BJ194J-9SY Power Analyzer User Manual Version

image

Contents

1. BLUE JAY Product Manual Tectnology of Electronic Automatic then press CV again enter the level 3 menu Use O and gt gt to input the new password Note Please do not change the password If necessary please contact Blue Jay technical 7 9 Menu Structure CD BA IME 0000 1000 Factory default is 0005 Clear energy Gemma counters CLr E Unrecoverable for Clear data SYS Manual or Display mode dISP Automatic Factory default is manual Change the password 0000 9999 Default is 0001 Net Lin e N 3 4 N33 NA Select the input signal network O HE Gi RAE measurement Voltage Range 100V 220V Select the range of measured U SCL 380V voltage signal Select the range of measured Signal input Current Range I SCL 5A and 1A current signal Voltage transformation 4 9999 Setting voltage signal ratio R PT transformation ratio 1 2 scale Current transformation 4 9999 Setting current signal ratio R CT transformation ratio 1 2 scale Address ADDR 1 247 Instrument address range 1 247 Communication Communication Parameters speed BAUD 4800 9600 Default is 4800 b us Protocol DATA 0 8 1 e 8 1 Factory default communication n 8 1 mode for the word n 8 1 Output type TYPE orn Alt OFF Default is Alr Set output delay DELY 0000 9999 Default is 0010 ioj Choose the electrical 13 H Digital output z TE parameter PArA PS H U3 H ETAURA Set the alarm value VALU 0000 9999 D
2. 15 x T co i e D for 6 L 62 p Front view Side view Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 7 BLUE JAY Product Manual Tectnology of Electronic Automatic Notes Input signal BJ194J using a separate acquisition calculate for each measurement channel to ensure consistent in use for different load forms it s a variety of connection mode Access wire shall be met the current 2 5 square mm voltage of 1 5 square millimeters A Voltage input Input voltage should not exceed the rated input voltage products 100V or 400V Otherwise you should use external CT Suggest 1A fuse be installed in the voltage input side B Current Input Standard input current is 5A if greater than 5A should use external CT When the CT is connected with other instruments make sure wiring methods be used in series Before remove the current input connection must be sure to disconnect the primary circuit or shorted secondary circuit of CT In order to facilitate disassembly please do not connect to CT directly and the terminal block is suggested C Please make sure that the input voltage and current corresponding to the same phase sequence and the same direction Otherwise the Values and symbols will be wrong Power and Energy The input network configuration of instrument depends on the CT number
3. Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 28 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 5 2 Choose the electrical parameter In level 1 menu of AO 1 Choose item PArA meter shows like this Ho PA A then press CV enter the level 3 menu user can choose the output parameter Ho i PACH ti 9 U Note The analog parameter can set la Ib Ic Ua Ub Uc P Q H F default is UA 7 5 3 Set the low value for transmission output In level 1 menu of AO 1 Choose item LDIS meter shows like this Ho di 5 then press CDH enter the level 3 menu user can set the low value Ho man I LUN i Press to input the number from 0 9 Press CZD to move the cursor After password switch press CYD to confirm the input value is 1 9999 Default 0000 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 29 BLUE JAY Technology of Electronic Automatic Product Manual Note Alarm value is about the secondary side value such as AC100V AC5A Voltage unit is 0 1V Current unit is 0 001A Active power unit is 0 1W Re
4. 42 10 SAFETY CONSIDERAT IONS 49 11 MAINTENANCE 49 12 TECHNICAL SERVICE 50 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 2 BLUE JAY Product Manual Tectnology of Electronic Automatic 1 SUMMARIZE BJ194J 9SY series Power Analyzer is a high end multifunction power meter It is the ideal choice for monitoring and measuring of power systems It can measure all of the power parameters in power grid Current Current harmonics 2 63 times Voltage Voltage harmonics 2 63 times Frequency Voltage and current THD Active power Harmonics factor Reactive power Voltage crest factor Apparent power Current K factor Energy Active Reactive Multi tariffs ratio Power factor And it can also transmit the parameter into 2 route relay output 2DO and 4 route switch input 4DI 2 route analog output 2AO For transformers generators capacitor banks and motors of the distributed detection automatic control system on line monitoring display 194J provide max 50 lists event logging real time saving DI DO acted events It can replace th
5. 0 pa of II 0 0 0 dy Dn D2 D3 DI4 Ke Ko Py 6 LU 0 Ap Se Sea Dl DIZ DI3 DI4 DO1 DO2 Tel 0086 023 86850812 Fax 0086 023 67636974 Product Manual line 1 for positive sequence current line 2 for negative sequence current i line 3 for zero sequence current line 1 show eU line 3 show el Email tech cqbluejay com Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 19 BLUE JAY Product Manual Tectnology of Electronic Automatic Screen 17 Display voltage THD NTG 1000 00 000 T oup UW 2f ors w LINE 3FDIDIDOY IEEE AA AL g 15 press CV can show the 2 63 times voltage harmonic distortion tOhd total odd harmonic distortion tEhd total even harmonic distortion tHFF telephone harmonic form factor CF crest factor Screen 18 Display current THD Be 100000 000 F L LILI UL o 2000 00 000 np LIL s 3FDODIDID LILI ULE J press CY can show the 2 63 times harmonic distortion tOhd total odd harmonic distortion tEhd total even harmonic distortion tHFF telephone harmonic form factor CF crest factor Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 20 BL
6. 9 3 6 THD and Individual harmonic Max 15 times A phase Voltage THD unit 0 1 B phase Voltage THD A phase Current THD unit 0 1 C phase Current THD 0x508 0x545 HUa int 62 A phase voltage harmonic content ratio for 2 to 63 times unit 0 1 0x548 0x585 HUb int 62 B phase voltage harmonic content ratio for 2 to 63 times unit 0 1 0x588 0x5c5 HUc int 62 C phase voltage harmonic content ratio for 2 to 63 times unit 0 1 6x5e8 0x605 ian SA none content ratio for 2 to 0x608 0x645 ita Se ae content ratio for 2 to 0x648 0x685 int 62 C phase current harmonic content ratio for 2 to 63 times unit 0 1 TOHDUa int A phase voltage total odd harmonic distortion 0x688 3 unit 0 196 TOHDUb int 1 B phase voltage total odd harmonic distortion 0x689 unit 0 1 TOHDUc C phase voltage total odd harmonic distortion unit 0 1 0x68b TEHDUa A phase voltage total even harmonic distortion unit 0 1 TEHDUb B phase voltage total even harmonic distortion unit 0 1 0x68d TEHDUc C phase voltage total even harmonic distortion unit 0 1 THFFUa A phase voltage telephone harmonic form factor unit 0 1 THFFUb int 1 B phase voltage telephone harmonic form Ox68f factor unit 0 1 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 47 BLUE JAY Product Manual Tectnology of Electronic Automatic THFFUc int 1 C phase volta
7. Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 11 BLUE JAY Product Manual Tectnology of Electronic Automatic 6 OPERATION MODE When the 194J 9SY is powered up the entire symbol will be on and the meter starts to self test After some seconds the meter is ready for operation and shows one of the available screens lt K CH Parameters on display can be switched by pressing key CKD or C gt LCD shown on screen at any moment When the key lt gt is pressed the screen CURRENT values of each phase are now showing Pressing again the key XK the screen will show the following parameters successively In setting menu pressing CKD can move the setting cursor to left Pressing gt gt gt can enter the number 0 9 y P4 This key named SET key pressing it can open the programming menu and return to previous menu Ps a gt KI a ae This key named Enter key pressing this key you can exit it with saving any modification that you might have done in menu operation press Enter key and user can go to the next menu d Note Press key CKO or in normal standby status and the meter will show different data in main screen In the menu set mode when changes the parameter and exit setting the meter will ask to SAVE press CAD exit without saving press CY save
8. 138 UA UB UC lower alarm 103 DO3 108 1A upper alarm 139 1A lower alarm 104 DO4 109 1B upper alarm 140 1B lower alarm 110 IC upper alarm 141 IC lower alarm 111 IA IB IC3 upper alarm 142 IA IB IC3 lower alarm 112 PA upper alarm 143 PA lower alarm 113 PB upper alarm 144 PB lower alarm 114 PC upper alarm 145 PC lower alarm 115 total active power upper alarm 146 total active power lower alarm 116 QA upper alarm 147 QA lower alarm 117 QB upper alarm 148 QB lower alarm 118 QC upper alarm 149 QC lower alarm 119 total reactive power upper alarm 150 total reactive power lower alarm Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 48 BLUE JAY Tectnology of Electronic Automatic Product Manual 120 SA upper alarm 121 SB upper alarm 152 SB lower alarm 122 SC upper alarm 153 SC lower alarm 123 total apparent power upper alarm 154 total apparent power lower alarm 124 total power factor upper alarm 155 total power factor lower alarm 125 frequency upper alarm 156 frequency lower alarm 151 SA lower alarm 126 DI1 close alarm 127 DI2 close alarm 128 DI3 close alarm 129 D14 close alarm 130 DI5 close alarm 131 DI6 close alarm 157 DI1 open alarm 158 DI2 open alarm 159 DI3 open alarm 160 DI4 open alarm 161 DI5 open alarm 162 DI6 open alarm Note 1 Not all of the data above can be read by RS485 t
9. BAUD and the meter shows like this bUS bAUd Then press CYD enter the level 3 menu allowing us to set the Baud rate 2400 4800 or 9600 bUS bU5 bU5 bAud IbAUd bRUd 2400 4800 9600 7 3 3 Choose communication format In level 1 menu of bus Choose item data and the meter shows like this bUS dAtHA Then press CA enter the level 3 menu allowing us to set the communication data format Factory setting n 8 1 bU5 bUS bU5 JALA JAER o dRER 0 6 CH nG Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 27 BLUE JAY Tectnology of Electronic Automatic Product Manual 7 4 Digital Output Setting Press CA return to level 1 menu In this section user will set 1 Digital output type 2 Output delay 3 Choose the electrical parameter 4 Set the alarm value 5 Set the hysteresis value Note If the meter have more than one channel digital output you can set the DO 2 DO 3 as the following step please select the appropriate output settings in the level 1 menu 7 4 1 Output type In level 1 menu use CKD and C gt gt to choose item DO 1 and the meter shows like thi
10. GB T17882 1999 IEC61268 1995 2 Accuracy standards HY Voltage Current Active Power Reactive Power Apparent power Power Factor Active Energy Reactive Energy Frequency 3 Input Voltage Rated 400V optional 100V Current Rated 5A optional 1A Frequency 45 65Hz 4 Load Voltage lt 0 1VA phase rated 220V Current lt 0 4VA phase rated 5A 5 Overload Current 1 2 times rated continuous 1 seconds for 10 times the rated Voltage 1 2 times the rated continuous 10 seconds for 2 times the rated 6 Dielectric strength IEC 688 IEC 255 3 1989 2kV AC RMS 1 minute between input output case power supply Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 5 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 EMC Test standard Test voltage Electrostatic discharge immunity IEC 61000 4 2 8Kv test level 4 Electrical fast transient burst e input ikv Power sunoiy 2kV immunity test p PPly Surge Shock immunity test ey ae ivi mode test voltage 8 Work environment Temperature 20 C 60 C Humidity RH 20 95 No condensation 9 Protection Panel IP54 Case IP20 10 Storage Conditions Temperature 25 C 70 C Humidity RH 20 95 11 Working Power AC 80 265V 45 65Hz DC 80 380V DC 20 60V Optional Maximum po
11. Use CKD and C to select the hour setting value from 00 23 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 32 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 6 6 Set minute In level 1 menu of TIME Choose item MIN meter shows like this tl an nin then press amp again enter the level 3 menu Use CKD and C to select the minute with setting value from 00 59 7 6 7 Set second In level 1 menu of TIME Choose item SEC meter shows like this E j nn SEC then press amp again enter the level 3 menu Use gt and C to select the second setting value from 00 59 7 6 8 Set billing date In level 1 menu of TIME Choose item E DAY meter shows like this 1 tian EJAY then press CV again enter the level 3 menu Meter will show Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 33 BLUE JAY Product Manual Tectnology of Electronic Automatic tian EdAY NMANI iJ I i Use CKD and C to select the billing date Note Default value is 0101 mean the billing date is At 1 00 on the 1st of each month NINI U tit t S
12. and exit Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 12 BLUE JAY Product Manual Tectnology of Electronic Automatic Screen 1 Displays the three phase voltage Ua Ub Uc As shown Ua 380 0V Ub 380 0V Uc 380 0V JOGUE he wen KAHA bo bo j In the bottom character Ep show total active energy is 83 6KWh In other display area region show the system information DI1 DI2 DI3 DI4 in the close state DO1 DO2 in the open state Communication transceiver normal Note Detail information for each symbol please refer chapter 5 following sections as same Note in the high voltage measurement X10 mean the showing voltage value multiplied by 1000 in the screen diagram mean the voltage is 10X1 000 10 000volt Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 13 BLUE JAY Product Manual Tectnology of Electronic Automatic Screen 2 Display the three phase current la Ib Ic In the bottom Ep shows total negative active energy oli Di2 DI3 DI4 DO1 DO2 j Screen 3 Display the total active power total reactive power and tot
13. com Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 53
