Home

Datasheet - AEMC Instruments

image

Contents

1. in a tabular and graphic format as well as operator and test site information Comments typed by the operator will also be included Typical DataView Functional Digital amp Graphical Displays Control Panel Trend View Sey lt Title Bar File Edit View Instrument Tools Help eB AEX ARAQa BOO tm Tools Menu Bar 4 Parameter Cmm amr Selection Buttons Channel Color CursorMIN CursorAVG Cursor MAX Window MIN Window AVG Window MAX vi 219 6 V 219 6 V 219 6 V 216 8 V 219 4 V 220 9 V TA 20 oy aov aav PES Tabular Listing of Data 4 5 399 1V 339 1V 399 1V 383 7V 338 5 V 339 5 V at Cursor Position EN 3so sv 356 5 V 356 5 V 351 8 V 356 1 V 356 9 V m Movable Cursor Data Plot Listing Area 3 12 2012 11 15 00 AM 1 min Div For Help press F1 Logger Navigation Tree In the PEL Control Panel you will find all the necessary tools and selection buttons to review recorded data as trend plots or tabular lists Also logger selection when multiple loggers are detected is accomplished in the Control Panel 1 INSTRUMENTS Technical Assistance 800 343 1391 www aemc com 6
2. 2 75 PEL 103 8220 100mA to 3000Aac aan e 8230 et 8435 1 to 1000A4c 1 to 1300Apc Battery operated PEL 102 3990 PEL 103 8333 8230 8435 8336 8336 AEMC 3 WWW aemc com Technical Assistance 800 343 1391 INSTRUMENTS POWER QUALITY ANALYZERS METERS amp LOGGERS Optional Accessories TYPICAL MAX LIMITED ACCURACY ERROR USED WITH RANGE IF TYPICAL ON AT EA MODEL USED WITH 50 60HZ MODEL SL261 0 Oo 5 to 100A4c pc 4 0 5 PEL 102 PEL 103 8333 50mA to 10Aac pc 3 Battery operated B 2 83 Cw RU 50 to 3500Aac 419 8333 50 to 5000Apc g g Busbar 8336 5 x 1 69 8435 127 x 43mm Battery operated eX Maximum current reduced by a factor of 2 for 400Hz fundamental frequency SENSOR TYPE CURRENT RANGE Note Refer to the power meter s product user manual for complete specifications AC DC Current Probe BNC Adapter for Model SL261 only Catalog 2140 40 CATALOG NO DESCRIPTION 1201 51 AC DC Current Probe Model SL261 BNC 2140 28 AC Current Probe Model MR193 BK 2140 32 AC Current Probe Model MN93 BK 2140 33 AC Current Probe Model SR193 BK 2140 34 AmpFlex Sensor 24 Model 193 24 BK 2140 35 AmpFlex Sensor 36 Model 193 36 BK 2140 36 AC Current Probe Model MN193 BK 2140 48 MiniFlex Sensor 10 Model MA193 10 BK 2140 49 AC DC Current Probe Model J93 BK amp INSTRUMENTS Technical Assistance 800 343 1391 www aemc com 4 DATAVIEW Control P
3. anel Name EEE Visibility 9 Visible Invisible Contrast 3 Name PEL 103 PROT 301 10 min Normal mode brightness il f Stand by mode brightness MAC address 00 0B 3C 32 2E FE Enable DHCP IPaddres 10 1 10 E Lock out the Control button on the instrument front panel This will prevent the start and stop of recording also the enabling and disabling of Bluetooth at the instrument UDP portnumber 3041 Bluetooth Network password V Enable password protection Password 9900 16 characters max The instrument dock differs from this computer s dock by 22171 second s This password will be required when configuring the instrument via Bluetooth and Ethernet network connections Basic information regarding Auto Power Off instrument name The Communication tab provides information about the various and location display brightness and contrast Model PEL 103 communication mediums supported by the instrument with clear setting of the real time clock and SD card formatting is easily and easy setup of all functions from one dialog box accomplished from the General tab V Record now Duration Shows Schedule recording Startdate 6 19 2012 ly Start time 12 05 54PM H pase 4 Enddate 6 19 2012 J Endtime 8 05 54PM H Nominal vatape and lage ratos i V Set a Voltage Transformer Ratio Trends demand interval Primary 100 v 50 650000 Phase to
