Home
Honeywell VFD Tips 3.02
Contents
1. E MotorTorquePct 7 Multipl Out 0 0 ok Ind 0 0 ok eee OutputPowerPct Multipl E OutputYoltage 7 Multipl E DCLinkYolts Multipl Ed t Ou 304 Y ok nvoDrvSpeed G Numeric Point Out 0 ok ea R nvoDryCurnt Numeric Point Out 0 0 4 fok a ee nvoDrvPwr Numeric Point Out 0 0 kW ok er eee Page 3 of 3
2. Honeywell HVFD Smart Drive Tips and Notes READ MANUAL FIRST 1 Drive SELECTION tips Obtain motor nameplate information 1 Drives are sized by voltage and current not HP Verify the current capacity of the selected drive meets or exceeds the motor name plate It is acceptable to use a drive with higher amp amp HP rating than the motor name plate if needed If using single phase input in lieu of 3 phase power feed de rate the drive selection per recommendations Radio Frequency Interference RFI and drive chokes are required in most commercial applications When not provided as standard equipment purchase as an extra cost option HIGHLY recommended If existing cables are used and the drive to load distance exceeds 100 add an external dV dT output filter Verify physical space requirements Allow for minimum clearances for ventilation and service Select NEMA 1 chassis for most commercial applications Open chassis models should be installed in separate ventilated cabinets Select a NEMA 12 drive chassis when installed in harsh environments Select NEMA 3R enclosure for outside applications Verify ambient operating temperatures do not exceed drive specifications Allow for extended lead time Some drives and drive bypass combinations have extended delivery times 2 Drive INSTALLATION READ the installation instructions before proceeding 9 7 2 3 4 5 6 Verify drive matches the order Store and protect d
3. NS Assign configured interval to one of the 3 time channels More than one interval can be assigned to the same time channel to allow different start stop times for different days Assign the time channel to the drive run command point using the Control Signal 1A parameter MAIN MENU gt PARAMETERS gt I O CONFIG gt DIGITAL INPUTS gt CTRL SIGNAL 1A Change default from DigINSIotA1 digital input 1 to the desired timer channel 7 Using and Adjusting Built in PID Control These are some of the important parameters settings that must be considered when utilizing a drive s built in PID application These parameters control how the error value output changes the drive speed in response to input signal changes and must be adjusted and tuned to meet the requirements and conditions of the installation Use the PID Wizard to assist in initial setup of PID loops MAIN MENU gt QUICK SETUP gt PID MINI WIZARD Carefully read the on line help displayed prior to each parameter setting Note that the engineering unit for inches of water column is designated as in wg Note that the process min and max are the low and high ranges of the input sensor ex 0 5 inches water When selecting the feed back source select the analog input location where the input sensor is wired Be sure that the slide switches next to the display match the signal type voltage or current Error Inversion changes the action of the PID loop Normal Reverse acting typical
4. ltage volts NvoProcessOut 200 0 DC Link Voltage volts Example programming wire sheet nviRstFault_state O DriveReady Boolean Writable Boolean Point Out False ok def Int fl Inte nl SSeS DriveRunning nciNmlFreq Numeric Writable J Oul 57 Hz ok oO nvoProcessOut1 Numeric Point Out true ok EE Boolean Point Out false ok SS Sarees CounterClockwise O Ini nuly Boolean Point Inte fl nciNmlSpeed Numeric Writable TS ne nal ae nviClrCntr_value Oo Numeric Writable into fl finde fl res nviClrCntr_state Boolean Writable Out False ok def into fl Inde nuly EE Out false ok E DriveWarning oO Boolean Point Out False ok EE DriveAtSpeed Boolean Point Out false ok E Honeywell VFD tips 3 02 doc nvoProcessOut3 o Numeric Point Out 0 000 ok aS nvoProcessOut4 Numeric Point Out 0 000 96 ok ES ee nvoProcessOutS o Numeric Point Out 0 000 ok E nvoProcessOut6 o Numeric Point Out 0 000 ok E nvoProcessOut C Numeric Point Out 1 520 9 ok eR NET nvoActFault Numeric Point nvoDrvRunHours o Numeric Point Out 3346 hr ok nvoDrvEnrgy Numeric Point OutputFreq Multipl E Out 0 0 Hz fok Ina 0 ok InB 2 0 ok a OutputSpeed Multipl E Out rpm ok nA 0 ok InB 200 0 ok ae ee A OutputCurrent Inb 20 0 ok
5. mechanical issue and or reduce maximum frequency to prevent faults Change a viewable parameter on the control page display to DC link voltage Quickly reduce motor speed If DC voltage rises motor is acting as a generator than increase the deceleration ramp time parameter Adjust fan speed though all frequencies and verify there is no excessive vibration Use prohibited frequencies feature to avoid resonance vibrations Check for stable operation and functionality of all inputs and outputs Honeywell VFD tips 3 02 doc Page 1 of 3 5 Using Montior display Multimonitor display and Favorites list To change the multimontor view Select MAIN MENU gt MONITOR gt MULTIMONITOR to display 9 values at one time Highlight and select any value to pick an alternate data point from a select list to best fit the application To monitor any point MAIN MENU gt MONITOR Select point group then the point to view then MONITORING To add data to the favorite list Select ADD TO FAVORITES from the points monitor menu Items on the favorite list may be viewed adjusted or removed from the favorite list at MAIN MENU gt FAVORITES 6 Using Internal Time Clock and Time Event Intervals There are 5 separate event intervals that can be defined with each event configured with a unique start and stop time as well as a start and stop day of the week for using the drive schedule functions Configure intervals using MAIN MENU gt PARAMETERS gt TIMER FUNCTIO
