Home

ERNT-ASLTY40 ERNT-ASLTY50 ERNT

image

Contents

1. Item Use Precautions Width dimension The wiring may interfere with the adjacent module Use of the Mitsubishi of module LG69 space module is recommended lt MELSEC AnS Series gt lt MELSEC L Series gt Space Module LG69 cS 16 5mm 28 5mm 34 5mm 45mm Depth and Height dimension Installation with the Base Adapter Because the module is increased in depth dimension check dimensional data before installing the module MELSEC L k Conversin Adapter Base Adapter Installation with the DIN rail I I i I i 1 ee a L a Mounting bracket T supplied with MELSEC L Series Nar L Series Conversion Adapter System DIN rail Mounting bracket fixing screw M3 5 x 6 supplied with Conversion Adapter Conversion adapter installation screw M3 x 25 Precaution Conversion Adapter MELSEC AnS Series terminal block MELSEC AnS Series terminal block installation screw M4 5 1 Installation Method Terminal block cover supplied with Convers
2. Maximum voltage drop at ON OFF ON 2ms or less 0 5ms or less Resporise 2ms or less 1ms or less ime ON OFF resistance load rated load resistance load Surge killer Zener diode Zener diode 3 2A one common Fuse None non replaceable Yes Protection function None overheat protection function overload protection function 100mA TYP all points ON 16 points 1 common 18 point terminal block 120mA TYP all points ON 8 points 1 common 20 point terminal block Internal current consumption Wiring method for common External connection system Make sure the section of the above table meets the specification of the machines and equipment connected to the MELSEC L Series module Internal current consumption TYP all points ON Protection function None overheat protection function overheat protection function overload protection function overload protection function 270mA 79mA 100mA TYP all points ON TYP all points ON Wiring method for common 8 points 1 common 8 points 1 common 16 points 1 common External connection system Make sure the 20 point terminal block 20 point terminal block equipment connected to the MELSEC L Series module 18 point terminal block section of the above table meets the specification of the machines and 3 3 ERNT ASLTY80
3. Mitsubishi General Purpose Programmable Controller Renewal Tool Conversion Adapter Model ERNT ASLTY40 ERNT ASLTY50 ERNT ASLTY80 User s Manual sa MITSUBISHI ELECTRIC ENGINEERING COMPANY LIMITED HEAD OFFICE Hulic KUDAN BLDG 1 13 5 KUDANKITA CHIYODA KU TOKYO 102 0073 JAPAN NAGOYA ENGINEERING OFFICE 139 SHIMOYASHIKICHO SHIMOYASHIKI KASUGAI AICHI 486 0906 JAPAN SAFETY PRECAUTIONS Always read these precautions prior to use Before using this product please read this manual carefully and pay full attention to safety to ensure that the product is used correctly The precautions presented in this manual are concerned with this product only For Programmable Controller system safety precautions refer to the user s manual of the MELSEC L series CPU module to be used In this manual the safety precautions are ranked as WARNING and CAUTION Mee a ene eee nee ee ee pe ee ee ee et fee eg ne ae ed ee ee I Indicates that incorrect handling may cause hazardous conditions I Z N WARNING resulting in death or severe injury l l A CAUTION Indicates that incorrect handling may cause hazardous conditions resulting in medium or minor injury and or property damage L427 I t e Note that failure to observe the A CAUTION level instructions may lead to a serious consequence according to the circumstances Always
4. Manufacturers who recognize their products are compliant to the EMC and Low Voltage Directives are required to declare that print a CE mark on their products Authorized representative in Europe Authorized representative in Europe is shown below Name Mitsubishi Electric Europe BV Address Gothaer strasse 8 40880 Ratingen Germany 1 Overview This manual describes specifications handling and other information about the Conversion Adapter ERNT ASLTY40 ERNT ASLTY50 ERNT ASLTY80 available as Renewal Tools for the Mitsubishi General Purpose Programmable Controller The Conversion Adapter is a product for effecting conversion to transcend difference in pin assignment between the MELSEC AnS Series and the MELSEC L Series Before attempting to make a switch from MELSEC AnS Series to MELSEC L Series in your installation consult the user s manual supplied with individual module under the latter series to learn about how they differ in various aspects including performance and function Once you have opened the packaging verify that it contains the following products Product Shape Quantity Conversion Adapter 1 Mounting bracket 1 Mounting bracket fixing screws M3 5 x 6 1 Terminal block cover 1 This manual 1 2 General Specifications Item Specifications operating ambient 0 to 55 C Maximum surrounding air temperature 55 C emperature Storage ambient 25 to 75 C temp
