Home
FA168C-GP Installation Manual
Contents
1. RED JUMPER ON CONTROL BOARD TO ENABLE BELL SOUNDER SUPERVISION sounder 001 VO DO NOT CONNECT THE RESISTOR AT THE ALARM OUTPUT TERMINALS THEMSELVES Figure 5 Sounder Wiring Supervised Notes This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances Temporal pulse sounding for a fire alarm consists of 3 pulses pause 3 pulses pause 3 pulses etc e The 12VDC sounder output activates when an alarm occurs e Total current drawn from this output cannot exceed 2 amps going beyond 2 amps will overload the power supply or may cause the electronic circuit protecting the sounder output to trip e You must install a battery since the battery supplies this current UL e Use only UL Listed sounding devices for UL installations e Bell supervision is required for fire alarm installations e The total current drawn from the alarm output and the auxiliary power output combined cannot exceed 600 mA In addition the sounding device must be a UL Listed audible signal appliance rated to operate in a 10 2 13 8 VDC voltage range and must be mounted indoors Wiring the AC Transformer 1321 Transformer Connect the 1321 Transformer to terminals 1 and 2 on the control board See Wire Run Chart at right for wire size to use Use 1321CN in Canada 1361X10 Transformer required if using Powerline Carrier devices 1 Spl
2. Mounting and Wiring the Control Smoke Detectors continued Notes 4 Wire Smoke Detectors 3 Connect 4 wire smoke detectors up to 16 depending on detector current draw to any zone from 2 8 as shown below e Do not use 4 wire smoke detectors on zone 1 This control does not automatically reset power to 4 wire smoke detector zones so you must use a relay e g 4204 4229 or on board trigger to reset power also required for fire verification Do this by programming the designated relay trigger as zone type 54 fire zone reset see On Board Trigger section for other information NOTE Maximum current on trigger 17 is 100mA Figure 7 4 Wire Smoke Detector Connections PROGRAM AUX PWR RE OUTPUT lt TERMINALS TYPE 54 POWER AUX PWR 5 FIRE ZONE SUPERVISION RELAY MODULE TO OUTPUT 17 E ATT T18B PROGRAM OUTPUT 17 EOL FOR OUT NORM POWER HOMENTARILY UPON CONTACT LOW YES IN 79 MENU SUPERVISION FIRE ALARM RESET S VIOLET WHICH CLOSES MODE AND AS ZONE RELAY MODULE AIRE SMOKE WHEN POWER TYPE 54 IN 4 WIRE SMOKE A77 716B OR COMBUSTION IS APPLIED 80 MENU MODE OR COMEUSTION USE DETECTOR CONTACT S WHICH CLOSES WHEN POWER IS APPLIED ZONE TERM TO ZONE TERM i HEAT E HEAT DETECTOR 3 DETECTOR 3 TO ZONE TERM 3 TO ZONE TERM 2 3 4 Wire Smoke Detector Using Relay for Power Reset 4 Wire Smoke Detector Using Ou
3. 4 3 Part 2 Primary Subs Acct No 4 3 Partitions ara 1 1 3 1 Perimeter Burglary 3 3 Phone Line 2 12 Phone Line Monitor Enable 4 7 Phone Module 1 1 1 2 2 8 2 5 2 12 2 13 4 1 4 7 9 1 9 3 9 4 Phone Module Access Code 4 1 Phone System Select 4 3 Power Failure Power Supply 2 3 Power Up In Previous State 4 2 Powerline Carrier Device X 10 House dann 4 1 Powerline Carrier devices 2 4 Powerline Carrier Devices1 2 2 11 12 2 Primary Phone NO 4 3 Prompt Confirm 5 5 16 4 Q Quick Arm Enable 4 1 R Relay Module Addresses 2 10 Relay Modules Report Code Report Code Formats Reports In Armed Period Response Time ione teen ess 2 7 RF House ID Code 4 1 RF Interference RF jam detection RF Jam Option RF Receiver 2 1 2 2 2 5 2 8 3 6 Ring Detection Count 4 7 RJ31X 2 12 S SA4120XM Cable 2 4 Schedules 1 1 10 1 Secondary Phone No 4 3 Security Codes 1 1 12 1 Silent Burglary
4. The cursor will then move to the right in position for the next character 4 Repeat Step 3 to create the desired word s Note that the 4 key can be used to move the cursor to the left if necessary Remember no word or word string can exceed 10 characters 5 Press the 8 key to save the custom word s and return to the CUSTOM WORD display Repeat Steps 2 5 for other custom words to be entered To change a custom word just overwrite it If no more are to be entered now press 0 to return to the Descriptor entry The custom word s will be automatically added to the built in vocabulary Assigning Partition Custom Message Descriptors You can assign a partition descriptor up to 16 characters for each partition plus the common lobby Use the same procedure as for adding custom words described above but use the following word numbers in step 2 11 partition 1 12 partition 2 13 common lobby Use the SPACE character 32 to delete existing characters Once a custom word is entered in any of these word locations 11 13 the system displays the appropriate partition s word instead of the normal DISARMED READY TO ARM message 9 3 000 001 002 004 005 006 007 009 010 012 013 014 016 017 018 019 020 021 022 023 025 026 028 029 030 031 033 034 035 036 037 038 040 046 047 048 049 050 051 052 053 054 055 057 059 060 061 062 064 Note 3
5. INIO OT S CO PO Smoke Detectors 2 Wire Smoke Detectors 1 Connect up to sixteen 10 if clean me option used 2 wire smoke detectors across zone 1 terminals 8 and 9 as shown in the Summary of Connections diagram at the back this manual Observe proper polarity when connecting the detectors 2 Connect an EOL resistor across the loop wires at the last detector Notes Fire Verification zone type 16 The control panel will verify a fire alarm by resetting the smoke detectors after the first alarm trigger and then waiting 90 seconds for a second alarm trigger If the smoke detector or thermostat does not trigger again the control will disregard the first trigger and no alarm signal will occur This feature eliminates false alarms due to electrical or physical transients SIA Installations If using fire verification on zones other than zone 1 UL Fire Alarm Listed relay accessories must be used to reset power as described in step 3 at left The zone 1 alarm current supports only one smoke detector in the alarmed state Clean Me Option If enabled field 174 1 56 zone programming response time prompt 3 certain ESL smoke detectors send clean me reports as appropriate If used the maximum number of detectors is reduced to 10 not standard 16 Refer to the ESL documentation included with the smoke detector for information regarding compatibility with the clean me option
6. 4 12 Double Balanced 2 6 Download Phone Number 4 7 Dynamic Signaling Delay 4 4 Dynamic Signaling Priority 4 4 E Earth ECP Fail Display Enrolling na Entering Serial Number Entry Entry Delay 1 Entry Delay 2 BOER fel lai ELE Event Log Full Report Code Event Logging Exit Delay Exit Error Alarm PRA Exit Error Report Code Exit Time Display Interval Exit Expander Module Addresses 2 7 Expansion Zones Expert Programming Mode F FA260KP FA560KP 1 2 2 3 2 5 14 1 FA4285 1 1 1 2 2 3 2 5 2 12 2 13 4 1 4 7 9 8 14 1 FA4286 1 1 1 2 2 3 2 5 2 12 2 13 3 6 4 1 4 7 9 3 14 1 Factory Defaults Fast Busy Signal Fault Delay Time i Fire Alarm Sounder Timeout 4 2 Forced Bypass Function 4 1 Function Key Programming 8 1 Function Keys 3 3 G Go No Go Test Mode 13 2 H Handshake esses 11 1 hardwired zones 1 1 2 6 5 2 12 3 HAYES Modem House ID 1 IBM Personal 3 1 Ideal Model 61 035 2 5 I
7. to continue If zone list was selected this screen appears Otherwise skip to the next row Enter the desired zone list number associated with this output number NOTE Do not use pager zone lists 09 12 in output definitions Press to continue Enter the zone list event that will activate this output Enter Event 0 restore 1 alarm Alarm 1 2 fault 3 trouble NOTE For alarm fault and trouble an event on ANY zone in the list activates the output but ALL zones in the list must be restored before the output is restored Press to continue and skip to the Output Action prompt 2 see list at right 01 Enter Zn type Perimeter 03 If zone type was selected this screen appears Otherwise skip to the next row Enter the desired zone type associated with this output number See below for a list of available zone types CHOICES FOR ZONE TYPES 00 Not Used 05 Trouble Day Alarm Night 14 Carbon Monoxide 01 Ent Exit 1 06 24 Hr Silent 15 24 Hr Personal Medical 02 Ent Exit 2 07 24 Hr Audible 16 Fire w verification 03 Perimeter 08 24 Hr Aux 23 No Alarm Response 04 Interior Follower 09 Fire 24 Silent Burglary 10 Interior w Delay 77 Keyswitch zone 12 Monitor Zone 81 AAV Monitor Zone 90 91 Configurable CHOICES FOR SYSTEM OPERATION 20 Arming Stay RF 36 At Bell Timeout 52 Kissoff 21 Arming Away RF 38 Chime 54
8. 1 Place the 12 volt backup battery in the cabinet IMPORTANT The panel will not power up 2 After all connections to the control are completed and initially on battery power only You must plug the AC power has been applied connect the red and black transformer in first and then connect the battery flying leads on the control board to the battery Do not attach these leads to the battery terminals until all UL For UL installations and Residential fire connections are completed installations refer to the chart below for the Battery Saver Feature The battery will disconnect correct battery size required to meet the from the system after its voltage decreases below 9VDC mandatory standby time This assists the control panel in recharging the battery when AC is restored CALIFORNIA STATE FIRE MARSHALL CSFM AND UL RESIDENTIAL FIRE 24 HOUR BATTERY BACKUP REQUIREMENTS The California State Fire Marshal and UL have regulations which require that all residential fire alarm control panels must be provided with a backup battery which has sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby condition followed by at least 4 minutes in the intended fire alarm signaling condition This control panel can meet these requirements without using a supplementary power supply provided that the panel s auxiliary power and bell output currents are limited as indicated below OUTPU
9. 2 user access 3 latch key report REPEAT OPTION Repeat Option 0 do not repeat Enter the desired repeat option for this schedule e g To make a schedule that happens everyday you would select all 9 4 5 1 repeat schedule weekly days with a repeat count of 1 To make a schedule that runs for one 2 repeat schedule biweekly week then stops select everyday with a repeat count of 0 every other week 3 repeat schedule every third week 4 repeat schedule every fourth week to continue Randomize Applies to events 01 and 11 RANDOMIZE 0 no If selected the scheduled start and stop times will vary within 60 ONO Eee OK 1 yes minutes of the hour time For example if a schedule is set to start 10 2 to continue at 6 15pm it will do so the first time 6 15pm arrives but on subsequent days it will start anytime between 6 00 and 6 59 p m NOTE Do not use the random option if the start and stop times are within the same hour setting otherwise unpredictable results may occur e g the randomized stop time may occur before the start time SECTION 11 System Communication Panel Communication with Central Station When the panel calls the Central Station receiver it waits to hear handshake frequency from the receiver to confirm that the receiver is on line and ready to receive its message Once the panel hears the handshake it is programmed to listen for it sends its message The pan
10. 3 5 Silent 12 3 Single Alarm Sounding Per Zone 4 2 Smoke Detectors 2 6 Sniffer 13 2 sounder connections 9 4 Split Dual Reporting 4 3 Supervised Fire 3 4 Supplementary Power 2 3 Swinger Suppression 4 7 System Communication 11 1 System Operation 6 4 System Status Report Codes 4 4 System 5 13 1 T Tamper Switch 2 9 Telco Line 2 12 Telephone Line Monitoring 1 1 Test Mode 13 1 Test Procedures 13 1 Test Restore Report Code 4 5 Transmitter Battery Life 2 9 Transmitter Input Types 5 2 Trouble Displays 12 8 V VOCABULARY LIST 9 4 W Wireless Key Templates 5 6 Wiring Length Gauge Chart 2 3 Wiring Run Chart 2 3 Word String narren 9 3 2 Zone Doubling 2 6 Zone Lists 3 1 7 1 Zone Not 3 3 Zone Programming 5 1 Zone Programming Procedure 5 1 Zone Type Definitions 3 3 Zone Types 6
11. 13 3 Bell Supervision 1 1 Bell Supervision Jumper 2 4 Bypassing Zones 12 2 C Gabinet ae sis hein 2 1 CALIFORNIA STATE FIRE MARSHALL ERE 2 5 Caller ID 2 12 Cancel Report Code 4 5 Cancel 4 6 Character ASCII Chart 9 4 Charging Voltage 14 1 Chime By Zone 4 1 Chime Mode 12 2 Clean Me Option 6 4 9 Common zone 1 3 1 Communication 14 1 Configurable Zone Type Options 4 10 Configurable Zone Type Programming Fields 4 10 Confirmation Of Arming Ding 4 2 Contact ID Event Codes 11 2 Contact ID Reporting 14 1 Cross Zone Timer 4 6 Custom Message 9 3 Custom Words 9 3 9 4 D Data Field Programming Procedures3 5 Daylight Saving Time Defining Output Functions Descriptor Programming Device Address 2 3 2 7 2 10 3 6 4 2 4 12 6 1 12 3 Device Duration 1 2 4 9 Dialer Communication Test 13 3 BIE ELLE See 3 4 12 2 Display Partition Number
12. 600 mA 900 ft 274m 450 ft 137m 150 ft 46m 90 ft 27m 75 ft 23m 1400 ft 427m 700 ft 213m 240 ft 73m 140 ft 43m 120 ft 37m 1500 ft 457m 1100 ft 335m 350 ft 107m 220 ft 67m 170 ft 52m 1500 ft 457m 1500 ft 457m 550 ft 168m 350 ft 107m 270 ft 82m Includes Keypads RF Receivers Zone Expander Relay Units or FA4285 FA4286 Phone Module Maximum wire lengths for any device that is homerun to the control can also be determined from the Wiring Run Chart based on the current draw of that device alone The length of all wire runs for both partitions combined must not exceed 1500 feet 457m when unshielded quad conductor cable is used 750 feet if shielded cable is used This restriction is due to the capacitive effect on the data lines when quad cable is used 2 3 Installation Instructions Sounder Bell Connections 1 Make sounder connections to alarm output terminals 3 and 4 For supervised output continue with steps 2 and 3 2 Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the control board 8 Connect a 2k ohm resistor across the terminals of the last sounder TERMINALS ON CONTROL BOARD EXTERNAL ALARM SOUNDER 2000 OHM POLARITY EOL RESISTOR ALARM OUTPUT TERMINALS OBSERVE IF BELL SUPERVISION IS ENABLED RED JUMPER ON CONTROL BOARD IS CUT CONNECT A 2000 OHM RESISTOR ACROSS THE EXTERNAL SOUNDER AS SHOWN BY THE DOTTED LINE
13. MOTHERS MOTION MOTOR N NORTH NURSERY OFFICE OPEN OPENING OUTSIDE OVERHEAD P PAINTING PANIC PASSIVE PATIO PERIMETER PHONE POINT POLICE POOL POWER R RADIO REAR RECREATION REFRIGERATION RF RIGHT ROOM ROOF 5 SAFE SCREEN SENSOR SERVICE SHED 169 170 171 173 174 175 176 178 179 180 182 184 185 186 190 191 192 193 194 196 197 199 200 201 202 205 206 207 208 209 210 212 213 214 216 217 219 220 222 223 224 225 SHOCK SHOP SHORT SIDE SKYLIGHT SLIDING SMOKE SONS SOUTH SPRINKLER STATION STORE STORAGE STORY SUPERVISED SUPERVISION SWIMMING SWITCH T TAMPER TELCO TELEPHONE TEMPERATURE THERMOSTAT TOOL TRANSMITTER U UP UPPER UPSTAIRS UTILITY V VALVE VAULT VOLTAGE WALL WAREHOUSE WEST WINDOW WING WIRELESS X XMITTER Y YARD 2 2 2 226 0 227 1 228 1ST 229 2 230 2ND 231 3 232 3RD 233 4 234 4TH 235 5 236 5TH 237 6 238 6TH 239 7 240 7TH 241 8 242 8TH 243 9 244 9TH 245 Custom Word 1 246 Custom Word 2 247 Custom Word 3 248 Custom Word 4 249 Custom Word 5 250 Custom Word 6 251 Custom Word 7 252 Custom Word 8 253 Custom Word 9 254 Custom Word 10 NOTE Custom words 8 9 10 are words that can be programmed to display using Scheduling Mode Bulleted words in boldface type those that are also availab
14. Reporting Format selected 1 digit event qualifier new or restore 3 digit event code and 3 digit zone number user number or system status number see the following page Ademco Contact ID The Ademco Contact ID Reporting Format comprises the following 4 digit subscriber number 1 digit event qualifier new or restore 3 digit event code 2 digit Partition No 3 digit zone number user number or system status number see the following page Handshake 1400 2800 Hz Data Transmission DTMF 10 cps Kissoff 1400 Hz Transmit Time Under 3 secs Installation Instructions 11 2 Ademco Contact ID Reporting takes the following format CCCC Q EEE GG ZZZ where CCCC Customer subscriber ID Q Event qualifier where E new event and R restore EEE Event code 3 hexadecimal digits Note For a complete list of event codes refer to the central office receiver manual GG Partition Number system messages show 00 ZZZ Zone contact ID number reporting the alarm or user number for open close reports System status messages AC Loss Walk Test etc contain zeroes in the ZZZ location TABLE OF CONTACT ID EVENT CODES Medical Emergency sent upon zone type 15 faults Global Trouble Trouble Day Night Armed MAXIMUM Quick Arm STAY INSTANT 608 AAVioFolow Event Log 80 Full Latch Key log only 750 Reserved for Configurable Zone Type 789 report codes
15. SSV19 SNOILOANNOO TIY HOS 9189 ADYANI AALST ASN SLNIHHNI OVdAIM SLLOWSY 1nd1no HIMOd Xnv 1 101 OL VWOOL Gav NO VOT AGGNVLS TVLOL 3NIAH313Q OL SHAE 1SV31 1V HOS CIOVIdIY 38 LON G33N ATIVWHON QIov avan aavas VWOS9 LNIHHNI ONIDHYHI WAWIXYW ONIDHVHI AHaLlva SHH v LSV37 LV ASN ABANVLS AHVIOHNE AON39H3W3 HO ALIOVAVO AH3LLVE SNOLLONYLSNI 33S H3MOd vu009 HOS AHI LLVEA HVZ ZL ASN SNOLLVTTVLSNI 5 AHALIVE HH vZ Figure 17 Summary of Connections 16 5 LIMITED WARRANTY Honeywell International Inc Honeywell International Inc acting through its First Alert Professional Security Systems business Seller 165 Eileen Way Syosset New York 11791 warrants its First Alert products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 36 months from the date stamp control on the product or for products not having a date stamp for 30 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period in which case the shorter period shall apply Seller s obligation shall be limited to repairing or replacing at its option free of charge for materials or labor any product which is proved not in
16. System Setup Fields 20 29 Installer Code The Installer Code is used to assign the 4 digit Master Security Code Enter 4 digits 0 9 See Master Code in the System Operation section for procedure NOTE Installer s code is automatically disabled 4 hours after power up Powering down then powering up again will re enable the installer code for another 4 hours Quick Arm Enable If enabled a user code is not needed to arm the system Instead users 0 do not allow quick arm can press the key followed by an arming key to arm the system 1 allow quick arm However the user code is always needed to disarm the system 0 no RF jam detection signal 1 send RF jam report UL installations must be 1 if wireless devices are used Quick Forced Bypass All zones bypassed by this function will be displayed after the bypass 0 no forced bypass is initiated 1 automatically bypass all faulted zones UL installations must be 0 no forced bypass RF House ID Code The House ID identifies receivers and wireless keypads If a 5827 or 00 disable all wireless keypad usage 5827BD Wireless Keypad or 5804BD Transmitter is being used a 01 31 House ID for partition 1 2 and House ID code must be entered and the keypad should be set to the common same House ID You can assign RF house ID for each partition Chime By Zone Zone List 3 If enabled you can define the specific zones intended to chime when 22 RF Jam Opt
17. and provides an alarm sound at the keypad and an audible external alarm Assign to a zone containing an emergency button or to a zone containing monitoring devices such as water or temperature sensors Sends a report to the central station and provides an alarm sound at the keypad No bell output is provided Provides a fire alarm on short circuit and a trouble condition on open circuit A fire alarm produces a pulsing bell output This zone type is always active and cannot be bypassed Provides entry delay using the programmed entry time if tripped when the panel is armed in the Away mode Entry Delay 1 begins whenever sensors in this zone are violated regardless of whether or not an entry exit delay zone was tripped first Bypassed when the panel is armed in the Stay or Instant modes if armed in Night Stay mode zones assigned to zone list 05 night stay zone list are not bypassed when system armed in Night Stay mode Works as a dynamic monitor of a zone fault trouble not alarm In the case of a short open the message ALARM 24 Hr Non Burg XXX where XXX is the zone number will be sent to the Central Station The system keypad will display a check message indicating the appropriate zone but keypad beeping does not occur Upon restoral of the zone the message RESTORE 24 Hr Non Burg XXX will be sent to the Central Station The check message will automatically disappear from the keypad dynamical
18. check with central station when using these codes Security Codes The system supports up to 48 security codes which can each be assigned one of 5 authority levels The authority level determines the functions each code can perform as follows SECTION 12 System Operation Authority Levels authority levels can be assigned to users 3 49 only users 1 and 2 cannot be changed Level User No Functions Installer 01 perform all security functions except can disarm only if used to arm can enter program mode can change System Master code cannot assign any other user codes Installer code expires 4 hours after power up see field 20 System 02 default 1234 only one system master code per system can perform all Master security functions add delete users in either partition change system master code view event log set system clock program keypad macro program scheduled events activate output devices triggers relays Partition 1 03 same as Master except add delete users limited to Master P2 33 assigned partition only these users can be assigned different authority default levels any user can be assigned the partition master authority level 0 User 03 49 perform security functions arm disarm etc only cannot add delete users view event log set system clock or program scheduled events 1 Arm Only see user arm system only 2 Guest see user disarm the sy
19. curit des r seaux de t l communications comme le prescrivent les documents concernant les exigences techniques relatives au mat riel terminal Le Minist re n assure toutefois pas que le mat riel fonctionnera la satisfaction de l utilisateur Avant d installer ce mat riel l utilisateur doit s assurer qu il est permis de le raccorder aux installations de l enterprise locale de t l communication Le mat riel doit galement tre install en suivant une m thode accept e da raccordement L abonn ne doit pas oublier qu il est possible que la conformit aux conditions nonc es ci dessus n emp che pas la d gradation du service dans certaines situations Les r parations de mat riel nomologu doivent tre coordonn es par un repr sentant d sign par le fournisseur L entreprise de t l communications peut demander l utilisateur da d brancher un appareil la suite de r parations ou de modifications effectu es par l utilisateur ou cause de mauvais fonctionnement Pour sa propre protection l utilisateur doit s assurer que tous les fils de mise la terre de la source d energie lectrique de lignes t l phoniques et des canalisations d eau m talliques s il y en a sont raccord s ensemble Cette pr caution est particuli rement importante dans les r gions rurales Avertissement L utilisateur ne doit pas tenter de faire ces raccordements lui m me il doit avoir racours un service d inspection des installat
20. or if no valid RF signals from at least one supervised transmitter are received within 12 hours If the receiver is mounted remotely e Place the RF receiver in a high centrally located area for best reception e Do not locate the receiver or transmitters on or near metal objects This will decrease range and or block transmissions e Do not locate the RF receiver in an area of high RF interference indicated by frequent or prolonged lighting of the LED in the receiver random flicker is OK Do not locate RF receiver closer than 10 feet from any keypads to avoid interference from the microprocessors in those units YELLOW A A 0 RED gt TO CONTROL S MODEL NO ON CIRCUIT 86 REMOTE KEYPAD S BLACK CONNECTION 5882 DIP GREEN POINTS MOUNTING LOCATION SWITCH HOLES INTERFERENCE WIRING OPENING INDICATOR E KNOCKOUT AREA CIRCUIT BOARD FOR SURFACE WIRING RELEASE CIRCUIT BOARD REMOVE SCREWS AND BACK TABS Figure 9 5881 5882 RF SOCKET PLUG Receiver cover removed Installing a 5800TM Module 1 Mount the 5800TM next to the RF receiver between one and two feet from the receiver s antennas using its accompanying mounting bracket Do not install within the control cabinet Connect the 5800TM to the control panel s keypad connection terminals as shown on the Summary of Connecti
21. 3 1 2 seconds to continue This prompt appears only for hard wired zones 01 08 zone 02 is used as an example in display Option 3 used for clean me option on zone 1 see field 174 NOTE If zone doubling is being used the response time selected for zones 01 08 automatically applies to each zone s associated doubled zone 10 INPUT TYPE RF TRANS 3 Input Device type In 2 AW Aux wired zone 3 RF supervised RF transmitter 4 UR unsupervised RF transmitter 5 Button type RF transmitter unsupervised to continue This prompt is skipped if zone doubling was enabled at Hardwire Type prompt All of the RF transmitters have one or more unique factory assigned input loop ID codes Each of the inputs requires its own programming zone e g a 5804 s four inputs require four programming zones RF Transmitters can be enrolled as one of the following types Type Description Sends periodic check in signals well as Supervised RF fault restore and low battery signals The transmitter must stay within receiver s range UR Sends all the signals that the RF type Unsupervised RF does but the control does not supervise the check in signals The transmitter may therefore be carried off premises BR Unsupervised Sends only fault signals It will not send a Button RF low battery signal until it is activated The transmitter may be carried off prem
22. 4 58 Expert Programming Mode Procedures sisi 5 4 Wireless Key Programming Templates seen 5 6 Section 6 Output Device Programming e eeee ecce eese ee ee enses 6 1 About Output Device Programming ie 6 1 79 Menu Mode Output Device Mapping R E EEEN QUUD IPIS Ai 6 1 80 Menu Mode Defining Output Functions 6 3 Section 7 Zone Lists 81 Menu 7 1 About asia qe dives to iet rp auto 7 1 Zone List Programming ti eerte en pee Gee rate ete sn ter daon entiere 7 1 Section 8 Function Key Programming 57 Menu Mode ccssscccssssscsssssscsssssssccssssssccsssssssscssssecoes 8 1 About Function Key Programming Programming Function Keys reet NN ee RUE Section 9 Alpha Descriptor Programming 82 Menu Mode ssessseesseeeessessessseseseesee 9 1 About Descriptor Programmi ng sein eec 9 1 Programming Zone Descriptors program menu mode 82 ci 9 1 Adding Custom Words will not be annunciated by FA4285 FA4286 Phone Module 9 3 Section 10 Creating Schedu les eee epo et oa eee co e resereven sonder e ee UE ro eee e Ye ssccecesesess 10 1 About Schedules ERES 10 1 Section 11 System Communication cccccssocccssssscscssssscccssssscssssssscssssssscsscssssccsssssessscs
23. 5 2 7 2 10 3 6 14 1 4229 1 1 1 2 2 5 2 6 2 7 2 10 3 1 3 6 6 1 6 2 12 2 14 1 4300 Transformer 2 4 2 11 14 2 4 Wire Smoke Detectors 2 7 5 5800 Series Transmitters 14 3 14 4 5800TM 2 9 3 6 14 1 14 4 14 5 5804 wireless 5 6 5804BD wireless 2 9 5 6 2 9 5827BD 2 9 881 2 9 AAV Connections 2 13 AC Power Supply 1 2 AC Transformer 2 4 AD120612 noe ms 2 3 Alarm Output 1 2 2 4 2 5 Alarm Sounder Timeout 4 2 Alpha Descriptor Alpha Programming Alpha Vocabulary List Arm Away Stay Report Code 4 5 Attm AWay giorni 3 4 Arming 12 2 Arming 12 2 Arming Modes 12 2 Arming Stay 12 2 3 4 Audio Alarm Verification 1 2 2 12 4 7 Authority Levels 12 1 Auto STAY 4 6 AUXILIARY DEVICE CURRENT DRAW WORKSHEET Auxiliary Output INDEX B Backup Battery 1 2 2 5 Battery 2 9 Battery 5