4. e Phase RMS Voltages 10 to 1000Vrms 0 1V 0 2 Rdg 0 2V Phase to Phase RMS Voltages 17 to 1700Vrms 0 1 to 1V 0 2 Rdg 0 4V 400Hz 340 to 460Hz Single Phase RMS Voltages 10 to 600Vrms 0 1V 1 Rdg 1V Phase to Phase RMS Voltages 17 to 1200Vrms 0 1 to 1V 1 Rdg 1V DC 100 to 1000V 0 1V 1 Rdg 3V typical PT Ratios Programmable from 50V to 65 0000V 0 01V to 0 1V CURRENT MEASUREMENT Current Probe MiniFlexe Sensor MA193 200mA to 100Arms 1 to 100mA 1 2 50mA 0 8A to 400Arms 10 to 100mA 1 2 0 2A 4A to 2000Arms 0 1 to 1A 1 2 1A 20A to 10 000Arms 0 1 to 10A 1 2 CT Ratios Programmable from 1 1 to 25 000 1 probe dependent POWER MEASUREMENTS Active Power P 2 to 2GW 0 001W 0 5 Rdg 0 005 Pnom Reactive Power Q 2 to 2Gvar 0 001 var 1 Rdg 0 01 Qnom Apparent Power S 0 to 2GVA 0 001VA 0 5 Rdg 0 005 Snom Power Factor 1 to 1 0 001 0 05 Tangent 6 active reactive power ratio 3 2 to 3 2 0 001 0 02 ENERGY MEASUREMENTS Active Energy EP 0 to 4 x 10 1Wh 0 5 Rdg Reactive Energy EQ 0 to 4 x 10 1varh 2 Rdg Apparent Energy ES 0 to 4 x 10 1Vah 0 5 Rdg THD 655 Individual Harmonics 1 to 50 displayed in percentage 1 to 7 at 400Hz External Supply 110V 250V 10 50 60Hz 400Hz Back Up Power Source Charge Time Rechargeable 8 4V NiMH battery pack Approximately 5 hours Battery Life 30 minutes minimum 60 minutes typical MECHANICAL Communication Ports USB 2 0 Ethernet RJ45 Wireless Bl
5. nutes and view available memory for data storage MC 5 www aemc com Technical Assistance 800 343 1391 INSTRUMENTS The Measurement tab specifies the electrical distribution system voltage ratios nominal frequency and current probe options and ratios DATAVIEW Graphical Display amp Report Generation DataVietw DataView software provides a convenient way to configure an He and control power and energy tests from a computer Through the use of clear and easy to use tabbed dialog boxes all PEL 100 series functions can be configured and tests can be initiated gt C patiment peLios 12 4412042 TAM AM 3 min 56 Configure all functions of the PEL Display and analyze real time data on your PC e Configure functions and parameters from your PC e Customize views templates and reports to your exact needs Create and store a complete library of configurations that can be uploaded as needed e Zoom in and out and pan through sections of the graph to analyze the data e Download display and analyze recorded data Display waveforms trend graphs harmonic spectrums text summaries transients event logs and stored alarms e Print reports using standard or custom templates you design e Free updates are available on our website www aemc com reme ee pes muni My RENS Reports can be displayed on a PC and printed Each report includes all test results
6. phase Phase to neutral Period The aggregation starts at rounded hours Secondary 100 V 50 650000 Phase to phase Phase to neutral Recording options V Record one second trends ME a V Record current and voltage harmonics Q 100A 2000A V An external CT is used Longest possible recording is 47 days because of the limitation of file size 4 GB in FAT32 regardless of available 400A 10000A Primary 10000 i of Caution Recording harmonics will consume a considerable amount of storage space and will greatly increase download Number of primary wraps 1 1 2or 3 e and analysis time see help for more information IE see Installed SD Card status NOE o 3 Longest possible recording on the installed SD Card is 18 days divided by the number of primary wraps V An external CT is used Primary 10900 For example with 2 primary wraps for a 2000 A range the nominal current will be 1000 A instead of 2000 A 4 1 07 of the SD Card space has been used Scary 5 1898 MB is available on the installed SD Card with BNC ad 1919 MB is the total capacity of the SD Card Nominal current 1000 A 1 25000 Output voltage 1 V Sensor output voltage must not exceed 1 7 V peak o jJ e J we J In the Recording tab configure the instrument to measure and record over a user selectable recording period from a few hours to a month or longer Select demand intervals from one to sixty mi
7. ratios and aggregation period can be configured from the front panel of the PEL 103 Max Mode P S Lid Real time updates are displayed for voltage current power frequency power factor and tangent Harmonic Mode D gt FEATURES e Simple to use single dual split phase and three phase Y A power amp energy loggers e Designed to work in 1000V CAT III and 600V CAT IV environments and fits in many distribution panels e Power measurements VA W and var e Energy measurements VAh Wh source load and VAHh 4 quadrants e DataView software for configuring real time communication with a PC and report generation with pre defined or user defined templates e Ethernet compatible Minimal programming required e Displays stored measurements display or via Bluetooth Class 1 communicates up to 300 ft to a PC or the Android based mobile application e Satisfies the requirements of T ICID w v e A W Total Harmonic Distortion THD can be displayed by phase or phase to phase Neutral current THD can also be displayed Max values for voltage current including neutral current power and harmonics Android App Available gt PRODUCT INCLUDES PEL 102 amp PEL 103 Kit Small classic tool bag three MiniFlexe MA193 10 BK sensors 5 ft USB cable four black test leads and alligator clips power cord 12 color coded ID markers Multifix mounting s
