Contents
1. A current limiting resistor can be used to limit inrush current however the operating characteristics of the ac input circuit will be affected If a 6 8K Q resistor is placed in series with the input the inrush current is reduced to 35 mA In this configuration the minimum on state voltage increases to 92V ac Before adding the resistor in a hazardous environment be sure to consider the operating temperature of the resistor and the temperature limits of the environment The operating temperature of the resistor must remain below the temperature limit of the environment 1762 IN002A US P MicroLogix 1762 IA8 120V ac Input Module Wiring the Finger Safe Terminal Block When wiring the terminal block keep the finger safe cover in place Note Finger safe cover not shown 1 Route the wire under the terminal pressure plate You can use the stripped end of the wire or a spade lug The terminals will accept a 6 35 mm 0 25 in spade lug 2 Tighten the terminal screw making sure the pressure plate secures the wire Recommended torgue when tightening terminal screws is 0 904 Nm 8 in lbs Note If you need to remove the finger safe cover insert a screw driver into one of the sguare wiring holes and gently pry the cover off If you wire the terminal block with the finger safe cover removed you will not be able to put it back on the terminal block because the wires wi
2. Installation Instructions Wy MicroLogix 1762 1A8 120V ac Input Module Inside Deseti pti yeere ta 3 Installation pei onanan an 4 MOUNTING ossein ina EE TY YT Y 5 System Assembly 7 Field Wiring Connections 7 1 0 Memory Mapping 10 Specifications vce 11 Hazardous Location Considerations 13 Environnements dangereux 14 1762 IN002A US P 2 MicroLogix 1762 IA8 120V ac Input Module For More Information For Refer to this Document Pub No nformation on installing wiring and MicroLogix 1200 Programmable 1762 UM001A US P operating a MicroLogix 1200 Controllers User Manual Programmable Controller nstallation guide for the MicroLogix MicroLogix 1200 Programmable 1762 IN006A ML P 1200 Programmable Controller Controllers Installation nstructions nstallation guide for the MicroLogix MicroLogix 1200 Memory 1762 IN001A US P 1200 Memory Module and Real Time Module and or Real Time Clock Clock nstallation Instructions nstallation guide for the 1762 OW8 1762 OW8 Relay Output Module 1762 IN003A US P Discrete Output Module nstallation Instructions nstallation guide for the 1762 1Q8 1762 108 DC Input Module 1762 IN004A US P Discrete Input Module nstallation Instructions nstallation guide for the 1762 IF20F2 1762 IF2OF2 Analog Input 1762 IN005A US P Analog 1 0 Module Output Module Installation nstructions More information on proper wiring and Industrial Aut
3. e can damage integrated circuits or semiconductors if you touch bus connector pins Follow these guidelines when you handle the module Touch a grounded object to discharge static potential Wear an approved wrist strap grounding device Do not touch the bus connector or connector pins Do not touch circuit components inside the module If available use a static safe work station When not in use keep the module in its static shield box Remove Power ATTENTION Remove power before removing or installing this module When you remove or install a module with power applied an electrical arc may occur An electrical arc can cause personal injury or property damage by e sending an erroneous signal to your system s field devices causing unintended machine motion e causing an explosion in a hazardous environment causing permanent damage to the module s circuitry Electrical arcing causes excessive wear to contacts on both the module and its mating connector Worn contacts may create electrical resistance 1 Pollution Degree 2 is an environment where normally only non conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected 2 Over Voltage Category Il is the load level section of the electrical distribution system At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product s insulation Pollution De
