Fluke 430 Series three-phase and Fluke 43B single

image

Contents

1. General Specifications Memory size 4000 events Power Battery type Battery life 3 5V lithium non replaceable 7 years Mechanical 85 mm x 68 mm x 35 mm 1209 Environmental Operating temperature 40 to 70 C Relative Humidity Safety O to 95 non condensing Warranty 1 year Fluke Corporation P O Box 9090 Everett WA USA 98206 Fluke Europe B V P O Box 1186 5602 BD Eindhoven The Netherlands Fluke UK Ltd 52 Hurricane Way Norwich Norfolk NR6 6JB United Kingdom Tel 0207 942 0700 Fax 0207 942 0701 E mail industrial uk fluke nl Visit us on the world wide web at up and running http www fluke co uk CSA Certification pending CSA NRTL to UL 3111 certification pending Complies with requirements of EN61010 1 1993 For more information call In the U S A 800 443 5853 or Fax 425 456 5116 In Europe M East Africa 31 0 40 2 675 200 or Fax 31 0 40 2 675 222 In Canada 905 890 7600 or Fax 905 890 6866 From other countries 1 425 456 5500 or Fax 1 425 456 5116 Visit us on the world wide web at hitp www fluke com Copyright 2004 Fluke Corporation All rights reserved Printed in the Netherlands 09 04 Data subject to alteration without notice Pub_ID 10808 eng
2. 5 counts 0 25 Hz 2nd 3 51st 15 Fund 5 51st 15 10 3 8 counts Readings 2 10 counts Cursor readings 2 12 counts Cursor Readings Average 2 10 counts Arms Actual Arms max min AC DC 50 00 A 500 0 A 5 000 KA 50 00 kA Technical Specifications Fluke 43B single phase Power Quality Analyzer Recording Ranges Accuracy THD Volt Fund amp Harmonic Amps F amp H Watts F amp H Freq H H of total Phase H KF Scope DC Voltage DC Current AC Voltage AC Current Frequency Pulse Width or Phase Duty cycle or Peak max Peak min Peak min max Crest Factor Transients 40 ns 20 50 100 200 above or below reference signal Reference signal After START the Vrms and frequency of the signal are measured From these data a pure sinewave is calculated as reference for threshold setting Vpeak min Vpeak max at cursor 10 V 25 V 50 V 125 V 250 V 500 V 1250 V 5 of full scale Rated 600V CAT III Inrush Current Ranges Accuracy Current ranges selectable 1 A 5 A 10 A 50 A 100 A 500 A 1000 A Inrush times selectable ls 5s 10s 50s 100 s 5 min Cursor readings A peak max at cursor 1 and cursor 2 5 of full scale Time between cursors 4 to 235 pixels 0 2 2 pixels Scope dual channel scope with measurement reading Input Impedance Input 1 1 MQ 12
3. Cos p DPF 0 003 Flicker Pst 1min Pst Plt PF5 instantenous Flicker 0 00 20 00 0 01 Within 5 of tabulated values Dc Dmax and Time d t exceeds limits according IEC61000 4 15 0 0 100 0 for Dc and Dmax 0 1 for Dc and Dmax and 10 ms 1 for Dc and Dmax and 20 ms As described per IEC 61000 3 3 9 999s for Time 1 for Time for Time for Time Unbalance Volts 0 0 5 0 0 1 0 5 Current 0 0 20 0 1 1 Transient capture Volts 6000 Vpk 1 V 15 of cursor reading 2 5 of Vrms Minimum detect duration 5 ps Sampling rate 200 kS s Inrush mode Arms AC DC 0 000 20 00 kArms 0 001 10 Arms 1 of meas 5 counts Inrush Duration mm ssi mmm between 7 5 s 10 ms 30 m selectable 20 ms Fnominal 50 Hz Trend recording Method AutoTrend automatically records min max and average values over time for all readings being displayed for the 3 phases and neutral simultaneously Volts Amps Hertz Harmonics Power amp Energy Flicker and Unbalance mode Sampling Memory Recording time Zoom Dips amp Swells mode Sampling Memory Recording time Zoom Inrush Currents and Flicker PF5 mode Sampling Memory Recording time Zoom Monitor mode Sampling Recording time Memory Limits Measurement method Vrms Arms Vpeak Apeak V Crest Factor A Crest Factor Hz Vrms Arms 5 readings sec continuous