6. of pressure control loop Inverted Direct acting typical of a cooling control loop Additional PID Parameters for adjustment can be found under MAIN MENU gt PARAMETERS gt PID CONTROLLER 1 Gain default 100 This is the proportional gain a k a throttling range as a percentage of input If the input is a 0 5 wc sensor a PID Gain of 50 would result in a output value from 0 100 as the input changed 2 5 of wc beyond setpoint Ifa drive is slow to respond reduce this value If a drive hunts for stable control double this value Integral Time default 1 This is the time required to correct the offset between the controlled value and the setpoint This corrects for errors which occur using proportional gain alone Typical values are 100 to 600 seconds If a drive is slow to respond reduce this value If a drive hunts for stable control double this value Derivative Time default 0 The default value of 0 is adequate for almost all HVAC applications Deadband default 0 This is the amount of deviation away from setpoint before the PID loop adjust Set this value above 0 in order to reduce constant speed adjustments and to prevent unstable operation when operating near setpoint Deadband delay default 0 This is the time in seconds that the PID loop will halt before a new adjustment will calculate Set this value above 0 to reduce constant speed adj
7. rive in a clean and dry location until installed Keep the wire length from the drive to the motor as short as possible to reduce interference On new installations do not exceed recommended load cable distances typically 300 lt 2HP 900 gt 2HP If existing cables are used and the drive to load distance exceeds 100 add an external dV dT output filter Provide the proper sized conductors Do not use conductors that exceed the terminal size Provide a proper electrical ground per instructions Failure to do is unsafe and will cause interference It is recommended that the output wires from the drive remain disconnected until after initial startup test 10 Wire I O per application Typical I O control requires both an analog speed control amp digital start stop signal Analog Input 1 2 is the default selection Use either input but not both e Analog input 1 preconfigured as 2 10v or Analog Input 2 preconfigured as 4 20ma e Digital Input 1 is preconfigured as Run start stop clockwise 3 Drive CONFIGURATION Initial power up with drive output wires disconnected 2 3 4 5 6 7 If using the digital display the reset to factory defaults is enabled from the USER SETTINGS gt PARAMETER BACKUP menu Factory Default restarts the configuration wizard If using Drive Care Tool use either a standard Ethernet cable or Honeywell serial adapter cable Use actual motor name plate information for amps and rpm paramete
8. rs when using the startup wizard MAIN MENU gt IO AND HARDWARE gt POWER UNIT SETTINGS gt FAN CONTROL gt FAN STOP may be enabled to allow the VFD cooling fan to cycle on temperature instead of running continuously All motor parameters may be viewed and adjusted from MAIN MENU gt PARAMETERS Double check motor NOMinal parameters match motor nameplate data note CosPhi power factor Edit if necessary Verify PROTECTIONS and AUTO RESET parameters meet application requirements default no auto reset 4 Verify Motor Operation amp Local keypad control note power down to connect motor leads 1 2 3 4 Check for faults A properly configured drive will not generate any fault code during normal operation Use Keypad Local Remote LOC REM button to access local keypad on off amp speed adjust control page If drive without bypass and motor rotates backwards swap the terminal connections of any two of the three drive output wires to reverse If drive with bypass and motor rotates backwards in the drive mode swap the terminal connections of any two of the three drive output wires to reverse If drive with bypass and motor rotates backwards in bypass mode swap the connections of any two of the three main input connections check the drive again and reverse the drive output connections if needed If possible run motor to full speed and verify actual operating current does not exceed name plate current parameter setting Fix
9. ustments and to prevent unstable operation 8 Backup amp restore drive parameters using storage memory in keypad All drive parameters may be copied from the drive s non volitile memory into the keypad s storage memory location for backup amp stored parameters can be copied to a drive from the keypad via user settings menu e MAIN MENU gt USER SETTINGS gt PARAMETER BACKUP gt SAVE TO KEYPAD Honeywell VFD tips 3 02 doc Page 2 of 3 Using Honeywell LON option card notes e Reference the VACON Lon OPTION C 4 LONWORK USER s MANUAL e The option card does NOT include a service pin O Setting the service pin is a software parameter function from the keyboard Some data requires mathematical correction for proper readings Other data point values are defined by individual status bits Common LON data points with correction factors where applicable NvoDrvStatus NvoDrvStatus NvoDrvStatus NvoDrvStatus NvoDrvStatus NovDrvStatus Bit 0 Not Ready 0 Ready 1 Bit 1 Stopped 0 Running 1 Bit 2 Clockwise 0 CounterClockwise 1 Bit 3 No Fault 0 Fault Active 1 Bit 4 No Warning 0 Warning 1 Bit 5 Not at reference speed 0 At reference speed 1 NvoProcessOut1 2 0 Output Frequency Hz NvoProcessOut2 200 0 Output Speed rpm NvoProcessOut3 20 0 Output Current amps NvoProcessOut4 20 0 Motor Torque NvoProcessOut5 20 0 Output Power NovProcessOut6 20 0 Output Vo
Download Pdf Manuals
Related Search
Related Contents
Samsung SGH-Z107 Bruksanvisning E5x70 Generic IT Gopal 7.5 RC1 Content.indd ST9100S – User Guide User Manual FavorPrep Plasmid DNA Extraction Maxi Kit 7300 Series 4 / 8 / 16 Channel User Manual Owner`s Manual - Wilson Trailer Paulmann Cardano AMP-25 AMP-25-EUR ESPECIFICACION DE REQUERIMIENTOS DE SOFTWARE Rockola Questions du questionnaire à l`intention des chauffeurs professionnels Copyright © All rights reserved.
Failed to retrieve file