1. e g extending a detection zone During such circumstances it would be advisable to disable that zone so that it will not give false alarms Similarly you may wish to disable a zone that has a fault that has not been fixed or a zone covering an area with a temporary unusual environment such as an area which is dusty because of construction work etc Delays In public places it may be desirable to delay the activation of an alarm until the responsible person has verified the cause of the alarm This would avoid a panic evacuation caused by a smoky room or a maliciously activated call point On verification of the alarm the sounders can be started by pressing the override button or the panel can be reset in the case of a false alarm If a delay has been set it must be recorded on the system configuration chart at the back of this manual Power Supply Equipment General Description The INFINITY 8 FACP has an integral linear power supply capable of supplying 1 2 amps in total It contains a current limited output for charging sealed lead acid batteries 3 4 Ah maximum The PSE is monitored for main supply failure the battery not taking a charge low battery voltage and resistance If the battery voltage drops below approximately 20VDC a fault condition the battery charging current will be turned off thus stopping charging This PSE is only capable of supplying power to the CIE and is not designed for any other use Approved Docum
2. u asuntu un naa etas ea 11 OZONE TES 12 Winky use Zone MOST En 12 92 10 PROGRAMME ZONEN TEST deca a a b can ebd 12 9 3 NOTES OON TEST Z u obviare Bu cioe anta e er En rtis Uc 12 103 3 YSTEM DESCRIPTION utut 13 Tie FIRE ALARM LOG BOOK P a o ey 14 12 COMMISSIONING THE SYSTEM INCLUDING P S E 18 12 1 DESIGN INSTALLATION amp COMMISSIONING CERTIFICATES 18 Approved Document No GLT 201 7 2 PAGE 2 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 1 FIRE ALARM CONTROL PANEL SAFETY ISSUES There is no need to open this fire alarm during normal operation Any work carried out on this system must be performed by a competent person who is familiar with this type of system This equipment will operate safely provided it has been installed correctly in compliance with the Installation Manual It is recommended that the system is serviced frequently It is customary to arrange a regular maintenance contract with a competent organisation Ask the installation company for recommendations The system needs a thorough maintenance check annually at the very minimum If any part of this Fire Alarm Control P
3. 6 Take appropriate action to limit the rate of false alarms 47 2 f Ensure that all detectors and manual call points remain unobstructed at all times 47 2 0 Liaise with maintenance personnel to ensure that cleaning maintenance or building work does not interfere with the functioning and reliability of the fire alarm system 47 2 h 9 Ensure any changes to the system are recorded with updated drawings operating instructions etc 47 2 i 10 Ensure that there are spare parts especially Call point elements held on site 47 2 j 1 amp 2 Greece qoe With the nfinity 8 Range of Fire Alarm Panels we recommend the following tests are carried out Daily Inspection e Check that the green Power LED is lit e If there are any yellow fault LEDs lit or the green Power LED is not lit report the fault s to the designated site maintenance engineer Weekly Test you may wish to temporarily disconnect the Aux relay during the following Tests e Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate e Do not test the same device each week Test a different zone each week using a different call point or detector so that eventually all the devices will be tested e Reset the System by pressing Stop sounders Silence fault tone Reset e Enter access code Press the LED Test button Check that all LEDs light and the buzzer sounds e Check that no call points or fire detectors are obs
4. OVERRIDE EAE BUZZER RESET SOUNDER Two levels of control are available to the User s of this Fire Alarm Panel 4 1 GENERAL CONTROLS When the Panel is in its Normal state the indicator lights on the front of the enclosure give a comprehensive overview of the System s current status Any Fire and Fault conditions are clearly displayed and any disablements highlighted For detailed descriptions of what each indicator means please refer to the table on the opposite page The only functions that can be performed by the User when the Panel is in its Normal state are Esa e Overriding any Delays which may have been programmed into the Panel by pressing the L oer Override Sounder Delay button Putting the Panel into the Accessed state see below 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY To avoid unauthorised changes to critical parts of the Fire Alarm System controls such as silencing the Sounders resetting an Alarm condition and implementing Disablements are only accessible via a secure method of entry which puts the panel into the Accessed state To put the Panel into the Accessed State Entre the access code 1245 then To exit accessed state press three times If the wrong code is entered three times then the LED display will light a combination of LED s If this happens you will need to contact GLT Exports for the code Changing the Access Code Enter the current access code and