4. by IEC61000 4 30 Inrush current The inrush current begins when the Arms half cycle rises above the inrush threshold and ends when the Arms half cycle rms is equal to or below the inrush threshold minus a user selected hysteresis value The measurement is the square root of the mean of the squared Arms half cycle values measured during the inrush duration Each half cycle interval is contiguous and non overlapping as recommended by IEC 61000 4 30 Markers indicate inrush duration Cursors allow measurement of peak Arms half cycle General Specifications Case Design Rugged shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and Vibration Shock 30g Vibration 3g Sinusoid Random 0 03g Hz according to MIL PRF 28800F Class 2 Display Bright Full Color LCD with CCFL backlight 80cd m size 115 2 x 86 4 mm Resolution 320 x 240 pixels Contrast and brightness User adjustable temperature compensated Memory Screens 50 screen memories on Fluke 434 25 screen memories on Fluke 433 Data 10 data memories for storing data including recordings on Fluke 434 5 data memories for storing data including recordings on Fluke 433 Limit templates 2 preprogrammed 2 administrator programmable via FlukeView 2 user locations Real time clock Time and date stamp for AutoTrend Transient display and SystemMonitor Mechanical Size 256 x 169 x 64 mm Weight 2 kg Power Line power Switchable 115V 230
5. on Fluke 43B 1 year on accessories Ordering Information Fluke 43Basic Power Quality Analyzer Single phase Fluke 43B Power Quality Analyzer Single phase Fluke 43Kit Power Quality Analyzer Single phase Standard available in all models 43Basic 43B 43Kit Fluke 43B Power Quality Analyzer BP 120 NiCd Battery Pack installed PM 8907 Battery Charger Line Voltage Adapter TL24 Test Leads AC20 Industrial Test Clips TP4 Slim Reach Test Probe Set 4 mm BB120 Banana to BNC Adapter Plug Model difference i200s AC Current Clamp 200 A 80i1500s AC Current Clamp 500 A SW43W FlukeView Software for Windows PM 9080 Serial Interface Adapter Cable C120 Hard Case TP1 Slim Reach Test Probe Set flat blade AC85 Large Jaw Alligator Clips Power Quality Video Users Manual Application Guide Manual CD 43B Promotional Model Numbers VPS40 Voltage Probe Fluke 61 IR Thermometer Fluke VR101S Voltage Event Recorder System FLUKE Technical Specifications Fluke VR101S Voltage Event Recorder System Riot You TA cape Ordering Information Note At least one VR101S is required for proper operation VR1015 Voltage Event Recorder System VR101 Voltage Event Recorder Computer Hardware Requirements for EventView software IBM PC or 100 compatible with Windows 3 1 or Windows 95 98 NT XP or 2000 installed and o
6. pF with BB120 20 pF 2 pF with BB120 3 pF Input 2 1 MQ 10 pF with BB120 18 pF 2 pF with BB120 3 pF Vertical Voltage ranges 50 mV div to 500V div 1 2 pixels Vertical sensitivity resolution 5 mV div to 500V div 8 bit 256 levels Bandwidth channel 1 voltage DC to 20 MHz at inputs or with BB120 and VPS40 standard with Fluke 43B 1 MHz with TL24 Leads 10 kHz with supplied current clamps Coupling Horizontal TimeBase ranges 0 4 1 pixel Sampling rate min max samples Trigger source Trigger Mode Automatic Connect and View Free Run Single Shot Connect and View Advanced automatic triggering that recognizes signal patterns and automatically adjusts triggering timebase and amplitude Automatically displays stable pictures of complex and dynamic signals like motor drive and control signals Pre trigger Up to 10 divisions Measurement readings Volts amp Amps DC AC AC DCrms Peak max Peak min Peak min max per channel selectable Frequency Duty cycle or Phase Pulse Width or Crest factor Ohms Diode Continuity Capacitance Ohms 500 0 Q 5 000 KQ 50 00 KQ 500 0 KQ 0 6 5 counts 5 000 MQ 30 00 MQ Diode voltage O to 3 000 V 2 5 counts Continuity shorts gt 1 ms Beeper on at lt 302 5Q Capacitance 50 00 nF 500 0 nF 5 000 pF 50 00 pF 2 10 counts 500 0 pF Temperature 100 0 C to 400 0 C 0 5 5 counts 200 0 F to 80
