Home
IEI HubMax/HubMax II Install
Contents
1. H m3 A Power Limited Non Power Power Limited Limited Page 8 of 48 1 HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 2 3 Lithium Battery Replacement The lithium battery used for keeping the time and date is located on the left hand side of the Door Control Module above the relay K2 The battery holder is labeled BH1 To replace the battery first power down the module using the On Off switch SW1 SW4 located on the backplane Then remove the battery carefully by lifting up the bottom edge and pull it out of the clip Replace the battery with a Renata CR1225 or Varta CR1225 3 Volt Lithium battery Use of another battery may present a risk of fire or explosion WARNING The battery may explode if mistreated Do not recharge disassemble or dispose of in a fire Page 9 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 3 0 Installation This section contains detailed unpacking and installation procedures and wiring diagrams for the IEI HubMax HubMax Il Access Control System This section is presented as steps and should be followed in the order indicated Not all steps are necessary for every application Note Programming commands are inserted into the installation procedure for your convenience Progr
2. 16 5VAC Class 2 Transformer LOAD All terminal blocks are removable for easy wiring Page 32 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 14 Power up the System Plug the transformer into a grounded 110 VAC electrical outlet You should now have power to your system Check the power status by checking the following On the HubMax Backplane e LED 5 should be lit This indicates that AC Power is present e LED 2 should be lit This indicates that DC Power is available on the Backplane On the Hub Door Control Module e LED 2 should be lit This indicates that the HubMax Module is receiving power e LED 3 should be lit This indicates that the Front End Reader is receiving power If the above requirements are met the system is now powered up and ready for programming and operation If the above requirements are not met see the Troubleshooting Section below Troubleshooting HubMax Backplane Symptom Probable Solution LED 5 is not lit 1 2 Disconnect the transformer from the Backplane and read the AC output Verify the AC output from the transformer is 16 5 VAC If the transformer reads 16 5 VAC and LED 5 is not lit Unplug the transformer from the electrical outlet Reconnect the transformer to the Backplane Confirm you have solid connections on the TS2 Terminal Block Plug tra
3. 4 Conductor Stranded Shielded cable with overall foil shield Drain Wire Connect to fast tab on HubMax backplane 250 Ft 22AWG 500 Ft 20AWG NOTE 1000 Ft 18AWG These products have NOT been evaluated b Uu y nium BLK BLK RED to RED sw2 WHT BLK to WHT BLK lt In Out Selection WHT YEL to WHT YEL NOTE This product has NOT been evaluated by On Both Pins OUT ULL On One Pin IN Models To Hub Door Control Module PROXPOINT Se PROXPRO SQ NOTE This product has PROXPRO with Keypad MINIPROX THINLINE 1 MAXIPROX NOTE These products are U L Listed On Both Pins OUT On One Pin IN Drain Wire Connect to fast tab on HubMax backplane Wire Color to Color 4 Conductor Stranded Shielded cable with overall foil shield 250 Ft 22AWG 500 Ft 20AWG 1000 Ft 18AWG Connection Red to POS Black to NEG Wht Black to DI Wht Yellow to DO 4C Stranded Shielded Cable 250 22AWG 500 20 AWG 1000 18AWG NOT been evaluated by U L Drain Wire Connect to fast tab on HubMax backplane Wb bs To Hub Door Control Module LED 3 LED 2 LED 1 Page 15 of 48 HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 www ieib com Wiring to Front End Readers SSWFX 6 Conductor Wire Harness IN OUT LOGGING I
4. Event Numbers are listed below next to the corresponding Event Name 1 Record 0 Do Not Record Event Name Event Event Name Number Access Denied Print Program Denied In User Entered Program Mode Out User Egress Request to Exit REX Bad Timezone Door Ajar Toggle On Door Closed Toggle Off Forced Door First In Auto Unlock Log Erased Relock Page 39 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 4 4 Printing the Transaction Log Printing the Transaction Log list of events recorded in chronological order can be accomplished in two ways 1 Entering a DUMP USER code or token 2 Putting the Hub Door Control Module into Programming Mode and entering the command to print the Transaction Log 1 Commands for programming for a dump code or card pet w ek Enter Program Mode 99 Master Code Assign LOG DUMP code 2 User Location 4 New Code New Code Assign LOG DUMP token 2 User Location Swipe Token at Reader Sa v t R Exit Program Mode To use a DUMP USER to print the Transaction Log e Ifthe DUMP USER is a code it can be entered at either the Hub Door Control Module programming keypad or a keypad Front End Reader e fthe Dump User is a card it can only be used at the Front End Reader 2 Print the Transaction log without a DUMP USER
5. Unlock Page 42 of 48 HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 www ieib com Programming Options Chart continued To Enter Programming Mode Enter 99 Master Code To Exit Programming Mode Enter 24 Disable 1 IN Auto Unlock 25 Enable Remote Access Disable Remote Access 31 07 0 31 08 1 31 08 0 31349 4 134 x Duress uses the Door Ajar relay Disable Duress 31 4 9 4 0 4 Select Modem String HubModem 35 2 0 Select Modem String Boca 14 4 only Enable Print Live 31 10 1 Disable Print Live 31 10 0 Enable Log Almost 31 11 1 Full Warning Disable Log Almost Full Warning Enable Duress 31 11 0 31 12 1 Panic uses the Door Ajar relay 36 Disable Panic 31 12 0 Note Options 16 17 below only available in the HubMax II controller 37 Enable Daylight Savings Time 31 16 0 k 38 Disable Daylight Savings Time 39 Select US DST Format 40 Select European DST 31 17 1 Format Note Commands 20 21 and 29 below are not supported in the HubMax II controller 41 Sy Controller to 29 0 0 eceive Data 42 Send a Range of 20 FFF LLL k Users FFF First User Location LLL Last User Location 21 0 0 KX P Ona AN Data Sends all users and doo
6. 3 4 D4b Fax Document Number 5034 www ieib com Wiring to Front End Readers Prox pad proximity keypad Model Number 0205676 UL B 4 Conductor Stranded Shielded Cable UP TO 250 22 AWG UP TP 500 20 AWG UP TO 1000 18 AWG To Hub Door Control Module TI 00000 000000 P3 P OO 00 ooo mu 2000 Foil Shield mW Drain Wire must be terminated to the Drain Wire Fast Tab Connections Wire Harness Wire Color Front End Terminal Block Black Black P 1 Red Red P3 Green White Black White White Yellow NOTE This product is U L Listed Page 18 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 7 Wire a Request to Exit REX device and Door Contact to the Hub Door Control Module Hub Door NOTE EZ Touch not Control Module evaluated by U L Door contacts must be U L Listed NOTE Use stranded wire with overall foil Remove Loop shield for the REX and dd di Door Contact cables contacts Connect the drain with to the fast tab on the Place on one pin backplane so it doesn t get Normally Open Exit Device Example Used Normally Closed IEI Part EZ Touch Magnetic Door Contact During installation it will be easier to distinguish between terminal blocks if you label them first REX This is a NORMALLY OPEN loop when momentarily cl
7. Action Press Enter the Programming Mode 99 Master Code k Print the Transaction Log 70 0 0 After Print is complete Exit the Program Mode After the Transaction Log has been printed it may be desirable to erase the Event Buffer Action Press Programming Mode press 99 Master Code Erase the Event Buffer 4 4 5 Printing a User List After Print is complete Exit the Program Mode 76 00000 00000 It is possible to print the USER LIST of the Hub Door Control Module This printout contains the USER LOCATION and USER CODE or encoded USER TOKEN associated with it Action Press Enter the Programming Mode press 99 Master Code Print USER LIST command 25 0 0 After Print is complete Exit the Program Mode Page 40 of 48 www ieib com HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 5 Programming Daylight Savings Time Note This feature is only available in the HubMax II The Hub DCM supports Daylight Savings Time which can be enabled or disabled by using the commands below Daylight Savings Time is enabled by default Action Press Enter Program Mode 99 master code Disable Daylight Savings Time 31 16 1 OR Enable Daylight Savings Time 31 16 0 Exit Program Mode
