1. Pwnourr PANDUIT TX6A 10GiG COPPER CABLING SYSTEM TESTING PROCEDURES PN524 Introduction Copper cabling transmission performance depends on cable characteristics connecting hardware patch cords and cross connect wiring the total number of connections and the care with which they are installed and maintained To qualify for a PANDUIT System Warranty post installation performance testing must be done using Panduit approved field test instruments to verify that the installed cabling will meet or exceed the performance requirements of the designated classification defined in the Commercial Building Telecommunication Standards These standards based test results should then be submitted to the PANDUIT Warranty Department for review PANDUIT offers warranty on the TX6A 10GiG Copper Cabling System for the current standards or ANSI TIA 568B 2 10 to channel or ISO 11801 Amendment 1 Class E Ch AMD1 Channel Test Configuration The channel test configuration is to be used by system designers and users of data communications systems to verify the performance of the overall channel Channel performance is the most critical to the end user as this is how their network will perform The channel includes up to 90 m 295 ft of horizontal cable a work area equipment cord a telecommunications outlet connector an optional transition consolidation connector and two connections in the telecommunications room TIA EIA recommends and
2. 0 63 3 60 3 61 58 0 4 4 2 63 0 60 5 19 0 51 2 48 2 58 9 56 4 8 5 8 58 2 55 6 19 0 45 2 42 2 52 4 49 8 10 6 5 56 6 54 0 19 0 43 3 40 3 50 1 47 5 16 8 2 53 2 50 6 18 0 39 2 36 2 45 0 42 4 20 9 2 51 6 49 0 17 5 37 2 34 2 42 5 39 8 25 10 2 50 0 47 3 17 0 35 3 32 3 39 8 37 1 31 25 11 5 48 4 45 7 16 5 33 4 30 4 36 9 34 2 62 5 16 4 43 4 40 6 14 0 27 3 24 3 28 0 24 2 100 20 9 39 9 37 1 12 0 23 3 20 3 19 0 16 2 200 30 1 34 8 31 9 9 0 17 2 14 2 4 7 1 8 250 33 9 33 1 30 2 8 0 15 3 12 3 0 8 3 7 350 40 6 30 6 27 6 6 6 12 4 9 4 10 0 13 0 500 49 3 27 9 24 8 6 0 9 3 6 3 21 4 24 5 For Technical Support www panduit com resources install_maintain asp Page 8 of 9 Panduit Corp 2009 TESTING PROCEDURES PN524 version 2 4 PANDUIT TX6A 10GiG Copper Cabling System Product List Part Number ack Modules J6X88TG JS6X88TGY O S CD n Q gt B fs ro lt INI COM TX6A 10GIG M UTP Jack Module IN COM TX6A 10GIG Shielded Jack Module able UR6X04 X6 10GIG CMR UTP Copper Cable UR6A04 X6A 10GIG CMR UTP Copper Cable UP6X04 UPGA04 UL6X04 UC6X04 SR6004 SP6004 UFL6X04 SL7004 atch Cords EE N ee TP6X Y X6 10GIG UTP Patch Cords TP6A X6A 10GIG M UTP Patch Cords TP6X X6 10GIG STP Patch Cords il NIN ata patch Panels P 6X88T GY PA 6X88TGY P6 10GIG M Modular Punchdown Patch Panel P6 10GIG M A
3. as the victim file as titled from the internal file selected 5 Select the appropriate standard from the test limit menu 6 Select end 1 and PSANEXT from the radio buttons Run test and follow the directions Connect the main and remote as shown below The Main will always be the victim and the Remote the disturber For PSANEXT both units are on the same end and the opposite end will have terminated plugs Run a separate disturber test for each non victim link of the bundle for end 1 while making the appropriate connection changes This involves moving the remote and termination plug to the next disturber Disturbed Link Disturber Link fa if Rees Terminating Plugs O Synchronization link uses patch cable N aa m between Alien Crosstalk RJ45 module connectors 7 When finished select end 2 and repeat 8 When finished select PSAACR F Repeat as for PSANEXT but now the main and remote units will be on opposite ends as shown below If the patch cord is not long enough use 2 patch cords and a separate link as the synchronization link For Technical Support www panduit com resources install_maintain asp Page 5 of 9 Panduit Corp 2009 USB Connection to PC TESTING PROCEDURES PN524 o version 2 4 LE Disturbed Link x Terminating Plug Connector Pi Plug T Cee Disturber Link h 1 gt Synchronization Link Connectors 1 se ER Syn