5. follow the precautions of both levels because they are important to personal safety Please keep this manual in an easy to access location for future reference and be sure to provide the manual to the end user Precautions before using CAUTION When making a switch from the MELSEC AnS Series to the MELSEC L Series be sure to consult user s manual supplied with individual module under the MELSEC L Series to confirm differences in various aspects including performance function CPU input output signals and buffer memory addresses between the two series Installation Precautions CAUTION Use the Conversion Adapter in the environmental conditions that are specified in the general specification If the Products are used in any environment beyond the bounds of the general specification electric shock fire malfunction or damage to or degradation of the Products will result Do not directly touch any conductive parts of Conversion Adapter Contact will cause malfunction or failure in the system Fasten the Conversion Adapter and the Mounting Bracket securely with retaining screws and tighten the screws by applying torque within specified limits Loose screws can lead to the dropping of the Conversion Adapter or Mounting Bracket possibly causing breakage thereof Excessive tightness of the screws can lead to breakage of the screws Conversion Adapter Mounting Bracket or MELSEC L Series Module possibly causing the dropping shortin
6. from causes not attributable to MEE opportunity losses or lost profits incurred by the user due to Failures of MEE products damages or secondary damages arising from special circumstances whether foreseen or unforeseen by MEE compensation for accidents compensation for damages to products other than MEE products or compensation for other work carried out by the user Changes in Product Specifications The specifications given in the catalogs manuals and technical documents are subject to change without notice This document is a new publication effective September 2014 Specifications are subject to change without notice Developed September 2014 50CM D180178 B
7. achines and equipment connected to the MELSEC L Series module 4 Mounting and Installation 4 1 Handling Precautions 1 Before attempting to install the Unit or carry out the necessary wiring make certain that the external power supply used in the system is shut off on all three phases Failure to do so may result in electric shock or damage to the product 2 Do not touch live terminals There is a danger of electric shock or malfunction 3 Do not modify the Conversion Adapter or take it apart Doing so will cause failure malfunction personal injury or fire 4 Do not touch the energized part of the Conversion Adaptor directly Contact will cause malfunction or failure in the system 5 Fasten the Conversion Adapter and the Mounting bracket securely with retaining screws and tighten the screws by applying torque within specified limits Loose screws can lead to the dropping of the Conversion Adapter or Mounting bracket possibly causing breakage thereof Excessive tightness of the screws can lead to breakage of the screws Converter Adaptor Mounting bracket or MELSEC L Series Module possibly causing the dropping shorting and malfunction thereof 6 Use care to prevent foreign materials including cuttings and wiring debris from entering the Conversion Adapter or the MELSEC L Series Module These will be cause for fire failure or malfunction 7 Do not drop the Conversion Adapter and Mounting Bracket or do not give a str