24. 5819WHS amp BRS and 5850 The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations Installation Instructions Transmitter Battery Life See Wireless Transmitter paragraph in the Limitations of This Alarm System statement located at the end of this manual for information on transmitter battery life Some transmitters e g 5802 and 5802CP contain long life but non replaceable batteries and no battery installation is required At the end of their life the complete unit must be replaced and a new serial number enrolled by the control Button type transmitters such as 5801 5802 and 5802CP should be periodically tested for battery life The 5802MN and 5804 Button Transmitters have replaceable batteries Do not install batteries in wireless transmitters until you are ready to enroll during system programming After enrolling batteries need not be removed Installing a Keyswitch Notes 1 Connect the 4146 keyswitch s normally open Use 4146 keyswitch or keyswitch momentary switch to a zone s 2 8 terminals Use only one keyswitch per partition Remove the 2000 ohm EOL resistor if connected When using a keyswitch the zone it is connected across the selected zone to is no longer available for use as a protective 2 Using a standard keypad cable as shown zone Connect the yellow and white keyswitch wires to trigger connector pin 3 12V C
25. 90 a message can be sent to the central station receiver when the log is 80 full If the log becomes full new messages overwrite the oldest messages in the log Event Log Enables 0 no event logging 1 log Alarm Alarm Restore 2 log Trouble Trouble Restore 4 log Bypass Bypass Restore 8 log Open Close x log combination of events add value of entries This system has the ability to record various events in a history log up to 100 events At any time the downloader operator can then upload the log and view or print out all or selected categories of the log The downloader operator can also clear the log Event log can also be viewed at an alpha keypad The display printout at the central station will show the date time event and description of the occurrences Data Entry Example To select Alarm Alarm Restore and Open Close enter 9 1 8 to select all events enter 15 Option Selection 0 none 1 Local Lockout 2 Sounder Delay 4 Using Audio Alarm Verification AAV unit 8 Enable Exit delay restart TT UL UL installations using the AAV feature must use the ADEMCO UVCM module part of the ADEMCO UVS system Exit Delay Restart Reset must be disabled FOR SIA INSTALLATIONS Exit delay should be enabled Multiple choice example for both AAV and Exit delay restart enter 12 4 8 for all 1 2 4 8 enter 15 Select the desired options by adding the val
26. AD12612 Keypad Addresses Keypad Address Keypad Address no 1 16 no 5 20 no 2 17 no 6 21 no 3 18 no 7 22 no 4 19 no 8 23 The first keypad is address 16 which is always enabled and set for partition 1 with all sounds on AUI NOTE Use of AUI is independent from standard keypads and does not affect the number of standard keypads the System can support e AUI keypads must be set for either address 1 or address 2 depending on which unit is enabled in field 189 To ensure proper AUI device operation connect only to controls having microprocessor version 3 0 or higher and use AUI devices with the following rev levels FA700KP series use version 1 0 9 or higher FA800KP Symphony series use version 1 1 175 or higher Keypads powered from supplies that do not have a backup battery will not function if AC power is lost Make sure to power at least one keypad in each partition from the control s auxiliary power output UL Use a UL Listed battery backed supply for UL installations The battery supplies power to these keypads in case of AC power loss The battery backed power supply should have enough power to supply the keypads with the UL required minimum standby power time Wire Run Chart For Devices Drawing Aux Power From The Control 12V amp 12 TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN 50mAorless 100mA 300mA 500
27. Audio Alarm Verification AAV unit refer to Audio Alarm Verification AAV section for special wiring connections CAUTION To reduce the risk of fire use only No 26 AWG or larger telecommunication line cord for phone line connections UL FA4285 and FA4286 modules are UL Listed only for use on residential fire and UL residential burglar alarm installations If no touch tones are produced following access to the security system from on premises this problem may arise in rare cases it may be necessary to reverse the wires connected to terminals and 4 on the phone module and the wires connected to terminals 21 amp 22 on the control The wiring diagram shows the wiring connections that will provide proper operation in most cases Connection to the incoming telco line via a RJ31X jack and direct connect cord as shown is essential even if the system is not connected to a central station The FA4285 or FA4286 will not function if this is not done and an error signal fast busy signal will occur when trying to access the system via the phone The house phone lines gray and brown wires must be wired to the phone module terminals not to the control terminals Otherwise an error signal fast busy signal will occur when trying to access the system from an on premises phone INCOMING HANDSET TELCO LINE TERMINALS ON CONTROL CALLER ID UNIT IMPORTANT NOTE FOR EXISTING INSTALLATIONS EXISTING WI
28. Configurable Zone Type Options Auto Restore entry 2 Faults on zones set for this option are cleared and restore messages sent upon restoral of faults Vent Zone entry 2 Zones set for this option are ignored if faulted when arming the system but are protected if the zone is later restored e g an open window can be ignored when arming but if the window is later closed it will be protected opening the window again causes an alarm Bypass Disarmed entry 4 Zones set for this option can be bypassed only while the system is disarmed Bypass Armed entry 4 Zones set for this option can be bypassed when the system is armed or disarmed Dial Delay entry 6 Alarms on zones set for this option participate in dial delay central station reporting if system dial delay enabled in field 50 Fault Delay entry 6 Faults on zones set for this option are delayed by the time set in field 87 Do not use this option if using entry exit delay for this zone type Faults Display entry 7 Selects how faults on zones set for this zone type are displayed Power Reset Verification entry 7 Selects whether the system resets power when user enters code OFF and whether the system performs alarm verification see description for zone type 16 in Programming Overview section when a fault occurs on these zones Use Entry Delay entry 8 Selects whether to use the system s entry delay times Use Exit
29. DRAW WORKSHEET FA245KP Keypad OMA FA260KP Keypad 1 1 1 SMA FAS60KP Keypad 1 1 1 J FA245RF Keypad Transceiver 105 mA 5881 5882 RF Receiver 35MA 5 J J 5883 Transceiver soma J 4219 Zone Expander MA J J 4204 Relay Unit 15 1 2229 Zone Expander Relay Unit anomna T_T FA4285 Phone Module 160mA J p 5 O FA4286 Phone Module 300mA cel ae eee a __ Current available from Aux terminals 600 mA TOTAL If using hardwire devices such as PIRs refer to the specifications for that particular unit s current draw T In UL installations maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600 mA 500 mA max from Auxiliary Output t Figures are for relays OFF relays ON 2 5 Installation Instructions Hardwire Zones Normally Open Zones Normally Open EOLR Zones 1 Connect open circuit devices in parallel across the loop for EOLR zones connect the EOLR across the loop wires at the last device 2 Enable normally open EOLR zones using Zone Programming mode Hardwire Type prompt Normally Closed Zones Normally Closed EOLR Zones 1 Connect closed circuit devices in series in the high side of the loop for EOLR zones connect the EOLR in series following the last de
30. MICROPHONE an SWITCH SWITCH BANK 1 BANK 2 ON FALLING VOICE TRI m LI cem CH cH CH om ce of lt e 3 x lo o E 2 BE GND 1 Li IN ON d 9 L LLL REFERI YO S iron ZONE TERMINALS 1004 1980087 EOL RING EARTH GROUND OUTPUT 18 EC RED GREEN T GREY R OPTIONAL MONITORING BROWN CONNECTION sn USE ZONE TYPE 81 PREMISES HANDSET INCOMING PHONE LINE 4285 4286 uem 004 VO Figure 16 Connection of AAV Unit When Using a FA4285 or FA4286 Phone Module 2 15 Installation Instructions 2 16 SECTION 3 Programming Overview About Programming You can program the system at any time even at the installer s premises prior to the actual installation Programming can also be performed remotely from the installer s office home using an IBM personal computer a modem and Compass downloading software The following is a list of the various Programming modes used to program this system Programming Mode Used to Data Field Programming Program basic data fields used for setting the various system options Most of the data fields in this system have been programmed for specific default values However some fields must be programmed for each particular installation to establish its specific alarm and reporting features 56 Zone
31. No Response Arm Stay Arm Away Disarm Function 24 hour audible Arm Stay Arm Away Disarm TEMPLATE 4 TEMPLATE 5 TEMPLATE 6 Zone Type Installation Instructions SECTION 6 Output Device Programming 79 80 Menu Mode About Output Device Programming Output Devices The system supports up to 16 relays and or Powerline Carrier devices X 10 devices plus 2 built in trigger outputs in any combination These 18 outputs are assigned to system wide output numbers 01 18 Use 79 Menu Mode to assign output numbers and map them to device addresses Output Functions The system also provides installer defined output functions which can be assigned to any of the physical outputs Therefore the action of any one of the outputs can be based on as many of these functions as desired This lets a single relay or X 10 device perform many functions The controls support up to 48 output functions Use 80 Menu Mode to define output functions Relays and output devices are not recommended for life safety applications NOTE When navigating the 79 and 80 menus The key is used to accept an entry and advance to the next prompt The key is used to revert back to the last question to check or change an entry Press to go forward again Output Device programming involves 1 Use 79 Menu Mode to assign module and output numbers and map them to device addresses NOTE You must map outpu
32. Pager 1 for each partition 0 No reports sent Pager Report Note In order for pager reports to be sent to the 1 Open close for all users enabled to paget pager phone number you must also enter a primary field 41 or 4 All alarms and troubles secondary field 42 phone number 5 All alarms troubles and open close for all users enabled to page Reports to pager only when arming close disarming open from a 12 Alarms and troubles for zones entered in zone list 9 13 Alarms and troubles for zones listed in zone list 9 and open close for all users enabled to page keypad using a security code command auto arming disarming arming with assigned button and keyswitch arming do not send pager messages 163 Pager 2 Phone No If you enter fewer than 20 digits exit by pressing and next field Enter up to 20 digits number To clear entries from this field press 163 164 Pager 2 Characters See field 161 for explanation of entries If fewer than 16 characters Enter up to 16 characters exit by pressing and next field number To clear entries from this field press 164 165 Pager 2 Report Options Enter the types of reports to be sent to Pager 2 for each partition see Pager 1 reports field 162 for entries except use zone list 10 4 9 Installation Instructions FIELD fl TITLE and DATA ENTRIES EXPLANATION Pager 3 Phone No If you enter fewer than 20 digits exit by pressing and n
33. Programming Form then enter the other information zone number zone type loop number etc relevant to that device 58 Expert Programming Mode Procedures This method is designed for use by installers with previous experience in programming First Alert Professional control panels This mode is also used to program wireless keys using pre defined templates Start Expert Programming mode by pressing 58 while in Data Programming mode The following prompts are displayed PROMPT VALID ENTRIES EXPLANATION SET TO CONFIRM 0 NO 1 ES 0 Confirm no 1 yes to continue This display appears upon entry into this mode The default is 0 No If 1 Yes is entered you will be prompted to confirm each transmitter after entering the serial and loop numbers at the XMIT TO CONFIRM prompt later Zn ZTP HW RT 01 09 1 10 EL 1 Zn ZT P RC IN L 10 Summary Screen 01 64 zone number 00 quit to continue OR D to go to prompts for wireless key programming templates summary screen will appear showing zone 1 s currently programmed or default values Enter the zone number being programmed then press which displays a summary screen for that zone See next prompt in this example zone 10 is being entered If programming a wireless key press the D key then skip to the Wireless Key Programming Templates section following this section When D is pressed you can choo
34. Programming Mode see Automatic Upload Note below Prevent installer code reentry Press 98 Exits Programming Mode and prevents re entry by Installer Code 8 0 0 To enter the programming mode if 98 was used to exit you must first power the system down Then power up again and press and at the same time within 50 seconds of powering up UNLESS Local Lockout is enabled field 91 If so re entry to programming mode is permitted only by Installer code 8 0 0 Allow installer code reentry Press 99 Exits Programming Mode and allows re entry by Installer Code 8 0 0 or by Pressing and at the same time within 50 seconds of power up NOTE Installer code is automatically disabled 4 hours after power up AUTOMATIC UPLOAD NOTE After exiting program mode the control automatically initiates a download session and uploads all programming information After a successful upload alpha keypad displays Upload Completed the following fields are locked and are no longer accessible via local programming mode 20 Installer Code 40 46 Telephone and Account Numbers and 94 Download Phone Number However these fields are accessible by the downloader To stop the upload press 0 within 30 seconds of exiting program mode Table of Device Addresses This Device Uses Address Reports ast Enabled By RF Receiver 00 100 56 z
35. Quit 00 No prompt so that another list can be programmed if desired from list followed by to accept each zone 00 to continue Installation Instructions Notes Any list may include any or all of the system s zone numbers zone list can be assigned to more than one output relay e When creating zone list 4 for cross zoning include only zones assigned to zone types 8 4 or 5 Do not include zones that have delays entry exit zones interior w delay or 24 hour zones as these zone types may produce unpredictable operation and may not function as intended 7 2 About Function Key Programming SECTION 8 Function Key Programming 57 Menu Mode The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds Typical functions listed below include single button arming turning lights on off or single button paging Programming Function Keys Function key programming involves 1 Assigning the function key number and partition 2 Selecting the desired function for that key Start Function Key Programming mode by pressing 57 while in Data Programming mode The following prompts are displayed PROMPT VALID 5 EXPLANATION Press Key to Pgm 0 Quit 0 Function Key Press the desired function key A D to con
36. State must be 1 power up in previous state 40 PABX Access Code or Call Waiting Disable If call waiting is used call waiting disable option in field 91 must be set 50 Burglary Dial Delay delay must be minimum of 30 seconds 59 Exit Error Alarm Report Code Always enabled 69 Recent Closing Report Code Always enabled 91 Option Selection Exit Delay option should be enabled If call waiting is used Call Waiting Disable must be set to 1 enabled 93 No reports in Armed Period Must be set for 1 or 2 report pairs NOTES 15 3 Installation Instructions NOTES 15 4 NOTES 15 5 Installation Instructions NOTES 15 6 NOTES 15 7 Installation Instructions NOTES 15 8 SECTION 16 Limitations and Warranty WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system it does not offer guaranteed protection against burglary fire or other emergency Any alarm system whether commercial or residential is subject to compromise or failure to warn for a variety of reasons For example e Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device Intrusion detectors e g passive infrared detectors smoke detectors and many other sensing devices will not work without power Battery operated devices will not work without batte
37. and troubles to a pager use 81 Zone List menu mode to assign the zones associated with each pager zone lists 9 12 Function Keys To assign functions to the function keys use 57 Function Key menu mode To assign emergency key functions function key option 00 first program the respective emergency zone number 95 for key 96 for key 99 for key with the desired zone type using 56 Zone Programming mode then use 57 Function Key menu mode to assign the desired key If using a function key to activate a relay action 57 Menu mode key function 07 use 79 Menu mode to map the output and use 80 Menu mode to define the output s action select system operation type 66 If using a function key for a user macro use 57 menu mode to activate the desired key then define the actual macro functions using the user code 4 6 6 command Output Devices To program a device for manual activation user code st 7 8 2 digit device number or for scheduled automatic activation simply map the device using 79 Menu mode To program a device to automatically activate upon a system event or function key use 79 Menu mode to map the device then use 80 Menu mode to define the automated device action If the device action is based on more than one zone use 81 Zone List menu mode to assign the zones Zone Type Definitions You must assign a zone type to each zone which de
38. compliance with Seller s specifications or proves defective in materials or workmanship under normal use and service Seller shall have no obligation under this Limited Warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than First Alert Professional factory service For warranty service return product transportation prepaid to First Alert Professional Factory Service 165 Eileen Way Syosset New York 11791 THERE ARE NO WARRANTIES EXPRESS OR IMPLIED OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the products it sells may not be compromised or circumvented that the products will prevent any personal injury or property loss by burglary robbery fire or otherwise or that the products will in all cases provide adequate warning or protection Customer understands that a properly installed and maintained alarm may only reduce the risk of a burglary robbery fire or other events occurring without providing an alarm but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or
39. down to minimize deep discharge of the battery Comm Failure FC A communication failure has occurred Open Circuit OC The keypad is not receiving signals from the control and sees an open circuit Long Rng Trbl bF Backup LRR communication failure Bell Failure 70 Bell supervision failure RCVR Jam 90 RF jam detected KEYPAD LOW BAT 00 BAT Wireless keypad low battery Phone Okay Cd The dialer test has been successful CID code 601 Dialer Off dO The dialer is disabled Test in Progress dd Walk test mode is active CID code 607 Upload Completed dC The upload or download session was completed Upload Failed dF The upload or download session failed before completion SECTION 13 Testing the System About Test Procedures After the installation is complete you should perform the following tests System Test Checks that all zones have been installed properly and the system properly responds to faults Dialer Test Checks that the phone connection to the central station is working properly Go No Go Test Checks that transmissions can be received from transmitters Should be performed before permanently mounting transmitters RF Sniffer Mode Checks that RF transmitter serial numbers have been properly entered into the system Battery Tests Automatic battery tests are performed by the system See Automatic Battery Test paragraph for details System Test With the system in the disarmed state check that all
40. either partition is armed external sounder activates External sounder will be turned off by normal bell timeout or by security code plus OFF from either partition it does not have to be the one that was armed Entry 1 Sets the length of time a phone line fault must remain after detected before the second digit option is activated Entry 2 Selects the desired phone line fault response Option 2 may be used even if a relay unit or Powerline carrier device is not connected to the control Programmed Output Device must either be programmed to be STOPPED in field 80 or STOPPED by entry of security code 8 device number Partition in 80 should be set to 0 for STOP UL Field 92 must be enabled for fire alarm installations UL commercial burglar alarm installations and UL residential burglar alarm installations If the control unit is used on a UL commercial burglar alarm system which requires 2 methods of remote communication then the control units DACT and the other method of signal transmission must monitor each other against communication failure and line fault The fault must be received and annunciated within 200 seconds of its occurrence No of Reports In Armed Period per Zone Swinger Suppression 0 unlimited number of reports 1 1 report pair per zone per armed period 2 2 report pairs per zone per armed period This option can be used to limit the number of alarm alarm restore message
41. mode e Bypassed automatically when the panel is armed in the Stay or Instant modes if armed in Night Stay mode zones assigned to zone list 05 night stay zone list are not bypassed when system armed in Night Stay mode Type 05 e Assign to a zone that contains a foil protected door or window such as in a store Trouble by Day or to a zone covering a sensitive area such as a stock room drug supply room etc Alarm by Night Can also be used on a sensor or contact in an area where immediate notification of an entry is desired Provides an instant alarm if faulted when armed in the Away Stay Night Stay Instant or Maximum night modes During the disarmed state day the system will provide a latched trouble sounding from the keypad and a central station report if desired 3 3 Installation Instructions Type 07 24 hour Audible Alarm Type 08 24 hour Auxiliary Alarm Type 09 Supervised Fire Type 10 Interior w Delay Type 12 Monitor Zone Type 14 24 Hour Carbon Monoxide Monitor Type 15 24 Hour Medical Personal Emergency Type 16 Fire w Verification Type 20 Arm Stay BR only Type 21 Arm Away BR only Type 22 Disarm BR only Type 06 Usually assigned to a zone containing an emergency button 24 hour Silent Alarm Sends a report to the central station but provides no keypad display or sounding Assign to a zone that has an emergency button Sends a report to the central station
42. not enrolled will not turn off its zone number Go No Go Test Mode The Go No Go Test verifies adequate RF signal strength from the proposed transmitter location and allow you to reorient or relocate transmitters if necessary before mounting the transmitters permanently This mode is similar to the Transmitter Test mode except that the wireless receiver gain is reduced This will enable you to make sure that the RF signal from each transmitter is received with sufficient signal amplitude when the system is in the normal operating mode 1 Enter Installer code 4 from the partition being tested For multi partition systems repeat this test for each partition 2 After you have placed transmitters in their desired locations and the approximate length of wire to be run to sensors is connected to the transmitter s screw terminals if used fault each transmitter Do not conduct this test with your hand wrapped around the transmitter as this will cause inaccurate results a The keypad will beep three times to indicate signal reception and display the appropriate zone number b Ifthe keypad does not beep you should reorient or move the transmitter to another location Usually a few inches in either direction is all that is required 4 Ifeach transmitter produces the proper keypad response when it is faulted you can then permanently mount each of the transmitters according to the instructions provided with them 5 Exit the
43. on the transmitter label by typing digits in the X locations using the A advance or B back keys as required You can also perform two open and close sequences for button type transmitters that means pressing and releasing the button twice NOTE If you want to copy the previous zone s serial number press the C key Press to advance to the loop number then enter loop number Press to accept the existing serial and loop number and continue to the Confirm prompt below If necessary press to back up and re enter or edit the serial number 10 INPUT S N L A000 0000 0 To Delete a Serial Number to continue To delete an existing serial number enter 0 in the loop number field The serial number will change to all 0 s as shown If 0 was entered in error simply re enter the loop number and the serial number will return to the display 10 XMIT TO CONFIRM PRESS TO SKIP Confirm to continue The prompt to confirm appears This prompt will only appear if the first prompt after entering 58 was answered Yes To confirm activate the loop input or button that corresponds to this zone The system checks for duplicate If a duplicate exists a long error beep will sound Press to back up and re enter the serial and or loop number If Serial or Loop Numbers do not match after activating the transmitter to continue If the serial loop number combination tra
44. sequence If entering less than the maximum digits available e g phone number field enter the desired digits then press and the next data field number to be programmed to end the entry Review a Data Field Press Field Number Field s data is displayed but no changes can be made Deleting an Entry Press Field No applies only to phone number account number and pager character fields Interactive Mode Programming 56 57 58 79 80 81 82 Entering Interactive Mode Press Interactive Mode No for example 56 while in Program Mode The Alpha display keypad will display the first of a series of prompts requesting entries After making the appropriate entry press the key to accept the entry and continue to the next prompt 3 5 Installation Instructions Loading Factory Defaults Initializing for Download To Load Default Entries Press 97 while in Program Mode This resets all data fields to the default values shown on the Program Form Use 97 only if you wish to return to the original factory programmed defaults To Initialize Download ID Press 96 while in Program Mode This initializes the system for downloading and resets all the subscriber account numbers and CSID Do not press 97 to load defaults if any programming has been done previously data already programmed into the system will be changed Exiting the
