Home

Display - Service, Support

image

Contents

1. 8 7 6 5 4 3 2 1 ee AREA CLASSIFICATIONS 1 NO REVISION TO DRAWING WITHOUT PRIOR FM APPROVAL 2 FOR INSTALLATIONS IN THE U S THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE FM APPROVED HAZARDOUS AREA UNCLASSIFIED AREA 3 FOR INSTALLATIONS IN CANADA THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE CANADIAN CERTIFIED INTRINSICALLY SAFE GAS 3 ORDINARY LOCATION 4 FOR ZONE INSTALLATIONS THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE ATEX IEC CERTIFIED CLASS 1 DIVISION 1 II Ill GROUPS A B C D E F D 5 ASSOCIATED APPARATUS AND FIELD DEVICE MANUFACTURER4ES INSTALLATION DRAWING MUST BE FOLLOWED CLASS 1 ZONE 0 WHEN INSTALLING THIS EQUIPMENT 6 INSTALLATIONS IN THE U S SHOULD BE IN ACCORDANCE WITH ANSI ISA RP12 06 01 INSTALLATION OF FARER TOR ae tet CLASS L I III DIVISION 2 GROUPS A B C D E F G INTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS CLASSIFIED LOCATIONS6 AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE ANSI NFPA 70 NON SPARKING 7 INSTALLATION IN CANADA SHOULD BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CLASS 1 ZONE 2 IIC C22 1 CANADIAN ELECTRICAL CODE PART 8 ZONE INSTALLATIONS SHALL BE IN ACCORDANCE WITH LATEST ED
2. 37 of 50 9 Specifications System EEE Platform Compliance Fully compliant HART 7 1 device complies with HART 7 1 Wireless Adapter device type Backward compatible to HART 5 devices HART Sub Devices Supports up to 8 wired HART sub devices maximum number depends on multi drop installation Radio A _ OA AAA Range Operating Frequency 2 4 GHz to 2 4835GHz 16 Channel frequency hopping Modulation of Channels RF Output Power 10dBm 10mW Series Loop Voltage Drop 1 0VDC 2 5VDC user settable in 0 5VDC steps Series Loop Operating 3 2 ma to 25 mA DC operating Protected against overvoltage over current and Current reverse connections Ext Power Operating Voltage 7VDC to 32VDC Reverse voltage protection Ext Power Operating Current Typical lt 1mA Max 20 mA HART Output Level Fully HART compliant trapezoidal wave 1200 2200 Hz Multi Drop Direct Power 32mA DC maximum 8 devices at 4mA DC Multi Drop Loop Power 24mA DC maximum 6 devices at 4mA DC Loop Current Monitoring and 4 0mA to 20mA DC Accuracy 1 FSR 40C to 85C Environmental Operating Temperature Hazardous Location Temperature Class T5 40 C to 85 C Temperature Class T6 40 C to 75 C Operating Temperature General Purpose 40C to 85 C Ordinary Location Humidity relative Storage Temperature 100 40 C to 85 C 100 SS 40 Cto 85 C A AAA Height 100 mm 3 9 Diameter 60 8 mm 2 4 Weight 0 46 kg 1l
3. 4 4 4 Clear All Alerts method This will clear the entire alert history for the SITRANS AW210 4 4 5 ALERT Direct Power Out of Range Description The SITRANS AW210 is configured for Direct Power Mode and the voltage on the Direct Power input is outside of the allowable operating range for the SITRANS AW210 Corrective Action Correct the Direct Power source supply Timestamps Start Set when the alert is first detected Stop Set when the alert state goes away 4 4 6 ALERT Loop Power Out of Range Description The SITRANS AW210 is configured for Loop Power Mode and the current on the loop power connection is outside of the allowable operating range for the SITRANS AW210 Corrective Action Correct the loop power supply Timestamps Start Set when the alert is first detected Stop Set when the alert state goes away 4 4 7 ALERT Temperature Out of Range Description The electronics temperature inside of the SITRANS AW210 is outside of the allowable operating range for the SITRANS AW210 DM1101020UBB Copyright 2012 27 of 50 Corrective Action Ensure that the SITRANS AW210 is installed in an environment with its environmental operating range Timestamps Start Set when the alert is first detected Stop Set when the alert state goes away 4 4 8 ALERT Power Mode Miss configured Description The power mode detected on the inputs for the SITRANS AW210 currently does not match the powe
4. E e o a NOTE 1 CD Y A E AA 0O i CURRENT LOOP RETURN WHITE i HART YELLOW zs mel SIGNAL WIRE COLOR NOTE 1 ISOLATE BLACK LEAD WIRE FIGURE 25 Configuration 1 SITRANS AW210 inserted into the current loop between the power source positive terminal and the FIELD DEVICE positive current loop terminal L1 DM1101020UBB Copyright 2012 14 of 50 FIELD DEVICE CURRENT LOOP CONNECTIONS LI L2 GROUNDING CONNECTION v EARTH GROUND GRN YEL Y _ DIRECT POWER BLACK a CURRENT LOOP LOOP POWER RED cil DAL T UD dD tz RETURN WHITE e CURRENT LOOP Perre ha HART YELLOW me SIGNAL WIRE COLOR NOTE 1 ISOLATE BLACK LEAD WIRE FIGURE 26 Configuration 2 SITRANS AW210 inserted into the current loop between the FIELD DEVICE negative current loop terminal L2 and the power source negative terminal 3 3 4 SITRANS AW210 with HART Field Devices in Multi Drop Mode The SITRANS AW210 can support up to a maximum of eight 8 wired HART enabled Field Devices These can be any combination of either input or output wired HART enabled Field Devices The maximum number of wired HART Field Devices that any loop can support is installation dependent The actual number of allowed Field Devices on any loop is restricted by the insertion voltage drop of all Field Devices wire losses and minimum Loop Power Source voltage 3 3 5 SITRANS AW210
5. Set the Power Configuration for the SITRANS AW210 EO OS From the Main DD screen select Configure Select Guided Setup Select Configure Power Mode Follow the on screen instructions and select the proper power configuration for the application Configure Burst settings le 2 3 From the Main DD screen select Configure Select Manual Setup Burst Settings Set the Automatic Burst Mode to the desired update rate recommended or set this to disabled If not using the Automatic Burst Mode manually set the burst mode configuration for each Burst Message Note Sub devices must be detected before configuring the manual Burst Mode configuration Transfer the updated information to the SITRANS AW210 by clicking on the Send or Transfer button Configure WirelessHART Network settings AI on From the Main DD screen select Configure Select Guided Setup select Join Device to Network Follow the on screen instructions and enter in the WirelessHART Network ID and join key After accepting the settings the SITRANS AW210 will attempt to join the network if the WirelessHART gateway is in range Monitoring WirelessHART Network join status 1 2 3 From the Main DD screen select Service Tools Select Communications Wireless Status Monitor the progress of the WirelessHART join If Join Failed under Join Status becomes set check the Network ID and Join Key that were used t
6. 12 INSTALLATION OF EXISTING FIELD DEVICE MUST FOLLOW MANUFACTURERS INSTALLATION DRAWINGS CONNECTION 13 TERMINATE UNUSED LEAD WIRES AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE AND OR PRACTICES QD INTERNAL EGND cuva ASSOCIATED 14 SPLICE DENOTES LEAD WIRE TO LEAD WIRE CONNECTION INSTALL AS REQUIRED BY NATIONAL REGIONAL OR DIRECT POWER Black ES NOTE 13 NOTE 14 APPARATUS LAW AND OR PRACTICES LOOP POWER RED SAKE 15 INSTALL EXTERNAL GROUNDING CONNECTION AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE ANS OR PRACTICES RETURN Were gt SALE EXTERNAL GROUNDING CONNECTION WILL ACCEPT UP TO A 10AWG 4mm 2 WIRE HART varw gt FELD DEVICE ENCLOSURE NOTE 17 amp NOTE 18 16 THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS WITH ASSOCIATED D a APPARATUS WHEN THE FOLLOWING IS TRUE EXTERNAL GROUNDING CONNECTION ads Ui gt Uo li gt lo Pi gt Po Co gt SUM OF ALL Ci S CCABLE Lo gt SUM OF ALL Li S LCABLE Ui 30V li 120MA Pi 0 9W Ci 0 Li 596uH 17 SITRANS AW210 WirelessHART ADAPTER MODELS 7MP3111 1AB00 0AAO and 7MP3111 2AB00 0AA0 ENTITY PARAMETERS INTRINSICALLY SAFE Ui 30V li 120MA Pi 0 90W Ci 0UF Li 596uH WHEN Ca OF THE BARRIER IS gt 22UF THEN TOTAL CABLE CAPACITANCE SHALL BE LIMITED TO 22UF FIGURE 1 LOOP POWER 1 THE TOTAL CABLE CAPACITANCE PLUS THE TOTAL OF ALL Ci S SHALL NOT EXCEED THE Co OF THE ASSOCIATED APPARATUS B THE TOTAL CABLE INDUCTANCE PLUS THE TOTAL OF ALL Li
7. 15 INSTALL EXTERNAL GROUNDING CONNECTION AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE ANS OR PRACTICES EXTERNAL GROUNDING CONNECTION WILL ACCEPT UP TO A 10AWG 4mm 2 WIRE 16 THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS WITH ASSOCIATED mh APPARATUS WHEN THE FOLLOWING IS TRUE Ui gt Uo li gt lo Pi gt Po Co gt SUM OF ALL Ci S CCABLE Lo gt SUM OF ALL Li S LCABLE 17 SITRANS AW210 WirelessHART ADAPTER MODELS 7MP3111 1AB00 0AA0 and 7MP3111 2AB00 0AAO ENTITY PARAMETERS INTRINSICALLY SAFE Ui 30V li 120MA Pi 0 90W Ci OUF Li 596uH WHEN Ca OF THE BARRIER IS gt 22UF THEN TOTAL CABLE CAPACITANCE SHALL BE LIMITED TO 22UF THE TOTAL CABLE CAPACITANCE PLUS THE TOTAL OF ALL Ci S SHALL NOT EXCEED THE Co OF THE ASSOCIATED APPARATUS THE TOTAL CABLE INDUCTANCE PLUS THE TOTAL OF ALL Li S SHALL NOT EXCEED THE Lo OF THE ASSOCIATED APPARATUS HAZARDOUS AREA INTRINSICALLY SAFE GAS AREA CLASSIFICATIONS UNCLASSIFIED AREA ORDINARY LOCATION CLASS 1 DIVISION I Il III GROUPS A B C D E F CLASS 1 ZONE 0 SUITABLE FOR CLASS 1 1 11l DIVISION 2 GROUPS A B C D E F G NON SPARKING CLASS 1 ZONE 2 IIC INTRINSICALLY SAFE DUST ZONE 20 FIELD DEVICE FIELD DEVICE CURRENT LOOP SIEMENS CONNECTIONS SITRANS AW210 L1
8. BE CANADIAN CERTIFIED INTRINSICALLY SAFE GAS ORDINARY LOCATION 4 FOR ZONE INSTALLATIONS THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE ATEX IEC CERTIFIED CLASS 1 DIVISION 1l IIGROUPSABCDEF D 5 ASSOCIATED APPARATUS AND FIELD DEVICE MANUFACTURER4ES INSTALLATION DRAWING MUST BE FOLLOWED CLASS 1 ZONE 0 WHEN INSTALLING THIS EQUIPMENT 6 INSTALLATIONS IN THE U S SHOULD BE IN ACCORDANCE WITH ANSI ISA RP12 06 01 INSTALLATION OF SUITABLE FOR _ aoe CLASS JI II DIVISION 2 GROUPS A B C D E F G INTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS CLASSIFIED LOCATIONS AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE ANSI NFPA 70 NON SPARKING 7 INSTALLATION IN CANADA SHOULD BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CLASS 1 ZONE 2 IIC C22 1 CANADIAN ELECTRICAL CODE PART 8 ZONE INSTALLATIONS SHALL BE IN ACCORDANCE WITH LATEST EDITION OF THE WIRING PRACTICES AND INTRINSICALLY SAFE DUST m OR REGULATIONS FOR THE COUNTRY OF INSTALLATION ZONE 20 9 FOR INSTALLATION IN THE US AND CANADA CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC FIELD DEVICE 10 FOR INSTALLATIONS IN EUROPE CONTROL ROOM EQUIPMENT CONNECTED TO INTRINSICALLY SAFE SIEMENS LL ASSOCIATED APPARATUS SHALL NOT USE OR GENERATE MORE THAN THE MARKED UM OF THE ASSOCIATED APPARATUS Mi TRA eae 1 ote irelessHART Adapter ENCLOSURE S S z FIELD DEVICE MODEL 7MP3111 1AB00 0AA0 gt CURRENT LOOP 11 RESISTANC
9. S SHALL NOT EXCEED THE Lo OF THE ASSOCIATED APPARATUS 18 THE ASSOCIATED APPARATUS MUST BE A RESISTIVELY LIMITED SINGLE OR MULTIPLE CHANNEL APPROVED CERTIFIED BARRIER HAVING PARAMETERS LESS THAN THOSE QUOTED AND FOR WHICH THE OUTPUT AND THE COMBINATIONS OF OUTPUTS IS NON IGNITION CAPABLE UNATHORIZED DUPLICATION OF THIS DRAWING AND OR USES OF INFORMATION IS PROHIBITED WARN N G S AEC GENE NOE ae aay ALL INFORMATION HEREIN IS CONSIDERED CONFIDENTIAL AND PROPRIETARY TO MACTek CORPORATION A slds PATE MACTek Corporation 1 TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE ATMOSPHERE DISCONNECT POWER BEFORE SERVICING chk DM 100072012 SITRANS AW210 2 MAXIMUM OPERATING TEMPERATURE IS 85C CAUTION IN HANDELING ANY POTENTIALLY HOT SURFACE exer DMK poca WIRELESSHART ADAPTER 3 FIELD WIRING MUST BE RATED FOR 85C MINIMUM o ES CONTROL DRAWING D AT1101030C AA SCALE NONE FILENAME SHEET 4 OF 4 8 7 6 4 4 3 2 1 DM1101020UBB Copyright 2012 47 of 50 8 7 6 5 4 3 2 1 e AREA CLASSIFICATION 1 NO REVISION TO DRAWING WITHOUT PRIOR FM APPROVAL CLASSIFIC ONS 2 FOR INSTALLATIONS IN THE U S THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE FM APPROVED HAZARDOUS AREA UNCLASSIFIED AREA 3 FOR INSTALLATIONS IN CANADA THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST
10. Soft Reset Via DD Through the DD a reset command can be performed to reset the SITRANS AW210 Soft Reset Via Power connections Disconnect all power sources to the SITRANS AW210 for 5 seconds Reapply power and the SITRANS AW210 reset Hard Reset Since the SITRANS AW210 has a large internal energy store to perform a true Hard Reset complete power loss disconnect all power sources to the SITRANS AW210 for 5 minutes Then re apply power to the SITRANS AW210 Resets to factory default setting DM1101020UBB Copyright 2012 36 of 50 8 Product Order Information PRODUCED BY MACTek Corporation Gates Mills Ohio 44044 USA ORDER INFORMATION Order Number 7MP3111 aAbcO0 0AAO Where a denotes number of multi drop devices supported 1 2 devices 2 8 devices b denotes protection type B Intrinsically Safe C Explosionproof Flameproof c denotes housing material O Aluminum Order Number 7MP3111 1AB00 OAAO Product Description 2 multi drop devices supported Intrinsically Safe Aluminum Housing Order Number 7MP3111 2AB00 DAAO Product Description 8 multi drop devices supported Intrinsically Safe Aluminum Housing Order Number 7MP3111 1AC00 OAAO Product Description 2 multi drop devices supported Explosionproof Flameproof Aluminum Housing Order Number 7MP3111 2AC00 OAAO Product Description 8 multi drop devices supported Explosionproof Flameproof Aluminum Housing DM1101020UBB Copyright 2012