8. Users 500 HubMax 2000 HubMax Il Base Capacity Supports 1 4 Hub Door Control Modules Controls 1 4 Doors Additional Capability Network up to 32 doors with additional Secured Series Door Control Products Audit Trail 1000 Transaction Buffered Audit Trail HubMax 1500 Transaction Buffered Audit Trail HubMax 11 Front End Support Each Hub Door Control Module supports two front end readers for IN OUT operation Programming Hub Door Control Module support keypad or PC programming Auto Unlock Time Zones 9 00 A M to 5 00 P M Monday Friday Eight user definable time zones for auto unlock or access control Sixteen holiday time zones First In Auto Unlock Requires valid entry to initiate auto unlock schedule Remote accessible via modem Forced Door Alarm Relay Timer Alarm Zone Shunting Relay Timed Egress Input Non Volatile EEPROM Memory Indicates a feature is only available using software 1 2 Specifications Electrical Power Supply 16 5VAC 40VA or 50VA Class 2 Transformer Revere RT G1640SL M Revere RT G1650SL M or Globtek Inc DA 40 16 5G Current Requirements 100mA backplane with one module Add 40mA for each DCM Front End 13 8 VDC 300 mA max current draw Main Relay 12 24 VAC DC 2A max contact current Alarm Shunt Door Ajar and Forced Door Relays 12 24 VAC DC 1A max contact current REX Door Loop
9. www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 11B Connecting a Serial Line Printer to the HubMax HubMax II Backplane lelelelelelele ogcooogogog oocogogogg oocogogogg e eee KD exe Male DB 25 Connector not included To Female DB 25 Connector on back of serial line printer Connections Wiring Requirements IEI recommends 4 different serial line printers Wire 4 Conductor Stranded Shielded The printers are identified along with their cable between Port A terminals and wiring and programming instructions on the DB25 Connector next page Port A to DB25 Dist to AWG GND Pin 7 1000 18 AO Pin 2 250 22 Pin 3 500 20 Page 25 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Wiring and Programming serial line printers for use with the HubMax IEI recommends the following four serial line printers Epson LQ300 Okidata 184 Microline Citizen GSX 190 Okidata 320 Turbo Note All interconnecting devices must be U L Listed Epson LQ300 or the Citizen GSX 190 Wiring Programming Program the printer so the following settings are active Follow the wiring instructions on the e Serial Mode 1200 baud
10. Dry contact closure Mechanical HubMax Enclosure Height Width Length Material Environmental Temperature Tolerance Surface mount 4 25 10 8cm 19 5 49 5 cm 16 5 41 9 cm 19 gauge steel 20 F to 130 F 28 C to 54 Recommended Use For indoor use only 1 3 System Defaults www ieib com Page 4 of 48 HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Parameter Default Setting Master Code 1234 Main Relay Time 5 Seconds Door Ajar Time 30 Seconds Forced Door Time 10 Seconds Printer Output RS 232 Port Keypress Feedback Enabled Door Number 01 First In Auto Unlock Off Auto Unlock Time Zone Without software 9 A M to 5 P M Monday through Friday Key required to active relay after entering valid code On Communication Setup Local Daylight Savings Time Enabled Daylight Savings Time Format US 1 4 Hub Door Control Module Diagram The diagram below shows the component locations and terminal connections on the Hub Door Control Module Hub Door Control Module Program Mode Main Relay Status Red De Energized Green Energized OLED1 Yellow OLED4 Bi Color Programming gt Switch a sw pr oQ Es Main Alarm Door Relay Shunt Ajar Keypad 52 Tech During installation it w
11. The Hub DCM can also be programmed for either US or European Daylight Savings Time format To select the format use the commands below Action Press Enter Program Mode 99 master code k Select US Daylight Savings Time Format 31 3 17 0 4 Select European Daylight Savings Time Format 31 17 1 Exit Program Mode The US and European Daylight Savings Time formats are described below Page 41 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 5 0 Programming Options Chart The following chart is provided as a quick reference to experienced programmers Explanations of these programming commands are available in Section 4 of this manual To ENTER Programming Mode Press To EXIT Programming Mode 99 master code Press Action Desired Press Enter Program Mode 99 Master Code Must be entered prior to any programming Default master code is 1234 Exit Program Mode Must be entered when programming is finished Change Master Code and Main Relay Time Relay Time 1 New Code New Code Relay Time must be a two digit number from 01 90 seconds Example 10 1 4321 4321 Sets the relay time to 10 seconds and changes master code to 4321 Adding Users Notes User Location is the number of the memory slot the user is to occupy HubMax User 2 to
12. previous page e 8DataBits e 1StopBit e Auto Line Feed is enabled Okidata 184 Microline Wiring Programming In addition to the wiring instructions Dip Switch Settings on Dip Switch Settings on the serial card on the previous page short these the mother board pins on the Male DB 25 Connector Bank1 Bank 1 2 3 4 8 OFF ShortPin 20 to Pin 6 5 e Short Pin 4 to Pin 5 e 5 6 7 ON Not Used Okidata 320 Turbo Wiring Programming In addition to the wiring instructions Program the printer so the following settings are active on the previous page short these pins on the Male DB 25 connector Serial Mode 1200 baud 8 Data Bits 1 Stop Bit Auto Line Feed is enabled e ShortPin 20 to Pin 6 e Short Pin 4 to Pin 5 To Print 1 Enter your DUMP CODE if programmed or present your DUMP TOKEN if programmed 2 If you don t have a DUMP CODE or TOKEN you must either program one or e Put the Hub Door Control Module into Program Mode 99 MASTER CODE e Enter PRINT TRANSACTION LOG 25 0 0 or PRINT USER LIST 70 0 0 commands Once you have performed either option A or B the bi color LED on the Hub Door Control Module starts alternating RED GREEN The contents of the Transaction Log Buffer then start printing out on the printer You can also set the Hub Door Control Module to PRINT LIVE When this feature is enabled the Hub Door Control Module sends events to the printer as the
13. supplied 12B Networking HubMax Backplanes Method 2 Door 1 Door 2 Door 3 Door 4 METHOD 2 If HubMax units are greater than 6 feet of each other use a 3 Conductor Stranded Shielded cable to connect from the Port C screw terminal block of the first HubMax to Port A screw terminal block of the second HubMax Page 29 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Wiring Requirements 4 conductor stranded shielded cable between Hub MiniMax and HubMax 12C Networking Hub MiniMax to HubMax 250 22AWG 500 20AWG 1000 18AWG Connections Hub MiniMax TS1 HubMax TS1 Terminal Block Terminal Block GND Terminal GND Terminal TX Terminal AO Terminal RX Terminal A1 Terminal 12D Networking HubMax to Hub MiniMax Door 2 Door 3 Connections HubMax TS1 Hub MiniMax TS1 Terminal Block Terminal Block GND Terminal GND Terminal TX Terminal AO Terminal RX Terminal A1 Terminal Page 30 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Wiring Requirements 4 conductor stranded shielded cable between HubPlus Kit and HubMax 250 22AWG 500 20AWG 1000 18AWG 12E Networking HubPlus Kit to HubMax Connections HubPlus Kit