4. gree 2 and Over Voltage Category Il are International Electrotechnical Commission IEC designations 1762 IN002A US P MicroLogix 1762 IA8 120V ac Input Module 5 Mounting ATTENTION Do not remove protective debris strip until after the module and all other equipment near the module is mounted and wiring is complete Once wiring is complete and the module is free of debris carefully remove protective debris strip Failure to remove strip before operating can cause overheating Minimum Spacing Maintain spacing from enclosure walls wireways adjacent Side Miraton equipment etc Allow 1200 50 8 mm 2 in of space on all sides for adequate ventilation as shown i lt _ o D Side 1762 1 0 1762 1 0 1762 1 0 Bottom Note 1762 expansion I O may be mounted horizontally only ATTENTION During panel or DIN rail mounting of all devices be sure that all debris metal chips wire strands etc is kept from falling into the module Debris that falls into the module could cause damage when power is applied to the module 1762 IN002A US P 6 MicroLogix 1762 IA8 120V ac Input Module DIN Rail Mounting The module can be mounted using the following DIN rails 35 x 7 5 mm EN 50 022 35 x 7 5 or 35 x 15 mm EN 50 022 35 x 15 Before mounting the module on a DIN rail close the DIN rail latch Press the DIN rail mounting area of the module against the DIN rail The latch will momen
5. ll be in the way Wire Size and Terminal Screw Torgue Each terminal accepts up to two wires with the following restrictions Wire Type Wire Size Terminal Screw Torgue Solid Cu 90 C 194 F 14 to 22 AWG 0 904 Nm 8 in lbs Stranded Cu 90 C 194 F 16 to 22 AWG 0 904 Nm 8 in lbs 1762 IN002A US P 9 10 MicroLogix 1762 IA8 120V ac Input Module I O Memory Mapping Input Data File For each input module the input data file contains the current state of the field input points Bit positions 0 through 7 correspond to input terminals 0 through 7 Bit Position 5 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 007 0000 01010 r r r r r r r r r read only 0 always at a 0 or OFF state Addressing The addressing scheme for 1762 a VO is shown below Data File alor ie Word always zero for this module Y t 0 Bit 0 7 Input gt gt an Bit Delimiter Slot JL Word Delimiter 1 1 0 located on the controller embedded 1 0 is slot 0 1 0 added to the controller expansion 1 0 begins with slot 1 1762 IN002A US P Specifications General Specifications Specification Dimensions MicroLogix 1762 IA8 120V ac Input Module 11 Value 90 mm height x 87 mm depth x 40 mm width height including mounting tabs is 110 mm 3 543 in height x 3 425 in depth x 1 575 in width height including mounting tabs is 4 33 i
6. n Approximate Shipping Weight with carton 209 g 0 46 Ibs Storage Temperature 40 C to 85 C 40 F to 185 F Operating Temperature 0 C to 55 C 32 F to 131 F Operating Humidity 5 to 95 non condensing Operating Altitude 2000 meters 6561 feet Vibration Operating 10 to 500 Hz 5G 0 030 in max peak to peak Shock Operating 30G panel mounted Agency Certification C UL certified under CSA C22 2 No 142 UL 508 listed CE compliant for all applicable directives Hazardous Environment Class Class Division 2 Hazardous Location Groups A B C D UL 1604 C UL under CSA C22 2 No 213 Noise Immunity NEMA standard ICS 2 230 Radiated and Conducted Emissions EN50081 2 Class A Electrical EMC The module has passed testing at the following levels ESD Immunity IEC1000 4 2 4 kV contact 8 kV air 4 KV indirect Radiated Immunity IEC1000 4 3 10 V m 80 to 1000 MHz 80 amplitude modulation 900 MHz keyed carrier Fast Transient Burst IEC1000 4 4 2 KV 5 kHz Surge Immunity IEC1000 4 5 2 KV common mode 1 kV differential mode Conducted Immunity IEC1000 4 6 10V 0 15 to 80 MHzll Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz 1762 IN002A US P 12 MicroLogix 1762 IA8 120V ac Input Module Input Specifications Specificati
7. ockwell International Corporation Printed in the U S A
