1. PRIMEXTM 3 PC 1000 Specifications 3 5 Power inputs The controller is designed to run on 120 VAC control power lt is internally fused and protected with a MOV transient protector It uses a transformer isolated regulated power system with the following specifications Input voltage 120 Volt A C or 15 50 to 70 Hz Maximum current 0 25 Amps 4 0 CONNECTOR PIN DEFINITIONS CONNECTOR J1 PIN FUNCTION 1 OFF FLOAT INPUT 2 GROUND 3 LEAD FLOAT INPUT 4 GROUND 5 LAG FLOAT INPUT 6 GROUND 7 HIGH ALARM FLOAT INPUT 8 GROUND 9 PUMP 1 SEAL FAIL SENSOR INPUT 10 GROUND 11 PUMP 2 SEAL FAIL SENSOR INPUT 12 GROUND 13 PUMP 1 TEMPERATURE FAIL SENSOR INPUT 14 GROUND 15 PUMP 2 TEMPERATURE FAIL SENSOR INPUT 16 GROUND CONNECTOR J2 PIN FUNCTION 1 120 VAC HOT POWER TO CONTROLLER 2 120 VAC NEUTRAL POWER TO CONTROLLER 3 CHASSIS GROUND 4 HIGH ALARM LIGHT NEGATIVE CONTACT 5 HIGH ALARM LIGHT POSITIVE CONTACT 6 SEAL FAIL RELAY CONTACT 7 SEAL FAIL RELAY CONTACT 8 RUN INPUT 2 CONNECT TO AUX CONTACT STARTER 1 9 MUTE SWITCH INPUT 10 ALARM HORN NEGATIVE CONTACT 11 ALARM HORN POSITIVE CONTACT 12 GROUND 13 RUN INPUT 1 CONNECT TO AUX CONTACT STARTER 1 14 POWER TO MOTOR STARTER 2 15 POWER TO MOTOR STARTER 1 16 120 VAC HOT MOTOR STARTER POWER Notes Header and plugs use copper conductors only Torque requirement for plugs 1 47 Ft Lbs Unit operates at Pollution Degree 2 PRIMEX 4 PC 1000 Specific
2. 000 ohms then the seal fail indicator for that pump will be turned on This action does not disable the pump however it does demote the pump to the lag position in the alternation order The pump controller has two inputs for pump temperature sensors If the controllers detects a short between these inputs and ground then a temperature failure condition does not exist If the short to ground is removed then a temperature failure condition exists and the pump associated with that in put will be disabled and the Temp Fail indicator illuminated This condition does not latch up and will return to normal if the short to ground is reestablished All of the float and sensor inputs are transient protected and filtered to prevent electrical interference from causing improper operation PRIMEX 2 PC 1000 Specifications The controller has two switches that select what mode the two pumps are in These HOA switches have the following function H When in HAND the pump will be constantly called to run O When in OFF the pump will be off A When in AUTOMATIC the pumps will be called by the pump controller The Hand and Off functions of these switches will operate even if the controller is off or has failed The controller has a switch that is used to select the lead pump When this switch is in the center position ON then the two pumps will alternate as lead pump each pump cycle When in the 1 2 po sition then pump one is the lead and when in the 2 1
3. PO 0 0 OO DUPLEX PUMP CONTROLLER User Manual O 2easace7sderr92 Ashland OH 800 363 5842 LL PP lt 22 50349 1005 Detroit Lakes MN 888 342 5753 WWW PRIMEXCONTROLS COM Milford OH 513 831 9959 PN 1038549A 2013 SJE Rhombus Rev 09 13 PRIMEX is a trademark of SJE Rhombus PO OoO0O 1 0 INTRODUCTION The model PC 1000 is a float switch based duplex pump controller intended primarily for wastewater lift station and other pump down applications lt includes sensor inputs for the seal fail and tempera ture fail sensors for most submersible pumps lt connects to four switches to measure the tank level and has out puts to control two pumps an alarm horn a seal fail light and a high alarm light It has built in HOA hand off auto switches and pump running lights A lead pump selector switch permits either pump to be selected as lead pump or alternation can be selected causing the pumps to alter nate as lead The PC 1000 uses removable terminal strips to make replacement in the field guick and easy With the addition of an enclosure circuit breakers and motor starters the PC 1000 makes a complete low cost lift station controller 2 0 OPERATION The PC 1000 uses four normally open floats as level sensing inputs so when the tank is empty all of the floats are open On rising water the Off float closes first which causes the controller to take no action The Lead float will close next as the water rises The controller wi