11. THE TOTAL OF ALL Li S SHALL NOT EXCEED THE Lo OF THE ASSOCIATED APPARATUS Ui 30V li 120MA Pi 0 9W Ci 0 Li 596uH FIGURE 2 LOOP POWER 2 B 18 THE ASSOCIATED APPARATUS MUST BE A RESISTIVELY LIMITED SINGLE OR MULTIPLE CHANNEL APPROVED CERTIFIED BARRIER HAVING PARAMETERS LESS THAN THOSE QUOTED AND FOR WHICH THE OUTPUT AND THE COMBINATIONS OF OUTPUTS IS NON IGNITION CAPABLE UNATHORIZED DUPLICATION OF THIS DRAWING AND OR USES OF INFORMATION IS PROHIBITED W ARN N G S NE CHANGE NOTICH a RE ALL INFORMATION HEREIN IS CONSIDERED CONFIDENTIAL AND PROPRIETARY TO MACTek CORPORATION A SIONAURE DATE MACTek Corporation 1 TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE ATMOSPHERE DISCONNECT POWER BEFORE SERVICING o nocte E A 2 MAXIMUM OPERATING TEMPERATURE IS 85C CAUTION IN HANDELING ANY POTENTIALLY HOT SURFACE eon tei seer WIRELESSHART ADAPTER 3 FIELD WIRING MUST BE RATED FOR 85C MINIMUM CONTROL DRAWING D AT1101030C AA SCALE NONE FILE NAME SHEET 2 OF 4 8 7 6 5 4 4 3 2 1 DM1101020UBB Copyright 2012 48 of 50 2 1 NOTES 1 NO REVISION TO DRAWING WITHOUT PRIOR FM APPROVAL 2 FOR INSTALLATIONS IN THE U S THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE FM APPROVED 3 FOR INSTALLATIONS IN CANADA THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE CANADIAN CERTIFIE
12. and Suitable for use when installed per SIEMENS Drawing AT1101030C Explosionproof for Class I Il Ill Division 1 Groups A B C D E F G DUST IGNITIONPROOF for Class Il IIl Division 1 Group E F G FACTORY SEALED CONDUIT SEAL NOT REQUIRED CLASS DIVISION DUST Class Il Division 2 Groups E F G ZONE MARKINGS Intrinsically Safe GAS 111 G Zone 0 Ex ia IIC Temp Class T5 T6 Intrinsically Safe DUST 11 1 D Zone 20 Ex iaD 20 IP68 T95 C Non Sparking GAS Encapsulation GAS II 3 G Zone 2 Ex nA nC IIC T5 T6 Flameproof GAS II 2 G Class 1 Zone 1 Ex d IIC T5 T6 Gb TEMPERATURE CLASS T5 40 C to 85 C T6 40 C to 75 C ENCLOSURE RATING TYPE 6P IP68 1 8m 24hr DM1101020UBB Copyright 2012 42 of 50 11 4 1 2 Canadian continued ENTITY PARAMETERS Ui 30V li 120mA Pi 0 9W Ci OuFD Li 596uH CLASS 1 ZONE O Special Condition of Use This product enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction Care must be taken into account during installation and use to prevent impact and friction Explosionproof and_Ex d IIC Special Condition of Use The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated within an Canadian Certified terminal or junction facility suitable for the location and conditions of use Ex d IIC Special Condition of Use Requires the use of an Canadian Certified cable
13. bandwidth for the burst settings If not either adjust the WirelessHART network settings or adjust the burst times for the SITRANS AW210 If the burst messages being dropped are for a wired Sub device ensure that there are no other HART masters on the connection as these can cause burst message delays Timestamps Start Set when the first HART Burst packet was dropped Stop Set when the last HART Burst packet was dropped 4 4 15 ALERT Field Device Power Control Description The field device power control mode is set to Switching however the burst event configuration will keep the device always powered on Corrective Action If the Field Device Power Control Mode Switching is not required change this option Else reduce the burst times for the wired Sub devices such that the system will switch the power to the devices Check the Field Device Estimate On Percentage for an estimated duty cycle that the Field Devices will be powered on for This alert will be set whenever this value is 100 and the Field Device Power Control Mode is set to Switching Timestamps Start Set when the Field Device Power Control issue is first detected DM1101020UBB Copyright 2012 30 of 50 Stop Set when the Field Device Power control issue is corrected 4 4 16 ALERT Wireless Capacity Denied Description The WirelessHART network has denied a request for Wireless bandwidth Corrective Action Check the burst mode settin
14. loop current in milliamps that above which will set a HART loop current warning 4 1 9 7 Lower Limit of Proportional Range This is the value of the loop current in milliamps that below which will set a HART loop current warning 4 1 9 8 Lower Fault Current This is the value of the loop current in milliamps that below which will set a HART loop current error 4 2 Automatic Burst Mode Configuration When Automatic Burst Mode Configuration is enabled the SITRANS AW210 will automatically configure burst messages for SITRANS AW210 itself and all of the connected sub devices The Automatic Burst Mode Configuration setting can be set from within the DD and allows the user to select several different fixed update rates 1 second 2 seconds 4 seconds 8 seconds 16 seconds 32 seconds 1 minute 2 minutes 5 minutes 10 minutes 30 minutes 60 minutes at which all of the burst messages will be published to the WirelessHART gateway If this mode is disabled burst mode can be configured manually using the DD NOTE lf the Automatic Burst Mode Configuration setting is set this will override any manual configuration of the burst mode settings If any manual burst mode settings are configured Automatic Burst Mode will be automatically turned off 4 3 Factory Reset Executing the factory reset will reset the following SITRANS AW210 parameters and then cause the SITRANS AW210 to reset The software controlled factory reset can be initiat
15. lower this value is the less amount of power will be used DM1101020UBB Copyright 2012 20 of 50 4 1 1 7 External Battery Settings The SITRANS AW210 has internal circuitry to monitor battery consumption when an external battery is used for the Direct Power input Since the battery is external there are many possible battery options that the user could employ therefore the SITRANS AW210 battery measurement circuitry is very flexible and configurable There are two major variables measured to determine the remaining battery life the battery voltage and the battery coulomb discharge rate Both of these measurements are continuously being performed by the SITRANS AW210 on the battery and both of these measurements are used to determine the remaining battery life and the power status 4 1 2 Power Status WirelessHART defines three power status levels for battery powered devices Power Status Nominal The power for the device is operating correctly Power Status Low The power source for the device has under 25 days of life remaining The power source should be exchanged when the low indication is set Power Status Critical The power source for the device is critically low and loss of power will happen in the immediate future 4 1 2 1 Battery Life Remaining The amount of days of battery life that the system is expected to be able to run based on the average battery consumption rate from the previous one hour of opera
16. num E 18 Date 1 Event Mode TS a eee 19 Burst Message 18 2 Subdevice Tag i Retry Ti 2 Subdevice Supported 21 Country i S A 3 Power Modes Supported 22 SI Unit Control 5 Max Update Time 4 Set License Key 23 Write Protect AE 6 Event Mask A eee 7 Event Status 8 Event Message 8 reenter 1 Clear Alerts 1 Status Mask Byte 1 1 Wireless Mode E 2 Join Status 24 Status Mask Byte 24 1 Device Status 1 Field Device Pwr Ctrl 3 Join Mode 2 Ext dev Status Sec eee 4 Join Duty Cycle 3 Diag status 0 a Kle Ime 5 Advertisement Count 4 Alerts O e EE 4 On Estimated Percent 6 Neighbor Count 1 Clear Event 5 WirelessHART Status ebay us 7 Join Attempts 2 Event Status 6 Device Specific Status 6 Off Time 8 Burst Service Requested 3 Date of First Unack Event 2 Device Status 7 Cfg chng count 7 On Percent 9 Burst Service Granted 4 Time of First Unack Event 8 Extemal Battery 5 Latched Status Byte 1 3 Power 1 Generated Packets 1 PV Units 2 Terminated Packets 28 Latched Status Byte 24 5 ee 3 CRC Errors 4 Communications 1 Perform Master Reset 5 e a Mode 4 DLL failures 2 Self test x PVU eS cda ae 5 NL Session failures 3 Factory reset 5 Py pe ham Value 6 Nonce Counter Values 5 Maintenance 4 Advertise to Wireless Dev y 5 Scavenging Voltage 6 Upper Fault Current y 7 Upper Limit of Prop Range 1 STX Count 6 Ti 8 Lower Limit of Prop Range 2 ACK Count TS 9 Lower Fault Current 3 BACK Count 1 System Up
17. permanently mark the type of protection chosen for the specific installation Once the type of protection has been marked it shall not be changed Ex d IIC Special Conditions of Use 1 The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated within a suitable ATEX Certified Ex d or Ex e terminal or junction facility 2 The Ex d IIC configuration requires the use of an ATEX Certified cable seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility 11 4 3 IEC Certificates Certification Number IECEx FMG12 0033X Intrinsically Safe GAS 8 II 1 G Zone 0 Ex ia IIC Temp Class T5 T6 Intrinsically Safe DUST amp 11 1 D Zone 20 Ex iaD 20 IP68 T95 C Non Sparking Encapsulation GAS 6 Il 3 G Zone 2 Ex nA nC IIC T5 T6 Certification Number IECEx FMG 12 0034X Flameproof GAS amp Il 2G Class 1 Zone 1 Exd IIC T5 T6 Gb Flameproof DUST amp II 2 D Class 1 Zone 21 Ex tb IIIC T95 C TEMPERATURE CLASS T5 40 C to 85 C T6 40 C to 75 C ENTITY PARAMETERS Ui 30V li 120mA Pi 0 9W Ci OuFD Li 596uH DM1101020UBB Copyright 2012 44 of 50 11 4 3 IEC Certificates continued ENCLOSURE RATING IP68 1 8m 24hr Zone 0 Special condition of use X This product enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction Care must be taken in
18. the DIRECT POWER source verify that the HART modem and PC or HART communicator is operating as expected and proceed to the following section QUICK SETUP Wire Color Description Green Yellow Internal Earth Ground Red HART External Earth Ground DM1101020UBB Copyright 2012 7 of 50 POWER SUPPLY 7VDC 32VDC am E POSITIVE ES NEGATIVE NOTE 1 ISOLATE RED LEAD WIRE SIGNAL WIRE COLOR HART MODEM amp HOST PC OR HART COMMUNICATOR FIGURE 1 BENCH TOP CONFIGURATION SETUP NOTES By default the SITRANS AW210 is at HART polling address 15 By default all WirelessHART Adapters are configured as a primary HART master The HART communicator used to configure the SITRANS AW210 should be configured in Secondary HART master mode WARNING THE SITRANS AW210 CAN BE DAMAGED IF THE DIRECT POWER SOURCE IS GREATER THAN 32VDC 2 2 Device Configuration Using Device Description DD NOTE DD and Simatic PDM Setup instruction are included in SIEMENS INSTALLATION CD There are generic instructions that should help with your DD based configurator Set the HART Tags for the SITRANS AW210 From the Main DD screen select Configure Select Manual Setup SITRANS AW210 Information Enter in the HART Tag Enter in the HART Long Tag Transfer the updated information to the SITRANS AW210 by clicking on the Send or Transfer button ASIS DM1101020UBB Copyright 2012 8 of 50
19. using a HART capable host such as a HART communicator or PC with HART modem By Default the SITRANS AW210 is at HART polling address 15 Through the DD the polling address can be set to any value between O and 63 4 1 6 2 HART Master Mode This is the HART Master mode used by the SITRANS AW210 when it is communicating as a HART master with wired HART devices By Default the SITRANS AW210 is configured as a HART primary master Through the DD the master mode can be changed to be elther a HART secondary or primary master 4 1 6 3 RT Retry Count This is the amount of retries the SITRANS AW210 will attempt when communicating as a HART master to wired HART devices By Default the SITRANS AW210 is configured to use 3 retries Through the DD the retry count can be set to 2 3 4 or 5 4 1 6 4 HART Number of Response Preambles This is the amount of preambles the SITRANS AW210 will use when responding to HART commands sent by a HART master such as a HART communicator or PC with HART modem on the wired HART connection DM1101020UBB Copyright 2012 22 of 50 By Default the SITRANS AW210 is configured to use 5 preambles Through the DD the response preamble count can be set between 5 20 preambles 4 1 6 5 Write Protect This setting allows the configuration inside of the SITRANS AW210 to be write protected The write protect setting is controlled through the DD By Default the SITRANS AW210 is configured to have write p
