SAG589200300 LXP INTRODUCTION MODEL XP4890 OVERVIEW

image

Contents

1. TOP VIEW ACCESS COVER REMOVED DETAIL A BAT C O GROUND 1 4 20 Captive Nuts 6 Places Factory supplies lug mounting hardware 1 4 20 x 0 5 Threaded Studs 10 Places Factory supplies lug mounting hardware Note All dimensions are in inches Page 77 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Overall Dimensions List 11 12 13 14 Power Shelves NOTES 1 All dimensions are in inches 2 Weight In Pounds Net Shipping Shelf 19 Ib 12 oz 25 Ib 4 oz 2 lb 14 oz 4 Ib 9 oz PCU 51b 4 oz 7 lb 13 oz Ring Gan 3lb 80z 516 0 oz 3 Finish Shelf and Module Bodies Bright Zinc Front Panels Textured Cool Gray M500 146 4 Mounting Position 1 shown with optional List 72 Ringing Generator
2. 78 Installer s Connections Locations and Dimensions List 11 12 13 14 AC Input Alarm Control amp arl 79 Installer s Connections Locations and Dimensions List 11 12 13 14 Distribution and Battery 80 Overall Dimensions List 90 91 93 Battery Temperature 81 Overall Dimensions List 92 Temperature Concentrator Module 82 Overall Dimensions Part No 528927 Load Shed 83 Overall Dimensions Part No 528608 Ringing Distribution Module 84 RELATED DOCUMENTATION 85 REVISION RECORD 86 Page 6 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 LIST INFORMATION E
3. Mounting Position for GMT Assembly When Factory Installed Page 34 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Home Alarm Type Fuses Note When used for power distribution load should not exceed 80 of device rating except 10 and 15 amp fuses for which load should not exceed 70 of device rating BUSSMANN GMT ALARM TYPE FUSES FUSE AMPERE RATING PART NUMBER COLOR 18 100 GMT A 248610301 1 4 248610200 VIOLET 1 2 248610300 RED 3 4 248610500 BROWN 1 1 3 248610700 WHITE 2 248610800 ORANGE 3 248610900 BLUE 5 24861 1000 GREEN 7 1 2 24861 1300 BLACK WHITE 10 248611200 RED WHITE 15 248611500 RED BLUE Safety 248898700 u use Cover Replacement Dummy Fuse 248872600 These fuses recommended for use in P N 528608 Ringing Distribution Module Table 7 Replacement Cables MCA Control Bus Termination Plug Features Plug must be installed in unused MCA control bus port J10 One plug is furnish
4. See recommended position Mounting MTG MTG MTG Angle POS POS POS MCA DISTRIBUTION Distribution Alarm amp Detail 1 2 3 Control Wiring Entrance Battery Wiring Entrance RIGHT SIDE VIEW 23 000 FRONT VIEW MOUNTING ANGLE DETAIL 0 220 0 250 x 0 375 AC Input BT Accepts 3 4 Conduit Fittings 0 500 0 LEFT SIDE VIEW 1 000 Page 78 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Installer s Connections Locations and Dimensions List 11 12 13 14 AC Input Alarm Control amp Reference MTG MTG MTG AC INPUT OS P P Cover Removed o o ooo n a C3 O FRONT VIEW TB1 jut i ee ALARM REFERENCE amp CONTROL Located on MCA inside the cabinet Alarm Outputs 1 Hi amp Control Inputs Wee PCB
5. 300 List 91 30 List 93 LIST 91 93 DIGITAL PROBE NOTE All dimensions are in inches Page 81 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Overall Dimensions List 92 Temperature Concentrator Module TXM K 1 835 0 190 DIA 2 PLACES 3 6 586 6 100 5 510 LN INNS I o RET qn ENS qo WES qo EE e ENSE Exe EE EIER EE ESE k 2 070 LEFT SIDE RIGHT SIDE Notes 1 All dimensions are in inches 2 Weight in lbs Net 9 oz Shipping 2 lbs 8 oz 3 Finish Off White Page 82 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Gui
6. LOAD SHED S R DISCON hh mm or LOAD SHED S R NO TIMER or LOAD SHED 51 81 IN hh mm ss PANEL 5 RECONNECT LD BATT vv vv V or PANEL S RECONNECT LD BATT MANUALLY or LOAD SHED S R RECON vv vv V GO TO FUNCTION MENU RELAY ASSIGNMENT MENU ASSIGN RELAY S P Ri 248 FUNCTION RF 1 GO TO CONFIGURE MENU 2 GO BACK TO MENU TREE BEGINNING SPECIAL FUNCTION SELECTION MENU SPECIAL FUNCTION SF DEFINITION GO TO CONFIGURE MENU 2 GO BACK TO MENU TREE BEGINNING NETWORK ADDRESS MENU MAC ADDRESS GO TO CONFIGURE MENU 2 GO BACK MENU TREE BEGINNING Page 68 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited N To Sheet 8 From Sheet 8 SPECIAL FUNCTION DEFINITION MENU cq _ TEMPERATURE PROBE 1 ALARM c TEMPERATURE PROBE 2 ALARM cq BINARY INPUT IS OP CL GO TO SPECIAL FUNCTION MENU 2 GO BACK TO MENU TREE BEGINNING System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 SHEET 8 RELAY FUNCTION DEFINITION MENU r TEMPERATURE PROBE
7. SHEET 6 SYSTEM ADJUSTMENT MENU From ALARM ADJUSTMENT MENU 1s Sheet 4 FUNCTION MENU cont d from previous page ADJUST THE SYSTEM 142 VOLTS amp AMPS ADJUST THE ALARM 148 sETPOINTS MM RA 162 ADJUST THE BATTERY eA ee ME SETPOINTS BATTERY ADJUSTMENT MENU 100 PCU CURRENT IS aaaaaA 147 or POWER LIMIT CURRENT aaaaaA MAX TEMES RAUB One 1 GO TO FUNCTION MENU HI 1 IS OFF T or 2 GO BACK TO MENU TREE TEMPERATURE PROBE BEGINNING Sheet 7 HI ff ttt C F LO 2 IS OFF or TEMPERATURE PROBE 158 LO 2 ttt TEMPERATURE 2 IS OFF or TEMPERATURE PROBE HI 2 ttt C F MIDPOINT D RS H A1 ALARM IS OFF or MIDPOINT D RS H A1 vwv vvV TEMPERATURE PROBE LO 1 IS OFF or TEMPERATURE PROBE 457 LO 1 ttt MIDPOINT D RS Hit A2 ALARM IS OFF or MIDPOINT D RS H A2 2 GOBACK TO MENU TREE BEGINNING GO TO FUNCTION MENU 2 GO BACK TO MENU TREE BEGINNING Page 67 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 Issue AH June 6
8. 479 7499 90A m E 66 99 100A 5929 Recommended Crimp Lug i Hole 245312200 245312400 245312400 245350400 245350600 245350700 245350800 2 hole 245342300 245342300 245342300 245390200 245346700 245346800 245346900 Table 2 Recommended Distribution Wire Size and Lug Selection Load and Load Return Notes for Tables 2 Wire sizes are based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for wire rated at 90 C conductor temperature operating in ambient temperatures of 40 C 50 C and 65 C was used For other operating ambient temperatures refer to the NEC For operation in countries where the NEC is not recognized follow applicable codes Recommended wire sizes are sufficient to restrict voltage drop to 1 0 volt or less at listed branch current for the loop lengths shown Loop length is the sum of the lengths of the positive and negative leads Wire Size Loop Length Combination Calculated using 40 C Ambient Operating Temperature Wire Size Loop Length Combination Calculated using 50 C Ambient Operating Temperature Wire Size Loop Length Combination Calculated using 65 C Ambient Operating Temperature One hole lugs are 1 4 bolt clearance Two hole lugs are 1 4 bolt clearance on 5 8 centers Refer to drawing 031110100 for
9. 1 ALARM 0 TEMPERATURE PROBE HI 2 ALARM o TEMPERATURE PROBE LO 1 ALARM r TEMPERATURE PROBE LO 2 ALARM lt TEMPERATURE PROBE NO SIGNAL cr SINGLE RINGER FAILURE zxj RINGER PAIR FALURE zr NO RINGERS IN INVENTORY zx MIDPOINT D RS H HI 1 ALARM 4 MIDPOINT D RS H HIGH 2 ALARM cq MIDPOINT D RS H LO 1 ALARM 4 MIDPOINT D RS H LO 2 ALARM _ MIDPOINT D RS H NO SIGNAL cd BINARY INPUT Bl IS From 1 OP CL Sheet 7 RELAY FUNCTION SELECTION MENU RELAY FUNCTION RF GO TO RELAY FUNCTION DEFINITION MENU GO BACK TO MENU TREE GO TO CONFIGURE MENU BEGINNING GO BACK TO MENU TREE BEGINNING To Sheet 7 Page 69 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 3 1 9 3 1 10 External Control Circuits A Binary Inputs The MCA provides four 4 Binary Inputs for external control of system functions The inputs must be mapped by the user to the Special Functions that they are to control The following Special Functions a
10. 1520 0 991 099 1678 0 99 299 496 4 596 se se 1664 oss ees 608 65 1686 0 99 eis o os oam 8 as 182 4 40 s esa 763 762 0 1520 0 966 909 n0 636 1668 0 96 1675 0 96 0 989 oso ees 79 203 240 349 375 382 387 386 289 498 545 587 608 09 76 468 521 550 574 579 Page 49 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 60 Hz Input 25 C Ambient Number Nominal Percent Input Current Input Input Power fficiency Heat of PCUs Input of Full Amperes VA Watts Factor Dissipation Installed Voltage Load BTU Hr 4 m o os 6 25 sss s 45 754 50 100 221 099 100 12 96 1562 1559 0 997 83 7 87 4 87 5 87 3 872 N 2 0 95 0 99 2 0 95 Max 0 99 253 87 1 85 4 89 4 0 95 0 994 29 6 295 85 5 394 89 9 91 1 91 0 90 1 0 99 0 oe 72 25 354
11. 98 Amperes 4500 Watts max 208 240V 49 Amperes 2250 Watts max 120V 25A 58 0VDC to 32 6A 46VDC 1500 Watts max 208 240V 12 5 58 0VDC to 16 3A 46VDC 750 Watts max 120V List 1 2 3 4 100 Amperes max List 11 12 13 14 100 Amperes 50C or less ambient 90 Amperes above 50C ambient UL 60950 Recognized CAN CSA 22 2 Equipment Shelf for Relay Rack Mounting 23 12 3 5 5 List 1 2 3 4 Front amp sides for installation front for operation and maintenance List 11 12 13 14 Front for installation operation and maintenance None Microprocessor Textured Cool Gray 120V Line Cord Kit 240V Line Cord Kit Local Computer Access Cable MCA Control Bus Cable Analog Battery Temperature Probe Digital Battery Temperature Probe Battery Temperature Probe Concentrator Module 50 VA Redundant Ringing Generator Module Circuit Breakers Fuses Lugs Replacement MCA Control Bus Cable Replacement MCA Control Bus Termination Plug Load Shed Card Ringing Distribution Module AP6C57EA EB Ring amp Distribution Module Field Replaceable Components 20 C to 65 C 4 to 149 F 65 C to 80 C 149 F to 176 F Page 3 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it with
12. GO BACK TO MENU TREE Sheet 2 vv vvV INT BEGINNING 86 TOTAL LOAD CURRENT PCU CURRENT MENU TOTAL PCU CURRENT PCU S P CURRENT 88 aaaaaA 89 aaaaaA TOTAL BATTERY CURR GO TO MEASUREMENT FUNCTION MENU CHARGE aaaaaA MENU ll See 2 GO BACK TO MENU TREE VIEW THE SYSTEM Hein CURE BEGINNING MEASUREMENTS B FLOAT IS ACTIVE BATTERY RESERVE TIME CHANGE MODE hhh mm BATTERY CURRENT MENU or 92 9 PANEL S SET FLOAT MODE BATTERY RESERVE TIME CHARGE aaaaaA or hhh mm EST 91 or EQUALIZE IS ACTIVE as DIST PANEL Si hhh mm BATTERY HEALTH DISCH aaaaaA iid 93 CLEAR ALARM a 4 GOTO MEASUREMENT paper oa BATTERY COMPENSATED MENU E FOR ttt or or 2 GO BACK TO MENU TREE SET EQUALIZE MODE 94 VIEW THE TEMPERATURE q BEGINNING 98 or MEASUREMENTS BATTERY TEST ACTIVE hhh mm ss VIEW THE MIDPOINT 4 TEMPERATURE MENU BATTERY xu ACTIVE TEMPERATURE PROBE JU 1 ttt C F CHANGE MODE GO TO FUNCTION MENU 95 or 2 BACK TO MENU TREE GO TO MEASUREMENT SET BATTERY TEST denen dia g MENU KOSE 2 GO BACK TO MENU TREE E q BEGINNING THE EQUALIZE INPUT IS ACTIVE or MIDPOINT MENU THERMALCRUNAWAY MIDPOINT D RS H IS ACTIVE oz VIEW THE SYSTEM 1 GO TO MEASUREMENT 99 INVENTORY MENU 2 GO BACK TO MENU TREE BEGINNING To To Sheet 5 Sheet 6 Page 65 of 86 This document is the property of Emerson Network Power
13. Page 55 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 E Refer to Figure 3 for a curve that represents the typical LXP1500 output power characteristics at various ambient temperatures Output voltage and current limit are set to maximum Thermal Power Limit 208 240Vin Typical LE m gt 30 80 C C 70 C 65 C 20 10 0 0 4 8 12 16 20 24 28 32 36 AMPS Thermal Power Limit 120Vin Typical o LE m gt 30 80 C 75 C 70 C 65 C 20 10 0 0 2 4 6 8 10 12 14 16 18 AMPS Figure 3 Page 56 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission
14. 4 oz 7 lb 13 oz Ring Gen 3lb 80z 516 002 3 Finish Shelf and Module Bodies Bright Zinc Front Panels Textured Cool Gray M500 146 TOP VIEW 4 Mounting Position 1 shown with optional List 72 Ringing Generator See recommended position Mounting MTG MTG MTG Angle POS POS POS MCA DISTRIBUTION Distribution Alarm amp Control Detail 1 2 3 l l Wiring Entrance Wiring Entrance RIGHT SIDE VIEW 22 250 23 000 MOUNTING ANGLE DETAIL FRONT VIEW 0 220 x 0 250 x 0 375 SLOT AC Input 0 500 Accepts 3 4 Conduit Fittings 0 O 1 000 LEFT SIDE VIEW 1 000 0 500 0 220 Page 74 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Installer s Connections Locations and Dimensions List 1 2 3 4 AC Input Alarm Control amp Reference AC INPUT Cover Removed FRONT VIEW ALARM REFERENCE amp CONTROL
15. 88 796 0 94 50 649 1563 1516 097 0 989 3923 0 99 0 99 3353 3323 0 991 3355 0 99 25 50 120 14 o 9 0 96 0 98 MEM 099 3327 3300 25 50 240 c N Page 50 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 60 Hz Input 25 C Ambient Number Nominal Percent Input Current Input Input Power fficiency Heat of PCUs Input of Full Amperes VA Watts Factor Dissipation Installed Voltage Load BTU Hr 1 o os 763 T 875 87 876 2588 2582 873 87 3 o o tes amp osm 286 E 897 wo 2 a 5 0 2 5 2 5 5039 897 o os 1 sa 0494 862 902 100 1880 45 0 4485 099 91 1 5026 4986 30 5033 4640 Page 51 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems
16. Ft Length Ft 90 C Contact rules Temper 1 0 Volt 0 25 Volt Wire Emerson Network Anderson P ature Drop Drop Size Power Part No Part No ee 40 C 47 11 6 247108670 Red 130003 Red 50 C 47 11 6 AWG 45 65 52 13 6 AWG 247108671 Black 1300G4 Black Table 3B Recommended Battery Wire Size and Lug Selection List 11 12 13 and 14 Power and Distribution Shelves Notes for Tables 3B 1 Wire sizes are based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for wire rated at 90 C conductor temperature operating in ambient temperatures of 40 C 50 C and 65 C was used For other operating ambient temperatures refer to the NEC For operation in countries where the NEC is not recognized follow applicable codes Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading or less at the current shown in the Current per Battery String column for the loop lengths shown in this column Loop length is the sum of the lengths of the positive and negative leads Use hand crimping tool Anderson Part No 1309G4 Contacts should be crimped to the specifications given in the manufacturer s instructions furnished with the crimp tool or connector Page 30 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc
17. Located on MCA inside the cabinet Alarm Outputs amp Control Inputs Not used in this model TB2 9 9 9 0 2 9 9 9 9 9 9 9 2 9 9 9 9909595959095959095959096959590 9050509695909050969550505090069 9990909095909090909050908096 9595059995009500959005950599059 9595909995099590959090959590909 Coe eoe 0900590 00500909500959090050095969095 9509050505090505050509090505050 9999500959595950095959595999595 09500909500959090950095969095 959595999509959 09500099 00090909590060095909590900690 9990959695909590959595900590060 005006 095009099099599 0202020200000200 EO OO COE 9950095959095909095009595209590 CUTAWAY VIEW CABINET RIGHT SIDE TB2 aa FRAME GROUND No 8 32 x 0 563 Threaded Stud J3 Battery Temperature Probe J8 Web Interface Ethernet Note All dimensions are in inches Page 75 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide Spec No 589200300 Model XP4890 SAG589200300 Issue AH June 6 2007 Installer s Connections Locations and Dimensions L
18. NO SIGNAL GO TO MAIN ALARM MENU GO BACK TO MENU TREE BEGINNING 1 ALARM TEMPERATURE PROBE ALARM LIMIT ttt C F HI 42 ALARM 8 NOW AT ttt C F ALARM LIMIT ttt C F 8 NOW AT ttt C F ALARM LIMIT ttt C F 8 NOW AT ttt C F Page 64 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited PCU S P EMERGENCY SHUTDOWN PCU S P HI VOLTAGE SHUTDOWN PCU S P AC OFF OR NO AC DATA PCU S P AC LINE TOO LOW PCU S P AC LINE TOO HIGH PCU S P POWER FACTOR FAIL PCU S P DC DC CONVERTER PCU S P OUTPUT IS INHIBITED PCU S P THERMAL CURRENT LIMIT PCU S P LOAD SHARE IMBALANCE PCU S P FAN SLOW OR STOPPED PCU S P IS DUPLICATED PCU S P NO RESPONSE GO TO PCU ALARM MENU 2 GO BACK TO MENU TREE 4 BEGINNING System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Home SHEET 4 LOAD CURRENT MENU MEASUREMENT MENU PANEL S SYSTEM OUTPUT SENSE vv vvV REM 1 GO TO MEASUREMENT From 85 or MENU SYSTEM OUTPUT SENSE 2
19. Postion 2 o o o o o o o o 99 TB2 p I e TOUR O a um Dn SR prp p E nm 95 ORO 8 9956 ot 9 OO T 9 x mr 9 exe 9 28 US SOG Hm 99 pnr p xum dU FRAME GROUND No 8 32 x 0 563 Threaded Stud O 9 ELIIIITIIITIITE 5 d 96 KE di E 9 0909099 J3 CUTAWAY VIEW Battery CABINET RIGHT SIDE Temperature Probe O Q E Q Q J8 Web Interface Ethernet Note All dimensions are in inches Page 79 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Installer s Connections Locations and Dimensions List 11 12 13 14 Distribution and Battery Load Connections 1 4 20 Threa
20. iot Rp P 42 2 2 Input iier t Ram vefte nie T iere 44 2 3 standard 5 acc tote it mense fuo ere debe in octal 53 P M 59 3 1 Standard Features teri corem dne ioe fe esee nl desees eaa Rande 59 uoa edlen MI X TN 70 4 List 72 Redundant Ringing Generator System 71 Pede teda 71 71 4 3 Environmental e 71 4 4 Standard 72 PHYSICAL SIZE 74 Overall Dimensions List 1 2 3 4 Power 74 Installer s Connections Locations and Dimensions List 1 2 3 4 AC Input Alarm Control amp hijiirlpupeeeem c 75 Installer s Connections Locations and Dimensions List 1 2 3 4 Distribution 76 Installer s Connections Locations and Dimensions List 1 2 3 4 77 Overall Dimensions List 11 12 13 14 Power
