Contents

1. o e 5 L L lows selection of Language o eoguege display languages oc i English 1 t Config Menu e Turm only Allows selection of single or i LoadType o oad ype 3 phase motor protection N oc 1 3Ph Motor a Contig Menu Por TUOMBE ONN Allows selection of PowerBase o PowerBase power base type used ec iz SelfProtStr 4 Contig Menu s Allows selection of thermal e AuxFan 72 AuxFan protection for fan cooled motors 1 l oo Ng oA i Config Menu Hor EUCMTIBE only Allows selection of the correct CT_Ratio 72 l CT_Ratio current transformer used oc 2908 eccl En i Config Menu 2 i Allows user to exit L J Config menu Contains product references 1 Reference Config settings OFF oc Main Menu Allows selection of items or 2_Display o 2 Display displayed during Run mode TEN e eo 21 AvCurrent o Main Menu e Contains basic settings or 3 Setup o 3 Setup accessible during Run mode oc SILFLASe 5 Main Menu 4e Contains advanced settings or 4 AdvSetup eo 4 AdvSetup accessible during Off mode Run oo A1 Trip Class Main Menu KS Contains settings for RS 485 Sub 5_CommSetup eo 5 CommSetup Modbus communication port ubsequent e e 51 Drop i power ups NS ee Main Menu K Allows configuration of
2. Submenu Parameter Function Reference Definition line 1 line 2 line 1 line 2 l 6_Module Parameter 1 16 _ Line 1 shows the parameter number 1 through 16 65_Param hex 0000 Line 2 shows the parameter setting in Hex see 2 5 6 6 The parameters are settable from 0000 to FFFF Default setting for all 16 parameters is 0000 ENT Sends to parameters settings NOTE Press amp or to enable stepping through all the parameters numbers ESC Returns to 6_Module page 69 5 2566 Parameter 1 16 Option Module Parameter setting a Parameter Setting naire a line 1 line 2 Definition l Setting of parameters codes 1 to 16 can be done in either decimal or hex i iin Press the ENT key to begin parameters setting Parameter 1 00000 0____ lt First digit of the parameter 1 decimal Decimal e Press amp or Q to increment the first digit 2 000001 0 to 6 eococe NOTE See individual option module instruction 000005 sheets for code definitions ENT Press the ENT key to enter the first value and send to 50000 0 amp X the second digit 50000 0 The same procedure is followed for the remaining digits occ NOTE In the decimal mode the Multifunction Control 2 500003 Unit will not allow a digit to scroll past the ENT 65535 maximum value 53000 0 Pressthe ENT key to enter the second value and send to the third digit 253210 A4
3. D Bit Range Unit Pm a Information 469 0 2 000 FLA IL3 Current 470 0 2 000 FLA min IGF Current 471 0 100 IMB Phase Imbalance 472 40 to 4200 Degrees C Control unit Internal Temperature 473 0 65535 None 0 Configuration Checksum Checksumrotate registers 600 699 474 599 Reserved From 600 to 630 configuration registers read and write accessible if the starter is stopped ne Bit Range Unit pon zi Information 600 0000 9999 4 digits 0000 Password 601 0 0 1 Off On 1 Configuration Required Can not set to if CT Ratio is invalid 1 0 1 Off On 0 Reserved 2 0 1 Off On 1 TeSys model U Power Base Type 0 Starter or Overload relay Controller 1 Self protected starter 3 0 1 Off On 0 Power Base size 12 Amp on A1A2 4 0 1 Off On 0 Power Base size 32 Amp on A1A2 5 0 1 Off On 0 Reserved 6 12 0 1 Off On 0 Reserved 13 0 1 Off On 1 3 Phase Motor 14 0 1 Off On 0 1 Phase Motor 15 0 1 Off On 0 Aux Fan Cooled Can not be set on LUCMT1BL 602 0 0 1 Off On 1 Reset Mode Manual Must set 1 0 1 Off On 0 Reset Mode Remote Ent one bit in 2 0 1 Off On 0 Reset Mode Auto dl 3 0 1 Off On 0 RS 485 Comms parity 4 0 1 Off On 1 Enable Comms control 5 0 1 Off On 1 RS 485 Watchdog Ignore Must set 6 0 1 Off On 0 RS 485 Watchdog Warning one bit in 7 0 1 Off On 0 RS 485 Watchdog Dropout india 8 0 1 Off On 0 RS 485 Watchdog Trip 9 0 1 Off On 0 RS 485 Watchdog Start future
4. 56 2 5 4 7 1 Tp ecce 2 5 4 7 2 TripTimeStrt 2 5 4 7 3 TripTimeRun pa 2 5 4 7 4 Jes aa E aaa aaa 2 5 4 7 5 iue A AA A NU SA A 2 5 4 7 6 Wan Level mec 2 5 4 8 48 Jam Jam Protection men an nenanem est sedia etes ANA AKA A 59 2 5 4 8 1 jj TA Na T 59 2 5 4 8 2 MAPTE sis a a a a Petanda EEE Kt kangen banana 60 2 5 4 8 3 MMP CVE Em 60 2 5 4 8 4 Warning sa KU C p 60 2 5 4 8 5 Ia EL 60 2 5 4 9 49 UnderLoad Under Load Protection aaa 61 2 5 4 9 1 UA gs cares DIA sitet 61 2 5 4 9 2 MIU TMG ap E E A O A 62 2 5 4 9 3 a mE 62 2 5 4 9 4 WADING ena NAN A A A a an T ia 62 2 5 4 9 5 Warn Level 62 2 5 4 10 410 LongStrt Long Start Protection 469 2 5 4 10 1 TID see 2268 2 5 4 10 2 UM c 64 2 5 4 10 3 Tile Vel 22 iit i et ute e pet AA rt bebe eee Led 64 2 5 4 10 4 WANG eeo perite reete yi eee eee n de e Deep nene oai ee erre dd 64 2 5 4 10 5 Warn Level snek Kanan a a Ka Gt a a a ai kai 64 2 5 5 5 CommSetup nan anna a a a aaa A aan Sanana da 65 2 5 5 1 51 Drop Modbus Slave Number enak 66 2 5 5 2 52 Baud Modbus Baud Rate ssssssssssssssemeeeees 67 2 5 5 3 53_Parity Asynchronous Protocol Parity aaa 67 2 5 5 4 54 Comtrol Write Control aite de e ree a ERI iie ge d 67 05 2004 Table of Contents 5 ENGLISH Multifunction Control Unit Table of Contents Pa
5. Yes No 22 ThermCap No Yes 23 L1Current No Yes 24_L2Current No Yes 25_L3Current No Yes 26_GFCurrent No Yes 27 ASHP nn naa No Yes 28 Phaselmb No Yes 29 ONhours aa No Yes 05 2004 Chapter 1 General information 13 x e l 2 Z m Multifunction Control Unit S Default Setting Menu Submenu Function Parameter or Referen ee Optional values 3_Setup 31_FLASet LUCMx6BL 0 15A 0 15 to 0 6 for LUCM BL UCMixBL 0 35 A 0 35 to 1 4 onl N LUCMOBBL 1 25A 1 25105 Determined by l Multifunction LUCM12BL 3A 3t012 l Control Unit LUCM18BL 4 5 A 4 5 to 18 reference l LUCM32BL 8A 8 to 32 1 among the 6 for LUCMT1BL LUCMT1BL 0 35A 0 35 to 1 05 only CT Ratio CT Ratio 32 TestTrip No Yes 33 PauseMtr No Yes 34 Language English Francais Espafiol Deutsch for LUCMeBL only Italiano l 35_PauseMode Yes No 4_AdvSetup 41 TripClass 5 25 to 30 42_ResetMode Manual Remote Ent Auto 43 RstAdjust ResetTime z 120 Sec 1to 1000 ResetLevel 80 35 to 95 Capacity l 44_MagTrip forLUCM BL only 1420 FLA 300 to 1700 45 OLWarning Warning On Off Warn
6. 2 5 3 5 35 PauseMode Software Motor Stop Lockout Function Setting one line 1 line 2 Definition 35_PauseMode Yes Allows opening and closing the main power contacts with the 33_PauseMtr function see 33_PauseMtr page 41 Enabled by default No Allows user to lockout the 33_PauseMtr function so that the main power contacts cannot be opened or closed with the 33_PauseMtr function see 33_PauseMtr page 41 ENT Saves setting and returns to 3_Setup page 41 ESC Does not save a setting returns to 3_Setup page 41 44 Chapter 2 Operation 05 2004 Multifunction Control Unit 25 4 4 AdvSetup Provides access to advanced protection functions and parameters These functions can be enabled or disabled when the Multifunction Control Unit is in the Config mode first power up configuration and settings page 21 or Off Ready and Pause modes subsequent power ups and settings page 22 These functions can always be viewed in either the Run mode settings page 23 or Config mode first power up configuration and settings page 21 or Off Ready and Pause modes subsequent power ups and settings page 22 Submenu Function T line 1 line 2 Definition 4_AdvSetup 41_TripClass see CAUTION page 47 see 2 5 4 1 p 47 Sets Motor Trip Class which represents the nominal thermal trip time in seconds during a 600 FLA overload condition
7. 88 Appendix 05 2004 Multifunction Control Unit From 100 to 277 statistics registers read only aan Bit Range Unit a wt Information 186 0 2 000 FLA 0 Trip n 1 IL3 Current 187 0 2 000 FLA min 0 IGF Current 210 0 65535 None 0 Trip n 2 Fault Number 211 25 100 FLA max 0 FLA Current Setting 212 0 100 0 Thermal Level 213 0 2 000 FLA 0 IIAV Average Current 214 0 2 000 FLA 0 IL1 Current 215 0 2 000 FLA 0 IL2 Current E 216 0 2 000 FLA 0 IL3 Current z 217 0 2 000 FLA 0 IGF Current 240 0 65535 None 0 Trip n 3 Fault Number 241 25 100 FLA max 0 FLA Current Setting 242 0 100 0 Thermal Level 243 0 2 000 FLA 0 IIAV Average Current 244 0 2 000 FLA 0 IL1 Current 245 0 2 000 FLA 0 IL2 Current 246 0 2 000 FLA 0 IL3 Current 247 0 2 000 FLA 0 IGF Current 270 0 65535 None 0 Trip n 4 Fault Number 271 25 100 FLA max 0 FLA Current Setting 272 0 100 Yo 0 Thermal Level 273 0 2 000 FLA 0 IIAV Average Current 274 0 2 000 FLA 0 IL1 Current 275 0 2 000 FLA 0 IL2 Current 276 0 2 000 FLA 0 IL3 Current 277 0 2 000 FLA 0 IGF Current eut Bit Range Unit mae x Information 450 0 1000 Seconds 0 Time to Auto Reset 451 see LULC031 communication module user s manual
8. 92 Appendix 05 2004 Multifunction Control Unit From 600 to 630 configuration registers read and write accessible if the starter is stopped eles Bit Range Unit D Information 602 10 0 1 Off On 0 Pause on Power Up future 11 0 1 Off On 1 Enable Pause mode 12 15 Reserved 603 1 247 Address 1 Modbus slave address 604 1200 4800 Baud 19200 Modbus Baud Rate 9600 19200 605 300 to 1700 FLA 1420 Magnetic Trip For LUCM BL only 606 5 10 15 20 Motor Class 5 Load Class 25 30 607 1 1000 Seconds 120 Thermal Reset Time 608 35 100 Capacity 75 Thermal Reset Level 609 10 100 Capacity 85 Thermal Warn Level 610 1 12 0 1 Sec 10 Ground Fault Trip Time 611 20 500 FLA min 30 Ground Fault Trip Level 612 20 500 FLA min 30 Ground Fault Warn Level 613 2 200 0 1 Sec 7 Phase Imbal Trip Time Start 614 2 200 0 1 Sec 50 Phase Imbal Trip Time Run 615 10 30 IMB 10 Phase Imbal Trip Level 616 10 30 IMB 10 Phase Imbal Warn Level 617 1 30 Seconds 5 Jam Trip Time 618 100 800 FLA 200 Jam Trip Level 619 100 800 FLA 200 Jam Warn Level 620 1 200 Seconds 10 Underload Trip Time 621 30 100 FLA 50 Underload Trip Level 622 30 100 FLA 50 Underload Warn Level 623 1 200 Seconds 10 Long Start Trip Time 624 100 800 FLA 100 Long Start Trip Level 625 100 800 FLA 100 Long Start War
9. NOTE When installed in the Power Base the Multifunction Control Unit secures the options modules The Multifunction Control Unit must be removed for installation or removal of the option modules 132 Operating temperatures Y LU B and LU S d 2 0 mm 0 in 45 C 113 F d29mm 0 35in 55 C 131 F d220mm 0 75in 60 C 140 F LUTM BL d Omm 0 in 65 C 149 F NOTE The Multifunction Control Units can be operated at 5 C 9 F for AC motor loads less than 12 0 full load Amps on Power Bases LU Bee and LU See only The Multifunction Control Unit has internal temperature watchdog functions that can not be disabled An Warn IntTmp warning will be displayed if the internal temperature reaches 80 C The Motor starter will trip and the control unit will display Int Trip if the internal temperature reaches 90 C The internal temperature may be monitored via the RS485 port locally using the PowerSuite software remotely using the Modbus bus see Fault mode diagnostics page 25 for reseting of an Int Trip fault Chapter 1 General information 05 2004 Multifunction Control Unit 1 3 3 1 334 Control connections LUCM BL The LUCM BL Multifunction Control Unit has two 24V DC power inputs The coil control input accessible only by the A1 A2 terminals on the Power Base and the auxiliary power input on the face ofthe Mu
10. see 2 5 4 6 1 p 54 damage Function Parameter Definition line 1 line 2 46 GroundFIt Trip Enables or disables the Ground Fault Protection function If the Multifunction Control Unit detects a continuous ground fault current above a set level a trip of the base mechanism is initiated after the set TripTime page 54 expires NOTE If this parameter is enabled a ground fault always trip the Power Base mechanism and will require a Manual Reset regardless of the selected reset mode see 42 ResetMode page 48 TripTime see 2 5 4 6 2 p 54 Sets the Ground Fault Trip Time parameter The Trip Time parameter is defined as the delay in seconds before the Multifunction Control Unit initiates a trip upon detection of a Ground Fault Protection current above the set level TripLevel see 2 5 4 6 3 p 54 Sets the Ground Fault Trip Level parameter The Trip Level parameter is defined as the level of continuous current at which the Multifunction Control Unit initiates a ground fault trip after the set TripTime page 54 expires Warning see 2 5 4 6 4 p 54 Enables or disables the Ground Fault Warning function A warning is activated if the Multifunction Control Unit detects a ground fault current above the set Warn Level page 55 Warn Level see 2 5 4 6 5 p 55 Sets the Ground Fault Warn Level parameter NOTE Press amp or to enable stepping through all the display par
11. ENT Saves setting and returns to CT_Ratio page 29 ESC Does not save a setting returns to CT_Ratio page 29 Parameter Parameter line 1 Submenu Definition line 2 Others Primary Sets the current transformers primary current rating see 2 4 5 9 1 p 32 The parameter is settable from 1 to 65535 Secondary Sets the current transformers secondary current rating see 2 4 5 9 2 p 33 The parameter is settable from 1 to 65000 Exter_Pass Sets the number of passes through the current see 2 4 5 9 3 p 33 transformer core that have been made with the power primary wiring Example 2 would indicate two passes of the power wiring through the current transformer coil doubling the current measured by the secondary of the current transformer Parameter is settable from 1 to 65000 NOTE Press or to enable stepping through the Other parameters submenu ENT Sends to parameters submenu settings ESC Does not save a setting returns to CT_Ratio page 29 Parameter Settin Submenu line 5 Definition line 1 Primary 00000 Press the ENT key to begin parameters setting 00000 0____ lt First digit of parameter setting e 000001 Press or Q to increment the first digit ecce 0 to 6 000005____ ENT Press the ENT key to enter the first value and send to the 50000 0 X second digit 32 Chapter 2 Operation
12. x e l o Z m LUCMT1BL Pause mode see 33_PauseMtr Software Motor Stop page 43 for disabling Pause mode Main Menu KS read and write 4_AdvSetup o 4 AdvSetup Cee 4_AdvSetu Main Menu p o 4 AdvSetup Main Menu 4_AdvSetup 8_Password 05 2004 Chapter 2 Operation 21 Multifunction Control Unit 2 2 2 Off Ready and Pause modes subsequent power ups and settings Main Menu page 35 settings can be modified in the Off Ready or Pause modes See 33_PauseMtr page 41 function for enabling Pause mode Should it be necessary to re enter the Config Menu Configuration Menu page 27 and change a configure setting the user must first validade the 84_RstToDfts page 77 function This resets all parameters back to factory default settings Indicates main contacts are open and no power detected at A1 A2 terminals Indicates main contacts are closed with less than 10 of the set FLA current is detected Indicates main contacts are open with power detected at A1 A2 terminals see warning 33 PauseMtr Software Motor Stop page 43 gt m or
13. NOTE Press amp or to enable stepping through all the display functions Definition I e l o Z m ENT Sends to functions settings ESC Returns to Main Menu page 35 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 2541 41 TripClass Motor Trip Class CAUTION Incorrect Trip Class setting The Trip Class Adjustment must be set to match the thermal heating characteristics of the motor Incorrect setting of the Trip Class function can result in equipment damage E ier Definition 41 TripClass 5 Sets trip time to 5 seconds for an overload of 600 FLA Enabled by default 10 Sets trip time to 10 seconds for an overload of 600 FLA 15 Sets trip time to 15 seconds for an overload of 600 FLA 20 Sets trip time to 20 seconds for an overload of 600 FLA 25 Sets trip time to 25 seconds for an overload of 600 FLA 30 Sets trip time to 30 seconds for an overload of 600 FLA ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 05 2004 Chapter 2 Operation 47 ENGLISH Multifunction Control Unit 2 5 4 2 42 ResetMode Fault Reset Mode A DANGER Unintended motor starting If A1 A2 power is present and Automatic Reset is selected the motor will start runnin
14. 05 2004 Multifunction Control Unit 24592 S 2 45 93 E Primary 50000 0 The same procedure is followed for the remaining digits ooo NOTE The Multifunction Control Unit will not allow a digit 50000 3 to scroll past the 65535 maximum value mo Press the ENT key to enter the second value and send to ENT CR the third digit 253000 0 253210 A4 When the last digit value has been selected and the ENT ENT key pressed the Primary setting will be set 53214 m ENT Saves setting and returns to Primary page 32 ESC Does not save a setting returns to Others page 32 econdary Secondary Current Transformer Rating Parameter A Submenu pa Definition line 1 Secondary z1 Press the ENT key to begin parameters setting e Press amp or to increment the value 2 NOTE The Multifunction Control Unit will not allow a digit Q O A to scroll past the 65000 maximum value or a value UU that would allow a current transformer ratio 10 less than 1 10 ENT When the desired value has been selected and the ENT key pressed the Secondary setting will be set 10 mm ENT Saves setting and returns to Others page 32 ESC Does not save a setting returns to Others page 32 xter Pass Power Wiring Passes Parameter h Submenu PES Definition line 1 Exter Pass 21 Press the ENT key to begin parameters setting Q Press amp or to incr
15. 14 AWG not fitted with cable end 2 Conforms to IEC 1000 4 6 when 46 GroundFIt TripLevel is set lt 50 FLA minimum 3 Conforms to IEC 1000 4 6 when 46 GroundFIt TripLevel is set gt 50 FLA minimum 05 2004 Chapter 1 General information 17 x e l o Z m Multifunction Control Unit 1 3 6 2 Power circuit Operating voltage range V 110 to 690 VAC a insulation voltage Conforming to IEC 947 1 V 690 VAC i I Operating frequency Hz 47 63 Rated operational current A LUCMX6BL e 0 15 to 0 6 LUCMTxBL eeeseessesee e eM 0 35 to 1 4 LUCMOBBL ea AA 1 2510 5 LUCM12BL emma 3to12 UCMi8BL ea niu ee 4 5 to 18 LUCM32BL eeeeseseseeeme eH emen 81032 ENGLISH Approved for use upstream of variable frequency drives Not approved for use downstream of variable frequency drives 4 For use with 110 to 690 V 50 60 Hz AC motors only Not approved for use with DC motors 1363 Control circuit supply A1 A2 terminals and auxiliary power input Operating voltage V 20 4 to 31 2 VDC Rated insulation voltage Ui Conforming to IEC 947 1 V 380 VAC Cabling aux power only Solid or stranded cable 1 conductor mm 0 5to 1 AWG 20 to 18 Stranded cable 1 conductor mm 0 5 to 1 with cable end AWG 20 to 18 Solid cable 2 conductors mm 0 2 to 1 AWG