14. n n px Reactive energy Vam of 7 7 x Mutt tar rato Eneray wn 1 7 7 x Max demana Wivarva mx 7 7 ets eo Vottagercurrent unbalance 7 Individual harmonic current content Up to the 63 th Notes Phase phase voltage is Uab Ubc Uca voltage data determined by the different wiring Available x Display and communications xx Only can read in RS485 communication The 194J 9SY delivers the visualization of parameters listed above by means of LCD type displays In the main display area shows 4 power parameters with other display area show the various parameters and state of meter on each page jump For more details of measurement parameters please refer to the subsequent for displays introduction and RS485 communication instructions OTHER FEATURES Low size 96 x 96 mm panel mounting meter True R M S measuring system Instantaneous maximum and minimum values of each measured parameter Energy measurement indication through a lighting led RS 485 or Ethernet optional type communication to a PC Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 4 BLUE JAY Product Manual Tectnology of Electronic Automatic 3 2 Specifications 1 Reference standard Basic electricity GB T13850 1998 IEC688 1992 Active power GB T17215 2002 IEC61036 2000 Reactive power
15. of the system in the condition of 2 CT select the three phase three lines two components in the condition of 3 CT select the three phase four lines three component mode Instrument connection mode set of the instrument programming input network NET should be the same load wiring as measured wiring Otherwise the measurement instrument will lead to incorrect voltage or power In three phase three wire mode the measurement and shows the line voltage In three phase four wire mode the measurement and shows the phase voltage Auxiliary power BJ194J Series Power Analyzer with universal AC DC power input if not for a special statement we provide the 220VAC DC or 110VAC DC power interface for standard products Instruments limit work power supply AC DC 80 270V please ensure that the auxiliary power can match with BJ194J series meter to prevent damage to the product A Suggest install 1A fuse in the fire line side B For the areas with poor power quality suggest install lightning surge suppressor and rapid burst suppressor to prevent lightning strikes Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 8 BLUE JAY Product Manual Tectnology of Electronic Automatic 4 2 Connection Terminal Upper connection terminal 115 16 50 49 48 47 eo 59 58 2 1 ao aow Re res Ap Apr
16. to level 1 menu In this section user will set 1 Meter communication address 2 Baud rate 3 Communication format Note Not all the meter have communication function please make sure your purchase meter first if no communication mode you can skip this section 7 3 1 Meter communication address setting One or some BJ194 meter can be connected to a P C With this system we can get all the parameters in one central point of reading The BJ194 has a serial RS 485 or RS 232 type output according to the model If we connect more than one device to the same communication line RS 485 we have to assign to each of them a different code or direction from 1 to 247 since the P C needs the identification of every measuring point In level 1 menu choose the item bus the meter shows like this bUS Then press CY enter the level 2 menu choose the item Addr the meter shows like this bUS Addr Press gt gt to input GA the number from 0 9 Press CKD to move the cursor After password press CV to confirm the input value is 1 9999 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 26 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 3 2 Communication Baud rate setting In level 1 menu of bus Choose item
17. 3 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 23 BLUE JAY Tectnology of Electronic Autes t 100V Maximum measured value is 100V 380V Maximum measured value is 380V aa Hin ULL USEL UG 380 Product Manual Note A different range will affect the accuracy of measurements If the accuracy is 0 5 Select 100V range means the minimum scale value is 0 5V 100 x 0 5 Select 380V range means the minimum scale value is 1 9V 380 x 0 5 7 2 3 Current measure range In level 1 menu of IN Choose I SCL meter shows like this it NT 1 SEL then press CH enter the level 3 menu user can see the current range n LSL 5 5A Maximum measured value is 5A 1A Maximum measured value is 1A B S a SLL Note Select a different range will affect the accuracy of measurements if the accuracy is 0 5 Select 1A range means the minimum scale value is 0 005A 1 x 0 5 Select 5A range means the minimum scale value is 0 025A 5 x 0 5 7 2 4 Voltage transformation ratio In level 1 menu of IN Choose item r PT meter shows like this Tel 0086 023 86850812 Fax 0086 023 67636974 Email tech cqbluejay com Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 24 BLUE JAY Product Manual Tec
18. 46 a 8 49 bi 12 13 kad Note 1 For communication with the master unit customers can choose the RS 232 to RS 485 converter to use 2 Full range of BJ 194Q meter RS485 PIN number is 58 59 60 3 Due to product modifications or custom requirements the interface pin place may be change For details please refer to product label on the rear board Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 42 BLUE JAY Product Manual Tectnology of Electronic Automatic 9 2 MODBUS protocol Modbus RTU Frame Format Address code 1 BYTE Slave device address 1 247 Function cade 4 BYTE Indicates the function codes like read coils inputs Starting address high byte Starting address low byte Data code weve Number of registers high byte Number of registers low byte Cyclical Redundancy Check Error Check code 2 BYTE CRC MODBUS FUNCTIONS Code Meaning Description This function permits to read all PANG TIGN 03 Reading of n Words the electrical parameters of the BJ194 series Write value in to the relevant FUNCTION 16 Preset Multiple Registers register Notes Blue Jay Default disable the write function if want change configuration via RS485 please contact Blue Jay Sales Team before your order Tel 0086 023 86850812 Email tech cqbluejay com F
19. 5 RS485 data refer to Communication protocol and calculate their energy cost You can set up 12 billing segment in one day The segment 1 setting steps are as follows and other segment setting method is the same In level 1 menu of S EG1 Choose item E Mod meter shows like this SEG i Enod then press CYD enter the level 3 menu user can choose the billing mod SEL SEL Enod Enod tl nE PEAP Tel 0086 023 86850812 Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing Note Above mean Sharp Peak Flat Valley SEL SEL i Enod Enod FLAE i Lo Email tech cqbluejay com BLUE JAY Product Manual Tectnology of Electronic Automatic 7 8 System Setting Press CA return to level 1 menu In this section user will set 1 Backlight time of the LCD 2 Clear energy counters 3 Set display mode 4 Change the password 7 8 1 Set the LCD backlight time In level 1 menu use CKD and gt gt gt to choose item SYS meter shows like this 545 then press CV enter the level 2 menu choose LCd t meter show 545 LCdt then press GA again enter the level 3 menu Use lt K and gt gt to select the value Note Minimum step is 1 minute 000