7. 0 0 F Max current max open circuit volt 0 5 mA lt 4 V all functions above Memory Number of screens 20 General specifications Optical Isolated RS 232 Interface To printer Supports HP LaserJet DeskJet Epson FX LQ and Postscript printers with optional PAC91 Printer Adapter Cable To PC FlukeView Power Quality Analyzer software with PM9080 Interface Adapter included with 43B and 43Kit FlukeView Power Quality Software Hardware requirements PC or 100 compatible with Windows 95 98 Me 2000 NT4 0 1 pixel inrush time 250 Requires optional temperature accessory FLUKE o Power Line voltage adapter battery charger included Installed battery Rechargeable NiCd pack 4 to 6 Vdc Operating time 4 hours Charging time 4 hours unit OFF 12 hours unit ON Refresh Cycle 8 to 14 hours to keep NiCd battery capacity optimal Environmental Operating Temperature OPC to 50 C 32 F to 122 F Shock amp Vibration MIL 28800E Type 3 Class III Style B Case IP51 dust drip water proof Mechanical Data Size H x W x D 232 x 115 x 50 mm Weight 1 1 kg Safety For measurements on 600 Vrms Category III installations Pollution Degree 2 in accordance with EN61010 1 1993 IEC 1010 1 ANSI ISA 82 01 1994 CAN CSA C22 2 No 1010 1 92 UL3111 1 Surge protection 6 kV on input 1 and 2 Floating measurements 600 Vrms from any terminal to ground Warranty 3 years parts and labor
8. 10 100 1000 mV A and variable 40 70 Hz 16 bit analog to digital converter on 8 channels 200kS s on each channel simultaneously 5000 samples on 10 12 cycles according IEC 61000 4 30 4096 samples on 10 12 cycles according IEC 61000 4 7 Available in Scope and Transient mode Captures 8 waveforms simultaneously Display update rate 5x per second Up to 10 12 times horizontal zoom Cursors Single vertical line showing min max avg reading at cursor position Shows real time phasor diagram Available in Scope and Unbalance mode Display update rate 5x per second Available in Volts Amps Hertz Harmonics Power amp Energy Flicker and Unbalance mode Available in Volts Amps Hertz Dips amp Swells Harmonics Power amp Energy Flicker Unbalance Inrush and Monitor mode Cursors single vertical line showing with min max avg reading at cursor position Bargraph Available in Harmonics and Monitor mode Eventlist Available in Dips amp Swells and Monitor mode Measurement modes Scope Vrms Arms Vcursor Acursor Vfund Afund Hz V phase angles A phase angles Volts Amps Hertz Vrms Vpk V Crest Factor Arms Apk A Crest Factor Hz Dips and Swells Vrms Arms Captures up to 1000 events with date time duration magnitude and phase identification with programmable thresholds Harmonics DC 1 50 Power and Energy Flicker Unbalance Transients Inrush Currents System Monitor Harmonic Volt
9. RKLUKE Fluke 430 Series a Quality three phase and Fluke 43B single phase Power Quality Analyzers Technical Data Analyze your power network quickly In industry healthcare and business in fact wherever electrical and electronic equipment is indispensable power quality plays a critical role in maintaining continuity Non linear loads switching load changes and equipment problems can result in poor power quality Poor power quality is not only costly in terms of wasted energy and unnecessary downtime it s also dangerous and increases risk of equipment failure Fluke has an unrivalled range of power quality analyzers to help you maintain high quality power systems The tools give you the power to analyze every parameter power related event or anomaly faster safer and in more detail than ever before The range comprises the Fluke 430 Series three phase power quality analyzers and the 43B single phase power quality analyzer Power Quality Selection Table 434 433 43B Application Three phase Single phase Inputs 4 voltage and 4 current 1 voltage and 1 current for 3 phases and neutral Measurements Vrms Arms Hz W VAR VA PF Cos DPF Crest Factors Harmonics and THD V A W k factor Inter harmonics J Optional J kWh and KVARh KVAh demand interval Optional J Flicker Plt Pst PFS 6 Unbalance Recorder A