14. 500 HubMax Il User 2 to 2000 Token refers to access media mag card prox card prox key or touch chip Code Only User Location New Code Repeat New Code Token Only User Location Swipe Token at Reader Head Code and Token User Location New Code Repeat New Code Swipe Code or Token 52 1 User Location New Code Repeat New Code Swipe sequentially adang 53 1 Starting User Location Swipe Tokens at Reader Head users Token Only gle the Main Relay Add Change Users to To 00 User Location New Code New Code 9 Code Only 00 User Location Swipe Token at Reader Head 10 Token Only 00 User Location New Code New Code Swipe 11 Code and Token 12 Code or Token 52 00 User Location New Code New Code Swipe Deleting Information 13 Delete User User Location 14 Reset System Defaults Only 46 0 0 Erase Entire Unit and Reset Defaults 46 00000 00000 k Delete Transaction 76 00000 00000 Log Buffer Programming System Options Select IR LED 31 03 0 Select RS 232 Port 31 03 1 Enable Time Zone 31 04 1 Disable Time Zone 31 04 0 k Enable Auto Unlock 31 05 1 Disable Auto Unlock 31 05 4 0 st Enable 1 IN Auto 31 07 481 S
15. Door Control Modules are purchased for this system they must be inserted into the remaining ports in the following order Hub Door Control Module Additional modules sold separately e e e e e e e o N googooogog bod n 0 C 0 EE DOD MODULE 2 ON OFF MODULE 1 ON OFF WW m3 m3 E T MODULE 3 ON OFF MODULE 4 ON OFF 8 install additional Door Control Modules Slide the Door Control Module onto the pin rail marked Px x Expansion Port Example P2 located on the HubMax backplane Align the 3 holes in the Door Control Module with the standoffs mounted on the backplane Gently press down on the Module to snap it on onto the standoffs Turn the Module Power Switch located on the backplane to ON Page 12 of 48 www ieib com HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 5 Wire an electric door lock to the MAIN RELAY of the Hub Door Control Module 0 NOTE All locking devices must U L Listed 0 MAIN RELAY Terminal Block NOTE All four relays Mai
16. HUBMAx Il BACKPLANE STEP 12 NETWORK THE HUBMAX HUBMAx II 12A NETWORKING HUBMAX BACKPLANES METHOD 1 12B NETWORKING HUBMAX BACKPLANES METHOD 2 12C NETWORKING HUB MINIMAX TO HUBMAX 12D NETWORKING TO HUB MINIMAX 12E NETWORKING HuBPLus KIT HUBMAX 12F NETWORKING HUBPLUs KIT STEP 13 COMPLETE CONNECTIONS BETWEEN THE 16 5 VAC TRANSFORMER AND HUBMAX 32 STEP 14 POWER UP THE SYSTEM TROUBLESHOOTING 4 0 PROGRAMMING THE HUBMAX HUBMAX II Page 2 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 1 PROGRAMMING METHODS 4 2 PROGRAMMING FEATURES 4 3 SENDING INFORMATION BETWEEN NETWORKED HUB DOOR CONTROLLERS 4 4 PRINTING THE TRANSACTION LOG AND USER LIST 4 4 1 SELECTING THE PRINTING OUTPUT PORT 4 4 2 SETTING THE TIME DATE AND DOOR NUMBER 4 4 3 SETTING MASKING EVENTS FOR LOGGING IN EVENT BUFFER 4 4 4 PRINTING THE TRANSACTION LOG 4 4 5 PRINTING A USER LIST 4 5 PROGRAMMING DAYLIGHT SAVINGS TIME 5 0 PROGRAMMING OPTIONS CHART 6 0 DEFINITIONS OF TERMS AND HUBMAX FUNCTIONS 7 0 WARRANTY Page 3 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 1 0 System Features and Specifications The following section outlines the HubMax HubMax Il features specifications and default settings 1 1 System Features Feature Description Details
17. HubMax TS1 Port C Terminal Block Green Terminal _____ GND Terminal Blue Terminal amp 4 Terminal Gray Terminal lt gt Terminal 12F Networking HubMax to HubPlus Kit Door 1 Door 2 Door 3 Door 4 Connections HubMax TS1 Hubplus Kit Terminal Block Port A GND Terminal 44 y Green Terminal TX Terminal r Blue Terminal Terminal Gray Terminal Page 31 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 13 Complete connections between the 16 5 VAC transformer and HubMax Connect the 16 5 VAC Transformer included with the HubMax to the Backplane at the terminals marked AC Provided with the HubMax are Backup Battery Connection Cables Connect these cables from your 12V battery Recommended to the HubMax Backplane at the terminals marked B and B Polarity is an issue Be sure you know which battery terminals are positive and negative BEFORE you connect your battery to the HubMax Backplane ererere fefe e e lelelelelelelelele I DO mem DOOS m DOO l
18. HubMax is controlling a door that is monitored by an external alarm system No programming is required The Hub Door Control Module energizes both the Main Relay and Alarm Shunt Relay with any valid access or egress The Alarm Shunt Relay is used to shunt the door contact wired to the external alarm system The door may now be opened without triggering the external alarm The Alarm Shunt Relay remains energized until the door is closed The Alarm Shunt Relay de energizes one second after the door is closed This Relay is rated to handle 1 Amp of current at either 12 or 24 Volts AC DC NOTE This feature requires that you wire a DEDICATED door position switch to the Hub Door Control Module per diagram also REMOVE Loop Jumper JP1 Ld Hub Door Q Control Module Remove Loop Tech Tip Jumper JP1 During when using door Installation it will contacts be easier to distinguish Place on one pin between terminal so it doesn t get blocks if you lost label them first Normally Closed Magnetic Door Contact DEDICATED Normally Closed Magnetic Door Contact DEDICATED Page 20 of 48 1 HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 9 Wire the Door Ajar Relay This output alerts personnel that the door is being held or propped open after a valid access or egress To accomplish this the Hub Door Control Module comes equippe
19. IEI HubMax HubMax II Installation Programming Manual www ieib com Document Number 6065034 Rev 3 4 Manual Revision Date 3 2 05 HubMax Firmware Revision U2 1 0p U10 1 1F HubMax II Firmware Revision U2 2 0a 010 2 36 Fax Document Number 5034 Page 1 of 48 HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 1 0 SYSTEM FEATURES AND SPECIFICATIONS 1 1 SYSTEM FEATURES 1 2 SPECIFICATIONS 1 3 SYSTEM DEFAULTS 1 4 HUB DOOR CONTROL MODULE DIAGRAM 1 5 II BACKPLANE DIAGRAM 2 0 UL REQUIREMENTS 2 1 TAMPER REQUIREMENTS 2 2 POWER AND NON POWER LIMITED WIRING 2 3 LITHIUM BATTERY REPLACEMENT 3 0 INSTALLATION STEP 1 UNPACK THE II AND CHECK THE PACKING LIST STEP 2 MOUNT THE HUBMAX HUBMAx Il ENCLOSURE STEP 3 GROUND THE HUBMAX HUBMAx II STEP 4 CONNECT ADDITIONAL HUB DOOR CONTROL MODULE TO THE BACKPLANE STEP 5 WIRE AN ELECTRIC DOOR LOCK TO THE MAIN RELAY oF THE HUB DOOR CONTROL MODULE STEP 6 CONNECT A FRONT END READER TO THE HUB DOOR CONTROL MODULE STEP 7 WIRE A REQUEST TO EXIT REX DEVICE AND DOOR CONTACT TO THE HUB DOOR CONTROL MODULE STEP 8 WIRE THE ALARM SHUNT RELAY STEP 9 WIRE THE DOOR AJAR RELAY STEP 10 WIRE THE FORCED DOOR RELAY STEP 11 CONFIGURE THE II TO PRINT 11A PRINTING FROM HUBMAX USING HANDHELD INFRARED PRINTER 11B CONNECTING A SERIAL LINE PRINTER TO THE HUBMAX
20. Max System is designed to be wall mounted surface mounted with the supplied hardware The system must be installed within the protected area in accordance with the National Electrical Code NFPA 70 local codes and the authority having jurisdiction It should also be located in an area that is accessible for programming purposes After the installation is complete the HubMax cabinet door should remain closed and locked to protect the contents For additional information see illustration drawing 6225034 Rev 2 2 dated 3 2 05 located on the inside of the cabinet door In addition all other interconnecting devices must be U L Listed A minimum of three 3 user codes must be programmed for controlling access Note The modem interface was not evaluated by U L The Panic and Duress functions also were not evaluated by U L The PC software is only used for downloading and uploading data The PC does not make access control decisions or monitor the door 2 1 Tamper Requirements To meet U L requirements a U L Listed tamper switch must be installed in the cabinet of HubMax systems The tamper switch must be mounted inside the locked cabinet and must activate if the cabinet door is opened The tamper switch must be wired to an alarm panel or other device that sounds an alarm and or prevents anyone from gaining access through the protected door IEI recommends using a Sentrol 3012 tamper switch not provided To use this tamper switch simpl