5. REQUIRED COMPLETED Approved Document No GLT 201 7 2 PAGE 17 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 12 COMMISSIONING THE SYSTEM INCLUDING P S E e The commissioning of this fire alarm system should be performed by a qualified commissioning engineer who has an understanding of sections 2 3 amp 4 of BS5839 pt 1 2002 i e Design considerations Limitations of false alarms Installation recommendations e The system layout drawing should be checked for accuracy amp stored in a safe place accessible to any fire officer e The system set up data chart GLT MAN 110 section 9 should be checked for accuracy e The fire alarm log book contact details should be checked for completeness e The insulation of cables should be checked in accordance with BS5839 Pt1 2002 clause 38 2 for compliance e The Earthing should be checked in accordance with BS5839 Pt1 2002 clause 38 2 for compliance e The PSE mains feed from a 3A spur should be checked It should be protected by an over current device MCB NOT an earth leakage device RCD e The PSE Charger voltage should be checked amp adjusted if necessary 28 3 with batteries disconnected e battery voltage should be checked should be between 24 amp 27V e All call points amp detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel e The Sound pressure level throu
6. TRE PANEL tise dvor cies erbe eei e d are Debes Dur Pura teat vere hri ren 7 o TEE TAUEITCONDETDIONL Ss did ies Eta Eau Dis mr yw an CS COE 8 O L DIFEERENT TYPES OFRFAU u unuy qud u nuna Do detta s ro 8 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS 9 Pim 10 7 1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM 10 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDERS 10 7 3 TO ENABLE A ZONE AND OR EXTERNAL SOUNDERS 10 B USING SOUNDER DELAYS Lu uu uu e n cS 11 ST WHAT ISA SOUNDEP DEEA Y uuu umumi a Putas s Cuba prod E Cave o da cvv 11 92 SOUNDER DELAY SE THN G Zx iu nuusan uma n Paw tnc aded la pup S a bouis 11 8 3 HOW THE PANEL INDICATES SOUNDER DELAY 11 8 4 A FIRE ALARM CONDITION ON A DELAYED PANEL ener 11 8 5 OVERRIDING A DELAY IN THE EVENT OF A GENUINE FIRE 11 8 6 RESET THE SYSTEM IN THE EVENT OF A FALSE 11 TO TURBN OFE THE SOUNDER DELAY u u u uuu
7. can be reasonably ascertained of an acceptable standard l The entire system has been inspected and tested in accordance with the recommendations of 39 2 of BS 5839 1 2002 _I The system performs as required by the specifications prepared by _I Taking into account the guidance contained in section 3 of BS 5839 1 2002 I we have not identified any obvious potential for an unacceptable rate of false alarms _I The documentation described in Clause 40 of BS 5839 1 2002 has been provided to the user The following work should be completed before after delete as applicable the system becomes operational The following potential causes of false alarms should be considered at the time of the next service visit Before the system becomes operational it should be soak tested in accordance with the recommendations of Clause 35 2 6 of BS 5839 1 2002 for a period of enter a period of 1 week the period required by the design specification or the period recommended by the signatory to this certificate whichever period is the greatest or delete if not applicable Approved Document No GLT 201 7 2 PAGE 22 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK Acceptance Certificate Certificate of ACCEPTANCE for the Infinity 8 Fire Alarm System installed at ADDRESS I we being the competent person s responsible as indicated by my our signatures below for the acceptance of the f