10. V adapter with country specific plug Battery power Rechargeable NiMH installed Battery operating time gt 7 hours Battery charging time 4 hours Power saving Adjustable time for dimmed backlight with on screen power indicator Standards Measurement methods used TEC61000 4 30 class A Power Quality ENSO160 Flicker IEC 61000 4 15 Harmonics IEC 61000 4 7 Safety Compliance IEC EN61010 1 2nd edition pollution degree 2 CAN CSA C22 2 No 101 1 ANSI ISA 82 01 Max voltage on banana input 1000 V CAT III 600 V CAT IV Max voltage on current BNC input 42 Vpeak Environmental Operating temperature O C to 50 C Storage temperature 20 C to 60 C Humidity 10 30 C 95 RH non condensing 30 40 C 75 RH non condensing 40 50 C 45 RH non condensing Maximum operating altitude 3000 m Derate to 1000 V CAT II 600 V CAT III 300 V CAT IV above 2000 m Maximum storage altitude 12 km Warranty 3 years on mainframe 1 year on included accessories Ordering Information 1 depending clamp scaling Fluke 433 Power Quality Analyzer three phase 2 50Hz 60Hz nominal frequency according to IEC 61000 4 30 Fluke 434 Power Quality Analyzer three phase Add clamp accuracy 7 4 12 Fluke 433 UGK Upgrade Kit for Fluke 433 The advanced functions interharmonics Energy Transients and Inrush are f optional for the Fluke 433 and standard available on the Fluke 434 includes 433AF OC4USB and SW43W Fluke 433AF Advanced Functions Upgrade Kit for F
11. anges Accuracy Input impedance 1 MQ 20 pF Voltage rating 600 Vrms CAT III Volt Amps Hertz True rms voltage AC DC 5 000 V 50 00 V 500 0 V 1250 V 1 10 counts True rms current AC DC 50 00 A 500 0 A 5 000 KA 50 00 kA 1250 kA 1 10 counts Frequency 10 0 Hz to 15 0 kHz 0 5 2 counts CF Crest Factor 1 0 to 10 0 5 1 count Power W VA VAR Reactive Power 1 phase and 3 phase 3 conductor balanced loads PF Power Factor DPF Displacement Power Factor 250 W 2 50 kW 25 0 kW 250 kW 2 50 MW 25 MW 250 MW 625 MW 1 56 GW 0 00 to 1 00 0 00 to 0 25 0 25 to 0 90 0 90 to 1 00 2 6 counts Total Power 4 4 counts Fundamental Power 0 04 not specified 0 04 0 03 Hz Frequency Fundamental 40 0 to 70 0 Hz 0 5 2 counts Harmonics Volts Amps Watts Fundamental V A 3 2 counts W 5 2 counts 2 to 3lst Harmonic V A 5 3 counts W 10 10 counts Frequency of fundamental Phase K Factor Amps amp Watts THD Sags amp Swells Recording times selectable Vrms Actual Vrms max min AC DC 32 to 51st Harmonic 40 Hz to 70 Hz Volt amp Amps between Fund amp Harmonic Watts between Volt Fund amp Amps Harmonic 1 0 to 30 0 0 00 to 99 99 4 min to 16 days 5 000 V 50 00 V 500 0 V 1250 V V A 15 5 counts W 30
12. luke 433 OC4USB Serial Interface Adapter Cable USB PM9080 Serial Interface Adapter Cable RS232 SW43W FlukeView Software FLUKE o Accessories Fluke 430 Series Accessories C430 Hard case with clamp holders i400s current clamps 4 TLS430 Test leads and alligator clips 4 black 1 green BP190 NiMH Battery pack installed BC430 Battery charger line voltage adapter SW43W FlukeView Software Fluke 434 only OC4USB Serial interface adapter cable USB Fluke 434 only WC100 Color localization set Getting Started printed User Manual CD ROM Technical Specifications Fluke 43B single phase Power Quality Analyzer The Fluke 43B Power Quality Analyzer is optimized for industrial measurements on the 50 Hz fundamental frequency Since its usable fundamental frequency range extends from 10 Hz to 400 Hz the 43B is ideal for industrial aviation marine and railway applications Mode Usable bandwidth Harmonics on 400 Hz fundamental Typical accuracy for 400 Hz fundamental Volt Amp Hz 10 Hz 3 5 KHZ 9th harmonic 5 20Hz 2 kHz 5th harmonic 10 Harmonics 10 Hz 3 5 kHz 9th harmonic 10 Channel 1 50 Channel 2 Note Current harmonics measurements can be done via channel 1 with improved accuracy Accuracies are stated as percentage of reading counts without probes unless otherwise noted Specifications are valid for signals with a fundamental between 40 and 70 Hz Input Characteristics R
