Home
BWTTM System Installation Guide
Contents
1. 2 10 Installing Standard FTPA BWT Buffers and Transducers April 2004 is 3 ee Inserting the BWT 3 Torque the transducer to 15 to 18 ft Ib 20 to 25 N m DO NOT Transducer cont OVERTIGHTEN 4 Verify the junction box is properly oriented as discussed in the pervious section 5 Connect the transducer to the electronics and or preamplifier as described in the flowmeter s Startup or User s Manual Caution Do not place insulation on or around the transducer or junction box The transducer and junction box act as a heat sink that protects the transducer from high and low temperatures 6 After you install the FTPA Buffers and transducers you must allow the epoxy to cure for 8 hours However while the epoxy cures you should verify the transducer and buffer are working properly as described below Caution While the epoxy cures do not remove re torque or adjust the transducer or you will crack the epoxy 7 Repeat the above steps for the other transducer Verifying Installation 1 Power up the electronics 2 Refer to Displaying Diagnostics in the flowmeter s Service or User s Manual to display the up and down
2. 2 Using an adjustable wrench turn the first nut 1 8 turn Turn first nut 1 8 turn 4 Hole Flange 8 Hole Flange 2 6 Installing Standard FTPA BWT Buffers and Transducers April 2004 XT Torquing the Studs 3 Turn the second nut 1 8 turn The second stud should be cont diametrically opposite the first stud Proceed to tighten the remaining studs in the order shown below or in a similar manner Turn second nut 1 8 turn 4 Hole Flange 8 Hole Flange 4 Turn each nut an additional 1 8 turn TURN NUTS IN SEQUENCE 5 Use Table 2 1 below to determine the appropriate torque Table 2 1 Recommended Torque using Kamprofile Gaskets Stud Stud Rating Diameter Torque 4 Studs in ft Ib Flange Rating Flange x Length in N m 316 Stainless Steel 1 1 2 ANSI 150 B8M C 1 1 2 x 3 1 4 56 76 1 1 2 ANSI 300 B8M C 1 3 4 x 4 3 4 82 111 1 1 2 ANSI 600 B8M C 1 3 4 x 4 3 4 82 111 1 1 2 ANSI 900 B8M C 1 1 x6 107 145 1 1 2 ANST 1500 B M C 1 1 x 6 107 145 Carbon Steel 1 1 2 ANSI 150 B7 1 2 x 3 1 4 56 76 1 1 2 ANSI 300 B7 3 4 x 4 3 4 82 111 1 1 2 ANSI 600 B7 3 4 x 4 3 4 82 111 1 1 2 ANSI 900 B7 1 x6 107 145 1 1 2 ANSI 1500 B7 1 x 6 107 145 Installing Standard FTPA BWT Buffers and Transducers 2 7
3. ic la Stud Quality Rating Side View 2 4 Installing Standard FTPA BWT Buffers and Transducers April 2004 Inserting the Standard 5 Install the remaining studs in the order shown below but do not FTPA Buffer cont tighten the nuts yet 4 Hole Flange 8 Hole Flange 6 Center the buffer in the middle of the lap joint flange Feel 360 degrees around the flanges to ensure equal spacing by placing your hands around the diameter of the buffer flange and the nozzle flange 7 Align the flanges as shown below IMPORTANT Make sure the gasket is in the center of the flanges Proper Gasket Alignment End View End View 8 Tighten the nuts and studs further by hand to maintain the centering Visually inspect that the buffer is centered in the lap joint flange if necessary adjust the buffer by hand until it is centered Installing Standard FTPA BWT Buffers and Transducers 2 5 April 2004 Torquing the Studs It is important to torque the studs properly for a good seal However you should not over torque them so as to cause an acoustic short or change the transducer alignment The studs must be tightened and torqued in stages as described below 1 Check the flange and buffer alignment again Make sure the flanges are consistently parallel to each other
4. 4 4 Installing Non Flanged FSPA FWPA BWT Buffers and Transducers April 2004 i Verifying Installation 1 Power up the electronics 2 Refer to Displaying Diagnostics in the flowmeter s Service or User s Manual to display the up and down signal strength 3 Record this data in the Service Record in the back of the flowmeter s Service or User s Manual 4 Verify that the signal strength diagnostics are the same or better after 8 hours This completes the installation of the FSPA FWPA buffers and transducers Refer to the flowmeter s Startup or User s Manual for instructions on obtaining flow rate measurements Installing Non Flanged FSPA FWPA BWT Buffers and Transducers 4 5 Chapter 5 Specifications April 2004 Specifications Table 5 1 BWT Transducer Specifications Transducer BWT for Liquids BWT for Gases Designation Hazardous area applications high temperature and high pres sure applications petrochemical industry High temperature and high pres sure applications superheated steam Installation Type Wetted removable under pressure Material Standard 316LSS Optional Titanium Field Mounting Meter Body cold tap Process Connection 1 5 flanged standard 1 NPT 1 socket weld 1 5 flanged standard Holder Type FTPA FIPA FSPA FWPA Holder Ratings 150 300 600 900 1500 and 2500 Lapjoint Operating Fr
5. GE Panametrics BWT System Installation Guide April 2004 Process Control Instruments BWT System Installation Guide 916 058B GE Panametrics April 2004 Table of Contents Chapter 1 General Information Introduction ote ese een oN aed et vens ou e Ga ae eS eigenen 1 1 Types of BWT Butters iii s ces ese eR ee I Bun e oe e was le 1 1 General Guidelines for Transducer Position and Location 1 2 BWT Met r Body 1 mta hese kee DE CREUSE AREE La UNE qued ed 1 3 Single Traverse Meter Body 1 3 Double Traverse Meter Body 1 4 Handling and Installing a Meter Body 1 5 Unpacking a Meter Body 1 5 Installing a Meter Body 1 5 Welding Requirements sms Danses Mate ATIG ne 1 6 Meter Body Requirements When Flushing 1 7 Chapter 2 Installing Standard FTPA BWT Buffers and Transducers Introduction iex ies ae an heed Ode Lei hea ede ee 2 1 Identifying and Checking Components 2 1 Assembling the Standard FTPA Buffer 2 3 Inserting the Standard FTPA Buffer 2 4 Torquing the St dsz cc
