1. according to the total compressor run time F35 2 The lower load of the cooling system the less often defrosting cycles occur The end of the defrosting cycle comes after passing F33 time In difficult working conditions if there is a need of an additional evaporar defrosting Process can be started manually pressing button fer 5 sec Defrosting diode blinks during the manual defrosting cycle 6 ALARM MESSAGES When alarm activates the indicator e starts blinking and the sound signaller beep will be activated when F83 1 According to the occurence controller turns on off output and the front panel displays one of the following alarm messages Statement Occurence Control output operation Abd Bistate input activation Output inactive e Chamber sensor error Output inactive OPE open circuit SHr short circuit High temperature alarm No influence RLELo Low temperature alarm No influence 7 INSTALLATION Be aware of the conditions where the controller operates Install in a place where there is not too high temperature and humidity and no condensation Should be ventilated in order to remove the heat ATTENTION It is not allowed to work with electric cables when the device is energized You should avoid crossing wires using short connections We recommend securing the source of controller power supply and temperature sensor input against electrical interference 8 MOUNTING Mounting on a DIN rail
2. TS35 50 cm width 3 modules 50 3 mod _ 67 2 89 5 Protection class IP67 6 5 GENERAL DESCRIPTION 5 1 ADJ USTMENT Controller is used to maintain T temperature with desired hysteresis T in cooling or heating devices Actuator control is in progress by the relay output and the temperature measurement is made by the temperature sensor The principle of operation of the temperature control when cooling and heating Temp COOLING iat HEATING a a 6 C 91 fat 1c fat 1c T 5C T 90 C tat 1 C T AT 1 C 4 89 C gt Time gt Time Output Output a A 1 1 0 gt Time 0 gt Time 5 2 TEMPERATURE ALARM You can set upper and lower alarm threshold in controller parameters F15 and F16 parameters after exceeding which the high or low temperature alarm turns on Temp A F15 30 C High temperature alarm F16 10 C Low temperature alarm gt Time Alarm ae A Switching delay F17 0 1min ag 1 0 gt Time The alarm is turned on after the delay time F17 parameter Recommended time setting is 15 minutes so that the alarm does not turn on too often in case of rapid temperature jumps The delay can be reduced to the minimum i e 6 seconds 0 1min if the temperature does not change abruptly The alarm is signalled by internal buzzer or commands on the display high temperatu
3. 31 me F37 Compressor turned on during the defrosting cycle 0 NO 1 YES 0 1 0 3 F50 Digital input D1 0 unused 1 alarm when short circuit 2 alarm when short circuit with maintaince of alarm signalling 0 4 0 i 3 alarm when opened 4 alarm when opened with maintance of alarm signalling igs F80 Password to access the configuration menu OFF password protection inactive F80 0000 no password 0000 9999 OFF F82 Display resolution 0 0 1 C 1 1 C 0 1 0 F83 Sound signalling when an alarm 0 buzzer muted 1 buzzer active 0 1 1 F84 SMART function 0 active 1 inactive 0 1 0 z r You can change temperature quickly using the pointers e F98 Reserved F99 Controller test Disconnect output device to make the test Otherwise the system can crash End Exit the menu
4. 9 WIRING DIAGRAM T1 temperature sensor X D1 digital input 11 112 13 14 15 16 OUT1 l oN Make sure that the electrical parameters of the device correspond to the parameters of the controller maximum voltage and current rating Connection diagram of the heating device for example boiler heater or cooling device fan circulation pump Heating or cooling device IN o L 230VA oN 30VAC 10 ADMISSIONS Controller meets the requirements for immunity to electromagnetic interference in an industrial environment according to the following standards Electromagnetic compatibility EMC EN 61000 part 6 4 requirements for emissivity in an industrial environment EN 61000 part 6 2 requirements for immunity in an industrial environment It also meets the safety requirements according to standard EN 61000 part 1 safety requirements for eletrical devices Controller meets the requirements of EU directives No 72 23 EEC 93 68 EEC 89 336EEC p gum gmg TM evenees i ES 10D TEMPERATURE CONTROLLER Version 3 0 USER MANUAL WARRANTY 1 SPECIFICATIONS Input Measuring range Measuring accuracy Sampling period Display resolution Setting resolution Display Control form Temperature sensor NTC 5Q by 25 C bistate input normal
