PSU-U-24V/AC-6A/8/FTA/PTC-TR-MC PSAC 08246
Contents
1. Outputs 0 41 1 63 AWG 26 14 TAMPER output cables 30cm The casing is equipped with distance from the mounting basis in order to guide the wiring system convection cooling User safety table 5 PN EN 60950 1 2004 protection class I first PN EN 60529 2002 U protection degree IP20 Insulation electric strength between the input network circuit and output circuits of the power supply I P O P 3000 V AC min between the input circuit and the PE protective circuit 1 P FG 1500 V AC min between the output circuit and the PE protective circuit O P FG 500 V AC min Insulation strength wince between the input circuit and the output or protective circuit 100 MQ 500 V DC Operation parameters table 6 Surges during operation unacceptable Direct exposure to sunlight unacceptable Vibrations and surges during transport According to PN 83 T 42106 2 Installation 2 1 Requirements AC power supply shall be mounted by the qualified installer having appropriate required and necessary for a given country permissions and qualifications for connecting operating 230V AC installations and low voltage installations The device should be mounted in closed rooms according to II environmental class with air humidity of RH 90 maximum and the scope of temperature within 10 C and 40 C table 6 The power supply should work in horizontal or vertical position Before installation is started the b
2. Pulsar PSU U 24V AC 6A 8 FTA PTC TR MC PSAC 08246 v 1 0 AC AC power supply unit EN Edition 1 dated 03 03 2010 Replaces edition KESA CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of elements and connectors of the power supply 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Procedure of installation 3 Signalling the operation of power supply module 3 1 Optical signalling 3 2 Technical output 4 Service and operation 4 1 Overload and short circuit 4 2 Maintenance 1 Technical description 1 1 General description AC AC PSAC 08246 power supply is using for supply alarm systems devices requiring AC voltage of 24 V with overall efficiency of 6A 24 V AC Basic features of the power supply e 8 outputs protected independently with fuses or PTC failure short circuit within the circuit of any of the outputs will result in burnout of the safety device insert actuation of the PTC and isolation of the circuit from power supply e regulation of the output voltage in case of installation where significant drops in voltage in effective resistance of receiver supply cables can occur it is possible to correct the value of output voltage with the help of U1 U2 jumper independently for each AUX output optical work signalling informing about the condition of outputs and or failure AW technical output informing about output failure activity of t
3. and connectors of the power supply table 1 table 2 fig 2 fig 4 oe Description of LB8 24V 27V AW elements Fx Fx x a Fx x jumper used polymer protection device selected Jumper of the AUX output voltage change independently for each output U2 U1 ca U2 jumper used voltage on AUXx U2 output U2 U1 zai U1 jumper used voltage on AUXx U1 output Table 1 Terminals and elements of LB8 24V 27V AW fuse block Jumper of the change in PTC fuse element safety E type Fx Fx x a Fx jumper used fuse element protection device selected 2 9 amp BO Oe i O AUX5 COM AUX6 COM AUX7 COM AUX8 COM COM U1 U2 e IN E E E O N N N Law y 108mm cs SE 115mm Esd E Fig 2 View of the LB8 24 27 AW fuse block Element No Fig 4 Description of power supply elements Table 2 Terminals and elements of the power supply 4 Pulsar Fig 3 View of the power supply panel 4 O4mm E Fx 5 Fx8 1 PTC fuse F Ps Fe fuse o Voltage selection U1 U2 E F41 F4 fuse PTC fuse Lia Wg WUC Fig 4 View of the power supply 1 4 Technical parameters electri
4. made and fully operational circuit of the shock protection is UNACCEPTABLE It can result in failure of devices and electric shock 4 Connect the cables of consumers to the AUXx COM terminals on LB8 24V 27V AW fuse block 5 If necessary connect device cables alarm unit controller signaller etc to technical outputs of the power supply AW output signalling the activity of the fuse output of the LB8 24V 27V AW fuse block TAMPER output signalling opening of the power supply casing 6 In case of installation where significant drops in voltage in effective resistance of receiver supply cables can occur it is possible to correct the value of output voltage with the help of U1 U2 jumper independently for each AUX output 7 Connect 230 V AC supply 8 Check optical signalling of the power supply operation LED L1 L8 diodes green should be constantly illuminated 9 Close the casing after installing and verifying the correctness of the power supply activity 3 Monitoring of the of power supply The power supply is equipped with optical signalling the status of operation Presence of voltage on power supply outputs is signalled by illumination of green LED diodes on the PCB plate of LB8 24V 27V AW fuse block Failure is signalled by red LED diode AW Condition of the power supply may be controlled remotely by AW technical output 3 1 Optical signalling e LED L1 L8 green diodes signal the feeding status on AUX1 AUX8 output