21. or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 4 If AC line cords are required order one 1 List 47 120VAC or 48 240VAC per shelf as required for voltage and cord length Note List 47 120VAC line cords are restricted to powering one 1 PCU each 5 If battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multiple probes order One 1 List 92 TXM and List 91 probes as required 6 For bullet nose distribution positions order circuit breakers as required per Table 5 7 For bullet nose distribution positions order fuses as required per Table 6 8 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above 9 Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug one hole 1 4 bolt clearance as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse distribution positions order fuses as required per Table 7 11 Order Battery connectors as required per Battery Wire Sizes and Connectors List 11 12 13 and 14 Power and Distribution Shelves in the ACCESSORY INFORMATION section 12 For ringing and DC distribution in imbedded subscriber loop carrier systems such as SLC 96 or SLC
22. or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 List 3 23 Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Load Disconnect List of Parts Features Provides common equipment for one 1 Integrated Power amp Distribution Shelf rated for up to 98 Amperes 4500W of power conversion and 100A of distribution Provides 4 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers or fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Caution The maximum size circuit breaker or fuse used in ambient temperatures above 50 ambient SHALL BE 40 amperes Provides 10 mounting positions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current 1 battery shunt and Low Voltage Load Disconnect Provides mounting positions for one 1 MCA and up to three 3 PCUs Provides one 1 AC input circui
23. 2 GOBACK TO MENU TREE BEGINNING DISTRIBUTION INVENTORY MENU PANEL S INCLUDES 1 POSITION or PANEL S INCLUDES POSITIONS GO TO INVENTORY MENU GO BACK TO MENU TREE BEGINNING RELAY INVENTORY MENU RELAY BOARD S P IS REPORTING GO TO INVENTORY MENU 2 GOBACK TO MENU TREE BEGINNING RINGER INVENTORY MENU RINGER S P L R IS 125 REPORTING 1 GO INVENTORY MENU 2 GOBACK TO MENU TREE BEGINNING CONTROLLER INVENTORY DETAIL MENU CONTROLLER SERIAL 131 IHEHHHHHHHHHE CONTROLLER BOOTCODE THHHHHHHEHHHE CONTROLLER SOFTWARE THHHHHHHEHHHE CONTROLLER S P IN SHELF 132 133 134 BINARY Bi ALARM ON OPEN INPUT 135 or BINNARY ALARM ON CLOSED INPUT 1 GO TO CONTROLLER MENU 2 GO BACK TO MENU TREE BEGINNING TEMPERATURE INVENTORY MENU TEMPERATURE PROBE IS REPORTING GO TO INVENTORY MENU 2 GO BACK TO MENU TREE BEGINNING MIDPOINT INVENTORY MENU MIDPOINT D RS P H 140 IS REPORTING 1 GO TO INVENTORY MENU 2 GOBACK TO MENU TREE BEGINNING Page 66 of 86 PCU INVENTORY DETAIL MENU PCU S _P ASSEMBLY THHHHHHHHHHHE PCU S _P SERIAL THHHHHHHHHHHE PCU S _P BOOTCODE THHHHHHHHHHHE PCU S _P SOFTWARE THHHHHHHBHHHE PSC S _P BOOTCODE THHHHHHHHHHHE PSC Sit P SOFTWARE THHHHHHHHHHHE GO TO PCU INVENTORY 2 GOBACK TO MENU TREE BEGINNING 2 120 121 122 123 DISTRIBUTION
24. 2007 From Sheet 6 FUNCTION MENU cont d ADJUST THE LVD 181 sETPOINTS TURN PCUs OFF OR RESET RESTART 186 or ENERGY MANAGEMENT IS IN CONTROL CHANGE CONFIGURATION 189 PARAMETERS FUNCTION TEST MODE IS OFF 263 or SPECIAL FUNCTION SF IS ACTIVE LAST NODE RECOGNIZED PCU 5 or LAST NODE RECOGNIZED DSM Si 264 or LAST NODE RECOGNIZED RCB S P or LAST NODE RECOGNIZED RNG S P L R 2 GO BACK TO MENU TREE BEGINNING SHEET 7 PCU ENABLE MENU PCU 5 IS NOW ON TURN IT OFF or PCU S P IS NOW OFF TURN IT ON RESET RESTART PCU S P RESET RI 1 GO TO FUNCTION MENU 2 GO BACK TO MENU TREE BEGINNING CONFIGURE MENU IHHHHHHHHHHHHHHHHHHHE PROCESSED or CONFIG FILE BEING PROCESSED or CONFIG FILE ERROR PROCESSED or NO CONFIG FILE WAS PROCESSED or NO CONFIG FILES ARE PRESENT 189A ASSIGN RELAYS TO 247 FUNCTIONS gag DEFINE SPECIAL FUNCTIONS 254 CHANGE NETWORK 255 ADDRESSES RINGER S P L R IS ACTIVE or RINGER S P L R INACTIVE SET ACTIVE 261 262 1 GO TO FUNCTION MENU 2 GO BACK TO MENU TREE BEGINNING 2 GO BACK TO MENU TREE BEGINNING System Application Guide Spec No 589200300 Model XP4890 LVD ADJUSTMENT MENU PANEL S DISCONNECT LD BATT vv vv V or LOAD SHED S R DISCONE vv vv V or
25. Amperes 4500W of power conversion and 100A of distribution Provides 4 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers or fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Caution The maximum size circuit breaker or fuse used in ambient temperatures above 50 ambient SHALL BE 40 amperes Provides 10 mounting positions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current Provides mounting positions for one 1 MCA and up to three 3 PCUs Provides one 1 AC input circuit via front access terminal block connections Conduit opening is provided on side panel in front of mounting angle Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug Mounts in a standard 23 relay rack Restrictions None Ordering Notes 1 2 BUE IS IR I ON Order one 1 List 32 MCA Order PCUs per List 55 as required Order Ringing Generators per List 72 as required If
26. Busbar link 534621 Assembly cable distribution 2U ISD 128824 Contactor 1C SPDT 150 Amp 48VDC Page 39 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 List Part 2 40 1 524769 Cord AC input NEMA L5 30P 8AWG 14 5 ft 524770 Cord AC input NEMA L6 30P 8AWG 14 5 ft 44 1 525102 Kit AC vertical feed input assembly 534840 Cord AC input NEMA 5 15 10AWG 10 ft 534841 Cord AC input NEMA 5 15 10AWG 6 ft 525008 Blank module 534842 Cord AC input NEMA 6 20 10AWG 10 ft 2 534843 Cord AC input NEMA 6 20 10AWG 6 ft 525008 Blank module 486534200 PCU 1500W 48VDC 120 208 240VAC 1 487112200 Ringing Generator Module complete includes 2 P N 487112100 Ringing Generators 30 i S262 Probe battery temp analog Page 40 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc A
27. Does not exceed 26 dBrn C 2 Typically 0 100 millivolt psophometric Does not exceed 1 millivolt psophometric B Wide Band Noise Complies with Telcordia GR 947 CORE 1 Typically 150 millivolt peak to peak Does not exceed 250 millivolt peak to peak 2 Typically 10 millivolts rms Does not exceed 100 millivolt rms 2 2 Input Ratings 2 2 1 Voltage A Nominal 120 208 240 volts AC single phase 50 60 Hz with an operating range of 90 175 volts Reduced Power Mode and 176 264 volts Full Power Mode Acceptable input frequency range is 45 to 65 Hz 2 2 2 Harmonic Content Meets EN 61000 3 2 2 2 3 Inrush Current Peak does not exceed 2 times the RMS input current at full load nominal input voltage and for any duration of AC input interrupts Under the above conditions standard AC distribution circuit breakers will not trip Page 44 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 A System output is initially adjusted to 54 48 volts DC as measured at the shelf output terminals at 50 of full load and nominal inpu
28. North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 B Maximum Input Current At 100 of full load with output adjusted to 58 volts DC as measured at the output bus 60 Hz Input 25 C Ambient Nominal Input Number of Input Current Input Voltage Voltage PCUs Installed Amperes E 2 14 ME OMEN NE NN 208 240 oa Page 52 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 2 3 Standard Features 2 3 1 2 3 2 2 3 3 Type of Power Conversion Circuit High frequency Float Charging Output Mode In this mode of operation system output voltage is constant and output current does not exceed the current limit setting During normal operation the battery is not required to furnish load current and remains in a fully charged condition The float voltage setting can be checked
29. Provides eight 8 relays that can be individually configured as additional alarm relays or as Low Voltage Disconnect control relays for reducing the system load load shed If configured for load disconnect control of the relays can be based upon either system voltage or battery discharge elapsed time Provides four 4 battery midpoint monitoring inputs All functions are configured and controlled by the system MCA External mounting Includes one 1 2 ft MCA control bus cable P N 524410 and one 1 control bus termination plug P N 524653 See Physical Size Information for Load Shed Card dimensions See Load Shed Card Installation and Operating Instructions Section 5985 for complete specifications Restrictions Load shed contactors are not included A system battery shunt is required for timed Load Shed MCA version 3 0 or newer is required Maximum number of Load Shed Cards supported by MCA is four 4 Maximum combined MCA control bus cable length must not exceed 125 feet Ordering Notes 1 Where MCA control bus cable lengths other than the furnished 2 ft cable are required order per List 81 Ringing Distribution Module Part No 528608 Features Designed to accept a bulk ringing input signal and provide six 6 fused ringing distribution outputs Page 36 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and propr
30. after a preset programmable time period 3 Method 3 Automatic Equalize THE AUTOMATIC EQUALIZE FEATURE IS INTENDED FOR USE ONLY WITH WET CELL BATTERIES USING THIS FEATURE WITH VALVE REGULATED BATTERIES IS NOT RECOMMENDED This feature can be enabled or disabled by a user via the MCA The default state is disabled The Automatic Equalize feature is a time based function that is controlled by a customer selectable multiplier and by the Battery on Discharge BOD alarm setpoint The MCA s default setting is for a multiplier of zero which disables the Automatic Equalize feature When the Automatic Equalize feature is enabled if system voltage drops to less than the BOD alarm setpoint the MCA initiates a timing cycle to measure the discharge time period The MCA requires at least 15 minutes of continuous BOD alarm in order to prevent nuisance equalization cycles When system voltage rises to above the BOD alarm setpoint the MCA ends the discharge timing cycle and assuming a minimum of 15 minutes has elapsed places the PCUs into the equalize mode for a customer selectable multiple of the discharge time period the discharge time period includes the initial 15 minutes Page 53 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it wi
31. and or adjusted without removing a PCU or affecting the load One adjustment changes the output of all PCUs Note If the current demanded by the load exceeds the current limit setting of the system the battery is required to furnish the difference in load current and begins discharging Note If the system is used with a battery temperature probe the MCA automatically adjusts system output This ensures proper voltage to the battery as battery ambient temperature fluctuates Equalize Charging Output Mode A This mode of operation is used if higher output voltage is required for equalizing the charge on all battery cells of a conventional flooded cell battery or for recharging the battery following a commercial power failure The Equalize voltage setting can be checked and or adjusted without removing a PCU or affecting the load One adjustment changes the output of all PCUs Note If the system is used with a battery temperature probe equalize mode of operation is not used B There are three methods of placing the system from the Float mode to the Equalize mode 1 Method 1 Manual Equalize A user manually places the system into the Equalize mode via the MCA interface A user must manually return the system to the Float mode via the MCA interface 2 Method 2 Manually Initiated Timed Equalize A user manually places the system into the Equalize mode via the MCA interface The system automatically returns to the Float mode
32. bottom starting with the highest capacity and working to the lowest capacity Table 5 Page 32 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 TPS TLS Type Fuses Home A single fuseholder provides for installation of a 3 to 100 ampere Bussmann TPS type or Littelfuse TLS type fuse This fuseholder plugs into a single mounting position This fuseholder also provides a GMT A alarm type fuse which operates open to provide an alarm indication if the distribution fuse opens Ordering Notes 1 Order fuses per Table 6 Note Load should not exceed 80 of device rating Caution A fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Caution List 1 2 3 4 only The maximum size fuse used in ambient temperatures above 50 C ambient shall be 40 amperes Caution List 11 12 13 14 only The maximum size circuit breaker or fuse used in ambient temperatures above 50 C ambient SHALL BE 50 amperes A circuit breaker or fuse located in the mounting
33. position adjacent to a 40 or 50 ampere circuit breaker or fuse SHALL BE a maximum of 30 amperes Where two 40 or 50 ampere circuit breakers or fuses are used an empty mounting space SHALL BE provided between them 2 Order one 1 Part No 117201 TPS TLS type fuseholder for each fuse 3 For lug and wire size selection refer to Table 4 TPS TLS TYPE FUSES AMPERE RATING PART NUMBER 3 248230900 5 248231000 6 248231200 10 248231500 15 248231800 20 248232100 25 248232400 30 248232700 40 248233300 50 248233900 60 248234200 70 248234500 80 118413 90 118414 100 118415 TPS TLS Type Fuseholder 117201 Fuseholders are not furnished and must be ordered as required Order 1 Part No 117201 for each fuse position required Fuseholder includes 1 alarm fuse Bussmann GMT A 18 100 amp Emerson Network Power 248610301 and 1 alarm fuse safety cover Emerson Network Power P N 248898700 Unless otherwise specified fuses shall be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Table 6 Page 33 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is
34. to Table 5 for recommended wire sizes and lugs at rated maximum total distribution load 100 amperes When making connections observe correct polarity 2 For other available lugs and hardware refer to drawings 031110100 through 031110300 Maximum Ambient Loop Loop 5 Current Operating Length Ft Length Ft e Temperature 1 0 Volt Drop 0 25 Volt Drop p ug e 59 14 12AWG 1 245346900 119 29 2 2AWG 2 245346900 T I 59 14 12AWG 1 245346900 119 29 2 2AWG 2 245346900 e 75 18 2 4AWG 2 245346800 112 28 8 4AWG 3 245346800 Table 3A Recommended Battery Wire Size and Lug Selection Notes for Tables 3 Wire sizes are based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for wire rated at 90 C conductor temperature operating in ambient temperatures of 40 C 50 C and 65 C was used For other operating ambient temperatures refer to the NEC For operation in countries where the NEC is not recognized follow applicable codes Recommended wire sizes are sufficient to restrict voltage drop to the voltage shown in the column heading or less at rated full load output current of the shelf for the loop lengths shown in this column Loop length is the sum of the lengths of the positive and negative leads Two hole lug 1 4
35. use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 RELATED DOCUMENTATION Home Installation Instructions Section 5978 User Instructions Section 5979 Color MCA Menu Tree Section 5956 TXM Instructions Section 5940 Load Shed Card Instructions Section 5985 Ringing Distribution Module Instructions Section 5991 Schematic Diagram SD589200300 Wiring Diagram 589200300 Lug Detail Drawings 031110100 031110200 031110300 Page 85 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 REVISION RECORD Home Change Issue Number Description of Change Date Approved ECO AA LLP205185 New 2 24 06 J Kirkpatrick 2 14 06 J Rader AB LLP205652 Added Part No 528927 Load Shed Card 5 1 06 J Kirkpatrick Added tables to List 80 and 81 descriptions 5 1 06 J Jasko Updated MCA Menu Tree to version 3 0 AC LLP206112 Added L
36. volts DC Battery Test voltage is adjustable from 45 00 to 58 00 volts DC Float Equalize and Battery Test voltages are factory set at 54 00 volts unless otherwise specified The output voltage temperature coefficient does not exceed 0 01 per degree centigrade from 40 C to 65 C B With Battery Charge Temperature Compensation Probe With an optional battery temperature probe installed the MCA automatically increases or decreases the output voltage as battery temperature decreases or increases respectively Float voltage is factory set at approximately 54 48 volts at 25 C battery temperature The Float Equalize and Battery Test voltage ranges are the same as without battery charge temperature compensation Using battery and equipment manufacturers recommendations the user selects the following temperature compensation curve parameters via the MCA Figure 1 details a user defined Temperature Compensation Curve 1 The temperature compensation slope in volts C Adjustable from zero to 200 millivolts C Factory set at OV C NO TEMPERATURE COMPENSATION 2 The maximum voltage limit in volts DC Adjustable from float up to 58 00 volts DC but automatically limited to one volt below the High Voltage Shutdown setting Factory set at 56 50 volts DC 3 The minimum voltage limit in volts DC Adjustable from float down to 47 00 volts DC Factory set at 52 00 volts DC Page 42 of 86 This document is the property of Emerson Netw