5. ly opened or normally closed 50 4 150 C 0 5 330 ms 0 1 C in whole range 0 1 C in whole range LED 4 digits 11mm height with graphic icons ON OFF with hysteresis Protection class Ip20 Il Power supply 230V 15 lub 12V max 3VA 5 60 C 0 85 RH non condensing 40 85 C 0 85 RH non condensing Operation conditions Storage conditions 2 OBCIAJALNOSC WYJ SC i Maximum resistive charge Maximum inductive charge Output Relay e g Heater e g Engine By eae 20A 4500W 8A 1500W 2HP 2KM 3 FRONT PANEL temperature display temperature unit indicator M0 entry to the parameters menu temperature setting button value increasing button value decreasing button pressing for more than 5 sec forces defrosting cycle O00 temperature setting signalling cooling output signalling LIGHTS output active BLINKS output waits for start up see F21 heating output signalling LIGHTS output active BLINKS output waits for start up see F21 defrosting signalling LIGHTS automatic defrosting mode BLINKS manual defrosting emergency states signalling BLINKS alarm active 5 4 DEFROSTING for cooling applications Defrosting cycle is performed by the stoppage of the compressor Cycles control is performed automatically and run periodically from time to time F35 1
6. perature value possible to set by the user 50 0 150 0 150 0 C E F14 Minimum temperature value possible to set by the user 50 0 150 0 50 0 G 3 F15 High temperature alarm F15 OFF alarm off 50 0 150 0 OFF C F16 Low temperature alarm F16 OFF alarm off 50 0 150 0 OFF C F17 High and low temperature switching delay 0 1 99 9 15 Minutes F19 Temperature sensor calibration This is the value of rescaling the temperature sensor in relation to actually measured temperature 20 0 20 0 0 0 C E F21 Main output minimal down time It also means the delay time of switching the output on after giving power supply 0 0 10 0 0 0 Minutes a Parameter protects devices e g engine against too frequent switching in case of power failure ei i Z The recommended setting is 3 minutes in cooling system with compressor F29 Control output work mode COOLING HEATING COOL HEAT HEAT F31 F37 parameters for cooling applications w F831 Interval between defrosting cycles 0 1 99 9 12 0 Hours 26 F33 Maximum defrosting cycle length 1 99 30 Minutes E 8 F34 Dripping time of the evaporator after defrosting cycle It is also the delay time of switching the compressor on after defrosting 0 99 5 Minutes Oo g F35 Defrosting cycles control method OFF defrosting off 1 automatically from time to time equals to F31 OFF 1 2 OFF o 2 automatically if the total time of compressor operation reaches the value equal to F
7. r 2 sec and the controller saves the new setting A Remarks press M in any time to cancel the setting the setting change can be limited by F13 and F14 parameters Information To improve quick increasing or decreasing settings values hold or button constantly for at least 1 sec 4 3 PARAMETERS PROGRAMMING Enter the menu pressing If the access to the menu ea M button for 5 sec Until is protected press button to cancel the parameter setting command command displays information displays y ey Using 5J and Hold A or J button for at least 1 sec to improve quick increasing and decreasing of setting rt 4 buttons enter the values password and confirm with set eT Using or button Mr Using or button tot choose the parameter LU st the desirad you want to change and enter with key parameter value A T E 3 nm Using set key confirm roe Finish programming LIL the new parameter rete pressing button or value and return to the enter the a ie NN parameter list and press the set key b or wait 30 sec without pressing any button 4 3 DESCRIPTION OF THE PARAMETERS Group Code Description Range Default Units F11 Temperature setting value Range of changes is limited by the F14 and F13 parameters F14 F13 0 0 C fe F12 Hysteresis temperature control accuracy 0 1 20 0 1 0 C 5 F13 Maximum tem
8. re alarm low temperature alarm Buzzer can be muted by pushing any button lub turned off permanently in F83 parameter 5 3 DIGITAL INPUT Controller has digital input D1 for emergency states signalling for example system failure pressure control or safety thermostat activation etc Input type normally opened normally closed is programmed by F50 parameter After input activation the controller turns off the outputs turns on the beeper and the display indicates AL d1 code Emergency state sound signalling can be maintained until the alarm reset by using the buttons F50 2 or 4 4 CONTROLLER HANDLING 4 1 TEMPERATURE SETTING Using J or set the desired temperature Press set button CHA for 2 seconds Diode lights up Confirm the set with set g 5 g Button siz set Diode goes off Remarks press M button in any time to cancel the setting the setting change can be limited by F13 and F14 parameters Information To improve quick increasing or decreasing the settings values hold the or button constantly for at least 1 sec 4 2 TEMPERATURE SETTING when the SMART function is active parameter F 84 1 Smart function allows for rapid temperature change with no need of pushing the SET button It is a very useful function for users who often change temperatures J gg Set the temperature by or pointer in any time Diode goes off afte
Download Pdf Manuals
Related Search
Related Contents
Fiches Contact Introduction to the EZ Lite Cruiser DECLARATION DE CONFORMITE CE Eminent EM8021 取扱説明書 - Panasonic VADT/VADR4900WDM A & E User Manual - big StarTech.com 1 Port RS232 Serial to IP Ethernet Converter / Device Server - Aluminum Mode d`emploi NuTone CK230 User's Manual Copyright © All rights reserved.