13. perating At least one free RS 232 serial port A pointing device recommended 2 MB hard drive space 4 MB RAM 8 MB for Windows 95 98 or higher Included Accessories VR101S VR101 Voltage Event Recorder Optical interface cable 9 to 25 pin adapter EventView Software on two 31 2 inch floppies Users Manual Included Accessories VR101 VR101 Voltage Event Recorder Instruction Sheet Fluke Keeping your world Electrical voltage versions plug style and manual languages are determined by country Voltage Version Operating range Nominal frequencies Power consumption 120 V 70 V to 140 V 50 Hz or 60 Hz 2W 230 V 140 V to 270 V 50 Hz or 60 Hz 3 W Sags Swells and Outage Measurements Voltage Version Range Accuracy Resolution 120 V Hot to neutral O to 200 V rms 2 V rms 1 V rms Neutral to ground 3 to 200 V rms 2 V rms 1 V rms 230 V Hot to neutral O to 400 V rms 4 V rms 2 V rms Neutral to ground 3 to 120 V rms 2 V rms 1 V rms Transient Measurements Range Accuracy Resolution Hot to neutral 100 to 2500 V peak 10 reading 10 V 10 V 50 to 2500 V peak 10 reading 10 V 10 V 20 to 180 a i S 200 to 380 Minimum pulse width 1 ps Frequency Measurements Range Accuracy Resolution OSH AON Hz Scyclos min Ol Hz Time Measurements Events lt 1 second Accuracy Resolution 0 5 cycles Events 1 second time stamp Accuracy Resolution 2 sec day 8 sec 8 sec
14. rdance with IEC 61000 4 30 Technical Specifications Fluke 430 Series three phase Power Quality Analyzers Measurement method continued Harmonics Calculated from 10 12 cycle gapless harmonic group measurements on Voltage and Amps according to IEC 61000 4 7 Watt Selectable Total or Fundamental real power display Calculates average value of instantaneous power over 10 12 cycle period for each phase Total Active Power Pp P P P VA Selectable Total or Fundamental apparent power display Calculates apparent power using Vrms x Arms value over 10 12 cycle period Total Apparent Power is root mean square of real and apparent power VAR Selectable Total of Fundamental reactive power display Calculates reactive power as root of VA squared minus Watt squared over 10 12 cycle period Capacitive and inductive load is indicated with capacitor and inductor icons Power Factor Calculated Watt VA Cos DPF Cos of angle between fundamental voltage and current Unbalance The supply voltage unbalance is evaluated using the method of symmetrical components according to IEC61000 4 30 Plicker According to IEC 61000 4 15 Flickermeter Functional and design specification Includes 230V 50Hz lamp and 120V 60Hz lamp models Transient capture Captures waveform triggered on signal envelope Additionally triggers on dips swells interruptions and Amps level as specified
15. s THD Volt Harmonic Amps THD Amps K Amps Harmonic Watts THD Watts K Watts Interharmonic Volts Interharmonic Amps relative to fundamental or to total rms Watts VA VAR Power factor Cos DPF Arms Vrms kWh kVAh KVARh peak demand interval using trend KYZ revenue meter verification via optional input Pst min Pst Plt PF5 Vrms Arms Dc Dmax TDEX Vneg Vzero Aneg Azero Vfund Afund Hz V phase angles A phase angles Vrms Arms Vcursor Acursor Inrush Current Inrush duration Arms Vrms Vrms Arms Harmonic Volts THD Volts Plt Vrms Arms Vneg Hz dips and swells unbalance All parameters are measured simultaneously in accordance with EN50160 Using Flagging to indicate unreliable readings according IEC61000 4 30 Accuracy resolution and range Volt Amps Hertz Measurement range Resolution Accuracy Vrms AC DC 1 1000 Vrms 0 1 Vrms 0 5 of nominal voltage Vpk 1 1400 Vpk 1V 5 of nominal voltage CFV 1 0 gt 2 8 0 1 5 Arms AC DC 0 20 000 Arms 0 001 10 Arms 1 of reading 5 counts with included clamps 0 400 Arms 0 1 and 1 Arms Apk using 1mV A scaling O 5500 Apk 10A 5 CFA using 1mV A scaling ve 10 0 1 5 Hz 50Hz nominal 42 50 57 50 Hz 0 01 Hz 0 1 of nominal frequency 60Hz nominal 51 00 69 00 Hz 0 01 Hz 0 1 of nominal frequency Dips and swells Vrms 1 AC DC 0 0 100 of nominal vol
