Home
Fluke 434 - Transcat
Contents
1. Fluke 430 Series Three Phase Power Quality Analyzers Pinpoint power problems faster safer and in greater detail CAT IV 600 V and CAT III 1000 V safety rating Designed to help protect you and your equipment against electrical shock and fire the Fluke 430 Series analyzers accessories and charger are all certified to meet the stringent safety standards for use in CAT IV 600 V and CAT III 1000 V environments They are the first tools of their kind to carry the CAT IV rating and therefore can be used at virtually all power connections and outlets in a low voltage power distribution system Power Quality Technical Data Va tung 1143 Up funa 114 3 Ve puna 114 5 Hz 60 03 Same 120 Sec 120 Sem 120 06 16 04 17 08 20 Quickly see the trend Auto Trend feature allows fast insight into changes over time Every displayed reading is automatically and continuously recorded without having to set thresholds or intervals and without manually starting the process Quickly view trends for voltage current frequency power harmonics or flicker on all phases and neutral Analyze the trends using the cursors and zoom tools even while background recording continues VOLTS AMPS HERTZ 0 00 13 432 412 494 648 13 Le 18 03701704 09 02 59 120U 60H236 WYE 5 000k FULL 2 eet z LEIN a dm i20U 60H 36 UVE ZO0M gt gt spear a BACK ENS0160 CURSOR ONI OFF AutoTrend automatically records all di
2. Cos of angle between fundamental voltage and current Unbalance The supply voltage unbalance is evaluated using the method of symmetrical components according to IEC61000 4 30 Flicker According to IEC 61000 4 15 Flickermeter Functional and design specification Includes 230 V 50 Hz lamp and 120 V 60 Hz lamp models Transient capture Captures waveform triggered on signal envelope Additionally triggers on dips swells interruptions and Amps level as specified by IEC61000 4 30 The inrush current begins when the Arms half cycle rises above the inrush threshold and ends when the Arms half cycle rms is equal to or below the inrush threshold minus a user selected Inrush current hysteresis value The measurement is the square root of the mean of the squared Arms half cycle values measured during the inrush duration Each half cycle interval is contiguous and non overlapping as recommended by IEC 61000 4 30 Markers indicate inrush duration Cursors allow measurement of peak Arms half cycle 6 Fluke Corporation Fluke 430 Series Three Phase Power Quality Analyzers Power Quality General Design Rugged shock proof with integrated protective holster Drip and dust proof IP51 according to IEC60529 when used in tilt stand position Shock and Vibration Shock 30 g Vibration 3 g Sinusoid Random 0 03 g Hz according to MIL PRF 28800F Class 2 Bright Full Color LCD with CCFL backlight 80cd m 115 2 x 86 4 mm 4 5 x 3 4 in 320
3. I 600 V CAT IV 300 V above 2000 m 6561 ft 12 km 39 372 ft 3 years on mainframe 1 year on included accessories IEC61000 4 30 class A EN50160 IEC 61000 4 15 IEC 61000 4 7 IEC EN61010 1 2nd edition pollution degree 2 CAN CSA C22 2 No 101 1 ANSI ISA 82 01 CAT III 1000 V CAT IV 600 V 42 Vpeak Maximum operating altitude Maximum storage altitude Warranty Accessories Included Hard carrying case with clamp holders BC430 4 current clamps i400s 5 Test leads 4 black 1 green 5 Alligator clips 4 black 1 green Battery Charger Eliminator BC430 FlukeView Software SW43W Fluke 434 only Optical Cable for USB OC4USB Fluke 434 only Color localization set WC 100 Getting Started printed User Manual CD ROM depending clamp scaling 50 Hz 60 Hz nominal frequency according to IEC 61000 4 30 3 Add clamp accuracy The advanced functions interharmonics energy transients and inrush are optional for the Fluke 433 and standard available on the Fluke 434 Fluke 430 Series Three Phase Power Quality Analyzers Fluke Corporation 7 Power Quality Optional 430 Series Accessories Fluke offers a full suite of power quality test tools to locate predict prevent and troubleshoot power problems e Handheld troubleshooters for instant analysis e Ready to use event loggers e Full Disclosure power analyzers e Power calibrators and standards backed by Fluke metrology expertise The Fluke power quality se
