Home

Contactors - IMPOL-1

image

Contents

1. Checking activity designation Optical inspection from outside 1x annually 1x to 2x annually depending on ap plication Inspection of the main contacts Inspection of the auxiliary contacts Every 2 years Extraordinary services need only be carried out if there has been a significant and extraordinary recorded number of switchings under fault conditions If the contactors are being used in particularly dirty environ ments the checking intervals for the optical inspection should be shortened because dirt can impair the insulation clear ances and there is therefore the possibility of a shorter ser vice life or an operational fault e High voltage supply cables or current bars Check of the high voltage supply cables bars and the tightening torques of the fastening screws e Earthing Check of the supply cables and the tightening torques of the fastening screw e Cleaning In case of excessive dirt the surface of the contactors should be cleaned e Inspection of the main contacts Disconnect the main terminals and remove the Upper Module Inspect the main contacts both fixed and movable contacts It requires some experience to evaluate the state of the contacts Even after only a few switchings under load the contacts look used and polluted for the inexperienced eye Contacts need only to be replaced if the wear of the contact tips is more than 70 Replace the Upper Module and secure it Reconnect the main term
2. Mounting of the Upper Module Electrical installation of the main circuit 7 ks os lt A k v x Close the 4 latching levers and make sure that all 4 lock bars have snapped in safely The Upper Module must be fixed tightly to the Lower Module If you use wires for the connection of the main terminals the cable lugs can be placed on top of the main terminals and tightened with the appropriate screws Schaltbau strongly recommends Schnorr Washers or similar to secure the screws The screws must be tightened with the rated torque re fer to label on the Upper Module If you want to use current bars as recommended by Schaltbau it is better to mount the bars below the main terminal This way maintenance is much easier and the upper module can be removed without removing the current bars Schaltbau is supplying CT1000 contactors without the press nut for this purpose AN Make sure the connection areas are free of corrosion The photos show the connection of CT1130 08 The connec tion of CT1115 04 and CT1130 04 is identical If the current bars are even slightly flexible they can be connected to the main terminals directly Q Page 17 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E N A i E s oy P ee d f gt BM 5 7 A d A E nt 5 Ki 4 mr oy A J ay 4 p A A l P pons ee mA s s iA fi iy If the current bars are rather infl
3. Before carrying out any inspection and maintenance work on CT1000 contactors the contactors must be de energized and in addition life wires made safe by earthing If the environ ment has no disconnecting and earthing device other suita ble measures must be used to ensure that no voltage is pre sent Please make sure that any capacitors in the main circuit are discharged before touching main wires We recommend securing the supply lines to prevent switching back on The 2 black protection caps must not be removed for opera tion They are part of the insulation system Operation without the 2 black protection caps is not permissible All inspections and the replacement of components may only be performed by qualified personnel and must be done ac cording to Schaltbau specification All components which have to be replaced must be original components defined by Schaltbau During continuous operation the contactors will warm up It is recommended to wait an appropriate time before starting any service and touch the contactors CT1000 contactors are designed to be mounted in environ ments defined by pollution degree PD3 according to EN6007 7 1 Pollution degree PD3 Conductive pollution or dry non conductive pollution occurs which becomes conductive due to condensation which is to be expected Example Indoor location not directly exposed to rain snow and heavy dust CT1000 contactors contain strong magnets for the perma