20. with HART Field Devices in LOOP POWER Multi Drop Mode For proper HART communication the Wired HART network requires a 2500 terminating resistor When configured for LOOP POWER the terminating resistor must be hard wired into the system as shown in Figure 27 The HART terminating resistor must be located in series with either power source terminal The location of the HART terminating resistor will not affect the wiring shown in Figure 27 To operate in this mode the Device Description DD parameter FIELD DEVICE POWER CONTROL must be set to the OFF position which is the factory default setting DM1101020UBB Copyright 2012 15 of 50 FIELD DEVICE FIELD DEVICE FIELD DEVICE 1 8 2 THROUGH 7 CURRENT LOOP CONNECTIONS CURRENT LOOP CONNECTIONS CURRENT LOOP CONNECTIONS POWER SOURCE F EARTH GROUND GRN YEL de POSITIVE HART YELLOW RETURN WHITE Se J Loop POWER RED J DIRECT POWER BLACK Qq m NEGATIVE TERMINATING RESISTOR SIGNAL WIRE COLOR NOTE 1 ISOLATE BLACK LEAD WIRE FIGURE 27 LOOP POWER Multi Drop Configuration Figure 27 is a simplified representation of this LOOP POWER multi drop configuration The DIRECT POWER black lead wire is not required for this configuration and is not shown The EARTH Grounding connection is not shown 3 3 6 SITRANS AW210 with HART Field Devices in DIRECT POWER Multi Drop Mode When configured for DIRECT POWER the HART termin
21. 10 power configuration options are either existing loop power scavenging or local direct power The SITRANS AW210 when loop powered saves users the long term cost of battery maintenance replacement and disposal programs The SITRANS AW210 Local Direct power option can be used when the field device is powered either by a DC power supply or an external battery solar system In the case of external battery power the SITRANS AW210 provides battery power management by cycling the field device power and taking periodic readings Typical Use Cases e Upgrade legacy wired HART or analog only field devices with WirelessHART communication capability to communicate the PV and other device data and diagnostic information to the gateway and ultimately the host application e Access HART device diagnostic information in HART enabled devices in order to lower maintenance cost and improve plant operations e Low cost wireless access to stranded monitoring and control data from improved o Asset management o Condition monitoring o Device diagnostics e Connect up to 8 HART devices using only 1 SITRANS AW210 making WirelessHART more cost effective Remote lO applications of hard to reach locations Substitute for multiplexers or legacy DCS upgrade to HART enabled I O External Battery powered wireless remote I O data collection Low cost low risk means to test and evaluate WirelessHART networks Monitor control of rotating and mobile equipment Features e HART
22. ANDELING ANY POTENTIALLY HOT SURFACE ea DORIAN WIRELESSHART ADAPTER ENGR DMK 100CT2012 3 FIELD WIRING MUST BE RATED FOR 85C MINIMUM CONTA CONTROL DRAWING SIZECAGE CODE DWG NO REV D AT1101030C AA SCALE NONE FILE NAME SHEET 4 OF 4 8 7 6 5 4 4 3 2 1 DM1101020UBB Copyright 2012 50 of 50
23. As Clear AACHEN h a be de coll 27 4 45 ALERT Direct Power Out Of Range occooccocccccnocccoconcononocococoncnnnnonconanonnnoronanonnrnronanennnnnenanos 27 4 4 6 ALERT Loop Power Out Of Range i sisaan a aian ia a e i ai 27 4 4 7 ALERT Temperature Out of RQnNge ccooccocccccconcoccconocononononcnnnononnncnnnnnonnnnnncanonnnennnanenenns 27 4 4 8 ALERT Power Mode Miss configured oocooccocccoccccoocncoconconnnonccnconnnnnncnnonanonnonronanennnonenonos 28 449 VARS VV ALCMOOG ROSES Jonas ven N a eh ae 28 ARTO ALERT Slack OVOHIO Waits ia aio aa 28 4 4 11 ALERT Duplicate HART Master Detected ooccooccoccocconccnocnocnocnoconcnnconcnoncnncononncannnnos 29 4 4 12 ALERT HART Devices Count Exceeded cooccooccocccccocccoccoconconoccnconancnnonnonnnnnnnnronanonnnoninanos 29 A413 ALERT HART Sub DevVICe LOSt sauce wees ao a 29 4 4 14 ALERT Burst Packets are Being Dropped ccoccoccocconconcocccnconococononnnconcnnconnnononnnononnononanes 30 4 4 15 ALERT Field Device Power Control cccccccscceecceeceeceeeceeceeceeeceeceeseseceeseeseeeeeeseesesess 30 4 4 16 ALERT Wireless Capacity Denied cccccccecceecceeseeceecceeseeseeeceeceeseeeceecueseeseeeseeseeees 31 4 4 17 ALERT Burst Message Configuration ISSUE ooccooccocccciocncoccononnncnncononanonncnnonanonnnnninonos 31 4 4 18 ALERT Wired Device in Burst MOde cccccccecccecceeceeeceeceesee
24. Certifications occconccnnconcconiconconcconocononnncononononnnnnnonononnnnanenanens 40 11 4 Hazardous Location Certificates cooccconconncccnocncoononcnnnnonnnonnnnnnonnnoncnnnnonanoncncnnnnanons 40 11 4 1 North America Certificates ocooccoccconconcccoconionoonoconoononnononoononnnnonnononnnnnnnnnonnnnaneanenoss 41 11 4 2 European ATEX CertifiCates ooccoocconconcccnconconoconcononcononcononnnnnncanonnnnnnnnnonnnnanennenons 43 As ECC bo 44 11 4 4 Required Certification Notices and WAarningS ooccoccooncocoocnconcnconcnnnnnnnonononnnnronannnnnononoos 45 12 CONTROL DRAWING sra 47 DM1101020UBB Copyright 2012 2 of 50 1 Introduction 1 1 Overview The SITRANS AW210 enables new and existing wired HART field devices to communicate with host applications by means of WirelessHART technology The SITRANS AW210 is permanently installed by attaching it directly into an available spare port of a HART field device or by means of using a short right angle elbow conduit connector The SITRANS AW210 can be inserted anywhere on the loop using a junction box or T fitting A wired HART field device retrofitted with a SITRANS AW210 communicates its PV over the existing wire and simultaneously communicates the PV SV TV and QV as well as diagnostic and alarm data over the WirelessHART network to process control asset management and other automation and engineering applications The SITRANS AW2
25. D 4 FOR ZONE INSTALLATIONS THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE ATEX IEC CERTIFIED 5 ASSOCIATED APPARATUS AND FIELD DEVICE MANUFACTURER4ES INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT 6 INSTALLATIONS IN THE U S SHOULD BE IN ACCORDANCE WITH ANSI ISA RP12 06 01 INSTALLATION OF INTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS CLASSIFIED LOCATIONS6 AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE ANSI NFPA 70 7 INSTALLATION IN CANADA SHOULD BE IN ACCORDANCE WITH THE LATEST EDITION OF THE C22 1 CANADIAN ELECTRICAL CODE PART I 8 ZONE INSTALLATIONS SHALL BE INACCORDANCE WITH LATEST EDITION OF THE WIRING PRACTICES AND OR REGULATIONS FOR THE COUNTRY OF INSTALLATION 9 FOR INSTALLATION IN THE US AND CANADA CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC 10 FOR INSTALLATIONS IN EUROPE CONTROL ROOM EQUIPMENT CONNECTED TO INTRINSICALLY SAFE ASSOCIATED APPARATUS SHALL NOT USE OR GENERATE MORE THAN THE MARKED UM OF THE ASSOCIATED APPARATUS 11 RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN 1 0 OHM C 12 INSTALLATION OF EXISTING FIELD DEVICE MUST FOLLOW MANUFACTURERS INSTALLATION DRAWINGS 13 TERMINATE UNUSED LEAD WIRES AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE AND OR PRACTICES 14 SPLICE DENOTES LEAD WIRE TO LEAD WIRE CONNECTION INSTALL AS REQUIRED BY NATIONAL REGIONAL OR LAW AND OR PRACTICES
26. D APPARATUS AND FIELD DEVICE MUST BE ATEX IEC CERTIFIED CLASS 1 DIVISION I II II GROUPS AB C DE F D 5 ASSOCIATED APPARATUS AND FIELD DEVICE MANUFACTURERS INSTALLATION DRAWING MUST BE FOLLOWED CLASS 1 ZONE 0 WHEN INSTALLING THIS EQUIPMENT 6 INSTALLATIONS IN THE U S SHOULD BE IN ACCORDANCE WITH ANSI ISA RP12 06 01 INSTALLATION OF SUITABLE FOR ES CLASS JIL II DIVISION 2 GROUPS A B C D E F G INTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS CLASSIFIED LOCATIONS6 AND THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE ANSI NFPA 70 NON SPARKING 7 INSTALLATION IN CANADA SHOULD BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CLASS 1 ZONE 2 IIC C22 1 CANADIAN ELECTRICAL CODE PART I 8 ZONE INSTALLATIONS SHALL BE IN ACCORDANCE WITH LATEST EDITION OF THE WIRING PRACTICES AND INTRINSICALLY SAFE DUST OR REGULATIONS FOR THE COUNTRY OF INSTALLATION ZONE 20 9 FOR INSTALLATION IN THE US AND CANADA CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC FIELD DEVICE 10 FOR INSTALLATIONS IN EUROPE CONTROL ROOM EQUIPMENT CONNECTED TO INTRINSICALLY SAFE SIEMENS FIELD DEVICE SITRANS AW210 L1 L2 CURRENT LOOP ASSOCIATED APPARATUS SHALL NOT USE OR GENERATE MORE THAN THE MARKED UM OF THE ASSOCIATED APPARATUS Wireless HART Adapter RA G CONNECTIONS MODEL 7MP3111 1AB00 0AA0 11 RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN 1 0 OHM MODEL NESTI ABOLOAAD ENCLOSURE S alle C
27. E BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN 1 0 OHM MODEL AP AEA CHASSIS LR CONNECTIONS C 12 INSTALLATION OF EXISTING FIELD DEVICE MUST FOLLOW MANUFACTURERS INSTALLATION DRAWINGS ASSOCIATED 13 TERMINATE UNUSED LEAD WIRES AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE AND OR PRACTICES APPARATUS INTERNAL EGND MGs 7 NOTE 14 14 SPLICE DENOTES LEAD WIRE TO LEAD WIRE CONNECTION INSTALL AS REQUIRED BY NATIONAL REGIONAL OR DIRECT O OWER GA aa Seu UN LAW AND OR PRACTICES LOOP POWER RED SPLIC 15 INSTALL EXTERNAL GROUNDING CONNECTION AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE ANS OR PRACTICES RETURN WHITE EXTERNAL GROUNDING CONNECTION WILL ACCEPT UP TO A 10AWG 4mm 2 WIRE HART eow NOTE 17 amp NOTE 18 FEILD DEVICE noe 16 THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS WITH ASSOCIATED D p APPARATUS WHEN THE FOLLOWING IS TRUE EXTERNAL GROUNDING CONNECTION Ui gt Uo li gt lo Pi gt Po Co gt SUM OF ALL Ci S CCABLE Lo gt SUM OF ALL Li S LCABLE NOTE 17 SITRANS AW 210 WirelessHART ADAPTER MODELS 7MP3111 1AB00 0AA0 and 7MP3111 2AB00 0AAO ENTITY PARAMETERS INTRINSICALLY SAFE Ui 30V li 120MA Pi 0 90W Ci OUF Li 596uH WHEN Ca OF THE BARRIER IS gt 22UF THEN TOTAL CABLE CAPACITANCE SHALL BE LIMITED TO 22UF THE TOTAL CABLE CAPACITANCE PLUS THE TOTAL OF ALL Ci S SHALL NOT EXCEED THE Co OF THE ASSOCIATED APPARATUS THE TOTAL CABLE INDUCTANCE PLUS
28. F INTRINSICALLY SAFE APPARATUS WITH ASSOCIATED NOTE p APPARATUS WHEN THE FOLLOWING IS TRUE SOY li 120MA PICO 120 Li 596UH Ui gt Uo li gt lo Pi gt Po Co gt SUM OF ALL Ci S CCABLE Lo gt SUM OF ALL Li S LCABLE 17 SITRANS AW210 WirelessHART ADAPTER MODELS 7MP3111 1AB00 0AAO and 7MP3111 2AB00 0AAO ENTITY PARAMETERS INTRINSICALLY SAFE FIGURE 4 DIRECT POWER REPEATER Ui 30V li 120MA Pi 0 90W Ci 0UF Li 596uH WHEN Ca OF THE BARRIER IS gt 22UF THEN TOTAL CABLE CAPACITANCE SHALL BE LIMITED TO 22UF THE TOTAL CABLE CAPACITANCE PLUS THE TOTAL OF ALL Ci S SHALL NOT EXCEED THE Co OF THE ASSOCIATED APPARATUS B THE TOTAL CABLE INDUCTANCE PLUS THE TOTAL OF ALL Li S SHALL NOT EXCEED THE Lo OF THE ASSOCIATED APPARATUS 18 THE ASSOCIATED APPARATUS MUST BE A RESISTIVELY LIMITED SINGLE OR MULTIPLE CHANNEL APPROVED CERTIFIED BARRIER HAVING PARAMETERS LESS THAN THOSE QUOTED AND FOR WHICH THE OUTPUT AND THE COMBINATIONS OF OUTPUTS IS NON IGNITION CAPABLE UNATHORIZED DUPLICATION OF THIS DRAWING AND OR USES OF INFORMATION IS PROHIBITED WARNINGS NE CHANGE NOTICH a RE ALL INFORMATION HEREIN IS CONSIDERED CONFIDENTIAL AND PROPRIETARY TO MACTek CORPORATION A SIONAURE DATE MACTek Corporation DWN DMK 100CT2012 7380 Stoneham Road Gates Mills OH 44040 USA 1 TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE ATMOSPHERE DISCONNECT POWER BEFORE SERVICING CHK pk 100072012 SITRANS AW210 2 MAXIMUM OPERATING TEMPERATURE IS 85C CAUTION IN H
29. INSTALLATIONS FOR EITHER ORDINARY LOCATION OR HAZARDOUS LOCATION SHOULD ONLY BE PREFORMED BY QUALIFIED PERSONAL TRAINED IN THE APPLICABLE NATIONAL REGIONAL LOCAL CODES AND PRACTICES INSTALLATION IN EXPLOSIVE ATMOSPHERE MUST COMPLY WITH HAZARDOUS LOCATION APPROVALS AND THE MARKINGS ON THE NAMEPLATE EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT OPERATING TEMPERATURE RANGE IS 85C CAUTION IN HANDLING ANY POTENTIALLY HOT SURFACES 3 2 SITRANS AW210 installation to Field Device 3 2 1 Field Device Mechanical Connection The SITRANS AW210 7 male NPT port allows direct connection into a spare Field Device enclosure port or a junction box The SITRANS AW210 7 NPT will accept adapters to interface into other entry thread types such as M20 WARNING TO PREVENT THE POTENTIAL OF ALUMINUM GALLING AN ELECTRICALLY CONDUCTIVE THREAD LUBRICANT IS RECOMMENDED TO BE APPLIED TO THE NPT THREADS PRIOR TO ASSEMBLY 3 2 2 Antenna Positioning The SITRANS AW210 has an internal antenna which radiates out from top cap in a 360 pattern The SITRANS AW210 should be positioned vertically and located approximately 1 meter from any metal or conductive material which could impact the W irelessHART communications The SITRANS AW210 can placed anywhere on the current loop and does not need to be positioned directly next to the associated Field Device This allows positioning the SITRANS A