8. display press override sounder delay VERY SLOW 025HZ 4 4 CHECKING THE PANELS INDICATION LEDS To test panel LED s press p button All the LEDs on the front panel will light and the panel s internal buzzer will also sound This function is available at Level 1 Approved Document No GLT 201 7 2 PAGE 6 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 5 THE FIRE CONDITION 5 1 HOW THE NFINITY 8 INDICATES AN ALARM fl OPERATING INSTRUCTIONS GENERAL INDICATIONS FIRE ALARM CONTROL PANEL Poa Deak ondoa WLED on xu Sapa ipei EN54 2 amp EN54 4 REFER TO MANUAL j gt Fee FAULT DIA ZONAL INDICATIONS me fu cam a GENERAL GENERAL CONTROLS ZONE FIRE DISABLEMENT ZONE FRE nea E Mm BP oisastewent ENABLED TEST TEST 1 E E 5 gt gt 2 6 m 3 gt gt 7 gt b gt 4 gt 8 START STOP SILENCE OVERRIDE SOUNDERS a SOUNDERS BUZZER RESET SOUNDER When the nfinity 8 Fire Alarm Panel is set into alarm by a Detector or Manual Call Point located in a zone that is not already in alarm it will e Light the General Fire LED and appropriate Zone Fire LED s on the front of its enclosure e Sound Internal buzzer e Start the Alarm Sounder and Auxiliary output provided there is no Delay set on the sounders The building evacuation procedure should now be followed IMPORTANT NO
9. INFINIT Y FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE amp LOG BOOK INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK Contents 1 FIRE ALARM CONTROL PANEL SAFETY ISSUES eese eise sene aaia nana rina 3 2 IHE PURPOSEOFA FIREALABNESYSTENU au uu a uya mu yy fusca Races 3 3 USER RESPONSIBILITIES amp MAINTAINENCE OF THE FIRE ALARM SYSTEM INCLUDING THE FAGP S ITS INTEGRAL PSE witout eens uqa E teeta vated Yd Yo bsa ss 4 A PANEL INDIGATIONS a CONTROLS tti de DERE Da bronca Qut Con eite su C 5 Aol GENERAL GON T ROUS ais sut aka du s ins 5 4 2 ACCESSED CONTROL AVAILABLE TO AUTHORISED USERS ONLY 5 4 3 SUMMARY OF LED COMBINATIONS AND THEIR 6 4 4 CHECKING THE PANELS INDICATION LEDS a a a 6 S THESEIBE GONDITFION o pare rt aa Pec eu a Suma 7 5 1 HOW THE INFINITY 8 INDICATES AN ALARM usun ak ee i e rec cce 7 5 2 TO TURN OFF THE ALARM SOUNDERS nennen nnnm nnn nnns 7 5 3 A SECOND ALARM SIGNAL FROM NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING uu E 7 50 RESELL LING
10. LT FLASHING YELLOW circuits GEN FLT amp FLASHING YELLOW There is a short circuit fault in the wiring of one or both of the sounder SND FLT FLASHING YELLOW circuits GEN S C FLASHING YELLOW GEN FLT amp CONSTANT YELLOW A processor fault has occurred To reset If problem persists consult your SYSTEM FLT CONSTANTYELLOW dealer GEN FIRE NOLED A manual evacuation has occurred ONLY The sounders will be active GEN FIRE amp CONSTANT RED A fire has occurred in the zone indicated ZONE FIRE CONSTANT RED The sounders will be active GEN FIRE amp CONSTANT RED A fire has occurred in the zone indicated ZONE FIRE amp CONSTANT RED The sounders have a delay set and will oecome active after the GEN DISABLE CONSTANT YELLOW amp DEL CONSTANT YELLOW GEN DISABLE FLASHING YELLOW The panel is ready for selecting disable or test mode FAST 4 HZ GEN DISABLE FLASHING YELLOW The panel is in SELECT DISABLEMENT MODE SLOW 05HZ GEN DISABLE FLASHING YELLOW The user is scrolling through zones to select which one to disable or user ZONE DISABLE SLOW 05HZ has just enabled the zone GEN DISABLE CONSTANT YELLOW The indicated zone is disabled ZONEDISABLE CONSTANT YELLOW GEN DISABLE CONSTANT YELLOW The Sounders are delayed by the amount set on the rotary switch DEL CONSTANT YELLOW GEN TEST FLASHING YELLOW The indicated zone is in Test Mode ZONEDISABLE FLASHING YELLOW programmed delay To override the
11. SIGN for the Infinity 8 Fire Alarm System installed at ADDRESS I we being the competent person s responsible as indicated by my our signatures below for the design of the fire alarm system particulars of which are set out below CERTIFY that the said design for which I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name Block Letters sitios Signature ates For amp onbehalfof Addres o O The extent of liability of the signatory is limited to the system described below System Category see BS 5839 1 2002 Clause 5 o O Variations from the recommendations of section 2 of BS 5839 1 2002 see Clause 7 Extent of system covered by this certificate Brief description of areas protected not applicable for Category M L1 or P1 systems Approved Document No GLT 201 7 2 PAGE 19 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK Design Certificate vzo Measures incorporated to limit false alarms Account has to be taken of the guidance contained in section 3 of BS 5839 1 2002 and more specifically tick as appropriate l The System is manual Type amp siting of manual call points takes account of the guidelines co