37. when a shorter cable is needed Page 23 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 ACCESSORY INFORMATION Home Recommended Wire Sizes and Branch Circuit Protection AC Input Wire Sizes Branch Circuit Protection Features Screw compression type terminals are provided for connection of AC input wiring These terminals are accessed through the front of the Power Shelf threaded stud 8 32 is provided for installation of frame ground wiring The stud is accessed through the front of the Power Shelf Ordering Notes 1 For Lists 1 2 3 and 4 one AC input circuit refer to Tables 1A 120 240VAC and 1B 208VAC for recommended wire sizes and branch circuit protection 2 ForLists 11 12 13 and 14 two AC input circuits refer to Tables 1C 120 240VAC and 1D 208VAC for recommended wire sizes and branch circuit protection 3 Notes referenced in tables are found after Table 1D List 1 2 3 4 120 240 VAC Input One AC Input Circuit Recm Line Terminals Ground Ambient Branch Operating Cir
38. 0 0 Table 4 MCA Basic Settings Page 59 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Home Parameter Max Min ae Battery Charge Current Alarm Amps 30000 0 150 Battery ipic 57 00 45 00 48 00 Equalize Mode Output Volts 58 00 47 00 56 50 Equalize Time hh mm ss 99 59 00 00 1 00 01 00 00 Auto Equalize Multiplier 15 0 0 Temp Comp Slope mV C 200 ien ican Temp Comp Max Volts 58 00 47 00 56 40 Temp Comp Min Volts 58 00 47 00 52 00 Battery Test End Setpoint Volts 57 00 45 00 46 00 Battery Test Sample Interval Seconds 3600 1 60 Battery Test Duration hh mm ss 99 59 00 00 1 00 01 00 00 Battery End Of Reserve Setpoint Volts 51 60 39 60 42 00 Battery Health Setpoint 99 0 75 Battery Reserve Low Setpoint Minutes 600 0 60 Expected Battery Reserve Setpoint hh mm 99 59 00 00 8 00 No Alarm on Recharge Setpoint Hours 24 1 12 Battery High Temp 1 Alarm C 100 50 100 Battery High Temp 2 Alarm C 100 50 100 B
39. 1 Electrical Fast Transient Burst Immunity Complies with EN61000 4 4 Level 4 1 1 12 Mounting Front and side access are required for wiring Recommended minimum aisle space clearance is 2 6 for the front of the Power Distribution System 1 2 Compliance Information 1 2 1 Safety Compliance Page 41 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 A This unit meets the requirements of UL 60950 Standard for Information Home Technology Equipment and is UL Recognized as a power supply for use in Telephone Electronic Data Processing or Information Processing Equipment B This unit meets the requirements of CAN CSA 22 2 No 60950 00 and is tested and Certified by UL c UR as a Component Type Power Supply 1 3 Local Controls and Indicators See specifications for PCU and MCA 2 PCU 2 1 Output Ratings 2 1 4 Voltage Nominal 48 volts DC Positive Ground A Without Battery Charge Temperature Compensation Float voltage is adjustable from 47 00 to 58 00 volts DC Equalize voltage is adjustable from 47 00 to 58 00
40. 180 182 183 184 185 190 191 251 259 PANEL S DISCONNECT LD BATT vv vv V or LOAD SHED S R DISCON vv vv V or LOAD SHED S R DISCON hh mm or LOAD SHED S R NO TIMER or LOAD SHED S R IN hh mm ss PANEL S RECONNECT LD BATT vv vv V or PANEL S RECONNECT LD BATT MANUALLY or LOAD SHED S R RECON vv vv V TO SHEET 2 MAIN ALARM MENU or NORMAL DISPLAY MENU This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide Spec No 589200300 Model XP4890 SAG589200300 Issue AH June 6 2007 9 10 11 12 SYSTEM HIGH VOLTAGE 2 ALARM vencer __ BINARY INPUT IS OP CL SPECIAL FUNCTION SF IS ACTIVE GO TO FUNCTION MENU GO BACK TO MENU TREE BEGINNING 76 77 78 80 82 83 1 2 c MAIN ALARM MENU SYSTEM LOW VOLTAGE 1 ALARM SYSTEM LOW VOLTAGE 2 ALARM SYSTEM HIGH VOLTAGE 1 ALARM 1 PANEL FUSE OR BREAKER ALARM or PANELS FUSE OR BREAKER ALARM AC POWER TO 1 PCU HAS FAILED or AC POWER TO PCUs HAS FAILED or ALL AC POWER HAS FAILED ALARM LIMIT vv vv V NOW AT w vv V SHEET 2 ALARM
41. 20030014 Connections up to 98 Amps 4500W of power conversion 2U equipped with Load amp Battery Shunts amp LVBD 32 58920030032 LXC300 Meter Control Alarm Assembly MCA with Ethernet AC Line Cord Kit 2 14 5 ft Cords 120VAC NEMA L5 30P ai Plugs for List 1 2 3 and 4 T 41 58920030041 AC Line Cord Kit 2 14 5 ft Cords 208 240VAC NEMA L6 30P Plugs for List 1 2 3 and 4 43 58920030043 AC Input Vertical Feed Assembly AC Line Cord Kit 2 120VAC NEMA 5 15P Plugs 6 and 10 ft _ length available for List 11 12 13 and 14 only AC Line Cord Kit 2 240VAC NEMA 6 20P Plugs 6 and 10 ft _ riis length available for List 11 12 13 and 14 only 50 58920030050 Blank Module LXP1500 Power Conversion Unit PCU 1500W 48V BW 58920030055 120 208 240VAC 72 58920030072 Redundant Ringing Generator Module 50VA In shelf 73 58920030073 Replacement Ringing Generator for List 73 80 58920030080 Cable Local Computer Access This document is the property of Emerson Network Power Energy Systems North America and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Page 7 of 86 SAG589200300 Issue AH June 6 2007 System Application Guide Spec No
42. 23 Power and Distribution Shelf List of Parts with Load and Battery Shunts Features Provides common equipment for one 1 Integrated Power amp Distribution Shelf rated for up to 98 Amperes 4500W of power conversion and 100A of distribution Provides 4 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers or fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Caution The maximum size circuit breaker or fuse used in ambient temperatures above 50 ambient SHALL BE 40 amperes Provides 10 mounting positions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current and 1 battery shunt Provides mounting positions for one 1 MCA and up to three 3 PCUs Provides one 1 AC input circuit via front access terminal block connections Conduit opening is provided on side panel in front of mounting angle Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug Mounts in a standard 23 relay rack R
43. 23 Web Browser Microsoft Internet Explorer 5 0 or newer is required 3 2 4 Screen Resolution 1024 x 768 or greater is required 3 2 5 Users 64 maximum 3 2 6 Security A Password Protection When logging onto the system the user is prompted to enter a User Password B Page Access Levels User configurations provide a Page Access Level which can be used to limit the functions available to a particular user Eight Page Access Levels are available 4 LIST 72 REDUNDANT RINGING GENERATOR SYSTEM 4 1 Output Ratings 4 1 1 Power 50 VA 4 1 2 Frequency A Nominal 20 Hz B Accuracy The initial frequency is 15 with output variation from no load to full load over the specified temperature and input voltage range C Distortion Total harmonic distortion THD is less than 596 of the fundamental frequency 4 1 3 Voltage A Nominal 86 VAC RMS B Regulation 5 from no load to full load within the specified input voltage range 4 2 Input Ratings 4 2 1 Voltage Negative 44 to 58 volts DC positive ground Negative 60 volts DC maximum transient 4 2 2 Current A No Load 90 milliamperes at 48V B Full Load 1 28 amperes at 48V 423 Filtering Noise fed back to a 50 ampere hour battery is less than 32 dBrnC Noise with no battery and one PCU as the source does not exceed 50dBrnC at any ambient temperature 4 3 Environmental Ratings 4 3 1 Operating Ambient Temperature Range A Start and Operate 40 C to 20
44. 3 Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Battery E 12 List 11 23 Front Access Power and Distribution Shelf with Load 5 13 List 12 23 Front Access Power and Distribution Shelf with Load and Battery Shunts 14 List 13 23 Front Access Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Load Disconnect 15 List 14 23 Front Access Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Battery 6 1 16 List 32 Model LXC300 Meter Control and Alarm Assembly MCA 17 List 40 AC Line Cord Kit 120VAC rirerire nnns nnns nnne assess entes sintassi nasse assis 18 List 41 AC Line Cord Kit 208 240VAC sisse ener nennen nnne 18 List 43 AC Input Vertical Feed Assembly ssssssssssssssssseeeee enne enne nnns enne 19 List 47 AC Line Cord Kit 120VAC 0 0 ccccccccscecseceseeecsseeecsaesecseecseeescaaeeeeeecaeeecaaeescaseceeeeecsueeessaeessaeeesaees 19 List 48 AC Line Cord Kit 240VAQ oo cccccccscecssecesseecsseeecssesesseeceseeescaaeeeeeeesaeeecaaeeseaseseseeecsaeesesaeees
45. 5 front projection Includes two 2 50VA ringers with automatic transfer capability N 1 redundancy Provides 35 DC distribution fuse positions configured in five groups of seven feeding five channel banks Includes 35 dummy fuses Connectorized cables are available for SLC 96 or SLC Series 5 applications Required DC distribution fuses are included with each cable assembly ordered Order Wire Option provides a connection interface for an analog communication link over a metallic pair with surge protection See Ring amp Distribution Module Installation and User Manuals IM6C57E and UM6C57E for complete specifications Restrictions Use with List 11 12 18 or 14 only Ordering Notes 1 For a Ring amp Distribution Module equipped with two 2 50VA ringers only order AP6C57EA A7000626 2 For a Ring amp Distribution Module equipped with two 2 50VA ringers and the Order Wire option order AP6C57EB A7000796 Page 37 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 3 Order dis
46. 589200300 Model XP4890 List m Mounting No Part Number Description Positions 1U 1 3 4 81 58920030081 Cable RJ 45 MCA Control Bus 90 58920030090 Battery Temperature Probe Analog 91 58920030091 Battery Temperature Probe Digital 25 ft cord 92 58920030092 Temperature Probe Concentrator Module TXM 93 58920030093 Battery Temperature Probe digital 2 1 2 ft cord 94 58920030094 Cable interface to MCA 10 ft long 95 58920030095 Cable interface TXM to MCA 15 ft long See also the following located in this document System Overview Table of Contents e List of Parts Accessory Information e Specifications e Physical Size Information e Related Documentation Page 8 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 List Descriptions List 1 23 Power and Distribution Shelf List of Part with Load Shunt LISt Of Farts Features Provides common equipment for one 1 Integrated Power amp Distribution Shelf rated for up to 98
47. C 40 F to 4 F B Specification Compliant Full Output 20 C to 65 C 4 F to 149 F C Reduced Load 65 C to 80C 149 F to 176 F Page 71 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 4 3 2 Storage Temperature Range 40 C to 85 C 40 F to 185 F Home 4 3 8 Humidity Capable of operating in an ambient relative humidity range of 0 to 95 non condensing 434 Altitude The maximum operating ambient temperature should be derated by 10 C at an elevation of 10 000 feet above sea level For elevations between 3 000 feet and 10 000 feet derate the maximum operating ambient temperature linearly 4 3 5 Heat Dissipation BTUs Typical Percentage Mode of Full Total Load Active Standby 0 15 15 30 50 25 15 43 100 41 15 56 4 4 Standard Features 4 4 1 Input Protection A Fusing An internal non replaceable 5 ampere fuse is provided in the negative input lead of each Ringing Generator B Low Voltage Inhibit If input voltage decreases below approximate
48. C input or 750W 120VAC input per PCU Within this ambient temperature range the PCUs will operate as a constant voltage source or a constant power source depending upon load demands Transition between source types is completely automatic e Constant Voltage For any initial output voltage setting from 47 to 58 volts output voltage remains constant regardless of load This is the normal operating condition in which loads are being supplied and batteries are float charged PCUs will operate as a constant voltage source unless load increases to the point where the product of load current and output voltage is a non adjustable value of 1500W 208 240VAC input or 750W 120VAC input e Constant Power As load increases above approximately 1500W 208 240VAC input or 750W 120VAC input output current continues to increase but output voltage decreases as required to maintain constant output power Maximum current available per PCU is approximately 32 6 amps 208 240VAC input or 16 3 amps 120VAC input at 46 volts Load demands above this point result in output voltage dropping rapidly to maintain current and power within their limits Current Limit Mode With the system set to the Current Limit mode within the normal operating ambient temperature range the maximum user adjustable output current available is 27 5 amps 208 240VAC input or 13 75 amps 120VAC input per PCU Within this ambient temperature range the PCUs will operate as a cons
49. ER PROBE HI 1 ttt C F or TXM PROBE T 1 IS OFF or 155 TXM PROBE T HI 1 ttt C F or DIST PROBE S T HI 1 IS OFF or DIST PROBE S T HI 1 ttt C F 158 SHEET 1 The user navigates the MCA Display using the Keypad on the MCA Control Panel These pages indicate the actual text shown on Lines 1 and 2 of the MCA Display Line 2 also displays applicable message symbols See page 1 for explanation of symbols CONTROLLER PROBE HI 2 IS OFF or CONTROLLER PROBE HI 2 ttt C F or TXM PROBE T HI 2 IS OFF or TXM PROBE T HI 2 ttt C F or DIST PROBE S T HI 2 IS OFF or DIST PROBE S T HI 1 ttt C F or CONTROLLER PROBE LO 1 IS OFF or CONTROLLER PROBE LO i ttt C F or TXM PROBE T LO 1 IS OFF or TXM PROBE T LO 1 ttt C F or DIST PROBE S T LO 1 IS OFF or DIST PROBE S T LO 1 ttt C F CONTROLLER PROBE LO 1 IS OFF or CONTROLLER PROBE LO 1 ttt C F or PROBE T LO 1 IS OFF or PROBE T LO 1 ttt C F or DIST PROBE S T LO 1 IS OFF or DIST PROBE 51 71 LO 1 ttt C F or 159 164 169 172 MIDPOINT D RS Hi A1 ALARM IS OFF or MIDPOINT D RS H A1 vv vvV MIDPOINT D RS H A2 ALARM IS OFF or MIDPOINT D RS H A2 vv vvV CONTROLLER PROBE COMPENSATION or TXM PROBE T COMPENSATION or DIST PROBE S T COMPENSATION Page 62 of 86 178 179
50. Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 Issue AH June 6 2007 System Application Guide Spec No 589200300 Model XP4890 From Sheet 4 100 Sheet 4 D 139 INVENTORY MENU 1PCUIS REPORTING or PCUs ARE REPORTING or NO PCUs ARE REPORTING 1 PCU POSITION IS EMPTY or PCU POSITIONS ARE EMPTY or NO PCU POSITIONS ARE EMPTY 1 DIST PANEL IS REPORTING or DIST PANELS ARE REPORTING or NO DIST PANELS ARE REPORTING 1 RELAY BOARD IS REPORTING or RELAY BOARDS ARE REPORTING or NO RELAY BOARDS ARE REPORTING 1 RINGER IS REPORTING or RINGERS ARE REPORTING or NO RINGERS ARE REPORTING CONTROLLER ASSEMBLY THHHHHHEHHHHE SENSE VOLTAGE IS REMOTE INPUT or SENSE VOLTAGE IS INTERNAL 1 TEMP PROBE IS REPORTING or TEMP PROBES ARE REPORTING or NO TEMP PROBES ARE REPORTING 1 MIDPOINT IS REPORTING or MIDPOINTS ARE REPORTING or NO MIDPOINTS ARE REPORTING 141 UPDATE THE INVENTORY 1 GO TO FUNCTION MENU 2 GO BACK TO MENU TREE BEGINNING HEET 5 PCU INVENTORY MENU PCU S P IS RATED 101 aaaaaA 1 GO TO INVENTORY MENU
51. G589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Ordering Notes Home Notes 1 Order as a replacement part only Two Ringing Generators are included with each List 72 ordered List 80 Local Computer Access Cable Features Category 5 Crossover cable terminated at each end with an RJ 45 plug Required for local PC access to the MCA s Web interface Plugs into MCA s Ethernet connector on the Power Shelf Cable identification color is yellow Ordering Notes 1 Order the required length from the following table Length Part Number Length Part Number 36 inches 514642 25 feet 514645 4 feet 514643 50 feet 514646 6 feet 514644 100 feet 514647 15 feet 524726 List 81 RJ 45 MCA Control Bus Cable Features Category 5 Straight Through cable terminated at each end with an RJ 45 plug Required for MCA control bus interconnections Cable identification color is blue Restrictions Maximum combined MCA control bus cable length must not exceed 125 feet Ordering Notes 1 Order the required length from the following table Length Part Number Length Part Number 5 inches 524409 2 feet 524410 6 inches 509070 3 feet 514639 10 inches 528520 4 feet 509900 15 inches 509071 25 feet 514640 List 90 Battery Temperature Probe Analog Output Features List of Parts Senses battery internal temperature via mo
52. Generator will shut down and lock out if output voltage exceeds approximately 105 VAC RMS non adjustable Manual restart is required Can be restarted locally or via Web Interface Page 72 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 4 4 3 4 4 4 4 4 5 Over temperature Protection If internal Ringing Generator component temperatures increase above a preset value the Ringing Generator will inhibit When the temperature decreases to a safe level the Ring Generator will automatically resume operation Load Transfer Function A Automatic If the output voltage of the active Ringing Generator decreases below approximately 65 VAC RMS non adjustable for any reason except an overload condition the load will immediately transfer to the standby Ringing Generator B Manual The load can be transferred from one Ringing Generator to the other by means of local controls or from a remote location via the system MCA Web Interface Indicators A STATUS indicator is provided on each of the two Ringing Generators in the Ring