30. ITION OF THE WIRING PRACTICES AND INTRINSICALLY SAFE DUST A OR REGULATIONS FOR THE COUNTRY OF INSTALLATION ZONE 20 9 FOR INSTALLATION IN THE US AND CANADA CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS Sere MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC SITRANS AW210 WirelessHART Adapter 10 FOR INSTALLATIONS IN EUROPE CONTROL ROOM EQUIPMENT CONNECTED TO INTRINSICALLY SAFE MODEL 7MP3111 1AB00 0AAO JUNCTION BOX OR ENCLOSURE ASSOCIATED APPARATUS SHALL NOT USE OR GENERATE MORE THAN THE MARKED UM OF THE ASSOCIATED APPARATUS MODEL 7MP3111 2AB00 0AAO ENCLOSURE 11 RESISTANCE BETWEEN INTRINSICALLY SAFE GROUND AND EARTH GROUND MUST BE LESS THAN 1 0 OHM GROUNDING E ASSOCIATED CONNECTION Cy i C 12 INSTALLATION OF EXISTING FIELD DEVICE MUST FOLLOW MANUFACTURERS INSTALLATION DRAWINGS D INTERNAL EGND oanveL __ iani APPARATUS BLACK 13 TERMINATE UNUSED LEAD WIRES AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE AND OR PRACTICES ee e oe nee SPLIC TODC 14 SPLICE DENOTES LEAD WIRE TO LEAD WIRE CONNECTION INSTALL AS REQUIRED BY NATIONAL REGIONAL OR RETURN Whitey SPLICR paG POWER SOVRGE LAW AND OR PRACTICES KARTA SPLIC TOHART i TERMINATING RESISTOR 15 INSTALL EXTERNAL GROUNDING CONNECTION AS REQUIRED BY NATIONAL REGIONAL OR LOCAL CODE ANS OR PRACTICES D EXTERNAL GROUNDING CONNECTION WILL ACCEPT UP TO A 10AWG 4mm WIRE NOTE 17 amp NOTE 18 EXTERNAL GROUNDING CONNECTISY 16 THE ENTITY CONCEPT ALLOWS INTERCONNECTION O
31. ITRANS AW210 s RETURN white lead wire NOTE When used in loop powered mode the SITRANS AW210 cannot control the loop current It is up the user to ensure that the loop current is limited to within the operating specifications DM1101020UBB Copyright 2012 13 of 50 WARNING THE SITRANS AW210 CAN BE DAMAGED IF THE DIRECT POWER SOURCE IS GREATER THAN 32VDC 3 3 2 SITRANS AW210 with a 4 20mA Analog only Non HART Field Device The SITRANS AW210 is connected in series with 4 20mA analog output only Field Device which does not support HART The SITRANS AW210 is capable of monitoring and reporting the analog loop current to the WirelessHART network 3 3 3 SITRANS AW210 with a HART enabled Field Device The SITRANS AW210 is connected in series with a HART Field device such as a 4 20mA HART transmitter which also controls the loop current The SITRANS AW210 is capable of monitoring and reporting the analog loop current to the WirelessHART network and will also communicate wired HART data with the connected wired HART sub device The SITRANS AW210 and the Field Device are connected in series so the inductance has to be considered Connect the SITRANS AW210 and Field Device as shown in either Figure 25 Configuration 1 or Figure 26 Configuration 2 drawings FIELD DEVICE CURRENT LOOP CONNECTIONS L1 L2 GROUNDING CONNECTION fa EARTH GROUND GRN YEL f d 7 CURRENT LOOP DIRECT POWER BLACK
32. L2 WirelessHART Adapter a MODEL 7MP3111 1AB00 0AA0 ENCLOSURE a MODEL 7MP3111 2AB00 O0AAO CHASSIS gt J lt CONNECTION ASSOCIATED D INTERNAL EGND ore NOTE 14 APPARATUS DIRECT POWER BLack gt gt ISPLICE m LOOP POWER RED NOTE 13 RETURN WHITE gt e HART errow ca FEILD DEVICE ENCLOSURE NOTE 17 amp NOTE 18 EXTERNAL GROUNDING CONNECTION Y NOTE 15 Ui 30V li 120MA Pi 0 9W Ci 0 Li 596uH FIGURE 3 DIRECT POWER FIELD DEVICE CONTROL B 18 THE ASSOCIATED APPARATUS MUST BE A RESISTIVELY LIMITED SINGLE OR MULTIPLE CHANNEL APPROVED CERTIFIED BARRIER HAVING PARAMETERS LESS THAN THOSE QUOTED AND FOR WHICH THE OUTPUT AND THE COMBINATIONS OF OUTPUTS IS NON IGNITION CAPABLE UNATHORIZED DUPLICATION OF THIS DRAWING AND OR USES OF INFORMATION IS PROHIBITED W ARN N G S EEE CHANGE NOTICE STE ae ALL INFORMATION HEREIN IS CONSIDERED CONFIDENTIAL AND PROPRIETARY TO MACTek CORPORATION A SOMENTE AE MACTek Corporation 1 TO PREVENT IGNITION OF FLAMMABLE OR COMBUSTIBLE ATMOSPHERE DISCONNECT POWER BEFORE SERVICING o oer Sean 2 MAXIMUM OPERATING TEMPERATURE IS 85C CAUTION IN HANDELING ANY POTENTIALLY HOT SURFACE ue dst WIRELESSHART ADAPTER 3 FIELD WIRING MUST BE RATED FOR 85C MINIMUM a o CONTROL DRAWING D AT1101030C AA SCALE NONE FILE NAME SHEET 3 OF 4 8 7 6 5 4 4 3 2 1 DM1101020UBB Copyright 2012 49 of 50
33. NTITY PARAMETERS Ui 30V li 120mA Pi 0 9W Ci OuFD Li 596uH CLASS 1 Zone O Special Condition of Use This product enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction Care must be taken into account during installation and use to prevent impact and friction DM1101020UBB Copyright 2012 41 of 50 11 4 1 United States continued Explosionproof and Class 1 Zone 1 AEx d IIC Special Condition of Use The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated within an NRTL Approved Listed or Recognized terminal or junction facility suitable for the location and conditions of use Class 1 Zone 1 AEx d IIC Special Condition of Use Requires the use of an NRTL Approved Listed or Recognized cable seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility CLASS Zone Notice Using the box provided on the nameplate the user shall permanently mark the type of protection chosen for the specific installation Once the type of protection has been marked it shall not be change 11 4 1 2 Canadian Certificates CLASS DIVISION GAS DUST and FIBER Intrinsically Safe for Class I Il Ill Division 1 Groups A B C D E F G Non Incendive for Class I Division 2 Group A B C D Suitable for Use Class Il Ill Division 2 A B C D E F G Intrinsically Safe
34. Notice Using the box provided on the nameplate the user shall permanently mark the type of protection chosen for the specific installation Once the type of protection has been marked it shall not be changed Explosion proof Installation Notice FACTORY SEALED NO CONDUIT SEAL REQUIRED DM1101020UBB Copyright 2012 A5 of 50 US Listing Special Condition of Use The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated within an NRTL Approved Listed or Recognized terminal or junction facility suitable for the location and conditions of use The Class I Zone 1 AEx d IIC configuration requires the use of an NRTL Approved Listed or Recognized cable seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility CANADIAN Listing Special Condition of Use The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated within a Canadian Certified terminal or junction facility suitable for the location and conditions of use The Class I Zone 1 Ex d IIC configuration requires the use of a Canadian Certified cable seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility ATEX Listing Special Condition of Use The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated w
35. Registered fully HART compliant for communication reliability Universal connectivity works with all registered HART devices Supports WirelessHART MESH and STAR network configurations Loop powered no batteries or other power sources required Connects directly to HART field device and optionally anywhere on the 4 20 mA control loop StepVolt technology sets insertion voltage in steps from 1 to 2 5 volts to optimize the tradeoff between available loop power and Wireless communication bandwidth e Direct Power option when local DC power is available system power external battery solar system e In Direct Power mode can switch field device on off to take periodic readings to save power e Internal 250 Ohm loop current sense and HART terminating resistor provided configurable by WirelessHART command e Multidrop support for up to 8 devices maximum number depends on installation e 235 meters open air range nominal e Rugged internal antenna design DM1101020UBB Copyright 2012 3 of 50 1 2 Basic Operation The SITRANS AW210 WirelessHART Adapter allows new and existing wired HART devices to be connected integrated into a WirelessHART network This allows remote access to diagnostic data digital process variables and alarm data stored inside HART devices The SITRANS AW210 has both a Wireless interface to communicate with the WirelessHART network and a wired HART interface to communicate to a traditional 4 20mA current loop d
36. W210 in an optimal location for RF coverage DM1101020UBB Copyright 2012 11 of 50 The operating range can be reduced by interference from other nearby devices transmitting in the 2 4 GHz ISM band These external sources of interference can prevent the establishment of WirelessHART connection and may result in intermittent loss of network connections causing HART network message retries To maintain optimum antenna performance periodically removal any accumulated material from the dome such as dust fiber snow and ice Use caution in removing any material off the resin dome so as not to damage the dome or mechanically stress the NPT threaded connection 3 2 3 Nameplate SITRANS AW210 nameplates contain multiple hazardous location approvals There is a Class Zone and ZONE installation requirement to permanently mark the nameplate for the selected installation protection type On each nameplate there is a box at the start of each line of approval markings so the nameplate can be permanently marked to denote the type of protection chosen for that specific installation Once the SITRANS AW210 is installed and nameplate marked it should not be re installed using any other protection type Class Division installation do not have the same nameplate marking requirement as Class Zone and ZONE Although not required a box is provided at the start of each Class Division approval marking line to mark the nameplate 3 2 4 Field Device Electrica
37. WirelessHART Adapter SITRANS AW210 7MP3111 User Manual 11 2012 SITRANS Answers for industry SIEMENS Table of Contents INTRODUC HON irreal coo od co 3 LO E a o o E O RO O O ra a en aa a cata 3 EZ Basie OPE AIN ii 4 ko INPC USA A ee 4 kA 0 ROO CEE ea ce es a ee ele ce eee rs at eee ae 4 TAA Loop Powered NOGGnic eee ee e ees 5 142 OPVO BENN cia ia is 6 1 4 3 Direct POWEIEO MOOG orcas e A canst count A ie 6 CONFIGURATION uscar 7 21 BENCENO Ooty 0 01 UD a T 2 2 Device Configuration Using Device Description DD oocooccconcccncoccooncoconoconanoncnnnnonanononnnos 8 INSTALLATION tin 9 31 Ordinary ana Hazardous LOCATIONS osas 10 3 2 SITRANS AW210 installation to Field Device occooccoccconcoccooccconccononcnconocanonanonnonanos 11 3 2 1 Field Device Mechanical CONNECtION oocooccconconcococcnconoococononnnonocnnonnnnnonnnonnnnnonnnnnnnnnenons 11 32 2 Antenna POSO a aa 11 329 Nameplate a anda 12 3 2 4 Field Device Electrical CONNECTION occocconccoccccncnncoconcnnnncnconcnnnncnoncnnnnnnrnnrnnnnrnnrnronanonncncnnons 12 e E O nave owe oeeee ake 13 39 Installation ONIONS arianna vaceae saaehereaaans od 13 3 3 1 SITRANS AW210 as a Standalone WirelessHART Router Repeater oocoocccccocccoccocooo 13 3 3 2 SITRANS AW210 with a 4 20mA Analog only Non HART Field Device ooccooooocoooo o 14 3 3 3 SITRANS AW210 with a HART enabled Field Device oocoo
38. ating resistor requirement can be meet by either by physically wiring a resistor into the system or by using the SITRANS AW210 internal terminating resistor The SITRANS AW210 provides a switchable resistor connecting a 250 Ohm resistor between the HART yellow lead wire and RETURN white lead wire To use the SITRANS AW210 internal resistor the operator must properly configure the Device Description DD The operator must configure the DD parameter FIELD DEVICE POWER CONTROL to the ON setting Refer to section 2 Configuration Detailed Setting Field Device Power Control section for the description and use of the Device FIELD DEVICE FIELD DEVICE FIELD DEVICE 1 8 2 THROUGH 7 CURRENT LOOP CONNECTIONS CURRENT LOOP CONNECTIONS CURRENT LOOP CONNECTIONS POWER SOURCE a EARTH GROUND GRN YEL POSITIVE DIRECT POWER BLACK RETURN WHITE E 1 LE J HART YELLOW J LOOP POWER RED q SIGNAL WIRE COLOR NOTE 1 ISOLATE RED LEAD WIRE FIGURE 28 DIRECT POWER Multi Drop Configuration FIELD DEVICE CONTROL ON position Figure 28 is a simplified schematic representation of this DIRECT POWER multi drop configuration with FIELD DEVICE CONTROL is set to the ON position The LOOP POWER red lead wire is not required for this configuration and is not shown The EARTH Grounding connection is not shown DM1101020UBB Copyright 2012 16 of 50 3 3 7 SITRANS AW210 with a 4 20mA Field Device