6. da sie in bereinstimmung mit Artikel 3 Absatz 3 gute Ingenieurpraxis der Druckger te Richtlinie 97 23 EG f r DN lt 25 geliefert werden Shannon July 1 2003 pu hab Mr James Gibson GENERALDIREKTOR NSAI x i U H C LS EN ISO 9002 UV ESSEN Shannon ISO 9001 U S CERT DOC Rev G1 5 28 02 GE Panametrics We GE Panametrics 221 Crescent Street Suite 1 Waltham MA 02453 U S A as the manufacturer declare under our sole responsibility that the product Type BWT Ultrasonic Flow Transducer to which this document relates in accordance with the provisions of ATEX Directive 94 9 EC Annex II meets the following specifications CE ua e 1180 KEMA01ATEX2051X 40 C to 70 C 200 Vpp 5 mA Furthermore the following additional requirements and specifications apply to the product Having been designed in accordance with EN 50014 and EN 50018 the product meets the fault tolerance requirements of electrical apparatus for category d The product is an electrical apparatus and must be installed in the hazardous area in accordance with the requirements of the EC Type Examination Certificate The installation must be carried out in accordance with all appropriate international national and local standard codes and practices and site regulations for flameproof apparatus and in accordance with the instructions contained in the manual Access to the circuitry must not be made during operation Only tra
7. 5 pipe diameters of straight undisturbed flow downstream from the point of measurement The more straight run available the better Undisturbed flow means avoiding sources of turbulence such as valves flanges and elbows You should also avoid swirl cross flow and cavitation in liquids It is important to locate the transducers on a horizontal plane This specifically applies to mounting transducers on a horizontal pipe One transducer cannot be on top of the pipe and one on the bottom because the top of the pipe tends to accumulate gas in liquids and the bottom tends to accumulate sediment in gas and liquids These contaminants can attenuate or block the ultrasonic signal There is no similar restriction with vertical pipes However in liquid applications you should avoid vertical downward flow to ensure a full pipe 1 2 General Information April 2004 BWT Meter Body Single Traverse Meter Body BWT installations typically use a tilted diameter meter body A tilted diameter meter body is so named because the transducers send their pulses at an angle across the diameter of the pipe This type of meter body can be configured as a single traverse or double traverse installation Note The mounting angle for the transducer is typically 45 but other angles 20 30 or 60 can be used as required Tilted diameter can also refer to paths that are off diameter such as the mid radius path A meter body is cr
8. April 2004 Torquing the Studs cont You must torque the flange studs in small increments Divide the appropriate torque by 10 to determine the number of steps For example if the appropriate torque is 90 ft lb the steps would be 20 30 40 50 60 70 80 and 90 ft lb Set the torque wrench for the first setting and torque the studs in sequence Turn each stud a maximum of a 1 8 turn at a time Repeat Step 7 for each torque setting Check the flange alignment again to ensure that the flanges are parallel to each other Measure the spacing between the flanges with the caliper on at least four equally distant points the maximum tolerance is 0 2 mm difference between the four points If you cannot achieve a tolerance of 0 2 mm or less replace the gasket with a new gasket and repeat the entire procedure 10 Repeat the above steps for the remaining flanges 2 8 Installing Standard FTPA BWT Buffers and Transducers April 2004 Installing the BWT Installing the BWT transducers into the FTPA Buffer requires three Transducer steps Installing and Orienting the Junction Box Inserting the BWT transducers Verifying Installation Installing and Orienting Before placing the BWT transducer into the FTPA Buffer the Junction Box permanently you must
9. and Installing a Meter Body 1 5 Welding Requirements 1 6 Meter Body Requirements When Flushing 1 7 April 2004 Introduction Types of BWT Buffers Installing the BWT System consists of creating a meter body installing the transducer buffer and then mounting transducers into the buffer GE Panametrics offers a variety of buffers and meter bodies for liquid and gas applications This section consists of general information for the following Types of BWT Buffers General Guidelines for Transducer Position and Location BWT Meter Body Handling and Installing a Meter Body Welding Requirements Meter Body Requirements When Flushing Refer to the appropriate section of this manual to install the BWT buffers and transducers that you ordered Buffers are used to protect the BWT transducers from temperature extremes Since they mount directly into the pipe coupling or nozzle they also act as barriers against the process making it possible for the transducers to be removed without interrupting the process or emptying the pipe There are three BWT buffer types available for transducers for liquid and gas applications Standard BWT Buffer part number FTPA is used for liquid and gas applications The buffer has a flanged process connection and is available in two lengths 2 in temperatures up to 600 F 315 C and 6 in temperatures up
10. be either flanged or welded into the existing pipeline Use the following steps to position the meter body into the pipeline refer to Figure 1 4 on the next page IWARNING Before installing the meter body make sure pipe flushing is completed For additional information when flushing is necessary refer to Meter Body Requirements When Flushing on page 1 7 1 Find the tag plate with the words TOP and FLOW DIRECTION marked on it If the meter body is flanged two bolt holes should straddle the vertical centerline IMPORTANT In general including cases where the meter body axis is not horizontal be sure that the installation does not allow gas or sediment to deposit in the transducer ports Otherwise the sound waves could be attenuated or blocked entirely General Information 1 5 April 2004 Installing a Meter Body cont Welding Requirements 2 Place the meter body in the pipeline so that the FLOW DIRECTION arrow mark is in the direction of flow and the top is appropriately located Be sure the transducer ports are in a horizontal plane IMPORTANT f you cannot place the meter body in the required orientation consult the factory otherwise operational problems may occur 3 Do one of the following Bolt the meter body into place and proceed to the appropriate section that follows to mount the BWT buffers and transducers Weld the meter body into place in accordance with the requirements described
