1. o then o Q ge N c 3 71 SPAN 95 8mm ADJUSTMENT ZERO ADJUSTMENT ORIFICE SCREW Factory Mutual T 1500 I P and E P Transducers intrinsically Safe Class Division 1 Groups A B C amp D T4 Ta 70 C Entity Non Incendive Class Division 2 Groups A B C amp D T4 Ta 70 C Dust Ignition Proof Classes Il amp Ill Division 1 Groups E F amp G T4 Ta 70 C Suitable Classes II amp Ill Division 2 Groups F amp G T4 Ta 70 C Type 4X NEMA 4X Entity Parameters V a 30 V dc E 100 mA C D uF L 0 mH Canadian Standards Association T 1500 I P Transducers Hazardous Locations Class Division 2 Groups A B C amp D Type 4X NEMA 4X I P transducer rated V 30V dc I 100mA Temp Code T4 Max ambient 70 C IN COMPLIANCE WITH STD C22 2 No 213 Intrinsically Safe Entity Hazardous Locations Class Groups A B C amp D Class Il Group E F amp G Class Ill Type 4X NEMA 4X I P transducer Entity Parameters V 90V dc ly 100mA C 0 Le 0 Intrinsically Safe when connected per Installation Instruction 010632 Temp Code T4 Max ambient 70 C www marshbellofram com 800 727 5646 ATEX intrinsically safe for Il 1 G EEx ia IIB T4 Tamb 20 to 65 C Input Parameters V ak 30V Pi 1W li 100 mA Reg 180 OHMS MA C 0 L 24mH Models are CE marked for use in the European Union and meet the EMC heavy machinery directives
2. 0 004 of nominal span per F typical 0 022 of nominal span per F maximum 0 013 of calibrated span per F typical 0 022 of calibrated span per F maximum 0 02 F zero and span effects combined 20 F to 160 F 29 to 71 C 0 F to 160 F 18 to 71 C 40 F to 200 F 40 to 93 C 15 F to 200 F 26 to 93 C Less than 0 5 of span per 1G 5 2000 Hz 3G maximum 3 axes Not measurable Less than 10 VDC drop at 20 mA Less than 12 VDC drop at 50 mA 9 VDC to 28 VDC less than 20 mA 9 VDC to 40 VDC less than 20 mA No effect 6000 Ohm minimum Less than 0 25 of span change in output 10V meter 20 1000 MHz Reference SAMA PML 33 1 1978 2 abc No effect 0 07 SCFM 2 LPM maximum 100 psig 6 9 BAR maximum Pneumatic 1 4 NPT Electrical 1 2 NPT For models with zero output capability maximum supply pressure 40 PSI 2 8 BAR above maximum output except for 0 100 PSI and 0 120 PSI models that have a maximum supply pressure of 130 PSI 9 BAR amp 140 psi 9 7 BAR respectively Bellofram specifies the use of instrument quality air clean dry oil free for all transducers Transducers should be used within the following conditions Dew Point lt 35 F 2 C indoor Oil Content lt 1PPM Particles lt 3um The use of filters in the supply air system is highly recommended Contact us for information on our filters and filter regulators www marshbellofram com 800 727 5646 T
3. A Technical Construction 10 50mA gt gt e T S A File Serial 107 was written and Certificate of Conformity issued by a Competent Body m LI 042 1 630 961 139 000 852 FilterNote z Bellofram specifies the use of instrument quality air Type 1000 Options and Accessories clean dry oil free for all transducers The use of Part Number filters in the supply air system is highly recommend Explosion Proof Mounting Kit 971 079 000 ed Contact us for information on our filters Explosion Proof Panel Mounting Kit gn479900 ani ditar TSpUARIO RS DIN Rail Kit 010 115 000 For output pressures less than 3 PSI 0 2 BAR or Hirschman Connector Kit 3 prong 971 126 000 greater than 30 PSI 21 BAR the Type 1000 transducer Filer Kit b meron 010 139 000 can be coupled to Bellofram Type 75 pneumatic relay 0 tG oane eede eane D Consult Applications Engineers for further information utput bauges puon le las Igits Decome l l l Dielectric Strength Testing Option 12 ie last 3 digits become 012 bi M icu di ipid d NEMA 4X Type Enclosure Option Option 4 ie last 3 digits become 004 o NEA 4 ong f 60 MARSH BELLOFRAM gt gt 800 7275646 9 www marshbellofram com Group of Companies Type 1000 Explosion Proof Dimensional Drawing 82 6 3 25 11 9 0 47 TERMINAL BLOCK s NO 1 POSITIVE NO 2 NEGATIVE f GROUND 180 2 7 09 I P TRANSDUCER T REMOVABLE ORIFICE x ELECTRICA
4. For output pressures less than 3 psi or greater than 30 psi the Type 1000 transducer can be coupled to Bellofram Type 75 pneumatic relay Consult application engineers for further information m M MARSH BELLOFRAM 61 Group of Companies www marshbellofram com 800 7275646 D 5 o Q c e 62 Type 1001 I P amp E P Transducers The Type 1001 is a patented family of electro pneumatic instruments that is used to reduce a supply pressure to a regulated output pressure which is directly proportional to a two wire current or three wire voltage input This design incorporates closed loop sensing of the output pressure to achieve excellent accuracy and vibra tion stability It also features a unique damping circuit which can be adjusted to prevent over shoot and actuator hunting Model selection includes General Purpose NEMA 1 Rainproof NEMA 3R and Watertight Corrosion Resistant NEMA 4X NEMA 4X models are also explosion proof and all models are intrinsically safe e 0 1 accuracy typical e Closed loop pressure feedback control minimizes effects of vibration temperature supply pressure and mounting angle e Built in volume booster provides flows up to 12 SCFM e Easy access zero and span adjustment e Damping pot prevents over shoot and hunting e Low air consumption e Mounts at any angle NEMA 3R limited e Compact and lightweight e Virtually no sensitivity to supply pres
5. The Bellofram T 1500 Transducers were tested and found to comply with Electromagnetic Compatibility Directive effective January 1 1996 The relevant EMC specifications tested were the following EN 50081 1 C 1992 and EN 50082 1 1992 A Technical Construction File Serial 107 was written and Certificate of Conformity issued by a Competent Body Ex MARSH BELLOFRAM 71 Group of Companies D 5 o Q c e 72 Type 2000 I P amp E P Transducers The Marsh Bellofram Type 2000 is a robust electronic instrument that regulates an incom ing supply pressure down to a precise output pressure which is directly proportional to an electrical control signal The secret to the Type 2000 s precise reliable performance under a variety of demanding environmental conditions is a patented piezo ceramic actuator with many industry wide firsts The Type 2000 has been designed to meet the electro pneumatic needs of the world Field selectable inputs and direct reverse split ranging Multiple input output mounting configurations Precise reliable performance under extreme conditions of temperature vibration orienta tion supply pressure changes supply voltage changes RFI EMI humid oil laden media and corrosive surroundings The Type 2000 s precisely regulated pneumatic output can be used to operate Valve Actuators Louver and Damper Actuators Valve Positioners Relays Clutches and