4. nent magnetic blow out Make sure that these magnets do not attract any ferromagnetic particles into the contactors ei ther opened or closed These magnets may destroy data on credit cards or such During the short time of the switching off operation strong magnetic fields are generated in the vicinity of the pole plates They may affect other components close to the contactor Q Page 7 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 SCHALTBAU Technical data Applied standards Refer to catalogue C20 data sheets and measured drawings Refer to catalogue C20 EN60077 1 2003 04 EN 60077 2 2003 04 EN 50124 1 2010 11 EN 61373 2011 04 EN 50125 1 2010 11 Railway applications Electric equipment for rolling stock Part 1 General service conditions and general rules IEC 60077 1 1999 modified Railway applications Electric equipment for rolling stock Part 2 Electrotechnical components General rules IEC 60077 2 1999 modified Railway applications Insulation coordination Part 1 Basic requirements Clearances and creepage dis tances for all electrical and electronic equipment Railway applications Rolling stock equipment shock and vibration tests Railway applications Environmental conditions for equipment Part 1 Equipment on board rolling stock Q Page 8 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E N Description Upper M
5. 1 1 User Manual Power contactors series CT 1115 04 and CT1130 04 Introduction TT SCHALTBAU CT1000 contactors are air switching components with arc breaking in ce ramic They use a highly sophisticated principle of arc control combining the permanent magnetic and electro magnetic blow out technique This allows practically unrestricted operation for all AC and DC voltages and currents within the technical specification CT1015 contactors are designed for nominal voltages of 1 500 V CT1030 contactors are designed for nominal voltages of 3 000 V Due to the very high rated insulation voltage CT1030 contactors can be used for peak voltages up to 5 000 V This manual refers to single pole contactors with a conventional thermal current of 400 A For single contactors for 800 A refer to manual C20 08 M CT1000 contactors provide excellent switching performance from very small up to heavy loads CT1000 contactors are available for vertical and horizontal mounting CT1000 contactors have been designed and tested according to National and International Railway Standards Due to their unique features they can also be used in a variety of industrial applications CT1000 contactors offer the following design related advantages Compact rugged design 2 voltage levels several current levels Double break contacts cadmium free contact tips 1 2 and 3 pole versions Easy maintenance o Easy in
6. Q Page 23 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E TR Auxiliary contacts If the auxiliary switches have to be replaced all switches of one type S826 or S870 should be replaced AN Only original spare parts are to be used as a replacement CC CT1130 04 Protection cap coil terminal CA CT1130 04 Protection cap auxiliary switches AS 870 Switch group with 2x S870 order 1 per contactor as appro priate S826 a L Snap action switch S826 order 2 or 4 per contactor as ap propriate Disconnect the main cables current bars Remove the Upper Module Remove the protection caps Dismount the contactor Removal of the auxiliary switch subassembly Remove the 2 knurled thumb screws and the 2 Allen head screws M4 Note the mounting position of the subassembly and the individual switches Pull the subassembly out in the direction of the arrow Q Page 24 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E RN Dismount and mount the switches or the S870 switch group one by one to avoid wrong mounting If all switches are removed together and mounted again a readjustment of the frame is necessary Changing the S870 assembly Use a POZIDRIV cruciform screw driver size 1 to remove the 2 screws on the top of the frame Mount the replace assembly in the same mounting position Do not forget the washers Changing the S826 snap action switches Use a POZIDRIV cr
7. sure that all the washers are close to the nuts when you mount the cover The wash ers must remain outside of the cover Secure the nuts by hand force as tight as possible The protection cap for the auxiliary switches must not be removed for operation It is part of the insulation system Operation without the protection cap is not permissible Connect the coil control wires to the cage clamp terminals No polarity must be observed Bundle and fix the wires as shown below Fix the protection cap with the M4 x 10 screw plus flat washer and Schnorr washer The coil is protected against excessive overvoltages which will occur when the coil is switched off by a bi directional suppressor diode The value of the overvoltage limitation is part of the magnetic system and must not be changed or short circuited by external means It is explicitly stated that the use of diodes is prohibited for that purpose Take care there is no such diode in the external control circuit Q Page 16 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E N Mount the Upper Module onto the Lower Module Make sure all 4 latching levers are in the open position Attention The modules are mechanically coded Only one mounting position is possible Attach the Upper Module in the correct position Optical marks and coding pins are provided to ensure the proper positioning Do not try to force the Upper Module into the wrong position
