Santa Fe Classic Dehumidifier User Manual

image

Contents

1. 4 Compressor terminals C and S No continuity indicates an open start winding The compressor must be replaced Normal start winding resistance 3 to 7 ohms 5 Compressor terminals C and R No continuity indicates an open run winding The compressor must be replaced Normal run winding resistance is 5 to 2 ohms 6 Compressor terminal C and overload terminal 1 No continuity indicates a defective overload lead 7 Overload terminals 1 and 3 If there is no continuity the overload may be tripped Wait 10 minutes and try again If there is still no continuity it is defective and must be replaced 8 Compressor terminal C and compressor case Continuity indicates a grounded motor The compressor must be replaced 9 Disconnect the yellow wires from the capacitor Set the ohmmeter to the Rx1 scale The capacitor is shorted and must be replaced if continuity exists across its terminals lf there is no needle movement with the meter set on the Rx100000 scale the capacitor is open and must be replaced 10 Reconnect the wires to the compressor and capacitor Plug in and turn on the unit If the compressor fails to start replace the run capacitor 11 If the unit doesn t start adding a hard start kit relay amp capacitor will provide greater starting torque If this doesn t work the compressor has an internal mechanical defect and must be replaced 5 6B Replacing a Burned Out Compressor The refrigerant and oil mixture i
2. Replacement filters can be ordered from the factory or purchased locally if available DO NOT operate the unit without the filters or with a less effective filter The heat exchange coils inside the unit could become clogged and require disassembly to clean 5 Service A CAUTION Servicing the Santa Fe Classic with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Only qualified service people should service this unit 5 1 Warranty A warranty certificate has been enclosed with this unit Read it before any repair is initiated If a warranty repair is required call the factory first at 1 800 533 7533 for warranty claim authorization and technical assistance 5 2 Technical Description EVAPORATOR FILTER DRIER CONDENSER The Santa Fe Classic uses a refrigeration system similar to an air conditioner s to remove heat and moisture from incoming air and add heat to the air that is discharged see figure 1 Hot high pressure refrigerant gas is routed from the compressor to the condenser coil see figure 1 The refrigerant is cooled and condensed by giving up its heat to the air that is about to be discharged from the unit The refrigerant liquid then passes through a filter drier and capillary tubing which cause the refrigerant pressure and temperature to drop It next enters the evaporator coil where it abs
3. amp outlet not shown Optional Outlet Collar for ducting outlet only not shown Condensate Pump Kit See page 10 Ductable Inlet Kit see page 12 Silencer Kit See page 13 8 Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC ACCESSORIES LIST o 70 order contact your reseller or call 1 800 533 7533 ITEM PART NO DESCRIPTION 4021468 Pre Filter 2 4021475 MERV 11 Filter 16 x20 x2 3 4022220 Pump Kit 4 4022561 Muffler Kit 5 4021453 Duct Kit includes 8 supply collar 6 4020656 6 Inlet Exhaust Hood T 4020623 8 Supply Collar 8 4020175 Remote Dehumidistat SANTA FE CLASSIC OPTIONAL REMOTE HUMIDITY CONTROL A CAUTION This should only be performed by a qualified electrician 5 Insert a romex connector or conduit connector into the hole in the cabinet that is left after the dehumidistat is removed Pass A 110 120 VAC remote humidity control is available from the the cable to be used to connect to the remote dehumidistat factory This replaces the factory mounted humidity control on through the connector the cabinet of the dehumidifier and allows the unit to accurately 6 Disconnect the dehumidistat leads and reconnect with the new sense the humidity in an area other than the one where the unit is wires located 7 Replace the wiring box and screws Replace the front cover 1 Unplug the unit and screws Tighten any loose screws on the connector 2 Pull th
