CoolCube 12 User`s Manual
Contents
1. Controller Programming Menu 1 Make sure the unit has power 2 Pushing the POWER button turn the unit OFF 3 Press the following buttons in sequence S U D S 4 The display will begin flashing P1 and a number If there is no display repeat the sequence making sure the unit has power but is turned OFF 5 To adjust any program parameter press the ARROW UP or ARROW DOWN 7 button until the desired value is displayed 6 Use the MODE button to scroll through the programmable parameters P1 through P16 7 If no buttons are pushed the display will then return to the OFF position after about 50 seconds Programming Parameters P1 High Fan Speed Limit Setting P2 Low Fan Speed Limit Setting P4 Temperature Sensor Calibration P10 Temperature Display F or C P13 Supply Fan Operation Cycling or Continuous P1 P2 To adjust fan speed settings P1 represents the high fan speed parameter while P2 represents the low fan speed parameter When using nozzle kits discharge duct adapters and evaporator plenums setting P1 to 85 will help to avoid freeze ups Xtreme Power Conversion Corporation Page 20 CoolCube 12 User s Manual Portable Air Conditioning P4 Adjust the P4 setting to match the actual INSIDE room temperature if needed P10 Use this parameter to display temperatures in the desired units P13 To cycle the evaporator fan with the compressor access code P 13 Press t
2. 23 PASS CAE E E 24 ES ER a a E 25 SOR VI CC ana a ae er nec 00 Xtreme Power Conversion Limited 27 Xtreme Power Conversion Corporation Page 2 CoolCube 12 User s Manual Portable Air Conditioning Forward This manual provides the user with basic details for the installation and operation of the CoolCube 12 spot cooler It is recommended to read and fully understand the instructions outlined within this manual before operating the unit As with all commercial air conditioning equipment it is recommended to have the CoolCube 12 sized and installed by a licensed specifying engineer and contractor in accordance with all local and state codes The length of ser vice received can be extended by following the installation and preventive maintenance instructions Notice In our ongoing process of continuous improvement the items and procedures described in this manual are subject to change without notice Please note model and serial number of the CoolCube 12 when contacting the factory Xtreme Power Conversion Corporation Page 3 CoolCube 12 User s Manual Portable Air Conditioning General Description The CoolCube 12 is a portable air cooled spot cooler designed for permanent or temporary spot cooling The entire air conditioning unit has been built in an premium sheet metal cabinet equipped with heavy duty casters for mobil
3. 2 2 7 SATE TANK Installation Receiving Inspection Upon receiving your CoolCube 12 inspect the packaging for any damage All units are shipped on a skid and packaged a triple wall carton for added protection In shipment some wear may occur on the packaging If the packaging is heavily damaged or broken file a claim with the freight company immediately Carefully unpack the unit and remove all wrapping materials Save all documentation and fill out the Warranty Card and mail it to Xtreme Power Before Installing Check the CoolCube 12 for any damage All Xtreme Power products are thoroughly inspected at the factory and carefully packaged If any damage is evident file a claim with the delivering carrier immediately Electrical Requirements Check the nameplate located on the back of the unit to make certain that the proper power is available for the unit Refer to Specifications section for voltage and amperage requirements For proper NEMA receptacles refer to Electrical service plug configuration When using extension cords use the properly sized cord and check cord voltage to the unit TIME DELAY FUSES CIRCUIT BREAKERS ARE RECOMMENDED WARNING Operating the unit on improper voltage will void the warranty Accessories Verify that all accessories are correct for the model and that they installed in accordance with all instructions Start Up Install the unit in accordance with all local and state bu