16. 30 3 No Returns to CT_Ratio parameter selection page 27 Yes Sets CT_Ratio to 30 3 Sets FLASet range to 3 5 10 5 Amps see 31_FLASet page 42 ENT Saves setting and returns to CT_Ratio page 29 ESC Does not save a setting returns to CT_Ratio page 29 2 4 5 2 30 2 Parameter Setting RD line 1 line 2 Definition 30 2 No Returns to CT_Ratio parameter selection page 27 Yes Sets CT_Ratio to 30 2 Sets FLASet range to 5 2 15 7 Amps see 31_FLASet page 42 ENT Saves setting and returns to CT_Ratio page 29 ESC Does not save a setting returns to CT_Ratio page 29 2 4 5 3 30 1 Parameter Setting ED line 1 line 2 Definition 30 1 No Returns to CT_Ratio parameter selection page 27 Yes Sets CT_Ratio to 30 1 Sets FLASet range to 10 5 31 5 Amps see 31_FLASet page 42 ENT Saves setting and returns to CT Ratio page 29 ESC Does not save a setting returns to CT Ratio page 29 30 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 4 5 4 50 1 Parameter Setting e line 1 line 2 Denniton 50 1 No Returns to CT_Ratio parameter selection page 27 Yes Sets CT Ratio to 50 1 Sets FLASet range to 17 5 52 5 Amps see 31 FLASet page 42 ENT Saves setting and returns to CT Ratio page 29 ESC Does not save a setting returns to CT Ratio page 2
17. 452 0 0 1 Off On 0 Short Circuit Fault 1 0 1 Off On 0 Magnetic Fault 05 2004 Appendix 89 ENGLISH Multifunction Control Unit From 450 to 454 monitoring fault registers read only cine Bit Range Unit pis a Information 452 2 0 1 Off On 0 Ground Fault 3 0 1 Off On 0 Thermal Overload Fault 4 0 1 Off On 0 Long Start Fault 5 0 1 Off On 0 Jam Fault 6 0 1 Off On 0 Phase Imbalance Fault 7 0 1 Off On 0 Underload Fault 8 0 1 Off On 0 Shunt Trip network 9 0 1 Off On 0 Test Trip Fault 10 0 1 Off On 0 Comm Loss Fault 11 0 1 Off On 0 Control unit Internal Fault 12 0 1 Off On 0 Module Identification Fault 13 0 1 Off On 0 Module Internal Fault and loss of communication 14 0 1 Off On 0 Module Trip Fault 15 0 1 Off On 0 Module dropout fault OA1 and OA3 1 Forced to 1 0 Forced to 0 453 1 0 1 Off On 0 No action fault 454 Reserved From 455 to 459 monitoring status registers read only Dan Bit Range Unit oe m Information 455 0 0 1 Off On 0 Ready 1 0 1 Off On 0 On 1 contactor switched on 2 0 1 Off On 0 Fault overload magnetic short circuit internal fault 3 0 1 Off On 0 Warning 4 0 1 Off On 0 Tripped 5 0 1 Off On 0 Reset authorized 6 0 1 Off On 0 A1 A2 on 7 0 1 Off On 0 Motor Running 8 13 0 1 Off On 0 Average Current 14 0 1 Off On 0 Reserved 15 0 1 Off On 0 Motor Starting 90
18. Appendix 05 2004 Multifunction Control Unit From 455 to 459 monitoring status registers read only maine Bit Range Unit eae zs Information 456 0 0 1 Off On 0 Auto Resetting 1 0 1 Off On 0 Motor Paused 2 15 0 1 Off On 0 Reserved 457 see LULC031 communication module user s manual 458 Reserved 459 Reserved From 460 to 464 monitoring warning registers read only z ud Bit Range Unit pis ue Information 9 460 0 65535 None Warning Number d 461 0 1 0 1 Off On Reserved 2 0 1 Off On Ground Fault Warning 3 0 1 Off On Thermal Warning 4 0 1 Off On Long Start Warning 5 0 1 Off On Jam Warning 6 0 1 Off On Phase Imbalance Warning 7 0 1 Off On Under Current Warning 8 9 0 1 Off On Reserved 10 0 1 Off On Comm Loss 485 port 11 0 1 Off On Control unit Internal Temperature 12 0 1 Off On Module Identification Warning 13 14 0 1 Off On Reserved 15 0 1 Off On Module Warning 462 0 Reserved 463 0 Reserved 464 0 Reserved Somn Bit Range Unit real a Information 465 0 100 TripLevel Thermal Capacity Level 466 0 2 000 FLA IIAV Average Current 467 0 2 000 FLA IL1 Current 468 0 2 000 FLA IL2 Current 05 2004 Appendix 91 Multifunction Control Unit ENGLISH From 465 to 599 monitoring measurements registers read only
19. gt 2 or gt T 4 za 5 9c 9 P Main Menu 4653 read only z 1 Reference o 1 Reference o e 11 Catalog Main Menu KE read and write 2_Display 2_Display oo 21 AvCurrent Main Menu 4653 read and write 3 Setup p 3 Setup oo D i S1_FLASet e Main Menu KE read and write 4_AdvSetup o 4 AdvSetup e Main Menu KE read and write 4_AdvSetup o 4 AdvSetup eoo 4 varni pe Main Menu KE read and write 5_CommSetup o 5 CommSetup oc 51_Drop i Main Menu 4653 read and write 6 Module 6 Module oo 61 Reference 1 Main Menu 4653 read only 7 Statistics o 7 Statistics oc UIT 000 Main Menu KE read and write 8_Password em 8 Password If key is not touched 3 B1 Unlock _ During Off Ready Pause modes gt 1 Reference parameters are read only During Off Ready Pause modes 2 Display parameters are read and write During Off Ready Pause modes 3 Setup parameters are read and write During Off Ready Pause modes EA 4 AdvSetup parameters are read and write _ During Off Ready Pause modes EE 5 CommSetup parameters are read and wite During Off Ready Pause modes 6 Module parameters are read and write During Off Ready Pause modes v 7 Statistics parameters are read only During
20. 15g closed 11 milliseconds Vibration resistance Conforming to IEC 68 2 6 2g open 4g closed 5 to 150 Hz Ambient air temperature Storage c 35 to 85 around the device oF 31 to 185 Operation C 20 to 60 see 1 3 2 Operating F 4 to 140 temperatures page 10 for derating considerations Flame resistance Conforming to UL 94 v2 Maximum operating altitude m 2000 ft 6562 Operating position In relation to normal Horizontal or vertical 30 angle vertical mounting plane front or back Electromagnetic compatibility Conforming to IEC 1000 4 2 kV 8 Electrostatic discharge evel 3 Electromagnetic compatibility Conforming to IEC 1000 4 3 V m 10 Electromagnetic field evel 3 Electromagnetic compatibility Conforming to IEC 1000 4 4 kV 4 Fast transient burst level 4 Conforming to IEC 1000 4 5 Common mode Serial mode Electromagnetic compatibility Level 4 Power circuit kV 6 4 Surge immunity Level 1 Control circuit kV 1 0 5 Level 2 Communication circuit kV 1 1 Electromagnetic compatibility Conforming to IEC 1000 4 6 V 3 Conducted disturbances evel 3 10 Rated undissipated pulse Conforming to IEC 947 1 kV 2 withstand U imp Resistance to low frequency Conforming to IEC 947 2 disturbances supply harmonics Appendix F Clause F4 1 Resistance to micro breaks Conforming to IEC 1000 4 11 1 Only applicable when power cabling to Power Base exceeds the following sizes 1 5 mm 16 AWG fitted with cable end or 2 5 mm
21. 2 5 2 1 2 5 2 2 2 5 2 3 2 5 2 4 2 5 2 5 2 5 2 6 2 5 2 7 2 5 2 8 2 5 2 9 2 5 3 2 5 3 1 2 5 3 2 2 5 3 3 2 5 3 4 2 5 3 5 2 5 4 2 5 4 1 2 5 4 2 Table of Contents Page Config Menu Configuration Menu 27 Language Unit Display Language eee 28 LoadType Motor Load Type eeeem mene 28 Base Motor Starter Power Base Type 28 AuxFan Auxiliary Fan Cooled Motor mee 29 CT Ratio Current Transformer Ratio sss 29 IO M Em 30 cn r H Hut 30 co 30 BO 31 agd 231 ied gu EE E 32 Others Other Current Transformer Ratio Settings 32 Primary Primary Current Transformer Rating aaa 32 Secondary Secondary Current Transformer Rating 33 Exter Pass Power Wiring Passes 33 End Config End Configuration Mode 34 M in M n 35 1 JBeference ose Le IRE e AN Sei 36 PMCID 37 21 AvCurrent Average Three Phase Current sss 38 22 ThermCap Thermal Capacity used aaa 38 23 L1Current Current measured in L1T1 98 24 L2Current Current measured in L2T2 2 39 25_L3Current Current measured in L3T3 39 26 GFCurrent Ground Fault Current 39 27 astinip Last Fault Type cce teet dette reete imd A decus 40 28 Phaselmb Phase I
22. ENT When the last digit value has been selected and the ENT key pressed the parameter code will be set 53214 l Parameter 2 16 00000 NOTE Setting of parameter 2 to 16 follows the same Decimal ENT procedure 000000____ 05 2004 Chapter 2 Operation 71 ENGLISH Multifunction Control Unit hex Parameter 1 00000___ lt First digit of the parameter 1 hex hex hex e Press amp or to increment the first digit 200001 0 to F Q x14 NOTE See individual option module instruction 20000F sheets for code definitions ENT Press the ENT key to enter the first value and send to F000 0 the second digit F240___B ENT When the last digit valve has been selected and the ENT key pressed the parameter code will be set F24B Parameter 2 16 0000 NOTE Setting of parameter 2 to 16 follows the same procedure NS ENT Saves setting and returns to 6 Module page 69 ESC Does not save a setting returns to 6 Module page 69 72 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 7 7 Statistics e The 7 Statistics submenu allows access to the Fault history stored in the Multifunction Control Unit memory The Multifunction Control Unit stores information on the last 5 Faults as well as Fault and Run history totals NOTE Internal Fault Trips are not displayed in last 5 faults Enabling the 83 Rst Stats page 76 function clears
23. Off Ready Pause modes 8 Password parameters are read and write 22 Chapter 2 Operation 05 2004 Multifunction Control Unit 223 Run mode settings e Line 1 of the display shows Run when the Power Base main contacts are closed and more than 10 of the set FLA current is detected Line 2 of the display can be set to scroll certain information for monitoring see 2 5 2 2_Display page 37 e Only functions 2 Display page 37 and 3 Setup page 41 can be modified when the Multifunction Control Unit is in the Run mode Power up Run o o Run Y Therm 65 iIL1 25 ___ Run 707 Run 22 ThermCap Thermal 23_L1Current Phase1 IL2 3 5A ___ IAV 2 5A capacity current 24 L2Current Phase 2 21 AvCurrent Average current 3 phase current Scrolling Run info I display 77 if more than one item selected a n 25 LSCurrent Phase 3 0 TAROS current z 29 _ONhours Total _________ Run TT hours of Run time n Run IR SAEC s IGR 0 2A 4 Jmbal 1 0A____ LT Over Load 5 GFCurent Ground 28_Phaselmb Phase 27 LasfTrip Last trip fault current y imbalance type p mmm ead oni _ During Run mode z 1_Reference eo 1 Reference 1 Reference parameters are read only gt oo 11 Catalog Main Menu 653 read and write n _ During Run mode F 2_Disp
24. m 100 Class 30 Class 5 Time to trip sec eo a 3x 17x 0 01 0 001 100 1 000 10 000 FLA 05 2004 Appendix 81 Multifunction Control Unit A 2 Trip Times cold Motor Load 10 000 1 000 100 ENGLISH 10 Class 30 Time to trip sec o L 0 01 0 001 100 1 000 10 000 FLA 82 Appendix 05 2004 Multifunction Control Unit A3 Reset Times With Aux Fan Cooled function disabled Reset Timing Self Ventilated Motor Class 5 Class 10 Class 15 3 Class 20 3 Class 25 e Class 30 x o l o Z m Reset Level of thermal overload trip level page 50 0 1000 2000 3000 4000 5000 6000 7000 Time to reset A 4 Reset Times With Aux Fan Cooled function enabled Reset Timing Aux Fan Cooled Motor Class 5 Class 10 Class 15 lt Class 20 Class 25 e Class 30 Reset Level of thermal overload trip level page 50 0 200 400 600 800 1000 1200 1400 1600 1800 Time to reset 05 2004 Appendix 83 ENGLISH Multifunction Control Unit Appendix B Display Words LCD Display Words line 1
25. settings that the set TripLevel page 58 of imbalance current is detected before initiating a phase imbalance trip see 2 2 3 Run mode settings page 23 TripLevel Sets Phase Imbalance Phase Loss Protection see 2 5 4 7 4 p 58 Trip Level parameter The Trip Level parameter is defined as the ratio of imbalance current to the average current in all three phases that is detected for the set time period before initiating a phase imbalance trip 56 Chapter 2 Operation 05 2004 Multifunction Control Unit Function Parameter line 1 line 2 47_Phaselmb Warning Enables or disables the Phase Imbalance Phase see 2 5 4 7 5 p 58 Loss Protection Warning function If the Multifunction Control Unit detects a phase imbalance condition above the set Warn Level page 58 a warning is actived The Warning deactivates itself when the imbalance condition drops 5 below the set level Definition Warn Level Sets the Phase Imbalance Phase loss Warn Level see 2 5 4 7 6 p 58 Parameter NOTE Press amp or to enable stepping through all the display parameters ENT Sends to parameters settings ESC Returns to 4_AdvSetup page 45 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume T e l o Z m 25 47 1 Trip Parameter Setting um line 1 l
26. 2 Definition Units 25_L3Current No Disables the display of Current measured in Amps L3T3 in the Run mode settings page 23 Disabled by default Yes Sets display to scroll Current measured in L3T3 in the Run mode settings page 23 ENT Saves setting and returns to 2_Display page 37 ESC Does not save a setting returns to 2_Display page 37 2 5 2 6 26_GFCurrent Ground Fault Current Function Setting T line 1 line 2 Definition Units 26 GFCurrent No Disables the display of the Ground Fault Current Amps in the Run mode settings page 23 Disabled by default see 46 GroundFIt page 46 Yes Sets display to scroll the Ground Fault Current in the Run mode settings page 23 ENT Saves setting and returns to 2 Display page 37 ESC Does not save a setting returns to 2 Display page 37 05 2004 Chapter 2 Operation 39 X e m o z m Multifunction Control Unit 25 27 27 LastTrip Last Fault Type ENGLISH Function Setting T T line 1 line 2 Definition Units 27 LastTrip No Disables the display of the Last Fault Type in the Run mode settings page 23 Disabled by default Yes Sets display to scroll the Last Fault Type in the Run mode settings page 23 ENT Saves setting and returns to 2 Display page 37 ESC Does not save a setting returns to 2 Display page 37
27. 24 to 18 Stranded cable 2 conductors mm 0 2 to 1 5 AWG 20 to 18 Terminal tightening torque aux N m 0 5 to 0 6 power only Ib in 4 6 to 5 6 18 Chapter 1 General information 05 2004 Multifunction Control Unit 1 3 6 4 RS 485 Serial port RJ 45 connector Electrical Interface RS 485 Connector RJ 45 RJ 45 pin out cable connector top view D A A 1 D B DB 4 ism i E 5V saan E Ss common Isolation V 1kV Max line length m ft 1000 m 3280 ft max tap off length m ft 20 m 65 ft Parity None 1 start bit 8 data bits and 1 stop bit 10 bits total Default Even 1 start bit 8 data bits even parity and 1 stop bit 11 bits total Modbus RTU commands The Multifunction Control Units shall support the following Modbus RTU commands Code 3 03 hex Normal read holding registers maximum 100 registers Code 6 06 hex Preset write single register Code 16 10 hex Preset write multiple registers maximum count 46 Code 65 41 hex Private identification request specific for drives The Multifunction Control Units shall support the following Modbus RTU reponses Code 3 03 hex Normal read holding registers reponse Code 6 06 hex Normal preset write single register reponse Code 16 10 hex Normal preset write multiple registers reponse Code 65 41 hex Privat
28. 3 3 2 LUCMT1BL 1 3 4 Minimum required setup 12 1 3 5 Default settings and optional values aaa 13 1 3 6 Specifications sss eee 17 1 3 6 1 zia ilo nasi a nn eaa Ma aaa Kerian aan ain aii 17 1 3 6 2 egere a EE 18 1 3 6 3 Control circuit supply A1 A2 terminals and auxiliary power input 18 1 3 6 4 RS 485 Serial port RJ 45 connector a 19 Chapter 2 Operation noatro troquet usus 20 2 1 Men v str ctu re ocio derniere Herten Fee Lag rer Ete dee pl Lets 20 2 2 Configuration and settings sss 21 2 2 1 Config mode first power up configuration and settings 21 2 2 2 Off Ready and Pause modes subsequent power ups and settings 22 2 2 3 Run mode settihigs 5i tede e rettet peii ana ERE PUER 23 2 3 Monitoring the MOtOF Hee 24 2 3 1 Run mode monitoring a kakak aa aaa 24 2 3 2 Warning mode diagnostiCS emm 24 2 3 3 Fault mode diagnostics sss 2 3 4 Warnings and Faults diagnostics 05 2004 Table of Contents 3 I e E o Z m ENGLISH Multifunction Control Unit 2 4 2 4 1 2 4 2 2 4 3 2 4 4 2 4 5 2 4 5 1 2 4 5 2 2 4 5 3 2 4 5 4 2 4 5 5 2 4 5 6 2 4 5 7 2 4 5 8 2 4 5 9 2 4 5 9 1 2 4 5 9 2 2 4 5 9 3 2 4 6 2 5 2 5 1 2 5 2
29. ENT Sends to parameters settings ESC Returns to 4_AdvSetup page 45 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 2 5 4 10 1 Trip Parameter Setting Sere line 1 line 2 pennition Trip Off Disables the Long Start Protection Trip parameter Disabled by default On Enables the Long Start Protection Trip parameter ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 05 2004 Chapter 2 Operation 63 ENGLISH Multifunction Control Unit 254402 TripTime Parameter Setting 2 5 4 10 3 T 254404 Warning 2 5 4 10 5 Warn Level The Warn Level parameter is adjustable from 100 to 800 of the FLA setting in increments of 10 Default setting is 100 FLA line 1 line 2 Definition Units TripTime 10Sec Use amp or to select the desired time Sec The Trip Time parameter is adjustable from 1 to 200 seconds in increments of 1 second Default setting is 10 seconds ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 ripLevel ere vie Definition Units TripLevel 100 FLA Use amp or to select the desired level FLA The Trip Level parameter
30. Level 85 10 to 100 Capacity 46_GroundFlt Trip On Off TripTime z 1 0 Sec 0 1 to 1 2 TripLevel xA 20 to 500 30 FLA min Warning On Off Warn Level xA 20 to 500 3096 FLA min 47 Phaselmb Trip On Off TripTimeStrt 0 7 Sec 0 2 to 20 TripTimeRun 5 0 Sec 0 2 to 20 TripLevel 10 IMB 10 to 30 Warning On Off Warn Level 10 IMB 10 to 30 Chapter 1 General information 05 2004 Multifunction Control Unit Menu Submenu Function Parameter a e Optional values 4 AdvSetup 48 Jam Trip Off On TripTime 5 Sec 1 to 30 TripLevel 200 FLA 100 to 800 Warning Off On Warn Level 200 FLA 100 to 800 49 UnderLoad Trip Off On TripTime 10 Sec 1 to 200 TripLevel 50 FLA 30 to 100 Warning Off On Warn Level 50 FLA 30 to 100 410 LongStrt Trip Off On TripTime 10 Sec 1 to 200 TripLevel 100 FLA 100 to 800 Warning Off On Warn Level 100 FLA 100 to 800 5 CommSetup 51 Drop sese 1 to 247 52 Bad a alaa 19200 bps 1200 to 19200 59 Par ra None Even 54 CONTON ius cen ta aar On Off 55 Commbloss Ignore Dropout Trip Warning 6_Module 61 ID Clear Yes No 62 Referenc