4. using this installation method or consider the option below 2 1E In A Remote Area Duct Inlet Only When the Santa Fe Classic is located in a room separate from the main area to be dehumidified it may be desirable to dehumidify and or slightly pressurize that room Pressurization assures that open combustion devices do not back draft This can be accomplished by installing a duct from the humid room to the Santa Fe Classic inlet and by allowing the Santa Fe Classic to discharge dehumidified air into the room in which it s located An adequate air flow path must exist between the two rooms for this method to work well An additional humidity control may need to be mounted in the humid area and wired to the Santa Fe Classic to accurately maintain the desired humidity Local electrical codes must be followed when wiring the control 2 2 Electrical Requirements The Santa Fe Classic plugs into a common grounded outlet on a 15 Amp circuit It draws between 6 and 7 Amps under normal Operating conditions 2 3 Condensate Removal Condensate drains by gravity via the clear hose extending from the unit Route hose to a floor drain Use care to keep the hose as flat to the floor as possible Excessive humps or kinks will prevent proper drainage lf the Santa Fe Classic is located too far from a floor drain for the attached hose to reach 1 2 PVC pipe can be used to extend it It is commonly available in 10 lengths from building supply plu
5. 345555455545546454655554 444544544545455465554 LARAROROADADE Res Santa Fe Classic Muffler Kit Installed 12 Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC FILTER INSTALLATION INSTRUCTIONS Instructions To prevent damaging the foam filter place it grid side up on top of the pleated filter and slide them both into the filter slot Foam filter with plastic grid up Pleated filter with air flow arrows pointed down s t LA La w 4 ka K 4 a WVA Foam filter with plastic grid up Pleated filter with air flow arrows pointed down MILLIS IA AA u s POE Lh L Wy 13 Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 X Santa Fe Limited Warranty CLASSIC Limited Warranty Therma Stor LLC Therma Stor warrants as follows i the Santa Fe Classic dehumidifier Product will be free of material defects in workmanship or materials for a period of one 1 year One Year Warranty following the date of initial purchase of such Product by an original customer purchasing from Therma Stor or an authorized reseller Customer and ii the Product s condenser evaporator and compressor will be free of material defects in workmanship or materials for a period of five 5 years following the date of initial purchase of such Product by a Custome
6. CLAIM SHALL UNDER NO CIRCUMSTANCES EXCEED THE PURCHASE PRICE OF THE PRODUCT COMPONENT OR PART UPON WHICH THE CLAIM IS PREMISED Applicable Law and Venue ANY ARBITRATION ENFORCEMENT OF AN ARBITRATION OR LITIGATION RELATED TO THE PRODUCT WILL BE BROUGHT EXCLUSIVELY IN DANE COUNTY WISCONSIN AND CUSTOMER CONSENTS TO THE JURISDICTION OF THE FEDERAL AND STATE COURTS LOCATED THEREIN SUBMITS TO THE JURISDICTION THEREOF AND WAIVES THE RIGHT TO CHANGE VENUE CUSTOMER FURTHER CONSENTS TO THE EXERCISE OF PERSONAL JURISDICTION BY ANY SUCH COURT WITH RESPECT TO ANY SUCH PROCEEDING Miscellaneous If any term or condition of this Limited Warranty is found by a court of competent jurisdiction to be invalid illegal or otherwise unenforceable the same shall not affect the other terms or conditions hereof or thereof or the whole of this Limited Warranty Any delay or failure by Therma Stor to exercise any right or remedy will not constitute a waiver of Therma Stor to thereafter enforce such rights Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 Therma Stor we Information in this document is subject to change without notice No part of 4201 Lien Rd e Madison WI 53704 this document may be reproduced or transmitted in any form or by any means Phone 608 237 8400 Fax 608 222 1447 electronic or mechanical for any purpose without the express written permission Web www thermastor com Email sales t