4. which warranty is desired e TIA Cat 6A Channel e ISO ClassE Ch AMD1 For channel testing install all patch cords prior to testing Note PANDUIT recommends for installers to install and test a few channels before completing the entire system Begin testing your installed channels with the Fluke DTX 1800 Series Digital Cable Analyzer and save all test results Optional Panel Patch Panel Outlet cross connect Consolidation Beginning Point End of of channel channel 7 Troubleshoot and repair any failing channels Channels resulting in a PASS are considered a PASS and will be acceptable for warranty Note The Fluke HDTDX analyzer and HDTDR test are very helpful when troubleshooting failing channels Both can be found on the SINGLE TEST menu and will also run automatically when a failure occurs Also make sure that Store Plot Data is set to Extended under Setup Instrument settings For Technical Support www panduitcom resources install maintain asp Page 3 of 9 Panduit Corp 2009 TESTING PROCEDURES PN524 version 2 4 8 Submit electronic channel test reports to the PANDUIT Warranty Department with all required warranty paperwork A channel warranty will then be given based on passing test results Note PANDUIT recommends for installers to install and test a few channels before completing the entire system Alien Crosstalk Testing Optional Alien Crosstalk testing is not needed for shielded cable sy
5. ISO requires that the consolidation point be located at least 5 m 16 4 ft from the telecommunications room to reduce the effect of multiple connections in close proximity on NEXT loss and return loss Per the TIA standard the total length of equipment cords patch cords or jumpers and work area cords shall not be more than 10 m 32 8 ft If total patch cords are longer than 10 meters the entire channel length must be de rated by the length exceeding 10 meters depending either by 20 or 50 depending on the patch cord cable type used The connections to the equipment at each end of the channel are not included in the channel definition The channel definition does not apply to those cases where the horizontal cabling is cross connected to the backbone cabling A schematic representation of a channel can be found below TIA EIA 568B 2 10 Field test instrument A B C D Field test d instrument Work Optional Horizontal Cross connect Area Consolidation or Interconnect Outlet point Maximum length B C 90 m 295 ft A D E 10m 32 8 ft For Technical Support www panduit com resources install_maintain asp Page 1 of 9 Panduit Corp 2009 TESTING PROCEDURES PN524 version 2 4 PANDUIT System Warranty PANDUIT has different types of warranties These include the CERTIFICATION PLUS System Warranty and the PAN NET Performance Guarantee Each warranty is standards based PANDUIT will typically provid
6. alibration with the Precision Calibration is STRONGLY RECOMMENDED 3 Tester holds last calibration Tester must be recalibrated if using a different DualRemote upgrading the software when transitioning from Cat7 Class F copper cable test to Cat6A Class E or lower performance categories or after 30 days 4 Universal Cat6A Channel SmartProbes should be in optimal condition See owner s manual For Technical Support www panduit com resources install_maintain asp Page 7 of 9 Panduit Corp 2009 TESTING PROCEDURES PN524 version 2 4 Appendix A Standards Limits TIA Category 6A Channel Freq Insertion NEXT PSNEXT Return ACR F PS ACR F ACR N PSACR N MHz Loss db dB dB Loss dB dB dB dB dB 1 3 65 0 62 0 19 0 63 3 60 3 4 4 2 63 0 60 5 19 0 51 2 48 2 8 5 8 58 2 55 6 19 0 45 2 42 2 10 6 5 56 6 54 0 19 0 43 3 40 3 16 8 2 53 2 50 6 18 0 39 2 36 2 20 9 2 51 6 49 0 17 5 37 2 34 2 25 10 2 50 0 47 3 17 0 35 3 32 3 31 25 11 5 48 4 45 7 16 5 33 4 30 4 62 5 16 4 43 4 40 6 14 0 27 3 24 3 100 20 9 39 9 37 1 12 0 23 3 20 3 200 30 1 34 8 31 9 9 0 17 2 14 2 250 33 9 33 1 30 2 8 0 15 3 12 3 350 40 6 30 3 27 3 6 6 12 4 9 4 500 49 3 26 1 23 2 6 0 9 3 6 3 ISO Class E Ch AMD1 Freq Insertion NEXT PSNEXT Return ACR F PSACR F ACR N PSACR N MHz Loss db dB dB Loss dB dB dB dB dB 1 4 65 0 62 0 19
7. assification defined in the ANSI TIA EIA Category 6A Standard it is important that the following steps are followed Channel Testing 1 Verify that your DTX 1800 Series tester has the most up to date software software version 2 12 or better is required The latest software updates can be found on the Fluke website at http www flukenetworks com fnet en us supportAndDownloads downloadsAndUpdates pid 50004 2 Perform a Set Reference procedure in the special functions prior to testing Fluke Networks recommends that a Set Reference procedure be performed every 30 days to ensure the maximum accuracy of the test results DTX Reference Module part DTX REFMOD is recommended for Cat6A testing For Technical Support www panduit com resources install_maintain asp Page 2 of 9 Panduit Corp 2009 TESTING PROCEDURES PN524 version 2 4 For detailed instructions on Set Reference procedure refer to Fluke Network s DTX 1800 Series Users Manual page 20 on Setting the Reference for Twisted Pair Cabling The link for the Users Manual is http www flukenetworks com fnet en us techdocs Manuals htm pid 50004 Note Fluke Networks also recommends factory calibration once a year to ensure that the test tool meets or exceeds the published accuracy specifications Select the Fluke Channel Adapter DTX CHAOO1A AxTalk and attach them to the DTX 1800 Series Main and Remote unit Select from the following Fluke Test Limts for
