1. eee button Remove the 2 screws from the housing and open it Electronic The settings are done with the button located on the electronic board board see photo beside Principle By pressing on this button for more than 3 seconds you can validate the setting and go to the next setting By pressing quickly on this button you can incrementa value and scroll down the different options or values This button enables 1 to activate deactivate an alarm set point a ee 2 to program the action of the alarm icising falliaghequlation actioni 3 to set the set point value Oe 4 to set the time delay feemporisalion _ Toset the different options 1 Activating deactivating the alarm After pressing the set point configuration button for more than 3 seconds will be displayed Ahen AL GFFOr depending on the last configuration of the transmitter Afterwards by briefly pressing on this button you can switch between JAL on 1 alarm on and AL GFF alarm off To validate your choice press again for 3 seconds If you chose AL JFF then you will exit the configuration mode and switch back to the measurement mode If you chose 1 47 you will move to the next parameter OFF rt 2 Programming the action of the alarm rising falling regulation action Rising action 1 set point the alarm will activate when the me
2. 50 C standard model 20 to 80 C duct mount and remote sensor Unit of measurement 0 0000 C F Example HST A Accuracy asia hice Fae diedacheicnssnncdmocteeses 1 of reading 0 4 C in the range 5 to 80 C Model humidistats HST with a duct mount probe 2 of reading 0 6 C in the range 20 to 5 C Response time cccceceeen 1 e 63 15 s Standard Resolution 0enn 01 C Type Of fluid ce cceeeeeeneees air and neutral gases E Features of the housing Housing ss nice tesosasuinisenescustionesnpeienecanitonss ABS Fire proof claSS ccccccseeeeeees HB as per UL94 DIMENSIONS c ccccscesecseeseeeeeeeeeeees see drawing beside Protection oo cccccecccecsecseeseeteeeeees IP 30 standard model IP 65 duct mount and remote sensor Display 5 digit LCD Dimensions 50 x 15 mm Duct mount Alternating display of humidity and temperature n gt eee Height of the digits 0 0 0 0 10 mm 0 Cable grip ou ecccceececeeeeseeeeeeees for cables 7 mm max Weight c ccc ceeeeeteseeeeeeeeeees 145 g E Technical specifications Output occ eeeeeeeee 1 RCRrelay 3A 230 Vac Relay and alarm status red LED in front Set point 2 configurable set points C and RH Power Supply ccceeeeeeeeee 24 Vac Vdc 10 Consumption ccccceeeeees 2VA Electro magnetical compatibility EN 61326 Electrical connection Screw terminal block
3. KIMO Bieieabbrcrsacc INSTRUMENTS Pressure Temperature Humidity Air Velocity Airflow Sound level Humidistats aa HST standard H ST C 4 IP30 e Measuring ranges from 0 to 100 RH and 0 to 50 C 20 to 80 C e RCR relay 3A 230Vac Power supply 24Vac Vdc e Visual alarm red LED in front e P65 and IP 30 ABS housing with display e Alternating display of humidity and temperature e Quick and easy mounting with the 1 4 turn system with wall mount plate I A h remote E Features of the transmitter HST aly Humidity duct Gi Working principle the measurement of temperature and humidity is made mount IP 65 by only one digital component CMOS complementary metal oxyde ed E semiconductor including a capacitive element and a thermistor This technology guarantees an excellent stability in the long term along with a great accuracy of the measurement Measuring range ccceceeeees 0 to 100 RH Unit of measurement 00 RH W Part number Accuracy ern 2 of reading 2 RH in the range of 10 to 90 RH To order Just add the code to complete the part number Response time ccccceeeseereeeees 1 e 63 4 s Probe Resolution 0 cece seen 0 1 RH A Standard Type of fluid ce ceteeeeceee air and neutral gases Duct mount Remote Temperature Measuring range 0 to
4. asure exceeds the set point and will stop when the measure goes below the set point Falling action 1 set point the alarm will activate when the measure goes below the set point and will stop when the measure goes above the set point Regulation mode 2 set points the set point values will determine the action type Two possibilities are available Measurement set point 1 gt set point 2 TE set point 2 gt set point 1 oD rr A O setpoint ll Ean A eee set point 2 Alarme set e set point 2 lt T gt Time delay Time set point 1 Time Measure gt set point 1 Alarm activation Measure lt set point 1 Alarm activation Measure lt set point 2 Alarm stop Measure gt set point 2 Alarm stop set point 2 lt Measure lt set point 1 No change set point 1 lt Measure lt set point 2 No change Press the button for 3 seconds to confirm your choice You will then move on to the last parameter 3 Programming the set point value The set pointis a limit which when being reached and or exceeded activates the relay and the visual red LED alarm The first digit will start to blink by briefly pressing on the button you can choose if the set point will be either positive 0 or negative Then press the button during 3 seconds to confirm your choice The second digit will start to blink Press the button briefly to change the value Then press the b
5. for cables 1 5mm max Connection to PC Kimo RS 232 cable Working temperature housing 0 to 50 C Working temperature probe 0 to 50 C standard model 20 to 80 C duct mount and remote sensor Storage temperature 10to 70 C Environment air and neutral gases All the accuracies indicated in this technical datasheet were stated in laboratory conditions and can be guaranted for measurements carried out in the same conditions or carried out with calibration compensation Connection l Relay O Set point c NC Normally closed Y setting button DIP switch COM vissiin Common yer LO NO oasian Normally open Connection to PC Power supply via LCC 100 software 6 Vdc direct voltage D GND ground a VAC wees alternative voltage phase Relay OF Vac alternative voltage neutral terminal block Cable grip to insert the cable it is required to slightly cut the rubber Power supply terminal block De Cable grip E Electrical connections as per norm NFC15 100 This connection must be made by a qualified technician To make the connection the transmitter must not be energized NC Rela aiid COM Power supply block NO LO 24 Vac Class ll Power supply Vdc terminal block GND Neutral Phase Power supply 24 Vac E Configuration Conf