6. Certificate of Conformity issued by a Competent Body www marshbellofram com Type 1001 Exhaust Capacity Type 1001 Output Pressure Droop 10 0 69 10 0 69 0 62 co I Ls SUPPLY 100 psi 6 9 BAR spon ae R p E IUU psi 9 7 048 E amp z SUPPLY 100 psi 6 9 BAR SET POINT 9 psi 0 6 BAR e on CLl 3 psi z 5 035 L AT T d 4j Eana a 2 ee ee ee E E on ee ae ee LLL To o o TT So To To 1 0 07 Pie SETPOINT 9 psi 0 6 BAR g o SUPPLY 20 psi 1 4 BAR SCFM 0 2 3 4 5 6 SCFM 0 12 4 6 8 10 12 14 16 LPM 0 28 57 85 113 142 170 LPM 0 57 113 170 221 283 340 397 453 Reverse Flow FonwanD Flow SCFM pe 1001 Specifications Accuracy per ISA 51 1 Hysteresis Dead Band Repeatability Ambient Temperature Effect Span Temperature Effect Operating Temperature Range Buna N elastomers Viton elastomers Storage Temperature Range Buna N elastomers Viton elastomers Vibration Effect Mounting Position Effect Loop Load I P Transducer Supply Voltage E P Transducer Intrinsically Safe Nonincendive General Purpose Supply Voltage Effect Signal Impedance E P Transducer RFI EMI Effect NEMA 4X Supply Pressure Sensitivity Air Consumption Supply Pressure Port Sizes 0 10 of output span typical 0 25 of output span maximum Guaranteed 0 01 of output span typical 0 10 of output span maximum No effect 0 01 of output span typical 0 10 of output span maximum
7. com Direct Reverse Acting Direct Acting transducers regulate to their minimum output when supplied with minimum input maximum out with maximum in Reverse Acting transducers regulate to their maximum output at minimum input Easy Access Top Cover 1 Isolated electronics 2 Calibration adjustments 3 Configuration switches 4 Switch information on inside of cover Mounting Options 1 In Line 2 Direct Holes on left rear and bottom faces 3 Bracket Mounting options Panel Pipe Valve DIN Rail Integral Booster Flows up to 21 scfm for quick system response 1 8 NPT on all models Not shown rear face Factory Mutual T 2000 I P amp E P Transducers Explosion Proof Intrinsically Safe Model Explosion Proof Class Division 1 Groups A B C amp D T6 Ta 60 C Dust Ignition Proof Classes II amp Ill Division 1 Groups E F amp G T6 Ta 60 C Type 4X NEMA 4X IP66 Intrinsically Safe Classes Il amp Ill Division 1 Groups A B C D E F amp G T4 Ta 60 C Entity Type 4X NEMA 4X IP66 Non Incendive Class Division 2 Groups A B C amp D T4 Ta 60 C Suitable Class Il Division 2 Groups F amp G T4 Ta 60 C Suitable Class Ill Division 2 T4 Ta 60 C Type 4X IP66 Entity Parameters Input Option b 42 V 30V I 200 mA P 1W C 0 L 0 Input Option b 01 05 11 15 or 19 V 30 V Ip 100 mA P 0
8. ressure Gauge Kit 010 138 000 M Manifold Mount 15 PSIG 1 BAR Agency Approval Pressure Gauge Kit F FM CSA 30 PSIG 2 1 BAR 010 138 001 C ATEX S Unit Only E G Certified to CSA Standards Pressure Gauge Kit 010 138 002 Electrical Input 60 PSIG 4 1 BAR 42 4 20 mA Pressure Gauge Kit 160 PSIG 11 BAR LU MS 15 1 5 V 19 1 9 V 1 10 V Type 2000 Notes 01 0 10 V Enclosure Mode Availability S E D Direct Acting R Reverse Acting i UE bs Mode Electrical Port M Yes Yes F Full Range H Yes No H Split Range High T Yes No Pneumatic Output 3 Bottom O Ring Ports 005 0 5 PSIG 0 0 3 BAR E Enclosure and A 015 0 15 PSIG 0 1 0 BAR N Electrical port required D 315 3 15 PSIG 0 2 1 0 BAR 5 Not Agency Approved S 117 1 17 PSIG 0 07 1 2 BAR ponia cdd n pend F C G E 030 0 30 PSIG 0 2 1 BAR 100 PSIG enu AUI rd FM CSA ATEX Gas 630 6 30 PSIG 0 4 2 1 BAR nins ntrinsic 327 3 27 PSIG 0 2 1 9 BAR S Safety Yes Yes No 060 0 60 PSIG 0 4 1 BAR Enclosure Exnlosi E Er nd Yes No Yes 100 0 100 PSIG 0 6 9 BAR Maximum Supply for ii these regulators is 120 0 120 PSIG 0 8 3 BAR 140 PSIG Special Terminal Block I P Transducer E P Transducer OO None S N C Signal Signal Power Supply Signal Common Connections and Switch Positions Switch 1 PSIG BAR 2 3 4 5 6 psig BAR 7 8 9 ia Ws 0 15 0 1 0 3 15 0 2 1 0 1 17 0 07 1 2 Voltage n uia ON 0 30 0 2 1 aoe Salon Input Split Low oo oe PEVE Ful
9. 0 PSIG 7 BAR 0 15 of span per 1 5 PSIG 6 1 BAR lt 1 0 of span lt 0 5 of span lt 1 0 of span 12 SCFM 339 SLPM 7 SCFM 336 SLPM 0 1 SCFM 2 8 SLPM 1 4 NPT and 1 2 NPT 2 1 8 X 2 1 8 X 4 54 X 54 X 101 2 1 Ib 0 95 kg Type 1000 Extended Range 5 PSIG 0 4 BAR above max output to 150 PSIG 10 4 BAR 100 PSIG 7 BAR for 2 60 PSIG 0 1 4 1 BAR models 0 004 of span per 1 0 PSIG 0 07 BAR 2 096 of span 0 596 of span 1 096 of span 24 SCFM 677 SLPM 150 PSIG 10 4 BAR Supply 2 SCFM 56 5 SLPM 0 07 SCFM 2 0 SLPM 1 4 NPT and 1 2 NPT 2 8 X 2 1 8 X 4 54 X 54 X 101 2 1 Ib 0 95 kg 4110 32 UNF 2A X 38 DP 2 MOUNTING HOLES 2 LEADS 18 GA WIRE 18 LONG EA 1 BLACK 1 WHITE ALTERNATE OUTPUT GAUGE PORT www marshbellofram com 800 7275646 MOUNTING BRACKET 25 1 4 18 NPT 4 PLACES 1 2 14 NPT 30 2 1 19 SIGNAE ALTERNATE OUTPUT GAUGE PORT Type 1000 Explosion Proof 3 PSIG 0 2 BAR above max output to 100 PSIG 7 BAR t 0 15 of span per f 1 5 PSIG 0 1 BAR 1 096 of span 0 596 of span 1 096 of span 12 SCFM 339 SLPM 2 SCFM 56 5 SLPM X 0 1 SCFM 2 8 SLPM f 1 4 NPT and 1 2 NPT 6 13 32 X 5 15 16 X 7 9 16 163 X 151 X 192 5 2 Ib 2 4 kg ELZ To Ee 8 03 14 The Type 1000 has long been a standard in the I P amp E P industry With a
10. 00 uses a unique temperature compensated piezo resistive sensor suitable for gauge pressure measurement of non corrosive liquids and gases The sensor has excellent dynamic response and is virtually insensitive to mounting orientation and ordinary industrial vibration Mounting holes on the transmitter housing are arranged to permit direct pipe 2 mounting for minimum installed cost Type 5000 oe 5000 Functional Diagram INPUTS psig BAR 0 15 0 1 0 4 20 mA o 3 15 0 2 1 0 TYPE 5000 or 10 30 VDC 5 3 27 0 2 1 9 P I 10 50 mA T z 6 30 0 4 2 1 TRANSDUCER 5 0 100 0 6 9 2 Display Recorder n Computer Controller Approval Notes TYPE 5000 Max Load Resistance VS Supply Voltage 4 20 mA Output RI 50 ohms volt Factory Mutual 10 50 mA Output RI 20 ohms volt T 5000 P I Transducers NEMA 4X Explosion Proof Class Division 1 Groups B C amp D T6 APPROVED 2500 Dust Ignition Proof Classes Il amp Ill Division 1 Groups E F amp G T6 Type 4X NEMA 4X Canadian Standards Association e 2000 T 5000 P I Transducers Hazardous Locations Class Groups B C amp D Class Il Group E F amp G Class Ill Encl 4 NEMA 4 lt P I transmitter rated output 4 20mA dc or 10 50mA dc power supply 30V z dc max 5 1500 E The Bellofram T 5000 Transducers were tested and found to comply with a Electromagnetic Compatibility Directive effective January 1 1996 The rel evant E
11. 1 4 NPT 1 4 BSPT 1 4 BSPP on BRWN oon hh WN WN Input Signal 4 20 mA DC 0 5 VDC 1 9 VDC 1 10 VDC 0 10 VDC 1 5 VDC Output Pressure 3 15 PSIG 0 2 1 0 BAR 3 27 PSIG 0 2 1 9 BAR 6 30 PSIG 0 4 2 1 BAR 0 15 PSIG 0 1 0 BAR 0 30 PSIG 0 2 1 BAR 0 60 PSIG 0 4 1 BAR 0 120 PSIG 0 8 3 BAR Electrical Connection 1 2 NPT 1 4 NPT Ports Only Terminal Block Indoor Use General Purpose Only Hirschmann Connection DIN 43 650 A 1 2 BSPT Conduit 1 4 BSPT or BSPP Ports Only Elastomer Nitrile Fluorocarbon Agency Approvals and Certifications 0 FM CSA and ATEX Intrinsically Safe 1 None General Purpose Only 0 L1 INOTE Individual regulators FRs filters and lubricators come complete with bracket FRL assemblies come complete with all bracket connectors 68 MARSH BELLOFRAM Group of Companies 800 727 5646 www marshbellofram com LER Lele VET TicelleMe late PETI A G Type 1500 Dimensions Principle of Operation Number of Length A Length B The T 1500 manifold assembly allows multiple Transducers T 1500 Transducers to be mounted in parallel 757 6 83 This minimizes the number of individual supply 3 192 3 mm 173 5 mm air lines required Manifolds are available to hold three five or ten units Each manifold 5 10 75 10 01 comes with check valves so that a unit can be 273 1 mm 254 3 mm pul