4. er power quality health check on one display A single push of the MONITOR button delivers a single dashboard display of rms voltage har monics flicker interruptions rapid voltage changes swells unbalance and frequency The dashboard is updated live showing compliance of each parameter to EN50160 limits or your own limits Color coded bars clearly show which parameters are inside pass or outside limits fail During a Monitor session you can easily drill down to more detail of any parameter and view and capture its trend for a report MOHI TOR Amn da0 U_ 0 03 09 A 4x E E fl Limit The System Monitor overview screen gives instant insight into whether the voltage harmonics flicker frequency and the number of dips and swells fall outside the set limits 10 0001 10 000 10 000 10 000 ALE O00 10 000 10 000 10 000 09701704 08 23 4 38 098 09701704 08 3638098 09 0 1704 065138098 09701704 08 53 38 093 09701704 0655 26 058 09701704 09 Oe 562056 09701704 0904 56 058 b O9701704 09 03 39 099 er ee aCe Ce Cee aC ee ee A m E in in Lm in in in im in 22 nl aE ae Be ae 2 ae ENSO160 99 01 04 T 12 03 1200 SoH 38 WYE SEEL NORMAL E a O era EIS BSE A detailed list is given of all events falling outside the set limits By scrolling through the event list and selecting an event the event can be analyzed in detail Extensive data analysis possibilities The Fluke 430 Se
5. f nominal voltage 5 of nominal voltage v 5 with included clamps O to 400 Arms O 1 and 1 Arms Apk using 1mV A scaling 10 A 5 CFA using 1mV A scaling 5 50 Hz nominal 0 1 of nominal frequency 60 Hz nominal 0 1 of nominal frequency Dips and swells Vrms AC DC 0 0 to100 of nominal voltage 1 of nominal voltage Arms AC DC O to 20 000 Arms 0 001 Arms to 10 Arms 1 of reading 5 counts with included clamps O to 400 Arms 0 1 Arms and 1 Arms Threshold levels Programmable in percent of nominal voltage Duration hhh mm ss mmm with half cycle cycle time resolution Q GIS g Harmonic selection n DC 1 to 50 a Inter Harmonic selection Off 1 to 49 a a Vrms Relative of O 0 to 100 0 0 1 0 1 n x 0 1 0 4 for r Absolute 0 0 to 1000 Vrms 0 1 Vrms 5 of reading 2 counts Relative f 0 O to 100 0 0 1 0 1 n x 0 1 0 4 for Yor Absolute 0 0 to 4000 mV x selected clamp scaling Watts Relative 0 0 to 100 0 nx2 Absolute depends on selected clamp 5 of reading n x 2 and voltage scaling of reading 10 counts DC voltage Relative 0 1 1 Absolute 0 0 to 1000 V 0 1 V 5 of reading 10 counts Power and Energy Watt kWh 1 mVrms x selected clamp scaling 5 of reading 5 counts 5 of reading 10 counts 5 of reading 10 counts 5 of reading 10 counts 5 of reading 10 coun
6. n for PF5 recordings Zoom Up to 12 x horizontal zoom Sampling Combination of 5 readings sec and 100 120 readings sec continuous sampling per channel depending on the parameter measured Up to 1 week with 10 min resoluton 1008 min max and avg points for each reading According ENSO160 or customer definable Measurement method Vrms Arms 10 12 cycle contiguous non overlapping intervals using 500 416 samples per cycle in accordance with IEC 61000 4 30 Measured every 10 sec in accordance with IEC61000 4 30 Vrms Arms Value is measured over 1 cycle commencing at a fundamental zero crossing and refreshed each half cycle This technique is independent for each channel in accordance with IEC 61000 4 30 Harmonics Calculated from 10 12 cycle gapless harmonic group measurements on Voltage and Amps according to IEC 61000 4 7 Watt selectable Total or Fundamental real power display Calculates average value of instantaneous power over 10 12 cycle period for each phase selectable Total or Fundamental apparent power display Calculates apparent power using Vrms x Arms value over 10 12 cycle period Total Apparent Power is root mean square of real and apparent power selectable Total of Fundamental reactive power display Calculates reactive power as root of VA squared minus Watt squared over 10 12 cycle period Capacitive and inductive load is indicated with capacitor and inductor icons Calculated Watt VA Cos DPF