11. have centered the buffer tighten the studs further by hand to maintain the centering Visually inspect that the buffer is centered in the lap joint flange if necessary adjust the buffer by hand until it is centered 3 6 Installing Acoustic Isolation FIPA BWT Buffers and Transducers April 2004 71 Torquing the Studs You must torque the studs to give a good seal However you should not over torque them so as to cause an acoustic short or change the transducer alignment The nuts must be tightened and torqued in stages as described below 1 Check the flange and buffer alignment again Make sure the flanges are consistently parallel to each other Bad Alignment Unequal Distances lt A X S x Top View Proper Alignment Equal Distances A XP lt 2 WGN Top View Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 7 April 2004 Torquing the Studs 2 Using an adjustable wrench turn the first nut 1 8 turn cont Turn first nut 1 8 turn 4 Hole Flange 8 Hole Flange 3 Turn the second nut 1 8 turn The second stud should be diametrically opposite the first stud Proceed to turn the remaining studs in the order shown below or in a similar manner Turn second nut 1 8 turn 4 Hole Flange 8 Hole Flange 4 Turn each nut an additional 1 8 turn TURN NUTS IN SEQUENCE 3 8 Installing Acoustic Isolation FIPA BWT Buffers and Transducers April 2004 ee B EN To
12. provide necessary acoustic isolation 2 Mating lap joint flanges 2 Junction boxes Preamplifier s for gas application only 3M epoxy or equivalent for permanent bond not shown in photo Required studs nuts and washers not shown in photo 10 ft 3 m Coaxial cable with BNC connectors not shown in photo Additional cable to connect preamplifier to electronics for gas only not shown in photo Installing Standard FTPA BWT Buffers and Transducers 2 1 April 2004 Identifying and You will need to supply the following Checking Components cont Copperslip SS316 Molykote grease P47 CS or equivalent anti seizing compound Adjustable torque wrench with 15 148 ft Ib range 20 200 N m with socket drive standard and deep sockets adjustable wrench 12 in handle or equivalent Steel wool Calipers Figure 2 1 Components for FTPA Buffer Kamprofile with Metal Centering Ring Typical Kamprofile without Metal Centering Ring Figure 2 2 Gaskets 2 2 Installing Standard FTPA BWT Buffers and Transducers April 2004 Assembling the Standard FTPA Buffer Note Ifthe BWT system is shipped with the buffers already installed 1 in the nozzles proceed to Installing the BWT Transducer on page 2 9 Slide the lap joint flange over the threaded end of the FTPA Buffer Make sure you orient the flange as shown below Lap Joint Flange FTPA Buffer Raise
13. that you follow the instructions outlined in this document If you do not GE Panametrics cannot ensure the proper operation of your equipment Before you install the BWT transducers you should make sure you have all the needed equipment Use the list below to identify the needed components GE Panametrics will supply you with the following see Figures 3 1 and 3 2 on the next page to help you identify each component Note The list below is for a one path installation 2 Acoustic Isolation FIPA Buffers fully assembled 2 BWTI transducers 2 Kamprofile gaskets IMPORTANT Kamprofile gaskets must be used for two reasons they ensure a leak tight seal and they provide sufficient acoustic isolation 2 Junction boxes Preamplifier s for gas application only e 3M epoxy or equivalent for permanent bond not shown in photo Required studs nuts and washers not shown in photo 10 ft 3 m Coaxial cable with BNC connectors not shown in photo Additional cable to connect preamplifier to electronics for gas only not shown in photo Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 1 April 2004 ees Identifying and You will need to supply the following Checking Components cont Copperslip SS316 Molykote grease P47 CS or equivalent anti seizing compound Adjustable torque wrench with 15 148 ft lb range 20 200 N m with socket drive standard and deep sockets adjus
14. the pipe nozzle face and inside if cont necessary Inspect Pipe Nozzle 5 Insert the buffer gasket assembly into the nozzle Top View Top View 3 4 Installing Acoustic Isolation FIPA BWT Buffers and Transducers April 2004 Inserting the Acoustic 6 Apply Copperslip Molykote or equivalent anti seize compound Isolation FIPA Buffer on the first several threads at both ends each stud cont 7 Insert one stud through the flanges Make sure the stud quality rating e g B7 is facing away from the meter body Hand tighten a washer and nut on to each end of the stud Make sure you leave an equal number of threads exposed on each end of the stud Caution Do not adjust the studs on the FIPA isolation flange The isolation flange is already set to specification determined at the factory Stud Quality Rating Equal Amount of Threads Top View Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 5 April 2004 Inserting the Acoustic 8 Install the remaining stud in the order shown below but do not Isolation FIPA Buffer tighten the nuts yet cont 4 Hole Flange 8 Hole Flange 9 Run your hands around the diameter of the buffer flange and nozzle flange to ensure equal spacing 10 Then align the flanges as shown below IMPORTANT Make sure the gasket is in the center of the flanges Proper Gasket Alignment End View End View 11 Once you