45. set to the selected address to continue Module Addresses Address Module 07 1st 4229 with zones 09 16 08 2nd 4229 with zones 17 24 09 3rd 4229 with zones 25 32 10 4th 4229 with zones 33 40 11 5th 4229 with zones 41 48 12 1st 4204 13 2nd 4204 14 3rd 4204 15 4th 4204 Relay Position 1 4 relay position to continue XX REL POSITION 1 4 22 This the actual or physical relay number with respect the Relay Module upon which it is located For 4204 modules relay numbers are 1 4 For 4229 modules relay numbers are 1 2 The system returns to the Output Number prompt for programming the next device 80 Menu Mode Defining Output Functions Use this mode to program output function definitions up to 48 functions that provide automated control of any of the output devices based on events occurring on individual zones or zones with certain zone types Each output definition is identified by an output function number and includes the following components Output Definition Components Component Description Output Function No A reference number that defines an output s characteristics Activated By Determines whether the initiating event occurs on a zone a zone list or a zone type Event Event that triggers the output action Can be an event occurring on a specific zone number or a zone
46. system so that alarm signals can still be sent to the alarm monitoring station in the event that the telephone lines are out of order alarm signals are normally sent over the phone lines if connected to an alarm monitoring station Table Of Contents Section 1 Features and Installation Highlights sssssssssesssssssssssssssssocsssccocssssovsssssrssossnrsosrnnrrnsrnnr 1 1 Capabilitios amp aree na ian Alunni tam ete anite ae 1 1 Functions renna Rana RA 1 1 Compatible Devices telnet 1 2 Important Installation Highlights Installer Please Read 1 2 Section 2 Mounting and Wiring the Control cele e ecce eee ee ee seen sese etta sese teta sese teta aee teen ases tesa sese eee 2 1 Cabinet and Dock oisi eere ere rte e re e tine ee not dede eit ire 2 1 Mounting the PC 1 cede niece este ple i ce dettes recede de ada eade dba ede dae nodes 2 1 Mounting Board with RF Receiver 2 2 Wiring to i de tete ne 2 3 Sounder Bell Connections nete e hire 2 4 Wiring the AC Transformer oen end Gp epa pmi 2 4 Backup Battery vr een UOTE RE UID OBERE ERI RIED Laise 2 5 Earth Ground PEE 2 5 Hardwire Zones nie esses nenten dieque ide ieu ev eeu iaia 2 6 Do bl Balanced Zon s RITE 2 6
47. the next field Call Waiting If the subscriber s phone service has call waiting and is not using PABX enter 70 11 plus t 13 pause as the PABX entry to disable call waiting during control panel calls If the subscriber does not have call waiting and is not using PABX make no entry in this field NOTES 1 The call waiting disable feature cannot be used on a line 2 Using Call Waiting Disable on a non call waiting line will prevent successful communication to the central station Primary Phone No Enter up to 20 digits Do not fill unused spaces 0 9 11 for 12 for 13 for a pause 2 seconds If you enter fewer than 20 digits exit by pressing To clear entries from field press 41 NOTE Backup reporting in which 8 calls are made to the secondary phone number if no kissoff is received after 8 attempts to the primary number is automatic only if there is a secondary phone number field 42 Pager Report Note In order for pager reports to be sent to the pager phone number you must also enter a primary field 41 or secondary field 42 phone number Secondary Phone No Enter up to 20 digits Do not fill unused spaces 0 9 11 for K 12 for 13 for a pause 2 seconds If you enter fewer than 20 digits exit by pressing To clear entries from field press 42 See backup reporting note in field 41 See Pager Rep
48. those words in the Alpha Vocabulary List shown in boldface type The phone module will not provide annunciation of the other words If a Phone Module is added to an existing system the Alpha descriptors presently in the system should be reprogrammed selecting from those words shown in boldface type in the Alpha Vocabulary List The phone module will not provide annunciation of any other words Programming Zone Descriptors Menu Mode 82 Descriptor programming involves 1 Entering index numbers for up to three words from the vocabulary list for each descriptor 2 Entering up to ten 10 digit custom words if desired which can then be used in descriptors When defining descriptors e Pressing the 6 key accepts the entered index number and moves the cursor to the next position for a descriptor e Pressing the 8 key saves the entered descriptor and moves to the next descriptor Start Zone Descriptor Programming mode by pressing 82 while in Data Programming mode The following prompts are displayed PROMPT VALID ENTRIES EXPLANATION Program Alpha Program Alpha The Program Alpha prompt will appear 0 no Press 1 to continue 0 No 1 Yes 00 1 yes to continue Custom Words The Custom Words prompt will appear Custom Words 0 no Press 0 to program standard alpha descriptors from the fixed O No 1 Yes 00 1 yes vocabulary The system will then automatically display the descriptor to conti
49. with other system messages until the clock is set Set the time and date by doing the following 1 E EI EM E 6113 Alpha Display Security Code DISARMED READY TO ARM 2 Press when the time date is displayed TIME DATE SAT 64 64PM 16 17 88 Current time display A cursor appears under the first digit of the hour To move cursor ahead press gt To go back press e Enter the 2 digit hour setting e Enter the 2 digit minute setting e Press 1 for PM or 2 for AM e Enter the last two digits of the current year e Enter the 2 digit month setting e Enter the 2 digit day setting 3 To exit press when cursor is at the last digit or wait 10 seconds TIME DATE SAT 84 84Peaaa 8 17 Time date editing display TIME ZONE NOTE Use field 83 Time Zone Setting to select the appropriate time zone in which the control is installed This setting provides proper downloader time synchronization if downloading from a different time zone TEST REPORT NOTE When the system clock is set for the first time a test report is automatically set for schedule 32 A test report is sent 12 hours later thereafter the test report is sent every 28 days 12 3 Installation Instructions Various System Trouble Displays 12 4 Alpha Display Fixed Disp Meaning CANCELED ALARM C
50. 02 Entry exit 2 09 Fire 21 Arm AWAY 03 Perimeter 10 Interior w Delay 22 Disarm 04 Interior Follower 12 Monitor Zone 23 No Alarm Resp 05 Trouble Day Alarm Night 14 Carbon Monoxide 24 Silent Burglary 06 24 Hr Silent 15 24 Hour Medical 77 Keyswitch Personal Emerg 76 Arm Maximum 81 AAV Monitor Zone 5800 button type trans only 90 91 Configurable 10 Partition 1 Partition 1 3 partition 3 common to continue Enter the Partition number for this zone Partition 1 is shown entered 10 Report Code 1st01 2nd00 10 Report Code RC First Digit 1 9 10 for 0 11 for B 12 for C 13 for D 14 for E 15 for F 00 to disable Second Digit same as above to continue Enter the report code for this zone which consists of 2 hexadecimal digits each in turn consisting of 2 numerical digits For example for a report code of 10 enter 01 and 00 For Contact ID entering any non zero entry as the first digit enables the report code for this zone Refer to the System Communication section for information about report codes and formats 02 HARDWIRE TYPE EOL 0 Hardwire Type 0 EOL zone doubling ZD 12NC 4 double balanced 2 NO DB to continue This prompt appears only for zone numbers 02 08 Zone 1 is automatically set for EOL operation 02 Response Time Response Time RT 0 10mSec 1 350mSec 2 700mSec
51. 1 the control panel and also supplies signals from the control panel through the premises AC wiring to the Powerline Carrier devices which are plugged into AC outlets You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system home automation UL Powerline Carrier devices are not UL Listed for fire or burglary functions and are intended for 8 PIN TRIGGER CONNECTOR 3 4 5 6 7 8 1 RED OUTPUT 17 ORANGE 12 AUX OUTPUT 18 GREEN BLUE PURPLE 000000 BLACK 10 PSC04 POWERLINE INTERFACE SA4120XM 1 CABLE MODULAR PHONE CORD not supplied 1 BLACK 2 RED 3 GREEN 4 YELLOW PSC04 Powerline Interface Connections 2 12 Mounting and Wiring the Control On Board Triggers Connect field wiring to the desired trigger pin on the 8 pin trigger connector centrally located above the terminal strip If using 1361 10 transformer and powerline carrier devices use the SA4120XM 1 cable part of 4120TR Trigger Cable See Wiring the AC Transformer section for transformer connections If only using the on board triggers you can use 4 wire cable N4632 4 supplied with the control as shown below UL If on board triggers are used the wiring between the control unit and the UL Listed device must be run in conduit be no more than 3 f
52. 2 space 33 34 35 36 37 38 Word Space A AIR ALARM ALLEY AMBUSH AREA APARTMENT ATTIC AUDIO B BABY BACK BAR BASEMENT BATHROOM BED BEDROOM BELL BLOWER BOILER BOTTOM BREAK BUILDING CALL CAMERA CAR CASH CCTV CEILING CELLAR CENTRAL CIRCUIT CLOSED COMPUTER CONTACT D DAUGHTERS DELAYED DEN DESK DETECTOR DINING DISCRIMINATOR DISPLAY DOOR DOWN DOWNSTAIRS DRAWER DRIVEWAY DUCT 065 066 067 068 e 069 071 072 073 075 076 077 079 080 081 082 083 084 085 e 089 e 090 091 e 092 093 094 e 095 096 098 099 100 101 102 103 104 105 106 107 108 109 110 111 113 114 ALPHA VOCABULARY LIST For Entering Zone Descriptors E EAST ELECTRIC EMERGENCY ENTRY EQUIPMENT EXIT EXTERIOR F FACTORY FAMILY FATHERS FENCE FIRE FLOOR FLOW FOIL FOYER FREEZER FRONT G GARAGE GAS GATE GLASS GUEST GUN H HALL HEAT HOLDUP HOUSE I INFRARED INSIDE INTERIOR INTRUSION J JEWELRY K KITCHEN L LAUNDRY LEFT LEVEL LIBRARY LIGHT LINE LIVING LOADING 115 116 117 118 119 121 122 123 125 126 128 129 130 131 132 134 135 136 138 139 140 142 143 144 145 146 147 148 150 151 152 153 155 156 157 159 160 161 162 163 164 165 166 167 168 LOCK LOOP LOW LOWER M MACHINE MAIDS MAIN MASTER MEDICAL MEDICINE MONEY MONITOR
53. 4 1A 00S d9 0891V4 VAYNV9 NI ASN HOS AALST 39 LSNN NOILVTIVLSNI NVIQVNVO V d3Sn S3IHOSS299v ANY 5391 TV SHV3A AH3A3 FONO 1SV31 1V NVIOINHOIL v LSAW WALSAS SIHL NOLLIGQV NI NALSAS SIHL 40 NOIL VH3dO H3dOHd 3HNSN3 OL CIUINDAY SI ONILSAL AIIM NOILVH3dO CIHISIONN ISNVO AVW LVHL 3ON3H3HH31NI I3ATIO3H 39N3H3HHSLNI ANY Ld399V LSNIN 391430 SIHL 39N3H3dH3LNI 3SNV9 LON AVN SIHL 1 SNOLLIONOO OML ONIMOTIOS JHL OL LOSPANS SI NOLIVH3dO SHINY 994 40 SI S3IIdWOO 391430 SIHL 8l0 39N3 IVAIO3 HI ONIH 37 00tt VSn89S ON 151934 994 89 LHvd STINH 293 HLIM SINAWOO LINN SIHL SNIOIAH3S 3H0338 MOVE 09131 LV 3NI13NOHd3131 LOANNOOSIG 300HS 40 HSIH 1N3A3Hd OL NINHVAM SNOLLOQHLISNI 33S STVNINYAL 3NOHd OL S3 1ndOW dlA 9 HO 58 1VNOILdO 40 NOLLO3NNOO HOS ON GVO190G VOVNVO NI V8EVI 9 LOANNOO SNIGNNOYD 193H1Q MOVP XLErH VIA H3dOHd 3NOHd3 13L SNOLLONHISNI INN 3NOHd 335 13SQNVH annoys Hlava T N3349 vu 9NH ONE dil INOZ 404 NIBIA TVOIdAL Ot INOZ A96 MOT38 39VLION S 1OHLNOO dl 9NISSIIOUd NOI19313Q HOSNIS NMOQ SLNHS W31SAS NMOGLNHS HAMOd SV YSISILNAG ALINALLYAN
54. 4286 Phone Module is used the other shows connections when the FA4285 FA4286 is not used Connections use one of the on board triggers UL UL installations using the AAV feature must use the ADEMCO UVCM module part of the ADEMCO UVS system Suggested AAV Module ADEMCO UVS shown or Eagle 1250 AUXILIARY AUDIO LEVEL ADJUSTMENT TRIM POT UVCM MODULE NOTE REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE Notes Set field 91 for AAV and program the appropriate output output 17 or 18 using 80 Menu mode select zone type 607 For voice session monitoring connect a zone to UVCM module terminals 6 amp 7 and program the zone as zone type 81 56 Menu mode E g Using output 18 for the trigger program an output function in 80 Menu as ZT 60 P 0 Action 1 Device 18 TRIGGER X connector OPTIONAL AD MONTORINE zone CONNECTION USE ZONE TYPE 81 CEN PREMISES HANDSET SWITCH BANK 2 SWITCH SWITCH BANK 1 BANK 2 FALLING VOICE TRIG SWITCH BANK 1 INCOMING PHONE LINE aav_uvem 003 VO Figure 15 Connection of AAV Unit When Not Using a FA4285 FA4286 Phone Module CONTROL AUXILIARY AUDIO LEVEL O ADJUSTMENT TRIM 2 6 12VDC c lt z 2 5 REFER UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND
55. A will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended e g exit door left open but the system was disarmed during the Entry Delay time The alarm sounder and keypad sound continuously but stop when the system is disarmed No message will be transmitted to the central station EXIT ALARM EA will appear when the Exit Delay ends if an exit or interior zone contained a fault during closing The alarm sounder and keypad sound continuously until the system is disarmed or timeout occurs An Exit Alarm message is sent to the central station Also results if an alarm from an exit or interior zone occurs within 2 minutes after the end of an Exit Delay CHECK CHECK indicates that a problem exists with the displayed zone s and requires attention CLOCK NOT SET C5 indicates the system s real time clock has not been set ALARM 1xx 1 indicates that communication between control and a zone expander or wireless FAULT 1xx 1 receiver is interrupted where is the device address Check the wiring CHECK 1xx 1xx DIP switch settings on the units 91 If field 199 is set to 1 all ECP module problems are displayed as 91 If there are wireless sensors in the system the Check condition may also be caused by some change in the environment that prevents the receiver from receiving signals from a particular sensor SYSTEM LO BAT BAT with no zone number indicates that th
56. BOARD TAMPER SWITCH N C e a fire alarm installation the keyswitch must be located next to an alphanumeric display keypad The Ademco 4146 keyswitch is UL Listed 00 trigcon 004 V2 EOLR use appropriate value Figure 10 Keyswitch Wiring Connections 2 10 Connecting Relay Modules 1 Mount either remotely or in the control panel 2 Connect to controls keypad terminals using the connector harness supplied with the module Use standard 4 conductor twisted cable for long wiring runs 3 Set each module s device address according to the table at right 4 Connect the desired field wiring to the unit s relay contact terminals UL For UL installation requirements refer to the Installation Instructions for the 4204 Mounting and Wiring the Control Notes Use 4204 or 4229 modules e Supervision 4204 and 4229 modules are supervised against removal The module s device address is displayed as follows if a module is disconnected from the control s terminals or if the module cover is removed and the tamper jumper is installed Alpha CHECK xx Wire Expansion FAULT xx Wire Expansion ALARM xx Wire Expansion Fixed Glass lxx or 91 if field 199 set for 2 digit display where xx is the module s address e If communication tamper failure occurs on a device with zones wired to it all zones on the device will be displayed in their respective partitions Relay Module Add
57. Delay entry 8 Selects whether to use the system s exit delay time Interior Type entry 8 Zones set for this option are treated same as standard zone type 4 bypasses when armed STAY faults displayed Alarm Sounds entry 9 Selects the type of alarms sound for zones set for this zone type Bell Timeout entry 9 Alarms on zones set for this option sound for the duration set in fields 32 amp 33 Fire Zone entry 9 Zones set for this option respond in the same manner as if programmed for zone type 9 Do not set fire zones to respond as a fault in entries 1 6 Trouble Sounds entry 10 Selects the type of trouble sounds for zones set for this zone type periodic beeps once every 30 seconds trouble beeps rapid beeping Chime Enable entry 10 Zones set for this option cause a chime when Chime mode is on 4 11 Installation Instructions Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is Intact EOL Open Shorted RF zone normal RF zone N A RF zn off normal 0 normal 0 normal 0 normal 1 alarm 4 alarm 1 alarm 2 trouble 8 trouble 2 trouble 3 fault 12 fault 3 fault see note 5 see note 6 Entry 1 EOL Open Entry 2 Short Auto Restore Vent Zone ENTRY 3 ENTRY 4 Response when armed STAY and zone is Auto Restore Vent Zone Intact EOL RF zone normal 0 normal 1 alarm 2 trouble 3
58. Fire Zone Reset 22 Disarming RF 39 Any Fire Alarm 58 Duress 31 End of Exit Time 40 Bypassing 60 AAV 32 Start of Entry Time 41 AC Power Failure 66 Function Keyt 33 Any Burglary Alarm 42 System Battery Low 67 Bell Fail 43 Comm Failure Use 0 Any for Partition No P entry 68 Telco line cut 76 Arming Maximum RF 78 Keyswitch red LED 79 Keyswitch green LED Or at Disarming whichever occurs earlier Use 57 Menu Mode to assign the function key function 07 Note In normal operation mode Code 7 NN Key Entry starts Device NN Code 8 NN Key Entry stops Device NN Enter the partition in which this zone type will occur 01 Partition 0 any partition 1 partition 1 Any partition 0 2 partition 2 3 common Press to continue and skip to the Output Action prompt 01 Enter Zn 12 Zone Number If zone number was selected this screen appears Enter the desired zone number associated with this output number Press to continue Enter the zone event that will activate this output 01 Enter Event 0 restore 1 alarm fault trouble Restore 0 Press continue the Output Action prompt 01 Output Action Close for 2 sec 1 Output Action 0 6 see list at right Enter the desired device action as listed below Press the key to continue 0 off 4 Change Device Stat
59. Go No Go Test mode by entering any user code partition specific OFF Dialer Communication Test 1 Enter Installer Code 5 TEST then press 1 at the prompt to start the Dialer Test 1 DIAL 0 WALK no special display on Fixed Word keypads The following will be displayed accompanied by 2 beeps if test is successful PHONE OKAY Cd displayed on Fixed Word Display Keypads A Contact ID report will also be sent code 601 If the dialer test is unsuccessful the following is displayed COMM FAILURE FC displayed on Fixed Word Display Keypads 2 Enter Installer code OFF to clear the display and exit Automatic Standby Battery Tests 1 An automatic test is conducted every minutes to ensure that a standby battery is present and properly connected If a battery is not present or is not properly connected a LOW BATTERY message is displayed and if so programmed will be reported to the central station 2 A battery capacity test is automatically conducted for 2 minutes every 4 hours beginning 4 hours after exiting the Programming mode or after powering up the system In addition entry into the Test mode will also cause a battery capacity test to be initiated If the battery cannot sustain a load a Low Battery message is displayed and if so programmed will be reported to the central station 13 3 Installation Instructions 13 4 SECTION 14 Specifications amp Accessories SEC
60. ID ENTRIES EXPLANATION Zone List No 00 Quit 01 Zone List Number 01 12 zone list number to continue Enter the Zone List Number to program or 00 to end these entries Press to advance In the following displays zone list 01 has been selected for programming 01 Enter Zn Num Zone Number 01 64 zone numbers followed Enter each zone number to add to the zone list followed by pressing example 01 02 03 After all zones are entered press 00 to 00 Quit 00 by to accept each continue zone IMPORTANT Do not include fire zones in zone lists that are used 00 to continue to STOP device actions 01 Del Zn List Deleting Zone Lists To delete the zone list enter 1 All zones in the zone list will be even 0 don t delete list deleted automatically and the system returns to the Zone List No 0 No 1 Yes 0 1 delete this zone list prompt to continue To save the zone list enter 0 Deleting a Zone To save the entire zone list enter 0 and the system returns to the 01 Delete Zones 0 don t delete zones Zone List No prompt 0 No 1 Yes 0 1 to next prompt to delete delete a zone or zones in a zone list enter 1 to continue zones to continue 01 Zn to Delete Delete the Zone Enter each zone to be deleted from the list followed by After all nuo SPS 01 64 zones to be deleted zones to be deleted are entered enter 00 to return to the Zone List 00
61. ILOL H3aNnos SSOHOV A1193HIG HOLSITTEH WHO 0002 LOANNOO NOISIAH3dh S TI38 HOS LNO uadwnr 8 gt pWH3LOL 9 c Qi 3 24 S BS 5o Viva ng gt 3 1 7 woo 0 TM SVI ONIAH ONAS 4 LL 3s amavo 000000 oF Z NXOZIHVS 3sn 8199 5 SNOLLONHLSNI 33S 3 5 5 HO SNOLLO3NNOO HANHOASNVEL 01 1961 HOS CISN Nid 8 HIANNN AONADYAWA OL G31L D3NNOO 38 LON TIVHS 1VN9IS NUVIV uv19una ONIAVH ALIHOHINY 1Y901 SHL JO NOISSIAH3d HL AINO CILLINHId 38 TIVHS INOLLVLS TVHLNIO V HO SHILUYNOOAVAH Wavy IHIH V OL TVNDIS WHv1Vv 3414 JHL 40 NOLLOSNNOO NINA SIHL OL SI JOINS HIVJAH ONINNYId NOLLYNOVAI ONVNILNIVIN ONILSIL NOILVH3dO NOLLWTIVLSNI H3dOHd ONIGINOSAG NOILVWHOHNI Q31NIHd 69220 VIN AONINO HHVd HOHVI AH3LIVG NOILVI9OSSV NOILOFLOHd AIA H31dVHO 22 GHVONVLS S NOILVIOOSSY NOILOILOHd 3414 3H HLIM 39NVOHOOOV NI OITTVLSNI 38 CINOHS LNAWdINOA SIHL SNOLLO3NNOO SNOLLONYLSNI 339 aasn 301430 MH3lHHVO 3NI1H83MOd N3HM NOIZE HO 1281 JO 3OV Id NI FOVAHILNI H3WHOJSNVH LOLXI9EL ASN va VNVO NI NOLZEL ON ISN izer VASE OVAS 9L HAINHOASNVUL NI ONTd
62. LONHLSNI 33S WOHJH3MOd 1139 AZI HO SNIMVHO N3uis 202 ISN NYO SHOIA3QU3HIO 3ui4u04 ONIONNOS TIVONV TvHOdWaL SNOLLLLUVd DINVA AHVIOHNE HOS HLOB jgvais HIMOd XNV N INSHHnO owiamoNi aovsn S AVAA in HO xv vuuoo9 ILON xvwvz oaagei sor INdLNO NUVIV ON gt 4 H3MOd SLAdLNO SNOLIVTIVISNI XV vuoos 13110 G3HOLIMSNN M OVAOLLOL DONV EL SOL XVW 09 Andino HAMOd xnv WSL 3NOZ OL heerd SNOLLONHLSNI VOVNVO NI 2885 33s OLdN 91889 ed SOLAN Wises IQON Naw 08 1 8939007 8OLdN 11889 SV GNV aon 391430 HOS S3NOZ SS3TAHIM NAN NI SA MOTI HOLIMS H3AIHO3H JH uo si 3 A Mino SH3AI303H 9d L 1989 deem Bs HO ANY 535019 HOIHM I LNdLNO v any AMINO SALO SNOLLO Nosinuadns SiL SAYTAH Lnd1no em sassauaav 9 SMd SANOZ 4703 103 gt 3 pem 3 InQOW AV 13H NOISNVdX3 CAUIM 1 hinano HOLIMS Beer TN SUNN 138 HO AN Di S3NOZ 4703 8 3ndOW NOISNVdX3 SNOLLO3NNOO 19313 H108 WOH4 L TAA gt LWHALOL NEO gt 9INH
63. OO SAVH LSNW SHOLOS130 91 SI L INOZ NO SHOLO3 13G 3MOWS AHIM E 40 HAENNN WOIWIXVIN FTAVNINVYDOHd DISIN 00 HO OSE OL 8 1 S3NOZ 3SNOdS3H 4103 519 SINHO 00 3NOZ H YA 39NVLSIS3H 9007 WAWIXVIN lt o e 47103 103 W103 4703 4103 4703 4103 47103 ini D m 5 SWHO SWHO SWHO SWHO SWHO SWHO SWHO SWHO n m 2 0002 0007 0007 0007 0007 0007 0007 0007 2 z n A E gt x S 5 9 E 15 2 lt N N N N N n o o o o o o m X gt Iz z z z z z z gt gt o 2 5 2 o a w N lt o 2 2 gt x S E pd 5 d pd Sd bd yod 5 d bd Ix 2 sea a 5 T d d amp ie s 9 o E n d d d d d d d d 8 9 Q 2 j zl sl b zl 5 5 3NOZ ONIMIM TVOIdAL 3NOZ X 91 ss3uaav OL 135 WALSAS JHL NIVW3H ON Q33N 108 98 Y HLIM INOG 38 LSM 17901 SQVAIN dM09SV4 HO 4HOSVA dxispzv4 ISN NYO SQVdA33 SLOWSY 1885 Oct ezev 6124 98zv S8zv WL008s 9 5 H3HLO SLOWSY CISN 38 NVI OOIXAW NI G3 18WN3SSV d95S S0 SH 5 Nouv novo 33S NOLIVIHOJNI 3131dW09 XNV NI LSNN S vSWH3L SNOL
64. Options include response to entry exit delays Configurable response opens shorts types of alarm trouble sounding dial delay and unique Contact ID report codes Types 92 and 93 can only be programmed via downloader UL installations Zone Types 90 93 may not be used as fire or burglar alarm zones on fire or UL burglar alarm installations NOTE All of the zone types described are available for the wireless portion of the system if used Mechanics of Programming To program the system from a keypad e You must use a 2 line Alpha display keypad e Both partitions must be disarmed Data Field Programming Procedures Task Procedure Entering Program Mode A Press both and at the same time within 50 seconds after power is applied to the control OR B After power up enter Installer code 8 0 0 long beep indicates one of the partitions is armed and system cannot enter program mode method is disabled if you exit the program mode using 98 also Installer code is automatically disabled 4 hours after power up Go to a Data Field Press Field Number for example 21 A display of EE or Entry Error means you have entered a nonexistent field Simply re enter plus a valid field number Entering Data When the desired field number appears simply enter the digits required The keypad beeps three times after the last digit is entered and automatically displays the next data field in
65. Programming Assign zone characteristics report codes alpha descriptors and serial numbers for 5800 RF transmitters 57 Function Key Programming Program each of the four alphabet function keys to perform one of several system operations 58 Zone Programming Assign zone attributes similar to 56 mode but provides a faster Expert Mode programming procedure and is intended for those more experienced in programming controls of this type 79 Output Device Mapping Assign device addresses used by 4229 or 4204 Relay modules and map specific relays and device outputs and assign unit codes for Powerline Carrier devices 80 Output Definitions Define up to 48 output definitions which can control the output relays mapped using 79 Output Device Mapping mode 81 Zone List Programming Create Zone Lists for relay powerline carrier zones chime night stay cross zones and pager zones 82 Alpha Programming Create alpha descriptors for easy zone identification Scheduling Mode code 64 Create schedules to automate various system functions Zones and Partitions Each protection zone needs to be programmed with various attributes using 56 Zone Programming mode or 58 Expert Programming mode Refer to those sections for detailed procedures The system can control two independent areas of protection known as partitions for use by independent users if desired by simply assigning zones to one or the
66. RD WHITE MOUNTING CLIP MOUNTING CLIP NOTE R ov BLACK RED MOUNTING CLIP Notes Do not mount the cabinet on or near metal objects This will decrease RF range and or block RF transmissions from wireless transmitters e Do not locate the cabinet in an area of high RF interference revealed by frequent or prolonged lighting of the LED in the receiver after it is operational random flicker is OK CABINET SUPPORTING SLOTS CIRCUIT BOARD i MOUNTING CLIP DETAIL SIDE VIEW OF BOARD SUPPORTING SLOTS MOUNTING CLIP ANTENNA e ee DO A COMBINATION OF THESE MOUNTING CLIPS HAS BEEN INCLUDED IN YOUR INSTALLATION KIT USE THE APPROPRIATE CLIPS FOR MOUNTING IF NO RF RECEIVER IS USED MOUNT THE PC BOARD USING EITHER THE WHITE OR BLACK CLIPS WHICHEVER ARE INCLUDED IN THE CONTROL PANEL S HARDWARE KIT ANTENNA MOUNT 2 PLACES DETAIL B ANTENNA AND GROUNDING LUG INSTALLATION po_mount 001 V1 Figure 3 Mounting the PC Board and RF Receiver Mounting and Wiring the Control Wiring to Keypads 1 Connect keypads to the control s keypad terminals as shown on the Summary of Connections diagram Determine wire size using the Wire Run Chart below 2 Set keypad addresses Refer to the address setting instructions included with the keypads and set each keypad device address according to the chart at right 3 Program the keypad addresses partition assignme