12. 75 W C 0 L 0 Special Conditions of Use The T 2000 Non ncendive not for use with natural gas or other non inert gases as a process medium T 2000 E P or I P Transducers Intrinsically Safe Model Intrinsically Safe Classes Il amp Ill Division 1 Groups A B C D E F amp G T4 Ta 60 C Entity Non Incendive Class Division 2 Groups A B C amp D T4 Ta 60 C Suitable Class Il Division 2 Groups F amp G T4 Ta 60 C Suitable Class Ill Division 2 T4 Ta 60 C Type 4X NEMA 4X Entity Parameters When Electrical Input Option c 42 VMax 30 V IMax 200 mA PMax 1 W C 0 L 0 When Electrical Input Option c 05 15 19 11 or 01 V 30V 1 100 mA P 0 75 W C 0 L 0 T 2000 E P or I P Transducers Intrinsically Safe with Terminal Block Model Intrinsically Safe Class Division 1 Groups A B C amp D T4 Ta 60 C Entity Non Incendive Class Division 2 Groups A B C amp D T4 Ta 60 C Entity Parameters When Electrical Input Option c 42 V 30V 1 200 mA P 1W C 20 L 0 When Electrical Input Option c 05 15 19 11 or O1 V 30 V 1 100 mA P 0 75 W C 7 0 L 0 Canadian Standards Association T 2000 I P amp E P Transducers Hazardous Locations Class Division 1 Groups A B C amp D Class Il Groups E F amp G Class Ill www marshbellofram com 800 727 5646 Split Ranging High or Low The Type 2000 can be configured to regu
13. Brakes Controllers Air Cylinders Industry Applications Include e Chemical and Petrochemical Industries e Petroleum Production e Pipeline Transmission e Electric Utilities e Water and Wastewater Systems e Pulp and Paper e Textiles e Semiconductor Industry e Food and Beverage e Environmental Control Systems e Construction Equipment e Agricultural Equipment e Machine Tool e Material Handling e Automotive Testing and Assembly e Medical Equipment MARSH BELLOFRAM Group of Companies le of O eration The Type 2000 I P and E P transducers utilize closed loop pressure feedback control for preci sion pressure output and minimized effects of temperature supply pressure changes supply voltage changes and mounting angle Supply pressure is reduced by the supply valve to provide an output pressure which is internally routed to a precision temperature compensated piezo resistive pressure sensor Supply pressure is also routed to an externally removable orifice which provides a reduced pilot pressure to a chamber containing a servo diaphragm and nozzle Pilot pressure is controlled by modulating the gap between the face of a nozzle and an adjacent piezo ceramic actuator which is part of a unique patented mechanism The piezo ceramic actuator serves as a control link between electrical input and pressure output as follows e The input current I P or voltage E P signal is conditioned to provide a no
14. I P E P amp P I Transducers Type 1000 Type 1000EX Type 1000HR Type 1000 Hazardous Use Type 1001 Type 1001 Nema 3R Type 1001 Nema 4X Type 1500 Type 1500 Zero Based Type 2000 Type 2000 Hazardous Use Type 5000 MARSH BELLOFRAM Group of Companies Transducers x j 3 4 gt sJ npsueilL 58 Type 1000 I P amp E P Transducers The Type 1000 Transducer is an electro pneu matic device that reduces a supply pressure to a regulated output pressure directly proportional to an electrical input signal The Type 1000 accepts a wide range of supply pressures ranging from a minimum of 3 psig 0 2 BAR above the maximum output up to 100 PSIG 6 9 BAR An integral pneumatic volume booster is included in the design to provide high flow capacity up to 12 SCFM 339 SLPM Model selections include general purpose NEMA 4X Type extended range high relief intrinsically safe and explosion proof Applications The Type 1000 Transducer converts an electri cal signal to a pneumatic output which can be used to operate the following e Valve actuators Damper and louver actuators e Valve positioners Controllers Relays Air cylinders Clutches and brakes Used in Liquid gas and slurry processing instrumen tation HVAC systems Paper handling controls Textile processing systems Energy management systems Petrochemical processing systems St
15. Intrinsically Safe when installed Two sets of Entity Parameters may be used in the installation of this product Entity Parameters I P V 30VI 200mA P 1 0W C OmF L OmH E P Vua 30V I 100mA P 0 75W C OmF L OmH ATEX EUROPEAN MODEL T 2000 I P amp E P Transducers INTRINSIC SAFETY I 1 G EEx ia IIC T4 20 lt Ta lt 60 EN 50014 1997 A2 EN 50020 1994 EN 500284 1999 ENTELA T 2000 I P Transducers Explosion Proof Class Division Groups C and D T3 Exia IIB Ci 0 Li 0 24VDC 25mA Note Meets the requirements for CSA Class Div 1 Group D media gas Natural Gas Use Also includes factory conduit seal EN 50081 1 Residential commercial amp light industry EN 50082 2 Heavy Industrial Certified to CSA C22 2 No 30 14 157 1010 The Bellofram T 2000 Transducers were tested and found to comply with Electromagnetic Compatibility Directive effective January 1 1996 The relevant EMC specifications tested were the following EN 50081 1 1992 and EN 50082 1 1992 A Technical Construction File Serial 107 was written and Certificate of Conformity issued by a Competent Body MARSH BELLOFRAM 73 Group of Companies Type 2000 Specifications The secret to the Type 2000 s 0 1 of full scale output typical 0 25 guaranteed includes effects of precise reliable performance Accuracy hysteresis dead band and repeatability Electrical under a variety of demanding biis Syitchesclectable env
16. L 1 4 18 TAPERED IN ADAPTER 1 4 18 TAPERED o SESSIONE bee cei ey IN x5 ELI A xxm WW PNEUMATIC Hmm au 254 ea a 1 00 FLAME ARRESTOR 150 9 95 2 16 7 5 94 3 75 66 Optional Mounting Bracket amp Hardware Optional Mounting Hardware Order kit 201 971 079 000 69 9 Order Kit 201 971 078 000 53 8 aa ara 25 8 3 DIA Drawings and dimensions i 328 4 holes are for reference only o 1 69 o O 5 a 1 4 Thick CDS 4 25 8 3 DIA S 328 4 holes F 228 6 TYP 9 0 oe 1000 Hazardous Location Use Ordering Information Output Impedance Agency Approvals Input BAR PSIG Part Number Nominal See notes Type 1000 Explosion Proof 4 20mA 0 2 1 0 3 15 961 098 000 180 2 Explosion Proof Factory Mutual 0 2 1 0 3 15 961 098 100 180 2 CSA Explosion Proof 1 9v 20 100 3 15 961 142 000 985 Q Explosion Proof Factory Mutual Type 1000 Intrinsically Safe 0 2 1 0 3 15 961 099 000 180 Q Intrinsically Safe Factory Mutual 0 2 1 9 3 27 961 100 000 220 Q Intrinsically Safe Factory Mutual 0 2 1 0 3 15 961 105 000 180 2 Intrinsically Safe CSA p 4 20mA 0 2 1 9 3 27 961 106 000 220 Q Intrinsically Safe CSA f 0 4 2 1 6 30 961 101 000 220 Q Intrinsically Safe Factory Mutual s 1 0 0 2 15 3 961 175 000 180 Q Intrinsically Safe Factory Mutual 1 9 0 2 21 3 961 176 000 220 Q Intrinsically Safe Factory Mutual y 2 1 0 4 30 6 961 177 000 220 Q Intrinsically Safe Factory Mutual