4. The controller has auto restart capability A built in memory retains the settings and the unit will restart to the last set point automatically after a power failure Fan Speed Control One of the features of the electronic controller is that the unit supply fan can be controlled automatically or manu ally In AUTO mode the evaporator blower will adjust air flow automatically for added comfort and performance Or if desired the fan speed can be set to MANUAL mode and the evaporator blower will run continuously at one of six levels of fan speed Condensate Reservoir Tank The CoolCube 12 unit comes equipped with a Condensate Reservoir Tank for handling the condensate generated during the cooling process When the tank is full the word CON will be displayed The tank can be easily removed from the unit and emptied as required Filters CoolCube 12 are equipped with washable filters at the air intakes Electrostatic mesh air filters located behind the evaporator return air grill serve to filter the air before it is cooled and behind the condenser return air grill to prevent dust build up Both filters can be easily removed and cleaned High Pressure Safety Switch Located on the back of the CoolCube 12 is a manual re set high pressure switch used for the protection of the compressor If the condensing pressure exceeds the limit setting the cut out shuts down the compressor while the evaporator fan remains running The display will indicate C
5. 14 filter NOTE When installing the condenser return air plenum with the ceiling panel kits allow for a minimum separa tion distance of 2 feet between the unit discharge duct and the return air duct s It is also recommended to direct the condenser discharge air away from the condenser return air ducts Xtreme Power Conversion Corporation Page 18 CoolCube 12 User s Manual Portable Air Conditioning Remote Thermostat Kit RTK 1 The RTK 1 is a field installed kit that allows for the display of the CAC1211 to be installed remotely allowing the unit to be controlled from within the conditioned space The kit includes a cover plate for the unit and a display installation panel NOTICE The RTK 1 requires a display cable sold separately 012 006 6 ft Display Cable 012 008 75 ft Display Cable 012 009 25 ft Display Cable 012 010 50 ft Display Cable Deluxe Electronic Controller The CoolCube 12 controller is equipped with many features for a more precise level of cooling and operation Ad ditionally the controller can be removed from the unit and installed for remote operation if desired accessory parts may be required Xtreme Power Conversion Corporation Page 19 CoolCube 12 User s Manual Portable Air Conditioning When power is connected the controller will display 888 momentarily and will then go blank Press the POWER button then press the TEMP SELECT button until the SET POINT is displayed
6. Adapter CDA 8 A discharge adapter is available for installations where it is required to duct air from the unit The discharge adapter easily attaches to the evaporator and or the condenser discharge and provides an 8 inch flange for con necting 8 inch flexible ducting Evaporator Discharge Condenser Discharge Xtreme Power Conversion Corporation Page 17 CoolCube 12 User s Manual Portable Air Conditioning Evaporator Return Air Plenum CEP 6 An evaporator return air plenum is available for installations where it is required to duct air to the inlet of the evaporator The evaporator return air plenums allow the user to connect round duct flexible or rigid to the re turn air intake to reduce air noise and increase the number of options for solving difficult cooling problems The plenum attaches to the front of the unit replacing the return air grill The CEP 6 transitions the return air opening to 2 6 inch round ducts The CEP 6 has space provided for a 16 X 8 Filter NOTE When a evaporator return air plenum is installed it is recommended to set the evaporator blower speed to high to avoid evaporator freeze up Condenser Return Air Plenum CCP 8 A condenser return air plenum is available for installations where it is required to duct air to the inlet of the con denser The plenum easily attaches and is provided with an 8 inch flange for connecting 8 inch flexible ducting The CCP 8 has space for a 16 X
7. GIVES THE ORIGINAL OWNER OF THE PRODUCT SPECIFIC LEGAL RIGHTS YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY BY EACH JURISDICTION USEFUL INFORMATION MODEL SERIAL NUMBER DATE PURCHASED INSTALLED BY DATE INSTALLED Xtreme Power Conversion Corporation Page 27
8. the address provided by the Technician 5 Refer to the Warranty statements in this manual for additional details on what is covered Xtreme Power Conversion Corporation Page 26 CoolCube 12 User s Manual Portable Air Conditioning Xtreme Power Conversion Limited Warranty Xtreme Power Conversion warrants to the original owner that the Product will be free from defects in material or workmanship for a period not to exceed one 1 year from date of installation If upon examination by the Manu facturer the Product is shown to have a defect in material or workmanship during the warranty period the manu facturer will repair or replace at its option that part of the Product which is shown to be defective The Manufacturer further warrants that the product s compressor motor will be free from defects in materials and workmanship for five 5 years from the date of installation If upon examination by the Manufacturer the Compressor Motor is shown to have a defect in materials or workmanship during the warranty period the Manu facturer will repair or replace at its option that compressor which is shown to be defective Electrical parts such as relays overloads capacitors etc and the sealed refrigeration system condenser and evaporator are included in the one year limited warranty but not with the five year limited warranty of the compressor This limited war ranty does not apply a if the Product has been subjected to misuse or neg