7. WITCH cc cc cccccccccsesecesseeesesseseseseeeseeseeeeeeseeeeseees 4 4 M intenance cccccsccsccseessesseseesesseeseesessseeeeeeessenseneessenss 4 4 1 Air ee 4 5 SOT VICE ciedecievistsceninsidanasavstecadesdawudersdavsdadebuvadadetsuedasubexnvarsbenacens 4 5 1 WGI ANDY ssccncscresassecensavaravabsntranatettinvebsatvayetaiasaersintvereiavaees 4 5 2 Technical G SCriIPtION cccccscccsssessssseeessseeeeesseeeeeees 4 S3 NPOUDIC SMOOUN Os ioen 4 5 4 Refrigerant Charging i is 5 5 5 Blower REplaCeMentt ccsscessssesessssussssrsusesensusesensnssens 5 5 6 Compressor Capacitor Replacement 5 5 6A Checking Compressor Motor Circuits 0 5 5 6B Replacing A Burned Out Compressor i e 5 5 6C Replacing a Compressor Nonburn Qut 6 5 7 Humidity CONTON c cee cceseceeseeseseeesseeeesseeeeseeeessneeeees 6 5 8 Defrost Thermostat 6 5 9 Condensate PUMP ccccccscccssesssecsssseeeseesesseseseeesees 6 6 Wiring DiAQrain cccccccccsssceecsseescseeesesseesesseeesecsatesessetesens 7 7 Service Parts LiSt cece eecsssesscssseesessseesesseeeeesseeeseseneeeens 8 8 Accessories List cireusresuxtuniaqnerernariniin tinea 9 Optional Remote Humidity Control sassen 9 Condensate Pump Installation Instructions 10 Ductable Inlet Mounting Detail 11 Muffler Kit Instructions i e 12 Filter Installation Instructions ccccsesccsssssessesseseesesseeeees 13 WAITANLY cccccccesececesseeecsseec
8. ations The foregoing limited warranty extends only to a Customer and shall be null and void upon attempted assignment or transfer A defect under the terms of the limited warranty shall not include problems resulting from Customer s or Customer s employees agents invitees or a third party s misuse improper installation improper design of any system in which the Product is included abuse lack of normal care failure to follow written instructions tampering improper repair or freezing corrosion acts of nature or other causes not arising out of defects in Therma Stor s workmanship or material If a Product or Component is replaced while under warranty the applicable limited warranty period shall not be extended beyond the original warranty time period The limited warranty does not cover any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer 14 Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the applicable warranty period Therma Stor shall have no obligation hereunder with respect to any claim received by Therma Stor after the expiration of the applicable warranty period As a further condition to obtaining warranty cov
9. capacitor 6 Unbolt the blower capacitor from the blower motor required for removal clearance 7 Remove the nuts amp bolts holding the blower outlet flange to the cabinet end and remove the blower 8 Reassembling with the new blower is the above procedure reversed 5 6 Compressor Capacitor Replacement This compressor is equipped with a two terminal external overload run capacitor but no start capacitor or relay See Fig 2 A CAUTION ELECTRIC SHOCK HAZARD Electrical power must be present to perform some tests these tests should be performed by a qualified service person 5 6A Checking Compressor Motor Circuits Perform the following tests if the blower runs but the compressor does not with the blower switch OFF and the humidity control ON 1 Unplug the unit remove the cabinet side with two screws in center and the electrical connection cover on the compressor top 2 Plug in the unit and turn the humidity control to ON Check for 110 volts from compressor terminal R to overload terminal 3 using an AC voltmeter If voltage is present go to step 3 If no voltage the high pressure control or relay are open or there is a loose connection in the compressor circuit Test each component for continuity see the appropriate section if a defect is suspected 3 Unplug the unit then disconnect the red and yellow wires from compressor terminals R amp S Using an ohmmeter check continuity between the points listed below