12. TE If a zone has been disabled it cannot be triggered into Alarm This should be remembered when disabling part of the system See Disabling zones or sounders later in this manual 5 2 TO TURN OFF THE ALARM SOUNDERS e The Alarm Sounders may be silenced by entering the access code section 4 2 and momentarily pressing pem the 222223 button The Alarm Sounders will cease to sound but the light s for the Zone s in Alarm and the red General Fire light will stay lit The Auxiliary Fire relay will remain active The Panels internal buzzer can also be silenced by pressing SILENCE the E23 button 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE If another detection Zone is activated after the Alarm Sounders have been silenced the panel will e Restart the sounders e Light the Zone Fire LED s for any new Zone s in alarm e Keep the light s for the previous Zone s in fire and General Fire lit 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING e Enter code and press momentarily pressing the 8 will cause the Alarm sounders to sound STOP Pressing the button again will Silence the Alarm Sounders STOP START Note If the Alarm Sounders have been disabled pressing the button will have no effect 5 5 RESETTING THE PANEL e Check the cause of the alarm activation If the cause of the alarm was an activated call point reset it if resettable type or fit a new glass elemen
13. anel becomes damaged contact the company responsible for system maintenance to arrange repair replacement European Union Directives Conformance Statement This product has been manufactured in conformance with the requirements of all applicable EU Council Directives The Declaration of Conformance for this product is located at the following Address GLT Exports Ltd 72 78 Morfa Road Hafod Swansea SA1 2EN United Kingdom 2 THE PURPOSE OF A FIRE ALARM SYSTEM A Fire Alarm System is used to provide an early warning of a fire so that the property can be evacuated and the fire extinguished if it can be safely tackled or the local fire brigade called according to the company evacuation procedure Alarms can come from Smoke or Heat Detectors or manually be a person operating a Manual Call Point Split the system into Zones each covering a different area of a building This will indicate which area of the system is giving the alarm or fault During an alarm the panel will start its sounders and indicate which zone has the fire It will also activate its auxiliary relay Fault Monitoring All circuits must be checked for line integrity If a part of the system has a problem which may affect its operation a fault warning must be given by the fire alarm panel LED amp buzzer indication The fault relay will also activate Disablements An engineer may be required to work on part of a system while the system is still active
14. ause 7 The wiring has been tested in accordance with the recommendations of clause 38 of BS 5839 1 2002 The test results have been recorded and provided to o Unless supplied by others the as fitted drawings have been supplied to the person responsible for commissioning the system see BS 5839 1 2002 clause 36 2m o Approved Document No GLT 201 7 2 PAGE 21 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK Commissioning Certificate Certificate of COMMISSIONING for the Infinity 8 Fire Alarm System installed at ADDRESS I we being the competent person s responsible as indicated by my our signatures below for the commissioning of the fire alarm system particulars of which are set out below CERTIFY that the said work for which I we have been responsible complies to the best of my our knowledge and belief with the recommendations of Clause 39 of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters Position Signature ates 00 0 For amp onbehalfof Address fe The extent of liability of the signatory is limited to the system described below Extent of the installation work covered by this certificate Variations from the recommendations of clause 39 of BS 5839 1 2002 see clause 7 All equipment operates correctly I Installation work is as far as
15. code default 1245 and press 2 Hold the Disable button for 3 seconds START 3 Type the number of the zone you want to disable If you want to disable a sounder press Start Sounders button 4 Press to disable the selected zone or sounder 5 To exit the disable mode Hold the Disable button for 3 seconds wvepamsmse CONTROLS RM 25 Showing all the Disabled Zones 1 Enter access code and press 2 Press Disable c 7 3 TO ENABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Enter access code and press 2 Press and hold Disable button for 3 seconds Disable and zone light flash 9 Press 4 Press and hold the disable button for 3 seconds Disable LED goes out 5 Press OK three times to exit NOTES The option of disabling or enabling zones 2 3 4 5 6 7 and 8 is only available if these zones are present on the panel Approved Document No GLT 201 7 2 PAGE 10 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 8 USING SOUNDER DELAYS 8 1 WHAT IS A SOUNDER DELAY In certain circumstances it may be desirable to have a delay between the panel detecting a fire and starting its external sounders to allow the responsible person to check the cause of the alarm to stop building evacuation by an obvious false alarm If the cause of the Alarm is found to be a true fire hazard the Delay can be overridden and the Alarm Sounders activated immediately Alternat