31. Option module Firmware revision is displayed in line 2 Rev 0 00 fID code is 0 Firmware revision is displayed as 0 00 ENT Sends to parameters settings NOTE Press Q or to enable stepping through all the display parameters ESC Returns to 6 Module page 69 x 2 E Oo z i 2 5 6 3 63 Id Set Option Module Identification number Function Setting line 1 line 2 Definition 63 Id Set 0 Use amp or to select the desired option module ID number The ID set parameter is settable from 0 to 149 Default setting is 0 ENT Saves setting and returns to 6 Module page 69 ESC Does not save a setting returns to 6 Module page 69 2 5 6 4 64 Param dec Option Module Parameter Dec setting Submenu Parameter Function Reference Definition line 1 line 2 line 1 line 2 6 Module 64 Param dec Parameter 1 16 Line 1 shows the parameter number 1 through 16 00000 Line 2 shows the parameter setting in decimal see 2 5 6 6 The parameters are settable from 00000 to 65535 Default setting for all 16 parameters is 00000 ENT Sends to parameters settings NOTE Press or to enable stepping through all the parameters numbers ESC Returns to 6_Module page 69 70 Chapter 2 Operation 05 2004 Multifunction Control Unit 25 65 65 Param hex Option Module Parameter Hex setting
32. Quantity 0 Number Magnetic Trips 102 0 65535 Quantity 0 Number Ground Fault Trips 103 0 65535 Quantity 0 Number Thermal Trips 104 0 65535 Quantity 0 Number Long Start Trips 105 0 65535 Quantity 0 Number Jam Trips 106 0 65535 Quantity 0 Number Phase Imbal Trips 108 0 65535 Quantity 0 Number Shunt Trips 109 0 65535 Quantity 0 Number Comm Loss Trips 110 0 65535 Quantity 0 Number LULC031 communication module Internal Faults 111 0 65535 Quantity 0 Number Module identification Faults 112 0 65535 Quantity 0 Number Module internal Faults 113 0 65535 Quantity 0 Number Module Trips 114 0 65535 Quantity 0 Number Module Dropouts 115 0 65535 Quantity 0 Number Auto Resets 116 0 65535 Quantity 0 Number Thermal Warnings 117 118 0 4 2 billion Quantity 0 Number of Starts 119 120 0 4 2 billion Seconds 0 Operating Time 136 years 121 0 200 Degrees C 0 Max Control unit Internal Temp 150 0 65535 None 0 Trip n O Fault Number 151 25 100 FLA max 0 FLA Current Setting 152 0 100 Yo 0 Thermal Level 153 0 2 000 FLA 0 IIAV Average Current 154 0 2 000 FLA 0 IL1 Current 155 0 2 000 FLA 0 IL2 Current 156 0 2 000 FLA 0 IL3 Current 157 0 2 000 FLA 0 IGF Current 180 0 65535 None 0 Trip n 1 Fault Number 181 25 100 FLA max 0 FLA Current Setting 182 0 100 0 Thermal Level 183 0 2 000 FLA 0 IIAV Average Current 184 0 2 000 FLA 0 IL1 Current 185 0 2 000 FLA 0 IL2 Current
33. Setting range from 5 to 30 in increments of 5 see Appendix A Thermal Trip and Reset curves page 81 42_ResetMode see DANGER page 48 see 2 5 4 2 p 48 Defines the method of resetting the device after fault detection see Fault mode diagnostics page 25 See 2 3 4 Warnings and Faults diagnostics page 26 for fault and reset messages 43_RstAdjust see CAUTION page 50 see 2 5 4 3 p 50 Sets the time delay and thermal capacity level required before the reset of a thermal overload fault can be made Both the adjustable ResetTime page 50 and ResetLevel page 50 parameters in this function must be reached before a restart is allowed NOTE Selecting Manual Reset Mode see 42_ResetMode page 48 or cycling coil control power to A1 A2 terminals resets the thermal fault but not the internal thermal memory timer A fault trip may reoccur immediately after restart if the internal thermal capacity of the Multifunction Control Unit is exceeded 44_MagTrip see DANGER page 51 see 2 5 4 4 p 51 Sets level of Magnetic Overload Protection for the l for LUCM BL only Self Protected Starter Power Base Trips the base device if the magnetic trip setting is exceeded for more than 100 ms 45 OLWarning Sets the Thermal Overload Warning function see 2 5 4 5 p 51 The Warning page 52 is activated if the thermal capacity of the motor reaches the set percentage of its capacity
34. Warning page 52 deactivates if thermal capacity l drops below set Warn Level page 52 05 2004 Chapter 2 Operation 45 I e l o Z m ENGLISH Multifunction Control Unit Submenu line 1 Function line 2 Definition 4_AdvSetup 46_GroundFlt see 2 5 4 6 p 53 see DANGER page 53 Sets the Ground Fault Protection function Trip page 54 parameters can be set for ground currents that exceed a set TripLevel page 54 for a set TripTime page 54 delay Warning page 54 parameters can be set for ground currents that exceed a set Warn Level page 55 47 Phaselmb see 2 5 4 7 p 56 see WARNING page 56 Sets the Phase Imbalance Phase Loss Protection function Trip page 57 parameters can be set for currents that differ in one phase by more than a set percentage from the average current in all three phases for a set time period Different time delays can be set for motor startup TripTimeStrt p 57 and for normal run TripTimeRun page 58 conditions Warning page 58 parameter can be set for imbalance loss currents that exceed a set Warn Level page 58 NOTE The Phase Imbalance Phase Loss Protection function is automatically disabled if Multifunction Control Unit is configured for single phase motor loads see LoadType page 28 48_Jam see 2 5 4 8 p 59 Sets the Jam Protection function Trip page 59 parameters can be set fo
35. automatically start the motor if coil control power is still applied to A1 A2 terminals Tripped fault types can not be displayed without auxiliary control power to the LUCM BL or or We TAV 2 5A If the Warning If the Warning is disabled is disabled x e o Z m som seconds later mae gt Tripped Over load Fault message see 2 3 4 Warnings and E Faults diagnostics page 26 KS read only _ During Run mode z 1_Reference o9 1 Reference 1 Reference parameters are read only gt Q i Main Menu KE read only EES Tati _ During Run mode gt 7_Statistics e LBtatatcs 7 Statistics parameters are read only k 1 1 inp X for 0 sec see 2 5 7 7 Statistics page 73 Faults that show Int Trip in line 1 of the display and Fault type code in line 2 indicate internal Faults detected by the Multifunction Control Unit A Manual Reset and cycling of the auxilliary control power from On to Off will be required before a Restart can be made 05 2004 Chapter 2 Operation 25 Multifunction Control Unit 234 Warnings and Faults diagnostics Warning or Warning Fault Message Fault Type message Manual Mode Remote Ent Mode Auto Mode Tripped Over_Load Wait xxx Secs Auto xxx Secs 4 gt D 2 3 2 o lt 5 ES o
36. current secondary current ratio see 31 FLASet page 41 50 1 Sets FLA current scale for current transformers with a see 2 4 5 4 p 31 50 1 primary current secondary current ratio see 31 FLASet page 41 100 1 Sets FLA current scale for current transformers with a see 2 4 5 5 p 31 100 1 primary current secondary current ratio see 31 FLASet page 41 200 1 Sets FLA current scale for current transformers with a see 2 4 5 6 p 31 200 1 primary current secondary current ratio see 31_FLASet page 41 05 2004 Chapter 2 Operation 29 x e l o Z m Multifunction Control Unit CT_Ratio 400 1 Sets FLA current scale for current transformers with a for LUCM BL see 2 4 5 7 p 31 400 1 primary current secondary current ratio only see 31 FLASet page 41 800 1 Sets FLA current scale for current transformers with a see 2 4 5 8 p 32 800 1 primary current secondary current ratio see 31 FLASet page 41 Others Sets FLA current scale for current transformers ratios see 2 4 5 9 p 32 not shown above see 31 FLASet page 41 NOTE Press amp or to enable stepping through all the CT Ratio parameters ENT Sends to parameters settings ESC Does not save a setting returns to Config Menu page 27 2454 30 3 Parameter Setting line 1 line 2 penninon
37. cycle e When the Start cycle has ended the display will show Run indicating the Run mode monitoring The user can then compare actual Run values with protection settings and make adjustments as necessary see 2 2 3 Run mode settings page 23 RunStart IAV 2 5A some some seconds later seconds later v v Second v Second 5 i Scrolling i z mG Scrolling a line J Scrolling ye Scrolling a line d gt Run D IAV 2 5A z Average 3 phase current Thermal capacity Ground fault current E 2 Display 21 AvCurrent 2 Display 22 ThermCap Y 2_Display 26_GFCurrent Display Yes by default Display No by default Display No by default o 9 9 4 l 4 4 Man Menu 65 1 Reference Oo 1 Reference see 2 5 2 2 Display page 37 Td c Ca EROS SEA T Se aay ee cert see 2 2 3 Run mode settings page 23 232 Warning mode diagnostics When an enabled warning occurs line 1 of the display will show Warn followed by the warning type see 2 3 4 Warnings and Faults diagnostics page 26 By pressing ENT when a warning is displayed the user may scrole through the settings and verify the set Warn Level Adjustment of the Warn Level is done in Off mode see 2 2 p 21 RunStart or or IAV 2 5A A A PS aN some some seconds later seconds later v WV Second Second A line Scrolling line P um NN Scrolling i Scrol
38. is 30 of the minimum FLA setting Example The 0 15 to 0 60 Multifunction Control Unit has an adjustable range from 0 03 to 0 75 A in increments of 0 01 A with a default setting of 0 04 A ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 254 64 Warning Parameter Setting line 1 line 2 Definition Warning 0n Enables the Warning parameter Enabled by default Off Disables the Warning parameter ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 I 54 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 54 65 Warn Level Parameter Setting e o line 1 line 2 Definition Units Warn Level xA Use amp or Q to select the desired level Amps The Warn Level parameter is adjustable from 20 to 500 of the minimum FLA setting of the Multifunction Control Unit in increments of 10 Default setting is 30 of the minimum FLA setting Example The 0 15 to 0 60 Multifunction Control Unit has an adjustable range from 0 03 to 0 75 A in increments of 0 01 A with a default setting of 0 04 A ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 05 2004 Chapter 2 Operation 55 I e l o z m Multifunction Control Unit 2 5 4 7 47_Phaselmb Phase Imbalance Phase Loss Protect
39. is adjustable from 100 to 800 of the FLA setting in increments of 10 Default setting is 100 FLA ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 ae hee Definition Warning Off Disables the Warning parameter Disabled by default On Enables the Warning parameter ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 p yu Definition Units Warn Level 100 FLA Use amp or to select the desired level FLA ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 64 Chapter 2 Operation 05 2004 Multifunction Control Unit 25 5 5 CommSetup The 5 _CommSetup submenu allows access to the controls of the RS 485 serial port compatible with Modbus protocol on the front face of the Multifunction Control Unit The RS 485 asynchronous interface supports the Modbus RTU slave protocol Remote display or configuration devices must be Modbus RTU masters which initiate communications by reading and writing 16 bits register data in the Multifunction Control Unit See Appendix C Register data format page 86 See 1 3 6 4 RS 485 Serial port RJ 45 connector page 19 For detailed information on the Modbus9 protocol see www modbus org _A WARNING Improper communication port usage appl
40. must conform with national and local safety regulations and codes Failure to follow these instructions can result in death serious injury or equipment damage Function Setting line 1 line 2 Definition 33_PauseMtr No Allows closing of the main power contacts by energizing the coil with coil control power already applied to A1 A2 terminals on the LUeBee and LU S or energizing the output 13 23 relays while 24V DC is still applied to inputs 11 and I2 on the LUTM BL Disabled by default Yes Opens the main power contacts by de energizing the contactor coil with coil control power still applied to A1 A2 terminals on the LU Bee and LU S or de energizing the output 13 23 relays while 24V DC is still applied to inputs 11 and I2 on the LUTM BL ENT Saves setting and returns to 3 Setup page 41 ESC Does not save a setting returns to 3 Setup page 41 05 2004 Chapter 2 Operation 43 Multifunction Control Unit 253 4 34 Language Unit Display Language js No Definition 34 Language English Sets display to English Enabled by default Francais Sets display to French Espanol Sets display to Spanish for LUCMe BL only Deutsch Sets display to German for LUCM 9 BL only Italiano Sets display to Italian for LUCMe BL only ENT Saves setting and returns to 3 Setup page 41 ESC Does not save a setting returns to 3 Setup page 41
41. or download the Multifunction Control Unit function settings Definition NOTE Press amp or to enable stepping through all the display functions ENT Sends to functions settings ESC Returns to Main Menu page 35 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume I e l o Z m 2 5 8 1 81_Unlock Disable Password Protection Function Setting line 1 line 2 Definition 81 Unlock Passwd The Disable Password Protection function initiates the 0001 9999 Unlock sequence The Multifunction Control Unit displays Passwd Use Q or to increment the first digit from 0 to 9 Press the ENT key to enter the first value and move to the second digit The same procedure is followed for the second third and fourth digits Once the fourth and last digit has been selected and the ENT key is pressed a setting can be modified NOTE The Disable Password Protection function only disables the password feature temporarily The password must be set at 0000 to completely disable the password ENT Saves setting and returns to 8 Password page 76 ESC Does not save a setting returns to 8 Password page 76 05 2004 Chapter 2 Operation 77 ENGLISH Multifunction Control Unit 2 5 8 2 82 Lock Enable Password Protection Function Se
42. protection ENT Saves setting and returns to Config Menu page 27 ESC Does not save a setting returns to Config Menu page 27 Base Motor Starter Power Base Type EN CAUTION Incorrect Power Base setting Changing the Power Base setting does not affect motor protection functions or current interruption capacity of the Power Base Setting incorrect Power Base may cause the wrong Power Base to be read and displayed by the LCD or remote network device Incorrect setting of the Power Base function can result in serious injury or equipment damage Function Setting Ce line 1 line 2 Definition Base SelfProtStr Sets identification reference for a self protected motor for LUCM BL starter which provides both short circuit and overload only protection for a motor branch circuit Enabled by default Starter Sets identification reference for a motor starter which provides only overload protection for a motor branch circuit ENT Saves setting and returns to Config Menu page 27 ESC Does not save a setting returns to Config Menu page 27 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 4 4 AuxFan Auxiliary Fan Cooled Motor A CAUTION Incorrect AuxFan setting When the AuxFan option is set the reset motor cool down time is reduced by a factor of 4 Ifthe motor i
43. references and the functions set in the Config Menu Configuration Menu They can be viewed in either the Run mode settings page 23 or Configuration and settings page 21 Menu Function Submenu Reference Definition line 1 line 2 line 1 line 2 Main Menu ENT 11 Catalog l 1_Reference LUCMx6BL Catalog number is displayed Line 2 12_Firmware Rev XX XX Firmware revision is displayed Line 2 13_FLA Range 0 15 Ato0 6A_ Minimum to maximum Amps motor current ENGLISH setting range is displayed Line 2 see 2 5 3 1 31 FLASet Full Load Amp Setting page 42 l 14_LoadType same setting as 2 4 2 3 PhMotor read only The Motor Load Type function is displayed Line 2 l 15_AuxFan same setting as 2 4 4 No read only The Auxiliary Fan Cooled Motor function is displayed Line 2 16_PowerBase SelfProtStr same setting as 2 4 3 read only The Motor Starter Power Base Type function is displayed Line 2 ENT Sends to functions for viewing NOTE Press or to enable stepping through all the function references ESC Returns to Main Menu page 35 Chapter 2 Operation 05 2004 Multifunction Control Unit 25 2 2 Display The 2_Display submenu allows access to the viewable Run mode settings values shown on the unit display see 2 2 3 Run mode settings page 23 These functions can be enabled or disabled in either the Run mode
44. 2 5 2 8 28 Phaselmb Phase Imbalance Current Function Setting eT line 1 line 2 Definition Units 28 Phaselmb No Disables the display of the Phase Imbalance Current in the Run mode settings page 23 Disabled by default Yes Sets display to scroll the percentage of Phase Imbalance Current measured in the Run mode settings page 23 ENT Saves setting and returns to 2 Display page 37 ESC Does not save a setting returns to 2 Display page 37 2529 29 ONhours Total hours Function Setting line 1 line 2 Definition Units 29 ONhours No Disables the display of the Total hours in the hrs Run mode settings page 23 Disabled by default Yes Sets display to scroll the hrs of Total hours detected in the Run mode settings page 23 ENT Saves setting and returns to 2 Display page 37 ESC Does not save a setting returns to 2 Display page 37 Chapter 2 Operation 05 2004 Multifunction Control Unit 25 3 3 Setup The 3 Setup submenu allows access to basic setup functions These functions can be enabled or disabled in either the Run mode settings page 23 or Config mode first power up configuration and settings page 21 or Off Ready and Pause modes subsequent power ups and settings page 22 A WARNING Improper Inadvertant settings Setup values can be modified in Run mode settings page 23 Values can be set via the network External programmi