67. RES CONNECTED TO THE HANDSET TERMINALS ON CONTROL MUST BE MOVED FROM THERE TO TERMINALS 3 AND 4 ON THE FA4285 4286 RING gt BROWN T FA4285 FA4286 VIP MODULE LOUDER 2 VOLUME FA4286 ONLY KEYED HEADER 555 9 UNUSED YELLOW TO DATA OUT term 7 CONTROL NO CONNECTION PANEL CONNECTOR RED TO AUX term 5 TERMINALS WITH FLYING BLACK TO AUX GROUND term 4 USED FOR LEADS GREEN TO DATA IN term 6 KEYPAD CONNECTIONS CONNECT GROUND DIRECT CORD PREMISES ANSWERING MACHINE AND PHONES ANSWERING MACHINE NOTE IF THE TELEPHONE HAS BUILT IN CALLER ID THE CALLER ID FUNCTION MAY NOT WORK FA4285 FA4286 TERMINAL ASSIGNMENTS TIP RING TIP PHONE OUTPUT PHONE INPUT NO CONNECTION AUDIO OUT FA4286 ONLY 1 2 3 4 5 6 7 Lee Se ses 4286 cntrl 10 001 VO 2 14 Long Range Radio Connections Connect the data in data out terminals and voltage input terminals of the Long Range Radio to the control s keypad connection points Set the radio s address to 03 following the instructions provided with the radio Mounting and Wiring the Control Notes Use compatible Long Range Radios e g 7720PLUS 7820 7835C or 78450 Audio Alarm Verification Connections AAV listen in Refer to the connection diagrams below One diagram shows connections when a FA4285 FA
68. T LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACKUP REQUIREMENTS AND UL RESIDENTIAL FIRE INSTALLATIONS OUTPUT CURRENT LIMITATIONS BATTERY INFORMATION To Use Amp Hrs Yuasa Model No 600mA maximum total of NP4 12 or ADEMCO 467 auxiliary power plus bell NP7 12 output currents NP4 12 two NP7 12 two NPG18 12 NOTE Use two batteries connected in parallel Obtain an Ademco Battery Harness Kit SA5140 1 Both batteries will fit inside the panel s cabinet Earth Ground Notes Metal Cold Water Pipe This product has been designed and laboratory Use a non corrosive metal strap copper is recommended tested to ensure its resistance to damage from firmly secured to the pipe to which the ground lead is generally expected levels of lightning and electrically connected and secured electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in areas of severe electrical activity terminal 25 on the control board or the cabinet may be used as the ground connection point The examples of good earth grounds listed at the left are available at most installations AC Power Outlet Ground Available from 3 prong 120VAC power outlets only To test the integrity of the ground terminal use a 3 wire circuit tester with neon lamp indicators such as the UL Listed Ideal Model 61 035 or equivalent available at most electrical supply stores AUXILIARY DEVICE CURRENT
69. The system will now check for a duplicate serial loop number combination 10 INPUT S N L A022 4064 1 Enroll Summary to continue If the serial loop number combination is not a duplicate in the system a display showing the serial number and loop number entry will appear XMIT TO CONFIRM PRESS TO SKIP Confirmation Option to continue This prompt will only appear if you answered Yes at the first prompt in this section The system will enter a confirmation mode so that the operation of the actual programmed input can be confirmed Activate the loop input or button that corresponds to this zone Entd A022 4063 1 Rcvd A022 4064 1 If Serial or Loop Numbers do not match after activating the transmitter to continue If the serial number transmitted does not match the serial number entered a display similar to the one shown appears If the loop number does not match it will also be displayed If so activate the loop input or button on the transmitter once again If a match is not obtained i e summary display does not appear press the key twice and then enter or transmit the correct serial number 10 INPUT S N L A000 0000 0 To Delete a Serial No enter in loop number field undo deletion to continue To delete an existing serial number enter 0 in the loop number field The serial number will change to 0 s If 0 was entered in error simply re enter the loop numbe
70. UND TERM 4 4 12VDC gt TERM 5 ver DATAIN lt FROM gt TERM 7 CONTROL TERMINATE EACH PROGRAMMED ZONE WITH 1000 OHM 1K END OF LINE RESISTOR EACH ZONE S MAX LOOP RESISTANCE G 300 OHMS EOL 4229 002 V0 2 8 Mounting and Wiring the Control Installing the RF Receiver Use any 5800 Series Wireless Receivers such as RF Receiver No of Zones 5881L 5882L upto8 5881M 5882M up to 16 5881H 5882H up to 40 5883 Set Device Address to 00 as described in its instructions set all switches to the right off position Mount the receiver noting that the RF receiver can detect signals from transmitters within a nominal range of 200 feet Connect the receiver s wire harness to the control s keypad terminals Plug the connector at the other end of the harness into the receiver Refer to the installation instructions provided with the receiver for further installation procedures regarding antenna mounting etc NOTE ANTENNAS CIRCUIT BOARD IS MOUNTED IN INSERT IN CONTROL S CABINET GROUNDING 4 LUGS 2 PROVIDED MUST BE INSERTED q IN LEFT HAND TERMINALS OF ANTENNA BLOCKS AND SECURED TO CABINET SEE RECEIVER S AND CONTROL S INSTRUCTIONS INSERT IN RIGHT HAND TERMINALS RIGHT HAND 22 TERMINALS a T Notes The receiver is supervised and a trouble report is sent CHECK 100 displayed if communication between the panel and receiver is interrupted
71. URITY CONTROL 1 Physical 12 1 2 W x 14 1 2 Hx 3 D 318mm x 368mm x 76mm 2 Electrical VOLTAGE INPUT 16 5VAC from plug in 25VA transformer Ademco No 1321 in U S A RECHARGEABLE BACKUP BATTERY 12VDC sealed lead acid type Charging Voltage 13 8VDC ALARM SOUNDER 12V 2 0 Amp output can drive 12V BELLS or can drive one or two 702 series connected self contained 20 watt sirens Do not connect two 702s in parallel AUXILIARY POWER OUTPUT 12VDC 600mA max Note For UL installations Alarm Sounder plus Auxiliary Power currents should not exceed 600mA total 3 Communication FORMAT SUPPORTED ADEMCO Express 10 characters sec DTMF TouchTone Data Tones 1400 2300Hz ACK 1400Hz KISSOFF ADEMCO Low Speed 10 pulses sec 1900Hz Data Tone 1400Hz ACK KISSOFF Radionics SESCOA 20 pulses sec 1800Hz Data Tone 2300Hz ACK KISSOFF Can report 0 9 B F Ademco Contact ID 10 characters sec DTMF TouchTone Data Tones 1400 2300Hz ACK 1400Hz KISSOFF LINE SEIZE Double Pole RINGER EQUIVALENCE 0 1B FCC REGISTRATION No 5GBUSA 44003 AL E 4 Maximum Zone Resistance Zones 1 8 300 ohms excluding EOLR standard zones COMPATIBLE DEVICES Keypads FA245KP FA260KP Fixed Word Keypads FA560KP Alpha Keypad FA245RF FA260RF FA700KP Touch Screen Keypad Symphony Advanced User Interface Wireless Receivers 5881L 5882L accepts up to 8 transmitters 5881M 5882M accepts up to 16 transmitters 5881H 5882H accepts up to sys
72. Zone Dorblin gece a ilo 2 6 Smoke Detectors iano nas vereer ke rede he ek ene vande eese einde SKA alu 2 6 4219 4229 Expansion Zones iet eee O 2 8 Installing the RE Receiver rie eti n m a er eir 2 9 Installing 5800 TM Mod le eee m i e ee Lian 2 9 Installing the Transmitters ii 2 9 Installing a Keyswitbch iei tete t 2 10 Connecting Relay 2 11 Powerline Carrier Deylcesg 2 12 On Board Triggers secs nale Lele 2 13 Phone Line Phone Module Connections i 2 14 Long Range Radio Connections i 2 15 AAV Connections AIA exten TA REI ii 2 15 Section 3 Programming Overview sssssssssosoossocoossoooossooossreoosoreooesroosooroo00rnr00s00r000000000000 000000 teen ae 000000 0000 3 1 About Programming aspres 3 1 ZONES ANG Partitions ss ie 3 1 Keypads 1 lib tense v eet deni e ela 3 2 Wireless Receiver and Transmitters i 3 2 Pager Prosrammine spa eves sods cova RR eat 3 2 Function Keys ennio iaia E lE eater nie darsi 3 3 Output Devices ett a 3 3 ode o
73. a data field 195 keypad 8 23 n a data field 196 5800TM Module 28 n a automatic Addressable devices are identified by 1 plus the device address when reporting Enter a report code for zone 91 to enable addressable device reporting default reports enabled See field 199 for addressable device ECP 3 digit 2 digit identification keypad display options 3 6 SECTION 4 Data Field Programming About Data Field Programming The following pages list this controls data fields in numerical order Field numbers are listed in the left column followed by a Title and Data Entries column which lists the valid entries for each field Experienced installers can simply follow this column when programming the data fields The Explanation column provides explanatory information and special notes where applicable Programming Data Fields Data field programming involves making the appropriate entries for each of the data fields Start Data Field programming by entering the installer code 8 0 0 NOTE The following fields will not be accessible after the automatic upload that occurs when you exit program mode 20 Installer Code 40 46 Telephone and Account Numbers and 94 Download Phone Number See Automatic Upload note in Mechanics of Programming Exiting Program Mode section SIA Guidelines Notes in certain fields give instructions for programming the FA168CP GP for False Alarm Reduction
74. all all Burglary Dialer Delay 0 dial delay 1 15 seconds 2 30 seconds 3 45 seconds Provides delay of BURGLARY ALARM report to the central station which allows time for the subscriber to avoid a false alarm transmission This delay does not apply to zone type 24 alarms silent burglary or to 24 hour zone types 6 7 and 8 silent panic audible alarm auxiliary alarm which are always sent as soon as they occur UL must be 0 SIA Installations delay must be minimum of 30 seconds 4 3 Installation Instructions FIELD fl TITLE and DATA ENTRIES EXPLANATION 54 Dynamic Signaling Delay Intended for use with Long Range Radio reporting 0 disabled both signals sent This field lets you select the time the panel should wait for 1 15 entry times a 15 second delay acknowledgment from the first reporting destination see 55 before e g 1 15 seconds 2 30 seconds etc it attempts to send a message to the second destination Delays can be selected from 0 to 225 seconds in 15 second increments This delay is per message If 0 is entered in this field the control panel will send redundant reports to both Primary Dialer and LRR UL Installations For Fire Alarm and UL Burglar Alarm installations without Line Security Grade A the maximum Dynamic Signaling Delay must be no more than 15 seconds For UL Burglar Alarm installations with Line Security Grade AA Dynamic Signaling Delay
75. als that the RF Type does but the control does not supervise the check in signals The transmitter may therefore be carried off premises BR Unsupervised Button RF Type only send fault signals They do not send restore or check in signals They will indicate a low battery condition when tested or activated normally The transmitter may be carried off premises LOOP 3 3 LOOP 2 LOOP 4 S lt YOU MUST TI 2 v MUST gt va LOOP 4 m LOOP 2 ENROLL JAS L i 2 4 JE YOU MUST THIS RU LOOP THIS LOOP 1 5 ENROLL BUTTON LOOP 1 BUTTON f r THIS BUTTON LOOP 3 Qu loop i SET HOUSE CODE 5801 5802MN ENROLL AS ENROLL AS 5804BD UR OR RE UR OR RE ENHOLL vee BR ENROLL AS BR LOOP 1 PRIMARY gt 2 LOOP 2 LOOP 2 AR 5808 Lo AUX ENROLL AS RF REED REED A CENTER LOOP 1 LOOP 1 4 dg TERMINALS ALTERNATE SRO LI TERMINALS ay LOOP 3 LOOP 1 OSITION N FOR LOOP 2 RIGHT 5809 5816 817 ENROLL AS RF ENROLL AS RF ENROLL ro RF LOOP 2 7 2 LOOP 2 REED REED LOOP 3 TERMINALS LOOP 1 NE INTERNAL SHOCK 1 LOOP 1 pd LOOP 3 p TERMINALS SENSOR TERMINALS BE 5890 581 58195 WHS amp BRS 5850 GBD ENROLL AS ENROLL AS ENROLL AS RF ENROLL AS RF RF OR RM vzor oosvo NOTE For information on any transmitter not shown above refer to the instructions accompanying that transmitter for details regarding loop numbers etc UL NOTE The
76. and safety hazards like smoking in bed violent explosions escaping gas improper storage of flammable materials overloaded electrical circuits children playing with matches or arson Depending on the nature of the fire and or location of the smoke detectors the detector even if it operates as anticipated may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual Passive Infrared Detectors do not provide volumetric area protection They do create multiple beams of protection and intrusion can only be detected in unobstructed areas covered by those beams They cannot detect motion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperature of the protected area approaches the temperature range of 90 to 105 F 32 to 40 C the detection performance can decrease Alarm warning devices such as sirens bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors If warning devices are located on a different l
77. ard Trigger Connector with 4 Wire Cable for Trigger Use Only 2 13 Installation Instructions Phone Line Phone Module Connections 1 Connect incoming phone line and handset wiring to the main terminal block via an RJ31X jack as shown in the Summary of Connections diagram at the back of this manual Wire colors represent the colors of the cable to the RJ31X jack If using a phone module continue with the following steps 2 Make 12 and and data in and data out connections from the phone module to the control using the connector cable supplied with the phone module then insert the keyed connector at the other end of the connector cable into the header on the phone module Connect Phone Module terminals as shown below Use an RJ31X jack with a direct connect cord and make all connections exactly as shown Caller ID Units If a Caller ID unit is being used connect the unit directly to the Handset terminals 21 amp 22 on the control as shown Phone Module Problems Notes e Use FA4285 or FA4286 Phone Modules Compatibility FA4286 Phone Modules must have software version WA4286 15 1 or higher refer to the label on the square FA4286 microprocessor chip e Only one phone module can be used and it can only be connected to partition 1 e The phone lines must be in service for the phone module to function even when accessing the system from an on premises phone e If you are also using an
78. ble on Zone 1 If used this option limits the number of smoke detectors to 1 enable a maximum of 10 rather than 16 To enable the clean me feature a time response setting of 3 1 2 seconds must be entered in 56 Zone Programming for zone 1 Device Duration 1 2 These entries set the duration for output action options 5 Duration 0 15secs 6 2 1 2min 12 8 min 1 and 6 Duration 2 programmed in 80 Output Function 1230secs 7 3min 13 10 min Programming 2 45secs 8 4min 14 12 min 3 60secs 9 5min 15 15 min 4 90secs 10 6 5 2 11 7 181 50 60 Hz Operation Select the type of power applied to the control 0 60 Hz This option is used for Real Time Clock synchronization 1 50 Hz 4 10 Configurable Zone Type Programming Fields The system allows you to define up to 4 custom zone types zone types 90 93 based on the options described All configurable zone types can be programmed via the downloader Configurable zone types 90 and 91 can also be programmed from keypad using data fields 182 185 described below UL installations Do not configure zones as fire alarm or UL burglar alarm zones Configurable Zone Type 90 0 15 values for each of 10 entries 0 9 10 10 11 11 12 12 18 13 14 14 15 15 Enter appropriate value for each entry 1 10 based on charts on the next page To calculate the value for eac
79. button must be assigned Type 23 e Can be used on a zone when an output relay action is desired but with no No Alarm Response accompanying alarm e g lobby door access The system can still be armed when these zone types are in a faulted condition Type 24 Usually assigned to all sensors or contacts on exterior doors and windows where Silent Burglary bells and or sirens are NOT desired Provides an instant alarm with NO audible indication at any keypad or external sounder if the zone is faulted when the system is armed in the Away Stay Instant or Maximum modes A report is sent to the central station Type 76 e Arms the system in Maximum mode when the zone is activated Arm Maximum BR e Pushbutton units send the user number to the central station when arming or only disarming e User number for button must be assigned Type 77 e Assign to zone wired to a keyswitch Keyswitch Do not use devices assigned as input type BR with this zone type Type 81 Assign to zone connected to AAV module AAV Monitor Zone Monitors 2 way voice sessions as follows When the zone is faulted all alarm sounding and dialer reporting stops except for fire alarms which immediately terminate the voice session and cause a fire report to be sent When the zone is restored session ended sounding resumes if bell timeout has not expired and reports that were stopped are sent Types 90 93 Allows for various custom responses
80. d This system uses addressable keypads and Zone Expander Modules see table of addresses in Programming Overview section Keypads must be set for addresses 16 23 first keypad is address 16 which is different from previous controls and programmed in data fields 190 196 Zone Expander Modules must be set for specific addresses 07 11 based on the zone numbers used see table of addresses in 4219 4229 Expansion Zones section 4204 Relay Modules must be set for specific addresses 12 15 see Connecting Relay Modules section This control will not power up unless AC power is connected will not power up on battery alone However once the system is powered up it will operate on battery power in the event of AC loss Relays have two programming menu modes Use 79 Menu mode to map module addresses and device output numbers Use 80 Menu mode to define the output functions see Output Device Programming section This system supports programmable function keys Use 57 Menu mode to define the function keys see Function Key Programming section This system provides various paging features Refer to the Programming Overview section for a summary on pager programming SECTION 2 Mounting and Wiring the Control This section describes the procedures for mounting and wiring this control and its peripheral devices In the following subsections procedures are listed in the left column while notes and pertinent explanatio
81. d Option NOTE Address 16 is reserved for keypad 1 which is automatically set 0 no suppression to partition 1 with all sounds enabled 1 suppress arm disarm and E E beeps 2 suppress chime beeps only 3 suppress arm disarm E E beeps and chime beeps MEIN Keypad 3 Device Address 18 Keypad 3 See field 190 for entries and explanation ME Keypad 4 Device Address 19 Keypad 4 See field 190 for entries and explanation KEEN Keypad 5 Device Address 20 Keypad 5 See field 190 for entries and explanation ME Keypad 6 Device Address 21 Keypad 6 See field 190 for entries and explanation NES Keypad 7 Device Address 22 Keypad 7 See field 190 for entries and explanation MEG Keypad 8 Device Address 23 Keypad 8 See field 190 for entries and explanation Exit Time Display Interval If enabled keypads display the exit time remaining after arming the 0 no display system with display updates at the interval selected i e if the exit 1 5 seconds between display updates delay is 30 seconds and 2 is selected in this field the keypad display refreshes every 2 seconds displaying 30 28 26 24 etc An interval greater than 1 may be necessary for some older keypads to allow users time to enter key presses between display updates FIXED WORD KEYPAD NOTE Do not use exit times greater than the 180 second delay option if using 3 digit display keypads and not greater than the 96 second delay option if using 2
82. digit display keypads e g FA245RF Using a longer delay time may cause end user confusion because 3 digit display keypads cannot display times greater than 199 and 2 digit display keypads cannot display times greater than 99 If longer exit times are required by the installation it is recommended that exit time display be disabled 0 198 Display Partition Number If selected the partition number is displayed in the upper left corner of 0 1 yes the display This is useful when using the GOTO partition function 199 Fail Display Select 0 if using Alpha keypads and or 3 digit Fixed Word Display 0 3 digit display 1 device address keypads ECP faults will display 1 plus the device address 00 30 of 1 2 digit fixed display as 91 device causing the fault e g faults on device 07 display as 107 Select 1 if using 2 digit Fixed Word Display keypads e g FA245RF If selected ECP faults for all devices will display as 91 on 2 digit displays and 191 on 3 digit or Alpha keypads NIGHT STAY NOTE Setting this field to 1 disables the control s Night Stay feature code 3 3 In addition the Canceled Alarm display is also disabled field 86 4 13 Installation Instructions SECTION 5 Zone Programming 56 and 58 Menu Modes About Zone Programming 56 Zone Programming is used to program zones zone types rep
83. e 1 Close for 2 seconds 5 Duration 1 see data field 177 2 Stay Closed 6 Duration 2 see data field 177 3 Pulse 1 sec ON 1 sec OFF m 3 2 A o c c S 2 R02 02 Output Number 01 16 output no 17 18 on board triggers Enter the device output number programmed in 79 Menu Mode you want associated with this output Press to continue 02 A E P TRIG RO2 1 1 3 ZL 00 Summary Screen summary screen appears showing the programmed settings Press to continue Installation Instructions About Zone Lists Zone lists let you group individual zones for use with certain system actions The following table shows the available zone lists and their purposes SECTION 7 Zone Lists 81 Menu Mode List No Used for 1 2 general purpose 3 chime by zone 4 cross zones 5 night stay zones night stay feature is disabled if field 199 is set to 1 6 7 8 general purpose 9 zones that activate Pager 1 10 zones that activate Pager 2 11 zones that activate Pager 3 12 zones that activate Pager 4 Zone List Programming Zone List programming involves 1 Selecting an appropriate zone list number 2 Adding the desired zone numbers to be included in that list Start Zone List Program Mode by pressing 81 while in Data Programming mode The following prompts are displayed 81 Menu Mode PROMPT VAL
84. e Entry Delay 1 2 0 no 1 delay 1 2 delay 2 Respond as Interior Type 0 8 yes Use Exit Delay 0 no 4 use exit delay see note 2 ENTRY 10 Trouble Sounds 0 none 1 periodic beep 2 trouble beeps Respond as Fire Zone Mode On see zone type 09 see note 4 Chime when Chime INTACT EOL OPEN SHORTED ZONE 002 V0 Zone Conditions Represented in Entries 1 6 Configurable Zone Type Notes 1 Do not use the fault delay option with a configurable zone type if it is set for an entry or exit delay otherwise unpredictable results may occur 2 To create an interior type zone select respond as interior zone type entry 8 interior type yes and set zone response to fault in entries 3 4 to ensure fault displays do not set as normal alarm or trouble 3 Do not set fire zones to respond as a fault entries 1 6 otherwise faults will not display unless the key is pressed 4 4219 4229 modules must use EOLRs or unpredictable results may occur 5 RF Zones The open options in entries 1 3 and 5 are not applicable for RF zones Use the intact EOL option for normal RF zone conditions and shorted for off normal RF zone conditions 6 a Zone Doubling Double Balanced A short on either zone of a zone doubled pair or on a double balanced zone causes a tamper condition b For double balanced z
85. e is initially set See Periodic test report note in Enter Event prompt below ENTER EVENT NOTE Events 07 and 10 cause the keypad to beep every 30 seconds when messages are displayed Stop the beeps and clear the display by pressing any key Enter Event 00 clear event 01 Relay On Off 02 User Access 03 Latch Key Report to Pager 04 Forced Stay Arming 05 Forced Away Armingt 06 Auto Disarm 07 Display Reminder 10 Display custom words tt 11 Periodic Test Reportttt to continue Enter the desired event number for event you want to occur at a specified time Events 10 11 are reserved for the installer only Latch key report option 03 is sent to all pagers in the user s partition and is active only when the system is armed message sent is 777 7777 User must be enabled for paging see User Attributes in System Operation section t Forced bypass is automatically enabled regardless of setting in field 23 tt if selected system displays custom words 8 9 and 10 at defined time Can be used as installer s reminder message to the end user ttt A test report is automatically set for schedule 32 when the system time is initially set and the first report is sent 12 hours later thereafter the test report is sent every 28 days DEVICE NUMBER XX Device Number 01 18 device number to continue This prompt appears if event 1 relay on off was selected otherwise it i
86. e system s main standby battery is weak LO BAT BAT with a zone number and a once per minute beeping at the keypad indicates that a low battery condition exists in the wireless sensor displayed zone 00 indicates a wireless keypad If the battery is not replaced within 30 days a CHECK display may occur Note Some wireless sensors contain a non replaceable long life battery which requires replacement of the entire unit at the end of battery life e g Nos 5802 5802CP TELCO FAULT 94 Telephone Line Failure indicates that a monitored telephone line if programmed in field 92 has been cut or disconnected Depending on how the system was programmed the keypad may also produce a trouble sound and the external sounder may be activated Silence by entering installer code OFF Busy Standby dl If this remains displayed for more than 1 minute the system is disabled Modem Comm The system is communication with the central station for change of function or status verification no display no display Power Failure If there is no keypad display at all and the LEDs are unlit operating power AC and battery for the system has stopped and the system is inoperative If the message LOSS Alpha display keypads or NO AC Fixed Word display keypads is displayed the keypad is operating on battery power only If the battery standby capacity is used up during a prolonged AC power outage the control s power will shut
87. ed enter 1 KEN Confirmation Of Confirmation of arming is 1 2 second external sounder ding Arming Disarming Ding Confirmation of disarming is two short dings 0 no ding If 1 selected ding occurs when closing opening report is sent or at 1 confirmation ding after the end of Exit Delay arming disarming system If 2 selected ding occurs upon reception of the wireless 2 confirmation ding after arming disarming arming disarming command from RF button or RF keypad only UL installations must be 1 for UL Commercial Burglar Alarm installations 39 Power Up In Previous State When the system powers up armed an alarm will occur 1 minute 0 always power up in a disarmed state after arming if a zone is faulted 1 assume the system status prior to Note that if the previous state was armed Away or Stay the system power down will not respond to sensor changes for 1 minute which allows time for sensors such as PIRs to stabilize UL installations must be 1 power up in previous state SIA Guidelines must be 1 Dialer Programming 40 50 FIELD TITLE and DATA ENTRIES EXPLANATION PABX Access Code or Call Waiting Disable Enter up to 6 digits if PABX is needed to access an outside line Do not fill unused spaces 0 9 11 for 12 for 13fora pause 2 seconds To clear entries from field press 40 If fewer than 6 digits need to be entered exit by pressing which advances to