16. ect the fault Usually by contacting the service engineer On the nfinity 8 panel the fault indications except system fault are non latching That is when the fault has been cleared the fault indication will turn off When all faults have been cleared the panel will return to its quiescent normal condition When a fault has been rectified the indicator light for that Fault is automatically turned off If all Faults are cleared the General Fault light will go out and the Panel s Internal Sounder will be silent if not already muted Approved Document No GLT 201 7 2 PAGE 9 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 7 DISABLEMENTS 7 1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM Certain parts of this Fire Alarm Panel can be temporarily disabled i e switched off to suit prevailing conditions For example if there is a risk of a False Alarm in a zone for example from vehicle exhaust smoke in a loading bay it is possible for the user to disable that zone during the risk period and then enable it again afterwards During a disablement of a zone s no fire or fault signal will be processed for that zone s Only zone s in a non alarm state can be disabled that is zones already in fire cannot be disabled External sounders can also be disabled as could be required in certain conditions 7 2 TO DISABLE A ZONE AND OR EXTERNAL SOUNDERS 1 Enter the access
17. ent No GLT 201 7 2 PAGE 3 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 3 USER RESPONSIBILITIES amp MAINTAINENCE OF THE FIRE ALARM SYSTEM INCLUDING THE FACP amp ITS INTEGRAL PSE According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings BS5839 Pt 1 2002 the owner or person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm System Clause 47 1 Below is a summary of the main functions the Responsible Person is expected to carry out This summary is not intended to replace Section seven User responsibilities of BS5839 Pt 1 2002 available from BSI or your local library It is meant to give a brief outline of user responsibilities for the safe upkeep of the Fire Alarm System The number in brackets shows the relevant BS5839 Pt 1 2002 clauses The responsible person must Have sufficient authority to carry out the duties associated with being the responsible person 47 2 a Check the system at least once every 24 hours to ensure there are no faults present 47 2 b Ensure there are arrangements for testing and maintaining the system 47 2 c Ensure the log book is up to date and available for inspection 47 2 d Instruct all relevant occupants on the basic operation of the system including start evacuation silence alarms silence faults and system reset 47 2
18. ghout the building should be checked for compliance with the recommendations of BS5839 Pt1 2002 clause 16 2 e Any deviations from BS5839 Pt1 clause 7 2 should be listed in the Certificate of Installation amp Commissioning e The Certificate of Installation amp Commissioning should be completed and the whole user manual passed to the relevant person on site They should be given a brief training on the basic operation of the FACP 12 1 DESIGN INSTALLATION amp COMMISSIONING CERTIFICATES The guidelines in BS 5839 Pt1 2002 say that each stage of the system design and installation should have a separate certificate Before this User Manual is handed over to the relevant person s on site the following certificates or the relevant company s equivalent should be completed by the system designer the installation engineer and the commissioning engineer The System Description sheet should also be completed on Page 12 as should the relevant parts of the Log Book section on Page 13 The user or responsible person should then complete the acceptance certificate to acknowledge that they have been instructed in the use of the fire alarm have witnessed that it is operational and have been given all the relevant paperwork drawings log book user manual etc Approved Document No GLT 201 7 2 PAGE 18 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK Design Certificate Certificate of DE