9. Adjust the SET POINT to the desired temperature and the unit will heat cool as required The systems controls temperature within 2 Turns the unit ON OFF when power is supplied When ON the display will light up and show the room 9 temperature MODE Selects the mode of operation from COOL to Moisture Control COOL The system will operate in cooling mode only MOISTURE CONTROL The system operates in the cooling mode to reduce humidity within the conditioned space Every 4 hours the fan is started circulating the air and the air temperature is recorded by the controller The cool ing cycle is started for one hour or until the room temperature drops 2 whichever comes first This cycle repeats every four hours FAN SPEED The operator can select between AUTO and MANUAL fan speed control Pressing the FAN SPEED button will switch speed from AUTO to MANUAL In MANUAL mode pressing the FAN SPEED button will change fan speed from low to high In AUTO the fan speed is controlled automatically In cooling mode the controller automatically adjusts the fan speed to high and as the inside temperature approaches the set point the fan speed will reduce In heat mode the fan speed goes from low to high as the temperature approaches the set point TEMP SELECT Allows the operator to view the controller temperatures INSIDE return air temperature OUT SIDE supply air temperature SET POINT can be seen and adjusted by pressing or
10. CENSED TECHNICIAN WARNING TO AVOID INJURY DISCONNECT UNIT POWER PRIOR TO SERVICING WARNING HAZARDOUS MOVING PARTS DO NOT OPERATE UNIT WITH PANELS REMOVED A Fan Motors 1 Remove cabinet s left side panel when looking at the front of the unit 2 Evaporator fan motor disconnect evaporator motor wires from evaporator fan motor leads on the power module Fan L 1 Fan L 2 Condenser fan motor disconnect condenser motor leads from power module Pump L 1 Pump L 2 Remove the wire leads from the wire races accordingly buy cutting the wire ties 3 Remove the screws securing motors and inlet ring to blower housings all screws are external and visible and remove blower wheel motor assembly Remove the blower wheel set screw and disassemble the blower wheel from the motor shaft and remove the motor 4 Install the new motor reversing the removal procedure 5 Re secure all wires to the existing wire races with wire ties making sure that all wires are secured from motion near moving parts B Electronic Controller 2 Parts 1 To remove the Cooling Only display locate the two screws securing the display to the front panel Once the display is removed unplug the display cable and remove the display Install new display by plugging in the display cable and securing the display on to the cabinet front 2 To remove the Power Module remove the left side panel Disconnect wires leads and cable connections going to the Power Module and r
11. CoolCube 12 12 000 User amp Installation Manual www xpcc com 2014 Xtreme Power Conversion Corporation All rights reserved Rev 10 28 14 CoolCube 12 User s Manual Portable Air Conditioning Table of Contents GENEALO GSCI ON esse os sisses encens eee a se ni D a aan aan han css est sciac E ins SONU A EL OS 6 6 7 CORTE 8 AON E E 9 25 45 ete Den ane 10 Installation PermanentlyConnected cscsscscssscscescncesscuscncusscuscncuscesesseussseusecususousesscscuuseseens 11 Installation Stackinge KIC Oe 12 installation Rack MOUNTING ROK 1 13 ACCE l 14 D l xe EIS CU ONG CONTE OIC Fea a ae ae at 19 SOVICE Ll Troubleshooting GUJE eae cn a 21 Replacement Procedure For 22
12. ON The compressor can be re started once the condensing pressure has lowered by depressing the RESET button Power Cords CoolCube 12 units come with a 10 ft power cord allowing for convenient connection and portability The power cord is equipped with a Leakage Current Detection Interrupt LCDI device for added safety Applications Spot Cooler The CoolCube 12 can be used in an open environment to cool specific objects or spots Spot Cooling is a con venient and economical way to provide air conditioning where cooling the entire space is impractical Cool air is discharged from the unit and is directed where it is needed Nozzle kits can be used to improve direction of the Xtreme Power Conversion Corporation Page 6 CoolCube 12 User s Manual Portable Air Conditioning cooling airflow Room Air Conditioner With the condenser fully ducted the CoolCube 12 can be used as a room air conditioner to cool an enclosed space Using the condenser return air panel CP 8 and ceiling discharge kit CK 8 the CoolCube 12 can operate as a room air conditioner with the condenser air isolated form the conditioned space Ceiling Mount The CoolCube 12 can be hung above a space or be installed above a drop ceiling allowing the unit to cool a room or area without taking up any valuable floor space Rack Mount The CoolCube 12 can be rack mounted inside a 19 inch computer rack occupying just 12U of rack space Front Back EVAP
