1. AND A Warning DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS ATEX Zone 2 This module must be mounted in an enclosure certified in accordance with EN60079 15 for use in Zone 2 Group IIC and rated IP54 The enclosure shall only be able to be opened with the use of a tool
2. backplane reset is complete Off NA NA Module does not have power or backplane reset is not complete NETWORK Yellow Static On n a Module is holding the PROFIBUS token and is able to transmit PROFIBUS telegrams Flashing Non Between 0 5 Hz and Module is sharing the PROFIBUS token with other cyclic 100 Hz master on the network Off NA Module is not configured or has not received the token permission from the network Red Static On NA Module has found a communication problem with at east one network slave usually connection timeout MOD STATUS Green Flashing Cyclic 5 Hz o error in configuration found module is ready for communication it tries to open a connection to a slave but is not connected yet Flashing Non 3 times fast at 5 Hz Power Up Configuration missing For details on cyclic 8 times between 0 5 Hz hardware configuration refer to Chapter 3 and 1 Hz Runtime Firmware has found a critical problem such as a watchdog timeout Static On NA Module has established at least one connection to another device on the network Yellow Flashing Cyclic 1 Hz Module is in boot loader mode and is waiting for firmware download Flashing Cyclic 5Hz Firmware download is in progress Flashing Non 3 times fast at 5 Hz Hardware or non recoverable runtime error cyclic 8 times between 0 5 Hz detected module may need to be replaced and 1 Hz Off A NA o power Module Status Information For details on using the Co
3. 2359E Slave Configured Bits This 128 bit array indicates which slaves on the PROFIBUS network are configured Each slave has a corresponding bit in this array A slave s configuration status address equals Start Address Station Address of the slave For example if the configuration status bits are mapped to 100001 the status for the slave at Station Address 5 would be found at l00001 5 100006 Slave Diagnostic Bits This 128 bit array indicates which slaves on the PROFIBUS network have diagnostic data available The diagnostics can be read using the Get Device Diagnostics COMMREQ command 4 Each slave has a corresponding bit in this array A slave s diagnostic status address equals Start Address Station Address of the slave For example if the configuration status bits are mapped to 100001 the status for the slave at Station Address 5 would be found at 100001 5 I00006 Connecting the Module to the PROFIBUS Network The module contains a standard female DB9 connector labeled PROFIBUS that can be connected to a PROFIBUS bus terminal that complies with EN 50170 The PROFIBUS module has no built in termination If termination is required you must use a bus terminal that has built in selectable termination m PROFIBUS DB 9 connector recommendation Siemens 6ES7 972 OBB50 OXAO 12MB Caution Do not connect any devices to the 5Vdc pin pin 6 It is to be used for termination purposes only Doing so could damage equi
4. Important Product Information PACSystems RX3i GFK 2359E March 2015 The PACSystems RX3i PROFIBUS Master Module IC695PBM300 allows the host RX3i CPU to send and receive data via a PROFIBUS DP network The IC695PBM300 module provides the following PROFIBUS communications features Supports all standard data rates Supports a maximum of 3 584 bytes of input data and 3 584 bytes of output data Supports a maximum of 125 PROFIBUS DP slaves IC695PBM300 CC PROFIBUS Master Module PROFIBUS OK NETWORK MOD STATUS PBM300 Supports a maximum of 244 bytes of input data and 244 bytes of output data for each PROFIBUS MASTER slave Supports Sync and Freeze modes Supports DP V1 Read Write and Alarm messages Has PROFIBUS compliant module and network status LEDs The PROFIBUS Master module must be located in an RX3i Universal Backplane and requires a host RX3i CPU with firmware version 2 9 or later The PROFIBUS module receives its firmware upgrades indirectly via the host controller CPU using the WinLoader software utility WinLoader is supplied with any updates to the PROFIBUS module software Release Information Version 1 04 of the IC695PBM300 RX3i PROFIBUS Master resolves the following issues When multiple Lumberg devices 8in 4out are connected to the bus and power is removed from these devices but the PBM300 remains powered the inputs assigned to the Lumberg devices will toggle between 1 and 0 Configuring slaves with a large am