8. omation Wiring 1770 41 grounding technigues and Grounding Guidelines If you would like a manual you can e download a free electronic version from the internet www ab com micrologix Or www theautomationbookstore com e purchase a printed manual by contacting your local distributor or Rockwell Automation representative visiting www theautomationbookstore com and placing your order calling 1 800 963 9548 USA Canada or 001 330 725 1574 Outside USA Canada 1762 IN002A US P Description MicroLogix 1762 IA8 120V ac Input Module 3 Item la Description upper panel mounting tab 1b lower panel mounting tab 1 0 diagnostic LEDs module door with terminal identification label bus connector with male pins bus connector cover flat ribbon cable with bus connector female pins 7 terminal block 8 DIN rail latch 9 pull loop 1762 IN002A US P 4 MicroLogix 1762 IA8 120V ac Input Module Installation 1762 VO is suitable for use in an industrial environment when installed in accordance with these instructions Specifically this equipment is intended for use in clean dry environments Pollution degree 20 and to circuits not exceeding Over Voltage Category mn IEC 60664 1 Prevent Electrostatic Discharge ATTENTION Electrostatic discharg
9. on 1762 1A8 Voltage Category 100 120V ac Operating Voltage Range 79V ac to 132V ac at 47 Hz to 63 Hz Number of Inputs 8 Bus Current Draw max 50 mA at 5V dc 0 25W Heat Dissipation max 2 0 Total Watts Signal Delay max On Delay 20 0 ms Off Delay 20 0 ms Off State Voltage max 20V ac Off State Current max 2 5 mA On State Voltage min 79V ac min 132V ac max On State Current 5 0 mA min at 79V ac 47 Hz 12 0 mA nominal at 120V ac 60 Hz 16 0 mA max at 132V ac 63 Hz nrush Current max 250 mA Nominal Impedance 12K Q at 50 Hz 10K O at 60 Hz EC Input Compatibility Type 1 Power Supply Distance Rating 6 solated Groups Group 1 inputs 0 to 7 internally connected commons nput Group to Backplane solation Verified by one of the following dielectric tests 1517V ac for 1 sec or 2145V dc for 1 sec 132V ac working voltage IEC Class 2 reinforced insulation Vendor I D Code 1 Product Type Code 7 Product Code 114 1762 IN002A US P MicroLogix 1762 IA8 120V ac Input Module 13 Hazardous Location Considerations This equipment is suitable for use in Class I Division 2 Groups B C D or non hazardous locations only The following ATTENTION statement applies to use in hazardous locations ATTENTION EXPLOSION HAZARD e Substitution of components may impair suitability for Cla
10. ss I Division 2 e Do not replace components or disconnect equipment unless power has been switched off e Do not connect or disconnect components unless power has been switched off e This product must be installed in an enclosure e In Class I Division 2 applications the bus connector must be fully seated and the bus connector cover must be snapped in place e In Class I Division 2 applications all modules must be mounted in direct contact with each other as shown on page 6 If DIN rail mounting is used an end stop must be installed ahead of the controller and after the last 1762 I O module 1762 IN002A US P 14 MicroLogix 1762 IA8 120V ac Input Module Environnements dangereux Cet quipement est con u pour tre utilis dans des environnements de Classe I Division 2 Groupes A B C D ou non dangereux La mise en garde suivante s applique une utilisation dans des environnements dangereux ATTENTION DANGER D EXPLOSION La substitution de composants peut rendre cet quipement impropre une utilisation en environnement de Classe I Division 2 Ne pas remplacer de composants ou d connecter l quipement sans s tre assur que l alimentation est coup e Ne pas connecter ou d connecter des composants sans s tre assur que l alimentation est coup e Ce produit doit tre install dans une armoire Pour les applications de Classe I Division 2 le connecteur de bus doit tre correctemen