7. ries provides three ways to analyze measurements Cursors and zoom tools can be used live while taking measurements or Power Quality off line on stored measurement data The stored measurements can also be transferred to a PC with FlukeView software The software s view mode allows cursors and zoom tools to be used on stored measurements Perform custom analy sis and create reports measurement data can also be exported to common spreadsheet pro grams Store up to 10 measurement datasets each dataset can contain up to 32 parameters and up to 50 screens for use in reports Aut De jes Finst Cubed Mjm storied Grea Lining the Fluka aba E Perform custom analysis and create reports with FlukeView Power Quality software Measurement data can also be exported to common spreadsheet programs Easy to use Thanks to thoughtful features like user friendly menus in local languages and setups with mini mal steps The high resolution color screen updates every 200 mS and displays waveforms and wiring diagrams color coded to industry standards Handy on screen wiring diagrams for all commonly used three phase and single phase configurations guide you through connections 3 PHASE UYE FLUKE 434 000 00 077 The full color display uses region specific industry standard color coding user selectable to correlate measurements with actual wiring Fluke 430 Series Three Phase Power Quality Analyze
8. rs Fluke Corporation 3 Input characteristics Voltage inputs Number of inputs Maximum input voltage Maximum peak voltage Input impedance Bandwidth scaling 4 3 phases neutral 1000 Vrms 6 kV 4 MQ 5 pF 9 kHz up to 100 kHz for transient display 1 1 10 1 100 1 1000 1 and variable Number of inputs Type Range 4 3 phases neutral Clamp on current transformer with mV output 1 to 400 Arms with included clamps I400S 0 1 to 3000 Arms with optional clamps 50 KQ 9 kHz 0 1 1 10 100 1000 mV A and variable 40 to 70 Hz Input impedance Bandwidth scaling Nominal frequency Sampling system 16 bit analog to digital converter on 8 channels Maximum sampling speed 200 kS s on each channel simultaneously RMS sampling 5000 samples on 10 12 cycles according IEC 61000 4 30 PLL synchronization 4096 samples on 10 12 cycles according IEC 61000 4 7 Display modes Waveform display Available in Scope and Transient mode Captures 8 waveforms simultaneously Display update rate 5 x per second Up to 10 12 times horizontal zoom Cursors Single vertical line showing min max avg reading at cursor position Shows real time phasor diagram Available in Scope and Unbalance mode Display update rate 5 x per second Matrix readings Available in Volts Amps Hertz Harmonics Power amp Energy Flicker and Unbalance mode Available in Volts Amps Hertz Dips amp Swells Harmonics Power amp Energy Flicker A
9. splayed parameters in the back ground Toggle between data and trend view and use cursors and zoom to analyze measurements without interrupting the recording 2 Fluke Corporation Power Quality Measures everything Measure true rms amp peak voltage and current frequency dips and swells transients interrup tions power and power consumption peak demand harmonics inter harmonics flicker and unbalance Volts Amps Hertz Dips amp Suells Harmonics Power amp Enersgy Flicker Unbalance Transients Inrush Currents Simple menu structure with logical function grouping gives fast access to key measurements HARMOHICS BAS 4s 3 Fr F WS 300 r Ho 279 0 00 15 aa Lh l N i th l g E al yla 3 ir dem a Bi Ta 6 ae EH50160 A c cHARH HOLD VAN HW mm lle a OM Track harmonics up to the 50th and measure and record THD in accordance with IEC61000 4 7 requirements Automatic transient display Every time an event or distortion on voltage is detected the instrument triggers and automati cally stores voltage and current waveforms on all three phases and neutral The analyzer will also trigger when a certain current value level is exceeded Up to 40 dips swells interruptions and transients can be captured this way You can see voltage transients as high as 6 kV and as fast as 5 microseconds Fluke 430 Series Three Phase Power Quality Analyzers System Monitor Multi paramet
10. t of products offers the highest level of performance and maintains the Fluke promise of rugged and reliable test tools 8 Fluke Corporation Fluke 430 Series Three Phase Power Quality Analyzers 1400s AC Current Clamp Replacement current clamp for the Fluke 430 Series It is compatible with any oscilloscope scopeMeter Test Tool or Power Quality Analyzer that accepts BNC connectors and is capable of millivolt measurements TLS430 Test Lead Set Test lead replace ment set for the 430 Series Power Quality Analyzer Set includes five test leads and five alligator clips WC100 Multi Color Wire Clips 32 wire clips in 8 colors easily snap onto test leads and current clamp cables to organize multiple leads and cables in a work area CCS430 Color coding set for Fluke 430 Series C430 Hard carrying case OC4USB Optical cable for USB BC430 Battery charger 230 V 110 V Fluke 433 UGK Upgrade kit for Fluke 433 includes FlukeView software USB cable and advanced feature upgrade Ordering information Model Fluke 433 Three Phase Power Quality Analyzer Fluke 434 Three Phase Power Quality Analyzer Fluke 433UGK Upgrade Kit for Fluke 433 Fluke Keeping your world up and running TRANSAT 35 Vantage Point Drive Rochester NY 14624 1 800 800 5001 2004 Fluke Corporation All rights reserved All copyrights are the property of their respective owners Printed in U S A 9 2004 2276752 D US N Rev A