5. e number and types of slave devices that can exchange data with the master are constrained by various memory resources within the module The amount of memory available for the PROFIBUS configuration is affected by the number and types of slave modules in the network configuration The total slave configuration data size is limited to approximately 9KB Data Sizes The amount of data that can be configured on the IC695PBM300 PROFIBUS network provides up to 3584 input bytes and 3584 output bytes DOIO Functionality DOIO functionality is not supported in the embedded PROFIBUS interface at this time The DOIO function block returns an error if it is executed using the embedded PROFIBUS as a target PLC C Toolkit Version Requirements Version 4 00 Build 50A1 or later of the PLC C Toolkit must be used for C programming Problems Resolved by this Revision The following problems are resolved in version 1 04 Subject Description Inputs to Lumberg devices blink when devices are powered down In previous versions when multiple Lumberg devices 8in4out are connected to the bus and power is removed from these devices but the PROFIBUS master remains powered the inputs assigned to the Lumberg devices will toggle between 1 and 0 This problem has been corrected in version 1 04 Incorrect error returned when memory space exceeded Configuring slaves with large amount of parameter data returns the incorrect error code
6. isplays incorrect information for Master Type and Device ID The Network Settings window which can be displayed while configuring a PBM300 in Machine Edition does not indicate correct information for Master Type and Device ID This information is only displayed to the user and does not affect any underlying configuration information sent to the master module or its slaves The Device ID also known as PROFIBUS Ident Number if correctly displayed should be 0x0934 Specifications IC695PBM300 Environment Storage temperature 40 C to 85 C Operating temperature 0 C to 60 C Backplane Compatibility RX3i PCI Backplane Current 440 mA 3 3 Vde Consumption Data rates Supports all standard data rates 9 6 kBit s 19 2 kBit s 93 75 kBit s 187 5 kBit s 500 kBit s 1 5 MBit s 3 MBit s 6 MBit s and 12 MBit s Status Information Available Slave Status Bit Array Table Network Diagnostic Counters DP Master Diagnostic Counters Firmware Module Revision Slave Diagnostic Address Data Sizes The amount of data that can be configured on the PBM300 PROFIBUS network provides up to 3584 bytes input and 3584 bytes output For product standards and general specifications refer to the PACSystems RX3i System Manual GFK 2314 4 PROFIBUS Master Module 1C695PBM300 CC GFK 2359E LEDs LED Color State Frequency Meaning PROFIBUS OK Green Static On NA Module has power and
7. mmunication Request function to communicate with the PROFIBUS master module refer to the PACSystems RX3i PROFIBUS Modules User s Manual GFK 2301 Slave Status Bit Array The Slave Status bit array contains a bit for each slave If communication with a slave has no errors the bit corresponding to the slave determined by its network address is set If the communication has errors or is not occurring for any reason the bit is cleared The Master also maintains its own status in the bit corresponding to its network address Slave Diagnostics ID Array If diagnostics are pending the first word of this two word array contains the station address of the first slave that has diagnostics The diagnostics can be read using the Get Device Diagnostics COMMREQ command 4 This clears the word and the master then places the next pending diagnostic address into the Slave Diagnostics word If this word is zero there are no pending diagnostics The second word of this array is reserved and set to 0 DPV1 Alarm Status Array The 32 bit DPV1 Alarm Status array is used at the beginning of a scan to receive the station address of a slave that has sent a DPV1 Alarm message If another slave has sent a DPV1 alarm message it is ignored until the first one has been serviced and will then appear in a subsequent scan For details on the status format refer to DPV1 Alarm Acknowledge COMMREQ in GFK 2301 PROFIBUS Master Module C695PBM300 CC 5 GFK