6. ia software with the optional LCC100 software I I H I 2 An easy and friendly way to configure 3 1234 You can configure the measuring units the set point the time delay n 4 Switch 2 For all the parameters humidity and temperature Switch 1 magaya e In order to balance an eventual drift of the transmitter you can add an offset to the value displayed by the HST gt example the HST indicates 48 RH the standard reference indicates 45 RH gt via the LCC100 you can add an offset of 3 to the value To access the configuration via software you must first position the DIP switches as per the following picture shown beside and then connect the cable to the transmitter see connection drawing Please refer to the user manual of the LCC 100 to make the configuration A Caution The configuration can be made either via switch or via software you can not combine both solutions E Mounting Installation mount the ABS plate on the wall this plate is supplied with the transmitter Drilling 6 mm with the screws and pins supplied with the transmitter Insert the transmitter into the plate see points A of the drawing shown beside by tilting it at 30 Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed For the model with remote sensor an additional drilling of 814 mm must be done before mounting the pla
7. iguration of measuring units set points can be carried out different ways DIP switch push button and or software connections and on the drawing connection Configuration of measuring units by DIP switch 4 F To configure the transmitter please unscrew the 2 screws from the housing ne A m oe and then open it To configure the transmitter it must not be Identification of the DIP switches energized Then you can make the settings Electronic board on the electronic board required thanks to the DIP switches as shown on the drawing beside DIP switch 1 When the transmitter is configured you can 2 power it up 3 1 234 4 DIP Caution DIP switch 2 Inactive Please follow carefully the combinations beside with the switch 1 DIP switch Seting of units If the combination is wrongly done the following message will appear on the display of the transmitter CONF ERROR On off switch In that case you will have to unplug the transmitter replace the DIP switches correctly and then power the transmitter up gt Setting Of units ee Configurations To set the measuring unit please put the on off switches e 3 and 4 as shown beside Combinations Set points configuration with the push button Set point Power the transmitter up it will then display its current configuration PN Pr configuration To modify the configuration please proceed as follows
8. r on the right of the screen is relative to the unit of measurement ex from 500 to 1000 Pa 2 The status of the alarm 4 The set point alarm on When the alarm is off the following message is displayed f49F This message is displayed ex 258 which means that the alarm When the alarm is on the following message is displayed PLOR will be activated as soon as the Mmeasuremeni exceeds this value e When the alarm is off the transmitter displays which confirms If you chose regulation mode the second set point will appear the end of initialization and that you can start the measurements e When the alarm is on the transmitter displays the parameters relative to 5 The time delay alarm on the relay set point program of the alarm time delay This message is displayed 5 amp The temporisation is in seconds from 0 to 60 sec 3 Action of the alarm rising or falling action ae OEE ee If the relay is programmed in rising action the following message is displayed a A a a If the relay is programmed in falling action the following message is displayed 4 ih measuremeni This message is displayed ex 258 which means that the alarm If the relay is programmed in regulation mode the following message is displayed mime Configuration v
9. te E Maintenance Please avoid any aggressive solvent Please protect the transmitter and its probes from any cleaning product containing formol that may be used for cleaning rooms or ducts E Options E Optional accessories m Power supply class 2 input 230 Vac output 24 Vac ref KIAL 100A Stainless steel sliding connection PC connection gland Stainless steel clamp Wall mounting plate for remote humidity probe with connection RS 232 cable E mn E Configuration software LCC 100 supplied m ABS clamp with connection gland 7 T E E Ref FT ang HST 10 06 C We reserve the right to modify the characteristics of our products without notice EXPORT DEPARTMENT Tel 33 1 60 06 69 25 Fax 33 1 60 06 69 29 e mail export kimo fr
10. utton during 3 seconds to confirm your choice Repeat this sequence until you have reached the last digit and then confirm the set point If you selected regulation mode you will program the second set point 4 Setting of the time delay dead band temporisation 60 sec max When the set point is reached and or exceeded the time delay will wait the specified time before energizing the relay if the set pointis still reached and or exceeded When the first digit starts blinking press briefly on the button to change the value Then press the button during 3 seconds to confirm your choice Repeat the process until all digits have the desired value and press the button for 3 seconds to confirm 3 your choice The programming is now done and the display switches back to the measurement mode 3 Initialization of the transmitter When the transmitter is powered up it initializes and displays the digits 2 0 and then its configuration including the measuring range 3 action of the alarm rising falling or regulation action 2 the status of the alarm 4 the set point 5 time delay dead band temporisation 1 The measuring range The following message is displayed _4 _ This is the low value of the measuring range and its digit value ex _ 998 The following message is displayed 4 This is the high value of the measuring range and its digit value ex 80a The arrow displayed at the bottom o