19. ided by the purchaser or user MAINTENANCE It is strongly recommended that after completion the system is maintained in accordance with section 6 of BS 5839 1 2002 USER RESPONSIBILITIES The user should appoint a responsible person to supervise all matters pertaining to the fire alarm system in accordance with the recommendations of section 7 of BS 5839 1 2002 Approved Document No GLT 201 7 2 PAGE 20 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK Installation Certificate Certificate of INSTALLATION for the Infinity 8 Fire Alarm System installed at ADDRESS I we being the competent person s responsible as indicated by my our signatures below for the installation of the fire alarm system particulars of which are set out below CERTIFY that the said installation for which I we have been responsible complies to the best of my our knowledge and belief with the specifications described below and with the recommendations of BS5839 1 2002 except for the variations if any stated in this certificate Name Block Letters sitios Signature ates For amp onbehalfof Addres o O The extent of liability of the signatory is limited to the system described below Extent of the installation work covered by this certificate Specification against which the system was installed Variations from the specification and or section 4 of BS 5839 1 2002 see cl
20. ire alarm system particulars of which are set out below ACCEPT the system on behalf of Name Block Letters Signature For amp on behalf of Address The extent of liability of the signatory is limited to the system described below Extent of the system covered by this certificate All installation work appears to be satisfactory system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre operates correctly Delete if not applicable The following documents have been provided to the purchaser or user l As fitted drawings Operating and maintenance instructions I Certificates of Design Installation and Commissioning A log book _I Sufficient representatives of the user have been properly instructed in the use of the system including at least all means of triggering fire signals silencing and resetting the system and avoidance of false alarms I All relevant tests defined in the purchasing specification have been witnessed Delete if not applicable The following work is required before the system can be accepted Approved Document No GLT 201 7 2 PAGE 23 Issue 1 2 Authorised Date 27 3 2012
21. ively in the case of a false alarm the Panel can be reset 8 2 SOUNDER DELAY SETTING On the nfinity 8 panel the sounder delay can be programmed on zones 2 8 zone 1 cannot have a delay That is all zones will be delayed by the same amount The delay can be set between 1 minute and 10 minutes or the delay can be left off sounders activate immediately Changing the delay time should only be done by the engineer responsible for setting up the system But turning the delay on or off can be done by the user Activate Deactivate Sounder delay e Enter Access code default 1245 OVERRIDE SOUNDER DELAY J button e Press OVERRIDE OU e Press L button again to deactivate sounder delay 8 3 HOW THE PANEL INDICATES SOUNDER DELAY If a Delay has been programmed into the Panel the General Disablement amp DEL AY LEDs will be lit When a zone processes an alarm signal the panel will indicate fire in the usual way but the sounders will not be active until the delay period has expired To override this delay press Delay Override Switch which will cause the external sounders to energise If there is no delay programmed the Delay Override Switch has no function 8 4 A FIRE ALARM CONDITION ON A DELAYED PANEL When an alarm occurs on a Delayed Panel the panel will e Light its General Fire and appropriate Fire Zone light s e Sound its Internal buzzer e Start the Delay countdown sequence e Wait until the end of the delay and then star
22. ntained in section 3 of BS 5839 1 _I The system incorporates automatic fire detectors and account has been taken of reasonably foreseeable causes of unwanted alarms particularly in the selection and siting of detectors l An appropriate analogue system has been specified l An appropriate multi sensor system has been specified l A time related system has been specified Details _I Fire signals from automatic fire detectors result initially in a staff alarm which delays a general alarm transmission of signals to an alarm receiving centre delete as applicable for min l Appropriate guidance has been provided to the user to enable limitation of false alarms l Other measures as follows INSTALLATION amp COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be undertaken in accordance with the recommendations of section 4 and section 5 of BS 5839 1 2002 respectively SOAK TEST _I In accordance with the recommendations of clause 35 2 6 of BS 5839 1 2002 it is recommended that following commissioning a soak period of should follow enter a period of at least 1 week l As the system incorporates no more than 50 automatic fire detectors no soak test is necessary to satisfy the recommendations of BS 5839 1 2002 VERIFICATION Verification that the system complies with BS 5839 1 2002 should be carried out on completion in accordance with BS 5839 1 2002 Clause 43 Yes To be dec