13. ORATOR DISCHARGE CONDENSER DISCHARGE EVAPORATOR RETURN CONDENSER RETURN Electrical Portable Configuration The CoolCube 12 is equipped with a 10 ft power cord for ease of movement and portability The cord is to be plugged into a 15 Amp receptacle A dedicated circuit is required MODEL PLUG CONFIGURATION RECEPTACLE 15A 125 VOLT CAC1211 NEMA 5 15 NEMA 5 15R Service Cord The CoolCube 12 is equipped with a ten foot long service cord with LCDI Leakage Current Detection amp Interrup tion device that serve as a means of electrical protection DO NOT USE THE LCDI AS AN ON OFF SWITCH FOR THE UNIT Xtreme Power Conversion Corporation Page CoolCube 12 User s Manual Portable Air Conditioning A DAMAGED LCDI POWER SUPPLY CORD MUST BE REPLACED WITH A NEW POWER SUPPLY CORD AND NOT REPAIRED Use Of Extension Cords CAUTION AN EXTENSION CORD CAN BE USED PROVIDED IT IS RATED AT LEAST 15 AMPS 115 VOLTS WITH GROUNDING TYPE ATTACHMENT PLUG AND GROUNDING TYPE CONNECTOR LOAD FITTING Permanent Installation The CoolCube 12 can be installed in a permanent configuration and the control box is suitable for field wiring The unit can be hung from 5 16 threaded rods or be installed with the use of UniStrut Instructions for Permanent installations are on Pages 8 and 9 in the manual When hanging and permanently connecting the CoolCube 12 all applicable local state federal building codes must be followed The struc
14. S ONLY N 7 8 DIA CONTROL BOX FIELD WIRING Installation Stacking Kit SK 1 Two or three CoolCube 12 units are required when redundancy is critical cooling large areas or high heat loads The CoolCube 12 can be stacked on top of each other to produce a capacity of 24 000 or 36 000 BTUH while main taining the same footprint To facilitate the stacking of the CoolCube 12 units a stacking kit SK 1 is required for each additional unit 1 Disconnect Power before Servicing Remove Handles from units and remove the casters from the unit to be stacked Install rubber feet on base of unit to be stacked Carefully stack the units each unit weights approximately 130 Ib Secure the stacked unit to the one below it by using the stacking rails provided Install rails on both sides of units aS Xtreme Power Conversion Corporation Page 12 CoolCube 12 User s Manual Portable Air Conditioning Installation Rack Mounting Kit RCK 1 19 Inch Rack Kit allows for the CoolCube 12 be installed into any 310 0 4 Post of 2 Post rack enclosure The kit includes 2 heavy duty rails 4 side mounting brackets and a rear mounting rail The rails have a vibration dampening foam layer secured to the top for noise reduction The hardware included in the kit will accommodate most installations such as Square Hole Racks 12 24 Threaded Racks 10 32 Threaded Racks and round hole racks 1 os Disconnect Power befo
15. U H Air flow high low evaporator 400 320 CFM Air flow condenser 490 CFM Refrigerant R410A ELECTRICAL Power supply voltage 115VAC Power supply frequency 60Hz Current consumption 12A Circuit breaker size 15A Power consumption 1180W NEMA plug 5 15 Power cord length 10 ft Automatic restart Unit automatically restarts when power is reapplied after outage PHYSICAL Dimensions W x D x H 17 3 x 24 0 x 20 0 in Weight 133 lbs Operating conditions 65 105 Hot air duct diameter 8 Condensate tank capacity 2 gal APPROVALS UL cUL WARRANTY 1 year system USA 5 year compressor warranty Xtreme Power Conversion Corporation Page 5 CoolCube 12 User s Manual Portable Air Conditioning Unit Description Standard Features Cabinet The CoolCube 12 spot cooler has a cabinet that is constructed of 18 gauge steel with a polyester powder coated finish The matte black finish compliments any surrounding space and the cabinet is lined with sound absorbing insulation for cool quiet comfort The CoolCube 12 comes equipped with handles and premium swivel casters for portability and convenient set up Deluxe Electronic Controller The CoolCube 12 unit is equipped with deluxe electronic controller When power is connected to the unit the thermostat will control the unit to cool a space to the desired temperature The thermostat is also capable of con trolling the fan to operate automatically when needed or continuously Auto Restart Feature