10. ce a warm space s RH to a lower level than that of a cool space For example the Santa Fe Classic may reduce an 80 F space to 30 RH However if the same space is 65 F it may only reduce it to 40 RH It is therefore pointless to set the humidity control to excessively low levels in cool rooms Doing so will result in long periods of ineffective dehumidifier run time Quality humidity meters are available from the factory and are recommended to accurately monitor humidity levels Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC INSTALLER S AND OWNER S MANUAL 3 2 Blower Switch Turning ON the fan switch will cause the unit s internal blower to run continuously whether the unit is dehumidifying or not This function is desirable if the unit is used for air circulation 4 Maintenance 4 1 Air Filter The Santa Fe Classic is equipped with 2 air filters A foam pre filter followed by a standard MERV 11 65 efficient pleated fabric filter These should be checked every six months Operating the unit with dirty filters will reduce dehumidifier capacity and efficiency and may cause the compressor to cycle off and on unnecessarily on the defrost control If dirty the foam pre filter can be vacuumed or carefully hand washed with warm water and mild detergent then rinsed The pleated fabric filter can generally be vacuumed clean several times before needing replacement
11. e black humidity control knob off from the side of the 8 Run the new wire to the location desired to sense relative unit exposing 2 screws Remove the screws humidity Install a 110 120 VAC dehumidistat according to local stags electrical codes 3 Remove the front panel of the dehumidifier by removing 6 Screws 4 Remove the 4 screws securing the wiring box to the inside of the blower end of the dehumidifier and pull the box away from the cabinet to allow access 9 Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC CONDENSATE PUMP INSTALLATION INSTRUCTIONS SANTA FE DEHUMIDIFIER H i PERRA d STEP 1 The condensate pump kit STEP 2 Pre drilled mounting holes are located STEP 3 Secure the condensate pump to the includes drain hose condensate pump two near the bottom and on the same side of the unit with the two provided screws mounting screws and instructions unit as the drain hose p pas STEP 4 Cut the condensate drain hose at a 45 STEP 5 Example of hose cut at a 45 angle angle approximately 10 inches from the unit The angle prevents the hose from sealing tight against the bottom of the pump reservoir STEP 7 Insert the drain hose into the STEP 8 Install the provided drain hose over STEP 9 Route the condensate pump drain hose condensate pump reservoir as shown the condensate pump nipple to an appropriate drain and plug the conden
12. eesseeeeesseeeeecseeesecsueeesssueeessseteeenees 14 Read the installation operation and maintenance instructions carefully before installing and using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Santa Fe Classic dehumidifier k _ When unpacking make sure to remove corrugated shipping cardboard from top of unit Specifications Part Number 4029700 Blower 275 CFM 0 0 WG Power 720 watts 80 F and 60 RH Supply Voltage 115 volt 1 phase 60 Hz Current Draw 6 4 Amps Energy Factor 3 0 L kWh Operating Temp 45 F Min 95 F Max Sized for 2500 Sq Ft Typical Minimum Performance at 80 F and 60 RH Water Removal 110 Pints Day Efficiency 6 4 Pints kKWh Air Filter MERV 11 Efficiency Standard 65 Efficient ASHRAE Dust Spot Test Size 16 x 20 x 2 10 110 120 VAC Ground 9 16 ID x 8 Direct Gravity Drain Hose Santa Fe Dimensions Power Cord Drain Hose Unit With Duct Kit Shipping Width 20 23 20 Height 30 42 1 2 43 Depth 17 17 24 Weight 110 Ibs 117 Ibs A CAUTION This symbol means important instructions Failure to heed them can result in injury or material property damage 2 Installation 2 1 Location The Santa Fe Classic is designed to be installed indoors and is ideal for unfinished and finished basements The Santa Fe Classic is designed to operate in temperatures between 45 and 95 F Temperatu
13. erage hereunder the Customer must present forms of invoices evidencing proof of purchase of a Product If such invoices do not clearly indicate the date of initial purchase by a Customer the applicable Product s date of manufacture will be used instead of the date of initial purchase for the purpose of calculating the commencement of the applicable warranty period Warranty service must be performed by Therma Stor or a servicer authorized by Therma Stor In order to obtain warranty service the Customer should call Therma Stor at 1 800 533 7533 and ask for the Therma Stor Products Service Department which will then arrange