17. MA PMC 33 1 2 abc 12 30 VDC Less than 0 005 per volt change at the input terminals within specified power supply limits Multi turn Zero and Span potentiometers with 25 min adjustment Via test jacks within enclosure without disturbing field wiring 1 4 18 NPT female pressure input 1 2 14 NPT female electrical output Suitable bracket or optional 1 4 20 U bolt pipe mounting kit P N 971 109 000 Epoxy coated aluminum body and cover 1 7 Ibs 0 8 kg 1 5 Minimum to remove Bonnet 1 4 14 NPT Electrical Port Type 5000 Ordering Information oR WN 1 Input 0 15 PSIG 0 1 0 BAR 3 15 PSIG 0 2 1 0 BAR 3 27 PSIG 0 2 1 9 BAR 6 30 PSIG 0 4 2 1 BAR 0 2 1 0 BAR 3 15 PSIG 0 100 PSIG 0 6 9 BAR Output 4 20 mA 10 50 mA Agency approval 1 X P FM CSA Options 000 None 001 Pipe Clamp Mounting Kit 800 727 5646 2 www marshbellofram com
18. MC specifications tested were the following EN 50081 1 1992 and 1000 EN 50082 1 1992 A Technical Construction File Serial 107 was written and Certificate of Conformity issued by a Competent Body 500 200 10 15 20 20 30 35 Supply VOLTAGE vs voLTs www marshbellofram com 800 7275646 __ SMASH BELLOFRAM 77 Group of Companies Type 5000 Dimensions 8 64 0 34 4 places Ly VJ 35 6 1 8 r 1 mm inches 1 4 18 NPT Pressure Port 1 59 2 places O Specifications Output Signal Output Protections Accuracy includes nonlinearity hysteresis and non repeatability Overpressure Allowable Loads Response Time Temperature Range Operating Temperature Effect RFI Effect Power Supply Power Supply Effect 3 Calibration Adjustments In Process Output Monitoring Connections Mounting Finish j Weight 78 MARSH BELLOFRAM Group of Companies 0 15 PSIG 0 1 0 BAR 3 15 PSIG 0 2 1 0 BAR 3 27 PSIG 0 2 1 9 BAR 6 30 PSIG 0 4 2 1 BAR 0 2 1 0 BAR 3 15 PSIG 0 100 PSIG 0 6 9 BAR 4 20 mA DC 2 wire 10 50 mA DC 2 wire Reverse polarity protected 0 1 span typical 0 25 span max 45 PSIG 3 1 BAR without calibration shift 60 PSIG 4 1 BAR without failure See Graph Less than 10 msec for step change to 99 R 40 F to 180 F 40 C to 82 C Zero Less than 0 01 R F Span Less than 0 01 R F Less than 1 R at 10V meter per SA
19. View MOUNTING BRACKET SUPPLIED 8 32 UNC 2B X 31 7 9mm LONG 4 SCREWS SUPPLIED 0 213 5 4mm 2 HOLES BOTTOM VIEW www marshbellofram com 800 7275646 Side View Lom COVER REMOVABLE ORIFICE 1 43 OUTPUT 36 3 Side View Vertical Mount Only NEMA 3R TAMPER RESISTANT SCREWS SEALING WASHER REMOVABLE METAL COVER SEALING GASKET 3 85 MAX 98 o then o Q gt ge N SIDE VIEW NEMA 3R Vertical Mount Only Top View ALTERNATE BRACKET POSITION OPEN DOOR AS SHOWN FOR ACCESS TO ZERO AND SPAN ADJUSTMENT SCREWS SEE WIRING TERMINATION TABLE PAGE 66 MARSH BELLOFRAM 65 Group of Companies Side Views iri Termination NO 10 32 UNF 2B PWB Terminal Block P Transducer X 28 7 1 mm DEEP 2 HOLES DIRECT MOUNTING Position 3 Positive 7 Position 2 mE No Connection Position 1 Negative 2 12 SQ 53 8 BONNET 1 4 18 NPT IN OUT PORTS lO 254 S 1 2 14 EXPLOSION PROOF PIPE TAP 566 ELECTRICAL PORT sJ npsue ilL Bottom View SEE WIRING TERMINATION TABLE TOP VIEW 999 66 MARSH BELLOFRAM se007225646 o Www marshbellofram com Group of Companies E P Transducer Supply Common Signal REMOVABLE ORIFICE Type 1500 I P amp E P Transducers Type 1500 Description The T 1500 is a new series of electro pneumatic transducers that convert an
20. andard Features Low Cost Built in Volume Booster Small Size Field Reversible Low Air Consumption Mounts at Any Angle Convenient External Span amp Zero Adjusts Except for Explosion Proof Models Light Weight Wide Supply Pressure Range Low Supply Pressure Sensitivity Principle of Operation The Type 1000 Transducer is a force balance device in which a coil is suspended in the field of a magnet by a flexure Current flowing through the coil generates axial movement of the coil and flexure The flexure moves against the end of a nozzle and creates a back pressure in the nozzle by restricting air flow through it This back pressure acts as a pilot pressure to an integral booster relay Consequently as the input signal increases or decreases for reverse acting output pressure increases proportional ly Zero and span are calibrated by turning eas ily accessible adjusting screws on the front face of the unit The zero adjusting screw causes the nozzle to move relative to the flexure The span adjusting screw is a potentiometer that limits the current through the coil A thermistor circuit in series with the coil provides temperature compensation The 4 20 mA input 3 15 PSIG output model can be recalibrated to provide 3 9 PSIG or 9 15 PSIG output for split ranging applications The Type 1000 transducers can be pipe panel or bracket mounted in any position Positions other than vertical will re
21. built in booster the T 1000 provides a flow capacity up to 12 SCFM making it a versatile transducer for many applications X MARSH BELLOFRAM 59 Group of Companies oe 1000 General Purpose Ordering Information Output Impedance Magnet Input BAR PSIG Part Number Nominal Assembly 0 2 0 6 3 9 961 072 000 90 Q d 0 6 1 0 915 961 073 000 90 O Ko M 0 2 1 0 3 15 961 070 000 180 Q ee mospheric 4 20mA 0 2 1 9 3 27 961 074 000 220 Q Pressure 0 4 2 1 6 30 961 075 000 220 Q Bis 0 07 1 2 1 17 961 116 000 250 Q Re SEX 0 210 315 961089000 1202 _ 2 0 2 1 0 3 15 961 076 000 10 2 10 50mA 0 2 1 9 3 27 961 077 000 85 Q Exhaust 0 4 2 1 6 30 961 078 000 85 Q Yale 0 2 1 0 9115 961 079 000 615 Q Supply Giai 0 5V 0 2 1 9 3 27 961 080 000 530 2 Pressure Pressure 0 42 1 6 30 961 081 000 530 Q ES 1 9V 0 2 1 9 3 27 961 086 000 840 Q S O eee Supply Regulated 0 4 2 1 6 30 961 087 000 840 Q _ JAtmosprere Pressure Pressure NOTE For NEMA4X add 004 suffix Type 1000 Extended Range Ordering Information Agency Approval Notes Output Impedance Factory Mutual Input BAR PSIG Part Number Nominal T 1000 I P Transducers Intrinsically Safe Class Division 1 Groups A B C amp D T6 De dm 0 60mA 0 1 8 3 2 120 961 107 000 220 Q Non Incendive Class Division 2 Groups A B C amp D T6 0 2 8 3 3 120 961 111 000 260 Q T 1000 I P E P Transducer sp 4 20mA 0 14 1 2 60 961 117 000 225 O Explosion Proof Class Division 1 G
22. electrical signal to a proportional pressure output It provides precision electro pneumatic control to actuators valves positioners final control elements and is ideally used for high flow control devices The Type 1500 s compact size and accessibility to ports and adjustments allow the unit to be installed in space constrained locations or in a manifold for multi device control DIN rail and manifold assemblies are available in kits that provide three five or ten mounting points An integral pneumatic volume booster is in cluded in the Type 1500 design to provide high flow capacity See specifications for flow data Standard Features Small footprint compact size Manifold mounting configurations Built in volume booster Electrical Connections Conduit 1 2 NPT or BSPT Terminal Block Hirschmann Connectors DIN 43 650 A e Supply and output ports on front and back of unit Low air consumption e External zero and span adjustments Low cost Field accessible orifice e Electrical conduit connection meets CE requirements Options Available Intrinsically Safe FM CSA ATEX e NEMA 4X FM CSA Excludes Terminal Block Applications The T 1500 transducer can be used as an electro pneumatic control device to operate Valve actuators Valve positioners HVAC systems Material handling systems Paper handling controls Automation systems Liquid and gas processing systems www marshb