15. to 1 1009F 6009C Acoustic Isolation BWT Buffer part number FIPA is used for gas applications at lower pressures The buffer has a flanged isolation section that reduces acoustic short circuit The outer buffer has a flanged process connection and is available in two lengths 2 in temperatures up to 600 F 315 C and 6 in temperatures up to 1 100 F 600 C General Information 1 1 April 2004 Types of BWT Buffers cont General Guidelines for Transducer Position and Location Non Flanged BWT Buffer part number FSPA is used in liquid applications and has a 1 in NPT thread Socket Weld BWT Buffer part number FWPA is used in liquid applications and has a 1 in coupling that is welded into the pipe coupling Whichever transducer type is selected for your installation flowmeter accuracy depends on proper transducer location spacing alignment and electronics programming However even though every transducer installation has specific location considerations the following location guidelines apply to all transducers regardless of type Caution A flowmeter s accuracy and performance depends on the location spacing and alignment of the transducers The specific spacing of your transducers are unique to your installation 1 To help assure a uniform flow profile locate the buffers so that there are at least 10 pipe diameters of straight undisturbed flow upstream and
16. Sana Pia RG RR iR eme GEO LG acd asada 2 6 Installing the BWT Transducer 2 9 Installing and Orienting the Junction Box 2 9 Inserting the BWT Transducer 2 10 Verifying Installation see La 222124 EUER Suge GOES RG O dan ELA EO Meine 2 11 Chapter 3 Installing Acoustic Isolation FIPA BWT Buffers and Transducers Introduction oce e CR PDC ie b t iot 3 1 Identifying and Checking Components 3 1 Inserting the Acoustic Isolation FIPA Buffer 3 3 Torquing the Studs 13 44 eue uem de e ade 3 7 Installing the BWT Transducer 3 11 Installing the Orienting the Junction Box 3 11 Inserting the BWT Transducer 3 12 Verifying Installation mio mersis gets be Ged tas Yee a Ba he ee ua 3 14 Installing Additional Acoustic Isolation 3 15 Chapter 4 Installing Non Flanged FSPA FWPA BWT Buffers and Transducers Installing Non Flanged FSPA FWPA BWT Buffers and Transducers 4 1 Installing the FSPA FWPA Buffer 4 2 Installing and Orienting the Junction Box 4 3 Inserting the BWT Tr
17. T KEMAOIATEX2051 X KEMA Ultrechtseweg 310 Arnhem The Netherlands e EN 61326 1998 Class A Annex A Continuous Unmonitored Operation following the provisions of the 89 336 EEC EMC Directive and the 94 9 EC ATEX Directive The units listed above and any ancillary sample handling systems supplied with them do not bear CE marking for the Pressure Equipment Directive as they are supplied in accordance with Article 3 Section 3 sound engineering practices and codes of good workmanship of the Pressure Equipment Directive 97 23 EC for DN 25 Shannon July 1 2003 pu hak Mr James Gibson GENERAL MANAGER NSAI x i U H C LS ENISO9002 V ESSEN Shannon ISO 9001 U S CERT DOC Rev G1 5 28 02 GE Panametrics DECLARATION CONFORMITE GE Panametrics Shannon Industrial Estate Shannon Co Clare Ireland d clarons sous notre propre responsabilit que les T5 Ultrasonic Flow Transducer T8 Ultrasonic Flow Transducer T11 Ultrasonic Flow Transducer BWT Ultrasonic Flow Transducer r latif cette d claration sont en conformit avec les documents suivants EN 50014 1997 A 1 A2 1999 EN 50018 2000 II 2 G EEx d HC T6 T5 KEMA01ATEX2045 X T8 KEMAO2ATEX2283 X T11 KEMAO2ATEX2252 BWT KEMAOIATEX2051 X KEMA Ultrechtseweg 310 Arnhem The Netherlands EN 61326 1998 Class A Annex A Continuous Unmonitored Operation suivant les r gles de la Directive de Compatibilit Electromagn tique 89 336 EEC
18. and Orienting the Junction Box Before placing the BWT transducer into the FSPA FWPA Buffer permanently you must make sure the preamplifier junction box will be properly oriented once installed Note The following drawings show the FSPA Buffer only 1 Screw the transducer into the junction box as shown below 2 Screw the transducer junction box assembly into the FSPA FWPA Buffer 3 Check the junction box orientation The junction box lid should be at a downward angle so water can drain If it is not adjust the junction box until it does 4 Remove the transducer junction box assembly 5 Repeat the above steps for the other transducer Installing Non Flanged FSPA FWPA BWT Buffers and Transducers 4 3 April 2004 EEG Inserting the BWT IWARNING Transducers Follow all applicable safety codes and safety procedures when installing or removing the plugs 1 Apply the epoxy couplant 2 mm in diameter to the flat face of the BWT transducer and screw it into the buffer picture below does not show the junction box 2 Hand tighten transducers then torque it to a maximum of 15 ft lb 20 N m 3 Check the junction box orientation The junction box lid should be at a downward angle so water can drain If it is not adjust the junction box until it does 4 Connect the transducer to the preamplifier and electronics as described in the flowmeter s Startup or User s Manual
19. ansducers 4 4 Verifying Installation 2 4 5 Chapter 5 Specifications Specifications 5s LEAL Pe P e aos bo du gn debba bee d Fats 5 1 lii April 2004 Warranty Return Policy Each instrument manufactured by GE Panametrics is warranted to be free from defects in material and workmanship Liability under this warranty is limited to restoring the instrument to normal operation or replacing the instrument at the sole discretion of GE Panametrics Fuses and batteries are specifically excluded from any liability This warranty is effective from the date of delivery to the original purchaser If GE Panametrics determines that the equipment was defective the warranty period is one year for general electronic failures of the instrument one year for mechanical failures of the sensor If GE Panametrics determines that the equipment was damaged by misuse improper installation the use of unauthorized replacement parts or operating conditions outside the guidelines specified by GE Panametrics the repairs are not covered under this warranty The warranties set forth herein are exclusive and are in lieu of all other warranties whether statutory express or implied including warranties or merchantability and fitness for a particular purpose and warranties arising from course of dealing or usage or trade If a GE Panametrics instrum