for applicable warranty service Warranty service will be performed during customary daytime working hours If the Product must be shipped for service Customer shall be solely responsible for properly packaging the Product for all freight charges and for all risk of loss associated with shipment Limitation of Liability IN NO EVENT SHALL THERMA STOR IN CONNECTION WITH THE DESIGN SALE INSTALLATION USE REPAIR REPLACEMENT OR PERFORMANCE OF ANY PRODUCT COMPONENT PART THEREOF OR WRITTEN MATERIAL PROVIDED THEREWITH BE LIABLE TO THE EXTENT ALLOWED UNDER APPLICABLE LAW UNDER ANY LEGAL THEORY FOR ANY SPECIAL DIRECT INDIRECT COLLATERAL OR CONSEQUENTIAL DAMAGES OF ANY KIND NOTWITHSTANDING THE ABOVE LIMITATIONS AND WARRANTIES THE SOLE AND EXCLUSIVE LIABILITY OF THERMA STOR REGARDLESS OF THE NATURE OR THEORY OF THE
14. g Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line filter driers will probably clean up the system If sludge is evident in the discharge line it will likely be found in the suction line This indicates the compressor burned out while running Sludge and acid has been pumped throughout the system Several changes of the liquid and suction filter driers will probably be necessary to cleanse the system 5 Correct the system fault that caused the burn out Consult the factory for advice 6 Install the replacement compressor with a new capacitor and an oversized liquid line filter In a running burn out install an oversized suction line filter drier between the accumulator and compressor Thoroughly flush the accumulator with refrigerant to remove all trapped sludge and to prevent the oil hole from becoming plugged A standing burn out does not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accurate vacuum gauge Leave the pump on the system for at least an hour An alternate method of removing moisture and non condensibles from the system requires evacuation to 29 Hg vacuum Then break the vacuum with 35 to 50 PSIG refrigerant vapor charge Leave the vapor charge in the system from at least 5 minutes before removing it Repeat the vapor charge wait remove sequence twice more and then charge the system with the quantity and
15. hermastor com of Therma Stor LLC 2008 Therma Stor LLC All rights reserved
16. mbing and hardware stores It will slide tightly inside the end of the drain hose lf more than one length of pipe is required they can be joined with a short piece cut from the end of the drain hose 2 4 Ducting 2 4A Optional Ducting An inlet shroud with an 8 round collar and an 8 round exhaust collar are available from the factory that will allow round ducting to be attached to the inlet and or outlet of the santa Fe Classic 2 4B Ducting for Dehumidification Ducting the Santa Fe Classic as mentioned in sections 2 1B 2 1E requires consideration of the following points Duct Sizing For total duct lengths up to 25 feet use a minimum 8 diameter round or equivalent rectangular For longer lengths use a minimum 10 diameter or equivalent Grills or diffusers on the duct ends must not excessively restrict air flow Isolated Areas Effective dehumidification may require that ducting be branched to isolated stagnant areas Use 6 diameter branch ducting to each of two or three areas use 4 to each of four or more areas 3 Operation 3 1 Humidity Control Adjustment The dehumidifier will run continuously until relative humidity RH is reduced to the humidity control dial setting Setting the humidity control to lower RH levels will NOT increase the unit s dehumidification rate it will simply run longer to reduce the area s RH to the setting The Santa Fe Classic unit and refrigerant based dehumidifiers in general will redu