20. 5 for 5 minutes which means if not any operation in 5 minutes the backlight will turn off Set value gt 1000 the backlight always on Set value 0000 the backlight always off 7 8 2 Clear energy counters In level 1 menu of SYS Choose item CLr E meter shows like this Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 36 BLUE JAY Product Manual a eu LLr then press CV again to confirm clear all the energy data meter display 545 ice SUrE And then press CH again to save the operation and exit Press CAD without save and exit 7 8 3 Set display mode In level 1 menu of SYS Choose item dISP meter shows like this 595 di 5P P then press GSA enter the level 3 menu user can choose the display mode 545 395 di SP di SP nAn Hika Note Man means the screen display will change by press KO and gt Auto means the screen display will change in every 10 sec 7 8 4 Change the password In level 1 menu of SYS Choose item CodE meter shows like this 595 Lod amp Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 37
21. BLUE JAY Product Manual Tectnology of Electronic Automatic BJ194J 9SY Power Analyzer User Manual Version 3 0 er BABB 2 2088 X Pra nG aa HA ma Imp Total Net Exp kVAh Ayaw Bp A i Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing BLUE JAY Product Manual Tectnology of Electronic Automatic Read me When you use BJ194J 9SY series Power Analyzer be sure to read this user manual carefully and be able to fully understand the implications the correct guidance of operations in accordance with user manual which will help you make better use of BJ194J 9SY series Power Analyzer and help to solve the various problems at the scene 1 Before the meter turning on the power supply be sure that the power supply within the provisions of the instrument 2 When installation the current input terminal must non open voltage input terminals must Non short circuit 3 Communication terminal RS232 RS485 or Ethernet is strictly prohibited to impose on high pressure 4 Be sure the instrument wiring consistent with the internal system settings 5 When communicating with the PC instrument communication parameters must be consistent with the PC o Please read this user manual carefully Please save this document Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Buil
22. DURE 18 7 1 Input Password 18 7 2 Input Signal Selection 18 7 3 Communication Preferences 22 7 4 Digital Output Setting 24 7 5 Analog Output Setting 28 7 6 Time and Date Setting 31 7 7 Muti tariff Setting 34 7 8 System Setting 36 7 9 Menu Structure 38 7 10 Display Character instructions 40 8 PULSE OUTPUT 41 9 COMMUNICATION INTERFACE
23. Gud rs456 RSAGEA Power supply 1 Supply voltage input 0 V 47 Active energy pulse output 2 Supply voltage input 220 Va c 48 Active energy pulse output 58 RS 485 49 Reactive energy pulse output 59 RS 485 50 Reactive energy pulse output 60 RS 485 GND 16 Analog output 15 Analog output Middle connection terminal 22 21 20 19 70 71 72 73 74 DO2 DO1 COM DI1 DI2 DI3 DI4 20 Route 1 digital output 70 Digital input COM pin 19 Route 1 digital output 71 Route 1 digital input 22 Route 2 digital output 72 Route 2 digital input 21 Route 2 digital output 73 Route 3 digital input 74 Route 4 digital input Lower connection terminal 14 13 12 1 9 8 7 6 5 4 C phase Current B phase Current A phase Current 4 Current A phase S1 input 9 Current C phase S2 input 5 Current A phase S2 input 11 Voltage A phase input 6 Current B phase S1 input 12 Voltage B phase input 7 Current B phase S2 input 13 Voltage C phase input 8 Current C phase S1 input 14 Neutral Voltage input Notes The terminal pin will change depends on customer order please refer to the label on the meter Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 9 BLUE JAY Product Manual Tectno
24. UB 3E9H UC 3E7H IA 1384H IB 1388H IC 138AH 100 0 100 1 99 9 4 996 5 000 5 002 Pa eee ON ON Notes 1 User can write register data for meter testing and remote control the meter 2 When the write is unsuccessful no return data from the slave in this addition user can send write inquiry again Tel 0086 023 86850812 Fax 0086 023 67636974 Email tech cqbluejay com Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 50 BLUE JAY Product Manual Tectnology of Electronic Automatic 10 SAFETY CONSIDERATIONS All installation specification described at the previous chapters named INSTALLATION AND STARTUP INSTALLATION MODES and SPECIFICATIONS Note that with the instrument powered on the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts This instrument is factory shipped at proper operation condition 11 MAINTENANCE The 194J does not require any special maintenance No adjustment maintenance or repairing action should be done when the instrument is open and powered on should those actions are essential high qualified operators must perform them Before any adjustment replacement maintenance or repairing operation is carried out the instrument must be disconnected from any power supply source When any protection failure is suspected to exist the instrument must be immediatel
25. UE JAY Product Manual Tectnology of Electronic Automatic Screen 19 Display individual voltage harmonic data press CY can show the 2 63 times data Harmonic E sD Screen 20 Display individual current harmonic data press CYD can show the 2 63 times data L DI1 DI2 DI3 DI4 DO1 DO2 j Notes not all the 194J can display 63 time harmonic data please contact Blue Jay Sales team for more details Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 21 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 SETUP PROCEDURE The SETUP procedure of the BJ194J 9SY is performed by means of several SETUP options Once into the SETUP use the keyboard to select different options and enter required variables 7 1 Input Password A 4 figure password is required to be entered in case that in case that the meter will work without permission At normal display mode press AD to enter the programming mode meter display PASS Meter display p Ask for the password Press gt gt gt to input the password number from 0 9 Press lt lt gt to move the cursor After password switch press GA to confirm the input If password is correct met
26. Y Tectnology of Electronic Automatic Product Manual 7 10 Display Character instructions n dlana O IE DN ric O C23 COWS o ni Dodo Cc a NUN Mill LEET Cu O mo User passwords Input error User settings menu Communication settings menu Shows scal input value Set the decimal point Communication parameter setting Metter address setting Baud rate 8 data bits 1 stop bit even parity 8 data bits 1 stop bit odd parity 8 data bits 1 stop bit no parity Confirm the change Input voltage selection Input current selection Set CT ratio range range Set PT ratio Select phase Route 1 switch output settings Route 2 switch output settings System parameter settings Choose Setted parameter The corresponding parameters Set the alarm value Show Low alarm setting Show High alarm setting System password Year Month Week day Date Hour Minute Second Tariff segment Tariff Sharp Peak Flat Valley Billing day Tel 0086 023 86850812 Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 40 Email tech cqbluejay com BLUE JAY Product Manual Tectnology of Electronic Automatic 8 PULSE OUTPUT BJ 194J power analyzer provides 2 ro
