Home
        Before installation
         Contents
1.    Is it possible to achieve a sufficiently high room temperature through thick   solid wooden planks     Answer  A room temperature of approximately 20   C is easily achievable   Of course  this requires that the building is correctly insulated  and that you  follow the advice and recommendations in Dinesen s instructions  In older  buildings with inadequate insulation  it will often be necessary to have a  supplementary heat source     10     11     12     22    Is the energy consumption higher with solid floors than with 15 mm engineered  wood flooring     Answer  As wood has insulating properties  a certain heat loss should be  expected through the construction  Therefore  when the heat has to pass  through a thicker layer  there will be a higher heat loss  A thick floor therefore  requires a higher flow temperature to achieve the same surface temperature  as a thin engineered wood floor  However  this does not lead to a significantly  higher energy consumption     Does the energy consumption go up when the flow temperature is raised   Answer  The first time the water is heated to 45   C instead of 35   C  it uses  slightly more energy  but in subsequent use  it makes no difference  This is  because the energy consumption depends exclusively on the difference between  the flow and return temperature    Why is it important to start the underfloor heating up gradually    Answer  The wood needs to adapt to the temperature changes gradually  If the  change is too rapid the wo
2.  22  35 mm Douglas 0 035   0 13   0 27  22 mm Oak 0 022   0 17   0 13  30 mm Oak 0 030   0 17   0 18       As shown in the examples above  the thickness of the floor affects its insulation  ability  The thicker the floor  the better the insulation  Therefore you may have to set  a higher flow temperature to achieve a suitable surface temperature  The impact on  energy consumption is minimal  The difference in energy consumption between a  tile floor and a solid floor with 28 mm thick planks is max  5 10   And the difference  in energy consumption between floors with 28 versus 35 mm Douglas planks is at  most a few percent  See also section 4 1 3     4 1 3 Heating requirement    When designing private homes  the goal is typically to ensure a room temperature   of 20 21   C in the winter  Over the years  insulation requirements have gone up  considerably  and this is reflected in the energy consumption of private homes  The  energy consumption for heating in modern buildings will be 35 45 W m   compared to  45 75 W m  in older buildings  Therefore  you should carry out a formal assessment of  the actual heating requirement of the building     The surface temperature of a plank floor must never exceed 27   C  and the surface  can therefore not emit more than 75 W m   The surface temperature in a well   insulated house will typically need to be 2   C above the desired room temperature   The less effective the insulation  the higher the surface temperature will need to be     4 1 
3.  In the winter months  the  electrical underfloor heating must be switched on all the time to provide basic  heating for the house  It may be an advantage to combine electrical underfloor  heating with radiators  Electrical underfloor heating is installed by a carpenter and  an electrician     Constructions    4 31 Underfloor heating in concrete    The heating coils are tied onto a mesh and embedded in a 10 cm thick layer of concrete  on top of the insulation  The construction is simple and only requires that the heating  coils are closely attached to the mesh  The surface of the concrete floor must be   level with a maximum deviation of 2 mm  measured across a 2 metre straightedge   The concrete moisture must not exceed 85  RH  and a vapour barrier must be used   Insulation must conform to the building code     4 3 1 1 Directly on concrete with heating coils    Place a sound absorbing vapour barrier on top of the concrete  Dinesen  recommends Platon Stop  Make sure that the vapour barrier is impenetrable to  irregularities in the concrete  Fasten the floor planks directly to the concrete with  a Dinesen screw and Dinesen rawlplug as described in Dinesen s    Installation     instructions  Make sure to push the planks firmly into the substructure    You should be aware that this type of floor is relatively hard to walk on and is  therefore generally less comfortable than other installation types  Installing the  floor directly on the concrete layer requires knowing exactly wh