8. erature Operating ambient humidit P 5 Storage ambient 5 to 95 RH non condensing humidity Constant Half Frequency acceleration amplitude Sweep count Compliant with Under 5 to 8 4Hz 3 5mm 40 times each in Vibration JIS B 3502 intermittent 2 A z resistance and vibration 8 4 to 150Hz 9 8m s a X Y Z directions IEC 61131 2 Under 5 to 8 4Hz 1 75mm continuous 2 vibration 8 4to150Hz 4 9m s Compliant with JIS B 3502 and IEC 61131 2 Shock resistance 147 m s 3 times each in 3 directions X Y Z 3 2 ERNT ASLTY50 Operating atmosphere No corrosive gases Operating altitude 1 0 to 2000m Installation location Inside a control panel Overvoltage category 2 ll or less Pollution degree 3 2 4 Do not use or store under pressure higher than the atmospheric pressure of altitude Om 2 This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within premises Category Il applies to equipment for which electrical power is supplied from fixed facilities 3 This index indicates the degree to which conductive material is generated in terms of the environme
9. g and malfunction thereof Always check for correct match between MELSEC L Series and the Conversion Adapter Incorrect match can cause damage to the MELSEC L Series Module When installing the Conversion Adapter take care not to get your hand snagged on the Mounting Bracket or the like Injury may result When installing or removing the MELSEC L Series Module complete with a Converter Adapter be sure to hold it with both hands Dropping may lead to breakage Wiring Precautions Before attempting to install the Unit or carry out the necessary wiring make certain that the external power supply used in the system is shut off on all three phases Failure to do so may result in electric shock or damage to the product After installation and wiring close the terminal block cover before turning on the module for operation Failure to do so may result in electric shock Wiring Precautions Carry out wiring for the Conversion Adapter correctly after checking the specification and terminal arrangement for the module used Connecting a power supply with a different voltage rating or incorrect wiring may cause a fire or failure Tighten the MELSEC AnS Series terminal installation screws and terminal screw securely by applying torque within the specified limits Loose screws will cause short circuit fire or malfunction Excessive tightening will damage the screws or the Conversion Adapter which in turn will cause dro
10. inafter referred to as MEE should occur within the gratis warranty period MEE shall repair the product free of charge via the distributor from whom you made your purchase I Gratis Warranty Period The gratis warranty period of this product shall be one 1 year from the date of purchase or delivery to the designated place Note that after manufacture and shipment from MEE the maximum distribution period shall be six 6 months and the gratis warranty period after manufacturing shall be limited to eighteen 18 months In addition the gratis warranty period for repaired products shall not exceed the gratis warranty period established prior to repair Gratis Warranty Range The gratis warranty range shall be limited to normal use based on the usage conditions methods and environment etc defined by the terms and precautions etc given in the instruction manual user s manual and caution labels on the product Warranty Period after Discontinuation of Production 1 MEE shall offer product repair services fee applied for seven 7 years after production of the product has been discontinued Discontinuation of production shall be reported via distributors 2 Product supply including spare parts is not possible after production has been discontinued Exclusion of Opportunity Loss and Secondary Loss from Warranty Liability Regardless of the gratis warranty period MEE shall not be liable for compensation for damages arising
11. ion Rated load voltage 12 24VDC 12 24VDC 12 24VDC Maximum load auivant 0 1A point 0 1A point 0 5A point 0 8A common 0 8A common 5A common Current is limited by the overload protection function 0 1mA or lower 0 2VDC TYP 0 5A 0 3VDC MAX 0 5A Maximum in rush current 0 4A 10ms or less 0 7A 10ms or less 0 1mA or lower 0 1VDC TYP 0 1A 0 2VDC MAX 0 1A 0 1mA or lower 1 0VDC TYP 0 1A 2 5VDC MAX 0 1A Leakage current at OFF Maximum voltage drop at ON OFF ON 2ms or less ims or less 0 5ms or less Response time ON OFF 2ms or less ms or less 1ms or less resistance load rated load resistance load rated load resistance load Surge killer Zener diode Zener diode Zener diode Fuse 1 6A one common None None non replaceable Yes Yes A Before replacement No of After replacement Conversion Conversion Adapter a A Model MELSEC AnS Series output MELSEC L Series No of Adapter Module Model points Module Model modules Weight g ERNT ASLTY50 A1SY50 16 LY40NT5P 1 75 Internal circuit diagram of ERNT ASLTY50 Terminal Signal Terminal Signal No Name No Name L TB1 Yoo TBI Yoo L TB2 Yo01 TB2 Yo01 A1SY50 L TB3 Yo2 TB3 Yo2 LY40NTSP Terminal B