88. een FA TOBC GP Security System Installation and Setup Guide LLL CL N First Alert K PROFESSIONAL SECURITY SYSTEMS A Honeywell Company K5305 5GPV2 9 04 Rev A ii RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke heat detectors we subscribe to the recommendations contained in the National Fire Protection Association s NFPA Standard 72 noted below Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows For minimum protection a smoke detector should be installed outside of each separate sleeping area and on each additional floor of a multi floor family living unit including basements The installation of smoke detectors in kitchens attics finished or unfinished or in garages is not normally recommended For additional protection the NFPA recommends that you install heat or smoke detectors in the living room dining room bedroom s kitchen hallway s attic furnace room utility and storage rooms basements and attached garages In addition we recommend the following Install a smoke detector inside every bedroom where a smoker sleeps e Install a smoke detector inside
89. eet apart and have no intervening barriers or walls 8 PIN TRIGGER CONNECTOR 1 gt 3 4 5 6 7 8 O ORANGE GREEN PURPLE N co E 4 LE 2 5 2 lol gt e 2 o SA4120XM 1 CABLE TRIGCON 003 VO Figure 12 On Board Trigger Connector with SA4120XM 1 Cable for Use With 1321X10 Transformer Notes There are two on board triggers that can be used to activate output devices These outputs are normally high and go low upon programmed condition The outputs can be programmed for inverted operation normally low go high using 79 Menu mode Program these triggers using 80 81 Menu modes as you would for any other relay output When using these outputs note pin 1 output number 17 trigger 1 15 ohms to ground when closed output low open when off output high normal default can be used to reset smoke detector power must set output normal low yes in 79 Menu mode and set for zone type 54 fire zone reset in 80 Menu mode or can support 12V relay module that draws less than 100mA pin 5 output number 18 trigger 2 100 ohms to ground when closed output low open when off output high normal default or can support 12V relay module that draws less than 20mA t e g Altronix AX RBS 8 PIN TRIGGER CONNECTOR 3 4 5 6 7 8 o8 606000 GREEN 3 zl N E 2 n E 2 o 12 AUX OUTPUT 18 00 trigcon 005 V2 Figure 13 On Bo
90. el then waits for a kissoff frequency from the receiver acknowledging that the message was received and understood If the handshake frequency is not given or is not understood by the panel the panel will not send its message Once the handshake frequency is received and understood by the panel the panel sends its message If there is an error in the transmission the receiver does not receive a valid message the kissoff frequency is not given by the Central Station receiver The panel makes a total of eight attempts to the primary telephone number and eight attempts to the secondary telephone number if programmed to get a valid message through If the panel is not successful after its numerous attempts the keypad displays COMM FAILURE on alpha keypads or FC on fixed word keypads Report Code Formats The following chart lists the formats and types of handshake kissoff frequencies the panel supports FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME Low Speed 4 2 1400 Hz 1900Hz 10PPS 1400 Hz Under 15 secs Standard report Contact ID 1400 2300 Hz DTMF 10 cps 1400 Hz Under 3 secs The following table describes each format in greater detail FORMAT TYPE DESCRIPTION 4 2 Format Comprises a 4 digit subscriber number and 2 digit report code Report codes are entered in Programming mode ADEMCO Contact ID Comprises a 4 or 10 digit subscriber number depending on format
91. eld 192 20 keypad 5 e data field 193 21 keypad 6 data field 194 22 keypad 7 e data field 195 23 keypad 8 e data field 196 To enable keypads 1 Set desired address at keypad refer to keypad s instructions for setting the address 2 Use data field program mode to enable keypad addresses assign a partition enable sound options in fields 190 196 as shown in the table above 3 If desired use data field 198 to turn on the display of the partition number 4 Set the following keypad related data fields as required by the installation 21 Quick Arm Enable 23 Forced Bypass 84 Auto STAY Arm 5 If using AUI enable each unit in field 189 and set AUI 1 to address 1 AUI 2 to address 2 Wireless Receiver Transmitters and Wireless Keys keyfobs Receiver Set the receiver s address to 00 using its DIP switches then set the following options 22 RF Jam Option 24 RF House ID Code if using wireless keypads for each partition 67 Transmitter Low Battery Report Code These fields must be enabled for Residential 75 Transmitter Low battery restore report code Fire UL Residential Burglar Alarm and UL Commercial Burglar Alarm installations Transmitters Use 56 or 58 Zone Programming Menu modes to program zone information and enroll transmitters Wireless Keys Use Wireless Key Programming Templates section of the 58 Zone Programming Menu mode to program zone information and enroll each bu
92. ellaneous System Fields IELD I TITLE and DATA ENTRIES EXPLANATION 77 Daylight Saving Time Enter the start and end month for daylight savings time if Start End Month applicable to the region 0 Disabled 4 April 1 Jan 10 Oct 2 Feb 11 Nov 3 Mar 12 Dec 78 Daylight Saving Time Enter the start and end weekend for daylight savings time if Start End Weekend applicable to the region 0 disabled 4 fourth 1 first 5 last 2 second 6 next to last 3 third 7 third to last 79 Output Device Mapping Menu Use this menu mode to enter output devices powerline carrier Mode devices into the system See Output Device Programming section for procedures 80 Output Programming Menu Mode Use this menu mode to define output functions for use with output devices powerline carrier devices See Output Programming section for procedures 81 Zone List Programming Menu Use the menu mode to define zone lists See Zone List Mode Programming section 82 Alpha Descriptor Programming Use this menu mode to assign alpha descriptors to zones and or Menu Mode create partition descriptors 83 Time Zone Selection Select the appropriate time zone in which the control is installed 0 Eastern 2 Mountain This setting provides proper downloader time synchronization if 1 Central 3 Pacific downloading from a different time zone 84 Auto Stay Arm If enabled the system will automatical
93. er switch Transmitter e Has unique input loop codes Loop 1 Built in shock sensor loop wired to TB1 normally closed Loop 2 For a closed circuit contact loop using the built in reed switch in conjunction with a magnet Loop 3 Externally wired closed circuit contact loop connected to TB2 5827 Wireless Uses House ID Can be used to turn the burglary protection on and off Keypad only e Features the same built in panic functions as wired keypads e The keypad is identified as zone 00 on wired keypads when it transmits with a low battery 5827BD Wireless Two Uses House ID Requires 5800TM Transmitter Module Way Keypad only e Operates the system similarly to wired keypads including panic functions e Can indicate system status via its 3 LEDs and sounder e Includes 3 panic keys 5849 Glassbreak RF House ID must also be set Detector Requires both sound and shock of breaking glass to cause alarm to be transmitted 5890 PR Detector RF Dual element passive infrared detector transmitter with built in selectable pulse count Note There is a 3 minute lockout between fault transmissions to conserve battery life 5899 Magnets Package of 4 magnets for use with 5816 and 5817 transmitters 14 5 Installation Instructions 14 6 SECTION 15 Regulatory Agency Statements RADIO FREQUENCY EMISSIONS Federal Communications Commission FCC Part 15 This device complies with part 15 of the FCC rules Operation is s
94. erted output Use the worksheet on the Programming Form printed separately to organize device numbers Output Normally Low 0 no standard default 1 yes to continue 17 OUT NORM LOW 0 NO1 YES 0 This prompt appears only for Triggers 17 and 18 Selecting 0 no sets the output level normally high Selecting 1 yes sets the output normally low Output Trigger 17 can be used for resetting 4 wire smoke detectors by connecting it to the negative power terminal of the smoke detector selecting 1 at this prompt and setting as zone type 54 fire zone reset in 80 Menu mode After entry display returns to Output Number prompt Use 80 Menu mode to program the function of the trigger XX OUTPUT TYPE Output Type Select whether this is a relay or a Powerline Carrier X 10 device 0 delete If X 10 is selected go to A prompt DELETE 0 1 relay on 4204 4229 module If relay is selected skip to prompt 2 Powerline Carrier device to continue A Unit Number If X 10 is selected a prompt for the unit number appears XX UNIT No 01 16 predefined address Enter the unit code set at the device and press yy to continue The system returns to the Output Number prompt Module Address If relay is selected this prompt appears XX MODULE ADDR 07 15 predefined address Enter the predefined address for this module as listed below Make 07 15 yy sure the module s DIP switches are
95. evel of the residence from the bedrooms then they are less likely to waken or alert people inside the bedrooms Even persons who are awake may not hear the warning if the alarm is muffled by noise from a stereo radio air conditioner or other appliance or by passing traffic Finally alarm warning devices however loud may not warn hearing impaired people Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of service Telephone lines are also subject to compromise by sophisticated intruders Even if the system responds to the emergency as intended however occupants may have insufficient time to protect themselves from the emergency situation In the case of a monitored alarm system authorities may not respond appropriately This equipment like other electrical devices is subject to component failure Even though this equipment is designed to last as long as 10 years the electronic components could fail at any time Continued 16 1 Installation Instructions WARNING THE LIMITATIONS OF THIS ALARM SYSTEM Continued The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance This alarm system should be tested weekly to make sure all sensors and transmitters are working properly The security keypad and remote keypad should be tested as well Wireless transmitters used in some syste
96. every bedroom where someone sleeps with the door partly or completely closed Smoke could be blocked by the closed door Also an alarm in the hallway outside may not wake up the sleeper if the door is closed e Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humidifiers are used 9 DINING e Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet 12 meters long o o LIVING ROOM BEDROOM Vion Wi Smoke Detectors for Minimum Protection P Smoke Detectors for Additional Protection Install smoke detectors in any room where Ebs A Heat Activated Detectors alarm control is located or room lea es where alarm control connections to mE A LVNG RM CLOSED GARAGE source or phone lines are made If detectors are not so located a fire within the room could prevent the control from reporting a fire or an intrusion floor_plan 001 VO THIS CONTROL COMPLIES WITH NFPA REQUIREMENTS FOR TEMPORAL PULSE SOUNDING OF FIRE NOTIFICATION APPLIANCES Recommendations For Proper Intrusion Protection For proper intrusion coverage sensors should be located at every possible point of entry to a home or commercial premises This would include any skylights that may be present and the upper windows in a multi level building In addition we recommend that radio backup be used in a security
97. exit delay and an EXIT ALARM message will be sent to the central station With Contact ID format the message will contain the zone number and error code 374 ALARM EXIT ERROR 4 4 IELD TITLE and DATA ENTRIES EXPLANATION Trouble Report Code This will be sent if a zone has a trouble condition 0 no report UL Required for UL commercial burglar alarm installations and 1st digit non zero send report required for residential fire alarm installations Bypass Report Code This will be sent when a zone is manually bypassed 0 no report UL Required for UL commercial burglar alarm installations 1st digit non zero send report AC Loss Report Code Timing of this report is random with up to a 4 hour delay If AC 0 no report restores before the report goes out there is no AC RESTORE 1st digit non zero send report report UL Required for UL commercial burglar alarm installations and required for residential fire alarm installations Low Bat Report Code Sent when a low battery condition exists in the system s battery 0 no report UL Required for UL commercial burglar alarm installations and 1st digit non zero send report required for residential fire alarm installations Test Report Code Sent periodically to test that the communicator and phone lines are 0 no report operational Frequency of report is set in Scheduling mode event 11 1st digit non zero send report NOTE A test report is au
98. ext field Enter up to 20 digits number To clear entries from this field press 166 167 Pager 3 Characters See field 161 for explanation of entries If fewer than 16 characters Enter up to 16 characters exit by pressing and next field number To clear entries from this field press 167 Pager 3 Report Options Enter the types of reports to be sent to Pager 3 for each partition see Pager 1 reports field 162 for entries except use zone list 11 Pager 4 Phone No If you enter fewer than 20 digits exit by pressing and next field Enter up to 20 digits number To clear entries from this field press 169 Pager 4 Characters See field 161 for explanation of entries If fewer than 16 characters Enter up to 16 characters exit by pressing and next field number To clear entries from this field press 170 Pager 4 Report Options Enter the types of reports to be sent to Pager 4 for each partition see Pager 1 reports field 162 for entries except use zone list 12 Pager Delay Option for Alarms This field determines the delay of alarm reports to the pager This 0 none 2 2 minutes gives the Central Station enough time to verify the alarm report that 121 minute 3 3 minutes it received before the dialer attempts to dial the pager This delay is for ALL pagers in the system Miscellaneous System Fields Clean Me Option This is a maintenance feature for ESL 2 wire smoke detectors 0 disa
99. fault RF zone N A 0 normal 4 alarm 8 trouble 12 fault see note 5 Entry 3 EOL Open ENTRY 5 Response when armed AWAY and zone is Open Intact EOL RF zone normal 0 normal 1 alarm 2 trouble 3 fault RF zone N A 0 normal 4 alarm 8 trouble 12 fault see note 5 Entry 5 EOL Open ENTRY 7 Display Faults Power Reset Verification 0 show alarms 0 no when armed 4 power reset amp disarmed after fault 1 don t show alarms when 12 verification armed show see zone alarms trbles type 16 faults when disarmed 3 never show any alarms trbles faults Entry 7 Fault Display Power Entry 8 Entry Delay 1 Entry Delay 2 Exit Delay Reset Verification Interior Zone Type ENTRY 9 Alarm Sounds Use Bell Timeout 0 4 yes steady bell see fields 32 and keypad 33 3 pulsing bell and keypad Entry 9 Alarm Sounds Bell Timeout Fire Zone ff Entry 10 Trouble Sounds Chime Open with code OFF Byp when Shorted disarmed RF zn off normal 0 normal 1 alarm 2 trouble 3 fault see note 6 Entry 4 Short Byp Disarmed Byp Armed ENTRY 6 Dial Delay see field 50 Fault Delay Shorted see field 87 RF zn off normal 0 normal 1 alarm 2 trouble 3 fault see note 6 Entry 6 Short Dial Delay Fault Delay 8 use delay 0 4 use delay see note 1 ENTRY 8 Us
100. fines the way in which the system responds to faults in that zone Zone types are defined below Type 01 e Assign to zones that are used for primary entry and exit Entry Exit Burglary 1 Provides entry delay when zone is faulted if control is armed in the Away Stay or Night Stay modes No entry delay provided when the panel is armed in the Instant Maximum mode Entry delay 1 is programmable for each partition field 35 Exit delay begins whenever the control is armed regardless of the arming mode selected and is independently programmable field 34 Type 02 e Assign to zones that are used for entry and exit and require more time than the Entry Exit Burglary 2 primary entry exit point Provides a secondary entry delay in same manner as entry delay 1 Entry delay 2 is programmable for each partition field 36 Exit delay is same as described for Type 01 Type 03 e Assign to all sensors or contacts on exterior doors and windows Perimeter Burglary e Provides an instant alarm if the zone is faulted when the panel is armed in the Away Stay Night Stay Instant or Maximum modes Type 04 e Assign to a zone covering an area such as a foyer lobby or hallway through Interior Follower which one must pass upon entry to and from the keypad e Provides a delayed alarm using the programmed entry 1 time if the entry exit zone is faulted first Otherwise this zone type gives an instant alarm e Active when the panel is armed in the Away
101. following transmitters are not intended for use in UL installations 5802MN 5802MN2 5804 5804BD 5814 5816TEMP 5819 5819WHS amp BRS and 5850 14 3 Installation Instructions Compatible 5800 Series Transmitters Table Also refer to Appendix A for transmitter input loops button locations Model Product Enter as Description Input Device Type 5801 Wireless UR or RF e Has four pushbuttons each with a unique input loop code Panic e Programmable responses e g Panic Arm Stay Arm Away Transmitter Disarm etc 5802 Pendant BR Only Has single pushbutton EN Usually programmed for response type of 24 Hr audible or 24 Hr Silent other zone responses are possible Transmitter 5802CP Belt Clip BR Only Same as 5802 Personal Emergency 5802MN Miniature UR or RF Has single pushbutton Personal Usually programmed for a response type of 24 Hr Audible or Emergency 24 Hr Silent other zone responses are possible Transmitter 5804 Wireless Key BR Only Has four pushbuttons each with a unique input loop code Transmitter Programmable responses e g Arm Stay Arm Away Disarm etc 5804BD Bi BR House ID must be set Directional Requires 5800TM Transmitter Module Wireless Key Can indicate system status via its 2 LEDs and built in sounder e Has four pushbuttons each with a unique input loop code e Operates the system similarly to
102. h entry add the values of the selected options in each of the entry s columns shown in the respective chart one option per column For example to program entry 2 for alarm response to short auto restore on but not a vent zone enter 5 1 for alarm short 4 for auto restore yes 0 for vent zone no Zone Type 90 Report Codes ALARM ID XXX TROUBLE ID XXX Use existing Contact ID codes if appropriate or define unique codes in CID code range 750 789 Enter the desired 3 digit Contact ID report codes for alarms and troubles occurring on zones assigned to this zone type Press to accept and continue Important Notice on Report Codes To avoid confusion at the central station it is recommended that existing Contact ID codes be used with configurable zone types whenever possible See list in System Communication section and or check with the central station for a complete list of Contact ID report codes If none of the codes are suitable choose a code in the reserved range of 750 789 reserved for configurable zone type report codes and make sure to define the code with your central station see 182 for entries Configurable Zone Type 91 See field 182 for explanation of entries Zone Type 91 Report Codes 91 ALARM ID XKX TROUBLE ID XXX See field 183 for explanation of entries and read the Important notice on using these codes
103. ice one end of a 3 conductor cable to the wire ends of the SA4120XM 1 Cable 2 Connect the SA4120XM 1 cable plug to the 8 pin connector on the control see the Summary of Connections diagram for location of the 8 pin connector 3 Connect the other end of the 3 conductor cable to the 1361X10 Transformer as shown Canada See Powerline Carrier Device section for connections to the PSC04 X 10 Interface and trigger pins Notes e Use caution when wiring the transformer to the control to guard against blowing the transformer fuse the fuse is non replaceable e Wiring to the AC transformer must not exceed 250 feet using 16 gauge wire The voltage reading between terminals 1 and 2 of the control must not fall below 16 5VAC or an AC LOSS message will be displayed e Do not plug the transformer into the AC outlet while making any wiring connections to the control As a safety precaution always power down the control when making such connections Wire Run Chart Distance from control Wire Size Up to 50 feet 20 50 100 feet 18 100 250 feet 16 8 PIN TRIGGER CONNECTOR Dn 1361X10 TRANSFORMER RED OUTPUT 17 0 60000 4 5 6 7 8 12 AUX ORANGE OUTPUT 18_ GREEN BLUE PURPLE BLACK DATA COM SA4120XM 1 CABLE 00 trigcon 001 V2 Figure 6 Connections of 1361X10 Transformer to the Control Board Mounting and Wiring the Control Backup Battery Notes
104. in option 4 34 Exit Delay The system waits the time entered before arming entry exit zones If 00 96 0 96 seconds the entry exit door is left open after this time expires an alarm will 97 120 seconds occur Common zones use same delay as partition 1 98 180 seconds UL installations For UL Commercial Burglar Alarm Grade AA and 99 240 seconds UL Residential Burglar Alarm installations with line security total exit time must not exceed 60 seconds For UL Burglar Alarm installations without line security Grade A total exit time must not exceed 120 seconds SIA Installations minimum exit delay is 45 seconds 35 Delay 1 Upon entering the system must be disarmed before the time entered 00 96 0 96 seconds expires otherwise it sounds an alarm Common zones use same 97 120 seconds delay as partition 1 98 180 seconds UL installations For UL Residential Burglary Alarm installations 99 240 seconds must be set for a maximum of 30 seconds entry delay plus dial delay should not exceed 1 min For UL Commercial Burglar Alarm total entry delay may not exceed 45 seconds SIA Installations minimum entry delay is 30 seconds EEN Entry Delay 2 See 35 above for entries and explanation 37 Audible Exit Warning Warning sound consists of slow continuous beeps until last 10 seconds 0 no 1 yes then it changes to fast beeps Sound ends when exit time expires SIA Installations must be enabl
105. in this descriptor 8 save word and end descriptor go to next zone Press 6 to accept the selected word and continue to the next word NOTE If this is the only word you are using for the descriptor press 8 instead of 6 to save that word in memory ZN 01 BACK Second 3 Digit Index No Poor see index for entries to continue Enter the 3 digit number for the next word In our example the word is DOOR whose number is 057 Enter 0 5 7 ZN 01 BACK Accept Second Word 6 save word and go to last DOOR 0 word this descriptor 8 save word and end descriptor go to next zone Press 6 to accept the selected word NOTE If these are the only words you are using for the descriptor press 8 instead of 6 to save them in memory The two words in our example have now been entered Note however that up to three words may be entered provided the number of characters will fit on the screen Press 8 to save all words in memory ZN 01 BACK Summary Screen DOOR to continue The flashing cursor will disappear indicating that the word s are stored in memory for that zone as shown in the summary display at the left To enter a descriptor for the next zone press plus the desired zone number e g 02 The summary display will appear Now repeat the previous steps to enter the descriptor for the next zone To exit the Alpha descriptor mode press 0 0 at the s
106. ion 1 for yes 0 for no 4 RF Zone No 5 Open Close Paging 12 1 Installation Instructions Keypad Functions The following is a brief list of system commands For detailed information concerning system functions refer to the User s Manual For AUI users refer to the separate AUI User s Guide Function Description Silence alarms Pressing any key will silence the keypad sounder for 10 seconds Disarming the system will silence both keypad and external sounders Quick Arm If enabled field 21 you can press in place of the system s security code plus the desired arming key Away Stay Night Stay Instant Maximum Single Button arming If programmed 57 Function Key menu mode lettered keys A D can be used for arming using options 3 AWAY 4 STAY 5 NIGHT STAY or 6 Step Arming If used no security code is required to arm the system Alarm Memory When the system is disarmed any zones that were in an alarm condition during the armed period will be displayed To clear this display simply repeat the disarm sequence enter the security code and press the OFF key again Arming Away Enter code AWAY 2 or simply press appropriate lettered key on the keypads see Single Button Arming above If the Auto Stay Arm feature is enabled field 84 and the entry exit door is not opened and closed within the programmed exit delay time the system will automatically arm in STAY mode if armed f
107. ion If enabled a report is sent if the system detects an RF jamming 0 zone list chimes on fault of any faulted while the system is in Chime mode Use zone list 3 to assign entry exit or perimeter zone when chime these zones see 81 Zone List Programming section for details mode on 1 use zone list chimes on fault of specific zones programmed in relay zone list 3 when Chime mode on FIELD TITLE and DATA ENTRIES EXPLANATION Powerline Carrier Device X 10 Powerline Carrier devices require a House ID identified in this field House ID Program Powerline Carrier devices in interactive modes 79 80 and 0 A 6 G 11 L 81 1 B 7 H 12 M Not intended for fire or UL installations 2 C 8 1 13 3 D 9 J 14 0 4 E 10 K 15 P 5 F 28 Access Code for Phone Module You need to assign a 2 digit access code for the FA4285 FA4286 Phone 1 9 first digit of access code Module if used Example If desired access code is 7 7 is the first or second digit of access code enter amp entry and 11 for is the second entry 11 for or 12 NOTE A 0 in either digit disables the phone module Must be 00 for UL Commercial Burglar Alarm installations 4 1 Installation Instructions FIELD fl TITLE and DATA ENTRIES EXPLANATION 29 Long Range Radio Output If selected all messages programmed to go to the primary telephone 0 not used line receiver will also be sent to