4.  from Dinesen provides a firm foundation  To ensure the high level  of quality and careful processing  every plank passes through 10 pairs of hands on its  way through the production process  Generally  we always recommend the thicker  planks  They are more stable  have a deeper sound and last a generation or two longer     Dinesen planks are always delivered unfinished  and after installation  the floor must  be sanded and finished  This gives you the opportunity to choose the finish that  matches your expectations of the floor  It is important to consider the advantages  and disadvantages of the various finishes carefully  You can read more about this in    Dinesen s    After installation    instructions     The properties of wood    Wood is a hygroscopic material  which absorbs and emits moisture from the  surrounding materials  Wood will always adapt to an equilibrium level of humidity  in relation to the temperature and the relative humidity of the air  When delivered   Dinesen planks are dried to a moisture content of 8 10   This corresponds to a  relative air humidity  RH  of 40 50   If the air humidity decreases  the wood will  emit moisture and shrink in width  which results in contraction gaps  Contraction  gaps will always appear in winter  and at this stage  the floor has its most beautiful  appearance  Generally  however  the goal should be to prevent the air humidity from  dropping below 35  RH     Below is an overview of the reaction of the floor planks to vary
5.  of humidity in relation to the temperature and the relative humidity of the   air  When delivered  Dinesen planks are dried to a moisture content of 8 10   This  corresponds to a relative air humidity  RH  of 40 50   If the air humidity decreases   the wood will emit moisture and shrink in width  which results in contraction gaps   The higher the surface temperature  the lower the air humidity just above the floor   and the more the wood will contract  Contraction gaps will always appear in winter   and at this stage  the floor has its most beautiful appearance  Generally  however  the  goal should be to prevent the air humidity from dropping below 35  RH  cf  Table 1     The capacity of a material to conduct heat is called its thermal conductivity    w m  k      For plank floors  the thermal conductivity depends on the density of the wood  kg m     Therefore  Oak has a slightly better thermal conductivity than Douglas     12    The thermal conductivity is used to calculate the thermal resistance     Guideline values for thermal resistance             Wood type Thermal resistance  Oak 0 17  Douglas 0 13       Thermal resistance is calculated based on the thickness of a material divided by its  thermal conductivity  Thus  thermal resistance reflects the insulation ability and is  normally labelled R     thickness       thermal conductivity    Thermal resistance  calculation examples                   Thickness and variant Formula and result  R   28 mm Douglas 0 028   0 13   0
6.  the conductivity  of heat     RSS 7775 yyvywyyyw  yw     dv   vV _   TT_ Floor plank         Cardboard      E EAS RE    Vapour barrier    oe ee O mee    4 3 2 Underfloor heating with heat emission plates    Underfloor heating with heat emission plates provides a very responsive underfloor  heating construction and a pleasant floor to walk on  All in all  it is a very comfortable  solution     16    4 3 2 1 Heat emission plates on laths on top of joists    The floor planks are laid in the same direction as the joists  We recommend  installing the planks lengthwise in the building  With this solution you therefore  need to install the joists lengthwise  so that the laths can be laid across the joists   Install the joists at approximately 60 cm intervals with insulation in between    On top of the joists  install a layer of planed 21 x 100 28 x 120 mm laths at  approximately 30 mm intervals to make room for the grooves in the heat  emission plates  Next  install the heat emission plates  fastening them with    nails on one side  After installing the heating coils  lay out grey flooring  cardboard  400 g m    and fasten the floor planks to the laths with screws   Pay attention to the placement of the coils        Floor plank    aa OO DS   TT Flooring cardboard          Heat emission plate  Lath   Heating coil   Joist   Vapour barrier  Concrete       Figure 3  Cross section  heat emission plats on laths on top of joists    4 3 2 2 Heat emission plates on laths between joists    T
7.  time  and sanding and re finishing the floor may be  sufficient     Measuring residual humidity    When installing a Dinesen floor make sure that the residual humidity in the concrete  does not exceed 85  RH  It is difficult to carry out an accurate measurement of  concrete moisture  and surface hygrometers are not nearly accurate enough  You  need to measure the moisture content in the middle of the concrete layer  This may  be done by placing a sensor in a hole drilled into the concrete  After some time  the  sensor achieves moisture equilibrium with the concrete  and the relative humidity  can be determined  A more accurate measuring is to carve a piece of concrete out  of the middle of the concrete layer and carry out a humidity test in a laboratory  The  finding of this test is documented in a humidity report  which can serve as part of  the contractor s quality assurance process  A humidity measurement is a very cost   efficient insurance that may save the contractor and the client substantial costs     10    3 8    3 9    Liability and warranty    The responsibility for drying the concrete is often in a grey zone  which means that  no one feels ultimately responsible  Client and contractor need to agree who is  responsible and agree not to install the floor before Dinesen s requirements are met   Expansions  warping and other deformation of the floor planks due to high levels of  humidity are not covered by Dinesen s warranty     Change of delivery time    Be realisti