45. 2 5 7 6 76 Totals Historical Count Totals for Start Run and Fault Events Function Value mare line 1 line 2 Definition 76_Totals Total Starts Contains the total number of motor starts detected A start is defined as closure of the power contacts Auto Resets Contains the total number of Auto Resets detected Shunt Trips Contains the total number of Shunt Trips detected ON Hours Contains the total number of Hours that the Power Base contacts have been closed SC Trips Contains the total number of Short Circuit Trips detected Mag Trips Contains the total number of Magnetic Fault Trips detected OL Trips Contains the total number of OverLoad Faults detected GF Trips Contains the total number of Ground Fault Trips detected Imbal Trips Contains the total number of Phase Loss and Phase Imbalance faults detected Jam Trips Contains the total number of Jam faults detected UndrLd Trips Contains the total number of UnderLoad faults detected LongSt Trips Contains the total number of Long Start faults detected Comm Trips Contains the total number of RS 485 serial port Communication Loss faults detected Int Fit Contains the total number of Internal Multifunction Control Unit Faults detected Warn OL Contains the total number of Overload Warnings detected Mod ID Contains the total number of Option Module ID detection Faults ex incorrect or missing
46. 4 0 1 Off On 1 LUCM BL Multifunction Control Unit 76 1000 29999 LUCMesBL Firmware revision 77 1000 29999 0 LUCMeeBL Compatibility revision 78 0 65535 0 1 4000 Sensor Scale Ratio max min x1000 3000 For LUCMT1BL only 79 0 65535 01A 6 0 15 to 0 6 A Sensor maximum 14 0 35 to 1 4 A 50 1 25to5A 120 3to 12A 180 4 5to18A 320 8 to 32 A 80 0 0 1 Off On 0 Power Base unknown 1 0 1 Off On 0 Overload relay Controller 0 1 Off On 0 Starter 3 0 1 Off On 1 Self protected combination starter 4 15 0 1 Off On 0 Reserved 81 0 65535 0 1A 120 12A Power Base Range 320 32A 8400 Overload relay Controller 86 Appendix 05 2004 Multifunction Control Unit From 50 to 95 identification registers read only 16 bit a Default register Bit Range Unit erii Information 82 87 Overload relay Controller Catalog Number 88 92 Overload relay Controller Serial reference 93 Overload relay Controller Firmware revision l 94 Reserved 95 10 8000 0 1 10 Current Transformer Ratio Calculated For LUCMT1BL only x e l 2 Z m 05 2004 Appendix 87 ENGLISH Multifunction Control Unit From 100 to 277 statistics registers read only Bira Bit Range Unit Ea EA Information 100 0 65535 Quantity 0 Number Short Trips 101 0 65535
47. 78 2 5 8 4 84_RstToDfts Resets all Configurable Functions to factory default settings 78 Chapter 3 Run Start Cycle 79 Appendix A Thermal Trip and Reset curves A 1 Trip Times Hot Motor Load A 2 Trip Times Cold Motor Load ssssssss eme A 3 Reset Times With Aux Fan Cooled function disabled 83 A 4 Reset Times With Aux Fan Cooled function enabled 83 Appendix B Display Words 84 Appendix C Register data format 86 Appendix D Fault and Warning Codes 96 D 1 Fault code summary eee 96 D 2 Warning code summary eme 97 Appendix E Powersuite M e nn 98 Table of Contents 05 2004 Multifunction Control Unit Chapter 1 General information 1 1 Introduction The LUCMe BL Multifunction Control Units provide control protection and monitoring capabilities for the following TeSys model U Products LU B Self protected combination starters LU S Starters LUTM BL Overload relay controller It requires a control circuit supply of 24 V DC The functions provided are typical to those for other multifunction relays that protect single and three phase electric motors NOTE The LUCMeeBL Multifunction Control Units are for use with AC motor loads only The LUCMT1BL Multifunction Control Units are for use with 3 Phase AC motor loads only Protection functions Overcurrent protection Overload protection sel
48. 9 2 4 5 5 100 1 Parameter Setting n line 1 line 2 Definition 100 1 No Returns to CT Ratio parameter selection page 27 2 Yes Sets CT Ratio to 100 1 Sets FLASet range to 35 105 Amps 2 see 31 FLASet page 42 ul ENT Saves setting and returns to CT Ratio page 29 ESC Does not save a setting returns to CT Ratio page 29 2 4 5 6 200 1 Parameter Setting TON line 1 line 2 Pe inition 200 1 No Returns to CT Ratio parameter selection page 27 Yes Sets CT Ratio to 200 1 Sets FLASet range to 70 210 Amps see 31 FLASet page 42 ENT Saves setting and returns to CT Ratio page 29 ESC Does not save a setting returns to CT Ratio page 29 2 4 5 7 400 1 Parameter Setting DE line 1 line 2 Be inition 400 1 No Returns to CT Ratio parameter selection page 27 Yes Sets CT Ratio to4 800 1 Sets FLASet range to 140 420 Amps see 31 FLASet page 42 ENT Saves setting and returns to CT Ratio page 29 ESC Does not save a setting returns to CT Ratio page 29 05 2004 Chapter 2 Operation 31 Multifunction Control Unit 2 45 8 800 1 2 4 5 9 Others Other Current Transformer Ratio Settings 2 45 91 Primary Primary Current Transformer Rating Parameter Setting line 1 line 2 Derinition 800 1 No Returns to CT_Ratio parameter selection page 27 Yes Sets CT_Ratio to 800 1 Sets FLASet range to 280 840 Amps see 31_FLASet page 42
49. D a a Q I o Q D 5 3 2 2e imm dimmi Short circuit Fault ine 1 Tripped a f LUCMeBL only These faults Line 2 Short ara anes vege a will reset f i Shunt trip Fault 1 automaticaly Tipp i EEMB On nn inthe Magnetic Fault LUCMT1BL M Tripped i LUCM BL only f Tripped Ground Fault Ground Fault Warmm GF 1 1 1 1 1 1 1 L Tripped L ENGLISH Phase Imbalance i i i Tripped o 35 a E 5 a T m PIDE Seri ESRC a 4 Tripped Tripped di EFS I muri MEE Nga Home UnderLoad c 1 1 1 1 1 i 1 1 1 1 1 1 1 1 1 1 1 1 Tripped Test Trip Fault i TestTrp Wait xxx Secs Auto xxx Secs a Se pelea Internal Fault H Int Trip Mam MR see list below fault type 1 XX 1 XX Xx Internal temperature BN Int Trip B Int Trip d Int Trip Fault serolled Run info 51 51 51 Lost Communications Wamcomm EEIE OffComm Fault scrolled Run info CommLoss Ent to Reset i aa a an eel Rs ee a aS pete a a ae 4 TON i Manm TTE ottwxx 1 Option Module Fault ecrotied Run no Mxxx EnttoReset APP LA AO daa 2 igs SoS LeU et LE et Oe quun na Ae Oe Se 2 See option module instruc
50. Decimal NOTE This function sets the same parameters as found in 65 Param hex 65 Param hex see 2 5 6 5 p 71 Allows entering option module parameter codes in Hex NOTE This function sets the same parameters as found in 64 Param dec NOTE Press or to enable stepping through all the display functions ENT Sends to functions settings ESC Returns to Main Menu page 35 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 2 5 6 1 61 ID Clear Option Module Identification Number Reset po EE Definition 61 ID Clear Yes Resets option module identification number to O zero Enabled by default No Disables option module identification number reset ENT Saves setting and returns to 3_Setup page 41 ESC Does not save a setting returns to 3 Setup page 41 05 2004 Chapter 2 Operation 69 I e l o z wi Multifunction Control Unit 2 5 6 2 62 Reference Option Module References Submenu Parameter Function Reference Definition line 1 line 2 line 1 line 2 6_Module Module Option module ID code is displayed in line 2 62_Reference ID 0 ID 20 indicates unknown or no option module present Catalog Option module Catalog number is displayed in line 2 If ID code is 0 Catalog number is displayed as Firmware
51. TeSys model U LUCMe BL and LUCMT1BL User s manual Multifunction Control Unit 05 2004 EJ Telemecanique TeSys ICM32B pie waned Schneid a Telemecanique ENGLISH Multifunction Control Unit A WARNING HARZARDOUS OPERATION This device must be installed set up and serviced only by qualified personnel User must follow all applicable codes standards and regulations Do not alter or modify this equipment Failure to follow these instructions can result in death serious injury or equipment damage 2 05 2004 Multifunction Control Unit Table of Contents Page Chapter 1 General information 7 1 1 Introduction ann sng AA A AAA 7 1 1 1 Protection functions 1 1 2 Alarm functions 1 1 3 Diagnostic functions aa 1 1 4 Configuration and Monitoring aaa 7 1 2 Presentation naa nan a SA qth aul aan Ani A Aan nk ames 8 1 2 1 Multifunction Control Unit aaa 8 1 2 2 Keypad programming principles sss 8 1 3 Technical data eee Loren Her utes A bee Hr dene de e duoi Pr Aan uus 10 1 3 1 Installation irte enne rete nere stds epe einer pere n edd nera 10 1 3 2 Operating temperatureS eee 10 1 3 3 Control connectiONS eem 11 1 3 3 1 LUCMesBL 1
52. Time begins when Max RunStart Time Coil control power is applied to A1 A2 terminals 10 sec 2 A time period of 10 seconds that starts when coil control power is applied to A1 A2 terminals on the Power Base with the 410 LongStrt page 47 function Trip or Warning parameter Disabled for currents that continuously exceed 150 FLA current threshold for currents that never exceed 150 FLA current threshold Current RunStart Current i MET 77777777 Threshold 7 150 FLA 1 RunStart Time Time RunStart Time begins when Max RunStart Time Coil control power is applied to A1 A2 terminals 10 sec 05 2004 Chapter 3 Run Start Cycle 79 Multifunction Control Unit 3 The time period from when coil control power is applied to A1 A2 terminals on the Power Base until the motor load current drops below an adjustable TripLevel current threshold with the 410 LongStrt page 47 function Trip or Warning parameter Enabled for currents that exceed the adjustable TripLevel current threshold Current Adjustable TripLevel mE V Current Threshold 100 to 800 FLA 15096 by default i RunStart Time Time RunStart Time begins when Adjustable TripTime Coil control power is applied to A1 A2 terminals 1 to 200 sec 10 sec by default 4 An adjustable TripTime period that starts when coil control power is applied to A1 A2 terminals on the Power Base with the 410_LongStrt p
53. Trip parameter Disabled by default On Enables the Jam Trip parameter ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 05 2004 Chapter 2 Operation 59 I e l o z m ENGLISH Multifunction Control Unit 25 48 2 TripTime Parameter Setting 25 483 T 25 48 4 Warning 25 485 Warn Level The Warn Level parameter is adjustable from 100 to 800 of the FLA setting in increments of 10 Default setting is 200 FLA line 1 line 2 Definition Units TripTime 5Sec Use amp or to select the desired time Sec The Trip Time parameter is adjustable from 1 to 30 seconds in increments of 1 second Default setting is 5 seconds ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 ripLevel ere iem Definition Units TripLevel 20096 FLA Use amp or to select the desired level FLA The Trip Level parameter is adjustable from 100 to 800 of the FLA setting in increments of 10 Default setting is 200 FLA ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 dro pa Definition Warning Off Disables the Warning parameter Disabled by default On Enables the Warning parameter ENT Saves setting and returns to 4_A
54. Write commands to the following registers are always possible and not affected Remote keypad register 1100 Multifunction Control Units state control register 704 Multifunction Control Units extended state control register 705 Option module configuration registers 680 690 Private registers above 20000 NOTE Write commands are disabled while the Multifunction Control Unit is in the Run mode monitoring page 24 except for writes to the 31_FLASet page 42 Setting register 653 and the list of always enabled registers above Changes to configuration registers 600 through 626 are disabled while keypad changes are in process ENGLISH 55_CommLoss Enables or disables the external RS 485 serial port see 2 5 5 5 p 68 watchdog A CommLoss fault is defined as any inactive period longer than 5 seconds A start delay of 10 seconds follows each time coil control power is applied to the A1 A2 terminals NOTE Press amp or to enable stepping through all the display functions ENT Sends to functions settings ESC Returns to Main Menu page 35 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 255 1 51 Drop Modbus Slave Number Function line 1 51 Drop Setting line 2 1 Use amp or to select the desired Modbus Slave Number can be selected The Modbus S
55. a warning The warning is deactivated when the communication is again established with the Multifunction Control Unit ENT Saves setting and returns to 5_CommSetup page 65 ESC Does not save a setting returns to 5_CommSetup page 65 68 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 6 6 Module The 6 Module submenu allows for the configuration of option modules that can Read and Write into the Multifunction Control Unit data registers Configuration of these option modules can be made by entering parameter codes with the keypad or by a remote configuration device connected to the RS 485 serial communication port see 1 3 6 4 RS 485 Serial port RJ 45 connector page 19 Seeindividual option module instructions for parameter code definitions see 2 5 6 1 p 69 Submenu Function Em line 1 line 2 Definition 6_Module 61_ID Clear Allows user to reset the option module identification back to 0 disabling the watchdog function see Fault code summary page 96 62_Reference see 2 5 6 2 p 70 Displays option module references as they are written to the Multifunction Control Unit by the option module 63 Id Set see 2 5 6 3 p 70 Set the option module identification into the Multifunction Control Unit so as to provide watchdog and configuration functions 64 Param dec see 2 5 6 4 p 70 Allows entering option module parameter codes in
56. age 47 function Trip or Warning parameter Enabled for currents that continuously exceed the adjustable TripLevel current threshold NOTE Under this condition the device will initiate a Trip or Warning at the end of this Run Start Cycle ENGLISH Current Adjustable TripLevel ee Te ee ee DM HENRI Current Threshold 100 to 800 FLA 150 by default i RunStart Time i Time RunStart Time begins when Adjustable TripTime Coil control power is applied to A1 A2 terminals 1 to 200 sec 10 sec by default 5 An adjustable TripTime period that starts when coil control power is applied to A1 A2 terminals on the Power Base with the 410_LongStrt page 47 function Trip or Warning parameter Enabled for currents that never exceed the adjustable TripLevel current threshold NOTE Under this condition the device will not initiate a Trip or Warning at the end of this Run Start Cycle Current l Adjustable TripLevel Se EE CMM AUN MC MM LN Ma aa MM Ld LL Current Threshold 100 to 800 FLA 15096 by default gt i RunStart Time i Time RunStart Time begins when Adjustable TripTime Coil control power is applied to A1 A2 terminals 1 to 200 sec 10 sec by default 80 Appendix 05 2004 Multifunction Control Unit Appendix A Thermal Trip and Reset curves A 1 Trip Times Hot Motor Load 10 000 1 000 x e E 2 Z
57. all stored statistics data The Fault history can be accessed during the Run mode settings page 23 or Config mode first power up configuration and settings page 21 or Off Ready and Pause modes subsequent power ups and settings page 22 Submenu Function Definition line 1 line 2 7_Statistics 71 TripO Contains stored Historical Information Last fault T 7 see 2 5 7 1 p 73 detected 5 72_Trip1 Contains stored Historical Information Second to g see 2 5 7 2 p 74 last fault detected ul 73 Trip2 Contains stored Historical Information Third to last see 2 5 7 3 p 74 fault detected 74 Trip3 Contains stored Historical Information Fourth to last see 2 5 7 4 p 74 fault detected 75 Trip4 Contains stored Historical Information Fifth to last see 2 5 7 5 p 75 fault detected 76 Totals Contains Historical Count Totals for Start Run and see 2 5 7 6 p 75 Fault Events as detected by the Multifunction Control Unit NOTE Press the ENT key to view the Totals item in first line and the actual count in the second line NOTE Press or to enable stepping through all functions ENT Sends to function ESC Returns to Main Menu page 35 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 2 5 7 1 T1 TripO Historical Information Last fault Functi
58. ameters ENT Sends to parameters settings ESC Returns to 4 AdvSetup page 45 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 05 2004 Chapter 2 Operation 53 I e o z m Multifunction Control Unit 25 461 Trip Parameter Setting m line 1 line 2 benniton Trip 0n Enables the Ground Fault Trip parameter Enabled by default Off Disables the Ground Fault Trip parameter ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 25 462 TripTime Parameter Setting z line 1 line 2 Definition Units a TripTime 1 0 Sec Use amp or to select the desired time can be Sec o selected 5i The Trip Time parameter is adjustable from 0 1 to 1 2 seconds in increments of 0 1 seconds Default setting is 1 0 second ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25463 TripLevel Parameter Setting en line 1 line 2 Definition Units TripLevel xA Use amp or to select the desired level Amps The Trip Level parameter is adjustable from 20 to 500 of the minimum FLA setting of the Multifunction Control Unit in increments of 10 Default setting
59. are set to their default values see 1 3 5 Default settings and optional values page 13 ENGLISH 12 Chapter 1 General information 05 2004 Multifunction Control Unit 1 3 5 Default settings and optional values 1_Reference Submenu Function Parameter MU LE Optional values or Reference Language eee English Francais Espafiol Deutsch for LUCM BL only Italiano LoadType for LUCM BL only 3 PhMotor 1 PhMotor Base for LUCM BL only SelfProtStr Starter AA a AA Ban a No Yes CT_Ratio 30 3 No Yes 3 5 10 5A for LUCMTIBL 30 2 No Yes 5 2 15 7 A onl y 30 1 No Yes 10 5 31 5A no default must be set 50 1 No Yes 17 5 52 5 A 100 1 No Yes 35 105 A 200 1 No Yes 70 210A 400 1 No Yes 140 420 A 800 1 No Yes 280 8404 Others Parameter Submenu Primary 1 to 65535 Secondary 1 to 65000 Exter Pass 1 to 65000 End Config us No Yes 11 Catalog uo LUCMx6BL see 31 FLASet Determined by 12 Firmware Rev Xx Xx Multifunction 18 FLA Range 0 15 A to 0 6 A pose ted Min to Max see 31 FLASet 14 LoadType 3 PhMotor read only 1D _AUNF AN nn anna an ani No eae 16 PowerBase SelfProtStr 2 Display 21 AvCurrent