39. bs Housing Aluminum alloy ROHS complaint corrosion coating polyurethane enamel Physical Dimensions Dimensions Enclosure paint Dome propriety resin One Male Y NPT Connection Field Termination 5 lead wires x 600mm 24 long exiting from male Y NPT opening 5 leads 4 signal and 1 internal earth grounding connection Enclosure 1 external earth grounding screw SS 10 32 with captive washer DM1101020UBB Copyright 2012 38 of 50 10 Mechanical 10 1 1 Dimensional Drawing 2 393 60 79mm SIEMEN SITRANS AW210 WirelessHART Adapter 4 477 113 72mm Order No 7MP3111 wAxyz OAAO Produced by MACTek Corporation for Siemens AG Si he iemens AG D 76181 Karlsrul Dimensions are in inches millimeters 10 1 2 Enclosure The SITRANS AW210 enclosure is a die cast low copper aluminum alloy housing is protected by a ROHS complaint corrosion coating and polyurethane enamel paint As with any aluminum threads to prevent the potential of aluminum galling an electrically conductive thread lubricant is recommended to be applied to the SITRANS AW210 NPT threads prior to assembly Refer to Section 11 Certifications for the enclosure ratings DM1101020UBB Copyright 2012 39 of 50 11 Certifications 11 1 European Directive Information The EU Declaration of Conformity for this product can be found on the SIEMENS web site www siemens com wirelesshart ATEX Directive 94 9 EC Th
40. ccoccocccoconcconocnncnconnnnanonnnnoos 14 3 3 4 SITRANS AW210 with HART Field Devices in Multi Drop Mode oococcoccoccocccccocconcoccnnoo 15 3 3 5 SITRANS AW210 with HART Field Devices in LOOP POWER Multi Drop Mode 15 3 3 6 SITRANS AW210 with HART Field Devices in DIRECT POWER Multi Drop Mode 16 3 3 7 SITRANS AW210 with a 4 20mA Field Device with Battery Powered Operation 17 DETAILED SETTINGS AND PARAMETER DEFINITIONS ococcoconcoconcononcanoncancnrancaroncaroncaronrannarano 17 A AEWA Bt AMVC Y ANNA SS aia Seidel ri ied Spm So lb iat wba 17 4 1 1 Configure Power Mode method cccccceccsecceeceeceecceeceeseeccseseeceeeceeseeseeeceesaeseeseeesenseeees 17 AZ NROWEe rotas an tt dd Mises cotta dd tad silo 21 4 1 3 Join Device to Network Method coocooccocccocccccocncoconcnononoconconnnonconconnnnnnonnrnnnrnnnnronanennnnnenanos 22 AE NEW ON ID e a da a 22 A OM a o do Melee e 22 AOS Rado QUIDUEPFOWE sacsasioe tad a a a E ae eaeeeee 22 AT Scanfor Devices MeMO rirnan aE o 24 ATO AZO MA SINO Sr oie 24 Aek E NTU ce Bee Seat hhc aca Mech se ch ag a eta aga egal 24 4 2 Automatic Burst Mode Configuration ccccccccecceecseeeeeeseeeeeeeeeeseeeaeeeeeeseeeaeeaeeeseeeneeseeenes 25 A y OOO R O CL aa 25 4 4 ALERTS A A A 26 AAT A A no celecatehatelanatanelatguaceiasiementaagneteasnieaekianiuadeciaanes 26 Az SALE IST usada da dista 27 AS GICAL Alen Metod sais 27 AA
41. ction Description The radio module inside the SITRANS AW210 is malfunctioning Corrective Action Report this issue to SIEMENS Timestamps Start Set when the radio malfunction was detected Stop Set when the radio malfunction clears 4 4 21 ALERT Variable Simulation Description One or more of the device variables are being simulated Corrective Action Check the simulation settings for the variables Timestamps Start Set when one of the device variables is put into simulation mode Stop Set when all of the devices variables are put into normal mode DM1101020UBB Copyright 2012 32 of 50 4 4 22 ALERT Field Device Cutoff Occurred Description The Field Device Cutoff function is enabled and the direct power voltage dropped below this setting causing the Field Device power to be cutoff Corrective Action Ensure the direct power voltage is a high enough voltage Timestamps Start Set when the field device cutoff occurs Stop Set when the field device cutoff ends by having a direct power voltage high enough 4 4 23 ALERT Low Battery Description The SITRANS AW210 is configured to use an external battery and the battery voltage has dropped below the Battery Low Voltage parameter or the calculated remaining battery life is under 25 days remaining Corrective Action Replace the external battery Timestamps art when the external battery voltage or remaining life calculation passes the l
42. d prior to installation of the SITRANS AW210 in the field Initial configuration is performed through the use of a HART Device Descriptor DD or Device Type Manager DTM for the SITRANS AW210 over the wired HART connection Once connected to the WirelessHART network configuration changes can be made using the DD DTM over either the wired HART interface or the WirelessHART interface 2 1 Bench Top Hookup Tools Required e 7 32VDC Power Supply e HART modem e WirelessHART network settings Network ID an Join Key e PC with DIM Frame application PACTware with the SITRANS AW210 and Com DTMs installed Before configuring the bench top configuration test setup adjust the DIRECT POWER source to a voltage between 7 32VDC and turn off the DIRECT POWER source Configure the SITRANS AW210 DIRECT POWER source and HART communicator per Figure 1 Referring to Figure 1 connect the DIRECT POWER source positive terminal to the SITRANS AW210 s black lead wire and the DIRECT POWER source negative terminal to the SITRANS AW210 s white lead wire Connect HART modem to the SITRANS AW210 The SITRANS AW210 s HART signal connections are polarity independent Connect the HART modem leads to the SITRANS AW210 s white lead wire and yellow lead wire Ensure the Loop Power lead wire RED is not connected to any terminal of the DC power Source and or Earth Ground Green Yellow Re verify the test setup is configured per Figure 1 and then turn on
43. detected Stop Set the last time the duplicate HART Master was detected 4 4 12 ALERT HART Devices Count Exceeded Description A HART Master has been detected that is configured as the same Master type as the SITRANS AW210 This will prevent the SITRANS AW210 from communicating with connected Sub Devices while the other HART master is present Corrective Action lf there is another HART Master present ensure that it and the SITRANS AW210 are configured for different HART Master types When using a HART Handheld ensure that it is not set for the same Master Type as the SITRANS AW210 Timestamps Start Set the first time that too many HART devices were detected Stop Same as the start time 4 4 13 ALERT HART Sub Device Lost Description A Sub device connected to the SITRANS AW210 has stopped communicating and has been dropped from the sub device list DM1101020UBB Copyright 2012 29 of 50 Corrective Action If the Sub device was removed intentionally clear the alert Else check the connection power to the sub device and verify communications with a wired HART handheld or PC Timestamps Start Set when the sub device was lost Stop Same as the start time 4 4 14 ALERT Burst Packets are Being Dropped Description One or more burst packets have been dropped from the SITRANS AW210 to the WirelessHART Network Corrective Action Check to ensure that the WirelessHART Network has granted the requested
44. disabled this cutoff will not occur and the Field Device Cutoff Voltage parameter is not used 4 1 1 4 Field Device Cutoff Voltage When enabled defines the direct power voltage at which the Field Device Cutoff will occur There is a built in 0 5V hysteresis in this to bring the SITRANS AW210 out of the Field Device Cutoff mode DM1101020UBB Copyright 2012 19 of 50 4 1 1 5 Field Device Power Control Switching Mode When the SITRANS AW210 is used in the Field Device Power Control Switching mode the SITRANS AW210 will control this switch to power on and off HART Field Devices as needed by the network operation This is useful when running off a limited power source such as an external battery or solar cell and can be used to power off the HART field devices between measurements When used in combination with Burst mode the SITRANS AW210 will schedule measurements from the HART devices connected and will turn on the loop when a scheduled measurement is needed After all the measurements have been read from the connected HART devices the SITRANS AW210 will remove power from the field devices by turning off the Field Device Power Control switch For this mode to work properly the user needs to determine and configure the Power On Time parameter for the connected wired HART field devices Field Device Turn On Time The time in seconds that a HART field device needs to be powered on in order to obtain an accura
45. e selected model of the SITRANS AW210 is appropriate for that installation For Class Zone and Zone installations the SITRANS AW210 nameplate is to be permanently marked to denote that installation Refer to Section 3 2 3 Nameplate for more details For all installations in areas classified as a hazardous location denoted as Class Division Class Zone and or Zone refer to Section 11 Certifications for any the special condition of use notices and or instalaltion warnings For all installations in areas classified as a hazardous location denoted as Class Division Class Zone and or Zone all fittings junction boxes conduit seals cable glands cabling wiring conduit and any other materials related to the installation of this product must be approved listed and or recognized as suitable for use by a recognized approval agency notified body and or national certification body for use in that classified area for that specific protection type and temperature class DM1101020UBB Copyright 2012 10 of 50 Refer to Section 12 CONTROL Drawings for Intrinsically Safe Non Incendive and Non Sparking installation requirements No SITRANS AW210 installed in a non Intrinsically Safe installation can be re installed in a Intrinsically Safe installation A non Intrinsically Safe installation for this product includes ordinary location non incendive explosion proof and installations employing protection types nA nC d and tb WARNINGS
46. e the remaining battery life the battery voltage and the battery coulomb discharge rate Both of these measurements are continuously being performed by the SITRANS AW210 on the battery and both of these measurements are used to determine the remaining battery life and the power status 4 Detailed Settings and Parameter Definitions 4 1 HART Dynamic Variables The SITRANS AW210 appears as a HART device on both the wired HART and WirelessHART networks and supports four HART dynamic variables These can be read using standard HART commands and are displayed in the SITRANS AW210 DD HART Variable WirelessHART Packets per Second Primary Variable PV Loop Current mA secondary Variable SV Direct Power Voltage V Tertiary Variable TV Internal Temperature C Quaternary Variable QV Storage Voltage V Internal to the SITRANS AW210 4 1 1 Configure Power Mode method The Configure Power Mode DD Method guides the user through the selection of the proper power mode settings for their configuration DM1101020UBB Copyright 2012 17 of 50 4 1 1 1 SITRANS AW210 Power By Default the SITRANS AW210 is configured for loop powered operation with a 1 0V insertion voltage drop Through the DD the power setting can be changed to set the insertion voltage drop to 1 0V 1 5V 2 0V or 2 5V The power mode setting can also be set to several different direct power modes Adapter Power Setting WirelessHART Packets per Second Direct Pow
47. eceeceeseeeceeseeseeseeeseeserees 31 4419 ALERT SITRANS AW210 Failed to Join the Network cccceceececceceeenceueenseneeneenes 32 44 20 ALERT Radio MalfuUNC ION ooooooccccnccccccncnncnnnnnnnncnnnnnonnnn cnn nro nr anno n nr rr nn narran narra rra nrnnnnnnnnss 32 4 4 21 ALERT Variable SimulatiON oocococconcococonocncococonconoononononnnononnnonnnononnnnnnnnnonnnennnnninonn 32 4 4 22 ALERT Field Device Cutoff Occurred oocoocccccocccoccncoocococonconononconconnnonnnnnonanonnnnroncnnnnnnninanos 33 d2 ALERT LOW DAY AE a E 33 4 5 HART Device Description DD TREE ooccocccoccnccncconoconccnnconocononcnconaconanonconnnoncnnnrnnarenannns 34 5 MAINTENANCE sara 35 6 COMMISSIONING iii dias 35 7 TROUBLESHOO TNG OS 36 8 PRODUCT ORDER INFORMATION coococcoconcoconcoroncanoncanancnncarancnrnncaronrnnnnrnnnnrnrrnrnnrnrnnraronrnanarano 37 9 SPECIFICA TON Su A a 38 10 MECHANICAL cae aaeiicadas 39 10 1 1 Dimensional Drawing occoocconcococcnconconoconnononcocnncnnonnnnnnnnnonnnonnnnnnnnnnnnnnnonnnnnnrnnennnnnninnenoss 39 T2 ENCON 39 11 GERTIEICA TON Sisa 40 11 1 European Directive InforMatiON ooccoocconconcoccoccconconoonoocncancnnonnnnnonnncononnnnnonnnanennannnns 40 11 2 Telecommunication Compliance occoocccncoccociccnconcononnoncnnononnnnnnononnnonnnnnonnnnnnnnncanennnneos 40 AA A ha E at ae ieee Jeet oye a eran dae 40 PZA RE e o ee Oe ee 40 11 3 Ordinary Locations