8. 4 Heat loss    If the building has insufficient insulation  there may be days when underfloor heating  alone cannot provide the desired room temperature  There is a considerable heat loss  through floors  walls  ceilings and windows  The building code contains requirements  to insulation effectiveness   the so called U value   which buildings must conform to     13    4 2    The U value for a ground floor with underfloor heating must not exceed 0 10  That  typically requires insulation with at least 300 mm polystyrene  The U value for heat  loss through the foundations with underfloor heating must not exceed 0 12  Heat  loss through the foundation has a considerable impact on heat energy consumption   You also need to consider thermal bridges and leaks  The building code also states  U values for external walls  ceilings  windows  outer doors etc     Heat loss through windows  regardless of the type of glazing  far exceeds heat loss  through walls  and the size of the glazed area will therefore have a major impact on  the total heat loss  Note that the placement of windows in relation to the points of  the compass  open areas or the sea may cause above average heat loss  just as cold  downdraughts from windows can be substantial  This should be countered with  convectors along windows that go all the way to the floor  The convectors can also  be used to draw heat into the room quickly  Convector grids can be made in the  same wood as the floor to achieve a beautiful architect
9. Instructions    Before installation    Hp    TT i    Um da    KUH    DID y    ep PU    W    V DDD DP 4  y RIE    YA  OH    Fi  0101  van     Ih y    ji  un    HN pt A  NM i  area    Y i   gt     UA     ma w N  M    y  Y  M M 0 I         TI Ny plug HN   I  Vy Ue   lf a    N   COZZA  oi   IG Dinesen      N       April 2014    A Dinesen floor is a unique piece of nature  It is a living material which must be  treated with care  Our instructions explain in detail how you get the best result so  the floor can last for centuries     If you need any additional advice about Dinesen floors  you are very welcome to  contact us     To order and purchase products in the maintenance series  please go to  webshop dinesen com    Contents    1    1 1    2 1    3 1   3 2  3 3  3 4  3 5  3 6  3 7  3 8  3 9    41   4 2  4 3  4 4    5 1    74  7 2    A solid plank floor    The properties of wood    How to succeed    General requirements for humidity and climate    Humidity    Humidity and plank floors  Air humidity   Construction humidity  Drying of concrete   Humidity in the substructure  Damage   Measuring residual humidity  Liability and warranty  Change of delivery time    Underfloor heating under Dinesen floors  Conditions   Types of underfloor heating  Constructions   Test  start up and use    Pitfalls    Dinesen recommends    FAQ    General guidance    Dinesen instructions  Literature    12  12  14  15  19  20    20    21    23    23  23    11    A solid plank floor    A solid plank floor
10. adapt to 6   which means that it contracts   The underfloor heating does not in itself lead to larger contraction gaps  The  higher the surface temperature  the larger the contraction gaps  You should  expect the planks to contract by an average of approximately 1  in width    cf  Table 1     Does underfloor heating cause more warping     Answer  With seasonal variations  floor planks will warp slightly  That is the  nature of wood  it occurs regardless of underfloor heating and is of no concern   Significant warping only occurs if there are problems with humidity levels in the  building  or if the construction humidity has not been fully eliminated before the  floor planks were installed     Does underfloor heating make the wood creak     Answer  If you follow Dinesen s recommendations for temperature and air  humidity  underfloor heating will not make the floors creaky  Creaking often  occurs because the joists are too wet  the joists are placed too far apart or  the blocking up of the joists is not good enough  However  large variations in  temperature or air humidity can temporarily cause individual planks to creak  slightly     Why must the surface temperature not exceed 27   C     Answer  A temperature above 27   C will not be pleasant  If the temperature  exceeds 27   C  the air humidity can drop below 30  RH  which depletes the  wood and may cause cracks and scratches  If the building is properly insulated   a surface temperature above 27   C will never be necessary  