12. ion Adapter 7 Before replacement No of After replacement Conversion Conversion Adapter MEL SEC AnS Series output MELSEC L Seri Adapt Model tpu eries No of japter Module Model points Module Model modules Weight g ERNT ASLTY80 A1SY80 16 LY40PT5P 1 75 Internal circuit diagram of ERNT ASLTY80 Terminal Signal Terminal Signal No Name No Name L TB1 Yoo TB1 Yoo TB2 Yo01 TB2 Yo01 A1SY80 L TB3 Y02 TB3 Yo02 LY40PT5P Terminal Block E TB4 Y03 TB4 Yo3 Terminal Block TB5 Y04 TB5 Yo04 TB1 TB2 TBI TB2 tes f L TB6 Yo05 TB6 Yo05 Ta TBS TB4 as L TB7 YO6 TB7 Yo6 786 55 ee TB7 E TB8 Yo7 TB8 Y07 TB8 e FB10189 ED TB9 COM1 TB9 Yo08 TBk tet TB10 ov B10 Yoo 1812 B73 TB13 TB14 Biase E TB11 Yo08 TB11 YOA TB16 815 meeter t L TB12 Yoo TB12 YOB TBT8 et azole L TB13 YOA TB13 YOC E TB14 YOB TB14 YOD L TB15 Yoc TB15 YOE E TB16 YoD TB16 YOF E TB17 YOE TB17 COM L TB18 YOF TB18 ov o __TB19 COM2 TB20 ov 110mm 161 3mm 51 3mmUP a Installation with the DIN rail Installation with the Base Adapter Installation with the DIN rail Remove the existing MELSEC AnS Series base unit and install the base Install the DIN rail on the control panel For how to install the DIN rail refer to the user s Precautions for wiring 1 a the switch concerned causes the number of points per common to change from 8 two circuits t
13. l modules Weight g A1SY40 ERNT ASLTY40 16 LY40NT5P 1 75 A1SY40P Internal circuit diagram of ERNT ASLTY40 Terminal Signal Terminal Signal No Name No Name L TBI Yoo TB1 Yoo 3 TB2 Yo01 TB2 Y01 A1SY40 e L TB3 Y02 TB3 Y02 LY40NT5P AISY40Pg 2 TB4 Yo3 TB4 Yos Terminal Block Terminal Block TB5 Y04 TB5 Yo4 TB1 TB2 IBI Te2 a3 E TB6 Yo05 TB6 Yo05 Ta T83 TB4 Has L TB7 Yo6 TB7 Y06 766 25 e TB7 L TB8 YO7 TB8 YO7 TBS mr mBo BS TB9 12 24VDC TBO Y08 TB 10 e741 Terre E TB10 COMI TB10 Yoo Tet T513 1B14Fg75 L TB11 Yo08 TB11 YOA TB16 1815 TB16 TB17 LaiatBt7 L TB12 Yoo TB12 YOB TB18 Tezo 59 c TB13 YOA TB13 YOC E TB14 YOB TB14 YOD E TB15 Yoc TB15 YOE L TB16 YOD TB16 YOF k TB17 YOE TB17 V TB18 YOF TB18 COM TB19 12 24VDC e TB20 COM2 Precautions for wiring oe the switch concerned causes the number of points per common to change from 8 two circuits to 16 one circuit an alteration to the wiring is required if the terminal numbers TB9 and TB19 and TB10 and TB20 on the MELSEC AnS side terminal block have been used in separation from each other lt Specification Comparison gt MELSEC AnS Series MELSEC L Series A1SY40 A1SY40P LY40NT5P Specifications Sink type Sink type Sink type No of output points 16 points 16 points 16 points Isolation method Photocoupler isolation Photocoupler isolation Photocoupler isolat
14. lock L TB4 Y03 TB4 Yo3 Terminal Block L TB5 Y04 TB5 Y04 TB1 Ter E1 Teze f L TB6 YOS TB6 YOS TB3 Te4 tes LL TB7 YO8 TB7 Yo06 Tt Tes 186 1B7 T TB8 Yo7 TBS YO7 TBS Tr TB9 TB9 12 24VDC TBO Yo08 TB10 B101T TETI B12 E TB10 COM1 TB10 Yoo apie TB13 1B14F5T5 L TB11 Yo08 TB11 YOA 7516 815 ITBT6 Mei Fel BT t L TB12 Yoo TB12 YOB TB18 rea B19 L TB13 YOA TB13 Yoc L TB14 YOB TB14 YOD L TB15 Yoc TB15 YOE L TB16 YOD TB16 YOF L TB17 YOE TB17 V L TB18 YOF TB18 COM TB19 12 24VDC e TB20 COM2 Precautions for wiring ED 2 2cause the switch concerned causes the number of points per common to change from 8 two circuits to 16 one circuit an alteration to the wiring is required if the terminal numbers TB9 and TB19 and TB10 and TB20 on the MELSEC AnS side terminal block have been used in separation from each other lt Specification Comparison gt Model MELSEC AnS Series MELSEC L Series A1SY50 LY40NT5P Specifications Sink type Sink type No of output points 16 points 16 points Isolation method Photocoupler isolation Photocoupler isolation Rated load voltage 12 24VDC 12 24VDC r 0 5A point 0 5A point Maximum load current ACAR A emon Current is limited by the overload protection function 0 1mA or lower 0 2VDC TYP 0 5A 0 3VDC MAX 0 54 Maximum in rush current 4A 10ms or less 0 1mA or lower 0 9VDC TYP 0 54 1 5VDC MAX 0 5A Leakage current at OFF