4. ations FIG 1 4 600 SSSSSSSSSSSSSSSS 009 0 1 500 22 5 4 8 12 9 3 2 x z 2 2 ALARM o ALARM 2 b LET Pela HORN a LIGHT lt 7 000 O GO a O PUMP 1 ON 1 2 ALTERNATE h PC 1000 NN DUPLEX PUMP CONTROLLER FLOATS SEAL FAIL TEMP FAIL 0085 PRIMEXTM 0 Lod 009 0 PC 1000 Specifications 230 VAC 3 PHASE O CB3 10A ALARM LIGHT N Z 1 J2 PC1000 DUPLEX FLOAT SWITCH CONTROLLER FLOATS SEAL FAIL TEMP FAIL OFF LEAD LAG HIGH P1 P2 P1 P2 1 213 475 677 8 9 10 1112 1314 15 16 SSSSSSSSSSSSSSSS a L 2 2 P1 P2 OFF LEAD LAG HIGH LEAK LEAK TEMP TEMP FLOAT FLOAT FLOAT FLOAT SENSOR SENSOR SENSOR SENSOR DRAWN BY PAGE 1 DWG NO DATE DWG NAME DUPLEX 230V 3P 5 HP 21 FLA PC1000 CONTROLLER PRIMEX PC 1000 Specifications
5. ll then turn on the lead pump If this pump causes the water level to fall the lead pump will be turned off when both the Lead and Off float are out of the water and open If the lead pump is not sufficient to control the water level then the lag pump will be started when the Lag float closes The two pumps will not be turned off until the Lag Lead and Off floats are out of the water and open at which time all pumps will be turned off The controller has delays built into the software which will insure that whenever a pump is turned on the second pump cannot come on for at least 8 seconds Another delay insures that when a pump is turned off the other one cannot turn off for 4 seconds These delays help insure smooth pump opera tion and prevent excessive electrical surges The last float input is for the High float Whenever the high float is under water closed then the high alarm condition is set When a high alarm condition is set the alarm light will flash on and off and the horn will be activated The horn can be silenced using an external mute button connected to pin j2 9 Both the alarm light and horn will turn off when the high float input opens The PC 1000 has an alarm test button on the front panel which can be used to test the alarm horn and light The pump controller has two inputs for pump seal fail leak sensors one for each pump These inputs measure the resistance between the input and ground If the resistance is less than 50
6. position pump two is the lead The controller has two inputs which should be connected to the auxiliary switches on the two motor starters These inputs when shorted cause the pump running indicators to be illuminated Using these inputs may eliminate the need for panel mounted pump running lamps 3 0 SPECIFICATIONS 3 1 Float and Sensor Input There are four float inputs two leak sensor inputs and two temperature fail inputs They use current limiting resistors and a zener diode for transient protection They also have a resistor capacitor filter as well as a software filter to avoid electrical interference They have the following specifications Short circuit current less than 2 mA Open circuit voltage 5 0 VDC 3 2 Aux contact inputs There are two sets of inputs for the auxiliary contacts on the motor starters When these inputs are shorted the pump running lamps are illuminated These inputs have the following specifications Short circuit current less than 2 mA Open circuit voltage 12 0 VDC 3 3 Relay outputs There are three form A SPST relay outputs Two are to call the pumps and one for the seal fail They have the following specifications Maximum current at 120 VAC 5Amps with a resistive load Maximum voltage 140 Volts 3 4 Driver outputs There are two 12VDC driver outputs They are used to drive the alarm light and alarm horn which must be 12VDC devices or 12VDC relays They can drive a maximum of 100 MA

Download Pdf Manuals

image

Related Search

PC 1000 pc 1000 pc 1000 dollars pc 10000 pc 1000 euro pc 1000 fps pc 1000 reais pc 1000w pc 10000$ pc 1000 euro gaming pc 1000 diversion pc 1000 eligibility pc 10000 euro

Related Contents

Sony XM-2100GTX Car Audio Amplifier  Sunbeam Fan FA7400 User's Manual    Samsung P50FP Brugervejledning  Philips Forecast Radius  Abrégé du mode d`emploi pour les contributeurs arras.cef.fr  京都市火災予防条例運用基準(PDF形式, 8.99MB)  Bulletin CA71  Anti-blackout system for grid connected solar  Samsung SC21F50HD שואב נגרר יוקרתי, 450 וואט יניקה מדריך למשתמש (Windows 7)  

Copyright © All rights reserved.
Failed to retrieve file