20. at the above steps for the other transducer Inserting the BWT Please read the following steps before installing the BWT transducer Transducer IMPORTANT After you install the BWT Buffer and transducers you must allow the epoxy to cure for eight hours Note In gas applications the typical minimum pressure should be 5 barg 75 psig to see a signal at all A higher pressure will give a better signal to noise ratio 1 Place a small droplet 2 mm in diameter of 3M Epoxy or equivalent on the center of the end of the transducer picture below does not show the junction box 3 12 Installing Acoustic Isolation FIPA BWT Buffers and Transducers April 2004 Inserting the BWT 2 Screw the transducer junction box into the receptacle fitting at Transducer cont the end of the buffer When the transducer begins to feel tight stop turning it Wait for 5 seconds to give the couplant a chance to spread out BWT Transducer Junction Box Zo Top View 3 Torque the transducer to 15 to 18 ft lb 20 to 25 N m DO NOT OVERTIGHTEN 4 Verify the junction box is properly oriented as discussed in the previous section 5 Connect the transducer to the electronics and or preamplifier as described in the flowmeter s Startup or User s Manual Caution Do not place insulation on or around the transducer or junction box The transducer and junction box act as a heat sink that protects the transducer from high and low temperatu
21. d Edge SS Side View Side View Check the raised face of the spool nozzle flange to make sure it is free from paint rust dirt corrosion and damage If necessary clean the raised faces with steel wool In addition clean the buffer flange if you are reusing the buffer Inspect the GE Panametrics supplied gaskets They must not be used warped pitted or scratched Place one gasket on the end of the buffer assembly Gasket Side View Installing Standard FTPA BWT Buffers and Transducers 2 8 April 2004 Inserting the Standard 1 FTPA Buffer Inspect the pipe nozzle Make sure it is free from dirt rust Use the steel wool to clean the pipe nozzle face and inside if necessary Insert the buffer assembly into the nozzle Nozzle Side View Side View Apply Copperslip Molykote or equivalent anti seize compound on the first several threads at both ends each stud Insert one stud through the flanges Make sure the stud quality rating e g B7 is facing away from the meter body Hand tighten a washer and nut on to each end of the stud Make sure you leave an equal number of threads exposed on each end of the stud E Side View Equal Amount of Threads
22. eated by mounting the nozzles on the existing pipeline or on a meter body A meter body is a precision manufactured section of matching pipe that contains the ports where the transducer buffers will be mounted This setup allows more accurate transducer alignment before mounting the meter body into the pipeline If requested a meter body can be calibrated prior to shipment All meter bodies are factory supplied A single traverse configuration consists of two transducers mounted on opposite sides of the pipe so that the signal they transmit passes through the fluid just once at a typical 45 angle Figure 1 1 below A single traverse configuration may include more than one path Figure 1 2 on the next page Top View End View Figure 1 1 Single Traverse 2 Path Diagonal 45 Meter Body General Information 1 3 April 2004 Single Traverse Meter Body cont SECTION A A Figure 1 2 Single Traverse 2 Path Mid Radius Meter Body Double Traverse Meter A double traverse configuration consists of two transducers mounted Body on the pipe so that the signal traverses the fluid two times before reaching the other transducer See Figure 1 3 below P Distance that the signal travels through the liquid from one transducer to the other L Projected distance of acoustical path in liquid Figu
23. ent malfunctions within the warranty period the following procedure must be completed 1 Notify GE Panametrics giving full details of the problem and provide the model number and serial number of the instrument If the nature of the problem indicates the need for factory service GE Panametrics will issue a RETURN AUTHORIZATION NUMBER RAN and shipping instructions for the return of the instrument to a service center will be provided 2 If GE Panametrics instructs you to send your instrument to a service center it must be shipped prepaid to the authorized repair station indicated in the shipping instructions 3 Upon receipt GE Panametrics will evaluate the instrument to determine the cause of the malfunction Then one of the following courses of action will then be taken Ifthe damage is covered under the terms of the warranty the instrument will be repaired at no cost to the owner and returned If GE Panametrics determines that the damage is not covered under the terms of the warranty or if the warranty has expired an estimate for the cost of the repairs at standard rates will be provided Upon receipt of the owner s approval to proceed the instrument will be repaired and returned Chapter 1 General Information IHTOAUCHON se eee are d rasa kr a 1 1 Types of BWT Buffers names do arc aaa 1 1 General Guidelines for Transducer Position and Location 1 2 BWT Meter Body i su ere ree xxn nn 1 3 Handling
24. equency 0 5 MHz Standard 200 kHz Optional 500 kHz Pressure Range 100 to 3480 psig 2500 flange 100 to 3480 psig 2500 flange Contact factory for minimum pressure Electrical Rating 200 V peak to peak 5 mA Ambient Temperature North America 20 to 60 C 4 to 140 F Range Europe 40 to 70 C 40 to 158 F Process Temperature Standard 190 to 300 C 310 to 572 F Range Optional 190 to 600 C 310 to 1112 F Note Mechanical buffer assembly not transducer is exposed to process temperatures North American Certification Explosion proof Class I Division 1 Group C D C US European Certification Flameproof Il 2 G EEx d IIC T6 80 C Tam 40 to 75 C 40 to 167 F KEMA 01ATEX2051X North American Certification Weatherproof IP66 TYPE 4X SB 200Vpp 5mA European Certification Weatherproof C US IP alu Specifications GE Panametrics aia TON CONFORMITY GE Panametrics Shannon Industrial Estate Shannon Co Clare Ireland declare under our sole responsibility that the T5 Ultrasonic Flow Transducer T8 Ultrasonic Flow Transducer T11 Ultrasonic Flow Transducer BWT Ultrasonic Flow Transducer to which this declaration relates are in conformity with the following standards EN 50014 1997 A 1 A2 1999 EN 50018 2000 II 2 G EEx d HC T6 T5 KEMA01ATEX2045 X T8 KEMAO2ATEX2283 X T11 KEMAO2ATEX2252 BW