108. ions lectriques ou un lectricien selon le cas AVIS L indice d quivalence de la sonnerie IES assign chaque dispositif terminal indique le nombre maximal de terminaux qui peuvent tre raccord s une interface La terminaison d une interface t l phonique peut consister en une combinaison de quelques dispositifs la seule condition que la somme d indices d quivalence de la sonnerie de tous les dispositifs n exc de pas 5 15 1 Installation Instructions 10 11 UL NOTICES Entry Delay No 1 and No 2 fields 35 36 cannot be greater than 30 seconds for UL Residential Burglar Alarm installations and entry delay plus dial delay should not exceed 1 minute For UL Commercial Burglar Alarm installations total entry delay may not exceed 45 seconds For UL Commercial Burglar Alarm Grade AA and UL Residential Burglar Alarm installations with line security total exit delay time must not exceed 60 seconds For UL Burglar Alarm installations without line security Grade A total exit delay time must not exceed 120 seconds The maximum number of reports per armed period field 93 must be set to 0 unlimited for UL installations Periodic testing see scheduling mode must be at least every 24 hours Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations Aux power 500mA max All partitions must be owned and managed by the same person s All partitions m
109. ired zones entered as an example in the display at left 09 48 wireless expander zns Enter a report code for zone 91 to enable addressable device 49 64 RF button zones reporting 91 addr device report enable Enter a report code for zone 92 to enable duress reporting 92 duress report enable 95 96 99 are emergency panic key zones 95 96 99 emergency zones 00 to quit to continue Zn ZT PRC In L Summary Screen summary display appears 10 00 110 RF 1 to continue IN L appears for wireless zones and indicates input type and loop IN AD appears for hardwire expansion zones AW and indicates OR the module s address AD which is based on the zone number HW RT appears for hardwire zones and indicates configuration Zn ZT PRC In AD EOL NO NC zone doubling double balanced and response time 10 00 110 AW 07 selection OR Zn ZT PRC HW RT 10 00 110 EL 1 Installation Instructions PROMPT VALID ENTRIES EXPLANATION 10 Zone Type Perimeter 03 Zone Type ZT see table at right types 92 93 only programmable via downloader Each zone must be assigned to a zone type which defines the way in which the system responds to faults in that zone Enter the Zone Type code from the list below Note If 00 is entered Delete Zone will be displayed 00 Not used 07 24 Hr Audible 16 Fire w Verify 01 Entry exit 1 08 24 Hr Aux 20 Arm STAY
110. ises NOTES e For the built in hardwired zones the Input Device type is automatically displayed as HW and cannot be edited e To change the input type of a previously programmed wireless device type RF UR BR to a wired zone type AW you must first delete transmitter s serial number see To Delete A Serial Number prompt on next page 5 2 PROMPT VALID ENTRIES EXPLANATION 10 INPUT S N L A022 4064 1 Serial number Entry and Loop Number Entry see explanation to continue Used only when enrolling wireless transmitters a Transmit two open close sequences If using a button type transmitter press and release the button twice but wait about 4 seconds before pressing the button the second time OR b Manually enter the 7 digit serial number printed on the label of the transmitter Then press the key the cursor will move to the L position You can edit the loop number if necessary When the loop number is acceptable press c Press key C to copy the serial number previously enrolled used when programming a transmitter with several input loops 10 INPUT S N L A022 4 O A Loop Number Change to continue NOTE If the C key is used to copy the previously enrolled serial number the cursor will move to the Loop column L with the previous serial number displayed and display a highlighted question mark for the loop number Enter the loop number and press
111. le for use by the Phone Module If using a phone module and words other than these are selected for Alpha descriptors the phone module will not provide annunciation of those words 39 40 A k 42 43 4 45 46 47 48 49 50 51 52 53 54 B D CHARACTER ASCII CHART For Adding Custom Words 55 56 57 58 59 60 61 62 ON VAT 63 64 65 66 67 68 69 70 m mmoou g 71 72 73 74 75 76 77 78 ZzraCcTIio 79 80 81 82 83 84 85 86 87 88 X 89 90 Z lt CHANDOVOS 9 4 About Schedules The system provides up to 32 schedules which can be used to control 11 types of system events at pre defined times Sixteen schedules are intended for use by the end user and sixteen are reserved for the installer In addition some events are also reserved for the installer only listed in the Enter Event prompt paragraph below SECTION 10 Creating Schedules Start Scheduling mode by entering installer code 4 6 4 while in normal operating mode NOTE The master code can only access schedules 01 16 and events 00 07 The following prompts are displayed PROMPT VALID 5 EXPLANATION ENTER SCHED NO 00 QUIT 00 Schedule Number 01 16 end user schedules 17 32 installer only schedules to continue Enter the desired schedule number NOTE Schedule 32 is automatically set for periodic test reports when the system tim
112. list or a specific zone type Partition If the output is activated by zone type this defines the partition in which the programmed event is to cause the device action Output Action Defines the action of the relay X 10 device when the defined event occurs Can close for 2 seconds stay closed until reset continuously pulse 1 second close open close open etc toggle the device state or activate for a defined duration set in data field 177 Output No Assigns this function to a specific output number defined in 79 Menu Mode This is the output number that will perform this function upon the triggering event Note that each defined function is associated with only one output number This means that if more than one output device needs to perform this particular function you need to define another output function number with the same attributes but assign the appropriate output number i e output devices can be assigned more than one function number but each function number can only be assigned a single output number For example if you want to pulse a strobe light upon fire alarms on zone 4 using a relay mapped to output number 2 as programmed 79 Menu Mode program the following in 80 Menu Mode Prompt Output Funct Activated By Enter Zn No Output Action Output Number Entry 01 assuming this is the first output function 3 zone number 04 requires 2 digit zone numbers 8 con
113. ly when the zone restores a user code off sequence is not needed to reset the zone Faults of this zone type are independent of the system and can exist at the time of arming without interference Since this is a trouble zone type do not use this zone type with relays set to activate upon alarm Assigned to any zone with a carbon monoxide detector e The bell output will pulse when this zone type is alarmed e Always active and cannot be bypassed e Usually assigned to a zone containing an emergency button Sends a report to the central station Contact ID event code 100 and provides an alarm sound at the keypad no bell output is provided UL installations may not use this zone type in UL installations Provides a fire alarm when zone is shorted but only after alarm verified System verifies alarm by resetting zones for 12 seconds after short is detected A subsequent short circuit within 90 seconds triggers fire alarm e Provides a trouble response when zone is open e Arms the system in Stay mode when the zone is activated e Pushbutton units send the user number to the central station when arming or disarming e User number for button must be assigned e Arms the system in Away mode when the zone is activated e Pushbutton units send the user number to the central station when arming or disarming e User number for button must be assigned e Disarms the system when the zone is activated e User number for
114. ly change 0 no AWAY MAXIMUM modes to STAY INSTANT modes respectively 1 partition 1 only if the entry exit door is not opened and closed within the exit 2 partition 2 only delay time after a user arms in AWAY mode from a wired keypad 3 both partitions non RF device An Opening report followed by an Armed Stay report is sent to the Central Station If the door is opened and closed within the exit delay period the system remains in AWAY mode Any RF device that arms the system AWAY overrides this feature and the system remains armed in the AWAY mode 85 Cross Zone Timer Sets the maximum amount of time in which two cross zones must 0 15secs 6 2 1 2 min 12 8min be tripped in an armed system to send an alarm message to the 1 30secs 7 3 min 13 10 min Central Station If only one cross zone is tripped during this time 2 45secs 8 4min 14 12 min a trouble message CID code 380 for that zone is sent to the 3 60 secs 9 5min 15 15 Central Station 4 90 secs 10 6 Assign cross zone pairs zone list 4 5 2 min 11 7 min This option not for use in UL installations 86 Cancel Verify Keypad Display When enabled 1 yes this feature causes CANCELED 0 no ALARM display on the LCD keypad under the following 1 yes conditions After the kissoff of the cancel message to the Central Station indicating a successful transmission When an alarm is successfully canceled before the Cen
115. mmary display does not appear press the key and then enter the correct serial number If the serial number transmitted matches the serial number entered the keypad will beep 3 times and will return you to step 8 Zone Number prompt to enter the starting zone for the next wireless key Or you can return to 58 Menu mode by pressing 00 at the Zone Number prompt NOTE Following the successful enrollment of each wireless device remove ONE of the serial number labels from the device and affix it in the appropriate column on the ENROLLED TRANSMITTERS worksheet of the Programming Form then enter the other information zone number zone type loop number etc relevant to that device Wireless Key Predefined Default Templates GREEN YELLOW LOOP 3 _ voorz LOOP 1 Note These transmitters are not intended for use in UL installations RED YELLOW LED L Nt AM S 0 Of Loop 3 M ENROLL AS BR 5804 001 V1 5804 Wireless Key Transmitter For 5804 Loop TEMPLATE 1 Function No Response Disarm Arm Away No Response Function No Response Disarm Arm Away Arm Stay Function TEMPLATE 2 TEMPLATE 3 Disarm Arm Away Arm Stay 24 hour audible Zone Type ENROLL AS BR LOOP 2 THIS BUTTON 5804BD 007 V0 5804BD 2 Way Wireless Key Transmitter For 5804BD Loop Function No Response No Response Arm Away Disarm Function
116. ms are designed to provide long battery life under normal operating conditions Longevity of batteries may be as much as 4 to 7 years depending on the environment usage and the specific wireless device being used External factors such as humidity high or low temperatures as well as large swings in temperature may all reduce the actual battery life in a given installation This wireless system however can identify a true low battery situation thus allowing time to arrange a change of battery to maintain protection for that given point within the system Installing an alarm system may make the owner eligible for a lower insurance rate but an alarm system is not a substitute for insurance Homeowners property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property We continue to develop new and improved protection devices Users of alarm systems owe it to themselves and their loved ones to learn about these developments 16 2 1 1321 AC Transformer 1 2 2 4 1321X10 1 2 2 4 2 11 14 2 15 Second Dialer Delay Burglary 4 3 2 24 Hour Audible Alarm 3 4 24 Hour Auxiliary Alarm 3 4 24 Hour Silent Alarm 3 4 2 Wire Smoke Detectors 2 6 3 3 Digit Number 9 2 4 4204 1 2 2 5 2 6 2 10 3 1 3 6 6 1 6 2 12 2 14 1 4219 1 1 1 2 2
117. must 0 The reports will be sent to both the dialer and the LRR 55 Dynamic Signaling Priority Intended for use with Long Range Radio reporting 0 Primary dialer first You must also enable field 29 OUTPUT TO LONG RANGE RADIO 1 Long Range Radio LRR first Select the initial reporting destination for messages as follows Primary Dialer First selected 0 UL Installations For UL Commercial e If acknowledged before delay expires see 54 then message will Burglary installations that use a DACT and not be sent to LRR LRR the DACT must be programmed for If not acknowledged before delay expires then message is sent to priority option 0 both the Primary Phone No and LRR Long Range Radio First selected 1 e If acknowledged before delay expires then message will not be sent to the primary dialer If not acknowledged before delay expires then message is sent to both the Primary Phone No and LRR 56 Zone Programming Menu Mode Use this menu mode to program zone information See Zone Programming section for procedures 57 Function Key Menu Mode Use this menu mode to program keypad function keys See Function Key section for procedures 58 Expert Zone Programming Menu This menu mode can be used to quickly program zone information Mode but is recommended only for those already familiar with 56 menu mode See Zone Programming section for procedures System Status Repor
118. nput Device Type 5 4 Installer Code 4 1 Interior Follower 3 3 Interior w Delay 3 4 K Keypad Addresses 2 3 9 2 Keypad Functions 12 2 Keypad Programming Fields 4 12 Keyswitch Kissoff eene 16 3 Installation Instructions L Local 4 7 2 1 Long Range Radio 1 2 2 13 3 6 4 2 4 4 14 1 Low Battery Message 13 3 M Macros sus 1 1 Master Security Code 4 1 Model A12 seen 2 9 Modem 1 Module Addresses 6 2 Momentary Switch 9 N No Alarm Response Normally Closed Zones Normally Open Zones On Board Triggers 2 11 2 13 Output Definition Components 6 3 Output Device Mapping 6 1 Output Devices Output Functions Output relays en Output To Long Range Radio 4 2 P PABX Access Code Pager 1 Phone No st Pager Format Pager Programming Pager Programming Fields 4 8 Pager Report Options 4 8 Panic 12 3 Part 1 Primary Subs Acct No
119. ns are provided in the right column Cabinet and Lock 1 Mount the control cabinet to a sturdy wall in a clean dry area which is not readily accessible to the general public using fasteners or anchors not supplied with the four cabinet mounting holes Remove cabinet door then remove the lock knockout from the door Insert the key into the lock Position the lock in the hole making certain that the latch will make contact with the latch bracket when the door is closed When correctly positioned push the lock until it is held securely by its snap tabs Notes The cabinet can be closed and secured without lock by using 2 screws in the cover s edge PUSH ON LOCK CHECK UNTIL IT IS SEATED POSITION SECURED LOCKED 85 L 1 1 I 1 Se LJ gt UNLOCKED S 3 8 CABINET DOOR x BOTTOM STEP 1 STEP 2 2 mn 8 Figure 1 Installing the Cabinet Lock Mounting the PC Board Alone no RF Receiver 1 2 Hang two short mounting clips provided on the raised cabinet tabs see Detail B in Fig 2 a Insert the top of the circuit board into the slots at the top of the cabinet Make sure that the board rests on the correct row see Detail A b Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws see Detail B Notes e Before installing the cabinet s contents remove the metal cabinet knockou
120. nsmitted does not match the serial and loop number entered a display similar to the one below will appear If the loop number does not match it will also be displayed If so activate the transmitter s loop input or button one or more times If a match is still not obtained i e summary display does not appear press the key twice and enter the correct loop input or if correct press again and then enter the correct serial number Zn ZTP RC L 10 03 1 10 RF 1s Note that an s indicates that a transmitter s serial number has been enrolled Summary Screen to continue If the serial number transmitted matches the serial number entered the keypad will beep 3 times and a summary display will appear showing the programmed information for that zone Press begin programming the next zone See first Summary Screen prompt paragraph on previous page Installation Instructions Wireless Key Programming Templates This procedure programs the wireless keys but a key is not active for arming disarming until it is assigned to a user number see System Operation section assigning attributes command If the key was previously pressed from 58 Menu mode to program 5804 and or 5804BD wireless keys the following screens appear PROMPT VALID 5 EXPLANATION TEMPLATE Tem plate Number 1 Enter Template number 1 6 from next page 1 6 1 1 8 5804 templa
121. nts and sound options in data fields 190 196 NOTE Each keypad must be assigned a unique address starting at address 16 Keypads programmed with the same address will give unpredictable results Supplementary Power optional 1 Connectas shown Be sure to connect the negative terminal on the power supply unit to terminal 4 AUX on the control SUPPLEMENTARY POWER SUPPLY CONTROL TERMINAL STRIP AUX AUX DATA DATA IN OUT 0 IMPORTANT E 2 2 MAKE THESE 2 2 gt a g Z a CONNECTIONS X 8 Z 5 alol gt IE 5 E a Al QIO SCREW a ja ja la lt LIL 8 TERMINALS AS t ul SHOWN 8 uv x Yi i e elele eleel i Figure 4 Using a Supplementary Power Supply Notes Typical Fixed Word Display FA245KP FA260KP Typical Alpha Display FA560KP Keypad Transceivers FA245RF FA260RF e AUI Up to two Symphony FA800KP see note below or FA700KP Touch Screen keypads The system supports up to 8 keypads which can be assigned to partitions in any combination see program fields 190 196 For single 4 wire runs determine the current drawn by all units then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size Use supplementary power if the control s aux power load for all devices exceeds 600mA Suggested power supply
122. nu mode enter 00 at this prompt 9 Press to accept Serial Number 10 Manually enter the serial number printed on the label for the INPUT S N na to continue wireless key or press and release the button to transmit its serial AXXX XXXX number 11 Press to accept the serial number The system will check for duplicate 12 If necessary press the key to back up without saving and re enter the serial number Use the A key to move forward within the screen and the B key to move backward XMIT TO CONFIRM PRESS TO SKIP Confirm to continue 13 If Yes was entered at the SET TO CONFIRM prompt previously see first prompt following entry into the 58 Expert Programming Mode the display on the left will appear Confirm serial and loop numbers by activating the wireless key IMPORTANT When confirmed the key is not active for arming disarming until it is assigned to a user number using the assigning attributes command attribute 4 See System Operation section for procedure Entd A022 4063 Revd A022 4064 YOU MUST PROGRAM on THIS BUTTON LOOP 4 YN Not Confirmed to continue If the serial number transmitted does not match the serial number entered a display similar to the one shown will appear If the loop number does not match it will also be displayed If so activate the button on the wireless key once again If a match is not obtained i e su
123. nue for zone 1 Press 1 to define custom words described later in Adding Custom Words section Summary Screen Note that this is a Summary mode and that no entries can be ZN 01 i y to continue made Entries can be made only when the display contains a flashing cursor which signifies the Entry mode Press to continue 9 1 Installation Instructions Flashing Cursor ZN 01 g to continue delete or change the default descriptor for zone 1 press plus the same zone number 01 This will clear that descriptor and allow changes to be made at the flashing cursor NOTE If you do not wish to change the existing descriptor for zone 1 enter plus the next zone number for which you wish to enter or check a descriptor A summary display for that zone will appear You must then press plus the same zone number again to gain access to the entry mode flashing cursor for that zone First 3 Digit Index No ZN 01 BIAC K see index for entries to continue Press plus the 3 digit number for the first word from the Alpha Vocabulary List Example The descriptor that we wish to enter for zone 1 is BACK DOOR From the list BACK 013 Therefore you would enter 013 Note If you accidentally enter the wrong word simply press plus the correct 3 digit number for the word you want ZN 01 BACK Accept First Word 6 save word and go to next O word
124. one programming input device type entry AUI 1 01 101 automatic if AUI enable field 189 enabled for AUI 1 AUI 2 02 102 automatic if AUI enable field 189 enabled for AUI 2 Long Range Radio 03 103 automatic if output to long range radio field 29 enabled FA4286 Voice Module 04 104 automatic if pnone module access code field 28 enabled Zone Expanders 4219 4229 56 zone programming input device type entry 2 then module 1 for zones 09 16 07 107 automatic if zone no 9 16 entered as AW type or relay assigned module 2 for zones 17 24 08 108 automatic if zone no 17 24 entered as AW type or relay assigned module 3 for zones 25 32 09 109 automatic if zone no 25 32 entered as AW type or relay assigned module 4 zones 33 40 10 110 automatic if zone no 33 40 entered as AW type or relay assigned module 5 zones 41 48 11 111 automatic if zone no 41 48 entered as AW type or relay assigned Relay Modules 4204 79 output device programming device address prompt module 1 12 112 entered at device address prompt module 2 13 113 entered at device address prompt module 3 14 114 entered at device address prompt module 4 15 115 entered at device address prompt Keypads data field programming as listed below keypad 1 16 n a always enabled for partition 1 all sounds enabled keypad 2 17 n a data field 190 keypad 3 18 n a data field 191 keypad 4 19 n a data field 192 keypad 5 20 n a data field 193 keypad 6 21 n a data field 194 keypad 7 22 n
125. ones this entry must be 0 c For zone doubled zones both zones of the doubled pair must be assigned the same response to a short 4 12 Touch Screen Device AUI Enable FIELD fl TITLE and DATA ENTRIES EXPLANATION 189 AUI Device 1 and 2 Enable For Touch Screen style keypads 0 disabled The system supports up to two touch screen style keypads e g 1 partition 1 Symphony Advanced User Interface AUI and FA700KP Touch 2 partition 2 Screen Keypad 3 partition 3 Enter each touch screen AUT device s home partition NOTE Use of AUI does not affect the number of standard keypads AUI 1 address must be set to 1 AUI 2 supported address must be set to 2 AUI Compatibility Note To ensure proper AUI device operation connect only to controls having microprocessor version 3 0 or higher and use AUI devices with the following rev levels 6270 series use version 1 0 9 or higher 8132 8142 Symphony series use version 1 1 175 or higher Keypad Programming Fields NOTE Each keypad must be assigned a unique address Keypads programmed with the same address will give unpredictable results FIELD TITLE and DATA ENTRIES EXPLANATION 190 Keypad 2 Device Address 17 Keypad 2 Entry 1 Partition Assignment Entry 1 Enter the partition in which the keypad is located 0 keypad disabled Entry 2 Enter the desired sound option for this keypad 1 partition 1 2 partition 2 3 common Entry 2 Soun
126. onnect the Red and Green LED wires to the e Use 56 Menu mode to program the keyswitch zone and assign it zone type 77 appropriate output 17 output 18 trigger connector e Use 80 Menu mode to program the LED pins functions program outputs 17 and 18 for system 3 Connect a 2000 ohm EOL resistor across the operation zone type 78 red LED and 79 green momentary switch LED as appropriate see Output Device 4 You can wire an optional closed circuit tamper switch Programming section model 112 in series with the zone If the switchplate is then removed from the wall the tamper will open disabling keyswitch operation until the system is next disarmed from the keypad If the tamper is opened when the system is armed an alarm will occur 8 PIN TRIGGER CONNECTOR 6 7 8 OO 1 gt Im Ox 3 4 5 OOO OUTPUT 17 YELLOW OUTPUT 18 GREEN 4146 KEYSWITCH UL A UL Listed keyswitch is required for fire installations and UL commercial and residential burglar alarm installations YELLOW If a keyswitch is used on e an installation that transmits opening and closing signals the keyswitch zone must be programmed to send opening and closing signals e a UL commercial burglar alarm installation the keyswitch s tamper switch must be connected in to the alarm system This tamper switch zone must also be programmed for Zone Type 05 Trouble by Day Alarm by Night TYPICAL ZONE ON CONTROL
127. ons diagram and set to address 28 Notes e Use this module only if you are using one or more wireless bi directional keypads or keyfobs with a wireless Receiver 5800TM is not necessary if using a Transceiver e g 5883 e The 5800TM must be set to address 28 cut red W1 jumper The 5800TM can be used in partition 1 only For additional information regarding the 5800TM refer to the 5800TM s instructions Installing the Transmitters 1 To be sure reception of the transmitter s signal at the proposed mounting location is adequate perform a Go No Go Test described in the Testing the System section Install transmitters in accordance with the instructions provided with each Set 5827 5827 BD 5804BD transmitters to the programmed House ID field 24 using its DIP switches 5827 or follow the instructions provided with the device Notes Refer to the table of compatible devices at the back of this manual Supervised transmitters send check in signals to the receiver at 70 90 minute intervals If at least one check in message is not received from each transmitter within a 12 hour period the missing transmitter number s and is displayed T Hand held transmitters e g 5802 5802CP 5804 5804BD 5827 5827 BD do not send check in signals UL The following transmitters are not intended for use in UL installations 5802MN 5802MN2 5804 5804BD 5814 5816TEMP 5819
128. ort Note in field 41 Part 1 Primary Subs Acct No Enter digits 0 9 11 for B 12 for C 13 for D 14 for E 15 for F To clear entries from field press 43 Part 1 Secondary Subs Acct No Enter digits 0 9 11 for B 12 for C 13 for D 14 for E 15 for F To clear entries from field press 44 Part 2 Primary Subs Acct No Enter digits 0 9 11 for B 12 for C 13 for D 14 for E 15 for F To clear entries from field press 45 Part 2 Secondary Subs Acct No Enter digits 0 9 11 for B 12 for C 13 for D 14 for E 15 for F To clear entries from field press 46 A N Phone System Select If Central Station Receiver is not on WATS line 0 Pulse Dial 1 Tone Dial If Central Station Receiver is on WATS line 2 Pulse Dial 3 Tone Dial Select the type of telephone service Report Format Primary Secondary 2 4 2 ADEMCO L S STANDARD 7 ADEMCO Contact ID 4 digit Format Select report format for primary and secondary phone numbers Split Dual Reporting 0 standard backup reporting only all reports only to primary unless unsuccessful then will attempt secondary 1 5 see table to right To Primary No To Secondary No 1 alarms restore cancel others 2 allexcept open close test open close test 8 alarms restore cancel all 4 allexcept open close test all 5
129. ort codes enroll 5800 RF Wireless Transmitter serial numbers and identify the type of loop input device s This mode can also be used to enter alpha descriptors for programmed zones however we recommend entering descriptors in menu mode 82 Alpha Descriptor Programming after all zone programming has been completed For a faster method of zone programming you can use the 58 Expert Programming Mode instead of 56 Zone programming The 58 Expert Programming Mode is designed for those who have had previous experience in programming control panels of this type NOTE Alpha display prompts are shown in a double line box 56 Zone Programming Procedure Zone Programming involves 1 Entering the zone number to be programmed 2 Making appropriate entries at the prompts 3 Confirming the serial number of wireless transmitter zones Start Zone Programming mode by pressing 56 while in Data Programming mode The following prompts are displayed PROMPT VALID ENTRIES EXPLANATION SET TO CONFIRM Set to Confirm If 1 Yes is entered you will be prompted to confirm each 0 NO 1 YES transmitter after entering the serial and loop numbers at the 1 yes TO CONFIRM prompt later in this procedure We recommend that you confirm the programming of every transmitter Enter Zn Num Zone Number Enter the zone number that you wish to program Zone 10 has been 00 Quit 10 01 08 w