21. Pres 99 Master Code Select IR Port 31 03 0 OR el Select RS 232 Port 31 03 1 Exit Program Mode 4 4 2 Setting the Time Date and Door Number To enable the accurate recording of the events that occur at a door the TIME DATE and the DOOR NUMBER must be programmed into the Hub Door Control Module Action Press Enter Program Mode 99 Master Code Set TIME in real time clock 44 HHMM 0 HHMM Hours and Minutes in 24 hour format Military Time Set DATE in real time clock 42 MMDDYY Day of Week MMDDYY Month Day and Year all in two digit numbers Day of Week Sunday 1 Monday 2 Tuesday 3 Set DOOR NUMBER 43 0 DN DN a double digit number from 01 to 32 Exit Program Mode Page 38 of 48 1e HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 4 3 Setting Masking Events for logging in Event Buffer This option enables you to select which events you want to record in the Event Buffer This eliminates the possibility of the log filling up with events that have no bearing on your needs Enter these commands on the Hub Door Control Module keypad to select the events Action Press Enter Program Mode 99 Master Code Disable Enable recording of an 73 Event Number 0 1 Event Exit Program Mode
22. S Brown and Blue wires are not used PROGRAMMABLE SEE SSWFX MANUAL FOR PROCEDURE 4 Conductor Stranded Shielded Cable UP TO 250 22 AWG UP 500 20 AWG UP TO 1000 18 AWG To Hub Door Control Connections Four Conductor Front End Drain Wire Wire Harness Terminal Block Black Black terminated Red Red to the Drain White Black White Black ae Fast White Yellow White Yellow ab NOTE This product has NOT been evaluated by U L Page 16 of 48 1 HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Wiring to Front End Readers KP500XT and KP500MP KP500XT KP500MP IN OUT LOGGING Not available on KP500XT 4 Conductor Stranded Shielded Cable UP TO 250 22 AWG UP 500 20 AWG UP TO 1000 18 AWG Connections Four Conductor Wire Harness Front End Terminal Block Black Red White Black White Yellow Black Red White Black White Yellow To Hub Door Control Module Drain Wire must be terminated to the Drain Wire Fast Tab To Hub Door Control Module IN OUT LOGGING See KP500MP instructions for details Drain Wire must be terminated to the Drain Wire Fast Tab NOTE These NOTE These products have NOT been evaluated by UL have NOT been evaluated by U L Page 17 of 48 HubMax Installation Programming Manual Document 6065034 Rev
23. amming should only be done after all electrical connections are made and the system is powered up in step 13 Step 1 Unpack the HubMax HubMax Il and Check the Packing List Open the box and inside is a metal enclosure The metal enclosure has a removable lid so the installer has easier access when wiring Inside the metal enclosure is 1 HubMax Backplane mounted on standoffs 1 16 5VAC Transformer see section 1 2 for approved transformers 1 Camlock with key 1 Hardware Pack containing o 4 Wire nuts ORANGE 4 Wall anchors BLUE 4 8 114 sheet metal screws 1 Set of battery cables BLACK AND RED 4 Ground cables BLACK wire with RED flush tab receptacle one per Hub Door Control Module Port 1 Hub Door Control Module 1 detachable keypad for programming Pre mounted to Hub Door Control Module 1 Secured Series Software Package 1 Secured Series HubMax HubMax II Installation and Programming Manual Please check the contents of the enclosure and verify all components on the packing list are present Taking this inventory will familiarize you with the components as well as ensure you have a complete kit Step 2 Mount the HubMax HubMax II Enclosure The HubMax enclosure must be mounted on the secured side of the door and must not be used as an access device as a means of gaining access or egress through the door Ideally the enclosure should be mounted in a secure area such as a locked utility closet However this is not always available so w
24. annot stress enough the importance of completely grounding the HubMax before making any connections or even touching the Backplane the large circuit board in the enclosure Wire as shown and plug the transformer into a grounded electrical socket Hub Door Control Module HubMax Backplane oogoogog D D ejejejaje eje e e e 919191999900 EB e pod ra o ofo i u 013 16 5VAC Class 2 Transformer Do not make any AC Power connections until Step 13 of the installation GND LOAD All terminal blocks are removable for easy wiring TOUCH THE GROUNDED METAL CABINET BEFORE TOUCHING THE BACKPLANE OR THE HUBMAX CONTROL MODULE THIS WILL REMOVE ANY STATIC CHARGE ON YOUR PERSON STATIC ELECTRICITY CAN DAMAGE THE ELECTRONIC COMPONENTS USED ON THE CONTROLLERS Page 11 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 4 Connect Additional Hub Door Control Module to the Backplane The HubMax HubMax Il backplane has 4 expansion ports for Hub Door Control Modules Provided with the HubMax is one Hub Door Control Module which is installed into port 1 of the Backplane If additional Hub
25. commands to record or mask an event are located in section 4 4 3 It is also possible to print a list of the Users programmed into a Hub Door Control Module See section 4 4 5 The Transaction Log Audit Trail and User List can also be accessed using the Secured Series Software to print with a computer Please see the Secured Series Software Manual for this information Programming the DOOR NUMBER into the Hub Door Control Module When a Hub Door Control Module is networked with other door controllers HubMax HubMax II MiniMax MiniMax II HubPlus Kits or stand alone Hubs you need to program a unique DOOR NUMBER for each door controller Without a DOOR NUMBER the network will not communicate to either a printer or a PC A DOOR NUMBER should be programmed into each Hub Door Control Module even when not networked to other door controllers The DOOR NUMBER prints out on the transaction log so you can distinguish which door was accessed Every Secured Series Controller is factory set to DOOR 01 Programming Procedure Action Press Enter Program Mode 99 Master Code Set Door Number 43 0 4 DN DN DOOR NUMBER which must be in a two digit format Door 1 01 Door 2 02 Door 32 32 Exit Program Mode If you are networking two HubMax Backplanes the Hub Door Control Module in Port 1 of the second HubMax Backplane must be programmed as DOOR 5 Page 23 of 48 ie HubMax Installation Programming Man
26. d line cannot be through a PBX system The HubMax Backplane has eight position pin rail labeled S1 designed to plug an IEI modem onto it The pin rail is located on the top of the PCB above module 1 see diagram in section 1 5 The modem board has a corresponding connector mounted on the bottom side of the board so the components are facing away from the module when connected It is then supported by two card guides on both ends that snap into holes in the Backplane The pin rail makes all the connections necessary for the modem to operate and no additional wiring is needed You just need to connect the phone line The ON OFF switch on the Backplane also controls power to the modem connector For instructions and diagrams to connect the HubModem Kit to the HubMax consult the Secured Series HubModem Installation Guide Document 6060551 which is included in the Secured Series HubModem Kit Before the HubModem Kit became available IEI specified the Boca 14 4 for use at the HubMax which is no longer available but since there may still be units out there this manual covers all the programming commands used with the Boca 14 4 To enable remote communication on the HubMax you must first enable Remote Access then Select the Modem String in Hub Door Control Module 1 WActionza press Tech Note When connecting the IE Enter Program Mode 99 Master Code Secured Series HubModem Kit to a ee network of two or m