17. ms and finished areas to install the Santa Fe Classic in an adjacent equipment room or unfinished area Air is transferred between the humid room and the unit via ducting The factory mounted humidity control on the Santa Fe Classic cabinet may not sense the humidity in the humid room accurately enough with this installation method If so an additional humidity control can be mounted in the humid room and wired to the Santa Fe Classic Local electrical codes must be followed when wiring the control 2 1D In A Remote Area Duct Outlet Only A simpler remote installation method than above uses ducting between the Santa Fe Classic discharge and the humid room the Santa Fe Classic inlet draws air from the room in which it s located This works well if there is an adequate air flow path between the two rooms e g high door undercut louvered door or wall grill This eliminates the need to remote mount the humidity control There are several potential disadvantages to using this method First humid air is drawn into the room where the Santa Fe Classic is located Second to accurately sense humidity the blower in the Santa Fe Classic may need to run continuously to draw air from the humid room into the Santa Fe Classic room Third a slight negative pressure is created in the room with the Santa Fe Classic which could back draft open combustion devices located there If such devices are present call the factory for specific instructions before
18. n a compressor is chemically very stable under normal operating conditions However when an electrical short occurs in the compressor motor the resulting high temperature arc causes a portion of the refrigerant oil mixture to break down into carbonaceous sludge a very corrosive acid and water These contaminants must be carefully removed otherwise even small residues will attack replacement compressor motors and cause failures The following procedure is effective only if the system is monitored after replacing the compressor to insure that the clean up was complete 1 This procedure assumes that the previously listed compressor motor circuit tests revealed a shorted or open winding If so cautiously smell there frigerant from the compressor service port for the acid odor of a burn out Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC INSTALLER S AND OWNER S MANUAL 2 Remove and properly dispose of the system charge DO NOT vent the refrigerant indoors or allow it to contact your eyes or skin 3 Remove the burned out compressor Use rubber gloves if there is any possibility of contacting the oil or sludge 4 To facilitate subsequent steps determine the type of burn out that occurred If the discharge line shows no evidence of sludge and the suction line is also clean or perhaps has some light carbon deposits the burn out occurred while the compressor was not rotatin
19. orbs heat from the incoming air and evaporates The evaporator operates in a flooded condition which means that all the evaporator tubes contain liquid refrigerant during normal operation A flooded evaporator should maintain constant pressure and temperature across the entire coil from inlet to outlet The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil The accumulator prevents any liquid refrigerant from reaching the compressor The compressor evacuates the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature gas to repeat the process 5 3 Troubleshooting No dehumidification Neither blower nor compressor run with fan switch FAN AUTO 1 Unit unplugged or no power to outlet 2 Humidity control set too high or defective Sec 3 1 amp 5 7 3 Loose connection in internal wiring No dehumidification Compressor does not run but blower runs with fan switch FAN AUTO and humidity control turned to ON all the way clockwise 1 Defective compressor or compressor run capacitor Sec 5 6 2 Loose connection in compressor circuit See Fig 2 3 Defective compressor overload Sec 5 6A 4 Defective compressor Sec 5 6 5 Defrost thermostat open Sec 5 8 Blower runs with fan switch FAN AUTO but compressor cycles ON amp OFF 1 Low ambient temperature and or humidity causing unit to cycle through defrost mode 2 Defecti