48. ed by means of the HART Device Description DD A password will be requested s part of the this reset process password siemens DM1101020UBB Copyright 2012 25 of 50 SITRANS AW210 Parameter Default Value 1229 44555354 4E455457 4F524B53 524F434B hex Don t Join HARTRetryCount Pt HART Polling Address 5 HART Response Preambles DO Write Protect HART Lock State HART Polling Scan Start Address Electronics Temperature Units 3 15 A HART Polling Scan Stop Address 5 mA Enabled PY ts ma a lt _ 5 4 4 ALERTS The SITRANS AW210 will detect and log system events to alert the user when something has occurred that could effects system operation Note All Alerts are also mapped into HART Command 48 status bits 4 4 1 Active Alerts The condition that caused the alert is still present Active alerts cannot be cleared corrective action must be taken to eliminate the alert such as modifying some external source of the event such as the power supply or by changing an incorrect setting in the SITRANS AW210 DM1101020UBB Copyright 2012 26 of 50 4 4 2 Alert History The condition that caused the alert is no longer present or the alert is a onetime event The start timestamp indicates when this alert first occurred and the stop timestamp indicates when the alert stopped or the last time the alert was detected 4 4 3 Clear Alert method This will clear the current alert
49. ered Max Bandwidth 101 40 Direct Powered Power Save 26 66 Direct Powered Battery 26 66 NOTE The value shown in WirelessHART Packets per second column is the value reported back in HART Command 777 Loop Powered This allows for different StepVolt settings to be selected when operating in a loop powered mode Direct Powered Max Bandwidth This allows for the maximum WirelessHART bandwidth possible and assumes that the direct power source can supply maximum power Direct Powered Power Save This assumes that the direct power source is limited and will limit the amount of WirelessHART packets to a small amount to conserve power Direct Powered External Battery This assumes that the direct power source is an external battery and this will enable the built in battery management functionality battery life calculations battery alerts in the SITRANS AW210 DM1101020UBB Copyright 2012 18 of 50 NOTES e The SITRANS AW210 will power up and begin to operate with any valid power installation regardless of what the SITRANS AW210 s Power setting is configured as This allows for the user to change this setting even if it is configured incorrectly however any changes to this should be performed before the SITRANS AW210 has joined the WirelessHART network If this power setting set different than how the SITRANS AW210 is actually powered such as a Direct Powered setting is selected but the unit is actuall
50. evice The SITRANS AW210 communicates as a wired HART master to connected HART devices on the loop and can transmit and receive HART data from these connected HART devices to the WirelessHART network The SITRANS AW210 also supports being configured like a wired HART slave device so traditional HART configuration tools such as HART Field Communicators and PCs with HART modems can be used to configure the SITRANS AW210 In WirelessHART terminology any wired HART devices that can be communicated with a WirelessHART Adapter are known as a sub device A single SITRANS AW210 WirelessHART Adapter can support up to eight 8 wired HART sub devices The WirelessHART Gateway maintains a list of all of the devices in the WirelessHART network including sub devices connected to WirelessHART Adapters Host applications that communicate with the WirelessHART gateway communicates in directly with the wired HART sub device through the WirelessHART Adapter The WirelessHART gateway and WirelessHART Adapter transparently handle the message conversion between the Host application and wired HART sub device WirelessHART supports publishing of data from devices to the WirelessHART Gateway on a periodic basis This is called burst mode in HART terms but is much more advanced than the burst mode traditionally supported by HART devices Data can be burst based on an user defined update time or by a user specified triggered event such as a process variable ala
51. gs for the device and reduce the requested bandwidth Timestamps Start Set when the WirelessHART Network first denies bandwidth Stop Set when the WirelessHART Network grants bandwidth 4 4 17 ALERT Burst Message Configuration Issue Description A burst message is configured to a command that is not supported by the selected Sub device Corrective Action Change the command number of the burst message to a command that is supported by the Sub device Timestamps Start Set when the configuration issue if first detected Stop Set when the configuration issue is corrected 4 4 18 ALERT Wired Device in Burst Mode Description A wired device is configured for wired burst mode which may conflict with the SITRANS AW210 burst settings Corrective Action Change the configuration of the wired device to not be in wired burst mode Timestamps Start Set when the wired burst mode message is first detected Stop Set when the last wired burst mode message was detected DM1101020UBB Copyright 2012 31 of 50 4 4 19 ALERT SITRANS AW210 Failed to Join the Network Description The SITRANS AW210 has failed to join the WirelessHART Network Corrective Action Check the Network ID and Join key set on both the SITRANS AW210 and the WirelessHART Network Timestamps Start Set when the WirelessHART Network Join procedure failed Stop Set when the WirelessHART Network Join procedure succeeds 4 4 20 ALERT Radio Malfun
52. he loop after the SITRANS AW210 is powered execute the Scan for Sub Devices method or reset the SITRANS AW210 to detect them The SITRANS AW210 can support a maximum of eight sub devices If more than eight wired HART devices are detected only the first eight devices will be used 4 1 6 8 Scan Start Address This is the first HART polling address that will be used when a scan for Sub devices is performed DM1101020UBB Copyright 2012 23 of 50 4 1 6 9 Scan Stop Address This is the last HART polling address that will be used when a scan for Sub devices is performed 4 1 7 Scan for Devices method The Scan for Devices DD method will perform a scan for sub devices connected to the SITRANS AW210 across the HART polling addresses defined This method allows for the existing sub device list to be either retained or erased prior to the new scan 4 1 8 4 20 mA Settings The SITRANS AW210 has the ability to measure the loop current from field devices when wired in a loop powered mode The SITRANS AW210 can be connected to analog only 4 20 mA field devices with no HART capability and report this loop current value to the WirelessHART Network The SITRANS AW210 can convert the 4 20 mA value read from a field device into engineering units that are reported to the WirelessHART network as the Primary Variable PV of the SITRANS AW210 The SITRANS AW210 can also implement a lookup table to linearize this conversion 4 1 9 PV Uni
53. ing connection is typical tied to the internal earth grounding terminal of the Field Device or junction box WARNING GROUND EQUIPMENT AS REQUIRED BY NATIONAL REGIONAL LOCAL ELECTRICAL CODES AND PRACTICES 3 3 Installation Options The flowing sections describe several installation options for the SITRANS AW210 Please contact SIEMENS if you need help in determining how best to connect the SITRANS AW210 for your application To contact SIEMENS Support Center call 49 0 180 5050 222 or visit the SIEMENS web site at http www siemens com automation support request 3 3 1 SITRANS AW210 as a Standalone WirelessHART Router Repeater The SITRANS AW210 is not attached to any Field Devices It is strictly used at key points in a WirelessHART network to help with the WirelessHART routing of packets on behalf of other network connected devices This is useful when it is identified in a WirelessHART network that additional WirelessHART devices located at key points will improve the overall network robustness In this installation option the SITRANS AW210 is powered by a DC power source supplied by direct power The SITRANS AW210 can be powered by an external DC power source such as DC power supply battery or solar panel The DIRECT POWER specified input voltage range is 7VDC to 32VDC For direct powered operation connect the DC power source positive terminal t DIRECT POWER black lead wire and the DC power source negative terminal to the S
54. ings 12 Sub Device 6 13 Sub Device 7 1 Burst Mode E 1 Join Device to Network b 14 Sub Device 8 2 Disc Device from Network 3 Ta e e 1 Configure Power Mode 3 Network ID a Update Period 2 Join Device to Network 4 Join Mode 5 Advanced 5 Radio Output Power 6 4 Guided Setup 6 Over the Air Upgrade 5 pores 1 Trigger Mode 3 Wired 1 Master Mode 2 Trigger Level 2 Manual Setup 4 4 20 mA 2 Retry Count ae tne 3 Polling Address AN O 5 Burst Settings E 5 Device Variables 6 Event Settings 4 Sub Device Time Sync 7 Device Information 5 Scan on Power Up cia ale aaa 6 Scan Start Address 1 Ta 7 Scan Stop Address 2 E Tag 8 Scan for Devices 1 Burst Variable Code 1 3 Device Information a lesa 5 License Information 3 MAC Address 1 Battery Capacity 4 Burst Variable Code 4 i 4 Serial Number 2 Battery Low Voltage 5 Burst Variable Code 5 5 Model Number 3 Battery Critical Voltage 6 Burst Variable Code 6 6 Production Date 4 Power Status 7 Burst Variable Code 7 q Wireless Manufacturer 7 Lot Num 5 Battery Life Remaining 8 Burst Variable Code 8 2 Device Type a ende S Sais Seeley He 3 Device Revision 10 da od oa meee A Sonware Rev Field device rev 8 Battery Capacity Remain 1 Burst Cmd 6 Hardware Rev 1 E rev 9 Last Battery Changed 2 Value Ol aa e A mi 7 Software Rev Minor ie en nt 3 ean ity 8 Software Rev Patch ie e Date 9 Software Rev Build a ae J Point Burst m 6 Time Burst Message 17 Final asmbly
55. is product compiles with the ATEX Directive Electro Magnetic Compatibility Directive EMC 2004 108 EC This product compiles with the EMC Directive Radio and Telecommunications Terminal Equipment Directive R amp TTE 1995 EC This product compiles with the R amp TTE Directive Declaration of Conformity The Declaration of Conformity can be obtained be either contacting the SIEMENS or visiting the web site at www siemens com wirelesshart 11 2 Telecommunication Compliance All Wireless devices require certifications of compliance to ensure that they meet applicable regulations regarding to the RF spectrum This type of certification is required by most countries SIEMENS is seeking certification in the countries of use as required by national regulations to provide a fully compliant product 11 2 1 FCC IC This device complies with FCC rules Part 15 of CFR 47 and IC specification RSS 210 The operation of this devise is subject to the following conditions of use This device will not cause harmful interference This device must accept any interference received including inference that may cause undesirable operation To ensure FCC and IC compliance this device is to be used as configured from the factory No modifications to either the radio or antenna are allowed 11 2 2 R amp TTE Radio and Telecommunications Terminal Equipment Directive R amp TTE 1995 EC This product compiles with the R amp TTE Directive 11 3 Ordina
56. ith the WirelessHART Gateway verify that the SITRANS AW210 has been detected and that all of the connected wired HART sub devices have been detected NOTES e The SITRANS AW210 should be installed after the WirelessHART gateway has been installed and is verified to be working NOTE To speed the WirelessHART joining procedure it is recommended to turn on the Active Advertising mode of the WirelessHART Gateway whenever new devices are added DM1101020UBB Copyright 2012 35 of 50 7 Troubleshooting Does Not Detect Wired HART Sub Devices Verify the SITRANS AW210 wiring for the mode of operation that is being used Verify HART communication with the SITRANS AW210 with a HART Communicator or PC with HART modem Once this is working without moving the HART connections on the modem verify HART operation with the HART sub device lf the HART Communicator is able to communicate with both the sub device and the SITRANS AW210 the SITRANS AW210 should be able to communicate with the sub device Cannot Connect to the WirelessHART Network Check the WirelessHART Gateway for the correct Network ID and Network Join Keys Using the SITRANS AW210 HART DD both of these settings are entered in with a decimal format It is possible that either of these settings are shown in a hexadecimal format on the WirelessHART Gateway If so convert these values into a decimal format before entering them into the SITRANS AW210 Resetting the SITRANS AW210