23. ellofram com o 800 7275646 Principle of Operation See Fig 2 and 6 The T 1500 Transducer is a force balance device in which a coil is suspended in the field of a magnet by a flexure Current flowing through the coil generates axial movement of the coil and flexure The flexure moves against the end of a nozzle and creates a back pressure in the nozzle by restricting air flow This back pressure acts as a pilot pressure to an integral booster relay Consequently as the input signal increases or decreases for reverse acting output pressure increases proportionally In the zero based T 1500 the output of the transducer section is routed to an integral nega tive bias booster relay The bias relay allows the complete unit to regulate output pressure down to 0 psig BAR The bias relay also amplifies the output of the transducer which allows the zero based units to regulate higher output pressures than the standard T 1500 Zero and Span are calibrated by turning easily accessible adjusting screws on the front face of the unit see Figures 3 4 5 7 8 and 9 The zero adjustment causes the nozzle to move relative to the flexure The span adjustment is a potentiometer that limits the flow of current through the coil A thermistor circuit in series with the coil provides temperature compensa tion Mounting The T 1500 can be mounted at any angle but should be calibrated after mounting For maximum output pressure stability t
24. he T 1500 should be mounted vertically in a vibration free location or such that the vibration is isolated to the X and Z axis The T 1500 can be in line panel pipe DIN rail or manifold mounted Air Connections 1 Supply Air must be instrument quality air regulated between 5 PSI above maximum output pressure up to 120 PSIG 8 3 BAR See table Supply Pressure Range 2 Instrument quality air consists of a A dew point less than 35 F b No particles larger than three microns c Maximum oil content of 1 ppm 3 All unused ports must be plugged ELZ Ta Ee 8 03 14 Supply Connect supply to either of two ports marked IN on the base of the transducer Avoid get ting pipe sealant inside the piping or transducer Output Connect output to either of two ports marked OUT on the base of the transducer The second OUT port may be used for a pressure gauge f t MARSH BELLOFRAM 67 Group of Companies D o Q c v Type 1500 Transducers Hysteresis Repeatability Linearity Independent Flow Mid Range Maximum Air Consumption Exhaust Capacity Supply Pressure Range Weight Port Size Supply Pressure Sensitivity Temperature Range Input Signal Output Range Standard Range 0 7554 of span 0 596 of span 0 7554 of span lt 1 0 of span for fluorocarbon units 6 5 SCFM Minimum 15 0 PSIG 1 0 BAR output pressure 120 PSIG 8 3 BAR sup
25. ing in the voltage mode E P can be adjusted with the span potentiometer for any input between 0 10 VDC The input range is limited to a minimum 4VDC difference between 100 and 0 Input voltage 2 Standard NEMA 1 enclosure is conversion coated only Standard NEMA 3R and NEMA 4X enclosures are epoxy painted Span Potentiometer Zero Potentiometer Damping Potentiometer Terminal Block Ground Screw 1 2 NPT Electrical Port D 5 o Q c e Coil Coil Wire Connector Removable Orifice 1 8 NPT Gauge Port 1 4 NPT Supply Pressure Port PSIG 05 0 5 030 060 0 100 107 315 327 630 39 915 02 0 020 420 mA 06 20 08 09 05 0 03 04 0 0 B Uy 10 50mA 1 6 45 98 89 15 12 87 14 0 90 BI 17 0o5VDC 2 26 18 02 29 25 22 85 24 30 8 B 2 15VD0 Al 36 AB 38 339 g 32 33 34 50 ad B 37 19VD0 A2 46 40 48 0 49 45 42 43 44 60 5 B y 1 0 VDC A3 56 B6 58 89 55 8 53 54 8 6 B OST 0 10VDC A4 66 70 68 69 65 62 63 64 800 99 23 64 MARSH BELLOFRAM 0 00 0 0 0 0 0 0 0 0 0 0 0 00 800 7275646 www marshbellofram com Group of Companies Front View DAMPING ADJUSTMENT POT ZERO SPAN ADJUSTMENT POTS CIRCUIT BOARD ASSEMBLY PRESSURE SENSOR SERVO DIAPHRAGM COIL FLAPPER NOZZLE REMOVABLE ORIFICE OUTPUT pda DIAPHRAGM Supply Pressure Regulated Pressure Atmosphere Pilot Pressure Bottom
26. ironmental conditions 1 2 NPT or 20mm Conduit Connections DIN Hirschmann S model only actuator with many F External Terminal Block S model only industry wide firsts Power Supply 5 28VDC with voltage inputs only Lue Direct Reverse Acting Switch Selectable Pneumatic 0 5 0 15 3 15 1 17 0 30 6 30 3 27 0 60 0 100 or 120 PSIG Outputs 0 0 1 0 0 3 0 1 0 0 2 1 0 0 07 1 2 0 2 1 0 4 2 1 0 2 1 9 0 4 1 0 6 9 0 8 3 BAR 1 4 NPT BSPT or BSPP threads Forts Unput duiputi Bottom ported for Manifold Mounting Exhaust Explosion proof only 1 8 27 NPT Ports Gauge 1 8 NPT For 0 5 PSIG 0 3 BAR Through 0 60 PSIG From 5 PSIG 0 3 BAR above maximum output to 100 PSIG maximum Supply For 0 100 PSIG and 0 120 PSIG Ranges From 5 PSIG 0 3 BAR above maximum output to 140 PSIG maximum Split Ranging Switch Selectable Full Range or Split Range High or Split Range Low Consumption 4 SCFH maximum 1 9 LPM Range Sensor Flow k PSIG BAR PSIG BAR SCFM LPM rir 0 5 0 0 3 5 0 3 11 312 Jl d EI IL 0 15 0 1 0 15 1 0 15 423 CT 3 15 0 2 1 0 15 1 0 15 423 THT T 1 17 0 07 1 2 15 1 0 15 423 Fini Capacity 0 30 0 2 1 30 2 1 15 423 3 27 0 2 1 9 30 2 1 15 423 6 30 0 4 2 1 30 2 1 15 423 0 60 0 4 1 50 3 5 17 480 Typical Flow 100 PSIG 6 9 BAR in and maximum out o 0 100 0 6 9 100 6 9 21 595 Al mosoherie 0 120 0 8 3 100 6 9 21 595 P Pressure Typical Flow 140 PSIG 9 7 BAR in and maximum ou
27. l P 0 5 VDC Full 0 60 0 4 1 Acting 3 27 0 2 1 9 E P 0 100 0 6 9 6 30 0 4 2 1 ee qu 0 100 0 6 9 Switch 1 PSIG BAR 2 3 4 5 6 psig BAR 7 8 9 1 9 VDC 3 15 0 2 1 0 Un ai e ee E m h Bin PE ds a a En Ea 420mA Pg i 6 30 0 4 2 1 dinis prit mg MARSH BELLOFRAM 75 www marshbellofram com 9 800 7275646 Group of Companies Type 2000 Dimensions 1 2 14 NPT 2X M3X0 5 2X 8 32 UNC 2B X 250 DEEP X 375 DEEP MOUNTING HOLES 270 TYP 1 4 18 NPT TYP Bellofram Drawings and dimensions are for reference only J 76 MARSH BELLOFRAM Group of Companies 2 www marshbellofram com 800 727 5646 Type 5000 P I Transducers Description _ _ LOITUIIEEENNMEBENUN The Type 5000 series is a compact rugged and 0 1 accuracy typical reliable family of two wire pressure transmit Piezo resistive pressure sensor resists vibration ters designed for industrial field service These instruments convert a signal pressure input into a precise 4 20 or 10 bOmA output The lightweight transmitter housing includes a NEMA 4X housing approved for explosion 1 4 NPT pressure port and a 1 2 NPT conduit proof service port for field wiring Connections are easily accessible simply by removing the top cover Zero and span adjustments are available within the field wiring compartment for fine on site calibration adjustment Mounts at any angle Easily accessible zero and span adjustments The Type 50