15. n Adapter Mounting bracket fixing screw M3 5 x 6 supplied with Conversion Adapter Conversion adapter installation screw M3 x 25 MELSEC AnS Series terminal block installation screw M4 MELSEC L Series System Terminal block cover supplied with Conversion Adapter adapter ERNT ASLB k For how to install the base adapter refer to the base adapter manual manual of the MELSEC L CPU module v v 1 the terminal block installation screw Terminal block Fremove the terminal block attached with the MELSEC L Series module after loosening the erminal block installation screws 1 place The MELSEC L series terminal block is not used Open the terminal cover and loosen 2 Press the terminal block fixing holes until the lower part of the terminal block is disengaged from the module and then remove the terminal block Terminal block cover Terminal block installation screw 1 serial number display area at the bottom of the MELSEC L Series module Fully insert the projections on the top of the Conversion adapter into the terminal block fixing holes Terminal block fixing holes projections Precaution i i Mounting bracket 4 nstall the Conversion Adapter to the MELSEC L Series module and secure it using the Conversion Adapter installation screws M3 x 25 1 place Serial
16. nt in which the equipment is used Pollution level 2 is when only non conductive pollution occurs A temporary conductivity caused by condensing must be expected occasionally 3 Product Specifications For detail specifications which do not appear in the specification comparison charts contained herein see the user s manual supplied with the MELSEC L Series module you use Those parts of the specification that differ between the MELSEC AnS Series and the MELSEC L Series are where a switch from the first series to the second is subjected to specification related restrictions Check the specification of the devices to be connected for more details Furthermore it is recommended to refer to the Transition from MELSEC AnS QnAS Small Type Series to L Series Handbook Fundamentals L NA 08258ENG issued by Mitsubishi Electric 3 1_ERNT ASLTY40 Before replacement No of After replacement Conversion Conversion Adapter 2 s Model MELSEC AnS Series output MELSEC L Series No of Adapter Module Model points Module Mode
17. number display J Z N Press the Conversion adapter until it snaps into place Terminal block fixing holes a Secure the mounting bracket to the MELSEC L Series module using the mounting bracket ixing screws M3 5 x 6 1 place Position the mounting bracket to the 2 Tighten the Mounting bracket fixing screw M3 5 x 6 Mounting bracket fixing screw M3 5 x6 w Tighten the Conversion Adapter installation screw M3 x 25 Conversion Adapter installation screw M3 x 25 Before tightening the installation screws check that the Conversion Adapter has been securely installed on the MELSEC L Series module Tightening the screws in floating off state or tilting state will damage the Conversion Adapter installation screws and the mounting bracket a Install the MELSEC L Series system to the base adapter DIN rail portion or the DIN rail Secure the MELSEC AnS Series terminal block to the Conversion Adapter with the supplied MELSEC AnS Series terminal block installation screw M4 2 places top and bottom a Remove the terminal block cover from the MELSEC AnS Series terminal block and fit the terminal block cover supplied with the Conversion Adaptor in place 5 2 Tightening Torque Tighten the installation screws to the specified torque below An inappropriate tightening torque could cause the product to fall or resul
18. o 16 one circuit an alteration to the wiring is required if the terminal numbers TB9 and TB19 and TB10 and TB20 on the MELSEC AnS side terminal block have been used in separation from each other lt Specification Comparison gt Model MELSEC AnS Series MELSEC L Series A1SY80 LY40PT5P Specifications Source type Source type No of output points 16 points 16 points Isolation method Photocoupler isolation Photocoupler isolation Rated load voltage 12 24VDC 12 24VDC i 0 8A point 0 5A point Maximum load current E Sanaa Current is limited by the overload protection function 0 1mA or lower 0 2VDC TYP 0 5A 0 3VDC MAX 0 5A Maximum in rush current 8A 10ms or less 0 1mA or lower 1 5VDC MAX 0 8A Leakage current at OFF Maximum voltage drop at ON OFF ON 2ms or less 0 5ms or less Resporise 2ms or less 1ms or less time ON OFF resistance load rated load resistance load Surge killer Zener diode Zener diode Fuse 5A one common None non replaceable Yes Protection function None overheat protection function overload protection function 100mA TYP all points ON 16 points 1 common 18 point terminal block 120mA TYP all points ON 8 points 1 common 20 point terminal block Internal current consumption Wiring method for common External connection system Make sure the section of the above table meets the specification of the m