8. E a e E E A E E E E E E Unpacking and Nandi sessir E acboumenwmuarenmmnnaues Operating POSIHON asesinos nnana ds eee cemented Gach E SEREDE EA E E E Mechanical requirements ccccccscccsseccesceceeeeceeeceeeceueeceueessueesaeessueeseueessaeens Electrical requirements cccccsccccsecccececsceceeeceeceaeeceeecsueeceueesseesseeeseusessaeens MECHANICA installati n asceenecsseereuearearnte uxeenacbenstecduereuecsdewouennedinescueaedendeenensadievaee Electrical installation of the auxiliary SWItCNES cccecccsececeeeeseeeeeeeesaeeesaeeees Electrical installation of the Magnetic drive cccccccececeececeeeeseeeeseeesaeeesaeeees Mounting of the Upper Module ccccccceceeccceeeeaeeeeeeceeeeeeseeeeseeeeseeeaeeesseeess Electrical installation of the main circuit cece ccecceeeeeeeeeeeeeeseeeeseeesaeeesaeeens Electrical installation of the earth terminal ccccccceeccceeeeeeeeeseeeeseeesaeeesaeeees COMMISSIONI O eE EE R MENANG E ee E A E Recommended regular service intervals cccccceccceeeceeeceeeeeeeeeeeseeeeeeeeseeeaees Unscheduled Service interval ccccccccsccceeecseeceeesaeecaeecaeecesecegecceseeeeeeenenans Inspection activities 20 00 ceccceeccceeeceececeeecaeeceaeeceucesaueesausecaeeceueesaueeseeesseeessaeess Spare parts replacement Of Parts cc ecccccccceececeeeeceeeeeeeeeseeeseeeeseeeeseeeeaaeeeaes Q SCHALTBAU Page 5 25 Rev
9. Q SCHALTBAU Connect Contact Control Contactors CT1115 04 CT1130 04 Single Pole NO Power Contactors for AC and DC Manual C20 04 M en Q Page 2 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 SCHALTBAU Revision History 1 1 26 10 2012 21 Part number of glue for ceramic protection insert Neuwieser changed from 13600310 to 13650290 Page 3 25 Rev 1 1 User Manual Power contactors series CT 1115 04 and CT 1130 04 SCHALTBAU Conventions for this To highlight particularly important instructions the following symbols are Manual used in this handbook NOTICE refers to technical features and methods aimed at facilitating work or to particularly important information DANGER refers to processes operations which have to be followed exactly in order to avoid personal injuries CAUTION refers to processes operations which must be fol lowed to avoid damaging structural components the system or other user materials WARNING refers to hazardous electrical voltages General legal notice e CT1000 contactors must only be used under operating conditions according to the technical specification and the instructions in this manual e CT1000 contactors must only be used when all protective devices are present have been installed properly and are fully operational e CT1000 contactors must not be converted or otherwise modified without prior consent of SCHALTBAU GmbH V
10. auges must be selected in coordination with their insulation class and the operating conditions Undersized gauges for the earth terminal may produce a safety hazard Refer to catalogues for the power consumption of the magnetic drive system and the electrical data of the auxiliary switches C20 Catalogue for Contactors CT1115 04 CT1130 04 CT1115 08 and CT1130 08 D26 Catalogue for Snap Action Switches S826 D70 Catalogue for Snap Action Switches S870 AN Installation must be carried out by qualified personnel only Clean the surface of the mounting plate and the base plate of the contactor Lower Module Put the Lower Module on the mounting plate and secure with the appropri ate screws using the correct tightening torque Schaltbau strongly recom mend Schnorr Washers or similar to secure the screws Q Page 15 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 SCHALTBAU Electrical installation of the auxiliary switches Electrical installation of the magnetic drive Connect the wires for the auxiliary contacts For the a1 and bO contacts Switches S870 no polarity must be observed For the general purpose contacts Snap action switches S826 the polarity must be observed The position of the switches and the terminal numbers are shown on a label on the protection cap Bundle and fix the wires as shown below Fix the protection cap and tighten the knurled thumb screws Make
