Data Sheet DB EN IB IL 24 DI 4-ME
Contents
1. IB IL 24 DI 4 ME Inline Terminal With Four Digital Inputs Data Sheet 703500 04 2004 Function The terminal is designed for use within an Inline station It is used to acquire digital input signals Features Connections for four digital sensors Connection of sensors in 2 and 3 wire technology Maximum permissible load current per sensor 250 mA Maximum permissible load current from the terminal 1 0 A Diagnostic and status indicators Figure 1 IB IL 24 DI 4 ME terminal men PHCENIX CONTACT 5550B001 7035A001 IB IL 24 DI 4 ME Local Diagnostic and Status Indicators Des Color Meaning D Green Diagnostics Status indicators of the inputs Terminal Assignment Point Segment voltage Us for 2 and 3 wire termination for 3 wire termination Signal input 3 IN 3 Signal input 4 IN 4 Ground contact GND 7035A002 Figure2 IB IL 24 DI 4 ME PH NIX 703500 CONTACT IB IL 24 DI 4 ME Internal Circuit Diagram Protocol chip bus logic including voltage conditioning Local bus Key LED status indicator U ac Optocoupler Digital input Electrically isolated area Ss ale iat de He 24 V Ug c avu COEEE H alte C 3 a 5550C003 Figure 3 Internal wiring of the terminal points 703500 PHCENIX CONTACT IB IL 24 DI 4 ME Connection Example VAN See ereett
2. a Order Designation IB IL 24 DI 4 ME Housing dimensions width x height x depth 12 2 mm x 120 mm x 71 5 mm 0 480 x 4 724 x 2 815 in Permissible humidity operation 75 on average 85 occasionally Permissible air pressure operation 80 kPa to 106 kPa up to 2000 m 6562 ft above sea level Permissible air pressure storage transport 70 kPa to 106 kPa up to 3000 m 9843 ft above sea level Degree of protection IP20 according to IEC 60529 Class of protection Class 3 according to VDE 0106 IEC 60536 Power Consumption 703500 PHGNIX T7 CONTACT IB IL 24 DI 4 ME Power Consumption segment supply voltage Us 24 V DC nominal value Nominal current consumption at Us 1 0 A maximum Supply of the Module Electronics and I O Through Bus Terminal Power Terminal Connection method Through potential routing Digital Inputs Input design According to EN 61131 2 Type 1 Definition of switching thresholds Maximum low level voltage Ui max lt 9 V Minimum high level voltage Uumin gt 15 V Common potentials Segment supply ground Nominal input voltage Uy 24V DC Permissible range 30 V lt Uj lt 30 V DC Nominal input current for UIN 3 mA minimum Permissible cable length to the sensor 30 m 98 48 ft to ensure conformance with EMC Directive 89 336 EEC Use of AC sensors AC sensors in the voltage range lt Uy are limited in application corresponding to the input design Characteristic Curve Curren
3. eemmivonsene When using the IB IL PD terminals the 24 V sensor supply voltage is provided by the potential jumpers Us of the Inline station IB IL 24 DI 4 ME IB IL PD 24V IB IL PD GND J 0 1H 1H agde mini aga 2 2 2 212 2 Soo 44 OoO 0 O1 0 oO 37 AO mA ry L Me We lethal ala 2 4 24 V OIQOIQO A B 7035A003 Figure 4 Typical sensor connections A 3 wire termination B 2 wire termination 4 PHGNIX 703600 CONTACT IB IL 24 DI 4 ME The sensors can also be connected via external bus bars Ensure that the sensors and Us are supplied from the same voltage supply External 24 V External L 7035B004 Figure 5 Typical connection of sensors when using external bus bars 703500 PHGNIX 5 CONTACT IB IL 24 DI 4 ME Programming Data Process Data Configuration Data INTERBUS BE a a Lengh code Input address area Output address area Parameter channel O bits PCP Assignment of the Terminal Points to the IN Process Data Register length bus Byte bit Byte Bit 0 3 0 2 10 1 view Terminal point 2 4 1 4 2 1 1 1 signal Terminal point 2 5 1 5 2 2 1 2 24 V Other Bus Systems Terminal point 2 6 1 6 2 3 1 3 GND Status LED 4 3 2 J1 indicator PH NIX 703500 CONTACT IB IL 24 DI 4 ME Technical Data General Dat
4. gic 24 V supply I O 500 V AC 50 Hz 1 min 24 V supply I O functional earth ground 500 V AC 50 Hz 1 min Error Messages to the Higher Level Control or Computer System None PHGNIX 703500 CONTACT IB IL 24 DI 4 ME Ordering Data Terminal with four digital inputs IB IL 24 DI 4 ME 28 63 92 8 including connector and labeling field pack of 4 Configuring and Installing the INTERBUS IB IL SYS PRO UME 27 43 048 Inline Product Range user manual Accessories Terminal for potential distribution 24 V IB IL PD 24V PAC 28 62 98 7 including connector and labeling field Terminal for potential distribution GND IB IL PD GND PAC 28 62 99 0 including connector and labeling field Phoenix Contact GmbH amp Co KG Flachsmarktstr 8 32825 Blomberg Germany 49 0 52 35 3 00 49 0 52 35 3 4 12 00 Za www phoenixcontact com amp Worldwide Locations www phoenixcontact com salesnetwork PHCENIX CONTACT 703500 Phoenix Contact 04 2004 Technical modifications reserved TNR 90 20 82 4
5. t Depending on the Input Voltage and the Ambient Temperature T Supply Input Current Input Current According to t gt 20 s Voltage With T 25 C 77 F With Ta 55 C 131 F The current is reduced depending on the ambient temperature Ta and the number of inputs that are switched on internal module temperature PH NIX 703500 CONTACT IB IL 24 DI 4 ME Power Dissipation Formula to Calculate the Power Dissipation of the Electronics 4 Pe 0 24 W x Un X 0 003 A Total power dissipation in the terminal Index of the number of set inputs n 1 to 4 Input voltage of the input n Power dissipation of the housing Pyoy 0 6 W maximum within the permissible operating temperature Limitation of Simultaneity Derating Derating No limitation of simultaneity no derating Safety Equipment Surge voltage Protective circuits of the power terminal Polarity reversal Protective circuits of the power terminal 703500 PH NIX 9 CONTACT IB IL 24 DI 4 ME Electrical Isolation Common Potentials The 24 V main voltage 24 V segment voltage and GND have the same potential FE is a separate potential area Separate Potentials in the System Consisting of Bus Terminal Power Terminal and I O Terminal Test Distance Test Voltage 5 V supply incoming remote bus 7 5 V supply bus logic 500 V AC 50 Hz 1 min 5 V supply outgoing remote bus 7 5 V supply bus logic 500 V AC 50 Hz 1 min 7 5 V supply bus lo