Home

1 installation - ASCON POLSKA Sp. z oo

image

Contents

1. an Pin connector Z 1 4 mm 0 055 in max DO Fork shape AMP 165004 5 5 mm 0 21 in ET Stripped wire L 5 5 mm 0 21 in PRECAUTIONS NC d Despite the fact that the instru ment has been designed to work in harsh and noisy environments level IV of the industrial standard IEC 801 4 it is recommended to follow these suggestions A All the wiring must comply with local regulations The supply wiring should be rout ed away from the power cables Avoid using electromagnetic con tactors power relays and high power motors nearby Avoid power units nearby espe cially if controlled in phase angle mode Keep the low level sensor input wires away from the power lines and the output wires If this is not achievable use shielded cables on the sensor input with the shield connected to ground 2 2 SUGGESTED WIRE ROUTING 2 Electrical connections Conduit for supply and output cables A Supply B Outputs C Analogue inputs D Analogue output E Digital I O and Serial Comms Conduit for low level sensor cables IO 2 Electrical connections 2 3 EXAMPLE OF WIRING DIAGRAM VNC VT Notes 1 Make sure that the power supply voltage is d Power the same indicated on the instrument Pn 2 Switch on the power supply only after all the electrical connections have been
2. 34 SENSOR OR STRAIN GAUGE BREAK ALARM FUNCTION During the configuration phase page 17 set fields O JP Q i DEVIATION ALARM During the configuration phase page 17 set fields O P O R to value 4 active high or 5 R to value 1 When the PV over comes the sensor range limits the sensor break alarm intervention is immediate When the alarm con dition is no longer present the alarm stops ABSOLUTE ALARM During the configuration phase page 17 set fields O P Q to value 2 actve high or 3 active low active low BAND ALARM During the configuration phase page 17 set fields O P o R to value 6 active in or 7 active out AL1 RATE ALARM FUNCTION During the configuration phase page 17 set field s to value 8 When the changing rate of the PV connected to the alarm is higher than the specified threshold AL T1 is activated Setting range O 1 5 0 digit s For rates between O 1 1 0 digit s AL1 will be activated after 6 1 s For rates between 1 5 digit s AL1 will be activa ted after 1s 40ms Line configuration In order to optimize the rejection to line frequency it is necessary to set this parameter to the cor rect value 50 60 Hz 4 6 2 INl CONFIGURATION SUB MENU Engineering Lin iE units This parame
3. ToEH 1 r Alarm parameters 4 3 2 PARAMETERISATION PARAMETERS MENU 4 Operations I SR ETERO 2 d 4 m Mei pm 3 D D ec p Gc D 23 a ee L 3 g 9 E 2 E j HT i dH E O CH O Li O dg Bao G q m gd _ d en p D ER D La D Ce 2 CC h CCP ___ ep iH EINE i 3 adi G nz _ CD Oo O LI qP 110 a Ta 7 CO D D q e Q ou gd mm d D CC uu gt CC CC P Toners J ae Back to Operator mode 4 3 3 CONFIGURATION MENU ea L DII OY ABO y LIF or LU S ILA A PIPE LL I7 F lL JUL QS Configuration menu Tool an Input 1 Configuration Tolin it Input 2 Configuration To Ire St Gin Configuration 7 LI I 4 Operations Analogue Output bod SEL Base Configuration sub menu Configuration uu C__ 1 Ist Configuration ToHU5rc LUI I code Aux Configuration Vi o Y _ ini Pi S 2nd Configuration To iL 1 L UI code Alarm Configuration E S2 S amp CO T CD Line frequency Torin a LL TI J configuration di A BVA O Select the line Calibration p frequency 50 60 Hz Configuration a To jor iL To Shit dt B t Back to Qperator Mode 4 Operations Inf IL Input 1 Configuration sub menu P T LE gd LI IL I FO a DIL II I
4. ASCON spa ISO 9001 Certified ASCON spa via Falzarego 9 11 20021 Baranzate Milano Italy http www ascon it e mail support ascon it Indicator Transmitter Strain Gauge Input for Melt Pressure amp Load Cell Transducers 1 8 DIN 96x48 J 5 line User Manual e M I U J 5 1 06 CE C US 10 Cod J30 478 1AJ 5 E LISTED Indicator Transmitter Strain Gauge Input for Melt Pressure amp Load Cell Transducers 1 8 DIN 96x48 J 5 line afl Fit ol LUUT Il 12 SI z 6 an M ld Information CE NOTES ON ELECTRIC SAFETY AND ELECTROMAGNETIC COMPATIBILITY IN Please read these instructions carefully before proceeding with the installation of the controller Class Il instrument rear panel mounting This indicator has been designed in compliance with Regulations on electrical apparatus appliance systems and installations according to the European Community directive 73 23 EEC amended by the European Community direc tive 93 68 EEC and the Regulations on the essential protection requirements in electrical apparatus EN61010 1 93 A2 95 Regulations on Electromagnetic Compatibility according to the European Community directive 89 336 EEC amended by the European Community directive 92 31 EEC 93 68 EEC 98 13 EEC and the following regulations Regulations on RF emissions
5. B 3555 engineering units Input Shift 000 digits used to shift the input scale Table 1 Engineering units inf CIN Configuration I zd d L JUL td Je un iE sub menu Value Description Value Description DI Degrees Centigrade J g 0 001 kg L In t Degrees Fahrenheit La kg CUBO nant none Lon t 1000 kg nu mv H q 100kg Li Volt hed hPa L mn L HA mA UPd Pa amp S Aso H Ampere Nbdr mbar J bdc Bar cia MMH20 P5 PSI fifi mmHg Loan i ch Rh UI kom 2 0 Ph pH afl Nm Tolautt Calculated value select monkey in M inc Gin Low linit AZA Z AZA CIHCHCI CH JJJ Jenn AJ AJ AJ A not present if PO E LULC nant Gn High linit AZA CI ICH ICI OO JJI Tess JIII not present if EN El Jor L lLc r Cin No of decimals range L 3 not present if E M QI LULL unaont 4 Operations Auk Analogue output Configuration sub menu UTC IIS ST c E V T Art LI ICI IILH L JI E S2 G0 1 source nant L iic wm Arelogue oulputtype TT am dl DIN Uu c 1 14 ECH 4 Operations HUH Auxiliary Parameters Configuration sub menu If 2 IL ol TT n LO l II TI Lt Vi O IL2 digital input function table 2 IL3 digital input function table 2 Co
6. Corrosive atmosphere Sak al WZ Explosive atmosphere 1 5 PANEL MOUNTING 1 1 5 1 INSERT THE INSTRUMENT 1 Prepare panel cut out 2 Check front panel gasket position 3 Insert the instrument through the cut out UL note 1 For Use on a Flat Surface of a Type 2 and Type 3 raintight Enclosure 1 5 2 INSTALLATION SECURING 1 Attach the mounting clamps as shown 2 Push the mounting clamps toward the panel surface to secure the instrument 1 5 3 CLAMP REMOVAL 1 Insert the screwdriver in the clips of each clamp 2 Rotate the screwdriver 1 Installation 1 5 4 INSTRUMENT REMOVAL ENC 1 Push and 2 Pull forward to remove the instrument Electrostatic discharges can damage the instrument Before removing the instrument the operator must dis E charge himselfto 1MQ ground IN 2 Electrical connections 2 ELECTRICAL CONNECTIONS Banc CC de E alic N sl n c 2 fag nic 5 fc EL 2 Bac S 9 Exc 8 es Ae 7 N C zd NETS uc CAL1 e SIG B3 cal Eg ors SIG n IN2 a ALA E UL note 1 Use 60 70 C copper Cu conductor only 2 Wire size 1 mm 18 AWG Solid Stranded 100 2 1 TERMINAL BLOCK 1 28 screw terminals M3 Option terminals Tightening torque 0 5 Nm Positive screw driver PH1 Negative screw driver 0 8 x 4 mm Terminals AG Rear terminal cover 5 7 mm 0 22 in