11. and  fasten floor planks to the chipboard with screws  Pay attention to the  placement of the coils     con Floor plank    Flooring cardboard   Heat emission plate   Heating coil   Underfloor heating chipboard  Vapour barrier   Concrete          Figure 7  Longitudinal section  underfloor heating chipboard on concrete    18    4 3 3 Underfloor heating plates    Underfloor heating plates are used in an underfloor heating system where  polystyrene will establish an insulating layer directly on the levelled sand layer    For example  lay out a layer of polystyrene that is 250 mm thick  On top of this  lay  out a vapour barrier and a layer of 50 x 50 mm joists at 60 cm intervals  In between  the joists  lay a 25 mm layer of polystyrene and  on top of that  25 mm underfloor  heating plates  tracked polystyrene plates with aluminium heat emission plates with  room for heating coils   After installing the heating coils  lay out grey flooring  cardboard  400 g m    and fasten the floor planks to the joists with screws     ZE ZA ZE       T F oor plank  u u IA       4 4    Flooring cardboard   Joist   Underfloor heating plate  Heating coil   Polystyrene plate  Vapour barrier  Polystyrene plate    EH     Levelled sand    Test  start up and use       Start up the underfloor heating slowly and gradually     It is important that the plumber pressure tests the system to make sure there are   no leaks  that the coils match the room specifications  and that the thermostats   are working  The u
12. because a large volume of concrete has to be heated before  the heat reaches the plank floor  Heavy underfloor heating therefore makes it harder  to control the room temperature than light underfloor heating  The benefit of heavy  underfloor heating is that the construction of the floor is simple  and that the heating  system can be used to dry out the concrete floor  Heavy underfloor heating is  installed by a mason and a plumber     4 2 2 Light underfloor heating    Light underfloor heating is based on heat emission plates in aluminium  where the  heating coils are placed in curved grooves  The heat emission plates are placed just  underneath the plank floor  and because aluminium is a good thermal conductor  the  heat is quickly distributed throughout the floor surface  Aluminium responds quickly  to changes in the demand for heating  so the room temperature will feel more stable  than with heavy underfloor heating  The construction is slightly more complicated  but provides a more pleasant floor to walk on  as the substructure is usually a joist  construction  Light underfloor heating is installed by a carpenter and a plumber     4 2 3 Electrical underfloor heating    Electrical underfloor heating is typically constructed with heat cables distributed  in a joist construction  As with the other types of underfloor heating  the surface  temperature must not exceed 27   C  The cost of electricity should be included in  considerations to install electrical underfloor heating 
13. c in your assessment of the drying time for the concrete  At Dinesen  we  will remind you of the importance of concrete moisture  and we will only reluctantly  deliver the planks before the building is dry  Instead  we offer to postpone production  and delivery  and normally  we also have the storage capacity to store the planks  until the conditions are right     11    41    Underfloor heating under Dinesen floors    Dinesen recommends installing underfloor heating under Dinesen floors as a  comfortable and durable solution  About 80  of our projects are established  with underfloor heating  Dinesen has years of experience with underfloor heating  under solid floors  and it is an unproblematic solution  provided you adhere to the  conditions described below     In principle   water based  underfloor heating is simply a plastic coil that is  embedded in the floor construction  Sending hot water through the coil heats up  the construction and thus the room  Depending on the building s insulation  it may  be necessary to use supplementary heat sources in the form of radiators  a heat  recovery system or a wood burning stove     If the underfloor heating is to be the only heat source  the total heat loss from the  room must be less than the heat emitted by the floor surface  That requires a formal  energy or heat loss assessment  especially in older buildings or in connection with  renovation projects  Even if the building lives up to the insulation requirements   in the buildin
14. e requirements in this instruction manual  and verifying this is your  responsibility  If any of the conditions are not met  this must be rectified before  the planks are installed     Dinesen recommends    20    Light underfloor heating with heat emission plates provides the shortest  response time and the easiest temperature control     Make sure the building conforms to the U value requirements in the current  building code at any given time     Install convectors in front of windows that go all the way to the floor     Always start up the underfloor heating system slowly and gradually     FAQ    21    Will underfloor heating result in more cracks and similar damages     Answer  If the air humidity is kept between 30 and 60  RH  underfloor heating  will not result in cracks etc  If the surface temperature of the floor exceeds 27   C   it will bring the air humidity under 30   which may deplete the wood and cause  cracks  Low air humidity and inadequate care and maintenance can cause  minor cracks     Does underfloor heating mean larger contraction gaps     Answer  Wood will always strive for an equilibrium moisture level in relation  to the air in the environment  Dinesen floors have been dried to 8 10   and  regardless of underfloor heating  they will contract in the winter  when the air  humidity is low  With an interior air humidity between 40 and 45  RH  the  wood will adapt to a moisture content of 8  wood humidity  If the air humidity  drops to 30  RH  the wood will 