27. d with a relay and internal timer circuit Once the door has been opened with a valid access or egress the Hub Door Control Module begins to count until the door closes The DOOR AJAR RELAY energizes if the amount of time the door is open exceeds the DOOR AJAR TIME programmed into it the Hub Door Control Module Kit The alarm then sounds continuously until the door is closed The DOOR AJAR RELAY can be used to switch power to an alarm device i e horn strobe This Relay is rated to handle 1 Amp of current at either 12 or 24 Volts AC DC Alarm device s are not included with equipment NOTE This feature requires that you wire a DEDICATED door position switch to the Hub Door Control Module per diagram also REMOVE the Loop Jumper JP1 Hub Door Control Module Remove Loop Tech Tip Jumper JP1 During when using door installation it will contacts be easier to distinguish Place on one pin between terminal so it doesn t get blocks if you label them first Normally Closed Magnetic Door Contact DEDICATED Alarm Device Example Switching the positive leg of power to an alarm device V V Programming the DOOR AJAR TIME default DOOR AJAR TIME is 30 seconds Door Ajar is the length of time the door can remain open after an authorized access egress before the Door Ajar relay energizes Action Press Enter Program Mode 99 Master Code P
28. der The connection between the Hub Door Control Module and the Front End Reader is made with four conductor stranded with overall foil shield type cable not included You must use this type of cable to ensure signal integrity After you have made your connection it is also vital to terminate the drain wire of the cable The drain wire is a bare wire that runs the entire length of the cable inside the shield and along side the other four conductors This drain wire is to be terminated at the fast tab located on the HubMax Backplane beneath the Door Control Module Each Module Port on the Backplane has a fast tab located on the lower edge of the Backplane The fast tabs are labeled FTx whereas x represents the Module Port number See diagram in section 1 5 IEI has included four ground cables and wire nuts to make this connection Do not terminate the drain wire at the Front End Reader Cut off the exposed drain wire and wrap the insulation and the foil shield in electrical tape Page 14 of 48 1e HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Wiring Front End Readers 4C Stranded Models Shielded Cable KP5001 CR KP500W To Hub Door Control Module Model 250 22AWG KP500W PRX500W K lt CR500W 5007 20 AWG KES00WP PRX500WM A To Hub Door Control 1000 KP500R TCH500W Module Drain Wire Connect to fast tab on HubMax backplane Wire Color to Color lt
29. e Hub Door Control Module you want to program limited options Programming all information through the Secured Series Software and exporting that information to the Hub Door Control Module s This manual only covers the first method programming directly to Hub Door Control Module shown below Information on the second method is in the Secured Series Software User Manual included with the HubMax Programming using method 1 The first step to program a Hub Door Control Module is to connect the detachable keypad You can connect the detachable keypad to either S2A or S2B connectors on the Hub Door Control Module depending on which way you mount the HubMax Cabinet Use S2A to mount the cabinet horizontally and use S2B to mount it vertically Detachable Keypad Hub Door Control Module 0 LED1 Yellow I LED4 Bi Color S2A Detachable Keypad Connector Backplane 010 S2B Detachable Keypad Connector LED2 0 O LED3 SW2 Jp1 REX Test Ga Main Alarm Door Forced REX Door Relay Shunt Ajar Door Front End Switch NCCNONCCNONCCN 1 HubMax Installation Programming Manual Www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 2 Programming Features e Each HubMax Module has 500 user locations HubMax Il has 2000 user locations Location 1 is the Master Code The Master Code is used to put the Hub Door Control Modul
30. e into Program Mode The Master Code can also be used to open the door as any user code This leaves 499 HubMax 1999 HubMax Il locations to be dedicated to user data User data can be data from User Token such as a magnetic stripe card proximity cards touch chip touch keys or keypad codes A User Token cannot be programmed into location 1 Location 1 can only be programmed as a code Code data for all model keypads can be from one to six digits in length and numbers can be repeated within a User Code Programming Example Objectives Change MASTER CODE to 4321 Set RELAY TIME to 10 seconds Add USER CODE of 2268 to USER LOCATION 2 Set DOOR AJAR TIME to 440 seconds Enable PRINT LIVE Perform the following actions on the Hub Door Control Module programming keypad Action Press Enter Program Mode 99 MASTER CODE Change MASTER CODE to 4321 10 1 4321 4321 Set RELAY TIME to 10 seconds Add USER CODE of 2268 to USER LOCATION 2 2 2268 2268 Set DOOR AJAR TIME to 440 seconds 44 440 03 Enable PRINT LIVE 31 4 10 4 1 EXIT Program Mode Page 35 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 3 Sending Information Between Networked Hub Door Controllers Note Feature not available with HubMax Il Door Control Module IEI Secured Series Door Controllers have the ability to
31. e programmed USER INFORMATION from one controller to another USER INFORMATION is the code and or token programmed into a USER LOCATION Sending ALL DATA This feature is used to send the entire programming of one controller to another This includes all USER INFORMATION and all DOOR SETTINGS DOOR SETTINGS include DOOR NUMBER MAIN RELAY TIME FORCED DOOR TIME DOOR AJAR TIME PRINTER OUTPUT PORT KEYPRESS FEEDBACK STATUS Page 36 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Below are detailed instructions on sending information between door controllers Step 1 At the Destination Door Controller SOURCE DESTINATION Action Press Enter Program Mode 99 Master Code Program the door 29 0 0 k controller to RECEIVE DATA LED Status e BI COLOR LED on Controller will flash RED GREEN Step 2 At the Source Door Controller Action Press Enter Program Mode 99 Master Code Method 1 DESTINATION Copy a RANGE OF USERS 20 FFF LLL SOURCE first USER LOCATION range Example 001 LLL last USER LOCATION in range Example 500 Method 2 Copy ALL DATA 212 03 0 4 LED Status During the transmission of data The YELLOW and the GREEN LED s flash simultaneously DATA TRANSMISSION Once the data
32. ed until an authorized user is recognized at the Front End Reader This is a number that represents the number of seconds the door can be seen as open before the DOOR AJAR RELAY is energized It can be programmed from 10 to 900 seconds in 10 second intervals 10 20 30 TRANSACTION LOG COMMANDS LOG DUMP CODE LOG DUMP TOKEN LOG EVENTS ACCESS DENIED PROGRAM DENIED REX DOOR AJAR DOOR CLOSED FORCED DOOR LOG ERASED PRINT IN BAD TIME ZONE TOGGLE ON TOGGLE OFF First In AUTO UNLOCK RE LOCK This special USER CODE cannot open the door when entered the Hub Door Control Module prints the contents of the TRANSACTION LOG BUFFER This special USER TOKEN cannot open the door when entered the Hub Door Control Module prints the contents of the TRANSACTION LOG BUFFER An unrecognized USER attempted to gain ACCESS An unrecognized MASTER CODE tried to enter PROGRAM MODE Free Exit normally open device wired to REX terminals was energized The door was held open longer than the programmed DOOR AJAR TIME The door was recognized as closing after an authorized ACCESS or EGRESS The door was recognized as opening without an authorized ACCESS or EGRESS The TRANSACTION LOG BUFFER was erased through programming A DUMP CODE or DUMP TOKEN was entered and the TRANSACTION LOG was PRINTED An authorized User gained access through a Front End Reader designated as IN An authorized User gained egress through a Fron