53. INVENTORY DETAIL MENU PANEL S LD BATT P IS INSTALLED PANEL S HAS A LD BATT LVD or PANEL S LD BATT LVD NOT INSTALLED PANEL S ASSEMBLY THHHHHHHEHHHE PANEL S SERIAL THHHHHHHEHHHE PANEL S BOOTCODE THHHHHHHHHHHE PANEL S SOFTWARE THHHHHHHEHHHE GO TO DISTRIBUTION INVENTORY GO BACK TO MENU TREE BEGINNING RELAY INVENTORY DETAIL MENU RELAY S R IS AN ALARM RELAY or RELAY S R IS A LOAD SHED or SET RELAY S R TO ALARM RELAY or SET RELAY S R TO LOAD SHED BOARD S ASSEMBLY THHHHHHHEHHHE BOARD S SERIAL THHHHHHHEHHHE BOARD S BOOTCODE THHHHHHHHHHHE BOARD S SOFTWARE THHHHHHHEHHHE GO TO RELAY BOARD INVENTORY GO BACK TO MENU TREE BEGINNING RINGER INVENTORY DETAIL MENU RINGER S P L R ASSEMBLY THHHHHHHEHHHE RINGER S P L R SERIAL THHHHHHHHHHHE RINGER S P L R BOOTCODE THHHHEHHHHHHE RINGER S P L R SOFTWARE THHHHHHHEHHHE GO TO RINGER INVENTORY GO BACK TO MENU TREE BEGINNING This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007
54. LIMIT vv vv V NOW AT vv vv V ALARM LIMIT vv vv V NOW AT vv vv V ALARM LIMIT vv vv V NOW AT vv vv V 1 PCU HAS FAILED or PCUs HAVE FAILED or NO PCUs ARE IN INVENTORY 1 DIST PANEL HAS FAILED or DIST PANELS HAVE FAILED or NO DIST PANELS ARE IN INVENTORY 1 LVD IS OPEN or LVDs ARE OPEN LVDs ARE INHIBITED 1 RELAY BOARD HAS FAILED or RELAY BOARDS HAVE FAILED or CONTROLLER RELAYS INOPERATIVE 1 RINGER HAS FAILED or RINGERS HAVE FAILED or NO RINGERS ARE IN INVENTORY CONTROLLER POINTER REQUEST CONTROLLER TOO MANY NODES CONTROLLER NODE IS UNIDENTIFIED CONTROLLER clock FAILURE CONTROLLER MEMORY FAILURE THE CONTROLLER IS INITIALIZING NO REMOTE SENSE INPUT or NO INTERNAL SENSE INPUT 1 TEMPERATURE ALARM or TEMPERATURE ALARMS 1 MIDPOINT ALARM or MIDPOINT ALARMS NORMAL DISPLAY MENU PCU ALARM MENU PCU S P FAILURE GO TO MAIN ALARM MENU GO BACK TO MENU TREE BEGINNING DISTRIBUTION ALARM MENU DIST PANEL Si FAILURE GO TO MAIN ALARM MENU 45 GO BACK TO MENU TREE BEGINNING LVD ALARM MENU PANEL S LD BATT LVD IS OPEN or LOAD SHED S Ri LVD IS OPEN or RECONNECT LOAD SHED S R LVD or RECONNECT ALL LVDs GO TO MAIN ALARM MENU 2 GO BACK TO MENU TREE BEGINNING E RELAY ALARM MENU RELAY BOARD S P 47 FAILURE 4 GO TO MAIN ALARM MENU 2 GO BACK TO MENU TREE BEGIN
55. NING RINGER ALARM MENU RINGER S P L R FAILURE GO TO MAIN ALARM MENU GO BACK TO MENU TREE BEGINNING FUSE ALARM MENU PANEL S LOAD BATT IS OPEN GO TO MAIN ALARM MENU 2 GO BACK TO MENU TREE BEGINNING 1 AC ALARM MENU a PCU 5 AC OFF OR NO AC DATA PCU 5 AC LINE TOO LOW PCU 5 AC LINE TO HIGH GO TO MAIN ALARM MENU GO BACK TO MENU TREE BEGINNING RINGER ALARM DETAIL MENU RINGER S P L R RING CIRCUIT RINGER S P L R CURRENT LIMIT RINGER S P L R PAIRED UNIT MISSING RINGER S P L R PROCESSOR RINGER S P L R IS DUPLICATED RINGER S P L R NO RESPONSE GO TO MAIN ALARM MENU GO BACK TO MENU TREE BEGINNING N MIDPOINT ALARM MENU From Sheet 3 ALARM LIMIT aaaaaA 7 NOW AT aaaaaA ALARM LIMIT aaaaaA 7 NOW AT ALARM LIMIT aaaaaA NOW AT aaaaaA ALARM LIMIT hh mm NOW AT hh mm ALARM LIMIT 81 NOW AT 1 To Sheet 4 MIDPOINT D R S H 70 1 ALARM ALARM LIMIT vv vv V 6 NOW AT vv vv MIDPOINT D R S H MIDPOINT D R 5 72 LO s ALARM MIDPOINT D R S Hi 73 LO 2 ALARM MIDPOINT D R S H NO SIGNAL GO TO MAIN ALARM MENU 2 GO BACK TO MENU TREE BEGINNING 74 Page 63 of 86 This document is the property of Emerson Network Power Energy Systems North America In
56. North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 2 3 11 Output Current Walk In Output current gradually increases after the system is switched on or AC service is initially supplied or restored as indicated below Minimum Elapsed Load Current 96 Time seconds 20 50 2 5 75 5 0 90 8 0 2 3 12 Cooling Forced Convection Cooling A three speed fan control circuit is provided When the feature is enabled fan operation is determined by ambient temperature and load current as shown in the following table Values shown are typical Ambient Vin z Vin z C Operation 120VAC 240VAC Always high speed zn rat 35 Go to medium speed if now low speed amp currrent gt 8 6 gt 16 5 32 Go to medium speed if now high speed Go to medium speed if current gt 8 6 gt 16 5A Go to low speed if current 8 0A lt 15 3A 7 Go to medium speed if now low or high speed amp currrent gt 8 6 gt 16 5A 10 Always medium speed 17 Hold present speed 20 Always high speed The fan control feature be enabled or disabled by a user via the MCA When disabled the fans operate at high speed at all times The
57. Series 5 order one 1 AP6C57EA EB Ring amp Distribution Module See Accessory Information List 13 23 Front Access Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Load Disconnect List of Parts Features Provides common equipment for one 1 Integrated Power and Distribution Shelf rated for up to 98A 4500W of power conversion and 100A of distribution at ambient temperatures of 50C or less and 90A at ambient temperatures above 50C All installer s connections are front access Provides 3 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers or fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other circuit breaker or fuse Caution The maximum size circuit breaker or fuse used in ambient temperatures above 50 C ambient SHALL BE 50 amperes A circuit breaker or fuse located in the mounting position adjacent to a 40 ampere or 50 ampere circuit breaker or fuse SHALL BE a maximum of 30 amperes Where two 40 ampere or 50 ampere circuit breakers or fuses are used an empty mounting space SHALL BE provided between them Provides 10 mounting posi
58. Voltage Protection 1 2 120V Operation If AC input voltage decreases below approximately 90 volts non adjustable each PCU s power conversion circuitry inhibits disabling system output When AC input voltage increases to approximately 90 volts non adjustable the PCU automatically restarts 208 240V Operation If AC input voltage decreases to within the range of approximately 90 175 volts non adjustable the PCUs continue to operate but at a reduced maximum output or approximately 750 watts When AC input voltage increases to approximately 176 volts non adjustable the PCU automatically switches to full output power If AC input voltage decreases below approximately 90 volts non adjustable the PCU s power conversion circuitry inhibits disabling system output When AC input voltage increases to within the range of approximately 90 176 volts non adjustable the system automatically restarts and operates in the reduced power mode B High AC Input Voltage Inhibit If AC input voltage increases to a preset non adjustable value the PCU s power conversion circuitry inhibits disabling system output When AC input voltage decreases to another preset non adjustable value the system automatically restarts Designed to inhibit at approximately 285 volts AC and to restart at approximately 264 volts AC Output Protection A Power Limiting The system can be set for Power Limiting or Current Limiting Factory def
59. Wire Size Selection List 11 12 13 14 120 240 VAC Input Two AC Input Circuits Page 25 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 List 11 12 13 14 208 VAC Input Two AC Input Circuits Recm Line Terminals Ground Ambient Branch R R Operating Circuit ecm ecm Temperature Protection 90 C 90 C m Amperes Wire Size Wire Size 0 4 Table 1D Recommended AC Input Branch Circuit Protection and Wire Size Selection List 11 12 13 14 208 VAC Input Two AC Input Circuits Notes for Tables 1A 1B 1C and 1D 1 Wire sizes based on recommendations of the American National Standards Institute ANSI approved National Fire Protection Association s NFPA National Electrical Code NEC Table 310 16 for copper wire at 90 C conductor temperature operating in ambients of 30 C 40 C 50 C and 65 C was used For other operating ambient temperatures refer to the NEC For operation in countries where the NEC is not recognized follow applicable codes The AC input branch circuit protective device shou
60. aeeesaees 19 List 50 Blank MOGUIGs RM 20 List 55 Model LXP1500 Power Conversion Unit 20 List 72 Model LXRO50 Redundant Ringing Generator 20 List 73 Replacement Ringing Generator nennen nentes nennen nes 20 List 80 Local Computer Access Cable enne nnne nennen nnns nennen 21 List 81 RJ 45 MCA Control Bus Cable ssssessssssessssesses eene enne nennen sentier rennen nnns 21 List 90 Battery Temperature Probe Analog Output 21 List 91 Battery Temperature Probe Digital Output ennemis 22 List 92 Temperature Concentrator Module 22 List 93 Battery Temperature Probe Digital Output ener nnne enne 23 List 94 TXM MCA Interface Cable enne 23 List 95 TXM MCA Interface Cable snnt trien rens nennen 23 ACCESSORY INFORMATION m en 24 Recommended Wire Sizes and Branch Circuit Protection 24 AC Input Wire Sizes Branch Circuit Protection esses eene ennemis 24 Distribution Load Wire Sizes and Lugs Bullet Nose Breakers and TPS TLS Fuseholde
61. an AC line cord is required order List 40 120VAC or List 41 208 240VAC If battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multiple probes order One 1 List 92 TXM and List 91 probes as required For bullet nose distribution positions order circuit breakers as required per Table 5 For bullet nose distribution positions order fuses as required per Table 6 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug two hole 1 4 bolt clearance holes on 5 8 centers as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse distribution positions order fuses as required per Table 7 11 Order Battery lugs as required per Battery Wire Sizes and Lugs List 1 2 3 and 4 Power and Distribution Shelves in the ACCESSORY INFORMATION section Page 9 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 List 2
62. and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 External Alarm Reference and Control Wire Sizes Features External Alarm Reference and Control connections are made to TB1 on the MCA 28 to 16 22 AWG for Loop Lengths Up to 200 ft Screw Clamp 18 20 AWG for Loop Lengths Over 200 ft Table 4 Recommended Alarm Reference and Control Wire Size TB1 and TB2 on MCA Page 31 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Distribution Devices Bullet Nose Type Circuit Breakers Each circuit breaker plugs into a single mounting position Ordering Notes 1 Order circuit breakers per Table 5 Note Load should not exceed 80 of device rating Caution A circuit breaker with a rating greater tha
63. attery Low Temp 1 Alarm C 100 50 50 Battery Low Temp 2 Alarm C 100 50 50 Battery Halfstring A1 Setpoint Volts 5 000 0 5 000 Battery Halfstring A2 Setpoint Volts 5 000 0 5 000 Halfstring Alarm Delay Setpoint Seconds 240 0 120 LVD Disconnect Volts 50 00 37 00 42 00 LVD Reconnect Volts 56 00 44 00 49 00 Table 5 MCA Battery Related Settings Remote On Off TR The operation of any or all PCUs can be inhibited TR via the MCA s Control Panel or Web Interface A PCU fail alarm is NOT issued Local Controls See User Manual for complete descriptions Location Name Description Type MCA 4 Function Select Up Increase Function Set Yes Pushbutton Switch Control Function Select Down Decrease Function Set No Pushbutton Switch Panel 4 Function Set Enter Pushbutton Switch Page 60 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide Spec No 589200300 Model XP4890 SAG589200300 Issue AH June 6 2007 3 1 7 Local Status and Alarm Indicators See User Manual for complete descriptions Location NAME Descripti
64. ault is for Power Limiting In this mode the maximum power delivered by each PCU is limited to 1500 watts 208 240V operation or 750 watts 120V operation B Current Limiting When the system is set for Current Limiting the maximum current delivered by the system can be programmed from 10 to 110 of total system capacity The MCA automatically adjusts the current limit circuit on each PCU so that this value is not exceeded If a PCU fails the MCA automatically resets each remaining PCU s current limit point to maintain this value The MCA also insures that the current limit circuit on any Page 54 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 PCU is not set above 110 of its capacity The default current limit setting in the Home Current Limit mode is the sum of each installed PCU s output rating One adjustment changes the setting of all PCUs C Output Fusing Output fusing is provided in each PCU If a fuse opens local and remote PCU Fail Alarms activate This fusing is not customer replaceable D Thermal Pow
65. bolt clearance hole 5 8 centers Refer to drawing 031110100 for lug crimping information Page 29 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Battery Wire Sizes and Connectors List 11 12 13 and 14 Power and Distribution Shelves Features Battery connections are made to locking type plugs Connections are provided for three 3 battery strings These connections are accessed through the front of the cabinet Restrictions Maximum wire size is 6 AWG Mating plugs are not provided with the shelf and must be ordered separately Ordering Notes 1 Battery wire size varies depending on load therefore no specific information is provided for selecting a wire size Refer to Table 3B for recommended wire sizes and connectors at rated maximum total distribution load 100A at or below 50 C ambient 90A above 50 C ambient Current is shown evenly distributed between two battery strings N 1 redundancy Current per ambient Loop Loop Recm Housing with 2 Amp pou Operating Length
66. by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited
67. c and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited ALARM LIMIT V 71 His ALARM 6 NOW AT vv vv V ALARM LIMIT vv vv V 6 NOW AT vv vv V ALARM LIMIT vv vv V 6 NOW AT V SAG589200300 Issue AH June 6 2007 System Application Guide Spec No 589200300 Model XP4890 From Sheet 2 To Sheet 2 From Sheet 2 To Sheet 2 From Sheet 2 To Sheet 2 To Sheet 2 SHEET 3 PCU ALARM DETAIL MENU DISTRIBUTION ALARM DETAIL MENU PANEL S LD BATT P NOT FOUND 36 37 RELAY ALARM DETAIL MENU RELAY 54 88 IS STUCK RELAY BOARD S LVD FAILURE RELAY BOARD S IS DUPLICATED RELAY BOARD S NO RESPONSE 2 GO BACK TO MENU TREE BEGINNING TEMPERATURE ALARM MENU TEMPERATURE PROBE PANEL S LD BATT P OVER CURRENT PANEL S LVD FAILURE PANEL S OPTION CHANGE PANEL S PROCESSOR PANEL S IS DUPLICATED PANEL S NO RESPONSE GO TO DISTRIBUTION ALARM MENU GO BACK TO MENU TREE BEGINNING 38 39 40 41 2 ALARM LIMIT ttt C F 8 NOW AT ttt C F TEMPERATURE PROBE LO 1 ALARM TEMPERATURE PROBE LO 2 ALARM TEMPERATURE PROBE
68. confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 A System output is initially adjusted to 54 48 volts DC as measured at the shelf output terminals at 50 of full load and nominal input Percent of Full Load refers to percent of 25 Amperes per PCU with nominal 208 240V input or percent of 12 5 Amperes per PCU with nominal 120V input 2 2 5 Typical Input Data 60 Hz input 25 C ambient Note At 120V nominal input PCUs operate in the Reduced Power Mode In the Reduced Power Mode PCUs provide 1 2 the output current and power available in Full Power Mode 60 Hz Input 25 C Ambient Number Nominal Percent Heat Input Current Input Input Power Efficiency n 7 of PCUs Input of Full Dissipation Installed Voltage Load Amperes Factor a BTU Hr o os e s oa 17 25 204 296 230 741 205 _ 346 829 20 29 651 787 0996 869 349 704 s 0997 975 10 710 8 0997 868 382 18 712 850 o997 867 25 50 ass oes 306 o o ee 424 0 950 787 0973 25 50 wo
69. converter failure condition occurs again within 5 minutes the PCU again shuts down and again restarts in approximately 30 seconds If a failure condition occurs a third time within 5 minutes the PCU shuts down and locks out Manual restart is then required If the PCU does not experience a DC DC converter failure condition within the 5 minute time period the restart circuit is reset 2 3 8 Power Factor Corrector Converter Failure If a PCU s power factor corrector converter fails the PCU shuts down After approximately 30 seconds the PCU automatically restarts 239 Paralleling This system may be connected in parallel with any rectifier of the same polarity and adjusted to the same output voltage 2 3 10 Load Sharing The MCA load sharing feature automatically balances the load to within 1 of the PCUs rated output currents If the MCA s load sharing feature is disabled for any reason pre programmed slope control in each PCU balances the load to within 10 of their rated output currents The MCA will balance a system of up to 17 PCUs within 5 minutes The MCA s load sharing feature is disabled whenever the system is in current limit the system is delivering more than 97 capacity or the system is delivering less than 396 capacity Page 57 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems
70. cuit Temperature Protection Capacity Type Recm Recm 90 C Recm 90 C Amperes Torque Wire Size Wire Size 20 to 6 AWG 10 AWG 50 C 30 j Table 1A Recommended AC Input Branch Circuit Protection and Wire Size Selection List 1 2 3 4 208 VAC One AC Input Circuit Page 24 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 List 1 2 3 4 208 VAC Input One AC Input Circuit Recm Line Terminals Ground Ambient Branch Operating Circuit Temperature Protection Capacity Type Pecm Recm 90 C Recm 90 C 1 Amperes Torque Wire Size Wire Size 2 8 AWG crew Clamp 10 AWG 6 AWG Table 1B Recommended AC Input Branch Circuit Protection and Wire Size Selection List 1 2 3 4 208 VAC One AC Input Circuit List 11 12 13 14 120 240 VAC Input Two AC Input Circuits Recm Line Terminals Ground Ambient Branch Operating Circuit Reem Temperature Protection 90 C 90 1 Amperes Wire Size Wire Size Table 1C Recommended AC Input Branch Circuit Protection and
71. d order one 1 List 47 120VAC or 48 240VAC per shelf as required for voltage and cord length Note List 47 120VAC line cords are restricted to powering one 1 PCU each If battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multiple probes order One 1 List 92 TXM and List 91 probes as required For bullet nose distribution positions order circuit breakers as required per Table 5 For bullet nose distribution positions order fuses as required per Table 6 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug one hole 1 4 bolt clearance as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse distribution positions order fuses as required per Table 7 11 Order Battery connectors as required per Battery Wire Sizes and Connectors List 11 12 13 and 14 Power and Distribution Shelves in the ACCESSORY INFORMATION section 12 For ringing and DC distribution in imbedded subscriber loop carrier systems such as SLC 96 or SLC Series 5 order 1 AP6C57EA EB Ring amp Distribution Module See Accessory Information List 14 23 Front Access Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Battery Disconnect List of Parts Features Provides common equipment for on
72. de SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Overall Dimensions Part No 528927 Load Shed Card 2 0 781 Lm m Top View 4 3 000 gt 0 250 DIA 4 2 187 gt 5 PLACES A A R0 125 A4 R 0 250 J3 CANINTERFACE J2 2 PLACES DONN Ur 1 000 M i NO 1 000 eH agp kac M NC SN m C NC 1 Cp o NC 1 000 i 7 250 NC N LOAD SHED CARD 1 000 STATUS PIN 12 7 625 NO 1 ge 1 000 NC I NO fe 1 000 d I BATTERY MDPOINT 0 MONITOR 0 625 1234 1 v pe v 0 375 SESS v Left Side View Front View Right Side View NOTES pe 1 All Dimensions are in Inches Unless Otherwise Specified 2 Finish Bright Zinc Lorain Spec M500 53 2 3 Weight Net 12 7 oz Bottom View Shipping 24 oz Page 83 of 86 This document is the property of Emerson N
73. ded Hole 1 Place per Distribution Position View with Door Open Factory supplies lug mounting hardware Load Return Connections Battery Ground Busbar GMT Alarm Type Connectors Distribution Fuse Load and Load Return Connections TB1 on back of door 69099999999 je 9 1 1 4 20 x 1 2 Threaded Stud 1 Place per Distribution Position Factory supplies lug mounting hardware Note All dimensions are in inches Page 80 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Overall Dimensions List 90 91 93 Battery Temperature Probes PROBE ATTACH TO NEGATIVE BATTERY TERMINAL CLEARANCE FOR 5 16 HARDWARE L 3 amp 180 3 00 LIST 90 ANALOG PROBE 0 25 DIA e N le 3 00 0 75 2 25 E L
74. default state is disabled Should a PCU fan fail the STATUS indicator will go red and the MCA will generate a fan fail alarm Note When the fan speed control feature is enabled the PCUS individually use their internal temperatures and output currents to control fan speed It is therefore possible that in a system with many PCUS and under certain conditions fans in the various PCUS will operate at different speeds 2 3 13 Local Controls None 2 3 14 Local Status and Alarm Indicators Location Name Type LED Green AC OK Operation Normal Yellow blinking Being ID d by MCA or communication with MCA lost Red PCU Fail PCU STATUS Page 58 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 3 MCA 3 4 Standard Features 3 1 1 MCA Interface A Local Via the MCA s Control Panel B Remote Via the MCA s Web Interface See Paragraph 3 2 3 1 2 MCA Local Display Provides digital metering of system load voltage and current individual PCU current and individual load shunts Also d
75. e 1 Integrated Power and Distribution Shelf rated for up to 98A 4500W of power conversion and 100A of distribution at ambient temperatures of 50C or less and 90A at ambient temperatures above 50C All installer s connections are front access Provides 3 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers or fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other circuit breaker or fuse Caution The maximum size circuit breaker or fuse used in ambient temperatures above 50 ambient SHALL BE 50 amperes A circuit breaker or fuse located in the mounting position adjacent to a 40 ampere or 50 ampere circuit breaker or fuse SHALL BE a maximum of 30 amperes Where two 40 ampere or 50 ampere circuit breakers or fuses are used an empty mounting space SHALL BE provided between them Provides 10 mounting positions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current 1 battery shunt and Low Voltage Battery Disconnect Provides mounting positions for one 1 MCA and up to three 3 PCUs Page 16 of 86 This document is the proper
76. e alarms 25ft long cable Same as List 93 except for cable length See Physical Size Information for probe dimensions Restrictions For use in single probe applications only Cannot be used with a List 92 TXM For multiple probe applications with a TXM order List 90 probes Ordering Notes 1 Order one 1 List 91 or List 93 per system List 92 Temperature Concentrator Module TXM List of Parts Features Provides the system MCA with a means of monitoring up to eight 8 List 90 battery temperature probes Plugs into J3 on the MCA System MCA can be set to compensate on the hottest probe the average temperature of all connected probes or the lowest numbered probe connected Mounts externally Includes 25 ft cable for interface to MCA connector J3 See Physical Size Information for dimensions See Installation and User Instructions Section 5940 for complete specifications Restrictions Requires List 90 temperature probes Cannot be used with List 91 temperature probes Ordering Notes 1 Order one 1 List 92 per List 1 ordered 2 Order up to eight 8 List 90 analog probes as required Page 22 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written perm
77. ed with each List 1 Integrated Power Distribution Shelf ordered Ordering Notes 1 Forareplacement plug order P N 524651 RJ 45 MCA Control Bus Termination Plug Features Plug must be installed in unused RJ 45 MCA control bus port J3 One plug is furnished with each List 1 Integrated Power Distribution Shelf ordered Ordering Notes 1 Forareplacement plug order P N 524653 Page 35 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Bulk Output Cable for List 72 Ringing Generator Home Features 6 ft long cable connects to rear of List 72 Ringing Generator Module to provide ringing output connection Also provides DC power connection for a Part No 528608 Ringing Distribution Module Ordering Notes 1 For a replacement cable order Part No 529059 TXM Extension Cable Part No 514153 Features Can be used between a List 90 Battery Temperature Probe cable and the List 92 or to extend a Part No 521228 TXM to MCA interface cable 25 ft long Load Shed Card Part No 528927 Features
78. ent Cables wns ii c M 35 MCA Control Bus Termination 9 35 RJ 45 MCA Control Bus Termination Plug sse enne nnne nnns nnne inneren 35 Bulk Output Cable for List 72 Ringing 36 Extension Cable Part No 514153 36 Load Shed Card Part No 528927 36 Ringing Distribution Module Part No 5286068 ceres 36 AP6C57EA EB Ring amp Distribution Module 37 Field Replaceable 38 LIST OF PARTS obo cuu ac EN dd nube 39 5 41 1 System enne rece ee 41 1 1 Environmental Ratlngs care a an pie tt edet ptit Co ete dee Ce 41 1 2 Compliance Information ssssssssssssseeee ener entente nns senis sn nnne inneren 41 1 3 Local Controls and INGICALOIS ccccccccceecsesseseeecececeeseeseseceeececseseaaeseeeeseecseseeaaeseseeeesseeseaaeseceseeeseseaeeeeess 42 ei 42 231 Output Ratings
79. er Limiting Each PCU continuously monitors the ambient temperature surrounding the power conversion unit circuit If this temperature for any reason such as a high ambient office temperature increases above approximately 65 C 149 F the PCU will not shut down Rather the PCU will limit its maximum output power to maintain the temperature of the power conversion circuit within design parameters Full power capability is restored when the temperature decreases to below approximately 65 C 149 F Figure 2 illustrates typical operating parameters Warning The PCU is rated for continuous operation at full output power up to 65 C 149 F Operation between 65 C and 80 C 149 F and 176 F is considered abnormal and should be used on a temporary basis only i Temporary Operation at Abnormal Temperature Temporary operation refers to a period of not more than eight consecutive hours per day and a total of not more than 15 days in a year This refers to a total of 120 hours in any given year but no more than 15 occurrences in that one year period LXP1500 Thermal Power Limit Curve Typical 1500 LS 1250 m 208 240Vin 2 1000 LT 2 750 569 a 500 v 120Vin 250 07 66 20 40 45 50 55 60 65 70 75 80 C 4 104 113 122 131 140 149 158 167 176 F NORMAL i ABNORMAL CONTINUOUS TEMPORARY i OPERATION i OPERATION i AMBIENT TEMPERATURE Figure 2
80. er one 1 List 32 MCA Order PCUS per List 55 as required Order Ringing Generators per List 72 as required If AC line cords are required order one 1 List 47 120VAC or 48 240VAC per shelf as required for voltage and cord length Note List 47 120VAC line cords are restricted to powering one 1 PCU each If battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multiple probes order One 1 List 92 TXM and List 91 probes as required For bullet nose distribution positions order circuit breakers as required per Table 5 For bullet nose distribution positions order fuses as required per Table 6 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above Page 13 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 9 Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug one hole 1 4 bolt clearance as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse dis
81. ery component contained in each List Number Note See also Field Replaceable Components List Part Description Number Number ptio Assembly shelf 2U ISD Shunt DC 175A 25 mV Kit Mounting 2U ISD Busbar w o LVD 2U ISD Assembly cable distribution 2U ISD 528171 Assembly shelf 2U ISD 528229 Shunt DC 175A 25 mV 528242 Kit Mounting 2U ISD 528262 Busbar link 2U ISD 528277 Assembly cable distribution 2U ISD 528171 Assembly shelf 2U ISD 528229 Shunt DC 175A 25 mV 528242 Kit Mounting 2U ISD 528260 Busbar link 2U ISD 528277 Assembly cable distribution 2U ISD 128284 Contactor 1C SPST 150A 45V 528171 Assembly shelf 2U ISD 528229 Shunt DC 175A 25 mV 528242 Kit Mounting 2U ISD 528261 Busbar link 2U ISD 528277 Assembly cable distribution 2U ISD 128284 Contactor 1C SPST 150A 45V 536650 Assembly shelf 2U ISD 528229 Shunt DC 175A 25 mV 536647 Busbar load batt 534749 Busbar link 534621 Assembly cable distribution 2U ISD 536650 Assembly shelf 2U ISD 528229 Shunt DC 175A 25 mV 536647 Busbar load batt 534749 Busbar link Assembly cable distribution 2U ISD 536650 Assembly shelf 2U ISD 528229 Shunt DC 175A 25 mV 536637 Busbar com link 536638 Busbar LVLD link 534621 Assembly cable distribution 2U ISD 128824 Contactor 1C SPDT 150 Amp 48VDC 536650 Assembly shelf 2U ISD 528229 Shunt DC 175A 25 mV 534748 Busbar link 534749
82. estrictions None Ordering Notes 1 2 KR N 2 co Order one 1 List 32 MCA Order PCUS per List 55 as required Order Ringing Generators per List 72 as required If an AC line cord is required order List 40 120VAC or List 41 208 240VAC If battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multiple probes order One 1 List 92 TXM and List 91 probes as required For bullet nose distribution positions order circuit breakers as required per Table 5 For bullet nose distribution positions order fuses as required per Table 6 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug two hole 1 4 bolt clearance holes on 5 8 centers as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse distribution positions order fuses as required per Table 7 11 Order Battery lugs as required per Battery Wire Sizes and Lugs List 1 2 3 and 4 Power and Distribution Shelves in the ACCESSORY INFORMATION section Page 10 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use
83. etwork Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Overall Dimensions Part No 528608 Ringing Distribution Module R 0 125 R 0 250 2 PLACES 0 250 DIA POWER 2 PLACES RINGING DISTRIBUTION MODULE OUTPUT FUSES 2A MAX FUSE F2 F4 F5 F6 5 250 REPLACE WITH SAME TYPE AND RATING OF FUSE TB1 POSITIVE RINGING OUTPUTS LN 12345699 YA Y Left Side 0 375 Front View Right Side View View NOTES 1 All Dimensions are in Inches Unless Otherwise Specified 2 Finish Clear Zinc Lorain Spec M500 53 3 Weight Net 8 oz x Shipping 16 oz Bottom View Page 84 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying
84. f the air entering the PCUs does not exceed the Operating Ambient Temperature Range stated above In addition the distance from the rear of each Power Shelf to a wall or other solid structure must not be less than 6 inches This will assure proper airflow through the PCUs See also Paragraph 1 1 12 Mounting 1 1 7 Audible Noise The audible noise at any point one meter from any vertical surface of the Power Shelf with one PCU installed and fan operating does not exceed 55 dBA typical when ambient temperature is below 32 C 89 6 F and 65 dBA typical when ambient temperature is above 32 C 89 6 F A Sound Level Meter conforming to ANSI S1 4 was used 1 1 8 EMI RFI Suppression PCUs operating in a Power Shelf conform to the requirements of FCC rules Part 15 Subpart B Class B for Radiated and Conducted emissions limits 1 1 9 Surge Protection Compliance with EN61000 4 5 Installation Class 4 and capable of withstanding surges per ANSI IEEE C 62 41 1991 Category B across the input terminals Note This level of protection is a widely used standard for telecommunications power equipment As with all such equipment it is the end user s responsibility to provide an adequately sized Surge Suppression Device at the commercial power service entrance of the building that reduces all incoming surges to levels below the classes categories stated for the equipment 1 1 10 ESD Protection Complies with EN61000 4 2 Level 4 8kV contact 1 1 1
85. ficiency Heat of PCUs Input of Full Amperes VA Watts Factor Dissipation Installed Voltage Load BTU Hr 8 o om oss 25 e e oss 758 so 1022 i226 1218 oso 840 666 874 876 873 2583 872 Max 87 we 049 5 895 5045 89 4 o os s 25 s2 moo osas 975 3 2260 os72 770 _ 10 1889 as34 4 amp 9 o99 91 0 304 5033 4092 20 1720 93 25 58 50 120 o 9 03 856 296 4582 305 305 a 05 25 72 50 770 240 Page 47 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 B Maximum Input Current At 100 of full load with output adjusted to 58 volts DC as measured at the output bus 50 Hz Input 25 C Ambient Nominal Input Number of Input Current Input Voltage Voltage mr Installed mE E 208 240 Page 48 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains
86. g SAG589200300 System Application Guide EMERSON Spec No 589200300 Model XP4890 Network Power Issue AH June 6 2007 LXP INTRODUCTION Horis LXP is Emerson Network Power s next generation small power platform MODEL XP4890 OVERVIEW Model XP4890 is a 48VDC Integrated Power System that operates with LXP Power Conversion Units PCUs powered from 120 208 240 VAC and featuring constant power design This single shelf Power System provides up to 4500 watts of power conversion and distribution PCUs The heart of this system is the Model LXP1500 PCU The unit operates at 0 99 power factor and with less than 5 THD Designed for positive ground applications the PCU normal output voltage ranges from 47 to 58 volts with an equalize voltage adjustable down to 47 volts and a test voltage adjustable down to 45 volts Each PCU monitors the input voltage and automatically selects one of two operating modes Full output is available for nominal 208 240VAC operation A reduced power mode provides half power for nominal 120VAC input For 208 240V applications the reduced power mode means that the PCU does not inhibit at low line but reduces its output to half The system can be set by the user to operate the PCUs in either the Power Limit or Current Limit mode Power Limit Mode With the system set to the Power Limit mode within the normal operating ambient temperature range the maximum output power available is 1500W 208 240VA