7. 64 30 84 98 ascon france wanadoo fr AGENCE EST T l 33 3 89 76 99 89 Fax 33 3 89 76 87 03 AGENCE SUD EST T l 433 0 4 74 27 82 81 Fax 33 0 4 74 27 81 71 USA ASCON CORPORATION 472 Ridgelawn Trail Batavia Illinois 60510 Tel 1 630 482 2950 Fax 1 630 482 2956 www asconcorp com info asconcorp com DISTRIBUTORS ARGENTINA MEDITECNA S R L Phone 5411 4585 7005 Fax 45411 4585 3434 AUSTRALIA ONETEMP PTY IPA INDUSTRIAL PYROMETER Aust PTY LTD Phone 61 8 8352 3688 Fax 61 8 8352 2873 FINLAND amp ESTONIA Tim TOOL ov Phone 358 50 501 2000 Fax 4358 950 55 144 GERMANY Mesa INDUSTRIE ELEKTRONIK GMBH Phone 49 2365 915 220 Fax 49 2365 915 225 GREECE CONTROL SYSTEM Phone 30 31 521 055 6 Fax 30 31 515 495 BRANCH OFFICE Phone 30 1 646 6276 Fax 30 1 646 6862 HOLLAND TEMPCONTROL IEP B V Phone 31 70 3476431 Fax 31 70 3825516 POLAND ASCON POLSKA Sp z 0 0 Phone 48 34 35 33 619 Fax 48 34 35 33 884 PORTUGAL REGIQUIPAMENTOS LDA Phone 351 21 989 0738 Fax 351 21 989 0739 SPAIN INTERBIL S L Phone 34 94 453 50 78 Fax 34 94 453 51 45 BRANCH OFFICE Phone 3493 311 98 11 Fax 34 93 311 93 65 Phone 43491 656 04 71 Fax 34 91 677 21 26 SWITZERLAND CoNrROLTHERM GMBH Phone 441 1 954 37 77 Fax 441 1 954 37 78 TURKEY KONTROL SISTEMLERI LTD Phone 490 216 302 19 70 71 Fax 490 216 302 19 72 UNITED KINGDOM EUKERO CONTROLS LTD Phone 44 20 8568 4664 Fax 44 2
8. automatic calibration operation calibration process of the strain gauge see page 30 Normal Start e Bersani alibration Closing the contact causes the starting of the automatic strain gauge calibration SERIAL COMMUNICATIONS PARAMETERS OPTIONAL The parameters that follow are displayed only when the option al serial communications is installed in the instrument Communications protocol Paud rate Parity protocol Instrument seri al address Setting values Protocol Modbus bus Baud rate 200 2400 4800 9600 19200 38400 57600 baud Parity olof Le un st dd Instrument serial address 1 247 Default values Protocol J bus Baud rate 9600 baud Instrument serial address 1 Parity n nt SAFETY PARAMETERS Set Cal menu access code 1 Set Par menu access code 2 Set Conf menu access code 3 These parameters allow the user to change the factory default passwords When one code is set to zero the access to the menu s con nected to that code is are free see page 21 When using the serial communications port the user sets a code to 65535 the menu s connected to that code is are locked Setting ranges 0 65535 Default values Codel 1234 Code2 1111 Code3 3333 4 Operations 4 6 7 ALARM PARAMETERS CONFIGURATION SUB MENU The entries of this menu allow the user to configure the func tioning parameters of alarms AL1 AL2 AL3 and ALA AL1 alarm source AL2 alarm source A
9. com pleted 3 In accordance with safety regulations install a circuit breaker on the instrument power supply line that is clearly identified with that instrument or group of instruments The breaker shall be easily accessible by the operator 4 The instrument is PTC protected In case of failure it is suggested to retum the instru ment to the manufacturer for repair 5 To protect the instruments internal circuits use 2 AT fuse for Relay outputs 220 Vac SIG aL S de IN2 E 4 AT fuse for Relay outputs 110 Vac H 24K 1A acT fuse for Triac outputs 6 Relay contacts are already protected with varistors Only in case of 24 Vac inductive loads use model A51 065 30D7 varistors on a request 2 3 1 POWER SUPPLY INC Switching power supply with mul tiple isolation and internal PTC protection e Standard version nominal voltage 100 240Vac 15 10 Frequency 50 60Hz e Low Voltage version Nominal voltage 24Vac 25 12 Frequency 50 60Hz or 24Vdc 15 25 Included PTC ECH L Supply o For better protection against noise itis recommended not to connect the ground clamp pro vided for domestic installations 2 3 2 MAIN INPUT IN1 A1 For mV A2 4wire Strain G nal b i Input e Set code L 1 or 2 See page 16 to obtain 5 or 10 Vdc stabi ilized power supply for the external strain gauge bridge termina
10. first the unit value then the value of the second digit the third and so on In this way the user can quickly reach a value similar to the one desired and then the target value step by step If the value stops changing the min max value has been reached ee LI Cl I J LI A ae ES vy f FAI User Calibration LTL menu TI Lut J av i a e SCH i EE JL JAMIN a gt A none HU LI LI fe A A To mai J J Ee AVN na a se A e cz Looe request At the beginning only the units dgtis increrrerted Then only tens are increrrented then only the hundreds digt and soon upto a nurrber rear the desired one as 4000 Similarly when the nurrber is decre mented at the beginning changes only units digit Then only tens are decrerrerted then near the user reaches the coce step by step 4 2 2 MNEMONIC CODES SETTING e g configuration see page 25 Press the A or Wy to display the next or previous mnemonic for the selected parameter Continued pressing of A or SZ will display further mnemonics at a rate of one mnemonic every 0 5 s The mnemonic displayed at the time the next parameter is selected is the one stored in the parameter a se A ld Pp A ell navi F a gt 2 _ Engineering Units
11. logical status O of the output ports operation lock The retransmission analogue output is forced to the low limit 0 or 4 MA Normal Alarm acknowledge Closing the contact causes the acknowledgement of the active alarms Normal Reset Peak and Closing the contact causes the reset of the stored maximum and minimum operation Valley value Normal Measure Closing the contact locks the measurement of the IN1 input In accordance operation hold locked Notes all the values directly connected to IN1 measure are locked The display shows the maximum value read all the time the contact is operation value read closed The number displayed changes in case of higher max values The display shows the minimum value read all the time the contact is operation value read closed The number displayed changes in case of lower min values Normal Max value The display shows for a programmable period of time HL dE 1 the max value read then retums to normal operation The display shows for a programmable period of time HL dit f operation normal operation read then retums to normal operation For all the period the contact is closed the display shows the value of the varia the min value ble set with the d Dt parameter Normal Set the new Closing the contact causes the storing of the PV as tare value Normal Reset the Closing the contact causes the reset of the stored tare value Normal Enable Closing the contact enable the