15. ere the heating  coils are placed to avoid drilling or screwing into them     15    Sinking screws into concrete is more time consuming than other types   of installation  An alternative option is to use full surface gluing to install  the planks on the concrete  cf  Dinesen s    Installation    instructions and the  supplementary    Full surface gluing    instructions     PRESSE LL LL LLL AZ Floor plank         A  es  ge 3 pe ne a e e     Mero barrier  o KJE ee  oe  KR   Concrete    Heating coil        o  e   e   o e    4 3 1 2 Plywood chipboard on concrete with heating coils    On concrete floors  always use a vapour barrier of at least 0 20 mm PE foil  with 20 cm taped overlay  Let the vapour barrier continue up the wall and cut  it off behind the skirting board  Make sure that the vapour barrier is  impenetrable to irregularities in the concrete  Lay out grey flooring cardboard   400 g m   on at least 22 mm plywood or chipboard  The planks are installed  with hidden screws or screwed from above as described in Dinesen s     Installation    instructions  The advantage of this type of installation is that it  is relatively simple  In addition  the solution ensures an effective separation  between the concrete and the wood construction  Due to the thickness of the  planks  the flow temperature needs to be slightly higher  but as mentioned  above  this only has a marginal impact on the heat energy consumption  as  long as there are no cavities or irregularities that may block
16. g code   for example in a new building   the conditions listed below  should still be considered in the decision making process     Conditions    4 1 1 Humidity and underfloor heating    Regardless of whether the floor has underfloor heating  concrete moisture will always  be very harmful for a plank floor  It is very important to ensure that the humidity  content of the concrete does not exceed 85  RH  If heating coils have been  embedded in the concrete  the underfloor heating should be switched on after 30 days  when the concrete has hardened  Even in the warmest summer and with high outdoor  temperatures  the underfloor heating should be switched on at an acceptable  temperature for at least 1 month before the floor is installed  and you must always  check the concrete moisture before installing the floor  Dinesen recommends a  destructive measurement of concrete moisture  An indicative surface measurement    for example a GANN measurement   is not accurate enough  If the underfloor heating  is not switched on  the residual humidity will not leave the concrete until after the floor  is installed  and the heat is switched on  that may cause severe damage to the floor    A vapour barrier should always be installed on top of the dry concrete floor     4 1 2 The properties of the floor with underfloor heating    As mentioned before  wood is a hygroscopic material  which absorbs and emits  moisture from the surrounding materials  Wood will always adapt to an equilibrium  level
17. he floor planks are laid across the joists  This construction can be used on a tier  of beams or a new tier of joists with a cc distance of 60 cm  Place insulation in  between the joists  Install at least 45 x 45 mm planed battens fillets at 60 cm  intervals between the joists  Recess them  so the top of the laths is level with  the top of the joists  Lay out a layer of planed 21 28 x 120 95 mm laths at  approximately 30 50 mm intervals to make room for the grooves of the heat  emission plates  Install the heat emission plates  and fasten them with a nail  on one side  After installing the heating coils  lay out grey flooring cardboard   400 g m    and fasten the floor planks to the joists  Pay attention to the  placement of the coils     Floor plank  Flooring cardboard  Heat emission plate  Lath   Heating coil  Batten fillet   Joist   Insulation   Vapour barrier  Concrete       Figure 4  Longitudinal section  heat emission plates on laths between joists    4 3 2 3 Self supporting heat emission plates on joists    Install the joists with a cc distance of 60 cm with insulation in between  Install  the self supporting heat emission plates directly on the joists  nailed onto the  plates through the steel bands that run across  After installing the heating  coils  lay out grey flooring cardboard  400 g m   lay out the floor planks across  the joists  and fasten the planks to the joists with screws     17       Floor plank   i Flooring cardboard  Heat emission plate   Heat emissio