8. chronizing connection uses RJ45 connectors in each unit s Allen Crosstalk module 9 When finished select end 2 and repeat Pass fail determination e Any single failure of any pair will result in an overall fail For additional information see Alien Crosstalk User Manual located under the help tab in the AxTalk Analyzer application For Technical Support www panduit com resources install_maintain asp Page 6 of 9 Panduit Corp 2009 TESTING PROCEDURES PN524 version 2 4 Approved Test Leads For PANDUIT Mini Com TX6A 10GicG Jack Modules and DP6 10Gic Patch Panels Channel Firmware Version Software Version Calibration Equipment Autotest Test Leads Personality Module Comments Fluke Networks DTX 1800 Series Cable Analyzer Fluke Networks Website Software V2 04 or later Linkware Software V3 01 or later Part DTX CHAOO1 Cat6 Class E Channel Adapter 1 Consult Fluke Networks website for the latest Firmware and Software Version 2 It is STRONGLY RECOMMENDED that the tester is calibrated prior to testing Agilent WireScope Pro N2640A Agilent Technologies Website WireScope Pro Software 2 1 9 or later WireScope Pro ScopeData Pro Il Software 2 19 or later Cat6A Channel Part N2644A 100 Universal Cat6A Channel SmartProbe 1 Consult Agilent s website for the latest Software Version 2 C
9. e a system warranty in the following way Channel Warranty is based on passing channel test results It is recommended to keep the patch cords installed after testing as there may be variations between patch cords As stated previously passing test results must be obtained using an approved field test instrument PANDUIT Corp places each handheld test instrument thru an evaluation before approving it for use in the field This ensures the integrity of the test data submitted for warranty Current field testers approved for 10Gig Category 6A e Fluke DTX 1800 e Agilent Wirescope Pro N2640A Testing Required for TIA EIA CAT6A Channel Operation Warranty PANDUIT requires that internal channel performance be verified for each link to obtain the warranty PANDUIT does not require that field alien crosstalk testing be performed as the TX6A 10GIG Copper Cabling System has been thoroughly lab tested and verified to meet alien crosstalk requirements under worse case conditions of 6 around 1 tightly bundled configuration The customer may wish to perform optional alien testing and this procedure is included for reference Fluke DTX 1800 Series Digital Cable Analyzer PANDUIT has evaluated the Fluke DTX 1800 Series Digital Cable Analyzer and approves the use of this tester for the certification of installed 10Gig cabling channels In order to verify that the installed cabling will meet or exceed the performance requirements of the designated cl
10. ngled Modular Punchdown Patch Panel Modular Panels o PPL WBLY MINI COM Modular Faceplate Patch Panels PPL M6BLY MIN COM M6 Style Modular Faceplate Patch Panels PPLA WBLY MINI COM Angled Modular Faceplate Patch Panels s P BLY PPL WRBLY PP FMWBLY PPA FMWBLY Part Number S EE EE S Er EE Modular Panels For Technical Support www panduit com resources install_maintain asp Page 9 of 9
11. stems For UTP systems Alien Crosstalk testing can be done with the Fluke DTX1800 using part DTX 10GKIT recommended The Alien Test Kit contains the following items DTX PLA002 Permanent Link adapters AXTALK Analyzer Software software version 3 0 or newer is required The latest software updates can be found on the Fluke website at http www flukenetworks com fnet en us supportAndDownloads downloadsAndUpdates pid 50004 DTX ATERM Link Terminators 2 RJ45 to RJ45 Couplers 2 for channel testing DTX CHAOO1A channel test heads DTX AXTK1 2 Alien Crosstalk Modules Items needed in addition to the kit Patch cords 2 Laptop computer For Technical Support www panduit com resources install_maintain asp Page 4 of 9 Panduit Corp 2009 TESTING PROCEDURES PN524 version 2 4 Process description 1 Determine bundles and cables to test e Select the longest and shortest links e Apply rules for TIA 568 B 2 10 2 For alien testing Fluke recommends performing a Set Reference at least once a day 3 Perform permanent link internal testing to the appropriate standard and save all internals of the bundle under test to a separate folder All links must pass internals 4 Open the AxTalk Analyzer application and click on the new icon to start a new victim file Browse for the folder containing the bundle internal tests Select the file to be used as the victim link By saving the application will automatically title