12. mM millivolt No unit defined H 44 V Volt 4 3 PARAMETERISATION MAIN MENU This instrument has a 3 levels of password protection which allows the administrator to protect access to the various Menus Operator mode a al HB TE EE KSE El L HL TI ZS DIO Note The password used can be set to a value between O and 65535 Where O menu always accessible 1 65534 valid Password values 65535 menu always inaccessible can be set only through the serial communication interface LS Once the user selects the menu to be used the indicator asks for the specific password When all the passwords are set c ad the most important one arf can access all the Password 3 Entry Must be equal to Code or p Ana a LIJE Or I 021 COOC J page 23 Zl I 4 Operations menus c ade 2 the intermediate one dc com access the 2 less important menus c di Pdr cod 3 the third password allows the access only to the calibration menu c dL CI L UII SV 090 Jf Password CISTI J 1 Entry CJ OOo Ld Mette equal to l Code I o g NO ror menu Backto Lant menu page 24 Qperalor page 25 AVAILABLE PARAMETERS 4 Operations Shunt for strain gage cal Com
13. 0 8568 4115 E ICONS TABLE Main universal input Special Functions Digital input Icons table Strain gauge input Display the minimum stored value I Isolated contact Digital input connected functions Display the maximum nas stored value NPN open collector D Auto Manual SG Custom Le WEN Linearize Custom input HOLD PEAK Hold peaks or valleys DI TTL open collector RUN Run Hold Reset and PA program selection mA and mV HOLD PV Hold the PV Setpoint E do le o PV hold Te Thermocouple Conditioned Input Local NE d Setpoint slopes inhibition Pt100 WU fH NO NC Alarm status SAND BY Stand by SPST Relay E Frequency B a Keypad lock E Start up function os Triac F ER Delta Temp 2x RTD RTD Pt100 x Outputs lock us Timer function E a SPDT Relay Auxiliary input Current transformer EM Memorized Remote EZ E gt 2 REM Volt Remote setpoint res Setpoint programmer I ES Logic zur Feedback pizzi potentiometer
14. DU H FID LI 3 ZI Software TTT release Engineering Minimum value SS qm 7l 71 71 7 MI 2 read 3900 LI LI table 2 page 25 m m EE cL Fri Unt oo Sp Back to INL OV p U DI Maodimum value read Notes Back to IN 15050 1 To exit the Display functions and retum to the Operator mode wait IN 5 seconds without touching the instrument buttons 2 Lact is displayed when the outputg are locked page 36 Un st is displayed when the outputs are unlocked 6 Commands 6 COMMANDS COMMANDS TO THE INDICATOR AND OPERATING PROCEDURE The commands can be entered in 3 ways 6 1 KEYPAD 6 2 DIGITAL INPUTS 6 3 SERIAL see page 40 see page 32 COMMUNICATIONS see the manual on this topic e Keypad lock e Outputs lock 6 1 KEYPAD COMMANDS 6 1 1 KEYPAD LOCK UNLOCK To lock unlock the keypad press and hold the keys and simultaneously for 2 seconds With keypad locked if the user presses a key the instrument dis plays the message Lact The keypad lock unlock can also be achieved over serial com munications AN The keypad lock is retained in the event of power failure Operator mode ms OPP ELD set Li LI DIR IZBA VY A Press simultaneously for 2 seconds 6 1 2 OUTPUTS LOCK UNLOCK The outputs are switched to the OFF status by pressing and hold ing the keys and Dy simultaneously for 2 seconds With the outputs locked when displaying the
15. EN61000 6 3 2001 residential environments EN61000 6 4 2001 industrial environments Regulation on RF immunity EN61000 6 2 2001 industrial equipment and system It is important to understand that it s the responsibility of the installer to ensure compliance with the regulations on safety requirements and EMC The device has no user serviceable parts and requires special equipment and specialised engineers Therefore a repair cannot be carried out directly by the user For service or repair contact the manufacturer or your sales representative All the information and warnings about safety and electromagnetic compatibility are marked with the EXC sign at the side of the note Main universal input Auodliary input mA V Si 3 digital inputs ILL HES Ee Modbus RS485 EC xv Configuration and Supervision option Special functions pe i Digital inputs IL1 IL2 or IL3 functions ZU DES VS ES Quiputs o gt gt ae C5 mA opt CPA output can be used for calibration shunt when strain gauge autorratic calibration is required Table of contents TABLE OF CONTENTS pee m IwMsratLtLanOonw Page 4 ES 5 ELECTRICAL CONNECTIONS Page 8 INI INZ IN PRODUCT CODING e 14 E ces 4 OPERATION cccccsccsestestnstnstnee 18 DISPLAYS 34 e COMMANDS ss 35 rA TECHNICAL SPECIFICATIONS 37 A 1 Installation peas INSTALLATION Installation must be carried ou
16. H UJ TL CS 80 den Note No of decimals for linear scale only range 7 3 INL Filter constant time JF F 1 305 Low range ni Z Z Z OO JJJ Jess JJI for linear scale only min 100 digit Pa II VL 7 E I7 L L HL I FP ICL III I JUI S2 ABO High range OO AZA AZA ZA ICI ICI JJJ Jenn J AJ AJ AJ for linear scale only rin 100 digit Input conditioning eu id I EL D rice 2n c Urut Gut off square root DU 0 9495959 engineering units Input Shift 000 digits used to shift the input scale 1 Cut off the square root of the input value enables the user to round to zero a result that is too low to be important 26 d e FF LEI LI ILL TT ell ue VU LH SZ Cs O Tot int No of decimals for linear scale only range LH 3 Filter constant ime DF F 1 30s Low range 000 OO JJJ Jenn J AJ AJ AJ for linear scale only min 100 digit Input 2 Configuration sub menu LI VU C U 1 wees Ea IUL LU jl I7 I al Lui L uat Keck Inc JU CT SZ A High range MMi OO JJ San d sl sl sl for linear scale only min 100 digit Input conditioning uS E IIS PEL D rici 2i c d Li cic Qut off square root 1