18. ing degrees of air  humidity at a normal temperature of 18 25   C  The recommended intervals and  tolerances in air humidity are highlighted in grey     The overview applies to a correctly installed floor  cf  the guidelines in this and the  other instructions from Dinesen  and the information is only intended as a general  guide                 Climate condition Reaction   60 70   RF Slight transverse warping should be expected   50 60   RF No contraction gaps  slight warping should be expected   40 50   RF The floor planks are stable and level   30 40   RF Moderate contraction gaps  approximately 1  of plank width  and    slight warping should be expected       20 30   RF Contraction gaps of 1  of the width or more and moderate transverse  warping should be expected  There will also be minor drying cracks        lt 20   RF More pronounced transverse warping and drying cracks will appear   The floor will be depleted  and the lifetime of the planks will be reduced       21    How to succeed      Consider the humidity factor throughout  from the design stage to  construction  Let the humidity factor play a decisive role from the beginning   and never allow yourself to be pressured into installing floors under conditions  where the humidity presents a problem       Always make sure to measure the moisture content of the concrete prior to  installation     All work that might add moisture to the construction  such as masonry work    and basic paint work  must be finished prior t
19. n plate   Heating coil   Joist   Insulation    Vapour barrier  Concrete          Figure 5  Longitudinal section  self supporting heat emission plates on joists    4 3 2 4 Underfloor heating chipboard on joists    22 mm floor heating chipboard can be installed on top of an insulated layer  of joists with a cc distance of max  60 cm  Grooves have been prepared in  the chipboard for the heat plates and 16 or 17 mm heating coils  Lay out grey  flooring cardboard  400 gr m   and fasten the floor planks to the chipboard  with a screw  Pay attention to the placement of the heating coils     LLL LL LIL LL LL LL LI LI LL LALA LALALA LIZ Floor plank  O  Flooring cardboard  n  Heat emission plate  Heating coil  Underfloor heating chipboard  Joist    Vapour barrier  Concrete          Figure 6  Longitudinal section  underfloor heating chipboard on joists    4 3 2 5 Underfloor heating chipboard on concrete    The surface of the concrete floor must be level with a maximum deviation of 2 mm   measured across a 2 metre straightedge  The concrete moisture must not  exceed 85  RH  and a vapour barrier must be used     On the dry and straight concrete floor  place a 22 mm underfloor heating  chipboard on top of a vapour barrier of at least 0 20 mm PE foil with 20 cm  taped overlay  Let the vapour barrier continue up the wall and cut it off behind  the skirting board  Make sure that the vapour barrier is impenetrable to  irregularities in the concrete  Lay out grey flooring cardboard  400 g m    
20. o the installation of the floor       For the vapour barrier  use at least 0 20 mm PE foil or similar       The building must be dry and without construction humidity in accordance with  Dinesen s humidity guidelines  Never have the floor planks delivered until the  building is sealed off  dry and warm  and the humidity levels are under control       Place a good hygrometer in the building and keep an eye on the humidity  level  The building must be at an equilibrium with the season s mean humidity   A digital hygrometer can be purchased from Dinesen       Check  document and conform to the values in Table 2     General requirements for humidity and climate          Measuring point Level  Room temperature 18 25  C  Room humidity 35 65  RH       Concrete moisture content    Max  85  RH when a vapour barrier is used  If you  leave out the vapour barrier  the residual moisture  content must be less than 65  RH  NB  85  RH  corresponds to approximately 2 0 CM depending on  the type of concrete etc  Be aware of any restrictions  in the national standard requirements       Humidity in joists beams    Max  10 12        Humidity in plywood chipboard    Max  8 10        Vapour barrier    Min  0 20 mm PE foil       3 1    3 2    3 3    Humidity    Humidity should be one of the main focal points in connection with the design   planning and installation of a solid Dinesen plank floor     Humidity and plank floors    Much construction work requires proper drying  and materials such as pla