25. et d ATEX 94 9 EC Les mat riels list s ci dessus ainsi que les syst mes d chantillonnages pouvant tre livr s avec ne portent pas le marquage CE de la directive des quipements sous pression car ils sont fournis en accord avec la directive 97 23 EC des quipements sous pression pour les DN lt 25 Article 3 section 3 qui concerne les pratiques et les codes de bonne fabrication pour l ing nierie du son Shannon July 1 2003 pu hab Mr James Gibson DIRECTEUR GENERAL NSAI LS EN ISO 9002 V ESSEN Shannon ISO 9001 U S CERT DOC Rev G1 5 28 02 GE Panametrics KONFORMITATS ERKLARUNG GE Panametrics Shannon Industrial Estate Shannon Co Clare Ireland erkl ren in alleiniger Verantwortung da die Produkte T5 Ultrasonic Flow Transducer T8 Ultrasonic Flow Transducer T11 Ultrasonic Flow Transducer BWT Ultrasonic Flow Transducer folgende Normen erf llen EN 50014 1997 A 1 A2 1999 EN 50018 2000 II 2 G EEx d IIC T6 T5 KEMAOI ATEX2045 X T8 KEMAO2ATEX2283 X T11 KEMAO2ATEX2252 BWT KEMAOIATEX2051 X KEMA Ultrechtseweg 310 Arnhem The Netherlands EN 61326 1998 Class A Annex A Continuous Unmonitored Operation gem den Europ ischen Richtlinien Niederspannungsrichtlinie EMV Richtlinie Nr 89 336 EG und ATEX Richtlinie Nr 94 9 EG Die oben aufgef hrten Ger te und zugeh rige mitgelieferte Handhabungssysteme tragen keine CE Kennzeichnung gem der Druckger te Richtlinie
26. in Welding Requirements below Once welding is completed proceed to the appropriate section that follows to mount the BWT buffers and transducers Bolt holes straddle centerline symmetrically Top View End View Figure 1 4 Top View of a Flanged Meter Body Prior to welding do the following Remove power from the flowmeter console and disconnect the cables from the transducers Make sure the inside diameter of the meter body and process pipe are properly aligned Misalignment can affect measurement accuracy 1 6 General Information April 2004 Meter Body Requirements When Flushing GE Panametrics strongly recommends using a dummy meter body during flushing operations otherwise damage may occur for the following reasons Fast moving solid objects in the flowing medium could damage the buffer faces Flushing residue sediment could clog nozzles In the event that a dummy meter body is not available for flushing operations remove the buffers and plug the holes properly for the temperature and pressure used Blind flanges are typically used Reinstall the buffers and transducers after flushing using the information in this guide Caution Be sure to use new gaskets when reinstalling buffers Never reuse gaskets for safety reasons and acoustic performance of the flowmeter General Information 1 7 Chapter 2 Installing Standard FTPA BWT Buffers and Transduce
27. ined competent personnel may install operate and maintain the equipment The product has been designed so that the protection afforded will not be reduced due to the effects of corrosion of materials electrical conductivity impact strength aging resistance or the effects of temperature variations The product cannot be repaired by the user it must be replaced by an equivalent certified product Repairs should only be carried out by the manufacturer or by an approved repairer The product must not be subjected to mechanical or thermal stresses in excess of those permitted in the certification documentation and the instruction manual The product contains no exposed parts which produce surface temperature infrared electromagnetic ionizing or non electrical dangers The product is provided with a 1 NPT male thread For electrical connection the product must be mounted in a certified metal enclosure of flameproof protection type d the assembly complying with the requirements of EN50018 Measures must be taken to ensure a good bonding connection and to prevent the connection from self loosening CE 2 CERT ATEX C 7 16 03 USA GE Panametrics 221 Crescent Street Suite 1 Waltham MA 02453 3497 Telephone 781 899 2719 Toll free 800 833 9438 Fax 781 894 8582 E Mail panametrics ps ge com Web www gepower com panametrics Ireland GE Panametrics Shannon Industrial Estate Shannon County Clare I
28. iper on at least four equally distant points the maximum tolerance is 0 2 mm difference between the four points If you cannot achieve tolerance of 0 2 mm or less replace the gasket with a new gasket and repeat the entire procedure we Improper Gasket Alignment Proper Flange Alignment Top View 10 Repeat the above steps for the remaining flanges 3 10 Installing Acoustic Isolation FIPA BWT Buffers and Transducers April 2004 ee Installing the BWT Installing the BWT transducers into the FIPA Buffer requires three Transducer steps Installing and Orienting the Junction Box Inserting the BWT transducers Verifying Installation Installing the Orienting Before placing the BWT transducer into the FIPA Buffer the Junction Box permanently you must make sure the junction box will be properly oriented once installed 1 Screw the transducer into the junction box as shown below 2 Screw the transducer junction box assembly into the FIPA Buffer BWT Transducer Junction Box Top View Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 11 April 2004 Installing the Orienting 3 Check the junction box orientation The junction box lid should be the Junction Box cont at a downward angle so water can drain If it is not adjust the junction box until it does 4 Remove the transducer junction box assembly 5 Repe