27. active power unit is 0 1VAR Power factor Is 0 001 Frequency 0 01HZ 7 5 4 Set the full scale value for transmission output In level 1 menu of AO 1 Choose item HDIS meter shows like this Ho Hdi 5 then press CDH enter the level 3 menu user can set the full scale value Ho Hd 5 NaN LUN Press CP to input the number from 0 9 Press CZD to move the cursor After password switch press CV to confirm the input value is 1 9999 Default 5000 Note Alarm value is about the secondary side value such as AC100V AC5A Voltage unit is 0 1V Current unit is 0 001A Active power unit is 0 1W Reactive power unit is 0 1VAR Power factor Is 0 001 Frequency 0 01HZ 7 5 5 Example of analog output Set analog output TYPE 4 20mA LdlS 0000 PARA select la HdlS 5000 This mean when A phase current is 0 000A output 4mA current is 5 000A output 20mA Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 30 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 6 Time and Date Setting Press CA return to level 1 menu In this section user will set the meter system time which will affect the function of Muti tariff 7 6 1 Set year In level 1 menu use lt K and gt gt to choose item TIME meter shows like th
28. al factor In the bottom Eq shows total active energy Screen 4 Display the frequency of a phase In the bottom Eq shows total negative reactive energy IVIDIDIVIDIDVIDID HOI YI LILO LI kvarh DI1 DIZ lt lt Ke j Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 14 Product Manual BLUE JAY Tectnology of Electronic Automatic Screen 5 Display independent active phase only Three phase 4 wire type In the bottom Ep shows total active energy Lo DM Di Di DIE so Ss RON DOR o Screen 6 Display independent reactive phase only Three phase 4 wire type In the bottom Ep shows total negative active energy kok UENIR g 270700 00 LILI i Li Ep var s FDD NLA UGE aten Dn D2 D DI4 Screen 7 Display independent apparent phase only Three phase 4 wire type In the bottom Eq shows total active energy Sang ABO 2 3 IAM Ea k kiat kVA WE g PO Ad PO Ad ILIE war D11 DI2 DI3 DI4 Email tech cqbluejay com Tel 0086 023 86850812 Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Pa
29. ax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 43 BLUE JAY Product Manual Tectnology of Electronic Automatic 9 3 Register address table 9 3 1 Basic Power Data Primary Side Address Data Bytemode instruction Phase to Line Voltage Unit V Phase to Phase Voltage Unit V Ox0c la float 2 Three phase Current Unit A owe moa 2 Con Pa moa 2 0x14 Pb float 2 Individual phase active power Unit kW Cona qa moa 2 Oxtc Qb float 2 Individual phase reactive power Unit kVar Total power factor 0 1000 Frequency Unit0 01Hz Positive active energy Unit KWh Inductive reactive power Unit kVarh Capacitive recive power 9 3 2 Basic Power Data Secondary Side Address Data Bytemode Instruction 0x100 Phase to Line Voltage Unit 0 1V 0x101 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 44 BLUE JAY Product Manual Tectnology of Electronic Automatic int 1 n oar m 1 oao Pa mj Ox10a_ Pb im 1 Individual phase active power Unit W oaa oa m oxt0e Qb it 1 Individual phase reactive power Unit Var Ka 0x13 Total apparent power Unit VA I 1 CT ET Con s m 1 owns reversed 7171 KU aara int Tota
30. d is seen to give an incoherent Power factor and Cos reading 0 01 or similar This is again a current transformer and voltage phase connection error phase A must correspond to the current transformer installed in phase A phase B must correspond to the current transformer installed in phase B and phase C must correspond to the current transformer installed in phase C This connection is clearly shown on the back of the analyzer 3 The BJ 194J is measuring in average voltage and is displaying the secondary voltage for example 110 volts Ensure that the voltage Transformer ratio has been correctly set see section on chapter7 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 52 BLUE JAY Product Manual Tectnology of Electronic Automatic 4 The BJ 194J does not correctly display the current reading It shows values varying between 0 to 5 amps of current Ensure that the Transformer ratio has been correctly set once correctly set the current measurement shall be shown correctly see section on chapter7 For any inquiry about the instrument performance or any failure contact to Blue Jay s technical service Blue Jay After sales service Building 13 2 8 Jialing third village Pioneer Park Jiangbei District 400020 Chongqing Tel 0086 023 86850812 Fax 0086 023 67636974 E mail tech cqbluejay
31. ding 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 1 BLUE JAY Product Manual Tectnology of Electronic Automatic Directory CONTENTS Page 1 SUMMARIZE 3 2 APPLICATIONS 3 3 FEATURES 4 3 1 Electricity metering 4 3 2 Specifications 5 4 INSTALLATION AND START UP 7 4 1 Installation 7 4 2 Connection Terminal 9 4 3 Connection Drawing 10 5 SCREEN DISPLAY 11 6 OPERATION MODE 12 7 SETUP PROCE
32. e traditional analog or many digital measurement instruments such as ammeter voltmeter power meter power factor meter frequency meter etc with the advantages of improving system reliability making the on site wiring convenient and reduce system cost With serial port BJ194J 9SY Power Analyzer can connect with PC and use Modbus to set programming and read the data Based on this power meters you can simply set up a monitoring system with the IPC and central software 2 APPLICATIONS All power parameter measurement Power factor measurement and control Energy Measurement Replacing the three phase power meter three phase electricity transmitter Transformers generators capacitors and electric motors distributed detection Medium and low pressure systems SCADA EMS DCS integrators Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 3 BLUE JAY Product Manual Tectnology of Electronic Automatic 3 FEATURES 3 1 Electricity Metering By means of an internal microprocessor it simultaneously measures mu mag Single phase votege v x x x 7 Phase phase vottage v x x x 7 C a Frequency a fp dP xd Powertactor Co x x x x Active power WO xp xp xd Reactive power Va x x x x Apparent power VA x x x x Active energy Who pol
33. efault is 0050 hysteresis value HYS 4800 9600 Default is 4800 Tel 0086 023 86850812 Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing Email tech cqbluejay com 38 BLUE JAY Product Manual Tectnology of Electronic Automatic Output type TYPE 12 20 4 20 0 20 Default is 12 20 Choose the elocineal OA UB UC FR Default is UA parameter PArA Analog Output low value for Setting AO 1 transmission output 0000 9999 Default is 0000 LdlS full scale value for transmission output 0000 9999 Default is 5000 HdlS Year YEAR 00 99 Default is 20XX Month MON nom lolo owe ow Billing time of segment 1 Default 0000 TIME Billing date of segment 1 S EG1 Sharp TinE Peak PEAK Flat FLAt Valley LOW Segment 1 billing tarfiff E Mod Muti tariff Setting E SEG Billing date of Billing time of segment 12 segment 12 Default 0000 S EG12 TIME Sharp TinE Peak PEAK Flat FLAt Valley LOW Segment 1 billing tarfiff E Mod Note Not all 194J series power analyzer have the complete menu settings Please confirm your purchased power analyzer has the corresponding extension module Without the module the corresponding part of the menu is not valid Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 39 BLUE JA