16. sampling per channel 1800 min max and avg points for each reading From 30 min with 1 second display resolution up to 450 days with 6 hour display resolution Up to 6x horizontal zoom 100 120 readings sec continuous sampling per channel 3600 min max and avg points for each reading From 90 sec with 25 msec display resolution up to 450 days with 3 hr display resolution Up to 12x horizontal zoom 100 120 readings sec continuous sampling per channel 3600 min max and avg points for each reading From 7 5 sec with 25 msec display resolution up to 30 min with 500msec display resolution for Inrush measurements and up to 2 5 hr with 2 5 sec display resolution for PF5 recordings Up to 12x horizontal zoom Combination of 5 readings sec and 100 120 readings sec continuous sampling per channel depending on the parameter measured Up to 1 week with 10 min resoluton 1008 min max and avg points for each reading According EN50160 or customer definable 10 12 cycle contiguous non overlapping intervals using 500 416 samples per cycle in accordance with IEC 61000 4 30 Absolute highest sample value within 10 12 cycle interval with 40ys sample resolution Measures ratio between the Vpeak and Vrms Measures ratio between the Apeak and Arms Measured every 10 sec in accordance with IEC61000 4 30 Value is measured over 1 cycle commencing at a fundamental zero crossing and refreshed each half cycle This technique is independent for each channel in acco
17. tage 0 1 Vrms 1 of nominal voltage Arms 7 AC DC O 20 000 Arms 0 001 Arms 10 Arms 1 of reading 5 counts with included clamps O 400 Arms 0 1 Arms and 1 Arms Threshold levels Programmable in percent of nominal voltage Duration hhh mm ss mmm with half cycle cycle time resolution FLUKE o Harmonics Harmonic selection n Inter Harmonic selection Relative f Absolute Relative f Absolute Measurement range Resolution Accuracy DC 1 50 Off 1 49 100 0 0 1 1000 Vrms 0 1 Vrms 0 0 100 0 0 1 0 0 4000 mV x selected clamp 1 mVrms x selected clamp scaling scaling 0 1 n x 0 1 0 4 for r 5 of reading 2 counts 0 1 n x 0 1 0 4 for r 5 of reading 5 counts DC voltage Relative Absolute Relative Absolute 0 0 100 0 0 1 depends on selected clamp and 5 of reading n x 2 of reading voltage scaling 10 counts 0 0 100 0 1 0 0 1000V 5 of reading 10 counts n x 2 E25 Hz O 3500 Hz 1 Hz t 1Hz Phase angle 360 360 1 tnx 15 Power and Energy 1 5 of reading 10 counts VA 1 0 VA 20 00 MVA 1 5 of reading 10 counts VAR 1 0 VAR 20 00 MVAR 1 5 of reading 10 counts E 1 5 of reading 10 counts kVA 00 00 kVAhr 200 0 GVAhr 1 5 of reading 10 counts KVAR 00 00 KVARhr 200 0 GVARhr 1 5 of reading 10 counts 0 03
18. utoTrend 0 0 e e e System Monitor Real time scope Phasor diagrams e e e e e Dips and swells Half cycle based e e e e e Transient displaycapture 6 Optional Inrush current J Optional J EN50160 compliance IEC61000 4 30 4 7 4 15 compliance Built in general purpose Scope and DMM 7 Memory screens data 50 10 25 5 standard 20 for screens and data 50 10 optional FlukeView software and interface cable J Optional Depending on configuration EN61010 safety rating 600 V CAT IV 1000 V CAT III 600 V CAT III Optional functionality can be added with upgrade kit For details see ordering information Technical Specifications Fluke 430 Series three phase Power Quality Analyzers Input characteristics Voltage inputs Number of inputs Maximum input voltage Maximum peak voltage Input impedance Bandwidth Scaling Current inputs Number of inputs Type Range Input impedance Bandwidth Scaling Nominal frequency Sampling system Resolution Maximum sampling speed RMS sampling PLL synchronization Display modes Waveform display Phasor Matrix readings AutoTrend graph 4 3 phases neutral 1000 Vrms 6 kV 4 MQ 5 pF 9 kHz up to 100 kHz for transient display 1 1 10 1 100 1 1000 1 and variable 4 3 phases neutral Clamp on current transformer with mV output 1 400 Arms with included clamps 1400s 0 1 3000 Arms with optional clamps 50 KQ 9 kHz 0 1 1

Download Pdf Manuals

image

Related Search

Related Contents

  Manual do Utilizador do 5300 Series  Defiant 721-128-H Instructions / Assembly  Betriebsanleitung Operating Instructions  USER MANUAL - Hatteland Display AS  115XT HiQ coaxial stage monitor tage monitor tage monitor 115XT    OPERATING INSTRUCTIONS MANUAL FOR “GMS” SOLENOID  Manuale dell`utente Serie N2310  ME415 MP3  