33. f access media such as a Magnetic Swipe Card Proximity Card Proximity Key or Touch Chip This is the address programmed into the Hub Door Control Module that is used when networking Hub Door Control Modules The Door Number is a two digit number For Example All Hub Door Control Modules are factory set to Door Number 01 This feature uses the Real Time Clock in the Hub Door Control Module When enabled the Hub Door Control Module automatically UNLOCKS the door at 9 A M and LOCKS the door at 5 P M default Note Time Zone must be enabled for this feature to work This sends event reports to a serial LINE PRINTER as they occur 24 hours a day This feature causes the YELLOW LED on the Hub Door Control Module to blink once every 8 seconds when the Transaction Log Buffer reaches 80 of capacity or more You can reset the FLASHING YELLOW LED by entering the self test on the Hub Door Control Module through the Detachable Keypad www ieib com Page 45 of 48 HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 ACCESS CONTROL FEATURES FORCED DOOR TIME DOOR AJAR TIME This is a number that represents the number of seconds the FORCED DOOR RELAY is energized It can be programmed from 10 to 900 seconds in 10 second intervals 10 20 30 or it can be set to LATCH by entering a time of 00 NOTE When the FORCED DOOR is set to a LATCH TIME the FORCED DOOR RELAY remains energiz
34. herever you decide to mount the enclosure make sure it is accessible for programming purposes Mounting Procedure Unlock and open metal enclosure Notice that the enclosure lid opens from top to bottom and if you mount the enclosure horizontally the enclosure lid will form a tabletop and a convenient workspace You can also mount the enclosure vertically see section 4 1 1 Usethe supplied wall anchors and sheet metal screws to secure the HubMax Cabinet to the wall 2 Drill 11 64 diameter holes for the wall anchors 3 Tap the wall anchors into the wall until the outer flange is flush to the wall surface 4 Insert the sheet metal screws 34 of the way into the anchors Page 10 of 48 1e HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Hang the HubMax Cabinet by aligning the slotted holes cut into the rear of the cabinet with the sheet metal screws Space between slotted holes on center 17 Horizontally and 13 Vertically 6 The HubMax Cabinet should now be resting on the sheet metal screws 7 Tighten the sheet metal screws until they are snug Step 3 Ground the HubMax HubMax II Grounding the system before making any electrical connections is imperative By grounding the system first you not only increase personal safety during installation but you also protect the HubMax from damage due to static discharge or any other transient voltage effects We c
35. ill be easier to distinguish between terminal blocks if you label them first Backplane Connector U10 Module Power Front End Power E REX Test Forced Door SW2 JP1 lt Door Position REX Door Switch Shunt E Front End Switch Page 5 of 48 www ieib com HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 1 5 HubMax HubMax II Backplane Diagram The diagram below shows the component locations and terminal connections on the HubMax HubMax II Backplane 51 MMe Modem Connector e e 3 y N oocooooooo ooooooooog srsre e fefersre e e 0 eefefefefefefefefe X 4 TS2 LED3 LED4 LED2 LED5 BATT AC IN LED1 Des m3 oo m oo m STEM MODULE 1 RX TX MODULE 2 DC AC MODULE 3 IR LED MODULE 4 FT3 ON OFF B B ACACEGND ON OFF ON OFF FT4 NOT USED LOCAL REMOTE ON OFF FT1 FT2 PORT A PORT Page 6 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 2 0 UL Requirements The IEI HubMax and HubMax II controllers U L Listed products and comply with U L 294 To install these products to meet U L requirements all the instructions in this section and throughout this manual must be followed The Hub
36. ming FORCED DOOR TIME default FORCED DOOR TIME is 10 seconds Forced Door is the length of time the Forced Door relay energizes upon an invalid ingress Action Press Enter Program Mode 99 Master Code Program Forced Door Time 45 Forced Door Time 0 Enter in 10 second Example 45 40 0 for 40 seconds intervals 10 990 Entering 00 latches the output Exit Program Mode Page 22 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 11 Configure the HubMax HubMax ll to Print There are two methods to print from the HubMax HubMax II without software 1 Using the Infrared Handheld Printer IRPRINT 2 Connecting the Hub Door Control Module to a SERIAL LINE PRINTER only way to print LIVE Both methods are described in this section HubMax Modules are equipped with a 1000 event Transaction Log HubMax II modules can hold 1 500 events This means that the Door Control Module records events occurring at the door When the log buffer reaches its capacity of events the oldest event is overwritten with the new event NOTE The first transaction on the list is the most recent transaction You can program the Hub Door Control Module to mask out not record certain events This feature is used in situations where the end user does not want the transaction buffer to be filled with non essential transactions The
37. n Alarm Shunt Forced m e Door Door Ajar are FORM C DRY 0 CONTACT which means there is output Q Q 0 voltage on the relay contacts These relays can be used on a dry contact loop or switch one leg J ROM of power to an external device as shown in the Main illustrations below T M T qoedepgmesemoesagmoesasmoeds 000 NC C NO Connecting a Maglock Connecting an Electric Strike Fail Safe Connection Fail Secure Connection E V V V represents one leg of power from an external power source If you are using DC Voltage for the lock put the positive leg here If you are using AC it does not matter which leg you use The HubMax Backplane powers the Hub Door Control Modules and Front End Readers Only DO NOT power any external locking device with the HubMax Programming the MAIN RELAY TIME default MAIN RELAY UNLOCK TIME is 05 seconds Action Press Enter Program Mode 99 Master Code Program Relay Time Relay Time 1 Master Code Master Code Two Digit Number 01 90 Example 10 1 5678 5678 Exit Program Mode Page 13 of 48 1e HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 6 Connect a Front End Reader to the Hub Door Control Module Hub Door Control Module S
38. nsformer back into electrical outlet If problem persists CALL IEI TECH SUPPORT If the transformer does not read 16 5 VAC 1 2 3 Unplug the transformer from the electrical outlet Read the AC output from the electrical outlet and verify that 110 120 VAC is present If this voltage is not present consult an electrician Hub Door Control Module Symptom Probable Solution LED 2 is not lit 1 2 Check the connection between the Hub Door Control Module and the Backplane Confirm that the pins on the P Connector are properly mated to the 751 Connector on the Hub Door Control Module LED 3 is not lit This indicates that the BLACK and RED lines going to the Front End Reader are shorted Disconnect the Front End Reader and see if LED 3 turns on If LED 3 does not illuminate there may be a problem on your Hub Door Control Module CALL IEI TECH SUPPORT www ieib com Page 33 of 48 HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 0 Programming the HubMax HubMax II This section contains the details of programming the HubMax HubMax II Door Control Module 4 1 Programming Methods There are two methods of programming the Hub Door Control Modules They are as follows 1 Programming directly to a Hub Door Control Module using the detachable keypad which is pre mounted on Hub Door Control Module 1 Simply move this keypad to th