34. el the alarm Example Alarm value 3 700A hysteresis value 0 03 Rising edge alarm Measured value is 3 700A then relay action output alarm When measured value is bellow 3 700 3 700 0 03 3 589A the alarm will be cancel Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 31 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 5 Analog Output Setting Press CA return to level 1 menu In this section user will set 1 Analog output type 2 Choose the electrical parameter 3 Set the zero value for transmission output 4 Set the full scale value for transmission output Note If the meter have more than one channel analog output you can set the AO 2 AO 3 as the following steps please select the appropriate output settings in the level 1 menu 7 5 1 Output type NG N In level 1 menu use CKD and C gt gt gt to choose item DO 1 meter shows like this Ho then press CV enter the level 2 menu choose LINE meter shows Ho Ere then press CH again enter the level 3 menu Use CKD and C to select the output type meter shows like this Ho 1 MHo Ao EYPE EYPE EYPE icdU 14 20 O QU Note output type can choose 12 20mA 4 20mA 0 20mA default is 12 20mA
35. equence current in primary side 0x38 foa 2 negative sequence current in primary side L oxs2a oat 2 zero sequence current in primary side L oxs2c toat 2 percentage of negative sequence voltage L oxs2E float 2 percentage of negative sequence current oxsso roat 2 A phase voltage deviation Mosa toat 2 B phase voltage deviation 0x334 __ float 2 C phase voltage deviation oss float 2 Frequency deviation 9 3 5 Multi tariffs ratio data Address Daa Bytemode instruction 0x402 Cumulative T1 Sharp long 2 The total sharp energy L oxaoa Current tol Total long 2 Total energy ofthis monn C oxan2 Curent T4 Vally long 2 Valley energy ofthis month Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 46 BLUE JAY Product Manual Tectnology of Electronic Automatic 0x416 Last_T1 Sharp long Sharp energy of last month 0x418 Last_T2 Peak aes Peak energy of last month Last_T3 Flat long 2 Flat energy of last month Last_T4 Vally Valley energy of last month Prior tol Total Nalang of the month before last 0x420 Prior 11 Sharp a a of the month before 0x422 Prior_T2 Peak o aay of the month before last 0x424 Prior_T3 Flat Paa of the month before last 0x426 Prior_T4 Vally long 2 Valley energy of the month before last month
36. er can enter next setting Notes the default password is 0001 7 2 Input Signal Selection Press A_ return to level 1 menu In this section user will set 1 Input net mode 2 Voltage measure range 3 Current measure range 4 Voltage transformation ratio 5 Current transformation ratio Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 22 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 2 1 Choice the input net mode In level 1 menu use CKD and to choose item IN and the meter shows like this n then press CH enter the level 2 menu choose LINE meter shows n Li nE Then press CV again enter the level 3 menu Use O and TI to select the right wiring mode meter shows like this fete toe A i n ne Ling n34 n3j Note Selecting the wiring mode must match with actual wiring or the reading data will go i L wrong 7 2 2 Voltage measure range In level 1 menu of IN Choose item U SCL and the meter shows like this raja r C un then press CYD enter the level 3 menu user can see the voltage range Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 1
37. ge telephone harmonic form 0x690 factor unit 0 1 0x691 A phase voltage crest factor unit 0 001 0x692 CFUb B phase voltage crest factor unit 0 001 0x693 C phase voltage crest factor unit 0 001 TOHDla int 1 A phase current total odd harmonic distortion 0x694 H unit 0 1 TOHDIb int 1 B phase current total odd harmonic distortion 0x695 R o unit 0 1 TOHDIc int 1 C phase current total odd harmonic distortion 0x696 R o unit 0 1 TEHDla int 1 A phase current total even harmonic distortion 0x697 unit 0 1 TEHDIb int 1 B phase current total even harmonic distortion 0x698 o unit 0 1 TEHDIc int 1 C phase current total even harmonic distortion 0x699 i o unit 0 1 A phase current K factor unit 0 01 0x69b KFIb B phase current K factor unit 0 01 C phase current K factor unit 0 01 9 3 7 SOE record Max 50 list Ad Byte 0 Fault channel Byte 1 Fault event Byte 2 3 Fault value Byte 4 Fault time Year 0X700 0X7F9 SOE 1 50 int 1 Byte 5 Fault time Month Byte 6 Fault Time Day Byte 7 Fault time Time Byte 8 Fault time Minute Byte 9 Fault time Seconds Byte 0 Byte 1 1 DI1 100 Remote control 2 DI2 101 UA upper alarm 132 UA lower alarm 3 DI3 102 UB upper alarm 133 UB lower alarm 4 DI4 103 UC upper alarm 134 UC lower alarm 5 DI5 104 UAB upper alarm 135 UAB lower alarm 6 DI6 105 UBC upper alarm 136 UBC lower alarm 101 D01 106 UCA upper alarm 137 UCA lower alarm 102 DO2 107 UA UB UC upper alarm
38. he reading address will be unsuccessful 2 The data can be read out depends on your multi function meter model please refer to the corresponding product manual before build your software 3 Some software has different definitions of the start bit of register address there will be offset please add 1 for the right address To get more info please contact technical support tech cqbluejay com 4 Blue Jay provide BOS1000 software for small measurement network and customer testing it can connect max 32pcs of power meter user can free to download this software on Blue Jay online site www cgbluejay com Tel 0086 023 86850812 Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 49 Email tech cqbluejay com BLUE JAY Tectnology of Electronic Automatic 9 4 Example Host to Slave inquiry Product Manual Addr Fun Data Address Data Address Data Number Datanumber CRC16 CRC16 high low high low low high OCH 03H 00H 00H 00H 06H C4H D5H PC user ask upload UA UB UC IA IB IC Slave to Host answer Byte Data1 Data1 Data2 Data2 Data3 Data3 Agar Fun count high low high low high low OCH 03H OCH 03H E8H 03H E9H 03H E8H Data4 Data4 Data5 Data5 Data6 Data6 CRC16 CRC1 high low high low high low low 6 high 13H 84H 13H 88H 13H 8AH A6H D6H Show the data UA 3E8H