87. g position in the Power Shelf Either ringing generator in the module can be selected to supply the load main generator with the other becoming the standby generator If a failure occurs in the main generator the ringing load will automatically transfer to the standby generator A failed ringing generator can be replaced without interrupting ringing power to the load Controlled and monitored by system s MCA MCA supports up to 4 List 72 Restrictions Provides bulk ringing output only Distribution must be external MCA interfaces with a maximum of 4 List 72s Outputs from multiple List 72s cannot be paralleled MCA version 4 0 or newer required for full compatibility Ordering Notes 1 Order one 1 List 72 for up to 50 VA of redundant bulk ringing power 2 For external ringing distribution order Part No 528608 Ringing Distribution Module List 73 Replacement Ringing Generator List of Parts Features Field replacement for one of the two Part No 487112100 Ringing Generators that are provided with List 72 Page 20 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SA
88. ietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Local and external fuse alarm circuits are provided Designed to mount on a wall or relay rack rail Includes six dummy fuses and six fuse safety covers Distribution fuses are not included and must be ordered separately See Physical Size Information for Ringing Distribution Module dimensions Ringing Input 67 5 to 105 VAC RMS 100 VA max 20 25 30 Hz Ringing Output Six outputs each fused at 2A max See Ringing Distribution Module Installation and Operating Instructions Section 5991 for complete specifications Restrictions Maximum recommended distribution fuse size is 2A Ordering Notes 1 Order ringing distribution fuses as required from Table 7 AP6C57EA EB Ring amp Distribution Module Features When used with List 11 12 13 or 14 this module is designed to supply a filtered and regulated 48 VDC source and a continuous 20 Hz ringing supply source to imbedded subscriber loop carrier telecommunication systems such as SLC 96 or SLC Series 5 requiring up to 45 A of load capacity Designed to mount in a 23 relay rack the module is one rack unit high with
89. ing Generator Module This three color LED illuminates as follows A Green Output available this generator selected to supply load B Amber Output available this generator in standby mode C Flashing Amber Operating in current limit or thermal current limit this generator selected to supply load D Red Failure condition this generator output not available Failure conditions include e Low output voltage due to generator failure e Output voltage exceeds approximately 105 VAC HVSD e Low input voltage Low Voltage Inhibit e Internal temperature exceeds a predetermined limit Over temperature Inhibit e Cooling fan failure or fan rotor blocked Page 73 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 PHYSICAL SIZE INFORMATION Home Overall Dimensions List 1 2 3 4 Power Shelves Battery Wiring Entrance Rear NOTES 1 All dimensions in inches 2 Weight In Pounds Net Shipping Shelf 19 Ib 12 oz 25 Ib 4 oz MCA 2 lb 14 oz 4 Ib 9 oz PCU 51
90. isplays system alarm messages and adjustment information as detailed in Paragraph 3 1 8 MCA Display 3 1 3 Meter Accuracy 0 01 V 0 005 C 3 1 4 Universal Adjustment Circuit Provides single point control of float equalize battery test thermal runaway management output voltages high voltage shutdown and current limit adjustments Note Should the MCA fail the PCUs remember the float and high voltage shutdown settings last delivered by the MCA The current limit control of each PCU goes to constant power mode Provides adjustments for all MCA alarm and control circuits Adjustment ranges and factory settings as follows All adjustments can be performed locally via the MCA Control Panel and most can be performed remotely via the MCA s Web Interface See Tables 4 and 5 for adjustment parameters Parameter Max Min Hira Float Mode Output Volts 58 00 47 00 54 48 High Voltage Shutdown Volts 59 50 48 00 58 50 Power Current Limit Full Load 128 10 Limit Mode High Voltage 1 Alarm Volts 59 00 48 00 55 50 High Voltage 2Alarm Volts 59 00 48 00 56 50 Low Voltage 1 Alarm Volts 56 00 40 00 51 00 Low Voltage 2Alarm Volts 56 00 40 00 47 00 System Total Current Alarm 30000 0 150 Loss of Redundancy Alarm 2 0 1 times the full output rating of 1 PCU PCU Sequencing Delay Seconds 20 0 0 Relay Test Interval Seconds 120 5 45 Number of Redundant PCUs 2
91. ission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 3 Fora shorter interface cable also order List 94 10 ft or 95 15 ft Home List 93 Battery Temperature Probe Digital Output List of Parts Features Mounts near the battery to sense battery ambient temperature Plugs into J3 on the MCA Provides MCA with data required for battery temperature related functions temperature compensated output voltage high and low battery temperature alarms 2 1 2 ft long cable Same as List 91 except for cable length See Physical Size Information for probe dimensions Restrictions For use in single probe applications only Cannot be used with a List 92 TXM For multiple probe applications with a TXM order List 90 probes Ordering Notes 1 Order one 1 List 93 or List 91 per system List 94 TXM MCA Interface Cable ECL C C List of Parts Features Cable interface connects between the output connector on the and MCA connector J3 10ft long Replaces the 25 ft interface cable provided with the List 92 TXM when a shorter cable is needed List 95 TXM MCA Interface Cable Features Cable interface connects between the output connector on the and MCA connector J3 158 long Replaces the 25 ft interface cable provided with the List 92
92. ist 1 2 3 4 Distribution WE B ooo il e 7 View with Door Open Tu eT l JF LAE Load Return Connections Ground Busbar GMT Alarm Type Distribution Fuse Load and Load Return Connections TB1 Load Connections 1 4 20 Threaded Hole 1 Place per Distribution Position Factory supplies lug mounting hardware 1 4 20 x 1 2 Threaded Stud 1 Place per Distribution Position Factory supplies lug mounting hardware Lug Alignment Pin 1 Place per Distribution Position Note All dimensions are in inches Page 76 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide Spec No 589200300 Model XP4890 Installers Connections Locations and Dimensions List 1 2 3 4 Battery SAG589200300 Issue AH June 6 2007 See Detail A
93. ist 95 Added Part No 110982 fuse to 5 17 06 J Kirkpatrick Field Replaceable Components 5 17 06 Clause AD LLP206694 Added List 72 and 73 Added Part No 528608 10 19 06 J Kirkpatrick and 529034 to Accessories Revised Menu 10 19 06 M Valerian Tree to MCA version 3 1 Added MCA version requirement to P N 528927 Load Shed Card description AE LLP207301 Added SNMP option Expanded List 32 MCA 1 28 07 J Kirkpatrick feature and ordering information Revised 1 29 07 J Jasko Menu Tree to MCA version 4 0 Updated contents of P N 534637 fan kit Corrected List 72 frequency tolerance AF LLP208124 Revised Menu Tree to MCA version 4 1 0 x 4 4 07 J Kirkpatrick 4 4 07 J Jasko AG LLP208425 Added Lists 11 12 13 14 47 48 5 9 07 J Kirkpatrick 5 9 07 J Jasko AH LLP208652 Added AP6C57EA EB Ring amp Distribution Module to Accessories NC 6 19 2007 6 19 2007 Emerson Network Power 1122 F Street Lorain Ohio 44052 2293 440 288 1122 In Canada Emerson Electric Canada Limited 122 Edward St St Thomas Ontario 122 519 637 4900 amp In Mexico Y Emerson Network Power de Mexico S A de C V EMERSON Apartado Postal 77001 Mexico 10 D F MX 11200 525 576 8277 Network Power Page 86 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned
94. itions provide 1 4 20 threaded holes for installation of customer furnished one hole lugs that have 1 4 in bolt clearance holes In List 1 2 3 and 4 the ground busbar provides 1 4 20 x 1 2 threaded studs for installation of customer furnished two hole lugs that have 1 4 in bolt clearance holes on 5 8 centers In List 11 12 13 and 14 the ground busbar provides 1 4 20 x 1 2 threaded studs for installation of customer furnished one hole lugs that have a 1 4 in bolt clearance holes For lug mounting hole size and spacing dimensions refer to Electrical Connection Locations and Dimensions in this document Maximum size of wire to be connected to a single fuseholder or circuit breaker position is 2 AWG For lug mounting hole size and spacing dimensions refer to the illustration provided the Physical Size Information section Restrictions All lugs for customer connections must be ordered separately Installer must supply lug mounting hardware Ordering Notes 1 The rating of the distribution device determines the wire size requirements For wire size and lug selection refer to Table 2 2 For other available lugs and hardware refer to drawings 031110100 through 031110300 Distribution Load Wire Sizes GMT Alarm Type Fuses Features Screw compression type terminals are provided for connection of Load and Load Return conductors to the GMT alarm type distribution fuse positions Terminals accept 14 AWG max Re
95. ld be of the time delay or high inrush type Equipment grounding conductors must be provided with the AC input conductors supplied to the shelf Frame ground terminals must be connected to earth ground not power system neutral A ring lug must be provided Equipment grounding conductor size based on recommendations of the NEC Table 250 122 for copper wire If aluminum or copper clad aluminum grounding conductor is used refer to Table 250 122 for increased conductor size For operation in countries where the NEC is not recognized follow applicable codes When List 11 12 13 or 14 is ordered with List 47 AC cords 120VAC only restricted to 1 PCU per cord recommended branch circuit protection is 15 amperes Page 26 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Distribution Load Wire Sizes and Lugs Bullet Nose Breakers and TPS TLS Fuseholders Features The installer connects lug terminated load conductors to the distribution device mounting positions and the ground busbar The distribution device mounting pos
96. le probes order One 1 List 92 TXM and List 91 probes as required 6 For bullet nose distribution positions order circuit breakers as required per Table 5 7 For bullet nose distribution positions order fuses as required per Table 6 8 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above 9 Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug one hole 1 4 bolt clearance as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse distribution positions order fuses as required per Table 7 11 Order Battery connectors as required per Battery Wire Sizes and Connectors List 11 12 13 and 14 Power and Distribution Shelves in the ACCESSORY INFORMATION section 12 For ringing and DC distribution in imbedded subscriber loop carrier systems such as SLC 96 or SLC Series 5 order one 1 AP6C57EA EB Ring amp Distribution Module See Accessory Information List 32 Model LXC300 Meter Control and Alarm Assembly MCA List of Parts Features Consists of one 1 Model LXC300 Meter Control and Alarm assembly MCA Refer to SPECIFICATIONS for a description of MCA functions Mounts in Main Power Shelf Controls and monitors the following LXP equipment Component Maximum Number PCU 17 in up to 3 shelves Distribution Cabinet DSM 4 List 72 Redundant Ringing Generator Module 4 2 generators ea Load Shed Ca
97. lug crimping information Use 1 hole lugs for Load connections on List 1 2 3 4 11 12 13 and 14 Use 1 hole lugs for Load Return connections on List 11 12 13 and 14 Use 2 hole lugs for Load Return connections on List 1 2 3 and 4 1 Page 28 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Battery Wire Sizes and Lugs List 1 2 3 and 4 Power and Distribution Shelves Home Features The installer connects lug terminated battery conductors to the terminals provided Captive nuts 1 4 20 on 5 8 centers are provided for installation of customer furnished two hole lugs These terminals are accessed through the cabinet top or rear panel For lug mounting hole size and spacing dimensions refer to the illustration provided in the Physical Size Information section Restrictions All lugs for customer connections must be ordered separately Customer must supply lug mounting hardware Ordering Notes 1 Battery wire size varies depending on load therefore no specific information is provided for wire size Refer
98. ly 38 volts non adjustable the Ringing Generator will inhibit Operation will automatically resume when input voltage increases to within normal input voltage range 4 4 2 Output Protection A Current Limiting Output current is limited to approximately 110 of rated full load non adjustable B Thermal Current Limiting Each Ringing Generator continuously monitors the ambient temperature surrounding the power conversion unit circuit If for any reason such as a high ambient office temperature this temperature increases above approximately 65 C 149 F the Ringing Generator will not shut down Rather the Ringing Generator will limit its maximum output current to maintain the temperature of the power conversion circuit within design parameters Full current capability is restored when the temperature decreases to below approximately 65 C 149 F Warning The Ringing Generators are rated for continuous operation at full output power up to 65 C 149 F Operation between 65 C 80 C 149 F and 176 F is considered abnormal and should be used on a temporary basis only Temporary Operation at Abnormal Temperature Temporary operation refers to a period of not more than eight consecutive hours per day and a total of not more than 15 days in a year This refers to a total of 120 hours in any given year but no more than 15 occurrences in that one year period C High Voltage Shutdown The Ringing
99. m List Structure When viewed electronically additional information is available for each option by clicking on the desired number in the column entitled List No List Options List Mounting No Part Number Description Positions 1U 1 3 4 Integrated Power amp Distribution Shelf 23 up to 98 Amps 1 epson 4500W of power conversion with Load Shunt zin Integrated Power amp Distribution Shelf 23 up to 98 Amps z 4500W of power conversion with Load amp Battery Shunts EM Integrated Power amp Distribution Shelf 23 up to 98 Amps 3 58920030003 4500W of power conversion with Load amp Battery Shunts amp 2U LVLD Integrated Power amp Distribution Shelf 23 up to 98 Amps 4 58920030004 4500W of power conversion with Load amp Battery Shunts amp 2U LVBD 23 Integrated Power amp Distribution Shelf All Front Access 11 58920030011 Connections up to 98 Amps 4500W of power conversion 2U equipped with Load Shunt 23 Integrated Power amp Distribution Shelf All Front Access 12 58920030012 Connections up to 98 Amps 4500W of power conversion 2U equipped with Load amp Battery Shunts 23 Integrated Power amp Distribution Shelf All Front Access 13 58920030013 Connections up to 98 Amps 4500W of power conversion 2U equipped with Load amp Battery Shunts amp LVLD 23 Integrated Power amp Distribution Shelf All Front Access 14 589
100. m Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 50 Hz Input 25 C Ambient Number Nominal Percent Input Current Input Input Power fficiency ICE of PCUs Input of Full Amperes VA Watts Factor Dissipation Installed Voltage Load BTU Hr 0 os m i0 090 25 384 0 983 50 6 m 75 4 8 0 99 100 13 05 1566 1561 0 997 83 6 872 0997 874 0997 sra 0 997 Max 0 997 0 87 0 87 0 85 1 89 4 90 5 304 30 29 6 295 245 0 95 3940 0 99 0 95 o os im 72 25 348 796 086 EEM oo 85 5 89 8 91 0 91 0 90 1 0 975 100 0 991 3317 3293 0 992 0 992 3347 3322 0 99 3325 0 992 25 50 120 14 o 9 097 0 983 MEM 099 3930 0 99 25 50 240 B o o Page 46 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 50 Hz Input 25 C Ambient Number Nominal Percent Input Current Input Input Power f
101. mation Base browser via the MCA Ethernet port Ordering Notes Order one 1 List 80 if local PC access to Web Interface is required 3 Order Battery Reserve Time Prediction Option if required 4 Order SNMP Option if required List 40 AC Line Cord Kit 120VAC Features Provides 1 14 5 ft long AC input cord equipped with a NEMA L5 30P 30A twist lock plug Cord is factory installed Restrictions For List 1 2 3 and 4 only Cannot be used with List 11 12 13 or 14 For 120 VAC only Not available with List 43 AC Input Vertical Feed Assembly Ordering Notes 1 For 120 VAC operation order one List 40 per Power Shelf List 41 AC Line Cord Kit 208 240VAC Features Provides 1 14 5 ft long AC input cord equipped with a NEMA L6 30P 30A twist lock plug Cord is factory installed Restrictions For List 1 2 3 and 4 only Cannot be used with List 11 12 13 or 14 For 208 240 VAC only Not available with List 43 AC Input Vertical Feed Assembly Ordering Notes 1 For 208 240 VAC operation order one 1 List 41 per Power Shelf Page 18 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibi
102. med to change state if a specific Alarm Definition alarms 3 2 Web Interface System Status bor Alarms Controter Bl Retay Alarms E Banor narmi Bl Temperature Alarms System Mode Float Bl Nams Bl LVO Alarms PCU Mode Constant Power Bl Batory Reserve Alma Bl Ringer Alarms System Measurements n Page 70 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 3 2 1 Description The Web Interface provides remote access to the system monitoring Home and control functions that are available locally at the MCA control panel See Chapter 5 Using the Web Interface in the System s User Manual for complete descriptions of all Web Interface functions 3 2 2 Connection Ethernet RJ 45 10BaseT jack This jack has a standard Ethernet pin configuration scheme twisted pair Use shielded Ethernet cable grounded at both ends The LXP s RJ 45 jack is connected to chassis ground The Ethernet port is suitable for connection to intra building or non exposed wiring or cabling only 3
103. n 75 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Caution List 1 2 3 4 only The maximum size circuit breaker used in ambient temperatures above 50 C ambient SHALL BE 40 amperes Caution List 11 12 13 14 only The maximum size circuit breaker or fuse used in ambient temperatures above 50 C ambient SHALL BE 50 amperes A circuit breaker or fuse located in the mounting position adjacent to a 40 or 50 ampere circuit breaker or fuse SHALL BE a maximum of 30 amperes Where two 40 or 50 ampere circuit breakers or fuses are used an empty mounting space SHALL BE provided between them 2 For lug and wire size selection refer to Table 4 BULLET NOSE TYPE CIRCUIT BREAKERS PART NUMBER PART NUMBER AMPERE RATING Electrical Mechanical Trip Electrical Trip Black Handle White Handle 1 101596 102272 3 101597 102273 5 101598 102274 10 101599 102275 15 101600 102276 20 101601 102277 25 101602 102278 30 101603 102279 35 101604 102280 40 101605 102281 45 121997 121998 50 101606 102282 60 101607 102283 70 101608 102284 75 101609 102285 80 121995 121996 100 101610 102286 Circuit Breaker Alarm Operation Provides an alarm during an electrical or manual trip condition Provides an alarm during an electrical trip condition only Unless otherwise specified circuit breakers shall be mounted from top to
104. ny copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 SPECIFICATIONS mm Note For all Part No 528927 Load Shed Card specifications refer to Section 5985 Section 5985 can be accessed via the CD Electronic Documentation Package furnished with your system 1 SYSTEM 1 1 Environmental Ratings 1 1 1 Operating Ambient Temperature Range A Operate 40 C to 20 C 40 F to 4 F B Specification Compliant Full Output 20 C to 65 C 4 F to 149 F C Reduced Load 65 C to 80 C 149 F to 176 F 1 1 2 Storage Ambient Temperature Range 40 C to 85 C 40 F to 185 F 1 1 3 Humidity This system is capable of operating in an ambient relative humidity range of 0 to 95 non condensing 1 1 4 Altitude The maximum operating ambient temperature should be derated by 10 C at an elevation of 10 000 feet above sea level For elevations between 3 000 feet and 10 000 feet derate the maximum operating ambient temperature linearly 1 1 5 Heat Dissipation See input data tables under Paragraph 2 2 Input Ratings 1 1 6 Ventilation Requirements The PCUs and optional Ringing Generators are fan cooled and utilize front to back forced ventilation Each Power Shelf must be mounted so ventilating openings are not blocked and temperature o
105. o hole 1 4 bolt clearance holes on 5 8 centers as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse distribution positions order fuses as required per Table 7 11 Order Battery lugs as required per Battery Wire Sizes and Lugs List 1 2 3 and 4 Power and Distribution Shelves in the ACCESSORY INFORMATION section Page 12 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 List 11 23 Front Access Power and Distribution Shelf List of Parts with Load Shunt Features Provides common equipment for one 1 Integrated Power and Distribution Shelf rated for up to 98A 4500W of power conversion and 100A of distribution at ambient temperatures of 50C or less and 90A at ambient temperatures above 50C All installers connections are front access Provides 3 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers o
106. oad to full load input voltage and input frequency at a constant ambient temperature regulation is 1 as controlled within the PCUs Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Page 43 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc If the MCA s regulation feature is disabled for any reason steady state SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 B Dynamic Response For any step load change within the range of 20 to 100 Home of rated output current per Telcordia GR 947 CORE the maximum voltage transient will not exceed 5 of the initial steady state voltage Recovery to within 0 7 of the initial steady state voltage does not exceed 30 milliseconds recovery to within 0 5 of the initial steady state voltage does not exceed five seconds and recovery to within 0 02 of the initial steady state voltage does not exceed 20 seconds 2 1 4 Filtering with or without battery Typical readings were taken at nominal input voltage nominal output voltage 5096 load and 25 C 77 F ambient A Voice Band Noise Complies with Telcordia GR 947 CORE 1 Typically 13 dBrn with C message weighting
107. of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 F High Voltage Shutdown Home 1 Internal If PCU output voltage exceeds an adjustable preset value and is delivering more than 10 of its rated current the PCU shuts down After approximately 3 seconds the PCU automatically restarts If PCU output voltage again exceeds the high voltage shutdown value within 5 minutes the PCU shuts down and locks out Manual restart is then required If the PCU does not experience a high voltage condition within the 5 minute time period the restart circuit is reset If two or more PCUs are installed in the Power Shelf or if the Power Shelf is paralleled with other Power Shelves only the PCU causing the high voltage condition shuts down The high voltage shutdown point can be checked and or adjusted without removing a PCU One adjustment changes the setting of all PCUs Adjustable from 48 00 to 59 50 volts DC Factory set at 57 50 volts unless otherwise specified 2 Remote See Paragraph 3 1 9 B 3 Backup If PCU output voltage exceeds a second non adjustable value the PCU shuts down and locks out regardless of load Manual restart is then required 237 DC DC Converter Failure If a PCU s DC DC converter fails the PCU shuts down After approximately 30 seconds the PCU automatically restarts If a DC DC
108. on Type MCA Control Panel Message Display Shows Active Alarms or SYSTEM OK Various Measurement Items and Values Various Inventory Items Various Adjustment Items and Values Various Operation Items Various Configuration Items and Settings See Paragraph 3 1 9 MCA Display MAJOR LED flashing red MINOR LED red AC LED green red EQ LED yellow BATTERY LED yellow red 3 1 8 Display Presented next are illustrations from the MCA Menu Tree Section 5956 Refer to the latest version of Section 5956 for the most recent MCA Menu Tree See Operation section of the System s User Manual for complete descriptions of menu items Page 61 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 Issue AH June 6 2007 System Application Guide Spec No 589200300 Model XP4890 INITIALIZATION MENU JEHHHHHHHHHRHHHHE PROCESSED or CONFIG FILE ERROR 3 PROCESSED or NO CONFIG FILE WAS PROCESSED 3A THHHHHHHHBHHE WAIT VIHHHHHHHHHHHE CHECK VALUES BEFORE STARTING 156 157 CONTROLLER PROBE HI 1 IS OFF or CONTROLL
109. ork Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide Spec No 589200300 Model XP4890 Home SAG589200300 Issue AH June 6 2007 Increasing _ h Voltage Determines Float Mode Output Voltage at 25 C Adjustable from 44 0V Decreasing to 58 0V max MAX W T Adjustable from Float to 58 5V max Maximum setting is automatically limited to 1 0 volt less than HVSD setting SLOPE Adjustable from 0 0 V C to 0 2 V MIN W T Adjustable from Float to 44V Decreasing 25 77 Temperature Figure 1 Typical Float Charge Thermal Characteristics Using Optional Battery Temperature Probe Increasing 2 1 2 Current Full Load Rated Current Amps Number of PCUs 120 VAC Input 208 240 VAC Input At 58 0 VDC At 46 0 VDC At 58 0 VDC At 46 0 VDC 1 12 5 16 3 25 32 6 2 25 32 6 50 65 2 3 37 5 48 9 75 97 8 2 1 3 Regulation A Static The associated MCA controls the steady state output voltage to within 0 5 of any voltage setting within the range of 47 0 to 58 0 volts DC for any and all combinations of load from no l
110. out the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 589200300 List 72 50VA Redundant Ringing Generator Module List 55 PCU List 32 MCA List 1 2 3 4 13 14 Power and Distribution Shelf Other Options List 40 AC Line Cord Kit 120VAC for List 1 2 3 4 List 41 AC Line Cord Kit 208 240VAC for List 1 2 3 4 List 43 AC Vertical Feed Assembly List 47 AC Line Cord Kit 120VAC for See ACCESSORY List 11 12 13 14 INFORMATION Section List 48 AC Line Cord Kit 240VAC for for List 11 12 13 14 Distribution Devices Recommended Wire List 50 Blank Module Sizes Branch Circuit List 73 Replacement Ringing Generator Protection and Lugs for List 72 TXM Extension Cable List 80 Cable Local Computer Access Load Shed Card List 81 Cable MCA Control Bus Ringing Distribution List 90 Battery Temperature Probe AP6C57EA EB Ring amp List 91 93 Battery Temperature Probe Distribution Module List 92 Battery Temperature Probe Concentrator Module TXM List 94 TXM Interface Cable 10 ft List 95 TXM Interface Cable 15 ft Page 4 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network P
111. ower Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 TABLE OF CONTENTS System List Accessory List of TNT Physical Size Related Overview Picture Information Information Parts Information Documentation LXP INTRODUCTION me 1 MODEL XP4890 OVERVIEW DR Roc oc od odo ea RUD 1 589200300 E ete 4 TABLE OF CONTENTS wesc EP E 5 LIST INFORMA T O N 7 List SHU 7 LAST OPUONS sos 7 See also the following located in this document 8 lrgirri upce 9 List 1 23 Power and Distribution Shelf with Load 9 List 2 23 Power and Distribution Shelf with Load and Battery 5 10 List 3 23 Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Load RETE wm 11 List 4 2
112. peres Provides 10 mounting positions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current 1 battery shunt and Low Voltage Battery Disconnect Provides mounting positions for one 1 MCA and up to three 3 PCUs Provides one 1 AC input circuit via front access terminal block connections Conduit opening is provided on side panel in front of mounting angle Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug Mounts in a standard 23 relay rack Restrictions None Ordering Notes 1 2 KR N 2 co Order one 1 List 32 MCA Order PCUs per List 55 as required Order Ringing Generators per List 72 as required If an AC line cord is required order List 40 120VAC or List 41 208 240VAC If battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multiple probes order One 1 List 92 TXM and List 91 probes as required For bullet nose distribution positions order circuit breakers as required per Table 5 For bullet nose distribution positions order fuses as required per Table 6 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug tw
113. peres A circuit breaker or fuse located in the mounting position adjacent to a 40 ampere or 50 ampere circuit breaker or fuse SHALL BE a maximum of 30 amperes Where two 40 ampere or 50 ampere circuit breakers or fuses are used an empty mounting space SHALL BE provided between them Provides 10 mounting positions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current and 1 battery shunt Provides mounting positions for one 1 MCA and up to three 3 PCUs Provides two 2 AC input circuits via terminal block connections Conduit openings are provided on side panel in front of mounting angle Provides connections for three 3 battery strings via locking type plugs Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug All installer s connections are made through the front See Physical Size Information for dimensions Restrictions Shelf accommodates max two 2 PCUs when List 47 is included Ordering Notes 1 2 3 Order one 1 List 32 MCA Order PCUS per List 55 as required Order Ringing Generators per List 72 as required Page 14 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use
114. r fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other circuit breaker or fuse Caution The maximum size circuit breaker or fuse used in ambient temperatures above 50 ambient SHALL BE 50 amperes A circuit breaker or fuse located in the mounting position adjacent to a 40 ampere or 50 ampere circuit breaker or fuse SHALL BE a maximum of 30 amperes Where two 40 ampere or 50 ampere circuit breakers or fuses are used an empty mounting space SHALL BE provided between them Provides 10 mounting positions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current Provides mounting positions for one 1 MCA and up to three 3 PCUs Provides two 2 AC input circuits via terminal block connections Conduit openings are provided on side panel in front of mounting angle Provides connections for three 3 battery strings via locking type plugs Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug All installer s connections are made through the front See Physical Size Information for dimensions Restrictions Shelf accommodates max two 2 PCUs when List 47 is included Ordering Notes Ord
115. r shelf P7000529 P7001140 P7001142 6 Spare parts for the AP6C57EA EB Ring amp Distribution Module can be ordered as required from the following table ORDERING CODE DESCRIPTION A0885525 1 33A Alarm SAN O Fuse A0885530 3A Alarm SAN O Fuse A0885531 5A Alarm SAN O Fuse A0885532 10A Alarm SAN O Fuse A7000627 AP8C55AA 50VA Ring Generator Field Replaceable Components Ordering Notes 1 MCA Order via List 32 2 PCU Order viaList 55 3 Fan PCU Order Part No 524397 4 DSM Order Part No 524520 5 Fuse Current Limiting P O GMT Assembly P N 528185 Bussmann Type TPS 35LB Order Part No 110982 6 Ringing Generator P N 487112100 for List 72 Order via List 73 7 Kit Fan Replacement for Part No 487112100 Ringing Generator Order Part No 534637 Kit includes 1 P N 534365 fan 3 P N 130823 mounting pins 3 P N 534571 washers Page 38 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 LIST OF PARTS Note This stocklist may not show ev
116. rd P N 528927 4 MCA maximum quantities may be otherwise restricted in your system Page 17 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Standard equipment includes a local user interface as well as a Web Interface for browser based remote access via an Ethernet port be equipped with a Battery Reserve Time Prediction Option With this software option installed the MCA monitors battery voltage during discharge and uses a Telcordia defined adaptive algorithm to predict remaining time before a user selectable voltage is reached A Battery Reserve Low alarm alerts user when the predicted remaining time is less than a user selectable alarm setpoint The option also provides a Battery Health Alarm which alerts user when batteries are nearing end of life be equipped with an SNMP Option With this software option installed the MCA supports SNMP v2 Simple Network Management Protocol interface in a TCP IP network Communications to and from the MCA is accomplished with a MIB Management Infor
117. re available 1 Emergency Stop Activation of an associated condition inhibits operation of all PCUs 2 High Voltage Shutdown Activation of an associated condition activates the HVSD circuit 3 Thermal Runaway Activation of an associated condition places all PCUs in the Battery Thermal Runaway Management mode of operation 4 Equalize Activation of an associated condition places all PCUs in the Equalize mode of operation 5 Battery Test Activation of an associated condition places all PCUs in the Battery Test mode of operation 6 Function Test Mode Activation of an associated condition blocks activation of any other Special Function definitions Permits testing of special functions such as High Voltage Shutdown or Emergency Stop without affecting operation of the system The binary inputs can be configured by the user to activate when contacts open or when contacts close B External System Voltage Meter Reading Leads can be extended from the MCA to an external voltage source This is the voltage source the MCA monitors for system alarms and displays as System Output Voltage External Alarm Circuits The MCA provides six 6 external alarm relays each with one set of Form C contacts A Contact Rating 2A at 30 VDC B Description of Operation The MCA provides 10 programmable Alarm Definitions Each Alarm Definition is programmed to alarm for selected conditions then each external alarm relay is program