17. L3 alarm source AL4 alarm source Sets for each alarm the signal source to be considered Setting values IN1 Cin IN2 Default value IN1 AL1 alarm output AL2 alarm output AL3 alarm output ALA alarm output These parameters connect each alarm to the output port to be activated when an alarm condi tion occurs Setting values none OP1 OP2 OP3 OP4 Default values AL1 OP1 S OP2 none AL4 none 4 Operations ALL AL2 AL3 ALA latching Rio function For each alam ittis possible to select one of the following functions nane none LE ch acknowledge blocking LCDL latching 4 blocking DH ISA ack sequence LA e LIL LL ILLI l J Hunk ISA ack sequence blocking Lich ALARM ACKNOWLEDGE FUNCTION Once an alarm occurs it is indi cated on the display until it is acknowledged To acknowl edge an alarm press Hefe key After this operation the alarm shuts off only when the alarm Condition is no longer present START UP DISABLING Ramp down AAL Disable REF On Off Start up Ramp up REF AAL On Off Disable Start up AAL Threshold REF range 156 ISA A ALARM RESET SEQUENCE The alarm intervention activates both the visual alarm the alarm LED on the display and the audible alarm the OP output used to acti vate for example a buzzer or a siren When the operator acknow ledges the alarm the status of the two alarms differs if
18. L4 alarms The range of the alarm threshold corresponds to the whole span When an alarm occurs the dis play will show the red LEDs 1 2 3 ana 4 respectively ON and when con figured with a change of the dis play colour Alarms reference value Internal reference value for devi ation and band alarm Used when Hl Tir int page 41 4 5 2 ALARM PARAMETER SUB MENU AL1 alam hysteresis AL2 alam hysteresis AL3 alam hysteresis AL4 alam hysteresis Hysteresis of the threshold of AL1 AL2 AL3 and ALA alarms It is specified as a of the full range AL1 alarm activation delay AL2 alarm activation delay AL3 alarm activation delay AL4 alarm activation delay Specifies a time in seconds that the indicator waits before activating an alarm Range 0 0 60s in steps of O 1 s 4 5 3 MEASURE MANAGEMENT SUB MENU The entries present in the menu allow the user to configure Display filter Measure peak hold time Display resolution The default display parameter Alternate display period Display fiter This parameter allows to con figure the period of time a redout must be sustained before to be diplayed Setting range 1 30 0 s Default value UE F filter bypass Measure peak HL ch 7 nota time This parameter allows the con figuration of the period of time a peak value must be sustained on the display Setting range 0 5 999 9 s Display v Gd resolution This pa
19. LIIU PPr a fldi hunt III n UF t FA o Al ac E GL Bg Bo Juko QS Enable edit mode for TT 1158 1560 tare value MIO Inn Pilenireterenoe PPI ni Sessa pow Lil See IL UI source L calibration menu UL L Factory reserved do E QA me ind Gin UF F Z amp amp O na acess this menu Enable fast selection of user strain gauge calibration ALL ALA alam DI UO output Jl du duna pont AE i GP2 P 3 DP4 ALL ALA alam action CU L m Toc NM it J wedge euc rcu TOLLAL 4 Operations 44 USER CALIBRATION MENU To access the sensor calibration and the tare setting functions the user must access the Cdl menu and insert at least the 3rd level password code 3 at page 39 If one of the passwords is set to zero the access to sensor calibration and tare setting functions is free t dc DH MENU E dre P menu can be accessed only ifthe con figuration parameter t dr ET is set to Un page 42 in the tare menu are present the functions displays the current tare value or if the SEN parameter E dr P E is set to Ln page 42 it is possible to modify the tare value manually using the A and SZ enters the new value LE sets a new tare value Press the keys A SV keys to sel lect the value E S enable the tare set ting starts the setting process During the calibration the instrument displays r un and atthe end dant LL E dr to reset the current tare value Press the keys Ay S
20. V Keyboard lock Output block Alarm acknowledge Min Max reset Measure hold Peak or Valley hold Display variable select Strain gauge calibration Tare set Features at 25 C em temperature OP1 output OP2 output opt OP3 output opt OP4 output OP5 analogue output option AL1 AL2 AL3 AL4 Description SPDT relay 2A 250Vac AA 120Vac for resistive load SPST relay N O 2A 250Vac 44 120Vac for resistive load SPST relay N O 2A 250Vac 4A 120Vac for resistive load SPST relay N O 2A 250Vac 4A4 120Vac for resistive load g4 20A 75002 15V max To retransmit IN1 IN2 or CIN Accuracy 0 1 Resolution 12 bit Galvanic isolation 500Vac lmn Hysteresis O L 10 0 Changing rate threshold O L 5 0 digit s Actontupe Deviation threshold range Band threshold O range Absolute threshold whole range Active high Active low Strain gauge break Action Sensor break Acknowledge latching Special Activation inhibit blocking functions OR ed of different sources of alam ISA A acknowledge sequence for activation of visual and audible alarm 7 Technical specification 7 Technical specification Features at 25 C em temperature Serial corrrrs optional Auxiliary power supply Operational safety General characteristics Description RS485 isolated Moche bus protocol 1200 2400 4800 9600 19200 36400 56800 bit s 3 wire 24Vdc 120 30 mA mex for a 4 20
21. Z keys to sellect the value YES 22 erases the tare value foce GUEI 5tdL MENU The 5 dL menu can be accessed only if the configuration parameter Sif dL is set to Gn page 42 Using the functions present in this menu it is possible to calibrate the sen sor on 2 different pons low range lr ac and high range c dL The possible ope rations in this menu are determined by the configuration parameter cd d page 42 LaL fid dut a 6 wire strain gauge automatic calibration When the user sets and confirms the value Do of the parameter dr ac the instrument starts the sensor calibration procedure when the cali bration starts no load must be applied to the sensor During this process the instrument calculates and stores the offset from zero then inserts the shunt resistance closing the OP4 output relay changes the measured value to the he dL configuration parameter calculates the span value stores the calculated value and returns to the normal operation mode CdL fid 5hunt 6 wire strain gauge calibration This procedure is similar to the previous one except for the fact that once calibrated at zero to start the calibration process of the second point the user must select and con firm the value Un for the 5 c di parameter LaL ho fdea manual calibration The operation is similar to the calibration with the shunt but when activated the calibration of the second point does not activate OP4 output c