39. hen press CYD enter the level 3 menu user can set the alarm value do et eit U ggg a om Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 30 BLUE JAY Product Manual Tectnology of Electronic Automatic Press gt gt gt to input the number from 0 9 Press CZD to move the cursor After password switch press CV to confirm the input value is 1 9999 Default 5500 Note Alarm value is about the secondary side value such as AC100V ACSA Voltage unit is 0 1V Reactive power unit is 0 1VAR Current unit is 0 001A Power factor Is 0 001 Active power unit is 0 1W Frequency 0 01HZ 7 4 5 Set the hysteresis value In level 1 menu of DO 1 Choose item HYS meter shows like this do H95 then press CH enter the level 3 menu and user can set the alarm value do NAN I LUN Press gt gt gt to input the number from 0 9 Press CZD to move the cursor After password switch press CV to confirm the input value is 1 9999 Default 0050 Hysteresis value is for cancel alarm status Formula X A x Y A for alarm value rising edge falling edge Y for Hysteresis value Only the difference between DO setting parameter value and real time monitor value is greater than value X that can canc
40. is ki an then press CV enter the level 2 menu choose YEAR meter show ki nn YEAr then press again enter the level 3 menu Use O and TI to select the year setting value from 00 99 7 6 2 Set month In level 1 menu of TIME Choose item MON meter shows like this tl nn non then press again enter the level 3 menu Use CKD and C to select the month with setting value from 1 12 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 31 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 6 3 Set week day In level 1 menu of TIME Choose item DAY meter shows like this ki nn dH4 then press CV again enter the level 3 menu Use CKD and C to select the day with setting value from 1 31 7 6 4 Set date In level 1 menu of TIME Choose item DATE meter shows like this ti nn dHAkA then press VY again enter the level 3 menu and gt gt gt to select the week day with setting value from 1 7 N 7 Use N 7 6 5 Set hour In level 1 menu of TIME Choose item HOUR meter shows like this ki nn Holir then press amp again enter the level 3 menu
41. l power factor 01000 O x Total power factor 0 1 000 Cone r1 ota Ep int 2 Positive active eneroy UNE Wh 9 3 3 Meter status data ass oaa ovome a Digital output 0x200 int 1 Bit O 1 show channel 1and channel 2 status 0 for open 1 for closed Digital input 0x201 int 1 Bit 0 3 show channel 1 to channel 4 status 0 for open 1 for closed 1 i Internal RTC real time clock Year Month OT Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 45 BLUE JAY Product Manual Tectnology of Electronic Automatic 9 3 4 Advanced electrical parameter Address Data Bytemode instruction osoo Pae toat 2 Present active power demand Unt Ww oxsoz Qde float 2 Present reactive power demand Unit var Losos toat 2 active power demand in last month oso oat 2 reactive power demand in last month oxsro roa 2 apparent power demand in last month os foa 2 ram power demand n mon before last month posts ra 2 fiag Poe demand in month before lasi month os toa 2 a Power demand in month before last month OS foa 2 reversed os2 foa 2 positive sequence voltage in primary side owz2 foa 2 negative sequence voltage in primary side osa foa 2 zero sequence voltage in primary side oso foa 2 positive s
42. logy of Electronic Automatic 4 3 Connection Drawing Power Supply ns liefie lt lt s0 leo 48 47 o so fse X 2 1 22 21 X 20 19 PPPD 70 74 72 73 74 141312119 8 7 6 5 4 q E e N o e9 _ sh N U z O W gt IMPORTANT REMARK If power 0 01 is shown for any of the phases and voltage and current are not zero for this phase check out following points Assure that A B and C phases coincide in voltage and current Correct polarity Reverse the current transformer placed at this phase Note This connection drawing is for reference only the actual connecting terminal please refer to the label on the rear part Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 10 BLUE JAY Product Manual Tectnology of Electronic Automatic 5 SCREEN DISPLAY 5 1 Panel Diagram Four Tariff Indicator Current Quadrant Indicator GRR midi ng rg y ua O O O r ma 2 ing 2 Yy nergy Parameter H k lt gt A i THO MIN O var COMM Indicator E 3 A A H Hz p for Active power 9 kVA q for Reactive pawar Avg Imp Total Net Exp kVAh r To BBG BHBHE RA s3 aii Total Separate Tariff Data Indicator JE sei ee pA MANG ag Se or Be oe te ors se ot Note Please see detail instructions of items at OPERATION MODE
43. o the setting value max is 3123 which means each month 31st 23 00 Date time 7 7 Muti tariff Setting Press CA return to level 1 menu In this section user will set 1 Billing segment setting 2 Ttariff setting Note BJ 194J contains 12 billing segments with the billing segment 1 setting method in this manual 7 7 1 Set the billing time of segment 1 In level 1 menu use lt gt and C gt gt to choose item S EG1 and the meter shows like this SEL N Then press CYD enter the level 2 menu choose TIME The meter shows 5 E Ti x mg i ki nn Then press GA again entering the level 3 menu Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 34 BLUE JAY Tectnology of Electronic Automatic Product Manual SEG tian ANAN JUGU Use CKD and C gt gt to select the billing date Note Default value is 0000 which means the billing date is at 00 00 on each day NAAN LUUU min sec Segment 1 is for the muti tariff starting time 7 7 2 Choose the segment 1 billing tariff Note BJ194J provides 3 months of energy data use Sharp Peak Flat Valley T1 T4 to calibrate the total energy data Users can get monthly energy data from panel display or RS48
44. ower left corner symbol d1 mean display the current month s max demand power d2 for last month max demand power d3 for the month before last month max demand power Screen 11 Display real time clock line 1 shows year line 2 shows month line 3 shows date Hs Sen DH D2 D3 Da DO1 DO2 J In the bottom line shows Hour minute and second Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 17 BLUE JAY Product Manual Tectnology of Electronic Automatic Screen 12 Display voltage deviation show three phase voltage deviation unit Re Oh PG Lo Aa DI1 DI2 DI3 DI4 DO1 DO2 DIZ Gordi Q N0 pg Uh p line 1 for positive sequence voltage amar bi 0 OQ o i line 2 for negative sequence voltage i 0 00 00 00 f line 3 for zero sequence voltage CID LY 1 12 40 DIM DI2 DIZ tf ee oe a ell Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 18 BLUE JAY Tectnology of Electronic Automatic Screen 15 Display th e current unbalance
45. ress CQ to move the cursor After password switch press CY to confirm the input value is 1 9999 Default 0010 Note The setting of relay value is indicating the width pulse output value 0000 is for level output The setting value resolution is 100ms which means 0001 is 100ms 9999 means 999 9s 0 for level output 1 9999 for pulse output Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 29 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 4 3 Choose the electrical parameter In level 1 menu of DO 1 Choose item PArA meter shows like this do PAA then press CYD enter the level 3 menu user can choose the output parameter Note There are two alarm mode indicate with XX H and XX L XX H mean the rising edge alarm XX L mean the falling edge alarm JA H mean when the A phase current is rising to a certain value then output alarm Example 13 H mean when one phase of A B C phase current is rising to a certain value then output alarm PS L mean when Three phase total power is falling to a certain value then output alarm 7 4 4 Set the alarm value In level 1 menu of DO 1 Choose item VALU meter shows like this do wALU t