8. ount of parameter data returns the correct error code when parameter data exceeds the available memory space The IC695PBM300 is field upgradable to firmware version 1 04 using the firmware upgrade utility Upgrade Kit 444753033 G02 Release History STATION ADDRESS Catalog Number Date Firmware Comments Version IC695PBM300 CC June 2010 1 04 Label change only No change in functionality performance or compatibility IC695PBM300 BC May 2006 1 04 IC695PBM300 BB Apr 2005 1 02 IC695PBM300 BA Feb 2005 1 00 IC695PBM300 AA Dec 2004 1 00 indicates a trademark of GE Intelligent Platforms Inc and or its affiliates All other trademarks are the property of their respective owners 2 GFK 2359E PROFIBUS Master Module C695PBM300 CC PBM300 Functional Compatibility Subject Description Series 90 30 PROFIBUS Customers using existing Series 90 30 PROFIBUS products should review the PACSystems Rx3i PROFIBUS Modules User s Manual GFK 2301 Changes have been made in items such as CommReg status words and data fields This module will report additional information in some instances and less information in other instances This product also supports PROFIBUS DP V1 functionality Programmer Version Requirements The IC695PBM300 can be configured and programmed with Machine Edition Logic Developer PLC version 5 0 Build 3227 SP2 or later Total Configuration Size Th
9. pment or cause erratic behavior 6 PROFIBUS Master Module 1C695PBM300 CC GFK 2359E Installation Location This product is intended for use with the RX3i system Its components are considered open equipment having live electrical parts that may be accessible to users and must be installed in an ultimate enclosure that is manufactured to provide safety Ata minimum the enclosure shall provide a degree of protection against solid objects as small as 12mm e g fingers This equates to a NEMA UL Type 1 enclosure or an IEC60529 IP20 rating providing at least a pollution degree 2 environment For details about installing RX3i rack systems refer to GFK 2314 If you need technical help contact Technical Support For phone numbers and email addresses see the back cover of this Guide Installation in Hazardous Areas The following information is for products bearing the UL marking for Hazardous Areas or ATEX marking for explosive atmospheres CLASS 1 DIVISION 2 GROUPS ABCD e This equipment is an open type device and is meant to be installed in an enclosure suitable for the environment that is only accessible with the use of a tool e Suitable for use in Class Division 2 Groups A B C and D Hazardous Locations or nonhazardous locations only A Warning EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS DIVISION 2 A Warning WHEN IN HAZARDOUS LOCATIONS TURN OFF POWER BEFORE REPLACING OR WIRING MODULES
10. when parameter data exceed the available memory space This problem is resolved in version 1 04 Problems Resolved in RX3i CPU IC695CPU310 The following problems were resolved in Release 3 00 of the RX3i CPU Subject Description PBM300 DPV1 Status data When a slave module sends a DPV1 Alarm Request to the PBM300 master the alarm information is displayed in the DPV1 Status input area The Sequence Number field in this status area will only indicate the value 0 in release 2 9 RX3i CPU firmware thus only slave DPV1 Alarms with Sequence Number 0 can be properly indicated This issue is corrected in release 3 0 of the RX3i CPU firmware release Discrete memory types for PBM300 COMMREQ In a PBM300 COMMREQ request the COMMREQ response reference memory area is indicated in the request Discrete reference memory types are now supported for the response data area PROFIBUS Master Module C695PBM300 CC 3 GFK 2359E PBM300 Restrictions and Open Issues Subject Description Get Master Status CommReq returns 1 or More Slaves Not in IO Exchange Mode on First Scan When a Get Master Status CommReg is called on the first scan of the PLC the CommReq may return a false positive saying that the PROFIBUS network has 1 or More Slaves Not in IO Exchange Mode The Get Master Status CommReq should not be called or relied upon for any data during the first scan of the PLC Machine Edition Logic Developer PLC d