5. the producer shall select the equivalent of the faulty device due to reasons lying in the domain of the producer including production and material faults unless these faults have been filed within the warranty period point 1 and 2 4 Device falling under warranty period should be delivered to the point where it was purchased or directly to the seat of the producer 5 Warranty covers complete devices with written description of the fault on properly filled claim application form 6 When a claim shall be positively considered the Producer shall be obliged to realise warranty repairs in the shortest possible time however this period of time should not extend 14 working days from the date when the device was delivered to the producer s service point 7 Repair period of which mention has been made in point 5 may be prolonged in case of lack of technical possibilities to perform the repair and in case of device conditionally accepted to the service point as the claimant did not meet the warranty conditions 8 All service activities resulting from the warranty shall be performed solely within the service point of the producer 9 Warranty does not cover faults of the device resulting from reasons not lying within the power of the producer mechanical failures improper storage and transport usage not compliant with the user manual or the anticipated use of the device random events including atmospheric discharges power line fai
6. alance of the power supply load shall be performed During normal operation the sum of the currents consumed by the receivers cannot exceed I 6 0A 24 V AC Because the power supply was designed for continuous work it is not equipped with supply switch hence it is essential to ensure proper overload protection in the supply circuit It is also necessary to inform the user about the manner of disconnecting the power supply from the network supply usually by isolating and determining proper fuse element in the fuse box Electric installation should be performed according to binding standards and regulations 2 2 Procedure of installation 1 Before initiating the installation it is necessary to ensure that the voltage in the 230 V power circuit is disconnected 2 Mount the power supply in the selected place and guide connecting conductors 3 Connect the power cables 230 V AC with L N power supply terminals Connect the earth conductor to the clamp marked with earthing symbol The connection should be performed with 3 core cable with yellow green PE protecting conductor Power conductors should be connected to proper terminals through seal wire The circuit of the shock protection shall be performed with a particular care i e the yellow and green protection wire of the power cable shall be connected from one side to the terminal marked by the symbol of in the casing of the power supply Operation of the power supply without the properly
7. cal parameters table 3 mechanical parameters table 4 user safety table 5 operation parameters table 6 Electrical parameters table 3 Supply voltage Supply frequency S power supply power Power consumption Output voltage U1 23 0 28 0 V AC 100 load 0 load U2 25 5 31 5 V AC 100 load 0 load Voltage setting range Voltage adjustment range AUX output power 8x 0 75A 26 0 A 24 V AC max or 25 5 A 27 V AC max 8x F 1 0A fuse element safety device or PTC 1A Short circuit protection SCP failure of the fuse element safety device requires changing the fuse element insert AC 24 V circuit 8x F 1 0A or PTC 1A AC 230V circuit 1x T 3 15A Overloading protection OLP Technical outputs AW output signalling failure of one of the AUX outputs activation of the safety device TAMPER output signalling opening of the power supply casing type OC 50mA max normal status L level 0 V failure status hi Z level microswitch NC connectors closed casing 0 5A 50 V DC max Optical signalling LED diodes L1 L8 green status of AUX1 AUX8 outputs normal status illuminated failure status not illuminated LED diode Law red failure signalling of min one AUX output normal status not illuminated failure status illuminated T 3 15A 250 V F1 F8 fuse F 1A 250 Vor PTC 1A Mechanical parameters table 4 210 x 228 x 56 WxHxD with casing 215 x 233 x 66 Supply 0 63 2 50 AWG 22 10