60. ces and the Config Menu Configuration Menu page 27 functions settings 2 Display see 2 5 2 p 37 Sets type of information that scrolls on the Multifunction Control Unit display while in the Run mode monitoring page 24 3_Setup see 2 5 3 p 41 Provides access to the basic unit protection and setup functions These are functions that can be set while the unit is in the Run mode monitoring page 24 4_AdvSetup see 2 5 4 p 45 Provides access to the advanced protection functions 5_CommSetup see 2 5 5 p 65 Provides access to the communication setting of the RS 485 external communication port 6_Module Provides access to the functions and settings of optional see 2 5 6 p 69 communication and function modules 7 Statistics Provides access to historical information data stored in see 2 5 7 p 73 the unit memory Includes information on the last five faults count totals and reset data 8 Password see 2 5 8 p 76 Provides password protection to prevent unauthorized changes to configurable functions Also provides access to unit function resets NOTE Press amp or to enable stepping through all the display Submenus ENT Sends to Submenu 05 2004 Chapter 2 Operation 35 I e l o z m Multifunction Control Unit 25 1 1 Reference The1 Reference submenu allows READ only access to product
61. dvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 jocis pu Definition Units Warn Level 200 FLA Use amp or to select the desired level FLA ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 60 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 4 9 49 UnderLoad Under Load Protection Function Parameter Tn line 1 line 2 Definition 49 UnderLoad Trip Enables or disables the Under Load Protection see 2 5 4 9 1 p 61 Trip function A trip command is initiated if the Multifunction Control Unit detects a RMS current below a set TripLevel p 62 for the set TripTime p 62 period after the Run Start Cycle page 79 has ended NOTE Fault reset method for this function depends on the reset type selected see 42 ResetMode page 48 TripTime Sets the Under Load Protection Trip Time parameter see 2 5 4 9 2 p 62 The Trip Time parameter is defined as the amount of time in seconds that the RMS current is detected below a set value before inititing an Under Load Protection Trip I e l o Z m TripLevel Sets the Under Load Protection Trip Level parameter see 2 5 4 9 3 p 62 The Trip Level parameter is defined as the ratio of RMS current to the FLA setting that is detected for a set time period before initiating an Under Load Trip Warnin
62. e Module ID 0 Catalog if ID 0 Firmware Rev 0 00 if ID 0 63 Id Set eas 0 0 to 149 64 Param dec Parameter 1 16 00000 00000 to 65535 65_Param hex Parameter 1 16 0000 0000 to FFFF 7_Statistics T1 NPO aet 72 Trip 2 ume Statistics data TONADA sirrinin is cleared T4_THIDS sse by default 78 Tip soso see 7_Statistics page 73 76_Totals 05 2004 Chapter 1 General information 15 x e 2 Z m ENGLISH Multifunction Control Unit Menu Submenu Function Parameter eee Optional values 8 Password B1 Unlock essetis Passwd 0000 9999 82 LOCK aient NewPSW 0000 9999 B3 Bst Stats No Yes 84 RstToDfts No Yes 16 Chapter 1 General information 05 2004 Multifunction Control Unit 1 3 6 Specifications 136 1 Environment Conforming to standards IEC 947 4 1 IEC 34 11 IEC 755 VDE 0106 VDE 0660 European community C marking Meets the essential requirements of low Voltage equipment directives LV amp Electromagnetic Compatibility EMC Approvals UL 508 CSA PTB Protective treatment TH Tropical Finish Degree of protection Conforming to IEC 947 1 IP 20 1 Pollution degree Conforming to IEC 664 3 Shock resistance Conforming to IEC 68 2 27 10g open
63. e identification reponse data specific for drives 0x01 0x01 B 2 B 2 B 2 B 2 B 2 X w 0x28 0x01 0x00 The Multifunction Control Units shall support the following Modbus RTU codes Code 01 Illegal function Code 02 Illegal data address Code 03 Illegal data value write command not completed The 54 Control Write Control page 67 enable feature can be used to enable On or disable Off write privilege to the Multifunction Control Units configuration registers If 54 Control Write Control page 67 is No write commands are restricted to the following list of always enabled registers Remote keypad register 1100 Multifunction Control Units state control register 704 Multifunction Control Units extended state control register 705 Option module configuration registers 680 690 Private registers above 20000 05 2004 Chapter 2 Operation 19 X e l o z m Multifunction Control Unit Chapter 2 Operation 2 1 Menu structure Config Menu Configuration Menu page 27 contains equipment specific settings not considered adjustable after initial configuration Main Menu page 35 contains application specific settings and parameters considered adjustable First power up see 2 2 1 p 21
64. ection of trip class 5 to class 30 Ground fault detections Protection against phase imbalance Protection against mechanical blockages during or after the starting phase Protection against under load conditions Starter tripped by an external signal option NOTE The LUCMT1BL does not provide overcurrent protection I e l o Z m Alarm functions The Multifunction Control Units include alarm functions The alarm thresholds are configurable and independent of the associated protection function thresholds Diagnostic functions The Multifunction Control Units record and display number of operating hours for the motor total number of starts total number trips reason for trip For the last five trips the Multifunction Control Units record the state of the Power Base at the time of the trip current values thermal state and trip type Configuration and Monitoring The Protection Alarm and Diagnostic Functions can be configured or monitored locally via the integrated display and keypad remotely via IBM compatible personal computer utilizing PC PowerSuite software VW3A8104 Pocket PC utilizing Pocket PC PowerSuite software VW3A8102 Programmable Logic Controller communication bus Door mounted dialog terminal XBT NU 400 05 2004 Chapter 1 General information 7 Multifunction Control Unit Presentation Multifunction Control Unit 1 Locking and extracti
65. ement the value M NOTE The Multifunction Control Unit will not allow a digit to scroll past the 65000 maximum value or a value that would allow a current transformer ratio 22 less than 1 22 When the desired value has been selected and the ENT ENT i key pressed the Exter_Pass setting will be set ENT Saves setting and returns to Others page 32 ESC Does not save a setting returns to Others page 32 05 2004 Chapter 2 Operation 33 I e m o z m ENGLISH Multifunction Control Unit 2 4 6 End Config End Configuration Mode Function Setting line 1 line 2 Derintion End Config No Returns to Config Menu Configuration Menu page 27 Disabled by default Yes Sets initial configuration and sends to Main Menu p 35 ENT Saves setting ESC Does not save a setting returns to Config Menu page 27 34 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 Main Menu The Main Menu is the initial menu displayed after the Multifunction Control Unit has been configured e It contains all the user menus for setting protection functions configuration of optional communication and I O modules accessing stored statistical information setting display characteristics Main Menu 1 Reference see 2 5 1 p 36 Displays Multifunction Control Unit referen
66. en the fault is detected 2 Trip1 Historical Information Second to last fault Function Value Seque line 1 line 2 Definition 72_Trip1 The items found under this function are identical to those found under 71 TripO page 73 NOTE Press or to enable stepping through all functions ESC Returns to 7 Statistics page 73 3 Trip2 Historical Information Third to last fault Function Value line 1 line 2 Definition 73_Trip2 The items found under this function are identical to those found under 71 TripO page 73 NOTE Press amp or to enable stepping through all functions ESC Returns to 7 Statistics page 73 Information Fourth to last fault Function Value TT line 1 line 2 Definition 74_Trip3 The items found under this function are identical to those found under 71 TripO page 73 NOTE Press or to enable stepping through all functions ESC Returns to 7_Statistics page 73 74 Chapter 2 Operation 05 2004 Multifunction Control Unit 25 75 75 Trip4 Historical Information Fifth to last fault page 73 Function Value qd line 1 line 2 Definition 75 Trip4 The items found under this function are identical to those found under 71 TripO NOTE Press or to enable stepping through all functions ESC Returns to 7_Statistics page 73
67. ent damage Function Setting ED b line 1 line 2 Definition Units 44 Magrrip 1420 FLA Use amp or to select the desired level FLA for LUCMeeBL The Magnetic Overload Protection function is only adjustable from 300 to 1700 of the FLA setting in increments of 20 NOTE A Magnetic Overload Protection trip always trips the base mechanism requiring a Manual Reset of the base device regardless of the selected reset mode see 42 ResetMode page 48 NOTE The Magnetic Overload Protection trip level cannot exceed 1420 at the max FLA setting For the 32 Ampere rated Multifunction Control Unit LUCMS2B the TripLevel cannot exceed 1300 at the max FLA setting The Multifunction Control Unit automatically decreases the Magnetic Trip level as the FLA setting increases NOTE The Magnetic Overload Protection function is not available when the Power Base type is set to Starter see Base page 28 The magnetic and instantaneous short circuit protection equipment must conform with national and local safety regulations and codes I e E o Z m ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 2545 45 OLWarning Thermal Overload Warning Function Parameter Definition line 1 line 2 45_OLWarning Warning The Warning parameter enables or disables the see 2 5 4 5 1 p 52 Thermal Overload Warning
68. ese six references Load Amperes level LUCMx6BL LUCM1xBL LUCMOSBL LUCM12BL LUCM18BL LUCM32BL 20 105A 20 35A 21 25A 3A 4 5A 8A Min Minimum setting to to to to to to to lis Enabled by 206A 14A 5A 12A 218A 232A Max default Range is variable for this one reference Sets desired Full LUCMT1BL Load Amperes level NOTE Value range is set by CT_Ratio in the Config Menu Configuration Menu Min page 27 to CT_Ratio Value shown is for a CT_Ratio of 1 1 Max NOTE Press amp or to increment from the Min value to the Max value ENT Saves setting and returns to 3 Setup page 41 ESC Does not save a setting returns to 3 Setup page 41 42 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 3 2 32_TestTrip Test Thermal Overload Fault ATE pw Definition 32 TestTrip No Disables the Test Trip function Disabled by default Yes Initiates a Test Trip ENT Saves setting and returns to 3 Setup page 41 ESC Does not save a setting returns to 3 Setup page 41 NOTE The test trip orders can be only performed when the motor starter is running 2 5 3 3 33 PauseMtr Software Motor Stop A WARNING I e l o z wi Unintended motor starting The PauseMtr function should never be used in place of a Stop or Off command Equipment operation
69. function Warn Level Adjusts the Warn Level parameter see 2 5 4 5 2 p 52 ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 05 2004 Chapter 2 Operation 51 ENGLISH Multifunction Control Unit 25 451 Warning Parameter Setting line 1 line 2 Deliniten Warning On Enables the Warning parameter Enabled by default Off Disables the Warning parameter ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25 452 Warn Level NOM pass Definition Units Warn Level 8596 Use amp or Q to select the desired level The Warn Level parameter is adjustable from 10 to en 100 of the thermal capacity in increments of 1 NOTE 100 Thermal capacity is obtained at 112 FLA ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 52 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 4 6 46 _GroundFIt Ground Fault Protection A DANGER Incorrect Ground Fault Trip setting Ground fault trip levels must be set to protect wiring and motor equipment Settings must conform to national and local safety regulations and codes Disabled or high Trip Level settings will result in death serious injury or equipment
70. function Disabled by default Yes Enables the Resets all Configurable Functions to factory default settings function clearing all settings ENT Saves setting and returns to 8_Password page 76 ESC Does not save a setting returns to 8_Password page 76 78 Chapter 3 Run Start Cycle 05 2004 Multifunction Control Unit Chapter 3 Run Start Cycle The Run Start Cycle is the period of time allowed for a motor to reach its normal full load current level after starting This cycle time which is adjustable in the 410_LongStrt page 47 function is used to set the start delays for the 48_Jam 49_UnderLoad and 47_Phaselmb protection functions NOTE The 410 LongSirt page 47 function will not override the thermal overload protection If the Multifunction Control Unit reaches the limit of its thermal capacity during the Run Start Cycle the device trips on a thermal overload fault The length of the Run Start Cycle is determined by one of five methods as described below 1 The time period from when coil control power is applied to A1 A2 terminals on the Power Base until the motor load current drops below the 150 FLA current threshold with the 410 LongStrt page 47 function Trip or Warning parameter Disabled for currents that exceed 150 FLA current threshold I e l o Z m Current RunStart Current CUIU mI a aaa a Threshold 150 FLA i Time RunStart
71. g Enables or disables the Under Load Protection see 2 5 4 9 4 p 62 Warning function A warning is actived if the Multifunction Control Unit detects an Under Load Protection condition above a set Warn Level page 62 The warning is desactivated when the Under Load Protection condition rises 5 above the set level Warn Level Sets the Under Load Protection Warn Level see 2 5 4 9 5 p 62 parameter NOTE Press or to enable stepping through all the display parameters ENT Sends to parameters settings ESC Returns to 4 AdvSetup page 45 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 254 94 Trip Parameter Setting line 1 line 2 Definition Trip Off Disables the Under Load Protection Trip parameter Disabled by default On Enables the Under Load Protection Trip parameter ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 05 2004 Chapter 2 Operation 61 ENGLISH Multifunction Control Unit 25 492 TripTime Parameter Setting line 1 line 2 Definition Units TripTime 10Sec Use amp or to select the desired time Sec The Trip Time parameter is adjustab
72. g after the thermal reset timing period Equipment operation must conform with national and local safety regulations and codes Failure to follow these instructions will result in death serious injury or equipment damage Function Setting hen line 1 line 2 Definition 42 ResetMode Manual Sets the Multifunction Control Unit to trip the Power Base device if an enable fault condition is detected A Manual Reset of the Power Base is required before a restart can be made Enabled by default NOTE In Manual Reset Mode the thermal ResetTime page 50 and ResetLevel page 50 functions have no effect on Thermal Overload Reset Delay The internal thermal memory function is enabled and a fault trip may occur immediately after restart if the internal thermal capacity of the Multifunction Control Unit is exceeded Remote Ent Sets the Multifunction Control Unit for remote resetting of thermal overload 32 TestTrip page 43 410 LongStrt page 63 47 Phaselmb p 56 49 UnderLoad p 61 48 Jam p 59 communication and option module faults Upon detecting a fault the Multifunction Control Unit de energizes the contactor coil without tripping the Power Base device To reset the fault do one of the following n applications using two wire control or with 24 V auxiliary power connected to the Multifunction Control Unit press the ENT button on the keypad Multifunction Control Unit NOTE With t
73. g function Config Menu Language see 2 4 1 p 28 Selects the language used in the Multifunction Control Unit display NOTE Language type can also be selected in 34_Language page 42 LoadType Sets motor protection functions for 3 phase or 1 phase see 2 4 2 p 28 NOTE Selecting the 1 phase setting with 3 phase motors for LUCMe BL will cause an internal trip 60 indicating only 24_L2Current detected in 1 phase mode Base see CAUTION page 28 see 2 4 3 p 28 Identifies the type of Power Base in which the Multifunction Control Unit will be installed The Power Base type is for pn marked on the side of the base device NOTE This function serves as an identifier only It does not influence the protection functions settings or type of protection that the Power Base provides AuxFan see CAUTION page 29 see 2 4 4 p 29 Sets thermal protection settings for motors cooled by auxiliary fans NOTE When enabled effective thermal reset time is reduced by a factor of 4 For reset times See Appendix A Thermal Trip and Reset curves page 81 CT Ratio see CAUTION page 29 see 2 4 5 p 29 Sets current scale in Amperes for protection settings and for LUCMT1BL display values The CT Ratio is set for the current only transformers sellected for the application NOTE CT_Ratio must be set before enabling the End Config page 34 function End Config Sets initial configuration and enab