21. od may warp  That applies both to the first start up  after installation and to any subsequent start ups for the winter season     What are the benefits of using an oil finish in connection with underfloor heating     Answer  Oil seals the surface and preserves the natural moisture content of the  wood  which helps prevent the plank floor from drying out     Can I use lye and soap on Douglas in connection with underfloor heating   Answer  Yes  It is important  however  to pay attention to the state of the floor  and to clean it in accordance with Dinesen s recommendations  The floor needs  moisture  soap as well as correct maintenance to avoid tiny depletion cracks in  the wood surface     How does the room temperature affect energy consumption     Answer  If the room temperature is lowered from 22   C to 21   C you can save  approximately 10  on your heating bill     71    7 2    General guidance    Dinesen instructions    Before installation  Installation  Full surface gluing  After installation    See also our detailed instruction videos concerning sanding  finishing  floor washing  and maintenance on dinesen com  The instruction videos are only to be seen as a  supplement to our instructions     Literature    Treeinformation     Tree 63  and  Tree 64     traeinfo dk     23    Dinesen  Klovtoftvej 2  Jels  6630 R  dding  Denmark     45 7455 2140  info dinesen com  dinesen com    
22. olystyrene base     If the air humidity is kept at 50  RH  and the temperature at 20   C  it will take   3 4 months to achieve a concrete moisture level of 85  RH  But often  the  temperature is lower  and the air humidity considerably higher  which makes it  necessary to extend the drying period by several months  Drying traditional concrete  to a level of 85  RH should therefore be expected to be a very lengthy process that  can easily last 4 6 months  And even that can only be achieved if the building has  been sealed off quickly to initiate the dehumidification process     Humidity in the substructure    Joists  beams and substructures consisting of existing beams  plywood or chipboard  must be dry before the new floor is installed  In renovation or restoration projects   existing substructures made of planks or beams may have absorbed humidity during  the construction period  Always check the humidity of the substrate substructure  before installing the new floor  and make sure that it does not exceed 12  for joists   beams and 10  for plywood chipboard and plank substructures  cf  Table 2     Damage    Long term impact of humidity will cause the planks to warp  and the gap between  the floor and the wall will disappear  In worst case scenarios  walls  joists etc  may  be dislocated when the planks expand  When that happens  it is probably necessary  to re install or replace the floor  With less severe humidity damage  the warp will be  fully or partially eliminated over
23. ser should also receive a user s manual and be given a thorough  introduction to the operation of the system  During the first week  the flow temperature  must not exceed 25   C  After the first week  it may be increased by max  5   C every  other day  until the required surface temperature has been reached  If the flow  temperature is raised too quickly  the planks will warp  Often  the underfloor heating  system is left on all year around  since it is controlled by in room thermostats and  therefore only uses energy when the thermostat reaches its pre set point     19    5 1    Pitfalls    Always consider humidity when planning the project  and before the planks are  delivered  Any damage that may occur is typically due to unintended high levels  of humidity because humidity has not been a focal point     Make sure to determine and agree who is responsible for the dehumidification  etc  during the construction process in order to prevent later complications     Upon delivery  always check that planks and accessories conform to order  specifications in terms of quality  quantity  moisture content and appearance   That makes it possible to rectify any shortcomings or misunderstandings right  away     Always carry the floor planks inside immediately after delivery   never  under  any circumstance  leave them outdoors     Always check the straightness and the condition of the subfloor before  beginning the installation  It is absolutely crucial that the subfloor lives up to  th
24. ster and wood  suffer considerable damage if they are exposed to high levels of humidity  Unfortunately   those responsible for construction projects often compromise on the drying phase   which results in severe damage  Construction humidity is the cause of major delays as  well as over expenditure  but fortunately  this is avoidable if humidity is included in the  planning process from the design stage     Make realistic timetables  plan the dehumidification process  and use the right type  of concrete     Air humidity    If the air is fully saturated with steam  the relative air humidity  RH  is 100   A relative  air humidity of 50  means that the air contains 50  of the maximal amount humidity  it can contain  When it rains  the relative air humidity exceeds 100   Air humidity  depends in part on the building s location  structure  heating and ventilation     The higher the temperature  the more water the air can hold  When cold outside  air enters the building and warms up  the air dries  Dry air absorbs humidity from  the plank  This causes the plank to contract and in turn leads to contraction gaps  between the planks  The gaps appear when the air is driest  and the lower the air  humidity  the larger the gaps  See also Table 1     Construction humidity    Concrete is a porous material  and throughout its lifetime  the concrete absorbs   and releases moisture to and from its environment  depending on the temperature  and the humidity of the environment  Concrete consis