22. an be used for different purposes e g as alarm The two points can be cali brated separately and independently Cdifld sde o single calibration This setting allows only the zero calibra tion procedure in the menu is present only the parameter dc ac 4 4 1 CALIBRATION AND TARE PROCESS The process that calculates the tare value or the calibration of the strain gauge per forms several controls in order to make the reading more accurate If the controls are not passed the instru ment displays an error code that indicates the problem found To correctly understand the meaning of the error messages some aspects of the cali bration or the tare setting processes must first be explained e For both the processes the input must be acquired in a known and stable con dition to avoid that electrical noise mechanical disturbances or variations of the input signal can change the qual ity of the reading The instrument uses an algorythm that verifies the stability of the input signal and returns an error if it is not stable e The strain gauge calibration process defines the zero and a measure span On these two measures a control can be made to avoid that a too small span value does not ensure a resolution bet ter than or equal to 10 bit e A further control is made on the strain gauge calibration in order to verify that the instrument is able to measure the whole range as the calibration process of the high end is ma
23. code D d to choose E g Enter the code c 3L to choose Dc input 0 20 mV ALL absolute active high Change the display color to AL2 absolute active low red when AL 1 is active AL3 disabled Peak hold disabled AL4 sensor break alarm IN1 Input range IN1 Input Type nm DC input O 20 mV oo DC input 0 50 mV 10 DC input O 100 mV 2 0 DC input O 1V 3 0 DC input 0 5 V Linear 4 0 DC input 1 5V 5 0 DC input O 10V 6 0 DC input O 20 mA 70 DC input 4 20 MA 80 DC input O 20 mV Strain gauge 5 V O 1 DC IDpuE dos 99 TR bridge excitation voltage 11 DC input O 100 mV 2 1 DC Input O 20 mV Strain gauge 10 V 02 DC INPUT Osis 20 TM bridge excitation voltage 1 2 DC input 0 100 mV 2 2 Notes 1 Selecting for code a value between O 3 the instrument uses forthe measurement terminals 11 and 12 The other measurements m values between 4 8 are made using terminals 9 and 10 2 To use a strain gauge input select the bridge excitation voltage of the transducer This selection is valid only if INI input range code is set for mV input codes O 2 3 Selecting the strain gauge input enables the transducer excitation power supply dedicated sensor break diagnostic routines on termi nals 8 9 11 12 and a specific strain gauge menu The bridge exci tatio
24. de at a value that is 50 100 of the full range Error messages Code Description Ere e Tare not set because the input signal is not stable 3 Strain gauge sensor not correctly con nected r 4 Low range calibration command not executed because the input signal is not stable r 5 High range calibration command not executed because the input signal is not stable E Strain gauge calibration span lower than 10 bit resolution i The instrument does not cover the whole strain gauge measure range Low range of strain gauge calibration out of range ve ECT LI Z tre Lee E e L ve 4 Operations 4 Operations 4 5 PARAMETERS DESCRIPTION 4 5 1 ALARM THRESHOLD SUB MENU For ease of operation of the indi cator its parameters have been grouped menu according to their functionality area OP1 OP2 OP3 and OP4 out puts can be used as alarms It is possible to configure up to 4 alarms AL1 AL2 AL3 and AL4 page 24 selecting for each of them type and operating condition of the alarm page 31 the functionality of the alarm acknowledgement latching page 34 thestartup disabling blocking page 34 Sensor or strain gauge break function page 34 Rate alarm only for AL 1 refer red to IN1 AL1 alarm threshold AL2 alarm threshold AL3 alarm threshold ALA alarm threshold Parameters to set the threshold of AL1 AL2 AL3 and A
25. ion with the alanm number 2 The parameter must be completed vvith the output number 3 ED Een BREE O IE L value enables rounding to zero those results too low to be important 4 3 2 PARAMETERISATION CALIBRATION MENU CONI Lut OS Amo Note 1 When using the AMS keys the user selects ToLurr Trasducer calibration sub menu Toe Dr oc Bat Back to Operator Mode t dre Tare sub menu vu Tare curent value LUUT Mew edit tare cur F KZ amp T rert value EDI L Set tare 1 Jl LL Set a new Tare value j SZ Ss T Valid values HD no 1 utc Gear tare alue 1 Li cl Set the Tare value to Vi BO zero J G Valid values HD noa To Se HL pe the indicator executes the command oo the indicator switches to the subsequent command 4 Operations cL FIL Trasducer calibration sub menu Jt Litt SIL TT l r zi f TV EH E Torn it Zero calibration 1 Valid values YES Ann Span calibration 1 Valid values SES Ann 1 J Filter time constant Display filter filter bypass ZE r U Display resolution Visual resolution me i II I I JL il I l ME AS Measure sub menu 2 Qo E i 0 EM LI K ud le Li D D D Du Visual tine in atemate auto mode Range 5 20s NZ LEN JCT
26. ion Code page 17 18 INI input value 1 In engineering units Over Under range range Alarm status LEDs reds AL1 ON AL2 ON AL3 ON AL4 ON HERE Alarm acknowledge Entry key for selection and value setting confirmation 4 1 2 KEY FUNCTIONS AND DISPLAY IN PROGRAMMING MODE A The parameter setting procedure has a timeout If no keys are pressed for at least 30 seconds the indicator switches back auto matically to the operator mode After having selected the para meter or the code press and DY to display or modify the value See page 25 The value is entered when the next parameter is selected by pressing the 1 key Until the Ay or WB are pressed or if you wait for 30 sec onds the parameter value is not enterted Pressing the key the next group of parameters is shown on the display 4 Operations Parameter Code Value 15 m E LI UU U CMN Zeen mi m m m me lU UU L UD I2 13 1 2 3 4 ce y A Lil e Back to previous parameter Menu access Strain gauge sensor calibration Parameter setting Parameter Configuration modification Entry key for selection and value confirmation 4 Operations 4 2 PARAMETER SETTING 4 2 1 NUMERIC ENTRY i e insert oJ 3 password Pressing A or MN momen tarily changes the value by 1 unit every push Continued pressing of A or changes
27. ls 8 and 9 e Set code 0 1 or 2 see page 16 to obtain suitable mV and 12 C input 50 20 or 100 mV terminals 11 Main 11 input IN1 mV Configuration example For strain gauge transducer rated 3500 3 3 mV V 10 V excitation Voltage select 1 Lt 2 Electrical connections Aq A3 6wire Strain Gauge inp eSet code 1 or 2 see page 16 to obtain 5 or 10 Vdc stabilized power supply for the external strain gauge bridge terminals 8 and 9 e Set code I 0 1 or 2 see page 16 to obtain suitable mV input 50 20 or 100 mv terminals 11 and 12 The calibration wires of the transducer must be connected to CAL terminals 34 and 35 OP4 Output Note The excitation current of the strain gauge transducer must not exceed 30 mA 11 2 Electrical connections B FormA V V mA Rj gt 10MQ B1 With 2 wire transmitter Transmitter B2 With 3 wire transmitter Transmitter Note 1 Auxiliary power supply for external transmitter 24Vdc 20 30mA max with no short circuit protection 12 2 3 3 AUXILIARY INPUT IN2 OPTION Nc d For mA and V Current 0 4 20mA Input resistance 300 Voltage 1 5V O 5V 0 10V Input resistence 300kQ 4 mA 2 3 4 DIGITAL INPUTS VNC e The input is active when the logic state is ON corresponding to the contact closed e The input is inactive when the l