28. late either half top or bottom of its normal output range when supplied with its normal full ranging electrical input For example a 0 10V 0 30 PSI unit set to split range low will regulate 0 15 PSI 0 10V It will regulate 15 30 PSI 0 10V if set to split range high Electrical Port Options 1 1 2 NPT Conduit 2 20mm Conduit 3 Hirschmann DIN 43 650 A 4 Terminal Block Easy Access Orifice Output Port Same as Input Port Not shown rear face Input Port Options 1 1 4 NPT 2 1 4 BSPP 3 1 4 BSPT Manifold Mounting Option Supply and Qutput ports on the bottom face rather than through the body Explosion proof I P amp E P Transducer Rated 28Vdc 8mA T Code T6 Enclosure Type 4X NEMA 4X IP66 Max Ambient Temperature 60 C IN COMPLIANCE WITH STD C22 2 No 213 APPROVED D CE ex o P Q E ge N c T 2000 I P amp E P Transducers intrinsically Safe Entity Hazardous Locations Class Divisions 1 amp 2 Groups A B C amp D Class Il Division 1 Groups E F amp 6 Division 2 Groups F amp G Class Ill Hazardous Locations Electro Pneumatic I P and E P Transducers Maximum Ambient Temperature 60 C Enclosure Type 4X NEMA 4X T4 Intrinsically Safe when installed Explosion proof Class Division 1 Groups A B C amp D Class Il Groups E F amp G Class Ill NEMA 4X Rated 28Vdc 8mA T Code T6 Enclosure Type 4X IP66 Max Ambient Temperature 60 C
29. led off of the manifold for service or replace 18 70 17 96 ment without affecting the whole manifold 10 475 0 mm 456 2 mm See Figure 1 Mounting gt The manifolds may be mounted flush with a wall or cabinet or may be mounted away from the wall Both mounting options are included in the basic manifold kit In addition all fittings required to mount the full number of units in each manifold are included in the basic kit An additional adapter kit may be purchased which contains all of the hardware required to mani fold mount a single T 1500 Transducer should the need arise Figure 1 Manifold Front View 2 50 Air Supply Attachment i N e a e The air supply can be attached to either side of the manifold via a 3 4 NPT connection or OOO 3 50 to the back of the manifold via a 3 8 NPT con O O 6100 l 88 9mm nection After an air supply port is selected the open ports should be plugged using the plugs zi A T N T o E provided with the manifold kit and a pneumatic sealant CHECK VALVES up CAPTIVE SCREW ADAPTER PLATE Output Air Attachment ee MX S Connect the output ports from each of the E T 1500 Transducers to the bottom or back of oe 1500 Manifold Ordering Information S the manifold After connecting the transducers Kit Part Number 7 plug the other 1 8 NPT ports using the plugs T 1500 Wall Mount Kit 3 unit 010 606 000 aaa a SB T 1500 Wall Mount Kit 5 unit 010 606 001 T 1500 Manifold Adapter Ki
30. ply pressure 3 SCFH 8 15 PSI 1 0 BAR output pressure 21 0 SCFM 5 PSI 0 4 BAR above set point 5 psi above maximum output up to 120 psig 8 3 BAR maximum 1 3 Ibs 1 4 NPT BSPT BSPP lt 2 5 of span for a supply pressure change of 15 PSIG 1 0 BAR 20 F to 150 F 4 20 mA DC 0 5 VDC 1 5 VDC 1 9 VDC 0 10 VDC 1 10 VDC 3 15 3 27 6 30 PSIG 0 2 1 0 0 2 1 9 0 4 2 1 BAR Zero Based lt 1 0 of span lt 0 5 of span lt 1 0 of span 9 0 SCFM Minimum 15 0 PSIG 1 0 Bar output pressure 150 PSIG 10 3 BAR supply pressure 18 SCFH Maximum output pressure gt 1 0 SCFM 5 PSI 0 4 BAR above set point 0 15 units 25 150 PSIG 1 7 10 3 BAR 0 30 units 40 150 PSIG 2 8 10 3 BAR 0 60 units 70 150 PSIG 4 8 10 3 BAR 0 120 units 125 150 PSIG 8 6 10 3 BAR 1 63 Ibs 1 4 NPT BSPT BSPP lt 1 7 of span change in output pressure over full supply pressure range 0 120 units 20 F to 150 F 4 20 mA DC 0 5 VDC 1 5 VDC 1 9 VDC 0 10 VDC 1 10 VDC 0 15 0 30 0 60 0 120 PSIG 0 1 0 0 2 1 0 4 1 0 8 3 BAR Electrical Connections Both the P amp E P versions are two wire devices plus a safety ground The E P requires a DC voltage input signal example 1 to 9 VDC The I P models require an input current of 4 to 20 mA Type 1500 Ordering Information 96 Enclosure Rating L NEMA 4X Includes Approvals Indoor Use General Purpose In and Out Pneumatic Port Connections
31. quire recalibration of the zero adjustment For maximum output pressure stability the Type 1000 should be mounted in a vibration free location or such that vibration is isolated to the X and Z axis shown on the dimensional drawings Field Reversible All Type 1000 transducers are calibrated at the factory for direct acting operation but may be used in the reverse acting mode by reversing the polarity of the signal leads and recalibrat ing When calibrated for reverse acting applica tions the Type 1000 transducers provide a minimum of their full rated output pressure i e 15 27 or 30 PSIG upon input signal failure Type 1000 for Extended Range Description The Bellofram Extended Range I P and E P Transducers are based on Bellofram s proven Type 1000 transducer line the best selling transducers in the business The large span adjustment range of this line allows recalibration to fit applications with output ranges from approximately 3 35 PSIG 0 2 2 4 BAR to 3 145 PSIG 0 2 10 BAR MARSH BELLOFRAM Group of Companies 800 7275646 Eellofram 4070 000 MEUT DATO rA GuT PUT 6 18 Fai BSWPPL Fi Tm 09 Fei A POR C The units accept supply pressures up to 150 PSIG 10 5 BAR and provide flow capacity to 24 SCFM 677 SLPM The Type 1000 I P and E P Transducers are more cost effective and more accurate than typical high output systems using transducers coupled to boosting or mul
32. rmalized control signal directly proportional to the desired pressure output Simultaneously the output of the pressure sensor is amplified and conditioned to pro duce a feedback signal The sum of the control signal and the feed back signal produce a command signal which is delivered as a DC voltage to the piezo ceramic actuator As voltage increases the force applied by the actuator increases so as to restrict nozzle bleed and thus increase pilot pressure Increased pilot pressure applied to the servo diaphragm directly causes opening of the supply valve and an increase in the output pressure until the output feedback signal and control signal combine to produce the correct command signal Fine Tuning Your Application For optimal performance in your application the calibration of the Type 2000 can be fine tuned in the field An easily removable cover provides access to the isolated electronics All potenti ometers connections jumpers and switches are clearly marked on the circuit board or on the handy chart located on the inside of the cover The three elements of calibration Gain Zero and Span are described below Consult the Type 2000 User s Manual for detailed calibration procedures cautions and instrumen tation requirements 800 727 5646 Adjustment Gain Dampin The output response of the Type 2000 can be optimized for varying downstream volumes by adjusting the system gain of the control circui