20. pressor 5 9 Condensate Pump Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the float switch Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC WIRING DIAGRAM 6 Wiring Diagram 115 Vac 60 Hz 1Ph FAN SWITCH RUN POAN KP HUMIDITY DEFROST Bi find RED CONTROL THERMOSTAT COMPRESSOR Figure 2 Electrical Schematic of the Santa Fe Classic Dehumidifier 7 Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC SERVICE PARTS LIST o 7o order contact your reseller or call 1 800 533 7533 ITEM CO CO N amp o1 P 10 PART NO 4022254 4021475 4021468 4026930 4028233 4029168 4029169 4029845 4028226 4021409 4029815 4028225 4029510 4021626 4021469 4021495 4025560 4021471 4021507 4021453 4020623 4022220 4021586 4022561 QTY DESCRIPTION Accumulator Air Filter Pleated 2 x 16 x 20 Air Filter Foam Element Blower w Capacitor Capillary Tubes Compressor Compressor Overload Compressor Run Capacitor 45 MFD Condenser Coil Cord amp Wire Harness Defrost Thermostat Evaporator Coil Filter Drier Hose Drain 56 ID x 8 Humidity Controller Knob Humidity Controller Switch SPDT for Fan Wheel 2 Plastic Wiring Diagram on cover not shown Optional Ducting Kit for inlet
21. r Limitation of Remedies CUSTOMER S SOLE AND EXCLUSIVE REMEDY UNDER THE ABOVE LIMITED WARRANTY AND THERMA STOR S ENTIRE LIABILITY THEREUNDER SHALL BE AT THE SOLE OPTION OF THERMA STOR REPLACEMENT OR REPAIR OF SUCH PRODUCT OR ITS COMPONENTS COMPONENTS BY THERMA STOR OR THERMA STOR S AGENTS ONLY REFRIGERANT PIPING SUPPLIES TRANSPORTATION COSTS LABOR COSTS INCURRED IN REPAIR OR REPLACEMENT OF SUCH COMPONENTS ARE NOT INCLUDED THIS DISCLAIMER AND EXCLUSION SHALL APPLY EVEN IF THE EXPRESS WARRANTY AND LIMITED REMEDY SET FORTH HEREIN FAILS OF ITS ESSENTIAL PURPOSE CUSTOMER ACKNOWLEDGES THAT NO REPRESENTATIVE OF THERMA STOR OR OF ITS AFFILIATES OR RESELLERS IS AUTHORIZED TO MAKE ANY REPRESENTATION OR WARRANTY ON BEHALF OF THERMA STOR OR ANY OF ITS AFFILIATES OR RESELLERS THAT IS NOT IN THIS AGREEMENT Notwithstanding the above during the term of the One Year Warranty only Therma Stor will provide free of charge to Customer all Components and labor except costs related to removal and installation of Product required to fulfill its obligations under such One Year Warranty Disclaimer of Warranties EXCEPT FOR ABOVE LIMITED WARRANTY WHICH IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED WITH RESPECT TO THE PRODUCT AND ITS COMPONENTS THERMA STOR HEREBY DISCLAIMS ALL EXPRESS AND IMPLIED WARRANTIES INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE Warranty Limit
22. refrigerant listed on the nameplate 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plugged Replace the suction filter drier if pressure drop occurs If a severe running burn out has occurred several filters driers may have to be replaced to remove all of the acid and moisture NOTE NEVER use the compressor to evacuate the system or any part of it 5 6C Replacing a Compressor Nonburn Out Remove the refrigerant from the system Replace the compressor and liquid line filter drier Charge the system to 50 PSIG and check for leaks Remove the charge and weigh in the refrigerant quantity listed on the nameplate Operate they system to verify performance 5 7 Humidity Control The humidity control is an adjustable switch that closes when the relative humidity of the air in which it is located rises to the dial set point It opens when the RH drops 4 to 6 below the set point 5 8 Defrost Thermostat The defrost thermostat is attached to the refrigerant suction tube between the accumulator and compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil The blower will continue to run causing air to flow through the evaporator coil and melt the ice When the ice has melted the evaporator temperature will rise and the thermostat will restart the com
23. res outside of these ranges will affect dehumidifier performance In order to efficiently control the humidity levels the area in which the dehumidifier is to be placed must be free of water intrusion or excessive fresh outside air infiltration Before installing the Santa Fe Classic water intrusion and air infiltration problems should be addressed A CAUTION e Installation outdoors or near a pool or spa will void factory warranty o Do not use the dehumidifier as a bench or table Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC INSTALLER S AND OWNER S MANUAL 2 1A In humid area no ducting The simplest installation is to place the Santa Fe Classic in the humid area with no ducting The air inlet on top and outlet on the side must be at least 1 from walls and other obstructions to air flow 2 1B In humid area duct inlet and or outlet lf the humid are is very large or has high ceilings dehumidification can be improved by adding an inlet and or outlet duct to circulate and destratify stagnant areas For a large are add inlet or outlet ducting to create flow across the area s greatest length For areas with ceilings higher than 12 use an inlet duct to draw warm moist air from near the ceiling See section 2 4 for attaching duct collars amp ducting 2 1C In A Remote Area Duct Inlet amp Outlet It is often desirable especially in billiard roo