57. ithin a suitable ATEX Certified Ex d or Ex e terminal or junction facility The Ex d IIC configuration requires the use of an ATEX Certified cable seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility IECEx Listing Special Condition of Use The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated within a suitable IECEx Certified Ex d or Ex e terminal or junction facility The Ex d IIC configuration requires the use of an IECEx Certified cable seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility DM1101020UBB Copyright 2012 46 of 50 12 Control Drawing 8 7 6 4 3 2 1 NOTES 1 NO REVISION TO DRAWING WITHOUT PRIOR FM APPROVAL AREA CLASSIFICATIONS 2 FOR INSTALLATIONS IN THE U S THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE FM APPROVED HAZARDOUS AREA UNCLASSIFIED AREA 3 FOR INSTALLATIONS IN CANADA THE ASSOCIATED APPARATUS AND FIELD DEVICE MUST BE CANADIAN CERTIFIED INTRINSICALLY SAFE GAS ORDINARY LOCATION 4 FOR ZONE INSTALLATIONS THE ASSOCIATE
58. l Connection The following table described the lead wire and function of the lead wires exiting the SITRANS AW210 NPT port Wire Color Wire Gage Description Green 14AWG Internal Earth Ground Yellow Red 20AWG LoopPower_ 20AWG 20AWG HART External Accepts External Earth Ground 10AWG 4mm Grounding Screw wire connection 3 2 4 1 Field Wiring Functional Description DIRECT POWER connections are between the black lead wire tied to the positive source terminal and RETURN the white lead wire to the negative source terminal LOOP POWER connections are between the red lead wire tied to the positive current loop source terminal and RETURN the white lead wire tied to the negative current loop terminal HART connections are between the yellow lead wire and the RETURN white lead wire The SITRANS AW210 HART connections are polarity independent DM1101020UBB Copyright 2012 12 of 50 WARNING TERMINATE UNUSED LEAD WIRES AS REQUIRED BY NATIONAL REGIONAL AND LOCAL ELECTRICAL CODES AND PRACTICES 3 2 5 Grounding The SITRANS AW210 provides an external and internal grounding connection The external grounding connection will accept up to a 1OAWG 4mm gage wire The grounding conductor is secured by means of a stainless steel screw 10 32 with a captive washer The internal ground connection is attached to the metal housing and exits the threaded Y NPT as a 14 AWG GREEN YELLOW lead wire This ground
59. n 0 5 Volt increments StepVolt allows users to select the best insertion voltage drop for their application The higher the voltage drop setting used the more WirelessHART messages the SITRANS AW210 will be able to transmit and receive In applications where there is very little voltage overhead in the loop such as transmitters on very long cable runs or with IS barriers StepVolt allows the selection of a low insertion voltage drop However in typical applications there is adequate voltage overhead on the loop to allow for a higher insertion voltage drop from the SITRANS AW210 A concern with a loop powered WirelessHART Adapter is being able to operate under worst case low current conditions since very little power is available to be used by the Adapter The SITRANS AW210 is designed to operate at the worst case operating conditions at all power settings and will respond to Wired or WirelessHART commands The SITRANS AW210 will operate as specified with reliable communications even under the following conditions Loop current of 3 2mA and 1 0V insertion voltage drop Temperature Extremes 40C to 85C Worst Case wired HART communication on the loop Constant wired HART communication addressed to the Adapter and the Adapter responding to every command Every WirelessHART timeslot filled and transmitting NOTES e On power up the insertion voltage drop will default to 1 0V until the SITRANS AW210 has finished initializa
60. o see that they are correct At this point the SITRANS AW210 is ready to be installed and commissioned in the field For installation information and wiring drawings proceed to Section 4 Installation 3 Installation The SITRANS AW210 was designed to be extremely flexible and support a variety of installation options A typical SITRANS AW210 installation to a field device is shown Figure 2 The SITRANS AW210 is attached to the field device using the standard commercially available hardware as required by the installation requirements and area classification In explosion proof locations instead of fittings we recommend to use a junction box due to the increased volume DM1101020UBB Copyright 2012 9 of 50 WirelessHART _ Adapter PORT ee 90 ELBOW FITTING UNION COUPLER ADAPTER SPARE 2nd PORT FIELD DEVICE FIGURE 2 Typical SITRANS AW210 Field Device installation 3 1 Ordinary and Hazardous Locations The SITRANS AW210 has been approved for use in both non classified denoted as Ordinary Location and areas classified as Hazardous Locations denoted as Class Division Class Zone and Zone The model number and approval marking on the nameplate defined where the SITRANS AW210 may be installed Refer to Section 8 Product Ordering information and Section 11 Certificates for the approval markings Each SITRANS AW210 nameplate located on the housing is clearly marked with that model approval markings Verify that th
61. ow battery reshold Stop Set when the external battery voltage is above the low battery threshold or the user clears the battery counters DM1101020UBB Copyright 2012 33 of 50 4 5 HART Device Description DD TREE 3 1 Alerts 1 Mfg ID 1 STXt i F 1 Overview o Subdevice 1 Turn On Time 2 Wireless Status 2 Device Type 2 ACK from Subdevice 2 Idle Time 2 Configure 7 e 5 E 3 BACK from Subdevice 3 Estimated On Percent s Loop Curren A Service Tools 5 Direct Power Voltage 5 Tag A Electronics T t 6 Long Ta e 7 Poll Addr 1 Configure Power Mode a ee 8 Sub Device 2 8 Loop Current Mode ES A D a A tae ea z 3 Field Device Power Ctrl a DERAN Mea vORage 9 Sub Device 3 9 Device Status 4 Battery Change 10 Sub Device 4 10 Command Support 4 Fid Device Pwr Settings 11 Sub Device 5 41 Statistics 5 External Battery Sett
62. r mode configuration settings Corrective Action Check the Adapter Power mode setting to ensure it is the same as how the SITRANS AW210 is wired Timestamps Start Set when the alert is first detected Stop Set when the alert state goes away 4 4 9 ALERT Watchdog Reset Description The microprocessor inside of the SITRANS AW210 has experienced a watchdog reset event Corrective Action Clear the alert report the event to SIEMENS Timestamps Start Set when the alert is first detected Stop Not Used 4 4 10 ALERT Stack Overflow Description The microprocessor inside of the SITRANS AW210 has experienced a stack overflow event Corrective Action Clear the alert report the event to SIEMENS DM1101020UBB Copyright 2012 28 of 50 Timestamps Start Set when the alert is first detected Stop Not Used 4 4 11 ALERT Duplicate HART Master Detected Description A HART Master has been detected that is configured as the same Master type as the SITRANS AW210 This will prevent the SITRANS AW210 from communicating with connected Sub Devices while the other HART master is present Corrective Action lf there is another HART Master present ensure that it and the SITRANS AW210 are configured for different HART Master types When using a HART Handheld ensure that it is not set for the same Master Type as the SITRANS AW210 Timestamps Start Set the first time the duplicate HART Master was
63. rm When the SITRANS AW210 is configured in burst mode it supports all of these advanced modes on behalf of any connected wired HART sub devices Burst mode is also very useful to publish device status data such as malfunctions or alarms to the Gateway on a periodic basis or immediately when a critical event occurs 1 3 Typical Usage In most typical network configurations the SITRANS AW210 will be used in conjunction with a wired HART sub device and configured to publish process data and device status data from the connected sub device to the WirelessHART network on a user defined periodic basis Such as every 8 seconds or every minute etc The SITRANS AW210 adds several features to make this typical usage mode very easy to configure such as the Automatic Sub Device detection and Automatic Burst mode configuration 1 4 Power The SITRANS AW210 WirelessHART Adapter has been designed to be extremely power efficient and flexible to allow for a wide variety of installation options The SITRANS AW210 can be installed to be powered by one of two sources either 1 current loop denoted as LOOP POWER or 2 by a DC source denoted as DIRECT POWER DM1101020UBB Copyright 2012 4 of 50 1 4 1 Loop Powered Mode The SITRANS AW210 can be wired in series with devices on a 4 20mA loop and be powered from the loop The SITRANS AW210 utilizes StepVolt technology to allow the user to set this insertion voltage drop between 1 0 2 5 Volts i
64. rotect disabled Through the DD the write protect setting can be enabled or disabled 4 1 6 6 Sub Device Time Synchronization lf a HART 7 or greater sub device is detected and it supports a real time clock the SITRANS AW210 can synchronize the sub device time with the WirelessHART Network time if this setting is enabled If the sub device does not support a real time clock this setting has no effect This synchronization will be performed when the SITRANS AW210 joins the WirelessHART network and then once per day 4 1 6 7 Sub Device Scan on Power up When Sub Device Scan on Power up is enabled the SITRANS AW210 will scan the 4 20mA loop for attached HART devices on power up or when the SITRANS AW210 is reset These will be added to the list of supported sub devices for the SITRANS AW210 and will be communicated with the WirelessHART gateway Within the DD Automatic Sub device detection can be enabled or disabled It is highly recommended that this mode always be left enabled If this mode is disabled the host must support scanning for sub devices in order for any sub device to be detected or you must manually execute the Scan for Sub Devices method The list of sub devices is not retained through a power cycle or reset of the SITRANS AW210 so the host would need to detect this and rescan for sub devices NOTES e The sub device scan is only performed after a power up or reset of the SITRANS AW210 If wired HART devices are added to t
65. ry Locations Certifications As requirement of the R amp TTE Directive and Hazardous Location approval process this product has been examined and tested to meet basic electrical mechanical and fire protection requirements of EN61010 1 and ANSI ISA 61010 1 11 4 Hazardous Location Certificates Issuing approval agencies FM Approvals for US Canada and IEC FM Approvals Ltd for ATEX DM1101020UBB Copyright 2012 40 of 50 11 4 1 North America Certificates 11 4 1 1 United States Certificates CLASS DIVISION GAS DUST and FIBER Intrinsically Safe for Class I Il Ill Division 1 Groups A B C D E F G Non Incendive for Class I Division 2 Group A B C D Suitable for Use Class Il III Division 2 Group E F G Intrinsically Safe and Suitable for use when installed per SIEMENS Drawing AT1101030C Explosionproof for Class I Il Ill Division 1 Groups A B C D E F G DUST IGNITIONPROOF for Class Il III Division 1 Group E F G FACTORY SEALED CONDUIT SEAL NOT REQUIRED ZONE MARKINGS Intrinsically Safe GAS 111 G Class 1 Zone O AEx la IIC Ga T5 T6 Intrinsically Safe DUST 111 D Zone 20 AEx iaD 20 IP68 T95 C Non Sparking GAS Encapsulated GAS II 3 G Class 1 Zone 2 AEx nA nC IIC T5 T6 Flameproof GAS II 2 G Class 1 Zone 1 AExd IIC T5 T6 Gb Flameproof DUST Il 2 D Zone 21 AEx tb IIICT95 C TEMPERATURE CLASS T5 40 C to 85 C T6 40 C to 75 C ENCLOSURE RATING TYPE 6P IP68 1 8m 24hr E
66. seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility Zone Notice Using the box provided on the nameplate the user shall permanently mark the type of protection chosen for the specific installation Once the type of protection has been marked it shall not be changed 11 4 2 European ATEX Certificates Certification Number FMATEX0082X Intrinsically Safe GAS 8 II 1 G Zone 0 Ex ia IIC Ga Temp Class T5 T6 Intrinsically Safe DUST amp II 1 D Zone 20 Ex iaD 20 IP68 T95 C Certification Number FMATEX0083X Non Sparking GAS Encapsulation GAS Il 3 G Zone 2 Ex nA nC IIC T5 T6 Certification Number FMATEX0084X Flameproof GAS Il 2 G Class 1 Zone 1 Exd IIC T5 T6 Gb Enclosure Type IP68 Flameproof DUST II 2 D Class 1 Zone 21 Ex tb IlIC T95 C TEMPERATURE CLASS T5 40 C to 85 C T6 40 C to 75 C ENTITY PARAMETERS Ui 30V li 120mA Pi 0 9W Ci OuFD Li 596uH DM1101020UBB Copyright 2012 43 of 50 11 4 2 European ATEX Certificates continued ENCLOSURE RATING IP68 1 8m 24h Zone 0 Special condition of use X This product enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction Care must be taken into account during installation and use to prevent impact and friction Zone Notice Using the box provided on the nameplate the user shall