39. ore HubMax Enable Remote Access 31 8 1 Backplanes Selecting the Modem String For HubModem Kit 3512101 The sYSTEM SWITCH on the first For Boca 14 4 only 3541503 Backplane must be set to REMOTE Exit Program Mode The SYSTEM SWITCH on the second Enter the Self Test 7890451234565 Backplane must be set to LOCAL This initializes the modem Page 27 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 At the remote PC Following these steps to set up your PC to operate remotely 1 Install the IEI Secured Series Software Kit which is supplied with 2 Install one of 4 external modems for your PC The four external modems that IEI supports are Boca 14 4 no longer available Boca 33 6 US Robotics 33 6 US Robotics 56k v 90 For complete instructions for setting up your PC please consult the appropriate documents in the IEI Secured Series Software kit Page 28 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 12A Networking HubMax Backplanes Method 1 Door 1 Door 2 Door 3 Door 4 METHOD 1 If HubMax units are within 6 feet of each other use the 4 Conductor Straight Patch Cord supplied to connect from Port C of first HubMax to Port A of second HubMax 6 Ft 4 Conductor Straight Patch Cord
40. osed activates the MAIN RELAY for the length of time programmed with the MASTER CODE DOOR This is a NORMALLY CLOSED loop that tells the Hub Door Control Module the door status Auto RE LOCK Auto Re lock automatically solves the problem of people tailgating in behind those using valid access or egress This feature allows the programmer to set a long door unlock time This feature overrides the main relay timer de energizing the main relay 1 second after the Hub Door Control Module sees the door contact open In many situations you will find the need for long door unlock time this allows people carrying packages enough time to get from the front end reader to the door and open it before the timer runs out Other people may only require a few seconds to do the same task Without auto re lock the door would be left un locked long enough for people to tailgate in behind authorized users For this feature to operate properly you have to utilize the door position switch input and REMOVE the loop jumper JP1 No programming is necessary After a valid access or egress the Hub Door Control Module monitoring the door contact sees the door switch open and de energizes the main relay immediately re locking the lock Page 19 of 48 1e HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 8 Wire the Alarm Shunt Relay The Alarm Shunt Relay is used when the
41. r settings Programming Access Control Features 44 Set Time in real time 41 HHMM 0 clock HHMM Hours and Minutes in 24 hour format Military Time 42 MMDDYY Day of Week k MMDDYY Month Day and Year all in two digit numbers Day of Week Sunday 1 Monday 2 Tuesday 3 43 0 DN DN a two digit number from 01 to 08 44 DOOR AJAR TIME 0 k DOOR AJAR TIME in 10 second intervals from 10 900 45 RELAY TIME 0 k FORCED DOOR TIME in 10 second intervals from 10 900 Enable Panic 31 16 1 31 17 0 45 Set Date real time clock 46 Set Door Number 47 Set Door Ajar Time 48 Set Forced Door Time Page 43 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Programming Options Chart continued To Enter Programming Mode Enter 99 Master Code To Exit Programming Mode Enter Programming Transaction Log Commands 49 Assign Log Dump Code S0 pog 2 User Location Swipe Token at Reader 51 Print Transaction Log 70 0 0 ae Transaction 76 00000 00000 53 Print the User List 25 0 0 2 User Location New Code New Code Page 44 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Doc
42. rogram Door Ajar Time 44 Door Ajar Time 0 Enter in 10 second Example 44 40 0 for 40 seconds intervals 10 990 Exit Program Mode Page 21 of 48 1e HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 10 Wire the Forced Door Relay This output alerts personnel that the door had been opened without authorization The FORCED DOOR ALARM remains energized until a code is entered at the FRONT END or Hub Door Control Module or the FORCED DOOR RELAY TIME elapses The FORCED DOOR RELAY TIME represents how long the FORCED DOOR RELAY stays energized The FORCED DOOR RELAY can be used to switch power to an alarm device i e horn strobe This relay is rated to handle 1 Amp of current at either 12 or 24 Volts AC DC Alarm device s are not included with IEI equipment NOTE This feature requires you to wire a DEDICATED door position switch to the Hub Door Control Module per the diagram below and to also REMOVE the Loop Jumper JP1 e Hub Door Control Module Remove Loop Tech Tip Jumper JP1 During when using door installation it will contacts be easier to distinguish i between terminal Nido eub blocks if you label them first Normally Closed Magnetic Door Contact DEDICATED Example Switching the positive leg of Alarm Device power to an alarm device Program
43. send pre programmed information between networked door controllers This is useful for applications that have networked controllers but are not using the Secured Series Software to program the controllers with a PC This feature also requires that you have access to both door controllers because it s done through the detachable keypad on each controller This feature requires two door controllers e The SOURCE door controller programmed with the information you want to send e The DESTINATION door controller where you want the information to be received The SOURCE and DESTINATION controllers can be any controller in the network regardless of the door number Below is an overview of the procedure Detailed instructions and diagram are on the next page Procedure Overveiw 1 At the DESTINATION controller e Put the controller into program mode e Enter the command to set controller into receive mode BI COLOR LED flashes RED GREEN 2 At the SOURCE controller e Put the controller into program mode e Enter the command to send the data The YELLOW and GREEN LED s flash simultaneously 3 After the Data Transmission is complete e The GREEN LED on the source controller reverts to solid RED with a slowly flashing YELLOW e Exit progam mode on both controllers Note There are two types of information that you can send between controllers e RANGE OF USERS e ALLDATA Sending a RANGE OF USERS This feature is used to send pr
44. t End Reader designated as OUT A User tried to gain access or egress outside of the authorized TIME ZONE The MAIN RELAY was latched OPEN by a TOGGLE USER The MAIN RELAY was latched CLOSED by a TOGGLE USER An authorized user triggered the AUTO UNLOCK TIME ZONE A RELOCK User locked the door www ieib com Page 46 of 48 HubMax Installation Programming Manual Document 6065034 Rev 3 4 D4b Fax Document Number 5034 7 0 Warranty International Electronics Incorporated IEI warrants its products to be free from defects in material and workmanship when they have been installed in accordance with the manufacturer s instructions and have not been modified or tampered with IEI does not assume any responsibility for damage or injury to person or property due to improper care storage handling abuse misuse normal wear and tear or an act of God IEI s sole responsibility is limited to the repair at IEI s option or the replacement of the defective product or part when sent to IEI s facility freight and insurance charges prepaid after obtaining IEI s Return Merchandise Authorization IEI will not be liable to the purchaser or any one else for incidental or consequential damages arising from any defect in or malfunction of it s products This warranty shall expire two years after shipping date for Door Gard Keypads Except as stated above IEI makes no warranties either expressed or implied as to any matter