11. de vices are undamaged i Page 13 25 Rev 1 1 User Manual Power contactors series CT 1115 04 and CT 1130 04 SCHALTBAU Operating position Make sure that you have received the correct contactors for the application CT1000 contactors for horizontal mounting must only be mounted horizontally Lock bars are yellow position is also shown on the labels they can be mounted in any position in reference to the direction of movement of the vehicle Make sure that both Upper and Lower Module are for horizontal mounting CT1000 contactors for vertical mounting must only be mount ed vertically Lock bars are red position is also shown on the labels Make sure that both Upper and Lower Module are for vertical mounting CT1000 contactors can be mounted horizontally or vertically aii D r 7 it ae gt b pa f 4 gt g an 4 vy pa alg Horizontal mounting position Vertical mounting position 1 Vertical mounting position 2 In most cases the contactors are mounted on mounting plates or mounting frames They must be solid enough to carry the weight of the contactors un der the shock and vibration conditions of the railway environment The contactors Lower Module are fixed with 4 or more mounting screws depending on the number of poles The screws and if applicable the nuts must be steel grade 8 8 Schaltbau strongly recommends Schnorr Washers or similar to secure the screws The screw
12. exible it is recommended to use an addition al angled bar This way it is possible to compensate mechanical tolerances between the mounting platform for the lower module and the current bars in all 3 axes The use of press nuts in the current bars will simplify installa tion and maintenance Electrical installation of Connect the earthing cable to the earth terminal with the appropriate screw Schaltbau strongly recommends a Schnorr Washer or similar to secure the the earth terminal SEW Commissioning After installation the following checks are recommended a Check the protective earth b Check the main connections C Check the control connections d Check the latching and locking between Upper and Lower Module e Check that both protection covers are fitted f Several activation and deactivation operations of the contactor with out the main circuit active g Check the function of the auxiliary contacts Q Page 18 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT 1130 04 SCHALTBAU Maintenance Recommended regular service intervals Unscheduled service in tervals Inspection activities CT1000 contactors are maintenance free within the rated mechanical life time The electrical life time depends on the number of switchings under heavy load conditions and may vary for different applications In normal use this corresponds to a decade long operating period Checking interval
13. he side Q Page 21 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E N The following steps concerning the ceramic protection insert are for CT1030 04 only The ceramic protection insert is fixed with glue It Cut the glue carefully with a knife and pry it has to be replaced only in case of apparent wear open or damage Remove all remains of old glue Apply glue to the replacement insert use Weicon Flex Super white part number 13650290 only Place the new protection insert in the correct posi tion and push it against the plastic guidance Re move excessive glue The insert must be in line with the plastic surface without projecting length Q Page 22 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E RN Reassembly of the fixed contacts Control the position of the nuts prior to assembly of the new fixed con tacts Replace the fixed contacts and push them into the locked position Retighten the four M5 screws Torque 5 Nm Check that the cable lug is tight Take special care concerning the correct position Take special care concerning the correct position of the wires close to the plastic CT1115 04 of the wires CT1130 04 Reinstall the Lower Module Replace the protection cap for the auxiliary switches Replace the protection cap for the magnetic drive Replace the Upper Module and secure it Reconnect the main cables current bars
14. ic protection insert If the main contacts have to be replaced all 4 contacts must be replaced the moving bridge and the 2 fixed terminals Disconnect the main cables current bars Remove the Upper Module Remove the protection caps Dismount the contactor Remove the moving bridge Remove the nut at the bottom of the contactor with a number 8 socket wrench and put the nut and the washer aside The nut is secured with red locking varnish which will be destroyed during that operation The moving bridge can be pulled out of the guidance Insert the replacement bridge Mount the new bridge from the top and secure it with washer and nut Torque 4 Nm Secure the nut again with red locking varnish Test the replacement bridge Lift the bridge The bridge must be movable up and down easily Q Page 20 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E aan Remove and replace the fixed contacts and ceramic protection insert Put the Upper Module onto the table upside down on a smooth surface The latching levers must be in the closed position to avoid damage Remove all four M5 screws with a number 8 socket wrench and put the screws and washers aside Two screws are secured with red locking varnish which will be destroyed during that operation The fixed contacts must be pushed slightly to the middle to meet the gap and can then be removed easily The copper wire may be pushed slightly to t