29. make sure the junction box will be properly oriented once installed 1 Screw the transducer into the junction box as shown below 3 Check the junction box orientation The junction box lid should be at a downward angle so water can drain If it is not adjust the junction box until it does 4 Remove the transducer junction box assembly 5 Repeat the above steps for the other transducer Installing Standard FTPA BWT Buffers and Transducers 2 9 April 2004 ees Inserting the BWT Please read the following steps before installing the BWT transducer Transducer IMPORTANT After you install the BWT transducers you must allow the epoxy to cure for eight hours Note Jn gas applications the typical minimum pressure should be 5 barg 75 psig to see a signal at all A higher pressure should give a better signal to noise ratio 1 Place a small droplet 2 mm in diameter of 3M Epoxy or equivalent on the center of the end of the transducer picture below does not show the junction box 2 Screw the transducer junction box into the receptacle fitting at the end of the FTPA Buffer When the transducer begins to feel tight stop turning it Wait for 5 seconds to give the couplant a chance to spread out
30. rawing below to properly set the rods When adjusting the rods make sure you pay attention to how the collets will be positioned on the buffer i e how the collets will face each other Side View 2 Use an Allen wrench to separate the two pieces of the collet so that it can be placed on the buffer Repeat for the other collet s Be sure not to mix pieces from different fixtures Loosen Using Allen Wrench Front View Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 15 April 2004 Installing Additional 3 Place the collet s on the buffer as shown below Acoustic Isolation cont Top View 4 Repeat the above steps for the other transducer You have completed the installation Refer to the flowmeter s Startup or User s Manual for instructions on operation 3 16 Installing Acoustic Isolation FIPA BWT Buffers and Transducers Chapter 4 Installing Non Flanged FSPA FWPA BWT Buffers and Transducers Installing Non Flanged FSPA FWPA BWT Buffers and Transducers 4 1 April 2004 Installing Non Flanged The Non Flanged FSPA FWPA Buffer is a pipe plug and coupling FSPA FWPA BWT assembly made of stainless steel or ti
31. re 1 3 Double Traverse Meter Body General Information April 2004 Handling and Installing a Meter Body Unpacking a Meter Body Installing a Meter Body To ensure proper nozzle alignment GE Panametrics uses the highest quality welding and machining techniques when manufacturing meter bodies Since proper alignment of the nozzles is important to making accurate flow measurement great care must be taken when unpacking and installing the meter body Upon receipt you should take great care in unpacking the meter body Although meter bodies are constructed of steel improper unpacking or handling can result in damage or affect nozzle alignment Use the guidelines below for unpacking the meter body Since the nozzles protrude from the pipe take care when removing packing material and the meter body from its shipping container so as not to disturb the nozzles After the meter body is removed from its shipping container never allow the full weight of the meter body to rest on the nozzle or buffer You should prop up the meter body to prevent it from rolling over which again may cause damage or misalignment of nozzles Do not let the meter body hit against other objects or surfaces Nozzle alignment can be affected if the meter body is dropped onto sand or the ground If the meter body is shipped with the buffers already installed in the nozzles take care as to not disturb the buffers when unpacking Meter bodies can
32. reland Telephone 353 61 470200 Fax 353 6 1 471359 E Mail info panametrics ie
33. res 6 After you install the FTPA Buffers and transducers you must allow the epoxy to cure for 8 hours However while the epoxy cures you should verify the transducer and buffer are working properly as described below Caution While the epoxy cures do not remove re torque or adjust the transducer or you will crack the epoxy 7 Repeat the above steps for the other transducer Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 13 April 2004 ees Verifying Installation 1 Power up the electronics 2 Refer to Displaying Diagnostics in the flowmeter s Service or User s Manual to display the up and down signal strength 3 Record this data in the Service Record in the back of the flowmeter s Service or User s Manual 4 Verify that the signal strength diagnostics are the same or better after 8 hours This completes the installation of the FIPA buffers and transducers Refer to the flowmeter s Startup or User s Manual for instructions on obtaining flow rate measurements 3 14 Installing Acoustic Isolation FIPA BWT Buffers and Transducers April 2004 Installing Additional If your application requires additional acoustic isolation you will Acoustic Isolation need the following to perform this procedure e 1 to 3 ring collets for 4 in pipes or larger Allen wrench 1 If you are using more than one collet adjust the spacing rods on each pipe riser fixture to 1 in 25 mm Use the d
34. rquing the Studs 5 Use Table 3 1 below to determine the appropriate torque cont Table 3 1 Recommended Torque using Kamprofile Gaskets Stud Diameter Stud Rating in Torque 4 Studs x Length ft Ib Flange Rating Flange in N m 316 Stainless Steel 1 1 2 ANSI 1508 B8M C 1 1 2 x 3 1 4 56 76 1 1 2 ANSI 3008 B8M C 1 3 4 x 4 3 4 82 111 1 1 2 ANSI 600 B8M C 1 3 4 x 4 3 4 82 111 1 1 2 ANSI 900 B8M C 1 1 x6 107 145 1 1 2 ANSI 1500 B8M C 1 1 x 6 107 145 Carbon Steel 1 1 2 ANSI 150 B7 1 2 x 3 1 4 56 176 1 1 2 ANSI 3008 B7 3 4 x 4 3 4 82 111 1 1 2 ANSI 6002 B7 3 4 x 4 3 4 82 111 1 1 2 ANSI 9007 B7 1 x6 107 145 1 1 2 ANSI 1500 B7 1 x 6 107 145 6 You must torque the flange studs in small increments Divide the appropriate torque by 10 to determine the number of steps For example if the appropriate torque is 90 ft lb the steps would be 20 30 40 50 60 70 80 and 90 ft lb 7 Set the torque wrench for the first setting and torque the studs in sequence Turn each stud a maximum of 1 8 of a turn at a time 8 Repeat Step 7 with the remaining torque settings Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 9 April 2004 ees Torquing the Studs 9 Check the flange alignment again to ensure that the flanges are cont parallel to each other Measure the spacing between the flanges with the cal
