instructions publication PanelView Plus PanelView Plus CE terminals and display 2711P INO01 modules in a panel High bright Display Modules Installation Provides specific guidelines and procedures on how to install Instructions publication 2711P INO26 a high bright display module to a PanelView Plus or PanelView Plus CE terminal in outdoor environments Wiring and Grounding Guidelines for Provides additional grounding and wiring guidelines for PanelView Plus Devices Technical Data PanelView Plus and PanelView Plus CE terminals publication 2711P TD001 You can view or download publications at http literature rockwellautomation com To order paper copies of technical documentation contact your local Rockwell Automation distributor or sales representative Publication 2711P INOO4J EN P September 20