19. ong impact to it This will cause damage 4 2 Use Precautions Width dimension Because the module is reduced in width dimension 34 5mm 28 5mm and of module thus in area available for wiring check dimensional data before installing the module lt MELSEC AnS Series gt lt MELSEC L Series gt Because the module is increased in depth and height dimension check dimensional data before installing the module ee MELSEC L Conversin jil Adapter Terminal block The terminal block cover for MELSEC AnS Series is bigger than the width of cover the MELSEC L Series Module Therefore it is necessary to replace it with the terminal block cover supplied with the converter adapter lt MELSEC AnS Series gt lt MELSEC L Series gt Terminal block cover for the MELSEC AnS Series Replace the terminal block cover with the one supplied with the Conversion Adapter 34 5mm 28 5mm 4 3 Installation Environment The installation environment is the same as MELSEC L series CPU Module to use Refer to the user s manual of the MELSEC L Series CPU Module to be used 5 Part Names and Installation Method Installation with the Base Adapter Base Adapter ue DIN rail portion MELSEC AnS Series terminal block Mounting bracket MELSEC L Series Supplied with Module Conversio
20. pping of parts short circuit or malfunction Use care to prevent foreign materials including cuttings and wiring debris from entering the Conversion Adapter or the MELSEC L Series Module These will be cause for fire failure or malfunction Startup and Maintenance Precautions N WARNING Do not touch live terminals There is a danger of electric shock or malfunction Shut off the external power supply for the system in all phases before cleaning or retightening the terminal screws Failure to do so may result in electric shock or cause the MELSEC L Series module to fail or malfunction Loose screws can lead to dropping shorting and malfunction Excessive tightness of the screws can lead to breakage of the screws Conversion Adapter Mounting Bracket or MELSEC L Series Module possibly causing the dropping shorting and malfunction thereof N CAUTION Do not modify the Conversion Adapter or take it apart Doing so will cause failure malfunction personal injury or fire Do not drop the Conversion Adapter and Mounting Bracket or do not give a strong impact to it This will cause damage Disposal Precautions N CAUTION When disposing of the product treat it as industrial waste EMC AND LOW VOLTAGE DIRECTIVES Compliance to the EMC Directive which is one of the EU Directives has been a legal obligation for the products sold in European countries since 1996 as well as the Low Voltage Directive since 1997
21. t in a short circuit product failure or malfunction Screw Location Tightening Torque Range Mounting bracket fixing screw M3 5x6 0 68 to 0 92N m Conversion Adapter installation screw M325 0 43 to 0 57N m MELSEC AnS Series terminal block installation screw M4 screw 0 78 to 1 18N m 6 External Dimensions Unit mm A Terminal block Conversion adapter cover Tau a J O i i a 2 E S 4 a 5 3 E E Z a Mounting bracke Z 3 Al O B L a ji i 8 E FU E 28 n iQ 5 Duplication Prohibited This manual may not be reproduced in any form in part or in whole without written permission from Mitsubishi Electric Engineering Company Limited 2014 MITSUBISHI ELECTRIC ENGINEERING COMPANY LIMITED ALL RIGHTS RESERVED MELSEC is a registered trademark of Mitsubishi Electric Corporation Product Warranty Details Please confirm the following product warranty details prior to product use Gratis Warranty Terms and Gratis Warranty Range If any fault or defect hereinafter referred to as Failure attributable to Mitsubishi Electric Engineering Company Limited here