23. on at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fire alarm events should be subdivided amp recorded on separate sheets in the log book The event categories are Maintenance work False alarms Where the sounders have activated with no signs of a fire Any other events This would be genuine alarms or faults Company Site Address System designed by System installed by System commissioned by aN RE Responsible Person s on Site System maintained by Approved Document No GLT 201 7 2 PAGE 14 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK MAINTENANCE WORK DATE TIME ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL WORK REQUIRED Approved Document GLT 201 7 2 PAGE 15 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK FALSE ALARMS DATE TIME ZONE CAUSE IF KNOWN MAINTENANCE MAINTENANCE CATEGORY FURTHER LOCATION OR ACTIVITIES IN VISIT NEEDED FINDINGS FALSE ALARM ACTION ALARM AREA YES NO REQUIRED Approved Document No GLT 201 7 2 PAGE 16 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME ZONE LOCATION DETAILS OF EVENT ACTION DATE INITIALS INCLUDING CAUSE IF KNOWN
24. press control Enable lit for 3 seconds panel will ral Re type the access code and press lt Type the new code Press for 5 seconds The will give a confirmation beep New code is active Press DY seo qe Information on how to use the accessed control can be found on Pages 8 to 11 of this User Manual Approved Document No GLT 201 7 2 PAGE 5 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 4 3 SUMMARY OF LED COMBINATIONS AND THEIR MEANING Use the table below to determine the condition of the panel LEDs LIT LED CONDITION PANEL STATUS POWER CONSTANT GREEN The panel is supplied with power and has no faults fires System Normal GEN FLT FLASHING YELLOW ONLY GEN FLT amp FLASHING YELLOW There is a problem with either the mains supply or the battery backup SUPPLY FLT FLASHING YELLOW Consult Installation manual for details of flash meanings GEN FLT amp FLASHING YELLOW There is a wiring problem One of the cables is touching the earth screen EARTH FLT CONSTANT YELLOW GEN FLT amp CONSTANT YELLOW There is an open circuit fault in the wiring of the zone indicated ZONAL FLT FLASHING YELLOW GEN FLT amp FLASHING YELLOW There is a short circuit fault in the wiring of the zone indicated ZONAL FLT FLASHING YELLOW GEN S C FLASHING YELLOW GEN FLT amp FLASHING YELLOW There is an open circuit fault in the wiring of one or both of the sounder SND F
25. reset The panel has been designed so it cannot be left in test mode if the user needs to access another function e g disable 9 2 TO PROGRAMME ZONE IN TEST 1 Enter access code and press ox 2 Hold AD button for 3 seconds 3 Select the zone you want to go in test mode by typing the number with the keypad 4 Press to start test mode 5 Press again to stop test mode 6 To leave test mode hold p es button for 3 seconds 9 3 NOTES ON TEST MODE Test mode provides a way to test a system without indicating there is a fire as the sounders turn off after about 4 seconds While extremely useful during system testing careless use of test mode could be dangerous if a real fire occurs in an area under test In order to limit the misuse of test mode the infinity panel uses the following methods 1 Only one zone at a time can be put into test mode leaving up to 7 zones fully functional and able to report a fire 2 Itis not possible to leave the panel in test mode while performing other panel functions such as disablement 3 Itis not possible to leave a zone in test mode If the panel is left in test mode it will time out after a period of inactivity Approved Document No GLT 201 7 2 PAGE 12 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 10 SYSTEM DESCRIPTION FIRE ALARM SYSTEM SUMMARY FIRE ZONE INFORMATION NUMBER A brief description of all the rooms and area