28. lue 0 Secondary input Reger This value is added to the mea sured input 2 value Its effect is to shift the whole IN2 scale of up to 1000 digits Default value O 4 6 4 CONDITIONED INPUT CONFIGURATION SUB MENU Calculated value Es selection Cin The Cin parameter selects the type of operation that must be applied to input 1 IN1 using the secon dary input IN2 the result is the conditioned input ir In the table that follows are listed the possible conditioning ope rations Id Description mt Cin IN1 iic Cin IN2 Sutil Cin IN1 IN2 Sub Cin IN1 IN2 I I nu LI tl Cin IN1 IN2 2 nid Cin MAX INI IN2 Lol Cin Min IN1 IN2 lut Cin IN1 xIN2 r so Cin IN1 IN2 eii coi incl These parameters defines the range for the conditioned mea sure in Number of deci rt und mals for Cin value This parameter allows the user to set the number of decimal digits to be displayed for the pri mary IN1 input For linear scales only Setting range O 3 4 6 5 ANALOGUE OUTPUT CONFIGURATION SUB MENU Analogue output source Selects the variable to be put on the analogue output Setting values None In1 Cin In2 FIDE up Analogue output type Selects the type of signal retran smitted by the analogue output Values 0 20 mA 4 20 mA Default value 0 20MA irene Hoe Range of the analogue output Halo 9999 99999 H
29. mA 2 Wire transmitter Input measure Parameters Access protection Power supply Safety Hectromagnetic compatibility UL amp CUL approval Protection EN60529 IEC529 Dimensions Detection of out of range short circuit or sensor break with autorratic activation of the safety strategy and alerts on display A non volatile memory stores for unlimited time all the configuration and parameter values 3 password levels to access the strain gauge calibration Configuration and Parameters data Keyboard lock Cutputs Block 100 240Vac 15 10 50 60Hz or 2ANAC 25 12 50 60Hz and Ll CATA PIRAS ES DAN 15 425 PTC protected Compliance EN61010 1 IEC 1010 1 installation dass 2 2 5k V pollution dass 2 dass Il instrument Compliance to the CE standards for industrial systerre and equipment File EL76452 pending IP65 front panel 1 8 DIN 96 x 48 depth 110 mm weight 250g approx EN WARRANTY We warrant that the products will be free from defects in material and workmanship for 3 years from the date of delivery The warranty above shall not apply for any failure caused by the use of the product not in accordance with the instructions contained in this manual Warranty Worldwide sales network NEM ASCON S WORLDWIDE SALES NETWORK SUBSIDIARY FRANCE ASCON FRANCE 2 bis Rue Paul Henri Spaak ST THIBAULT DES VIGNES F 77462 LAGNY SUR MARNE Cedex T l 433 0 1 64 30 62 62 Fax 433 0 1
30. meaningful SAFE Setting range 0 9999 Default value 0 IN1 input shift This value is added to the mea sured IN1 value Its effect is to shift the whole IN1 scale of up to 1000 digits Default value 0 4 Operations 4 6 3 IN2 CONFIGURATION SUB MENU anni The parameter defines the range of the secondary input IN2 Value p Z z E l Im III am Tcu Description DM a5 M 10V 20 mA 20 mA Number of deci PET mals IN2 input This parameter allows the user to set the number of decimal digits to be displayed for the secondary input IN2 poor For linear scales only Setting range O 3 Input 2 filter time constant Time constant in seconds of the RC input filter applied to the PV input When this parameter is set to UFF the filter is bypassed Filter response 100 63 2 PV O till Setting range 1 30 0 s IN2 input low range IN2 input high range These parameters allow the user to set the operating range of the primary IN2 input For linear scales only Setting range 9999 99999 IN2 measure geren This parameter allows the user to round to zero those results of the square root of IN2 conditio ning that are not meaningful GF dct enabled none disa bled Cut off square fub d root result This parameter allows the user to round to zero those results that are not meaningful Setting range 0 9999 Default va
31. mmunications protocol NU LE VII ILL uiu H d ul II LU ST I7 JL 1 Looe J IT Fr t l iJi l Vi I7 02 DO A Fl LE HDD pu d nat Puln add Set Password 1 corfiguration men i ri I I I7 DI LI esst 1 1 1 Set Password 3 user calibration dpud Table 2 Digital input functions see also page 38 IL JL cC IL J Value Description Value Description nante Not used HE PH Positive peaks sustained HDU Keypad lock display Ji Outputs lock ut mi Negative peaks sustained ncru display Met Nanmmacknowedge rue Ed Display a different parameter Ld SELL setae r HL Max and min reset MEL Reset tare CE JIE Hot d Measure Hold H d Enade strain gauge calibration He PH Positive peak enable vr a SetcalibratioySecond He PL Negative peak valle erede HL calibration step h if dL 4 Operations LIL Alarm configuration sub menu LL FIL Transducer Calibration sub menu DI HE CINI High calibration L Tare menu enable IL JI SIL CL value LOLL Dar E 3 SV C 80 VS O shurt value for strain S CH Enable tare menu 4 A eee ALL ALA alarm ot De a afi l 3 HI Caliration node LO Tare volue editing IL JI ls Dt az dad IL JL DI cone Ace LU
32. munications Address Calibration Mode Password 1 Password 2 Password 3 Alarm Source 1 Communications protocol Alarm Output 1 Baud rate Enable User cal menu Instrument calibration Digital Inout Conf Digital Input2 Conf Digital Input 3 Conf Latching blocking 1 Alarm Ref Source Output Action 2 Tare menu enable Et ont Parity Tare value editing enable Analogue out Source Analogue Out Low Range Analogue Out High Range Analogue Out Type frea CT Y g units onstant time dE High Range CIN no of decirral menu password 1 configuration code 2 configuration code Low Range conditioni ng Cut off square root 3 ok put conditioning shift Calculate value select DI Number of decimals Number of decimals IN2 filter constant time Low range INL engineer INIL filte Power supp 0 IN2 ino High range Inp Inp CIN Inp CIN Inp r L I JI Ul zi WR I tI l LI TL Li Il wm L ILL Il IL r r LI l J 117 La II Il ar LL ie eel el Looe L AE 7I Oo ot LD Ut Pt III 7 sac L IE 1 4 1 4 3 Cut off the square root of the input jr menu Default display parameter Alterete tive Ext Pc 1 The pararreter must be corrpleted Fide menu pessword AamSepoint 1 Alammintemal ref value Alamnhysteresis 1 Alemnadivetion dday 1 Filter tire constant Display resolut