16. be required PROBLEM UNIT DOES NOT POWER UP CAUSE Power interruption REMEDY Check external power supply making sure that the disconnect is ON Check for blown fuses or tripped circuit breakers Reset or replace if needed CAUSE LCDI has tripped REMEDY Check LCDI and reset LCDI on power cord CAUSE Loose display cable REMEDY Re seat display cable at display and power module Xtreme Power Conversion Corporation Page 21 CoolCube 12 User s Manual Portable Air Conditioning PROBLEM EVAPORATOR FAN RUNS BUT COMPRESSOR AND CONDENSER FAN DO NOT START Note there is a time delay for the compressor CAUSE SET POINT setting may be too high for cooling REMEDY Make sure set point is adjusted accordingly You should see a red dot to the right of the temperature display indicating compressor ON CAUSE Loose Display Cable REMEDY Examine the control unit for loose wires Tighten any loose connections CAUSE Condition Alarm CON REMEDY Check condensate tank and empty tank or check condensate pump and make sure pump is working properly and that there is no kink in the drain line from the pump CAUSE High Pressure Cut Out CON Check High Pressure Cut out Switch Press Reset and clear away any ob structions to the condenser intake or condenser discharge CAUSE Defective Power Module REMEDY Replace Power Module Replacement Procedure For Parts IT IS RECOMMENDED THAT ALL COOLCUBE 12 UNITS BE SERVICED BY A LI
17. e the warm condenser air Check local codes to assure compliance Ceiling Panel Conversion Kit CVK 8 The CK 8 can be converted to a dual ducted ceiling panel by use of the CVK 8 conversion kit The kit contains the parts necessary to install a second 8 Inch duct flange and a condenser discharge baffle onto the CK 8 ceiling panel This allows for ducting of condenser air to and from the drop ceiling plenum The kit contains an 8 inch duct flange and a discharge air baffle that can be installed onto the ceiling panel as shown below along with an 8 inch flex duct The baffle can be installed in various orientations to direct the discharge air away from the condenser return air above the ceiling panel Xtreme Power Conversion Corporation Page 15 CoolCube 12 User s Manual Portable Air Conditioning Note Drop ceiling spaces should be vented or large enough to handle the warm condenser air Check local codes to assure compliance WHEN INSTALLED THE CONDENSER DISCHARGE SHOULD BE DIRECTED AWAY FROM THE CONDENSER AIR RE TURN Condensate Pump Kit CPC 1 The condensate pump provides for the automatic removal of condensate water during the cooling process The pump is capable of pumping against a 20 foot head allowing for the routing of the drain line above the drop ceiling to a nearby drain The pump is controlled by an internal float switch which turns the pump on and off automati cally The pump is also equipped
18. emove power module Install new power module and re wire in ac cordance with the wiring diagram C Condensate Pump On Units With Condensate Pump Kits Installed 1 Remove the left side panel 2 Remove bracket screws securing condensate pump to the tank tray 3 Disconnect pump wire leads at Molex connectors Remove retainer clamp and tubing 4 Replace pump Xtreme Power Conversion Corporation Page 22 CoolCube 12 User s Manual Portable Air Conditioning install by reversing procedure D High Pressure Safety Switch 1 Remove the left side panel 2 Remove flare nut that secures capillary to the refrigeration system high pressure side NOTE A Schrader valve is located in the discharge port and allows removal without losing the refrigerant charge Remove two screws that secure the high pressure switch to the back panel Cut the wire leads at a place approximately 6 inches from the switch 5 Install new High Pressure Control and splice the wire leads from the switch to the existing low voltage wires To gain access to compressor and compressor run capacitor remove top right side panel Preventive Maintenance CoolCube 12 are designed to last a long time and to give maximum performance and reliability with minimum maintenance To prolong the life of the unit regular maintenance must be performed as specified below Blower Motors The motors on all units have permanently lubricated bearings No oiling is necessary Filt