24. sate pump into a standard 115VAC outlet 10 Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC DUCTABLE INLET MOUNTING Ductable Inlet Instructions Exhaust Collar Mounting Instructions 1 Remove the Filters from the unit 5 The six inch opening may be used as a fresh air inlet from 2 Remove the ductable inlet from the box and remove the outside release paper from the tape on the inlet flanges 6 Remove the exhaust collar from the box and bend the tabs in 3 Center the inlet above the filter guides and attach the inlet to 7 Place the collar over the blower outlet and line up the tabs the guides with the holes in the cabinet 4 Replace the filters in the unit 8 Using 4 screws from the kit attach the collar to the unit Ductable Inlet Exhaust Collar 11 Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC MUFFLER KIT INSTRUCTIONS Component List 1 Silencer 1 8 18 Screw 1 Instructions On the Santa Fe Classic the muffler kit and condensate pump kit may be used together but the pump will not be able to be mounted to the unit Note Washer and 2 screws are not used on the Santa Fe Classic Loosen these 2 screws enough to slide the silencer under the screw heads Insert 1 screw from the enclosed parts and tighten Y 443454545454646466545554 42654 644455 566656546654
25. ve compressor overload Sec 5 6A 3 Defective compressor Sec 5 6 4 Defrost thermostat defective Sec 5 8 Blower does not run with fan switch in either position Compressor runs briefly but cycles ON amp OFF 1 Loose connection in blower circuit see Fig 2 2 Obstruction prevents impeller rotation 3 Defective blower 4 Blower switch defective Santa Fe Classic Installer s amp Owner s Manual www sylvane com 1 800 934 9194 SANTA FE CLASSIC INSTALLER S AND OWNER S MANUAL Evaporator coil frosted continuously low dehumidifying capacity 1 Defrost thermostat loose or defective Sec 5 8 2 Low refrigerant charge 3 Dirty air filter or air flow restricted 5 4 Refrigerant Charging lf the refrigerant charge is lost due to service or a leak a new charge must be accurately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type 5 5 Blower Replacement The centrifugal blower has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1 Unplug the power cord 2 lf an outlet duct is connected to the unit remove it 3 Remove the cabinet side 4 Remove the 4 screws holding the electrical box located next to the blower 5 Disconnect the blower leads Black from the blower switch and white from the run
26. www sylvane com 1 800 934 9194 INSTALLER S amp OWNER S MANUAL HVAC INSTALLER PLEASE LEAVE MANUAL FOR HOMEOWNER SantaFe CLASSIC a m Free standing dehumidification for your home m Includes installation operating Pee and safety instructions warranty information and all ancillary products Read and save these instructions ENERGY STAR A WARNING P N 4029700 Serial No Install Date Sold by A Therma Stor uc 420l Lien Rd Madison WI 53704 e TOLL FREE 1 800 533 7533 e www thermastor com e sales thermastor com 2009 Therma Stor LLC e Manual P N TS 601 10 09 www sylvane com 1 800 934 9194 TABLE OF CONTENTS Table of Contents le CCI GAWOMNS serisinin anini anaE RAAE EAAS 2 e aO a a S AN 2 PEE ELIE EAE A A E 2 2 1A In Humid Area No Ducting 3 2 1B In Humid Area Duct Inlet and or Outlet 00 c 3 2 1C In Remote Area Duct Inlet amp Outlet ee 3 2 1D In Remote Area Duct Outlet Only 3 2 1E In Remote Area Duct Inlet Only ee 3 2 2 Electrical REQUIFEMENTS c cccccesecsessseessseeeessseeeeesees 3 2 3 Condensate Removal 3 24 DUCUNO srectctstcectescscachanchetanzactatsonatateenctateen nc trecenaeeternucers 3 2 4A Optional Ducting scvecssccavontsaxaricuvareredoreierwantnacemaaverees 3 2 4B Ducting for DehUMIIFICATION cceeeeeeeseeeeereees 3 OPEO eecseceacecetacaceusceavacuiese a E 3 3 1 Humidity Control Adjustment n 3 3 2 Blower S