25. tion and heat loss  The real limitation is the surface temperature  The  surface temperature of the plank floor must not exceed 27   C  as higher temperatures  may severely damage the floor  The room temperature is controlled by in room  thermostats  The thermostats turn the heat supply on or off to accommodate  additional heat from people in the room  the impact of sunlight  lighting etc    The thermostats are positioned in places unaffected by sunlight  on interior walls   1 5 metres above the floor  In room thermostats can be either cabled or wireless     Types of underfloor heating    Underfloor heating is typically water based  The two main categories are heavy  underfloor heating with coils embedded in concrete and light underfloor heating with  coils in heat emission plates  In rare cases  electric underfloor heating is used     4 21 Heavy underfloor heating  Heavy underfloor heating is based on heating coils embedded in concrete  where the  concrete distributes the heat to the entire floor surface  The concrete has good    thermal conductivity properties  but the challenge is that the concrete accumulates    14    4 3    a great deal of heat and therefore responds slowly  When there is a change in the  heat supply due to sunlight or when there are many people in the room  the concrete  stays warm for a long time after the thermostat has turned off the heat supply   When the need for heat arises again  it takes a relatively long time to bring the  temperature back up  
26. ts of sand and pebbles held  together by a paste of cement and water  Concrete hardens and acquires its strength  when the cement hydrates   meaning that it reacts chemically with water   and ina  process producing heat  it forms a binder that glues sand and pebbles together  This  process begins a couple of hours after the components are combined and is largely  complete after 1 month  During the hydration process  the cement binds 25  of its  weight in chemically bound water  In addition  the cement absorbs 15  of its weight  in water  Thus  in total  the hardening of the concrete floor consumes an amount of  water corresponding to 40  of the weight of the cement  The water that remains   in the concrete after this process is complete is so called free water  which has to  evaporate from the concrete surface     3 4    3 5    3 6    8 7    Drying of concrete    In simple terms  the quality of the concrete can be expressed in the ratio of water to  cement  w c   For example  concrete that contains 150 litres of water and 215 kg of  cement per m  has a w c ratio of 0 70  Once the concrete has hardened  about 64  litres of free water remain in the concrete  Eliminating this water is a time consuming  process  which is highly dependent on the room temperature  air humidity  one or  two sided drying  the quality of the concrete  the thickness of the concrete layer and  the substrate  A traditional concrete floor has a w c ratio of 0 65 and is often cast in  a 100 mm layer on a p
27. ural solution     The number of external walls in a room has a considerable impact on heat loss    The more external walls  the greater the heat loss  Be particularly careful to calculate  heat loss in small annexes that have three external walls and perhaps also have   large window sections  as the size of the thermally conducting floor surface affects  the ability to heat up the room  The area is reduced by kitchen units  cupboards   etc  Rugs  mats and runners also reduce the emission of heat and risks bringing   the temperature under the rugs etc  above the max  level of 27   C  Small rooms can  therefore be more difficult to heat up than large rooms  High ceilings or cathedral  ceilings may also lead to higher heat loss     4 1 5 Flow temperature and surface temperature    The flow temperature depends on the required output and the chosen flooring   Normally  the flow temperature is 30 to 45   C  and it should not exceed 50   C    The flow temperature has a limited impact on the heat energy consumption  If the  temperature is raised from 30 to 45   C  heat energy consumption only increases by  6   as energy consumption is determined by the difference between the flow and  return temperature  It is only marginally more expensive to heat a thick plank floor  than a thin engineered wood floor  but it takes a higher flow temperature to ensure  the required surface temperature     Dinesen cannot provide any additional advice on flow temperature  as it depends on  the construc
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
WinCon-8000 Getting Started  Grapholas 12.1 User Guide - Product Documentation  RCA RC142 User's Manual  Bedienungsanleitung Ersatzteilliste  Goldtouch - Applied Ergonomics  ï 3 m 20}5  Instruction Manual TFDVD7379  Notas de Aula - Parte II - Informática  DÉFIBRILLATEUR HEARTSTART FRx  Altronix ALTV248ULCBHI    Copyright © All rights reserved. 
   Failed to retrieve file