74. ge 2 5 5 5 55 CommLoss Communication Loss protection a 68 2 5 6 6 Module nur un Dee E MEER DE E Au 69 2 5 6 1 61 ID Clear Option Module Identification Number Reset 69 2 5 6 2 62 Reference Option Module References aa 70 2 5 6 3 63 Id Set Option Module Identification number 70 2 5 6 4 64 Param dec Option Module Parameter Dec setting 70 2 5 6 5 65 Param hex Option Module Parameter Hex setting 71 2 5 6 6 Parameter 1 16 Option Module Parameter setting aa 71 2 5 7 7 Staustics uc cic Kanada BA EE Adakala 73 2 5 7 1 71 TripO Historical Information Last fault 73 2 5 7 2 72 Trip1 Historical Information Second to last fault 74 2 5 7 3 73 Trip2 Historical Information Third to last fault sss 74 2 5 7 4 74_Trip3 Historical Information Fourth to last fault a 74 2 5 7 5 75_Trip4 Historical Information Fifth to last fault 75 2 5 7 6 76 Totals Historical Count Totals for Start Run and Fault Events 15 2 5 8 8 Password sena nan aan rei er Saat heatnedendd reb te ANA 76 2 5 8 1 81 Unlock Disable Password Protection aaa 77 2 5 8 2 82 Lock Enable Password Protection aaa 78 2 5 8 3 83 Rst Stats Resets the Statistics
75. hermal faults see 32 TestTrip page 43 a restart cannot occur until the thermal ResetTime page 50 and ResetLevel page 50 settings are reached The time until reset is shown in the second line of display Senda command through the network e For applications using three wire control restart the motor NOTE With thermal faults see 32 TestTrip page 43 cycling power resets the fault but not the internal thermal memory timer A fault trip may reoccur immediately after restart if the internal thermal capacity of the Multifunction Control Unit is exceeded 48 Chapter 2 Operation 05 2004 Multifunction Control Unit Function Setting line 1 line 2 Definition 42_ResetMode Auto see DANGER page 48 Sets the Multifunction Control Unit for automatic reset of a thermal overload fault Upon detecting a fault the Multifunction Control Unit de energizes the contactor coil without tripping the base device Forthermal fault the Multifunction Control Unit automatically resets the Power Base device closing the contactor coil once the thermal ResetTime page 50 and ResetLevel page 50 settings are reached the time until reset is shown in the command panel To reset 410 LongStrt page 68 47 Phaselmb page 56 49 UnderLoad page 61 48 Jam page 59 and communication faults do one of the following n applications using two wire control or with 24 V auxiliary power connected t
76. ications damage Communication ports should be used for non critical data transfers only Monitoring of contactor status and current levels are delayed by transmission time and should not be used for critical control decisions e Functions such as ShuntTrip and Pause should not be used for emergency or critical control Improper use of Communication Ports can result in death serious injury or equipment Function line 2 Submenu line 1 Definition 5 CommSetup 51 Drop see 2 5 5 1 p 66 Sets the RS 485 serial port Drop parameter The Drop parameter is defined as the configurable Modbus slave number for the external RS 485 serial port 52 Baud see 2 5 5 2 p 67 Sets the RS 485 serial port Baud rate parameter The Baud rate parameter defines the speed at which the Multifunction Control Unit can communicate with an external Modbus device 53 Parity see 2 5 5 3 p 67 Sets the asynchronous protocol parity for the external RS 485 serial port 05 2004 Chapter 2 Operation 65 T e l o Z m Multifunction Control Unit Submenu Function line 1 line 2 Definition 5_CommSetup 54_Control Enables or disables write access by remote see 2 5 5 4 p 67 configuration devices through the external RS 485 serial port If this function is disabled changes to the protection settings via the external RS 485 serial port can not be made
77. ifunction Control Unit display to show the percentage of Phase Imbalance Current measured while in the Run mode settings p 23 29 ONhours see 2 5 2 9 p 40 Sets the Multifunction Control Unit display to show the number of Total hours detected while in the Run mode settings p 23 NOTE Press or to enable stepping through all the display functions ENT Sends to functions settings ESC Returns to Main Menu page 35 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 05 2004 Chapter 2 Operation 37 I e m o z m Multifunction Control Unit 2 5 2 4 21_AvCurrent Average Three Phase Current ENGLISH Function Setting T n line 1 line 2 Definition Units 21_AvCurrent Yes Sets display to scroll Average Three Phase Amps Current or single phase current in the Run mode settings page 23 Enabled by default No Disables the display of Average Three Phase Current or single phase current in the Run mode settings page 23 ENT Saves setting and returns to 2 Display page 37 ESC Does not save a setting returns to 2 Display page 37 2522 22 ThermCap Thermal Capacity used Function Setting line 1 line 2 Definition Units 22 ThermCap No Disables the d
78. ine 2 pefinntisn Trip On Enables the Phase Imbalance Phase Loss Protection Trip parameter Enabled by default Off Disables the Phase Imbalance Phase Loss Protection Trip parameter ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25472 TripTimeStrt Parameter Setting I line 1 line 2 Definition Units TripTimeStrt 0 7Sec Use amp or to select the desired time Sec The Trip Time Start parameter is adjustable from 0 2 to 20 seconds in increments of 0 1 seconds Default setting is 0 7 second NOTE For configuration of the Run Start Cycle time see 410 LongsStrt page 47 ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 05 2004 Chapter 2 Operation 57 ENGLISH Multifunction Control Unit 25473 TripTimeRun Parameter Setting line 1 line 2 Definition Units TripTimeRun 5 0 Sec Use amp or to select the desired time Sec The Trip Time Run Mode parameter is adjustable from 0 2 to 20 seconds in increments of 0 1 seconds Default setting is 5 seconds NOTE For information on the Run Start Cycle time see 410_LongStrt page 47 ENT Saves setting and returns to 4 AdvSet
79. ing see Warnings and Faults diagnostics page 26 WarnMxxxxx run mode scroll Option Module Warning Warn GF run mode scroll Ground Fault Warning Warn Imbal run mode scroll Phase Imbalance Warning Warn IntTmp run mode scroll Multifunction Control Unit Internal Temperature Warning Warn Jam run mode scroll Jam Warning Warn LongSt run mode scroll Long Start Warning Warn OL run mode scroll Overload Warning Warn UndrLd run mode scroll Underload Current Warning 6 Mxxxxx indicates Warning Dropout or Fault code See option module instruction manual for Fault code identification 05 2004 Appendix 85 x e ES o z m ENGLISH Multifunction Control Unit Appendix C Register data format From 50 to 95 identification registers read only Hes Bit Range Unit ide m Information 50 to 63 see LULC031 communication module user s manual 64 to 69 ASCII 0 15 to0 6A LUCMx6BL Catalog Number 0 35 to 1 4 A LUCM1xBL 1 25to5A LUCMOSBL 3to 12A LUCM12BL 4 510 18A LUCM18BL 81032A LUCM32BL 0 35 to 1 05 A LUCMT1BL 70 to 73 LUCMe BL Serial reference 74 Reserved 75 0 0 1 Off On 0 Unknown Control unit 0 1 Off On 0 LUCA standard control unit 2 0 1 Off On 0 LUCB CC CD advanced control unit 3 0 1 Off On 0 Reserved
80. inputs 11 and I2 on the LUTM BL NOTE Should the Multifunction Control Unit lose control power while in the Pause mode it will return to the Pause mode when control power is reapplied 05 2004 Chapter 2 Operation 41 Multifunction Control Unit Submenu Function Definition line 1 line 2 3 Setup 34 Language Selects the Language used in the Multifunction Control Unit see 2 5 3 4 p 44 display NOTE Language type is also selected in the Config Menu Configuration Menu page 27 35 PauseMode Allows user to lockout the 33 PauseMtr function see 2 5 3 5 p 44 see 33_PauseMtr page 41 l NOTE Press or to enable stepping through all the display functions ENT Sends to functions settings ESC Returns to Main Menu page 35 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume ENGLISH 25 31 31 FLASet Full Load Amp Setting _A WARNING Incorrect FLA setting The FLA Adjustment must be set to match the Full Load Amp rating of the motor FLA sets default values for other motor protection functions Incorrect setting of the FLA function can result in injury or equipment damage Function Setting TT line 1 line 2 Dernution 31 FLASet Determined by Multifunction Control Unit reference Sets desired Full Range is fixed for th
81. ion mw WARNING Incorrect Phase Imbalance setting Phase Imbalance levels must be set to protect wiring and motor equipment Function disabled if configured for 1 phase motor loads Settings must conform to national and local safety regulations and codes Disabled or high Trip Level settings can result in death serious injury or equipment damage Function Parameter Definition line 1 line 2 47 Phaselmb Trip Enables or disables the Phase Imbalance Phase see 2 5 4 7 1 p 57 Loss Protection Trip function A trip command is initiated if the Multifunction Control Unit detects a continuous current in one phase that differs by more than a set percentage from the average current in all three phases for the set time period NOTE Fault reset method for this function depends on the reset type selected see 42 ResetMode page 48 ENGLISH TripTimeStrt Sets Phase Imbalance Phase Loss Protection see 2 5 4 7 2 p 57 Start Mode Trip Time parameter The Start Mode Trip Time parameter is defined as the amount of time in seconds during the Run Start Cycle that the set level of imbalance current is detected before initiating a phase imbalance trip see Chapter 3 Run Start Cycle page 79 TripTimeRun Sets Phase Imbalance Phase Loss Protection see 2 5 4 7 3 p 58 Run Mode Trip Time parameter The Run Mode Trip Time parameter is defined as the amount of time in seconds during the Run mode
82. ion Warning 13 Reserved Xx Multifunction Control Unit Warning provided by module 05 2004 Appendix 97 ENGLISH Multifunction Control Unit Appendix E Powersuite The software environment Powersuite version V1 40 can be used to configure and commission the control unit from a PC in a Microsoft Windows 95 98 NT4 2000 and XP environment It can be used Alone to prepare and store configuration files for the LUCM control unit on a diskette CD ROM or hard disk The control unit configuration can be edited on paper or exported to office software Connected to the ModBus port of the control unit to configure and adjust the different motor protection functions or download a configuration file from the PC to the control unit or vice versa A control panel displays the states and current values of the starter controller This fully functional instrument panel makes it possible to follow the main characteristics of the starter in real time and with a high level of user friendliness heat capacity mean value and value per phase of the motor current ground fault current 96 of phase unbalance The starter states and alarms related to the protection functions are also displayed The test controls for protection against thermal overload and over current are available on the control panel The configuration registers monitoring registers status and control registers of the control unit can be accessed and thei
83. ip command is initiated during the Run Start Cycle A trip command is initiated if the Multifunction Control Unit detects a RMS current that exceed a set TripLevel page 64 I when the Run Start Cycle page 79 has ended NOTE Fault reset method for this function depends on the reset type selected see 42 ResetMode page 48 TripTime Sets the Long Start Protection Trip Time parameter see 2 5 4 10 2 p 64 The Long Start Trip Time parameter is defined as the maximum length in seconds of the Run Start Cycle page 79 during a Long Start Fault condition I e ES o z m TripLevel Sets the Long Start Protection Trip Level parameter see 2 5 4 10 3 p 64 The Long Start Trip Level parameter is defined as the ratio of RMS current to the FLA setting that is detected as the Run Start Cycle page 79 expires before initiating a Long Start Trip Warning Enables or disables the Long Start Protection see 2 5 4 10 4 p 64 Warning function A warning is actived if the Multifunction Control Unit detects a Long Start condition above a set Warn Level page 64 before the Run Start Cycle page 79 has ended The warning is desactivated when the Run Start condition drops 5 below the set TripLevel p 64 or if the Run Start Cycle page 79 ends Warn Level Sets the Long Start Protection Warn Level see 2 5 4 10 5 p 64 parameter NOTE Press or to enable stepping through all the display parameters
84. ipLevel page 60 for the set TripTime page 60 period after the Run Start Cycle page 79 has ended NOTE Fault reset method for this function depends on the reset type selected see 42 ResetMode page 48 TripTime Sets the Jam Protection Trip Time parameter see 2 5 4 8 2 p 60 The Trip Time parameter is defined as the amount of time in seconds that a set TripLevel page 60 of RMS current is detected before initiating a Jam Trip TripLevel Sets the Jam Protection Trip Level parameter see 2 5 4 8 3 p 60 The Trip Level parameter is defined as the ratio of RMS current to the FLA setting that is detected for a set TripTime page 60 period before initiating a Jam Trip Warning Enables or disables the Jam Protection Warning see 2 5 4 8 4 p 60 function A warning will be activated if the Multifunction Control Unit detects a Jam condition above a set Warn Level page 60 The Warning deactivates itself when the Jam condition drops 596 below the set level Warn Level Sets the Jam Protection Warn Level parameter see 2 5 4 8 5 p 60 NOTE Press amp or to enable stepping through all the display parameters ENT Sends to parameters settings ESC Returns to 4 AdvSetup page 45 NOTE If no key is depressed for a period of 20 seconds while in the Run mode settings page 23 the scrolling display shall resume 254 84 Trip Parameter Setting line 1 line 2 Definition Trip Off Disables the Jam Protection
85. isplay of Thermal Capacity used in the Run mode settings page 23 Disabled by default Yes Sets display to scroll Thermal Capacity used in the Run mode settings page 23 ENT Saves setting and returns to 2 Display page 37 ESC Does not save a setting returns to 2 Display page 37 2 5 2 3 23 L1Current Current measured in L1T1 Function Setting T F line 1 line 2 Definition Units 23_L1Current No Disables the display of Current measured in Amps L1T1 in the Run mode settings page 23 Disabled by default Yes Sets display to scroll Current measured in L1T1 in the Run mode settings page 23 ENT Saves setting and returns to 2_Display page 37 ESC Does not save a setting returns to 2_Display page 37 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 2 4 24 L2Current Current measured in L2T2 Function Setting hare line 1 line 2 Definition Units 24_L2Current No Disables the display of Current measured in Amps L2T2 in the Run mode settings page 23 Disabled by default Yes Sets display to scroll Current measured in L2T2 in the Run mode settings page 23 ENT Saves setting and returns to 2 Display page 37 ESC Does not save a setting returns to 2 Display page 37 2 5 2 5 25 L3Current Current measured in L3T3 Function Setting m s line 1 line
86. ix 05 2004 Multifunction Control Unit From 700 to 705 command registers read write accessible alee Bit Range Unit D i Information 705 0 see LULCO31 communication module user s manual 1 0 1 Off On 0 Reset Statistic Counts 2 0 1 Off On 0 Reset Thermal Memory 3 15 0 1 Off On 0 Reserved iuf Bit Range Unit par da Information 2 1000 0 0 1 Off On 0 Escape Key 2 0 1 Off On 0 Up Key 2 2 0 1 Off On 0 Down Key 1000 3 0 1 Off On 0 Enter Key 1001 1006 Menu Ascii Line 1 1007 1012 Menu Ascii Line 2 icut Bit Range Unit steh 2 Information 1100 0 0 1 Off On 0 Escape Key 1 0 1 Off On 0 Up Key 2 0 1 Off On 0 Down Key 3 0 1 Off On 0 Enter Key 05 2004 Appendix 95 Multifunction Control Unit Appendix D Fault and Warning Codes D 1 Fault code summary A fault code number appears in register 451 and in the trip statistics Registers 150 180 210 240 and 270 upon an error condition per the table below NOTE Internal Multifunction Control Unit Faults are not saved in the trip statistics registers 150 etc l Code Fault condition 0 None 1 Short Circuit Trip 2 Magnetic Trip 3 Ground Fault Trip T 4 Thermal Overload Fault o 5 Long Start Fault E 6 Jam Fault 7 Phase Imbalance Fault 8 Underload Fault 9 Shunt Trip 10 Test Trip si
87. lave Number parameter is selectable from 1 to 247 Default setting is 1 Definition ENT Saves setting and returns to 5 CommSetup page 65 ESC Does not save a setting returns to 5 CommSetup page 65 66 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 5 2 52 Baud Modbus Baud Rate Function Setting m line 1 line 2 Definition Units 52 Baud 19200 bps Sets the Modbus amp Baud Rate parameter to bps 19200 bps Enabled by default 9600 Sets the Modbus Baud Rate parameter to 9600 bps 4800 Sets the Modbus Baud Rate parameter to 4800 bps 1200 Sets the Modbus Baud Rate parameter to 1200 bps ENT Saves setting and returns to 5 CommSetup page 65 ESC Does not save a setting returns to 5_CommSetup page 65 2 5 5 3 53 Parity Asynchro 2 5 5 4 5 nous Protocol Parity Function Setting line 1 line 2 Detiniion 53 Parity None Sets the Asynchronous Protocol Parity parameter to None 1 start bit 8 data bits and 1 stop bit Enabled by default Even Sets the Asynchronous Protocol Parity parameter to Even 1 start bit 8 data bits even parity and 1 stop bit ENT Saves setting and returns to 5 CommSetup page 65 ESC Does not save a setting returns to 5_CommSetup page 65 4 Control write Control Function Setting li