8. he SCP used for remote control of the activity protection short circuit protection SCP overload protection OLP overheat protection of the transformer OHP metal casing colour RAL 9003 with signalling panel Information about additional elements of PSAC 08246 power supply module of the AC AC power supply in ABS casing MSC 1512 module of MSC 12V 1 5A or 24V 1A power supply exchanged voltage allowing to create a 24 V AC and 12 V DC 24 V DC supply system Information about types PSAC 04244 AC AC 24 V AC power supply with overall current efficiency of 4 A 24V PSU U 24V AC 4A 4 FTA PTC TR MC and switched output voltage of 24 0 V 27 0 V Equipped with AUX outputs condition signaling panel IP20 metal casing with signaling panel equipped with TAMPER microswitch PSACH 01244 AC AC 24 V AC power supply with overall current efficiency of 4 A 24V PSU U 24V AC 4A 1 FTA TR HC and switched output voltage of 24 0 V 27 0 V Equipped with AUX outputs condition signaling panel ABS IP65 casing equipped with TAMPER microswitch PSACH 04244 AC AC 24 V AC power supply with overall current efficiency of 4 A 24V PSU U 24V AC 4A 4 FTA PTC TR HC and switched output voltage of 24 0 V 27 0 V Equipped with AUX outputs condition signaling panel ABS IP65 casing equipped with TAMPER microswitch 1 2 Block diagram fig 1 Fig 1 Block diagram of the power supply 1 3 Description of elements
9. lure fire flooding influence of high temperatures and chemical agents improper installation and set up not compliant with principles included in the user manual 10 Statement of performing changes in construction or repairs performed outside the service point of the producer or when the serial numbers or warranty stickers on the device were anyhow damaged shall result in the loss of warranty rights 11 Responsibility of the producer towards the purchaser shall limit to the value of the device settled according to the determined wholesale price suggested by the producer from the date of purchase 12 Producer shall bear no responsibility for faults resulting from damaging improper activity or impossibility to use the device especially when the above results from non observance of recommendations and requirements included in the user manual or use of the device Pulsar K Bogusz Sp j Siedlec 150 32 744 apczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl
10. oad from the power supply output for the period of about 1 min T Loading the power supply with the current exceeding 26 0A 24 V AC 110 150 of the S power results in the failure of the F fuse in the 230 V AC circuit and or F1 F8 fuses In case of failure it is essential to exchange the fuse compliant with original 4 2 Maintenance All maintenance procedure may be performed after disconnecting the power supply from the power network The power supply unit does not require performing any special maintenance procedures however in case of significant drop of the dustiness it is only essential to remove the dust from the interior with the help of compressed air In case of changing the fuse it is essential to use substitutes compliant with the original parts recommended WEEE MARKING The used electric and electronic device may not be thrown out together with common household wastes According to WEEE directive binding within the EU in case of used electric and electronic devices separate means of utilization should be utilized GENERAL WARRANTY CONDITIONS 1 Pulsar K Bogusz Sp j producer provides two year quality warranty for the device counting from the date of sale indicated on the bill of sale 2 In case when there is no bill of sale when filing the claim three year warranty period shall be counted from the date when the device was manufactured 3 Warranty shall cover free repair or provision of functional equivalent
11. s In case of loss of voltage on the output burnout of the fuse activation of the PTC appropriate LED diode stops to be illuminated L1 for AUX1 L2 for AUX2 etc e LED AW red indicates failure of at least one AUX output number of the output is signalled by the green LED 3 2 Technical output The power supply is equipped with signalling output enabling to submit information about the failure or sabotage e AW output signalling the activity of the fuse output of the LB8 24V 27V AW fuse block AW technical output during the proper operation of LB4 24V 27V AW fuse block is connected to the mass GND whereas in case of damaging one of the fuses the output shall be disconnected from the mass This status is also signalled by the red Law diode e TAMPER output signalling opening of the power supply casing output of the potential free contact signaling the status of the power supply doors power supply closed NC power supply open NO 4 Service and operation 4 1 Overload and short circuit of the power supply output Outputs of the AUX1 AUX8 power supply are protected against short circuits with fuse element safety device inserts or PTC In case of damaging fuse element safety device it is necessary to exchange the fuse compliant with the original If PTC polymer fuses protection was chosen then automatic disconnection of the output voltage was signalled by switching off the green diode It is then necessary to disconnect the l