33. roup D T6 eee A pust Ignition Proof Classes II amp III Division 1 Groups E F amp G T6 E 0 10V 0 2 8 3 3 120 961 112 000 805 Q Type 4 NEMA 4 C to 2 0 5V 0 14 1 2 60 961 118 000 500 Canadian Standards Association gt z T 1000 I P Transducers 7 oe 1000 High Relief Ordering Information Hazardous Locations Class Group D Class Il Groups E F amp G a Output Impedance Class I CSA Enc 4 NEMA 4 Input Part Number Nominal I P transducer supply pressure 100 psig max input 4 20mA output 3 15 psig BAR PSIG Intrinsically Safe and Non Incendive Systems For Hazardous 0 2 0 6 3 9 961 130 000 90 Q Locations Class Groups A B C amp D Class Il Groups E F amp G Class Ill 0 6 1 0 9 15 961 131 000 90 Q I P transducer rated input 4 20mA intrinsically safe when connected through CSA Certified 0 2 1 0 3 15 961 132 000 180 O diode safety barriers in accordance with Bellofram Installation Instruction 4 20mA 0 2 1 9 3 27 961 133 000 220 Q Explosion proof intrinsically safe and non incendive ratings are not affected by recalibrating 0 4 2 1 6 30 961 134 000 220 Q for split range or reverse acting applications 0 2 1 0 3 15 961 135 000 180 Q The Bellofram T 1000 Transducers were tested and found to comply with Electromagnetic 0 07 1 2 1 17 961 136 000 250 Q Compatibility Directive effective January 1 1996 The relevant EMC specifications tested i 491 nm were the following EN 50081 1 1992 and EN 50082 1 1992
34. sure changes e Removable orifice screw for easy maintenance Applications The Type 1001 s precisely regulated pneumatic output can be used to operate e Valve actuators e Louver and damper actuators e Valve positioners Relays Clutches and brakes Controllers Air cylinders Industry Applications Include Liquid and Gas Processing Pulp and Paper Petrochemical Processing HVAC Systems Textile Productions Energy Management e Environmental Control Medical Equipment Calibration Adjustments The Type 1001 contains multi turn Zero and Span adjustment potentiometers which are accessible on NEMA 1 models by sliding the cover window MARSH BELLOFRAM Group of Companies open to its first detent position Pots are clearly distinguished by legend on the cover On NEMA 3R and 4X models the cover should be removed to reach the pots marked Z for zero and S for span Adjust the pots clockwise to increase Zero and Span as required to optimize factory set output with appropriate input signal and supply pressure applied Damping Adjustment To eliminate undesirable system oscillation the Type 1001 features a unique damping adjust ment The output response is optimized to varying downstream volumes by adjusting the feedback time constant of the coil drive amplifier This is accomplished on NEMA 1 models by slid ing the cover window open to its second detent position to expose the single t
35. t 7 1500 Wall Mount Kit 10 unit 010 606 002 The T 1500 manifold kit includes the adapter T 1500 Manifold Adapter Kit Replacement 010 602 000 kits required for each transducer DIN Rail Mounting Kit 971 140 000 Electrical Connections Pneumatic Repair Kit 971 141 000 Two brackets supplied with the manifold kit 3 15 3 27 PSIG 0 2 1 0 0 2 1 9 BAR allow an electrical conduit to be attached to Pneumatic Repair Kit 971 141 002 the manifold Mounting screws and nuts are 6 30 PSIG 0 4 2 1 BAR provided and the brackets have an 11 64 Pneumatic Repair Kit Fluorocarbon 971 141 003 diameter hole which will fit standard 8 36 UNF 3 15 3 27 PSIG 0 2 1 0 0 2 1 9 BAR or 8 32 UNC screws not supplied Pneumatic Repair Kit Fluorocarbon Ds 6 30 psig 042 1 BAR 371 141 004 Pneumatic Repair Kit 0 120 PSIG 083 BAR SIME es I Pneumatic Repair Kit Fluorocarbon 0 120 psi 083 BAR 3p E Fee Electronic Repair Kit 4 20 mA 971 142 000 Electronic Repair Kit 0 5 VDC or 1 5 VDC 971 142 001 Electronic Repair Kit 1 9 1 10 VDC or 0 10 VDC 971 142 002 2 Pipe Mounting Kit 971 153 000 Filter Kit 60 Micron 010 139 000 MARSH BELLOFRAM 69 www marshbellofram com 800 7275646 Group of Companies EZRIUSIJMLEBEIIOUE X3 516 W 212 1 Figure 2 Type 1500 Extended Range Parts Number Description 1 Circuit Board Q 2 Worm Gear 3 Duckbill Valve NEMA 4X Only 4 Magnet Assembly D 5 Nozzle Assembly 6 Bonnet Gasket NEMA 4X Only 7 Ser
36. t Adjust the Gain Pot counterclockwise for in creased gain clockwise for increased oscillation damping For maximum allowable gain in your application the pot should be turned clockwise until oscillation just disappears Zero and Span Adjustments ___ _ The Type 2000 contains multi turn Coarse Zero Fine Zero and Span adjustment potentiometers which are clockwise positive Adjustment of either Zero Pot changes the unit s minimum output while the Span Pot changes the maxi mum output The adjustments are interactive so it may take iterations to reach the desired calibration Wide Rangeability The Type 2000 can be field calibrated to pres sure ranges other than the standard ones by combinations of recalibration pressure range switching and split high low ranging A unit should not be switched to a range outside its pressure sensor family eg a 0 15 PSIG can be switched to a 3 15 PSIG but not to 0 30 PSIG Caution Do not exceed the range of the on board pressure sensor For example the easiest way to recalibrate a 0 30 PSIG unit to 3 15 psig would be to change the switch setting to 3 27 PSIG then switch to split range low Field Selectable Features Onboard switches allow the user to easily recon figure the Type 2000 for any of several electrical inputs direct reverse acting or output split rang ing high low Fine tuning of the unit s calibration may be necessary after a reconfiguration www marshbellofram
37. t Pilot o Exhaust Capacity 3 SCFM 85 LPM Q5 PSIG 0 3 BAR above setpoint Pressure 0 15 PSIG range unit set at mid range E Supply Stability Pressure Supply Voltage Effect None Regulated Supply Pressure Effect None peel Vibration Effect lt 1 FS 1G 5 1000Hz Mounting Position Effect None Air Qualit RFI EMI CE Compliant Instrument quality air consists of Temperature Effect 0 02 FS F 40 to 180 F 40 to 82 C a A dew point less than 35 F Storage Temperature 00 t0200 F 401t093 C h 5 5 p No particles larger than three microns Approximate Weight 3 0 lbs 135kg e Maximum oil content of 1 ppm TYPE 2000 REGULATED PRESSURE VS FLOW EH T aia UDDAIIUESE Mounting Method Intrinsically Safe S Model Explosion Proof E Model In Line Yes Yes a Direct Mounting Side or Bottom Holes Side or Bottom Holes z 50 Panel Bracket Supplied Accessory E 40 Valve Bracket Accessory Supplied E Pipe Bracket Accessory Accessory z 30 DIN Rail Bracket Accessory Accessory 20 Manifold Plate Accessory Accessory 10 Mounting The Type 2000 can be mounted in line or directly to a panel via mounting holes located in the side and bottom of the unit In addition the S model includes a panel 0 mounting bracket while the E model includes a valve mounting bracket Kits are available for mounting of either model to panel valve pipe or DIN Rail A custom pla