46. rk Jiangbei District Chongqing 15 BLUE JAY Product Manual Tectnology of Electronic Automatic Screen 8 Display independent power factor only Three phase 4 wire type In the bottom Eq shows total negative reactive energy Annnnnnn CALISIA kvarh DI1 DIZ Hinata ah ake J Screen 9 Display the 4 tariff energy data In the top screen T1 T4 indicate current showing tariff In diagram show tariff 2 E0 E3 indicate the last three month E0 Three month total energy data E1 Current month energy E2 Last month energy E3 Month before last month energy In the bottom screen T1 T4 indicate the energy sum data in each tariff l DTO _ EE HAS oc Dili DIZ DI3 DI4 DOT DO2 j 0 T0 00003948 Note Press key CY can switch show other energy data Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 16 BLUE JAY Product Manual Tectnology of Electronic Automatic Screen 10 Display maximum power demand Notes use slip method slip interval 1 minute total of 15 minutes i line 1 for active power g N var line 2 for reactive power Q Re Demand be g f 0 VA line 3 for apparent power Dn D2 Ds DA oe Doe The l
47. s dos then press CH enter the level 2 menu choose TYPE The meter shows a do i then press amp again enter the level 3 menu Use CKD and gt gt to select the output type meter shows like this do LYPE Cn Tel 0086 023 86850812 Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing do LYPE or do kYPE Rir GFF Email tech cqbluejay com 28 BLUE JAY Product Manual Tectnology of Electronic Automatic r n Mean remote control mode there have pulse and level output mode more detail refer chapter 7 4 2 Host inquiry 01 05 00 01 FF 00 DD FA Relay value Address Code Relay address FFO0 close 0000 open CRC Slave answer 01 05 00 01 FF 00 DD FA Relay value Address Code Relay address FFO0 close 0000 open CRC RS485 communication please refer to RS485 protocol document ALr Mean directly alarm mode OFF Mean the relay will not work 7 4 2 Set output delay In level 1 menu of DO 1 Choose item DELY and the meter shows like this do dte 4 Then press Y gt enter the level 3 menu user can set the delay value do dELY ugg i Press to input the number from 0 9 P
48. tnology of Electronic Automatic in r PE then press CV enter the level 3 menu allowing us to set the current transformer nz r PE NAN tt UUU Press to input the number from 0 9 Press CZD to move the cursor After password switch press CV to confirm the input value is 1 9999 Note The input values represent the voltage transformer primary side voltage secondary side voltage Secondary side voltage is 100V or 380V user set it at section 7 2 2 7 2 5 Current transformation ratio In level 1 menu of IN Choose the item r CT meter shows like this n r CE then press CV enter the level 3 menu allowing us to set the current transformer n r CE AANA t Wu Press gt gt gt to input the number from 0 9 Press CZD to move the cursor After password switch press CV to confirm the input value is 1 9999 Note The input values represent the current transformer primary side voltage secondary side current Secondary side current is 1A or 5A user set it at section 7 2 3 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 25 BLUE JAY Product Manual Tectnology of Electronic Automatic 7 3 Communication Preferences N Press CA return
49. utes pulse output for the total active energy and total reactive energy The host PLC DI module can cumulative the data of both the active and reactive power energy sent by the pulse from optocoupler relay 1 Electrical specification voltage VCC lt 48V Iz s 50mA 2 Pulse 5000 imp kWh pulse upto 80ms This means When the meter detect 1 kWh the meter output 5000 pulse Note 1 kWh energy is for secondary side energy data if there have PT and CT accessed primary side energy data is 1 kWh xPT ratiox CT ratio For example In measure time T the received total pulse is N Primary side input of voltage is 10Kv Primary side input of current is 400A Secondary side measurement range is 100V and 5A In the time T energy accumulated is N 5000 x 100 x 80 pulse output 47 pa active power reactive power Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 41 BLUE JAY Product Manual Tectnology of Electronic Automatic 9 COMMUNICATION INTERFACE 9 1 Connection for the RS485 BUS The composition of the RS 485 cabling must be carried out with a meshed screen cable minimum 3 wire diameter of not less than 0 5mm with a maximum distance of 1 200 m between the BJ194 and the master unit This Bus may connect a maximum of 32 BJ194 485A 485B GND PREP ER EPL 58 59 60
50. wer consumption 6W 12 Dimensions L x W x H 96mmx96mmx71mm 13 Installation hole size L x W 91 0 8mm x 91 0 8mm Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 6 BLUE JAY Product Manual Tectnology of Electronic Automatic 4 INSTALLATION AND START UP The manual you hold in your hand contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep it in safety conditions The instrument must not be powered on and used until its definitive assembly is on the cabinet s door If the instrument is not used as manufacturer s specifications the protection of the instrument will be damaged When any protection failure is suspected to exist for example it presents external visible damages the instrument must be immediately powered off In this case contact a qualified service representative 4 1 Installation Mounting Instrument is to be mounted on panel cut out 91 0 8 x 91 0 8 mm Keep all connections into the cabinet Note that with the instrument powered on the terminals could be dangerous to touch and cover opening actions or elements removal may allow accessing dangerous parts Therefore the instrument must not be used until this is completely installed
51. y put out of service The instrument s design allows a quick replacement in case of any failure Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 51 BLUE JAY Product Manual Tectnology of Electronic Automatic 12 TECHNICAL SERVICE FAQ s 1 The BJ 194J Power Analyzer once cabled and connected is seen to give a correct voltage and current reading but shows negative values for active power generation This is an error with the cabling for the current transformer secondary the direction of the transformer current has to be respected as shown in the connection diagram The current transformers have a two face primary the current must pass from P1 to P2 giving the result in secondary S1 and S2 of 5 amps The error stems from a The current transformers have been incorrectly installed As a result it gives the direction of the current as passing from P2 to P1 to resolve this problem the current transformer does not have to be dismantled and installed again but the transformer secondary S1 and S2 just has to be inverted b The connection of the current secondary in the current transformers have been incorrectly connected to resolve this problem just connect the S1 transformer secondary to the S1 on the meter and the S2 on the current transformer to the S2 on the meter The BJ 194J once cabled and connecte