130. other partition during zone programming The system by default automatically distributes users between the two partitions The master user can change the user number distributions Zones can also be assigned to a common partition which is an area shared by users of both partitions such as a lobby in a building This allows either partition to arm while leaving the common partition disarmed for access into the other partition The following describes the functioning of the common partition The common zone sounds and reports alarms only when both partitions are armed If only one partition is armed the system ignores faults on the common zone Either partition may arm its system if the common zone is faulted but once armed the other partition will not be able to arm unless the common zone is first bypassed or the fault is corrected Faults on the common zone are displayed on common zone keypads and will also appear on another partition s keypad when that partition is armed Either partition can clear and restore the common zone after an alarm 3 1 Installation Instructions Keypads Keypads are identified by predefined addresses starting at address 16 as follows Address Keypad Program Field 16 keypad 1 always enabled for partition 1 all sounds enabled NOTE First keypad address is 16 17 keypad 2 e data field 190 18 keypad 3 data field 191 19 keypad 4 e data fi
131. pairs per zone sent to the central station in an armed period SIA Installations Must be set for option 1 or 2 Installation Instructions Download Phone Number Enter up to 20 digits as follows 0 9 11 for 12 13 for a pause Enter the phone number of the downloading computer Do not fill unused spaces End field by entering To clear entries from field press 94 Ring Count For Downloading 0 15 number of rings before control picks up phone line Refer to the chart below and program this field accordingly phone answer down module machine loading Set field 95 to yes no no 1 14 not 0 yes yes no higher than number of rings set on answer machine e g if ans machine is 4 rings set this field to 5 This allows access to the phone module if the answer machine is turned off yes no yes 1 14 not 0 yes yes yes 15 bypasses answer machine no no no no yes no 0 no no yes 1 14 no yes yes 15 T NOTE If 15 is entered to bypass an answering machine and a FA4285 FA4286 Phone Module is included in the system you should note the following When calling in from an off premises phone the user should make the initial call allow 1 or 2 rings only then hang up The user should then call again The phone module will now seize the line and 2 long tones sound followed by the usual voice prompt for the acces
132. pliant but can be programmed for False Alarm Reduction To program for False Alarm Reduction follow the SIA Guidelines noted in the applicable programming fields The FA168C GP control has the following major features Capabilities Partitions e Supports 2 partitions which can protect two independent areas as if each area had its own control e Common zone option allows either partition to arm while leaving a common area ex lobby or foyer disarmed for access into the other partition Zones e Supports up to 48 protection zones plus 16 keyfob zones zones 49 64 for total of 64 zones 8 basic hardwired zones zones 1 8 with optional zone doubling feature Up to 40 additional wired zones zones 9 48 using up to 5 4219 4229 modules Supports up to 40 wireless transmitter zones 5800 series zones 9 48 Supports up to 4 configurable zone types Security Codes Up to 48 Security Codes each with separate authority levels and partition access Downloading Via an IBM compatible computer Compass downloading software and a compatible HAYES or CIA modem specified by Ademco Functions e Single button arming feature Can use dedicated keys to arm the system AWAY or STAY e Schedules up to 32 to control devices and or auto arm disarm the system e Keypad macros up to 4 which can be activated by wired keypads Paging feature allows certain system conditions to be reported to up to 4 pager phone numbers can use a dedicated key on ke
133. property loss as a result CONSEQUENTLY SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING HOWEVER IF SELLER IS HELD LIABLE WHETHER DIRECTLY OR INDIRECTLY FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE REGARDLESS OF CAUSE OR ORIGIN SELLER S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER This warranty replaces any previous warranties and is the only warranty made by Seller on this product No increase or alteration written or verbal of the obligations of this Limited Warranty is authorized First Alert NINE SECURITY SYSTEMS A Honeywell Company 149 Eileen Way Syosset NY 11791 Copyright 2003 Honeywell International Inc K5305 5GPV2 9 04 Rev ev
134. r are included If programmed these entries can be used to manually activate or deactivate the device s for starting or stopping some action such as turning lights on or off etc These keypad entries are Security Code 7 2 digit Device activates starts that device Security Code 8 2 digit Device deactivates stops that device SUMMARY OF ARMING MODES Arming Mode Features for Each Arming Mode Du ee Tg ES eS TEA star N NIGHT STAY En e zones listed in Night hr aM zone list INSTANT Ye N nn MNA nme CE o 12 2 Panic Keys There are three Panic keys and that if programmed can be used to manually initiate alarms and send a report to the central station Each key can be programmed for 24 hour Silent 24 hour Audible Fire or Personal Emergency responses The programmed Panic response is activated when the appropriate key is pressed for at least 2 seconds The Panic keys are identified by the system as follows Keys Displayed as Zone A 1 95 B 99 C 3 96 IMPORTANT For a Silent panic function if programmed to be of practical value you must program a report code for the zone and the system must be connected to a central station Setting the Real Time Clock The keypad displays Clock Not Set alpha keypads or C5 fixed word keypads upon power up if the clock is not set This message toggles
135. r or press 4 and the serial number will return to the display Zn ZT RC 10 03 10 RF 15 Summary Screen to continue If the serial number transmitted matches the serial number entered the keypad will beep 3 times and a summary display will appear showing that zone s programming Note that an s indicates that a transmitter s serial number has been enrolled Press to accept the zone information and continue PROGRAM ALPHA 0 NO 1 YES 0 Alpha Descriptors 0 no 1 yes to continue If you want to program descriptors for zones now enter 1 Yes and refer to the Alpha Descriptor Programming section for available descriptors ENTER ZN NUM 00 QUIT 11 Next Zone Number 00 quit to continue If 0 No was entered above the system will return you to the ENTER ZN NUM prompt for the next zone When all zones have been programmed enter 00 to quit Installation Instructions Completing Zone Programming When you have finished programming all zones test each zone using the system s TEST mode Do not use the Transmitter ID Sniffer Mode for checking wireless transmitting devices as it will only check for transmission of one zone on a particular transmitter NOT the zones assigned to each additional loop NOTE Following the successful enrollment of each wireless device note the device serial number in the appropriate column on the ENROLLED TRANSMITTERS worksheet in the
136. reports enabled Step Arming arms STAY then NIGHT STAY1t then AWAY Output Device Control for device programmed as system operation type 66 function key in 80 Menu Mode Communication Test sends Contact ID code 601 Macro Key 1 define macro by user code 6 6 command Macro Key 2 define macro by user code 6 6 command Macro Key 3 define macro by user code 6 6 command Macro Key 4 define macro by user code 6 6 command 8 1 Installation Instructions SECTION 9 Alpha Descriptor Programming 82 Menu Mode About Descriptor Programming The system lets you assign zone descriptors for protection zones keypad panics and RF receiver supervision faults Each description can be composed of a combination of words up to 3 selected from a vocabulary of 196 words stored in memory see a following page In addition up to 10 installer defined words can be added to those already in memory plus 3 additional words can be assigned as partition descriptors Thus when an alarm or trouble occurs in a zone an appropriate description for that zone s location can be displayed at the keypad Zone descriptors are recommended for systems using Alpha display keypads and are necessary if an FA4285 or FA4286VIP Phone Module is used NOTE You can enter zone descriptors when the zone is being defined in 56 Menu mode but we recommend you do it using 82 Menu mode If using a VIP Phone Module select from
137. resses 4204 Address 4229 Address no 1 12 no 1 zn 09 16 07 no 2 13 no 2 zn 17 24 08 no 3 14 zn 25 32 09 no 4 15 no 4 zn 33 40 10 no 5 zn 41 48 11 4204 l DIP SWITCH NC FOR SETTING DEVICE ADDRESS SHOWN OEF NO AND ENABLING DISABLING TAMPER Orc RELAY NC COVER TAMPER REED SWITCH 3 t No 4 PIN TOUCHPAD PLUG RELAY 2 OT EITHER OR BOTH o no CANBEUSED o OL RELAY TB1 1 OF 3 2 3 OF no DATA IN FROM CONTROL GROUND DATA OUT TO CONTROL 12V 4204_conn 1 VO Figure 11 4204 Connections to Control 4229 Module is shown in the 4219 4229 Expansion Zones paragraph on page 2 7 2 11 Installation Instructions Powerline Carrier Devices Notes 1 Install the powerline carrier devices up to 16 devices if no relays are used according to the instructions included with each Output Device menu Mode triggers Canada Use the PSC04 Powerline Interface as shown below See connections diagram in the AC Wiring paragraph for connecting the 1361X10 transformer to the Transformer Use Programming Mode to enter the device house ID e The 1361X10 Transformer provides AC power to in data field 27 and enter the unit code using 79 keypads e When using Powerline Carrier devices you must use a 1361X10 Transformer instead of the 132
138. ries with dead batteries or if the batteries are not put in properly Devices powered solely by AC will not work if their AC power supply is cut off for any reason however briefly Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver Even if the signal path has been recently checked during a weekly test blockage can occur if a metal object is moved into the path A user may not be able to reach a panic or emergency button quickly enough While smoke detectors have played a key role in reducing residential fire deaths in the United States they may not activate or provide early warning for a variety of reasons in as many as 35 of all fires according to data published by the Federal Emergency Management Agency Some of the reasons smoke detectors used in conjunction with this System may not work are as follows Smoke detectors may have been improperly installed and positioned Smoke detectors may not sense fires that start where smoke cannot reach the detectors such as in chimneys in walls or roofs or on the other side of closed doors Smoke detectors also may not sense a fire on another level of a residence or building A second floor detector for example may not sense a first floor or basement fire Finally smoke detectors have sensing limitations No smoke detector can sense every kind of fire every time In general detectors may not always warn about fires caused by carelessness
139. rom a wired keypad non RF device If the door is opened and closed within the exit delay period the system arms in AWAY mode Arming Stay Enter code STAY 3 or simply press appropriate key on the keypads see Single Button Arming above See Arming Away above for Auto Stay arming feature Arming Night Stay Enter code STAY 3 STAY 3 or simply press appropriate key on the keypads see Single Button Arming above The Night Stay feature is disabled if field 199 is set to 1 e g if using a FA245RF keypad Arming Instant Enter code INSTANT 7 Arming Maximum Enter code MAXIMUM 4 See Auto Stay Arm description in arming Away above Operates similar except arms INSTANT instead of STAY Disarming Enter code OFF 1 If entry delay or an alarm is active you do not need to press OFF Bypassing Zones Enter code BYPASS 6 zone number s Forced Quick Bypass To automatically bypass all faulted zones use the Quick Bypass method Enter code BYPASS then wait for all open zones to be displayed Arm when display indicates ZONE BYPASSED and READY TO ARM Chime Mode Enter code CHIME 9 To turn chime off enter code CHIME again Quick Chime Mode 9 turns chime on 9 again turns chime off Activate Output Devices Ifrelay outputs via a 4204 or 4229 or Powerline Carrier devices are used two keypad entries available to the use
140. s 160 161 Pager 1 Characters Up to 16 optional characters may be sent as a prefix to the 7 digit Enter up to 16 characters system status code sent to Pager 1 if used Phone number in field 160 must have been entered If fewer than 16 characters exit by pressing and next field number To clear entries from this field press 161 For example these optional 16 characters may be composed of the following e PIN number to identify a specific pager to the paging company e Subscriber account number enter 11 to send enter 12 to send Pause enter amp 13 to allow a 2 second pause Any special character s the end user may decide to transmit Some paging systems require pause s before the prefix The format for the 7 digit system status code is defined as follows Pager Format XXX YYYY where XXX 3 digit event code 911 Alarm 811 Trouble 101 Opening disarm 102 Closing arm AWAY YYYY 4 digit user or zone number depending on type of event The first two digits must always be 00 and must be followed by the 2 digit user or zone number Example 1 Pager displays 911 0004 This indicates that the system is reporting an alarm 911 caused by a fault in zone 4 0004 Example 2 Pager displays 102 0005 This indicates that the system is reporting a closing system arming 102 by User 5 0005 162 Pager 1 Report Options Enter the types of reports to be sent to
141. s code If this procedure is not followed phone module operation will not be possible Command to Initialize CSID and Subscriber Account Number This is a command function not a data field Use this command if necessary to reset all subscriber account numbers and the internal CSID to the factory default values 97 Command to Reset System to Factory Default Values This is a command function not a data field Pressing 97 resets all data fields to the factory default values shown on the Program Form IMPORTANT Do not press 97 to load defaults if any programming has been done previously data already programmed into the system will be changed Command to Exit Program Mode with installer code lockout Exits Programming Mode and prevents re entry by Installer Code 8 0 0 To enter the programming mode if 98 was used to exit you must first power the system down Then power up again and press and at the same time within 50 seconds of powering up Command to Exit Program Mode Exits Programming Mode and allows re entry by Installer Code 8 0 0 or by Pressing and at the same time within 50 seconds of power up 4 8 Pager Programming Fields FIELD fl TITLE and DATA ENTRIES EXPLANATION 160 Pager 1 Phone No If you enter fewer than 20 digits exit by pressing and next field Enter up to 20 digits number To clear entries from this field pres
142. s skipped Enter the physical device number as programmed in 79 Menu Mode then press to continue to the Start prompt Device numbers 17 and 18 designate built in triggers 1 and 2 respectively GROUP NUMBER X Group Number 1 8 group number to continue This prompt appears if event 2 user access was selected Otherwise it is skipped Press to continue to the Start prompt PARTITION X Partition 0 all partitions 1 partition 1 2 partition 2 3 common to continue This prompt appears if events 3 7 10 were selected Otherwise it is skipped Press to continue to the Start prompt 10 1 Installation Instructions START SMTWTFS HH MMAM 0010000 Start Time 01 12 hour 00 59 minute 0 AM 1 PM Days place 1 under days to continue Enter the event s start time and days of the week to occur To select days position the cursor under the desired days using the key to move forward then press 1 to select the day STOP SMTWTFS HH MMAM 0010000 Stop Time 01 12 hour 00 59 minute 0 AM 1 PM Days place 1 under days to continue Enter the event s stop time and days of the week to occur To select days position the cursor under the desired days using the key to move forward then press 1 to select the day This entry applies only to the following events 1 relay on off
143. s two on board triggers up to 16 relays devices Use any combination of 4204 4229 and or Powerline Carrier Devices Output functions up to 48 FA4285 FA4286 Phone Module Part 1 only provides access to the system via on premises or off premises phones for arming disarming etc plus control of relay outputs and Powerline Carrier devices Audio Alarm Verification using module such as ADEMCO UVS or Eagle Model 1250 can be used in conjunction with an output trigger to permit voice dialog between an operator at the central station and a person at the premises Alarm output provides a 12VDC 2 AMP output that can drive the compatible sounders steady output for burglary panic or temporal pulse 3 pulses pause 3 pulses pause 3 pulses for fire Uses current limiting circuitry for protection Auxiliary Power Output 12VDC 600 mA maximum uses fuse for protection Backup Battery Rechargeable sealed lead acid type 12VDC 4AH minimum Long Range Radio Primary telephone number messages can be reported via ECP connection to various Long Range Radios check compatibility and availability of specific models AC Power Supply Plug in 120VAC transformer ADEMCO 1321 1321CN in Canada or if using Powerline Carrier devices ADEMCO 1361X10 Transformer Module NOTE All devices and accessories used in a Canadian installation must be Listed for use in Canada Important Installation Highlights Installer Please Rea
144. se from a series of preset templates for easy programming of wireless key zones When all zones have been programmed press 00 at this prompt to quit this menu mode Zn ZT P RC IN L 10 00110 RF 1 Zone Programming ZT see Zone Type chart shown in 56 Menu Mode Zone Type prompt partition 1 2 common RC 1 send CID report 0 no report IN input type L loop number to continue A summary screen with the selected zone s current programming appears Begin programming zone information as follows e Enter Zone Type ZT Partition P Report Code RC and Input Device Type IN sequentially but not the Loop No L e Use the A Advance and B Back keys on the keypad to move the cursor within the screen e Use the C key to copy the previous zone s attributes Press to save the programming and continue to the serial number loop number prompt If needed you can press the 4 key to back up without saving If HW hardwired or AW Auxiliary is entered for Input Device Type the next screen will be similar to the prompt shown except that HW or AW will be displayed under IN If RF BR or UR is entered a prompt for Serial and Loop number will be displayed as follows PROMPT VALID ENTRIES EXPLANATION 10 INPUT S N 5 x Serial number S N serial number L loop number to continue Manually enter the serial number found
145. sing an acceptable method of connection The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations Repairs to certified equipment should be coordinated by a representative designated by the supplier Any repairs or alterations made by the user to this equipment or equipment malfunctions may give the telecommunications company to request the user to disconnect the equipment Users should ensure for their own protection that the electrical ground connections of the power utility telephone lines and internal metallic water pipe system if present are connected together This precaution may be particularly important in rural areas Caution Users should not attempt to make such connections themselves but should contact appropriate electric inspection authority or electrician as appropriate Ringer Equivalence Number Notice The Ringer Equivalence Number REN assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not exceed 5 Industrie Canada AVIS l tiquette d Industrie Canada identifie le mat riel homologu Cette tiquette certifie que le mat riel est conforme aux normes de protection d exploitation et de s
146. ssssssssssssssssssseees 11 1 Section 12 System OperatiOn ssssoossssoossocoose00o0ceo0o0000o0000000000000 000000 000000 000000 00000 000000 000000 00000 000000 urea 000000 12 1 Security nee son n Wh er she ee ae ea el ee theses dan isa 12 1 Keypad Functions aa oi LET ages San RO aa EBORE 12 2 Various System Trouble Displays e 12 4 Section 13 Testing the Systein ere etti airline aironi 13 1 About Test Procedures sss A tee eiie et vie desires nre ute e 13 1 System Test odo RE RR Ian oe ti eee Nt he EO e teres 13 1 Go No Go Test Modems nine iI a NI TQUE I E RE guit RE IDE 13 2 Dialer Communication Test 4 eie erinnerte feeder endete nite centi tentur e eee ups 13 3 Section 14 Specifications amp Accessories eene ecce eere ee ee eene reverse reverse reverse vesvonsevevoonse reserve vevonssrre 14 1 Security Control nter ERES uenenum uiu aa ES 14 1 Compatible Devices oa se secet vedettes tiet iicet 14 1 5800 Series Transmitter Input Loop Identification 14 3 Section 15 Regulatory Agency Statements ee etae eese 15 1 Section 16 Limitations and Warranty e eeeee reserve ee etes sese seen sese seta sese teta sese eee sese teta sese 16 1 iv SECTION 1 Features and Installation Highlights This system is not certified as SIA com
147. stem only if it was used to arm the system 3 Duress see user performs security functions but also silently sends a duress message to the central station reports as duress code user number 4 Partition see user See Partition Master paragraph above used to assign Master other user numbers as partition masters Refer to the user guide for detailed procedures on adding deleting security codes and changing user attributes The following is a brief description of how to add user codes Changing the System Master code e Using Installer code Installer code 8 02 new code e Using current System Master code System Master code 8 02 new code new code again Adding a User Code Deleting a User Code Assigning Attributes Master code 8 2 digit user no user s code Master code 8 2 digit user no 0 Master code 8 2 digit user no attribute no value Attributes Values 1 Authority Level 0 4 see Authority Level table above 2 Access Group 0 8 0 not assigned to a group 3 Active Partition s 1 2 common for this user Enter partitions consecutively if more than one and press to end the entries Assigns user number to button type zone for arm disarm enter the zone number assigned to a button on the keyfob that will be used for arming disarming by this user Keyfob must be enrolled in system first see Wireless Key Programming Templates sect
148. stored 0 no report UL Required for UL commercial burglar alarm installations 1st digit non zero send report 72 Bypass Restore Report Code This is sent when a zone that has been bypassed is unbypassed 0 no report UL Required for UL commercial burglar alarm installations 1st digit non zero send report 73 Restore Code Sent when AC power has been restored after an AC power outage 0 no report UL Required for UL commercial burglar alarm installations and 1st digit non zero send report required for residential fire alarm installations 74 Low Bat Restore Report Code Sent when a system low battery condition is restored to normal 0 no report UL Required for UL commercial burglar alarm installations and 1st digit non zero send report required for residential fire alarm installations 75 RF Xmtr Low Batt Restore Code Sent when a transmitter s low battery condition is restored new 0 no report battery installed 1st digit non zero send report UL installations must be enabled if wireless devices are used Required for UL commercial burglar alarm installations and required for residential fire alarm installations 76 Test Restore Report Code This is sent when the Test mode is exited 0 no report UL Required for UL commercial burglar alarm installations and 1st digit non zero send report required for residential fire alarm installations 4 5 Installation Instructions Misc
149. t and Restore Codes Zone report codes are programmed using interactive 56 or 58 Zone Programming modes while system status non alarm codes and restore codes are entered in the following data fields UL installations Program fields 59 68 70 76 89 as required by the applicable UL Standards shown in each field s description Contact ID Reporting Enter any digit other than 0 in the first box to enable the zone to report Entries in the second boxes will be ignored FIELD TITLE and DATA ENTRIES EXPLANATION 59 Exit Error Report Code After arming the system entry exit and interior zones remaining open 0 no report after exit delay expires cause an alarm sound at the keypad and non zero send report external sounder keypad displays EXIT ALARM and entry delay begins Disarming before the end of the entry delay stops alarm sounding and no message is sent to the central station The keypad displays CA fixed word or CANCELED ALARM alpha display If the system is not disarmed before entry delay expires an EXIT ALARM message will be sent to the central station if Exit Error Report Code is enabled The keypad will display EA fixed word or EXIT ALARM alpha display and alarm sounding continues until the system is disarmed or timeout occurs An Exit Alarm condition will also result if a fault occurs in an exit or interior zone within 2 minutes following the end of the
150. t devices using 79 Menu Mode before you can use 80 menu Mode 2 Use 80 Menu Mode to create output definitions which control the output devices 79 Menu Mode Output Device Mapping Use this menu to assign Relay Module device addresses and specific relay numbers and Powerline Carrier unit numbers The system is based on predefined module addresses for 4204 and 4229 modules Refer to the table shown at the Module Address prompt on the next page and set the modules addresses via module DIP switches accordingly The following table shows how these outputs are identified Output Identification This output is identified by Relays the Relay Module s device address and the relay position on that module i e the physical relay number 1 4 on that module X 10 Device a house ID entered in data field 27 and the unit number of the device Built in Outputs the output number assigned 17 for Trigger 1 and or 18 for Trigger 2 Installation Instructions Start Output Device Mapping by pressing 79 while in Data Programming Mode The following prompts are displayed x79 Menu Mode PROMPT VALID ENTRIES EXPLANATION Device Output Number 01 16 17 18 to continue ENTER OUTPUT NO 00 QUIT XX This is the logical or reference relay number as used in the system Relays and X 10 devices are numbered 01 16 the on board triggers are numbered 17 and 18 and can be programmed for inv