88. lay e 2 Display 2 Display parameters are read and write 2 oo i21 AvCument Main Menu 653 read and write During Run mode i5 3 Setup o 35 tup 78 Setup parameters are read and write 7 55 Main Menu 653 read and write 3 Setup e 3 Setup oo S1 FLASet ____ Main Menu 653 read only _ During Run mode z Wr Oo i ep 4 AdvSetup parameters are read only gt 1411p Glass a Main Menu KE read only ET 3 During Run mode gt E e 2 Commsetup 5 CommSetup parameters are read only gt AI Drop LL sss Main Menu 459 read only _ During Run mode z E e i G Mode 6_Module parameters are read only gt QOT BeIerence is Main Menu 653 read only men During Run mode E E 153 Oo i Lopes 7 Statistics parameters are read only gt LETLIBpU aa Main Menu KE read only DURS _ During Run mode h 8_Password eo i a Password 8 Password parameters are read only gt 81_Unloc If key is not touched 05 2004 Chapter 2 Operation 23 Multifunction Control Unit 2 3 Monitoring the motor 231 Run mode monitoring l When the main power contacts are closed and more than 10 of the set FLA current is detected line 1 of the display will show Start indicating the Multifunction Control Unit is waiting for the motor to complete it s start
89. le from 1 to 200 seconds in increments of 1 second Default setting is 10 seconds ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25493 TripLevel ere vie Definition Units TripLevel 50 FLA Use amp or to select the desired level FLA The Trip Level parameter is adjustable from 30 to 100 of the FLA setting in increments of 1 Default setting is 50 FLA ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25494 Warning dro pa Definition Warning Off Disables the Warning parameter Disabled by default On Enables the Warning parameter ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25 495 Warn Level p ed Definition Units Warn Level 50 FLA Use amp or to select the desired level FLA The Warn Level parameter is adjustable from 30 to 100 of the FLA setting in increments of 1 Default setting is 50 FLA ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 62 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 4 10 410_LongStrt Long Start Protection Function Parameter fem line 1 line 2 Derinition 410 LongStrt Trip Enables or disables the Long Start Protection Trip function l see 2 5 4 10 1 p 63 A tr
90. les the Main Menu see 2 4 6 p 34 page 35 NOTE Once End Config page 34 is saved the Config Menu Configuration Menu is accessed by resetting the device back to factory default settings see 84 RstToDfts page 77 NOTE Press amp or to enable stepping through all the display functions ENT Sends to functions settings 05 2004 Chapter 2 Operation 27 I e l o z m Multifunction Control Unit 2 4 1 l l l an 77 mE 242 o cA W 2 4 3 Language uni Display Language See Ns Definition Language English Sets display to English Enabled by default Francais Sets display to French Espa ol Sets display to Spanish for LUCMesBL only Deutsch Sets display to German for LUCMeeBL only Italiano Sets display to Italian for LUCM BL only ENT Saves setting and returns to Config Menu page 27 ESC Does not save a setting returns to Config Menu page 27 LoadType Motor Load Type NOTE Load Type sets the calculated average current value in the Multifunction Control Unit as follows 3 Phase Load setting Average I1 I2 13 3 1 Phase Load setting Average I1 I2 13 2 D eo Definition LoadType 3PhMotor Sets unit configuration to three phase motor protection for LUCMeBL Enabled by default only 1PhMotor Sets unit configuration for single phase motor
91. line 2 Condition Config blank First power up see Config Menu Configuration Menu page 27 Config Menu menu option see Config Menu Configuration Menu page 27 Int Trip error code Multifunction Control Unit Internal Fault see Warnings and Faults diagnostics page 26 Main Menu menu option see Main Menu page 35 see Warnings and Faults diagnostics page 26 Off blank Motor Off contactor open with no power on A1 A2 terminals Off Mxxxxx Ent to Reset Option Module Dropout 5 manual remote auto reset mode Off Mod ID Ent to Reset Option Module ID Fault manual remote auto reset mode Off Comm Ent to Reset RS 485 communication Loss Fault remote auto reset mode Off Imbal Ent to Reset Phase Imbalance Fault remote auto reset mode Off Jam Ent to Reset Jam Fault remote auto reset mode Off LongSt Ent to Reset Long Start Fault remote auto reset mode Off OL Auto xxx seconds Thermal Overload Fault auto reset mode Off OL Ent to Reset Thermal Overload Fault remote reset mode Off OL Wait xxx seconds Thermal Overload Fault remote reset mode Pause blank Motor Paused contactor open with power on A1 A2 terminals Off Test Auto xxx seconds Test Trip network or keypad auto reset mode Off Test Ent to Reset Test Trip network or keypad remote rese
92. ling Scrolling DE eno L ONE gt IAV 2 5A T T T T T Average 3 phase current i Thermal capacity 2_Display 21_AvCurrent 2_Display 22_ThermCap Line 1 Warning message OL Display Yes by default Display No by default pisy eres oy Spray y GF Imbal Jam LS I 1 UL Input 1 IntTemp 9 L 4 4 Line 2 Parameter s selected Dum ye yea dais 1_Reference 1_Reference PEN i o some AN e seconds later ae If key is not touched 4X Ex Mile fre Fault A 2 1 30 sec message 24 Chapter 2 Operation 05 2004 Multifunction Control Unit 233 Fault mode diagnostics Detected faults will either trip the base mechanism or open the power contacts depending on the fault type see 2 3 4 Warnings and Faults diagnostics page 26 and reset mode selected see 42_ResetMode page 48 e Faults that trip the base mechanism will show Tripped in the line 1 of the display and the fault type in the line 2 A Manual Reset will be required before a restart can be made Faults that open the power contacts will show Off Fault Type in line 1 of the display and Ent to Reset in line 2 Reset can be made by pressing the ENT key or sending a remote reset signal via the RS 485 communication port or by an optional module Over load and Test Trip faults will show Wait and the delay in seconds before Ent to Reset appears NOTE On the LUCMPe BL resetting Off faults will
93. ltifunction Control Unit The auxiliary power input is only required for the following functions Initial configuration and setting before installation into a Power Base Initial configuration and setting before supplying coil control power to the A1 A2 terminals Operation of remote and auto reset functions with 3 wire control Modification of settings in the Off see 2 2 p 21 Trip or Fault modes see 2 3 4 p 26 Display of fault type or statistics in the Trip and Off modes see 2 3 4 p 26 Communicating with the Multifunction Control Unit in the Trip and Off modes see 2 3 4 Operation of certain optional communication and function modules NOTE Cycling coil control power to the A1 A2 terminals without auxiliary control power will reset all Off Faults functions allowing the main contacts to close see 2 3 4 Warnings and Faults diagnostics page 26 x e E o Z m The coil control input A2 is internally connected to the auxiliary power input terminal If the polarity of the A1 A2 terminals has been reversed the Multifunction Control Unit will trip on an Int Trip 62 fault see Fault mode diagnostics page 25 for reseting of an Int Trip fault 1 3 3 2 LUCMT1BL The LUCMT1BL Multifunction Control Unit has only one 24V DC control power input accessible only by the terminals on the LUTMe BL Power Base The control power input is required for configuration and opera
94. mbalance Current 40 29 ONhRours Total HOUS ssec BA rte dr e edge duin Prax 40 3 Setup aaa a aa 41 31_FLASet Full Load Amp Setting 42 32 TestTrip Test Thermal Overload Fault 43 33 PauseMtr Software Motor Stop seen dna ee 43 34 Language Unit Display Language 44 35 PauseMode Software Motor Stop Lockout aaa 44 4 AdvSetup ope rere eee Hos eee rere 45 41 TripClass Motor Trip Class Ann adan an aan a Sebatan an Sandi aa 47 42 ResetMode Fault Reset Mode akan 48 Table of Contents 05 2004 Multifunction Control Unit Table of Contents Page 2 5 4 3 43_RstAdjust Thermal Overload Reset Delay aaa 50 2 5 4 3 1 nip 50 2 5 4 3 2 Hesetl evel in tes eeepc ete redet d Hae n tein reed es 50 2 5 4 4 44 Maglrip Magnetic Overload Protection aaa 51 2 5 4 5 45 OLWarning Thermal Overload Warning ss 51 2 5 4 5 1 WANN aios E eane ue estu sq ovd aoe cuz os cotton ya dies eues quee rete RA Re dE UV IR ER ERE CN 52 2 5 4 5 2 MWantlceVel c este et tes Baa oda E 52 2 5 4 6 46_GroundFlt Ground Fault Protection aaa 53 2 5 4 6 1 Troc tester Pp RU RU IEIUNII IM 54 2 5 4 6 2 TRIP TUM c 54 NE 2 5 4 6 3 j 54 2 2 5 4 6 4 VET toon 54 2 5 4 6 5 EIE say nn A A ada A BA an a EES 55 ME 2 5 4 7 47_Phaselmb Phase Imbalance Phase Loss Protection
95. module Mod Int Contains the total number of Option Module Internal Faults Mod Trp Contains the total number of Option Module Fault Trips detected Mod Drp Contains the total number of Option Module Fault Dropouts detected NOTE Press amp or to enable stepping through all functions ESC Returns to 7 Statistics page 73 05 2004 Chapter 2 Operation 75 x e l o z m Multifunction Control Unit 25 8 8 Password The 8 Password submenu allows Password protection that prevents unauthorized access to the Multifunction Control Unit configuration The factory default password of 0000 disables the password feature The range for the password is from 0001 to 9999 This submenu also contains the functions that resets the configurable functions and statistics information back to factory settings Submenu Function Definition line 1 line 2 8 Password 81 Unlock Disables the password protection function see 2 5 8 1 p 77 If the password function 82 Lock page 76 is enabled it must be disabled before changes to the Multifunction Control Unit settings can be made NOTE The Multifunction Control Unit display prompts you to enter the password if you try to change a setting with the password enabled Once unlocked the password feature is only temporarily disabled until one of the following events occurs The ESC key is pressed while at the Main Menu page 35 the Key
96. mulates thermal overload 11 RS 485 Comm Loss Fault dropout 12 RS 485 Comm Loss Fault tripped 13 Reserved l 14 Module Identification Fault see 61_ID Clear page 69 and see 63_Id Set page 70 15 Module missing or not power up 51 Multifunction Control Unit Internal Temperature Fault or broken sensor 52 PROA read after write FPROAault 53 PROA initialize Fault 54 MPDB Fault 55 Stack Overflow Fault 56 RAM Fault 57 ROM flash Checksum Fault 58 Hardware Watchdog Fault l 59 Current detected while Off Pause 60 I2 detected in Single Phase Mode 61 Trip Indicator not detected only with smart module 62 A2missing wiring error 63 A1 Overvoltage XX Module Internal Fault provided by module XX Module Trip Fault provided by module XX Module Drop Out Fault provided by module Appendix 05 2004 Multifunction Control Unit D 2 Warning code summary A warning code number appears in register upon a warning condition per the table below NOTE Internal Multifunction Control Unit Faults are not saved in the trip statistics registers 150 etc l Code Fault condition 0 None 1 Reserved 2 Reserved 3 Ground Fault Warning 4 Thermal Overload Warning 5 Long Start Warning 6 Jam Warning m 7 Phase Imbalance Warning a 8 Underload Fault Underload Warning m 9 Reserved 10 RS 485 Communication Loss Warning 11 Multifunction Control Unit Internal Temperature Warning 12 Module Identificat
97. n Level 626 Reserved 627 Reserved 628 1 65535 None 0 Primary For 629 1 65000 None 1 Secondary a 630 1 65000 None 1 Exter_Pass 05 2004 Appendix 93 x e ES 2 Z m Multifunction Control Unit From 650 to 690 setting registers read write accessible dana Bit Range Unit Pus i Information 650 0 0 1 Off On 1 English 1 0 1 Off On 0 Francais Must set 2 0 1 Off On 0 Espa ol one bit in 3 0 1 Off On 0 Deutsch eed 4 0 1 Off On 0 Italiano 651 0 0 1 Off On 1 IIAV Average Current 1 0 1 Off On 1 Thermal Level 2 651 2 0 1 Off On 0 IL1 Current 2 3 0 1 Off On 0 IL2 Current g 4 0 1 Off On 0 IL3 Current 5 0 1 Off On 0 IGF Current 6 0 1 Off On 0 Last Trip 7 0 1 Off On 1 Phase Imbalance 652 25 100 FLA max 25 FLA Current Setting 681 683 see LULC031 communication module user s manual 690 see LULC031 communication module user s manual From 700 to 705 command registers read write accessible Bon Bit Range Unit pm i Information 700 703 see LULC031 communication module user s manual 704 0 0 1 Off On 0 Run Forward with LUCO31 Module 0 1 Off On 0 Run Reverse with LUCO31 Module 2 0 1 Off On 0 Reserved 3 0 1 Off On 0 Reset 4 0 1 Off On 0 Reserved 5 0 1 Off On 0 Initiate Test trip 6 11 0 1 Off On 0 Reserved 12 0 1 Off On 0 Shunt Trip network 18 0 1 Off On 0 Pause Motor 14 15 Reserved 94 Append
98. nable stepping through all the display parameters ENT Sends to parameters settings ESC Returns to 4_AdvSetup page 45 mode settings page 23 the scrolling display shall resume NOTE If no key is depressed for a period of 20 seconds while in the Run 25 431 ResetTime See appendix A 3 page 83 or See appendix A 4 page 83 RU pus Definition Units ResetTime 120 Sec Use amp or to select the desired delay Sec The Reset Time parameter is adjustable from 1 to 1000 seconds in increments of 1 second ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25432 ResetLevel dg vins Definition Units ResetLevel 80 Use amp or to select the desired level The Reset Level parameter is adjustable from 35 ety to 95 of the thermal capacity in increments of 5 NOTE 100 Thermal capacity is obtained at 112 FLA ENT Saves setting and returns to 4 AdvSetup page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 Chapter 2 Operation 05 2004 Multifunction Control Unit 25 44 44 MagTrip Magnetic Overload Protection A DANGER Incorrect Magnetic Trip setting Equipment selection and settings must conform to national and local safety regulations and codes Failure to follow this instruction wil result in death serious injury or equipm
99. ne 1 line 2 Definition 54_Control 0n Enables the Write Control parameter allowing write commands Enabled by default Off Disables the Write Control parameter ENT Saves setting and returns to 5_CommSetup page 65 ESC Does not save a setting returns to 5_CommSetup page 65 05 2004 Chapter 2 Operation 67 I e l o z m ENGLISH Multifunction Control Unit 2 5 5 5 55 CommLoss Communication Loss protection Function line 1 Setting line 2 Definition 55_CommLoss Ignore Disables the Communication Loss protection parameter Enabled by default Dropout Enables the Communication Loss protection Dropout setting Upon detecting a Communication Loss protection fault the Multifunction Control Unit causes the contactor coil to de energize without tripping the Power Base mechanism To reset the fault press the ENT key on the keypad or send a reset command via the external RS 485 serial port Register 704 bit 3 Trip Enables the Communication Loss protection Trip setting Upon detecting a Communication Loss protection fault the Multifunction Control Unit causes a trip of the Power Base mechanism This requires a Manual Reset of the Power Base mechanism Warning Enables the Communication Loss protection warning setting Upon detecting a Communication Loss protection fault the Multifunction Control Unit activates
100. ng devices must be write enabled Power must be applied to set values Use password to prevent unauthorized changes Failure to follow these instructions can result in death serious injury or equipment 2 damage o z Ww Submenu Function Definition line 1 line 2 3_Setup 31_FLASet see WARNING page 42 see 2 5 3 1 p 42 Sets the thermal overload protection level for a motor The Full Load Amp Setting FLA corresponds to the maximum steady state current that a motor can withstand The FLAvalue is found on the motor name plate NOTE This function sets the default levels for all protection functions based on a percentage of Full Load current 6 FLA 32 TestTrip Initiates a Test Thermal Overload Fault see 2 5 3 2 p 43 In Manual Reset Mode the Power Base trips requiring a Manual Reset Remote and automatic reset modes can also be tested by selecting that type of reset mode see 42 ResetMode page 45 Restart of a motor after a test trip can only be made after the thermal memory timer has elapsed 120 seconds by default For thermal memory timer adjustment see 43 RstAdjust page 45 33 PauseMtr see WARNING page 43 see 2 5 3 3 p 43 Opens the main power contacts by de energizing the contactor coil while coil control power is still applied to A1 A2 terminals on the LUeBee and LUsSee de energizing the output 13 23 relays while 24V DC is still applied to
101. o the Multifunction Control Unit activate the reset button in the command panel or press the ENT button on the Multifunction Control Unit Senda command through the network For applications using three wire control restart the motor I e l o z m NOTE This function requires either the use of two wire control or the connection of 24 V auxiliary power to the Multifunction Control Unit NOTE Press amp or to enable stepping through all the display settings ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 05 2004 Chapter 2 Operation 49 Multifunction Control Unit 2 5 4 3 43 RstAdjust Thermal Overload Reset Delay E CAUTION Incorrect reset time setting The thermal reset parameter settings must allow sufficient time for the motor to cool after a thermal fault Refer to motor manufacturer s instructions before setting this parameter Failure to follow these instructions can result in injury or equipment damage ENGLISH see 2 5 4 3 1 p 50 Delay in seconds after a thermal fault Function Parameter Definition line 1 line 2 43_RstAdjust ResetTime Sets the duration of the Thermal Overload Reset ResetLevel see 2 5 4 3 2 p 50 must drop before resetting a thermal fault Sets the level to which the motor s thermal capacity NOTE Press or to e