19. ers A clogged filter will cause the unit to operate at greatly reduced efficiencies We recommend that the filter be inspected on a regular bases every six weeks or more often depending on the environment The evaporator filter is located behind the return air grille and can be easily removed and cleaned The condenser filter is located in the lower backside of the unit Remove by loosening one screw holding retaining clip and pull out The filters must be washed periodically as needed by placing them in a dishwasher or soaking them in a solution of warm water and detergent for 10 minutes Then rinsing them clean with hot water and shaking excess moisture from filter Condensate Pump Condensate pumps come standard on all Size 60 models and may be installed as options on size 12 18 24 and 36 models When servicing pump follow these steps 1 Make certain that the unit is disconnected from the power source before attempting to service or remove any component 2 Be sure the floats move freely Clean as necessary 3 Remove the volute and check for obstructions Clean as needed 4 Clean the tank with warm water and mild soap when mineral deposits are visible 5 Check the inlet and outlet piping Clean as necessary Be sure there are no kinks in the lines that would inhibit flow General When necessary maintenance steps outlined above are followed the air conditioner will provide long and reliable service The refrigeration and electrical circuit
20. he up or down button to switch to CYC which means cycle the fan with the compressor The factory default setting is CON which means continu ous fan operation 8 Press POWER you should see a code A followed by numbers Press POWER and the unit will start at the new settings 1211 Program Parameters MODEL CODE SETTINGS CAC1211 P1 80 P2 50 NOTICE Program Parameters are NOT controller default values they are Factory Settings Display Faults LAC Low AC line power Failed Air Sensor unit will not run CON Empty Condensate Bucket Units with a bucket Condensate Pump Over Flow Alarm Units with pump High Pressure Cut Out Low condenser air supply correct problem and re set unit at HP RESET To check the number of hours on the unit 1 Disconnect unit power and reconnect unit power 2 When 888 appears in display push and release the arrow down button 3 The first set of numbers displayed reads thousands of hours 02 2000 04 4000 hours 00 means less than 1000 hours 4 second set of numbers read hours directly 58 58 hours 742 742 hours 5 Add the 2 number sets together to get total hours 03 and 486 3486 hours 01 59 1059 hours Total Hours Represents Compressor Run Time Service Troubleshooting Guide The following steps and procedures are recommended for correcting the problems indicated In the event that the problem cannot be corrected service may
21. ilding codes and install all accessories Allow for a clearance Xtreme Power Conversion Corporation Page 9 CoolCube 12 User s Manual Portable Air Conditioning around the unit for future maintenance and or service Level unit and lock casters when available Connect power and test the LCDI on the power cord if available Power up unit via thermostat and check for proper operation Refer to Thermostat Operation for more details HANDLES CONTROL PANEL LCDI POWER CORD al LOCKING CASTERS FRONT Installation Hanging Application The CoolCube 12 may be installed above a space or above a drop ceiling as required The unit can be hung from a building s structural beam by one of three means e Using 5 16 18 threaded rods secured into the top of the unit at the 4 corners Make sure there is a mini mum of 1 2 thread engagement into panel nuts Rods are to be secured to upper structure by means of washers and nuts e Using 12 ga Uni Strut P1000 Series or equivalent secured to the top of the unit by 5 16 18 bolts e Using 12 ga Uni Strut P1000 Series or equivalent secured beneath the unit by 5 16 18 bolts When hanging or permanently connecting the CoolCube 12 it is advised that you remove the unit casters and handles prior to installation CAUTION When hanging or permanently connecting the CoolCube 12 all applicable local state federal building codes must be followed The structural beam s must be capab
22. ity The CoolCube 12 can be operated as a stand alone spot cooler or can be permanently installed in a server rack or above a drop ceiling Equipped with a 10 foot power cord for electrical connection and added mobility in service This spot cooler is designed to direct air to specific areas or objects through a discharge grill located on the upper front of the unit while rejecting heat from the back of the unit The CoolCube 12 is a self contained unit with the entire cooling system evaporator and condenser fan motors and electrical components neatly arranged black polyester powder coated metal cabinet When connected to the proper source of electrical power the unit is controlled by a solid state electronic controller with numerous options of temperature and airflow controls that will provide the desired level of comfort and cooling A wide variety of accessories and factory installed options are available for the CoolCube 12 allowing for improved performance and added versatility Warranty Card It is important that the warranty card be filled out completely and returned to the factory within fourteen 14 days of installation of the unit in order to receive the benefits of the warranty Xtreme Power Conversion Corporation Page 4 CoolCube 12 User s Manual Portable Air Conditioning Technical Specifications MODEL NUMBER 1211 COOLING Cooling capacity 12 000 BT