15. inals e Inspection of the auxiliary contacts Disconnect the main terminals and remove the Upper Module Remove the protection cover The auxiliary switches are visible for a simple optical inspection from the outside housings are clean and do not show signs of short circuits etc Under normal working conditions no short cir cuit switching the life time of the auxiliary switches exceeds those of the contactors Replace the protection cap and the Upper Module and secure it Reconnect the main terminals Auxiliary switches S870 are not visible when you have removed the cap You will need to remove the 2 screws and lift the assembly for inspection Q Page 19 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 SCHALTBAU Spare parts replacement of parts The contactors are maintenance free There is therefore no general provi sion for replacing components during its service life However in case of permanent heavy load switchings of failures of short circuit switchings or in similar cases spare parts are offered by Schaltbau AN Only original spare parts are to be used as a replacement MC CT1015 04 CT1015 04 terminal with fixed contact order 2 per pole MC CT1030 04 CT1030 04 terminal with fixed contact order 2 per pole CB CT1030 04 CT1015 04 CT1030 04 moving contact bridge order 1 per pole PI CT1030 04 CT1030 04 protection insert order 2 per pole Main contacts and ceram
16. iolations against this will result in the exclusion of liability on the part of the manufacturer e We reserve the right to make technical alterations without prior notice e For updated product information visit www schaltbau gmbh com e Furthermore we refer to our General Terms and Conditions of Sale GCS for Goods and Services Copyright notice Without prior written consent of Schaltbau GmbH the operating instructions are not allowed to be electronically or mechanically reproduced as a whole or in parts be distributed changed transmitted translated into another language or used in any other way Page 4 25 Rev 1 1 User Manual Power contactors series CT 1115 04 and CT1130 04 Table of Contents BEEF OU COIR srona E E E SAEI MIOMA D seas E E AAR El ctica Nazad Speier eE EEEE NETE SAY NOCO S esana E E E E EAE EA General application NOtes cccccccccseeccsseccseeceuceceueeceeecueessusecsueessueesseesseeeseas TECC OALA sree a e E E E a Applied standards sssissisisuunuiisininuioni unnan a ana aia aai D ser pto Mosir aaa anaiai LOWS als 016 8 eee een en eens eee sen een ae eee eee eee Upper Module siete teicicsteecetaidu ania sttientncnteeadasrtenc beniediccatdajmend seeanteatieteaaneadecaseemeseannpnscucdmoneetas F UVAGUION ll description esorare naida ai iaa naria O rel Eea a EE E EE NE E EAE E E eee E E A AE SOIG O eE E E O a E E E EAA EA Ret rn SNIPMEN S sairasisrierseiaininrna iaa E E EEEa ai EEN
17. minals 03 4x NO NC S826 refer to catalogue D26 Flat tabs 6 3 x 0 8 Special versions Page 12 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 E RSN Storage Storage Return shipments Installation Unpacking and handling Schaltbau recommends storing the contactors in the original packing box The contactors should be stored in a dry and suitable place Schaltbau recommends using the original packing box for any return ship ments If no original packing box is available care should be taken to pack the contactor in a way that prevents damage during the shipment Before opening the packaging perform a visual inspection for any signs that could indicate damage having occurred during transport impacts bumps falling etc Unpack the contactor and put it on the table in an upright position With one hand press the release buttons on top of the arc chamber together and turn the 4 levers down one by one to unlatch the Upper Module Lift the Upper Module and put it on the table in an upright position N Remove both protection covers the small one is fixed with a M4 x 10 screw the big one with knurled thumb screws The Lower Module is ready for mounting If the contactor has been subject to excessive shock influ ence e g during transport do not install the contactor Only single pole contactors may be carried holding the Upper Module provided the contactors are safely locked and the