8. special POWER QUALITY ANALYZERS METERS amp LOGGERS product Power amp Energy Loggers PEL 100 Series n A Models PEL 102 amp PEL 103 UIS Visit the PEL 100 Series Monitor your power amp energy Bogen or more AX P information on e g usage amp costs locally or from ES iware uis T ificati bay C anywhere in the world specifications and more MOr Bm gt SPECIFICATIONS sO TS MODELS PEL 102 amp PEL 103 GENERAL Sampling Frequency 128 samples per cycle 50 60Hz 16 samples cycle 400Hz Data Storage Rate 1 per second Demand Period Storage Rate User selectable 1 2 3 4 5 6 10 12 15 20 30 and 60 minutes Recorded Parameters V W VA var PF Tan Wh VAh VARh THD V and 1 Single and Poly Phase Individual harmonics from 1 through 50 per phase Crest Factor CF Cos f DPF Event Log Tracks and records status changes and error messages along with recorded data Front Panel Indicator LEDs Bluetooth active recording in progress phase connection reversal overload battery charging and SD Card status Storage Capacity 2GB SD card included is used for storage SD cards up to 2GB SDHC cards 4 to 32GB formatted FAT32 are supported INPUTS Voltage 3 voltage input channels via 4mm safety banana jacks Current 3 current input channels via custom 4 pin jacks that accept AEMCe probes and sensors ELECTRICAL VOLTAGE MEASUREMENT RANGE RESOLUTION ACCURACY of Reading 50 60Hz 42 5 to 69Hz 0 1Hz Singl
9. uetooth Class 1 Dimension Weight 10 08 x 4 92 x 1 46 256 x 125 x 37mm lt 1kg Case Index of Protection Double insulated rubber over molded polycarbonate UL94 V1 rated IP54 non operating Mounting Security Embedded magnets on back side keyhole slot on back side Kensington anti theft system DISPLAY Display Type for Model PEL 103 2 63 x 2 16 67 x 55mm four line monochrome backlit LCD with adjustable brightness and contrast ENVIRONMENTAL SAFETY Operating Temperature Relative Humidity 50 to 122 F 10 to 50 C up to 85 Storage Temperature 4 to 122 F 20 to 50 C with batteries 4 to 158 F 20 to 70 C without batteries Safety Rating CE Rating Complies with IEC 61010 1 Ed3 and IEC 61010 2 030 Ed1 for 1000V CAT III 600V CAT IV Pollution Degree 2 Yes Maximum value is current probe dependent Computers with Class Il Bluetooth will restrict range to 40 ft Computers without Bluetooth will require a Class or Class Il Bluetooth radio adapter Maximum current reduced by a factor of 2 for 400Hz fundamental frequency AEMC 1 www aemc com Technical Assistance 800 343 1391 Q INSTRUMENTS MODEL PEL 103 MODEL PEL 102 POWER amp ENERGY LOGGER ON OFF START STOP A 8 POWER amp ENERGY LOGGER ON OFF START STOP c CN Information Mode Models PEL 102 amp PEL 103 Large Functional Displays Measurement Mode EI N W m Mw O9 Hook up voltage and current
10. ystem safety card sensor compliance sheet 2GB SD Card with USB SD Card reader quick start e Configure Measurements A l NEC Code 220 87 and Recordings ENS WT E a d E pau stick supplied wi e Measures AC DC Display Data in Real Time A x s E Ld DataViewe software current probe dependent e For Use on any Device with an Ww Ceo n and user manual Android Platform CATALOG NO DESCRIPTION 2137 51 Power amp Energy Logger Model PEL 102 no LCD w 3 MA193 10 BK Sensors 2137 52 Power amp Energy Logger Model PEL 103 with LCD w 3 MA193 10 BK Sensors 2137 61 Power amp Energy Logger Model PEL 102 no LCD or Sensors 2137 62 Power amp Energy Logger Model PEL 103 with LCD no Sensors AEMC INSTRUMENTS Technical Assistance 800 343 1391 www aemc com 2 POWER QUALITY ANALYZERS METERS amp LOGGERS Optional Accessories TYPICAL MAX LIMITED ERROR CONDUCTOR USED WITH RANGE IF ON AT MODEL USED WITH 50 60HZ SIZE MODEL ACCURACY TYPICAL 2 5 0 80 1 6 PEL 108 Bonn d i 41mm 8333 aes 8336 PEL 102 2 05 PEL o 8220 1 to 1200A4c 0 3 0 2 52mm 8333 8230 He 8435 AmpFlexe 193 100mA to 12 000Aac 1 24 or 36 sensor MN93 PEL 102 m 0 78 PEL 103 m dg C 5 20mm 8333 re 8336 MN193 0 o 200mA to 120Aac 1 0 75 PEL 102 A 0 78 PEL 103 8230 20mm 8333 8435 5mA to 6Aac 1 1 7 SENSOR TYPE CURRENT RANGE MiniFlexe MA193 PEL 102