45. transmission is complete the GREEN LED reverts to a solid RED with a flashing YELLOW Step 3 At the SOURCE and Destination Door Controller Action Exit Program Mode Page 37 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 4 4 Printing the Transaction Log and User List The HubMax HubMax Il Door Control Module has the capability to print a complete user list and transaction log The HubMax can store up to 500 users and 1000 events in the transaction event buffer The HubMax II can store up to 2000 users and 1500 events in the transaction event buffer The transaction event buffer stores events User In Forced Door etc that occur at the door the Hub Door Control Module is controlling This section describes the features relating to these functions 4 4 1 Selecting the Printing Output Port The first thing you need to do before you can print anything is choose which method of printing you want to use The HubMax HubMax Il Backplane is equipped with two output ports for printing They are 1 Infra Red IR LED for use with the hand held infra red printer IRPRINT 2 Serial RS 232 for use with a serial line printer After you ve selected which port you want to use you have to program the Hub Door Control Module to use that port Enter the appropriate command below on the Hub Door Control Module keypad Action
46. ual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 11A Printing From HubMax Using Handheld Infrared Printer Door 1 erefere ere ere oococogoogg gogoogooogj cogcogoog 5 Does Hold IR Printer no further than Handheld IR Printer 1 to 1 1 2 Part IRPRINT inches away from IR Port 6 Print A Enter the DUMP CODE if programmed at Hub Door Control Module present the DUMP TOKEN if programmed at FRONT END READER B If there is no DUMP CODE or TOKEN you must either program one or 1 Put Hub Door Control Module into Program Mode 99 MASTER CODE yellow LED starts flashing 2 Enter command to Print Audit Trail 70 0 0 or Print User List 25 0 0 see section 4 4 3 and 4 4 5 Once you have performed either option A or B the Red and Green LED s on the front of the Hub Door Control Module start flashing then e Hold the Handheld IR Printer up to the HubMax Backplane as shown above e Face the IR Port on the printer towards the IR Port on the HubMax Backplane e The printer must be no further than 1 to 177 inches away from the IR Port Page 24 of 48 ie HubMax Installation Programming Manual
47. ument Number 5034 6 0 Definitions of terms and HubMax Functions Please refer to these definitions of terms when consulting the Programming Options Chart COMMON TERMS MASTER CODE USER LOCATION RELAY TIME USER CODE TOGGLE USER USER TOKEN DOOR NUMBER AUTO UNLOCK PRINT LIVE LOG ALMOST FULL WARNING This code is stored in USER LOCATION 1 and activates the MAIN RELAY This code is also used to put the Hub Door Control Module into Program Mode by entering 99 MASTER CODE This is the number of the actual memory register that user data is stored in and they range from 2 to 500 HubMax or 2 to 2000 HubMax II USER LOCATION 1 is reserved for the MASTER CODE only and is defaulted to 1234 This is a two digit number that represents the number of seconds the MAIN RELAY is energized It is programmed in association with the MASTER CODE For Example The Default RELAY TIME associated with the MASTER CODE is 05 for five seconds This is the actual sequence of numbers that the user enters followed by the ASTERISK to gain access to the door For Example you have programmed a keypad code of 2468 into a USER LOCATION To gain access to the door controlled from the Hub Door Control Module enter 2468 at the Front End Reader This type of user is assigned a RELAY TIME of 00 A TOGGLE USER can LATCH the MAIN RELAY Energize or De energize until the same code or another toggle code is entered A form o
48. w During installation it will be easier 1 to distinguish between terminal blocks if you label them first L req Front End o o ofo ofo wlio o DOOS lt Drain Wire Terminate at fast tab located on the backplane beneath the Hub Door Control Module FT1 4 Use wire nut Electrical Tape ee aoe to the 4 Conductor Stranded Shielded gt Cable with overall foil shield The devices used at the door to gain access are Front End Readers not included IEI manufactures several to choose from such as keypads magnetic card readers proximity card readers and touch chip readers No programming commands are entered at the front end The Front End Reader is only able to send access information from the door to the Hub Door Control Module Choosing the correct front end for the application is important IEI manufactures light medium and heavy duty Front End Readers If you are not sure which front end to use call the IEI Sales Dept at 1 800 343 9502 The Hub Door Control Module can support 1 or 2 Front End Readers on a single door for N and OUT operation Simply wire the two Front End Readers in parallel at the door On the Hub Door Control Module there is a four screw terminal block labeled FRONT END Each of these screws is labeled with a color and they connect to the corresponding color of the four conductor wire harness that is included with the Front End Rea
49. whatsoever including without limitation to the condition of its products their merchantability or fitness for any particular application Page 47 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 International Electronics Inc 427 Street Canton 02021 U S A 781 821 5566 800 733 9502 Sales 800 343 9502 Sales FAX 781 821 4443 Fax Demand 781 821 0734 Visit our Web Site at www ieib com Page 48 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034
50. y clip the switch on the side of the cabinet on the interior then wire the leads to your alarm device using the appropriate U L type cable See diagram below Clip over side of cabinet Page 7 of 48 1 HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 2 2 Power and Non Power Limited Wiring To meet U L requirements the Power Limited and Non Power limited wiring must be routed away from each other and separated by a minimum of a 1 4 inch 250 See related descriptions and diagram below The following terminal connections are considered Power Limited Main Relay Alarm Shunt Relay Door Ajar Relay Forced Door Relay Front End Terminals REX Door Switch Terminals Port A RJ 11 Jack and TS1 terminal Port C RJ 11 Jack and TS1 terminal The following terminal connections are considered Non Power Limited e Transformer Input AC and EGND e Backup Battery Connection B and B oocogogo e E g eQ g 4 pod FrontEnd REX Door Imosivesiresipesisews moss en Ge eee Batt AC In
51. y occur at the door To set the Hub Door Control Module to PRINT LIVE you must e Put the Hub Door Control Module into Programming Mode 99 MASTER CODE e Enter the command to enable PRINT LIVE 31 10 1 PRINT LIVE is NOT recommended for heavy traffic systems with multiple doors Events occurring simultaneously at more than one door will collide and the printout will be illegible Page 26 of 48 ie HubMax Installation Programming Manual www ieib com Document 6065034 Rev 3 4 D4b Fax Document Number 5034 Step 12 Network the HubMax HubMax II This step describes how to network the HubMax HubMax II to other Hub Door Controllers and how to connect it to it modem for remote access using For instructions and diagrams to connect a PC Personal Computer to the HubMax consult the Hardware Installation Manual Document E000 0010 which is in the Secured Series Software Kit included Remote Access The HubMax can be accessed from a remote site via modem This enables you to manipulate any of the data in the system as if you were at the site with your personal computer but via phone This is described in this section NOTE The modem interface was not evaluated by U L At the HubMax For each network you need to install the IEI Secured Series HubModem Kit Part SS MODEM It is recommended that the site with the HubMax should have a dedicated phone line available to use this feature The dedicate
Download Pdf Manuals
Related Search
Related Contents
Epson PowerLite 825 Multimedia Projector User Replaceable Parts List Effective parameter (permittivity and permeability) estimator Mémento relatif à l`équipement après coup d`un véhicule Table of Contents Les diverses têtes lexicales et leurs compléments MHC-GR8 Philips Ceiling light 30175/30/76 N° 20 - mars 2006 - Site Officiel de la Municipalité de Montdidier Timbre Wolf User Guide 2 - Ricoh Copyright © All rights reserved.
Failed to retrieve file