18. mounting position Q Page 10 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT 1130 04 SCHALTBAU Functional description Zero position Main contacts Coil actuation a1 contact well closed b0 contact well opened Typical values The diagram below shows the switching states of the CT1000 contactors Typical pull in time 120 ms Typical drop off time 60 ms Time constant of magnetic drive app 90 ms Settling time for bO switch up to 10 ms 2 E 2 5S gt Meaning O a 6 Ala oO a o pp E Active E ap Closed p Closed Open Page 11 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT 1130 04 SCHALTBAU Example CT1130 04 V 110ET 00 001 Number of poles SS 11 1 pole version Order code Nominal voltage 15 1 5kV 30 3 kV Conventional thermal current 04 400A Mounting position H Horizontal yellow lock bars V Vertical red lock bars Supply voltage 24 24V 110 110V Supply voltage tolerance E 30 25 Coil suppression T Suppressor diode Auxiliary contacts 00 1xat1 S870 refer to catalogue D70 1x bO S870 refer to catalogue D70 M3 screw type terminals 2x NO NC S826 refer to catalogue D26 01 1xa1 S870 refer to catalogue D70 1x bO S870 refer to catalogue D70 Flat tabs 6 3 x 0 8 2x NO NC S826 refer to catalogue D26 02 4x NO NC S826 refer to catalogue D26 M3 screw type ter
19. ndicate the well closed position of the main con tacts EN60077 a1 1 contact to indicate the well opened position of the main con tacts EN60077 b0 2NO NC contacts Option 4NO NC contacts M3 screw or 6 3 x 0 8 mm fast on terminals Protection cap can be removed and fixed only when the Upper Module has been removed Coil terminal group TG Cage clamp terminals Protection cap can be removed and fixed only when the Upper Module has been removed fixation with screw M4 x 10 Upper Module Fixed contacts with main terminals FC Press nuts M10 for easy connection of cables Mounting hole 12 7 mm for easy connection of current bars Minimum wire gauges for connecting cables or current bars must be observed Double break contacts Arc chamber AC Permanent magnetic blow out system with magnets and pole plates Electro magnetic blow out system with blow out coils and pole plates Arc guidance plates Ceramic inserts for arc extinction Latching levers LL Latching and unlatching simply by turning pole plates No tool required Large handles for easy operation Lock bars LB Simple locking and unlocking mechanism with optical control No tool required for unlocking The Upper Module must be latched and completely locked before starting operation Red bars indicate contactors for vertical mounting posi tion Yellow bars indicate contactors for horizontal
20. odule Lower Module CT1000 contactors consist of two main modules Lower Module Magnetic drive MD with moving contact bridge MC not visible base plate BP auxiliary contact group AG coil terminal group TG AG and TG are under protection caps Upper Module Fixed contacts with main terminals FC arc chamber AC latch ing levers LL and lock bars LB Lower Module Magnetic drive MD with moving contact bridge MC Compact magnetic drive system for DC voltages Designed for standard railway supply voltages and tolerances Standard nominal supply voltages are U 24 V and U 110 V tolerances from 70 up to 125 of U Other nominal supply voltages are available on request Double break moving contact bridge Polarity independent overvoltage protection device The value of the overvoltage limitation is part of the magnetic system and must not be changed or short circuited by external means It is explicitly stated that the use of diodes is prohibited for that purpose Take care there is no such diode in the external control circuit Base plate BP 4 fixation holes Earthing terminal The contactor should be mounted on a metal rack to provide a se cure mounting as well as a heat sink for the magnetic drive Page 9 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT 1130 04 SCHALTBAU Auxiliary contact group AG Standard 1 contact to i
21. s must be tightened with the rat ed torque permissible for the screws and the nuts Mechanical requirements Device dimensions Refer to the dimensioned drawings of the contactors Installation dimensions Refer to the dimensioned drawings of the contactors Q Page 14 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT 1130 04 SCHALTBAU Electrical requirements Mechanical installation The minimum clearances to earth or other components must be observed Refer to the dimensioned drawings for details Switching electrical currents at high voltages will produce arcing and plasma may exit out of the arc chambers It is essential to observe the minimum clearance to earth and to the connecting bus bars to avoid the risk of a flash over The minimum clearance has been tested and specified in relation to the switching capacity of the contactors For switching heavy loads allow a minimum time of app 30 s between switchings Allow a recovery time of at least 10 min after 3 heavy load switchings in succession Ensure sufficient ventilation especially in the case of heavy arc switching Allow the exchange of surrounding atmosphere to avoid the risk of flasho vers and excessive corrosion The minimum gauges for the main terminals and the earth terminal must be observed Schaltbau strongly recommends current bars for the connection of the main terminals with a cross section of 40 x 4 mm If wires are being used the wire g