11. t install et son couvercle enclench Pour les applications de Classe I Division 2 tous les modules doivent tre install s en contact direct les uns avec les autres comme indiqu page 6 Si on utilise le montage sur rail DIN une but e doit tre plac e l avant de l automate et apr s la derni re unit d E S 1762 1762 IN002A US P MicroLogix 1762 IA8 120V ac Input Module 15 1762 IN002A US P MicroLogix is a trademark of Rockwell Automation M Reach us now at www rockwellautomation com Wherever you need us Rockwell Automation brings together leading brands in industrial automation including Allen Bradley controls Reliance Electric power transmission products Dodge mechanical power transmission components and Rockwell Software Rockwell Automation s unique flexible approach to helping customers achieve a competitive advantage is supported by thousands of authorized partners distributors and system integrators around the world Americas Headquarters 1201 South Second Street Milwaukee WI 53204 USA Tel 1 414 382 2000 Fax 1 414 382 4444 European Headquarters SA NV avenue Herrmann Debroux 46 1160 Brussels Belgium Tel 32 2 663 06 00 Fax 32 2 663 06 40 Asia Pacific Headquarters 27 F Citicorp Centre 18 Whitfield Road Causeway Bay Hong Kong Tel 852 2887 4788 Fax 852 2508 1846 Publication 1762 IN002A US P September 1999 Rockwell Automation PN 40071 070 01 A 1999 R
12. tarily open and lock into place Use DIN rail end anchors Allen Bradley part number 1492 EA35 or 1492 EAH35 for vibration or shock environments End Anchor Note For environments with greater vibration and shock concerns use the panel mounting method described below instead of DIN rail mounting Panel Mounting Use the dimensional template shown below to mount the module The preferred mounting method is to use two M4 or 8 panhead screws per module M3 5 or 6 panhead screws may also be used but a washer may be needed to ensure a good ground current Mounting screws are required on every module For more than 2 modules number of modules 1 x 40 mm 1 58 _ u5 057 Tu he 100 90 3 94 3 54 RER NOTE All dimensions are in mm inches Hole x spacing tolerance i ae or Jv 4 0 4 mm au 0 016 in MicroLogix 1200 Controller MicroLogix 1200 Bgarsion1 MicroLogix 1200 Expersion O 1762 IN002A US P MicroLogix 1762 IA8 120V ac Input Module 7 System Assembly The expansion I O module is attached to the controller or another I O module by means of a flat ribbon cable after mounting as shown below Note Use the pull loop on the connector to disconnect modules Do not pull on the ribbon cable ATTENTION EXPLOSION HAZARD e In Class I Division 2 applications the bus connector must be fully sea
13. ted and the bus connector cover must be snapped in place e In Class I Division 2 applications all modules must be mounted in direct contact with each other as shown on page 6 If DIN rail mounting is used an end stop must be installed ahead of the controller and after the last 1762 I O module Field Wiring Connections Grounding the Module This product is intended to be mounted to a well grounded mounting surface such as a metal panel Additional grounding connections from the module s mounting tabs or DIN rail if used are not required unless the mounting surface cannot be grounded Refer to Industrial Automation Wiring and Grounding Guidelines Allen Bradley publication 1770 4 1 for additional information 1762 IN002A US P 8 MicroLogix 1762 IA8 120V ac Input Module Input Wiring Basic wiring of input devices to the 1762 IA8 is shown below Ll NO ose t x INT IN 2 TT TT o N3 wonzova S IN4 fr a N5 N6 m Ll IN 7 _ AC com Commons are y connected L2 a internally A write on label is provided with the module Mark the identification of each terminal with permanent ink and slide the label back into the door ATTENTION Be careful when stripping wires Wire fragments that fall into a module could cause damage when power is applied Once wiring is complete ensure the module is free of all metal fragments 1
Download Pdf Manuals
Related Search
Related Contents
HQ HQHGU10MR16005 halogen lamp DeLOCK Converter 2,5“ Dale Tiffany PG10361 Instructions / Assembly ESTACION METEO PROFESIONAL WMR Service Manual Bedienungsanleitung - ROMMELSBACHER ElektroHausgeräte 1116 00 05 Rev0 UM Condicionador de Ar Benutzerhandbuch - Native Instruments L`apprentissage, une promesse d`avenir ! poR FaVoR, Lea atentamente todas Las instRUcciones antes de Copyright © All rights reserved.