151. tei ilaele 3 3 Mechanics of Programming d Idee iiti 3 5 Section 4 Data Field Programming eee ee ee eee eerte ee eee ee ee ee ee ento eee teet eo esee ee e ee eee eo sone eee e eese eee 4 1 About Data Field Programming eene enne ener nnne se RR RR sees RR Re sehen se nnns nena 4 1 Programming Data Fields uina ebur euam trae b redu 4 1 System Setup Fields 20 29 saar 4 1 Zone Sounds amp Timing 31 39 i 4 2 Dialer Programming 40 50 nrs eiae iie hack eene edd cbe ced dn delden obs decedente delden 4 3 System Status Report Codes 559 5068 ira 4 4 Miscellaneous System ntis decies pede iip cedi ei bid ce di 4 6 Pager Programming cie ce e dates v iena iaia cilea 4 8 Miscellaneous System Fields o co eee UE RE ERREUR ERA os 4 10 Configurable Zone Type Programming Fields ere enne nennen erre entes 4 11 K ypad Programming Fields ot i eu onte rr RH e ne eee etende MR nent 4 13 iii Section 5 Zone Programming ccicscccssocsccssscssecococessecccocesecccocssecececssececeessececessscecccesssececeessecesesssecccesssecceceerss 5 1 About Zone Programming MER HR ERR EET 5 1 56 Zone Programming Procedure ier er RN t iaia 5 1 Completing Zone Programming c Accede dede dese ettet 5
152. tem maximum transmitters 5800TM Transmitter Module used with 5827BD Wireless 2 Way Keypad Zone Expansion 4219 WIRED EXPANSION MODULE 4229 WIRED EXPANSION RELAY MODULE Relay Module 4204 RELAY MODULE Phone Modules FA4285 PHONE MODULE FA4286VIP PHONE MODULE Long Range Radio 7835C 7845C 14 1 Installation Instructions 14 2 2 Wire Smoke Detector i EE 2 Sounders 1400 1321 16 5VAC 25VA Plug In Transformer 1321CN in Canada 1361X10 16 5VAC 40VA Powerline Carrier Device Interface AC Transformer Ademco AB 12M 10 Motorized Bell amp Box Ademco 1011BE12M 10 Motorized Bell amp Box Ademco 702 Outdoor Siren Ademco 719 2 Channel Siren Ademco 747 Indoor Siren Ademco 747UL Indoor Siren Ademco 744 Siren Driver Ademco 745X3 Voice Siren Driver Ademco 705 820 5 inch Round Speaker Ademco 713 Speaker System Sensor PA400B beige PA400R red Indoor Piezo Sounder 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input loop ID codes Each of the input loops requires its own programming zone e g a 5804 s four inputs require four programming zones Transmitter inputs entered as RF Supervised RF Type send periodic check in signals as well as fault restore and low battery signals The transmitter must remain within the receiver s range Unsupervised RF Type send all the sign
153. tes See the defaults provided for each template in the chart that 4 6 5804BD templates follows these procedures to continue 2 Select from templates Press to display template 1 shown selected NOTE If necessary press to back up and re enter template number 3 Ifyou want to return to the 58 Menu mode Summary Screen press L 01 02 03 04 Template Display 4 When is pressed the selected template will be displayed to continue Top line of display represents loop numbers bottom line T 23 22 21 23 represents zone type assigned for each loop 5 Press to accept template PARTITION Partition 6 Enter the partition in which the key is to be active 1 partition 1 7 Press to continue 2 partition 2 3 common partition to continue Start Zone Number 8 The system will search for the highest available consecutive 4 ENTER START ZONE zone group the four zones in the case of the 5804 and 5804BD 00 QUIT 36 to continue and display the lowest zone number of the group If you want to start at a different zone enter the zone desired and press If that zone number is displayed the system has the required number of consecutive zones available beginning with the zone you entered If not the system will again display a suggested zone that can be used If the required number of consecutive zones is not available at all the system will display 00 To quit this mode and return to 58 Me
154. the connected 7720PLUS 7820 1 using Long Range Radio output 7835 or 7845 Radio sent in Contact ID format The data line is supervised as well as certain functions in the radio If communication is lost or a trouble develops an attempt will be made to send a message via both radio and telephone to the central station Program the radio for device address 8 Zone Sounds amp Timing 31 39 FIELD TITLE and DATA ENTRIES EXPLANATION 31 Single Alarm Sounding Zone desired selection per armed period 0 limit on alarm sounding per zone 1 limit alarm sounding to once per arming period for a given zone 32 Fire Alarm Sounder Timeout This control complies with NFPA requirements for temporal pulse 0 yes fire sounder timeout after time sounding of fire notification appliances programmed in field 33 Temporal pulse sounding for a fire alarm consists of the following 1 no fire sounder timeout continue 3 pulses pause 3 pulses pause 3 pulses sounding until manually turned off UL fire alarm installations must be 1 33 Alarm Sounder Timeout This field determines whether the external sounder will shut off 0 No timeout 3 12 min after time allotted or continue until manually turned off 1 4 min 4 16 min UL installations For residential fire alarm installation must be set 2 8 min for a minimum of 4 min option 1 for UL Commercial Burglary installations must be minimum of 16 m
155. tinue Press the desired function key A D you want to program NOTE A key programmed as a function key is no longer available to be used as an end user macro key or panic key E En En BE amp x 8 ci 0 8 8 00 E keypad_keys 00 001 Partition Partition Number 1 partition 1 2 partition 2 3 common partition to continue Enter the partition in which the function key is active Key A Func Zone 95 00 Define Key Function 00 12 see list to right to continue Returns to key number prompt with the next function key letter displayed T System defaults to these function key settings tt If night stay zones are listed in zone list 5 Enter the desired function for this key 00 to 12 from the options listed 00 selected for example display shown at left 007 01 02 03 04 05 06 07 08 09 10 11 18 For the Function key selected the function will be as follows If A selected Zone 95 emergency key same as 1 pair If selected Zone 99 emergency key same as pair If C selected Zone 96 emergency key same as 3 pair If D selected Single button paging Single button paging sends a 999 9999 message to pager Display time Arm AWAY reports as User 00 if closing reports are enabled Arm STAY reports as User 00 if closing reports are enabled Arm NIGHT STAY reports as User 00 if closing
156. tinuous pulse 02 device mapped in 79 Menu Mode Start Output Definition mode by pressing 80 while in Data Programming mode The following prompts are displayed 80 Menu Mode PROMPT VALID ENTRIES EXPLANATION Output Funct 00 Quit 01 Output Function No Enter the output function number to be defined or 00 to exit 01 48 output function number to continue 01 A E P Trig 200 0 0 21 00 Summary Screen This screen displays a summary of the current output programming to continue for this example Zone List has been selected this is the default screen A Output Action E Triggering event P Partition Trig Trigger type NOTE A question mark in the summary screen indicates that the device number shown has not been mapped Use 79 Menu mode to map the device 6 3 Installation Instructions 01 Activated By Activated By 0 delete Zone List 1 zone list 2 zone type 3 zone number to continue Select where the initiating event for this output definition is to occur as follows 0 delete deletes the output function and any previous programming see prompt below 1 zone list go to A prompt 2 zone type go to prompt zone number go to prompt If you enter 0 the following prompt appears Delete Press 1 to delete this 0 NO 1 YES output definition Zone List 01 Zn List 01 08 zone list
157. tomatically set for schedule 32 when the system time is initially set and the first report is sent 12 hours later thereafter the test report is sent every 28 days UL Required for UL commercial burglar alarm installations and required for residential fire alarm installations Open Report Code This is sent upon disarming of the system in the selected partitions 0 no report UL Required for UL commercial burglar alarm installations 1st digit non zero send report Arm Away Stay Report Code This option allows for independent programming of Away and Stay 0 no report reports for each partition including the common lobby 1st digit non zero send report NOTE OPEN reports are not sent if the associated closing report is not enabled 67 RF Trans Low Batt Report Code Sent when a wireless transmitter low battery condition exists 0 no report UL installations must be enabled if wireless devices are used 1st digit non zero send report Cancel Report Code This is sent upon disarming of the system after an alarm condition 0 no report was reported 1st digit non zero send report 70 Alarm Restore Report Code Sent when an alarm zone is restored to its non faulted condition 0 no report UL Required for UL commercial burglar alarm installations and non zero send report required for residential fire alarm installations 71 Trouble Restore Report Code This is sent when a trouble in a zone is re
158. tput 17 for Power Reset Installation Instructions 4219 4229 Expansion Zones 1 Connect each module to the control s keypad terminals 2 Assign each module a unique device address using its DIP switches Device address determines the zone numbers as shown in the table below Expander Module Addresses For Zones Set Module to Device Address 09 16 07 not available if zone doubling enabled 17 24 08 25 32 09 33 40 10 41 48 11 3 Connect sensors to the module s loops 4 If using relays with the 4229 connect the desired field wiring to the unit s relay contact terminals DIP SWITCH FOR SETTING ADDRESS AND ZONE A RESPONSE TAMPER JUMPER POSITION 4229 IN CABINET NOT TAMPER 4229 REMOTE TAMPER PROTECTED RELAYS OFF ZONES A B Figure 8 Wiring Connections 4219 amp 4229 4229 shown D E F Notes e Supports up to 40 expansion zones NO or NC using up to five 4219 4229 Zone Expander Modules e Use 1000 ohm end of line resistors at the end of loops connected to the 4219 4229 modules End of line resistors used on the control terminals are 2000 ohms Expansion zones have normal response time 300 500 msec except zone connected to each module s loop A which can be set for fast response 10 15 msec 4229 EITHER OR BOTH CAN BE USED TERMINALS ON CONTROL PANEL GRN DATA OUT gt TO CONTROL TERM 6 GRO
159. tral Station received the Alarm message E g if an alarm is incorrectly triggered and the user presses code OFF before the dial delay time has expired the message will never go out to the CS e When the Cancel report is not enabled and the system is disarmed a before dialer delay expires alarm report not sent message Canceled Alarm is displayed b after dialer delay expires message Canceled Alarm is not displayed NOTE Cancel display is automatically disabled if field 199 ECP FAIL DISPLAY is set to 1 2 digit display 4 6 FIELD fl TITLE and DATA ENTRIES EXPLANATION 87 Misc Fault Delay Time 0 15secs 6 2 1 2min 12 8 1 30secs 7 3 13 10 2 45secs 8 4 min 14 12 min 3 60 secs 9 5 15 15 min 4 90 secs 10 6 5 2 11 7 min Used with zones assigned to configurable zone type with fault delay on configurable zone type digit 6 and sets a zone response time of 15 seconds to 15 min It can be assigned to zones with sensors that provide a trouble indication when an oil tank is low or similar applications for critical condition monitoring where a non alarm response is desired UL May only be used on non burglar alarm and non fire alarm zones when used on a fire and or UL burglar alarm installation Event Log Full Report Code 0 1st digit non zero send report If an Event Logging selection is made in field
160. ts required for wiring entry Do not remove the knockouts after the circuit board has been installed CIRCUIT CABINET CIRCUIT BOARD Ge G y DETAIL A SIDE VIEW OF BOARD SUPPORTING SLOTS DETAIL B SIDE VIEW OF MOUNTING CLIPS MOUNTING 001 VO Figure 2 Mounting the PC Board Installation Instructions Mounting Board with RF Receiver a Remove the receiver board from its case then insert the top of the board into the slots at the top of the cabinet as shown in Detail A in Figure 3 Make sure that the board rests on the correct row b Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying c Insert the top of the control s board into the slot in the clips and position two clips at the lower edge of d Swing this board into place and secure it with two additional screws Insert grounding lugs supplied with the receiver through the top of the cabinet into the left hand terminals of the antenna blocks at the upper edge of the receiver board and secure them to the cabinet top with the screws provided as shown in Detail B 1 of tabs screws the board 2 3 Insert the receiver s antennas through the top of the cabinet into the blocks right hand terminals and tighten the screws CABINET RECEIVER CIRCUIT BOARD CONTROL CIRCUIT BOARD INSTALLATION WITH RECEIVER CIRCUIT BOA
161. tton of the wireless keys used Once a wireless key is enrolled it must be assigned to a user before it becomes active See Adding Deleting Security Codes section for procedure Pager Programming The system can send various reports to up to 4 pagers To program pager reporting do the following 1 Enter the appropriate information in the following data fields 160 168 166 169 Pager Phone Numbers for pagers 1 4 respectively 161 164 167 170 Pager Prefix Characters for pagers 1 4 respectively 162 165 168 171 Pager Reporting Options by Partition for pagers 1 4 respectively 2 Enable Pager Delay if desired in field 172 delays alarm reporting for ALL pagers 3 Make sure appropriate user open close pager reports are enabled see Security Codes Assigning Attributes in Section 12 System Operation Users that perform actions in partition 1 will if enabled attempt to report to all pagers enabled for open close reporting in partition 1 Users that perform actions in partition 2 will if enabled attempt to report to all pagers enabled for open close reporting in partition 2 4 If using latchkey pager report define the latchkey report schedule using Scheduling mode master code 6 4 select event type 03 System must be armed for the Latchkey report to be sent 5 If using a function key to manually send a message to a pager see Function Keys paragraph on the next page 6 If reporting zone alarms
162. ubject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation Industry Canada This Class B digital apparatus complies with Canadian ICES 003 Cet Appareil num rique de la classe est conforme la norme NMB 003 du Canada TELEPHONE MODEM INTERFACE FCC Part 68 This equipment complies with Part 68 of the FCC rules On the front cover of this equipment is a label that contains the FCC registration number and Ringer Equivalence Number REN You must provide this information to the telephone company when requested This equipment uses the following USOC jack RJ31X This equipment may not be used on telephone company provided coin service Connection to party lines is subject to state tariffs This equipment is hearing aid compatible Industry Canada NOTICE The Industry Canada Label identifies certified equipment This certification means that the equipment meets telecommunications network protective operational and safety requirements as prescribed in the appropriate Terminal Equipment Technical Requirements document s The Department does not guarantee the equipment will operate to the user s satisfaction Before installing this equipment users should ensure that it is permissible to be connected to the facilities of the local telecommunications company The equipment must also be installed u
163. ues of each desired option If Local Lockout enabled When exiting program mode with 98 can only reenter program mode by installer code 800 Sounder Delay If enabled delays external sounding by 15 seconds Exit Delay Restart reset option allows use of the key to restart the exit delay at any time when the system is armed STAY or INSTANT This feature also enables automatic exit delay reset which resets exit delay if the entry exit door is re opened and closed before exit delay time expires after arming AWAY Automatic Exit Delay Reset occurs only once during an armed period IMPORTANT AAV should not be used when Paging or Alarm Reports are sent to a secondary number unless the monitoring zone option is used which pauses calls Otherwise the call to the secondary number by the communicator after the alarm report will prevent the AAV from taking control of the telephone line and the AAV Listen in session cannot take place Phone Line Monitor Enable Entry 1 Timeout 0 disabled 1 15 1 minute to 15 minutes respectively 2 2 min 3 3 min etc 10 10 min 11 11 min 12 12 min 13 13 min 14 14 min 15 15 min Entry 2 Display Sound 0 keypad display when phone line is faulted 1 keypad display plus keypad trouble sound when line is faulted Each partition turns off its own trouble sound No automatic timeout 2 Same as 1 plus programmed output device STARTS If
164. ummary display Adding Custom Words will not be annunciated by FA4285 FA4286 Phone Module You can add up to 10 installer defined words to the built in vocabulary which can then be used when programming zone descriptors Each of the 10 words can actually consist of a word string of one or more words but no more than ten characters can be used for each word or word string When adding custom words the keypad keys perform the following functions 4 Moves cursor one space to the left 6 Moves cursor one space to the right 8 Saves the new word in the system s memory 1 Select Custom Word mode enter 1 when the prompt CUSTOM WORD is displayed 2 Enter the number 01 101 of the custom word or word string to be created corresponding to index numbers 245 254 respectively for example if you are creating the first custom word or word string enter 01 for the second enter 02 etc A cursor will now appear at the beginning of the second line or 11 12 18 for partition 1 partition 2 and common partition descriptors respectively See Assigning Partition Descriptors paragraph below NOTE Custom words 8 9 and 10 are reminder words that can be programmed to display using Scheduling Mode 3 Refer to the Character List of letters numbers and symbols on a following page Press followed by the two digit entry for the first letter you would like to display e g 6 5 for A
165. ust be part of one building at one street address If used the audible alarm device s must be placed where it they can be heard by all partitions For UL commercial burglar alarm installations the control unit must be protected from unauthorized access The tamper switch installed to protect the control unit enclosure door is suitable for this purpose Remote downloading without an alarm company technician on site unattended downloading is not permissible for UL installations Auto disarming is not a UL Listed feature Notes for SIA Installations 1 10 15 2 As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications the following UL requirements per UL681 are provided The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote monitoring location or to delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system or to arm the system and exit shall not exceed a 60 seconds for a system with standard line security or encrypted line security b 120 seconds for a system without standard line security or encrypted line security or c 120 seconds for a system that does not transmit an alarm signal to a remote monitoring location 34 Exit Delay minimum exit delay is 45 seconds 35 36 Entry Delay 1 and 2 minimum entry delay is 30 seconds 39 Power Up in Previous
166. vice 2 Enable normally closed EOLR zones using Zone Programming mode Hardwire Type prompt Double Balanced Connections as shown below resistor provided for one device IMPORTANT Double balanced zones provide zone tamper protection and should be used as burglary zones only Do not use double balanced zones as fire zones Zone Doubling Connections as shown below resistors provided 14 3 8 i ZONE 3 ZONE 4 i 6 2k Double Balanced Zones Zone Doubling Notes EOLR If the EOLR is not at the end of the loop the zone is not properly supervised and the system may not respond to an open on the zone e Zone 1 is intended for EOLR only UL For UL commercial burglar alarm installations use EOLR zones Zone Doubling This feature provides two hardwired normally closed zones for each standard hardwired zone connected to the control s terminals but does not increase the total number of zones supported by the control If enabled Zone Programming mode Hardwire Type prompt option 3 hardwire zones are automatically paired as follows Zone Paired with zone 10 11 12 13 14 15 16 Do not use zone doubling for fire zones NOTE A short across the EOL i e at terminal on either zone of a zone doubled pair or on a double balanced zone causes a tamper condition displayed as CHECK plus zone numbers
167. wired keypads 5806 Wireless RF One piece smoke detectors with a built in transmitter 5807 Photoelectric Smoke 5808 Detectors 5809 Heat RF One piece rate of rise heat detector with a built in transmitter Detector 5816 Door Window RF Has two unique input loop codes one for a wired closed Transmitters circuit contact loop the other for a built in reed switch used 5816MN with a magnet 5816 Low RF Transmits a fault condition when temperature drops below TEMP Temperature 45 F Sensor 5817 Multi Point RF Has three unique input loop codes one for a Primary Universal contact loop with programmable options the others for two Transmitter auxiliary closed circuit contact loops 5818 Recessed RF Reed switch magnetic contact sensor easily hidden in the Transmitter frame and edge of a door or window Has a single unique input loop code 14 4 Model Product Enter as Description Input Device Type 5819 Shock RF Connects to externally mounted inertia type shock detector Processor not supplied Transmitter Has built in tampered cover switch Has unique input loop codes Loop 1 Terminals for a wired N C sensor loop Loop 2 For a closed circuit contact loop using the built in reed switch in conjunction with a magnet Loop 3 Terminals for a wired closed circuit contact loop 5819WHS Shock RF e Has built in shock sensor 5819BRS Processor e Has built in tampered cov
168. y 30 seconds to alert that the end of Test mode is nearing 13 1 Installation Instructions 13 2 Checking Transmitter Enrollment Sniffer Mode Use this mode to verify that all transmitters have been properly programmed Make sure both partitions are disarmed before trying to enter this mode since this is a system wide command 1 Press Installer code 3 Note Ifthe communicator is in the process of sending a report to the central station the system will not go into the Sniffer mode If so wait a few minutes and try again The keypads in both partitions will display all zone numbers of wireless units in both partitions programmed into the system Fault each transmitter in turn causing each one to send a signal As the system receives a signal from each of the transmitters the zone number of that transmitter disappears from the display 2 After all transmitters have been checked exit the sniffer mode by keying Installer code OFF IMPORTANT Sniffer mode does not automatically expire You must manually exit Sniffer mode by entering Installer code OFF to return to normal operation Notes e All BR type units must physically be activated to clear the display e When one button of a transmitter RF UR or BR is activated all zones assigned to other buttons on that transmitter are cleared This also applies to 5816 and 5817 transmitters which have multiple loops zones transmitter that is
169. ypads to send a signal to a pager Built in Telephone Line Monitoring option can monitor the telephone line voltage and can cause a local display or a display and trouble alarm sound Event Logging records selected events up to 100 events in a history log control and readout from the log is done via Ademco Compass Downloader software or installer master code at Keypad Zone descriptors for all zones useful only when using Alpha display keypads and or the FA4285 FA4286 Phone Module Optional bell supervision detects external sounder wiring short or open causes a trouble condition keypad display and sends a report to the central monitoring station if enabled Optional RF jam detection for wireless systems detects a condition that may impede proper RF reception jamming or other RF interference causes keypad display and sends a report to the central monitoring station if trouble reporting is enabled 1 1 Installation and Setup Guide Compatible Devices Supports up to 8 Addressable Keypads FA245KP Fixed Word Display FA260KP Fixed Word Display Keypad FA560KP Alpha Display Keypad FA245RF FA260RF Keypad Transceivers Supports up to 2 AUI units in addition to up to 8 keypads described above Supports 4219 4229 addressable hardwire zone expander modules up to 5 modules for up to 40 expansion zones Supports 5881 series receiver and 5800 series transmitters Output relays and or Powerline Carrier Devices X 10 type plu
170. zones are intact not faulted Doors and windows with contacts should be closed PIRs should be covered use a cloth to mask them temporarily if necessary If a NOT READY message is displayed press to display the faulted zone s Restore faulted zone s if necessary so that the READY message is displayed 1 Enter Installer Code 5 TEST then press 0 at the prompt to start Walk Test mode 1 DIAL 0 WALK no special display on Fixed Word keypads The following will be displayed TEST IN PROGRESS dd displayed on Fixed Word Display Keypads A Contact ID report will also be sent code 607 2 Upon entering the system test mode the outside sounder should sound for 1 second If the backup battery is discharged or missing the sounder may not turn on and LOW BATTERY report will be transmitted with a TEST report The keypad will beep about every 40 seconds as a reminder that the system is in the Test mode NOTE Wireless motion detectors Passive Infrared units will send signals out only if they have been inactive for 3 minutes conserves battery life 8 Test all sensors using the procedure described in the User s Guide Testing the System section 4 After checking sensors turn off the test mode by entering installer code OFF NOTE Test mode automatically ends after 4 hours During the final 5 minutes after 3 hours 55 minutes of Test mode the keypad emits a double beep ever
Download Pdf Manuals
Related Search
Related Contents
376\377\000p\000a\000r\000t\000e\000 \0003\000 \000 sistema máster mejorado de la serie de controladores modulares Builder's Choice HDX162989 Installation Guide : Free Download, Borrow, and Streaming : Internet Archive Dataram 16GB(2 x 8GB) DDR2-667 ABC Office 4107 CC Paper Shredder User Manual Copyright © All rights reserved.
Failed to retrieve file