22. spection of main contact tips easy replacement of main contacts o Easy replacement of arc chamber upper module Drive system suitable for standard railway supply voltages and tolerances No economy circuit required for standard versions Drive systems for industrial applications on demand Insulation coordination o Functional insulation for main circuit o Basic insulation between main circuit and protective earth o Reinforced insulation between main circuit and control circuit main circuit and auxiliary circuits Long mechanical and electrical life No regular maintenance required Inspection intervals and exchange of wear parts depending on specific application Q Page 6 25 Rev 1 1 User Manual Power contactors series CT1115 04 and CT1130 04 SCHALTBAU Safety information Electrical hazards Safety notices General application notes CT1000 contactors are high voltage switches Getting into contact with conductive parts of the contactors can result in serious injury or even death Active parts are all piece parts associated with the main cir cuit All metal parts visible may potentially become active un der fault conditions A respective label is attached to the con tactor This label must not be removed For safety reasons the contactors must be connected to earth An earth terminal is provided for that purpose The wire gauge must be observed according to the specific short circuit conditions
23. try standards Connectors to suit the special requirements of communications engineering MIL connectors Charging connectors for battery powered machines and systems Connectors for railway engineering including UIC connectors Special connectors to suit customer requirements Snap action switches with positive opening operation Snap action switches with self cleaning contacts Enabling switches Special switches to suit customer requirements Single and multi pole DC contactors High voltage AC DC contactors Contactors for battery powered vehicles and power supplies Contactors for railway applications Terminal bolts and fuse holders DC emergency disconnect switches Special contactors to suit customer requirements Equipment for driver s cab Equipment for passenger use High voltage switchgear High voltage heaters High voltage roof equipment Equipment for electric brakes Design and engineering of train electrics to customer requirements We reserve the right to make technical alterations without prior notice For updated product information visit www schaltbau gmbh com
24. uciform screw driver size 1 to remove the screws 2 for each switch on the bottom of the frame Mount the replace switch in the same mounting position Do not forget the washers Reassembly of the switch subassembly After all switches have been replaced and the frame has been adjusted to a rectangular position the subassembly can be carefully reinserted in to its original mounting position Make sure to mount it in the correct same position as before Tighten the 2 Allen head screws M4 The 2 knurled thumb screws should be just turned once Do not forget the washers The actual version may differ from the photos Standard ver sions are 4x 826 and 2x S826 2x S870 as shown for CT1130 08 same for CT 1115 04 and CT1130 04 Reinstall the Lower Module Replace the protection cap for the auxiliary switches Replace the protection cap for the magnetic drive Replace the Upper Module s and secure it Reconnect the main ca bles current bars with compliments UVE R IS Ss 5 ISO 9001 2000 g BUREAU VERITAS BUREAU VERITAS a Certification Certification Certification Schaltbau GmbH The production facilities Schaltbau GmbH Schaltbau GmbH manufactures in of Schaltbau GmbH have has an environment has a quality manage compliance been IRIS certified since management system ment system that has with RoHS 2008 that has been certified been certified since 1994 since 2002 Connectors manufactured to indus

Download Pdf Manuals

image

Related Search

Related Contents

Owner`s Manual • Manual del usuario • Guide de l  Delta 144984-OB-A Installation Guide  BEA IS40 User's Manual  Manuale Tecnico GOLD rev.1.3  

Copyright © All rights reserved.
Failed to retrieve file