23. le of properly supporting the weight of the unit 130 Ibs WHEN INSTALLED UNIT IS TO BE PLUMB AND LEVEL Xtreme Power Conversion Corporation Page 10 CoolCube 12 User s Manual Portable Air Conditioning INSTALL 4 716 18 THREADED RODS NTO TOP PANEL OF UNIT UNI S TRUT INSTALLATION USE 4 56 18 x 1 BOLTS AHD WASHERS TO SECURE TO 5 USE 4 516 18 x 1 BOLTS AND WASHERS TO SECURE UMITTO UNIT STRUT Installation Permanently Connected The CoolCube 12 power cord may be removed and the unit be permanently connected to a power source for ap plications where desired Once the CoolCube 12 is installed and secured for a stationary installation the unit can be permanently wired 1 Remove the left side panel and locate the power cord and strain relief at the rear of the Unit 2 Disconnect the power cord from the ground lug and terminal strip 3 Remove the power cord and the strain relief 4 Install 1 2 conduit and a UL recognized bushing through the 7 8 diameter hole CONDUIT PORT and secure 5 Three 3 conductors a minimum of 14 AWG are required for LINE COMMON and GROUND can then be Xtreme Power Conversion Corporation Page 11 CoolCube 12 User s Manual Portable Air Conditioning connected to the unit and then be connected to a 115 VAC Single Phase 60 Hz that is rated at 15 A LEFT SIDE PANEL CONDUIT PORT LCDI POWER CORD 1211 USE COPPER CONDUCTOR
24. lect has been accidentally or intentionally damaged has not been installed maintained or operated in accordance with the furnished written instructions or has been altered or modified in any way b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any workmanship of the installer of the Product This limited warranty is conditional upon i shipment to the Manufacturer of that part of the Product thought to be defective Goods can only be returned with prior written approval from the Manufacturer All returns must be freight prepaid ii determination in the reasonable opinion of the Manufacturer that there exists a defect in material or work manship Repair or replacement of any part under this Limited Warranty shall not extend the duration of the warranty with respect to such repaired or replaced part beyond the stated warranty period THIS LIMITED WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EITHER EXPRESS OR IMPLIED AND ALL SUCH OTHER WARRANTIES INCLUDING WITHOUT LIMITATION IMPLIED WARRANTIES OF MERCHANTABILITY OR FIT NESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED AND EXCLUDED FROM THIS LIMITED WARRANTY IN NO EVENT SHALL THE MANUFACTURER BE LIABLE IN ANY WAY FOR ANY CONSEQUENTIAL SPECIAL OR INCI DENTAL DAMAGES OF ANY NATURE WHATSOEVER OR FOR ANY AMOUNTS IN EXCESS OF THE SELLING PRICE OF THE PRODUCT OR ANY PARTS THEREOF FOUND TO BE DEFECTIVE THIS LIMITED WARRANTY
25. nquiries can also be made at support xpcc com Please have the following information available BEFORE calling the Technical Support Department e Your name and address e The serial number of the unit e Where and when the unit was purchased e All of the model information about your UPS e Any information on the failure including LED s that may or may not be illuminated e Adescription of the protected equipment including model numbers if possible e A technician will ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available ask the Technical Sup port Technician about obtaining a replacement set of packaging material It is important to pack the UPS properly in order to avoid damage in transit Never use Styrofoam beads for a packing material 2 Include a letter with your name address daytime phone number RMA number a copy of your original sales receipt and a brief description of the problem 3 Mark the RMA number on the outside of all packages Xtreme Power cannot accept any package without the RMA number marked on the outside of the boxes 4 Return the UPS by insured prepaid carrier to
26. re Servicing Remove handles and casters from the unit Install rails in rack and secure with side brackets and hardware Carefully install Cool Cube into Rack onto of rails Secure the unit to the rails by use of the rear mounting rail Xtreme Power Conversion Corporation Page 13 CoolCube 12 User s Manual Portable Air Conditioning Accessories CONDENSER DISCHARGE CONDENSER CONDENSER RETURN DISCHARGE BAFFLE CONDENSER DISCHARGE RING RACK DIFFUSER CRD 1 0 8 DISCHARGE ADAPTER 8 CONDENSER RETURN PANEL COP 8 NOZZLE KIT CNK 1 EVAPORATOR RETURN PANEL CEP CONDENSATE PUMP KIT CPC 1 Xtreme Power Conversion Corporation Page 14 CoolCube 12 User s Manual Portable Air Conditioning Ceiling Panel Duct Kit CK 8 A ceiling panel kit is available for discharging the condenser air above a drop ceiling The ceiling panel duct kits are furnished with an 8 inch white vinyl coated flexible duct that allows for convenient installation A 2ft X 2ft ceiling duct panel is included to replace a 2ft X 2ft drop ceiling panel where the connection is desired The CK 8 ceiling panel kit consists of a 2 X 2 lay in ceiling panel with duct flange 8 Inch vinyl coated flex duct and the CDA 8 discharge adapter that attaches to the condenser air discharge opening on the back of the unit COMDENSER DESC HARGE Note Drop ceiling spaces should be vented or large enough to handl