35. rs Introduction a 2 528 iw u ern ev xx yes vidis ee ee Identifying and Checking Components Assembling the Standard FTPA Buffer Inserting the Standard FTPA Buffer Torquing the Studs eu kr innen Installing the BWT Transducer April 2004 Introduction Identifying and Checking Components The FTPA Buffer is used for liquid and gas applications The buffer has a flanged process connection and is typically available in two lengths e 2in X 6 in for low temperature ranges from 150 to 315 C 270 to 600 F e Gin X 6 in for high temperature ranges from 150 to 600 C 270 to 1 100 F Use the sections that follow to properly install the buffers and transducers Caution It is critical that you follow the instructions outlined in this document If you do not GE Panametrics cannot ensure the proper operation of your equipment Before you install the FTPA Buffer you should make sure you have all the needed equipment Use the lists below to identify the needed components GE Panametrics will supply you with the following use Figures 2 1 and 2 2 on the next page to help you identify each component Note The list below is for a one path installation 2 FTPA Buffers 2 BWTI transducers e 2 Kamprofile gaskets IMPORTANT Kamprofile gaskets must be used for two reasons they ensure a leak tight seal and they
36. signal strength 3 Record this data in the Service Record in the back of the flowmeter s Service or User s Manual 4 Verify that the signal strength diagnostics are the same or better after 8 hours This completes the installation of the FTPA buffers and transducers Refer to the flowmeter s Startup or User s Manual for instructions on obtaining flow rate measurements Installing Standard FTPA BWT Buffers and Transducers 2 11 Chapter 3 Installing Acoustic Isolation FIPA BWT Buffers and Transducers Introduction zus uua ah Rn ee kx x RR Ra 3 1 Identifying and Checking Components 3 1 Inserting the Acoustic Isolation FIPA Buffer 3 3 Torquind tlie Studs i123 ia Ga AG DG LD rad teas 3 7 Installing the BWT Transducer 3 11 Installing Additional Acoustic Isolation 3 15 April 2004 Introduction Identifying and Checking Components The FIPA Buffer is used for gas applications at lower pressures The buffer has a flanged isolation section that reduces acoustic short circuit The buffer has a flanged process connection and is typically available in two lengths e 2in X 6 in for low temperature ranges from 150 to 315 C 270 to 600 F e 6 in X 6 in for high temperature ranges from 150 to 600 C 270 to 1 100 F Use the sections that follow to properly install the buffers and transducers Caution It is critical
37. table wrench 12 in handle or equivalent Steel wool Calipers Tape Measure Acoustic Isolation FIPA Buffer fully assembled TORIA BWT Transducer Junction Box Figure 3 1 Components for Acoustic Isolation FIPA Buffer Kamprofile with Metal Centering Ring Typical Kamprofile without Metal Centering Ring Figure 3 2 Gaskets 3 2 Installing Acoustic Isolation FIPA BWT Buffers and Transducers April 2004 ee ZA Inserting the Acoustic When you receive the Acoustic Isolation FIPA Buffer it will be fully Isolation FIPA Buffer assembled Use the steps below to properly install the buffer Note Ifthe BWT system is shipped with the buffers already installed in the nozzles proceed to Installing the BWT Transducer on page 3 11 1 Check the raised face of the spool nozzle flange to make sure it is free from paint rust dirt corrosion and damage If necessary clean the raised faces with steel wool In addition clean the buffer flange if you are reusing the buffer Inspect Raised Face Side View 2 Inspectthe GE Panametrics supplied gaskets They must not be used warped pitted or scratched 3 Place one gasket on the end of the buffer Gasket Side View Installing Acoustic Isolation FIPA BWT Buffers and Transducers 3 3 April 2004 Inserting the Acoustic 4 Inspect the pipe nozzle Make sure it is free from dirt rust Use Isolation FIPA Buffer the steel wool to clean
38. tanium see Figure 4 1 below Buffers and l Transducers The FSPA is a threaded buffer that is screwed into the pipe coupling or nozzle The FWPA is a socket weld buffer that is welded into the pipe coupling Both types of buffers enable you to install and remove transducers easily without interrupting the process or emptying the pipe Installing the BWT transducers into the FSPA FWPA Buffer requires three steps Installing the FSPA FWPA Installing and Orienting the Junction Box Inserting the BWT transducers Verifying Installation FSPA Threaded Mount FWPA Socket Weld Mount Figure 4 1 Threaded FSPA FWPA Buffer Installing Non Flanged FSPA FWPA BWT Buffers and Transducers 4 1 April 2004 ess Installing the FSPA Both types of buffers are easily installed into the pipe coupling or FWPA Buffer flange as follows FSPA threaded mount Use Teflon tape or thread sealant on the buffer threads and screw the buffer into the transducer port Hand tighten once inserted the NPT threads will seal the connection no torquing is required gt FWPA socket weld mount Insert the buffer into the meter body transducer port and weld in accordance with all applicable safety codes and procedures IWARNING Welding should be performed by qualified personnel only Safety personnel should be consulted a y 4 2 Installing Non Flanged FSPA FWPA BWT Buffers and Transducers April 2004 Installing
Download Pdf Manuals
Related Search
Related Contents
14ecodanfloor04 SCAN-DIY CR-PRO User's Manual KitchenAid KBLS22KVSS00 User's Manual e- eeprom Samsung ME73A Manuel de l'utilisateur Anleitung - Fujifilm Ambush-AmbushIR EuroManual 2012-2.indd Thermaltake Level 10 GT Battle Edition POR ULTRASONIDO - Mega-Test Copyright © All rights reserved.
Failed to retrieve file