26. s contained in each zone SNDR MCP HEADS ER Re NES eee _ 2 Jj j i j 1 _ 3 j j j j og _ 5 j RENI 1 C E _ j j _ 7 j j j j ERI 1 EE j j NE j D es Sounder SOUNDER CIRCUIT DESCRIPTION QTY QTY Circuit A brief description of all the rooms and areas contained in each circuit SNDR BELLS Circuit 1 Circuit 2 Circuit 3 Circuit 4 Any Other Information about The Sounder Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output ADDITIONAL INFORMATION Any additional information the User needs to know about should be inserted into this box including details of the routing of any additional outputs details of inputs utilised etc THE INFORMATION ABOVE WAS COMPLETED BY NAME COMPANY POSITION DATE Approved Document No GLT 201 7 2 PAGE 13 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 11 FIRE ALARM LOG BOOK It is recommended that this LOG BOOK section of the Manual be maintained by the responsible person s on site who should ensure every event is properly recorded including fire alarm conditions failures tests temporary disconnections disablements enablement s dates of installing engineers visits together with a note of any outstanding work or panel conditions This LOG BOOK must be available for inspecti
27. t if glass type If the cause of the alarm was by detector activation Approved Document No GLT 201 7 2 PAGE 7 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK e g cooking smoke the smoke will have to be cleared from the room before the panel can be reset Reset the panel by pressing the C after the sounders and panel buzzer have been silenced e If the call point is still active or the detector is still smoky this will cause another alarm straight after the panel is reset so will set off alarm bells again 6 THE FAULT CONDITION 6 1 DIFFERENT TYPES OF FAULT The fire alarm monitors itself and any equipment connected to it for any faults that can occur If a fault occurs the Panel responds by activating its Internal buzzer and lighting the General Fault light and any other Fault light s relevant to the particular fault The Panel s Fault relay will also activate Typical faults are described below EMEN __ ___ pf Approved Document No GLT 201 7 2 PAGE 8 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs the responsible person should SILENCE e Enter the access code and press to enabled controls and press to silence the fault buzzer e Write down the fault s in the Log Book at the back of this Manual Take appropriate action to corr
28. t the sounders 8 5 OVERRIDING A DELAY IN THE EVENT OF A GENUINE FIRE ALARM OVERRIDE If on investigation the cause of the Alarm is found to be a true fire hazard pressing the DELAY will active the Alarm Sounders and Outputs with immediate effect 8 6 RESET THE SYSTEM IN THE EVENT OF A FALSE ALARM If on investigation the cause of the Alarm is found to be false enter the access code and press button 8 7 TO TURN OFF THE SOUNDER DELAY 1 Enter access code 1245 Lok OVERRIDE 2 Press Sounder Delay E OVERRIDE 3 Press Sounder Delay Eu again to deactivate Sounder Delay Approved Document No GLT 201 7 2 PAGE 11 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 9 ZONE TEST 9 1 Why use Zone Test To aid commissioning and assist routine maintenance checks a non latching One Man Test facility is available When a detector or manual call point is triggered on any zone in test the alarm sounders operate for approximately 5 seconds on and 5 seconds off This cycle continues until the cause of the alarm is removed either by the test smoke clearing from the detector or the manual call point being reset At which point the detector circuit is automatically rest Should an alarm occur on a zone that is not programmed to test the alarm will be processed iin the normal way The testing of the zone in test will temporarily be suspended until the alarm s from the other zones are
29. tructed in any way e g New furniture or decorations Quarterly Test to be carried out by authorised service personnel only e Check that any servicing or repairs required by all previous logbook entries has been undertaken e Visual inspection of the batteries and connections Check the alarm sounders work on battery only e Activate a device from each zone to test the fire alarm As per weekly test Annual Test to be carried out by authorised service personnel only Check every detector call point sounder and all auxiliary equipment for correct operation Check Cage output Voltage 30VDC Charger Voltage 27 6Vnormal 29 4V fast charge amp Battery Voltage 25 27V Every Five Years to be carried out by authorised service personnel only e Carry out a complete wiring check in accordance with the testing and inspection requirements of the relevant National wiring regulations in the UK this is the IEE Wiring Regulations The Batteries should be replaced because SLA batteries have a working life of 5 years Approved Document No GLT 201 7 2 PAGE 4 Issue 1 2 Authorised Date 27 3 2012 INFINITY 8 USER MANUAL MAINTENANCE GUIDE amp LOG BOOK 4 PANEL INDICATIONS amp CONTROLS OPERATING INSTRUCTIONS GENERAL INDICATIONS t Power LED on INFINITY em PED FIRE ALARM pub PANEL EN54 2 amp E ZONAL INDICATIONS FAULT FIRE DISABLEMENT ZONE i START STOP SILENCE 2