38. te is available SCFM 0 2 4 6 8 10 12 4 316 18 20 22 24 for mounting of the bottom ported version to a manifold See Accessories LPM 0 57 13 170 227 283 340 397 453 510 566 623 680 FORWARD FLow e High Flow LJ Med Flow mj Low Flow 74 MARSH BELLOFRAM soozzz5646 Group of Companies www marshbellofram com Type 2000 Orderino Information Type 2000 Accessories 2 K Part Number Encl I Is pm SW Panel Mounting Kit 010 135 000 E Explosion Proof Valve Mounting Kit 010 134 000 Electrical Port I E N 1 2 NPT Conduit esL NN 010 143 000 M 20mm Conduit S Unit Only Valve Mounting Kit is required H Hirschmann DIN Rail Adapter 010 115 000 T Terminal Block S Unit Only l LT 4 Pneumatic Ports Manifold Adapter Kit 971 158 000 N NPT Filter Kit 60 microns 010 139 000 T BSPT 7 P BSPP
39. tions Class Groups B C amp D Class Il Group E F amp G Class Ill Encl 4 NEMA 4 I P or E P transducer input 4 20 10 bOmA dc 0 5 1 5 1 9 amp 1 10V dc supply voltage 40V dc max supply current 100mA max maximum ambient temp 70 C Output pressure ranges Standard 3 9 9 15 3 15 3 27 6 30 1 17 psig Extended 0 15 0 120 psig T 1001 I P and E P Transducers Hazardous Locations Class Division 2 Groups A B C amp D 800 727 5646 gt CE P transducer rated input 4 20mA or 10 50mA 30V dc max E P transducer rated supply 24V dc 10mA rated 0 5 1 5 1 9 amp 1 10V dc IN COMPLIANCE WITH STD C22 2 No 213 Intrinsically Safe and Non Incendive Sys tems Hazardous Locations Class Groups A B C amp D I P transducer rated input 4 20mA or 10 50mA 30V dc max intrinsically safe when connected through CSA Certified zener barrier devices or converters as per Bellofram Installation Instruction E P transducer rated supply 24V dc 10mA rated input 0 5 1 5 1 9 amp 1 10V dc intrinsically safe when connected through CSA Certified zener barrier devices as per Bellofram Installa tion Instructions The Bellofram T 1001 Transducers were tested and found to comply with Electromagnetic Compatibility Directive effective January 1 1996 The relevant EMC specifications tested were the following EN 50081 1 1992 and EN 50082 1 1992 A Technical Construction File Serial 107 was written and
40. tiplying relays Type 1000 with High Relief Description Expanding upon the proven accuracy reliabil ity and rugged construction of the Type 1000 General Purpose these transducers provide extra fast blowdown for a very rapid release of downstream pressure The extra relief feature makes these units suitable for cylinder return stroke actuation air hoists and similar applica tions requiring fast exhaust These units accept supply pressures to 100 PSIG 6 9 BAR with output ranges from 1 17 PSIG 0 07 1 2 BAR to 6 30 PSIG 0 4 2 1 BAR and provide exhaust capacities of 7 SCFM 336 SLPM www marshbellofram com Type 1000 Transducers Supply Pressure Range Supply Pressure Sensitivity Linearity terminal based Repeatability Hysteresis Minimum Flow Rate at Midrange 100 PSIG 7 BAR Exhaust Capacity 5 psig 0 4 BAR above setpoint Air Consumption max at Midrange Port Size pneumatic electric inches mm Size Weight Type 1000 General Purpose 3 PSIG 0 2 BAR above max output to 100 psig 7 BAR 0 15 of span per 1 5 PSIG 0 1 BAR lt 1 0 of span lt 0 5 of span lt 1 0 of span 12 SCFM 339 SLPM 2 SCFM 56 5 SLPM 0 1 SCFM 2 8 SLPM 1 4 NPT and 1 2 NPT 2 1 8 X 2 1 X 4 54 X 54 X 101 2 1 Ib 0 95 Kg Type 1000 Dimensional Drawing 35 1 1 38 38 6 1 52 Type 1000 High Relief 3 PSIG 0 2 BAR above max output to 10
41. urn Damping Poten tiometer remove the cover on NEMA 3R and 4X models To optimize response turn the pot fully counterclockwise until system oscillation is just eliminated System oscillation may be observed by monitoring output pressure or by observing the behavior of directly actuated system compo nents in response to a changing input Mounting The Type 1001 transducers are designed to be position insensitive They can be panel valve or pipe mounted at any angle see NEMA 3R limita tion without a need for in place recalibration Panel mounting can be either direct or with the bracket furnished with each unit Mounting holes are located on the bottom and side to provide maximum mounting flexibility Users may order the optional DIN Rail Adapter or a bracket suit able for either valve or 2 pipe mounting Special pipe clamps may be ordered as a separate kit Agency Approval Notes Factory Mutual T 1001 I P and E P Transducers intrinsically Safe Class Division 1 Groups A B C amp D T6 Ta 40 C Non Incendive Class Division 2 Groups A B C amp D T6 Entity Parameters V 28 Vl 150 mA C 0 22 pF L 0 T 1001 I P and E P Transducers Explosion Proof Class Division 1 Groups B C amp D T6 Dust Ignition Proof Classes Il amp Ill Division 1 Groups E F amp 6 T6 Type 4X NEMA 4X Canadian Standards Association T 1001 and T 1001XP I P and E P Transducers Hazardous Loca
42. vo Diaphragm I P Section 8 Control Diaphragm I P Section 9 Pintle 10 Supply Seat 11 Coil Flexure Assembly 12 Servo Diaphragm Bias Relay 13 Control Diaphragm Bias Relay 14 Orifice Screw 15 Bias Spring e Dimensions Figure 3 Terminal Block Back Dimensions Figure 4 Hirschmann DIN 43 650 A d z 38 6mm gt 1 00 2 11 254m K 104mm 4 TERMINAL 2 TERMINAL 1 E axo Pg NO DO Q SPAN ADJUSTMENT s4 9Npsue lL 57 2mm 13 22m k 225 T FIGURE 5 1 2 NPT BSPT Drawings and dimensions are for reference only 2 25 o 57 2mm 70 MARSH BELLOFRAM gooz2z5646 Group of Companies 2 www marshbellofram com BAY of LEOTE ETT ET B SES Tae PN ET ce Figure 6 Type 1500 Standard Range Parts Number Description 1 Circuit Board 2 Worm Gear 3 Duckbill Valve NEMA 4X Only 4 Magnet Assembly 5 Nozzle Assembly 6 Bonnet Gasket NEMA 4X Only 7 Servo Diaphragm I P Section 8 Control Diaphragm I P Section 9 Pintle 10 Supply Seat 11 Coil Flexure Assembly Back Dimensions 152 38 6mm 1 00 25 4mm 10 32 UNF 2B MOUNTING HOLES Vibration Axes 0 77 19 6mm FIGURE 8 1 2 NPT BSPT J 225 57 2mm Figure 7 Terminal Block 2 87 k 72 9mm 6 DSD SPAN ADJUSTMENT 2 25 5 2mm Figure 9 Hirschmann DIN 43 650 A 211 10 4mm
43. ype 1001 Accessories Kits hune Panel Mounting Kit 010135 000 Valve Mounting Kit 010134 000 EROR KC required 010143 000 DIN Rail Adapter 010115 000 for NEMA 4X enclosure only 210136000 Type 1 Orifice with Buna N O rings 010137 000 Type 1 Orifice with Viton O rings 010137 002 5 Type 2 Orifice with Buna N O rings 010137 001 E Type 2 Orifice with Viton O rings 010137 003 E Filter Kit 60 microns 010139 000 Hirschmann Connector Kit Din 43 650 A 010142 000 3 prong plug O ring sealed Pressure Gauge Kit 15 PSI 010138 000 Pressure Gauge Kit 30 PSI 010138 001 Pressure Gauge Kit 60 PSI 010138 002 Pressure Gauge Kit 160 PSI 010138 003 Type 1 Kits to be used with based output units and 1 17 PSIG unit Type 2 Kits to be used with all other units Supplied standard with Nema 4X LATA 0104 By oy Yere ET Input Output Comments Part Number 4 20 mA 20 100 kPa NEMA1 962 145 000 4 20 mA 20 100 kPa NEMA3R 962 146 000 4 20 mA 0 200 kPa NEMA1 962 148 000 MARSH BELLOFRAM 63 Group of Companies oe 1001 Ordering Information Enclosures 6 NEMA 1 General Purpose 7 d NEMA 3R Rainproof 8 NEMA 4X Water tight Dust tight Corrosion Resistant and Explosion Proof Calibration See Input Output matrix below Agency Approvals 0 None 1 Factory Mutual and CSA Explosion Proof Options 00 None O6 Fluorocarbon Elastomeric Diaphragm Notes to Nomenclature 1 Transducer operat