27. s of the system should only be serviced by a fully qualified service technician Xtreme Power Conversion Corporation Page 23 CoolCube 12 User s Manual Portable Air Conditioning SUCTION UNE EVAPORATOR BLOWER Piping Schematic EVAPOTATOR COIL f CONDENSER CAPILLARY TUBES HP RESET BLOWER CONDENSER AIR COIL ACCESS a VALVES ALTERS DISCHARGE UNE REFRIGERANT FLOW PIPING SCHEMATIC COMPRESSOR Air Cooled Spot Cooler Xtreme Power Conversion Corporation Page 24 CoolCube 12 User s Manual Portable Air Conditioning Wiring Diagram OUTSIDE SCNEOR Bry RESET Single Phase COMPRESSOR 7 RUN STRIP LINE GROUND z COHODCHS PATEH SAFETY SWITCH 15 VOLT Lew crane 60 HZ VOLTAGE SPOT CINN SAFER Y RENE HSV 9 Xtreme Power Conversion Corporation Page 25 CoolCube 12 User s Manual Portable Air Conditioning Obtaining Service If the UPS requires Service 1 Use the TROUBLESHOOTING section in this manual to eliminate obvious causes 2 Verify there are no circuit breakers tripped 3 Callyourdealerforassistance lfyoucannotreachyourdealer oriftheycannotresolvethe problem call Xtreme Power Conversion Corp Technical Support at 800 582 4524 Technical support i
28. tural beam s must be capable of properly supporting the weight of the unit 135 Ibs Condensate Condensate Reservoir Tank The CoolCube 12 has a 2 gallon polyethylene tank for collecting condensate The tank is located in the lower front section of the unit A high water level cut out switch is used to stop the compressor and condenser fan automati cally when the tank s pre set water level has been reached The evaporator fan will continue to run circulating air SUMP DRAIN HOLE RUBBER TANK HANDLE SP RING Er i MAXIMUM WATER CONDENSATE 5 ao TANK TRAY CONDENSATE TANK HINGE FULL SWITCH CON DISPLAYS WHEN SWITCH IS DEPRESSED Xtreme Power Conversion Corporation Page 8 CoolCube 12 User s Manual Portable Air Conditioning Emptying The Condensate Reservoir Tank In the COOL Mode condensate will accumulate in the condensate tank When the tank becomes full the Deluxe Control will shut down the compressor and the word CON will be displayed along with the room temperature To empty the tank do the following 1 Press the POWER button to turn the unit off 2 Pull the tank from the lower front of the unit using the handle 3 Remove the rubber stopper and empty the tank in a nearby sink 4 Replace the rubber stopper 5 Place the tank back in to the unit making sure the tank is in correctly 6 Press the POWER button to re start the unit HH 22 REMOVE FULL
29. with a condensate over flow safety switch that will shut down the compressor when the pump is not working properly The word CON will be displayed along with the room temperature Kit includes the pump mounting hardware and 24 feet of condensate hose CONDENSATE PUMP KIT CPC 1 Feet Kit CFK 1 The CFK 1 is a field installed feet kit that replaces the casters used on the CoolCube 12 allowing the unit to be mounted in applications where movement is not desired The feet are made of oil resistant neoprene and serve to reduce unit vibration and noise Xtreme Power Conversion Corporation Page 16 CoolCube 12 User s Manual Portable Air Conditioning Rack Diffuser CRD 1 The CRD 1 is a field installed diffuser kit that allows for the directional discharge of the conditioned air vertically into a rack application The diffuser easily mounts to the front of the unit Discharge Air Nozzle Kit Assembly CNK 1 The optional discharge nozzle kits are used to direct the conditioned air to a specific target area By concentrat ing the airflow the nozzles increase the air velocity towards production lines to cool personnel or equipment In server rooms the nozzles can be used to induce airflow through the rack to remove the hot air from the area of the equipment CNK 1 for model CoolCube 12 with 2 4 inch diameter nozzles with an approximate compressed length of 15 inches The approximate extended length is 21 inches Discharge
Download Pdf Manuals
Related Search
Related Contents
Samsung NZ63H37070K/EF Manuel de l'utilisateur Manual de Usuario Manual de Usuario Monterey Installation Instruction Manual Cargar Dual-Port EtherNet/IP Communication Adapter User Manual Camera Control Software User Guide 100kHz から 3GHz までの 幅広い測定レンジ!アンテナ 型データロガー GeeVS Server Manual Copyright © All rights reserved.