33. n voltage 5 10Vdc is present on terminals 8 9 when 1 2 Display mode M Green t Red 1 Red when alarm 1 AL 1 active 2 Red when at least 1 alarm is active alarm OR 3 Alternate between IN1 IN2 and CIN value 4 Manual forced display of IN1 IN2 CIN Lo Hi and Unit value 5 Hold of the peak values N Disabled 0 Shows the max value HI peak for a programmable period of time 1 Shows the min value LO peak for a programmable period of time 2 Alarm type and function i 2 Non active O Sensor or strain gauge break alarm 1 Abssl te Active High 2 Active Low 3 Active High 4 Deviation ACBUBTDW 5 Band Active Out 6 Active In 7 Rate alarm AL1 only 8 3 Product coding 4 Operation ZEN OPERATIONS 4 1 1 KEY FUNCTIONS AND DISPLAY IN OPERATOR MODE Display mode of the Peak values MAX or MIN LEDs will be lit when the display shows a minimum or a maximum value HLD LED will be lit when the value displayed is locked by the HOLD command HOLD and PEAK commands stop the measurement procedure while the PEAK VALUES HOLD command returns to normal operation after a programmed period of time HL di parameter Digital input status LEDs yellows 11 i1 active 12 IL2 active 13 IL3 active Menu access Min and Max values display Note 1 The color of the display is set through field M of the Configurat
34. ogic state is OFF corresponding to the contact open TTL NPN Isolated contact 2 3 4 OP1 OP2 OPT OP3 OPT OP4 OUTPUTS NC CP SPDT relay output OP2 CP3 SPSI NOrelay outputs oma SPST NO relay output OP5 Retransmission analogue output OP1 relay output SPDT relay 2A 250Vac for resistive load fuse 2AT at 250Vac 4A 120Vac fuse 4AT at 120Vac OP2 OP3 relay outputs e SPST N O relay 2A 250Vac for resistive load fuse 2AT at 250Vac 4A 120Vac fuse 4AT at 120Vac OP4 Relay output SPST relay N O 2A 250Vac for resistive load fuse 2AT at 250Vac 4A 120Vac fuse AAT at 120Vac OP5 isolated analogue output e 0 4 20MA 750Q 15V max 2 3 5 ALARM OUTPUTS UNC OP1 output OP4 output NC Coil of the load contactor Notes 1 Varistor for inductive load 24Vac only To retransmit one of the following values IN1 IN2 or computed conditioned signal e Galvanic isolation 500Vac 1 min e 0 A 20mA 750Q or 15Vdc max 2 Electrical connections 2 3 7 SERIAL COMMUNICATIONS OPTION PANC 2 Galvanic isolation 500Vac 1 min Compliance to the EIA RS485 standard for Modbus J bus e Setting dip switches AN Please read gammadiue and deltadue series serial communication and configuration software technical manual 13 3 Product coding ER PRODUCT CODING The complete code is shown on the instru ment label The informa
35. olt 9999 99999 Default values H ol ui O 0 Holt 10000 10096 4 Operations 4 6 6 AUXILIARY PARAMETERS CONFIGURATION SUB MENU A function is assigned through the configuration procedure to each IL1 IL2 and IL3 digital input see the parameters set ting at table 2 at page 28 The configured function is activat ed when the digital input free volt age contact or open collector out put is in the ON state closed Itis deactivated by setting the input to the OFF state open The activation of the function through the digital input has the highest priority than through the keypad or through the serial communications IL1 digital input function IL2 digital input function IL3 digital input function 4 Operations Function None Keypad lock Outputs lock Alarm acknowledge Peak and Valleyvalue reset Measure hold Positive peak hold enable peak Negative peak hold enable valley Positive peaks sustained display Negative peaks sustained display Display a different parameter Set Tare Reset Tare Enable automatic calibration Start automatic calibration 38 Parameter Value Performed operation e e Off on With the keypad locked the commands from digital inputs and serial com Unlocked munications are still operating Normal Outputs Closing the contact causes the setting to the
36. process variables the instrument displays the mes sage 5L ac E instead of Un iE To unlock the outputs press the keys simultaneously again The outputs lock unlock can also be achieved over serial communications AN The outputs lock is retained in the event of power failure 6 Commands Operator mode wl fiL I DU Press simultaneously for 2 seconds 7 Technical specification VA TECHNICAL SPECIFICATIONS Features amp 25 Cenvi rg Description 5 digit high efficiency height 15 nm limits 9999 99999 AEE COON S red or green configurable depending on the user needs and or the alarm status A D converter with 16 bit resolution Common Overall response time 20 rre Characteristics Input shift 1000 digit Input filter 1 30 s OFF 0 IN1 Accuracy 0 1 1 digit between 85 240 Vac the error is negligible Main input M n ae 5V10V selectable 3500 10kQ bridge load bridge excitation see pages 11 12 and 16 IN2 second input option Digital inputs 3 logic not isolated from intemal electronics DC input Current DC input Voltage DC Current DC voltage The voltage free contact closure enables Engineering units Floating decimal point 0 20 mM O 1V Display resolution 0 50 NV O 5V 1 2 5 10 50 100 digits O 100mM 0 10V selectable Input drift lt O0 1 20 C ambient temperature Accuracy 0 1 Sampling rate 250 ms 1 0 5 O 10
37. rameter defines the reso lution in digit that the instrument applies to the display output to make the readout more stable Setting range 1 5 10 20 50 100 Default value 5 Default displayed variable Defines the name of the varia ble that is displayed by default when in manual forced display mode field set to 5 in the configuration code Value Description in input 1 Inc Input 2 E Conditioned input I L III Lo Minimum stored value z Hi Maximum stored value Haak Selected engineering unit Default value In 4 Operations period Cinacthe Parameter to set the display time of an alternate measure when the conditioned input is active t ID Setting range 5 20 s Default value 5 s 4 Operations 4 6 CONFIGURATION MENU For ease of operation of the indi cator all parameters have been organised in groups menu according to theirfunctionality area 4 6 1 BASE CONFIGURATION SUB MENU configuration code Field nm allows the selection of the range of the primary input IN1 page 17 code L allows the selection the strain gauge input Field M allows the selection of the function mode of the display page 17 Field N selects if and how the peak values are to be held or not on the display 2 d part of the configuration code Fields O P a and R select alarm type and function page 17 15 part of the