102. on Value TEXTU line 1 line 2 Definition Units 71 TripO Typezxxxxxxx The Typezxxxxxxx Statistics Item shows the type of fault detected See Appendix B Display Words page 84 for fault types FLA xxx A The FLA xxx A Statistics Item shows setting of the Amps I 31 FLASet page 41 function in Amps Therm xxx The Therm xxx Statistics Item shows the thermal FLA capacity in of thermal capacity used 05 2004 Chapter 2 Operation 73 Multifunction Control Unit ENGLISH 2 5 7 2 7 2 5 7 3 Y 2 5 7 4 74 Trip3 Historica Function Value nu 2 line 1 line 2 Definition Units 71 TripO IAV xxx A The IAV xxx A Statistics Item shows the average Amps current in amps as measure by the Multifunction Control Unit 5 IL1 xxx A The IL1 xxx A Statistics Item shows the L1 current in Amps amps as measure by the Multifunction Control Unit 5 IL2 xxx A The IL2 xxx A Statistics Item shows the L2 current in Amps amps as measure by the Multifunction Control Unit 5 IL3 xxx A The IL3 xxx A Statistics Item shows the L3 current in Amps amps as measure by the Multifunction Control Unit 5 IGR xxx A The IGR xxx A Statistics Item shows the ground fault Amps current in amps as measure by the Multifunction Control Unit 5 NOTE Press amp or to enable stepping through all values ESC Returns to 7 Statistics page 73 5 wh
103. on handle 2 Built in LCD screen 2 lines 12 characters 3 4 button keypad 4 Auxiliary control power input 24 V DC NOTE The LUCMT1BL does not provide access to this input as it is provided for on the LUTMeBL base 5 RJ 45 external communication port RS 485 6 Sealing option to prevent removal from the Power Base The built in keypad and display can enable in Configuration and settings page 21 local configuration of alarm and protection functions in Run mode settings page 23 selected real time motor load values The external RS 485 serial communication port on the front panel can be used to connect to an IBM compatible personal computer a Pocket PC a Programmable Logic Controller door mounted dialog terminal XBT NU 400 Keypad programming principles line 1 line 1 OE Maa line 2 line 2 SubMenu Function T line 1 line 2 Setting OR i Parameter The Multifunction Control Unit includes a two line display which allows the user to step up step down in the Submenu Function and Setting levels with the four button keypad Chapter 1 General information 05 2004 Multifunction Control Unit Steps up to the previous level in the menu structure NOTE The ESC key does not save a setting Successive key strokes may be required to return to the main menu Scrolls through the various possibilities within a menu gt the va
104. pad is inactive for more than 15 seconds coil control power is applied or both coil control and auxiliary control power are removed Changes via the external Modbus RS 485 serial ports are inhibited while changing functions from the Keypad ENGLISH 82 Lock Enables the password protection function in the see 2 5 8 2 p 78 Multifunction Control Unit The default password of 0000 completely disables the password feature NOTE The password value can be changed via the external Modbus RS 485 and internal Option Module serial ports only if the current password is zero disabled 83 Rst Stats Resets all Statistics and Fault history values to 0 see 2 5 8 3 p 78 see 7_Statistics page 73 NOTE Statistics values cannot be recovered after RstStats function is enabled External programming devices can be used to save or download the Multifunction Control Unit Statistics values 76 Chapter 2 Operation 05 2004 Multifunction Control Unit Submenu Function line 1 line 2 l 8_Password 84_RstToDfts Resets Multifunction Control Unit back to factory default see 2 5 8 4 p 78 Settings Enabling this function sends user back to the Config Menu page 27 This function reset the Statistics values 0 see 83 Rst Stats page 76 NOTE Function settings can not be recovered once the 84 RstToDfts page 78 function has been enabled External programming devices can be used to save
105. r RMS current that exceed a set TripLevel page 60 for a set TripTime page 60 period after the Run Start Cycle page 79 has ended Warning page 60 parameter can be set for jam currents that exceed a set Warn Level page 60 NOTE For configuration of the Run Start Cycle time see 410 LongSirt page 47 49 UnderLoad see 2 5 4 9 p 61 Sets the Under Load Protection Trip page 61 parameter can be set for RMS currents that fall below a set TripLevel page 62 for a set TripTime page 62 period after the Run Start Cycle page 79 has ended Warning page 62 parameters can be set for Underload currents that fall below a set Warn Level page 62 NOTE For configuration of the Run Start Cycle page 79 time see 410 LongsStrt page 47 46 Chapter 2 Operation 05 2004 Multifunction Control Unit Submenu Function line 1 line 2 4_AdvSetup 410 LongStrt Sets the Long Start Protection function see 2 5 4 10 p 63 Trip page 63 parameters can be set for RMS currents that exceed a set TripLevel page 64 after a set Run Start Cycle page 79 time has ended Warning page 64 parameters can be set for Long Start currents that exceed a set Warn Level page 64 NOTE The Run Start Cycle is defined as the period of time allowed for a motor to obtain its normal full load current level after power is applied to the Al A2 terminals For more information see Run Start Cycle page 79
106. r contents are displayed The contents of the configuration registers can be modified PomerSuite Workshop Soft TeSys2 Connected Oemo Fie Ed Configuration Command Montor Link Opon Window le ole amp a ve e se ss MR const unit Stowe eu ES Time Until Reset 2 Pree os o7 a Remote Resat on Control Unit Temp C Thermal Tes Tip 9 fei es Control Unit Display serre a o5 Tom So NNENENI No Option Module tav A3 Mer Eas 94 99 oc 94 99 os os 99 oc ve LS o7 oa o7 oa o7 NO o2 95 o2 oa oz oa on or 9 on o Col Otil Power ede Cum wie oc am wie ode am Wie Static ma nz mm 94 9 og 40 P wo 40 7 wo os A 20 20 o2 95x a Pas e on os 10 ae LI Cu T Cmm Cm m Terme Cae THp Lever Phase imbalance Control Unit Faults Control Unit Wamings Option Module Warnings For Help press F1 Connected Demo Posmne A X EA EB E00 ISS SRBOR HOM Moo sna min ami 38 Ecer PNG 19 See specific documentation 98 Chapter 1 General information 05 2004 1743237 02A55 05 2004
107. rious submenus within a submenu gt The various functions within a function gt the various settings NOTE Some menu levels only include functions and settings Others have functions that can consist of several parameters with different settings Scrolls through the function settings available NOTE Default or stored function setting values are indicated by and available values are indicated by Holding down the relevant key will accelerate the incrementing decrementing of a value I e l o Z m 1 Steps down one level in the menu structure 2 Saves and stores the function settings shown in the display NOTE Once a function setting has been saved with the ENT key the sign will be replaced by the sign the setting remains visible for 2 seconds then automatically steps up one level in the menu structure on eee Menu Function Function line 1 line 1 line 1 2 Configure LL YS LLLLLLLIE Language Bon J tine s Bde 2 et ETT cri EIN EID Default setting Optional setting Menu Function D Function e line 1 line 1 line 1 2 Configure te DT LoadType A line 2 line 2 loadT e Ir 4 21PhMotor ATIL 0 gt Function Default setting Optional setting 05 2004 Chapter 1 General information 9 Multifunction Control Unit 13 Technical data 13341 In ENGLISH stallation
108. s not equipped with an operating auxiliary cooling fan the calculated thermal capacity will be incorrect Incorrect setting of the AuxFan function can result in injury or equipment damage Function Setting line 1 line 2 Definition AuxFan No Disables Auxiliary Fan Cooled function setting thermal protection levels for motors not cooled by auxiliary fans Disabled by default Yes Enables Auxiliary Fan Cooled function setting thermal protection levels for motors cooled by auxiliary fans ENT Saves setting and returns to Config Menu page 27 ESC Does not save a setting returns to Config Menu page 27 2 4 5 CT_Ratio Current Transformer Ratio A CAUTION Incorrect CT_Ratio setting The CT Ratio must be set to match the current transformer being used CT Ratio sets default values for FLA and other motor protection functions Incorrect setting of CT Ratio function can result in injury or equipment damage Function Parameter Definition line 1 line 2 CT Ratio ooo No default value gt must be set for LUCMT1BL 30 3 Sets FLA current scale for current transformers with a only see 2 4 5 1 p 30 30 3 primary current secondary current ratio see 31_FLASet page 41 30 2 Sets FLA current scale for current transformers with a see 2 4 5 2 p 30 30 2 primary current secondary current ratio see 31 FLASet page 41 30 1 Sets FLA current scale for current transformers with a see 2 4 5 3 p 30 30 1 primary
109. see 2 2 2 p 22 6_Module O 6_Module optional modules eo 61 1D Clear __ Main Menu Contai M gem ontains stored Fault and 7 Statistics eo 7 Statistics H Run informations oo RARI NE Main Menu de Allows password enabling and 8 Password eo 8 Password H module resets for 81 Unlock e a settings and statistics o 20 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 2 2 2 1 Configuration and settings Config mode first power up configuration and settings The Multifunction Control Unit must be configured before it will allow the power contacts to be closed p Language Configuration can be made on the LUCMe BL by suppling 24V DC to either the auxiliary control terminals or to coil control A1 A2 terminals on the LUeBee and LU Se Power Base Configuration can be made on the LUCMT1BL by suppling 24V DC to the control power input on the LUTM BL Power Base The LUCMT1BL and when using only coil control power to the LUTM BL Power Base A1 A2 terminals the Multifunction Control Unit goes into the Pause mode when End Config page 27 is validated The power contacts can be closed by disabling the 33 PauseMtr page 41 function see warning 33 PauseMtr Software Motor Stop page 43 The LUCMT1BL Multifunction Control Unit has no default setting for the CT Ratio configuration The CT Ratio must be set before proceeding to End Config page 27
110. settings page 23 or Config mode first power up configuration and settings page 21 or Off Ready and Pause modes subsequent power ups and settings page 22 see 2 5 2 1 p 38 Submenu Function Definition line 1 line 2 2 Display 21 AvCurrent Sets the Multifunction Control Unit display to show Average Three Phase Current while in the Run mode settings page 23 22 ThermCap see 2 5 2 2 p 38 Sets the Multifunction Control Unit display to show Thermal Capacity used while in the Run mode settings page 23 23 L1Current see 2 5 2 3 p 38 Sets the Multifunction Control Unit display to show the Current measured in L1T1 while in the Run mode settings page 23 24 L2Current see 2 5 2 4 p 39 Sets the Multifunction Control Unit display to show the Current measured in L2T2 while in the Run mode settings page 23 25 L3Current see 2 5 2 5 p 39 Sets the Multifunction Control Unit display to show the Current measured in L3T3 while in the Run mode settings page 23 26 GFCurrent see 2 5 2 6 p 39 Sets the Multifunction Control Unit display to show the Ground Fault Current measured while in the Run mode settings page 23 27 LastTrip see 2 5 2 7 p 40 Sets the Multifunction Control Unit display to show the Last Fault Type while in the Run mode settings page 23 28 Phaselmb see 2 5 2 8 p 40 Sets the Mult
111. t mode Off Test Wait xxx seconds Test Trip network or keypad remote reset mode Off UndrLd Ent to Reset Underload Current Fault remote auto reset mode Pause blank Motor Paused contactor open with power on A1 A2 terminals Ready blank Power contacts closed with no current detected Start run mode scroll Motor Starting Tripped CommLoss Comm Loss Trip manual remote auto reset mode Tripped Ground Fault Ground Fault Trip Indication manual remote auto reset mode Tripped Mxxxxx Option Module Trip Tripped Jam Jam Fault manual reset mode Tripped LngStrt Long Start Fault manual reset mode Tripped MagTrip Magnetic Fault manual remote auto reset mode Tripped Over load Thermal Overload Fault manual reset mode Tripped Phaslmb Phase Imbalance Fault manual reset mode Tripped Short Short Circuit Fault manual remote auto reset mode Tripped Shunt Shunt Trip from network manual remote auto reset mode 84 Appendix 05 2004 Multifunction Control Unit LCD Display Words line 1 line 2 Condition Tripped Test Trip Test Trip network or keypad manual reset mode Tripped UndrLoad Underload Fault manual reset mode Warn Comm run mode scroll RS 485 communication Loss Warning Warn ModID run mode scroll Option Module ID Warn
112. tion NOTE Cycling control power will reset all Off Faults see 2 3 4 Warnings and Faults diagnostics page 26 A WARNING Loss of shutdown protection Components that disconnect power such as E stop or limit switches must be connected with the coil control positive terminal A1 Failure to follow these instructions can result in death serious injury or equipment damage 05 2004 Chapter 1 General information 11 Multifunction Control Unit 134 Minimum required setup See Config Menu Configuration Menu Warnings pages 28 and 29 The Multifunction Control Unit can be set up quickly by performing the minimum operations below LUCMe BL Supply power to the auxiliary power input 24V DC or LUCMT1BL Power the Overload relay controller LUTM BL 24V DC Program the Multifunction Control Unit as follows 1 Enter the Config Menu Configuration Menu page 27 by pressing the ENT key Validate the functions that define the Multifunction Control Unit profile and then enable the End Config page 34 function to enter the Main Menu page 35 or Pause mode see 33 PauseMttr page 43 for disabling Pause mode 2 Inthe Main Menu scroll past 1 Reference page 35 and 2 Display page 35 and enter into the 3 Setup page 35 submenu 3 In the 3 Setup submenu enter into the 31 FLASet page 41 parameter Scroll through and validate the desired full load motor current value NOTE All the other functions and parameters
113. tion Mxxx indicates Warning Dropout or Fault code material for fault codes See option module instruction manual for Fault code identification Fault Code Internal Fault Type Fault Code Internal Fault Type 51 Multifunction Control Unit Internal 57 ROM flash check Temperature see 1 3 2 Operating 58 Hardware Watchdog temperatures page 10 59 Current detected while OFF 52 Asic read after write 60 L2 current detected in 1 Phase Mode 53 Asic initialize check 61 Base trip not detected 54 Coil control and Asic watchdog 62 Control wiring fault 55 Stack Overflow check 63 Control overvoltage 56 RAM check EEROM Error EE Prom checksum 26 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 4 Config Menu Configuration Menu The Config Menu Configuration Menu is the initial menu displayed by the Multifunction Control Unit as shipped from the factory It contains the configuration settings that are equipment specific These settings are not typically adjusted after initial configuration To exit the Config Menu Configuration Menu you must save the End Config function To access the Config Menu Configuration Menu after the End Config is saved the Multifunction Control Unit must be reset to default factory settings see 84 RstToDfts page 77 These settings are always viewable in the 1 Reference page 35 menu The CT Ratio function in the LUCMT1BL must be set before accessing the End Confi
114. tting never line 1 line 2 Definition 82 Lock NewPSW The Enable Password Protection function initiates the 0001 9999 lock sequence The Multifunction Control Unit displays NewPSW Use Q or to increment the first digit from 0 to 9 Press the ENT key to enter the first value and move to the second digit The same procedure is followed for the second third and fourth digits Once the fourth and last digit has been selected and the ENT key is pressed gt the Multifunction Control Unit displays shows Confirmeeee You must then reenter the four values as before ENT Upon finishing the reentry of the password value the display quickly shows Done and then returns to 8 Password page 76 ESC Does not save a setting returns to 8 Password page 76 2 5 8 3 83 Rst Stats Resets the Statistics Function Setting hare line 1 line 2 Definition 83_Rst Stats No Disables the Resets the Statistics function Disabled by default Yes Enables the Resets the Statistics function clearing all statistics ENT Saves setting and returns to 8_Password page 76 ESC Does not save a setting returns to 8_Password page 76 2 5 8 4 84 RstToDfts Resets all Configurable Functions to factory default settings Function Setting nem line 1 line 2 petintion 84 RstToDfts No Disables the Resets all Configurable Functions to factory default settings
115. up page 45 ESC Does not save a setting returns to 4 AdvSetup page 45 25474 TripLevel iron pu Definition Units TripLevel 1096IMB Use amp or Q to select the desired level IMB The Trip Level parameter is adjustable from 10 to 30 Phase imbalance in increments of 1 Default setting is 10 IMB ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 25 475 Warning jours ves Definition Warning On Enables the Warning parameter Enabled by default Off Disables the Warning parameter ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 25 47 6 Warn Level jud pou Definition Units Warn Level 10 IMB Use amp or to select the desired level IMB The Warn Level parameter is adjustable from 10 to 30 phase imbalance in increments of 1 Default setting is 10 IMB ENT Saves setting and returns to 4_AdvSetup page 45 ESC Does not save a setting returns to 4_AdvSetup page 45 58 Chapter 2 Operation 05 2004 Multifunction Control Unit 2 5 4 8 48 Jam Jam Protection Function Parameter line 1 line 2 Definition 48_Jam Trip Enables or disables the Jam Protection Trip function see 2 5 4 8 1 p 59 A trip command is initiated if the Multifunction Control Unit detects a RMS current that exceeds a set Tr