11. ts l l JJ l l kVA 1 5 of reading 10 counts Cos DPF Oto 1 0 01 0 03 Pst 1min Pst Plt PF5 0 00 to 20 00 0 01 Within 5 of tabulated values instantenous Flicker according IEC61000 4 15 Dc Dmax and Time d t 0 0 to 100 0 for Dc and 0 1 for Dc and Dmax and 1 for Dc and Dmax and exceeds limits As described Dmax and 0 000 to 9 999s 10 ms for Time 20 ms for Time per IEC 61000 3 3 for Time Unbalance Volts 0 0 to 5 0 0 1 Current 0 0 to 20 0 1 Transient capture Volts 0 5 1 6000 Vpk 15 of cursor reading 2 5 of Vrms 200 kS s Minimum detect duration 5 ys Arms AC DC 0 000 to 20 00 kArms 0 001 to 10 Arms 1 of meas 5 counts Inrush Duration mm ss mmm between 7 5 s to 10 ms 20 ms Fnominal 50 Hz 30 m selectable sampling rate Fluke 430 Series Three Phase Power Quality Analyzers Fluke Corporation 5 Trend recording AutoTrend automatically records min max and average values over time for all readings being displayed for the 3 phases and neutral simultaneously Volts amps hertz harmonics power and energy flicker and unbalance mode Sampling Memory Recording time Zoom Sampling Memory Recording time Zoom Sampling Memory Recording time From 7 5 sec with 25 msec display resolution up to 30 min with 500 msec display resolution for Inrush measurements and up to 2 5 hour with 2 5 sec display resolutio
12. utoTrend graph Unbalance Inrush and Monitor mode Cursors single vertical line showing with min max avg reading at cursor position Bargraph Available in Harmonics and Monitor mode Eventlist Available in Dips amp Swells and Monitor mode Measurement modes Vrms Arms Vcursor Acursor Vfund Afund Hz V phase angles A phase angles Volts Amps Hertz Vrms Vpk V Crest Factor Arms Apk A Crest Factor Hz Dips and Swells Vrms Arms Captures up to 1000 events with date time duration magnitude and phase identification with programmable thresholds Harmonics DC 1 to 50 Harmonic Volts THD Volt Harmonic Amps THD Amps K Amps Harmonic Watts THD Watts K Watts Interharmonic Volts Interharmonic Amps relative to fundamental or to total rms Power and Energy Watts VA VAR Power factor Cos DPF Arms Vrms kWh kVAh KVARh peak demand interval using trend KYZ revenue meter verification via optional input Inrush Current Inrush duration Arms Vrms system Monitor Vrms Arms Harmonic Volts THD Volts Plt Vrms Arms Vneg Hz dips and swells unbalance All parameters are measured simultaneously in accordance with EN50160 Using Flagging to indicate unreliable readings according IEC61000 4 30 4 Fluke Corporation Fluke 430 Series Three Phase Power Quality Analyzers Power Quality Accuracy resolution and range Volt Amps Hertz Resolution Vrms AC DC 0 5 o
13. x 240 pixels User adjustable temperature compensated Type Size Resolution Contrast and brightness 50 screen memories on Fluke 434 25 screen memories on Fluke 433 10 data memories for storing data including recordings on Fluke 434 5 data memories for storing data including recordings on Fluke 433 2 preprogrammed 2 administrator programmable via FlukeView 2 user locations Time and date stamp for AutoTrend Transient display and SystemMonitor Screens Data Limit templates Real time clock Mechanical Size Weight Power 256 x 169 x 64 mm 10 x 6 6 x 2 5 in 2 kg 4 4 1b Line power Switchable 115 V 230 V adapter with country specific plug Rechargeable NiMH installed gt 7 hours 4 hours Adjustable time for dimmed backlight with on screen power indicator Battery power Battery operating time Battery charging time Power saving Standards Measurement methods used Power Quality Flicker Harmonics Safety Compliance Max voltage on banana input Max voltage on current BNC input Environmental Operating temperature O C to 50 C 32 F to 122 F Storage temperature 20 C to 60 C 4 F to 140 F Humidity 10 to 30 C 95 RH non condensing 50 to 86 F 95 RH non condensing 30 to 40 C 75 RH non condensing 86 to 104 F 75 RH non condensing 40 to 50 C 45 RH non condensing 104 to 122 F 45 RH non condensing 3000 m 9842 ft Derate to CAT II 1000 V CAT II