38. t only by qualified personnel Before proceeding with the installation of this indicator follow the instructions illustrated in this manual with particular attention to the installation precautions marked with the symbol related to the European Community directive on electrical protection and electromagnetic compatibility To prevent hands or metal touching parts that may be electrically live like the terminal block the indicator must be installed in an enclosure LE 1 1 GENERAL DESCRIPTION IP 20 Terminal block EN61010 1 IEC1010 1 Mounting clamps Panel surface Front panel IP65 protection EN 650529 IEC 529 1 2 DIMENSIONAS 96 mm 3 78in 110 mm 4 33 in 10 mm max 0 39 in max 10 mm max 0 39 in max 1 3 PANEL CUT OUT 4540 6mm 9210 8 mm 3 6210 031 in 1 Installation 1 7840 023in 65mm min 2 56 in min 113 mm min 4 45 in min ln 1 Installation 1 4 ENVIRONMENTAL CONDITIONS IO AR Operating conditions 2000 E Altitude up to 2000 m Ic Temperature 0 50 C 9o Rh Relative humidity 5 95 96 non condensing Suggestions Special conditions a Altitude gt 2000 m Use 24Vac supply version Ic Temperature gt 50 C Use forced air ventilation 9o Rh Humidity gt 95 96 Warm up RN Conducting atmosphere Use filter Forbidden Conditions Q D
39. ted through separate operator commands OP4 relay is associated to the Span calibration phase and is activated autorratically in order toinsertthe shunt of the 6 wire strain gauge Auto Both the Zero and Span are enabled The calibration pro cesses are started through an operator command CP4 relay is activated autorratically in order to insert the shunt of the 6 wire strain gauge Enable sensor calibration Enable set tare command Enable Disable the access the transducer calibration sub menu page 23 and to t dr DH sub menu page 23 When both are disa bled the 5C HL menu is hidden Setting values ON OFF Default value ON Enable edit tare Enable Disable the editing of the tare value with the urr com mand page 30 Setting values ON OFF Default value ON Factory calibration AN The instrument calibration is a factory procedure It must not be performed by the user The menu is protected with a password 5 Displays ru DISPLAYS 5 1 DISPLAYING THE PROCESS VARIABLES 1 5 2 DISPLAYING THE CONFIGURATION CODES 1 Operator mode Operator mode 1604 3 2 DE YU guration index FID LI I ZI 222 L 2L LU aj e IN2 reading En SZ 4 amp 9 CJ O 2 part of confi LI LE HU 2 guration index EVEN E LU dal AINI le Wau i LULL Conditioned LI 2 Hardware x Puis measure value nav ug pamm Back to INL E
40. ter sets the desired engineering units All the engi neering units available are listed on page 27 table 1 IN1 Input number of decimals This parameter allows the user to set the number of decimal digits to be displayed for the pri mary IN 1 input For linear scales only Setting range O 3 IN1 Input 1 filter time constant Time constant in seconds of the RC input filter applied to the PV input When this parameter is set to UE E the filter is bypassed Filter response 100 63 2 PV O till Setting range 1 30 0 s IN1 input low range IN1 input high range These parameters allow the user to set the operating range of the primary IN1 input For linear scales only Setting range 9999 99999 IN1 measure conditioning Parameter to enable the con ditioning of the IN1 measure The calculations available are square root of INl measure o6W rtby 16 segments or 17 points linea risation Ur ul When the value is nont no cal culation is made on the IN1 measure AN The 17 points to define the linearisation curve must be entered through the serial communications port please read the gam madue and deltadue series serial Communication and configuration software technical manual for more information 4 Operations Cut off square Cut root result This parameter allows the user to round to zero those results of the square root of IN1 conditio ning that are not
41. the alarm con dition has been removed or not In the table that follows the visual and audible alarm status are pointed out for each condition Alarm reference AL F15 source This parameter allows the user to select the reference value to be used for the alarms Values Int In2 Default Int the value set in HL EF page 32 Output OP1 action Output OP2 action a action Output OP4 action Sets the type of action of the output port Values direct relay coil acti vated in alam condition rever se relay coil not activated when in alarm condition Default value direct 4 Operations 4 Operations 4 6 8 TRANSDUCER CALIBRATION SUB MENU The LE SL menu allows the user to choose the transducer cali bration mode Shunt for strain Fobia This parameter sets the value in percentage of the higher calibration point of the strain gauge the shunt value Setting range 50 100 Default value 80 standard value of the 6 wire strain gauge shunt Transducer calibration mode This entry selects the type of calibration procedure to be performed Setting values 2f r o fd i CL zm qe JOO e IL Zero Enebles onlythe zero calibration Man Both the Zero and Span are enabled The calibration pro cesses are started through separate operator commands OP4 output is not associated to tne span calibration phase Shunt Both the Zero and Span are enabled The calibration pro cesses are star
42. tion about product coding is accessible from the front panel by means of the procedure described in section 5 2 page 43 Configuration code software Basic product code hardware Instrument label J 5 3750 0000 A0A 0450 2210 VAL N 100 240V 50 60 Hz AW HIBERUM E CE Jf MA 2 A202013 4 3 Product coding 3 1 MODEL CODE The product code indicates the specific hardware configuration of the instrument that can be modified by authorised personnel only Analog output for signal retransmission Second input IN2 Analog output Second input IN2 User manual English std Configuration Line Basic Accessories ISt part and part Model FEES DT o Fo 0 11 mn o P oiR Line J 5 Power supply Al 100 240Vac 15 10 3 24Vac 25 12 or 24Vdc 15 425 5 Outputs OP1 OP2 OP3 OP4 5 Relay Relay 7 Relay Relay Relay Relay 9 Serial Communications None LU RS485 Modbus J bus SLAVE 5 Options n None LU 1 2 5 8 3 Product coding 3 2 CONFIGURATION CODING A 444 index code follows the model of the indicator The code has to be set to configure the indicator see chapter 3 1 page 15 Index I L IMIIN Index 1st part of 2nd part of configuration configuration code code E g Enter the

Download Pdf Manuals

image

Related Search

Related Contents

  SmoothMoves User Manual v2  S1107 NE-CAT HBM - USER MANUAL-01  Route HDLC Manual  Instrukcja obsługi    Wireless Color Camera with Receiver  Zen Home Talk – Service User Guide  Philips KEY016 User's Manual  

Copyright © All rights reserved.
Failed to retrieve file