118. ring Notes 1 For 240VAC operation order one 1 List 47 per Power Shelf Order the required length from the following table Length Part Number 6 ft 534843 10 ft 534842 Page 19 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 List 50 Blank Module List of Parts Features Fills one PCU mounting position Ordering Notes 1 Order as required List 55 Model LXP1500 Power Conversion Unit PCU Features Consists of one 1 Model LXP1500 PCU Spec No 486534200 Ordering Notes 1 Shelf accepts up to three 3 PCUs List 72 Model LXR050 Redundant Ringing Generator Module Features Provides 1 Model LXRO50 Spec No 487112200 Redundant Ringing Generator Module Module accepts 2 50 VA Ringing Generators Ringing Generators are included Operates from the Power Shelf 48VDC output bus to provide a redundant single frequency ringing system with transfer capability Provides up to 50 VA of continuous ringing power Uses rack space Mounts in one PCU mountin
119. rs 27 Distribution Load Wire Sizes GMT Alarm Type 27 Battery Wire Sizes and Lugs List 1 2 3 and 4 Power and Distribution Shelves 29 Battery Wire Sizes and Connectors List 11 12 13 and 14 Power and Distribution Shelves 30 External Alarm Reference and Control Wire Sizes Page 5 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Distribution DOVICCS 25 fcc 32 Bullet Nose Type Circuit Breakers nnns innert 32 TP S T LS Ty Pe ESOS 3 ies eue er tes eder venta PR lpn 33 Plug In Alarm Type Fuse Distribution Assembly Part No 529034 6 GMT Alarm Type Fuse Positions for List 1 2 3 4 Power and Distribution 5 34 Alarm TYDE FUSES RE 35 Replacem
120. stribution Shelves in the ACCESSORY INFORMATION section Page 11 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 List 4 23 Power and Distribution Shelf with Load Shunt Battery Shunt and Low Voltage Battery Disconnect List of Parts Features Provides common equipment for one 1 Integrated Power amp Distribution Shelf rated for up to 98 Amperes 4500W of power conversion and 100A of distribution Provides 4 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers or fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other overcurrent protective device Caution The maximum size circuit breaker or fuse used in ambient temperatures above 50 ambient SHALL BE 40 am
121. strictions None Ordering Notes 1 The rating of the distribution device determines the wire size requirements For wire size refer to Table Page 27 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Home Euch 90 C Wire Size Breaker 14AWG 12AWG 10AWG 8AWG 6 AWG 4 AWG 2 AWG Amperage Loop Length feet E RA 37 6 49 5g 845 93 6 4 59 148 6 9 23649 376645 597 45 15A 24 65 3949 62 gg 4 1576459 250 45 3gg eunt 20A 29 3 4 46 3 4 5 74 3 4 5 118 3 4 5 188 3 4 5 298 3 4 5 25A Ex T 37 3 4 59 3 4 5 94 3 4 5 150 3 4 5 239 3 4 5 30A EK UL 31 3 4 49 3 4 5 78 3 4 5 125 3 4 5 199 3 4 5 35A m zs 42 34 67 355 107 170 6 9 40A __ 37 3 4 59 3 4 5 94 3 4 5 149 3 4 5 45A 529 83 132 50 29 4799 75 119 60 ages 62 99 59 70A 53 Bo 75A 50 79 80 a
122. strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Plug In Alarm Type Fuse Distribution Assembly Part No 529034 6 GMT Alarm Type Fuse Positions for List 1 2 3 4 Power and Distribution Shelves Features Mounts in 2 bullet nose distribution positions of a List 1 2 3 or 4 30A Maximum Capacity Provides Load Distribution Fuse Positions 0 25 to 15 GMT Alarm Type Fuses Screw clamp type terminals Includes 6 dummy fuses equipped with safety fuse covers Restrictions For List 1 2 3 or 4 only When factory ordered assembly will be installed in the two bottom most bullet nose positions unless otherwise specified Maximum size of wire to be connected to a single fuse position is 14 AWG Fuses are not included Ordering Notes 1 For List 1 2 or 4 order Part No 529034 Provides one Part No 528958 alarm fuse distribution assembly one Part No 529033 ground return link and hardware 2 Order fuses as required per Table 7 ma y Di i 9 o E l4 f e He MN
123. t Percent of Full Load refers to percent of 25 Amperes per PCU with nominal 208 240V input or percent of 12 5 Amperes per PCU with nominal 120V input 2 2 4 Typical Input Data 50 Hz input 25 C ambient Note At 120V nominal input PCUs operate in the Reduced Power Mode In the Reduced Power Mode PCUs provide 1 2 the output current and power available in Full Power Mode 50 Hz Input 25 C Ambient amber Nominal Percent Input Current Input Input Power Efficiency n Heat of PCUs Input of Full Amperes V Watts Factor Dissipation Installed Voltage Load BTU Hr 60 52 0867 25 1 235 230 0 978 090 100 099 N A 0907 849 0 907 52 2 8 52 0 57 35 0907 0 0 0 997 o o4 o s as 2o a20 4 0 960 5 0 99 0 95 0 99 o os s o as 179 430 os s 328 789 764 0 0 96 0 99 120 696 1672 1656 099 128 699 1679 1663 0 99 0 95 25 50 120 a 25 50 097 gt oe 0 992 099 25 50 240 Page 45 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 Syste
124. t via front access terminal block connections Conduit opening is provided on side panel in front of mounting angle Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug Mounts in a standard 23 relay rack Restrictions None Ordering Notes 1 2 KR N 2 co Order one 1 List 32 MCA Order PCUs per List 55 as required Order Ringing Generators per List 72 as required If an AC line cord is required order List 40 120VAC or List 41 208 240VAC If battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multiple probes order One 1 List 92 TXM and List 91 probes as required For bullet nose distribution positions order circuit breakers as required per Table 5 For bullet nose distribution positions order fuses as required per Table 6 Order one 1 Part No 117201 fuseholder per fuse ordered in 7 above Order one 1 Load lug one hole 1 4 bolt clearance hole and one 1 Load Return lug two hole 1 4 bolt clearance holes on 5 8 centers as required for each bullet nose distribution position per Table 2 10 For GMT alarm type fuse distribution positions order fuses as required per Table 7 11 Order Battery lugs as required per Battery Wire Sizes and Lugs List 1 2 3 and 4 Power and Di
125. tant voltage source or a constant current source depending upon load demands Transition between source types is completely automatic e Constant Voltage For any initial output voltage setting from 47 to 58 volts output voltage remains constant regardless of load This is the normal operating condition in which loads are being supplied and batteries are float charged PCUs will operate in the Constant Voltage Mode unless load current increases to the user adjustable current limit setpoint e Constant Current If load increases above the current limit setting output voltage decreases linearly to maintain output current at current limit Page 1 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 PCUS will continue to operate in higher ambient temperatures at reduced power Refer to Paragraph 2 3 5 for further information regarding thermal power and current limiting MCA The Model LXC300 MCA controls the steady state output voltage to within 0 5 of any setting from no load to full load The MCA provides a two line vacuum fl
126. ted System Application Guide Spec No 589200300 Model XP4890 List 43 AC Input Vertical Feed Assembly List 47 AC Line Cord Kit 120VAC SAG589200300 Issue AH June 6 2007 List of Parts Provides top or bottom feed of AC input wiring into the Power Shelf Features Restrictions Not available with List 40 41 47 or 48 AC Line Cord Kits Ordering Notes 1 For top or bottom AC feed order 1 List 43 List of Parts Provides 2 AC input cords equipped with a NEMA 5 15P plug Each cord powers one 1 PCU Features Cords are factory installed Blank Module is included to cover one 1 unused PCU mounting position Restrictions For List 11 12 13 and 14 only Cannot be used with List 1 2 3 or 4 Each cord assembly is rated to power one 1 PCU only limits shelf to two 2 PCUS total For 120 VAC only Not available with List 43 AC Input Vertical Feed Assembly Ordering Notes 1 For 120VAC operation order one 1 List 47 per Power Shelf Order the required length from the following table Length Part Number 6 ft 534841 10 ft 534840 List 48 AC Line Cord Kit 240VAC Features List of Parts Provides 2 AC input cords equipped with a NEMA 6 20P plug Cords are factory installed Restrictions For List 11 12 13 and 14 only Cannot be used with List 1 2 3 or 4 For 240 VAC only Not available with List 43 AC Input Vertical Feed Assembly Orde
127. thout the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 Issue AH June 6 2007 The equalize time period can be set for 0 to 15 times the discharge time Home 2 3 4 2 3 5 2 3 6 System Application Guide Spec No 589200300 Model XP4890 period up to a maximum of 300 hours A zero 0 setting disables the feature Battery Test Output Mode A This mode of operation is used if lower output voltage is required for battery plant testing The Battery Test voltage setting can be checked and or adjusted without removing a PCU or affecting the load One adjustment changes the output of all PCUS B There are two methods of placing the system from the Float mode to the Battery Test mode 1 2 Method 1 Manual Battery Test A user manually places the system into the Battery Test mode via the MCA interface A user must manually return the system to the Float mode via the MCA interface Method 2 Manually Initiated Timed Equalize A user manually places the system into the Battery Test mode via the MCA interface The system automatically returns to the Float mode after a preset programmable time period or when the end battery test voltage is reached whichever occurs first Input Protection Lists 1 2 and 4 each provide connections for one AC input branch circuit Customer to provide AC input branch circuit protection A Low AC Input
128. tions for GMT type distribution fuses 30A max total 1 15A fuses Provides 1 load shunt total distribution current 1 battery shunt and Low Voltage Load Disconnect Provides mounting positions for one 1 MCA and up to three 3 PCUs Provides two 2 AC input circuits via terminal block connections Conduit openings are provided on side panel in front of mounting angle Provides connections for three 3 battery strings via locking type plugs Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug All installer s connections are made through the front See Physical Size Information for dimensions Page 15 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Restrictions Shelf accommodates max two 2 PCUs when List 47 is included Ordering Notes a CoN Oo a 2 co Order one 1 List 32 MCA Order PCUS per List 55 as required Order Ringing Generators per List 72 as required If AC line cords are require
129. tribution cable assemblies as required from the following table Order up to five 5 cable assemblies one per channel bank Required fuses are included with each cable assembly Cable assemblies can be mixed ORDERING CODE DESCRIPTION P7000858 Cable assy for one SLC96 channel bank 8 ft P7001139 Cable assy for one SLC96 channel bank 20 ft P7000859 Cable assy for one SLC5 channel bank 8 ft P7001136 Cable assy for one SLC5 channel bank 20 ft P7000937 Cable assy for one channel bank generic applications 8 ft Note Each channel bank position on the panel has a maximum capacity of 11 4 Order Part No 535133 DC power cable kit as required Provides two 2 12 long cables to connect between a List 11 12 13 or 14 power shelf and the DC input terminals of one 1 Ring amp Distribution Module 5 For SLC 96 or SLC Series 5 applications order battery cable kits as required from the following table These mate with the battery connectors provided on the power shelf ORDERING CODE DESCRIPTION Anderson connector kit for 1 battery string rated up to 60 Up to 3 kits can be installed in the power shelf Battery cable kit for SLC96 legacy power shelf Molex connectors for 2 battery strings Up to 3 cable kits can be installed in the power shelf Battery cable for SLC5 legacy power shelf Molex connectors for 2 battery strings Up to 3 cable kits can be installed in the powe
130. tribution positions order fuses as required per Table 7 11 Order Battery connectors as required per Battery Wire Sizes and Connectors List 11 12 13 and 14 Power and Distribution Shelves in the ACCESSORY INFORMATION section 12 For ringing and DC distribution in imbedded subscriber loop carrier systems such as SLC 96 or SLC Series 5 order one 1 AP6C57EA EB Ring amp Distribution Module See Accessory Information List 12 23 Front Access Power and Distribution Shelf List of Parts with Load and Battery Shunts Features Provides common equipment for one 1 Integrated Power and Distribution Shelf rated for up to 98A 4500W of power conversion and 100A of distribution at ambient temperatures of 50C or less and 90A at ambient temperatures above 50C All installers connections are front access Provides 3 mounting positions for bullet nose Load Distribution Fuseholders or Circuit Breakers 3 to 100A TPS TLS Type Fuses or 1 to 100A Bullet Nose Type Circuit Breakers Unless otherwise specified circuit breakers or fuses will be mounted from top to bottom starting with the highest capacity and working to the lowest capacity Caution A circuit breaker or fuse with a rating greater than 75 amperes SHALL HAVE an empty mounting position between it and any other circuit breaker or fuse Caution The maximum size circuit breaker or fuse used in ambient temperatures above 450 C ambient SHALL BE 50 am
131. ty of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide SAG589200300 Spec No 589200300 Model XP4890 Issue AH June 6 2007 Provides two 2 AC input circuits via terminal block connections Conduit openings are provided on side panel in front of mounting angle Provides connections for three 3 battery strings via locking type plugs Included are two control bus termination plugs All control bus ports in the system must be filled with either a cable or a termination plug Allinstallers connections are made through the front See Physical Size Information for dimensions Restrictions Shelf accommodates max two 2 PCUs when List 47 is included Ordering Notes 1 Order one 1 List 32 MCA Order PCUs per List 55 as required 3 Order Ringing Generators per List 72 as required If AC line cords are required order one 1 List 47 120VAC or 48 240VAC per shelf as required for voltage and cord length Note List 47 120VAC line cords are restricted to powering one 1 PCU each 5 battery charge temperature compensation is required order a Battery Temperature Probe as required order per List 90 For multip
132. unting on negative battery terminal Mounting hole provides clearance for 5 16 bolt Provides MCA with data required for battery temperature related functions temperature compensated output voltage high and low battery temperature alarms Page 21 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited SAG589200300 System Application Guide Issue AH June 6 2007 Spec No 589200300 Model XP4890 Plugs into Distribution Sense Module DSM no temperature compensated output voltage or Home into List 92 Temperature Concentrator Module 15 ft long cable See Physical Size Information for probe dimensions Restrictions Not for connection to MCA digital probe jack J3 For single probe applications order List 91 or List 93 Ordering Notes 1 Order up to eight 8 List 90 per List 92 ordered List 91 Battery Temperature Probe Digital Output List of Parts Features Mounts near the battery to sense battery ambient temperature Plugs into J3 on the MCA Provides MCA with data required for battery temperature related functions temperature compensated output voltage high and low battery temperatur
133. uorescent display and keypad for local user interface as well as an integrated Web Interface for remote access via an Ethernet connection Distribution Power distribution is provided through up to 4 bullet nose circuit breakers or TPS TLS fuses as well as up to 10 GMT alarm type fuses Battery protection is available through Low Voltage Load Disconnect or Low Voltage Battery Disconnect options Ringing An in shelf ringing generator option provides 50VA of continuous ringing power with built in redundancy and transfer capability Page 2 of 86 This document is the property of Emerson Network Power Energy Systems North America Inc and contains confidential and proprietary information owned by Emerson Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited System Application Guide Spec No 589200300 Model XP4890 Family Spec No Model Output Voltage Output Capacity System PCU LXP1500 Total Distribution Agency Approval Framework Type Mounting Width Mounting Depth Mounting Height Front Projection Access Expansion Shelves Available Control Color List Options Accessory Options Environment Specification Compliant Full Output Reduced Load SAG589200300 Issue AH June 6 2007 LXP 589200300 XP4890 48VDC nominal