67. ss transmissions performed by these devices impact their battery life The more WirelessHART devices that a battery powered node has to route messages for the shorter its overall battery life The SITRANS AW210 is different since it is loop powered it can support Wireless messages indefinitely without any concerns of battery life By placing SITRANS AW210 at key locations in a WirelessHART network such as places that route messages for other WirelessHART nodes this routing function can be offloaded from battery powered nodes to the SITRANS AW210 and help to preserve their battery life of the battery powered nodes StepVolt Setting WirelessHART Packets per Second NOTES The value shown in WirelessHART Packets per second column is the value reported back in HART Command 777 Recommendation Using the highest StepVolt setting possible will improve the overall WirelessHART network performance 1 4 3 Direct Powered Mode The SITRANS AW210 can be powered by an external DC power source such as battery solar panel or the DC power supply used to power the Field device The DIRECT POWER voltage range is 7VDC to 32VDC The DIRECT POWER connections are 1 DIRECT POWER black lead wire to the positive potential and 2 RETURN white lead wire to the negative terminal of the external DC source DM1101020UBB Copyright 2012 6 of 50 2 Configuration This section contains information on configuration that should be performe
68. te measurement NOTES e Improper selection of the Power On Time parameter can lead to a field device reporting measurements outside of the published tolerances for the device Consult the field device documentation or contact the field device vendor to determine this information The Power On Time is different for every Field Device If not specified in the Field Device data sheet contact the manufacturer of the Field Device for this parameter Incorrect measurement reading from the Field Device may result if Power On Time parameter is not set properly The Field Device may not have adequate time to power up initialize and respond with a correct measurement value prior to power being removed Field Device Idle Time The time in seconds that the field device will remain powered after an unscheduled event This event could be a HART query over the WirelessHART handheld or detection of another HART master trying to communicate such as a wired HART handheld This parameter prevents the SITRANS AW210 from powering off a field device when some other master is attempting communication with the field device This parameter can generally be left at the default of 60 seconds 4 1 1 6 Field Device On Estimated Percentage This is the estimated time that the field device will be powered during normal operation This is a calculation based upon the Field Device Power On Time and the Burst mode settings of the SITRANS AW210 The
69. time 10 PV Linearization Table s 2 Curent Date 7 Simulate 3 Curent Time 1 STX Sent 1 Wireless Status 2 ACK Received 2 Wireless Statistics 3 OSTX Received 1 Simulate Loop Curent 3 Wired Slave Statistics 4 OACK Received 2 Simulate Direct Power 4 Wired Master Statistics 5 BACK Received 3 Simulate Temperature DM1101020UBB Copyright 2012 34 of 50 5 Maintenance The SITRANS AW210 has no scheduled maintenance requirements and has no serviceable parts As required to maintain optimum antenna performance periodically removal any accumulated material from the dome such as dust fiber snow and ice Use caution in removing any material off the resin dome so as not to damage the dome or mechanically stress the NPT threaded connection No solvents should used in the removal of any accumulated material 6 Commissioning Upon power up of the SITRANS AW210 in the field the SITRANS AW210 will attempt to identify any connected HART devices if the Automatic Sub device Detection option is enabled Operation can be verified through the use of the SITRANS AW210 HART DD via a HART communicator or PC with HART Modem Operation can also be verified via the WirelessHART Gateway interface With the DD verify that the correct HART sub device s have been detected by the SITRANS AW210 Also verify that the SITRANS AW210 is attempting to join or has joined the WirelessHART Network W
70. tion 4 1 2 2 Battery Capacity This is the capacity of the battery in milliamp Hours and is used by the coulomb counter algorithm to determine the remaining battery life in days 4 1 2 3 Battery Low Voltage This is the battery voltage value below which the power status will be set to Low and the battery life remaining will be 25 days or less This is an independent failsafe check for the coulomb counter remaining life calculation 4 1 2 4 Battery Critical Voltage This is the battery voltage value below which the power status will be set to Critical and the battery life remaining will be set to O days This is an independent failsafe check for the coulomb counter remaining life calculation DM1101020UBB Copyright 2012 21 of 50 4 1 3 Join Device to Network method The Join Device to Network DD Method guides the user through entering in the WirelessHART network ID and join key and starting the WirelessHART join procedure 4 1 4 Network ID The Network ID is the ID of the WirelessHART Network to join 4 1 5 Join Key The Join Key is a 32 character hexadecimal password broken into four 8 character blocks which is used to get access to the WirelessHART network 4 1 6 Radio Output Power The transmit power of the SITRANS AW210 s radio Can be set to either OdBm or 10dBm 4 1 6 1 HART Polling Address This is the HART polling address that is used to communicate to the SITRANS AW210 on the wired HART interface
71. tion After initialization the insertion voltage drop will change to the user specified value in the HART Device Description DD The SITRANS AW210 cannot control the loop current if connected in loop powered mode there must be device controlling the loop current such as a 4 20mA WARNING IF THE SITRANS AW210 HAS AN INTERNAL FAILURE AND STOP REGULATING TO THE SPECIFIED STEPVOLT VALUE THE MAXIMUM INSERTION VOLTAGE DROP CAN RISE TO 4 935VDC DM1101020UBB Copyright 2012 5 of 50 1 4 2 StepVolt M Benefits The benefit to using a high StepVolt setting is that the SITRANS AW210 will be able to support a much higher amount of WirelessHART packets per second Even if the particular device attached to the SITRANS AW210 is configured for a very low update rate being able to support a high amount of WirelessHART packets per second helps the overall WirelessHART network operation WirelessHART is a mesh network each node in the network will route messages on behalf of other nodes in the network This is done to expand the overall range of the network and also for the data reliability of the network by forming multiple redundant paths By setting the SITRANS AW210 to a high StepVolt setting more WirelessHART packets can be routed through the SITRANS AW210 for other nodes in the network Another consideration from a WirelessHART network standpoint is that many devices in a WirelessHART network are battery powered and all Wirele
72. to account during installation and use to prevent impact and friction Zone Notice Using the box provided on the nameplate the user shall permanently mark the type of protection chosen for the specific installation Once the type of protection has been marked it shall not be changed Ex d IIC Special Conditions of Use 1 The flying leads of the apparatus shall be suitably protected against mechanical damage and terminated within a suitable IECEx Certified Ex d or Ex e terminal or junction facility 2 The Ex d IIC configuration requires the use of an IECEx Certified cable seal suitable for the location and conditions of use installed at the apparatus and prior to the terminal or junction facility 11 4 4 Required Certification Notices and Warnings As required by the standards for which this product has been approved the following Notices and Warnings are required to be listed in this document WARNING FIELD WIRING MUST BE RATED FOR 85C MINIMUM WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT WHEN A FLAMMABLE OR COMBUSTIBLE ATMOSPHERE IS PRESENT WARNING MAXIMUM OPERATING TEMPERATURE IS 85C CAUTION WHEN HANDLING HOT SURFACES Class 1 Zone 0 and ZONE 0 Special Condition of Use This product enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction Care must be taken into account during installation and use to prevent impact and friction CLASS Zone and Zone
73. ts The engineering units that the SITRANS AW210 PV will be reported as 4 1 9 1 PV Linearization Mode This can be set to Linear or Special Curve If set to Linear the PV Upper Range Value and Lower Range Value will be the values in engineering units that correspond to the 4 and 20 mA points and a basic linear calculation will be performed to convert the measured loop current to engineering units It this is set to Special Curve the user can enter in data pairs a loop current value to a engineering unit value into the PV Linearization Table The table needs to have at least two data pairs and can have up to 32 pairs When converting the loop current to engineering units the SITRANS AW210 will use this lookup table to perform a more accurate linearization 4 1 9 2 PV Damping Value This is the damping value in seconds that will be applied to the PV measurement 4 1 9 3 PV Upper Range Value 20 mA When the Linearization Mode is set to Linear this is the value in engineering units that correspond to the loop current at 20 mA DM1101020UBB Copyright 2012 24 of 50 4 1 9 4 PV Lower Range Value 4 mA When the Linearization Mode is set to Linear this is the value in engineering units that correspond to the loop current at 4 mA 4 1 9 5 Upper Fault Current This is the value of the loop current in milliamps that above which will set a HART loop current alarm 4 1 9 6 Upper Limit of Proportional Range This is the value of the
74. with Battery Powered Operation In this installation option the SITRANS AW210 is connected in series with an either an analog only or HART enabled Field Device and can be configured for either Loop Power or DIRECT POWER An external battery or other DC power source such as solar is used to power the SITRANS AW210 and Field Device Configured for Loop power the SITRANS AW210 and Field Device are continuously powered and is not the optimum energy management configuration for battery operation When configured for DIRECT Power the SITRANS AW210 can control the power to the Field Device which will result in optimum energy management for battery operation To manage the battery power the SITRANS AW210 must be configured to use the FIELD DEVICE POWER CONTROL feature which allows the user to specify the battery powered on and off time This software controlled function is enabled by means of the HART Device Description DD The user configures the FIELD DEVICE POWER on time as required by the application and or as required by the Field Device to operate properly The SITRANS AW210 has internal circuitry to monitor battery consumption when an external battery is used for the Direct Power input Since the battery is external there are many possible battery options that the user could employ therefore the SITRANS AW210 battery measurement circuitry is very flexible and configurable There are two major variables measured to determin
75. y loop powered the system operation is not guaranteed and it is possible that the SITRANS AW210 will reset due to insufficient power once connected to the WirelessHART network The unit can be both Direct Powered and wired in series with the loop When configured in any of the Direct Powered modes there will be an insertion voltage drop of 1 0V if the SITRANS AW210 is also wired in series with the loop 4 1 1 2 Field Device Power Control When used in a direct power configuration the SITRANS AW210 can activate a switchable terminating resistor between the HART and the RETURN signal wires This can eliminate the need for an external terminating resistor in some installation and also allows for the field device power to be switchable and controlled automatically by the SITRANS AW210 The parameter Field Device Power Control can be set to three different states Off On or Switching Off The Field Device Power Control switch is never connected On The Field Device Power Control switch is always connected Switching The SITRANS AW210 will automatically control the operation of the Field Device Power Control switch 4 1 1 3 Field Device Cutoff Enable This option allows the SITRANS AW210 to cutoff power to the Field Devices when the direct power input drops below the voltage set in the Field Device Cutoff Voltage parameter To use the cutoff the Field Device Power control must set to either On or Switching When this parameter is

Download Pdf Manuals